Plans (149) FPS2O19-OO1 10 DESIGNED BY: DAVE MILLER, SET NICET LEVEL w FIRE ALARM SYS(EkIS RECEIVED 7/01/ zo22 DESIGN CRITERIA/NARRATIVE 1E3 , D ' N C AD R F- S S : AUG 2 7 2019 MS 35/Of A 41gP'NON SHOUA R tX NISIRIED A5 SUM O STRUCTURAL SPECIALTY CODE (OSSC) CITY N TIGARD BUILDING CODE: 2014 OREGON IMMUNOLOGY CQNSULTANTS LABORATORY BUILDING DIVISION � EDITION OF NFPA 72: 2013 7150 SW SANDBURG STREET 1— TOTAL OCCUPANT LOAD: <500 AUTOMATIC FIRE SPRINKLER? NO TIGARD, OR 97223 Z B SPRINKLER SYSTEM TYPE: N/A - PRIMARY USE GROUP: OCCUPANT LOAD OF PRIMARY USE: <500 QTY. OF WET RISERS: N/A VICINITY IV A 9 00 1- SECONDARY USE GROUP: QTY. OF DRY RISERS: N/A a � OCCUPANT LOAD OF SECONDARY USE: QTY. OF PRE-ACTION RISERS: N/A :SW S iridbur�� i,1 W SECONDARY USE GROUP: BACK FLOW IN VAULT: N/A �' Z � OCCUPANT LOAD OF SECONDARY USE: ELEVATOR INSTALLED ON PROJECT? NO 4`' f T Akan Metal O (f� LEVATOR RECALL REQUIRED? NO 1 f. $ BurkhartDenta Supply 1 SPeclaitles est (� ar ELEVATOR EMERG. SHUT DOWN REQ.? NO f - ••• A - I COMMENTARY: IMMUNOLOGY CONSULTANTS LABORATORY (ICL) IS PRIMARLY A B USE GROUP, WITH S USE GROUP ASSOCIATED ' iii.i '" +, , THROUGH OUT THE BUILDING. THE BUILDING OCCUPANT LOAD IS LESS THAN 500 FOR MORE RESTRICTIVE B USE GROUP, - _ 1 O --_-� � � � � SH ET I \ SEX � Q THEREFORE A MANUAL FIRE ALARM SYSTEM IS NOT REQUIRED. BOTH LEVELS CAN EXIT TO GRADE, THUS NO FLOORS ARE - Q ABOVE BELOW THE LEVEL OF EXIT DISCHARGE. THE OWNER HAS CHOSEN TO PROVIDE ANON-REQUIRED FIRE ALARM SYSTEM1 Southwest + + / } EA0.00 — COVER SHEET Z 0 1^r- -S•.P Q E� g §tre t."4 i WITH MANUAL PULL STATIONS AT EACH EXIT, NOTIFICATION THROUGHOUT, AND MONITOR OF DUCT SMOKE DETECTORS (BY Ce w ;,1� , - I",", AND TO SHUTDOWN ALL HVAC UNITS ON A2 CO NY SUPERVISORY INPUT FROM THE DUCT SMOKE DETECTORS. SMOKEt► . _ 4 L ,� EA1 .00 — FLOOR PLANS Z OTHERS, � WILL BE PROVIDED AT ALL FIRE SMOKE DOORS USING EXISTING MAGNETIC DOOR HOLD OPEN DEVICES. DOORS WILL "� , I • ;hrl, W DETECTORS / 3 r - . ! -, FA1 .01 — FLOOR PLANS Q ce BE RELEASED ON ANY FIRE ALARM CONDITION AND ON 120VAC FAIL AT FACP. Li- .'- j J � � �,; • • �� EA2.O0 — RISER DIAGRAM CODE REFERENCE RESPONSE wr ,• ' 907.2.2 GROUP B => 500 OCCUPANTS FOR ALL FLOORS SHALL HAVE NOT APPLICABLE . 3 1 P�. ` s i_ FA3.00 — FIRE ALARM DETAILS #1 A MANUAL FIRE ALARM SYSTEM 'il _ 907.3 - FIRE SAFETY FUNCTIONS SEE 907.3.1 - 907.3.4 _ '' FA3.01 — FIRE ALARM DETAILS #2 907.3.1 - DUCT SMOKE DETECTORS DUCT SMOKE DETECTORS WILL BE MONITORED, AND UNITS '4' . f,?, ;:,,,, • J .=/' _ SHUTDOWN (SEE ABOVE). ,.' 907.3.2 - DELAYED EGRESS LOCKS DOES NOT APPLY 907.3.3 - ELEVATOR EMERGENCY OPERATION DOES NOT APPLY 907.3.4 - WIRING WILL COMPLY 907.4 - INITIATING DEVICES SEE 907.4.1 - 907.4.3.1 907.4.1 - PROTECTION OF FACU A SMOKE DETECTOR WILL BE PROVIDED AT EACH FACU LOCATION INDICATED ON PLANS. 907.4.2 - MANUAL FIRE ALARM BOXES MANUAL STATIONS WILL COMPLY WITH 907.4.2.1 - 907.4.2.3 OWNER CONTACT INFO: WHERE INSTALLED. 907.4.3 - AUTOMATIC SMOKE DETECTION SEE PLANS FOR LOCATIONS; WILL COMPLY. w IMMUNOLOGY v CONSULTANTS 907.4.3.1 AUTOMATIC SPRINKLER SYSTEM. DOES NOT APPLY w LABORATORY 907.5 - OCCUPANT NOTIFICTION SYSTEMS. AN AUDIBLE AND/OR VISUAL NOTIFICATION SYSTEM WILL BE ❑ 7150 SW SANBURG INSTALLED PER THIS SECTION AND IN COMPLIANCE WITH Q ZST TIGARD, OR p 97223 CHAPTER 18 OF THE REFERENCED EDITION OF NFPA 72. ow Q 907.5.2.3.3 VISUAL DEVICES FOR "ADA" ROOMS (I-1, R-1 & R-4) DOES NOT APPLY z 6 w c V SUBMITTED FOR PERMIT BY: 907.6 - INSTALLATION. SEE 907.6.1 - 907.6.5 FUNCTIONAL MATRIX o < o " LT- L WILL COMPLY 0 cn ~o o >- >- ANDREW 907.6.1 - WIRING. _ C7 NELSON 907.6.2 - POWER SUPPLY. SYSTEM IS CALCULATED FOR A 24-HOUR STANDBY PERIOD, 0 Q O I— Z z I N o—c ,a_ LEA X51 10LEA FOLLOWED BY 5-MINUTES OF ALARM WITH A FULLY O O 0o z Q O O 0� D ❑ EXPIRATION : CONNECTED LOAD. I— I— W p 1- 5 z 5 - Z - in 10/ 1 /2020 907.6.3 - ZONES. THE SYSTEM IS ADDRESSABLE, THUS EACH INPUT DEVICE IS ccarc W 1— w w a ❑❑ a OFFICE COPY ITS OWN ZONE. Q Q ❑ H a a U O O U —ILu I U ❑ O ❑ < cc O cc < ' 907.6.3.1 ZONING INDICATOR PANEL. THE SYSTEM ANNUCIATOR IS AN LCD AND INTEGRAL TO a cc u) a F u- F- I- F- u- THE FACP. ALARM OUTPUTS SUPERVISORY TROUBLE CONTRACTOR: 907.6.4 - ACCESS. ALL DEVICES WILL BE INSTALLED WITH ACCESS AVAILABLE INPUTS CITY OF TIGARD IVO FOR MAINTENANCE & TESTING. ALARMS: REVIEWED FOR CODE COMPLIANCE PACIFIC NETWORKS INC. 907.6.5 - MONITORING A SOLE-PATH GSM COMMUNICATOR WILL BE USED TO O,5INE9s SOLUTIONS Approved« ] 16869 SW 65TH AVE. PROVIDE SIGNALS TO A REMOTE RECEIVING STATION. SMOKE DETECTOR X X X X OTC: I j COMMUNICATION IS VIA A COMMUNICATIONS PROTOCOL MANUAL PULL STATION X X X X rpt �Q Q� 1 #373 LAKE OSWEGO, Address: n <c....,, s+ / OR 97035 LISTED FOR THIS PURPOSE. Suite* - 907.7 - ACCETPANCE TESTS & COMPLETION SEE 907.7.1 - 907.7.3 SUPERVISORY: - By: �;" Date: q- )7 _ )ci PROJECT NAME: X X X • IMMUNOLOGY 907.7.1 - SINGLE- & MULTIPLE-STATION SMOKE ALARMS DOES NOT APPLY DUCT SMOKE DETECTOR MONITOR CONSULTANTS . LABORATORY 907.7.2 - RECORD OF COMPLETION WILL COMPLY TROUBLE: PLEASE PROVIDE FIRE ALARM DRAWINGS 907.7.3 - INSTRUCTIONS WILL COMPLYVAC COMPLETED NFPA72 REV: DATE/BY: REV DESCRIPTION: 120 FAIL X X X RECORD OF 100/00/00 xxx 907.8 - INSPECTION TESTING & MAINTENANCE WILL COMPLY ALL TROUBLE CONDITIONS FACP X X COMPLETION AT TSD XXX FINAL INSPECTION 10 R J - : T 2fNTA : TS x I B , LDI \ C OW \ I- R : ' ROJ - CT ARCI I TF- CT : - L - CTR CAL I - \ CIN - F- R : \ STALL \ G C0 \ TRACTOR : SYSTI- \A DI- SIGN - R : AHJ , DRAWING INFO: DRAWN BY: MTM IMMUNOLOGY CONSULTANTS LABORATORY CIDA INC. DOES NOT APPLY PACIFIC NETWORKS DAVE MILLER, SET CITY OF TIGARD PERMIT CENTER CHECKED BY: DCM lij 7150 SW SANDBURG STREET 15895 SW 72ND AVE, SUITE. 200 16869 SW 65TH AVE. #373 (NICET LEVEL IV FIRE ALARM SYSTEMS) 13125 SW HALL BLVD VALIDITY OF PERMIT SCALE: AS SHOWN N TIGARD, OR 97223 PORTLAND, OR 97224 LAKE OSWEGO, OR 97035 EXPIRES: 07/01 /2022 THEISSIfANCEE APERMIT DAIS 08/19/2019 TIGARD, OR 97223 gASEDONCONSTRUCTION 503.226. 1285 JARED KIMBER, PROJECT MANAGER 503.537.9200 503.718.2439 SHEET TITLE: WWW.CIDAINC.COM 971 .708.7136 dave@mcg design.net DOCUMENTS AND OTHER FIRE AEA�M O JARED.KIMBER@PACNETWORKS.COM DATASHALLNOTPREVEN _ THE CODE OFFICIAL FROM c o v J SUBMITTED FOR PERMIT BY: REOFIEIRRORS OSSC1�•4 N S E -T z ANDREW NELSON, LEA #51 1 0LEA SHEEP NUMBER: EXPIRATION: 10/1 /2020 EAO . 00 0 1SCALE: NTS SHEET 1 OF 7 ` J DESIGNED BY: DAVE MILLER, SET NICET LEVEL.N FRE NARY SYS1FNS • #96867 EXPIRES:07/01/2022 DEVICE LEGEND & BILL OF MATERIAL . DEVICE SYMBOL QTY. MANUFACTURER PART NO. DESCRIPTION COMMMENTS 110 II MN A Swr MRSquD R E 001611Im/6 SIM FACP 1 POTTER SIGNAL AFC-50 FIRE ALARM CONTROL PANEL, ADDRESSABLE P Pci I L1( Project Name:IlmmunologyConsultants Lab4 StandbyHours:124 I NPS 1 POTTER SIGNAL NPS-106 NOTIFICATION POWER SUPPLY, 10 AMPERE, X6 NAC, X1 AUX. Cn • 1he Symbol oI Protection I I Alarm Mi ns:I S I 2 TBD TBD BATTERY, 12V, 7.5AH Z AFC-50 Installed By:I Pacific Networks 1 Batt Efficiency:180% Battery& Voltage Drop Designed By:IMCG DESIGN SERVICES 1 SLC Type:'Class B FAC 1 NAPCO SLE-LTEV-FIRE GSM SOLE-PATH COMMUNICATOR ®prJrrcJ Calculations Date:18/20/2019 I NAC SourceVoltage:I20.4 I 0 18 POTTER SIGNAL PAD100-PD DETECTOR, SMOKE, ADDRESSABLE PHOTO J NAC Circuit Configuration& Voltage Drop (cont'd) Immunology Consultants Laborato 8/20/2019 Model#: AFC-50 Max Panel Current(amps): 5 18 POTTER SIGNAL PAD100-6DB DETECTOR BASE Panel ID:1 I User assumes all responsibility to ensure the quantities and F Location:!Electrical Room I current draw values in this worksheet are accurate prior to 6 POTTER SIGNAL PAD100-PSSA MANUAL PULL STATION, ADDRESSABLE ! submittal. Class: I Class B I Usage:I Notification I Description:I N5 I W CO A0"' 3 POTTER SIGNAL PAD100-0R01 X1 RELAY, X1 INPUT - ADDRESSABLE I/O MODULE I 1 AFC 50 Analog Addressable FACP 0.130 0.130 0.220 0.220 16 SYSTEM SENSOR SRL STROBE, RED, WALLI Cl) Panel Standby: 0.130 Panel Alarm: 0.220 #14 Solid 1 2.5 I 340 1 1.700 I 0.698 1 19.21 I 16 0 _ xC 8 SYSTEM SENSOR SCRL STROBE, RED, CEILING I ®4 22 SYSTEM SENSOR P2RL 2-WIRE, HORN STROBE, RED, WALL . 1 UD-1000 DACT Card 0.016 0.016 0.023 0.023 3 User Defined SRL,15 CD 0.000000 0.000000 0.043000 0.129000 0 O E RA-6075R LCD Annunciator 0.020 0.025 114 13 SYSTEM SENSOR PC2RL 2-WIRE, HORN STROBE, RED, CEILING 3 user Defined P2RL,15CD 0.000000 0.000000 0.054000 0.162000 0 2 User Defined PC2RL,75 CD 0.000000 0.000000 0.143000 0.286000 1; w RA-6500R(F) Flush Mount LCD Annunciator 0.020 0.050 1 User Defined P2RL,75 CD 0.000000 0.000000 0.121000 0.121000 LED-16(F) Flush Mount LED Annunciator 0.025 0.025 Ha 1 SYSTEM SENSOR P2RK 2-WIRE, HORN STROBE, RED, WALL, WP EXTERIOR, LOWER LEVEL mmI e LED-16 LED Annunciator LED Power* 0.015 0.210 User can add devices on the fly 11. 2 SYSTEM SENSOR PC2RK 2-WIRE, HORN STROBE, RED, CEILING, WP FILL LAB, UPPER LEVEL to these bottom devices 5 0• "'' CA-6075 Class A Module 0.012 0.044 PSN-1000(E) Power Expander 0.015 0.015 (No lookup function) I < PAD100-SLCE-127 SLC Expander 0.060 0.060 I w M LL m W NOHMI-SLCE-127** SLC Expander 0.060 0.060 Q z IDC-6 Initating Zone Expander 0.020 0.020 Total Standby: 0.00000 Total Alarm: 0.69800 U IDC-6 Initating Zone Expander Power* 0.030 0.270 0 RLY-5 Relay Expander 0.025 0.035 i a • RLY-5 Relay Expander Power* 0.010 0.135 I. DRV-50 LED Driver Module 0.025 0.025 Note:The cabinet will house two SAH or 18 AH batteries. The charging 1 ClassB I Notification I I N6 1 P 1'()iIJJ� Class: Usage: Description:circuit is ratedfor up to two 55AH batteries. Project Name:'Immunology Consultants Labor Standby Hours:124 I DRV-50 LED Driver Module LED Power* 0.010 0.215 FCB 1000 Fire Communications Bridge 0.025 0.025 P riff • Pie Symbol � I Alarm Mins:15 I 1 J ���-�Lit #14 50l id 1 2.5 1 230 ' 1.150 1 0.925 1 19.34 1 16 FIB 1000 Fiber Interface Board 0.030 0.030 POTTER i WC°,d Poteallort PSN-106 Installed By:'Pacific Networks 1 Batt Efficiency%:180% 1 MC-1000 Multi-Connect Expander 0.010 0.010 Battery& Voltage Drop Designed By:I MCG Designs 1 SPG-1000 Serial Parallel Gateway 0.040 0.040 NAC Circuit Configuration & Voltage Drop Immunology Consultants Lab 8/20/2019 Calculations Date:18/20/2019 I NAC Source Voltage:'20.4 I **REQUIRED IF USING NOHMI PROTOCOL SLC DEVICES1 User Defined SRL,15 CD 0.000000 0.000000 0.043000 0.043000 (Maximum current draw on P-Link limited to 1 Amp) P-LINK Standby: 0.016 P-LINK Alarm: 0.023 I Model#: PSN-106 Max Panel Current(amps): 10 1 User Defined SCRL,15 CD 0.000000 0.000000 0.041000 0.041000 *Only enter quantity if PUNK power is being used to power devices Usage:}Notification 1 Description:IN1 I Panel ID:I NPS1 I 1 User Defined P2RL,75 CD 0.000000 0.000000 0.121000 0.121000 1 ILocation ELECRICAL ROOM I User assumes all responsibility to ensure the quantities and current I 2 User Defined PC2RL,75 CD 0.000000 0.000000 0.143000 0.286000 - AFC/ARC Series draw values in this worksheet are accurate prior to submittal. I 2 User Defined PC2RL,135 CD 0.000000 0.000000 0.217000 0.434000 #14 Solid 1 2.5 1 145 1 0.725 1 0.392 1 20.12 1 16 18 PAD100-PD Analog Photo Smoke 0.000300 0.005400 0.000300 0.0054001 I User can add devices on the fly to these bottom 5 rows - PAD100-PHD Analog Photo Smoke/Heat 0.000300 0.000300 (No lookup function) 1 PSN-106 NAC Power Expander 0.075 0.075 0.075 0.075 PAD100-HD Analog Fixed Temp Heat 0.000300 0.000300 3 User Defined SRL,15 CD 0.0000001 0.000000 0.043000 0.129000 Panel Standby: 0.075 Panel Alarm: 0.075 PAD100-CD Analog Carbon Monoxide Detector 0.000300 0.000300 1 User Defined P2RL,95 CD 0.000000 0.000000 0.142000 0.142000 PAD100-DUCT Addressable Duct Detector 0.000300 0.000300 1 User Defined P2RL,75 CD 0.0000001 0. 000000 0.121000 0.121000 PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000 I Total Standby: 0.00000 Total Alarm: 0.92500 PAD100-DUCTR* Addressable Duct Detector w/Relay 0.000500 0.000500 User can add devices on the fly I 1 Notification N3 Class B 0.00000 0.88600 6 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.001200 0.000200 0.001200 to these bottom 5 rows I 2 Notification N4 Class B 0.00000 115600 PAD100-MIM Micro Input Module 0.000200 0.000200 (No lookup function) i OWNER CONTACT INFO: 3 Notification N5 Class B 0.00000 0.69800P�(u` lb,Sysoao+noowat PAD100-SIM Single Input Module 0.000240 0.000240 I 4 Notification N6 Class B 0.00000 0.92500 IMMUNOLOGY • Total Standby: 0.00000 Total Alarm: 0.39200 PAD100-DIM Dual Input Module 0.000240 0.000240 5 Notification N7 Class B 0.00000 0.89400 NAC Circuit Configuration& Voltaga Drop(cont'd) Immunology Consultants Laborato 8/20/2019 CONSULTANTS PAD100-RM Relay Module 0.000240 0.000240 6 Class B 0.00000 0.00000 LABORATORY 3 PAD100-ORO' One Relay One Input Module 0.000240 0.000720 0.000240 0.000720 I 1 AUX 0.00000 0.00000 I I 7150 SW SAN B U R G PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240 NAC Standby: 0.00000 NAC Alarm: 4.55900 ST TI GAR D O R Usage:lNotification 1 Description:IN2 I Class B Notification IN7I PAD100-ZM* Conventional Zone Module 0.000240 0.000240 Class: I I Usage:) I Description: PAD1oo-NAC* Notification Appliance Circuit 0.000200 0.000200 1 97223 #14 Solid 2.5 1 330 1 1.650 1 1.062 1 18.65 1 16 #14 Solid 1 2.5 1 370 1 1.850 1 0.894 1 18.75 1 16 J PAD100-SM Speaker Module 0.000240 0.000240 Panel Current: 0.07500 0.07500 PAD100-IM Isolator Module 0.000150 0.000150 I NAC Circuit Current: 0.00000 4.55900 PAD100-LED LED Module 0.000240 0.000240 SUBMITTED FOR PERMIT BY: 2 User Defined SRL,15 CD I 0.000000 0.000000 0.043000 0.0860001 Total Standby: 0.075000 Total Alarm: 4.63400 PAD100-LEDK Addressable LED w/Key Switch 0.000200 0.0002001 User Defined P2RL,30 CD I 0.000000 0.000000 0.074000 0.0740001 Standby Hours: 24 Alarm Mins: 5 • ANDRE W PAD100-SB* Addressable Sounder Base 0.000200 0.000200 6 User Defined P2RL,75 CD I 0.000000 0.000000 0.121000 0.7260001AH Required LSO AH Required 0.39 3 User Defined SRL,15 CD 0.0000001 0.000000 0.043000 0.129000 NELSON PAD100-LFSB* Addressable Low Frequency Sounder Base 0.000200 0.000200 1 User Defined IP2RK,75 CD 0.000000 0.000000 0.176000 0.176000 3 User Defined SRL,30CD 0.0000001 0.000000 0.063000 0.189000 � Total Combined Standby&Alarm AmpHours Required: 2.19 1 User Defined SCRL,30 CD 0.000000 0.000000 0.063000 0.063000 LEA #51 10 L EA PAD100-RB* Addressable Relay Base 0.000200 0.000200 I User can add devices on the fly PAD100 IB Addressable Isolator Base 0.000150 0.000150 to these bottom 5 rows Efficiency Factor•. 80% 1 User Defined P2RL,15 CD 0.000000 0.000000 0.054000 0.054000 PFC 6000 Series (No lookup function) Required Battery AmpHours: 2.74 1 User Defined P2RL,30 CD 0.000000 0.000000 0.074000 0.074000 EX P I RAT'0 N • 2 User Defined P2RL,75 CD 0.000000 0.000000 0.121000 0.242000 PSA Analog Photo Smoke 0.000325 0.000325 1 Battery AmpHours Provided: 1 7.51 1 User Defined PC2RL,75 CD 0.0000001 0.000000 0.143000 0.143000 10/ 1 /2020 PSHA Analog Photo Smoke/Heat 0.000325 0.000325 Total Standby: 0.00000 Total Alarm: 1.062001 (No lookup function) RHA Analog Rate of Rise Heat 0.000325 0.000325 FHA Analog Fixed Temp Heat 0.000325 0.000325 @POTTER Total Standby: 0.00000 Total Alarm: 0.89400 DDA Addressable Duct Detector 0.000325 0.000325 CONTRACTOR: P POTTER NAC Circuit Configuration & Volta a DropConsultants Laborato 8 20 2019 _ APS-SA/APS-DA Addressable Pull Station Single/Dual Action 0.000325 0.000325 g Immunology / / MCM Mini Contact Input Module 0.000325 0.000325 I/O Circuit Configuration & Voltage Drop Immunology Consultants Lab 8/20/2019 I I - SCM-4 Single Contact Input Module 0.000325 0.001000 I I7 1 ._ DCM-4 Dual Contact Input Module 0.000325 0.001000 1 I Class: I Class B I Usage:) I Description:I pAC(!F(C1ET{NORKS INC Class: I Class B I Usage:) Notification I Description:I N3 1E;s ictusfoA TRM-4 Twin Relay Output Module 0.000325 0.001000 Usage:1Notification 1 Description:1NPS1 INPUT 1 CIZM-4* Conventional Zone Input Mod 0.000325 0.001000 f * 0.001000 I I I I #14Solid I 2.5 I I 0.000 I 0.000 I 20.40 I 16 16869 SW 65TH AVE. MOM-4* Monitored Output Module 0.000325 1 #14 Solid 1 2.5 1 280 1 1.400 I 0.886 1 19.16 1 16 #373 LAKE OSWEGO, 1 #18 Solid 1 6.4 1 10 1 0.128 1 0.015 1 20.40 1 16 ARB* Detector Base w/Relay 0.000325 0.000325 OR 97035 ASB* Detector Base w/Sounder 0.000325 0.000325 SCI** Short Circuit Isolator(Class A) 0.000325 0.002340 1 User Defined PSN-106,INPUT 0.000000 0.0000001 0.015000 0.015000 ,AIB** Detector Base w/Isolator(Class A) 0.000325 0.002340 5 User Defined SCRL,15 CD 0.000000 0.000000 0.041000 0.205000 PROJECT NAME: IM/IB/SCI/AIB Class B** Current Draw from Install Manual I I I I I I 4 User Defined P2RL,75 CD 0.000000 0.000000 0.121000 0.484000 IMMUNOLOGY 1 1 User Defined P2RL,15 CD 0.000000 0.000000 0.054000 0.054000 SLC Loop Alarm LED Current 0.000000 0.000000 0.036000 0.0360001 1 User Defined PC2RL,75 CD 0.000000 0.000000 0.143000 0.143000 CONSULTANTS * Requires Aux Power(Configure Below) SLC Standby: 0.007320 SLC Alarm: 0.043320 User can add devices on the fly User can add devices on the fly LABORATORY ** See the installation manual for special considerations when installing AIB,SCI to these bottom 5 rows (No lookup function) User can add devices on the fly I to these bottom 5 rows FIRE ALARM DRAWINGS devices on Class B loops. I to these bottom 5 rows I (No lookup function) f (No lookup function) REV: DATE/BY: REV DESCRIPTION: I Total Standby: 0.00000 Total Alarm: 0.01500 1 Q 00/00/00 XXX II I 1 I Total Standby: 0.00000 Total Alarm: 0.00000 TSD XXX 1 Notification N1 0.00000 0.39200 1. Total Standby: 0.00000 Total Alarm: 0.886001 2 Notification N2 0.00000 1.06200 I NAC Standby: 0.00000 NAC Alarm: 1.45400II Usage:lAux Power I Description:LGSM POWERIi 1 lUsage:1 I Description:) I #18 Solid 6.4 1 10 I 0.128 I 0.200 1 20.37 1 16 1 Notification NPS1 INPUT 0.00000 0.01500 Class. 1 Class B I Usage:) Notification I Description:I N4 I X 2 Aux Power GSM POWER 0.07100 0.20000 1/0 Standby: 007100 I/O Alarm: 0.21500 J #14 Solid 1 2.5 1 1 0.000 I 0.000 1 20.40 1 16 = 1 User Defined GSM POWER INPUT. 0.0710001 0.071000 0.200000 0.2000001 #14 Solid 1 2.5 1 320 1 1.600 1 1.156 1 18.55 1 16 I 1 DRAWING INFO: 1 I I DRAWN BY: MTM Panel Current: 0.13000 0.22000 CHECKED BY: DCM w P-Link Current: 0.01600 0.02300 User can add devices on the fly I 1 User Defined SRL,15 CD 0.000000 0.000000 0.043000 0.043000 SCALE: AS SHOWN Nv SIC Device Current: 0.00732 0.04332 to these bottom 5 rows I 1 User Defined SCRL,15 CD 0.000000 0.000000 0.041000 0.0410001 - (f) NAC Circuit Current: 0.00000 1.45400 (No lookup function) 2 User Defined PC2RK,75 CD 0.000000 0.000000 0.176000 0.3520001 DATE: 08/19/2019 1/O Circuit Current: 0.07100 0.215001 1 2 User Defined PC2RL,135 CD 0.000000 0.000000 0.217000 0.4340001 SHEET[� TITLE: Q SLC Loop Type: Class B Total Standby: 0.224320 Total Alarm: 195532 Total Standby: 0.07100 Total Alarm: 0.20000 1 2 User Defined PC2RL,75 CD 0.000000 0.000000 0.143000 0.2860001 I I E A LA IV J 1 User can add devices on the fly I to these bottom 5 rows User can add devices on the fly (Sc (No lookup function) CL Device Addresses Used:27 Standby Hours: 24 Alarm Mins: 5 to these bottom 5 rows I CAL C S OC.. Device Addresses Available:50 AH Required: 5.39 AH Required: 0.17 I (No lookup function) Q Total Combined Standby&Alarm AmpHours Required: 5.56 I L E G E F\ D /3 0 V Z 5 Efficiency Factor: 80% I SHEET NUMBER: Required Battery AmpHours 6.95 Total Standby: 0.00000 Total Alarm: 1.15600 Total Standby: 0.00000 Total Alarm: 0.00000 01 o Battery AmpHours Provided: I 7.51 FAO . I SCALE: SHEET 2 OF 7 , DESIGNED BY: DAVE MILLER, SET NICEF ME N FRE MAN SYSIBIS 196887 WIRES:07/01/2022 flea WASP/IQ.OJ.D fl W *kp ld S. t CO I- L--I Z a I- -J U) W Z I- 0 I cn V >- > >- QC ® O 1' ct JQa o � Ce STORAGE Z ° a 013 Ci _ C z Q 2 m LU U JLei _ v ( )3: N1 2 95C0 JCe. FACP 014* HALL kt,„,„ 014-•I ©p ,OI IL-00t, WOMEN'S -5 I TO FACP 016 ivicA i - (E) ELECTRICA_ p , R11* tL-003 Dpribi.,_t 14/2 TP - FPR i_1 I1500 IL 4 it_ �1 l — OWNER CONTACT INFO: MEN'S p IMMUNOLOGY 11_-007 015 ©p ©p UPE ST2 CONSULTANTS ", II ST2 1L-004 71_-006 LABORATORY OPEN F r-----; III _\ 7150 SW SAN B U RG STORAGE IL , ST TIGARD, OR 017 97223 P 1 L-008 L--__ —J 14/2 TP - FPLIR SUBMITTED FOR PER MI BY: (E) MECHANICAL 1010* ANDREW c'=° r------1 NELSON 7- LAD (E) HALLWAY 012* LEA #51 10 LEA 018 N2-1 EXPIRATION : I-----J E 10/ 1 /2020 ST1 (E) HALLWAY 021* N2-2 \ --:N L 30CD LIFT STORAGE II O JE JC Fw1 Ir 006 1 002* PACIFIC NETWORK INC. Op 71_-009 I SOLUTIONS (E) SERVER _7 11 009* I 16869 SW 65TH AVE. LAB �% , 5 I UKAVt 1 STORAGE #373 LAKE OSWEGO, 019 IFI I D 003* 001* OR 97035 rit_6 PROJECT NAME: IMMUNOLOGY (E) H LLWAYI g CONSULTANTS - ooa* 1 UP _._.) LABORATORY n -ower, INy L FIRE ALARM DRAWINGS v 11_-011 F '-` I'i� { ] Ql- I-17REV: DATE/BY: REV DESCRIPTION: 7n56 (E) HALLWAY '� 00/00/00 XXX 005* _isco TSD XXX J r,CI: EDLR N2-7 II LAB STORAGE 71----Hp: )11 750D (E) STORAGE C • 020 ,O I 1 vvi-• 1004* 1 re) 5Co X BN i ' DRAWING INFO: N DRAWN BY: MTM I -- 1 I _ [XI X CHECKED BY: DCIS Lij SCALE: AS SHOWN N_ DATE: 08/19/2019 (l) SHEET TITLE: a_ LOWER LEU .L Q FLOOR LA\ z 1L LOWE E LEVEL E L F L O O R PLAN SHEET NUMBER: IN) FA 1 . 00 0 a ISCALE: s = SHEET 3 OF 7 • DESIGNED BY: DAVE MILLER, SET CAD NICEI LEVEL N CI Di D.2 D.3 © ® © MEµnRu sn1as J / #96867 EXPIRES: 07/01/2022 R66Iah3WR IYI!WDRi WGll�m/6 We CO 1- VESTIBULE ---...y- 149 iligt is ]I I 1- [ 111[ II - - -_ - - - - - - - I _ ,II. ,l I 0 1 I I I i—� t f t-� -1— 1 I I i I— +I + I �� I —�I r F 1 , I I 1 I 1 1 l 4 t — � � 4 1 1- 1- - I- -k- -1- -I- - rtrt I l r qLD _� -- __ _ 0 0 - - ' rt- _! _ ❑ _ _ _ _ _ _ _ 0 1- I I I I I 1 I I 5. vat STO'AGE MEM 1 - - H Cn 0,ICELIC4 __I _ LAEP`0-5 0 _ I-_ LAB I❑ H \ to o (A 7LLI _ 145 15CD 144 1 150 ! ti I I ♦1 Z 7 ___ I I I I I I o _____ LI -- � I � I I I I ; � N39 „) I ® I ® 1 ° Nse 10; 75cD 1�_I�I 'JI__1 '-_� �__1 1=_� �__I o >. ,_ I I I .�-. I 1 I ,SCD Q r -F'' I`i.-- -u U-- -U U-- li u) I I «r f I I V I I I 1 i,o o ��0 10) I,� D H >. OFFICE OPEN �7 N3 4 HALLWAY HALLWAY 1 ELISA 1 n 0 Co 146 I AGE, 151 1 LAB I I •I I]� r- I I 140 7Tis, -- -- -- 155 -- -- 77 I 1 `III O Ce C i n as 11 H C1 '1:./ q�EN 1 1 di , r 13�....D 11 7177-i �, O- -ICE ,s5CD _J L- I uL. 7 qt: 7-1 J aai_-- I 152_1 ' (� 1 (� 1 iICe 14 sco -- 10} / ` q I 1 ` J 110 C r 181 (81 II I @ Z 0 Ct— I ICe LAB STORAGE i 1__ LAS" I �j 1J, I €1 IL I W 0) 139 141 1 1- ____ 153 i z co HALLWAY n �. - - - - z , I iiict 148 1i 1 PI I h ' I 1 1L"026 1 - rt - - - - 3 — _1E2 \ 1,0:1 `_-' , b I I I I I I I 1 I I I I I it `$ I I I - I I - I I I I I - I I� 1 77 FILLED f Er br__ 7$co -- _ II 0 N45 --1 TISSUE CULTURE ] SII I �� LAB '� `} I �, L 75CD 0) 138 Y I 1�itl�■ D/ ---- -0 N4-8 1 --- rd r- 10) - 15CD �, ' 10, I ❑ L _ ' 0 ' - 1 LAB --- - - -I - - t - ---I- - -i 154 ----1-----1-----1---- _L_ ^ I 1 1 I 1 I 1 1 ', T r 1 1 ! v \� / ' 1 1 1 I I I I I n _ ----T----T----T---- I N}7 I . I I I I I I ' - -1 - - - -- � _ �1 15CD %13 i `� - ❑ - - - - - - - - -- HALLWAY / - I 0 - ' —1 ; I ® ' O Isco 162 I _— 0) �. 1L 0131124 ©P r DN TO FACP �7 --f 1 1 U I 1-I- 111 0 r� 7 10} J NscD 4_J I I I - - -Y - - - - � - 1 I N4 1 1 I II 1 - - 1 J r.1 » ' - - - - rii - - .. ` 1 I ]I I � � -1--� ;ii e--- I ; 1 �i �1 1 1 1 1 n 1 I 1 - nl I_1 I1 STORAGE ' I, -I ' I 1 I 1 , r- 160 JC c,PEN ----T-- --! �ff GAS F Itt 136 I 137 g ;� ,F WM +----� 00000000 1L-0,5 i ,� ���' r---1 - 1 - [ f - 1 I 1 1 I I I I 1 - ----� PACKAGING - I I I I I r 1 I r I �I I I .. 00000000 I I I I 1 1 17 I I f F1 I I l I I II 1 w r I 1 1 1 LAB ,0,� II I II 11 l I I �1 II 5 I 4 I ( 11 I '?:,,,4 _ ` 161 � M�r"41;-1 I I _ ____ - OWNER CONTACT INFO: 1R15C0 D I I I I I I 1 15CD T IMMUNOLOGY :L_I ®(,-;:p — - I I I I ANTIBODY PURITY I I --- -t- -�(E STAIR 2 LAB 1 1 E-i5E, CONSULTANTS © 0, 5T2 --i- -i-- --i-�-i-- 156 I --I-u-i-- i- ----� _ LABORATORY ,LPU,7 1L-0 /0_1_1 ____111 I 1 I 7150 SW SANBURG (0_11__u__11_0 Q- --- - <j),_11_____11_0 --H ST TIGARD OR ...L. t4M 1Y,�!Ns z u1:1:11- LJ 1 I I:1 J u u L , 5cu I1 I - 97223 10 0 ,rico --1--LI--I-- 1--�--I-- --I-----I-- ---1 L--- 11 — I 0 WO f ' I STORAGE0-11- -- -O o-i-- - - I (..)-1----1-0 i �Q �,�� HA LWAY 158 I I 1 1 I 1 �'_° O I SUBMITTED FOR PERMIT BY: ,�� E® --F-N-1-- I - -irt��-- --r-'�-- --r-�-�-- � ANDREW I I I I I 1 i NELSON O `,SCDI--I I I I I I I I I rt--. !� I I 1 1 I ,I r' LEA5110LEA —I— I I r 1 I I I r I I 1 I I e f I I I I I I lin: I RECEPTION ©L025 ' Il _- I _ I U I _ 1 1 ( , I I 1 I ®I I I IEF X11 I 1 102 1 II EXPIRATION : I I �I ISI 1 _ I - I f - I - - I _ I I - I - _ I _ I I _ 1 _ -r-� LAB I I ;0,1 // VESTIBULE 10/ 1 /2020 11 it �\ I El LAB 159 o r� I ,AO N54 I V 1 175C5° - I / CONFER:10ii'L1— 15CD I II I ll lil r 1132 I 1 I I I -1 ,•, 1 CONTRACTOR: 1 I I I ! \\,,......_ 7 L. 1 ., _ 1.7.'''' EOIR HALLWAY E STAIR 1 HALLWAY 131 0p ©P d• ST1 130 Op TL-0T8 iL-0iB E N5AiL-020 1L-0E3 - Nr8 \/ t5CD _ ,0, DRaGI 1 N5-6 v INC. 75DD ' ---- SOLUTIO N TO FACP iC H \\ , � f_ /'� I i 1 DN �Y \A\ II `•`147-12 EDLR UIV J15CD 16869 SW 65TH AVE. LOCKERS 1 ©1 - ( 119) ©P ��ii ��� iCVDCD ;� ' i- 'I.:,"'�;' 1\ 3730R LAKE -1-- C'�, FEREN 0-. N7-9 CON%E 77 N71 I — II1 108 III ]110 D 4�R' D I ;=4,03 �4 a QC _ LAB - - ilr\ CE 11 III 107 106 PROJECT NAME: AB rt HALLWAY 126 _1__ i�son°� �� H�L � - 1 1 1 1 1 1 1 �I I I I IMMUNOLOGY n `� It � CONSULTANTS 126 J CI 127 (❑ 109 I Ill _�- / I I 3000 \ I 7:�.D h 1 ---- '< ',L_ <<-_ ,.../e,„L_ 111 lel �r1_ LABORATORY --- OFFI E / �, II FFI II �/ V t d I J Mi. / 112 ••X I cl I p I4Pill 1 W FIRE ALARM DRAWINGS O,I - UP ® — REV: DATE/BY: REV DESCRIPTION: 5C0 1 J 164 6 A 00/00/00 XXX ! 0 0 10 0 k '� 1 - TSD XXX ST• "� STO'AGE I -4-- 1-- i _ q ❑p77"-- 11H M� J r 1 i- 1J - /c); _1H 115CD0 COPY PRINT R- o2a `� - (.0114 ` �,.� ROOM �• HALLWAY ` .;.:4 X • \ IO Isco / — \ O N78_ .= W `� �J I I . . — IIIQ1111II I I I� jr1 I I ! 1 1 1 W Ir I DRAWING INFO: N OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICEr',ti61 r4 I DRAWN BY: MTfrl 1 T /�� --111, I� 122 121 120 119 118 1 117 1 116 %= // I ` `� CHECKED BY: DCII W l� II ff rr !! 10 f }} ainonnnnnn SCALE: AS SHOWN N ‘,. IO �� i /� i lO {0lO l� {� l ODATE: 08/192019 (0 , I v^ %• r CD - r-- ��-- d0 ---I1--- ‘ F---1 - r--. -- Q -1 '-' 'C SHEET TITLE: I t ) I I (0 1 �� 1 V J / �� pH / i"¢ n a n O I. 7 I. 1 II ll lf__ II I1 :] fi >� ]IIC 711: 11 7FIDE ALARU eL FIRST FLOOD Q P LAN CD FRST FLoo PLA \ SHEET NUMBER: CC aD FA 1 . o 0 SCALE: = 1 SHEET 4 OF 7 l DESIGNED BY: DAVE MILLER, SET NICET LEVEL IV FIRE ALARM SYSTEMS 196867 EXPIRES:07/01/2022 TIM M IOW A'SAW.ION MOULD If!Cd6IW AS ane Cin I- z a I- z IIII- 0 1 u) V >- >- > WCO o � oc Baa oW � zoa Lim LL m W U ::IE 4.5 Z � O 1B \ , \ , \ , \ , \ , \ , \ , \ , \n, \,-,/ \,0,/- O .0 . 0 OWNER CONTACT INFO: /\ /\ IMMUNOLOGY ' 15 CD 30 CD 75 CD 30 CD 30 CD 30 CD 15 CD 30 CD 15 CD 15 CD 75 CD 75 CD CONSULTANTS N7-12 N7-11 N7-10 N7-9 N7-8 N7-7 N7-6 N7-5 N7-4 N7-3 N7-2 N7-1 1 B - EOLR LABORATORY \p/, 0 `0' ‘0/ O O O0 7150 SW SANBURG CABLE LEGEND ST TIGARD, OR 97223 N6-715 D 75 CD 75 N6-6 N6-5D 15 N6-4n 135 N6-3 D 135 N6-2 D 75 N6-1D 1 B DESIGNATION PURPOSE AWG TYPE RATING(FPL,FPLR,FPLP1 DESCRIPTION EOLR A SLC,IDC,PANEL INTERCONNECT 18 SOLID FPLR 2-CONDUCTOR i i i i i gni \„i \r,i i r 0\ 0\ p\ �\ ,o\ �Y\ /Y\ �Y\ p\ U B NAC 14 SOLID FPLR 2-CONDUCTOR SUBMITTED FOR PERMIT BY: T TELCO 22 SOLID N/A N/A 15 CD 15 CD 75 CD 75 CD 75 CD 15 CD 15 CD 15 CD 15 CD ANDREW N5-9 N5-8 N5-7 N5-6 N5-5 N5-4 N5-3 N5-2 N5-1 1 B :ELSON_ EOLR \c' \o' \o' \o !\0/1 o \o' 'c' LX51 10 LEA IRATION: 15 CD 75 CD 75 CD 75 CD 75 CD 135 CD 135 CD 15 CD 1 /2020 N4-8 N4-7 N4-6 N4-5 N4-4 N4-3 N4-2 N4-1 1 B 1 AEOLR ,C, \O \O ,\O \,Oi ,\O :Di ,\O ; ©P ©P ©P ©P ©P ©P ©P ©P ©P ©P — RM� _ FF1L013 1L014 1L015 1L016 1L017 1L018 1L019 1L020 1L020 1L021 1L022 1L023 1L024 1L025 1L026 1L027 15 CD 75 CD 75 CD 15 CD 15 CD 15 CD 15 CD 75 CD 75 CD 75 CD 15 CD COR: N3-11 N3-10 N3-9 N3-8 N3-7 N3-6 N3-5 N3-4 N3-3 N3-2 N3-1 EOLR FIRST FLOOR cI �I �I oI ^ I �i @I vi — = � PACIFIC NETWORKS INC. __ .... ------ ---asxRcas SOLUTIONS- 16869 SW 65TH AVE. FAC #373 LAKE OSWEGO, 1 A OR 97035 +-- 2T PROJECT NAME: @1 @-II @I IMMUNOLOGY NPS1 CONSULTANTS I LABORATORY I FIRE ALARM DRAWINGS B I B 1 +____ 2 T /� 00/00/00 XXX REV: DATE/BY: REV DESCRIPTION: I. ,I \n, , , , , , , , , I 1 A,y, e / \ TSD XXX \ \ 75 CD 75 CD 15 CD 75 CD 75 CD 75 CD 75 CD 75 CD 30 CD 15 CD 1 B FACP _ i Q P 0 P Op H F 1 — F F N2-10 N2-9 N2-8 N2-7 N2-6 N2-5 N2-4 N2-3 N2-2 N2-1 1L007 1L008 1L009 1L010 1L011 1L012 CO EOLR X O 11©1P 1©P 1©P 3 1©P H F H 1©P 75 CD 15 CD 15 CD 95 CD 15 CD 4 1L005 = 1 A N1-5 N1-4 N1-3 N1-2 N1-1 EOLR DRAWING INFO: N DRAWN BY: MTM Ili D O C CHECKED BY: DCM SCALE: AS SHOWN N DATE: 08/19/2019 U) I— LOWER LEVEL SHEET TITLE: 0 ISE. a_ DIAGRAM Q z SHEEP NUMBER: 0 0 ISE iIAGAV FA2 . 00 0 SCALE: 3/32 = 1' SHEET 3 OF 7 DESIGNED BY: POTTER PAD PROTOCOL SLC DEVICE ADDRESSING INFORMATION ° ° FIELD INSTALLER SHALL RECORD THE FOLLOWING DAVE MILLER, SET INFORMATION FOR DEDICATED 120VAC CIRCUIT. DO NOT PSN-106 TERMINATION SCHEDULE I PAD Device Dip Switch Addresses Table(Addresses 1-78) NICETLEVEL N ;L 0 ® o EXCEED 20-AMPERE BREAKER RATING: FRE PANEL: CIRCUIT #: ___—____ COMPONENT TB/TS I Switch N•�mber Switch N imb-r Switch N imber u SYSs Address 1 2 4 8 16 32 64 Address I 2 4 8 16 32 64 Address 1 2 4 8 16 32 64 #98867 TERMINALS CONNECTS TO: 1 , `27 F70'IRfS: 07/01/2022 PANEL LOCATED IN RM., RM. #: 1 2 28 5453 e 2 i To AC ,, AC PWR H/N/G 120VAC BY E.C. J 3 29 • 55 716610fA YTMf MI I� DREOaE1�A6610! a PROVIDE A PERMANENT LABEL WITH THE ABOVE INFORMATION AC TRBL & SEE CONNECTION ON DETAIL 5 30 31 • = 56 • CO ON THE FRONT OF THE FACP AND/OR CONTROL UNIT. MAIN TRBL 6 32 58M BOARD BATT -/+ CONNECT BATTERIES, OBSERVE 7 33 • 59 • : — — POLARITY 8 34 60 Z ® a t7v, OCOMBO Bili uw ��99990� O B R D 9 • 35 • II 61 • 0 0 0 iplE � FACTORY INSTALLED1 Q p ❑ ❑ __a�aa��®5, CONN. 1 D 36 62 11 • : 37 63 • : i— __ illiii;lio52 BRD FACTORY INSTALLED 12 38 64= 0 J CONN. 13 ! 39 • 65 • ii 1[434 11 14 40 66 ,[®]; [ill 9 Iii iii 53 NAC 1 —/+ TO N 3-1 • 3 2 C W ❑ o ■1!■�.. ❑ ❑ ❑ E01� 3J I 15 41 • 67 ❑ o :107=[r71 E D D =aallh611S. I 1642 6x Z MANili BOARD I/O BOARD NAC2 -/+ TO N 4-1 — '-- I oeliigh �7 * 60 0 9 I CO 9 • I/ 45 • 71 U n — — — � I I o aiggli�� NAC3 -/± TO N5-1 20 46 72 o Q BATTERIES TO BE INSTALLED HERE. 21 • 47 • 73 DO NOT MAKE CONDUIT PENETRATIONS ON BOTTOM EDGE OF All X69:91 o a ENCLOSURE. ° ■ — 22 I 48 • 74 O _ NAC4 —/+ TO N6-1 23 • 3 49 • 75 • 1 I • - 24 50 76 .,.,.,., „ ., r,!r r� r� rr rrr� >� >� r� I 0 BOARD 0 ce . .-, �,® ® coo ®' o1 `I :: c / I F c 1® ® QQ ii1u�_u uu.. uuu u ... — 25 • S1 • 77 • J a ,�..,�� k� l" �V V, p N�, NAc 2 N 4 5 1745 e + z ® NAC 5 /+ TO N 7— 1 �/ ZiQ No c o,o -awn+ - + I - + - + I - +I - + 1 + - + I EOE I - + Eat - + Ea 26 4t— 52 !_ 78 4t O m.n. NAC6 -/+ NOT USED NOTE: Each Box With Circle (•) Indicates Dip Switch is "ON", Each Empty Box Indicates "OFF" z • I PAD Device Dip Switch Addresses Table(Addresses 79- 127) Switch Setting Examples 14 n Ce DC PWR —/+ TO DOOR HOLDERS Switch Number S-vitcl- Number .1 W Address 1 2 4 8 16 32 64 Address 1 2 4 8 16 32 64 re REF. EOL CONNECT EOLR IF OTHER 79 •'5 106 • & 11 Q THAN 5. 1 K OHM • = 2 ;;111;3264 dumIN 1 +/—/EOL FROM FACP N1 SEE g2 107108 13264 CONNECTION TO TR BL RELAYS3 1 83_• 109 • Al] dip switches are set to the N 2 +/--/EOL NOT USED 84 HO default"OFF"position. CD85 • 111 • (Device Not Addressed) 86 � 112 87 • 113 • I 2 4 8 ;1113!12.; 88 114 oeoeOF 89 • 115 90 116 Dip switches set for address 42. 91 • 117 • Switches#2,8&32 arc"ON". (2+8+32=42) 92 118 IP - J'ahla�®6 93 • 119 • �O _ Power1 2 4 S 35 3264 Supp ® The Symbol�l�IC7teCtlOPI Gne6ON alrUrgiz•O .w pri s«•sln 95 • 120 W 31 • �e�e���OFF 96 122 Dip switches set for address 90. 97 • 123 ! Switches#2,8, 16&64 are"ON". 124 (2+8+ 16+64-90) 9998 • : 125 • 100126 �: 101 127 PO I I ER SIGNAL PSN- 106 POWER SUPPLY 102 103 OWNER CONTACT INFO: SCALE: NOT TO SCALE PSN-106 104 0 I M MU N O LOGY CONSULTANTS DETAIL GENERAL NOTES: EOLR: 5.1 K OHM LABORATORY FIELD INSTALLER SHALL RECORD THE FOLLOWING WIRING IS SHOWN DIAGRAMMATICALLY. ALL WIRING IS TO BE CONTAINED T T 1),,,7—EOLR: #3005013 7150 SW SANBURG INFORMATION FOR DEDICATED 120VAC CIRCUIT. DO NOT WITHIN THE BOX. THE LENGTH OF EACH CONDUCTOR SHALL EXTEND 6" ST TIGARD, OR r; ° ° EXCEED 20-AMPERE BREAKER RATING: AFC-50 TERMINATION SCHEDULE BEYOND THE OPENING OF THE BOX PER THE NEC. CLASS B, MULTIPLE _ C CONTACT INPUT 97223 I 111 �11 ' '; - or-E1 ® PANEL: CIRCUIT #: _ COMPONENT TB TS TERMINALS CONNECTS TO: USE MANUFACTURERS FURNISHED COVERPLATE AND MARK AS NOTEDTRO / EOLR: 5.1K OHM 11 I ! I I 0�� ❑ PANEL LOCATED IN RM., RM. #: / HERE WITH PERMANENT LABEL ON COVER. .4 BLE (pe PART #3005013 I ❑ �,� ,� ❑ AC AC PWR H N G 120VAC BY E.C. CLASS E ALARM/ MOUNTING OPTIONS: SUBMITTED FOR PERMIT BY: CO o,�II + J�I I I ❑ CONNECTION / / SEE MANUAL PULL STATION FOR IN/OUT CABLE LABELING REQUIREMENTS. TROUBLE INPUT PROVIDE A PERMANENT LABEL WITH THE ABOVE INFORMATION ANDREW ❑ ❑ fT■ II , I®)��� ❑ SEMI-FLUSH: UL LISTED ❑ I,�„� ON THE FRONT OF THE FACP AND/OR CONTROL UNIT. BATTERY CONNECT BATTERIES, OBSERVE NOTE: WHERE WIRING BETWEEN MODULE AND MONITORED DEVICE IS 2 " DEEP 2-GANG BOX NELSON 7117141)W - ❑ BATT -/+ EXPOSED, AND LESS THAN 10' AFF, PROVIDE RACEWAY AS REQUIRED BY ' ❑ """` °"" [LOUT D — u - B W o 0 0 o CONNECTION POLARITY 14" DEEP, 4" SQ. BOX 0 0 ❑ o o _ E^,�{���� �Y NEC FOR THE ENVIRONMENT TO PROTECT WIRING. WHERE WIRING LEA #51 10 LEA 0 C1 TROUBLE NC/COM/NO NOT USED EXTENDS BEYOND BUILDING ENVELOPE, PROVIDE SURGE PROTECTION. TO NEXT DEVICE -\ 0 ] I IIII II� � I _ �s� 0 TCP/IP ❑ SEE ASSOCIATED SURGE SUPPRESSOR DETAIL. ® EXPIRATION : [ ' 0 D SUPERVISORY NC/COM/NO NOT USED 0 a10/ 1 /2020 I IRP I w w, .�, .�, I RELAY �—� + _ . _ + _ . _ + . .I�.� IDETAIL FLAG NOTES: IIMMtl —. D TERMINATIONS . ❑ ❑ ❑aur■ o o a>1. USE RELAY/INPUT MODULE WHERE DESIGNATED ON FLOOR PLANS. _ :` - r r I ' DEARTH FAULT o I I ALARM NC/COM/NO NOT USED 'AI ,�r,c - -440 o CALMED fl t . << 2 , 3 , o D 2. INPUT IS RATED FOR CONTACT DEVICE ONLY; 1 CLASS B CIRCUITS. c ;, L,� 7 _lia LI D ❑ L ; 5 ; ' 6 : ❑ ❑ I/O 1 —/+ TO NPS1 INPUT (NAC) SEE CLASS B, MULTIPLE INPUT DIAGRAM FOR WIRING CONFIGURATION. FROM PREVIOUS-' © BOJ o CONTRACTOR: D DEVICE OR FACP 1 7 1 8 9 3. WHEN RELAY IS USED FOR DRY CONTACT INTERFACE, I.E. AN INPUT opo„�a ❑ I/O 2 -/+ TO GSM TROUBLE (IDC) TO ASSOCIATED SYSTEM, MODULE SHALL BE BE LOCATED WITHIN 3' P"°'°°°"° j D ACK I ( f o l ( � ❑ CD l I ) l OF THAT INPUT. I� 0 C PI D o I/O 0 0 o o NAC 1 -/+ TO N1 -1 INC. 4. WHEN USED FOR HVAC SHUTDOWN; BREAK 24VAC USING N.C. RELAY. LABEL SOE UT ONS I BATTERIES TO BE INSTALLED HERE. C P5 o I 1 I I NAC NAC 2 —/+ TO N2-1 16869 SW 65TH AVE. DO NOT MAKE CONDUIT PENETRATIONS ON BOTTOM EDGE OF P LINK ENCLOSURE. ` 00 .:�� j� :,)Q L'^, 'F '�1"''�''�' _ #373 LAKE OSWEGO, EIXIID : :� o 000�c;, cccccINI.,.1.. SLC POTTER SIGNAL PAD100—OROI BABY p I N� �o " N� I I ,�o 1,1 ��o*J ri -I KAP} g ��+0 3 OR 97035 P-LINK NOT USED SCALE: NOT TO SCALE PAD100-0R01 A PROJECT NAME: B • UD-100o: SLC -/+ SEE RISER DIAGRAM IMMUNOLOGY CONSULTANTS Q o1=11=1 o TCP/IP RJ-45 N/A PROGRAMMING ONLY LABORATORY • I I MOUNTS BEHIND DISPLAY LINE 1 RJ- 1 1 TO LINE 1 ON GSM FIRE ALARM DRAWINGS �3 ON MAIN CONTROL BOARD; o� OMWE ur,ra,E a�aE - AND CONNECTS USING p I„{I)� 0„' � 1 iI = III AFC-50 LINE 2 RJ-11 TO LINE 2 ON GSM �� �� �' RIBBON CABLE THAT IS M �I 0 REV: DATE/BY: REV DESCRIPTION: �' '""" I * (I . l I R^°' 1C0A '' PROVIDED FROM UD-1000 CONNECTION TO P5 MAIN �I� [f� �Rs�ll� (� 00/D0/00 xxx 1, aluWW - P1 TO P5 ON MAIN UD-1000 P1 RIBBON CONN. CONTROL BOARD .:. TSD XXX "p` 1 mu [ JIM Wu) CONTROL. 6999�9I1 AAAA® P—LINK —/+/A/B NOT USED o USE LINE 1 FOR P-LINK PII'I I 11 , — I ] INTERFACE TO GSM DIP SWITCHES SET TO ADDRESS 001 x � �DIIII�II��1 O [oJ, I - ADDRESS SWS. SINCL -ACTIO” COMMUNICATOR. REMOVE (� o �� v1 RSION s❑owN. _ �I®� SEE INSTALLATION 01 _ RJ-45 CONNECTOR ON MANUAL FOR GSM END, AND CONNECT DOUBLE-ACTION. 1 )I X m NI i GREEN CONDUCTOR TO TI, I _ - AD RED (') _ o RN ON GSM OTERM NAL OR TO P POTTER_____„12 BACKPLATE, REAR 0 IP10 0 n' o',„ a BLOCK. 1 .. DRAWING INFO: DRAWN BY: MTM DISABLE LINE 2 IN FRONT VIEW BLK - DROGRAM. )} # - # # # # - # # CHECKED BY: DCM W FROM FACP OR PREVIOUS DEVICE _ SCALE: AS SHOWN N ( 7 RED (+} DATE: 08/19/2019 LABEL CABLE WITH PREVIOUS DEVICE SHEET TTfLE: I- ADDRESS; IF FROM FACP OR NPS/SLC I nA •� n O C LABEL WITH "SOURCE" I I E A EV I JWIRE NUT TO PIGTAILS PROVIDED • - DETAILS # 1 z POTTER SIGNAL AFC-50 2� POTTER SIGNAL PAD100—PSSA SHEET NUMBER: SCALE: NOT TO SCALE AFC50 J SCALE: NOT TO SCALE PAD100PSS EA 3 . O 0 O I INTSLE: ' t SHEET 5 OF 7 DESIGNED BY: DAVE MILLER, SET MET LEVEL N FRE ALARM SY51E11S 06867 EXPRES: 07/01/2022 1I6 is mar A.6Pie,Or MOO tr IE Cd1511160 b SEM 1- Z a I- -I Cl) W Z I o , co V >- >- >- ce co C7 0 2 o toc Jaa o Ce J Z0Q ili I 1 I ¢ noeW o o Z Yellow Green AC 0 Troule ON LED 0 2 11 SLE-LTEVI-CFBPS PC Board LED � 1 All connections are power limited except AC Note:Connect IN2 to a J panel output used for a. moo IRL Mains and battery terminals identifying Telco line cut(this Power Supply is the DACT interconnect i wiring to the radio). ' (SLE-ULPS-R) re J Shunt!P1 on 0 bottom 2 pins Relay con- Q o w facts rated z ,—(21— max max 30VDC, Ogg 0.5A LI CO j _ U, illii'11 nn B " 0 12VDC z 0° LOCAL 0 n` output is DOWNLOADpower limited ?♦ p• 1 2 3 4 5 e 7 e TELCO TELCO y e0 ,I 12 ,3 0 0 0 U IT) I-I I-I LI IH ;-7 I.I y-I SECONDARY PRIMARY LI -I I.y (_) EGNI] Is 25 21 AC IN +12y_ NiIRED SLC < I Fuses I l I 1N2 II IN3 I IN4 INS ,� -8- G NIG .� t =rHERNE— r 1 121114151 1617 o 17 3 I 6 s 6 I re - .5A Fuse —our Battery n Note: Maintain OWNER CONTACT INFO: w© minimum 1/4" IMMUNOLOGY separation of © U battery leads from CONSULTANTS 16.5VAC all other wiring. LABORATORY 117%. Class 7150 SW SANBURG O ST TIGARD, OR Gqk ® Note:Maintain minimum 1/4"separation 97223 LABEL INCOMING E•""Gro°�I of all wiring in this compartment from the CABLE/WIRING WITH Chassis Mounted 16.5VAC 12OVA Transformer yellow wires of the transformer. PREVIOUS DEVICE DETAIL FLAG NOTES: SUBMITTED FOR PERMIT BY: ADDRESSES �(+) . - � ` 1 . CONNECT THE STARLINK RADIO TO THE CONTROL PANEL OUTPUT FOR TELCO TROUBLE (THIS IS THE DACT INTERCONNECT ANDREW jfi�,�;• \\V. ,; jfl/�• ,.. WIRING TO THE RADIO). REMEMBER TO PROGRAM THE STARLINK COMMUNICATOR MODULE TO REPORT THIS IN2 TELCO am ., .®. /���,� ;� �/.��� TROUBLE AND FOR LINE CUT (FOLK) TO THE CENTRAL STATION. IN ADDITION, PROVIDE 1 O OHM EOLR AT THE CONTROL NELSON SLC •,,/�1�1► # - # # # # - # # # / BOXES FOR MOUNTING BASES: PANEL TELCO TROUBLE OUTPUT. MONITOR AS SUPERVISORY FOR GSM TROUBLE. LEA #J I OLEA 2. USE FACP EOLR AT END OF CIRCUIT FOR TROUBLE RELAY (N.0.) AND WIRE TO I/O #2 ON FACP AS IDC. REMOVE JUMPER TO FACP/SLC V voir- © _I I +I�' SINGLE-GANGJ2 SO THAT CONTACT IS "DRY".� DOUBLE- AN EXPIRATION . DOUBLE-GANG 3. IN1 NOT SUPERVISED DO NOT USE. /�4):, /�� 3 " OCTAGON . ;•,- 4. LICENSED ELECTRICIAN REQUIRED TO WIRE THE 120VAC CONNECTIONS TO THE TRANSFORMER IN ACCORDANCE WITH N.E.C. 10/ 1 /2020 INDICATES THE SLC # -# # # LABEL INCOMIN \*,,.'" %��j `'Q� '~ 4" SQUARE AND LOCAL CODE REQUIREMENTS. REFER TO SECTION "SUPPLYING POWER". CABLE/WIRE AT FIRST C } LABEL OUTGOING �� 5. ROUTE 1 20VAC ONLY THROUGH THE TRANSFORMER COMPARTMENT KNOCKOUTS. "LOOP" (L) NUMBER USED _ -- WHEN MOUNTING IN ACOUSTICAL ON SYSTEM. NO NUMBER DEVICE WITH "SLC" TO CABLE/WIRING WITH 6. KEEP ALL NON—POWER LIMITED WIRING SEPARATE FROM ALL POWER—LIMITED WIRING INSIDE THE HOUSING BY 1/4". IN SIGNIFY THAT IT GOES NEXT DEVICE ADDRESS. TILE CEILING (ATC}, PROVIDE TILE ADDITION, MAINTAIN A MINIMUM 1/4" SEPARATION OF ALL PRIMARY WIRING IN THE TRANSFORMER COMPARTMENT FROM THE INDICATED HERE IMPLIES BRIDGE, SEISMIC CABLE AND ALL CONTRACTOR: THAT IT IS A SINGLE LOOP TO THE FACP YELLOW SECONDARY WIRES OF THE TRANSFORMER. TERMINALS. COMPONENTS NECESSARY FOR A 7. STARLINK MODULE MUST BE CONFIGURED TO TRIGGER PGM3 ON ANY TROUBLE. SYSTEM. CODE COMPLIANT INSTALLATION. 8. OUT1 N/C (TERMINAL 21) OF THE STARLINK MODULE MUST BE WIRED TO THE TROUBLE INPUT (TERMINAL 5) OF THE POWER ADDRESS OF DEVICE WHEN MORE THAN # — O O 1 ,‘..-- # - # # # SUPPLY. ON SLC CIRCUIT ONE SLC IS USED, LABEL EACH DEVICE WITH ADD THE SLC NUMBER INC TO BEGINNING OF THE MACHINE PRINTED, SELF SOLUTIONS LABEL. ADHERED LABEL WITH DEVICE 16869 SW 65TH AVE. ADDRESS. LABEL SHOULD #373 LAKE OSWEGO, POTTER SIGNAL PAD100-DB6 DETECTOR BASE POSVIEWONAON FLOORSTANDING NAPCO STARLINK GSM COMMUNICATOR W/PS OR 97035 SCALE: NOT TO SCALE PAD100DB6 SCALE: NOT TO SCALE STARLINK GS PROJECT NAME: IMMUNOLOGY � � AUDIO MODE _-- CONSULTANTS , -I , LABORATORY SEMI-FLUSH INSTALLATION SHALL USE ANY OF WP K-BACKBUX '-- ,,,, I SELECT�T: FIRE ALARM DRAWINGS THE FOLLOWING: W/MOUNTING PLATE ,14.4,1.SINGLE-GANG BOX �o O )11,11 REV: DATE/BY: REV DESCRIPTION: DOUBLE-GANG BOX l _ 00 OD o0. / / xxx 4 SQ. BOX e 1 ' 1CANDELA � ,�y { TSD XXX 4" OCTAGON _ 1 C .; ySLIDE —�_-�, �co I ► a � IFOR SURFACE MOUNTING, USE THE BOX /! _ t ., '� _ oH[]RN/STRIJBE � R ^T FURNISHED WITH THE "K" VERSION OF _ I l'O.Fla'' ' �'���10 0 �• ySETTINGS �� ` PRODUCT. Z _ _ 5 WALL MOUNT DEVICES SHOWN. SEE `� ro 1: P � i ���� �� SPECIFIC INSTALLATION SHEET FOR lI p ASSEMBLY, EXPLIJDEB VIEW FOR CEILING MOUNTED DEVICES, SEE � = WITH CEILING MOUNTED DEVICES. CO ■w A <:. 1 DETAIL FLAG NOTES: X --,M.0:%%.. ® LABEL WITH NEXT LABEL 0 ``= =r=�`- ® _ E►n-.� C k 1. LABEL EACH CABLE AT FIRST DEVICE WITH CIRCUIT THAT CORRESPONDS TO FACP, INSTALLATION MANUAL. ENSURE PROPER 1 . PREVIOUS DEVI j # I I I I ' ' '�" ' e NAC POWER SUPPLY, EVAC OR AMP CIRCUIT CONNECTION. I = INSTALLATION TECHNIQUES INCLUDING TILE 4` DEVICE ADDRESS ADDRESS I I BRIDGE IN ACOUSTICAL TYLE CEILINGS." 47 w" �`��` 'I- 4� 2. ON NEW CONSTUCTION, INSTALL SINGLE—GANG BOX IN EXTERIOR WALL, FLUSH WITH DRAWING INFO: N 47 O `i>�"'� � �� �? �� FACE OF SIDING. PROVIDE NEOPRENE GASKET AND SECURE K—BACKBOX TO NAC# NAC#—## NAC#—## �, NAC#—## TO NEXT DEVICE OR © 4Ml . SINGLE—GANG USING SCREW HOLES PROVIDED. CCHECKED YBY: DCM FROM FACP OR NA� - �f PLACE EOLR ACROSS = 3. LABEL EACH DEVICE WITH MACHINE PRINTED, SELF ADHERED LABEL WITH DEVICE N POWER SUPPLY • � [1 TERMINALS 1 & 3 r. ., SCALE: AS SHOWN FJ © NAC#-## ADDRESS. INDICATE ON LAST DEVICE EOLR IN ADDITION TO ADDRESS. LABELDATE: 08/19/2019 n ( SHOULD BE VIEWABLE FROM STANDING POSITION ON FLOOR/GROUND.ei,„ � � Fe Ce�I (( > /�� 1 LABEL EACH DEVICE WITH MACHINE PRINTED, SELF ADHERED 4. USE MOUNTING TABS TO SECURE HORN/STROBE K-BACKBOX TO WALL, UNLESS SHEET T{TLE: �ti _= i*� Q ` 1�-`�—�'lJi ' J LABEL WITH DEVICE ADDRESS. INDICATE ON LAST DEVICE BUILDING CAN BE IRREPARABLY DAMAGED BY SUCH ACTION FRE ALAS V o ---',.,1 -7,___:— O � �__ "EOLR" IN ADDITION TO ADDRESS. LABEL SHOULD BE 5. PROVIDE MANUFACTURER'S WP PLUG W/O-RING FOR EACH CONDUIT OUTLET NOW 0_ �'"� ` - —/ VIEWABLE FROM STANDING POSITION ON FLOOR. 3 ETAI LS #2 USED. NAC#-## NAC# ## z SYSTEM SENSOR 2-WIRE HORN/STROBE, LOW FREQ. SNDR, & STROBE MOUNTING DETAIL SYSTEM SENSOR WP HORN/STROBE (K BACKBOX) z 0 SHEET NUMBER: E SCALE: NOT TO SCALE SS-2WHS SCALE: NOT TO SCALE SS-2WHS FA 3 . 0 1 O INTSLE: SHEET 6 OF 7