Loading...
Report fpS2020 -4U6'477 730 Gu/ /Ju/2 41 WYATT FIRE PROTECTION , INC. 9095 S.W. Burnham Tigard, OR 97223 APR 7 2020 CITY OFT1GA€3D PBC 198- 1340 SPEC VAC 7340 SW DURHAM RD PORTLAND, OR 97224 c),, pPROF . 5 GNEF s/0 7 12089PE /ORE ON �' i O� �� MAY20, /XI N C O Apr 2, 2020 EXPIRES: 12/31/2020 FIRE PROTECTION EQUIPMENT SUBMITTAL Worldwide wwwtyco-fire.com tIIC1. I Contacts Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE - - The TYCO Series TY-FRB Sprinklers Description described herein must be installed �=a , , and maintained in compliance with The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the • Upright (TY313) and Pendent (TY323) applicable standards of the National Sprinklers described in this data sheet Fire Protection Association,in addition are quick response,standard coverage, to the standards of any other authori- € g,'� decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do sow sprinklers designed for use in light or may impair the performance of these ordinary hazard,commercial occupan- devices. cies such as banks, hotels, and shop- The owner is responsible for main- ping malls. taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- applicable, is intended for use in areas for or product manufacturer with any with a finished ceiling. This recessed questions. 3, pendent sprinkler uses one of the following: Sprinkler • A two-piece Style 15 Recessed Identification . .� Escutcheon with recessed adjust- mentuh t e in. siti mm) from Number (SIN) the flush pendent position. j,,:' • A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in.NPT Escutcheon with recessed adjust- TY323. . . .Pendent 5.6K,1/2 in.NPT ment up to 1/2 in. (12,7 mm) from the flush pendent position. Technical The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Intermediate level versions of Series Refer to Table A the rated temperature is reached, the TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently to shatter the Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to psi(17.2 bar)" activate and water to flow. 250 kler guards and shields are described P in Technical Data Sheet TFP780. -The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). • Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psi'/=(80,6 LPM/barn=) The TYCO Series TY-FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Always refer to Technical Data Finishes Sprinkler: the standard installation rules Sheet TFP700 for the "INSTALLER Sprinkler:Refer to Table B recognized by the applicable Listing or WARNING"that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and corn- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations. • to operate in a fire situation or cause Bulb Glass it to operate prematurely. Compression Screw Bronze Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* I,'WTfilE rZl by lyr_ 5 ��� 7/16" Y �_ -I (11,1 mm)NAL g�� } I�fc 4 NOMINAL 2" ] ( h MAKE-IN (50,8 mm) 1 \ // �- 2 17• 2" I) CV 1-3/8" 3 , ft (50,8 mm) 1 (34,9 mm) 1* ! WRENCH 1 7 I / FLATS 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Co Installation Step 2. With pipe-thread sealant applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the END"A") dance with this section. sprinkler fitting using only the W-Type General Instructions 6 Sprinkler Wrench(Figure 2).With ref- erenceFIGURE 2 Do not install any bulb-type sprin- to Figure 1,apply the W-Type 6 W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH a loss of liquid from the bulb.With the Torque sprinklers 7 to 14 lb-ft (9,5 to sprinkler held horizontally, a small air 19,0 N•m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in aye co in. (2,4 mm)for the 286°F(141°C) dance with the following instructions. temperature ratings. Ali `� I Step A. After installing the Style 15 A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the should be obtained by applying a sprinkler threads,and with pipe-thread minimum to maximum torque of 7 to sealant applied to the pipe threads, 14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairmentPUSH Step B. Tighten the sprinkler into the IN TO ENSURE WRENCH of the sprinkler. sprinkler fitting using only the W-Type N T Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WITH SPRINKLER eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N m). W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and The Series TY-FRB Upright and finishing, slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. pendent position. Install upright sprin- klers in the upright position. TFP172 Page 3 of 4 Care and 2-7/8" DIA. (73,0 mm) • Maintenance 2-1,a" DIA. The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. ` \ — , i FLUSH Before closing a fire protection system 3/8±5/16" main control valve for maintenance (9,5±7,9 mm) A.21 „� 'r 7 work on the fire protection system } / that it controls, obtain permission to �_r _ shut down the affected fire protection MOUNTING 1/8" systems from the proper authorities SURFACE _ (3,2 mm) and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TY-FRB PLATE 3/4"(19,1 mm) Absence of the outer piece of an • escutcheon, which is used to cover FIGURE 4 a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only 2-7/8" DIA. cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4" DIA. vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm) corrosion must be replaced. + m FLUSH • Automatic sprinklers must never be r —1 I r ,7 painted, plated, coated, or other- 1: wise altered after leaving the factory. } / �l� 1/8" t Modified sprinklers must be replaced. MOUNTING (3,2mm) Sprinklers that have been exposed to SURFACE corrosive products of combustion, but have not operated,should be replaced if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Limited Recessed Escutcheon be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has Warrant eon with(specify')finish, P/N(specify') lost liquid from its bulb. (Ref. Installs- Y Specify: Style 20 Recessed Escutch- tion Section.) For warranty terms and conditions,visit eon with(specify*)finish,P/N(specify') The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices Sprinkler Wrench in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order,indicate having jurisdiction. Contact the install- the full product name and Part Number ing contractor or product manufacturer (P/N). with any questions. Sprinkler Assemblies with NPT - Automatic sprinkler systems are rec- Thread Connections ommended to be inspected, tested, Specify: Series TY-FRB Upright or and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN tion Service in accordance with local (specify), K=5.6, Quick Response, requirements and/or national codes. (specify) temperature rating, (specify) finish, P/N(specify,refer to Table A). TFP172 Page 4 of 4 SPRINKLER FINISH (See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER° FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY313) and 175°F(79°C) Yellow 1,2,3,4,5,6 • PENDENT(TY323) 200°F(93°C) Green 5.6 286°F(141°C) Blue 1/2 in.NPT 135°F(57°C) Orange RECESSED PENDENT 155°F(68°C) Red • (TY323) 175°F(79°C) Yellow 1,2,3,4 Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc..for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact Johnson Controls.Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable. c. Frame and Deflector only,Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/Na 77 — XXX — X — XXX • SIN SPRINKLER TEMPERATURE FINISH RATINGS 370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C) POLYESTER Notes: SIGNAL WHITE(RAL9003) a. Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C) 77-370-4-175-I 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYESTER 9 CHROME PLATED 286 286°F(141°C) Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPR/NKLERS PART NUMBER SELECTION 1400 Pennbrook Parkway,Lansdale,PA 19446I Telephone+1-215-362-0700 OM/ �� e 2010 Johnson Controls.All rightsreeerved.All specificaeons and ether Information shown were current es of document revision date and are subject to change without notice. Johnson ♦ NATIONAL FIRE PROTECTION ASSOCIATION and NFPAere teglstered trademarks of National Fire Protection Aasoclatl°n'. Controls TEFLON Is a n9Mtered vad k ama,of DuPont Eddyth read 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE SIZE(in) WEIGHT(lbs/ft) I.D. (in) BUNDLE SIZE 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE SIZE(in) SCHEDULE 40 EDDYTHREAD 40 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems 1819 Clarkson Road For additional information, C U` OS �� � Chesterfield,MO 63017 contact your salesperson today at BULL MOOIP TI WI=COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED FAX:(636)537-2645 in the USA,or from Canada • www.bullmoosetube.com call(800)882-4666 41> A Lffig0 company e-mail:sales ibullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 Ductile Iron Threaded Fittings 4'°. ,.....„.....,„,,, $,ors.., ,,,,,„„ ,,,, } ,n . ..,..,7 ,� ao r+ "+� ..^tie..., .. iiiiii S fit.r, .. 6 E 4p' [1 E` # 4 S B . + �� c� � c tt � re ,fit :�3" , SMITH COOPEH® INTERNATIONAL Ductile Iron Threaded Fittings Specifications • '(' branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP C CO US • Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings 20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 i Ductile Iron Fittings- Class 300 UL/FM 1 tn-,1..1-.°t pLu, I C ® US 441101°- APPROVED - Fig. 35E 3-90°Elbow LISTED A Size A Packing Weight Part Number in in Inner Master lb 1/2 35E 3004 1.13 100 200 0.2 a 3/4 35E 3006 1.31 70 140 0.3 A 1 35L 3010 1.50 40 80 0.5 li��� 1-1/4 35E 3012 1.75 25 50 0.8 1 1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 - 2-1/2 35E 3024 2.70 1 4 8 3.2 Fig. 35RE3- 90°Reducing Elbow • B Size Part Number A B Packing Weight in in in Inner Master lb 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 -r - 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 358E3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 t67 30 60 0.7 1-1/2 x 1/2 3513E3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1,80 20 40 0-8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1,0 2 x 1/2 35RE3020004 1,60 1,97 18 36 1.0 - 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 350E3020010 1.73 2.02 '6 32 12 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 3514E3020014 2.07 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2.1/2 x 2 358E3024020 2.39 7.60 6 12 2.5 Fig. 35F 3-45°Elbow Size A Packing Weight Part Number in in Inner Master lb 1 r2 35F 3004 0.88 150 300 0 2 3/4 35F 3006 0.98 80 160 0 3 AM= 1 35F 3010 1.13 40 80 0 5 1-1/4 35F 3012 1.29 25 5041117110.71-1/2 35f 3014 1 44 20 400..A 2 35F 3020 1.69 10 20 1.6 21/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing Weight __ Part Number in in Inner Master lb �iI��L I A 351 3004 1 13 80 160 0.3 314 35T 3006 1.31 30 60 0.5 1 351 3010 1 50 25 50 �� � 1-1/4 35T 3012 1.75 10 20 10 7 � t� .1 , k A > 1-1/2 35T3014 '_94 10 70 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 302.4 2-70 4 8 4.3 111 5Mi•1'H-COOPER IV'1'8 RNAT.1O\ 11." • TO1,I,FREE 1-800-766-0076 • F:3X(3231 890-4436 • vVWvV..mithcuuper.cum I ucti e ron fittings- ass I I I ' c@us APPROVED Fig. 35RT3-Reducing Tee LISTED Size Part Number A B C Packing Weight in in in in Inner Master lb I C 3/4x 1/2 35R13006004 1.20 1.20 1.22 60 120 0.4 _ 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 a _ -- -- 1 x 1!2 x 1 35RT3010004010 1.50 1.36 1.50 30 6C 0.6 1 x 3/4 35R13010006 1.38 1.38 1.45 25 50 0.6 *1(< , 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35913012004 1,34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-114 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4x 1 350130'.2010 1.58 1.58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1,34 1.26 1.53 25 50 0.7 /-1/4 x 1 x 3/4 351113012010006 1 45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1 1/4 x 1 x 1 1/4 3511-13012010012 1.75 1.69 175 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1 1/2 x 1/2x 1 1/4 3591-3014004012 1-81 1.56 1-88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 3511 13014006 1.52 1.52 1-75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 - 1-1/2x3!4x 1-1/2 35913014006014 1.94 1.75 1.94 18 36 1-2 1-1/2x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2x 1 x 1/2 351113014010004 1,44 1.25 1 69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1-0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 12 1-1/2 x 1 x 1-1/2 35RT3014010014 1_94 1 80 1 94 12 24 1.3 1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 1-'/2x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 '.66 16 32 0.9 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 1 1/2 x 1-1/1 x 1 351113014012010 1.65 1 58 1 80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 I-1/2 x 1-61 x 1-62 35RT3011012014 1 94 1 88 1.94 14 28 1.4 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 2 x 3/4 359 13020006 1-60 1.60 1 97 10 20 1.6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35373020010020 2-25 2.02 225 8 16 1.9 2x1-1/4 35RT3020012 1.90 1,90 2.10 8 16 1.9 2 x 1 1/4 x 2 351113320612020 225 2.10 225 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35913020014004 1.49 1 41 1.86 10 20 1.3 2 x 1-1/2 x 3/4 3511113020014006 1.60 1.52 1.97 10 20 1.4 2x 1 1/2x 1 35R13020014010 1.73 1-65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2x1-1/2x11/2 35RT3020014014 2.02 1-94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee Size A B C Packing Weight I.■iL Part Number C in in in in Inner Master lb 3/4x 1 351313006010 1 45 1_45 1.37 30 60 0.6 1 x 1-1/4 35873010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35E313010011 1-80 1.80 1.65 15 30 1.0 < A )1 B 3 1-1/4 x 1 x 1-1/2 351373012010014 1.88 1.80 1.82 15 30 1.2 1-1/4 x 1-1/2 35B13012014 1.88 1-88 1.82 15 30 1.3 1-114 x 2 358-13012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1 1/4 x 2 351373014012020 2-16 2.10 202 10 20 1.8 1-1/2 x 2 358T3014020 2.16 2.16 2.02 8 16 1.8 S\it'l lI-COOPER INTERN.A"1'll)NAl-,' • TOI.1. 1-'I l I 1-800-766-0076 • 1\X 13231890-4456 • vVnwsmithcouper.com 112 Ductile Iron Fittings-Class 300 UL/FM c ® us APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED ._ a -': Size Part Number A Packing Weight in n Inner Master lb _ __ __ '12 35CP3004 1.38 200 400 0,1 3/4 35CP3006 1.63 100 200 0.2 - 1 35083010 1 75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35C83014 2.19 25 50 0./ 2 35CP3020 2.62 15 30 1,2 2-'/2 35083024 3.00 9 '8 27 Fig. 35RC3 -Hex Reducing Coupling Size Part Number A Packing Weight B in in Inner Master lb 1 x 1/2 35403010001 1.69 BC 160 0.3 1 x 3/4 35RC3010006 1.69 60 120 0.4 _�'. 1-1/4 x 3/4 35803012006 2.06 40 80 0.6 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight n in Inner Master lb B 1 x 1/2 35`433010004 1.06 180 360 0.2 1i 1 x 3/4 35HB3010006 1.06 180 360 0.1 ' il.A 1 1/4x1 35HB3012010 1.19 9C 180 0.2 1-1/2 x 1 35H83014010 '025 75 150 0.4 1-1/2x11/4 35HB3014012 I 25 75 150 0-3 ''' 2x1 35H83020010 1.38 40 80 0.6 _1- 2x_1-114 35HB3020012 1.38 40 80 0.6 . Viz" 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 Fig. 35SP3 -Square Head Plug Size A Packing Weight ' in Part Number in Inner Master lb 1/2 35SP3004 0.94 600 1200 0.07 IA 3/4 355P3006 1.12 350 700 0.1 1 35583010 '25 200 400 0.1 1-'/4 35SP3012 1.37 100 200 0.3 '--!.' , 35S03011 1-44 80 160 0.4 2 1 35SP3020 1.50 '45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size Part Number A Packing Weight _e1 limo in in Inner Master lb 1 35U 3010 2.19 20 40 1.0 r,. 1-1/4111111 7 35U 3012 2.50 15 30 2 _ 1-1/2 350 3014 2.62 10 20 1.7 Illi____ Jilill 2 35U 3020 3.12 6 12 2.4 illii • 113 SNIITII-COOPER INTERN AI'ION 1, • TOI,1, FREE I-800-766-0075 • I-AX(3231 890-4456 • vVNrw.smithcoopcccum -- ,'1 Ductile Iron Fittings- Class 300 UL/FM 1 QUALITY?LIE i C ® US 444> APPROVED Fig. 35X 3- Cross LISTED E )11 A ' Size A Packing Weight Illill/' in in Inner Master lb A Part Number 1 35X 3010 1.50 20 40 0.9 \ I 1-1/4 35X 3012 1.75 12 24 1.4 I MI IA 1 1/2 35X 3014 1.94 8 16 1.8 2 35X 3020 2.25 6 12 2.8 jail B B Fig. 35RX3-Reducing Cross ` '` ' Size A B Packing Weight Part Number i iiiitA in in in Inner , Master lb 1/4 x 1 35RX3012010 1.87 1.58 15 30 L2 ` im - - L--�i 1-1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 A 2 x 1 35RX3020010 2.02 1.73 8 16 2-0 nrilEir Fig. 35C 3- Cap Size Part Number A Packing Weight • in in Inner Master lb IA 1/2 35C 3004 0.87 300 600 0.1 3/4 35C 3006 0.97 200 400 0.1 I 35C 3010 1.'6 110 220 0.2 1-1/4 35C 3012 1.28 70 140 0.4 ' 1-1/2 350 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2.-112 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp Size A Packing Weight Part A n Numberin Inner Master lb 318 35803003 0.75 100 200 0.3 1/2 358C3004 0.75 80 160 0.5 S\1I 1,11-0001'FR 1\A F,RN.CFION.IL" • T0I.I, FREE I-800-766-0076 • LAX 13211 890-4456 • wwn.smithcooper.com 114 S"CARBON. STEEL IPEBCUT PRODUCTS 10.52 ry yam+ {,Y � co. ® LPCB'; FireLock6 'b.11 ie T 4918/27 SEEEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating y,3/4,and 1'715, 20 and 25mm outlets for directly connecting sprinklers,drop nipples, sprigs,gauges,drains and other outlet products.Available for 11/4 through 76.1 mm/32 to 76.1mm piping systems, Style 441 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068 kPa and VdS rated up to 16bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Gasket: • Grade"E"EPDM-Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Botts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel (North America, Latin America,Asia Pacific) • Red enamel(Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY C 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 1c au!1C° IPS CARBON STEEL PIPE • HOLE CUT PRODUCTS 10.52 - FireLock® tiet-T STYLE 922 DIMENSIONS Nominal Size Hole Approx. inches/mm Diameter Dimensions-inches/millimeters Weight Each . 'oEnf 3c 2'.4;41 * .,;-. !KaY .. 1'2 '16 13/16 1.30 110 387 2.56 1.0 ��� t I 3? X IS - 30 2 33.0 <l6 S 27.9 98 3 65 0 0.45 ��� �. T ��� y., 13/16 1.28 1.83 110 3.87 2.56 1.1 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 ,a�, ,niyy toil/ 1 13/16 1.52 2.18 110 3.87 2.56 1.2 �� adl __ 25 1 30.2 38.6 55.4 279 983 65.0 054 1 Y2 12 , 1 3/16 142 1.95 1,22 4.08 2.56 1.2 40 X 15 30,2 36,1 49.5 31.0 103.6 65.0 0.54 4 'i 13/16 140 1.95 1.22 4.08 2.56 1.2 20 1 30.2 356 49.5 31-0 1036 65.0 0.54 1 1 13/16 1.64 2.30 1.22 4.08 2.56 1.3 25 30 2 41.7 58 4 31.0 103.6 65.0 0.59 2 Va 1 13/16 1,66 2.19 146 4.60 2.56 1 3 50 x15 j 30.2 42.2 55.6 37,1 116.8 65.0 0.59 3/41 13/16 1.64 2.19 146 460 256 14 20 --a 302 417 55.6 371 116.8 65.0 064 1 I 1 3/16 1.88 2.54 1.46 4.60 2.56 1.5 25 j 30.2 47.8 64.5 37.1 116.8 65.0 0.68 21/2 Ya I 13/16 1.91 2.44 171 540 2.56 1.6 65 X 15 30.2 48.5 620 434 1372 650 0.73 / 1 13/16 1.89 2.44 1.71 5.40 2.56 1.6 20 I 30.2 480 620 434 1372 65.0 0.73 1 I 13/16 2.13 2.79 1./1 5.40 256 1,6 25 30.2 54.1 70.9 43.4 137.2 65.0 0.73 • 76.1 mm X V 2 i 13/16 191 44 1.71 5.50 2.56 1.6 15 1 30.2 485 62 0 43.4 139.7 65.0 0.73 1 3/. 1 13/16 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 1 13/16 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 1397 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. "Center of run to engaged pipe end for NPT threads(dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. iCt`auluC IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 FireLock® Outlet-T STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Sire+Outlet Size 213,Section 16)(C=120)`,FT Inches/mm et/meters 1'/a X 1 8.5 32 25 2.6 1'/¢ X 1 8.5 40 25.�._. 2.6 2 X 1 85 50 25 I 2.6 2 1 1 ' 8.5 65 X 25 2.6 76.1 mm X 1 —',.,. 85 25 26 *Hazen-Williams coefficient of friction is 120 www.victaulic.com •Cta ul1C VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. F, P.RODUCTs Fire I,. . ' .. Litiet :< STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete • installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 uctaulic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. Pipe Hangers Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig. B317ONF) QTOLCO Fig. 200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) 6 lJ us Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig. B317ONFC) LISTED Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm) pipe Material: Steel, Pre-Galvanized to G90 specifications ifMk Function: For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features: - • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe ,` types and protect CPVC plastic pipe from abrasion. Captured design �+ keeps adjusting nut from separating with hanger. Hanger is easily a installed around pipe. A r= • For hanger with non-captured nut order Fig. 200S. • (21/2" (65mm)thru 8" (2oomml) Spring tension on nut holds it securely in ;" - , hanger before installation.Adjusting nut is easily removed. S Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm1) Fq n /4 in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved(FM) (3/4" (20mm)thru 8" 1200mm)l. Fig.2001to 200-2 Fig.20o 21/7m200.4 Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69 &SP-58, Type 10. 1.* Maximum Temperature: 650°F(343°C) Finish: Pre-Galvanized. Stainless Steel 4* materials will be supplied with (2) hex nuts ` .r in place of a knurl nut. �, f Order By: Figure number and pipe size Designed to meet or exceed requirements of o, FM DS 2-0. ti,, 03 a. Fig.200 a Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 A Part No. in. (mm) in. (mml in. Imml lbs. (kg) -line 200-1/2 1/2" (15) 3/8"-16 31/8' (79.4) 25/8" (66.7) 11 (5.0) 200-3/4 2/4" (20) 3/8"-16 31/8' (79.4) 21/2" 163.5) 11 15.0) 200-1 1" (25) 3/8"-16 33/8' (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27f8" 173.0) 13 (5.9) 200-11p 11/2" (40) 3/8"-16 37/6" (98.4) 27/8" (73.0) 14 (6.4) 200-2 2" (50) 3/t-16 41/2" (114.3) 3" (76.3) 15 16.9) 200-21/2 21/2" (65) 3f1C-16 55/8" (142.9) 41/8 (104.7) 27 (12.3) -- 200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/2" (90) 3/8"-16 73/8" (187.31 51/4" (133.3) 34 (15.6) 200-4 4" 1100) 3/8"-16 73/8" (187.31 5" (127.0) 35 (16.0) 200-5 5" (125) 1/2%13 91/8" (231.8) 61/4" (158.71 66 (30.21 200-6 6" 1150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" 1200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 21 B-Line by 1E,S Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103) r / . B3205L - Threaded Rod (right& left hand threads) n Size Range: 3/8"-16 thru 3"-4 rod Specify Length Material: Steel • Function: Recommended for use as a hanger support in hanger assemblies. TLV��l Rod is threaded on both ends with right hand threads of the length shown.Also available with left and right hand threads-specify Fig. B3205L when ordering. 0" Thread size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load . Thread Size Thread length TL 650°F(343°C) 750°F(399'0) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205.3/4 x'L' 3/a"-16 21/2" (63.5) 730 (3.25) 572 (2.54) 83205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 8/e"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) 83205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) 83205-7/8 x'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) 83205-1 x'1.' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) ' 03205-1118 x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) B3205-11/4 x'L' 11/4'7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' 11/2' 6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) 83205-2 x'L' 2%41/2 8" (203.2) 24600 (109.42) 19625 (87.29) B3205-21/4 x'1' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) 03205-21/2 x'1.' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) 83205.23/4 x'1' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) 03205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100) Fig. 99 -All Threaded Rod Cut To Length 1l1� Size Range: /s"-16 thru 1 /2"-6 rod in 120"(3.05m)lengths or cut to length : ' Material: Steel Ti Lbs. (kg) N Maximum Temperature: 750°F(399°C) ,,.-- 0 Finish: Plain.Contact B-Line for alternative finishes and materials. d Order By: Part number, rod diameter and finish hs u ' Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) ATR 1/4"X 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/8"x 120 99-3/8"x length 16 730 (3,24) 29 (13.15) ATR 1/2"x 120 99-112"x length 13 1350 (6.00) 53 (24.04) ' ATR 3/4"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/8"x 120 99-3/4"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102,06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 6 Line Pipe Hangers&Supports 236 Revised 4/28/2014 by E 1 " .T"tY VERTICAL MOUNT SAMMYS SAMMYS° for Wood Not less than wood Fbonng 2'nominal width Product Features (1 4 •No pre-drilling required. Not less than •Quick to install using the Sammy 3'nominal Nut Driver with an 18V cordless thickness(24TP) (depth or sue drill/driver. A of vertical member) c •Saves time from traditional Double Sheeaock methods. 1 For vertical use- Ceiling install in carder of beer face. •Reduces installation cost. Minimum 7 embedment into base ` .- material for NFPA 13 compliance. Composite I Truss •Made in the U.S.A. � Consult truss manufacturer for recommended installation point. € • 'Pre nAng may be required for GST G 25-380.Tool evadable on page f0 a 1 I t4 Rod Part Screw Ultimate UL Test FM Test Box Case Approvals Model Size Number Descriptions Pullout(lbs) Load(ibs) Load(Ibs) Qty Qty 210(7/16"OSB) 1/4" 8002957 GST 100 1/4 x 1• - 25 125 o + 670(3/4"Ply) 1/4" 8003957 GST 200 1/4x 2" 1760 (Fir) 25 125 1/4' 8004957 GST 300 1144 3' 2060(Fir) 25 125 3/8" 8006957 GST 75 114 x 3/4" 564 (3/4"Ply) 25 125 '4.7;1'.. 4 1 t' 3/8" 8007957 GST 10 114 x 1" 210(7/16"0SB) 300 25 125 670(3/4'Ply) - i '' .' 318" 8008957 GST 20 1/4 x 2" 1760 (Fir) 850 1475 25 125 3i8 8068925 GST 20-SS 1/4 x7 1760(Fir) 850 25 125 - ' 3/8" 8009925 GST 25-380 318 x 2-112" 2113 (Fir) 1500 25 125 •� Nut 3/8" 8010957 GST 30 1/4 x 3" 2060(Fir) 1500 1475 25 125 Nu Black t Driver 3/8' 8069925 GOT 30-SS 1!4 x 3" 2060(Fir) 25 125 Part#8113910 3/8" 6011925 GST 40 1/4 x 4" 2180(Fir) 25 125 3/8" 8012925 GST 60 1/4 x 6" 2230 (Fir) 25 125 12" 8013925 GST2 1/4x2' 1760(Fir) 25 125 112" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125 1/2" 8015925 GST3 1/4 x3' 2275(Fir) 25 125 — 112" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125 1/2" 8017925 GST 6 1/4 x 6' 2230(Fir) 25 125 #14 SW Red _ Nut Driver Part#8114910 SAMMY Swivel Head° for Wood Product Features •Eliminates distortion of threaded rod. •Saves time from traditional methods. •Accommodates up to 3%"x 12 pitch roof. •Reduces installation cost. •Allows 17'deflection from vertical. •Made in the U.S.A. Rod Part Screw Ultimate UL Test FM Test Min Box Case Approvals Model Size Number Descriptions Pullout(Ibs) Load(Ibs) Load(Ibs) Thickness Qty Qty 6t. .e.D' 3/8" 8139957 SH-GST 20 1/4 x 2" 1257(Fit) 1050 1475 25 125 125 a•Q 318" 8141957 SH-GST 30 114 x 3" 1720(Fir) 1500 1475 25 125 .. #14 Black Nut Driver SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910 contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for,installations. For the most up to date information,visit www.sammysuperscrew.com 4 \ l2" s VicFlex M Sprinkler Fittings J4tau1 C' Series AH2-300 Braided Flexible Hose Assemblies 10.84 • Brackets: Style AB1 for suspended and hard-lid ceilings, allows installation before ceiling tiles in place Style AB1 Adjustable for suspended and hard-lid ceilings, allows installation before ceiling tiles in place (regionally available) Style AB2 for hard-lid ceilings, allows for vertical sprinkler Approvals/Listings: adjustment Style AB4 for hard-lid ceilings with hat furring channel ® grid systems, allows for vertical sprinkler adjustment Style AB7 for suspended and hard-lid ceilings Style AB7 Adjustable for suspended and hard-lid ceilings (regionally available) Product Description: Style AB9 for hard-lid ceilings with hat furring channel VicFlex sprinkler fittings provide sprinkler installation grid systems on suspended ceiling grids, wood or metal stud/joist or Style AB10 for Armstrong®TechZone- ceilings hat furring channel hard-lid ceilings utilizing a flexible, stainless steel hose and steel bracket assembly. Refer to the Installation Manual for all applicable ASTM ceiling material and installation standards. The system requires no welding for assembly. System Components • Hose: Series AH2-300 1" Nominal ID Braided Hose Hose lengths: 31, 36, 48, 60, 72"/90, 914, 1220, 1525, 1830mm. Note: length includes branch-line nipple and 5.757140mm straight reducer. • Sprinkler Reducers: l/" and 3/4"/15 and 20 mm sprinkler connections and 5.75'7140mm, 9"/230mm, 137330mm straight lengths and short, long 90° elbows. Note: The short 90° elbow is typically used with concealed sprinklers while the long 90°elbow is typically used in the installation of recessed pendent sprinklers. • Branch Connections: 1"/25mm NPT or BSPT branch line nipples for attaching to rigid pipe. 3/4720mm NPT or BSPT available for VdS. Job/Owner Engineer System No. l Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 10.84 7491 Rev.A Updated 11/2013 ©2013 Victaulic Company.All rights reserved. 1 .ctaul.C' victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Technical Specifications: Material Specifications: Maximum Working Temperature: 225°F/107°C • Series AH2-300 Maximum Working Pressure: Flexible Hose: Type 304 Stainless Steel • 300 psi/2068 kPa Collar/Weld Fitting: Type 304 Stainless Steel Connections: Gasket Seal: Victaulic Grade EV EPDM To branch line (inlet) via 1"/25.4 mm NPT or BSPT male thread Isolation Ring: Nylon OR Nut and Nipple: Carbon Steel, Zinc-Plated To branch line (inlet) via 3/4720 mm BSPT male thread (VdS only) Reducers (1/2 or 3/4'): Carbon Steel, Zinc-Plated To sprinkler head (outlet) via 1/2" or 3/4"/15 mm or 20 mm • Brackets: Carbon Steel, Zinc-Plated NPT or BSPT female thread Minimum Bend Radius of Flexible Hose: • 8"/200 mm Maximum Number of Bends per Flexible Drop: See friction loss charts below Maximum K-Factor of Sprinkler to be Connected to Reducer: • K8.0/11,5 (S.I.) (1/2/15mm reducer) • K14.0/20,2 (S.I.) (3/4"/20mm reducer) 10.84 7491 Rev.A Updated 11/2013 ©2013 Victaulic Company.All rights reserved. victaulic.com 2 .ctaul.c' victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Series AH2-300 Braided Hose Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2"/51mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 1 6 i 7 8 9 10 11 12 Hose Size i0 Bends Bends Bends Bends Bends Bends i Bends j Bends a Bends Bends Bends Bends Bends • inches inches feet/meters _ L_ 1 5.0/1.5 8.5/2.6 11.0/3.4 13.0/4.0 16.0/4.9 N.AN.A • N.A . N.A N.A N.A N.A 31 a " 6.5/2.0 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 N.A N.A ! NA N.A N.A N.A N.A N.A 1/2"._ 10.5/3.2, 13.5/4.1 16.0/4.9 18.0/5.5 : 19.0/5.8 21.0/6.4 N.A N.A N.A_L, N.A N.A N.A N.A '/a" 12.0/3.7 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N.A N.A ! _N.A N.A N.A N.A Vz' 11.5/3.5 15.5/4.7 17.0/5.2 19.5/5.9 20.0/6.1 .21.0/6.4 22.0/6.7 28.0/85132.0/9.8 NA N.A NA N.A 48 s/a^ 13.0/4.0 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9i 27.0/8.2 30.0/91 37.0/11.3 N.A N.A N.A N.A 60 3 15 5/4.7 21.5/6.6 •24.0/7.3 27.0/8.2 28.5/8.7 • 30.0/9.1 i /a .31.0/9.4 37.0/11 3 42.0/12 8 44.0/13.4 46.0/14.0 N.A N.A 16 0/4 9 23.0/7 0 24.0/7 3 28.0/8.5 29.5/9.0 30.5/9.3 131.0/9.4 38.0/1 1 6 42.0/12 8 44.0/13.4 46.0/14.0 N.A NA • 1i 72 Y 28.5/8.7 30.0/9.1 32.0/98 i36.5/11.1 37.5/11.4 405/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9 52.0/15.8 54 0/16 5 55.0/16.8 3/4 24.0/7.3 • 32.0/9 8;32.5/9.9,35.0/10.7 35.5/10.8,40.0/12.3 40.5/12.3.41.0/12.5 46.0/14.0 50.0/15.2 51.0/15.5 52 0/15.8 53.0/16.2 Note:Values for use wish 5.75"straight reducers. How to use this Design Guide: 1 For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends. In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. 2 It is possible that the actual installed condition of some of the flexble drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. 10.84 7491 Rev.A Updated 11/2013 ®2013 Victaulic Company.All rights reserved. victaulic.com 3 rgtaulra' victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 rM Friction Loss Data - Series AH2-300 Series AH2-300 Braided Hose for use with Style AB1, • • AB1 Adj.,AB2,AB4,AB7,AB7 Adj.,AB9,AB10 VicFlex Brackets. • Equivalent Length of Maximum Number Length of Stainless Steel i Sprinkler Outlet 1733.7mm of 90°Bends at 87200mm • Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius • inches Imperial/S.I. inches/type feet/meters i 1/2"/Straiqbt 235/71 • 31 5.6/8.1 y /90°Elbow 23/7.0 'I 2 _. 36 5.6/8.1 / /Straight 27.8/8.5 2 1/2790'Elbow 27.7/8.4 - — �- �ght '/�%90traighw 382/11.4 48 5.6/8.1 3 'h/Straight 42.4/12.9 - - 60 5.6/8.1 — --- -- 1 4 '/�/90°Elbow 43/13.1 1/275traight 46.6/14.2 72 5.6/8.1 I - - -1 4 ', I 1/2790"Elbow 485/14.7 3a... _..._ ..... 31 8.0/11.5 3 "/Straight 20J/6.3 2 '/90'Elbow 20.5/6.2 /4'/Stralght 3a 25.0/7.6 36 8.0/11.5 I .....--._.. _- 2 3i 3/a'/90'Elbow 24.6/7.5 ' 48 8.0/115 3 /Straight 35.5/10.8 3 /90°Elbow _ 34.7/10.6 3/4"/Straight 39.6/12.1 60 8.0/11.5 34/90 Elbow 40.1/12.2 4 //a"/Straight 43.5/13.2 72 8.0/11.5 4 — 90"Elbow ....._______--45.2/13.7 ____ 31 11.2/16.1 _. 1/4"/Straight _ 17.8/5.4 2 4----E 3/4"/9o-Elbow 18/5.5 3/4"/Strai ht 22.2/6.7 l 36 11.2/16.1 --- g_ - 2 3k/Straight 32.9/10.0 3/a/90°Elbow 22.1/6 7 48 11.2/16.1 _--W/90"Elbow 32.1/9.8 3 3/4"/Straight 36.8/11.2 60 11.2/16.1 3/4'790°Elbow 37.1/11.3 4 fa/Straight 40.5/12.3 72 11.2/16.1 3/a"/90"Elbow 41.9/12.7 4 .........._ ......_ ..___._____ _. 3/a ._.._4..___ a"/Straight 14.9/45 2 _._._.._ 34 90"Elbow_ - 15.5/4 72 31 14.0/20.2 ,/ 36 14.0/20.2 4� /Straight 19.4/5.9 1— 2 3 "/90"Elbow- 19.6/5.9 3/it"/Straight 30.3/9.2 48 14.0/200.2 3/a"/90°Elbow -- -- 29.5/8.9 •• 3 3/a'/Straight 33.9/10.3 60 14.0/20.2 -- - - - 4 72 14.0/20.2 '"/St Elbow 34.1/10 4 3 " /44 3/4"/Straight 37.5/11 4 , 4 3/d'/90 Elbow 38.6/11.7 FM Notes: Series AH2-300 Braided Flexible Hoses have been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13, 13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. Differences in equivalent lengths are due to varying test methods,per FM 1637.Refer to these standards for additional information regarding friction loss test methods. EXAMPLE A 48-inch Series AH2-300 hose installed with two 30°bends and two 90°bends at a 7-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. 10.84 7491 Rev.A Updated 11/2013 0 2013 Victaulic Company.All rights reserved. victaulic.com 4 rctaulrc' victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Product Details-Series AH2-300 Braided Hose Item Description 1 Flexible Hose 2 Isolation Ring 3 Gasket 4 Nut ! q p 5 Branch Line Nipple • I— 6 Braid 1-II umlululum!iul��I 7 1 Collar/Weld Fitting I 8 Hose Length Dimensions Hose Length A B oll inches inches inches 31 25.25 31 36 31.25 36 48 42.25 48 60 T 54.25 60 72 66.25 72 Standard C11ill11IIIl1 — 5.75'7140 mm straight reducer Optional ��IiIIIiI iII ilIlilli'lililliliMI' 9.0"/229 mm straight reducer 1111i li 11 lil llls i 11!T )] I,uinilrullu 13.0"/330 mm straight reducer 2.25"/ 57mm 2.25"/ • 111% —M 57 mm 1' 6.30"/ ti 480"/ 161 mm 123mm Short 90°elbow reducer Long 90°elbow reducer Note:The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. 10.84 7491 Rev.A Updated 11/2013 ®2013 Victaulic Company.All rights reserved. victaulic.com 5 Nictaulic victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 VicFlex Brackets Style AB1 ID • Suspended Ceilings lid • • Hard-Lid Ceilingsill �l Item Description 1 24"/610mm or48"/1219mm Square Bar* r e 2 Patented 1-Bee Center Bracket 3 End Bracket �� 0 Style AB1 Adjustable p h� A 1. • Suspended Ceilings y "I • Hard-Lid Ceilings411) 00.10. I:I Y Y� i Item Description _ 1 k 1 700mm or 1400mm Square Bar" OD 2 ' Patented 1-Bee`®Center Bracket 3 End Bracket(adjustable) .�y O Style AB2 © i t) • Hard-Lid Ceilings l.024 a Item Description 1 24"/610mm or 48'/1219mm Square Bar" I/ 2 Patent-Pending Adjustable Center bracket i i 3 End Bracket(adjustable) _ __ Note: s/u or 4mm hex key required for adjustment „ir' �� 1 1. 1 Style AB4 � � • Hard-Lid Ceilings with Hat furring channel 1 grid system Item . .. Description ..... _� I / I. 1 24"/610mmor48'/1219mm Square Bar* *, 2 Patent-Pendin Adjustable Center bracket �� .1\1.4p,..,,.:„ 3 Adjustable End Bracket for Hat Furring Channel Note: 1/a or 4mm hex key required for adjustment ;ir Il O %-il- 1\ li 11 0> Ni 10.84 7491 Rev.A Updated 11/2013 ©2013 Victaulic Company.All rights reserved. victaulic.com 6 rotauIC victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Style AB7 © 6 • Suspended Ceilings . • Hard-Lid Ceilings (FM Only) Item li Description A I 1 24"/610mm or 48/1219mm Square Bar* atented 1-Bee' ter et i 3 i End Bracket(optional adjustable ergs onBrrek regional availability) I -/ • Both sins P9 Y 1 i`^` es FM/VdS approved. 0 Style AB7 Adjustable a .i . • Suspended Ceilings • Hard-Lid Ceilings lifilitoobb. Item Description A 1 700mm or 1400mm Square Bar" 2 Patented 1-Bee'Center Bracket ;, � 3 End Bracket(adjustable) y 0 *Both sizes FM/VdS approved. r iiir e Style AB9 ' • Hard-Lid ceilings with Hat furring channel 1,e grid system it Item Description \rl I'k 1 247610mm or48"/1219mm Square Bar 2 Patented 1-Bee'®Center Bracket _ 3 Adjustable End Bracket for Hat Furring Channel A a• r`e' Style AB1O �� 1.of• Suspended ceilings . • Armstrong®TechZone"" :A Item Description ._ 1 4/100mm 6"/152mm Square Bar* 14- 2 Patented 1-Bee`"Center Bracket i� IJIi I - L3 End Bracket ._ _ 1 Jo, 10.84 7491 Rev.A Updated 11/2013 ©2013 Victaulic Company.All rights reserved. victaulic.com 7 Nictaulic victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Series AH2-300 Braided Hose Assembly Suspended Ceiling Grid with Recessed Sprinkler -Clearances above ceiling tile at various center-line bend radii I � Hose Clearance Chart Inches/ • Dimension mm Minimum Bend Radius"R" 8/200 ?/ see left Minimum"A" 16.75/425 I` 1 i f See Char Ind , • nl 95 mm t diriL *it V2707 3/4'/19mm Max. Recess Suspended Ceiling Grid with 90°Elbow (Long) ; A 11I�11� Hose Clearance Chart See Chart Inches/ 1.1 Dimension mm •, v� 8 I A Min. 200 i 3.75"/ I I 95 mm Note: Style AB1 and Series AH2-300 figures shown. Variations of ceiling grids, sprinkler heads, brackets and hoses are permitted but may result in clearance le differences from the figures above. -a"�`i1„ v �A 10.84 7491 Rev.A Updated 11/2013 ®2013 Victaulic Company.All rights reserved. victaulic.com 8 rctaulrc' victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 SERIES A112-300 Braided Hose Assembly Suspended Ceiling Grid with Hat Furring Channel Hose Clearance Chart Inches/ j " Dimension mm " Minimum Bend Radius"R" 8/200 R Chart Minimum"A" 16.3/14.5 1 \ . a Irm-, See Chart r -I ' N V2708'"/12.7mm Max. Recess ded Cei SuspenHose clealrag e c Grid with 90°Elbow (Short) 0 111111 h It, nc Inches/Dimensionmm I I 'r-P III ' - _ A Min. /,� �.. r�1 PP�rP .11 Note: Style AB1 and Series AH2-300 figures shown. ,,.I„ ;„ r 1� Variations of ceiling grids, sprinkler heads, brackets and ` hoses are permitted but may result in clearance .. , i — differences from the figures above. V3802 /712.7mm Max. Recess • 10.84 7491 Rev.A Updated 11/2013 ®2013 Victaulic Company.All nghts reserved. victaulic.com 9 Nictaulic victaulic.com I VicFlex Sprinkler Fittings I AH2-300 I Publication 10.84 Flexible Hose In-Plane Bend Characteristics ONE BEND TWO BENDS THREE BENDS • 2X 2X Min.mum Minimum Minimum 1 _ bend radius bend radius bend radius , \1 Minimum bend radius I OR OR i \ Minimum Minimum bend radius oend radius Minimum Minimum bend radius bend radius Minimum bend radius Note:For out of plane(three-dimensional)bends.care must be taken to avoid imparting torsional stress on the hose- . A WARNING • It is the responsibility of the system designer to verify suitability of Type 304/304L stainless steel flexible hose for use with the intended fluid media. • The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on Type 304/304L stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. Installation Note • Reference should always be made to the for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with even shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and VicFlex are registered trademarks of Victaulic Company. 10.84 7491 Rev.A Updated 11/2013 ©2013 Victaulic Company.All rights reserved. victaulic.com 10 Iictaulid