Plans • GENERAL CODES NOTES AERIAL VIEW CODES AND STANDARDS 1. ALL WORK SHALL COMPLY WITH 2017 OREGON ELECTRIC CODE(OEC),2017 OREGON ` ; * - t RESIDENTIAL SPECIALTY CODE,AND ALL STATE AND LOCAL BUILDING AND ELECTRICAL „.e "" ,. BLUE CODES. e "' RAVEN 2. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. SITE NOTES!OSHA REGULATION ` I '- , . : '' 1403 N RESEARCH WAY,BUILDING J I TP OREM,UT 84097 1, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. a " « ,..r 2. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY 800-377-4480 „ItT INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. t # 1" WWW.BLUERAVENSOLARCOM 3. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING ROOF VENTS. ° "� ,`,. '$, CONFIDENTIAL-THE INFORMATION 4. ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH '� -3 HEREIN CONTAINED SHALL NOT BE THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF USED FOR THE BENEFIT OF ' ANYONE EXCEPT COVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. BLUERAVENSOLAR NOR SHALL IT 5.NO.OF SHINGLE LAYERS-1 ' q QQ�} �^s Y�} p {" BE DISCLOSED IN WHOLE OR iN Pt ,, 1 2OJ� SOUt�1WCSt` PART TO OTHERS OUTSIDE SOLAR CONTRACTOR RECIPIENTS ORGANIZATION, 1. MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730. � Morningstar Drive EXCEPT IN CONNECTION WITH THE SALE AND USE DF THE UT THETIVE 2. IF APPLICABLE,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING EQUIPMENT WITHOUT THE ', -$' .. WRITTEN PERMISSION OF LUG HOLES PER THE MANUFACTURERS INSTALLATION REQUIREMENTS. "" 3. AS INDICATED BY DESIGN,OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED ry'` 5 +�' s' BLUERAVENSOLAR LLC. IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. T �`- NABCEP 4. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE :`"'". +f!' NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. > 5. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND T. CERTIFIED SEALED WITH A SUITABLE SEALING COMPOUND. ' ' PV INSTALLATION 6. DC WIRING LIMITED TO MODULE FOOTPRINT W!ENPHASE AC SYSTEM. �* ,.; if, q` "t . - ` PROFESSIONAL 7. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ `, j, s 1 • u Scott Gurney SUITABLE WIRING CLIPS. yn a .4r R PV-011719-015866 8. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR • + ;I - VOC UNLESS NOT AVAILABLE. IAN CONTRACTOR: 9. ALL INVERTERS,MOTOR GENERATORS,PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS, - BRS FIELD OPS AC PHOTOVOLTAIC MODULES,DC COMBINERS,DC-TO-DC CONVERTERS,SOURCE CIRCUIT *. 385.498.6700 COMBINERS,AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM . i WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4(B). A .> 10. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. , 11. TERMINALS AND LUGS WILL BE TIGHTENED TO MANUFACTURER TORQUE SPECIFICATIONS(WHEN PROVIDED)IN ACCORDANCE WITH NEC CODE 110.14(D)ON ALL ELECTRICAL CONNECTIONS. „ .� 0 4. 0 0 RS EQUIPMENT LOCATIONS - - ,�- 1. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL A EQUIPMENT WILL BE PROVIDED AS PER SECTION[NEC 110.26]. .. # , a ,, Lf j ;� Cr 2. EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING • E u . N Vi TEMPERATURE AS SPECIFIED BY[NEC 690.31 (A)-(B)]AND[NEC TABLE 310.15(B)]. ,f I, ' Z O co 3. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT - 0 n w TO THE UTILITY AC DISCONNECT,OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT. DESIGN CRITERIA SITE SPECIFICATIONS SHEET INDEX Q N- N 4. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO WIND SPEED: 120 MPH OCCUPANCY - R3 PV1 - COVER SHEET NEC APPLICABLE CODES. 5. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN GROUND SNOW LOAD: 40 PSF CONSTRUCTION - V-B PV2 - PROPERTY PLAN 2 o APPROPRIATE. WIND EXPOSURE FACTOR: C ZONING: RESIDENTIAL PV3 - SITE PLAN p m w SEISMIC DESIGN CATEGORY: D PV4 - EQUIPMENT &ATTACHMENT DETAIL u- H 0 0 H PV5 - ELECTRICAL SINGLE LINE DIAGRAM - r--. -a } co Cr) OFFICE COPY SCOPE OF WORK PV6 - ELECTRICAL CALCULATIONS & N ELECTRICAL NOTES u) H - H 0 INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM PV7 MAIN BREAKER DEBATE CALLS. DRAWING BY CITY OF TIGARD (IF NEEDED) DIN ENGINEERING REVIEWED FOR ODE COMPLIANCE 3.245 kW DC PHOTOVOLTAIC SOLAR ARRAY PV8 - LABELS & LOCATIONS Approved: [ ] ROOF TYPE: Comp Shingle PV9 CUSTOM DIRECTORY PLACARD DATE OTC; [ j MODULES: (11) SolarWorld 295 VALIDITY OF PERMIT (IF NEEDED - NEC 690.56(B)) March 17, 2020 lr5 ` �� - Opp �� INVERTER(S): Enphase IQ7 Microinverters,---- THE ISSUANCE OFA PERMIT RECEIVED PROJECT NUMBER Permit#: Address: 1y.531 54� OD RACKING-Ly iffitpot, Infinity BASED ON CONSTRUCTION 73236391 of IPt t DOCUMENTS AND OTHER Approved plans Suite#: The City of Tigard and its DATA SHALL NOT PREVENT PP SHEET NAME By: Date: 3I31 Za1A employees shall not be THE CODE OFFICIAL FROM shall be on job site. MAR 2 T 2 R COVER SHEET I responsible for discrepancies REQUIRING THE CORRECTION CITY OF TIGARD which may appear herein OF ERRORS. ORSC 105.4 BUILDING DIVt51�N PAGE NUMBER REVISION PV1 0 • LEGEND INV INVERTER&DC DISCONNECT M AC C N BLUE RAVEN I I — SUB (E) SUBPANEL MSFa LC (N) LOAD CENTER 1403 N RESEARCH WAY,BUILDING J AC AC DISCONNECT OREM,UT 84097 800-377-4480 M UTILITY METER o W W W.BLUE RAVENSOLAR.COM -THE INFO ❑ MSP MAIN SERVICE PANEL HEEREIN NFIDENTIAL CONTAINED SHALL NOTON BE USED FOR THE BENEFIT OF / JB JUNCTION BOX ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN TS TRANSFER SWITCH PART TO OTHERS OUTSIDE _> RECIPIENTS ORGANIZATION, '- • • EXCEPT IN CONNECTION WITH?HE C COMBINER BOX/AGGREGATOR OR SALE AND USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE 0 y ❑ PV PV REVENUE METER gLUERAVENSOLAR LLCITTEN PERMISSION . -C cW ❑ j FIRE SETBACK / 0 C EMT CONDUIT RUN //�,�Qp//'''�� G 0 ❑ (TO BE DETERMINED IN FIELD) 7 ""BC EP 7/1 = o CERTIFIED 0 ❑ PV WIRE STRING PV INSTALLATION o F— I PROFESSIONAL Z 1 Scott Gurney 0 ❑ ' PROPERTY LINE #PV-011719-016866 0 N C/) Ct CO u SCALE: 3/32°=1'-0" BPS HELD OPS T DO ❑ 385.498.6700 a) JB iSic _ 0 0 0 eic 121c CO +r La o eic eic tic IC) C d- N eic Ilc eic et iSic Z co N- LLI Q0))76 rn N li w co 2 p u m W v_ ~ i0 0 I- Z a I` a >- w a) cf) al U) F= a) co ROOF ATTACHMENTS SHALL BE SPACED I— N I— 0 NO GREATER THAN 24" ON CENTER IN DRAWING BY ANY DIRECTION WHERE LOCATED DIN ENGINEERING WITHIN 3' OF A ROOF EDGE, HIP, EAVE, OR RIDGE OSSC 3111.5.3 ITEM 3.2 DATE March 17, 2020 PROJECT NUMBER DC SYSTEM SIZE: 3.245 kW DC 73236391 ROOF TYPE: Comp Shingle SHEET NAME PROPERTY PLAN (11) SolarWorld 295 Enphase IQ7 Microinverters,----INVERTER PAGE NUMBER REVISION PV2 0 • LEGENDlitifilNir UNDERGROUND SERVICE LINE INV INVERTER&DC DISCONNECT BLUE RAVEN DISH M AC C SUB (E) SUBPANEL /N LC (N) LOAD CENTER S \ 403 N RESEARCH WAV,BUILDING J J / ` OREM,C UT 84097 AC AC DISCONNECT 800-377-4480 M UTILITY METER WWW.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION MSP MAIN SERVICE PANEL HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF O JB JUNCTION BOX ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN ❑ TS TRANSFER SWITCH PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, C COMBINER BOX/AGGREGATOR EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE PV PV REVENUE METER WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. O (ea FIRE SETBACK w EMT CONDUIT RUN • ❑ (TO BE DETERMINED IN FIELD) �BCEP O I CERTIFIED LL PV WIRE STRING PV INSTALLATION O ❑ = PROFESSIONAL f— ❑ 1 PROPERTY LINE Scott Gurney z #PV-011719-015866 0 00NTRACTOR: CC SCALE: 1/8"= 1'-0" Li_ e BRS FIELD OPS ❑ 385.498.6700 o 0 ❑ N U ❑ ❑ 0 4 in- - a In c C N Z O CO c7 0 2 N ❑ = N- W Q co N_ 2 3 0 ct MP1 O N m UJ UJ # OF MODULES: 11 JB Sic IL H O 0 AZIMUTH:178° z a N, >- PITCH:18° Lfc LIC F W co co o TSRF:88% � 1— N,— I— 0 AREA: 363.038 SQ. FT ,g� O Sic Sic ffC DRAWING BY DIN ENGINEERING AC DISCO WON'T EXCEED 10' AWAY Lcc Lc Sic Lc DATE FROM THE UTILITY METER March 17, 2020 PROJECT NUMBER DC SYSTEM SIZE: 3.245 kW DC 73236391 ROOF TYPE: Comp Shingle SHEET NAME SITE PLAN (11) SolarWorld 295 nphase IQ7 Microinverters,----INVERTER PAGE NUMBER REVISION PV3 0 ROOF ATTACHMENTS SHALL BE SPACED PV MODULE(BEHIND TRIM RAIL) Unirac SFM Infinity TRIM RAIL PV ARRAY INFORMATION NO GREATER THAN 24" ON CENTER IN ANY DIRECTION WHERE LOCATED !/ PV MODULE COUNT: 11 MODULES WITHIN 3'OF A ROOF EDGE, HIP, EAVE, LANDSCAPE BLUE RAVEN OR RIDGE OSSC 3111.5.3 ITEM 3.2 14 I 14 1'-11 #OF ATTACHMENT POINTS: 28 MAX 48" MAX. ARRAY AREA: Module Count x 17.51 ft2= 192.6ft2 1403 N RESEARCH WAY,BUILDING.) ROOF AREA: 2845.8ft2 OREM,UT 84097 PORTRAIT % OF ARRAY/ROOF: 6.8% Soo-377-4480 WWW.B ARRAY WEIGHT: Module Count x 501bs = 550.0Ibs MAX. 48" MAX. LUERAVENSOLAR.COM ARRAY DETAIL, FRONT VIEW CONFIDENTIAL-THE INFORMATION DISTRIBUTED LOAD: Array Weight:Array Area=2.86 Ibsfft2 SFM Infinity Flashkit HEREIN CONTAINED SHALL NOT BE Scale:3/8"= 1'-0" USED FOR THE BENEFIT OF POINT LOAD: Array Weight:Attachments= 19.61bs/attachment ANYONE EXCEPT RACKING ATTACHMENTS TO BE Unirac SFM Infinity FRAME BLUERAVENSOLAR NOR SHALL IT STAGGERED BY SHIFTING EACH BE DISCLOSED IN WHOLE OR IN SUBSEQUENT ROW OF ATTACHMENTS ® PORTRAIT PART TO OTHERS OUTSIDE ONE RAFTER OVER. RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE® ''I SALE QUI USE T, ITHUT RESPECTIVE EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF ( BLUERAVENSOLAR LLC. Unirac SFM Infinity UNIRACTRIMRAIL �� MODULE '• � LANDSCAPE NABCEP WIDTH O PV MODULE World 95 CERTIFIED a 0i ARRAY DETAIL, SIDE VIEW PV INSTALLATION z (E) ROOF 18 PROFESSIONALney Scale:3/8"= 1'-0" 012- gtll%1— MEMBRANE J. x Pv-on7ls ouess ODULE O IIr UNIRAC SLIDERS AND WIDTH CONTRACTOR: TRIMRAIL ROOF ATTACHMENTS BRS FIELD OPS f— ch 385.498.6700 m Ws to 2.5" MIN. EMBED. FLASHING I ROOF TYPE: Comp Shingle aI I j 5/16"STAINLESS STEEL LAG BOLT a U 0 WITH 2-1/2" MIN. EMBEDMENT ROOF FRAMING TYPE: Rafter AND FLAT WASHER (E) BUILDING RAFTER OR TOP CHORD(TRUSS)2x10 © 24"O.C. STRUCTURE CEILING JOIST OR BOTTOM CHORD(TRUSS)2x8 © 24"O.C. c �t C CV Z o Cr) Cj O 2 Cl] Unirac SFM Infinity < C o i -c 0 2 2 w 0 SolarWorld 295 z ~ (� 0 I- Z • PV MODULE — - N- 12 >- a 1III LU a cIs 0 A - O �.y I (E) ROOF I . _ 2.5" MEMBRANE DRAWING BY w ll = DIN ENGINEERING J - �__ 0 �_ o °� iwir UNIRAC SLIDERS DATE March 17, 2020 f j 2.5" MIN. EMBED. PROJECT NUMBER w FLASHING 73236391 5/16" STAINLESS STEEL LAG BOLT WITH 2-1/2" MIN. EMBEDMENT SHEET NAME = AND FLAT WASHER EQUIP. DETAIL (E) BUILDING STRUCTURE PAGE NUMBER REVISION PV4 0 • I1) 10*WGTrH41TtfW'N.2,CU.,&AC*011 11,0AAC 411 10.2UJF VI/6„ThH4ItHW*14,SOUDCU. MA ILO AAC tl) 10-IU'-01mkk1Wi6.T111 kITHWN.2.SQl MAX 11.OAM IiiL22TGFR,ThNk/iliWM-2.CU. MAX 11.DAAC 15 11) 10 AWOTNNNfr Ml-2,CU„RERtU) 240 VAC 3 240 Y AAC 2 240 VAC 1 Ili 6 VG SAM,CV WIC) 240 VAC (1) 10 AWGTtO(N/TNWN-2 CU..WHITE CIO (t1 10 AVM THIVI/TIAVN•2.CU„UREO-N1EGC1 (11 9,/4 INCH EMT EXTER10R D) VA1kC1I EMT mama 1mumE)RERiON BLUE U E RAVEN (11 6 AWGTHHN/T11WN•2,CU.,MACK(.11 ILO AAC 16 1U1 6 CUAVM 240 VAC (1) 10 AW6aT1MN/TIMM1.Z CV,WHITE(k) II) 10 AWGTHHN/TIMN4.2-CU..GMEEN 4EGC1 1403 N RESEARCH WAY,BUILDING J tl) 3/4 MNCKEM' EXTE6O11 OREM,UT 84097 , 800-377-4480 W W W.BLUERAVENSOLAR COM ALL CONDUIT TO BE RAN AT LEAST 7/8"ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, (E)200A MAIN SERVICE PANEL SUPPLY SIDE CONNECTION EXCEPT IN CONNEC TION WITH THE (E)200A/2P MAIN BREAKER PER NEC 240.21(B) SALE AND THETIVE & NEC 705.12(A) EQUIPMENT,USE O WIWITHOUUTT THE II- /!! (11)SOIHrWOdd 295 WITTEN PERMISSION OF BR ERAVE SOLAR LLC. 11 I 1 Enphase ID Combiner 3 UL 1703 COMPLIANT LC I LI ,x -JUNCTION BOX(S) c�ll33 PV DISCONNECT X3 R7` FUSED,100kAIC-R (SOLARAR LOADS ONLY) FOR WIRE SPLICING (11)Enphase 107 MICfOIflVertefS MICRO (E)200A LOCKABLE,VISIBLE OPEN ONLY-OPTIONAL IF INVERTERS NABCEP I SERVICE RATED 0-CABLE(TC-ER)OR UL 1741 COMPLIANT E��� 60A,240V,2-POLE OF-BUSED FOR 11 MODULES MAX FOR ALL SUB-BRANCH CERTIFIED ENTIRE HOMERUN CIRCUIT(S)TO COMPLY WITH VRIS CALCS I E) PV INSTALLATION O V LOADS - N JUNCTION BOX JUNCTION BOX PROFESSIONAL 20A _— Scott Gurney FUSES — ..© X PV-011719-015866 O O o CLASS R — (N)20A'£P (1) CIRCUIT 70 ® I A GA �I111111111111111flL, /1 u r\ I� OF 11 MODULES i� i CONTRACTOR: —71 Ill Ea _ _� I BRS FIELD OPS 120/240 VAC V v — 385.498.6700 60HZ 1 PHASE TO UTILITY 16 150 O 1 GRID a) U 0 0 cts GEC TA } • to �/� V N ` 01 Cr 6 0) w (E) GROUNDING F - n IV ELECTRODE(S) c 0) c 73 0 N = ;v w Z (I 0 F- p } E w ate) eo al CO H 92 N H 0 (I) I— -.:. DRAWING NOTES BYDIN ENGINEERING 1 SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)]. ? DISCONNECT NOTES " '' a DATE 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OP` March 17, 2020 OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE E: ti TERMINALS MARKED"LINE SIDE(TYPICALLY THE UPPER TERMINALS) ( ••,A PROJECT NUMBER 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE 1'` 73236391 LOCKABLE,AND BE A VISIBLE-BREAK SWITCH SHEET NAME ii ELEC. 3 LINE DIAG. ilik` ♦Yit j? °s .,, ; PAGE NUMBER REVISION � PV5 0 ) MODULE SPECIFICAT1ONS Sunmodule Plus SW Z95M Black DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS RATED POWER(STC) 295 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(15C)= 110 A AC \dr. MODULE VOC 40 V DC STATE Oregon JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 118 A AC MODULE VMP 31.5 VDC CITY Tigard CONDUCTOR(TGER,COPPER(90'C))= 12 AWG BLUE RAVEN MODULE IMP 9,45 A DC WEATHER STATION PORTLAND INTERNATIONAL AP CONDUCTOR RATING= 30 A MODULE ISC 10.1 A DC ASHRAE EXTREME LOW TEMP('C) -6 AMB.TEMP.AMP.CORRECTION= 0.96 VOC CORRECTION -0.31 %/'C ASHRAE 2%AVG.HIGH TEMP('C) 32 s ADJUSTED AMP,■ 28.8 > 13.8 1403 N RESEARCH WAY,BUILDING J VMP CORRECTION -0.43 %/-C 1 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 110 AAC OREM,UT 84097 SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS OR 1 CIR 2 CIR 3 OR 4 CIR 5 CIR 6 'JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 13.8 A AC 800-377-4480 ADJ.MODULE VOC#ASHRAE LOW TEMP 43.8 V DC NUMBER OF MODULES PER MPPT 11 T CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG WWW.BLUERAVENSOLAR.COM ADJ.MODULE VMP @ ASHRAE 2%AVG, HIGH TEMP 26.2 V DC I DC POWER RATING PER CIRCUIT(STC) 3245 f CONDUCTOR RATING= 30 A CONFIDENTIAL-THE INFORMATION TOTAL MODULE NUMBER 11 MODULES j CONDUIT FILL DEBATE= 1 HEREIN CONTAINED SHALL NOT BE MICROINVERTER SPECIFICATIONS Enphdse IQ7 Micrvinverters STC RATING OF ARRAY 3245W DC f OMB_TEMP.AMP.CORRECTION= 0.96 USED NYONE EXCEPT BENEFITOR THE OF POWER POINT TRACKING(MPPT)M1N/MAX 22 • 48 V DC AC CURRENT @ MAX POWER POINT(IMP) 11.0 3 ADJUSTED AMP,= 28.8 > 13,8 BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN MAXIMUM INPUT VOLTAGE 48 V DC MAX,CURRENT(IMP X 1_251 13.75 (JUNCTION BOX TO MAX SHORT CIRCUIT CURRRENT(15C)6 110 AAC PART TO OTHERS OUTSIDE MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(1SC X1.25)= 13,8 AAC RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH THE MAXIMUM USABLE DC INPUT POWER 350 W MAX.COMB.ARRAY AC CURRENT(IMP) 11.0 I CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG SALE AND USE OF THE RESPECTIVE MAXIMUM OUTPUT CURRENT 1 A AC MAX.ARRAY AC POWER 2640W AC 1 CONDUCTOR RATING= 30 A EQUIPMENT,WITHOUT THE WRITTEN PERMISSION OF AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DEBATE= l BLUERAVENSOLAR LLC. MAXIMUM OUTPUT POWER 240 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. VRISE(V) VEND(V) %VRISE IQ7.11 AMB.TEMP.AMP.CORRECTION= 0.96 CEC WEIGHTED EFFICIENCY 97 % VRISE SEC. I (MICRO TO JBOX) 39.6 12 Cu. 1.76 241.76 0.73% ADJUSTED AMP.= 28.8 > 13,8 ABC EP VRISE SEC.2(JBOXTO COMBINER BOX) 95 10Cu. 2.65 242.65 1.11% COMBINER 8OXTO INVERTER RATED AMPS 11.OAAC CERTIFIED AC PHOTOVOLATTC MODULE MARKING(NEC 690.52) VRISE SEC,3(COMBINER BOX TO POI) 10 10 Cu. 0:28 240,28 0.32% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPSX1-25)= 13,75 AAC NOMINAL OPERATING AC VOLTAGE 240 VAC TOTAL VRISE 4.69 244.69 196% CONDUCTOR(THWN-2,COPPER(75'C TERM,))- 10 AWG PV INSTALLATION NOMINAL OPERATING AC FREQUENCY 47-68 HZAC CONDUCTOR RATING= 35 A PROFESSIONAL Scott Gurney MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL (NEC 69(154) CONDUIT ALL DERATE= 1 #Pv-011719-015866 MAXIMUM AC CURRENT 1.0 AAC AC OUTPUT CURRENT 11,0 AAC OMB.TEMP.AMP.CORRECTION= 0.96 OR: MAXIMUM OCPD RATING FOR AC MODULE 20 AAC 1 NOMINAL AC VOLTAGE 240 VAC ADJUSTED AMP.= 33.6 > 13,8 F BRSCONTRACTOR: FIELD OPS 385.498.6700 d) > U C 1l 0 GROUNDING NOTES STRANDED,AND BARE WHEN EXPOSED. 690.8] FOR MULTIPLE CONDUCTORS 1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690-47]AND 11.EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO[NEC 8. ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED iFS [NEC 250-50]THROUGH[NEC 250-60]SHALL BE PROVIDED.PER NEC, 690.45] AND BE A MINIMUM OF#10AWG WHEN NOT EXPOSED TO DAMAGE(#6AWG AT LEAST 7/8"ABOVE THE ROOF SURFACE AND DEBATED ACCORDING TO[NEC TABLE i LO GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND SHALL BE USED WHEN EXPOSED TO DAMAGE). 310.15(B)(2)(a),NEC TABLE 310.15(B)(3)(a),&NEC 310.15(B)(3)(c)]. C 't BONDED TO AT THE SERVICE ENTRANCE.IF EXISTING SYSTEM IS INACCESSIBLE, 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR 9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV . . E coM OR INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL CODED GREEN(OR MARKED GREEN IF#4 AWG OR LARGER) RESISTANT,AND UL LISTED RATED FOR 600V,UV RATED SPIRAL WRAP SHALL BE O 0V C GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION 13. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF USED TO PROTECT WIRE FROM SHARP EDGES Li CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 = y N 2. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL 14.SYSTEM GEC SIZED ACCORDING TO[NEC 690.47],[NEC TABLE 250.66],DC INSULATED,90°C RATED,WET AND UV RESISTANT, RATED FOR 600V 3 (7) o DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SYSTEM GEC SIZED ACCORDING TO[NEC 250.166],MINIMUM#BAWG WHEN 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER CC: L IT SMALLER THAN#6 AWG COPPER WIRE PER NEC 250-64B.THE GROUNDING ELECTRODE INSULATED,#6AWG WHEN EXPOSED TO DAMAGE. VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. O N j N W CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS 15.EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, 12. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION Li_ ♦- 0 WITHIN LISTED EQUIPMENT PER[NEC 250.64C.). EQUIPMENTS,AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN 13. VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS z >+ Crj -p U) 3. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN#8 AWG AND ACCORDANCE WITH 250.134 OR 250.136(A)REGARDLESS OF VOLTAGE. 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS LU N cc*) al Cl) NO GREATER THAN#6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING FOLLOWS:DC POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) N _2' U ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. WIRING&CONDUIT NOTES 15. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: U) if r f-- 4. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 1.ALL CONDUIT SIZES AND TYPES,SHALL BE LISTED FOR ITS PURPOSE AND DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) DRAWING BY 250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO[NEC APPROVED FOR THE SITE APPLICATIONS 16. AC CONDUCTORS>4AWG COLOR CODED OR MARKED: 690.46]. 2.BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED PHASE A OR L1-BLACK, PHASE B OR L2-RED,PHASE C OR L3-BLUE,NEUTRAL- DIN ENGINEERING 5. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC CONDUCTOR(USE POLARIS BLOCK OR NEUTRAL BAR) WHITE/GRAY 690.42]. 3. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY DATE 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT DISALLOWED ABOVE LIVE PARTS,MEYERS HUBS RECOMMENDED BE USED INSIDE March 17, 2020 THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR 4. UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT "USE-2 IS AVAILABLE AS UV WHITE TO ANOTHER MODULE. OFF THE ROOF SURFACE IN ACCORDANCE WITH NEC 110.2,110.3(A-B).300.4 17. RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROJECT NUMBER 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH W/ROOF SURFACE TO BE USED FOR PROTECT WIRES. 73236391 IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. WIRE MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL B. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH RUNS. BE EITHER EMT,FMC,OR MC CABLE IF DC CURRENT COMPLYING WITH NEC 690.31,NEC SHEET NAME AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR 250.118(10).DISCONNECTING MEANS SHALL COMPLY WITH 690.13 AND 690.15 ELEC. CALCS. GROUNDING LUGS. CABLE LISTED AND IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO 19. CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE 9. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND SOURCE CIRCUIT COMBINER BOXES AS REQUIRED COMPLYING WITH NEC 230.6(4)AND SECURED NO GREATER THAN 6'APART PER NEC PAGE NUMBER REVISION GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 330.30(B). PVC 10. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR E-•:, Tt 1,• T A LABEL? JJ���, FOR PV DISCONNECTING MEANS WHERE ALL �r� 'NI P 011 H,`-' AT DIRECT-CURRENT EXPOSED RACEWAYS,CABLE TRAYS,COVERS AND ENCLOSURES OF JUNCTION BOXES,AND OTHER """`" TERMINALS OF THE DISCONNECTING MEANS MAY BE PA'-ER SOURCE.. WIRING METHODS:SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES,WALLS,PARTITIONS, M`" T� ELECTRIC SHOCX HAZARDENERGIZED IN THE OPEN POSITION. CEILINGS,OR FLOORS. BLUE RAVEN TERitiiNALS ON NE LINE AND [NEC 690.13(B),NEC 705.22] [NEC 690.31(G)(3&4)] LOAD SIDES MAY SE ENERGIZED . IN THE OPEN LABEL 8LABEL 11 SOLAR PV SYSTEM EQIi{PPED1 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY 41, 1yy PERMANENT DIRECTORY TO BE LOCATED AT 1403 N RESEARCH WAY,BUILDING J WITH RAPID SHUTDOWN AND CONDUCTORS LEAVING THE ARRAY: ` '` � MAIN SERVICE EQUIPMENT LOCATION IF ALL OREM,UT 84097 SIGN TO BE LOCATED ON OR NO MORE THAN 3 IMW dRSReUDON 4111LITYISIC0111111CM3 ELECTRICAL POWER SOURCE DISCONNECTING LABEL AR*ROD MrKN 1D 1nB Ntxtlx�rGKnlf7 tRll�a 1 800-377-4480 FT AWAY FROM SERVICE DISCONNECTING [,; AT EACH DC DISCONNECTING MEANS,INCLUDING THE IMMOITIOD* RkOmOENY ItNflfli RD4+Lolo SAUI SUPOutM MEANS (SOLAR ARRAY RAPID SHUTDOWN ORE + ,:1,1PREIIT WWW.BLUERAVENSOLAR.COM DC DISCONNECT AT THE INVERTER. 'OF�'ai36tt1pI TO MEANS TO WHICH THE PV SYSTEMS ARE ♦MM6NlNIl1}GYAY DiE170NR9CTN6 tlRM� SWITCH)ARE GROUPED AND IN LINE OF SITE OF t r!,;1T3VULTAly F(,1 ER SSCUI BKTf%SrMRPvterty "' CONNECTED AND SHALL INDICATE THE M/APOIASSIEDxt'h•440MO WE [NEC 690.53,NEC 690.13(B)] AND#tEDJC€ LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN AND it FT W)1ellUXA1 001. MAIN SERVICE DISCONNECTING MEANS. SiCO�14AV [NEC 690.56(C)&NEC 705.10]. CONFIDENTIAL-THE INFORMATION Ba TyT, y SWITCHES IF NOT AT THE SAME LOCATION. HEREIN CONTAINED SHALL NOT BE MAXIMUM VOLTAGE VOC� [NEC 690.56(C)(1)(A)] USED NYOTH EXCEPT OF MAX CIRCUIT CURRENT AI LABEL 12 •-� — ..Wr Y...J ,. BL NSOLAR NOR SHALL IT LABEL 9 a 4 PERMANENT DIRECTORY TO BE LOCATED AT BEE DISCLOSED IN WHOLE OR IN SOLAR P V SYSTEM EO(W�PPEG FOR PV SYSTEMS THAT ONLY SHUT DOWN y sisur":'u Atso` SOLAR ARRAY RAPID SHUTDOWN SWITCH PART TO OTHERS OUTSIDE W]IR RAMC.4SMU j t+'t`"L'N CONDUCTORS LEAVING THE ARRAY. SUPPLIED OM MAJ°Am0 kOUTIO DENOTING THE LOCATION OF THE SERVICE RECIPIENTS ORGANIZATION, LABEL 3 SIGN TO BE LOCATED ON OR NO MORE THAN 3 T`DI•=0 iR0U MUN flI5TR�175ON EQUIPMENT LOCATION IF SOLAR ARRAY RAPID EXCEPT IN CONNEC TION WITH THE PHOTOVOLTAIC SYSTEM AT POINT OF INTERCONNECTION,MARKED AT AC tJ11Nyp 1N1<8M111NNRM FT AWAY FROM SERVICE DISCONNECTING Irru r'DWGOWWEC1 UDCJC QED SHUT DOWN DISCONNECT SWITCH IS NOT SALE AND USE OF THE RESPECTIVE DISCONNECTING MEANS. #01DIEW#01181111 4 ib.A MEANS TO WHICH THE PV SYSTEMS ARE GROUPED AND WITHIN LINE OF SITE OF MAIN EQUIPMENT,WITHOUT THE AC DISCONNECT . [NEC 690.54,NEC 690.13(B)] atiE .f. 1116. CONNECTED AND SHALL INDICATE THE SERVICE DISCONNECTING MEANS. • WRITTEN PERMISSION OF RAID AC ODTDt]TCIIE i A � � [NEC 705.10] BLUERAVENSOLAR LLC. LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN Rpp+T SWITCHES IF NOT AT THE SAME LOCATION. WARN.OPERAINGACVOL iE V [NEC 690.56(C)(1)(B)1 , _. --�: LABEL13 "' "/►4" '>#' rro " ',,fi PERMANENT DIRECTORY TO BE LOCATED AT MAIN NABCEP SERVICE EQUIPMENT DENOTING THE LOCATION LABEL 4 - - LABEL 10 •uINJI "45611"."115"ONIRPl" OF THE PV RAPID SHUTDOWN SYSTEM CERTIFIED IF INTERCONNECTING ON THE LOAD SIDE,INSTALL THIS - SIGN LOCATED AT RAPID SHUT DOWN PROW WO WPM*NOIMtARNAt-MAN DISCONNECTING MEANS IF SOLAR ARRAY RAPID A[C LABEL ANYWHERE THAT IS POWERED BY BOTH THE DISCONNECT SWITCH[NEC 690.56(C)(3)]. ARRAY WPC WNODT#MI 111COINiCt! SHUT DOWN DISCONNECT SWITCH IS NOT PV INSTALLATION DUAL POWER SUPPLY UTILITY AND THE SOLAR PV SYSTEM:THE MAIN SERVICE 1a70At® RpIIR OENEXTTOVTUrtMETER GROUPED AND WITHIN LINE OF SITE OF MAIN PROFESSIONAL PANEL AND SUB-PANELS. _ SERVICE DISCONNECTING MEANS.[NEC 705.10, Scott Gurney SOURCES:UTLTTY GRID AND [NEC 705.12(8)(3)] NEC 690.56(C)(1)] #PV-011719-015866 PV SOLAR ELECTRIC SYSTEM CONTRACTOR: LABELING DIAGRAM FOR MICRO INV.: BRS FIELD OPS MAIN SERVICE PANEL 385.498.6700 ,,:,.,. LABEL S EXISTING SUB PANEL PV COMBINER ] ` PLACED ADJACENT TO THE BACK-FED BREAKER WARNIN 10 0 (IF WHERE POINT OF SUBPANEL- FROM THE INVERTER IF TIE IN CONSISTS OF LOAD INTERCONNECTION IF USED TO COMBINE AC JUNCTION BOX SIDE CONNECTION TO BUSBAR. 0) INVERTER OUTPUT CONNECTt41! [NEC 705.12(B)(2)(3)(b)] IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS OR AC COMBINER BOX > U DO NOT RELOCATE 3 & 4 ._ O 003 0 CI 0 THIS OVE#iCl)RttENT ° ° IF BREAKER USED _ CIITS DEVICE ° °° 08' 0 10 — 0 ., O11 OR 13 IF BREAKER USED C PLACARD 12 OR O •• 'E CV LABEL6 PLACARD Z O N (Y1 ,n (ONLY IF PV o-- ° w O 0 °/ 0O_ 2 III . , ,' A BUSBAR) N- SIGN LOCATED AT LOAD CENTER IF IT (ONLY IF PV Ti�S ELIUIINT FED BY t i L INTERCONNECTIOP NTERCONNECTION E CONTAINS 3 OR MORE POWER SOURCES. ....CONSISTS OF LOAD Q N SOURCES TOTAL RATING OF ALL [NEC 705.12(13)(2)(3)(C)] CONSISTS OF LOAD OVERCUiRENT DEOCES EXCLUDING SIDE BREAKER) SIDE BREAKER) *kw SUPPLY OVERCURREXT 0 y 5 2 Lu DEVICE.SIIALL NOT CEED LABELING DIAGRAM FOR STRING INV./DC OPTIMIZER INV.: LL ~ 0 CO Y OFMAIN SERVICE PANEL Z "„,__0 [� "O ` OEXISTING SUB PANEL PV COMBINER INVERTER(S) LLI O Cr) ai CO 1 (IF WHERE POINT OF SUBPANEL- ~ INTERCONNECTION IF USED TO COMBINE Cl) F— N I— 0 3 &O IS MADE) AC DISCONNECT PV OUTPUT CIRCUITS IF BREAKER USED DRAWING BY 0 0 0 0 0 DIN ENGINEERING OORO —_ G p G 08 O O O DATE C OR CI IF BREAKER USED AC JUNCTION BOX March 17, 2020 12 OR PLACARD OR O 2 o� OR COMBINER BOX LABELING NOTES: PLACARD 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS.ELECTRICIAN TO 5 5 PROJECT NUMBER DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND (ONLY IF PV (ONLY IF PV O 10 O ' 73236391 MAKE APPROPRIATE ADJUSTMENTS. INTERCONNECTION NTERCONNECTIOf� 2. LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE,OSHA STANDARD CONSISTS OF LOAD 19010.145,ANSI Z535. SIDE BREAKER)ONSISTS OF LOAD 1 1 �° O O SHEET NAME SIDE BREAKER) LABELS 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. LIBELS 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED AND INTEGRATED DC DISCONNECT SHALL NOT BE MINIMUMHANDWRITTEN[NEC HEIGHT110.H1] *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS 5. AND LABELS TOM N AN LETTERD[IFC 111OF 3/8",WHITE ON RED BACKGROUND;REFLECTIVE, PAGE NUMBER REVISION AND PERMANENTLY AFFIXED[IFC 605.11.1.1] PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL o`ro O REPRESENTATION OF PROPOSED SCOPE OF WORK. f V 8 \le Ga1ss1 BLUE RAVEN Enphase Microinverters Qegion.AMERICAS 1403 N RESEARCH WAY,BUILDING J Enphase IQ 7 and IQ 7+ Microinverters OREM,UT E140117 800-377-44130 INPUT DATA(DC) IC7-60 i.US1107-60.6,.iS IQ7PLUS•72.2•US/IQ7PLUS-72-11-tli .._ _._..,. ._—..- _.....__�.. WVWV.BLUERAVERAVENSOSOLAR.COM Commonly tMsdmodule palrfngz 235 W-350 W v 2815 W-440 W r Modulo cOmpalbillty 60-cell PV modules only 66-Cell and 72-cell PV moCU659 CONFIDENTIAL-THE INFORMATION Meaantan Iflpul DC v 11409 48 V 60 V HEREIN CONTAINED SHALL NOT BE The -;gh-powered smart grid-ready 8 a USED FOR THE BENEFIT OF Enphase Peat power tracking voltage 2 { 37V 27V-45V ANYONE EXCEPT BLUE RAVEN Enphase IQ ? Micro'. and Enphase IQ 7' MIcro taperallrtptirnge 16V 48V TOY*60Y SOLAR NOR SHALL IT BE Min/Max voltage 22 Y b8 V 22 V;60 V DISCLOSED IN WHOLE OR IN PART dramatically Simplify the installation process while TO OTHERS OUTSIDE RECIPIENTS IQ 7 and I Q 7+ MIX DC shod circuit curter*ImotklN lac) 15 A 1i A ORGANIZATION,EXCEPT IN achieving the highest system efficiency_ Over volage clans DC pat II II CONNECTION WITH THE SALE AND M i c r©inverters DC poet backfeed current O A O A USE OF THE RESPECTIVE Part of the Enphase IQ System,the IQ 7 and PV a a. nrFa xz;tu 1 x 1 Leerouxled a ny;No addt.anel DC deproe tapn aequ red EQUIPMENT,WITHOUT THE IQ 7+Microinverters integrate with the Enphase ac a de praec+,on Yogi re.ma,zoo ow tfare.P ._; U I WRITTRAV NEN RSOLAR MISSION COF BLUE OUTPUT DATA{AC) IQ 7 Mbrolnvener IQ 7•Mtcrorn ve der IQ.Envoy`,Enphase IQ Battery",and the Enphase Pak WW1 pOWer 2so VA z95 VA Enlighten monitoring and analysis software. Maximum cfrrtnuoua ourpur paws 24e VA �40 VA NABCEP N0n*i&(GL)voltage/range, 240 V 1 208 V 1 240 V i 208 V,' IQ Series Microinverters extend the reliability z11.21s4v 1s3�24v r11•z6av 1s3zzav CERTIFIED Maxlmun contnuoua clown curr EN 1 0 A{?40 VI I.15 A(20S VI 171 A(240 L) 1.30 A(208 111 standards set forth by previous generations and nindna(Redwiney 60 Hz 60 Hz PV INSTALLATION undergo over a million hours of power-on testing, u frequency range a' 6e N: :%•tie Hz PROFESSIONAL AC short circuit taint current over 3 cycles 5 8 Arms 5 Slums Scott Gurney enabiYng Enphase to provide an industry-leading Maximum units per 20 A.(L-L(brans craat' 16 240 VAC', 13(208 VAC 3(243'.='AC) 11 ins VAci rt PV-011719-015886 warranty of up to 25 years_ Own-vulva class AC pall ill III CONTRACTOR: AC poll beckfaed current D A i0 A Poe* 1.0 1 D BRS FIELD OPS re' r dilatable) rower Isola' 0.?loading 0.7lagging 0 7 leading 0 7legging385.498.6700 EFFICIENCY @11240 V @208V 4240 V 12Dll V pnkCEc tf6claricy 07.61 97.611, STAB 973%' C EC weighted efficiency 97,0% 970 a 97.0% 97-Q Easy to > Lail MECHANICAL DATA Acoward temperetwetanar -40'C lo't6M r'' • Lightweight and simple P;elalire humlday range 4,to 100'+;Iconiensrp) • Faster insfallaton with improved,fighter two-wire cabkng Cmr»ctor type(IQ7-00.2-MS6107PLU8.72-24S) MCP(at Methano114UTX with additional -DCC-5edaP4r) Cmnecretype(147-60.8•Ug6IQ7PLUS72.8uS) Friends PV2(MC4Interrruteeblel • &cult-in rapid shutdown compliant(NEC 201A&2017) Adaptors For module.with MC 4 or UTX connectors` -PV2 to MC4 order ECA•S20S22 161 •PV2 to UTX order ECA•S20-525 Productive and Reliable D6...a.riM rs(W B HB DI 212.trim a 175 mm a 30 21rw(Without nractat) Weight 1 dB kg I—'38 Iba) - --.; • Opdm:zed for high Dowered 60-cell and 72-cast•modules Cooing bar oral corrrecllph-No lulls • More than a rralbrxi hours of testing App-oved lot wet locahons vet • Class II double-insulated enclosure Pollution degree P03 • L1L listed Enclmue Class II double-nsulatld_caroY+on rarislant potymeuc."''>' Enrborrnantaf allegory!UV exposure rating NEMA Type 6 r outdoor FEATURES Smart Grid Ready CoMntrtlicaticn Power the (PLC) Monnoring Enlighten Manager and MyEnNghlen monitoring options. • Complies with advanced grid support voltage and Both options r equ.re Installation of an Erphaae 10 Envoy 14' frequency ride-through requirements 0iimui••*cling ing me ma The AC and DC corned ors have been evelrtted end approved by UL far um Nettie Rod-break • Remotely updates to respond to changing d emnnact reduced by NEC 690: grid requelonands Compliance CA Pule 21(UL 1741-SA) UL 52109-1,• Configurable for varying grid profiles CAN/C SA-C22.2 NO 1071-01 FCC Pen 15 Clasp B. ICES-0fl03 CFass B, • Meets CA Rule 21(UL 1741-SA) This product Is UL Listed as PV Rapid Strut DOwn Equlpmen1 end tc+,1©rrna with NEC-2014 end NEC-2017 section 69012 and C221.2015 finds64.218 Revd Shutdown of Psi Systems.for AC and DC conductors,when tnrtallad according menufaeluer'e instructiorn. •The curl 71 MIPO s troutard to support 7_p0 module ....._. �rR.�..-........ ,,.—....n,.....n.,,.....�.,--.._..—. . ..,..- CEITI IS I.No enlaced JC/AC rain Sac Inc eorpo dl it oak:aarm a bgpil.'Mpbaaa WLralaPlitlithTe p111VEMrt4p111U al 7 Ne.+oat wr1a loo ps ran be mended beyond llUnl. r rrcuind ley Ins sIIlr ie� H J,nr.Mroll way Asia to iw.al MP.,ilrna.l•lu&NNIe Ow umrbu of rrcro.nra l4a pet bmc1.n you ai r. To learn more about Enphase orlerincp,visit enphase.Co4T1 ENP• 'A E.• SHEET NAME To(earn more about Enphase offerings,visit anpbase.Dam e E N P H A S E. SPEC SHEET .+":+ tli.x: ....r.IP.AI�I.vhfle �� f/b. ,e„r Y:]c'r r, :.�.t,i CL.,. ... PAGE NUMBER REVISION SS 0 Nov' BLUE RAVEN . ,l„ -.1 Enphase IQ Combiner 3 Enphase Networlti n9 1403 N RESEARCH AY,BUILDING J MODEL NUMBER . ...,.. .. 1E)Ccenbiner 3 wlth..Enpha'a ICI Erwin'Welled crm&board for Integra tat ree.ni*adr FY 800-377-4480 production In rteg{ANSI C1220 N-O Vs)and optional,caeumpttat Mon8alrg(it+-2-5Ta).. yywyV.BLUERAVENSOLAR.COM ACCESSORIES A,C1 REPLACEMENT PARTS in of xts.ruffed,Ceder separatetvl __...,.„_.,_.. .,, ........,.. ,� .... -., .. - CONFIDENTIAL-THE INFORMATION EnphaaeMoNN Cornett' HEREIN CONTAINED SHALL NOT BE _ CEa LMooEM•433 Ida;'12-year data plan). Plug and play industrial grade emik Ian modem with data pin for system'up 1o60 USED FOR THE BENEFIT OF CELLMCOEM-01(3G i 5-vow data plan) mroinverlea.(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin Island,, ANYONE EXCEPT BLUE RAVEN CrLLMODEN•M114Gbai d LTEa47 5-yeer data Diem where Mere b adeduala cellular service loathe Irtotallalm itae) SOLAR NOR SHALL IT BE Enphase The Enphase IQ Combiner 3" wth Enphase ccrsamp;,cn MoneUr ing•CT DISCLOSED IN WHOLE OR IN PART CT-200-5PUT Spll;core current tra•tslarmer'enable whole heron'consumption met ering Ir+-2..Sn TO OTHERS OUTSIDE RECIPIENTS i �y� IQ Envoy" con so dates nterconnect:on Circus Bracken Supports Eum BR210,BR215,BR229,BR23t3,BR24©,8R250,and BR26D clactud breakers. ORGANIZATION,EXCEPT IN 1Q Combiner 3 CircusBRIO Br"et24{] Circuit breaker,2Ada«IOA,Eaten 0210 CONNECTION WITH THE SALE AND equ potent nto a s ng e enclosure and aaRR•1SA•2-240 c•rcem brinks,2poIR 15A Eaton 8FC 15 USE OF THE RESPECTIVE (X-IQ-AM 1-240-3 and BRIc•213k2P-240 Greve breakar,.2 poie,20A,Eaton 8R220 RIT EN EQUIPMENT, OF THE stream PV storage 'n5I8. at by WRITTRAPE SOLAR L C. BLUE EPLC-01 Power bee:Reuter(comnxn•calran bridge oar j.ovantdy 2 RAVEN SOLAR LLC. prov,d no a cons stent,pre-w red soluton ;or SA-PLUG-120-3 Actetwory receptacle fro Porter Lite Carrier er 10 Combiner 3 Crectuirec1 for EPLC-01) es•dent B! app catons It offers up to four kA-ENV PCBA•3 a:cT E ._ ., eri,-ir: l bnasd"gPCB)for C xr balsa 3 NABCEP ELECTRICAL SPECIFICATIONS ._ _---_. ...,..-- CERTIFIED 2-po e rlput crcua5 and Eaton BR sere$ Ratty c.„on , JJ> buster assertb'y, System vnaage 120,240 VAC,6o H: PV INSTALLATION Eaton OR series Weber rating 125 A PROFESSIONAL Stott Gurney Mac continuous cur ens;a Trig ioutpLA.to grid) 65 A t PV-011719-015866 Mai,lasso'cull rating{output) 90 A CONTRACTOR: — Branch travels Ieolar and%or'Iona gel Up to four 2-poi Eaton BR aeries Dletrtbuteo Generation(DGi breakers only(not ncluded) BRS FIELD OPS Mi Continuous current Wing{Input from PV) 64 A 385.498.6700 Max.r:•tai branch circuit breaker rating Kaput E04 of cestrbuted generaticx•,i 40.A with IQ Envoy breaker included Smart PruducLoh Metering CT 200 A load tors Otte-intlalied and wired ID IQ EnPay • • Includes tQ Envoy for communication MECHANICAL DATA ,..-r ) end control .� .-._«-.. ----- --- - ; DMnenewne I W 0 44D) 40,5 a 37 5 x 16 8 cue(19.5 x 14,75'i 6.63-).Halgei is 21.06'(52-.5 cm with mounting MKkelel. . r .e • Flexible networking supports WI-F1, 1i.mu ��`�' E. Ehernet,orcellular Weught 75kg(16.5me) t ,.x;. y°;1 "ft Ambirttemp waturerOng" -40°Cto.46°C(-40•to115°F) R • • Optional AC receptacle available/or PLc tt'; .-• 1tb br sage Cooling Natur41 cor`vadion,plus haat shield • Provides production melerng and optional Enclosure anvaortmwttalrating OIAdo6r,NRTL-cMt7gadNEMA typo:30.Polycarh•vvbcawtructart cortsvmplron monitor trig Wes sues • 27 A to 50 A breaker atputs. 1410 4 AWL ceppet conductors • 60 A breaker brooch irtpul. 4 to 10 A'WG copper conductors a • Man lug combined oulcut 10 is 2«0 AWC cope conductor:- Simple Always• folio*ground caal coderlo e9ui rnpnastla ON:t C1Cr 4lt,n0. • Reduced size from previous combiner AIMS* To 2000 meter'16.560Biel _ • Centered mounting brackets support single INTERNET CONNECTION OPTIONS stud mountng integrated WI-Ft 802.11bi0 n • Supports beck and side conduit entry EIhrrnel 0pliona I.802?,Ca15E{or Cat 4)UTP Ethernet cable inoi sncludedl • Up to tour 2-pole brunch circuits 1rr.240 VAC Cellular Optional,CELLMODEM-01(3G)cc CELLMOOEM-03 I4G) or CELLMOD13e-141(4Gtased LTE-M) ...... ._ _.._. ._.. plug-In breakers(not included, ;nor"(Waal • 80 A total PV or storage branch circuits r101AVLIANCE ;.-,ce,combust- vl t J1 CAN CSA C22.2 No.107,1 Reliable 47 CPR,Put 15,Close 8,ICES 003 Production metering ANSI C12.20 accurate class o 5(PV prrdtrtion) • Durable NRTL•certified NE MA type Cu-r,c,anca.IQ Envoy VI 60601.11CANCSA 22.2 No.610101 3R enclosure 4:) • Five-year warranty •Consumption monitorng is required for Enphase Storage Systems • kit listeConsumption USTE� To learn more about Enphase offerings,visit enpheae.can ENPHASE, Ft,.:{�.h:1 ,$,. •«..tic;¢ a- ".r I. .,x ,.,, , ,,,,. ,re-, .t.rr,.,•r.r., "e, ENPHASE. to learn nine about Enphase offerings,visitenphase,com t,J •a 32c'3 SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0 iid�t1 /art BLl3E RAVEN SunmoduleY Plus SOLAR�fv LD Sunmodule Plus SOLARWORLD SWA 285 . 290 MONO BLACK `I. SWA 285 - 290 MONO BLACK " �i� 403 N RESEARCH 0 FM UT 8409BUILDING J REAL VALUE REAL VALUE 800-377-4480 W WW.BLUERAVENSOLAR.COM r.. �_____ PERFORMANCE UNDER STANDARD TEST CONDITIONS(STCj' --_. CONFIDENTIAL-THE INFORMATION " Data thee: • " sv. SWA2 SWA MD HEREIN CONTAINED SHALL NOT BE 'n .. , ,, USED FOR THE BENEFIT OF v x .atws e, fi iw I maximum,lMfar P-+. '}svp 29@tvp ANYONE EXCEPT BLUE RAVEN � • Opel cHcaft V_ 39.2 V 39SY SOLAR NOR SHALL IT BE r DISCLOSED IN WHOLE OR IN PART Aaeximum V 32.OV 327V 11 f �= r'- d r '-- 'R TO OTHERS OUTSIDE RECIPIENTS .P ,•�°" <,-^" ( I 3halleaesiteserenr ty 952X 9604. ' ORGANIZATION,EXCEPT IN '«- Mex3meerpoerp6Vnrrnnt 90CFA 93}A Y.....,.. .0 .,._.. -..._m ., .,.............,.°a,e..e.9t.�....._ >_ .,.,,,,_..,,.,,,�.,. .<:a.�.._.-._.,......n_„_. ,.�...._..,... ... ._._..A ..........:.. CONNECTION WITH THE SALE AND Mode*efikletry 1- AO% t7-3t USE OF THE RESPECTIVE f: f t S 54266:ningirArranar{P,..1 tax ntr m 7uv Rhnntand 4 858 'SIC YaUOWJknt„fyy'_Arpi EQUIPMENT,WITHOUT THE ' I I I WRITTEN PERMISSION OF BLUE ft g PERFORMANCE AT BOO W/ms, OCTN ,AM 7,5 RAVEN SOLAR LLC 1 , i '[ r SWA2d5 WA 290 11 € € 1 4tex6eempe.tr -_ 8.;y aatwp awbwp NABCEP i [ I I, } openatvortge v.. )6,2V 36.6V n j I carrModnex partrpelavote a V..„, 24.5Y 119w CERTIFIED I Share e#rafte�nnt I. }gad I16A PV INSTALLATION 4 I811118.1081parerpretuntent L,, 727A TttA PROFESSIONAL I Mrrgt rtdsnct+4m in trttttoxy under portal load conditions et 2$`C:at ZOO WRm t.XXX 1«'3%1 at flit 66C ethaency POW WMsri it 7eetitved Scott Gurney I mnF r { ` - i 1. I #PV-01 1 71 9-01 5866 PARAMETERS FOR OPTIMAL SYSTEM INTEGRATION torn{ [s CONTRACTOR: I 1 I Arm:we owpf.Swp uo dam # Auatmumalm+wetecsta7Alct lvouv ``'�" BRS FIELD OPS -. Attaf Barr rrwrur.aam .SETA 1raf2 rl 385.498.6700 IWaoberdffypeusd2a►ld t _..._. apt 40to4e51 t106t r UM' .tw '°Nrre�k%l"tam * as r6eam b dail�nwbr�urystsr l• ttifpadownware.w pet uP«+ard - Pt2 OUP',ia4 QUALITY BY SOLARWOR .D AWrknwodefJp loads,taRe tea s itapddewnwara,Mpsfware* a�a�t) s4eav:.rnn mrw+.,rm ra:rr rt«ui•..mritu4awrt k.arerteln w.iskavawotnrwattays a .0018197, •, l' COMPONENT MATERIALS Solarwald`s foundation h buRt on mode than AO years of ongoing innovation,continuant optimization and technology expertise.All production stops Gorr rancor to module are astabllshtd at our production sites ensuring the highest possible quality for our customers,Out nodules coma in Ge'as rnOAWk .60 a variety o dift:at sites aid power,making thern suitable It(all global applications-horn residenti al solar systrons to large-scak power plants. [ekiypr ryuwimttftc r r. Ce9atmentbu o Ise 6inx6 t mi,N 156 rm.; - ! B. front Tenroerca safety glass Noah ARC(EN 12130) ® I o Sled Sl ALlin law IwlKner taekcMIda t be , frame 8cta^crhuM alunnuro 1leesnt arSthetAu de gn-entHely Hat solar module.ion $OlarWorkd EfWccOIF" V£Rt ter tedno{apyfo the highest 1,aea Ia65 the(Hit and tc WIN,maklr 5 POttitale l ds rya py,,,e NuiO3}xdh Mrphtnaiuntamrtc. iiimidmilimidimi rgy i. Extremely tough and Stable,despite cis light woghi-obit Patented corner design with integrated drainage to --- Atodult fife pnfonneece No 3 TSr a t .�+U t94 to handle loadtupto118 psi(ISLNATM optmtreedseftc(eaning ... -_,_._ _._.. .,_.. .. _ .�.._�_.._ T ,rd11111, Tested In extreme weather Cant/diem hail impact tested ._: High transmissive glass wthantitettcrtivecoating DIMENSIONS/WEIGHT THERMAL CHARACTERISTICS my and recusant to salt spray,frost,ammania,dust and sand "' tongiesm safety and guaranteed tap performance..- tiK7''}k I; .111111 III� Proven guarantee against hatspats and PE-4ee to 2h:year Irma'performance warranty,20-year product imp* e,SVS+n;u.rsm S) ItO[7 46Y 1 1 ,. lkL521l04-1 warranty WWI 39.40o,putt mml ►c t, OW It,1G 19.4 CWOfI - I!am(} orm MY .011NX 1io ia3} IVOttlt 357 lb 116Otrf{I TCp,,,, i3.39%A Ae units pooled aitnnptrial V eons prorated al parentheses i ORDERING INFORMATION CERTIFICATES AND WARRANTIES 044414e4401 Olsrrr#60# ICC 61774 ItE t1P15 IA r9.3., Cettfitati I !Zia 024i Svnrreottuk Plus SWA,t85 nexwbLxt IEC 62T16 IK6006&268 IEC t1R71 SS000aE0 5unmadukPkrs.SWA 290 mono blaek Wormntka, Roduet vtarramy 20 yarn ��nee linear heriontrinue Guariniee 25years .1+n+ww.••ww.ew o' MADE IN USA Yarraxe nerlteretues Prty ogram-we rntot,t tltroupn sahorsvmu r sssuro ut- OF to 68 888ni runt Wnnaray emeertvm P109mm-mmseWrnorditcnt6slurrnncr www.golarworkt-usa.con SWa,wocw ar,$rNat arc renown.the op to nuke ipesificanon rhanen wrinnut rasTN* t hn dara shwt conpsrswnh Mr rrgraeemimts ofi n!u:sillt SI EE--NAME SPEC SHEET PAGE NUMBER REVISION SS 0 1 BLUE RAVEN 4 3 2 1 1403 N RESEARCH WAY,BUILDING J _. _.�.. OREM,UT 84097 800-377-4480 W WW.BLUERAVENSOLAR.COM ITEM NO. PART NUMBER DESCRIPTION QTY. CONFIDENTIAL-THE INFORMATION JB-1 Bodyw/E-Z LOK POLYCARBONATE WITH UV HEREIN CONTAINED SHALL NOT BE 1 1 USED FOR THE BENEFIT OF TECHNOLOGY INHIBITORS ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE 2 JB 1 Lid w/Gasket POLYCARBONATE WITH UV 1 DISCLOSED IN WHOLE OR IN PART INHIBITORS TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, XCSAT IN 10-32 x 1" Phillips F CONNECTION WITH THE SALE AND 3 pan head bolt USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE B [86.66mm] • 4 #8 x 1-1/4" PhillipsWRITTEN PERMISSION OF BLUE 4 B RAVEN SOLAR LLC. 3.41 in pan head screw [41.37mm] e XABCEP 1.631n -. CERTIFIED ���� 15 20 lbs-in PV INSTALLATION Torque Specification: PROFESSIONAL Certifications: ULStandard 1741, NEMA3R ScottGNR,ey / ` #PV-011719-015868 _ Weight (LBS): 1.3 lbs CONTRACTOR: •304.80mrrI �� +- -+ �` [ ] 1 198.37mm BRS FIELD OPS 12.00in I 7.81 in 385.498.6700 — I I I EZ Solar [24.81mm] SLC, UT USA .98in Phone (385) 202-4150 f [77.09m ] _ www.ersolarproducts.com A 3.04in A LNLESS OTHERWISE SPECIFIED' NAME DATE [183.97mm] DIMENSIONS ARE IN INCHES DRAWN 7 nIn TOLERANCES: CHECKED TITLE: L'+ - FRACTIONAL! ANGULAR:MACH± BEND'- ENG APPR. [266.70mm] TWO PLACE DECIMAL ± EZ SOLAR THREE PLACE DECIMAL ± MFG APPR. 10.50i n IMERPRET GEOMETRIC Q.A. PROPRIETARY AND CONFIDENTIAL TOLERANCING PER: COMMENTS' THE INFORMATION CONTAINED IN THIS - . - MAMMAL -..SIZE IDWG. NO. REV DRAWING 15 THE 50LE PROPERTY OF REPU. B J B-1 REPRODUCTION IN PART OR AS A WHOLE F wSH WITHOUT THE WRITTEN PERMISSION OF NEXT ASSY USED ON <INSERT COMPANY NAME HERE>IS •----- PROHIBITED. APPLICATION DO NOT SCALE DRAWING SCALE: 1:2 WEIGHT: SHEET 1 OF 3 4 3 2 1 SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0 Nor 4 3 2 1 BLUE RAVEN [170.73mm] 6.72in 1403 N RESEARCH WAY,BUILDING J OREM,UT 84097 [19.81 mm] y [55.89mm] ,F 0.78in 2.20in 800-377-4480 V WWV.BLU ERAVENS OLAR.CO M CONFIDENTIAL-THE INFORMATION -------\\ ... HEREIN CONTAINED SHALL NOT BE USED[57.94mm] _ ANYONE OXCEP R THEBENEFIT IRAVEN 2.281n SOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS B / B ORGANIZATION,EXCEPT IN 12.42mm CONNECTION WITH THE SALE AND _A ��� [ ] USE OF THE RESPECTIVE �p3p M� FJ 0.49in EQUIPMENT,WITHOUT THE [60 0261n ] rO/ /?) 8 ��\EIP. (\ / {/ / ///// WRITTEN PERMISSION OF BLUE `Y �� �1 1 RAVEN SOLAR LLC. t •'% / NABCEP __ CERTIFIED IN INSTALLATION [15.88mm] PROFESSIONAL [304.80mm] 0.625in ® � A lJ ® scat PROFESSIONAL 12.00in uPv-01n19-016866 [50.80mm] _ [175.61 mm] 2.00in BRS FIELD OPS 6.91in 385.498.6700 [9.53mm] \Yl' • IJ 0.38in A N [5.55mm] 0.22in ._ SECTION A-A SCALE 1 : 1 Indent L57.94mm] A j - [266.70mm] - 2.28in A 10.50in UNLESS OTHERWISE SPECIE:ED: NAME DATE DIMENSIONS ARE IN INCHES DRAWN TOLERANCES: I ,I— ___1_ FRACTIONAL± CHECKED TITLE: ANGULAR:MACH± BEND ENGAPPR EZ SOLAR 4.... Two PLACE DECIMAL ± THREE PLACE DECIMAL ± MFG APPR. --- - -- INTERPRET GEOMETRIC OA PROPEIETAIY AND CONFIDENTIAL TOLERANCING PER _ _--- THE INFORMATION CONTAINED INQHD MATERIAL -- --COMMENTS: - DRAWING DRAWING IS THE SOLE PROPERTY OF SIZE DWG. NO. REV ANY LAR.REPRODUCTION -. - B JB-1 -- NEM ASSY-- USED ON -_-� - ANY REPRODUCTION IN PART FINISH ORASS WHOFE WIT ZSOLAE THEPWRITTEN PERMb510N OF EZ SOLAR IS PROHIBITED. --P- _'-- APPLICATION DO NOI SCALE DRAWING SCALE: 1:2 WEIGHT: SHEET 2 OF 3 4 3 • 2 i1 SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0 BLUE RAVEN 4 3 2 1 __ 1403 N RESEARCH WAY,BUILDING J _ _ OREM,UT 84097 v-._—!— 800-377-4480 • • 1 N V W.BLUERAVENSOLAR.COM CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE • USED FOR THE BENEFIT OF • ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE OUTSIDE INSIDE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND i USE OF NT, RESPECTIVE SECTION A-A B SCALE 1 :2 A f B WRITTEN PERMISSION OF BLUE RAVEN SOLAR LLC. / � BC E P �� r �1 CERTIFIED 101 I ` ` PV INSTALLATION _ PROFESSIONAL /" Scott Gurney V C' 1. �' #PV-011719-015868 / \ : CONTRACTOR: f B385.498.6700RS 1ELD S [198.37mm] 7.81 in JII_ b.........4 • j..„ [3.18mm] I .13in LID OVERHANG A+ [183.97mm] [22.23mm] 7.24in '88In A A '.: UNLESS OTHERWISE SPECIFIED: NAME DATE ---- DIMENSIONS ARE IN INCHES DRAWN TOLERANCES: TITLE: -- FRACTIONAL! CHECKED ANGULAR:MACH! BEND± ENG APPR. TWO PLACE DECIMAL ± EZ SOLAR THREE PLACE DECIMAL - MFG APPR. INTERPRET GEOMFTRC G.A. PROPRIETARY AND CONFIDENTIAL TOLERANCING PER; COMMEN'S: THE INFORMATION CONTAINED IN THIS MATERIAL SIZE DWG. NO. REV DRAWING IS THE SOLE PROPERTY OF EZ SOLAR.ANY _. _._..__. _ B JB-1 REPRODUCTION IN PART OR AS A WHOLE FINIS I WITHOUT THE WRITTEN PERMISSION OF NEXT ASSY USED ON <INSERT COMPANY NAME HERE.6 --- - PKII- tED. A=PUCATON DO NOT SCALE DRAWING SCALE: 1:2 WEIGHT: SHEET 3 OF 3 4 3 2 1 SHEET NAME SPEC SHEET PAGE NUMBER REVISION SS 0 sFm al SUNSYSTEM BONDING & GROUNDING ; •� y BLUE RAVEN RA*MEy■�)■{ 1403 N RESEARCH WAY,BUILDING J �� IICRORA L INSTALLATION GUIDE PAGE OREM UT 84097 800-377-4480 WWW.BLUERAVE NSOLAR.COM NFIDENTIAL-THE MATION I' ll __I-Ill II —w �'*� H I Ilk , _ - EEREIN CONTAINED SHALL NOT BE L 6 i—T— // USED FOR THE BENEFIT OF USED EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE I " DISCLOSED IN WHOLE OR IN PART (' I I ''T' TO OTHERS OUTSIDE RECIPIENTS l ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND tkw ® USE OF THE RESPECTIVE ry -- WRITTEN BLUE EQUIPMENT,WITHOUT THE �! IOC'�' � TTEN PERMISSION OF I, :. .. # ,... I111 , RAVEN SOLAR LLC. I I I �` 4. NABCEP I I � : CERTIFIED I 1 -, PV INSTALLATION ,. —.=r I E-W BONDING PATH: PROFESSIONAL I E-W module to module bonding is accomplished Scott Gurney #PV-011719-015866 i i with 2 pre-installed bonding pins which engage CONTRACTOR I : on the secure side of the MicrorailTM and splice. BRS FIELD OPS 1 I I I 385.498.6700 11 1 l 1 1 1 1 1 i 1 1J , 1 . . 1 ' 1 1 , a 7 I I I I I I I I I i I I t 1 I I I I i I I I 1 1 1 I I 1 I 1 I I I l �'�. I 1 I 1 [ J 1 I I � � I" star4 washer WEEBLLIC :- N-S €nate i BONDING PATH: TERMINAL TORQUE„ Ili N-S module to module bonding is Installnductorand accomplished with bonding clamp with 2 integral torque to the fotloww?ng: TERMINALTORQUE. TERMINAL TORQUE, bonding pins. ,, :,{ . ,. , �pw- 4-6 AMC.351n7ltrs istatt Conductor and Install Conductor and &AWG. 25 In•11;s P1Ique to the following: torque to the following: 10-14 AWG.20 in-,L: .14 AWG: 35"an-lbs 6.14 ANAL_7ft•tbs 40 I LUG DETAIL& TORQUE INFO LUG DETAIL & TORQUE INFO LUG DETAIL & TORQUE INFO o► '. Iisco Lay-In Lug (GBL-4DBT) Ilsco Flange Lug(SGB-4) Wiley WEEBLug (6.7) - • 10-32 mounting hardware • 1/4"mounting hardware • 1/4"mounting hardwareOM O, MN j ,a • Torque = 5 ft-lb • Torque = 75 in-lb • Torque = 10 ft-lb F�, ,. r;stid , `- j • AWG4-14-Solid or Stranded • AWG 4-14-Solid or Stranded • AWG 6-14-Solid or Stra nded TRIMRAIL BONDING PATH: NOTE: ISOLATE COPPER FROM ALUMINUM CONTACT TO PREVENT CORROSION Trimrail to module bonding is accomplished with System bonding is accomplished through modules.System grounding accomplished by attaching bonding clamp with integral bonding pin and a ground lug to any module at a Location on the module specified by the module manufacturer. bonding T bolt. ET NAME t t. ,1, k "a od } SHE SPEC SHEET PAGE NUMBER REVIS ON SS 0 \Or' tntertek AUTHORIZATION TO MARK BLUE RAVEN Total Quality.Assured. __.___._. . ._._. _..._.._ ...... . .. __ _ .. 1403 N RESEARCH WAY,BUILDING J This authorizes the application of the Certification Mark(s) shown below to the models described in the Products) OREM,UT 84097 Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also apples to multiple listee model(s) iderrtdiect on the correlation page of the Listing UERAVENSO imnprtortrr4t VWWV.BLUERAV-4480 R.COM R "' ' CONFIDENTIAL-THE INFORMATION HEREIN CONTAINED SHALL NOT BE This document is the properly of Intertek Testing Services and is not transferable. The certdication marks) may be USED FOR THE BENEFIT OF applied only al the location of the Party Authorized To Apply Mark. ANYONE EXCEPT BLUE RAVEN SOLAR NOR SHALL IT BE .. .. _... _ DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS Applicant: Unirac, Inc Manufacturer: Cixi Eureka Aluminum Co. Ltd ORGANIZATION,EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT,WITHOUT THE 1411 Broadway Blvd NE No,688 ChaoSheng Road WRITTEN PERMISSION OF BLUE Address: Abuquerque, NM 87102 Address• CIXI City RAVEN SOLAR LLC. Zhejiang Province 315311 Country: USA Country: China NABCEP Contact: Klaus Nicolaedls Contact: Jia Liu CERTIFIED Tom Young Robin Luo PV INSTALLATION 505-462-2190 +86-15267030962 PROFESSIONAL Phone: 505-843.1418 Phone: +86-13621785753 Scott Gurney 17l #PV 6 FAX: NA FAX: NA CONTRACTOR: klaLls.rri cola edis@un',rac.eom jia.i u@ m BRS FIELD OPS cxymj.co Email: toddg@unirac.com Email: buwan.luo@cxym j.c;om 385.498.6700 Party Authorized To Apply Mark: Same as Manufacturer Report Issuing Office: Lake Forest, CA U.S.A. J�I Control Number: 5003705 Authorized by: ILClTMti. for Dean Davidson,Certificali anager u5 u.iry Intertek This document supersedes all previous Authorizations to Mark for the noted Report Number.. I M h/I1Vln+als.;to Men le I.fur e+M1:s+:Cm III McArd.'a Gene erg lap 6r6b p/MIYe to M CMlpllon ereeemre tlpempn Inlellm enwl 01.tame Ydrer,10.is.axrat+h erg i:et.Llr:>•+' rnlec74h is-ftW cuoem,artne Ms1M num.ra 5Walr 1a urn RIM.utka MP as IM Casa tierJ7Plionceoath IN eplsalen.berry ba a mote,a derWeucam+:.•t try On um;VI eel b lam Only 1.o GIgMV•d,Tied Ia0OIrI e0ONq a dW4MIIRd IN0 kolhonignx,F Irpi.a,diton0llrn.rarely UiC 0 Iririk'e Ctessicskr me," near W Ia the amdllrte WO ow In Cre wean**and el its h lmlaEa,Ia 44ak Mr(IAII se al to Mina lame Sr ale ere a eelMeearmaz 0 Or Mpg mlelerlel.podia a remce r'.:u Aral M MPOrmea N oriKp IM Inpren Inoe F IIL#y Aylmasrwn a nr.n ediw.Imp MMEae SWIM'4 WPM a a>lftauq appaoaa uP d Ito GI•teeam net le eR'Pmr*eun tne Apreem en^_Try Mara la k perpeme a plam+am g,roily meta xl.d m nG reiawe ea 17pe CO MIN ampalan In RMe repee. Intertek Testing Services NA Inc_ 545 East Algonquin Road,Arlington Heights,IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Stttrldard(s): Mounting Systems. Mounting Devices. ClampingfRetention Devices, and Ground Lugs for Use with Flat- Plate Photovoltaic Modules and Panels[UL 2703:2015 Ed.11 Photovoltaic Mounting System, Sun Frame Microrail- Installed Using Unirac Installation Guide, Rev Product: PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20 Brand Name: Unirac Models: Unirac SFM SHEET NAME SPEC SHEET ATM tor Report 102393982LAX•002 Page 1 of 1 ATM Issued:9-Apr-2019 PAGE NUMBER REVISION ED IS 3 15 I2Mpt-171 laudatory SS 0 i BLUE RAVEN OM SYMEsFm F ' 1403 N RESEARCH WAY,BUILDING J le II MICRORAILN _ __ INSTALLATION GUIDE 1 PAGE OREM,UT 84097 800-377-4480 WWV W.B LU E RA V E N S O LA R.C O M CONFIDENTIAL-THE INFORMATION ' ;; ft 1 HEREIN CONTAINEDFOR DENEFI NOT BE OP' INSTALL SLIDERS ANDC USED FOR THE BENEFIT OF V ROOF ATTACHMENTS: ANYONE EXCEPT BLUE RAVEN 10111110„, ter/ SOLAR NOR SHALL IT BE _/ -'-� �:=� Follow manufacturer instructions UP-SLOPE DISCLOSED IN SE E IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION,EXCEPT IN ► �� _ for flashing installation procedures CONNECTION WITH THE SALE AND �' t USE OF THE RESPECTIVE � mom, EQUIPMENT, RESPE TTHE , . WRITTEN PERMISSION OF BLUE irkA IRAVEN SOLAR LLC. :A - \ • �'' :_ �BCEP CERTIFIED ._ PV INSTALLATION PILOT HOLES: FLASHINGS: PROFESSIONAL _. Scott Gurney Drill pilot holes for lag screws or Place flashings Mod NS+ 1" #PV-0,27,9-0,5866 structural screws (as necessary) at — RS HELD OPS ! CONTRACTOR: marked attachement points B385.498.6700 • • • • i .- 4� `—, IF '� 1 NOTE if N- module edge is within Vet the • shingke tootle above,you have the option to A p#vest r rotate slider at the attachment point • • • • • - tc span the next COW 5g and cut shingtes as/ required. ''*.k cut sh,ogles as Required I `` II r___�_•t Mod NS + 1• -`�-- may' : "y ieatt«te alder I INSTALL SLIDERS AND TRIMRAIL ROOF ATTACHMENTS: at.• Onott= r _ _ >r • Insert flashings per manufacturer instructions "" -LessThart t " -y.. - �' G"--'" :f '3 XIMUIT1 diameter of /1 " � _ • Attach sliders to rafters _ pa� I _ • Verify proper row to row spacing for module size (Mod NS+ 1") ; '` Y I • Ensure that TrimrailTM roof attachments in each row have sufficient I I engagement with slider dovetails for proper attachment. Oteeltit DOWN-SLOPE SHEET NAME I, I I ' 5r SPEC SHEET PAGE NUMBER REVISION SS 0