Loading...
Specifications 0,_)e �zc� - z • OFFICE COPY CONTRACTOR'S MATERIAL TEST CERTIFICATE ABOVEGROUND PIPING COSCO Fire Protection jAN 2 3 2008 PROCEDURE CITYOF fade Upon completion of work, Inspection and tests shall be made by the contractors representative and witnessed by an owner's representative. g CITY OF C All defects shall be corrected and system left in service before contractors personnel finally leave the job. ®U�LDINGO V A SI A certificate shall be filled out by and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. VSS G�'d d It is understood the owners representative's signature in no way prejudices any claim contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances. PROPERTY NAME 'DATE Dick's Sporting Goods ### PROPERTY ADDRESS 9402 Washington Square Road, Tigard, Oregon 97223 ACCEPTED BY APPROVING AUTHORITIES (NAMES) ADDRESS PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS BYES DNO EQUIPMENT USED IS APPROVED © YES ONO IF NO EXPLAIN DEVICES HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OYES ONO INSTRUCTIONS OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO, EXPLAIN LOCATION OF SYSTEM YEAR OF ORIFICE TEMPERATURE MAKE MODEL MANUFACTURER SIZE QUANTITY RATING SPRINKLERS Tyco TY -EC -11 2007 3/4" 11.2K 391 155 Tyco TY -FRB 2007 1/2" 5.6K 102 155 Tyco TY -FRB 2007 1/2" 8.0K 46 286 PIPE AND Type of Pipe Welded Sch 10, Threaded Sch 40, FITTINGS Type of Fittings Grooved, Threaded, MAXIMUM TIME TO OPERATE ALARM VALVE ALARM DEVICE THROUGH TEST CONNECTION OR FLOW TYPE MAKE MODEL MIN. SEC. INDICATOR Flow Switch Potter VSR -F DRY VALVE Q.O.D. MAKE MODEL SERIAL NO MAKE MODEL SERIAL NO. DRY PIPE TIME TO TRIP TIME WATER ALARM OPERATING THRU TEST WATER AIR TRIP POINT REACHED OPERATED TEST CONNECTION PRESSURE PRESSURE AIR PRESSURE TEST OUTLET PROPERLY MIN. SEC PSI PSI PSI MIN. SEC. YES NO WITHOUT Q.O.D. WITH Q.O.D. IF NO, EXPLAIN 'MEASURED FROM TIME INSPECTOR'S TEST CONNECTION IS OPENED. OPERATION ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC PIPING SUPERVISED ❑ YES ❑ NO DETECTING MEDIA SUPERVISED YES DNO DELUGE 8 DOES VALVE OPERATE FROM THE MANUAL TRIP AND /OR REMOTE CONTROL STATUS DYES DNO PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO, EXPLAIN VALVES ❑ YES ❑ NO I DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO MAKE MODEL SUPERVISION LOSS ALARM OPERATE VALVE RELEASE OPERATE RELEASE HYDROSTATIC: Hydrostatic test shall be at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) above static pressure in excess of 150 psi (10.2 bars) for two hours. Different dry-pipe valve clappers shall be left open during test to prevent damage. All aboveground piping TEST leakage shall be stopped. DESCRIPTION PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop which shall not exceed 1 -1/2 psi (0.1 bars) in 24 hours. Test pressure tanks at normal water level and air pressure drop which shall not exceed 1 -1/2 psi (0.1 bars) in 24 hours. ALL PIPING HYDROSTATICALLY TEST AT 200 PSI FOR 2 HRS. IF NO, STATE REASON DRY PIPING PNEUMATICALLY TESTED ❑ YES ❑ NO EQUIPMENT OPERATES PROPERLY E YES ❑ NO DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM SILICATE OR TESTS DERIVATIVES OF SODIUM SILICATE, BRINE OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR STOPPING LEAKS? ® YES ❑ NO DRAIN READING OF GAGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST TEST SUPPLY TEST CONNECTION CONNECTION OPEN WIDE UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING VERIFIED BY COPY OF THE U FORM NO. 858 E YES ❑ NO OTHER EXPLAIN FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING E YES ❑ NO BLANK TESTING NUMBER USED LOCATIONS NUMBER REMOVED GASKETS None WELDED PIPING YES ❑ NO IF YES... DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3 E YES ENO WELDING DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN © YES ENO COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9. LEVEL AR -3 DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED E YES ENO CUTOUTS DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS (DISCS) (DISCS) ARE RETRIEVED? E YES DNO HYDRAULIC NAME PLATE PROVIDED IF NO, EXPLAIN DATA NAMEPLATE E YES ❑ NO DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: REMARKS NAME OF SPRINKLER CONTRACTOR Cosco Fire Protection 11800 NE 95th ST Suite 240, Vancouver, Washington 98682 TEST WITNESSED BY SIGNATURES FOR PR ERTY 0 SI ED) TITLE DATE 1 cd.A4v o l 04 R SPRINKLER CONTRACTOR (SIGNED) TITLE DATE e-eZi — 1 F 1 1 -- 1 6 -4 ADDITIONAL EXPLANATION AND NOTES 6 o : -60 '7 ak, ,mi EQUIPMENT SUBMITTAL . � ;P' DICK'S SPORTING GOODS ``° , TIGARD, OREGON ,kb ,1 ITEM MANF. MODEL SIZE COMMENT o +�� • ,7 a .4 1�' • TAB #1 * ** SPRINKLERS * ** � _ � ` � -� ; Q� f Upright TYCO TY -FRB ' /z' Brass 155 it .1 J Rec. Pendent TYCO TY -FRB ' /z' White 155 (r , Sidewall TYCO TY -FRB '/Y' Brass 155 � a9 , i ., Extended Coverage Upright TYCO EC -11 3/4" Brass 155 i' �. \(, TAB #2 * ** VALVES * ** -4- C`: 1/ Backflow Device Wilkens 350ADA 6" Grooved Gate Valves Check Valve Reliable G 4" Grooved Butterfly Valve Star GBV 4 and 6" Grooved W/ Tamper Test - ANDrain Valve AGF 1000 2" TAB #3 * ** PIPE * ** Grooved Pipe ALLIED SCH 10 1" - 8" Grooved Black & GaIv. Threaded Pipe ALLIED SCH 40 1" - 2'/z' Threaded Black & GaIv. TAB #4 * ** FITTINGS * ** Grooved Couplings ANVILSTAR VARIES 2" - 4" Grooved Fittings ANVILSTAR VARIES 2" - 4" Screwed Fittings ANVILSTAR VARIES 1" - 2" Cast Iron TAB #5 * ** ELECTRICAL DEVICES * ** Flow Switch POTTER VSR -F 4" - 6" Electric Bell POTTER PBA 10" TAB #6 * ** HANGERS * ** Ring Hanger TOLCO FIG. 2 - 1" - 6" Top Beam Clamp TOLCO FIG. 68 3/8" In -Line Sway Brace Attachment TOLCO FIG. 4L Varies Sway Brace Attachment TOLCO FIG. 1001 Varies Universal Swivel Sway Brace Attach. TOLCO FIG. 980 Varies TAB #8 * ** HYDRAULIC CALCULATIONS * ** Remote Area #1 Ordinary Group II .17/3000 1ST Floor Retail Remote Area #3 Extra Hazard .4/2500 1st Floor Stock Room Remote Area #2 Ordinary Group II .17/3000 2ND Floor Retail High Area Remote Area #4 Ordinary Group II .17/3000 2ND Floor Retail Low Area 9 $cJ 3 City of Tigard ,'gip_ rived Plans � By ,. Ad __ D ate j,t)p - 2_6 OFFICE COPY 'AI tUC4i? ' Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY F ® 22, 4e2, 506, and &o Kafactor Upright, Pe , dent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage tained when exposed to corrosive at- General mospheres. Although corrosion resis- jam; . tant coated sprinklers have passed the D escription standard corrosion tests of the appli- _ cable approval agencies, the testing is The Series TY -FRB, 2.8, 4.2, 5.6, and not representative of all possible cor- 8.0 K- factor, Upright and Pendent rosive atmospheres. Consequently, it I I ' Sprinklers described in this data sheet is recommended that the end user be ''`' .-" ' are quick response - standard cover- consulted with respect to the suitability age, decorative 3 mm glass bulb type of these coatings for any given corro- spray sprinklers designed for use in sive environment. The effects of ambi- light or ordinary hazard, commercial ent temperature, concentration of - "%' occupancies such as banks, hotels, chemicals, and gas /chemical velocity, - ^"5-�' shopping malls, etc. should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be i plicable, is intended for use in areas exposed. with a finished ceiling. It uses either a An intermediate level versions of the ----- two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers ," I -. _ ,\ -, \. Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- i ` recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 l adjustment from the ( 19,1 mm ) of total - " adj 1 flush pendent position, or a two -piece WARNINGS Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- . . inch NPT) Recessed Escutcheon with scribed herein must be installed and - _. 1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this ment or up to 1/2 inch (12,7 rnm) of document, as well as with the applica- total adjustment from the flush pen- ble standards of the National Fire Pro - dent position. The adjustment pro- faction Association, in addition to the vided by the Recessed Escutcheon re- standards of any other authorities hav- Model/Sprinkler duces the accuracy to which the fixed ing jurisdiction. Failure to do so may pipe drops to the sprinklers must be impair the performance of these de- Identification cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- Numbers applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT with any questions. TY2231 - Pendent 4.2K, 1/2"NPT IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.OK, 3/4 "NPT WARNING" that provides cautions TY4231 - Pendent 8.OK, 3/4"NPT TY4831- Upright 8.OK, 1/2 "NPT TY4931- Pendent 8.OK, 1/2 "NPT with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 MARCH, 2007 TFP171 Page 2 of 10 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED SURFACE 1/2" MAKE-IN ESCUTCHEON DEFLECTOR i = rrr r W ; aTT1S��TTa 6 _ EU 4E 5 � 71 m 2.1/4" } (11,1 mm) 1 4 (57,2 mm) ��� � �� I NOMINAL I 2 1 1� MAKE -IN 1- 9/16" I �I ' `; 4.1 (55,6 mm) 2- 3/16" 3 (39,7 mm) WRENCH �g ri, FLATS � 1 7 II SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED SURFACE NP MAKE -IN ESCUTCHEON DEFLECTOR AiiiiiiliiffloViitiii 6 t ..„,-- �ff 5 EMI 7/16" � � 2- 3/16" t (11,1 mm) (55,6 mm) 111 III �wm- NOMINAL ; 4 I MAKE -IN li I 1 -1/2" I WRENCH `' 2 3/16" (38,1 mm) (55,6 mm) F LATS 3 14 i 1 SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED SURFACE 1/2" MAKE-IN ESCUTCHEON DEFLECTOR _ r - 7/16" ' 5 2- 3/16" } I �1! a � (11,1 mm) (55,6 mm) A =� U _�— I NOMINAL i f 1tJ MAKE -IN M 1 -1/2" III 1 1 2- 3/16" till . .F� 4 2 (38,1 mm) WRENCH (55,6 mm) ,0 i 3 _. A _. _ . _ F LATS s + t .l SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. - 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING NOMINAL RECESSED SURFACE NP MAKE-IN ESCUTCHEON DEFLECTOR 6 cry r� - - �cY :1TT",`��" 5 1/2" 2- 5/16" leIngi I (12,7 mm) I t (58,7 mm) ��1 � NOMINAL 4 MAKE -IN 1-9/16" I r � r 1 2-1/4" �Y iel 2 (39,7 mm) WRENCH 1 (57,2 mm) y 3 • --- -- FLATS 0 SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 3/4" NPT } PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Page 4 of 10 TFP171 7/16" (11,1 mm) NOMINAL SSU 1/2 MAKE -IN DEFLECTOR NPT f _—=---.-- IIII 2 -1/4" } 2- 3/16" l (57,2 mm) I =� ' I (55,6 mm) li 4 1 -9/16 WRENCH � '.y 2 (39,7 mm) FLATS 3 SSP* / 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical O. erasion Data The glass Bulb contains a fluid which expands when exposed to heat. When Approvals the rated temperature is reached, the UL and C -UL Listed. fluid expands sufficiently to shatter the FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to (Refer to Table A and B for complete activate and water to flow. approval information including corro- sion resistant status.) Design Maximum Working Pressure Refer to Table C. Criteria Discharge Coefficient K = 2.8 GPM /psil/ (40,3 LPM /bar1 /2) The Series TY -FRB Pendent and Up- K = 4.2 GPM /psi / (60,5 LPM /bar1 /2) right Sprinklers are intended for fire K = 5.6 GPM /psi / (80,6 LPM /bar1 /2) protection systems designed in ac- K = 8.0 GPM /psi / (115,2 LPM /bar1 /2) cordance with the standard installation rules recognized by the applicable Temperature Ratings Listing or Approval agency (e.g., UL Refer to Table A and B Listing is based on the requirements of Finishes NFPA 13, and FM Approval is based Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre - Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch- eon, as applicable, is to be used for recessed pendent installations. Physical Characteristics E Frame Bronze 0 Button Brass /Copper Sealing Assembly E Beryllium Nickel w /Teflont a Bulb Glass 0 Compression Screw Bronze a Deflector Copper /Bronze ix Bushing (K =2.8) Bronze 6 0 a m 0 I- TFPI79 Page 5 of 10 SPRINKLER FINISH (See Note 7) K TYPE TEMP. BULB NATURAL CHROME WHITE * ** LIQUID BRASS PLATED POLYESTER 135"F/57°C Orange PENDENT 155 °F /68 °C Red (TY1231) 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 2 8 (TY1131) 286"F/141°C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155"F/68°C Red PENDENT (TY1231)* 175 °F /79 °C Yellow Figure 6 200 °F /93 °C Green 1, 2, 5 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY1231) ** 175 °F /79 °C Yellow Figure 7 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY2231) and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 4.2 (TY2131) 286 °F /141 °C Blue 1 2 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY2231)* 175 °F /79 °C Yellow Figure 8 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY2231) ** 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re- sponse Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- klers. 5. Approved by the City of New York under MEA 354 -01 -E. 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. * ** Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS Page 6 of 10 TFP171 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1,2,3,5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135F/57°C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)* 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3231) ** 175F/79°C Yellow Figure 11 200F/93°C Green 135 °F /57 °C Orange (TY423N) 155F/68°C Red 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200 °F /93 °C Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135F/57°C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)* 175 °F /79 °C Red Figure 12 200 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231)** 175 °F /79 °C Yellow Figure 13 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4931) 1, 2, 5 1/2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6 NPT UPRIGHT 200 °F /93 °C Green (TY4831) 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. * ** Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED PENDENT (TY3231) and 2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A 1/2 RECESSED PENDENT NPT (TY323) PENDENT (TY4231) and 4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A 3/4" RECESSED PENDENT NPT (TY4231) PENDENT (TY3231) and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR) 5.6 UPRIGHT(TY3131) OR 1/2 RECESSED PENDENT 175 PSI (12,1 BAR) NPT (TY3231) N/A (SEE NOTE 1) PENDENT (TY4231) and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 8.0 UPRIGHT (TY4131) 3/4" RECESSED PENDENT NPT (TY4231) N/A 8.0 PENDENT (TY4931) 1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) NPT UPRIGHT (TY4831) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York. TABLE C, MAXIMUM WORKING PRESSURE tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting. Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the ft.lbs. (40,7 Nm) of torque is to be used sprinkler fitting using only the W -Type The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con- 6 Sprinkler Wrench (Ref. Figure 14). be installed in accordance with the fol- nections. Higher levels of torque may With reference to Figures 1, 2, 3, 4, lowing instructions: distort the sprinkler inlet and cause and 5, the W -Type 6 Sprinkler Wrench leakage or impairment of the sprinkler. i to be applied to the sprinkler wrench NOTES Do not attempt to make -up for insuffi- flats. Do not install any bulb type sprinkler if cient adjustment in the escutcheon The Series TY -FRB Recessed Pen - the bulb is cracked or there is a loss of plate by under- or over - tightening the dent Sprinklers must be installed in liquid from the bulb. With the sprinkler sprinkler. Readjust the position of the accordance with the following instruc- held horizontally, a small air bubble sprinkler fitting to suit. tions. should be present. The diameterofthe p 9 air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10. (1,6 mm) for the 135F/57°C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli- inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and temperature ratings. tions. with pipe thread sealant applied to the A leak tight 1/2 inch NPT sprinkler joint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin- should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting. to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type may be used to install sprinklers with Ste With pipe thread sealant ap 7 Recessed Sprinkler Wrench (Ref. ep e 1/2 NPT connections. A leak tight 3/4 St 2 the pipe a thr ea, hand tighten Figure 15). With reference to Figure 1, inch NPT sprinkler joint should be ob- 2, 3, and 4, the W -Type 7 Recessed Page 8 of 10 TFP171 2 -7/8" DIA. _ 2 -7/8" DIA. (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm 5/8 ±1/4" ) 1/2 ±1/8" ( mm) (15,9 ±6,4 mm) 1/4" (6,4 mm) (12,7 ±3,2 mm) 1/4" (6,4 mm 2 -1/4" DIA. 2 -1/4" DIA. ( mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" ��' (3,2 mm) �� I (3,2 mm) ---------=- V = 1/114 - • j ii 1 J . t \ , l r t MOUNTING l,I' MOUNTING I SURFACE SURFACE �, • ��� ► i •�� CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. _ 2 -7/8" DIA. - (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" 12,7 mm 5/8 ±1/4" ( ) 1/2 ±1/8" ( mm) (15,9 ±6,4 mm) 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4 " DIA. 2.1/4" DIA. 1/4" (6,4 mm) . FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" il (3,2 mm) � (3,2 mm) M ------ ill or M ------- i, IOW IP t d:4 N III MOUNTING ■ SUR FA CE SURFACE -• •- - CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm) CLOSURE TY-FRB TY -FRB 3/4" (19,1 mm) TY - 1" (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi- the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced. C. After the ceiling has been in affected fire protection system must be Sprinklers that have been exposed to Step C the - stalled the finish coat has been in- obtained from the proper authorities corrosive products of combustion, but and all personnel who maybe affected have not operated, should be replaced plied, slide on the Style 10, 20, 30, or by this action must be notified if they cannot be completely cleaned 40 Closure over the Series TY -FRB by wiping the sprinkler with a cloth or Sprinkler and push the Closure over The owner must assure that the sprin- the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush. comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam - the event ofa fire or inadvertent opera- age to the sprinklers - before, during, Care and tion may result. and after installation. Sprinklers dam - Absence of an escutcheon, which is aged by dropping, striking, wrench twist /slippage, or the like, must be re- M aintenance used to cover a clearance hole, may delay the time to sprinkler operation in placed. Also, replace any sprinkler a fire situation. that has a cracked bulb or that has lost The Series TY -FRB Sprinklers must liquid from its bulb. (Ref. Installation be maintained and serviced in accord- Sprinklers that are found to be leaking Section). ance with the following instructions: or exhibiting visible signs of corrosion must be replaced. Frequent visual inspections are rec- NOTES ommended to be initially performed for Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers, main control valve for maintenance painted, plated, coated or otherwise after the installation has been com- TFP171 Page 9 of 10 2 -7/8" DIA. _ 2 -7/8" DIA. _ 5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" i ' (3,2 mm) _ �� (3,2 mm) , ,, MOUNTING p i MOUNTING SURFACE _ / SURFACE ' °- - CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm) CLOSURE TY -FRB TY -FRB 3/4" (19,1 mm) 1" (25,4 mm) FIGURE 10 FIGURE 11 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. _ 2 -7/8" DIA. • 5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) (15,9 ±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING FACE OF SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" a (3,2 mm) " (3,2 mm) r et i g . ■ 1 li , i MOUNTING I I ji � i A NM i . MOUNTING SURFACE SURFACE ■ • __._. CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm) FIGURE 12 FIGURE 13 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT pleted, to verify the integrity of the cor- WRENCH rosion resistant coating. Thereafter, ' RECESS annual inspections per NFPA 25 should suffice; however, instead of in- WRENCH RECESS 0' specting from the floor level, a random (END "A" USED FOR sampling of close -up visual inspec- ^ 1/2" NPT MODELS) tions should be made, so as to better .�. determine the exact sprinkler condi- tion and the long term integrity of the ......, corrosion resistant coating, as it may WRENCH RECESS PUSH WRENCH be affected by the corrosive conditions (END "B" USED FOR IN TO ENSURE present. 3/4" NPT MODELS) ENGAGEMENT The owner is responsible for the in- FIGURE 14 WITH SPRINKLER WRENCHING AREA spection, testing, and maintenance of W -TYPE 6 SPRINKLER their fire protection system and de- WRENCH FIGURE 15 vices in compliance with this docu- W -TYPE 7 RECESSED ment, as well as with the applicable SPRINKLER WRENCH standards of the National Fire Protec facturer should be contacted relative to any questions. Association (e.g., NFPA 25), in . addition to the standards of any other It is recommended that automatic local requirements Service n ts accordance and/or national with authorities having jurisdiction. The in- sprinkler systems be inspected, odesequiremen stalling contractor or sprinkler manu- tested, and maintained by a qualified Page 10 of 10 TFP171 P/N 57 - XXX - X - XXX 1 1 TEMPERATURE MODEL/SIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155F/68°C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175F/79°C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200FI93°C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only. 360 8.0K UPRIGHT (1/2 "NPT) TY4831 361 8.0K PENDENT (1/2 "NPT) TY4931 TABLE D PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS Limited In no event shall TFBP be liable, in contract, tort, strict liability or under Ordering any other legal theory, for incidental, Warranty indirect, special or consequential dam- ages, including but not limited to labor Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num- ten (10) years against defects in mate- TFBP's liability exceed an amount bers. rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail - and properly installed and maintained The foregoing warranty is made in lieu ability. under normal use and service. This of any and all other warranties. ex warranty will expire ten (10) years Sprinkler Assemblies with NPT from date of shipment by TFBP. No press or implied. including warranties P warranty is given for products or com- of merchantability and fitness fora oar- Thread Connections: ponents manufactured by companies jicular purpose. Specify: (Specify Model /SIN), Quick Response, (specify K- factor), (specify not affiliated by ownership with TFBP This limited warranty sets forth the ex- temperature rating), Series TY -FRB or for products and components which clusive remedy for claims based on (specify Pendent or Upright) Sprinkler have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating), installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D). not been installed, maintained, modi- is made in contract, tort, strict liability fied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon: plicable Standards of the National Fire This warranty will apply to the full ex- S eci St Re Protection Association, and /or the P fY standards of an other Authorities tent permitted by law. The invalidity, in cessed Escutcheon with 30, or 40 th (speci fy *) fin - y whole or part, of any portion of this ish, P/N (specify *). Having Jurisdiction. Materials found warranty will not affect the remainder. by TFBP to be defective shall be either * Refer to Technical Data Sheet TFP770. repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56- 000 -6 -387. the sale of products or parts of prod- ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench, sprinkler system design errors or inac- P/N 56- 850 -4 -001. curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 m Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series EC-11 & EC-14 ® 11.2 and 1400 II- factor Extended Coverage (Light and Ordinary Hazard) Upright, Pendent, a d Rec. Pendent Sprinklers Corrosion resistant coatings, where General applicable, are utilized to extend the life of copper alloy sprinklers beyond Description that which would otherwise be ob- tained when exposed to corrosive at- J .., ,, r` , The Series EC -11 and EC -14 Ex- mospheres. Although corrosion resis- - ' .9 , v tended Coverage Upright and Pendent taut coated sprinklers have passed the ; :, ..,,,,,,.,.� a , Qs ` Sprinklers are decorative glass bulb standard corrosion tests of the appli- f �?` '- „.,1 1. sprinklers designed for use in light or cable approval agencies, the testing is `7i { t � ordinary hazard occupancies. They not representative of all possible cor- A E are intended for use in automatic rosive atmospheres. Consequently, it sprinkler systems designed in accord- is recommended that the end user be ' I Ex"a -_: ance with standard installation rules consulted with respect to the suitability j _�- �`a` =` i (e.g., NFPA 13) for a maximum cover- of these corrosion resistant coatings age area of 400 ft (37,2 m as com- for any given corrosive environment. pared to the maximum coverage area The effects of ambient temperature, of 130 ft (12,1 m for standard cover- concentration of chemicals, and age sprinklers used in ordinary haz- gas /chemical velocity, should be con - ard occupancies or 225 ft (20,6 m sidered, as a minimum, along with the for standard coverage sprinklers used corrosive nature of the chemical to in light hazard occupancies. which the sprinklers will be exposed. The Series EC -11 and EC -14 Sprin- r . klers feature a UL and C -UL Listing The Series EC a d EC -14 Ex- f^'� that permits their use with unob - structed or non - combustible ob tended Coverage Sprinklers described structed ceiling construction as de- herein must be installed and main- j , fined and permitted by NFPA 13, as tained in compliance with this docu- well as a specific application listing for me as well as with the applicable use under concrete tees. standards of the National Fire Protec- tion Association, in addition to the The Series EC -11 and EC -14 Ex- standards of any other authorities hav- tended Coverage Sprinklers have ing jurisdiction. Failure to do so may been fire tested to compare their per- impair the performance of these de- formance to that of standard coverage vices. spray sprinklers. These tests have The owner is responsible for maintain- odel ®Sprinkler shown that the protection provided is ing their fire protection system and de- equal to or more effective than stand- vices in proper operating condition. Identification and coverage spray sprinklers. The installing contractor or sprinkler manufacturer should be contacted Number with any questions. TY5137 - Upright, 11.2K IMPORTANT TY5237 - Pendent, 11.2K Always refer to Technical Data TY6137 - Upright, 14.0K Sheet TFP700 for the "INSTALLER TY6237 - Pendent,14.0K WARNING" that provides cautions TY5137 is a redesignation for C5137, with respect to handling and instal- G1894, and S2510. lation of sprinkler systems and com- ponents. Improper handling and in- TY5237 is a redesignation for C5237, stallation can permanently damage G1893, and S2511. a sprinkler system or its compo- TY6137 is a redesignation for C6137, nents and cause the sprinkler to fail G1896, and S2610. to operate in a fire situation or cause it to operate prematurely. TY6237 is a redesignation for C6237, G1895, and S2611. Page 1 of 8 FEBRUARY, 2007 TFP220 Page 2 of 8 TFP22O WRENCH 3/4" ** ESCUTCHEON PLATE FLAT NPT SEATING SURFACE 1 1 - Frame 2 Button / r�re n .711. 1 \., �_ 1 / riJ 3 - Sealing Assembly 2 5 -Com 5 - Com p ression Screw 6 - DeflectoDeflector 7/16" - 3 ;� ((61,9 mm) J Temperature rating is �� U PRIGHT & 4 p indicated on deflector PENDENT ' f 1 - 11116" ' 4 Pipe thread = (42,7 mm) connections per ISO �a: 5 7/1 can be provided � 1 on special request. • — — 1 - -� ` 1 6 1/2" (12,7 mm) I NOMINAL MAKE -IN CROSS UPRIGHT PENDENT SECTION FIGURE 1 SERIES EC -11 AND EC -14 EXTENDED COVERAGE SPRINKLERS 11.2 K- FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT 14.0 K- FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT SPRINKLER FINISH (See Note 5) HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE* LEAD LIQUID BRASS PLATED POLYESTER COATED 135F/57°C Orange UPRIGHT 155 °F /68 °C Red 1, 2, 3 * *, 4 LIGHT K =11.2 (TY5137) PENDENT 175 °F /79 °C Yellow K =11.2 (TY5237) 1 , 2, 4 1, 2, 4 200 °F /93 ° C Green K =14.0 Refer to Table B for (TY6237) UL and C -UL 286 °F /141 ° C Blue Sensitivity Rating 135 °F /57 °C Orange and REC. PENDENT 155 °F /68 °C Red 1, 2, 3, 4 Refer to Table C for K =11.2 (TY5237) N/A FM K =14.0 (TY6237) 175 °F /79 °C Yellow Sensitivity Rating With Style 30 200 °F /93 °C Green 1, 2, 4 Escutcheon 286 °F /141 ° C Blue UPRIGHT 135 °F /57 °C Orange K =11.2 (TY5137) 1, 2, 3, 4 ORDINARY K =14.0 (TY6137) 155 °F /68 °C Red 1, 2, 3, 4 and 175 °F /79 °C Yellow Refer to Table B for PENDENT 200 °F /93 °C Green 1, 2, 4 UL and C -UL K =11.2 (TY5237) Sensitivity Rating K =14.0 (TY6237) 286 °F /141 °C Blue and REC. PENDENT 135 °F /57 °C Orange Refer to Table C for K =11.2 (TY5237) 155 °F /68 °C Red FM K =14.0 (TY6237) 1, 2, 4 N/A Sensitivity Rating With Style 40 175 °F /79 °C Yellow Escutcheon 200 °F /93 °C Green NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL). 2.Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3. Approved by Factory Mutual Research Corporation (FM). 4. Approved by the City of New York under MEA 177 -03 -E. 5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. *Frame and Deflector only. Listings and approvals apply to color (Special Order). ** Pendent Only. N /A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS TFP220 Page 3 of 8 LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE 14 x 14 Up. or Pend. — — — — — QR QR QR QR SR 14 x 14 Style 30 Recessed — — — — — QR QR QR QR N/A 14 x 14 Style 40 Recessed — — — — — QR QR QR QR N/A 16 x 16 Up. or Pend. QR* QR" QR* QR" QR* SR SR SR SR SR 16 x 16 Style 30 Recessed QR" QR* QR* QR* QR* SR SR SR SR N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A 18 x 18 Up. or Pend. QR* QR" QR* QR* QR* SR SR SR SR SR 18 x 18 Style 30 Recessed QR* QR" QR* QR* QR' SR SR SR SR N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A NIA SR SR SR SR N/A 20 x 20 Up. or Pend. QR" QR* QR* SR" SR* SR SR SR SR SR 20 x 20 Style 30 Recessed QR* SR* QR* SR* SR* SR SR SR SR N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A QR: Quick Response SR: Standard Response N /A: Not Applicable * Does not apply to Upright K = 14.0 TABLE B SENSITIVITY RATING FOR UL AND C -UL LISTING OF SERIES EC -11 OR EC -14 SPRINKLERS (SEE TABLE D FOR PERMITTED K- FACTOR/AREA COMBINATIONS) LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE 14 x 14 Up. or Pend. — — — — — SR SR SR SR SR 14 x 14 Style 30 Recessed — — — — — N/A N/A N/A N/A N/A 14 x 14 Style 40 Recessed — — — — — N/A N/A N/A N/A N/A 16 x 16 Up. or Pend. QR* QR* N/A N/A NIA SR SR SR SR SR 16 x 16 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 18 x 18 Up. or Pend. QR* QR* N/A N/A N/A SR SR SR SR SR 18 x 18 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Up. or Pend. QR* QR* N/A N/A N/A SR SR SR SR SR 20 x 20 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A QR: Quick Response SR: Standard Response N /A: Not Applicable ' Pendent Only TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC -11 OR EC -14 SPRINKLERS (SEE FM LOSS PREVENTION DATA SHEET 2 -8N FOR PERMITTED K- FACTOR/AREA COMBINATIONS) Page 4 of 8 TFP220 ample: obstructions to sprinkler dis- Technical `) esign charge, obstructions to sprinkler pattern development, obstructions D ata Criteria to prevent sprinkler discharge from reaching hazard, clearance to stor- Approvals The Series EC -11 and EC -14 Ex- age, etc. UL and C -UL Listed. FM Approved. tended Coverage Sprinklers must only (Refer to Table A for complete ap- be installed in accordance with the ap- UL and C -UL Specific Application proval information including corrosion plicable UL and C -UL Listing or FM Listing Requirements For resistant status. The approvals apply Approval requirements as indicated Installation Under Concrete Tees to the service conditions indicated in below. Only the Style 30 or 40 Re- The Series EC -11 and EC -14 Ex- the Design Criteria section.) cessed Escutcheon is to be used for tended Coverage Upright and Pendent Maximum Working Pressure recessed installation, as applicable Sprinklers (TY5137, TY5237, TY6137 175 psi (12,1 bar) (Ref. Table A, B, and C)., & TY6237) have a UL and C -UL Spe- UL and C -UL Listing cific Application Listing for use under Pipe Thread Connection Requirements concrete tees when installed as fol- 3/4 inch NPT lows: Discharge Coefficients 1. The Series EC -11 and EC -14 Sprin- 1. The stems of the concrete tee con - K = 11.2 GPM /psis / klers may be used for the coverage (161,3 LPM /bar areas shown in Table D, based on struction must spaced at less than K = 14.0 GPM /psi / maintaining the minimum specified 7.5 feet (2,3 m) on center but more (201,6 LPM /bar / flow rate as a function of coverage than 3 feet (0,9 m) on center. The area and hazard group for all of the depth of the concrete tees must not Temperature Ratin sprinklers in the design area. exceed 30 inches (762 mm). The 135 °F /57 °C to 286 °F /141 °C maximum permitted concrete tee Finish 2. The Series EC -11 and EC -14 Sprin- length is 32 feet (9,8 m); however, Sprinkler: Refer to Table A klers are permitted to be used with where the concrete tee length ex Recessed Escutcheon: White Coated, unobstructed or non - combustible ceeds 32 feet (9,8 m), non- combus Chrome Plated, and Brass Plated obstructed ceiling construction as tible baffles, equal in height to the defined and permitted by NFPA 13. depth of the tees, can be installed so Physical Characteristics For example: that the space between the tees Frame Bronze does not exceed 32 feet (9,8 m) in Button Bronze Unobstructed, combustible or non- length. Sealing Assembly combustible, ceiling construction 2. The sprinkler deflectors are to be Beryllium Nickel w /Teflon f with a deflector to ceiling /roof deck located in a horizontal plane at or Bulb Glass (3 mrn dia.) distance of 1 to 12 inches (25 to 300 above 1 inch (25,4 mm) below the Compression Screw mm). bottom of the concrete tee stems. Bronze Deflector Brass Obstructed, non - combustible, ceil- 3. When the sprinkler deflectors are ing construction with a deflector to located higher than a horizontal Patents cation below structural members of 1 to 6 inches (25 to 150 mm) and a plane 1 inch (251,4 mm) beneath the U.S.A. Patent Numbers 5,366,022; maximum deflector to ceiling /roof bottom of the concrete tee stems, 5,579,846; 5,584,344; 5,609,211; deck distance of 22 inches (550 the obstruction to sprinkler dis- 5,862,994; and 5,865,256. mm) charge criteria requirements of NFPA 13 for extended coverage up- Operation 3. The Series EC -11 and EC -14 Sprin- right sprinklers applies. klers having been specifically tested FM Approval The glass bulb contains a fluid which and listed for non-combustible ob- 9 structed construction are permitted Requirements expands when exposed to heat. When The Series EC -11 and EC -14 Ex- the rated temperature is reached, the to be used within trusses barjoists tended Coverage Sprinklers are to be fluid expands sufficiently to shatter the having non - combustible web mem- installed in accordance with the appli- glass bulb, which then allows the tiers greater than 1 inch (25.4 mm) cable Factory Mutual Loss Prevention sprinkler to activate and flow water. when applying the 4 times obstruc Data Sheet for limited use in buildings tion criteria rule defined under "Ob- structions to Sprinkler Discharge of specific roof construction and for the Pattern Development protection of certain specific ordinary hazard (non- storage and /or non -flam- 4. The minimum allowable spacing be- or combustible liquid) occupan- tween the Series EC -11 and EC -14 cies. Information provided in the FM Sprinklers, to prevent cold solder- Loss Prevention Data Sheets relate to, ing, is 8 feet (2,4 m) for upright sprin but are not limited to, hydraulic design, klers and 9 feet (2,7 m) for pendent ceiling slope and obstructions, mini sprinklers. mum and maximum allowable spec- ing, and deflector -to ceiling distance. 5. The Series EC -11 and EC -14 Sprin- These criteria may differ from UL klers are to be installed in accord- and /or NFPA criteria, therefore the de- ance with all other requirements of signer should review and become fa- NFPA 13 for extended coverage up- miliar with Factory Mutual require - right and pendent sprinklers. For ex- ments before proceeding with design. TFP22O Page 5 of 8 2 -7/8" DIA. "FITTING SIDE" _ 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) TOWARDS SPRINKLER (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FITTING FACE OF (57,2 mm) SPRINKLER — �_ FITTING (3,2 mm) / WREN / ' WRENCH CH 1 ~I �� RECESS 4 \ (END ""A„) MOUNTING 70 I MOUNTING FIGURE4 SURFACE II.. CLOSURE A SURE I V PLATE W 3 SPRINKLER WRENCH 1 -3/8" (34,9 mm) WRENCH RECESS i�' 1 -1/8" (28,6 mm) r FIGURE 2 SERIES EC -11 AND EC -14 RECESSED PENDENT SPRINKLER ASSEMBLY ..... WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON ft )12 o , _ o 2 -7/8" DIA. _ - - 1 - 5/8 ±1/4" e (73,0 mm) 3/4" (19,1 mm) ME (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) W HEX FACE OF (57,2 mm) FIGURE 5 SPRINKLER 1 /8" W - TYPE 22 RECESSED FITTING (3,2 mm) SPRINKLER WRENCH 1 I11 i_ 4 MOUNTING MOUNTING SURFACE 411 PLATE CLOSURE 1 -3/8" (34,9 mm) 7/8" (22,2 mm) FIGURE 3 SERIES EC -11 AND EC -14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON Page 6 of 8 Tf: P220 GROUPI GROUP II LIGHT HAZARD ORDINARY HAZARD ORDINARY HAZARD 0.10 GPM /FT 0.15 GPM /FT 0.20 GPM /FT DESCRIPTION AREA GPM PSI GPM PSI GPM PSI TY5137 (K =11.2) UPRIGHT 14 x 14 - - 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 TY5237 (K =11.2) PENDENT 14 x 14 - - 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 TY6137 (K =14.0) UPRIGHT 14 x 14 N/A N/A - - - - 16 x 16 N/A N/A 39 7.8 51 13.3 18 x 18 N/A N/A 49 12.3 65 21.6 20 x 20 N/A N/A 60 18.4 80 32.7 TY6237 (K =14.0) PENDENT 14 x 14 - - - - - - 16 x 16 37 7.0 39 7.8 51 13.3 18 x 18 37 7.0 49 12.3 65 21.6 20 x 20 40 8.2 60 18.4 80 32.7 1 ft. = 0.3048 m 1 ft = 0.093 m 1 gpm = 3.785 Ipm 1 psi = 0.06895 bar 1 gpm /ft = 40.74 mm /min TABLE D FLOW CRITERIA FOR UL AND C -UL LISTING OF SERIES EC -11 AND EC -14 SPRINKLERS Installation Step 1. The sprinkler must be installed with the deflector parallel to the mount- ing surface. Pendent sprinklers must The Series EC -11 and EC -14 Sprin- be installed in the pendent position, klers must be installed in accordance and upright sprinklers must be in- with the following instructions: stalled in the upright position. NOTES Step 2. After installing the Style 30 or Do not install any bulb type sprinkler if 40 mounting plate (or other escutch- the bulb is cracked or there is a loss of eon, as applicable) over the sprinkler liquid from the bulb. With the sprinkler pipe threads and with pipe thread held horizontally, a small air bubble sealant applied to the pipe threads, should be present. The diameterofthe hand tighten the sprinkler into the air bubble is approximately 1/16 inch sprinkler fitting. (1,6 mm) for the 135 °F /57 °C to 3/32 Step 3. Wrench tighten upright or pen - inch (2,4 mm) for the 286 °F /141 °C dent sprinklers using only the W -Type temperature ratings. 3 (End A) Sprinkler Wrench. Wrench A leak tight 3/4 inch NPTsprinklerjoint tighten the recessed pendent sprin- should be obtained with a torque of 10 klers using only the W -Type 22 Sprin- to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi- kler Wrench. The wrench recess of the mum of 30 ft.lbs. (40.7 Nm) of torque applicable sprinkler wrench (Ref. Fig - is to be used to install sprinklers. ure 4 and 5) is to be applied to the Higher levels of torque may distort the sprinkler wrench flats (Ref. Figure 1). sprinkler inlet with consequent leak- age or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in an Escutcheon Plate by under- or over - tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. TFP220 Page 7 of 8 Care and stalling contractor or sprinkler ma L ®fed facturer should be contacted relative ive to any questions. Maintenance It is recommended that automatic Warranty The Series EC -11 and EC -14 Sprin- sprinkler systems be inspected, Products manufactured by Tyco Fire & klers must be maintained and serviced tested, and maintained by a qualified Building Products (TFBP) are war - in accordance with the following in- Inspection Service in accordance with ranted solely to the original Buyer for structions: local requirements and /or national ten (10) years against defects in mate - codes. rial and workmanship when paid for NOTE and properly installed and maintained Before closing a fire protection system under normal use and service. This main control valve for maintenance warranty will expire ten (10) years work on the fire protection system that from date of shipment by TFBP. No it controls, permission to shut down the warranty is given for products or com- affected fire protection systems must ponents manufactured by companies be obtained from the proper authori- not affiliated by ownership with TFBP ties and all personnel who may be or for products and components which affected by this action must be notified. have been subject to misuse, improper installation. corrosion, or which have not been installed, maintained, modi- Sprinklers that are found to be leaking fied or repaired in accordance with ap- or exhibiting visible signs of corrosion plicable Standards of the National Fire must be replaced. Protection Association, and /or the standards of any other Authorities Automatic sprinklers must never be painted, plated, coated, or otherwise Having Jurisdiction. Materials found after leaving the factory. Modi- repaired o TFBP be defective replaced, shall either altered a fied sprinklers must be replaced. repaired TFBP replaced, at TFBP's sole S Sprinklers that have been exposed to option. ri es any n assumes, e rsor to assume nor P p authorizes any person to assume for corrosive products of combustion, but it, any other obligation in connection have not operated, should be replaced with the sale of products or parts of if they cannot be completely cleaned products. TFBP shall not be responsi- by wiping the sprinkler with a cloth or ble for sprinkler system design errors by brushing it with a soft bristle brush. or inaccurate or incomplete informa- Care must be exercised to avoid dam- tion supplied by Buyer or Buyer's rep - age to the sprinklers - before, during, resentatives. and after installation. Sprinklers dam- In no event shall TFBP be liable, in aged by dropping, striking, wrench contract, tort, strict liability or under twist /slippage, or the like, must be re- any other legal theory, for incidental, placed. Also, replace any sprinkler that indirect, special or consequential dam - has a cracked bulb or that has lost ages, including but not limited to labor liquid from its bulb. (Ref. Installation charges, regardless of whether TFBP Section). was informed about the possibility of Frequent visual inspections are rec- such damages, and in no event shall ommended to be initially performed for TFBP's liability exceed an amount corrosion resistant coated sprinklers, equal to the sales price. after the installation has been com- The foregoing warranty is made in lieu pleted, to verify the integrity of the cor- of any and all other warranties. ex- rosion resistant coating. Thereafter, press or implied. including warranties annual inspections per NFPA 25 of merchantability and fitness for a should suffice; however, instead of in- particular purpose, specting from the floor level, a random sampling of close -up visual inspec- This limited warranty sets forth the ex- tions should be made, so as to better clusive remedy for claims based on determine the exact sprinkler condi- failure of or defect in products, materi- tion and the long term integrity of the als or components, whether the claim corrosion resistant coating, as it may is made in contract, tort, strict liability be affected by the corrosive conditions or any other legal theory. present. This warranty will apply to the full ex- tent permitted by law. The invalidity, in The owner is responsible for the in- or spection, testing, maintenance of wa ty part, not any portion this s P 9, warranty will not affect the remai nder. their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in- Page 8 of 8 TFP220 Ordering P/N 51 - AAA - B -CCC Procedure AAA = 893 (for TY5237 When placing an order, indicate the full K11.2 Pendent) product name. Please specify the AAA = 894 (for TY5137 Sprinkler Identification Number (SIN), K11.2 Upright) quantity, and temperature rating. Re- AAA = 895 (for TY6237 fer to the Price List for complete listing K14.0 Pendent) of Part Numbers. AAA = 896 (for TY6137 Contact your local distributor for avail- K14.0 Upright) ability. Sprinkler Assemblies with NPT B = 1 (for Natural Brass) Thread Connections: B = 3 (for White [RAL9010])* Specify: (specify SIN), (specify K -Fac- B = 4 (for White Polyester) tor), (specify temperature rating), B = 7 (for Lead Coated (specify Pendent or Upright) Extended B = 9 (for Chrome Plated) Coverage Sprinkler with (specify fin- ish), P/N (specify - from Table E, where applicable). CCC = 135 (for 135 °F /57 °C) CCC = 155 (for 155 °F /68 °C) Recessed Escutcheon: CCC = 175 (for 175 °F /79 °C) Specify: Style (specify 30 or 40) Re CCC = 200 (for 200 °F /93 °C) cessed Escutcheon with (specify fin- ish), P/N (specify). *Eastern Hemisphere sales only. Style 30 Recessed Escutcheon Chrome Plated PSN 56- 705 -9 -011 TABLE E White Color Coated PSN 56- 705 -4 -011 White (RAL9010)' PSN 56- 705 -3 -011 PART NUMBERS FOR Brass Plated PSN 56- 705 -2 -011 EC -11 AND EC -14 SPRINKLERS Style 40 Recessed Escutcheon Chrome Plated PSN 56- 700 -9 -010 White Color Coated PSN 56- 700 -4 -010 White (RAL9010)* PSN 56- 700 -3 -010 Brass Plated PSN 56- 700 -2 -010 *Eastern Hemisphere sales only. Sprinkler Wrench: Specify: W -Type 3 Sprinkler Wrench, P/N 56- 895 -1 -001 Specify: W -Type 22 Recessed Sprin- kler Wrench, P/N 56- 665 -7 -001 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 WILKINS Model 350ADA a gifig company Double Check Detector Assembly APPLICATION ., -. 1 Designed for installation on potable water connections in ,� fire sprinkler systems to protect against both backsipho- •k 7. nage and backpressure of polluted water into the potable . water supply. Model 350ADA shall provide protection where (with OS &Y gates) (with BGVIC valves) a potential health hazard does not exist. Incorporates me- tered by -pass to detect leaks and unauthorized water use. FEATURES STANDARDS COMPLIANCE ( 4 "- 8" Horz. & Vertical) Sizes: ❑ 2 1/2" ❑ 3" ❑ 4" ❑ 6" ❑ 8" ❑ 10" Maximum working water pressure 175 PSI • ASSE® Listed 1048 Maximum working water temperature 140 °F • AWWA Compliant C510 (with gates only) Hydrostatic test pressure 350 PSI • CSA® Certified End connections (Grooved for steel pipe) AWWA C606 • UL® Classified (21/2 " -10 ") (Flanged) ANSI B16.1 C -UL® Classified (21/2 " -10 ") OPTIONS Class 125 FM® Approved (Suffixes can be combined) • Approved by the Foundation for Cross Connection ❑ - with flanged end OS & Y gate valves (standard) Control and Hydraulic Research at the University of ❑ L - less shut -off valves (grooved body connections) Southern California (2 1 /2 " -10" except 10" BGVIC) ❑ LM - less water meter ❑ - with remote reading meter MATERIALS ❑ with gpm meter (standard) Main valve body Ductile Iron ASTM A 536 Grade 4 ❑ - with cu ft/min meter Access covers Ductile Iron ASTM A 536 Grade 4 ❑ G with grooved end OS &Ygate valves Coatings FDA Approved electrostatic epoxy finish CI FG - with flanged inlet gate connection and grooved Internals Stainless steel, 300 Series outlet gate connection NORYLTM, NSF Listed ❑ PI with Post Indicator Gate Valves (4"-10") Fasteners & springs Stainless Steel, 300 Series ❑ BGVIC - with grooved end butterfly valves Elastomers EPDM (FDA approved) Buna Nitrile (FDA approved) ACCESSORIES Polymers NORYLTM, NSF Listed ❑ Repair kit (rubber only) 1 ❑ Thermal expansion tank (Model WXTP) MODEL 350ADA ❑ OS & Y Gate valve tamper switch (OSY-40) !I with OS &Y option =I - m - I=I r1 B ❑ Test Cock Lock (Model TCL24) ' - •r,'.i : W !'. °:-,i1 likI —,I I %'h I� p , ° o DIMENSIONS & WEIGHTS (do not include pkg.) I � C , �� -11 WEIGHT a ----1 c D MODEL wm 4 350ADA WITHOUT WITH OS &Y WITH OS&Y BUTTERFLY SIZE GATES GATES (GXF) GATES (GXG) VALVES MODEL 350ADA with ^ : — ^ — BGVIC option I ii in. mm lbs. kg lbs. kg lbs. kg lbs. kg kal, 9 .• I .' B - " 21/2 65 105 47.5 207 94 199 90.3 123.8 56.2 Ill(!1f — d �I1� r✓ `� 3 80 104 47 224 101.5 214 97 124.4 56.5 I�bl I 11I IIiIMII C IF 4 100 91 41.3 245 111 219 99.4 123 55.8 - I 6 150 141 64 377 171 347 158 193 87.6 mai 8 200 302 137 778 353.2 754 342.3 410 186 B c 10 250 355 161 1040 472.7 918 416.5 527 239.3 A DIMS\SON (approximate) MODE E WITH 350ADA LESS E A BUTTERFLY C D OS&Y BUTTERFLY UTTERFLY F 0 Attention: Model 350ADA SEE VALVES VALVES OS &Y OPEN CLOSED VALVES (grooved body) and Model 350DA in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mrn (flange body) have different lay 21/2 65 351/8 892 321/8 816 201/8 511 41/2 114 9 229 163/8 416 137/8 352 8 203 6 152 71/4 184 3 80 361/8 918 325/8 829 201/8 511 4112 114 9 229 187/8 479 155/8 397 8 203 6 152 71/4 184 lengths. 4 100 38 965 331/8 842 197/8 505 41/2 114 9 229 223/4 578 181/4 464 91/8 232 6 152 8 203 6 150 47 1194 39 7/8 1013 25 7/8 657 5 1/2 140 10 1/2 267 30 1/8 765 23 3/4 603 10 1/8 257 7 178 10 254 8 200 615/8 1565 541/2 1384 381/2 978 10 254 12 305 373/4 959 291/4 743 1115/16 303 81/2 216 11 279 10 250 64 5/8 1642 54 1/2 1384 38 1/2 978 10 254 12 305 45 3/4 1162 35 3/8 899 13 5/16 338 8 1/2 216 12 305 (Patent No. 5,913,331) BOCUMENT #: REVISION: BF- 350ADA 11/06 Page 1 of 2 FLOW CHARACTERISTICS MODEL 350ADA 2 1/2 ", 3" & 4" (STANDARD & METRIC) FLOW RATES (Vs) 12.6 25.2 37.9 50.5 y 15 I { 104 0. 0 2 1/2" (65mm) i' 4" (100mm) y 2 10 ■ 169 P ° o ix 5 3" (80mm) 35 Er u) W 0 . cc 0 200 400 600 800 a FLOW RATES (GPM) MODEL 350ADA 6 ", 8" & 10 "(STANDARD & METRIC) FLOW RATES (Vs) 63.1 126.2 189.3 252.4 y 15 a 6" (150mm) _ powaff- .- 0 10 �_ a ° (2oomm) •� 10' (2somm) 69 9 g 5 _f — -- -�-- - D 35 cc 7 _�� _ • N 1 co V) 1 W W CC a s 0 1000 2000 3000 4000 eL FLOW RATES (GPM) ORated Flow (Established by approval agencies) TYPICAL INSTALLATION Capacity thru Schedule 40 Pipe (GPM) Local codes shall govern installation requirements. Unless Pipe size 5 ft /sec 7.5 ft /sec 10 ft/sec 15 ft/sec otherwise specified, the assembly shall be mounted at a 2 1/2" 75 112 149 224 minimum of 12" (305mm) and a maximum of 30" (762mm) 3" 115 173 230 346 above adequate drains with sufficient side clearance for 4" 198 298 397 595 testing and maintenance. The installation shall be made so 6" 450 675 900 1351 that no part of the unit can be submerged. 8" 780 1169 1559 2339 10" 1229 1843 2458 3687 =, 12" 1763 2644 3525 5288 PROTECTIVE �� ENCLOSURE E 1.1 = 0 � - AW 1 ,,.44 so 6 : via _.,,...- F 0 N2 I = �$= a_?�-, P I 12' MIN. • i��s 30' MAX. ;' AIR a� '! 4+.,,414, ,c t+ lsAk1 Az U€ QI ..�T II " l 1117 I.I - . n -rl _ - DIRECTION OF FLOW ` .) I ll 0 MODEL 350ADABGVIC (VERTICAL INSTALLATION) MODEL 350ADA (OUTDOOR INSTALLATION) SPECIFICATIONS The Double Check Detector Backflow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be NorylTM (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM. The first and second check valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector Backflow Prevention Assembly shall be a WILKINS Model 350ADA. Page 2 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805 /238 -7100 Fax:805/238 -5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905 /405 -8272 Fax:905/405 -1292 Product Support Help Line: 1- 877 - BACKFLOW (1- 877- 222 -5356) • Website: http: / /www.zurn.com Bulletin 807 Rev.E CO OM Rebabid Model G 2 / 3 4" & 6" co (65mm, 80mm, ° 100mm,150mm) Swing Check Valves m TM The Right -Check Features 1. Grooved end connections. 1 ( # 2. Compact, lightweight design. t. LISTE° 143 v 3. Non - slamming, spring loaded clap- ( ', g 4 flit • 1 per to minimize water hammer. ISO PSI 1993 4. Approved for horizontal and vertical , installation. 5. Streamlined body design provides very low friction loss. Figure 1 6. Elastomer faced clapper provides 3. Friction loss, expressed in equivalent length of leak -free, non- sticking sealing. Sch. 40 pipe with C = 120 (based on Hazen and Williams formula): General 2 - 7 ft. (65mm -231 cm) Reliable Model G Swing Check Valves are multiple 3" - 7 ft. (80mm - 213cm) purpose valves performing regular check valve 4" - 10 ft. (100mm- 305cm) duties with very low friction loss. All four sizes are 6" - 16 ft. (150mm - 488cm) approved for use in fire protection systems. Typical 4. Standard grooved end dimensions per ANSI /AWWA applications include connections between public C606. water supplies and private fire systems, at the Pressure J low tole discharge from fire pumps, at gravity tank connections and at fire department pumper O connections. The 4" (80mm) Model G Check Valve is provided t 1 /2 with a " • NPT (RY) supply side connection (Item 12, . c n om ^ C F c o F This supply side connection is optional for all other valve sizes and must be specified. d M o ,c. Grooved end connections provide fast and easy installation using listed or approved mechanical grooved couplings. Rigid style grooved couplings can be used for positive clamping to resist flexural and torsional loads. F low . gprn (L /ruin) Right- Check valves and associated equipment Technical Data should periodically be given a thorough inspection Face—to —Face and test. NFPA 25 provides minimum maintenance Valve Size Dimensions Shipping weight requirements. Check valves should be inspected and 21" (65mm) 7.03" (178mm) 9 lbs. (4kg) operated at least annually. Parts should be replaced 3" (80mm) 7.62" (193mm) 11 lbs. (5kg) as required. 4" (100mm) 8.44 (214mm) 17 lbs. (7.7kg) When Model G Swing Check Valves are installed 6" (150mm) 10.25 (260mm) 38 lbs. (17.25kg) vertically, the direction of the flow arrow must point upward. For horizontal installations, the hinge pin Approvals must be located at the top. 1. Listed by Underwriters Laboratories, Inc. Valve Description 2. Underwriters Laboratories certified for Canada. 1. Rated working pressure 250 psi (17,25 bar). 3. Approved by Factory Mutual Research Corp.` 2. Factory hydrostatic test pressure 500 psi (34,5 bar). 4. NYC MEA 258 -93 -E. Note: 1 bar =100 kPa " FM Approved both a "Single" check valve and "Anti -Water Hammer" check valve. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552 Parts List - Refer to Figure 2 Item Part Number No. Part Name Material Quantity 2y (65mm) 3" (80mm) 4" (100mm) 6" (150mm) 1* Valve Body Gray Iron, ASTM -A48 Class 30A 1 91005022 91005023 91005024 91005026 2* Seat Bronze C83600 or C93200, ASTM -B505 1 96020200 96020300 96020400 96020600 3 Clapper Stainless Steel 304, ASTM -A240 1 91816112 91816113 91816114 91816116 4 Facing Seal " EPDM Rubber 1 95520200 95520300 95520400 95520600 5 Clamping Ring Stainless Steel 304, ASTM -A240 1 95290300 95290300 95290400 95290600 6 Gasket" EPDM Rubber 1 93720302 93720302 93720604 93720604 7 Spring Stainless Steel 302, ASTM -A313 1 96400300 96400300 96400400 96400600 8 Hinge Pin Stainless Steel 303, ASTM -A582 1 95000280 95000300 95006824 95000600 9 Bolt Stainless Steel 304, ASTM -F593 1 91090300 91090300 91090400 91090600 10 Locknut " Stainless Steel 303, ASTM -F594 1 94911420 94911420 94913816 94913816 11 Plug, y" NPT Steel 1 95201800 95201800 95201800 95201800 12 Plug, X" NPT Steel 1 Optional Optional 98604402 Optional " Replacement Seal Kit 1 6888040025 6888040030 6888040040 6888040060 *Not field replaceable. Valve Disassembly 1. Close the main water supply valve and drain the L system. 2. Remove the check valve from the piping system. 0 O £ 0 2 3. Inspect the Seat (2) for any cuts, scrapes and { _ dents. Replace the valve if any damage is found. .../f , 4. To replace the Facing Seal (4), remove the Clapper (3), unscrew the Locknut (10) and remove the ,_, Retention. Bolt (9). 1 1,,,1 Valve Reassembly ?. 1. Thor clean the Clapper (3). Insert the ==- ■ • Retention Bolt (9) with a new Gasket (6). ' ___ . ° R'-�� _ Ir 2. Place the new Facing Seal (4) and the Clamping 1/2 Ring (5) against the Clapper (3). Tighten the new ... Locknut (10) to 21 in. -Ibs. (2.37N•m) torque in 2' • lamikt (63mm) and 3" (76mm) sizes and to 52 in. -Ibs. IN (5.87N•m) in 4" (101mm) and 6" (152mm) sizes. 3. Insert the clapper assembly into the valve through the downstream opening. Reinsert the Hinge Pin (8) 0 0 while holding the coils of the properly oriented 0 0 0 Spring (7) in place. Install the hinge pin Plug (11). Figure 2 4. Reinstall the check valve in the system. 5. Place the system back in service. Ordering Information Specify: 1. Model G Right— Check Valve. 2. Size. 3. 1" NPT (R1/2) optional supply side connection for valve sizes other than 4" (100mm). Contact the installing contractor or Reliable if any difficulties are experienced. Should replacement parts be needed, use only genuine Reliable parts. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by , + . „ ,, .. , z> , Aks< The Reliable Automatic Sprinkler Co., Inc. ® Recycled Paper. ® n ® (800) 431 -1588 Sales Offices . (800) 848 - 6051 Sales Fax Revision lines indicate updated or new data. R T (914) 668-3470 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 05/01 P/N9999970071 GROOVED VALVES FOR FIRE PROTECTION STAR ®PIPEPRODUCTS @ Y L LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 MODEL GBV -4 IS UL & ULC AND FACTORY MUTUAL APPROVED Fire Protection Valve. UL & LC Listed, FMRC Approved. 2 1/2" - 8" UL LISTED FOR Indoor & Outdoor Service Grooved mechanical end connections. Nylon coated ductile iron. Extended neck. Elastomer encapsulated disc. Supplied with two intemal supervisory switches. 300 PSI Non -Shock Cold Water 2 1/2" - 8" MATERIAL LIST PART 1. Upper Stern Stainless Steel AISI 420 2. Upper Bushing Carbon Steel ( Fiber -FIon +Glass Coating) 3. "O "Ring EPDM 4. Body Ductile Iron ASTM A -536 with Nylon Coating I t n■••y 5. Disc Ductile Iron ASTM A -536 with EPDM Encapsulation E . - -,- 6. Lower Bushing Carbon Steel (Fiber -FIon +Glass Coating) _ - - i _ (j 8. Lower Stem Stainless Steel AISI 420 e l A t � S 8. Dust Plug EPDM 'll , - � A 9. Nameplate Aluminum n, 10. Gear Operator Ductile Iron ASTM A -536, Powder Coated 11 nil ` . _N' 11. Indicator Flag Ductile Iron ASTM A -536, Powder Coated 1 3` 12. Handwheel Carbon Steel ASTM A 619 0 c D IV DIMENSIONS - WEIGHTS G r H - J SIZE A B C D E F G 11 . 2 1/2" 2.88 2.72 0.31 0.63 3.72 12.48 6.81 �� 11 :: I 3" 3.50 3.34 0.31 0.63 3.00 13.03 6.81 �i.� M - � � l� 1 4" 4.50 4.33 0.38 0.63 4.54 14.96 6.81 ' 13 6" 6.63 6.45 0.38 0.63 5.25 17.79 6.81 fi .. 0 8" 8.63 8.44 0.44 0.75 5.81 19.72 6.81 0 1.....__ Y ' O 0 K �i d' ! i4 s F SIZE H J K L M Weight �1 �j�� (16s.) WI 0 Al , 2 1/2" 2.95 5.31 5.31 3.35 4.92 18 3" 2.95 5.31 5.60 3.62 4.92 20 ME O W! 4" 2.95 5.31 6.89 4.25 4.92 24 -'- , 8r - 6" 2.95 7.60 8.27 5.71 8.86 34 O � ' 8" 2.95 7.60 9.21 6.69 8.86 50 $ 0 I MODEL GBV -3 IS UL LISTED AND FACTORY MUTUAL APPROVED Fire Protection Valve. 2 1/2" - 8" For Indoor and Outdoor Service. 10" for Indoor Service Only. Grooved mechanical end connections. Nylon coated ductile iron Extended neck. Elastomer encapsulated disc. Supplied with internal supervisory switches. Made in the USA. 300 PSI Non -Shock Cold Water 2 1/2" - 8" 175 PSI Non -Shock Cold Water 10" MATERIAL UST PART SPECIFICATION 1. Upper Stern Stainless Steel, ASTM A -582 Type 416 ' 2. Upper Bushing PTFE Bronze Sintered on Steel • 1 3. "O" Ring Buna -N 4. Body Ductile Iron ASTM A -395 with Nylon Coating • • 5. Disc Ductile Iron ASTM A -395 with EPDM Encapsulation 6. Lower Bushing PTFE Bronze Sintered on Steel 7. Lower Stern Stainless Steel, ASTM A -582 Type 416 8. Dust Plug PVC 9. Nameplate Aluminum _ ,' 10. Gear Operator Cast Iron and Steel E I I 11. Indicator Flag Cast Iron 41 L l 12. Handwheel Cast Iron -1 ' I L ' DIMENSIONS - WEIGHTS 8 IIR I S I Z E A B C D E F G H J �ru ,, 2 1/2" 2.88 2.72 0.31 0.63 3.85 2.42 11.71 3 63 4.18 i`,: t 3" 3.50 3.34 0.31 0.63 3,85 2.86 12.25 3 63 4.18 0 c p S I ' I 4" 4.50 4.33 0.38 0.63 4.56 3.84 13.95 3 63 4.18 ` H _� J - K L 5" 5.56 5.39 0.38 0.63 5.86 4.79 14.93 3 63 4.18 Q "T,.' ! 6" 6.63 6 45 0.38 0.63 5.86 5.73 17.31 3 63 4.18 Mile 77 III . / 8" 8.63 8.44 0 44 0.75 5.26 7.71 19.20 3 63 4.18 I II I ��� 10" 10.75 10.5E 0.50 0.75 6.29 9.56 25.11 438 3.00: - 7 , 0 I �� o` r SIZE K L MN P O R Wlbg,t ©- 0 -: 0 l 2 1/2" 2.50 7.81 543 4.19 3.25 6.00 3.46 22 -- , ...C.1°""- ��� 1 I�11 N 3" 2.50 7.81 5.68 4.44 N. 4 3.54 6.00 3.97 23 -N. ® 0 1_AII 4" 2.50 7.81 6.58 5.33 4.35 6.00 5.03 27 F n il © ,- II 5" 2.50 7.81 7.07 5.83 4.84 6.00 6.27 35 6" 2.50 7.81 8.35 7.11 5.93 6.00 7.25 42 ?,,,.._ p 8" 2.50 7.81 9.29 8.05 6.87 6.00 9.25 47 C i i `O 11 18" 3.00 7.68 11.50 9.86 9.17 9.00 11.25 62 Page 18 n s - }qq�''.,}./ {tt 01 1 1 1 I I . , - 4 41. ,,..i*t.: 1 .1 • rl . .. ';'r r � a r " r ye V... h u 1 k ,j . .I i re lc `C�' _ f1 1 . f '' t1 TEST .3 1 ,,, /// 4 r a Ji My � . �t ry/ a. tR "UIiIFICG S,'� ��.�w ,, s • P ∎ -10 ` . ;.'' -, ' ‘'4 .. i, ^ . 7,, 4 ,-.' ,,, ',..;4t. , a..--,- , , ' '•-• t' 1 . ' l `, ( fi r ? T :ti` ' '' .,.'` '.' r= r' r r - * ,w ,: � i . � ' 1 ' ' ` 1 5 1 i p$ umomq A; ; v ` `4 + . 7 , .r' t � T * i is LIL ti ti T � � ' % „ � a� , 1 TEST - ,- /:..;-:o 1 1 ; . _, o i } ` a ♦O _ r - Yer, Ce " wd i .�n. N .. �. t � f:S \ u i p C . � t. i'K . . p. I I 14;. - u - rt q.,, w rlw+w:••••i rg '' r i .., , ' ..m'+' . :::=4f. � I� t r � svi: ems. ' .... II �, � F 1 I''`i:- - i r .,, I1J. MODEL 1000 !> {", t : r' ,1 1 ,? . i .:'•'....''''. . • 1 1� 1 . �, 4 1 � 1 • • ill,EN 'AND OT DING { , • O The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multistory installat 1 Complies with all requirements of NFPA -13, NFPA -13R, and NFPA -13D u Positive shut off u Single Handle o Tapped for Pressure Gauge u Tamper Resistant Orifice permanently installed SENSIBLY . PRICED. • Available with all required Orifices NOT; J Orifice size noted on Indicator plate 41/ERPRICEDI' ci Lightweight and compact 300 PSI Rating • Integral tamper resistant sight glasses visit us on the Internet o Full range of sizes from 3/4” to 2" at �awww testandraln com U _ L MODEL 1000 300 PSI 1 1; - r L:NI ILI1® -_ _ _ 3/411 /4" 1 1./2" 2" PLAN VIEW FRONTVIEW/VERTICAL INSTALLATION . . I FRQM.:3RANCH T I GAUGE INI;T - Pj / -�` �/ PROVIDED J � � I 10 DPAIN ( \V.,:iyi i J L i ; � : • � L I - STREET a ;;:.:,) ____ f ' I FRONT VIEW /HORIZONTAL INSTALLATION � j to DP; N ~ I !�� . — E - -- ^ •I STREET El. •.-----': - - - -- 4 :RFPE / a i1 ■ I _ c_ . :_ . �i j- -- FOR RIGHT HAND /STRAIGHT INSTALLATION r ■ To DRAIN I , 1 APPROVALS: 1 -.. . J UL and ULC Listed , U D FM Approved except 3/4" ORIFICE SIZE L NYC BD. of S &A CAL. NO. 720-87-SM AVAILABLE - 3/8, 7/16, 1 /2, 17/32. ELO(5 /8)', ESFR(3 /4)• J CA. State Fire Marshall DIMENSIONS • INCHES SIZE A B C D E F G H 3/4'' 5' /tb" 1 1 /2 " 2 3 5 /a 3 1 /8" 13/16" 4 9/16" 6 " MATERIAL LIST 4 125mm 37.55mm 55 .6Srn 1 � t6 n, 93.23mm b5 68m 1 m 45.SCmm I i 7 I6% 4 ? /emm - - -- - - - _- 1" 51 6" 1 1 /2" 2 1/16. 3 5 /8 " 3 3 1 13 /16 " 416" 4 I28m 17.58mrn 5;65rnm 93 ?3 65 88mm 4 S.3C+nm 117 14::)2 42mm PART: MATERIAL: 1 1/4" 5 7 /16 " 1 11 /16' 2 93 /16 ' 4 1 /4" 3 5 /16' 1 6' 5 93 /I6 5 1 /2 HANDLE STEEL 137 4270mm 65.36rr.m 1 08.Stmm 82 L'dmm SO,b9 141 . 39mm 19? 28mm STEM ROD BRASS 7 " 13/16 3 T! 5 1 /10 „ 3 7 /8 , 2 8" 8 I /are U 7 / BALL C.V. BRONZE 1 1/211 �7 4550mm 8 1 SOn•,m 127 mm 99I8rnm 66.97 206.6: 273.tOmm BODY BRONZE VALVE SEAT IMPREGNATED TEFLON 2" 6 7 116' 1 13 /16" 3 1 /a" 5 'he," 3 7 48 " 2 5 43" 8 1/2" 10 7 /8" INDICATOR PLATE STEEL 163 3Smm 45 SOmm BI.SOmm _ 127rnm 99 I8mm 66.97mm 706.6 7.mm 273.COmm HANDLE LOCK SPRING STEEL 'Available on 1 1/4" to 2" size units only. USA Patent 0414/361 and other patents pending • . . • I The Reliable Automatic Sprinkler Co., Inc 525 N. MacQuesten Parkway JOB NAME: Mount Vernon, NY 10552 # %:'; ARCHITECT: Phone 800.431.1588 ENGINEER: I www.reliablesprinkler.com CONTRACTOR: _ _ MADE IN U.$ A. — • • • ." 1, ....'•;;;`, . ' ''. .r,"' - ',■:-.. ' ' fr . 1 -, ;,.;:, , l , ...',...- , ,.'' . . • .. !;.:L , , , i ,i , ' } ' ; ',1 ,." . ..■. '' ',.. • ., . j ', :', .' ', . ,., ' ' , • • ' ": t. : ,,,,. , „ -. • ,., , .., •:•; , ..., , J ,7,..r.. j . ,,.', ' ' ' ',..,.' , , : :., ''" -•' -- :f..* ',..,',, '' •,',..,... ',.. , .',. '; • ,..". .: `,1! '-''.• ,2: ' : .•;...:,,:•:,':' ■i; . ''' •I' • : : ' • ' ',., •,- ) C , , , ,'-' . , .1, :,', •_:, .,. , ' .',''...;:. :. ,.: ...;:,', ,,, ':, . • '. ; , , .> • ' .". .,.,.... '' ^•''', • . ,. ',"' ''''- . :.:: •'.. '' ' ''... ■• .: •-, ..-; -.- .. • .• • . ..:"- ''''.- : :1 ,).. '.''':- • ''' - . : ' . ' - - • .'". '. ' ':' - -.;:- '-' •. ..,' • .. . " 1 - -1 -',.-• ..''',..-'' ,;''..'' '.:•::•.:.:•'•-; -..." '''.', '......:' •,': : • i ' ... .•:: -. •• , ''' . • '' . ' ' .' :•'.-:•-• ..' '.• .• ''''. : ■ ; 1'..... ''''...`... '...,,• • , ', , ;.''' ..,:., ' .' ...,"..:' '''. ' , .. • '-' •••• ' .' ' 0 . ' ' ''• ' , . ' 1 '',' t ' • ' ' '. •:"- - ' . :-: ,• . ., . : . . • , . , . .:: '.... , .,,,.. . . . • .•.. ; ?' ,,' •.-, ' . ' ''. •...: '. '. •' - , •;%'''',•'''... - •:-..' '.'' ..;" . • ,. "• ' ' ' • ", ' '' ' ' ''. • • ' ''' i' - - •• ' ''' '' ' - • .. '. -' ' 1. --' TUBE f2S SONDUIT •-• , ,i' s ■ • ,.. ' ' .,•,; d •:::: .. ,..:..•.,,:,•....,. _..........•.„.,.;.......,......:,:.....:,...:J.......•,,•,,..14,......?...r.:,..::,•,,,.::...,:„...,:::•...,..::„..,.:.,... :!,..,,,,...:..,..,.......::•...,....,:.,::,.....;.:.:::_____,..: •••••...,.:.:..,..,..:::._. ::.•:..:1„,, „„..,::.........,..... ......,:::,..., ,...•.,:,.:,...,..,.....‘.:„...::;,.....•:;,.......:•.,!.:.:::::...,;.,,.,:::::,.,..:•......:.•• ... •..,.....,,,.....,,..:,..,....... ,.....„......-.....-•, .• ,...:•„:..,:,:,,,,,,............:•..... .... -...,.-.•• ,.. •...:•:„.....-,,,..::,,,,,:,..„.....„...:•-,::—....._„.,„::._.:,-.....,..,.......,:..... :......'.,.........•• .,.: , ,. •.:. ......... .: ....., ....„.: ..-..,.„, ...... .....• , . • - . .....,...,:„.... ........:•....,,...„.•,..,„ „.....,..:...,.....„..... ...., ....;.:•:,,,.- ....:.,..-.-:.•.;:. ,.- - . .. . .. ......,......,..ev, -' *N.,. -' . . - • . ..... ., ,.; „,,,..;,.. • . - ,,....., •* . -..,...-..---; . -.;...-..,:,-.-. ,. .. ... .. . • . 0. ,' - • -,. .-,,. . .-:-..,?,:',-...).. ,( ,•'... r . „. .''., '•••.„ ;'' -:•-'. . • .•!{, - - . . • . • - •i r „ . „. . ,, ..... ... . : . . , . -..(N, : . . e•:' . . • . -. - ),. \ • _ . ..,,....... . • . . ....,..._ .. ... _ .. . .. . . • ,.:, \•.s. . -..„'. . • • • . . . . . : -. . - - - . , .. ..,-4: ',%, .„... _ ..... •. . . - - .. ,..... .. ,, .. .. • ... .. , . .., 4.• .- . . . „ .. ,, , •il .. . . . , . 1 -, : r1 •': - .•' '1 '..; ; '-':•''''.:= X', ".. SI, • • . • . ..,,,,,,,,,,,,,.... ._. , , . _ ... , , . ., • ,.;"„. ,,, ,t.: - :,, 4 f.....- -t_ .. . .. , . 1 .',:- ,.. ;. - . 7 , , ;-,, - .,i... -1... ..,?,-. •,...c ',, \ .,.,11,',.-. ' '';'•- 1 • .. '''.; ''t. la '• ' '' -*, ,'''' ,'-'.•:..., :. -. •''1'1,, ., , - i; . ....'-44, .1 i : -' ;', 1 :•;: e ...,•;.7,tr ,,.., ,,, •1_,: • . „,._ ' -:.•,_.'..-1-4, - - - ii;77,. .•,:. ' • • 'r ', .., i ::- . . - ..,'- . . t 1,-: t - - 0 - :'.i.'-; ,1 1 , - - :','• .::.--. (:. ' .,-;!...,. /..- •;---!.' -- ,,•-.',-, :: , ' ',.,-'-'.',' ..: 4 4. ....,--`.-. c' ,::'„.,-.- -.:- — .-.,-. :-.. 4,14' ',';'. ,r..- ..,, . ...4.4.4,,,, , . ,... - e -..;, • , ,,,....- .-4 ., .,, V1. '-.1.?!, -.,, :-r-c".. .• :. , 4. > -**, • ' \ - ' • . 41V ';''.1..' fi -' - ., . • . -', •,,, - ?-:', • . ,- - • ,..,..„ ,, '''"•'' '*4 : :' .:,'. ''',.. -. ..!. .. r - ,:"•:., , . AP • 7 ' .'-' !-- 1.1 , rf '.:r , ',,,,,'^]N ,: 1:1 r'4` ',.' ' .; 11, • ,2k„ h •• , "i::: :V:' ' • ,- .,'''',;', 7 , ,,:.-- 1 .'" ,'1 ' ..4 4. -.11i ..: 4 :1 .. . , .:,1r. '..,' .,-, • .! ..\, ;:. ,,IM 9( ' f. ' %k ' 'al . .. '''‘Ai i r. '- 1-:::,.. - . ' '' .1: • =.,... 7 ,": - 11 , 1 ?- it.: '/..0 1 ' &l ti l i ...'' '1*,..41• - ; tv,',, .. . , . ;;, , b :••••••• :4 ..e - fa Ii• ' .1, , ' 11 '' ',,, ni , ' ' .- , • , $ „, .. . , ,,%.! a ',, % , ,, - 1.t...% i i ' " .. 4: '.:, ''. 4947,1.; ' ':,j ,,* ,l' 't w • ' it i7 ‘ 41 l: , 1•'• l' f - 4 4 ';;10t 4 .. .. . . . ..., ,,.., v,,T,',,< . tt^;-'-1. 3- cr' '-' : ' !'; :'' '''' ''. .? 1 :.:,-,.'i' - -;,.."-ar::.- - ,; : fe; - 4 ,.. ,,, ,", p - . , ,,„„....,.., ' ! " •,/ ' ' ,■..',';'-'..• 7 ... -: , . , : •- . ' , ' f ,•• :j ' '''':. ; ',"': '''''','%!..'-:--...,`,...'.3',7:77•X,,i.,.?•,i',. ,7../. - ,,,, ''..7: t„, • , „, , ,‘ jaj,! , i' ■''' ''.. ' „ ..1 ..-7, jt ',.-,`:.; Zi f, ... , 7... :'-, •' -, ':.- -1 ' ' • ,,,‘ •%.;'•'''.7,/,:i'l•T 14"e,01'. .1.1f,:i,:,;.. ' 'I ' '..1 - •': ,.1/4 ' ' - 1 , ,'. ` : .‘ . '.'''.: • i „,,r /,--f - a : 74 . -. ..r.':'....,..;,L: , - ,. , , , ' ''-: ;• S.. 'L.' ••:, C'e*•,', s i , '7 . .4t.:,-.. ] \ :. ,. .. , r '''-:,._....:•:•,,;,-,.,,, • ... ... ' i - . /1;'''' .1'4.41"0-inr.%..1.`14F -41. : : : -: 1111 `''' :- :' , , • ,•.- ,*, -. . ,yA rj,' -I - ' = '•-• ' -^' "'"."- ,:',' 2 ,. •• l'. .. , -' '.,, ' - F': 't :•:';',' ' - .,-..., , • ,' ( , -.11; 1.,i- .■,' i ',.,. --, :i. ,1 ,'..r.,:t.",,,,'•;-...:• ,...,s' i, ,,,,, / , ' PI :.•-.-- A •,:..,.;:''. • - -4 ,,4 '4.',', .7 - 4, .---, , ,.,--...4.q?,:,:.';,..:,-,.-,:,,,,-....-,...y.!.:-J,---,,..,,,,,...-it.„-44--1.. '-:.c- 1 ,1 - ,i,; : ;-, • .:` ; ,.. ; „ ,.: .. - I, , '. :,,: '•,- . • .- •• ,. . , .'-r:_' . .t , ' - `:‘-:r7•!:trJ.,....)r ,-• -.• . r ',.-!..•,,,-,-, -•:_•,„ •:- :4.0 r • .-3 •• ,- .1 4 F"'• ,..,' . ,,.. ,••.-„;.,,..•.,.,..e, i4.. , ,•,,,, . ill ;4 '1," , •'-..,r ,-, r' 4 ',"?.'. ',,- 5tu ' 4 ‘,:' ' '• :.' ..': ',1 : •, ' ,,,,,, ' - '• • •' „ .,i , ,,,,, , , `,t , '4. ' • y. ' , ti•P'+; .. .": ,::......... :i , , , , ,,. titi'',-: - . '" 1,1 1 ., r :,' ), „.." ' '''''4"; ,i.,.... ., ••,' •';t'''''" ,...,.,.._. . ■ . - - ... '''''' '''''-'' ' ' - '. • t'' ' '", ,i,...-=-....,A4...,',..,:..-:-'4-.':::' ... r - ''''' f ''...";'.' :., •• ''' ' ' '1‘:,•''SY.:'t..'W....i,'',-,, '77,17''.; ''-'1''-'--(.'..--;,''''• .7-'.''.-Al!,i,h-4..:14:...'_.--.,%. ''''''::::\., - •:`;.6-lif . g'' -.1-: . •Q` - l r : c . - .7:...- ...-..,_ .,,,,,,• ;Et; - 0 ...- ' •_ , -.. • is,T,','T-1::,: . • , . ' • .- - :' ,,-. ' 1_• , - , 'J' , ',' '.-, - - - - : " •.' .- 10. -, , .;', . . ' ' .. , . • ';;;T:.i.' - - - . • ' _ ' , - ' ) ,.,.:.,..--, t: - • ' ,.. „;. : 11 , '.: . - ' j W it h A B F P )Protection) ion /,,m:...,..,...,.i !re:'Y'.:,;:'••:.:.,.-,'5,::,;,,,,,,-,::.:.:4,7,H ---,,,,-,,f,, ,I ,, i,;,: , ::::: -, ... , .:1 , ::-, ,, ,,•;,,,,,,;,,,..;,,,,..,::,,.. , .., ,,,„,,,,,,,,,..,,,;,,..„,,,,,,,,, ..,,„.,, ,,,,....,,,.:,,,,,,,::::,...., :,:,,I,,;;;:,,;-„,,,,:;-:-.-,,b1,,,,,,,-,;:,...:::!,,,,,,,:,.,,,,:;:,,,.Lj;::::,!,::::;,,,,,,,,,..,,-..„....:.....,;,..,,,,„,,,,,;.... ,,,,,::,.,..,,,..:-..:L„,,,‘,, ,-.„,,,,,i,r..„,,,......,,,,,,,,,,,.:„,,,;3,,..-„p.,,i:i,1),;,,I,,,,.!::::.:t,:.:,,,•;:,,...1;,-,::.::',,,,;,:,:,*,,i,,,:ik.,-.:',!::',i,:'',.::'.::11::'1,..',1::::',..5:ii,:'-'4,-:.---•.'....'-'.':..''. „,.,,,,t..,...,....„,f, .: ,..,', ,'.,"'...,',,,,,••',..1;14.1'.,'T,',.-,1!.,;;F;,1,4•,,t,"4:•:-.+,,-.4,•••.".;;i ,!",:l.•1"-••,'1-:-'.,'.'•:';'•.•.;•:.-,.'''';•2.•.'“'!"-'4.,''•--•••..•'''''!"''.'2''-'''''''''.•,....•••-• ''••••,•-• ' ' ' ' ' '' ' '' ' '' 1,• • . ' ••:,••;,J!:,::L..,W ...i;'•,:l. •, ,,,,,', • .;‘;'.."• . ... . . • • - : . . . - lol. , 7,,. -1'.f''',',:--:•:?';';':''''''--4.if,':'''-'1." ' -. 7.; '• : . '''' - tilr .., ;1 ,•• ' ; -1 , •'•••' 4 . f. • ! -• ,11i : - 1- ''''''' : . ' 11 •:'-•- .' - '' ' ' '' '; ' ,'Y; ' ::1' . i ,1•';',', 0 :::,,,,, --:, , 0 ,...,;:.,,,...• f .4, ;',!. '''''''-', v 1:.;, , ...,,,: - :-• - .- . ‘, . ''.._ : '' E ,.„•,..,.•....... ..:,..,.. ......1..,......,......„. .... .,,,,...} .:,..„.::„...,, .....' .„.t., .. .„,.... : „.„:.5•:•....„•.6;.„..„,..,.., ...:„.......„:,„.,.„...,,:•:. ,.........:•:,....2........:.•,r....,„:„........,..••:.:....,...,,:„.„..„...:.:,...,....._..,...._•. • .. .... . ).,._..i:•.•::,,...1....,,,, :‘,., •„•,,,,,,,... 1•11.:,..: :,....i. _ 6 .,,...:•,•;,....,t,...,..,,,i..::,,...,.....„.,.,....„.„.....„,..,.,y,,....9v.o.,:ii.4.1v.:•:•:„,..,,,,,,....,,,,,,.71.„:7::::::..,:•r,i:;.1..,,,,.,..,;::,:„...;,..,,........,...,.._:,„:„.,,,.:...:,..,...::•.,...,_:A.,::::::1..:,....::......_•,,..:.::„.•::.."," .....i.,_,:::.,..,...,:;.,,,... ,,,„„.. .,„....,, „, .. , .. ,. :• ,, ..:::.,..: ,, .......t. „,„ •..1:.:0.:•...:6; , , , .. ,, ,, , ..,:::: , ......„.......:...„•:.•. , .... , .....,..„4_.:1•1 , 1,.,..;::::,,,,.:,.......:::.;.....,..:,.1.,, , :.:,,„.,:„...,.,..4:1....„i.:.„..,,i.1,.:::.,.....:::;11,...„,.,!,,,,......,..,,,,....J:•,„,..i.•,:f....,:::;...,:,,,,...±..,....,:::,.,..,,,,....::......,„..:,.,0.;;:, ; .,,....J...,., : : : ,....,....... 1 ..,. : ........ .,..1.,.:,.. ... :...,,,..,....:•_,,,, ;:,,, 5 ,,, .:•.::. , _ ,., •:. ,, •. , • , ... , .:... , • ,,. r , ; , • , 1 ,,,, . , i ,,, ;. ,, ... , ..::.:}..... „ :_ , ... ,, I. , ....:: „ .. , : , : , •: ,,,,,„ :. ,, , , I ,, • ,,,, :.:4.. , ..:::: , ..J.f ,„ 2:. , ,, , ,.... , . , ...: , .:,,, , ,.,,•,...,.....,•„:. , ...i.:.•,..:,,..,..,;.•:,,.,;:i_...,: , .;,..,,:..J.i.:_:,..,,r,„..,_._.u.,,...,i_,,,:,,t,,:,i...iz,,,,,...::::,:,..,::::_,it,:,..,..,...,....,4(1.;:.,,,..„),......ii..:...,..,.1..„1.!.;,.,„.;,.:;.„,:i...,,,,„•:..,....,......,1.......•:.,1,.,„ i .„:..i,„...;••:::.,,:.,. 1 ...„... :t i,,,c ) .:.,......,..„,., ; :i i ...,. : . : . :: ,,,..,,,. : ,...... : ..,.. ::::: „ : ,„,...„._,..,.,. :7: .,,,_ . „,....,...,., :. ..:. , ..:•0. , ......: , . , .,•.••.•... ,, •. „ ,..:•... , ....: „ .:•. , 4 , .,.. , ..... , ...... , ,, „ ..i.,. , ..:,: , ;... , ,•,, , u,.:.‘,... „ .,.1:,.,,;,. , ,. , ,:.,... , ,:., „ ,.,.:,.;:.,....i.,:!,..,•,,,,,•,4,,...,:i;.,,,:..„,..i...,T.,.,„..:..,...„.,,,...,..,„..7,.,:....,...:4it,,,,„,....;.:,.,1„...,..,,,.if:::4:....„:„!,:,,..,,,....,,i;4..„,,,..;,,,,„cv..:,.., 4 ...,,...„.,„.„ 7 ,,,„,...,... 01 . i . c . ; ,. ;;5 ,, vs ...,. : „.„,..,,,,, ; ,:„.._.,...,..,,..,.. : _....•_ ,, ..----. - .,:„..„,,,,..,...,.,.......,_...,...._ ..,„.,::„...,,....i....„,........„..,,,,,,.,...,...,,....,,..,... a , Wi t;' c . _.. ,i 4-®/Sc?_L.., Fully Listed and FM Approved Sprinkler Pipe When you specify Schedule -10 /Schedule -40 sprinkler pipe you get a UL listed and FM approved product. Although these products do not require separate approvals, Schedule -10 /Schedule -40 gives you the extra quality assurance you demand. Our Sch -10 (1' /4 "- 8 ") pipe and Sch -40 (1"- 2'4") pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Galvanized Pipe , , �7 , ... 7 r , Sch40 Specifications ` .,,,,.;.;;':•. ' ' F . NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ Wt/Litt (21') Wtllitt (24') Wtllitt (25') Schedule -10 /Schedule -40 product can be In; mm In; mm Lbs /Ft; Kg /m Lbs/Ft; Kg /m Lift Lbs; Kg Lbs; Kg Lbs; Kg "hot -dip" galvanized to meet FM 1" 1.049 1.680 2.05 70 2,470 2,822 2,940 requirements for dry systems in 25 26.6 2.5 3.05 70 1,120 1,280 1,334 accordance with the zinc coating specifications of ASTM A -123. 11/4" 1.380 2.270 2.93 51 2,431 2,778 2,894 32 35.1 4.36 4.36 51 1,103 1,260 1,313 Y '' 11z" 1.610 2.720 3.61 44 2,513 2,872 2,992 Superior Coati n,, z q r ; 40 40.9 4.0 5.37 44 1,140 1,303 1,357 Our advanced formula mill coating of- 2" 2.067 3.650 5.13 30 2,300 2,628 2,738 fers a clean, durable surface. It is also 50 52.5 5.4 7.63 30 1,043 1,192 1,242 paint -ready for custom color applications 21/2 2.469 5.790 7.86 19 2,310 2,640 2,750 without special preparation. 65 62.7 8.6 11.73 19 1,048 1,197 1,247 The internal surface of all black Allied Tube & Conduit Fire Sprinkler pipe r ` 1 Sch rS eeifi0atlonS products up to 4.5000" in diameter is ._ p coated with our new Antibacterial For- NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ Wt/Litt (21') WtlLitt (24') W1/Lift (25') mule, "ABF ". In scientific laboratory In; mm In; mm Lbs/Ft; Kg /m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg test, ABS proved to have superior resis- 1" 1.097 1.400 1.81 91 2,675 3,053 3,185 tance to microbial colonization of pipe 25 27.9 2.1 2.70 91 1,213 1,385 1,445 walls, thereby delaying or possibly pre- 11/4" 1.442 1.810 2.52 61 2,319 2,664 2,760 venting the onset of Microbiologically 32 36.6 2.7 3.75 61 1,052 1,208 1,252 Influenced corrosion (MIC) when the 11/2" 1.682 2.080 104 61 2,664 3,045 3,172 First Sprinkler System is first installed. 40 42.7 3.1 4.52 61 1,208 1,381 1,439 Americaii, , !-. 2 " 2.157 2.640 4.22 37 2,051 2,344 2,442 50 54.8 3.9 6.28 37 930 1,063 1,108 Meets "Buy American" requirement 21/2" 2.635 3.530 5.89 30 2,224 2,542 2,648 and is available through distributors in 65 66.9 5.3 8.77 30 1,009 1,153 1,201 the USA, Canada and Mexico. 3" 3.260 4.330 7.94 19 1,728 1,975 2,057 80 82.8 6.4 11.82 19 784 896 933 Specifications 8r.Api3idif als 4" 4.260 5.610 11.78 19 2,238 2,558 2,665 Schedule -10 /Schedule -40 pipe are in 90 108.2 8.3 17.53 19 1,015 1,160 1,209 compliance with the following: 5" 5.295 7.77 17.33 10 1,632 1,865 1,943 125 134.5 11.56 25.80 10 740 846 881 ASTM A -I35, and NFPA 13. Both pipe 6" 6.357 9.290 23.03 10 1,951 2,230 2,322 products have a working pressure rating 150 161.5 13.8 34.27 10 885 1,012 1,053 of 300 psi maximum and also meet the 8" 8.249 16.490 40.15 7 2,424 2,770 2,885 stringent requirement for the following 200 209.5 24.5 59.75 7 1,100 1,256 1,309 tests: • Welded Outlets 0 41 1: GO • Hydrostatic Pressure Listed Approved Listed • Side Wall Rupture • Vibration Test tax® / Row Control 1 16100 S. Lathrop • Harvey, IL 60426 Customer Service: allied 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882 5543 UBE & CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708 T S5 - 3 G STAR ®PIPEPRODUCTS GROOVED COUPLINGS U LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 The C-4 rigid coupling is designed for ' _ or ( 0448000 , .., _ rigid piping applications. Cast in place • teeth bite into the pipe /fitting shoulder to i _ I firmly restrict movement. C-4 RIGID COUPLING NOMINAL ACTUAL UL or FM MAX. MAX. ALLOW. NUTS /BOLTS DIM ENS IONS - Inch /,nr33 APPROX. SIZE PIPE WORKING END PIPE END (INCH) WEIGHT IN. SIZE P.S.I. /' LOAD SEP. QTY. SIZE A B C EACH IN.,,:,:,, Lbs.ir; IN.,, Lbs. ? 1 1/4 1.660 300 1623 0 - 0.06 2 3/8x2 4.20 2.55 1.70 1.48 1 1/2 1.900 300 2126 0 - 0.06 2 3/8x2 4.44 2.81 1.70 1.66 2 2.375 300 3323 0 - 0.06 2 3/8x2 1/4 4.88 3.28 1.76 1.85 J; 2 1/2 2.875 300 4869 0 - 0.06 2 3/8x2 1/2 5.53 3.78 1.76 2.11 3 O.D. 3.000 300 5301 0 - 0.06 2 3/8x2 1/2 5.93 4.00 1.76 2.21 3 3.500 300 7216 0 - 0.12 2 3/8x2 1/2 6.38 4.40 1.76 2.41 4 4.500 300 11928 0 - 0.12 2 3/8x2 1/2 7.68 5.59 1.98 3.17 5 5.563 300 17014 0 - 0.12 2 1/2x3 9.06 6.93 2.06 4.50 6 6.625 300 24130 0 - 0.12 2 1/2x3 10.75 7.87 1.98 5.84 6.5 O.D. 6.500 300 23228 0 - 0.12 2 1/2x3 10.25 7.99 2.06 5.82 8 8.625 300 35056 0 - 0.12 2 5/8x3 1/2 13.44 10.21 2.22 10.82 10 10.750 300 45381 0 - 0.12 2 7/8x5 16.70 12.88 2.62 21.50 12 12.750 300 51071 0 - 0.12 2 7/8x5 1/2 18.50 14.89 2.62 27.36 1. Working pressure and /or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. * Contact Star Pipe Products for actual listings on specific pipes The C -3 coupling is a flexible light weight style which - - . • is ideal for fire protection services and other services where low pressure and ambient temperature conditions . 0 1 - 1/4iittiod . are expected. C -3 LW FLEXIBLE COUPLING NOMINAL ACT UAL ULorFMMAX. MAX. ALLOW. NUTS /BOLTS DEFLECTION DIMENSIONS -Inch/mm AP P R OX. SIZE PIPE WORKING END PIPE END (INCH) DEG.PER PIPE WEIGHT IN. SIZE P.S.I. /' LOAD SEP. QT Y. SIZE COUP LING IN. /FT. A 8 C EACH IN r : r_; 'P;-r , Lbsdr^ IN.r, Lbs :u 1 1/4 1.660 300 649 0 - 0.13 2 3/8x2 4° -19' 0.90 3.82 2.53 1.65 1.16 1 1/2 1.900 300 851 0 - 0.13 2 3/8x2 3° - 46' 0.79 4.06 2.78 1.65 1.16 2 2.375 300 1329 0 - 0.13 2 3/8x2 1/4 3° - 01' 0.63 4.78 3.25 171 1.59 2 1/2 2.875 300 1948 0 - 0.13 2 3/8x2 1/4 2° - 29' 0.52 5.29 3.75 1.71 1.82 3 3.500 300 2886 0 - 0.13 2 3/8x2 1/2 2° - 03' 0.43 5.94 4.39 1.71 2.23 4 4.500 300 4771 0 - 0.25 2 1/2x2 3/4 3° -11' 0.67 7.68 5.81 2.06 4.42 ^::f 6 6.625 300 10342 0 - 0.25 2 5/8x3 1/4 2° - 10' 0.45 10.75 8.09 2.06 7.00 l 8 8.625 300 17528 0 - 025 2 3/4x4 114 1° - 40' 0.35 13.44 10.43 2.06 13.00 Contact Star Pipe Products for actual listings on specific pipes Page 5 G STAR ®PIPEPRODUCTS GROOVED COUPLINGS k U L 1 e• LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 The model C -1 is our standard coupling designed for a broad range of piping applications. It is a flexible style which provides allowance for controlled pipe movement caused by thermal changes, settling or seismic action as well as dampen noise and vibration. C -1 FLEXIBLE COUPLING NOMINAL ACTUAL ULoFMMAX. MAX. ALLOW. NUT S/BOLT 5 DEFLECTION DIMENSIONS- Inch /:a!^ AP PR OX. SIZE PIPE WORKING END PIPE END (INCH) DEG.PER PIPE WEIGHT IN. 51IE P.S.1. /• LOAD SEP. aT Y. SIZE COUPLING IN. /F 1. A 8 C EACH • IN... Lbs.. ::: IN.' -,:. Lbs.:;.:. . . - 1 1/4 1.660 300 2164 0 - 0.13 2 3/8x2 46 -19' 0.90 4.20 2.75 1.78 1.40 � =-;'--,.. 1 1/2 1.900 300 2835 0 - 0.13 2 3/8x2 39 - 4i' 0.79 4.44 3.03 1.78 1.48 r ^ > I 2 2.375 300 4430 0 0.13 2 3/8x2 39 -01' 0.63 4.88 3.46 1.84 2.00 2 1/2 2.875 300 6492 0 - 0.13 2 3/8x2 28 -29' 0.52 5.53 4.12 1.85 2.25 3 O.D. 3.000 300 7069 0 - 0.13 2 3/8x2 28 -29' 0.50 5.50 4.00 1.84 2.25 '- ' n.. • 3 3.500 300 9621 0 - 0.13 2 1/2x2 3/4 26 -03' 0.43 6.38 4.62 1.84 170 4 4.500 300 11928 0 - 0.25 2 112x2 3/4 315 41' 0.67 7.68 5.81 2.06 4.4 5 5.563 300 17014 0 - 025 2 5/8x3 1/4 20 -35' 0.54 9.68 7.12 2.06 6.26 '' 4; 6 6.625 300 24130 0 - 0.25 2 518x3 114 26 -10' 0.45 10.75 8.09 2.06 7.00 J • . •', ,- -. ,,=-. k ill 6.5 O.D. 6.500 300 23228 0 - 0.25 2 5 /8x3 1/4 28 -10' 0.46 10.50 8.00 2.06 7.00 8 ' 8.625 300 35056 0 - 0.25 2 3/4x4 1/4 16 -40' 0.35 13.44 10.43 2.38 13.00 , 10 10750 300 45381 0- 025 2 7/8x5 1/2 18 -20' 0.28 16.00 13.25 2.59 2100 12 12750 300 51071 0 - 025 2 7/8x5 1/2 16 or 0.23 18.50 15.38 2.59 28.39 1. Working pressure and /or end Toad are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. * Contact Star Pipe Products for actual listings on specific pipes Model C -7 couplings are available in sizes 3/4 -24 and are ideal for applications within industrial and commercial construction, power plants, mining, process piping and hydraulic elevator piping. It is a flexible style which provides allowance for controlled pipe movement caused by thermal changes, settling or seismic action as well as dampen noise and vibration. DIMENSIONS - WEIGHTS C -7 FLEXIBLE COUPLING NOMINAL ACTUAL ULarFMMAX. MAX. ALLOW. NUTS MIS DEFIE CT ION DIME NSIONS- Inch /non: APP ROX. _. r: - SIZE PIPE WORKING END PIPE END (INCH) DEG.PER PIPE WEIGHT IN. SIZE P .5.1./• LOAD SEP. 3T Y. SIZE COUP LING IN./FT . A 8 C EACH _ IN - Lbs.. :: IN.::.. Lbs.. • 3/4 1.050 500 865 0.0.13 2 3/8x2 66 -46' 1.42 3.63 2.13 1.75 1.3 I 1 1 1.315 500 ' 1358 0.0.13 2 318x2 515 - 26' 1.14 3.88 2.38 1.75 1.4 1 1 1/4 1.660 500 2164 6-0.13 2 112x2 1/2 48 - 19' 0.90 4.63 2.63 1.75 2.1 - - • 1 1/2 1.900 500 2835 0 - 0.13 2 112x2 1/2 38 - 46' 0.79 5.00 3.00 1.75 13 2 1375 500 4430 0 -0.13 2 112x2 1/2 315 - 01' 0.63 5.63 3.63 1.75 17 21/2 1875 500 6492 0 -0.13 2 112x23/4 28- 29' 0.52 6.25 4.25 1.75 3.8 3 3.500 500 9621 0 0.13 2 112x2 3/4 28 -03' 0.43 7.00 5.00 1.75 4.2 4 4.500 500 15904 0 - 0.25 2 518x3 1/4 38 -11' 0.67 8.50 6.38 2.00 7.0 5 5.563 500 24305 0 •0.25 2 314x4 114 28 - 35' 0.54 10.25 7.63 2.00 11.5 6 6.625 500 34471 0 - 0.25 2 3/4x4 1/4 20 -10' 0.45 11.50 9.00 100 13.5 8 8.625 500 46741 0 -0.25 2 718x5 115 -40' 0.35 14.50 11.38 2.38 23.0 - 10 10.750 500 72610 0.0.25 2 1x6 18- 20' 0.28 16.75 13.50 2.50 31.0 12 12.750 500 102141 0 -0.25 2 1x61/2 19- or 0.23 19.00 15.50 2.50 35.0 1. Working pressure and /or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. * Contact Star Pipe Products for actual listings on specific pipes Page 6 G STAR ®PIPEPRODUCTS GROOVED COUPLINGS LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 The RC -1 reducing coupling allows ° connecting two different pipe sizes on _ the same run. This coupling 1._ ,. replaces a reducer and two couplings. RC -1 REDUCING COUPLING • NOMINAL ACTUAL ULorFMMAX. MAX. ALLOW. NUTS /BOLTS OFFIFCTJON 1IMFN5IONS- Inrh / mrs' APPROX. SIZE PIPE WORKING END PIPE END (INCH) DEG.PER PIPE WEIGHT IN. SIZE P.S.I. /' LOAD SEP. QTY. SIZE COUP LING IN. /FT. A B C EACH IN Loss:.: IN.,.,, Lbs 2x1 1/2 2.38/1.66 300 1551 0 - 0.14 2 3/8x2 11 - 53' 0.40 4.88 3.30 1.85 2.05 2 1/2x2 2.88/2.38 300 2272 0 - 0.14 2 3/8x2 1 i - 33' 0.32 5.75 4.04 1.85 2.84 3x2 3.50/2.38 Son 3367 0 - 0.14 2 1/2x2 3/4 11 - 17' 0.26 6.42 4.54 1.85 3.65 3x2 1/2 3.50/2.88 inn 3367 0 - 0.14 2 1/2x2 3/4 1; - 17' 0.26 6.42 4.54 1.85 4.26 4x2 4.50/2.38 300 5567 0 - 025 2 1/2x2 3/4 2; - 38' 0.55 7.82 5.75 2.00 5.36 E. 1..' , 4x2 1/2 4.50/2.88 300 5567 0 - 0.25 2 1/2x2 3/4 21 - 38' 0.55 7.82 5.75 2.00 5.42 4x3 4.50/3.50 300 5567 0 - 0.25 2 1/2x2 3/4 21 - 38' 0.55 7.82 5.75 2.00 5.62 5x4 5.5614.50 300 8498 0 - 025 2 5/8x3 1/4 21 - 05' 0.44 9.56 6.80 2.14 6.50 . 6x4 6.63/4.50 inn 12065 0 - 025 2 518x3 114 11 - 44' 0.36 10.88 8.00 2.06 6.94 8x6 8.63/6.63 300 20449 0 - 0.25 2 7/8x5 1i - 15' 0.26 13.51 10.31 2.37 19.54 1. Working pressure and /or end load are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. * Contact Star Pipe Products for actual listings on specific pipes U L ® ,\ \ LISTED APPROVED t - , ` i The SF -1 Flange enables class 125/150 flange end components to be ` , . I . / connected directly into a grooved end piping system. A special gasket ti •J _ -- provides a permanent seal between the pipe and the mating flange. . . _ . Integral closing tabs on the O.D. of the flange facilitate assembly. SF -1 GROOVED FLANGE ADAPTER NOMINAL ACTUAL ULORFMMAX MAX. FLANGE NUTS/ DIMENSIONS - Inch /rrm APPROX. SIZE PIPE WORKING END BOLTS (INCH) MAX MIN WEIGHT IN. SIZE P.S.I. /• LOAD QTY. SIZE A B C BORE SURFACE EACH • IN Lbs.:;,;: D E Lbs . u<' 2 2.375 300 1329 4 5/8x2 3/4 6.00 4.75 0.75 2.375 3.270 3.20 21/2 2.875 300 1948 4 5/8x3 7.00 5.50 0.88 2.875 3.770 4.60 3 3.500 300 2886 4 5/8x3 7.50 6.00 024 3.500 4.395 5.70 4 4.500 300 4771 8 5/8x3 9.00 7.50 025 4.500 5.395 720 6 6.625 300 10342 8 3/4x3 1/2 11.00 9.50 1.00 6.625 7.520 10.00 8 8.625 300 17528 8 3/4x3 1/2 13.50 11.75 1.13 8.625 9.875 15.70 Note: The effective sealing area of the mating flange must be free from gouges or deformities of any type to ensure proper sealing of the gasket. 1. Working pressure and /or end Toad are total allowable, based on standard weight steel pipe, roll or cut grooved. 2. One time field test pressure may be increased to 1.5 times the figures listed above. 3. Working pressures on other pipe schedules may be found on page 54. 4. Required flange bolts to be supplied by installer. 5. See F -1, page 9, for additional technical information. * Contact Star Pipe Products for actual listings on specific pipes Page 7 GROOVED FITTINGS STAR®PIPEPRODUCTS , V L LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 "S" Series products are specifically designed for use in fire protection applications where economy is a factor. All products are UL & ULC listed as well as factory mutual approved. Maximum working pressure for these products is 300psi. I FIRE PROTECTION FITTINGS SK -1 GROOVED CAP • SE -1 90° ELBOW SE-2 45° ELBOW ST -1 TEE NOMINAL END APPROX. NOMINAL CENTER APPROX. CENTER APPROX. CENTER APPROX. SIZE to WEIGHT SIZE to WEIGHT to WEIGHT to WEIGHT IN. END EACH IN. END EACH END. EACH END EACH IN.:rir: Lbs.' IN. , Lbs ',, ,; IN . , r,1 Lbs a: IN. - :?- Lbs. r. ,: 1 1/4 0.87 0.32 2 2.75 1.50 2.00 1.29 275 2.27 11/2 0.87 0.39 21/2 3.00 2.14 2.25 2.00 3.00 3.30 2 1.00 0.54 3 3.38 3.60 2.50 3.06 3.38 5.04 21/2 1.00 0.75 4 4.00 5.78 3.00 4.89 4.00 7.86 3 1.00 1.23 6 5.50 11.78 3.50 9.95 5.50 19.05 4 1.06 1.95 8 6.81 21.10 4.25 15.40 6.94 33.30 6 1.06 4.58 8 1.19 8.98 Fittings are cast steel per ASTM A 958 or ductile iron per ASTM A536. .., SE -5 GROOVE X THREAD REDUCING 90 ELBOW :;11 NOMINAL O.D. Thread A B Weight Size (IN) (NPT) (IN) (IN) (Ibs.) IN. 1%x% 1.900 %- 14 1.75 1.38 0.63 1%x% 1.900 %- 14 1.88 1.38 0.70 1%x 1 1.900 1 - 11.5 2.03 1.50 0.80 2x% 2.375 y, -14 1.75 1.63 0.84 2 x% 2.375 %- 14 1.88 1.63 0.93 I'i O .D. 13 2 x 1 2.375 1 - 11.5 2.03 1.75 1.04 !1I m , 2' /:x %: 2.875 '/: -14 1.75 1.81 1.18 ■I e 2%x % 2.875 %- 14 1.88 1.81 1.30 1;I 2%x 1 2.875 1 - 11.5 2.03 1.94 1.50 A NPT SE -9 DRAIN ELBOW DIMENSION - WEIGHTS NOMINAL O.D. Thread C -E A Approx. Size Weight IN. (IN) (NPT) (IN) (IN) (Ibs.) 2 2.375 1 -11.5 2.75 2.16 1.70 2.5 2.875 1 -11.5 3.00 2.16 2.45 3 3.500 1 -11.5 3.38 2.16 3.50 4 4.500 1 -11.5 4.00 2.25 5.25 6 6.625 1 -11.5 5.50 2.25 14.00 Page 8 GROOVED FITTINGS STAR ®PIPEPRODUCTS Vi. LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 I 7 -I i I _; - E -1 90° I E -2 45° ( E -3 22 1/2° I E-4 11 1/4° I E•9 DRAIN ELBOW ELBOW ELBOW icy!) ELBOW ava ELBOW Ism NOMINAL CENTER APPROX. CENTER APPROX. CENTER APPROX. CENTER APPROX. CENTER APPROX. SIZE to WEIGHT to WEIGHT to WEIGHT to WEIGHT to WEIGHT IN. END EACH END EACH END EACH END EACH END EACH IN, Lbs- IN a: Lbs;'; IN, Lbs. IN.• Lbs'..,: IN Lbs.'. 11/4 2.75 1.1 1.75 0.8 1.75 0.8 1.37 0.5 2.75 1.2 11/2 2.75 1.2 1.75 0.9 1.75 1.0 1.37 0.7 2.75 1.8 2 3.25 2.0 2.00 1.5 2.00 1.6 1.37 0.9 3.25 2.3 21/2 3.75 2.9 2.25 2.2 2.00 2.1 1.50 1.5 3.75 3.0 3 0.0. 3.75 3.1 2.25 1.9 N/A N/A N/A N/A WA N/A 3 4.25 4.3 2.50 3.2 2.25 3.1 1.50 2.0 4.25 3.6 4 5.00 8.7 3.00 5.7 2.87 5.4 1.75 3.3 5.00 3.7 5 5.50 11.9 3.25 8.2 2.88 7.8 2.00 5.0 5.50 4.3 6 6.50 18.2 3.50 11 3.12 8.3 2.00 6.5 6.50 10.7 6.50.0. 6.50 15.0 3.50 11.2 N/A N/A N/A N/A N/A N/A SW = Segmentaly Welded Steel 8 7.75 32.2 4.25 20.4 3.87 17.9 2.00 10.0 7.75 20.8 * Forge Steel 10 9.00 49.0 4.75 31.5 4.75 30.0 2.12 14.5 9.00 29.0 Drain elbow has a standard 1" 12 10.00 70.0 5.25 44.1 4.87 40.4 2.25 18.7 10.00 33.0 Female NPT outlet Drain elbow is SCH 10 steel pipe r I- r,1- - -- - `L - _ ` `t_. I I 1 * 150 Ib. steel flanged 1 1/4" - 12" 14" - 24" T -1 TEE F -2 FLANGE NIPPLE(sw) K -1 GROOVED CAP NOMINAL CENTER APPROX. NOMINAL END APPROX. NOMINAL ACTUAL END APPROX. SIZE to WEIGHT SIZE to WEIGHT SIZE PIPE to WEIGHT IN. END EACH IN. END EACH IN. SIZE END EACH IN. Lbs. IN..: IN... Lbs. 11/4 2.75 1.7 11/4 4.00 2.8 11/4 1.660 1.00 0.40 1 1/2 2.75 1.8 1 1/2 4.00 3.2 1 1/2 1.900 1.00 0.51 2 3.25 2.9 2 4.00 5.2 2 2.375 1.00 0.68 21/2 3.75 4.6 21/2 4.00 8.0 21/2 2.875 1.00 0.99 3 O.D. 3.75 4.3 3 4.00 10.2 3 O.D. 3.000 1.00 0.94 3 95 6.9 4 6.00 17.2 3 3.500 1.00 154 4 5.00 10.9 5 6.00 21.4 4 4.500 1.06 2 5 , 5.50 17.8 6 6.00 26.0 5 5.563 1.06 4.43 6 6.50 25.0 8 6.00 38.4 6 6.625 1.06 6.64 6.5 6.50 24.5 10 8.00 65.0 6.5 6.500 1A0 5.50 8 7.75 42.1 12 8.00 91.0 8.625 1.19 11.28 ' - - 10 10.750 1.25 21.00 10 9.00 69.0 .. . . 12 12.750 1.25 35.50 12 10.00 91.0 .. SW = Segmentaly welded steel * Forged steel Page 9 GROOVED FITTINGS STAR®PIPEPRODUCTS ,A, ko L U 41> o LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 T-2 REDUCING TEE (sw) ._. NOMINAL CENTER APPROX. NOMINAL CENTER APPROX. NOMINAL CENTER APPROX. SIZE to WEIGHT SIZE to WEIGHT SIZE to WEIGHT nv. END EACH IN. END EACH IN. END EACH .. • IN. - , Lbs 6 . IN.( , ' Lbs ( 6, K r. . Lbs 1 i ' 7' 1 1/4 x 1 1/4 x 1 2.7 .. _ 424'4'442." 1.1 ,. );(1:)".2 5.00 10.1 8x 8 x 21/2 , „ ,3 4 c :5 -. (....- 775 38.4 L___i , 1 1/2 x 1 1/2 x 1 2.75 1.8 4 x4x21/2 (d) 5.00 10 8 989 9 7.75 36.5 1 1/2 x 1 1/2 x 1 1/4 325 2.0 4 )5 47c3(ct) 5.90 102 8 x 8 x 4 (d) 7.75 435 2 x 2 x 1(d) 3.25 2.2 5 x 5 x 1 5.50 1 8 x 8x 5 7.75 36.8 '-- 2x2x 11/4 3.25 2.6 5x 5 x 1 1/4 5.50 14.1 8 x 8 x 6 (d) 7.75 42.5 - 4,, F.2 1,, ■ 2 t n: ,,, 2x2 x 11/2 3.25 2.7 5 5 9 5.50 1 10 x 10x 2 9.00 57.1 :.„43,f.1 v 4:8 :8. :2 23 3, '2 ' 2 1/2 x 21/2 x 1 3.75 8;, ,<28 33; 4.1 ,.!5,5 5.50 14.5 10 2;1 9 21/2 9 21/2 x 11/4 3.75 4.2 5x 5 x21/2 5.50 14.8 10 x 10 x 3 9.00 57.4 'n A .,:, 9 ,,, :,..,: / .::.:)' 3, 72'? 27,2 2 1/2 x 2 1/2 x 11/2 3.75 42 5x 5x3 5.50 152 . 10 x . 10 x 4 - 2 1/2 x 21/2 x 2 (d) 3.75 , 95 ., ; ': 3,8 7.5 ; 6, ,: x 5 5.5 1s.s 19 x, x 5 57.8 ,.4.1., 3 x 3 x1 425 5.1 6 x6 x 11/4 6.50 26.0 19 9;90 58.0 39 3 4.25 52 6x 6 x11/2 6.50 262 .'.. ; 10910 x 8 1 9 3 x3x 11/2 4.25 5.3 6 6 2(d) 6.50 22.7 12 x 12 x 3 10.00 802 3 x 3 x2 4 .5 6 x 6 x / 22(2 (d) s.so 22.6 12 ?(12x 1 10.00 80.5 - 3 x 3 x 2 1/2 (d) 425 8.5 6 x 6 x 3 (d) 6.50 242 14 , .1: '' •:, 10.00 80.7 '5. , 13.3 ,..-3 . 1i!41:,,, 3.75 6.7 .:!..', 6 x 6 x 4 (d) 6.50 23.6 1 x6 10.00 80.9 SW = Segmentaly welded 4 4 91 5.00 9 8 6 x695 d) 6..50 25.6 1 Fx:!X 9 10 ,79 0 91 steel , , ,,,, ,,,',, ,. , , , , , , 4 x x,11/2 5.99 9.9 7.75 362 12 X19 (d) 10.00 101.6 (d) = Ductile iron -, .i‘‘...1 , !! T-3 REDUCING TEE/THD (SW) NOMINAL CENTER APPROX. NOMINAL CENTER APPROX. NOMINAL CENTER APPROX. --.. C. 10 I: - + ,....: - . SIZE to WEIGHT SIZE to WEIGHT SIZE to WEIGHT _1 IN. 3 83,1 IN. 1 1/4 x 1 1/4 x 1 2.75 1.1 4 x 4 x 2 1 1/2 x 11/2 x 1 END EACH ,,,, Lbs •c•;: 2.75 c t. ,: 1.8 IN'773773557 4 x 4 x 21/2 END EACH IN.f -,,' Lbs ! ,,, 5.00 101 5.00 10.3 M. 8 x8 x 3 2:3 8 23 , ,:' f3.; END EACH ' IN.' , , Lbs f ,,,, 7.75 36.5 8 x8 x 4 7.75 36.6 - ,', , '= A ,:, :•:,...:),J, 33.33: _ . .... ' :.' 11/2511/2x11/4 3.25 18 s 3.3, 333 2.0 4 x 4 x 3 5.00 10 2 x2 x9/4(d) c's 3.25 2.4 2.5 , . 5x5 x1 4:4,, '24 r 233 '27 5.50 140 54: ! x8 x5 7I7 8 5 8 x 8 .13 775 37.0 2x2x1(d) 3.25 2.5 5 x5x 11/4 5.50 14:1 : 10 10 i,) x y 2 9,00 57. :.;(, 2 x 2 x 11/4 3.25 26 5 x5 x 11/2 5.'5,0 143 10x 10x 21/2 9.00 87.3 .33 2 x 2 x11/2 3.25 2.7 5 x 5x 2 5.50 14.5 10 x10 x 3 9.00 57.4 .;.), , ..1 ...3 93 5,7 3883.8s.3 73. 3 85 2 1/2 x 21/2 x 1 3.75 4.1 5 x 5 x 21/2 5.50 14.8 10 x 10 x 4 9 57.6 W., , .:•': x n ` .; ' ',.- 3 3 33 1338 , 2 1/2 x 2 1/2 x 1 1/4 3.75 4.2 5 x5 x3 5. 15.2 10 x 10 x 5 9 57.8 1 ,;.,, ,., , 82 3'3 1 3 .. 3 21/2 x 2 1/2 x 11/2 3.75 r 4.2 5 x5 x4 5.50 15.8 10 x 10 x 6 9.00 58.0 . 15 7,3 '7' , '.;', n 1.).. /.9 27371 : 2;3 '.. 2 1/2 x 2 1/2 x 2 3.75 ' 4.3 6 x 6 x1 1/4 6.50 26.0 10 x10 x 8 9.00 5 4 , :15 ..3 , , :A. , :52 - 1,2 2,23 8,-8 , 398 3 x3 x1(d) 4.25 6.6 6 x6 x 11/2 6.50 26.2 12 x 12 x 3 10.00 802 :-) 4 '1" .-',.::, "88 3 33 1 33:,. 3 83: -, 82 ' 7 > 8 :3:- 3- /8 3 x 3 x 11/4 4.25 5.2 6 x6 x2 6.50 26.3 12 x 12 x 4 10.00 80.5 ,,., , ,:a . 82 1833. : 5 :88 17 . )13 3 3,:".: .3' :38 5 '8; 3x 3 x 11/2 4.25 ' 5.3 6 x 6 x21/2 6.50 26.5 12 x 12 x 5 10.00 80.7 .:() r IN , 13 3 22 7.73 3 8 ; , 33. ... 1338 7::33' 3' .338 x '23 234 33:9 3 x 3 x 2 4.25 5.5 6 x 6 x3 8.50 26.5 12 x 12 56 10.00 80.9 c_:) , :;.] v 83 138 , 18 : , ;88 , :8.33 185 12,< 357 353521/2 4.25 5.8 65654 6.50 26.6 1251258 10.00 91.4 139 25 1 ,;: ; - V; 33 if,3; 18-3 '1' :',7 x ',..)7 , 1.6' 4 x4x1(d) - 3.75 10.0 6 x655 6.50 27.0 12 x 12 x 10 10.00 91.8 3: - 32 ' 3, 3 .3 3 SW = Segment* welded 4 x4 x1114 5:9° 9.8 8 x 8 x2 7.75 36.2 :33 r 11/2 / 82 .33 ; 33f 3 ,3 1/2 steel 4x 4x 1 1/2 ' 5.00 9.9 8 x8 x 21/2 7.75 36. 133 r ,3C. 8 18.3 3 83 r 3:38 < 1/2 (d) = Ductile iron Page 10 GROOVED FITTINGS STAR ®PIPEPRODUCTS ` A4 U L LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 1c - n - - n R -1 CONCENTRIC REDUCER(sw) R -2 ECCENTRIC REDUCER(sw) NOMINAL END APP ROX. NOMINAL END APPROX. NOMINAL END APPROX. NOMINAL END APP R OX. SIZE 10 WEIGHT S IZE 10 WEIGHT 5IZE to WEIGHT SIZE to WEIGHT IN. END EACH 04. END EACH IN. END EACH IN. END EACH IN,s Lbs :v. :, IN {,�r; Lbs.n.0 .:. IN,<-<<: Lbs_:K::: IN.v >,, Lbs Ko, 11/4x1 3.31 0.60 5x21/2 350 4.5 1 8.50 0.60 5x21/2 11.00 7.8 11/2x1 3,31 0.73 5x3 3,50 4A 1 12x1 9,00 0.90 5X3 1:1,1,0 9.0 ... - _ 5x3 . ,.. 24 112x11/4 3. 0.73 5 x4 3.50 as 112x14.2 1/4 9. :424 ,. 00 1.0 , 5x4 11.00 11.0 . ,. 42 2x1 (d) 3.31 0.69 6x2 (d) 4.00 5.0 2x1 9.00 1.2 6 x2. 11 15.0 2x11/4 (d) 3.31 0.85 6x21/2 4.00 0.9 2x1 9.00 1,3 6x212 1150 15.3 2x1 12 (d) 3.31 0.83 6x3 (d) 4.00 4.6 2x1 1/2 9 1.4 6z3 1150 16.0 212x1 3.31 0.81 6x4 jd) 4.00 6.2 212x1 9.00 1.7 6x4 ,(d) 11.50 13.8 2 1/2x1 1/4 3.31 0.92 8x5 4.00 5.8 212x11/4 9.5 1.7 6x5 11.50 1 6 . 5 2 12x1 1/2 3,731 0.92 8x2 5.00 122 2 1/2411/2 950 1.8 832 12.00 215 212x2 331 0.92 8x21/2 5.00 12.1 2124 9.50 2,0 8x212 1100 215 3x1 3.31 1.2 8x3 (d) 5.00 10.0 3x1 9.50 2.0 8x3 1100 215 3 1/4 3.31 12 Bx (d) 5.00 9.5 3x1 1/4 9.50 2.1 8x4 12.00 21.5 3x1 1/2 331 12 8 %5 5.00 11.3 3x1 1/2 9.50 2.2 875 ( 12.00 22.5 3x2 (d) 331 1A 8%6.(tl) SAO 11,7 3 9 2.3 8x6. 12.00 23.5 3x21 (d) 3.31 1.... 10x4 6.00 21.9 3x2 1/2 9.5 4.0 10x4 13 35 4x1 3.38 22 10X5 6.00 21.6 4 10.00 4.9 10x 1 38.5 4x1 1/4 3.38 2.2 10X6` 6.00 21.1 4x1 1/4 10,00 4.9 10x6 13.00 37.0 4x1 1/2 (d) 338 2.7 10x8 6.00 19,5 4x1 10.00 4.9 10x8 13.00 03.0 4x2 (d) 3.38 2.5 12x4 7.00 28.0 4x2 10.00 3.1 12x4 14.00 47.0 4x2 1/2 (d) 3.38 16 12X5 7.00 29.0 4x21/2 10.00 3.4 12x5 14.00 48. 4x3 (d) 3.00 25 12* 7.00 30.0 4x3 (d) 10.00 50 1206 1400 49 5x11/2 3.50 4.6 12x8 7 .00 2 8.0 5x11/2 11 .00 7.5 12x8 14.00 51.0 2 :: 5 .. :2; .. < *..Y . 5x2 3.50 4.6 12x10 7.00 33.0 5x2 11.00 7.5 12x10 1 53.0 SW = Segmentaly welded steel SW = Segmentaly welded steel (d) = Ductile iron (d) = Ductile iron R -3 CONCENTRIC REDUCER/THD(sw) NOMINAL END APPROX. NOMINAL END APPROX. SIZE to WEIGHT SIZE to WEIGHT IN. END EACH IN. END EACH E 1 , 3 E - .- IN -: Lbs.. -,:: IN - ,, Lbs. F..: 1 1/2x1 3.31 0.73 3x2 1/2 3.31 1.2 ��_ 2x1 (d) 3.31 0.61 4x1 138 22 2x1 1/4 3.31 0.81 4x1 1/2 3.38 2.3 2x1 1/2 131 0.81 4x2 3.38 2.3 2 1/2x1 3.31 0.81 4x2 1/2 3.38 2.3 , 21/2x/2x1114 3.31 0.992 4x3 3.38 2.6 2 1/2x1 1/2 3.31 0.92 5x4 3.50 4.5 2112x2 3.31 0.92 6x1 3.50 5.9 • . 3x1 131 1.2 6x2 3.50 6.0 3x1 1/2 3.31 1.2 6x3 3.50 6.0 3x2 (d) 131 1.4 6x4 3.50 5.9 Page 11 G STAR ®PIPEPRODUCTS GROOVED FITTINGS/ MECHANICAL TEES UL LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 -- ' II' ..-- - I.:tIF - F - • ' I � t f I r - -- - - -- - - -- -- �: , _ „ r 10 c N -1 N -2 N -3 N -4 GxMPT GxB GxG GxH j • N -1 N -2 N -3 N-4 -�' ADAPTER NIPPLES HOSE NIPPLE C/ C 7 � NOMINAL END APPROX. NOMINAL END APPROX. t SIZE to WEIGHT SIZE to WEIGHT IN. END EACH IN. END EACH r•,, IN. :.0.:: Lbs n:f IN. r,,,i Lbs::,.,? X -1 1 3.00 0.40 1 3.25 0.40 CROSS(SW) 11/4 4.00 0.80 11/4 3.62 0.70 NOMINAL END APPROX. SIZE to WEIGHT i "` IN. END EACH 1 1/2 4.00 0.90 1 1/4 4.00 0.80 IN. <,; Lbs :( 2 4.00 1.20 2 4.62 1.3 11/4 3.75 2 21/2 4.00 1.90 21/2 5.50 21 11/2 3,75 22 3 4.00 2.50 3 6.00 3.3 2 3.75 3.0 4 6.00 5.50 4 7.25 5.5 2 1/2 3.75 5.0 t 5 6.00 7.40 5 9.75 8.1 3 425 7.1 6 6.00 9.50 6 11.00 13.2 4 5.00 11.9 8.. 6.00 14.20 8 12.50 24.0 5 5.25 17 10 8.00 27.00 10 14.00 29.00 6 . 6.50 27.5 12 8.00 33.00 12 16.00 46.00 8 7.75 47.0 SW = Segmentaly welded steel 10 9.00 68.0 (d) = Ductile iron 12 10.00 107.0 Model MT-3 & MT -9 Mechanical tee serves the same function as MT -1 & MT-8 but •' uses a steel electro plated u -bolt to save space and for easier installation in tight places. It is ideal for direct connections with sprinkler heads and drop nipples. HOUSING: Ductile iron ASTM A536 grade 65-45-12. C - E COATING: Zinc electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. s GASKET: EPDM - 30...F to + 230...F _ y A1 !I THREADS: MT-3 NPT perANSI /ASME 81.20.1 .._:� �� _ ■ B MT -9 British standard parallel (BSP) per BS21 - 1 � - � \ ' MT -3 & MT -9 MECANICAL TEES - --+ --+ NOMINAL MAX. HOLE DIMENSIONS.Incft/:,::n APPROX. SIT WORKING SIZE WEIGHT .•� D IN. P.S.I H . / IN. A 3 C D E EAC � Lb. 1 1/4 x 1/2 300 1.19 214 134 3.50 121 215 0 I 1 1/4 x 3/4 300 1.19 2.14 1.64 3.50 1.21 2.25 0.87 1 1 /4 x 1 300 119 127 111 3.50 121 215 1.06 1 1/2 x 1/2 300 1.19 2.26 1.76 3.50 1.33 2.25 0 1 1/2 ; x 3/4 300 1.19 216 1.76 330 113 215 187 ;1 1 1/ x 1 300 1 239 1.73 330 1.3 215 116 ( i 2 x1/2 300 1,19 2.51 2.01 3.75 1.56 2.25 0.67 2x 3/4 300 1.19 231 211 3.75 136 125 014 - 2 x 1 300 119 214 138 3/5 1 56 2.25 119 21/2 x 1/2 300 119 Z 76 2.26 425 1 81 2.25 0.89 • 7 1 2 1/2 3/4 9 00 1.1 2.76 2.26 4.25 1.81 2.25 198 2 1/2 x 1 300 1.19 2.88 2.22 415 1.81 2.25 114 1 30.0.x1/2 300 1.19 2. 2.32 4. 1.88 2.25 0.89 . 1 . 3 0.I/x3/4 300 1.19 212 2.32 415 188 215 038 3 0 D 300 1.19 2.95 2.29 4.z5 1 0,8, 2.25 1.14 \s,,,s. Page 12 C.1. r :READED FITTINGS , STARTIPEPRODUCTS oh. titg l el- 4 1> LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 Cast iron threaded fittings are UL, ULC listed and factory mutual approved for 300 psi service. Gray iron per ASTM Al26 class B. Dimensions conform to ANSI B16.4 class 125 except plugs conform to ASME B16.14. Threads are NPT per ANSI/ASME B1.20.1. - -1 - i • i - I 1 _I CAST : !ROWSTRAIGHT TEE LCAST•.IRON90.DEGREE:ELBOW; --- NOMINAL ITEM MAX DIMENSIONS WEIGHT NOMINAL ITEM MAX. DIMENSIONS WEJGHT SIZE CODE WORKING EACH SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE (INCH) # P.S.I. A B PIECE 1 CT333 300 1.50 1.50 1.21 1 CB90033 300 1.50 1.50 0.95 11/4 CT444 300 1.75 1.75 1.87 11/4 CB90044 300 1.75 1.75 1.34 11/2 CT555 300 1.94 1.94 2.51 11/2 CB90055 300 1.94 1.94 1.80 2 CT666 300 2.25 2.25 3.96 2 CB90066 300 2.25 2.25 2.90 2 1/2 CT777 300 2.70 2.70 6.45 21/2 CB90077 300 2.70 2.70 4.75 1 . , , . I . . 3 , 4 1,-..,,,r , v , z--`,..0';-:: 2 ,-. 7'4' • r 7- , re,,(i7r.e. '1 04 C ASTIIRONtRED1 COUPLING ':- t.:.; - , .1 ,-, A.:1 NOMINAL ITEM MAX. DIMENSION WBGHT 'f,.. SIZE CODE WORKING EACH CAST, IRON:45'DEGREE ELBOW NOMINAL ITEM MAX. DIMENSIONS WEIGHT (INCH) # P.S.I. A PIECE 1X1/2 CRCO31 300 1.70 0.62 SIZE CODE WORKING EACH 1X3/4 CRCO32 300 1.70 0.80 (INCH) # P.S.I. A B PIECE 1 CB45033 300 1.12 1.12 0.84 1 1/4 CB45044 300 1.29 1.29 1.40 . . 1 1/2 CB45066 0 5 300 1 300 1.43 6 .13 1.68 21..7800 2 B4 1,CAST IRON .R E D: 90 DEG EL BOW NOMINAL ITEM MAX. DIMENSIONS WEIGHT 1 ' SIZE CODE WORKING EACH .. (INCH) # P.S.I. A B PIECE 1X1/2 C890031 300 1.26 1.36 0.64 1X3/4 CB90032 300 1.37 1.45 0.87 5 CAST IRON PLUGS 1 1/4X1/2 CB90041 300 1.34 1.53 0.96 1 1/4X3/4 CI390042 300 1.45 1.62 1.13 NOMINAL ITEM MAX. DIMENSION WEIGHT 1 1/4X1 CB90043 300 1.58 1.67 1.16 SIZE CODE WORKING EACH 1 1/2x1 1/2 CB90051 300 1.41 1.66 1.17 (INCH) # P.S.I. A PIECE 1 1/2x3/4 CB90052 300 1.52 1.75 1.28 1/2 CPL001 300 0.94 0.10 1 1/2X1 CB90053 300 1.65 1.80 1.51 3/4 CPL002 300 1.07 0.17 1 1/2X1 1/4 CB90054 300 1.82 1.88 1.62 1 CPL003 300 1.25 0.28 2X1/2 CB90061 300 1.49 1.88 2.00 11/4 CPL004 300 1.36 0.44 2X3/4 CB90062 300 1.60 1.97 2.05 11/2 CPL005 300 1.45 0.62 2X1 CB90063 300 1.73 2.02 2.10 2 CPL006 300 1.56 0.91 2X1 1/4 C B90064 300 1.90 2.10 2.30 2X1 112 C690065 300 2.02 2.16 2.60 Page 19 C.I. THREADED FirrGS STAR®PIPE PRODUCTS 41) ih Al> LISTED LISTED APPROVED For fire protection services request submittal GRS 1.3 PAcAsriRoN ROSS - 1 -L. • NOMINAL ITEM MAX. DIM INSIONS WEIGHT SIZE CODE WORKING EACH • (INCH) P.S.I. A B PIECE • 1 CX033 300 1.50 1.50 1.54 1 1/4 CX044 300 1.75 1.75 2.40 11/2 CX055 300 1.94 1.94 3.10 2 CX066 300 2.25 2.25 4.00 1 1/4X1 CX043 300 1.58 1.67 2.05 1 1/2X1 CX053 300 1.65 1.80 2.40 2X1 CX063 300 1.73 2.02 2.75 CAST IRON REDUCIN3 TEE = • • - .1 4 4 ' , 1■ NOMINAL IT ENI MAX. DIMENSIONS WEIGHT SIZE CODE WORKING EACH ' (INCH) P.S.I. A B C PIECE MUM MEM Wiltialnak.MI NiMall==.11.L.UktiNIMI MEM EWE MUM MUM ELUILEMI IMMLUEM MUM MEM MEM MUM ■MiLtIlai■ - Mdiatal MUM ELIE Mr111 MEE MEM 11=1211/11MEIM MILL= ER.UM ELIE MUM ME,1-1E IIMIL1111.1111L-UkkEl EMU= MEE MUM MUM =UM MEMLLSIAle-ME MAIM= MIME ELLE MUM ELM MAIM IIMMILILLIUMME MILIMM MUM ELLE ELM MUM MILIM EIIIMIGULEME MIME IMLUEM MUM MEM MAIM M.61/111 MN FL K Ei MN MUM= MIA= MILLE ELIE WWI MILLEI ME* FL k.UNNIMMIMIMMLIM MUM Wail MUM M-laMI NE g FMNIIEULIM INELM MALE MUM MLE1M it FL Kim rt. tLEN MIALUM NEU= KUM ELM ELM MUM! MS FL , : 4 m ra Mira= MUM ELIE ELIE EOM MB EFL s FLYAA MILIUMI IMILLEM ERIE ELM ELLM NW= MalkraiNWLMII MILLIMI MU= WALE WALE IIVIE NOM= MIlkaldiitAUME EL.U.11M MILLI= ELM MUM MAIM MUM Ma= MUM ERIE ISALM MIME MMIALtIALLMIE 11111E11M NEU= ELIE ELIE ELLE MIME MilfattitailLIM Mdk11M MILLEN ELIWII ELIE ELLE MAIM 1111111 PA rk EMIL= Mala:=1 MUM ELIE ELL/MIME:El / IMILM ELM MUM MAIM M.L1M FeEi a FL E*Y MI 'SALIM' WM/MN MUM MUM InaLMI Mant.M KELM Makill MLLE 11M4Y2-M 'Wulff rV5 P.M M1 IMIEELM MLLE MAIM MAIM MIME =ILMR2AULLEIMI MNIEIM MEI= WALE WALE MUM MALIMI 1 112X1 1/2X1/2 IIMIL=1 MEM MEM MUM MEM MILLIEUREWEILMI IIIEULaM MEDI= MEM MUM MUM 1 1/2X1 1/2X1 MAIEESM =RIM MEM MEM MEM MUM MEDIMM MEM= mi.inialliaeammEtsm 1 1/2X1 1/2X2 MiBEEMIMaMEXEMIEKIMMEKAMMEOM MMEW-3a1111=1/01:1LEMMEM=IMEEMEAKIii WEEMI Min= 2X1 1/4X2 MaiMi MEM= NEEM WIEN WEE IWIEIM MIFXSik1411111E IIIIKELM MEM MUM MAIM MEICEM 2X1 1/2X3/4 INEMZEM IEEIL=111E1Ill Elan MEM MIXEM ME2310.3=1111 MELLMIIILIUMMILEM IELEMIIIMM 2X1 1/2X1 1/4 =aka= =Ea= MEM MAIM MEM 2X1 1/2X1 12 NiaTaiN =Ka= KEEN MEM MAIM EE. 2X1 1/2X2 ME321111M MEM MEM !MEM MiA/AM 2X2X1 2 if 300 MEM MUM MEM 2.6 2X2X3/4 MIME= 300 MIMI MEM KUM MAIM 2X2X1 MAIDIEll MEI= MAHN MAJKM Wan MDCOMI 2X2X1 114 MiiiiMM 300 ELLE MUM MEM MIEIIM 2X2X1 1/2 300 Egan WEEMIIIEEM 3.72 2x2x2 1/2 MFDMEM MEM= Min MEENWICEMMEEM Page 20 P POUER VANE TYPE WATERFLOW 8 The Symbol of Protection ALARM SWITCH WITH RETARD UL, ULC and CSFM Listed, FM and LPCBApproved, NYMEA Accepted, CE Marked Service Pressure: Up to 450 PSI (31 BAR) Minimum Flow Rate forAlarm: 10 GPM (38 LPM) Maximum Surge: 18 FPS (5,5 m /s) Contact Ratings: Two sets of SPDT (Form C) 15.0Ampsat 125/250VAC 2.O Amps at30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit _ Environmental Specifications: • Suitable for indoor or outdoor use with factory installed gasket and - die -cast housing. }p - • NEMA4 /IP54 Rated Enclosure - use with appropriate conduit fitting. • Temperature Range: 40 °F /120 °F, 4,5 °C /49 °C • Non- corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. • SizesAvailable: Steel Pipe schedules 10 thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thru 200mm Note: For copper or plastic pipe use Model VSR-CF. Service Use: Automatic Sprinkler NFPA -13 U.S. Pat. No. 3921989 One or two family dwelling NFPA -13D Canadian Pat. No. 1009680 Residential occupancy up to four stories NFPA -13R Other Patents Pending National Fire Alarm Code NFPA -72 Potter Electric, Rd., 1990 Optional: Cover Tamper Switch Kit, Stock No. 0090018 GENERAL INF0RMATION INSTALLATION: See Fig.2 The Model VSR -F is a vane type waterflow switch for use on wet These devices may be mounted on horizontal or vertical pipe. On sprinkler systems. It is UL Listed and FM Approved for use on steel horizontal pipe they should be installed on the top side of the pipe pipe; schedules 10 through 40, sizes 2" thru 8" (50mm thru 200nim). where they will be accessible. The units should not be installed within LPC approved sizes are 2" thru 8" (SOmm thru 200mm). 6" (15cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. The unit may also be used as a sectional waterflow detector on large Drain the system and drill a hole in the pipe using a circular saw in a systems. slow speed drill. The 2" (SOmm) and 2 1/2" (65mm) devices require a The unit contains two single pole, double throw, snap action switches hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm ±2mm). All other and an adjustable, instantly recycling pneumatic retard. The switches sizes require a hole with a diameter of 2" t1/8" (50rrun t2ntm). are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a Clean the inside pipe of all growth or other material for a distance equal period of time necessary to overcome the selected retard period. to the pipe diameter on either side of the hole. ENCLOSURE: The unit is enclosed in a general purpose, die -cast Roll the vane so that it may be inserted into the hole; do not bend or housing. The cover is held in place with two tamper resistant screws crease it. Insert the vane so that the arrow on the saddle points in the which require a special key for removal. A field installable cover direction of the waterflow. Install the saddle strap and tighten nuts tamper switch is available as an option which may be used to indicate altemately to an eventual 50 fl -Ibs. (68 n -m) of torque (see Fig. 2). The unauthorized removal of the cover. See bulletin no. 5400775 for Vane must not nib the inside of the pipe or bind in any way. installation instructions of this switch. Specifications subject to change without notice. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146 -4161 • Phone: 800- 325 - 3936 /Canada 888- 882 -1833 • wvw.pottersignal.com PRINTED IN USA MKT. 88800001 - REV W PAGE 1 OF 2 MFG. 45400761 - 7/02 08, VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD FIG. 1 FIG. 2 SWITCH TERMINAL CONNECTIONS OPTIONAL TAMPER SWITCH DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME CLAMPING PLATE TERMINAL RETARD ADJUSTMENT: TO CHANGE TIME TURN KNOB (EITHER DIRECTION '1 .., C ' TIGHTEN VS - NUTS (±) FOR DESIRED TIME DELAY. USE THE MINIMUM Al, oo. -:7 j �� ALTERNATELY TO AN AMOUNT of RETARD NECESSARY TO PREVENT - 4 %7 :` EVENTUAL 50FT. -LBS (68 n -m) �� cO FALSE ALARMS. A B" SETTING IS USUALLY �� 1; � � � OF TORQUE ADEQUATE FOR THIS. FACTORY IS SET TO "B ". � ; - l TO INSTALL, DRILL HOLE AS INDICATED: n a •, z1 CpC' / • PIPE SIZE HOLE SIZE �\ 0000 2 to 2 1/2 1 1/4" +1/8" -1/16" .7\ MOUNT ON PIPE SO (50mm to 65mm) (33mm ±2mm) 1 ��\ ARROW ON SADDLE POINTS IN DIRECTION CAUTION: OF WATERFLOW 3" to 8" 2" f 1 /8" An uninsulated section of a (80mm 10 200mm) 50mm ±2mm) ROLL PADDLE IN single conductor should not Cover DIRECTION be looped around the terminal Cover Tamper /I e- OF WATERFLOW (with cover in place) and serve as two separate connections. The wire must DIRECTION of be severed, thereby providing 0 © WATERFLOW supervision of the connection `= N.O. NC P (W110 (RFD) (BLR) \ APPROX. RETARD SETTINGS (IN SECS.) in the event that the wire 0 A B C 0 E becomes dislodged from under 0 10 -25 20 -40 35 -55 50 -70 60 -90 the terminal. DWG. b761 -30 FIG. 3 TYPICAL ELECTRICAL CONNECTIONS NOTES: FIG. 4 I. The Model VSR has two To remove knockouts: Place 2 SETS OF NORMALLY switches, one can be used screwdriver at edge of knockouts. OPEN CONTACTS WATERFLOW ZONE EOLR FROM t0 operate a central station ('I -OSE ON ALARM 00 FIRE PANEL FIRE PANEL not in the center. b + `�■ proprietary or remote signaling ® CM ® im ® �S unit, while the other contact is 0311-111g1 IU�I r IC I used to operate a local audible or i - =I visual annunciator. i �(, 1t-11 M I = M 3. th s prod i s LPC he Approval al ��1� �� � N� this product is that the electrical THE N.C. AND N.0. MARKINGS ON POSITIVE DC entry must be scaled to exclude / THE SWITCH ARE FOR AN ALARM OR HOT AC CONDITION. ' B[ LL moisture. o ��� /, p Iii 3. For supervised circuits see NEGATIVE DC OR O m O THE CONTACTS ARE REVERSED NEUTRAL AC fa WIIF.N THE DEVICE IS IN THE uWu.:oiz "Switch Terminal Connections NORMAL CONDITION. drawing and caution note DWG. 1761 -4 (Fig. 1). APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. TESTING The frequency of'inspection and testing for the model VSR -F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and /or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR -F is not recommended or advisable. A minimum flow of 10 gpm (38 Lpm) is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. PRINTED IN USA MKT. it8800001 - REV W PAGE 2 OF 2 MFG. 55400761 - 7/02 P POUER BELLS The Symbol of Protection PBA - AC & MBA - DC UL, ULC, and FM Approved Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm) Voltages Available: 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Sen'ice Use: Fire Alarm �, General Signaling Burglar Alarm ® Environment: Indoor or outdoor use (See Note I) -40° to 1 50°F ( -40° to 66 °C) (Outdoor use requires weatherproof hackhox.) Termination: AC Bells - 4 No. 18 AWG stranded wires DC Bells - Terminal strip Finish: Red powder coating 0 ® Optional: Model BBK -1 weatherproof backbox D Model BBX -1 deep weatherproofhackbox These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on a model BBK -1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK -1, Stock No. 1500001. ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: Size inches Voltage Model Number Stock Number Current (Max.) Typical dB at Minimum dB at (mm) 10 ft. (3m) (2) 10 ft. (3m) (1) 6 (150) 12VDC MBAl26 1750070 .12A 85 76 8 (200) 12VDC MBA 128 1750080 .12A 90 77 10(250) 12VDC MBAl210 1750060 .12A 92 78 6 050) 24VDC MBA246 1750100 .06A 87 77 8 (200) 24VDC MBA248 1750110 .06A 91 79 10 (250) 24VDC MBA2410 1750090 .06A 94 80 6 050) 24VAC PBA246 1806024 .17A 91 78 8 (200) 24VAC PBA248 1808024 .17A 94 77 10 (250) 24VAC PBA241 O 1810024 .17A 94 78 6 0 50) 120VAC PBA 1206 1806120 .05A 92 83 8 (200) 120VAC PBA 1208 1808120 .05A 99 84 10 (250) 120VAC PBA 12010 1810120 .05A 99 86 Notes: 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150 °F ( -34° to 66 °C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146 -4161 • Phone: 800 -325- 3936 /Canada 888- 882 -1833 • www.pottersignal.com PRINTED IN USA MKT. 08850001 - REV V PAGE I OF 2 MFG. 05400776 - 10/06 0 [p) '.' ti r' 0: I , ;4 _ ,i'• The Symbol of Protection PBA -AC & MBA -DC DIMENSIONS INCHES (mm) FIG. 1 BELLS FIG. 2 WEATHERPROOF BACKBOX 130X HAS ONE T13MI DED 1/2" CONDUIT ENTRANCE o I 10" 1 —� (250) 8• 'ri I 5 3/4.. O 3 3 ,• 5,. (20) (1461 (127) (i ' (150) I 0 1 I r (se) 86) 11/16° (41) �— 41/4" —,,, (68) (106) DWG 776 -1 IWG6 776 -2 FIG. 3 WIRING (REAR VIEW) A.C. BELLS FACP WIIITE(IN) A illiMllh h . WIIITE(OUT) ill FROM CONTROL • PANEL OR 1 II PRECEDING BELL i [■ ._- .......... ............_._............_ BLACK (INl .... . "-'1111111111111111111P _I— BLACK (OUT) To Next Device or CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. End -of -Lint Resistor NOTES: I. WHEN USING AC DELLS, TERMINATE EACII EXTRA WIRE SEPARATELY AFTER LAST DELL. 2. END -OF -LINE RESISTOR IS NOT REQUIRED ON AC BELLS. D W W'76 3 INSTALLATION 1. The bell shall be installed in accordance with NFPA 13. 72, or local Al - -J. The top of the device shall be no less than 90" AFF and not Tess than 6" below the ceiling. 2. Remove the gong. 3. Connect wiring (see Fig. 3). 4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction). PRINTED IN USA MKT. 48850001 - REV V PAGE 2 OF 2 MFG. 45400776 - I0 /06 • FOLCOY www.tolco.com .. 102) a brand of NIBCO• Revision 5/24/2001 Fig. 200 - "Trimline" Adjustable Band Hanger c C US LISTED Size Range — 1/2" thru 8" pipe F M Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features — • • (1/2" thru 2 ") Flared edges ease installation for ` all pipe types and protect CPVC plastic pipe from , abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily . installed around pipe. • (21/2" thru 8" Spring tension on nut holds it i., securely in hanger before installation. Adjusting nut is easily removed. T Approvals — Underwriters' Laboratories listed (1/2" thru 8 ") in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8 "). Conforms to Federal Specifications WW -H -171 E, Type 10 and Manufacturers Standardization Society SP -69, Type 10. Maximum Temperature — 650 °F Finish — Mil. Galvanized. For Stainless Steel materi- als, order TOLCOTM Fig. 200WON. Order By — Figure number and pipe size Dimensions • Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Length 1/2 3/8 8mm or 10mm 3'/ 2% 400 11 3/4 3/8 8mm or 1 Omm 31/2 212 400 11 1 3/8 8mm or 10mm 3% 2% 400 12 11/4 3/8 8mm or 10mm 3% 2 %e 400 13 11/2 3/8 8mm or 10mm 3% 2% 400 14 2 3/8 8mm or 10mm 41 3 400 15 212 3/8 lOmm 5% 41/2 600 27 3 3/8 lOmm 5 %e 4 600 29 312 3/8 10mm 73 51/4 600 34 4 3/8 10mm 7 5 1000 35 5 1/2 12mm 9 61/4 1250 66 6 1/2 12mm 101 6 1250 73 8 1/2 12mm 131 8 1250 136 OFFICE /MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX 951.737 0330 84 CUSTOMER SERVICE • 800 786.5266 www.tofco.com �,..:.� ,. w.,.r... .: -.. ,. „.�>•� .. - -:. - .�:'. May t...... ..r. ,� -r- - t , :, •.. t'9!`l”. fi .-a.. �,. e .. � rntiq....;11 fY `v;� '5 7 „_, y>v.'t' 1,.,.•::;-'ri.F ,. »ff _._, hl r...... 1 of 11fN,h.�ksJd1 �'er��A� ,r A' . � 1 ,• `� tAaj- �J i r i ; J n I .r..d�, I, cl�! r� t r2x r' S�. i 1 I � .:z..r .. -ur ,� 1 i*C( �' l re;StWh;A r.�:i), cc, r ie:-4f 3 il ? 0 t .. - �f�l r u , rlJ n aY''� a+;l' Y�.- } i J IA }.�Y . K r �'.�r,•.'.,{ r.., S � I Y..- y I w f ri!r.' t- rC x x eC :.Ir; irL �' l- C .(VO [ r F t45 1�1 • Y . _ . � P:, � I d' .�k i, 1 , ,: � .. ,�1r., r:• ?�.. t , . . ��..1�t.r.l,�"�rh .i .I.,t , Y,J T t In ' 5 1 F ! { f r'. w s:'l>•a t�. u� 1 w� r d'ri4�' t• L 5. `� +. . ti`' ' I', c,!!r� r ,> t';' } " .+a rg t v,., .r S ,.;� , r ,i I4 a �i F t... t 11, a r... WWW.tOICO ., 1 rl� � d I,t - ._ F 7'i�. �•l .S't r>, I'T'l. i.y:t fEGhu .FI>1 rt,.\rr�t har { q; ,114 1 n4.t trl 9y .ti. w .: 3,n - t.. 1 ':A ...., + x t ri,„ r - :' )� >r •Jc.'.,ur�e Ct4 �a,s:.0 �Ic f , „ rsn o , : .:�� r, g , ;tl ' a y,t',t, I , r."- I'' t•', ., L ∎r5 .t u . • ;,1 i .. =risk 1 4r ->- - •� . �t- .t:�' r"'��tt"`' . i 0:4.44,h z .'{ y , .•. Ir �p�+7 � CC�� r�, li:r ! rp� v � r , ,. G r�''�. �'Ct nJr S 1 I __.tt.��'T,: 1 ..,6 ,c ., rantl4of: N1BC ® a �,�' ,1. ? �t,..,.F' ; ,' '! ..1. 9. �, p dl ;Kt '.r',�5, �Ea k I ".I�'4 r { ,� f �,RE`VISIOrll1 %24/20072 -yi t,.> m. nf.. lt•_ ww��s�d; ��. � .�4mlr�Sw�lcr:ArrNaM!sw�4'�:! antra' n. r:�'I,K�44h.1�>.t�- .en:��.. - , 1x .V ' ��,t� I!1•,,,11 ✓- '�1`f�F�s�>ti �>h�.A�:� ruse; ��e�, Y_,_' N: 1�. �1�: c1, r1��aern'�.rr..�';.'�Y.' !�f ,- f.,in Fig. 68 - Wide Throat Top Beam "C" Clamp w/Locknut Size Range — 3/8r' thru 3/4" rod Function — For attachment to structural shapes requiring wider throat especially under roof with bar joist construction. This clamp may be used in the set screw down position only. Approvals — Conforms to Federal Specification WW -H -171 E, Type 23 and Manufacturers Standardization Society SP -69, Type 19. Finish — Plain Note — Available in Electro- Galvanized finish. Order By — Figure number, rod size and finish Note — Do not over tighten set screw. Dimensions *Weights Rod Max. Rec. Approx. Size Load Lbs. Wt./100 3/8 400 34 1/2 500 50 5/8 600 53 3/4 800 86 OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951 737 5599 • FAX 951.737.0330 62 CUSTOMER SERVICE • 800 786 5266 1•,n www.tolco.com �•; rx+ ,an J n�... u_ I I v - -. ;; . q�l. ,� -. a r�. i •. ?p 11 f}...�pb i 't +.4Y.;4r�1 ) a q �'y. ; c a' M1 �... F iya a P -: €..TI x -7,.- -; ?: I r : F , a �, 7aY o .. J,.,. N�. ^•N •. ,.w ", �'CIY.rr i� r-p I!.. k .. l,,..1 r T t l i oi :.:1 : P . t o �'4 . d.'7 • ,:: 91 , .. rr .• ?,. 5 j r ,..0 Yr>;, r' -n r3 'S ... 7 {a,f 1 �g ., , tr _�� �L ?�U ?- ?! 1t ,. 1 t., ..1 J d ��1<, ;.. t rt ^' 1.• GII t .�•"'"�`a"x. ,t3 ,. ri,r. a f ! ir . � z,t P 1y'r � � �y[ • '`F.�t'. 1 F ,rr �� {F �:. .. r. � I ,,4 � ti. {��;�. .y1 v > ��;Y. t � y ,I T t 'fTi -,- .:P / bl -��' I u t. i , , Jv,, i!' t ;„ {": t' r: 4 �Tl!.!lt �F W. I'f, t- 1 44' It .+ 1 : ,�,' 3,N.rtl I. +�:�•, I >..Ir �Iw�'� .•r �,� t K " ! r �. w ryry`` I .0 i i �. ,. ® --.7;. L �., , �� ., � J s � r, -.< 7 r} u .. ,] 1: � w�. ,F d ���16 �.t'I�� 1 f r r •!kI �IRJ I � � rye' i a � ..; � .„ I n �Y , 1 0 (? :k r e I' ,tk 1" . 0 r 3.e 1 n . r; lx X. � ° ,1 F . 4� i iM r :� v � a� � � I ,.� � .,; , . • . r: 1....rt•, t•.t^ ;:. a ,.. t. ,. :h i: i P '> ! 7 • . iiw er � . I. it :T'i � F r ( t•.. !tt ,f s� 1,., .�t li F j F j.cfn . ,:. ` I �' F ' ry tl ,,,,,,,' , • �sWWw t I�: li.�:t, ® l :t�vl c, AVr. +z, -.r+4v�x re:C' .., <It !. t _. d -1aY �r . K fit• i °. we M ..e Mt ,.? .x .1 L +'1 rt F t ) ' , Li , !:,w L:1,:, ai. i , a , : . r:i •thG"Kas ray p '' �{ ,:'i'—F+ r r: � t . -t.. Gii. t;•71 °+^r -4, rF`aFh:hEr -.rlr t v�.' -.. _ , va j °�,I ., I 1 ;w I dlJ :��!4 P •.4s1•�'• k. ` ,, ; . r , a t .."i�,.><� 'i N ITT F'1:i,� ,.n F n I a K,. "� ? r �J'., .I kt r � I ,I,4r^ 7 ,,.� , .ib � �, ." F. trs ,.,w� � �, . v'�" � , ��J�F r Revlslon� 5 /24/2001 ' ''�0::'4rl,t l I J I ,I , •• f�TV' d`i)raIldlAlcN1B�r�f� (� ,„! t d i� ; 'Je'',t G +�! � �t�, 9 � \�9� & N 7 ; tK2': � Y r r. i �, k��. r�atr�v�t�, v![ r��! �t• �tcrvai.` �, rj> ,:�!�.Yr�a�7RSf.rs�..irt,�E��'� 4xkTt§: h:. �� .1:�,�r��:.'�„r.�1nJr,MK.,Y'', r��:�! ,v�a�k�(� ?, t l '!`" �d. �a. �! ��J?i�< .f.u.�.- ��lr:.r{w:,? ±1�3r��:.x. �:„�- �,vx,7.�.Jsuw:.•1� . �.I i., ... rr :,. .r,ti Fig. 4L Longitudinal "In- Line" Sway Brace Attachment C UL US LISTED Size Range — 2 through 8" IPS. Material — Carbon Steel ; , ,4. Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriter's Laboratories Listed in the USA (UL) and Canada (cUL) 2 through 8 ". _ Installation Instructions — The Fig. 4L is the "braced pipe" attachment i , -- \ component of a longitudinal sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO structural attachment n A component to form a complete bracing assembly. NFPA 13 and /or OSHPD ,` / guidelines should be followed. To Install — Place the Fig. 4L over the pipe to be braced and tighten bolts. - . 1 // Then engage "bracing pipe" into jaw opening and tighten set bolt until hex �y head snaps off. Jaw attachment can pivot for adjustment to proper brace ' ` ,, `% angle. Finish — Plain 1 5 Note — Available in electro- galvanized and HDG finish. ,,..... Order By — Figure number, pipe size and finish. R TOLCO brand bracing components are desgined to be compatible ONLY with other TOLCO brand bracing components, resulting in a Listed seismic bracing_assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO R brand bracing components, in the instance that such TOLCO® brand bracing components are used in Longitudinal Brace combination with products, parts or systems which are not manufactured or sold under the TOLCO brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, where non -TOLCO brand bracing components have been, or are used. Dimensions •Weights • Bolt Max. Rec. Approx. Sizes A C D Size Load Lbs. Wt. /100 21/2 61/41e 21 2 1/2 2015 253 , 3 7 2 31/46 1/2 2015 268 4 81 3 3 1/2 2015 348 5 934 31/4 41/4 1/2 2015 380 4 - Way Riser Brace 6 11 5 51/4 1/2 2015 640 (Plan view) 8 13 6 61/4 1/2 2015 728 T , ; , 1 : OFFICE /MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH 951 737 5599 • FAX 951.737.0330 1 CUSTOMER SERVICE • 800 786 5266 1 „,,.,. www.tolco.com ���W.r�•. �'w"r. . r:,^. i.�C I'T ;r;. 3" r 1'.�e7.` �. � �L1371tP,a '11`: r 1;S „i;:, ..:3rr„ z�::!Y -� � C •!' „ti4 t '� 1.. � l T ! :l :r -: L t�r5_s,. I .+?.;:l++i �. .yy,,�r t �L� r lr,. 1,. - n ., '.a f ° - n ,�. a' ' g 7 �� a ,+f7 f' r., ;dry 9' t/. t3 i t •. r 1.: i„ : ,.. �'ul 1 �.:. � 1. Y � F' _7� �ti., ! , J �f ,. f. •. , �!'wxu sY�T v v i. .:4f� 7 t4 i4 �'r 1 �I 1 � 1 -h. � J l lu a . � y W h..,7 � Si. tt'] 1. r r f -. �t -. .a 1 - .'y:� I.IF V....�IJ �: , i; l ,.u.a .a+i�.y1rN.3� �,. , „- j�. ,!rv.i•wi w, 'J.u`nt,�l N1.'i}t l ll' 1'` l i!`N 6!'�r1 n :..s ��t Wl.; tr lax I Y � f { rt. as ,.. M r 1 ..k 1.11 r •a•. . r 5In ?(� 1 4 $ +t ! I N V 4 - � • i i ' ® � '� r ,��. � ��” I �.{ L I ,t �! � �,{1 �, I l s!( '' I I Ir t II. a, l l a } �' t � r 4 I �. r s +� ° v I _ p . :. ,t y, t - 1 .! . :'^ 'y. tll�ry1, r x -7< � r 1 n 1 k, Ff C p�t �4 n 1 I(i 1171 t kr t . >t r I, J .! (i ,.!, _ 7 ! t , 15 } U J 7i � �1 tv � 'i $�� r,. N q' ><': 1 .1` � d ~ i' P.�Ijul i �, a. T 1 �l? � .:. I 1 � F rv �ivT .�1 , 1 b 0(` ,, ti 1., �. t X �- ,� � s 3A � � K l _,( „ 1__ _� a > •�" . . _. � i' I. , :1 F a , ' -- �::a•Iu I v �.: tl� @r l z i w , ;. . n � 5 , n:ev g 1,� "� ; .t, • ,,,,, 1 , „ , -, i 4 .'tip a - A l, ;; e , kc ,�� WWW toIc0 con 1 ,,. 1!`P, t , i 1 I L i } . !7'' l l rv1 _ ' L C.1r .1,:F .. R • .'�` In j s. ekt.F. 15: 4 ,'.' n 't i , ■ !1 1 1 R 1 r 1 .1 r § 1F TF^ 7. ! q �M ,.. �yA, TP I 1 .,, � " .. '1 1 i li d.% .1 Ma:', l py,r . Vri � ,'� I i :4 r }1: :' +._ ^at- 1 ? 'f L 1. 1 1 ,� .� i 1 ^i. ( o ., t 1� �i e ly . ..,�. . ..r.t•a.. .1.� � , ,f ,� r � !!� ao�,. t;NVI- . q ,,; Ish r�.,.�, � ,.'}#. ��.�' '� „�� _,ly ion�4l27 /2006a 1 7 t tti 1 �ja . ?''''CIr(1vit. , .t1 J �i kph. R , .• f I 4 �((I d yl. 4 1 4;,i � , xf � :�. t,:r Revis Y '4 A ' & i G ,. 5 ' ,.� , � ` al biand!dI.N�BE . „ v,- i.. . l� 10 , '•i;�t l ad ,r. K:. 'rn 1 yr ; ,e4 1, . t,: '7 tIVS' f { e ,„�. . NZg fyyi 1 r” I r1 ,��3!��f��W.���-0U���114 ter'; F. r' ��3 �..±. vl u;”; n94... r•= �;.. n,. G; c,: h�M �i :,JSr�!�aMfhraS..,..w��r.��J �bx �� „�.AL�'� r�', }r�r� I�c�f(. �?�'ha.!P ar"s�"�.�f._1�.: �1L+ ��iM n.•�'kr.���SRi.v },�.,..v �._�'�'w ..�: t..�:1,.1, �' ,.a.;.:.n1:.c ., ,,; Fig. 1001 - Sway Brace Attachment c C US LISTEO Size Range — Pipe size to be braced: 21/2” thru 8" IPS.' Pipe size used Component of State of for bracing: 1 ” and 1 a' Schedule 40 IPS. California OSHPD Approved g Seismic Restraints System Material — Carbon St -.,,.- Function — For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: The Fig. 1001 is ;',/..,/ Ir` used in conjunction with a TOLCOTM 900 Series fitting and joined together ii,,/ ■ with bracing pipe per NFPA 13, forming a complete sway brace assembly. 4' / I Features — *Can be used to brace schedules 7 through 40 IPS. Field j ' ' -. adjustable, making critical pre- engineering of bracing pipe length unneces- I !!``', sary. Unique design requires no threading of bracing pipe. Can be used 11 as a component of a four -way riser brace. Comes assembled and ready 1 . for installation. Fig. 1001 has built -in visual verification of correct installa- %� "�' `' I ; tion. See installation note below.�?,,?1� Installation Note — Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads Maximum Design Load bottom out. A minimum of 1" pipe extension is recommended. Sch 7 - 1600 lbs. Brace pipe can be installed on top or bottom of pipe to be braced. Sch 10 & 40 w /1" Brace Pipe - 2015 lbs. Approvals — Underwriters Laboratories Listed in the USA (UL) Sch 10 & 40 w /11/4" Brace Pipe - 2765 lbs. and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish — Plain ' Note — Available in Electro- Galvanized and HDG finish. i Order By — Indicate pipe size to be braced followed by pipe size used for bracing, figure number and finish. Important Note — The Fig. 1001 is precision manufactured to perform l _. its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that the Fig. 1001 must be used only with other TOLCO I I bracing products. The Fig 1001 is not intended for use with the Fig. 907 4 -Way Longitudinal Brace Attachment. �` NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS L. )_1 , I /7 j it / ,/ , \ 1 -' ' OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVF. • CORONA, CA 92879 • PH: 951 737 5599 • FAX 951 737 0330 'ti CUSTOMER SERVICE • 800 786 5266 1163 h 'e: www.tolco.com ,..- -.. I ...g R ; -.. 1 ti;_, ,7iYa .v ilh3i f, 1l{. k i.:r *' ' iO lir' 'x r" .,y tilW1 {p-rs '�aJ ;IT.�i I! : t..`1. �+.�., + +:.. i .. , c u. M 4 . .... 0 ,. u!"i 'u .1 ,I F' r r f'li ..v � 4 •�' r ,,7t. _ 'M 1;1 .a1�,.7 ;�;,�+o �' i�'r:� :� is �k �.e � ,4.. !f- rr'•p. W r N .7"2.1, rt 1 � p :'Sk�'^ �;A.I�. :���• i .�'T i�1� It '� wt:�' + 1a Fl . �:•,� r +,. II, .a .. ti.��Y y -e + af, YS k t' 6 p �i , I p F� ;7 { ` C" Kr � d 5 � � 7�s r � } tii T, ; .1. �.., f,.le .:. 1ee�. - a r. >�;� .`:.: Y i K• ws. :;. SK 5 +' r ?lix4 + 4� �R {l,r, r .I,: i , :•.x�.k'.�'N. r : pk. el, L � ti w Lc '� . : '%• .1!I� - I ,;.�" 'rYIs: WYa : ..a i .: d _ e F';. 4§ is i IrjGF se +.,.�:.,ia$thn. Grc 7 Nt ,, .. 'S.. r I+rr.. 4 va '• .-. _ � c .,,1+',. t ., V.20,311' ,. =n, iy a 4M _l • fy '. +.iY� t•�erki 17 1 h . +4 d U lt,,r i ° a., ' i t 1� L 7., �' iRevision.'2 /17/2006 j'ra +'I4 �, r;��t' �- 4!'Y�,..P n . � ": 41 N�BC� J �>r. ?;rP�HIF rNj•�' h ; , 7T ��••,�� w i '� P , s : v �l . � -f = u�l:h•���r �Y +v ax��h: . ��.. ...h c i .t �t t vf �iY i t� sr'�a ` 6vN °!. W.I...�..,.4,..N�?�.�._i.� VEI.. Y.5..a:.�.......,T' Fig. 980 - Universal Swivel Sway Brace Attachment c 0 US LISTED Size Range — One size fits bracing pipe 1" thru 2 ", TOLCO 12 gauge channel, and all structural Component of State of California OSHPD Approved steel up to 1/4" thick. Seismic Restraints System Material — Carbon Steel Function — Multi- functional attachment to structure or 1►` braced pipe fitting. Features — This product's design incorporates a concentric attachment opening which is critical to the performance of �� \ structural seismic connections. NFPA 13 (2002) Figure I 9.3.5.9.1 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. A Installation — The Fig.980 is the structural or transitional attachment component of a longitudinal or lateral sway brace B assembly. It is intended to be combined with the "bracing • pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe ". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain Note — Available in Electro- Galvanized finish. Order By — Figure number and finish. PATENT #6,273,372 Dimensions • Weights ;rte \\ Max. Design Approx. Load Lbs. Wt./100 �� � A B H* 5 11/2 17/32 2765 132 " Available with hole sizes to accommodate up to 3/4" fastener. Consult factory. Lateral Brace TOLCO brand bracing components are desgined to be compatible ONLY with other TOLCO brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO brand bracing components, in the instance that such TOLCO brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under the TOLCO brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, where non -TOLCO brand bracing components have been, or are used. rv.a OFFICE /MANUFACTURING FACILITY • 1375 SAMPSON AVF. • CORONA, CA 92879 • PH: 951.737 5599 • FAX 951.737.0330 58f CUSTOMER SERVICE • 800 786 5266 Y "' www.tolco.com di j 1 ` -y ... Fire Protection by Computer Design COSCO FIRE PROTECTION 11800 NE 95TH ST. SUITE 240 VANCOUVER, WA. 98682 360- 883 -6383 Job Name : 1ST FLOOR RETAIL Building : WASHINGTON SQUARE MALL Location : 9402 WASHINGTON SQUARE MALL ROAD System : 1 Contract : 0052 Data File : 0052- FP -.wx1 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 COSCO FIRE PROTECTION Page 1 1ST FLOOR RETAIL Date 050207 H draulic Desi.n Information Sheet ne - DICK'S SPORTING GOODS Date - 5/09/07 Location - 9402 WASHINGTON SQUARE MALL ROAD Building - WASHINGTON SQUARE MALL System No. - 1 Contractor - S.D. DEACON Contract No. - 0052 Calculated By - NICK STALKUP Drawing No. - FP -2 Construction: ( ) Combustible (X) Non - Combustible Ceiling Height - 20' -0" Occupancy - ORDINARY GROUP II S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date E M Area of Sprinkler Operation - 3028 System Type Sprinkler /Nozzle Density - .17 (X) Wet Make TYCO D Area Per Sprinkler - 256 ( ) Dry Model EC -11 E Elevation at Highest Outlet - 18 ( ) Deluge Size 3/4" S Hose Allowance - Inside - ( ) Preaction K- Factor 11.2 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside - 500 N Note Calculation Flow Required - 1316.57 Press Required - 65.6 13.74 UNDER CURVE Summary C- Factor Used: 120 Overhead 140 Underground Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 4/28/05 Cap. - T Time of Test - Rated Cap.- Elev.- E Static Press - 82 @ Press - R Residual Press - 76 Elev. - Well Flow - 2042 Proof Flow S Elevation - -3.5 U P Location - 9300 SW WASHINGTON SQUARE ROAD P L Source of Information - TVFR WEBSITE Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water SI - 'ly Curve (C) COSCO Fliw PROTECTION Page _ 1ST FLOOR RETAIL Date 050207 City Water Supply: Demand: C1 - Static Pressure : 82 D1 - Elevation : 9.312 C2 - Residual Pressure: 76 D2 - System Flow : 816.57 C2 - Residual Flow : 2042 D2 - System Pressure : 65.600 Hose ( Adj City) Hose ( Demand) : 500 D3 - System Demand : 1316.57 Safety Margin : 13.736 150 E 140 130 p 120 R 110 E 100 S 90 _ C1 S 80 . _ — _ lJ 70 D R D3 • E 50 40 30 20 10 , D1 300 600 900 1200 1500 1800 2100 2400 2700 FLOW (N ^1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings l' 1 Summary COSCO F1Rt PROTECTION Page 1ST FLOOR RETAIL Date 050207 Fitting Legend Abbrev. Name 1/2 % 1 1''/ 1% 2 2% 3 3 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I 90' Grvd -Vic Elbow #10 0 0 2 3 4 3.5 6 5 8 7 8.5 10 13 17 20 23 25 33 36 40 J 90'Tee- Branch Gry Vic #20 0 0 4.5 6 8 8.5 10.8 13 17 16 21 25 33 41 50 65 78 88 98 120 T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD COSCO FIRE PROTECTION Page 4 1ST FLOOR RETAIL Date 050207 Node Elevation K -Fact Pt Pn Flow Density Area Press Actual Actual Req. 100 18.0 11.2 20.74 na 51.01 0.17 256 20.7 101 18.0 11.2 21.03 na 51.37 0.17 256 20.7 102 18.0 11.2 22.04 na 52.59 0.17 256 20.7 103 18.0 11.2 24.1 na 54.99 0.17 256 20.7 104 18.0 11.2 29.8 na 61.14 0.17 256 20.7 105 18.0 11.2 20.7 na 50.96 0.17 256 20.7 106 18.0 11.2 20.99 na 51.32 0.17 256 20.7 107 18.0 11.2 22.0 na 52.53 0.17 256 20.7 108 18.0 11.2 24.06 na 54.93 0.17 256 20.7 109 18.0 11.2 29.74 na 61.08 0.17 256 20.7 110 18.0 11.2 21.31 na 51.7 0.17 256 20.7 111 18.0 11.2 21.61 na 52.07 0.17 256 20.7 112 18.0 11.2 22.81 na 53.49 0.17 256 20.7 113 18.0 11.2 25.63 na 56.7 0.17 256 20.7 114 18,0 11.2 29.38 na 60.7 0.17 256 20.7 2 18.0 30.19 na 4 18.0 30.13 na 6 18.0 30.06 na 1 16.0 36.83 na 3 16.0 36.77 na 5 16.0 36.85 na 7 16.0 44.75 na 8 16.0 45.91 na 10 16.0 37.23 na 11 16.0 41.08 na 9 16.0 49.44 na 12 16.0 50.28 na RT1 17.5 50.16 na RB1 3.5 56.98 na RB2 3.5 57.01 na BF1 3.5 57.05 na '1 3.5 61.39 na 0.5 63.09 na .,r C -3.5 65.6 na 500.0 The maximum velocity is 24.12 and it occurs in the pipe between nodes 6 and 5 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen - Williams COSCO FIRE PROTECTION Page 5 1ST FLOOR RETAIL Date 050207 Hyd. Qa Dia. Fitting Pipe Pt Pt ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** . •oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 100 51.01 2.157 0.0 13.330 20.741 K Factor = 11.20 to 120 0.0 0.0 0.0 101 51.01 0.0220 0.0 13.330 0.293 Vel = 4.48 101 51.36 2.157 0.0 12.670 21.034 K Factor = 11.20 to 120 0.0 0.0 0.0 102 102.37 0.0797 0.0 12.670 1.010 Vel = 8.99 102 52.59 2.157 0.0 12.000 22.044 K Factor = 11.20 to 120 0.0 0.0 0.0 103 154.96 0.1717 0.0 12.000 2.060 Vel = 13.61 103 54.99 2.157 1J 10.461 9.750 24.104 K Factor = 11.20 to 120 0.0 10.461 0.0 2 209.95 0.3011 0.0 20.211 6.086 Vel = 18.43 0.0 209.95 30.190 K Factor = 38.21 104 61.14 2.157 1J 10.461 2.250 29.799 K Factor = 11.20 to 120 0.0 10.461 0.0 2 61.14 0.0308 0.0 12.711 0.391 Vel = 5.37 0.0 61.14 30.190 K Factor = 11.13 05 50.96 2.157 0.0 13.330 20.700 K Factor = 11.20 _J 120 0.0 0.0 0.0 106 50.96 0.0219 0.0 13.330 0.292 Vel = 4.47 106 51.31 2.157 0.0 12.670 20.992 K Factor = 11.20 to 120 0.0 0.0 0.0 107 102.27 0.0796 0.0 12.670 1.009 Vel = 8.98 107 52.54 2.157 0.0 12.000 22.001 K Factor = 11.20 to 120 0.0 0.0 0.0 108 154.81 0.1713 0.0 12.000 2.056 Vel = 13.59 108 54.93 2.157 1J 10.461 9.750 24.057 K Factor = 11.20 to 120 0.0 10.461 0.0 4 209.74 0.3006 0.0 20.211 6.075 Vel = 18.41 0.0 209.74 30.132 K Factor = 38.21 109 61.08 2.157 1J 10.461 2.250 29.742 K Factor = 11.20 to 120 0.0 10.461 0.0 4 61.08 0.0307 0.0 12.711 0.390 Vel = 5.36 0.0 61.08 30.132 K Factor = 11.13 110 51.70 2.157 0.0 13.330 21.310 K Factor = 11.20 to 120 0.0 0.0 0.0 111 51.7 0.0225 0.0 13.330 0.300 Vel = 4.54 111 52.07 2.157 0.0 14.670 21.610 K Factor = 11.20 40 120 0.0 0.0 0.0 12 103.77 0.0818 0.0 14.670 1.200 Vel = 9.11 112 53.49 2.157 0.0 16.000 22.810 K Factor = 11.20 to 120 0.0 0.0 0.0 113 157.26 0.1764 0.0 16.000 2.822 Vel = 13.81 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 6 1ST FLOOR RETAIL Date 050207 Hyd. Qa Dia. Fitting Pipe Pt Pt Bf. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** . oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 113 56.70 2.157 1J 10.461 3.750 25.632 K Factor = 11.20 to 120 0.0 10.461 0.0 6 213.96 0.3119 0.0 14.211 4.432 Vel = 18.79 0.0 213.96 30.064 K Factor = 39.02 114 60.70 2.157 1J 10.461 12.250 29.375 K Factor = 11.20 to 120 0.0 10.461 0.0 6 60.7 0.0303 0.0 22.711 0.689 Vel = 5.33 0.0 60.70 30.064 K Factor = 11.07 2 271.09 2.157 1J 10.461 1.500 30.190 to 120 0.0 10.461 0.866 1 271.09 0.4831 0.0 11.961 5.778 Vel = 23.80 0.0 271.09 36.834 K Factor = 44.67 4 270.82 2.157 1J 10.461 1.500 30.132 to 120 0.0 10.461 0.866 3 270.82 0.4822 0.0 11.961 5.768 Vel = 23.78 0.0 270.82 36.766 K Factor = 44.66 6 274.67 2.157 1J 10.461 1.500 30.064 to 120 0.0 10.461 0.866 5 274.67 0.4949 0.0 11.961 5.920 Vel = 24.12 0.0 274.67 36.850 K Factor = 45.25 1 - 126.58 4.26 0.0 16.000 36.834 to 120 0.0 0.0 0.0 3 - 126.58 - 0.0042 0.0 16.000 -0.068 Vel = 2.85 3 270.82 4.26 0.0 15.500 36.766 to 120 0.0 0.0 0.0 5 144.24 0.0054 0.0 15.500 0.084 Vel = 3.25 5 274.66 4.26 1J 21.067 179.870 36.850 to 120 0.0 21.067 0.0 7 418.9 0.0393 0.0 200.937 7.896 Vel = 9.43 7 0.0 4.26 0.0 29.500 44.746 to 120 0.0 0.0 0.0 8 418.9 0.0393 0.0 29.500 1.160 Vel = 9.43 8 0.0 4.26 1J 21.067 69.000 45.906 to 120 0.0 21.067 0.0 9 418.9 0.0393 0.0 90.067 3.539 Vel = 9.43 0.0 418.90 49.445 K Factor = 59.57 ' 397.67 4.26 11 9.217 2.000 36.834 120 0.0 9.217 0.0 10 397.67 0.0357 0.0 11.217 0.401 Vel = 8.95 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 7 1ST FLOOR RETAIL Date 050207 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 10 0.0 4.26 11 9.217 98.500 37.235 to 120 0.0 9.217 0.0 11 397.67 0.0357 0.0 107.717 3.844 Vel = 8.95 11 0.0 4.26 1J 21.067 213.330 41.079 to 120 0.0 21.067 0.0 9 397.67 0.0357 0.0 234.397 8.366 Vel = 8.95 0.0 397.67 49.445 K Factor = 56.55 9 816.57 6.357 1J 31.433 11.920 49.445 to 120 0.0 31.433 0.0 12 816.57 0.0192 0.0 43.353 0.833 Vel = 8.25 12 0.0 6.357 11 12.573 15.000 50.278 to 120 0.0 12.573 -0.650 RT1 816.57 0.0193 0.0 27.573 0.531 Vel = 8.25 RT1 0.0 6.357 11 12.573 14.000 50.159 to 120 1B 12.573 25.146 6.063 RB1 816.57 0.0192 0.0 39.146 0.753 Vel = 8.25 RB1 0.0 6.357 0.0 2.000 56.975 to 120 0.0 0.0 0.0 '132 816.57 0.0195 0.0 2.000 0.039 Vel = 8.25 rlB2 0.0 6.357 0.0 2.000 57.014 to 120 0.0 0.0 0.0 BF1 816.57 0.0190 0.0 2.000 0.038 Vel = 8.25 BF1 0.0 6.357 1Zic 0.0 6.000 57.052 to 120 0.0 0.0 4.223 * Fixed Toss = 4.223 BF2 816.57 0.0193 0.0 6.000 0.116 Vel = 8.25 BF2 0.0 6.357 1E 17.603 3.000 61.391 to 120 0.0 17.603 1.299 RB 816.57 0.0192 0.0 20.603 0.396 Vel = 8.25 RB 0.0 8.27 3E 85.404 47.620 63.086 to 140 1T 55.354 147.084 1.732 SRC 816.57 0.0040 1G 6.326 194.704 0.782 Vel = 4.88 500.00 Qa = 500.00 1316.57 65.600 K Factor = 162.55 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 � \ ® ' { > y \ ) \ } tr..; � : � g ' & : : � r ! y � -y< t > } � � \ \y \ _ Fire Protection by Computer Design COSCO FIRE PROTECTION 11800 NE 95TH ST. SUITE 240 VANCOUVER, WA. 98 88 360-883-6383 Job Name : Area # Stock Ro m Building • WASHINGTON SQUARE MALL Location :9 0 WASHINGTON SQUARE MALL ROAD System : 1 Contract :052 Data File : 0 5 - 3.WXF Computer Programs by Hy rate Inc. Route 111 Windham N.H. USA 03087 COSCO FIRE PROTECTION Page 1 Area #3 Stock Room Date 6/21/07 Hydraulic Design Information Sheet ne - DICK'S SPORTING GOODS Date - 5/09/07 Location - 9402 WASHINGTON SQUARE MALL ROAD Building - WASHINGTON SQUARE MALL System No. - 1 Contractor - S.D. DEACON Contract No. - 0052 Calculated By - NICK STALKUP Drawing No. - FP -2 Construction: ( ) Combustible (X) Non - Combustible Ceiling Height - 20' -0" Occupancy - GROUP A PLASTICS WITH 12' -0" HIGH SHELF S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 (X) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other UP TO 12' -0" HIGH SHELF STORAGE OF GROUP A PLASTICS T Specific Ruling Made By Date E M Area of Sprinkler Operation - 2500 System Type Sprinkler /Nozzle Density - .40 (X) Wet Make TYCO D Area Per Sprinkler - 100 ( ) Dry Model FRB E Elevation at Highest Outlet - 18 ( ) Deluge Size 1/2" S Hose Allowance - Inside - ( ) Preaction K- Factor 8.OK I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside - 500 N Note Calculation Flow Required - 1225.08 Press Required - 68.35 11.32 UNDER CURVE Summary C- Factor Used: 120 Overhead 140 Underground Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 4/28/05 Cap. - T Time of Test - Rated Cap.- Elev.- E Static Press - 82 @ Press - R Residual Press - 76 Elev. - Well Flow - 2042 Proof Flow S Elevation - -3.5 U P Location - 9300 SW WASHINGTON SQUARE ROAD P L Source of Information - TVFR WEBSITE Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Sr ply Curve (C) COSCO Flmc PROTECTION Page _ Area #3 Stock Room Date 6/21/07 City Water Supply: Demand: C1 - Static Pressure : 82 D1 - Elevation : 9.312 C2 - Residual Pressure: 76 D2 - System Flow : 1225.09 C2 - Residual Flow : 2042 D2 - System Pressure : 68.353 Hose (Adj City) Hose ( Demand) D3 - System Demand : 1225.09 Safety Margin : 11.315 150 140 130 I P 120 1 R110 1 E 100 j S 90 I C1 s 80 I — - D2 U 70 1 R60 1 E 50 IIIMPr 30 /_ 2 iv, 10 � D1 300 600 900 1200 1500 1800 2100 2400 2700 FLOW (NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings U 1 Summary COSCO FIRt PROTECTION Page Area #3 Stock Room Date 6/21/07 Fitting Legend Abbrev. Name Y: ' 1 1% 1% 2 2% 3 3'h 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I 90' Grvd -Vic Elbow #10 0 0 2 3 4 3.5 6 5 8 7 8.5 10 13 17 20 23 25 33 36 40 J 90'Tee- Branch Gry Vic #20 0 0 4.5 6 8 8.5 10.8 13 17 16 21 25 33 41 50 65 78 88 98 120 T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD COSCO FIRE PROTECTION Page 4 Area #3 Stock Room Date 6/21/07 Node Elevation K -Fact Pt Pn Flow Density Area Press Actual Actual Req. 300 18.0 8 26.91 na 41.5 0.4 100 7.0 301 18.0 8 27.08 na 41.63 0.4 100 7.0 302 18.0 8 27.67 na 42.09 0.4 100 7.0 306 18.0 8 26.02 na 40.81 0.4 100 7.0 305 18.0 8 26.18 na 40.94 0.4 100 7.0 304 18.0 8 26.76 na 41.39 0.4 100 7.0 307 18.0 8 27.94 na 42.28 0.4 100 7.0 308 18.0 8 28.09 na 42.4 0.4 100 7.0 313 18.0 8 25.0 na 40.0 0.4 100 7.0 312 18.0 8 25.14 na 40.11 0.4 100 7.0 311 18.0 8 25.65 na 40.51 0.4 100 7.0 310 18.0 8 26.73 na 41.36 0.4 100 7.0 314 18.0 8 27.99 na 42.33 0.4 100 7.0 315 18.0 8 28.15 na 42.45 0.4 100 7.0 320 18.0 8 25.05 na 40.04 0.4 100 7.0 319 18.0 8 25.19 na 40.15 0.4 100 7.0 318 18.0 8 25.7 na 40.56 0.4 100 7.0 317 18.0 8 26.78 na 41.4 0.4 100 7.0 321 18.0 8 28.12 na 42.42 0.4 100 7.0 322 18.0 8 28.27 na 42.54 0.4 100 7.0 327 18.0 8 25.16 na 40.13 0.4 100 7.0 326 18.0 8 25.3 na 40.24 0.4 100 7.0 325 18.0 8 25.81 na 40.64 0.4 100 7.0 324 18.0 8 26.9 na 41.49 0.4 100 7.0 328 18.0 8 33.33 na 46.19 0.4 100 7.0 330 18.0 8 33.23 na 46.12 0.4 100 7.0 331 18.0 8 35.68 na 47.79 0.4 100 7.0 333 18.0 8 35.68 na 47.79 0.4 100 7.0 335 18.0 8 35.7 na 47.8 0.4 100 7.0 303 18.0 29.03 na 309 18.0 29.11 na 18.0 29.17 na 18.0 29.3 na ,,c9 18.0 33.57 na 332 16.0 36.65 na 334 16.0 36.66 na 336 16.0 36.68 na 21 16.0 34.81 na 22 16.0 34.83 na 23 16.0 34.9 na 24 16.0 35.04 na 25 16.0 35.22 na 20 16.0 36.92 na 10 16.0 40.46 na 7 16.0 36.96 na 8 16.0 42.66 na 11 16.0 42.01 na 9 16.0 45.38 na 12 16.0 47.15 na RT1 17.5 47.62 na RB1 3.5 55.28 na RB2 3.5 55.36 na BF1 3.5 55.44 na BF2 3.5 62.83 na RB 0.5 64.96 na SRC -3.5 68.35 na The maximum velocity is 22.1 and it occurs in the pipe between nodes 7 and 8 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen - Williams COSCO FIRE PROTECTION Page 5 Area #3 Stock Room Date 6/21/07 Hyd. Qa Dia. Fitting Pipe Pt Pt ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** .point Qt Pf /Ft Eqv. Ln. Total Pf Pn 300 41.50 2.157 0.0 11.000 26.913 K Factor = 8.00 to 120 0.0 0.0 0.0 301 41.5 0.0150 0.0 11.000 0.165 Vel = 3.64 301 41.63 2.157 0.0 11.000 27.078 K Factor = 8.00 to 120 0.0 0.0 0.0 302 83.13 0.0543 0.0 11.000 0.597 Vel = 7.30 302 42.09 2.157 1J 10.461 1.250 27.675 K Factor = 8.00 to 120 0.0 10.461 0.0 303 125.22 0.1157 0.0 11.711 1.355 Vel = 10.99 0.0 125.22 29.030 K Factor = 23.24 306 40.81 2.157 0.0 11.000 26.024 K Factor = 8.00 to 120 0.0 0.0 0.0 305 40.81 0.0145 0.0 11.000 0.160 Vel = 3.58 305 40.94 2.157 0.0 11.000 26.184 K Factor = 8.00 to 120 0.0 0.0 0.0 304 81.75 0.0525 0.0 11.000 0.578 Vel = 7.18 304 41.38 2.157 1J 10.461 9.750 26.762 K Factor = 8.00 to 120 0.0 10.461 0.0 '03 123.13 0.1122 0.0 20.211 2.268 Vel = 10.81 0.0 123.13 29.030 K Factor = 22.85 307 42.28 2.157 0.0 10.000 27.937 K Factor = 8.00 to 120 0.0 0.0 0.0 308 42.28 0.0156 0.0 10.000 0.156 Vel = 3.71 308 42.41 2.157 1J 10.461 7.670 28.093 K Factor = 8.00 to 120 0.0 10.461 0.0 309 84.69 0.0561 0.0 18.131 1.017 Vel = 7.44 0.0 84.69 29.110 K Factor = 15.70 313 40.00 2.157 0.0 10.000 25.000 K Factor = 8.00 to 120 0.0 0.0 0.0 312 40.0 0.0140 0.0 10.000 0.140 Vel = 3.51 312 40.11 2.157 0.0 10.000 25.140 K Factor = 8.00 to 120 0.0 0.0 0.0 311 80.11 0.0507 0.0 10.000 0.507 Vel = 7.03 311 40.52 2.157 0.0 10.000 25.647 K Factor = 8.00 to 120 0.0 0.0 0.0 310 120.63 0.1080 0.0 10.000 1.080 Vel = 10.59 310 41.35 2.157 1J 10.461 2.330 26.727 K Factor = 8.00 to 120 0.0 10.461 0.0 309 161.98 0.1863 0.0 12.791 2.383 Vel = 14.22 0.0 161.98 29.110 K Factor = 30.02 314 42.33 2.157 0.0 10.000 27.994 K Factor = 8.00 to 120 0.0 0.0 0.0 315 42.33 0.0156 0.0 10.000 0.156 Vel = 3.72 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 6 Area #3 Stock Room Date 6/21/07 Hyd. Qa Dia. Fitting Pipe Pt Pt ?.f. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 315 42.44 2.157 1J 10.461 7.670 28.150 K Factor = 8.00 to 120 0.0 10.461 0.0 316 84.77 0.0563 0.0 18.131 1.020 Vel = 7.44 0.0 84.77 29.170 K Factor = 15.70 320 40.04 2.157 0.0 10.000 25.052 K Factor = 8.00 to 120 0.0 0.0 0.0 319 40.04 0.0140 0.0 10.000 0.140 Vel = 3.52 319 40.15 2.157 0.0 10.000 25.192 K Factor = 8.00 to 120 0.0 0.0 0.0 318 80.19 0.0508 0.0 10.000 0.508 Vel = 7.04 318 40.56 2.157 0.0 10.000 25.700 K Factor = 8.00 to 120 0.0 0.0 0.0 317 120.75 0.1082 0.0 10.000 1.082 Vel = 10.60 317 41.40 2.157 1J 10.461 2.330 26.782 K Factor = 8.00 to 120 0.0 10.461 0.0 316 162.15 0.1867 0.0 12.791 2.388 Vel = 14.24 0.0 162.15 29.170 K Factor = 30.02 21 42.42 2.157 0.0 10.000 28.115 K Factor = 8.00 to 120 0.0 0.0 0.0 322 42.42 0.0156 0.0 10.000 0.156 Vel = 3.72 322 42.54 2.157 1J 10.461 7.670 28.271 K Factor = 8.00 to 120 0.0 10.461 0.0 323 84.96 0.0565 0.0 18.131 1.024 Vel = 7.46 0.0 84.96 29.295 K Factor = 15.70 327 40.13 2.157 0.0 10.000 25.160 K Factor = 8.00 to 120 0.0 0.0 0.0 326 40.13 0.0142 0.0 10.000 0.142 Vel = 3.52 326 40.24 2.157 0.0 10.000 25.302 K Factor = 8.00 to 120 0.0 0.0 0.0 325 80.37 0.0509 0.0 10.000 0.509 Vel = 7.06 325 40.64 2.157 0.0 10.000 25.811 K Factor = 8.00 to 120 0.0 0.0 0.0 324 121.01 0.1087 0.0 10.000 1.087 Vel = 10.62 324 41.49 2.157 1J 10.461 2.330 26.898 K Factor = 8.00 to 120 0.0 10.461 0.0 323 162.5 0.1874 0.0 12.791 2.397 Vel = 14.27 0.0 162.50 29.295 K Factor = 30.02 328 46.19 2.157 1J 10.461 2.330 33.331 K Factor = 8.00 `i 120 0.0 10.461 0.0 X29 46.19 0.0183 0.0 12.791 0.234 Vel = 4.06 0.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 7 Area #3 Stock Room Date 6/21/07 Hyd. Qa Dia. Fitting Pipe Pt Pt ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** . oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 46.19 33.565 K Factor = 7.97 330 46.12 2.157 1J 10.461 7.670 33.235 K Factor = 8.00 to 120 0.0 10.461 0.0 329 46.12 0.0182 0.0 18.131 0.330 Vel = 4.05 0.0 46.12 33.565 K Factor = 7.96 331 47.79 2.157 11 4.307 1.170 35.680 K Factor = 8.00 to 120 0.0 4.307 0.866 332 47.79 0.0195 0.0 5.477 0.107 Vel = 4.20 0.0 47 36.653 K Factor = 7.89 333 47.79 2.157 11 4.307 1.170 35.685 K Factor = 8.00 to 120 0.0 4.307 0.866 334 47.79 0.0195 0.0 5.477 0.107 Vel = 4.20 0.0 47 36.658 K Factor = 7.89 335 47.80 2.157 11 4.307 1.170 35.703 K Factor = 8.00 to 120 0.0 4.307 0.866 336 47.8 0.0195 0.0 5.477 0.107 Vel = 4.20 0.0 47.80 36.676 K Factor = 7.89 303 248.35 2.157 1J 10.461 1.500 29.030 to 120 0.0 10.461 0.866 21 248.35 0.4108 0.0 11.961 4.914 Vel = 21.80 0.0 248.35 34.810 K Factor = 42.09 309 246.67 2.157 1J 10.461 1.500 29.110 to 120 0.0 10.461 0.866 22 246.67 0.4057 0.0 11.961 4.853 Vel = 21.66 0.0 246.67 34.829 K Factor = 41.80 316 246.92 2.157 1J 10.461 1.500 29.170 to 120 0.0 10.461 0.866 23 246.92 0.4065 0.0 11.961 4.862 Vel = 21.68 0.0 246.92 34.898 K Factor = 41.80 323 247.46 2.157 1J 10.461 1.500 29.295 to 120 0.0 10.461 0.866 24 247.46 0.4082 0.0 11.961 4.882 Vel = 21.73 0.0 247.46 35.043 K Factor = 41.80 329 92.31 2.157 1J 10.461 1.500 33.565 120 0.0 10.461 0.866 25 92.31 0.0659 0.0 11.961 0.788 Vel = 8.10 0.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 8 Area #3 Stock Room Date 6/21/07 Hyd. Qa Dia. Fitting Pipe Pt Pt ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 92.31 35.219 K Factor = 15.55 332 47.79 4.26 0.0 7.000 36.653 to 120 0.0 0.0 0.0 334 47.79 0.0007 0.0 7.000 0.005 Vel = 1.08 334 47.79 4.26 0.0 7.000 36.658 to 120 0.0 0.0 0.0 336 95.58 0.0026 0.0 7.000 0.018 Vel = 2.15 336 47.80 4.26 1J 21.067 24.750 36.676 to 120 0.0 21.067 0.0 20 143.38 0.0054 0.0 45.817 0.247 Vel = 3.23 0.0 143.38 36.923 K Factor = 23.60 21 248.35 6.357 0.0 9.000 34.810 to 120 0.0 0.0 0.0 22 248.35 0.0021 0.0 9.000 0.019 Vel = 2.51 22 246.67 6.357 0.0 9.000 34.829 to 120 0.0 0.0 0.0 23 495.02 0.0077 0.0 9.000 0.069 Vel = 5.00 23 246.92 6.357 0.0 9.000 34.898 120 0.0 0.0 0.0 ,.4 741.94 0.0161 0.0 9.000 0.145 Vel = 7.50 24 247.46 6.357 0.0 6.420 35.043 to 120 0.0 0.0 0.0 25 989.4 0.0274 0.0 6.420 0.176 Vel = 10.00 25 92.31 6.357 1J 31.433 22.500 35.219 to 120 0.0 31.433 0.0 7 1081.71 0.0324 0.0 53.933 1.745 Vel = 10.93 0.0 1081.71 36.964 K Factor = 177.92 20 143.38 4.26 0.0 7.500 36.923 to 120 0.0 0.0 0.0 7 143.38 0.0055 0.0 7.500 0.041 Vel = 3.23 0.0 143.38 36.964 K Factor = 23.58 10 - 243.19 4.26 11 9.217 213.330 40.464 to 120 1J 21.067 30.284 0.0 7 - 243.19 - 0.0144 0.0 243.614 -3.500 Vel = 5.47 7 1225.09 4.26 0.0 30.000 36.964 to 120 0.0 0.0 0.0 8 981.9 0.1900 0.0 30.000 5.700 Vel = 22.10 8 0.0 6.357 1J 31.433 69.000 42.664 to 120 0.0 31.433 0.0 9 981.9 0.0270 0.0 100.433 2.716 Vel = 9.93 0.0 981.90 45.380 K Factor = 145.76 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 9 Area #3 Stock Room Date 6/21/07 Hyd. Qa Dia. Fitting Pipe Pt Pt ff. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** . oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 10 243.19 4.26 11 9.217 98.500 40.464 to 120 0.0 9.217 0.0 11 243.19 0.0144 0.0 107.717 1.548 Vel = 5.47 11 0.0 4.26 1J 21.067 213.330 42.012 to 120 0.0 21.067 0.0 9 243.19 0.0144 0.0 234.397 3.368 Vel = 5.47 0.0 243.19 45.380 K Factor = 36.10 9 1225.09 6.357 1J 31.433 11.920 45.380 to 120 0.0 31.433 0.0 12 1225.09 0.0407 0.0 43.353 1.766 Vel = 12.38 12 0.0 6.357 11 12.573 15.000 47.146 to 120 0.0 12.573 -0.650 RT1 1225.09 0.0408 0.0 27.573 1.124 Vel = 12.38 RT1 0.0 6.357 11 12.573 14.000 47.620 to 120 1B 12.573 25.146 6.063 RB1 1225.09 0.0407 0.0 39.146 1.595 Vel = 12.38 RB1 0.0 6.357 0.0 2.000 55.278 to 120 0.0 0.0 0.0 B2 1225.09 0.0405 0.0 2.000 0.081 Vel = 12.38 rrB2 0.0 6.357 0.0 2.000 55.359 to 120 0.0 0.0 0.0 BF1 1225.09 0.0405 0.0 2.000 0.081 Vel = 12.38 BF1 0.0 6.357 1 Zic 0.0 6.000 55.440 to 120 0.0 0.0 7.142 * Fixed Toss = 7.142 BF2 1225.09 0.0407 0.0 6.000 0.244 Vel = 12.38 BF2 0.0 6.357 1E 17.603 3.000 62.826 to 120 0.0 17.603 1.299 RB 1225.09 0.0408 0.0 20.603 0.840 Vel = 12.38 RB 0.0 8.27 3E 85.404 47.620 64.965 to 140 1T 55.354 147.084 1.732 SRC 1225.09 0.0085 1G 6.326 194.704 1.656 Vel = 7.32 0.0 1225.09 68.353 K Factor = 148.18 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 - ;; i r z. is . _ . 13` _ _ Fire Protection by Computer Design COSCO FIRE PROTECTION 11800 NE 95TH ST. SUITE 240 VANCOUVER, WA. 98682 360- 883 -6383 Job Name : 2ND FLOOR RETAIL Building : WASHINGTON SQUARE MALL Location : 9402 WASHINGTON SQUARE MALL ROAD System : 2 Contract : 0052 Data File : 0052- FP -.wx2 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 COSCO FIRE PROTECTION Page 1 2ND FLOOR RETAIL Date 050907 Hydraulic Design Information Sheet me - DICK'S SPORTING GOODS Date - 5/09/07 Location - 9402 WASHINGTON SQUARE MALL ROAD Building - WASHINGTON SQUARE MALL System No. - 2 Contractor - S.D. DEACON Contract No. - 0052 Calculated By - NICK STALKUP Drawing No. - FP -2 Construction: ( ) Combustible (X) Non - Combustible Ceiling Height - 31' -0" Occupancy - ORDINARY GROUP II S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date E M Area of Sprinkler Operation - 1538 System Type Sprinkler /Nozzle Density - .2000 (X) Wet Make TYCO D Area Per Sprinkler - 213.00 ( ) Dry Model EC -11 E Elevation at Highest Outlet - 18 ( ) Deluge Size 3/4" S Hose Allowance - Inside - ( ) Preaction K- Factor 11.2 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside - 500 N Note Calculation Flow Required - 1468.63 Press Required - 76.96 1.78 UNDER Summary C- Factor Used: 120 Overhead 140 Underground .. Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 4/28/05 Cap. - T Time of Test - Rated Cap.- Elev.- E Static Press - 82 @ Press - R Residual Press - 76 Elev. - Well Flow - 2042 Proof Flow S Elevation - -3.5 0 P Location - 9300 SW WASHINGTON SQUARE ROAD P L Source of Information - TVFR WEBSITE Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Su- 'v Curve (C) COSCO FIRc PROTECTION Page _ 2ND FLOOR RETAIL Date 050907 City Water Supply: Demand: C1 - Static Pressure : 82 D1 - Elevation : 24.254 C2 - Residual Pressure: 76 D2 - System Flow : 968.63 C2 - Residual Flow : 2042 D2 - System Pressure : 76.959 Hose (Adj City) Hose ( Demand) : 500 D3 - System Demand : 1468.63 Safety Margin : 1.780 150 140 130 P 120 R 110 E 100 S 90 C1 n? C2 S 80 0 — U 70 D3 R 60 E 50 40 30 20 D1 10 300 600 900 1200 1500 1800 2100 2400 2700 FLOW N ^ 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings U- 1 Summary COSCO FIRc PROTECTION Page 2ND FLOOR RETAIL Date 050907 Fitting Legend Abbrev. Name /3 % 1 1'/, 1% 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I 90' Grvd -Vic Elbow #10 0 0 2 3 4 3.5 6 5 8 7 8.5 10 13 17 20 23 25 33 36 40 J 90'Tee- Branch Gry Vic #20 0 0 4.5 6 8 8.5 10.8 13 17 16 21 25 33 41 50 65 78 88 98 120 T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD COSCO FIRE PROTECTION Page 4 2ND FLOOR RETAIL Date 050907 Node Elevation K -Fact Pt Pn Flow Density Area Press Actual Actual Req. 200 52.5 11.2 20.7 na 50.96 0.17 195 20.7 201 52.5 11.2 21.03 na 51.36 0.17 195 20.7 202 52.5 11.2 22.22 na 52.8 0.17 195 20.7 203 52.5 11.2 24.8 na 55.78 0.17 195 20.7 206 52.5 11.2 25.34 na 56.38 0.17 195 20.7 205 52.5 11.2 25.73 na 56.82 0.17 195 20.7 207 52.5 11.2 20.73 na 50.99 0.17 195 20.7 208 52.5 11.2 21.06 na 51.39 0.17 195 20.7 209 52.5 11.2 22.25 na 52.83 0.17 195 20.7 210 52.5 11.2 24.84 na 55.82 0.17 195 20.7 213 52.5 11.2 25.37 na 56.41 0.17 195 20.7 212 52.5 11.2 25.77 na 56.85 0.17 195 20.7 214 52.5 11.2 30.66 na 62.01 0.17 195 20.7 215 52.5 11.2 31.13 na 62.49 0.17 195 20.7 217 52.5 11.2 32.88 na 64.22 0.17 195 20.7 218 52.5 11.2 34.4 na 65.69 0.17 195 20.7 220 52.5 11.2 34.54 na 65.82 0.17 195 20.7 204 52.5 28.13 na 211 52.5 28.17 na 216 52.5 33.42 na 219 52.5 35.1 na 221 51.0 36.82 na 222 51.0 36.87 na 223 51.0 37.02 na 224 51.0 37.27 na 225 38.0 44.17 na 226 38.0 44.29 na 227 38.0 44.44 na 228 38.0 44.69 na 229 38.0 45.42 na 230 38.0 46.09 na 38.0 47.63 na 38.0 44.93 na X03 38.0 45.41 na 234 38.0 46.16 na 235 38.0 48.41 na 236 38.0 49.58 na 237 18.0 59.7 na RT2 3.5 67.03 na RB2 3.5 67.08 na BF1 3.5 67.13 na BF2 3.5 72.31 na RB 0.5 74.15 na SRC -3.5 76.96 na 500.0 The maximum velocity is 28.47 and it occurs in the pipe between nodes 211 and 222 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen - Williams COSCO FIRE PROTECTION Page 5 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 3f. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 200 50.96 2.157 0.0 15.000 20.700 K Factor = 11.20 to 120 0.0 0.0 0.0 201 50.96 0.0219 0.0 15.000 0.329 Vel = 4.47 201 51.36 2.157 0.0 15.000 21.029 K Factor = 11.20 to 120 0.0 0.0 0.0 202 102.32 0.0797 0.0 15.000 1.195 Vel = 8.98 202 52.80 2.157 0.0 15.000 22.224 K Factor = 11.20 to 120 0.0 0.0 0.0 203 155.12 0.1720 0.0 15.000 2.580 Vel = 13.62 203 55.78 2.157 1J 10.461 0.500 24.804 K Factor = 11.20 to 120 0.0 10.461 0.0 204 210.9 0.3036 0.0 10.961 3.328 Vel = 18.52 0.0 210.90 28.132 K Factor = 39.76 206 56.38 2.157 0.0 15.000 25.338 K Factor = 11.20 to 120 0.0 0.0 0.0 205 56.38 0.0265 0.0 15.000 0.397 Vel = 4.95 205 56.82 2.157 1J 10.461 14.500 25.735 K Factor = 11.20 to 120 0.0 10.461 0.0 '04 113.2 0.0960 0.0 24.961 2.397 Vel = 9.94 0.0 113.20 28.132 K Factor = 21.34 207 50.99 2.157 0.0 15.000 20.727 K Factor = 11.20 to 120 0.0 0.0 0.0 208 50.99 0.0219 0.0 15.000 0.329 Vel = 4.48 208 51.39 2.157 0.0 15.000 21.056 K Factor = 11.20 to 120 0.0 0.0 0.0 209 102.38 0.0797 0.0 15.000 1.196 Vel = 8.99 209 52.84 2.157 0.0 15.000 22.252 K Factor = 11.20 to 120 0.0 0.0 0.0 210 155.22 0.1723 0.0 15.000 2.584 Vel = 13.63 210 55.81 2.157 1J 10.461 0.500 24.836 K Factor = 11.20 to 120 0.0 10.461 0.0 211 211.03 0.3039 0.0 10.961 3.331 Vel = 18.53 0.0 211.03 28.167 K Factor = 39.76 213 56.41 2.157 0.0 15.000 25.371 K Factor = 11.20 to 120 0.0 0.0 0.0 212 56.41 0.0265 0.0 15.000 0.397 Vel = 4.95 212 56.86 2.157 1J 10.461 14.500 25.768 K Factor = 11.20 to 120 0.0 10.461 0.0 211 113.27 0.0961 0.0 24.961 2.399 Vel = 9.94 0.0 113.27 28.167 K Factor = 21.34 214 62.01 2.157 0.0 15.000 30.658 K Factor = 11.20 to 120 0.0 0.0 0.0 215 62.01 0.0316 0.0 15.000 0.474 Vel = 5.44 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 6 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 215 62.50 2.157 1J 10.461 9.500 31.132 K Factor = 11.20 to 120 0.0 10.461 0.0 216 124.51 0.1145 0.0 19.961 2.286 Vel = 10.93 0.0 124.51 33.418 K Factor = 21.54 217 64.22 2.157 1J 10.461 5.500 32.880 K Factor = 11.20 to 120 0.0 10.461 0.0 216 64.22 0.0337 0.0 15.961 0.538 Vel = 5.64 0.0 64.22 33.418 K Factor = 11.11 218 65.69 2.157 1J 10.461 9.500 34.400 K Factor = 11.20 to 120 0.0 10.461 0.0 219 65.69 0.0351 0.0 19.961 0.701 Vel = 5.77 0.0 65.69 35.101 K Factor = 11.09 220 65.82 2.157 1J 10.461 5.500 34.538 K Factor = 11.20 to 120 0.0 10.461 0.0 219 65.82 0.0353 0.0 15.961 0.563 Vel = 5.78 0.0 65.82 35.101 K Factor = 11.11 204 324.09 2.157 1J 10.461 1.500 28.132 to 120 0.0 10.461 0.650 221 324.09 0.6722 0.0 11.961 8.040 Vel = 28.45 0.0 324.09 36.822 K Factor = 53.41 211 324.30 2.157 1J 10.461 1.500 28.167 to 120 0.0 10.461 0.650 222 324.3 0.6731 0.0 11.961 8.051 Vel = 28.47 0.0 324.30 36.868 K Factor = 53.41 216 188.73 2.157 1J 10.461 1.500 33.418 to 120 0.0 10.461 0.650 223 188.73 0.2471 0.0 11.961 2.956 Vel = 16.57 0.0 188.73 37.024 K Factor = 31.02 219 131.51 2.157 1J 10.461 1.500 35.101 to 120 0.0 10.461 0.650 224 131.51 0.1267 0.0 11.961 1.515 Vel = 11.55 0.0 131.51 37.266 K Factor = 21.54 221 324.09 6.357 0.0 13.000 36.822 to 120 0.0 0.0 0.0 222 324.09 0.0035 0.0 13.000 0.046 Vel = 3.28 222 324.30 6.357 0.0 12.500 36.868 to 120 0.0 0.0 0.0 223 648.39 0.0125 0.0 12.500 0.156 Vel = 6.55 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 7 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** . Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 223 188.73 6.357 0.0 12.000 37.024 to 120 0.0 0.0 0.0 224 837.12 0.0202 0.0 12.000 0.242 Vel = 8.46 224 131.51 6.357 1J 31.433 16.750 37.266 to 120 0.0 31.433 5.630 225 968.63 0.0264 0.0 48.183 1.271 Vel = 9.79 0.0 968.63 44.167 K Factor = 145.75 225 157.73 4.26 11 9.217 10.170 44.167 to 120 0.0 9.217 0.0 226 157.73 0.0064 0.0 19.387 0.125 Vel = 3.55 226 0.0 4.26 11 9.217 13.000 44.292 to 120 0.0 9.217 0.0 227 157.73 0.0065 0.0 22.217 0.144 Vel = 3.55 227 0.0 4.26 11 9.217 30.920 44.436 to 120 0.0 9.217 0.0 228 157.73 0.0064 0.0 40.137 0.258 Vel = 3.55 228 0.0 4.26 11 9.217 104.000 44.694 to 120 0.0 9.217 0.0 29 157.73 0.0065 0.0 113.217 0.731 Vel = 3.55 229 0.0 4.26 11 9.217 94.000 45.425 to 120 0.0 9.217 0.0 230 157.73 0.0064 0.0 103.217 0.665 Vel = 3.55 230 0.0 4.26 11 9.217 229.670 46.090 to 120 0.0 9.217 0.0 231 157.73 0.0065 0.0 238.887 1.541 Vel = 3.55 231 0.0 4.26 21 18.434 101.830 47.631 to 120 0.0 18.434 0.0 235 157.73 0.0065 0.0 120.264 0.776 Vel = 3.55 0.0 157.73 48.407 K Factor = 22.67 225 810.90 6.357 11 12.573 27.500 44.167 to 120 0.0 12.573 0.0 232 810.9 0.0190 0.0 40.073 0.761 Vel = 8.20 232 0.0 6.357 11 12.573 13.000 44.928 to 120 0.0 12.573 0.0 233 810.9 0.0190 0.0 25.573 0.486 Vel = 8.20 233 0.0 6.357 11 12.573 26.670 45.414 to 120 0.0 12.573 0.0 234 810.9 0.0190 0.0 39.243 0.744 Vel = 8.20 234 0.0 6.357 1J 31.433 87.000 46.158 to 120 0.0 31.433 0.0 235 810.9 0.0190 0.0 118.433 2.249 Vel = 8.20 .35 157.73 6.357 21 25.147 19.500 48.407 to 120 0.0 25.147 0.0 236 968.63 0.0264 0.0 44.647 1.178 Vel = 9.79 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 8 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 0.0 968.63 49.585 K Factor = 137.56 236 968.63 6.357 21 25.147 30.000 49.585 to 120 0.0 25.147 8.662 237 968.63 0.0264 0.0 55.147 1.454 Vel = 9.79 237 0.0 6.357 11 12.573 14.500 59.701 to 120 1B 12.573 25.146 6.280 RT2 968.63 0.0264 0.0 39.646 1.046 Vel = 9.79 RT2 0.0 6.357 0.0 2.000 67.027 to 120 0.0 0.0 0.0 RB2 968.63 0.0265 0.0 2.000 0.053 Vel = 9.79 RB2 0.0 6.357 0.0 2.000 67.080 to 120 0.0 0.0 0.0 BF1 968.63 0.0260 0.0 2.000 0.052 Vel = 9.79 BF1 0.0 6.357 1Zic 0.0 6.000 67.132 to 120 0.0 0.0 5.021 * Fixed loss = 5.021 BF2 968.63 0.0265 0.0 6.000 0.159 Vel = 9.79 BF2 0.0 6.357 1E 17.603 3.000 72.312 to 120 0.0 17.603 1.299 'B 968.63 0.0264 0.0 20.603 0.543 Vel = 9.79 i-d3 0.0 8.27 3E 85.404 47.620 74.154 to 140 1T 55.354 147.084 1.732 SRC 968.63 0.0055 1G 6.326 194.704 1.073 Vel = 5.79 500.00 Qa = 500.00 1468.63 76.959 K Factor = 167.41 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 t�. t t I r .4 J Fire Protection by Computer Design COSCO FIRE PROTECTION 11800 NE 95TH ST. SUITE 240 VANCOUVER, WA. 98682 360- 883 -6383 Job Name : 2ND FLOOR RETAIL Building : WASHINGTON SQUARE MALL Location : 9402 WASHINGTON SQUARE MALL ROAD System : 2 Contract : 0052 Data File : 0052- FP -3.wx4 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 COSCO FIRE PROTECTION Page 1 2ND FLOOR RETAIL Date 050907 Hydraulic Design Information Sheet me - DICK'S SPORTING GOODS Date - 5/09/07 Location - 9402 WASHINGTON SQUARE MALL ROAD Building - WASHINGTON SQUARE MALL System No. - 2 Contractor - S.D. DEACON Contract No. - 0052 Calculated By - NICK STALKUP Drawing No. - FP -2 Construction: ( ) Combustible (X) Non - Combustible Ceiling Height - 31' -0" Occupancy - ORDINARY GROUP II S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 ( ) 3 ( ) Ex.Haz. Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date E M Area of Sprinkler Operation - 1538 System Type Sprinkler /Nozzle Density - .2000 (X) Wet Make TYCO D Area Per Sprinkler - 213.00 ( ) Dry Model EC -11 E Elevation at Highest Outlet - 18 ( ) Deluge Size 3/4" S Hose Allowance - Inside - ( ) Preaction K- Factor 11.2 I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155 G Hose Allowance - Outside - 500 N Note Calculation Flow Required - 1245.43 Press Required - 67.54 12.05 UNDER Summary C- Factor Used: 120 Overhead 140 Underground Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - 4/28/05 Cap. - T Time of Test - Rated Cap.- Elev.- E Static Press - 82 @ Press - R Residual Press - 76 Elev. - Well Flow - 2042 Proof Flow S Elevation - -3.5 U P Location - 9300 SW WASHINGTON SQUARE ROAD P L Source of Information - TVFR WEBSITE Y C Commodity Class Location O Storage Ht. Area Aisle W. M Storage Method: Solid Piled % Palletized % Rack M ( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G E Horizontal Barriers Provided: Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Sr ly Curve (C) COSCO FIRE PROTECTION Page 2ND FLOOR RETAIL Date 050907 City Water Supply: Demand: C1 - Static Pressure : 82 D1 - Elevation : 18.840 C2 - Residual Pressure: 76 D2 - System Flow : 745.43 C2 - Residual Flow : 2042 D2 - System Pressure : 67.543 Hose ( Adj City) Hose ( Demand) : 500 D3 - System Demand : 1245.43 Safety Margin : 12.053 150 140 130 p 120 R 110 E 100 S 90 C1 5 80 e — U 70 C2 0 R 60 C3 E 50 40 30 20 D1 10 ,,. .......... . . ... . . . . . . . . 300 600 900 1200 1500 1800 2100 2400 2700 FLOW ( ^ 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings l' ri Summary COSCO FIiw PROTECTION Page 2ND FLOOR RETAIL Date 050907 Fitting Legend Abbrev. Name '/2 3 4 1 11/2 11/2 2 2% 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I 90' Grvd -Vic Elbow #10 0 0 2 3 4 3.5 6 5 8 7 8.5 10 13 17 20 23 25 33 36 40 J 90'Tee- Branch Gry Vic #20 0 0 4.5 6 8 8.5 10.8 13 17 16 21 25 33 41 50 65 78 88 98 120 T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Nressure / How Summary - 5 I ANUAKL) COSCO FIRE PROTECTION Page 4 2ND FLOOR RETAIL Date 050907 Node Elevation K -Fact Pt Pn Flow Density Area Press ^i ^ Actual Actual Req. 400 40.0 11.2 25.14 na 56.16 0.17 195 20.7 401 40.0 11.2 25.53 na 56.59 0.17 195 20.7 404 40.0 11.2 20.7 na 50.96 0.17 195 20.7 405 40.0 11.2 21.02 na 51.35 0.17 195 20.7 406 40.0 11.2 22.19 na 52.76 0.17 195 20.7 407 40.0 11.2 24.71 na 55.68 0.17 195 20.7 410 40.0 11.2 20.7 na 50.96 0.17 195 20.7 411 40.0 11.2 21.02 na 51.35 0.17 195 20.7 412 40.0 11.2 22.19 na 52.76 0.17 195 20.7 413 40.0 11.2 24.71 na 55.68 0.17 195 20.7 416 40.0 11.2 20.79 na 51.06 0.17 195 20.7 417 40.0 11.2 21.11 na 51.46 0.17 195 20.7 418 40.0 11.2 22.28 na 52.87 0.17 195 20.7 419 40.0 11.2 24.81 na 55.79 0.17 195 20.7 402 40.0 29.82 na 408 40.0 27.16 na 414 40.0 27.15 na 420 40.0 27.27 na 225 38.0 41.19 na 226 38.0 40.65 na 227 38.0 40.02 na 228 38.0 38.63 na 229 38.0 35.43 na 230 38.0 32.52 na 403 38.0 31.83 na 409 38.0 31.65 na 415 38.0 31.65 na 421 38.0 31.77 na 231 38.0 37.84 na 232 38.0 41.35 na 233 38.0 41.46 na ^ 38.0 41.61 na 38.0 42.09 na 38.0 42.81 na 237 18.0 52.37 na RT2 3.5 59.3 na RB2 3.5 59.33 na BF1 3.5 59.36 na BF2 3.5 63.52 na RB 0.5 65.15 na SRC -3.5 67.54 na 500.0 The maximum velocity is 18.54 and it occurs in the pipe between nodes 419 and 420 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen - Williams COSCO FIRE PROTECTION Page 5 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt `ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 400 56.16 2.157 0.0 14.670 25.140 K Factor = 11.20 to 120 0.0 0.0 0.0 401 56.16 0.0263 0.0 14.670 0.386 Vel = 4.93 401 56.58 2.157 31 12.922 32.170 25.526 K Factor = 11.20 to 120 0.0 12.922 0.0 402 112.74 0.0953 0.0 45.092 4.298 Vel = 9.90 0.0 112.74 29.824 K Factor = 20.64 404 50.96 2.157 0.0 14.670 20.702 K Factor = 11.20 to 120 0.0 0.0 0.0 405 50.96 0.0219 0.0 14.670 0.322 Vel = 4.47 405 51.35 2.157 0.0 14.670 21.024 K Factor = 11.20 to 120 0.0 0.0 0.0 406 102.31 0.0797 0.0 14.670 1.169 Vel = 8.98 406 52.77 2.157 0.0 14.670 22.193 K Factor = 11.20 to 120 0.0 0.0 0.0 407 155.08 0.1719 0.0 14.670 2.522 Vel = 13.62 407 55.68 2.157 11 4.307 3.750 24.715 K Factor = 11.20 to 120 0.0 4.307 0.0 1 08 210.76 0.3032 0.0 8.057 2.443 Vel = 18.50 0.0 210.76 27.158 K Factor = 40.44 410 50.96 2.157 0.0 14.670 20.700 K Factor = 11.20 to 120 0.0 0.0 0.0 411 50.96 0.0219 0.0 14.670 0.322 Vel = 4.47 411 51.35 2.157 0.0 14.670 21.022 K Factor = 11.20 to 120 0.0 0.0 0.0 412 102.31 0.0796 0.0 14.670 1.168 Vel = 8.98 412 52.76 2.157 0.0 14.670 22.190 K Factor = 11.20 to 120 0.0 0.0 0.0 413 155.07 0.1719 0.0 14.670 2.522 Vel = 13.61 413 55.67 2.157 11 4.307 3.750 24.712 K Factor = 11.20 to 120 0.0 4.307 0.0 414 210.74 0.3032 0.0 8.057 2.443 Vel = 18.50 0.0 210.74 27.155 K Factor = 40.44 416 51.06 2.157 0.0 14.670 20.787 K Factor = 11.20 to 120 0.0 0.0 0.0 417 51.06 0.0220 0.0 14.670 0.323 Vel = 4.48 417 51.46 2.157 0.0 14.670 21.110 K Factor = 11.20 to 120 0.0 0.0 0.0 418 102.52 0.0800 0.0 14.670 1.173 Vel = 9.00 418 52.87 2.157 0.0 14.670 22.283 K Factor = 11.20 120 0.0 0.0 0.0 419 155.39 0.1725 0.0 14.670 2.531 Vel = 13.64 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 6 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 419 55.79 2.157 11 4.307 3.750 24.814 K Factor = 11.20 to 120 0.0 4.307 0.0 420 211.18 0.3045 0.0 8.057 2.453 Vel = 18.54 0.0 211.18 27.267 K Factor = 40.44 402 112.74 2.157 1J 10.461 1.500 29.824 to 120 0.0 10.461 0.866 403 112.74 0.0953 0.0 11.961 1.140 Vel = 9.90 0.0 112.74 31.830 K Factor = 19.98 408 210.76 2.157 1J 10.461 1.500 27.158 to 120 0.0 10.461 0.866 409 210.76 0.3032 0.0 11.961 3.627 Vel = 18.50 0.0 210.76 31.651 K Factor = 37.46 414 210.74 2.157 1J 10.461 1.500 27.155 to 120 0.0 10.461 0.866 415 210.74 0.3032 0.0 11.961 3.627 Vel = 18.50 0.0 210.74 31.648 K Factor = 37.46 420 211.18 2.157 1J 10.461 1.500 27.267 to 120 0.0 10.461 0.866 421 211.18 0.3044 0.0 11.961 3.641 Vel = 18.54 0.0 211.18 31.774 K Factor = 37.46 225 - 350.13 4.26 11 9.217 10.170 41.192 to 120 0.0 9.217 0.0 226 - 350.13 - 0.0282 0.0 19.387 -0.547 Vel = 7.88 226 0.0 4.26 11 9.217 13.000 40.645 to 120 0.0 9.217 0.0 227 - 350.13 - 0.0282 0.0 22.217 -0.626 Vel = 7.88 227 0.0 4.26 21 18.434 30.920 40.019 to 120 0.0 18.434 0.0 228 - 350.13 - 0.0282 0.0 49.354 -1.392 Vel = 7.88 228 0.0 4.26 11 9.217 104.000 38.627 to 120 0.0 9.217 0.0 229 - 350.13 - 0.0282 0.0 113.217 -3.193 Vel = 7.88 229 0.0 4.26 11 9.217 94.000 35.434 to 120 0.0 9.217 0.0 230 - 350.13 - 0.0282 0.0 103.217 -2.911 Vel = 7.88 230 0.0 4.26 0.0 24.580 32.523 to 120 0.0 0.0 0.0 403 - 350.13 - 0.0282 0.0 24.580 -0.693 Vel = 7.88 ,03 112.74 4.26 0.0 13.000 31.830 to 120 0.0 0.0 0.0 409 - 237.39 - 0.0138 0.0 13.000 -0.179 Vel = 5.34 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 7 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn 409 210.75 4.26 0.0 14.670 31.651 to 120 0.0 0.0 0.0 415 -26.64 - 0.0002 0.0 14.670 -0.003 Vel = 0.60 415 210.75 4.26 0.0 14.670 31.648 to 120 0.0 0.0 0.0 421 184.11 0.0086 0.0 14.670 0.126 Vel = 4.14 421 211.18 4.26 11 9.217 162.750 31.774 to 120 0.0 9.217 0.0 231 395.29 0.0353 0.0 171.967 6.070 Vel = 8.90 231 0.0 4.26 21 18.434 101.830 37.844 to 120 0.0 18.434 0.0 235 395.29 0.0353 0.0 120.264 4.244 Vel = 8.90 0.0 395.29 42.088 K Factor = 60.93 225 350.13 6.357 11 12.573 27.500 41.192 to 120 0.0 12.573 0.0 232 350.13 0.0040 0.0 40.073 0.161 Vel = 3.54 232 0.0 6.357 11 12.573 13.000 41.353 to 120 0.0 12.573 0.0 '33 350.13 0.0040 0.0 25.573 0.102 Vel = 3.54 233 0.0 6.357 11 12.573 26.670 41.455 to 120 0.0 12.573 0.0 234 350.13 0.0040 0.0 39.243 0.158 Vel = 3.54 234 0.0 6.357 1J 31.433 87.000 41.613 to 120 0.0 31.433 0.0 235 350.13 0.0040 0.0 118.433 0.475 Vel = 3.54 235 395.30 6.357 21 25.147 19.500 42.088 to 120 0.0 25.147 0.0 236 745.43 0.0163 0.0 44.647 0.726 Vel = 7.54 0.0 745.43 42.814 K Factor = 113.92 236 745.43 6.357 21 25.147 30.000 42.814 to 120 0.0 25.147 8.662 237 745.43 0.0162 0.0 55.147 0.896 Vel = 7.54 237 0.0 6.357 11 12.573 14.500 52.372 to 120 1B 12.573 25.146 6.280 RT2 745.43 0.0162 0.0 39.646 0.644 Vel = 7.54 RT2 0.0 6.357 0.0 2.000 59.296 to 120 0.0 0.0 0.0 RB2 745.43 0.0160 0.0 2.000 0.032 Vel = 7.54 RB2 0.0 6.357 0.0 2.000 59.328 to 120 0.0 0.0 0.0 BF1 745.43 0.0165 0.0 2.000 0.033 Vel = 7.54 3F1 0.0 6.357 1Zic 0.0 6.000 59.361 to 120 0.0 0.0 4.058 * Fixed loss = 4.058 BF2 745.43 0.0162 0.0 6.000 0.097 Vel = 7.54 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Standard COSCO FIRE PROTECTION Page 8 2ND FLOOR RETAIL Date 050907 Hyd. Qa Dia. Fitting Pipe Pt Pt 'ef. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** oint Qt Pf /Ft Eqv. Ln. Total Pf Pn BF2 0.0 6.357 1E 17.603 3.000 63.516 to 120 0.0 17.603 1.299 RB 745.43 0.0163 0.0 20.603 0.335 Vel = 7.54 RB 0.0 8.27 3E 85.404 47.620 65.150 to 140 1T 55.354 147.084 1.732 SRC 745.43 0.0034 1G 6.326 194.704 0.661 Vel = 4.45 500.00 Qa = 500.00 1245.43 67.543 K Factor = 151.54 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087