Plans (321) \ . 0/ y2 244 i--Cx,;cic. I •:11141/AC'-:Residential & Light Commercial HVAC i oads Program Elite Software Development Inc Sky Heating &. A/C,.Inc,. Green Office Park:: :::: Pactland;: OR-97213 :................ _...................... ............................... ...:. _....:. 07:20 -2000 Page a ::: Toil Building Summary Loads Component Area Sen. Lat. Sen. Total Description Quan Loss Gain Gain Gain 3F Window Double Pane Low Emit Metal Frame 3,294 32,940 0 92,453 92,453 7L Skylight Double Low Emit Glass Metal Frame 84 2,730 0 11,928 11,928 8F Glass Door Single Low e Glass Metal Frame 264 2,640 0 2,282 2,282 12K Wall R -19 + 1" ExtrPoly Board(R -5.0) 7,351 17,277 0 9,883 9,883 16G Ceiling R -30 Insulation 168 278 0 272 272 16H Ceiling R -38 Insulation 4,583 5,958 0 5,839 5,839 22D Slab on Grade 2" Edge Insulation(R -11) 452 4,746 0 0 0 Subtotals for structure: - 16,196 66,569 0 122,657 122,657 Active People: 81 0 18,630 24,300 42,930 Inactive People: 81 0 8,505 18,225 26,730 Appliances: 0 0 0 0 0 Lighting: 29,916 0 0 102,014 102,014 Ductwork: 0 5,880 0 14,635 14,635 Infiltration: Winter CFM: 928.5, Summer CFM: 928.5 3,642 51,027 -189 25,510 25,321 Ventilation: Winter CFM: 0.0, Summer CFM: 0.0 0 0 0 0 0 Sensible Gain Total: 307,341 Temperature Swing Multiplier: X1.00 Building Load Totals: 123,476 26,946 307,341 334,287 Check Figures Total Building Supply CFM: 13,981 CFM per square foot: 1.037 Square feet of room area: 13,477 Square feet per ton: 394.653 Buil ding Loads • Total heating required with outside air: 123,476 Btuh 123.476 MBH Total sensible gain: 307,341 Btuh 92 % Total latent gain: 26,946 Btuh 8 % Total cooling required with outside air: 334,287 Btuh 27.857 Tons (based on sensible + latent) 34.149 Tons (based on 75% sensible capacity) Notes .............................. _ .. . Calculations are based on 7th edition of ACCA Manual J. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads. 1 Thursday, July 20, 2000 RHVAG Residential : &:Light Commercial :HlAG Loads :Progtam._.::. .._... ilp. Elite Software Development. Inc. :. Sky fleahng& NC, , km, C, Green Office Park ::Pcttland :OR: '97213 07:202000 Page 2 :::. Detailed Roorn Load 1.1 St Ft W Tenant Room Length: 51.0 Feet System Number: 1 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 1,899 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 10 % of Supply: 0 % Runout Air: 190 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 544* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.129 In.wg/100 Ft. ` Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 51.1 X 11.5 396 0.047 2.3 931 1.3 0 532 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S- GLAS -3F 2 -P 0-1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 W -GLAS-3F 2 -P 0-1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0-1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 FLOOR -22D 136 FT 136 0.210 10.5 1,428 0.0 0 0 Subtotals for structure: 1,702 8,781 0 16,015 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 801 0.050 0 1,988 Active People: 230 lat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 41,747 Temperature Swing Multiplier: X1.00 Room Totals: 16,821 2,988 41,747 . Thursday, July 20, 2000 : :::RHVAC -:I esideritiaGa:LightGOMMertialMAC :oads:Pr rare...:::::::: >::.::::: e ...__.....__ _.. ... ... ; Elite:BoPiwat� DeVel .. c ::::::::::::.:::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: :::::::::::::::::::::.::::::::: Green Office :Park ::: Pottland;:OR::97233 ' 07= 282000 Pita* 3 a9.. Deta lied Roomi Load ............................................................................................................................. ............................... . 2s 1stf1 alliance Room Length: 18.5 Feet System Number: 2 Room Width: 22.0 Feet Zone Number: 1 Area: 407.0 Square Feet Supply Air: 551 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 4,681.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 3 % of Supply: 0 % Runout Air: 184 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 527* Feet/Minute Actual Winter Infiltration Air: 41 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 41 CFM alloc. Actual Loss: 0.121 In.wg/100 Ft. ` Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain N - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 S - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 N - GLAS -3F 2 -P 0-3 S -1 100 %S 48 0.200 10.0 480 8.4 0 404 N - G.DR -8F 1 -P 0-2 S -1 100 %S 44 0.200 10.0 440 5.2 0 230 N - GLAS -3F 2 -P 0-3 S -1 100 %S 21 0.200 10.0 210 8.4 0 177 S - GLAS -3F 2 -P 0-3 S -1 44 %S 48 0.200 10.0 480 15.6 0 747 S- G.DR -8F 1 -P 0-2 S -1 81 %S 44 0.200 10.0 440 8.0 0 351 S - GLAS -3F 2 -P 0-3 S -1 89 %S 21 0.200 10.0 210 9.7 0 204 FLOOR -22D 44 FT 44 0.210 10.5 462 0.0 0 0 Subtotals for structure: 550 3,380 0 2,489 Infiltration: Winter: 41.0, Summer: 41.0: 226 9.965 2,252 4.982 -8 1,126 Ductwork: 0.050 282 0.050 0 577 Active People: 230 lat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 940 3,205 Sensible Gain Total: 12,122 Temperature Swing Multiplier: X1.00 Room Totals: 5,914 3,007 12,122 Thursday, July 20, 2000 RHVAC Resitfential:S LightCommercial 14VAC L:oads :Program ,. ...Elite :Software Development; int.:: : : . :SW Heating : &.i41C, Inc • * Green Office: Park : Portland;: OR x7243 • • 07:20=2000 • • Page 4 : :: Detailed:Roorri 1»oads 3 Lav(5)1st F1 Room Length: 14.0 Feet System Number: 2 Room Width: 8.0 Feet Zone Number: 2 Area: 112.0 Square Feet Supply Air: 0 CFM Ceiling Height: 12.5 Feet Required Vent. Air: 200 CFM Volume: 1,400.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 0 % of Supply: 0 % Runout Air: 0 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 0 Inches % of Supply: 0 % Runout Air Velocity: 0* Feet/Minute Actual Winter Infiltration Air: 0 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 0 CFM alloc. Actual Loss: 0.000 In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain Subtotals for structure: 0 0 0 0 Infiltration: Winter: 0.0, Summer: 0.0: 0 0.000 0 0.000 0 0 Ductwork: 0.050 0 0.050 0 0 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 105 lat/per, 225 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 0 Sensible Gain Total: 0 Temperature Swing Multiplier: X1.00 Room Totals: 0 0 0 Thursday, July 20, 2000 . RHVAC Residential :& Light-Commercial :HVACioads:Program ....... Elite: Software Development; 'Inc. Sky - Heating& A/C; Inc. Green Office Park : --::Portland; : OR '07213 .. - . ...07:20 =2(300 .. .Page 5 ::: :.Detaited : Room .Loads ...... ....._ .. 4 Stairwells Room Length: 17.0 Feet System Number: 2 Room Width: 8.0 Feet Zone Number: 3 Area: 136.0 Square Feet Supply Air: 8 CFM Ceiling Height: 40.0 Feet Required Vent. Air: 0 CFM Volume: 5,440.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 1 % of Supply: 0 % Runout Air: 8 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 2 Inches % of Supply: 0 % Runout Air Velocity: 379* Feet/Minute Actual Winter Infiltration Air: 0 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 0 CFM alloc. Actual Loss: 0.453 In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain UP- CEIL -16H DARK 17 X 8 136 0.026 1.3 177 1.3 0 173 Subtotals for structure: 136 177 0 173 Infiltration: Winter: 0.0, Summer: 0.0: 0 0.000 0 0.000 0 0 Ductwork: 0.050 9 0.050 0 9 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 105 lat/per, 225 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 0 Sensible Gain Total: 182 Temperature Swing Multiplier: X1.00 Room Totals: 186 0 182 Thursday, July 20, 2000 RHVAC :Residential: a :Light :ranunetcial HVACtoada:Ptogtarn . Elite SoftwareDeveloprnen Ind :: ....... - Skyfieatieg& AlC,.Inc, Green :Office Park : Pottland :OR: 97213 07:20=2000 Page: 6::: Detailed Room Loads : b.1 st F E Tenant Room Length: 51.0 Feet System Number: 3 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 1,899 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 10 % of Supply: 0 % Runout Air: 190 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 544* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.129 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. CIg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 51 X 11.5 395 0.047 2.3 928 1.3 0 531 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S- GLAS -3F 2 -P 0-1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 E -GLAS-3F 2 -P 0-1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0-1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 FLOOR -22D 136 FT 136 0.210 10.5 1,428 0.0 0 0 Subtotals for structure: 1,701 8,778 0 16,014 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 801 0.050 0 1,988 Active People: 230 lat/per, 300 sen /per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 41,746 Temperature Swing Multiplier: X1.00 Room Totals: 16,818 2,988 41,746 Thursday, July 20, 2000 RHVAC Residential. &: Light Commercial HVAC t oatls •Prograt ..... Elite: Software Development, Inc Sky Heating &: A/C, Inc,... RV Green Office Park : H Portland, OR 9721 3 ... - 07 -20 =2000. Page : 7 ::: :Detailed :Room Loads 6: 2nd FEW Tenant Room Length: 51.0 Feet System Number: 4 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 1,899 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 10 % of Supply: 0 % Runout Air: 190 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 544* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.129 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 51 X 11.5 395 0.047 2.3 928 1.3 0 531 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S -GLAS-3F 2 -P 0-1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 W -GLAS-3F 2 -P 0-1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0-1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 FLOOR -22D 136 FT 136 0.210 10.5 1,428 0.0 0 0 Subtotals for structure: 1,701 8,778 0 16,014 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 801 0.050 0 1,988 Active People: 230 Iat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat /per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 41,746 Temperature Swing Multiplier: X1.00 Room Totals: 16,818 2,988 41,746 Thursday, July 20, 2000 • RHVAC Residential: &: Light :Cornrnercial:HV /AC: Loads : Program Elite Software Development Inc. Sky#leating &A/C, Inc NV Green Office Park Porland,:OR:' 97213 07;20-2000 Page: 8 ::: Detailed: Rooms Loads 7 Hallways 2nd Ft Room Length: 18.5 Feet System Number: 2 Room Width: 22.0 Feet Zone Number: 4 Area: 407.0 Square Feet Supply Air: 551 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 4,681.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 3 % of Supply: 0 % Runout Air: 184 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 527* Feet/Minute Actual Winter Infiltration Air: 41 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 41 CFM alloc. Actual Loss: 0.121 In.wg/100 Ft. *Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain N - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 S - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 N - GLAS -3F 2 -P 0 -3 S -1 100 %S 48 0.200 10.0 480 8.4 0 404 N - G.DR -8F 1 -P 0 -2 S -1 100 %S 44 0.200 10.0 440 5.2 0 230 N - GLAS -3F 2 -P 0 -3 S -1 100 %S 21 0.200 10.0 210 8.4 0 177 S - GLAS -3F 2 -P 0 -3 S -1 44 %S 48 0.200 10.0 480 15.6 0 747 S - G.DR -8F 1 -P 0 -2 S -1 81%S 44 0.200 10.0 440 8.0 0 351 S - GLAS -3F 2 -P 0 -3 S -1 89 %S 21 0.200 10.0 210 9.7 0 204 Subtotals for structure: 506 2,918 0 2,489 Infiltration: Winter: 41.0, Summer: 41.0: 226 9.965 2,252 4.982 -8 1,126 Ductwork: 0.050 259 0.050 0 577 Active People: 230 lat/per, 300 sen /per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen /per: 9 945 2,025 Appliances: 0 0 Lighting: 940 3,205 Sensible Gain Total: 12,122 Temperature Swing Multiplier: X1.00 Room Totals: 5,429 3,007 12,122 Thursday, July 20, 2000 RHVA ...... . Residential:lhLight Commercial HVAC toads :Program _ _ ::::: ::::: ::.::: ::::: Elite: Sof Ware Development. :Inc.: : Sky Heatinga:A/C; Inc, • Green Office Park Penland; OR :97223 .. ' 07-202000 • Page 9 : :: Detailed: Room toads 8. ai (s) 2nd Ft . • Room Length: 14.0 Feet System Number: 2 Room Width: 8.0 Feet Zone Number: 5 Area: 112.0 Square Feet Supply Air: 0 CFM Ceiling Height: 12.5 Feet Required Vent. Air: 200 CFM Volume: 1,400.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 0 % of Supply: 0 % Runout Air: 0 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 0 Inches % of Supply: 0 % Runout Air Velocity: 0* Feet/Minute Actual Winter Infiltration Air: 0 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 0 CFM alloc. Actual Loss: 0.000 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Cig Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain Subtotals for structure: 0 0 0 0 Infiltration: Winter: 0.0, Summer: 0.0: 0 0.000 0 0.000 0 0 Ductwork: 0.050 0 0.050 0 0 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 105 lat/per, 225 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 0 Sensible Gain Total: 0 Temperature Swing Multiplier: X1.00 Room Totals: 0 0 0 Thursday, July 20, 2000 RHVAC Residential.8: Light Comrrietciel HVAC i oads :Program Elite Software Development; the Sky. Heating &: A/C . Inc. Green.0ffice Park Portland;: OR: :97213. 07:20 =2000 Page-10 :: Detailed Room toads 92ndflETenant Room Length: 51.0 Feet System Number: 5 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 1,899 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 10 % of Supply: 0 % Runout Air: 190 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 544* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.129 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Gig Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 51 X 11.5 395 0.047 2.3 928 1.3 0 531 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S- GLAS -3F 2 -P 0 -1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 E -GLAS-3F 2 -P 0 -1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0 -1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 Subtotals for structure: 1,565 7,350 0 16,014 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 729 0.050 0 1,988 Active People: 230 lat/per, 300 sen /per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 41,746 Temperature Swing Multiplier: X1.00 Room Totals: 15,318 2,988 41,746 Thursday, July 20, 2000 RHVAC = Residential:8: Light''Canienercial:HVAG i oadsprogram Ai. Elite: Soltware:Development,Inc .: - :Sky:HeatingA A/C Inc. Green :S ice Park Pettland :OR: :97213 0720 =2000 Page :1:7::: D.8talled Room toads 10: 3rd MNTenant Room Length: 51.0 Feet System Number: 6 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 2,018 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 11 % of Supply: 0 % Runout Air: 183 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 526* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.120 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 51 X 11.5 395 0.047 2.3 928 1.3 0 531 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S- GLAS -3F 2 -P 0 -1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 W- GLAS -3F 2 -P 0 -1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0 -1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 UP- CEIL -16H DARK 51 X 38.5 1,964 0.026 1.3 2,553 1.3 0 2,502 Subtotals for structure: 3,529 9,903 0 18,516 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 857 0.050 0 2,113 Active People: 230 lat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 44,373 Temperature Swing Multiplier: X1.00 Room Totals: 17,999 2,988 44,373 Thursday, July 20, 2000 RHVAC Residential & tight Commercral:HVAC Loads Progratsi Elite Software- Development, Inc. • Sky Heating &A/C; Inc ::: Green :Office Park Portland, OR972 #3 07:20 =2000 Page :12 =Detailed: Roorn Loads 11 3rd FI E Tenant Room Length: 51.0 Feet System Number: 7 Room Width: 38.5 Feet Zone Number: 1 Area: 1,963.5 Square Feet Supply Air: 2,018 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 22,580.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 11 % of Supply: 0 % Runout Air: 183 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 8 Inches % of Supply: 0 % Runout Air Velocity: 526* Feet/Minute Actual Winter Infiltration Air: 132 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 132 CFM alloc. Actual Loss: 0.120 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain S - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 W - WALL -12K 51 X 11.5 395 0.047 2.3 928 1.3 0 531 N - WALL -12K 38.5 X 11.5 299 0.047 2.3 703 1.3 0 402 E - WALL -12K 8 X 11.5 92 0.047 2.3 216 1.3 0 124 S -GLAS-3F 2 -P 0 -1 S -1 0 %S 144 0.200 10.0 1,440 21.4 0 3,085 W -GLAS-3F 2 -P 0 -1 S -1 0 %S 192 0.200 10.0 1,920 53.4 0 10,257 N - GLAS -3F 2 -P 0 -1 S -1 100 %S 144 0.200 10.0 1,440 8.4 0 1,213 UP- CEIL -16H DARK 51 X 38.5 1,964 0.026 1.3 2,553 1.3 0 2,502 Subtotals for structure: 3,529 9,903 0 18,516 Infiltration: Winter: 131.7, Summer: 131.7: 480 15.081 7,239 7.540 -27 3,619 Ductwork: 0.050 857 0.050 0 2,113 Active People: 230 lat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 4,516 15,400 Sensible Gain Total: 44,373 Temperature Swing Multiplier: X1.00 Room Totals: 17,999 2,988 44,373 Thursday, July 20, 2000 RHVAC .Residential : &: Light Cori merciai HVAG:L:oads:Program Elite SoftwateDevelopment,.Inc._ Sky floating &ANC, Ins Green:Offce Park. Pottland;:OR::972t3 07;20;2000 Page :43 .::. :Detailed: ROOT : Load;; 12. Hallway :3idFl Room Length: 18.5 Feet System Number: 2 Room Width: 22.0 Feet Zone Number: 6 Area: 407.0 Square Feet Supply Air: 1,230 CFM Ceiling Height: 11.5 Feet Required Vent. Air: 0 CFM Volume: 4,681.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 7 % of Supply: 0 % Runout Air: 176 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 6 Inches % of Supply: 0 % Runout Air Velocity: 895 Feet/Minute Actual Winter Infiltration Air: 56 CFM alloc. Design Loss: 0.100 In.wg /100 Ft. Actual Summer Infiltration Air: 56 CFM alloc. Actual Loss: 0.512 In.wg/100 Ft. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain N - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 S - WALL -12K 22 X 11.5 140 0.047 2.3 329 1.3 0 188 N - GLAS -3F 2 -P 0 -1 S -1 100 %S 48 0.200 10.0 480 8.4 0 404 N - G.DR -8F 1 -P 0 -1 S -1 100 %S 44 0.200 10.0 440 5.2 0 230 N - GLAS -3F 2 -P 0 -1 S -1 100 %S 21 0.200 10.0 210 8.4 0 177 S - GLAS -3F 2 -P 0 -1 S-1 0 %S 48 0.200 10.0 480 21.4 0 1,028 S- G.DR -8F 1 -P 0 -1 S -1 0 %S 44 0.200 10.0 440 20.2 0 890 S -GLAS-3F 2 -P 0 -1 S -1 0 %S 21 0.200 10.0 210 21.4 0 450 S -SKY -7L 2 -P 0 -0 S -48 0 %S 42 0.650 32.5 1,365 146.0 0 6,132 N -SKY -7L 2 -P 0 -0 S-48 0 %S 42 0.650 32.5 1,365 138.0 0 5,796 UP- CEIL -16H DARK 18.5 X 22 407 0.026 1.3 529 1.3 0 519 S - CEIL -16G DARK 31.5 X 4 84 0.033 1.6 139 1.6 0 136 N - CEIL -16G DARK 31.5 X 4 84 0.033 1.6 139 1.6 0 136 Subtotals for structure: 1,165 6,455 0 16,274 Infiltration: Winter: 56.2, Summer: 56.2: 310 9.965 3,089 4.981 -11 1,544 Ductwork: 0.050 477 0.050 0 1,287 Active People: 230 lat/per, 300 sen/per: 9 2,070 2,700 Inactive People: 105 lat/per, 225 sen/per: 9 945 2,025 Appliances: 0 0 Lighting: 940 3,205 Sensible Gain Total: 27,035 Temperature Swing Multiplier: X1.00 Room Totals: 10,021 3,004 27,035 Thursday, July 20, 2000 RHVAG Residcntal : Light Cbtnhiettial :HVACLoads :Program ............................ . _ ......... .......... . ... . ..Elite :Software Development ;tns ' SkV: Heating & A/C, Inc Green. Office Park :::: Portland; OR:: 97213 07-20;2000 Page:14 Detailed Roomtoads Room Length: 14.0 Feet System Number: 2 Room Width: 8.0 Feet Zone Number: 7 Area: 112.0 Square Feet Supply Air: 7 CFM Ceiling Height: 12.5 Feet Required Vent. Air: 200 CFM Volume: 1,400.0 Cubic Feet Actual Winter Ventilation Air: 0 CFM Number of Registers: 1 % of Supply: 0 % Runout Air: 7 CFM Actual Summer Ventilation Air: 0 CFM Runout Duct Size: 2 Inches % of Supply: 0 % Runout Air Velocity: 313* Feet/Minute Actual Winter Infiltration Air: 0 CFM alloc. Design Loss: 0.100 In.wg/100 Ft. Actual Summer Infiltration Air: 0 CFM alloc. Actual Loss: 0.310 In.wg/100 Ft. * Runout velocity constraints were not met due to duct schedule limitations. Item Area -U- Htg Sen. Clg Latent Sen. Description Quantity Value HTM Loss HTM Gain Gain UP- CEIL -16H DARK 14 X 8 112 0.026 1.3 146 1.3 0 143 Subtotals for structure: 112 146 0 143 Infiltration: Winter: 0.0, Summer: 0.0: 0 0.000 0 0.000 0 0 Ductwork: 0.050 7 0.050 0 7 Active People: 230 lat/per, 300 sen/per: 0 0 0 Inactive People: 105 lat/per, 225 sen/per: 0 0 0 Appliances: 0 0 Lighting: 0 0 Sensible Gain Total: 150 Temperature Swing Multiplier: X1.00 Room Totals: 153 0 150 Thursday, July 20, 2000 RHVAC Residential &Light Commercial HVAG Loads Program ....:. Elite: Software Development, Int. Sky Heating & NC, . Inc. Green Office Park Portland;: OR 972t3 _..... O7- -20= 2000 ::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: ::::::::::::::::::::::::::::::: Page :15 Room Load Summary Reports .................... ....... m: #1 RRoom:Load:System Summary Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1- 1 1 St Fl W 1964 16,821 340 10 -8 544 41,747 2,988 1,899 1.25 2,374 1,899 Tenant System 1 Totals 1964 16,821 340 41,747 2,988 1,899 2,374 1,899 Main Trunk Size: 16x16 in System #1 Cooling System Summary Cooling Sensible /Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.728 93 %/7% 41,747 2,988 44,735 Recommended: 4.639 75 %/25% 41,747 13,916 55,662 Thursday, July 20, 2000 RHVAC Residential:& Light 'Commercial :HVACtoadsProgram Elite: Software Development, Inc Slit' Heating A: A/C. Inc ..._........ _.- ...._..........._........._ ...._ ........... : .__ ':: ._.._.._. :: ... ::` .. ..:....::....: ............:......... office park - :: :Portland,: OR.: 97213 07-29;2000 Page:16::: :Ro0111 iLOad S t1 mai RepOrtS..... ............. :System : #2 :Room: Load: Summary Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM - Zone 1- 2 1st Fl Entrance 407 5,914 120 3 -8 527 12,122 3,007 551 1.35 744 551 Zone 1 Subtotal 407 5,914 120 12,122 3,007 551 744 551 -Zone 2- 3 Lav(s) 1st Fl 112 0 0 0 -0 0 0 0 0 1.00 0 0 Zone 2 Subtotal 112 0 0 0 0 0 0 0 - Zone 3- 4 Stairwells 136 186 4 1 -2 379 182 0 8 1.00 8 8 Zone 3 Subtotal 136 186 4 182 0 8 8 8 - Zone 4- 7 Hallways 2nd 407 5,429 110 3 -8 527 12,122 3,007 551 1.35 744 551 Fl Zone 4 Subtotal 407 5,429 110 12,122 3,007 551 744 551 -Zone 5- 8 Lav(s) 2nd Fl 112 0 0 0 -0 0 0 0 0 1.00 0 0 Zone 5 Subtotal 112 0 0 0 0 0 0 0 -Zone 6- 12 Hallway 3rd Fl 407 10,021 203 7-6 895 27,035 3,004 1,230 1.35 1,660 1,230 Zone 6 Subtotal 407 10,021 203 27,035 3,004 1,230 1,660 1,230 - Zone 7- 13 Lav(s) 112 153 3 1 -2 313 150 0 7 1.00 7 7 Zone 7 Subtotal 112 153 3 150 0 7 7 7 System 2 Totals 1693 21,703 439 51,612 9,018 2,348 3,164 2,348 Main Trunk Size: 18x18 in. :System: #2Cooling: System: Summary Cooling Sensible /Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 5.053 85 %/15% 51,612 9,018 60,630 Recommended: 5.735 75 %/25% 51,612 17,204 68,816 Thursday, July 20, 2000 - ::RHVAC ::ReStdential: g: Light CerriMentielHVAC Leads:Program Elite Software DevelOpftlent, Inc.' :: W. Heating A A/C:. Ino. Green:Office-Park: Portland; OR:: 97213 07-20.;2000 Page-17:.: Rqtti:Load:Sunimaryiteliorts System #3 Room Load Summary Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1— 5 1st Fl E Tenant 1964 16,818 340 10-8 544 41,746 2,988 1,899 1.05 1,994 1,899 System 3 Totals 1964 16,818 340 41,746 2,988 1,899 1,994 1,899 Main Trunk Size: 16x16 in. :t Ystern #3:1Coolmg System:Siktintairy ::::::::::::::::::::::::::::::::::::::::::::::::::: -:;-:;:;;;;;::;;;;:;-;::;::;;;;;;;;;;;;;;;;;;;:;;-:;;;;;;;;:-. ;;;;:;:.- . -. : :1 ::::::::::::::::::::::::::: Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.728 93%/7% 41,746 2,988 44,734 Recommended: 4.638 75%/25% 41,746 13,915 55,661 Thursday, July 20, 2000 RHVAiC Resiitential . &Light:COnrmereial:HitACLoads :Program �� Elite :SottwareDevelopment,lnc: Sky Heating &:A)C; Inc �J Green Office :Park :: ::: Portland; :OR:: 87213 0740;2000 .. Page.18: :Room Load Summary sports System :#4 Room Load Summary Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1- 6 2nd Fl W 1964 16,818 340 10 -8 544 41,746 2,988 1,899 1.25 2,374 1,899 Tenant System 4 Totals 1964 16,818 340 41,746 2,988 1,899 2,374 1,899 Main Trunk Size: 16x16 in. System #4 Co ling systemsurrnmary:: . Cooling Sensible /Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.728 93 %/7% 41,746 2,988 44,734 Recommended: 4.638 75 %/25% 41,746 13,915 55,661 Thursday, July 20, 2000 RHVAC Residential & Light :Commetcial:HKAGLoads :Ptograin Elite SoftwareDevelopment, lne. • Sky: leetiii4 x:NG Inc. Green :Office Park..: Portland;: OR: : MI3_.. .......... ..... ......_ ...:.........._ .........._ - ....._., ..........:.........:....07,20 =2000 Pagel 9 Roott Load:Summary - ... ...._._., ------------- :S #5 Rooin L Summary ........... ...... . . .._..... ..... ........................ . Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1- 9 2nd Fl E 1964 15,318 310 10 -8 544 41,746 2,988 1,899 1.05 1,994 1,899 Tenant System 5 Totals 1964 15,318 310 41,746 2,988 1,899 1,994 1,899 Main Trunk Size: 16x16 in. System #SCooling System Summary . Cooling Sensible /Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.728 93 %/7% 41,746 2,988 44,734 Recommended: 4.638 75 %/25% 41,746 13,915 55,661 Thursday, July 20, 2000 :RI4VAC:;:Residetitial: a:Light Commercial HVAC toads:Program .. • . • ...... . .... • ... • .. Ili). • . . • . • • , •Elito Software Development; :Inc.: $16i:Heatitig .40: A1C: Inc, .......................................................................................................................... . ' Green :::Pattland;:0£2:: 07-202000 Page 20.. Roont:Load SummaryReports System*Room Load Summary , • Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1— 10 3rd Fl W 1964 17,999 364 11-8 526 44,373 2,988 2,018 1.25 2,523 2,018 Tenant System 6 Totals 1964 17,999 364 44,373 2,988 2,018 2,523 2,018 Main Trunk Size: 16x16 in. skiiiim406.toolintil soteiiisiiiiiiiiiik ...................................... ''''''''''''''' ... '''''''''''''''''' ...... '''''''''''''''''''' .,.................. ''''''''''' . '''''''' .......................... ''''''''''''''''' Cooling Sensible/Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.947 94%/6% 44,373 2,988 47,361 Recommended: 4.930 75%/25% 44,373 14,791 59,163 Thursday, July 20, 2000 RHVACC Residential:& Light Own meraial:HVAC:Loads :Program Elite SoftwareDevelopment,:inc. &kyf1eating:& A/C, :Inc. Green Office Park: Portland;; OR :: 97213 07. 202000 ::: ::::::......: Page_ 2 R o o m Loact Sufmmary R e p o r t s . System #7 Room :Load Summary - .. Htg Htg Run Run Clg Clg Clg Zone Clg Air Room Area Sens Nom Duct Duct Sens Lat Nom Adj Adj Sys No Name SF Btuh CFM Size Vel Btuh Btuh CFM Fact CFM CFM —Zone 1- 11 3rd Fl E Tenant 1964 17,999 364 11 -8 526 44,373 2,988 2,018 1.25 2,523 2,018 System 7 Totals 1964 17,999 364 44,373 2,988 2,018 2,523 2,018 Main Trunk Size: 16x16 in. System: #7Coaling: System Summary Cooling Sensible /Latent Sensible Latent Total Tons Split Btuh Btuh Btuh Net Required: 3.947 94 %/6% 44,373 2,988 47,361 Recommended: 4.930 75 %/25% 44,373 14,791 59,163 Thursday, July 20, 2000