Report FPS201/-000 6 0 12550 S'tJ r3SIth g(/1" r June 17, 2011 u r RE: FIRE SPRINKLER SYSTEM City of Tigard -Project Information Building Permit: FPS2011-00060 Construction Type: 5-B Tenant Name: Wilde Residence Occupancy Type: SR-4 Address: 12550 SW 134th Ave. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2010 edition; National Fire Protection Association, Standard 13R. GENERAL 1. All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored when the system serves more than 20 heads. Section 903.4 OSSC • 2. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water-flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OSSC 3. New sprinkler system piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for two hours. Where addition or modification is made to an existing system affecting less than 20 sprinklers this test need not be done. UNDERGROUND 4. The fire service mains shall be completely flushed. The flow rate shall not be less than a velocity of 10 feet/second. 5. All piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for 2 hours. The test pressure shall be read from a gauge. Section10.10.2.2.1 NFPA 24. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC • When submitting revised drawings or additional information, please attach a copy of the City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard M t, in tracking and processing the documents. 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.639.4171 TTY Relay: 503.684.2772 • www.tigard-or.gov M } Respectfully, Dan Nelson, Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov • ES-A-3000E-FP • Series 3000B-FP A M E S Double Check Detector Assembly FIRE&WATERWORKS Sizes: 2" (50mm) • i° 2"(50mm) 30008-FP Features Series 3000E-FP Double Check Detector Assembly is designed exclusively for use in accordance with water utility authority containment requirements. It is mandatory to pre- • Bronze body vent the reverse flow of fire protection system substances,i.e.,glycerin wetting agents, • Replaceable seats and discs stagnant water and water of non-potable quality from being pumped or siphoned into the • Maximum flow at low pressure drop potable water line.The Series 3000E-FP is ideal for use on non-health hazard fire protection Compact for of installation systems to detect leaks or unauthorized water usage. •• Design simplicity for easy maintenance Modular check design concept facilitates maintenance and assembly access.All sizes are standardly equipped with resilient seated gear operated slow close isolation valves and • No special tools required for servicing 5/8"x 3/4"(16 x 19mm)meter. • Bronze body ball valve test cocks • Modular spring loaded checks Specifications • Furnished with bronze We"x 3/4" A Double Check Detector Assembly shall be installed on fire protection systems when (16 x 19mm)meter connected to a potable water supply.Degree of hazard present is determined by the • Gear operated,slow close shutoffs local authority having jurisdiction.The backflow preventer shall be a complete assembly including UL listed gear operated slow close main line isolation valves and four test cocks. • Pre-wired tamper switch(2) The assembly shall consist of two independently operating modular poppet-type check valves.The check valves shall utilize captured springs and shall have replaceable seats. The checks shall be double-guided,both along the outside edge of the check module and through the center stem assembly.The seats shall be replaceable without the use of spe- cial tools.Seat retention shall be done by the use of an interlocking bayonet-style cage and the use of threaded seats or seat screws is prohibited.Access to the internal check assemblies shall be via a single top entry cover.The cover shall be securely held in place by stainless steel bolts.The assembly shall include an auxiliary bypass line consisting of an approved backflow preventer and water meter. The acsPmbly shall be listed or approved under the requirements of ASSE Std. 1048, AWWA Std.C510 and CSA 864.5.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.The assembly shall be an Ames Company Series 3000E-FP. Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. - Approval_ Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Pies Technical Service.Ames reserves the right _ to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Available Models Pressure — Temperature " Suffix: Suitable for supply pressure up to 1 75psi(12.06 bar) - LM - less meter Water temperature at 110°F(43°C)continuous. CFM - cubic feet per minute meter GPM - gallons per minute meter Standards FP- UL approved slow close ball valves AWWA Standard C510-92 CSA B64.5 Materials IAPMO PS 31 • Bronze body • Durable tight seating silicone discs Approvals • Stainless steel springs G4pssipio • 5/a"x 3/4" (16 x 19mm)bronze bypass meter C le US Capacities 1048 *UL Rated Approved by the Foundation for Cross-Connection Control kPa psi 2a * and Hydraulic Research at The University of Southern 110 16 I California. cg3 12 Horizontal and Vertical °Flow Up" approval on all sizes. -I 69 10 o55 8 :x* 8 41 6 28 4 0.. 14 2 0 0 AP 0 20 40 60 80 100 120 140 160 180 gpm 0 76 152 228 304 380 456 532 608 684 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate - Dimensions — Weights Top View 17141111 ul_ll'�11' 111 Iui! Ii •,. .Ill pt,i.1 .. ��s 1Msys ,•Ili41# rLI ` — , B �, ,we ,., ill r0O■I:� ilomi "iitl7l') . '■' 42=a1:;,:<la /' I II—•1� 111 r�—il■Li' Ai— 4 A ..11_li-7i-4„1'l. • il_yn. Ili. I MODEL SIZE(DN) DIMENSIONS WEIGHT A A B C D E F G H in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 3000E-FP 2 50 306 486 6% 165 4% 108 2% 54 13343 340 15% 397 2%3 73 3% 92 19/ 495 44.1 20 IMPORTANT:Inquire with governing authorities for local installation requirements. __ Aoaauq ., - A M E S `•. " I9001-2008 FIRE&WATERWORKS www.am esfirew ater.com �- - cE NTI FIED A Watts Water Technologies Company USA: Backflow- Sacramento,CA•Tel.(916)928-0123•Fax(916)928-9333 Control Valves- Houston,TX•Tel.(713)943-0688•Fax(713)944-9445 Canada: Burlington,ONT.•Tel.(905)332-4090•Fax(905)332-7068 ES-A-30006-FP 1041 0 2010 Ames Fire&Waterworks Bulletin 006 Rev.D ® Model RFC43 (SIN RA0612) W _ eMod "e( RFC49 (SIN'RAO6? " Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a ' . minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1 . Very low water flow requirements. • " 1 �� 'i 2. /z (13mm) Total adjustment. ilk a 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. m Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada(cULus) 2. NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC43 and RFC49 Concealed Residential Sprinklers The RFC43 and RFC49 are UL Listed Residential Sprinklers are fast response residential fusible solder link automatic to be installed in the residential portions of any occupancy in sprinklers. Residential sprinklers differ from standard accordance with NFPA 13, 13R, & 13D. sprinklers primarily in their response time and water The RFC43 and RFC49 can reduce the need for precise distribution patterns. cutting of drop nipples. The threaded cover plate assembly I Model RFC43 and RFC49 sprinklers discharge water in a can be adjusted without tools to fit accurately against the hemispherical pattern below the sprinkler deflector. ceiling. The fire protection system need not be shut down to Residential distribution patterns are higher and generally adjust or remove the cover plate assembly. contain a finer droplet size than standard sprinkler patterns. The combination of speed of operation and high discharge Application and Installation pattern required for residential sprinklers has demonstrated, The RFC43 and RFC49, for residential installations, use a in fire testing, an ability for controlling residential fires, and 165°F(74°C)fusible solder link in a tuning fork style sprinkler thereby providing significant evacuation time for occupants. frame with a drop-down deflector. This assembly is recessed The RFC43 and RFC49 Sprinklers provide the best form of into the ceiling and concealed by aflat cover plate. The cover fire protection by combining an attractive appearance and plate is attached to the skirt, using 135°F (57°C) ordinary - 1'(13mm)of cover adjustment for ease of installation. The temperature classification solder. When the ceiling small diameter cover plate is easily and positively attached temperature rio ,the solder holding the cover plate releases and blends into the ceiling,concealing the most dependable the cover allowing the deflector to drop into position and fire protection available, an automatic sprinkler system. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 exposing the sprinkler inside to ceiling temperature. The should be taken to prevent damage to the sprinkler. DO NOT subsequent operation of the solder link opens the waterway WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP and cap ises the deflector to drop into position to distribute the ASSEMBLY. MODEL RFC43 AND RFC49 CONCEALED discharging water in a hemispherical pattern below the SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F sprinkler deflector. Any adjustment of thread engagement RATED COVERS. between the cover plate and cup will assure that the Cover assemblies provide up to l" (13mm) of drop-down deflector is properly located below the ceiling. adjustment. Turn the cover clockwise until the flange is in >• The residential distribution pattern contains a finer droplet size contact with the ceiling. For the push-on/thread-off option, than a standard sprinkler, and the pattern produces the cover assembly is pushed onto the cup and final significantly higher wall wetting. adjustment is made by turning the cover clockwise until the After a 2 5/8 inch diameter hole is cut in the ceiling, the skirt flange makes full contact with the ceiling. Cover sprinkler is to be installed with the Model FC Wrench. When removal requires turning in the counter-clockwise direction. installing a sprinkler, the wrench is first positioned into the In ceilings that have a plenum space above the sprinkler, sprinkler/cup assembly and around the hexagonal body of the plenum space may have neutral or negative the sprinkler frame. The Wrench must bottom out against the pressurization but must not be positively pressurized. Inspect cup in order to ensure proper,safe installation. The sprinkler all sprinklers after installation to ensure that the gap between is then tightened into the pipe fitting. When inserting or the cover plate end ceiling and the 4 slots in the cup are all removing the wrench from the sprinkler/cup assembly, care open and free from any air flow impediment. Temperature Rating Sprinkler Cover Plate Max.Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC43 (SIN RA0612) Minimum Required Sprinkler Maximum Minimum Sprinkler Discharge Thread Size K inch Size nm) Factor Spacing Distance Distance between ft.(m) to Wall ft.(m) sprinklers,ft.(m) Flow Press. gpm(Lpm) psi(bar) - 1 "(15mm) 4.3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54) 1/2"(15mm) 4.3 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63) /"(15mm) 4.3 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 9.1 (0.63) h"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(1.21) %"(15mm) 4.3 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 21 (79) 23.8(1.64) Note: 1 bar = 100 Kpa Installation Data: RFC49 (RA0616) Minimum Required Thread Size K Sprinkler Maximum Minimum Sprinkler Discharge inch(mm) Factor Spacing Distance Distance between ft.(m) to Wall ft.(m) sprinklers,ft.(m) Flow Press. gpm(Lpm) psi(bar) Y2"(15mm) 4.9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) I 13(49) 7.0(0.48) 1"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48) I 1"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83) Y"(15mm) 4.9 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 20(75.7) 16.7(1.14) Note: 1 bar= 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 2. Maintenance Model RFC43 and RFC49 Concealed Sprinklers should be 135°F(57°C). Cover plate assembly shall consist of a brass _ inspected quarterly and the sprinkler system maintained in cover plate and copper alloy retainer flange allowing a '/2" accordance with NFPA 25. Do not clean sprinklers with soap cover plate adjust Went. Any secure engagement between i. and water, ammonia or any other cleaning fluids. Remove the cover plate and the cup will .ssure that the drop-down dust by using a soft brush or gentle vacuuming.Remove any deflector is properly located below the ceiling. A plastic sprinkler cover plate assembly which has been painted(other protective cap shall be provided and factory installed inside than factory applied) or damaged in any way. A stock of the sprinkler cup to protect the drop-down sprinkler deflector spare sprinklers should be maintained to allow quick from damage,which could occur during construction before replacement of damaged or operated sprinklers. Prior to the cover plate is installed. Standard cover finish: [Chrome] installation, sprinklers should be maintained in the original [White][Specialty-specify]. Residential concealed sprinklers cartons and packaging until used to minimize the potential for shall be Reliable Model RFC43,SIN RA0612(Bulletin 006)or damage to sprinklers that would cause improper operation or Model RFC49, SIN RA0616(Bulletin 006). non-operation. Model RFC43 and RFC49 Residential Ordering Information Cover Plate Finishes(", Concealed Sprinkler Specification Specify: Standard Finishes Sprinklers shall be cUl us Listed low flow residential 1. Sprinkler Model Chrome concealed sprinklers with drop-down deflector and 2. Cover Plate Finish White adjustable flat cover plate engineered for a minimum design 3. Thread-On or density of 0.05 gprrt/fe. Sprinkler frame and deflector shall be Special Application of bronze frame construction having a 1/2" NPT thread. Push On Feature Finishes Thermal element shall consist of an approved black-painted Bright Brass beryllium-nickel fusible solder link with symmetric lever Black Plating mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly Black Paint containing no plastic parts. Sprinkler K-factor shall be nominal Off White 4.3(62.4), having a 7/16"orifice.Temperature rating shall be Satin Chrome Ordinary 165°F(74°C); cover plate temperature rating to be i"Other colors and finishes available. Consult factory for details. Note: Paint or any other . coatings applied over the factory finish will void all approvals and warranties. 1" x 1/2" REDUCING I TEE OR ELBOW ll T- .--T-- 1 r 21 (66.7mm] VIA. nil 24" [58.7mm] DL4 - L. -J HOLE IN CEILING CUP . _ : , ';`'. a frill! 2"(50.8mm] MAX, h1FAC£ OF FIITJNG ' -_ TO FACE OF CEILING DIMENSION ii..ia CEILING �...../ i" (12.7mm] MAX. I I 0� COVER ADJUSTMENT " DM. 3/15" 311 COVER PLATE [84.1mm] [4.8mmj .1300K , ASSEMBLY SPRINKLER mvmr COVER PLATE: 1/2" [12.7mm] ADJUSTMENT 3. Reliable. . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Supertrol electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gauges • Electrical sprinkler alarm switches • Identification signs • Water flow detectors • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation.or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable. Products manufactured and distributed by RELIABLE have been protecting lite and property for over 80 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. - Manufactured by. The Reliable Automatic Sprinkler Co.,Inc. Recycled Paper I1 IIa UI e (800)431-1588 Sales Offices (800)848�051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate uppdated or new data www.reliablesprinkler.com Internet Address E G.Pr feted in USA. 12l08 PIN 9999970261 Bulletin 135 Rev. H Ell ®le Model F1 * Rehab 5 Residential Sprinklers for cT Design Density of .05 gpm/ft2 Model Fl Res Sprinklers engineered for the lowest flows - to meet the minimum design density of.05 gpmffr Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed Pendent/F2 3. Fl Res 30 Recessed Pendent/FP F1 Res 30,49,58&76 F1 Res 30, 49, 58&76 4. F1 Res 49 Pendent Recessed Pendent/F1 Recessed Pendent/FP 5. F1 Res 49 Recessed Pendent/F1 6. F1 Res 49 Recessed Pendent/FP 7. F1 Res 58 Pendent f' 8. F1 Res 58 Recessed Pendent/F1 ` 9. F1 Res 58 Recessed Pendent/FP • 10. F1 Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. F1 Res 76 Recessed Pendent/FP 13. F1 Res 30 CCP Pendent F1 Res 30,49,58&76 F1 Res 44&58 14. F1 Res 49 CCP Pendent CCP Pendent Recessed HSW/F2 15. F1 Res 58 CCP Pendent 16. F1 Res 76 CCP Pendent 17. F1 Res 44 HSW f ; 18. F1 Res 44 Recessed HSW/F2 19. F1 Res 58 HSW 20. F1 Res 58 HSW Recessed HSW/F2 21. F1 Res 44 SWC Fl Res 44 SWC Listings &Approvals The 3mm glass-bulb pendent sprinklers permit the effi- 1. Listed by Underwriters Laboratories Inc.and cient use of residential water supplies for sprinkler cover- UL Certified for Canada (cULus) age in residential fire protection design. 2. NYC MEA 258-93-E The low flow F1 Res sprinklers are specially engineered Slope Ceiling Approvals: Refer to Bulletin 035 for fast thermal response to meet the sensitive fire protec- Sprinklers for .10 Density: Refer to Bulletin 176 tion application needs of the latest residential market stan- dards (UL 1626 Standard). Upon fire conditions, rising UL Listing Category heat causes a sprinkler's heat-sensitive glass-bulb to shat- Residential Automatic Sprinkler ter,releasing the waterway for water flow onto the deflector, UL Guide Number evenly distributing the discharged water to control a fire. VKKW Technical Data: Patents • Thermal Sensor: Nominal 3mm glass-bulb US Patent No. 6,516,893 applies to the • Sprinkler Frame : Brass Casting Model F1 Res 49&58 Pendent Sprinklers • Sprinklers' Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi -_ Product Description • Thread Size: 1/2" NPT(R1/2) Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are • K-Factor: 3.0(Actual) - F1 Res 30 Pendent Sprinkler fast response sprinklers combining excellent durability, 4.9(Actual)-F1 Res 49 Pendent Sprinkler high sensitivity glass-bulb and low profile decorative de- 5.8 (Actual)-F1 Res 58 Pendent&HSW Sprinkler sign. The F1 Res Horizontal Sidewall sprinklers(Figs. 5, 6 7.6(Actual)-F1 Res 76 Pendent Sprinkler _ - & 7) are equally attractive when above ceiling piping can- 4.4(Actual)-F1 Res 44 HSW Sprinkler not be used. • Density: Minimum 0.05 gpm/ft2 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Installation - Model F1 Res Sprinklers are used for Residential Fire Pro- Models F1 Res sprinklers are to be installed as shown. _ tection according to UL 1626 Standard*. Be sure that ori- Model F1, F2 and FP Escutcheons, illustrated herewith, fice size, temperature rating, deflector style and sprinkler are the only recessed escutcheons to be used with Model type are in accordance with the latest published standards F1 Res sprinklers. Use of any other recessed escutcheon of The National Fire Protection Association or the approving will void all approvals and warranties. For installing Model authority having jurisdiction. F1 Res Pendent sprinklers use only the Model D sprinkler • Model Fl Res 30 Recessed Pendent/F2 • Model Fl Res 30, 49, 58 &76 Pendent • Model Fl Res 49, 58 &76 Recessed Pendent/Fl ° ate. F1 escutcheon, 3/4" (19mm) adjustment r "- ` ...- 2 r/4'l ^)DK .j _I _I__ �. —1 115/16"DK� -- 109.4mm1 1 r�. Y�- , I. ] Y /]OEIXKER \ TURN MOP UNTO I ' TIGHT AGUNST 51,1WCCN -- IYRfNCn 9JST. F i 1 P ' 6=1 lli _FACE-,f/TTWG Tt1 l4WC lFMN9Cn' —am �y/i/ — J/r /le(FI E CUrcecoN) ,----� J/Ifi-1./ifi(FS LSL11IrHEJNi ..l . I, III, 1L - 11� tip i_ I • I35FG02A - a 27/32-ON. 135FG03 In m,m7 Fig. 1 Fig. 2 Wrench; for installing Models F1 Res Recessed Pendent, Escutcheon*, Fl or F2, Data: CCP& SWC sprinklers use only the Model GFR2 sprinkler Face of fitting • wrench; for installing Model F1 Res Recessed HSW sprin- Type Adjustment "A" to ceiling klers use only the Model GFR2 Sprinkler Wrench. Use of Inch(mm) Inch(mm) Inch(mm) wrenches other than those specified may damage these Min.=5/4"" (19.1) 3/,e- t5/1s -- sprinklers. Install F1 Res 44 with a ceiling to deflector dis- F1 3/4(19.0) Max.-1'/"(38.1) (4.7-24.0) tance of 4" - 12". Flow arrow on deflector must point away Min.='she"(23 8) She "/e from near wall and"Top" marking must face ceiling. F2 1/2(12.7) Max.=1'h"(38.1) (4.7- 17.4) *Note:Escutcheons F1 or F2 may be used with Model F1 Res 49,58&76 Recessed Pendent Sprinkler 2. Technical Data: F1 Res 30 Pendent and Recessed Pendent Thread Nominal Orifice Sprinkler Max Max. Actual Sprinkler Size Inch(mm) Temp.Rating Pressure Ambient Temp. K Length it °F °C psi(bar) °F °C Factor Inch(mm) /z(RN jT 68 21/sa"(8.2) 155 175 7g 175(12) 100 38 3.0 2.25(57) I Deflector-to-ceiling Maximum 1"(25mm)to 4"(100mm) Max. Flow Pressure Sprinkler Identification Sprinkler Spacing gpm(Lpm) psi(bar) Number(SIN) ft(m) 12 x 12(3,6 x 3,6) 8(30.3) 7.0(0,48) R3511 14 x 14(4,3 x 4,3) 10(37.8) 11 (0,76) Technical Data: F1 Res 49 Pendent and Recessed Pendent. Thread Nominal Orifice Sprinkler Max. Max. Actual Sprinkler Size Inch(mm) Temp.Rating Pressure Ambient Temp. K Length °F °C psi(bar) °F °C Factor Inch(mm) Y"NPT 155 68 100 38 (R'/z) '/t5"(11) 175 79 175(12) 150 66 4.9 2.25(57) Deflector-to-ceiling Deflector-to-ceiling Maximum 1"(25mm)to 4"(100mm) Maximum 4"(100mm)to 8"(203mm) Max. Max Sprinkler Sprinkler Sprinkler Flow Pressure Sprinkler Flow Pressure Spacing gpm(Lpm) psi(bar) Identification Spacing gpm(Lpm) psi(bar) Identification ft(m) Number(SIN) ft(m) Number(SIN) 12 x 12(3,6 x 3,6) 13(49) 7.0(0,48) 12 x 12(3,6 x 3,6) 15(57) 9.4(0,65) 14 x 14(4,3 x 4,3) 13(49) 7.0(0,48) 14 x 14(4,3 x 4,3) 16(60.5) 10.6(0,73) 16 x 16(4,9 x 4,9) 13(49) 7.0(0,48) R3516 16 x 16(4,9 x 4,9) 17(64.3) 12.0(0,83) R3516 . 18 x 18(5,5 x 5,5) 17(64.3) 12.0(0,83) 18 x 18(5,5 x 5,5) 19(72) 15.0(1,0) 20 x 20(6,1 x 6,1) 20(75.7) 16.7(1,14) 20 x 20(6,1 x6,1) 22(83.2) 20.2(1,4) `Note:The F1 Res 49 pendent and recessed pendent residential sprin- klers can be installed per NFPA 13 in beamed ceilings meeting the following criteria: 1. Maximum beam depth=7"(178mm) 2.Beam spacing at or greater than 7.5 ft. (2.3m)on center. Technical Data: F1 Res 58 Pendent and Recessed Pendent. Thread Nominal Orifice Sprinkler Max Max Actual Sprinkler Temp.Rating Pressure Ambient Temp. Length Size Inch(mm) °F °C psi(bar) °F °C K Factor Inch(mm) 1/2"NPT 155 68 100 38 (R1/2) /"(13) 175 79 175(12) 150 66 5.8 2.25(57) Max Sprinkler Flow Pressure Ceiling-to-Deflector Sprinkler Spacing gpm(Lpm) psi(bar) Inch(mm) Identification ft(m) Number(SIN) 12 x 12(3,6 x 3,6) 16(61) 7.6(0,53) 14 x 14(4,3 x 4,3) 16(61) 7.6(0,53) 4 16 x 16(4,9 x 4,9) 16(61) 7.6(0,53) (251 R3513 - 100) 18 x 18(5,5 x 5,5) 19(72) 10.8(0,75) - - 20 x 20(6,1 x 6,1) 22(83.3) 14.4(1,0) 3. Technical Data: Fl Res 76 Pendent and Recessed Pendent Thread Nominal Orifice Sprinkler Max. Max. K Sprinkler Size Inch(mm) Temp.Rating Pressure Ambient Temp. Factor Length • °F °C psi(bar) °F °C Inch(mm) 3/4"NPT 155 68 100 38 (RY2) 17/32"(13.5) 175 79 175(12) 150 66 7.6 2.25(57) t Max Flow Pressure Sprinkler Identification Sprinkler Spacing ft(m) gpm(Lpm) psi(bar) Number(SIN) 12 x 12(3,6 x 3,6) 21 (79.5) 7.6(0,53) 14 x 14(4,3 x 4,3) 21 (79.5) 7.6(0,53) 16 x 16(4,9 x 4,9) 21 (79.5) 7.6(0,53) R7618 18 x 18(5,5 x 5,5) 21 (79.5) 7.6(0,53) 20 x 20(6,1 x 6,1) 23(87.1) 9.2(0,63) • Model Fl Res 30,49,58&76 CCP Pendent • Model Fl Res 30, 49, 58 & 76 Recessed Pendent/FP +*` Wµue �k 0.i� E F ` 4. • FP push-on/thread-off escutcheon s s MVE IM(es.O...../ KK Cf0.RK. 2 5/8"[66.7mm]DIA. 2 5/16"DIA HOLE IN CEILING - [58.7mm] r CUP j ,-e air ttorrx 'IT 1'k1/2`REDUCER , i 1 I CUP \ ' 7 CEILING —� I f �M— '1 1 1/4"[31.5mm] L �� J -f MAX. FACE OF FITTING "''' � 97.1111 i TO FACE OF CEILING DIMENSION ��� �l��.l n I��I I ki14 i U Or tritimc D" COVER ADJUSTMENT HEIGHT , . ,�m1 w,y •. • 3 5/16"DIA. • 135FG04D [84.Imm] 'W�« FL RES 30, 4s 58 tic 76 CCP PE ID. Fl RES 49 PENDENT/FP Fig. 3 Fig. 4 Note:The F1 Res 76 will use a 1" x'3A" reducer. 4. Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent/FP ThreadNominal Sprinkler CCP Assembly Max Max K Sprinkler Size Orifice Temp.Rating Temp.Rating Pressure Ambient Temp. Factor Length Inch(mm) °F °C °F °C psi(bar) °F °C Inch(mm) 1/2" NPT 2'/64"(8 2) 155 68 135 57 175(12) 100 38 3.0 2.25(57) (R'F/) Max. Sprinkler Identification Sprinkler Spacing Flow Pressure Number ft lm) gpm(Lpm) psi(bar) (SIN) 12 x 12(3,6 x 3,6) 8(30.3) 7.0(0,48) R3511 14 x 14(4,3 x 4,3) 11 (41.6) 13.4(0,92) Technical Data: Fl Res 49 CCP Pendent and Recessed Pendent/FP CCP Nominal I Sprinkler Assembly Max Max Sprinkler CCP Options Data: Thread Orifice ! Temp. Temp. Pressure Ambient K Length Size Inch Rating Rating psi(bar) Temp. Factor Inch Cover Adjustment CCP Height (mm) ,F °C °F °C °F °C (mm) Inch(mm) Inch(mm) 1/2" NPT 716 (11) 155 68 135 57 175(12) 100 38 4.9 2.25(57) /2(12.7) 5/,E(24) (R'h) 5/16(7.9) 3/4 (19) Max. Flow Pressure Sprinkler FP Data"A": Sprinkler Spacing gpm(Lpm) psi(bar) Identification FP Position ft(m) Number(SIN) Inch(mm) 12 x 12(3,6 x 3,6) 13(49) 7.0(0,48) Max.Recessed 716(11) 14 x 14(4,3 x 4,3) 13(49) 7.0(0,48) Min. Recessed 15/16(24) 16 x 16(4,9 x 4,9) 14(53) 8.2(0,56) R3516 Note: Sprinklers shown in Fig. 3 and Fig. 4 18 x 18(5,5 x 5,5) 18(68.1) 13.5(0,93) are not suitable for installation in ceil- 20 x 20(6,1 x6,1) 20(75.7) 16.7(1,14) ings which have positive pressure in the space above. Technical Data: Fl Res 58 CCP Pendent and Recessed Pendent/FP Thread Nominal Sprinkler CCP Assembly Max Max K Sprinkler Size Orifice Temp. Rating Temp. Rating Pressure Ambient Temp. Factor Len h Inch(mm) °F °C °F °C psi(bar) °F °C Inch(mm) 1"NPT (R1/2) 72"(13) 155 68 135 57 175(12) 100 38 5.8 2.25(57) Max. Flow Pressure Sprinkler Identification Sprinkler Spacing gpm(Lpxn) psi(bar) Number ft(m) (SIN) 12 x 12(3,6 x 3,6) 16(61) 7.6(0,53) 14 x 14(4,3 x 4,3) 16(61) 7.6(0,53) 16 x 16(4,9 x 4,9) 16(61) 7.6(0,53) R3513 18 x 18(5,5 x 5,5) 19(72) 10.8(0,75) 20 x 20(6,1 x 6,1) 22(83.3) 14.4(1,0) Technical Data: FiRes 76 CCP Pendent and Recessed Pendent/FP ThreadNominal Sprinkler CCP Assembly Max Max Sprinkler Size Orifice Temp.Rating Temp.Rating Pressure Ambient Temp. K Length Inch(mm) °F °C °F °C psi(bar) °F °C Factor Inch(mm) /4"NPT "be"(13.5) 155 68 135 57 175(12) 100 38 7.6 2.25(57) (R3/4) 175 79 150 66 Max. Sprinkler Identification Flow Pressure Sprinkler Spacing Number ft(m) gpm(Lpm) psi(bar) (SIN) 12 x 12(3,6 x 3,6) 21 (79.5) 7.6(0,53) 14 x 14(4,3 x 4,3) 21 (79.5) 7.6(0,53) 16 x 16(4,9 x 4,9) 21 (79.5) 7.6(0,53) R7618 - 18 x 18(5,5 x 5,5) 22(83.3) 8.4(0,58) 20 x 20(6,1 x 6,1) 25(94.6) 10.8(0,74) 5. • Model Fl Res 44&58 HSW FACE OF ,TIDING ro WALL DIMENSION % 'z .*..,, ---I.—1 1/4"MIN. 2 1/4" HOLE DIA. [31.8mm] , • [3.2mmI CEILING TO 4. DEFLECTOR 1"X 1/2" REDUCER DIMENSION I 4 �f ' I fi __� 15/.6"DIA / �m,w , i.,. [49.2mmJ It ,'ip-mpp' 2 27/32" RA � iun �'� tl (77 Zmm] TURN COLLAR UNTIL 1 TIGHT AGAINST SPRINKLER WRENCH BOSS. 'L • Model Fl Res 44&58 Recessed HSW/F2 f35FC06-O 1/2 [13mmj ADJUSTMENT Fl RES 58 & 44 HSW/F2 N. Fig. 5 I :h 1` ►- s F2 escutcheon, 1/2" (13mm) adjustment Technical Data: Fl Res 44 HSW& HSW/F2 Escutcheon, F2, Data: ax Nominal Sprinkler Max. M Sprinkler Adjustment Face of Fitting TSB Orifice Temp.Rating Pressure Ambient K Length Type Inch(mm) to wall Inch(mm) °F oc psi(bar) 'C Factor Inch(mm) Inch(mm) le NPT 155 68 100 38 F2 72(13) 3ha- 1111s Abe" "(10) 175 79 175(12) 150 86 4.4 2.45(62) (4.7- 17.4) Max. A Sprinkler Temp. Sprinkler Ceiling to Flow Pressure Sprinkler Spacing Rating Identification Deflector gpm(Lpm) psi(bar) ft(m) Inch(mm) °F(°C) Number(SIN) 12 x 12(3,6 x 3,6) 155(68) 175(79) 12(45,4) 7.5(0,52) 14 x 14(4,3 x 4,3) 155(68) 175(79) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) 4_6 155(68) 175(79) 16(60,6) 13.3(0,92) 16 x 18(4,9 x 5,5) (101 - 152) 155(68) 175(79) 18(68,1) 16.8(1,16) 1 18 x 18(5,5 x 5,5) 155(68) 175(79) 19(72,0) 18.7(1,29) 16 x 20(4,9 x 6,1) 155(68) 175(79) 23(87,1) 27.4(1,89) R3531 - 12 x 12(3,6 x 3,6) 155(68) 175(79) 14(53,0) 10.2(0,71) 14 x 14(4,3 x 4,3) 155(68) 175(79) 16(60,6) 13.3(0,92) 16 x 16(4,9 x 4,9) 6- 12 155(68) 175(79) 17(64,4) 15.0(1,04) (152-305) 16 x 18(4,9 x 5,5) 155(68) 175(79) 20(75,7) 20.7(1,43) 16 x 20(4,9 x 6,1) 155(68) 175(79) 23(87,1) 27.4(1,89) 6. Technical Data: FiRes 58 HSW & HSW/F2 Escutcheon, F2, Data: Max. j _- Face of Fitting Thread nt Nominal Sprinkler Max. Ambient K Sprinkler Type A��m) to wall Orifice Temp. Rating Pressure Length Inch(mm) Size Inch(mm) i bar Temp. Factor Inch(mm) F C Ps ( ) of oC F2 ,/ (13) 3/,D-"fib /e" NPT ,(13) 155 68 175(12) 100 38 5.8 2.45(62) (4.7- 17.4) s (R%z) 175 79 150 66 Max. "A" Sprinkler Temp. Flow Pressure Sprinkler Sprinkler Spacing Ceiling to Deflector Rating Identification ft(m) Inch(mm) •F(`C) 9Pm(Lpm) psi(bar) Number(SIN) 12 x 12(3,6 x 3,6) 155(68) 175(79) 16(60,6) 7.6(0,53) 14 x 14(4,3 x 4,3) 155(68) 175(79) 18(88,2) 9.7(0,67) 16 x 16(4,9 x 4,9) (101- 152) 155(68) 175(79) 21 (79,5) 13.2(0,91) 16 x 18(4,9 x 5,5) 155(68) 175(79) 25(94,7) 18.6(1,28) 16 x 20(4,9 x 6,1) 155(68) 175(79) 29(109,8) 25(1,73) R3533 12 x 12(3,6 x 3,6) 155(68) 175(79) 22(83,3) 14.4(1,0) 14 x 14(4,3 x 4,3) 6- 12 155(68) 175(79) 22(83,3) 14.4(1,0) 16 x 16(4,9 x 4,9) (152-305) 155(68) 175(79) 26(98,4) 20.1 (1,39) 16 x 18(4,9 x 5,5) 155(68) 175(79) 31 (117,4) 28.6(1,97) y.._ • Model Fl Res 44 SWC f<•,a 12- [1o;.60mm To • I ,/¢-[Sr.7SmmJ TAox;mum 3Ga.acmm� Toff OI f?f;nq PUSH ON COVER, THEN To Wall O;menS;On TURN TO ADJUST UNTIL I1GHI AGATNGI WALL. 1. :➢W ,a• A! FerommenOetl 1 r won Hok [2 5/TB ,ry" 5/8' SBJmam - - -�- p 5/08" [65.c.4 J Dia , H [8a.,am l f �' 1 • - DTa. TARN COL( UNTIL COLLAR TIGHT AGAINST SPRINKLER , 2T/)2" WRENCH BOSS. [a2G7mmr rrnco/ 1/2"[12.romm/ F1 RES 44 SWC Fig. 6 Technical Data: Fl Res 44 SWC Cover Thread Nominal Sprinkler Temp. Max. Ambient K Sprinkler Orifice Temp.Rating P Pressure Length Size Inch(mm) of °C 0F Ratin oc psi(bar) oFo C Factor Inch(mm) Yz"NPT s/s-(10) 155 68 135 57 175(12) 100 38 4.4 2.45(62) (R'/7) ..A„ Max. Ceiling to Flow Pressure Sprinkler Sprinkler Spacing Identification tt(m) Deflector gpm(Lpm) psi(bar) Number(SIN) Inch(mm) 12 x 12(3,6 x 3,6) 13(49,2) 8.7(0,60) 14 x 14(4,3 x 4,3) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) (101-152) 17(64,3) 15.0(1,1) 16 x 18(4,9 x 5,5) 19(71,8) 18.7(1,13) - 16 x 20(4,9 x 6,1) 23(87,1) 27.4(1,89) R3531 12 x 12(3,6 x 3,6) 14(52,9) 10.2(0,71) - ' 14 x 14(4,3 x 4,3) 6- 12 15(56,7) 11.7(0,81) 16 x 16(4,9 x 4,9) (152-305) 18(68,1) 16.8(1,16) 16 x 18(4,9 x 5,5) 20(75,6) 20.7(1,43) 7. Maintenance - Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res 44 be a steel, two-piece escutcheon [with 1/2" adjustment(Model . Sprinklers should be inspected quarterly, and the sprinkler sys- F2)] [with 3/4"adjustment(Model El)][of push-on and thread off tem maintained in accordance with NFPA 25, 13, 13D,and 13R. design with' "adjustment(Model FP)].Standard finish shall be Do not clean sprinkler with soap and water,Ammonia or any oth- [brass][bright chrome] [white painted]. Residential recessed er cleaning fluids. Remove cL ist by using a soft brush or gentle pendent sprinklers shall be Reliable[Model F1 Res 30, 49&58 vacuuming.Remove any sprinkler which has been painted(oth- Recessed Pendent/F1] [Model F1 Res 30, 49&58 Recessed er than factory applied)or damaged in any way.A stock of spare Pendent/F2][Model F1 Res 30,49&58 Recessed Pendent/FP] sprinklers should be maintained to allow quick replacement of SIN R3511,R3516&R3513(Bulletin 135). damaged or operated sprinklers. Prior to installation, sprinklers model F1 Res 30,49&58 CCP Pendent(Concealed) should remain in the original cartons and packaging until used. Sprinklers shall be [cULus Listed] [New York City MEA Ap- This will minimize the potential for damage to sprinklers that could proved(258-93-E)]low flow residential concealed sprinklers en- cause improper operation or non-operation. gineered to provide a minimum design density of 0.05 gprr'ft2 Model F1 Res 30, 49 & 58 Pendent over the listed coverage area. Listed flows as specified by the Sprinkler Specifications manufacturer's technical data sheets are to be used.Residential Sprinklers shall be [cULus Listed] [New York City MEA Ap- sprinklers shall be installed in conformance with the manufac- proved (258-93-E)] low flow residential pendent sprinklers en- turer's installation guidelines and the applicable installation stan- gineered to provide a mink-num design density of 0.05 gpnyft2 dard. Where pendent residential sprinklers are installed under over the listed coverage area. Listed flows as specified by the sloped celtinys having a pitch fru n[4/12]to[8/12],the sprinklers manufacturer's technical data sheets are to be used. Residential shall be listed for such use. Sprinkler frame and deflector shall sprinklers shall be installed in conformance with the manufac- be of bronze fray r re construction having a 1/2"NPT thread. Water turer's installation guidelines and the applicable installation stan- seal assenloly shall consist of a Teflon-coated Belleville spring dard. Where pendent residential sprinklers are installed under washer with top-loaded extruded or cold head cup with 3 rum sloped ceilings having a pitch from[4/12]to[8/12],the sprinklers glass bulb containing no plastic parts,and having a temperature shall be listed for st rh use. Deflector-to-ceiling distance listing rating of 155°F(68°C). Cover plate assembly shall consist of a shall be 1" to 8" maximum. Sprinkler frame and deflector shall brass cover plate and copper alloy retainer flange. Method of be of bronze frame construction having a 1/2'NPT thread. Water attaching the cover plate to the sprinkler cup shall be a push- - seal assembly shall consist of a Teflon-coated Belleville spring on and thread-off design allowing a'/z"cover plate adjustment. washer with top-loaded extruded or cold head cup with 3 mm Cover plate temperature rating shall be 135°F(57°C). A plastic glass bulb containing no plastic parts,and having a temperature protective cap shall be provided and factory installed inside the rating of[155°F(68°C)] [175°F(79°C)]. Sprinklers shall have a sprinkler cup to protect the sprinkler from damage,which could _ nominal K-factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze] occur during construction before the cover plate is installed. [Chrome-plated][White Polyester][Specialfinish-specify].Real- Standard cover plate finish: [White] [Custom Color-specify]. ]. dential pendent sprinklers shall be Reliable Model F1 Res 30,49 Concealed pendent sprinklers shall be Reliable Model F1 Res &58,SIN R3511,R3516&R3513(Bulletin 135). 30,49&58 CCP,SIN R3511,R3516&R3513(Bulletin 135). Model F1 Res 49&58 Recessed Pendent/F1, Model F1 Res 44 Horizontal Sidewall Model F1 Res 30,49&58 Recessed Pendent/F2, Residential Sprinkler Specifications Model F1 Res 30,49&58 Recessed Pendent/FP Sprinklers shall be [cULus Listed] [New York City MEA Ap- Sprinklers shall be [cULus Listed] [New York City MEA Ap- pied(258-93-E)]low flaw residential horizontal sidewall sprin- proved (258-93-E)] low flow residential recessed pendent klers engineered to provide a minimum design density of 0.05 sprinklers engineered to provide a minimum design density 9Prnift2 over the listed coverage area Listed flows as speci- of 0.05 gpm/ft2 over the listed coverage area. Listed flows as fled by tie manufacturer's technical data sheets are to be'Iced. specified by the manufacturer's technical data sheets are to be Residential sprinklers shall be installed in conformance with the used. Residential sprinklers shall be installed in conformance manufacturer's installation guidelines and the applicable instal- with the manufacturer's installation guidelines and the applica- lation standard. Where horizontal sidewall residential sprinklers ble installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from[4/12]to are installed under sloped ceilings having a pitch from [4/12] [8/12],the sprinklers shall be listed for such use.Sprinkler frame to[8/12], the sprinklers shall be listed for such use. Deflector- and deflector shall be of bronze frame construction having a'/2' to-ceiling cdstance listing shall be 1" in 8" maximum. Sprinkler NPT thread. Water seal assembly shall consist of a Teflon-coat- _ frame and deflector shall be of bronze frame construction haw- ed Belleville spring washer with top-loaded extruded or cold ing a 1/2" NPT thread. Water seal assembly shall consist of a head cup with 3 rrrn glass bulb containing no plastic parts,and Teflon-coated Belleville spring washer with top-loaded extruded having a temperature rating of [155°F (68°C)] [175°F (79°C)]. _ or cold head cup with 3 rim glass bulb containing no plastic Sprinklers shall have a nor ninal K-factor of 4.4(62.8). Standard parts,and having a temperature rating of[155°F(68°C)][175°F finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin- _ (79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 & ish-specify]. Residential horizontal sidewall sprinklers shall be 5.8. Standard finish:[Bronze][Chrome-plated][White Polyester] Reliable Model F1 Res 44,SIN R3531(Bulletin 135). [Special finish-specify]. Recessed escutcheon assembly shall 8. Model F1 Res 44 Recessed Model F1 Res 76 CCP Pendent(Concealed) Horizontal Sidewall Sprinkler Sprinklers shall be [cULus Listed] low flow residential Use description for the Model F1 Res 44 horizontal side- concealed sprinklers engineered to provide a minimum wall sprinkler with the following modifications: Replace design density of 0.05 gprrtlft2 over the listed coverage "horizontal sidewall sprinkler" with "recessed horizontal area. Listed flows as specified by the manufacturer's sprinkler." Add: Recessed escutcheon assembly shall be technical data sheets are to be used. Residential spin- a steel, two-piece escutcheon with adjustment(Model klers shall be installed in conformance with the manufac- F2). Standard finish shall be[brass][bright chrome] [white turer's installation guidelines and the applicable instal- painted] [Special finish- specify]. Residential recessed lation standard. Sprinkler frame and deflector shall be horizontal sidewall sprinklers shall be Reliable Model F1 of bronze frame construction having a 3/4" NPT thread. Res 44/F2, SIN R3531 (Bulletin 135). Water seal assembly shall consist of a Teflon-coated Bel- Model F1 Res 76 Pendent leville spring washer with machined or cold head cup with Sprinklers shall be [cULus Listed] low flow residential 3 mm glass bulb containing no plastic parts, and having pendent sprinklers engineered to provide a minimum de a temperature rating of 155°F(68°C). Cover plate assem sign density of 0.05 gpm/ft2 over the listed coverage area. bly shall consist of a brass cover plate and copper alloy Listed flows as specified by the manufacturer's technical retainer flange. Method of attaching the cover plate to the data sheets are to be used. Residential sprinklers shall sprinkler cup shall be a push on and thread off design be installed in conformance with the manufacturer's in i allowi ng a 1/2" cover plate adjustment. Cover plate tem- stallation guidelines and the applicable installation Stan Perature rating shall be 135°F (57°C). A plastic protec dard. Sprinkler frame and deflector shall be of bronze Live cap shall be provided and factory installed inside the frame construction having a 3A" NPT thread. Water seal sprinkler cup to protect the sprinkler from damage, which assembly shall consist of a Teflon-coated Belleville spring could occur during construction before the cover plate washer with machined or cold head cup with 3 mm glass Is installed. Standard cover plate finish: [White] [Custom bulb containing no plastic parts, and having a tempera- Color-specify]. ]. Concealed pendent sprinklers shall be ture rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers Reliable Model F1 Res 76 CCP, SIN R7618(Bulletin 135). shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin- Finishes(1) ish-specify]. Residential pendent sprinklers shall be Reli- able Model F1 Res 76, SIN R7618(Bulletin 135). Standard Finishes Model F1 Res 76 Recessed Pendent/F1, Sprinkler Fl,F2,FP Cover Plates Escutcheons Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Bronze Brass White Painted Chrome Plated Bright Chrome Plated Chrome Sprinklers shall be [cULus Listed] low flow residential White and Black Polyester White Painted recessed pendent sprinklers engineered to provide a Coated minimum design density of 0.05 gpm/ft2 over the listed Special Application Finishes coverage area. Listed flows as specified by the manu- F1, F2, facturer's technical data sheets are to be used. Residen- Sprinkler Escutcheons Cover Plates tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable Bright Brass Bright Brass Bright Brass Black Plated Black Plated Black Plated installation standard. Sprinkler frame and deflector shall Black Paint Black Paint Black Paint be of bronze frame construction having a-3/4" NPT thread. Off White Off White Off White Water seal assembly shall consist of a Teflon-coated Bel- Satin Chrome Satin Chrome Satin Chrome leville spring washer with machined or cold head cup with n,Other finishes and colors are available on special order. 3 mm glass bulb containing no plastic parts, and hay- Consult factory for details. ing a temperature rating of[155°F(68°C)] [175°F(79°C)]. Note: Paint or any other coating applied over the factory finish will void Sprinklers shall have a nominal K-factor of 7.6. Standard all approvals and warranties. finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- cial finish- specify]. Recessed escutcheon assembly Ordering Information shall be a steel, two-piece escutcheon [with 1/2" adjust- specify: ment (Model F2)] [with 3A" adjustment (Model F1)] [of 1. Sprinkler Model push-on and thread off design with '/•z' adjustment(Mod- 2. Sprinkler Type el FP)]. Standard finish shall be [brass][bright chrome] 3. Temperature Rating [white painted]. Residential recessed pendent sprinklers 4. Sprinkler Finish shall be Reliable [Model F1 Res 76 Recessed Pendent/ 5. Escutcheon Finish F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1 6. Cover Plate Finish Res 76 Recessed Pendent/FP]SIN R7618(Bulletin 135). 9. - Reliable. . . For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections ' • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips - • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gaugesldentification signs • Electrical sprinkler alarm switches • Fire department connection • Water flow detectors The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly - qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. O Recycled � Re'lab' (800)84431-1588 Sales Offices w Paper (800)848-6051 Sales Fax Corporate Offices Revision lines indicate updated or new data. (914)829-2042 www.reliablesprinkler.com Internet Address EG.Primed in U.SA 09110 P/tJ 9999970235 tqc Fire SuppressionAer & Building Products rapid response Technical Services 800-381-9312 j+1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Dry-Type Residential Sprinklers, Horizontal Sidewall and Recessed Horizontal Sidewall 4.4 Nominal K-Factor General • sprinklers are used on systems that are seasonally drained to avoid freezing; Description for example,vacation areas. The Series LFII Dry-Type Residential Hod- The TYCO RAPID RESPONSE Series LFII zontal Sidewall Sprinklers are intended Dry-Type Residential Horizontal Sidewall for use in Residential Sprinkler systems ,r Sprinklers (TY2335)are decorative, for one- and two-family dwellings and h, fast response,frangible bulb sprinklers mobile homes per NFPA 13D;residential rW designed for use in residential occu- sprinkler systems for residential occu- pancies such as homes,apartments, pancies up to and including four stories • dormitories,and hotels.When aesthetics in height per NFPA 13R; or, sprinkler and optimized flow characteristics are systems for the residential portions of the major consideration,the Series LFII any occupancy per NFPA 13. Sprinklers(TY2335)should be the first choice.These sprinklers may be used in These sprinklers have a 4.4(63,4)K-factor wet pipe,dry pipe,or preaction systems. that provides the required residential flow Owners are responsible for maintaining rates at reduced pressures,supporting their fire protection system and devices in Residential sprinklers listed for dry pipe or smaller pipe sizes and water supply proper operating condition. The install- preaction systems must undergo special requirements. ing contractor or sprinkler manufacturer testing at Underwriters Laboratories, The recessed version is intended for use should be contacted with any questions. • Inc., including a 15-second delay while passing all UL1626 test criteria. The in areas with finished walls. It employs a The Series LFII Dry-Type Residential sprinklers described in this data sheet t o-piece Style 20 Recessed Escutcheon. Horizontal Sidewall Sprinklers must have undergone this special UL testing The Recessed Escutcheon provides 1/4 only be installed in fittings that meet and are therefore listed for the types of inch(6,4 mm)of recessed adjustment or the requirements of the Design Criteria residential designs cited below. up to 1/2 inch(12,7 mm)of total adjust- section. ment from the flush mounting surface Dry-Type Sprinklers are typically used position.The design of this escutcheon where: provides a level of flexibility in adjusting Model/Sprinkler • sprinklers are required on dry pipe sprinklers to fixed pipe drops. Identification systems that are exposed to freezing The Series LFII Dry-Type Residential temperatures; for example, sprin- Horizontal Sidewall Sprinklers are de- Number (SIN) kler drops from unheated portions of signed with heat sensitivity and water buildings. characteristics proven to help in control- TY2335 • sprinklers and/or a portion of the con- ling residential fires and improving the netting piping are exposed to freezing chance for occupants to escape or be temperatures; for example, sprinkler evacuated. drops from wet systems into unheat- ed areas. NOTICE The Series LFII Dry-Type Residential Horizontal Sidewall Sprinklers(TY2335) IMPORTANT described herein must be installed and Always refer to Technical Data maintained in compliance with this docu- - Sheet TFP700 for the "INSTALLER ment, as well as with the applicable WARNING"that provides cautions standards of the National Fire Protection with respect to handling and in- Association,in addition to the standards stallation of sprinkler systems and of any authorities having jurisdiction. components. Improper handling and Failure to do so may impair the perfor- installation can permanently damage mance of these devices. - - a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. i Page 1 of 8 JUNE 2010 TFP461 - TFP461 Page 2 of 8 Maximum Maximum Minimum Flowco and Residual Pressure for Horizontal Ceiling Coverage Spacing 155°F(68°C) Area I'> Ft.(m) Top-of-Deflector to Ceiling: Top-of-Deflector to Ceiling: Width x Length IN 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) Ft.x Ft. (m x m) WET PIPE DRY PIPE WET PIPE DRY PIPE 12 x 12 12 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) 15 GPM(56,8 LPM) 15 GPM(56,8 LPM) (3,7 x 3,7) (3,7) 8.7 psi(0,60 bar) 8.7 psi(0,60 bar) 11.6 psi(0,80 bar) 11.6 psi(0,80 bar) 14 x 14 14 14 GPM(53,0 LPM) 16 GPM(60,6 LPM) 15 GPM(56,8 LPM) 16 GPM(60,6 LPM) (4.3 x 4,3) (4,3) 10.1 psi(0,70 bar) 13.2 psi(0,91 bar) 11.6 psi(0,80 bar) 13.2 psi(0,91 bar) 16 x 16 16 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) 19 GPM(71,9 LPM) 19 GPM(71,9 LPM) (4,9 x 4,9) (4,9) 14.9 psi(1,03 bar) 14.9 psi(1,03 bar) 18.6 psi(1,28 bar) 18.6 psi(1,28 bar) 16 x 18 16 19 GPM(71,9 LPM) N/A 20 GPM(75,7 LPM) N/A (4,9 x 5,5) (4,9) 18.6 psi(1,28 bar) 20.7 psi(1,43 bar) 16 x 20 16 25 GPM(94,6 LPM) 25 GPM(94,6 LPM) (4,9 x 6,1) (4,9) 32.3 psi(2.23 bar) N/A 32.3 psi(2.23 bar) N/A (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)This dimension refers to Width(backwall where sprinkler is located)times Length(horizontal throw of the sprinkler). (c)The requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. • Sidewall sprinklers,where installed under a ceiling with a slope greater than 0 inch rise for a 12-inch run to a slope up to a 2-inch rise for a 12-inch run,must be located per one of the following: • Locate the sprinklers at the high point of the slope and positioned to discharge down the slope. - • Locate the sprinklers along the slope and positioned to discharge across the slope. TABLE A NFPA 13D AND NFPA 13R WET AND DRY PIPE HYDRAULIC DESIGN CRITERIA FOR SERIES LFII DRY-TYPE RESIDENTIAL SPRINKLERS(TY2335) Technical Physical Characteristics Operation Inlet Brass Data Plug Brass When the TYCO Series [Ell Dry-Type Yoke Stainless Steel Residential Horizontal Sidewall Sprinkler Approvals Casing Galvanized Steel is in service, water is prevented from UL Listed entering the assembly by the Plug with Refer to Table A and the Design Crite- Insert Bronze Sealing Assembly(Figure 1)in the Inlet ria section. Bulb Seat Stainless Steel of the Sprinkler. Maximum Working Pressure Bulb Glass The glass Bulb contains a fluid that ex- 175 psi(12,1 bar) Compression Screw Brass pands when exposed to heat.When the Deflector Brass rated temperature is reached, the fluid Discharge Coefficient Frame Brass expands sufficiently to shatter the glass K =4.4 GPM/psi''2(63,4 LPM/bar12) Guide Tube Stainless Steel Bulb then release the Bulb Seat. System Inlet Thread Connection Water Tube Stainless Steel water or air pressure then unseats the 1-inch NPT Bushing Brass Plug with Sealing Assembly. The Plug Plug Spring Stainless Steel Spring turns the Plug with Sealing As- Sprinkler Temperature Rating sembly aside, allowing the sprinkler to 155°F/68°C Sealing Assembly Beryllium activate and flow water. Nickel w/Teflon* - Finishes Escutcheon Carbon Steel Chrome-Plated, White Polyester- Patents Coated, or Natural Brass U.S.A. Patent No. 5,188,185 - Order Lengths Other patents pending Minimum: 3-3/4 inches (95,3 mm) Maximum: 24 inches(609,6 mm) - • *DuPont Registered Trademark _ TFP461 Page 3 of 8 PLUG WITH YOKE PLUG WATER GUIDE BULB 3 mm DEFLECTOR SEALING SPRING TUBE TUBE SEAT BULB ASSEMBLY I . mum \ i INLET VENT COMPRESSION INLET BAND BUSHING CASING FRAME HOLE SCREW FIGURE 1 ASSEMBLY FOR SERIES LFII DRY-TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS(TY2335) ORDER LENGTHS: - 5-1/2"to 24"(139,7 to 609,6 mm) el IN 1/4"(6.4 mm)INCREMENTS MINIMUM 2-1/4"(57,2 mm) FACE OF DEFLECTOR TO WRENCH RECESS SPRINKLER MOUNTING (USE END FITTING SURFACE ONLY) t 7 f FIGURE 4 5/16" - SPRINKLER FITTING (7.9 mm) SPRINKLERPWRENCH (REFER TO DESIGN CENTERLINE CRITERIA SECTION) OF WATERWAY FIGURE 2 I PUSH WRENCH SERIES!RI DRY-TYPE RESIDENTIAL I IN TO ENSURE HORIZONTAL SIDEWALL SPRINKLERS WITHOUT ESCUTCHEON ENGAGEMENT WITH SPRINKLER ® WRENCHING AREA ORDER LENGTHS: 3-3/4"to 24"(95,3 to 609.6 mm) Adi11°1141.I WRENCH IN 1/4°(6,4 mm)INCREMENTS RECESS 2-3/16" ±1/4" ," (55,6±6,4 mm) FACE OF FACE OF 5/16" --SPRINKLER MOUNTING (7,9 mm) FITTING SURFACE tWRENCH 2-7/8"DIA. FLAT / f (73,01mm) 1 SPRINKLER FITTING (REFER TO DESIGN CENTERLINE 1-3/4"DIA. FIGURE 5 CRITERIA SECTION) OF WATERWAY (44,5 mm) W-TYPE 7 RECESSED - SPRINKLER WRENCH FIGURE 3 _ - SERIES LFII DRY-TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS WITH STYLE 20 RECESSED ESCUTCHEON - TFP461 Page 4 of 8 Design For systems designed to NFPA 13,the The Series LFII Dry Type Sprinklers can number of required design sprinklers is also be installed in the 1-inch NPT outlet Criteria the four most hydraulically demanding of a GRINNELL Figure 730 Mechanical sprinklers.The minimum required dis- Tee.However,the use of the Figure 730 The TYCO Series LFII Dry Type Resi- charge from each of the four sprinklers for this arrangement is limited to wet dential Horizontal Sidewall Sprinklers is the greater of the following: pipe systems. (TY2335)are UL Listed for installation •flow rates listed in Table A for NFPA Only use the configuration in Figure 6 in accordance with the criteria listed in 13D and 13R as afunction of tempera- where the sprinkler fitting and water- this section. ture rating and the maximum allowable filled pipe above the sprinkler fitting When conditions exist that are outside coverage area. are not subject to freezing and where the scope of the criteria provided in this • minimum discharge of 0.1 GPM/sq. the length of the Series LFII Sprinkler section,refer to the technical data sheet ft.over the design area comprised of has the minimum exposure length per entitled Residential Sprinkler Design the four most hydraulically demand- Figure 8.Refer to the Exposure Length Guide(TFP490)for the manufacturer's ing sprinklers for the actual coverage section and Table B. recommendations that may be acceptable areas protected by four sprinklers. For wet-pipe system installations of the to the local authority having jurisdiction. 1-inch NPT Series LFII Dry Type Resi- Obstruction to Water Distribution dential Sprinklers connected to CPVC This section describes the following Sprinklers are to be located in accor- design characteristics: dance with the obstruction rules of NFPA piping, use only the following TYCO • System Types13 for residential sprinklers as well as CPVCfittings: y with the obstruction criteria described • 1"x 1"NPT Female Adapter(P/N 80145) • Water Delivery in technical data sheet TFP490. • 1"x 1"x 1"NPT Sprinkler Head Adapter • Hydraulic Design Tee(P/N 80259) Operational Sensitivity • Obstruction to Water Distribution The sprinkler must be located relative • Operational Sensitivity to the mounting surface as shown in NOTICE Figures 2 and 3. • Sprinkler Spacing Do not install the Series LFII Dry-Type •Sprinkler Fitting Sprinkler Spacing Residential Horizontal Sidewall Sprin- The minimum lateral spacing between klers into any other type fitting without • Prevention of Branch Line Freezing sprinklers is 8 feet(2,4 m).The maximum first consulting the Technical Services lateral spacing between sprinklers cannot Department. Failure to use the appro- System Types exceed the length of the hydraulically- priate fitting may result in the following: - Wet pipe,dry pipe,and preaction sys- calculated coverage area(refer to Table • failure of the sprinkler to operate tems may be utilized. A);for example, a maximum of 12 feet properly due to formation of ice over Water Delivery for a 12 ft. x 12 ft.coverage area or 18 the Inlet Plug or binding of the Inlet - For dry pipe and preaction systems,water feet for a 18 ft.x 20 ft.coverage area. Plug. delivery to the most remote sprinkler for Sprinkler Fittings • insufficient engagement of the in- a residential hazard shall not exceed 15 Install the 1-inch NPT Series LFII Dry- let pipe threads with consequent seconds as defined in Section 8.3.4.3 of Type Residential Horizontal Sidewall leakage. the 2010 edition of NFPA 13D or Section Sprinklers in the 1-inch NPT outlet or 7.2.3.6.3 of the 2010 edition of NFPA 13. run of one of the following fittings: Drainage BrUsing the TYCO SPRINKFDT Water •malleable or ductile iron threaded tee connected dtocross, and feed-main piping Resi- Delivery Calculation Program can help fittings that meet the dimensional re- connectedno Series Lnd FII subjectDryttofe g determine whether required delivery quirements of ANSI B16.3(Class 150). temdential Sprinklers must bpitched o freezingt determinetimes will likely be achieved prior to properperdrainares crdance withallow performing the actual installation. •cast iron threaded tee fittings that drainage,in accordance the meet the dimensional requirements minimum requirements of the National As an alternative to using a UL Listed of ANSI B16.4(Class 125). Fire Protection Association for dry pipe water delivery calculation program and For dry pipe system installations,only sprinkler systems. method, as referenced in NFPA 13D use the side outlet of maximum 2-1/2 or NFPA 13, using an inspector's test Exposure Length connection is required to provide flow inch reducing tees when locating the When using Series LFII Dry-Type Resi- equivalent to the smallest orovi sprin- Series LFII Dry Type Residential Sprin- dential Horizontal Sidewall Sprinklers kler, wherein the test orifice is located klers directly below the branch line. in wet pipe sprinkler systems to protect on the end of the pipe supplying the Otherwise,use the configuration shown areas subject to freezing temperatures, p p pp ym g in Figure 6 to assure complete drainage use Table B to determine a sprinkler's most remote sprinkler. from above the Series LFII Sprinklers p P appropriate exposed barrel length to Hydraulic Design and the branch line. prevent water from freezing in the con- . Table A lists the minimum required sprin- Do not install the LFII Series Dry-Type necting pipes due to conduction.The kler flow rate for systems designed to Residential Sprinklers into elbow fittings. exposed barrel length measurement must NFPA 13D or NFPA 13R as a function The Inlet of the sprinkler can contact the be taken from the face of the sprinkler of temperature rating and the maximum interior of the elbow,potentially damag- fitting to the surface of the structure or - allowable coverage areas.The sprinkler ing the Inlet seal. insulation that is exposed to the heated flow rate is the minimum required dis- area. Refer to Figure 8 for an example. charge from each of the total number Typically,the end sprinkler fitting on - of"design sprinklers," as specified in a branch line is plugged as shown in NFPA 13D or NFPA 13R. Figure 7. TFP461 Page5of8 HEATED t• AREA 1 AREA SUBJECT HEATED TO 1111 AREA ion PLUG FREEZING Ell OUTLET FACE OF SPRINKLER SPRINKLER1„„," SPRINKLER 1111 FITTING FITTING FITTING PLUG (SEE DESIGN (SEE DESIGN OUTLET CRITERIA 4 DSB-2 CRITERIA ( 1 I 1 SECTION) BOOT ion SECTION) ` "L/ 6 0„1,„,„,. Iii . so .„,,P I lid pm DSB-2 EXPOSURE DSB-2 /�� BOOT LENGTH BOOT (SEE DESIGN T TO DRY CRITERIA TO WET / SYSTEM SECTION) AP I SYSTEM / FIGURE 6 FIGURE 7 FIGURE 8 SPRINKLER FITTING IN SPRINKLER FITTING IN EXPOSURE LENGTH HEATED AREA UNHEATED AREA Temperatures for Heated Area'° Ambient Temperature Exposed to Discharge End of 40°F(4°C) 50°F(10°C) 60°F(16°C) - Sprinkler Minimum Exposed Barrel Length, Inches(mmr 40°F(4°C) 0 0 0 30°F(-1°C) 0 0 0 - 20°F(-7°C) 4(100) 0 0 10°F(-12°C) 8(200) 1 (25) 0 0°F(-18°C) 12(305) 3(75) 0 -10°F(-23°C) 14(355) 4(100) 1 (25) -20°F(-29°C) 14(355) 6(150) 3(75) -30°F(-34°C) 16(405) 8(200) 4(100) -40°F(-40°C) 18(455) 8(200) 4(100) -50°F(-46°C) 20(510) 10(255) 6(150) -60°F(-51°C) 20(510) 10(255) 6(150) Notes: (a)For protected area temperatures that occur between values listed above.use the next cooler temperature. (b)These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE B MINIMUM RECOMMENDED LENGTHS OF EXPOSED SPRINKLER BARRELS IN WET-PIPE SYSTEMS r1 __ TFP461 Page 6 of 8 Clearance Space 3. Wrench-tighten the sprinkler into the Exercise care to avoid damage to sprin- When connecting an area subject to sprinkler fitting using a pipe wrench klers before,during,and after installation. freezing and an area containing a wet- on the Inlet Band or the Casing(Fig- Never paint, plate,coat, or otherwise pipe sprinkler system,the clearance ure 1). alter automatic sprinklers after they space around the sprinkler barrel of • For plain-barrel horizontal side- leave the factory. Dry-Type Residential Sprinklers must wall sprinklers,apply the Wrench Replace sprinklers that: be sealed, in accordance with the Na- Recess End"A"of the W-Type 6 tional Fire Protection Association. Due Sprinkler Wrench(Figure 4)to the •were modified or over-heated. to temperature differences between the Wrench Flat. •were damaged by dropping,striking, two areas,the potential for the forma- wrench twisting,wrench slippage,or tion of condensation in the sprinkler and • For recessed horizontal sidewall the like. subsequent ice build-up is increased. If sprinklers,apply the Wrench Re- this condensation is not controlled, ice cess of the W-Type 7 Sprinkler •are leaking or exhibiting visible signs build-up can occur that might damage Wrench to the Wrench Flat(Fig- of corrosion. the dry-type sprinkler and/or prevent ure 5). •were exposed to corrosive products proper operation in a fire situation. Note:If sprinkler removal is necessary, of combustion but have not operated, Use of the Model DSB-2 Dry Sprinkler remove the sprinkler using the same if you cannot easily remove combus- Boot,described in technical data sheet wrenching method noted above. tion by-products with a cloth. TFP591 and shown in Figures 6 through Sprinkler removal is easier when a •have a cracked Bulb or have lost liquid 8,can provide the recommended seal. non-hardening sealant was used from the Bulb. Refer to the Installation and torque guidelines were followed. section in this data sheet. Installation After removal, inspect the sprinkler for damage. Responsibility lies with the owner for the f The TYCO Series LFII Dry-Type Resi- 4. After installing the ceiling or apply- inspection,heirfiprotection testing,andy maintenance s dential Horizontal Sidewall Sprinklers ing a ceiling finish,slide the Style 20 teir me system and devices as must be installed in accordance with Recessed Escutcheon Closure over in compliance with this document,and of the following instructions. the sprinkler. Push the closure over the as with the applicable Association of the mounting plate until its flange o NationalamplFire Protection A5) i addition to (for example, NFPA 25), in addition to NOTICE contacts the wall. the standards of any authorities hav- ing jurisdiction. Contact the installing The Series LFII Dry-Type Residential Care and contractor or sprinkler manufacturer Horizontal Sidewall Sprinklers must regarding any questions. only be installed in fittings that meet Maintenance Automatic sprinkler requirements of the Design Criteria systems are recom- section. For other important require- mended to be inspected, tested, and meets regarding piping design and The TYCO Series LFII Dry-Type Residential maintained by a qualified Inspection sealing of the clearance space around Horizontal Sidewall Sprinklers(TY2335) Service. the Sprinkler Casing,refer to the Design must be maintained and serviced in Criteria section. accordance with the following instruc- tions. Otherwise, inadvertent sprinkler Do not install any bulb type sprinkler if operation or non-operation in the event the Bulb is cracked or there is a loss of of a fire can result. liquid from the Bulb. With the sprinkler held horizontally,a small air bubble NOTICE should be present.The diameter of the air bubble is approximately 1/16 inch Before closing a fire protection system (1,6 mm). main control valve for maintenance Obtain a 1-inch NPT sprinkler work on the fire protection system that joint y applying leak-tight a 1-inch NPT it controls, obtain permission to shut torque of 20 to 30 ft.-Ibs.(26,8 to 40,2 down the affected fire protection systems Nm).Higher levels of torque can distort the from the proper authorities and notify all personnel who may be affected by sprinkler Inlet or Frame with consequent leakage or impairment of the sprinkler. this action. DDo not attempt to compensate for Absence of a Recessed Escutcheon oins note at adjuptmont in an Escutcheon Plate or a Domed Concealed Cover Plate by under-or over-tightening the Plate cover a c hole can delay. sprinkler. Re-adjust the position of the sprinkler operation in a nnr a fire situation. sprinkler fitting to suit. A Vent Hole is provided in the Bulb Seat 1. Install horizontal sidewall sprinklers (Figure 1)to indicate if the Series LFII only in the horizontal position with Dry-Type Residential Horizontal Sidewall centerline of waterway perpen- Sprinkler is remaining dry. Evidence of their their dicular to the back wall and parallel leakage from the Vent Hole indicates to the ceiling. The word TOP on the potential leakage past the Plug with Seal- Deflector is to face towards the ceiling. ing Assembly and the need to remove the sprinkler to determine the cause - ' 2. With a non-hardening pipe-thread of leakage(for example,an improper sealant such as Teflon tape applied installation or an ice plug). Close the to the inlet threads,hand-tighten the fire protection system control valve sprinkler into the sprinkler fitting. and drain the system before removing the sprinkler. TFP461 Page 7 of 8 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression&Building Products(TFSBP) ability.When placing an order, indicate are warranted solely to the original Buyer the full product name and Part Number for ten (10)years against defects in (P/N). Refer to the Price List for a corn- material and workmanship when paid plete listing of P/Ns. for and properly installed and main- tained under normal use and service. Horizontal Sidewall Sprinkler This warranty will expire ten(10)years Assembly from date of shipment by TFSBP. No Specify the following information: warranty is given for products or corn- •Series LFII Dry Type Residential Hori- ponents manufactured by companies zontal Sidewall Sprinkler(TY2335), not affiliated by ownership with TFSBP or for products and components which •with Recessed Escutcheon or without have been subject to misuse, improper Escutcheon, installation,corrosion,or which have not •4.4 K-Factor, been installed,maintained,modified or repaired in accordance with applicable • 155°F(68°C)Temperature Rating, Standards of the National Fire Protection •Sprinkler Finish, Association,and/or the standards of any • Escutcheon Finish(if applicable), other Authorities Having Jurisdiction. Materials found by TFSBP to be defec- •Order Length(value from Figure 2 or tive shall be either repaired or replaced, 3),and at TFSBP's sole option.TFSBP neither • P/N(from Table C). assumes,nor authorizes any person to assume for it, any other obligation in Separately Ordered Sprinkler connection with the sale of products Wrench or parts of products. TFSBP shall not Specify the appropriate wrench type: be responsible for sprinkler system de- •W-Type 6 Sprinkler Wrench(Figure 4), sign errors or inaccurate or incomplete P/N 56 000 6 387 information supplied by Buyer or Buyer's representatives. •W-Type 7 Recessed Sprinkler Wrench In no event shall TFSBP be liable, in (Figure 5), P/N 56-850-4-001 contract,tort, strict liability or under any other legal theory,for incidental, indirect,special or consequential dam- ages, including but not limited to labor charges,regardless of whether TFSBP was informed about the possibility of such damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied, including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products,materi- als or components, whether the claim is made in contract,tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law.The invalidity,in whole or part,of any portion of this warranty will not affect the remainder. TFP461 Page 8 of 8 P/N 63 - XXX - X - XXX ORDER LENGTH (EXAMPLES) 055 5.50" 082 8.25" MODEL/SIN Horizontal Sidewall TY2335 180 18.00" 12 with Recessed Escutcheon (Figure 2) RECESSED SPRINKLER FINISH ESCUTCHEON FINISH Horizontal Sidewall TY2335 187 18.75" 13 without Escutcheon (Figure 3) 9 Chrome Plated Chrome 240 24.00" 4 White White Polyester Coated TEMPERATURE RATING 2 Natural Brass Brass Plated 1 155`F(68°C) TABLE C PART NUMBER SELECTION FOR SERIES LFII DRY-TYPE RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLERS Copyright 0 2010 Tyco Fire Suppression&Building Products,451 North Cannon Avenue,Lansdale Pennsylvania 19446 • tqco I Fire & Buildingjar Products vapid response" HOME FIRE SPRINKLER SYSTEM Technical Services: Tel:(800)381-9312/Fax:(800)791-5500 BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description Technical Tyco® CPVC Pipe and Fittings pro- Data duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively Sizes for use in wet pipe automatic fire sprin- 3/4" to 3" M` y kler systems. The Tyco CPVC Pipe Maximum Working Pressure and Fittings are produced from Blaze- 175 psi Master® CPVC compound that is a "., specially developed thermoplastic Approvals compound composed of post chlorin- UL, FM, C-UL, NSF, LPCB, MEA,and • ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to (n- and state of the art additives. Tyco stallation Handbook IH-1900 dated • . CPVC Pipe and Fittings are easier to June 2008 for exact listing/approval • rrt install than traditional steel pipe sys- information.) tems, and at the same time, provide Manufacture Source superior heat resistance and strength U.S.A. as compared to traditional CPVC and PVC piping materials used in the Material plumbing trade. Various adapters are . Pipe: ASTM F442, SDR 13.5 available to connect CPVC pipe to me- tallic piping. All female pipe thread • Fittings: ASTM F438 (Sch. 40) and adapters have brass inserts for dura- ASTM F439(Sch. 80),ASTM F1970 bility. Grooved adapters connect di- Color rectly to grooved end valves and me- Orange tallic pipe, with flexible grooved end couplings. NOTICE Tyco® CPVC Pipe and Fittings pro- duced with BlazeMaster®CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. • The owner is responsible for maintain- ing their fire protection system and de- - vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted • with any questions. BlazeMaster®is a registered trademark • " of The Lubrizol Corporation Page 1 of 2 JUNE, 2008 TFP1915 • Page 2 of 2 TFP1915 installation Limited Warranty CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in Products manufactured by Tyco Fire& accordance with Installation Hand- Building Products (TFBP) are war- book IH-1900 dated June 2008. ranted solely to the original Buyer for ten(10)years against defects in mate- Care and rial and workmanship when paid for and properly installed and maintained Maintenance under normal use and service. This warranty will expire ten (10) years for the in- from date of shipment by TFBP. No The owner is responsible warranty is given for products or corn- spection, testing, and maintenance of ponents manufactured by companies their fire protection system and de- not affiliated by ownership with TFBP vices in compliance with this docu- or for products and components which ment, as well as with the applicable have been subject to misuse,improper standards of the National Fire Protec- installation, corrosion, or which have tion Association (e.g., NFPA 25), in not been installed, maintained, modi- addition to the standards of any fied or repaired in accordance with ap- authority having jurisdiction. The in- plicable Standards of the National Fire stalling contractor or product manufac- Protection Association, and/or the turer should be contacted relative to standards of any other Authorities any questions. Having Jurisdiction. Materials found Automatic sprinkler systems should be by TFBP to be defective shall be either ▪ inspected,tested,and maintained by a repaired or replaced, at TFBP's sole qualified Inspection Service in accord- option. TFBP neither assumes, nor ance with local requirements and/or authorizes any person to assume for it, national codes. any other obligation in connection with • the sale of products or parts of prod- ucts.NOTICE TFBP shall not be responsible for sprinkler system design errors or inac- Before closing a fire protection system gate or incomplete information sup- control valve for inspection or mainte- plied by Buyer or Buyer's repre- nance work on the fire protection sys- tem sentatives. thatitcontrols,permissiontoshut In no event shall TFBP be liable, in down the affected fire protection sys- contract, tort, strict liability or under tern must first be obtained from the any other legal theory, for incidental, proper authorities and all personnel indirect,special or consequential dam- who may be affected by this action ages, including but not limited to labor must be notified. charges, regardless of whether TFBP was informed about the possibility of After placing a fire protection system such damages, and in no event shall in service, notify the proper authorities TFBP's liability exceed an amount and advise those responsible for moni- equal to the sales price. toting proprietary and/or central sta- The foregoing warranty is made in lieu tion alarms. of any and all other warranties. ex- press or implied. including warranties of merchantability and fitness fora par- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. 0 2008 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 • HFS-4 • Effective 4/1/99 Revised 10/15/03 HARVEL° BLAZEMASTER"CPVC FIRE SPRINKLER PIPE, 1FML'ILPcF INsF-awl ASTM 5' • 2ha t L eE.fn.9 Btv 3 . ✓ ., klxa .i-,;, .iY �° .Fm h-,A'N#..p„� of .s tr.",^t ' 4iS.Y?i:s:m"—�JS sue# .1.Rd}F rdN.'Y to wx}2 4.&.J • DARNEL' PLASTICS. INC. Harvel® BlazeMasterco CPVC Fire Sprinkler Friction Loss Table t ` 44� . 411,t a S..• s. 2-7d ��� �likk * s , ,` lir 4 � a 4 `. A; e..rar...r .. ..,... � ,3 ` , m w The QUALITY Line •▪ " Friction Loss (PSI per linear foot) and Velocity (feet per second) ' (Hazen-Williams C Factor=150) Nominal Pipe Size: 3/4 inch 1 inch 1 1/4 inches 1 1/2 inches 2 inches 2112 inches 3 inches Avg,I.O. (inches) (.874) (1.101) (1.394) (1.598) (2.003) (2.423) (2.950) Friction Friction Friction Friction Friction Friction Friction GPM Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity 1 0.0008 0.5 0.0003 0.3 0.0001 0.2 0.0000 0.2 0.0000 0.1 0.0000 0.1 0.0000 0.0 2 0.0030 1.1 0.0010 0.7 0.0003 0.4 0.0002 0.3 0.0061 0.2 00000 0.1 0.0000 0.1 3 0.0063 1.6 0.0020 1.0 0.0006 0.6 0.0003 0.5 0.0001 0.3 0.0000 0.2 0.0000 0.1 4 0.0107 2.1 0.0035 1.3 0.0011 0.8 0.00106 0.6 0.0002 0.4 0.0001 0.3 0.0000 0.2 5 0.0161 2.7 0.0052 1.7 0.0017 1.1 0.0009 0.8 0.0003 0.5 0.0001 0.3 0.0000 0.2 6 0.0226 3.2 0.0073 2.0 0.0023 1.3 0.0012 1.0 0.0004 0.6 0.0002 0.4 0.0001 0.3 7 0.0300 3.7 0.0098 2.4 0.0031 1.5 0.0016 1.1 0.0005 0.7 0.0002 0.5 0.0001 0.3 8 0.0385 4.3 0.0125 2.7 0.0040 1.7 0.0020 1.3 0.0007 0.8 0.0003 0.6 0.0001 0.4 9 0.0478 4.8 0.0155 3.0 0.0049 1.9 0.0025 1.4 0.0008 0.9 0.0003 0.6 0.0001 0.4 10 0.0581 5.3 0.0189 3.4 0.0060 2.1 0.0031 1.6 0.0010 1.0 0.0004 0.7 0.0002 0.5 11 0.0693 5.9 0.0225 3.7 0.0071 2.3 0.0037 1.8 0.0012 1,1 0.0005 0.8 0.0002 0.5 12 0.0814 6.4 0.0264 4.0 0.0084 2.5 0.0043 1.9 0.0014 1.2 0.0006 0.8 0.0002 0.6 13 0.0944 7.0 0.0307 4.4 0.0097 2.7 0.0050 2.1 0.0017 1.3 0.0007 0.9 0.0003 0.6 14 0.1083 7.5 0.0352 4.7 0.0111 2.9 0.0057 2.2 0.0019 1.4 0.0008 1.0 0.0003 0.7 15 0.1230 8.0 0.0400 5.1 0.0127 3.2 0.0065 2.4 0.0022 1.5 0.0009 1.0 0.0003 0.7 16 0.1386 8.6 0.04,50 5.4 0.0143 3.4 0.0073 2.6 0.0024 1.6 0.0010 1.1 0.0004 0.8 17 0.1551 9.1 0.0504 5.7 0.0160 3.6 0.0082 2.7 0.0027 1.7 0.0011 1.2 0.0004 0.8 18 0.1724 9.6 0.0560 6.1 0.0177 3.8 0.0091 2.9 0.0030 1.8 0.0012 1.3 0.0005 0.8 19 0.1905 10.2 0.0619 6.4 0.0196 4.0 0.0101 3.0 0.0034 1.9 0.0013 1.3 0.0005 0.9 20 0.2095 10.7 0.0680 6.7 0.0216 4.2 0.0111 3.2 0.0037 2.0 0.0015 1.4 0.0006 0.9 21 0.2293 11.2 0.0745 7.1 0.0236 4.4 0.0121 3.4 0.0040 2.1 0.0016 1.5 0.0006 1.0 22 0.2499 11.8 0.0812 7.4 0.0257 4.6 0.0132 3.5 0.0044 2.2 0.0017 1.5 0.0007 1.0 23 02713 12.3 0.0881 7.8 0.0279 4.8 0.0144 3.7 0.0048 2.3 0.0019 1.6 0.0007 1,1 24 0.2935 12.8 0.0953 8.1 0.0302 5.0 0.0155 3.8 0.0052 2.4 0.0020 1.7 0.0008 1.1 25 0.3165 13.4 0.1028 8.4 0.0326 5.3 0.0168 4.0 0.0056 2.5 0.0022 1.7 0.0008 1.2 26 0.3403 13.9 0.1106 8.8 0.0350 5.5 0.0180 4.2 0.0060 2.6 0.0024 1.8 0.0009 1.2 27 0.3649 14.4 0.1185 9.1 0.0376 5.7 0.0193 4.3 0.0064 2.7 0.0025 1.9 0.0010 1.3 . 28 0.3903 15.0 0.1268 9.4 0.0402 5.9 0.0207 4.5 0.0069 2.9 0.0027 1.9 0.0010 1.3 29 0.4165 15.5 0.1353 9.8 0.0429 6.1 0.0220 4.6 0.0073 3.0 0.0029 2.0 0.0011 1.4 30 0.4435 16.0 0.1441 10.1 0.0457 6.3 0.0235 4.8 0.0078 3.1 0.0031 2.1 0.0012 1.4 31 0.4712 16.6 0.1531 10.4 0.0485 6.5 0.0249 5.0 0.0083 3.2 0.0033 2.2 0.0013 1,5 32 0.4997 17.1 0.1623 10.8 0.0514 6.7 0.0265 5.1 0.0088 3.3 0.0035 2.2 0.0013 1.5 33 0.5290 17.6 0.1718 11.1 0.0545 6.9 0.0280 5.3 0.0093 3.4 0.0037 2.3 0.0014 1.5 - 34 0.5590 18.2 0.1816 11.5 0.0576 7.1 0.0296 5.4 0.0098 3.5 0.0039 2.4 0.0015 1.6 35 0.5898 18.7 0.1916 11.8 0.0607 7.4 0.0312 5.6 0.0104 3.6 0.0041 2.4 0.0016 1.6 36 0.6214 19.3 0.2018 12.1 0.0640 7.6 0.0329 5.8 0.0109 3.7 0.0043 2.5 0.0017 1.7 37 0.6537 19.8 0.2123 12.5 0.0673 7.8 0.0346 5.9 0.0115 3.8 0.0046 2.6 0.0017 1.7 38 0.6868 20.3 0.2231 12.8 0.0707 8.0 0.0364 6.1 0.0121 3.9 0.0048 2.6 0.0018 1.8 39 0.7206 20.9 0.2341 13.1 0.0742 8.2 0.0381 6.2 0.0127 4.0 0.0050 2.7 0.0019 1.8 40 0.7551 21.4 0.2453 13.5 0.0777 8.4 0.0400 6.4 0.0133 4.1 0.0053 2.8 0.0020 1.9 41 0.7904 21.9 0.2568 13.8 0.0814 8.6 0.0418 6.6 0.0139 4.2 0.0055 2.9 0.0021 1.9 42 0.8265 22.5 02685 142 0.0851 8.8 0.0437 6.7 0.0146 4.3 0.0058 2.9 0.0022 2.0 43 0.8632 23.0 0.2804 14.5 0.0889 9.0 0.0457 6.9 0.0152 4.4 0.0060 3.0 0.0023 2.0 44 0.9007 23.5 0.2926 14.8 0.0927 9.2 0.0477 7.0 0.0159 4.5 0.0063 3.1 0.0024 2.1 45 0.9390 24.1 0.3050 15.2 0.0967 9.5 0.0497 7.2 0.0165 4.6 0.0065 3.1 0.0025 2.1 46 0.9779 24.6 0.3177 15.5 0.1007 9.7 0.0518 7.4 0.0172 4.7 0.0068 3.2 0.0026 2.2 47 1.0176 25.1 0.3306 15.8 0.1048 9.9 0.0539 7.5 0.0179 4.8 0.0071 3.3 0.0027 2.2 48 1.0580 25.7 0.3437 16.2 0.1089 10.1 0.0560 7.7 0.0186 4.9 0.0074 3.3 0.0028 2.3 49 1.0992 26.2 0.3570 16.5 0.1132 10.3 0.0582 7.8 0.0194 5.0 0.0077 3.4 0.0029 2.3 50 1.1410 26.7 0.3706 16.8 0.1175 10.5 0.0604 8.0 0.0201 5.1 0.0080 3.5 0.0031 2.3 52 1.2269 27.8 0.3985 17.5 0.1203 10.9 0.0649 8.3 0.0216 5.3 0.0086 3.6 0.0033 2.4 54 1.3156 28.9 0.4274 18.2 0.1354 11.4 0.0696 8.6 0.0232 5.5 0.0092 3.8 0.0035 2.5 56 1.4072 29.9 0.4571 18.9 0.1449 11.8 0.0745 9.0 0.0248 5.7 0.0098 3.9 0.0038 2.6 58 1.5016 31.0 0.4878 19.5 0.1546 122 0.0795 9.3 0.0265 5.9 0.0105 4.0 0.0040 2.7 60 1.5988 32.1 0.5193 20.2 0.1646 12.6 0.0846 9.6 0.0282 6.1 0.0111 4.2 0,0043 2.8 62 1.6988 33.2 0.5518 20.9 0.1749 13.0 0.0899 9.9 0.0299 6.3 0.0118 4.3 0.0045 2.9 64 1.8015 34.2 0.5852 21.6 0.1855 13.5 0.0954 10.2 0.0317 6.5 0.0126 4.5 0.0048 3.0 66 1.9071 35.3 0.6195 22.2 0.1963 13.9 0.1010 10.6 0.0336 6.7 0.0133 4.6 0.0051 3.1 • 68 2.0153 36.4 0.6546 22.9 0.2075 14.3 0.1067 10.9 0.0355 6.9 0.0141 4.7 0.0054 3.2 70 2.1264 37.4 0.6907 23.6 0.2189 14.7 0.1126 11.2 0.0375 7.1 0.0148 4.9 0.0057 3.3 GPM 72 0.7277 24.3 0.2306 15.1 0.1186 11.5 0.0395 7.3 0.0156 5.0 0.0060 3.4 ' 74 0.7655 24.9 0.2426 15.6 0.1247 11.8 0.0415 7.5 0.0164 5.1 0.0063 3.5 76 0.8042 25.6 0.2549 16.0 0.1311 12.2 0.0436 7.7 0.0173 5.3 0.0066 3.6 78 0.8438 26.3 0.2674 16.4 0.1375 12.5 0.0458 7.9 0.0181 5.4 0.0069 3.7 80 0.8843 27.0 0.2802 16.8 0.1441 12.8 0.0480 8.1 0.0190 5.6 0.0073 3.8 82 0.9256 27.6 0.2933 17.2 0.1508 13.1 0.0502 8.3 0.0199 5.7 0.0076 3.8 84 0.9678 28.3 0.3067 17.7 0.1577 13.4 0.0525 8.6 0.0208 5.8 0.0080 3.9 - 86 1.0109 29.0 0.3204 18.1 0.1647 13.8 0.0548 8.8 0.0217 6.0 0.0083 4.0 88 1.0548 29.7 0.3343 18.5 0.1719 14.1 0.0572 9.0 0.0226 6.1 0.0087 4.1 90 1.0995 30.3 0.3485 18.9 0.1792 14.4 0.0596 9.2 0.0236 6.3 0.0091 4.2 Nominal Pipe Size: 1 inch 1114laches 1 112 inches 2 inches 212 inches 3 inches Avg,1.D. (inches) (1.101) (1.394) (1.598) (2.003) (2.423) (2.950) Friction Friction Friction Friction Friction Friction GPM Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity Loss Velocity 92 1.1452 31.0 0.3629 19.3 0.1866 14.7 0.0621 9.4 0.0246 6.4 00094 4.3 94 1.1917 31.7 0.3777 19.8 0.1942 15.0 0.0646 9.6 0.0256 6.5 0.0098 4.4 96 1.2390 32.3 0.3927 20.2 0.2019 15.4 0.0672 9.8 0.0266 6.7 0.0102 4.5 98 1.2872 33.0 0.4079 20.6 0.2098 15.7 0.0698 10.0 0.0276 6.8 0.0106 4.6 100 1.3362 33.7 0.4235 21.0 0.2177 16.0 0.0725 10.2 0.0287 7.0 0.0110 4.7 110 1.5938 37.1 0.5051 23.1 0.2597 17.6 0.0864 11.2 0.0342 7.7 0.0131 5.2 120 1.8722 40.4 0.5933 25.2 0.3051 19.2 0.1015 12.2 0.0402 8.3 0.0154 5.6 130 2.1710 43.8 0.6880 27.3 0.3538 20.8 0.1178 13.2 0.0466 9.0 0.0179 6.1 GPM 140 0.7891 29.4 0.4058 22.4 0.1351 14.3 0.0534 9.7 0.0205 6.6 150 0.8966 31.5 0.4610 24.0 0.1534 15.3 0.0607 10.4 0.0233 7.0 160 1.0103 33.6 0.5195 25.6 0.1729 16.3 0.0684 11.1 0.0262 7.5 170 1.1302 35.7 0.5811 27.2 0.1934 17.3 0.0765 11.8 0.0294 8.0 180 1.2562 37.8 0.6460 28.8 0.2150 18.3 0.0851 12.5 0.0326 8.4 190 1.3884 39.9 0.7139 30.4 0.2376 19.3 0.0940 13.2 0.0361 8.9 200 1.5268 42.0 0.785D 32.0 0.2613 20.4 0.1034 13.9 0.0396 9.4 210 1.6708 44.1 0.8591 33.6 0.2859 21.4 0.1132 14.6 0.0434 9.9 220 1.8209 46.2 0.9363 35.2 0.3116 22.4 0.1233 15.3 0.0473 10.3 230 1.9770 48.3 1.0166 36.8 0.3384 23.4 0.1339 16.0 0.0513 10.8 240 2.1390 50.4 1.0999 38.4 0.3661 24.4 0.1449 16.7 0.0556 11.3 250 2.3067 52.6 1.1862 40.0 0.3948 25.5 0.1562 17.4 0.0599 11.7 GPM 260 1.2754 41.6 0.4245 26.5 0.1680 18.1 0.0644 12.2 - 270 1.3676 43.2 0.4552 27.5 0.1801 18.8 0.0691 12.7 280 1.4628 44.8 0.4869 28.5 0.1927 19.5 0.0739 13.1 290 1.5609 46.4 0.5195 29.5 0.2056 20.2 0.0788 13.6 300 1.6620 48.0 0.5532 30.5 0.2189 20.9 0.0839 14.1 Harvel® BlazeMaster' 310 1.7659 49.6 0.5878 31.6 0.2326 21.6 0.0892 14.6 _ 320 1.8727 51.2 0.6233 32.6 0.2467 22.3 0.0946 15.0 CPVC Fire Sprinkler 330 1.9824 52.8 340 2.0950 54.4 0.6598 33.6 0.6973 346 027759 23.11 77 0.1058 16.0 GPM 350 0.7357 35.6 0.2911 24.4 0.1117 16.4 360 0.7751 36.7 0.3067 25.0 0.1176 16.9 • 370 0.8154 37.7 0.3227 25.7 0.1237 17.4 Friction Loss Table 380 0.8566 38.7 0.3390 26.4 0.1300 17.8 390 0.8988 39.7 0.3557 27.1 0.1364 18.3 400 0.9419 40.7 0.3727 27.8 0.1429 18.8 410 0.9859 41.7 0.3901 28.5 0.1496 19.2 430 1.0767 43.8 0.4261 29.9 0,1634 20.2 450 1.1712 45.8 0.4635 31.3 0.1777 21.1 470 1.2693 47.9 0.5023 32.7 0.1926 22.1 490 1.3710 49.9 0.5425 34.1 0.2081 IIARIVEL® 510 530 1.5852 51.9 0.5842 36.9 0.2406 24.9 1.5852 54.0 0.6273 36.9 0.2406 24.9 550 1.6977 56.0 0.6718 38.3 0.2576 25.8 PLASTICS, INC. 570 1.8136 58.0 0.7177 39.7 0.2752 26.8 590 1.9331 60.1 0.7650 41.0 0.2934 27.7 300 Kuebler Rd.,P.O.Box 757,Easton,PA 18044-0757 610 2.0561 62.1 0.8136 42.4 0.3120 28.6 7 Phone:610-252-7355 Fax:610-253-4436 MI 6500.9151 43.8 0.3312 30.5 51 45.2 0.3509 30.5 www.HarvelSprinklerPipe.com •e-mail:harvel@harvel.com 670 0.9878 46.6 0.3712 31.4 690 1.0220 48.0 0.3919 32.4 720 1,1057 50.1 0.4240 33.8 750 1.1924 52.2 0.4573 35.2 780 1.2822 54.3 0.4917 36.6 Allowance for Friction Loss in Fittings 810 1.3749 56.4 0.5273 38.0 640 1.4706 58.4 0.5640 39.4 870 1.5692 60.5 0.6018 40.8 3/4" 1" 11/4" 112 2" 21f2 3" 900 1.6708 62.6 0.6407 42.2 930 1.7753 64.7 0.6808 43.7 Tee Run 1 1 1 1 1 2 2 960 1.8827 66.8 0.7220 45.1 Tee Branch 3 5 6 8 10 12 15 1000 2.0303 69.6 0.7786 46.9 90'Elbow 7 7 8 9 11 12 13 45'Elbow 1 1 2 2 2 3 4 . Coupling 1 1 1 1 1 2 2 • • FOR CPVC PIPE P POTTER. VSR-SG VANE TYPE WATERFLOW ALARM The Symbol of Protection SWITCH WITH RETARD AND GLUE-IN UNION CUL,UL and CSFM Listed Service Pressure: Up to 175 PSI(12,07 BAR) mv2 Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)-UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red powdercoat finish No.1144460: Cover held in place with tamper resistant screws No.1144461: Tamper:Cover incorporates micro-switch. Cover Tamper:Activated by cover removal Cover Tamper Switch Contacts: One set SPDT,Rated at 250VAC Cover Tamper Switch Terminations:8"22AWG wire leads Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC Conduit Entrances: Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed CPVC plastic piping systems manufactured by Central Sprinkler Corp.,Grinnell Sprinkler Corp.,Spears Manufacturing Co.,NIBCO,and IPEX(Scepter). Fits pipe sizes-1", 1-1/4", 1-1/2"and 2" AWARN 1 N G Environmental Specifications: • NEMA 4/1P55 rated enclosure suitable for indoor or outdoor use Installation must be perfomed by qualified personnel and in with factory installed gasket and die-cast housing accordance with all national and local codes and ordinances. • Temperature range:40°F to 120°F(4,5'C to 49°C)-UL Shock hazard. Disconnect power source before servicing. Stock Number: 1144460 Serious injury or death could result. 1144461 w/TSK Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13 injury or death could result. One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Replaceable Components:Retard/Switch Assembly,stock no. 1029030 The Model VSR-SG is a vane type waterflow switch for use on wet sprinkler on how to change paddle.Verify that the o-ring is properly positioned in its systems using CPVC plastic fittings manufactured by Central Sprinkler groove.Hand tighten the nut on the union after orienting the device in the Corp., Grinnell Sprinkler Corp., Spears Manufacturing Co., and IPEX appropriate direction to detect waterflow as shown in Fig.2. (Scepter)that use 1", 1-1/4", 1-1/2"or 2" pipe sizes.It is equipped with a union to accommodate installation in confined spaces. AI CAUTION The unit contains two single pole double throw snap action switches and an adjustable,instantly recycling pneumatic retard.The switches are actuated Do not over-tighten the union nut,hand tighten only. when a flow of 10 gallons per minute(38 liters per minute)or more occurs downstream of the device.The flow condition must exist fora period of time The vane must not rub the inside of the TEE or bind in any way.The stem necessary to overcome the selected retard period. should move freely when operated by hand. Installation(See Fig 1 and 2) Nose:Do not leave cover off for an extended period of time. These devices may be mounted on horizontal or vertical pipe.On horizontal pipe they should be installed on the top side of the pipe where they will be Inspection And Testing accessible.The units should not be installed within 6" (15 cm)of a valve, Check the operation of the unit by opening the inspector's test valve at the drain or fitting which changes the direction of the waterflow.The unit has a end of the sprinkler line or the drain and test connection,if an inspector's 1"male fitting for gluing into a CPVC plastic TEE test valve is not provided. Loosen the union nut and separate the 1" male fitting from the VSR-SG. If there are no provisions for testing the operation of the flow detection device Glue the 1" male fitting into the TEE following the TEE manufacturers on the system,application of the VSR-SG is not recommended or advisable. instructions for preparation and gluing of CPVC piping systems.(Note:The The frequency of the inspection and testing and its associated protective 1"male fitting must bottom out on the stop of the TEE for proper operation monitoring system should be in accordance with the applicable NFPA of the VSR-SG.See Fig.1.)Wait 2 to 4 hours to allow the glue to dry before Codes and Standards and/or authority having jurisdiction (manufacturer • attaching the VSR-SG to the 1" male fitting.Select the proper paddle for recommends quarterly or more frequently). the pipe size and type of TEE used.See Fig.3 and Fig.5 for instructions Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com - - PRINTED IN USA MFG.#5401205-REV F PAGE 1 OF 3 12/08 FOR CPVC PIPE - (_, POTTER VSR-SG VANE TYPE WATERFLOW ALARM The Symbol of Protection SWITCH WITH RETARD AND GLUE-IN UNION Fig. 1 Fig.2 Optional Cover Tamper Switch Do mt reme cover off for e.Vere*dperid oftlme 9 Retard Adjustment (MINIMUMREQUIRED CLEARANCEFOR1" MALE FITTING The delay can be adjusted b_ rotating the retard .. INSTALLATIONFOR �' g R�ARp OR MUST BOTTOM OUT AnrtiSTMENT �/ I� REMOVAL OF DEVICE) ON STOP adjustment knob from Oto the max setting(60- KNOB ` jl� � 90seconds).The time delay should beset atthe �.�. minimum required to prevent false alarms. ,� \ '> ili I l r ��: �1 wohaili' Fig 3 \.� .Er_.• � 41,1 ill ;, 1I Gr � Otl,n��� I' I ACAUTION �' Insure that O-mgiain ON BASEUNT SO ARROW NO BUSHINGS. ON POPvTS INSERTS OR MIC.�10E3-3]ji � �' IN DIRECTION OF ADAPTERS DWG. #1082-1 installing switch =-O = W.ATERFLOW' ARE PERNIITED Important: 7 paddles are furnished with each unit 1"MALE FITTING to accommodate the various sizes and ON ALL SIZES Glue the 1"male fitting into the TEE following manufacturers of TEES. The paddles have raised lettering that show the pipe size and the TEE manufacturer's instructions for the TEE manufacturer they are to be used ri1 preparation and gluing of CPVC piping with. The proper paddle must be used The ( 2) to systems. Wait 2 to 4 hours to allow the glue paddle must be properly attached(see Fig.3) to dry before attaching the VSR-SG to the 1" and the screw that holds the paddle must be RUN OF THE TEE male fitting. securely tightened. Flawing water activas MAY HE1,IIAP, deVice it ere drecticm oily 11/2",OR 2" - Fig.4 Typical Electrical Connections Cover Tamper Switch Notes: _ 0 NEGATNEDCOR (Shown with cover in place) r J NEUTRALAC 1. The Model VSR-SG has two switches, one can fl-?1 1=0 De - be used too rate a central station, ro rieta or .� — I+'1 I ORHOTAGPe h P rY r ti:Ef OR HOTACremote signaling unit,while the other is used to w • �I.'operate a local audible or visual annunciator. 1 1 �+,i Il " C. N.o. N C 2. For supervised circuits see "Switch Terminal I�r +�� II WATtalFLow ZONE wnn tREo> (BLK) Connections"drawingand caution note(Fig.6). • ON FIRE PANEL Fig.5 Grinnell TEE Fig 6 Switch Terminal Connections Clamping Plate Terminal TEE's manufactured prior TEE's manufactured to 5/99 alter 5,99 WIIS"SI rJ o. DWG. "062� A WARNING Notice: An uninsulated section of a single conductor should not he looped around the As of 5/99 Grinnell has changed the design of their TF,F,fittings.The new fittings will require terminal and serve as two separate connections.The wire must be severed, the use of the standard paddle,while you will still be required to use the paddle marked thereby providing supervision of the connection in the event that the wire Grinnell on all fittings manufactured prior to this date Failure to install the correct paddle become dislodged from under the terminal.Failure 10 sever the wire may could cause the device to malfunction or operate improperly. render the device inoperable risking severe property damage and loss of life. A CAUTION Watertlow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF,deluge,or chemical suppression systems.Watetflowswitches used forthis applicationmay result in unintended discharges caused by surges,trapped air,or short retard times. - PRINTED IN USA MFG.85401205-REV F PAGE 2 OF 3 12/08 FOR CPVC PIPE P . POTTER VSR-SG VANE TYPE WATERFLOW ALARM The Symbol of Protection SWITCH WITH RETARD AND GLUE-IN UNION Fig.7 Break out thin section of cover when wiring both switches from one conduit entrance. V') �?•' 14 • c.... 1 ( .dam '��'1.1/'I II DWG#1205-4 i Testing The frequency of inspection and testing for the Model VSR-SG and order replacement retard switch assembly stock number 1029030.There ` its associated protective monitoring system should be in accordance is no maintenance required,only periodic testing and inspection. with applicable NFPA Codes and Standards and'or the authority having Important Notice jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspectors test valve,that is usually located at the end Please advise the person responsible for testing of the fire protection system of the most remote branch line,should always be used for test purposes. that this system must be tested in accordance with the testing instructions. If there are no provisions for testing the operation of the flow detection Removal device on the system,application of the VSR-SG is not recommended • To prevent accidental water damage,all control valves should be or advisable. shut tight and the system completely drained before waterflow A minimum flow of 10 GPM(38 LPM)is required to activate this device. detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. Maintenance • Loosen union nut and separate unit from the glued in fitting. Inspectdetectors monthly for leaks.Ifleaks are found,replacethedetector. • Gently lift the unit far enough to get your fingers under it.With The VSR-SG waterflow switch should provide years of trouble-free your fingers,roll the vane so it will fit through the fitting while service. The retard and switch assembly are easily field replaceable.In continuing to lift the waterflow detector. the unlikely event that either component does not perfonn properly,please • Lift detector clear of pipe. - - PRINTED 1N USA MFG.#5401205-REV F PAGE 3 OF 3 12/08 • . p. PO BELLS The Symbol of Protection PBA-AC& MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) .)0 Voltages Available: 24VAC 120VAC a 1. - 12VDC(10.2 to 15.6)Polarized ',It*. 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm „t. General Signaling0 Burglar Alarm Environment Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWO stranded wires Q ( DC Bells-Terminal strip Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ` ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in III, for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA126 1750070 .12A 85 76 8(200) 12VDC MBA128 1750080 .12A 90 77 10(250) 12VDC MBA1210 1750060 .12A 92 78 6(150) 24VDC MBA246 1750100 .06A 87 77 8(200) 24VDC MBA248 1750110 .06A 91 79 10(250) 24VDC MBA2410 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PRA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have LJI,C listing. A WAR N I N G In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes • will not provide a weatherproof enclosure.If the bell and/or assembly • is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company,LLC•2081 Craig Road St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com - • PRINTED IN USA MFG.45400776-REV Y PAGE I OF 2 5/08 . . p0 BELLS e The Symbol of Protection PBA-AC& MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. l Fig.3 t i '[f]) R" • (200) 6' 1 (150) II III PROM CONTRO L.W Hn(IN) PANEL OR PRECEDING BELL A.C..C. BELLS 10111111411 111 BLACK(IN) �� WHITE our? HI ArK Kit CAUTION: WHEN ELECTRICALSUPERVISION IS REQUIRED USE IN AND MIT LEADS AS SHOWN_ 211/16" (68)_.] NDTIM I.WHEN USING AC BELLS,TERMINATE EACH ULTRA WIRE SEPARATELYAI•MR LAST HELL 2.ENU-IN•-LINE RESISTOR IS NOT RL'QUIREU ON AL:BELLS. OWES 76-3 Weatherproof Backbox Dimensions Inches(mm) • Fig.2 FACP Box has one threaded 112"conduit entrance 1 ■■I a 53(4" O _ 33/R" 5" 1 To Next (146) (') (127) 1 Device or _ _ End-of-line Resistor w 1..._ 33/R" 1 5/8" (86) (41) 4 1/4" (108) Installation OW'CA 776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and 'Q. not less than 6"below the ceiling. r. 2. Remove the gong. iii oft, o ... / 3. Connect wiring(see Fig.3). oi 4 •• 100 4. Mount bell mechanism to backbox(bell mechanism must be �L mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). �y» 6. Test all bells for proper operation and observe that they can Box-I / be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). AWARNING • Failure to install striker down will prevent bell from operating. • - PRINTED IN USA MFG.#5400776-REV Y PAGE 2 OF 2 5/0R r, s RBVS• UNIVERSAL BALL The Symbol of Protection VALVE SWITCH rt.,and ell,Listed,FM,CSFM Approved Dimensions: (including mounting clamps) Large Clamps: 6"L x 5"W x 5.2"H 15,2cm1.x12,7cmWx13,2cmH Small Clamps: 6"L x 4"W x 5.2"H 15,2cmLx 10,2cmWx13,2cmH Weight: With Large Clamps: 13.6 oz.(386,9 g.) With Small Clamps: 11.0 oz.(311,2 g.) Enclosure: Non-Corrosive Composite Material �' Environmental Limitations: • NEMA4 rated enclosure when proper electrical fittings are used.(IP67) • Temperature range:-40°F to 150'F(-40°C to 65°C) • Not for use in hazardous locations Housing Cover Tamper: Activated by housing cover removal US Patent No.6,945,509 (Stock No. 1000035 only) Contact Ratings: SPDT Contacts: l0A at 125/250 VAC RBVS Stock No.1000040(w/o Cover Tamper) 2A at 30 VDC RBVS-T Stock No. 1000035(w/Cover Tamper) SPDT Cover Tamper: 3A at 250 VAC General Installation On Lever Handle(See Fig.2) The Model RBVS is designed to monitor the fully open position of a ball valve I. Selectdamlxs and clamping bolts based upon pipe/valve size,see Table 1. installed in a sprinkler system.The unit will fit on most ball valves installed on 2. Insert rubber clamp grippers into clamps,see Fig.2. back-fiow-preventers and alarm trim lines of dry;alarm,and deluge sprinkler 3. Place one clamp on top of pipe/ball valve near the valve handle and valves.The switch operates if the ball valve handle is moved from the open insert clamping bolts through it. position.However,the switch does not track the position of the handle or ball. 4. Place other clamp over clamping bolts from beneath the installation and When the ball valve handle is in the open position,a spring-loaded switch button thread hex nuts onto the clamping bolts,but do not fully tighten,(be sure will contact the valve handle.When the handle is moved from the open position, hex nuts seat properly in clamp hex recesses).(NOTE:Some installations this switch button extends to the tripped position,and the REVS contacts change may require one of the mounting bolts to be inserted from the bottom of state,thereby opening or closing a circuit.Acover tamper switch is available and the brackets and then trimmed to allow the extension bracket to clear. is activated by the removal of the RBVS housing cover.If an attempt is made See Fig.4) to remove the RBVS by the removal of the mounting brackets,the unit will be 5. Attach extension bracket(if necessary to use for positioning)to top clamp set into the tripped mode by this action. using 3/4-20 X'/:"Ilex bolt and washer but do not fully tighten. The RBVS can be mounted to the hex portion of the ball valve or back-flow- 6. Attach"L"bracket(RBVS switch enclosure is loosely attached to"L" preventerorto the adjoining pipe via two clamps.The RBVS is shipped withtwo bracket)Laextensionbracketusing'/<-20X'/d'Hexboltandwasher,but sets of mounting clamps to accommodate various pipe and valve sizes,refer to do not fully tighten. Table 1.An"I."shaped and offset bracket for mounting the switch enclosure and 7. Be sure ball valve is in the fully open position. 8. Slide loosely assembled RBVS switch enclosure to a position that permits an extension bracket add to the mounting flexibility of the RBVS.See"Typical the switch button to contact the valve handle approximately 1" from its Mounting Diagram"and Installation and Operation"on following page. inside end.See Fig.I for approximate location.Cut and remove the plastic Testing coating from the ball valve handle to allow the RBVS switch button to The RBVS and its aaszviated pioi ttive monitoring system should be tested contact(and be activated by)the metal of the handle. in accordance with applicable NFPA codes and standards and/or the authority 9. Tighten clamping screws alternately to an eventual 30 in-lbs.(minimum) having jurisdiction(manufacturer recommends quarterly or more frequently). of torque. 10. Maintain position of switch enclosure over valve handle and secure bolt Fig.l Internal Components that holds the extension bracket to the clamping assembly. It may be NORMALLY OPEN necessary to close valve to access this bolt. 11. Position"L"bracket sin that it contacts tre back edge of the valve handle,and NORMALLY CLOSED ��,_ -�_, secure its boll It may be necessary m close valve to access this bolt. COMMON 1 °� �3, 12.With the actuator fully retracted, position RBVS switch enclosure to �' ��-Tj t ' \ C-_c �� contact the valve handle squarely.see Fig. 1. '�\'1 13. With RBVS switch enclosure held squarely in contact with valve handle, STRAIN RELIEF !"---�.- t �' ► 1�'�; SWITCH BUTTON securely tighten the two tamper resistant screws on the backside of the BLACK - N.O. \��+a( 1�2' COVER RED - N.C. -�•� LOCATION enclosure. TAMPER �� ON HANDLE wHnE - coM nl� 14. Close and open the valve to verify operation.The actuator should easily ,�_�' retract when the valve handle is in the open position. "�► 15. Fully open the valve. MOUNT so 16. Remove the cover and wire main switch and tamperswitch if applicable. SWITCH BUTTON ;\i, PP • PLASTIC COATING IS APPROX. 1` FROM REMOVED FROM Carefully route tamper switch wires through strain relief channel in switch • HANDLE INSIDE END BALL VALVE HANDLE enclosure.Fully seat the wires into the bottom of the channel.See Fig.1. IN SWITCH BUTTON Re place g DWG B 1 oae-t CONTACT AREA 17. RBVS switch enclosure cover and securely tighten cover screw. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com - - PRINTED IN USA MFG.#5401086-RSV U PAGE 1 OF 2 5/08 r. w P POTTERRBVS UNIVERSAL BALL e The Symbol of Protection VALVE SWITCH Fig.2 Typical Mounting Diagram Table 1 Clamp Sizing LENGTH Pipe Valve/Size Clamp Clamping Bolts 6' SWITCH 1/2"to 3/4"(12,5 to 19mm) Small 10-32 x 2 1/2 �� ENCLOSURE 1�1 I"to 2"(25 to SOmm) Large 1/4-20 x 4" 1' BRACKET �� HEIGHT Switch Terminal Connections,Clamping Plate Terminal .� �r —=_EM, BRACKET 0� 5.2- ��r =` (IF NECESSARY111.1111111 l r �� (' A CAUTION CLAMPS rl �� Anuninsulatedsectionofsingleconductor III ' l . ��������� should not be looped around the terminal ■ �� -i III and serve as twos teconnections.The I'i i t CLAMP r�1•� o TmU """�4'" wire must be severed,ere thereby providing GRIPPERS supervision of the connection in the event WIDTH 4" (SMALL) L'- that the wire becomes dislodged from DWG #1086-2 5' (LARGE) under the terminal. Typical Electrical Connections LOCAL CIRCUIT TRANSFORMER OR BATTERY POWER STYLE D (CLASS A) SUPERVISED LOOP STYLE B (CLASS B) SUPERVISED CIRCUIT N,C, '1r `^--I SICWLLING COM. COY. ;COH.C. KO. OEMCF CONTROL COM. END-OF-LINE RESISTOR N N.O.N.C. AV.0. UNIT N.O. DWG, /1086-4 Tamper Switch Connections Fig.3 COVER TAMPER & REVS CONNECTED COVER TAMPER & RBVS WIRED SWITCH wavu,E TO THE SAME ZONE ON THE FACP TO SEPERATE ZONES COVER Cql. N 0.C . P TAMPER / _ OFFSET BRACKET�' -^� COM Ito. COu i^\ ' I� FAG. COVER EO tR N�- �y 1 • DaiRER FMP MLR FNP EOLR 0 Q.-1 t KO. / ll ' ONO.41086-S .� r 1011�;,i or Installation on Tee Handle(See Fig.3) T s� "R NjN I�11 '' 1 1. Select clamps and clamping bolls based upon pipe/valve size,see Table 1. v IIIf 4�� 2. Insert rubber clamp grippers into clamps,See Fig.3. _ „I 3. Place one clamp on top of pipe/ball valve near the valve handle and "" { s �ur insert clamping bolts through it. � � 1 4. Place other clamp over clamping bolts from beneath the installation of"s r oeN and thread hex nuts onto the clamping bolts,but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses). 5. Loosely attach "L" bracket to the "offset" bracket and "offset" Fig.4 bracket to the RBVS housing. 6. Be sure ball valve is in the fully open position. —-- , 7. Slide loosely assembled RBVS switch enclosure to a position that KBEs permits the switch button to contact the valve handle approximately — all 1/2"from the end of the handle.Cut and remove the plastic coating I from the ball valve handle to allow the RBVS switch button to contact ,`•_ _ (and be activated by)the metal of the handle. 111112,. 1 8. Tighten clamping screws alternately and'/4-20X'/4"bolt to 30 in-lbs. (minimum)of torque. SOMEINSTALLArIONS MAY w9!„ 9. With the valve handle fully open, slide the RBVS housing down CAUSE INTERFERENCE _t until the switch operatesplus 1/8 inch.Tighten the screws holdingBETWEEN MouNnNG socuAND l�� _—� p g OFFSET BRACKET.INSTALL BOLT the REVS to the"offset"bracket. FROM BOTTOM AND TRIM AS ■ ■ PIPE - 10.Remove the REVS switch enclosure cover. NEEDED TO CORRECT. / 11� 11.Close and open the valve to verify operation. The actuator should ���� ���� easily retract upwhen the valve handle is in the open position. ▪ 12.Fully open the valve. .11.1111111. 13.Wire main switch and tamper switch(if applicable).Carefully route • l""F tamper switch wi res through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel.See Fig. 1. DWG;Joao-+ 14.Replace RBVS switch enclosure cover and securely tighten cover screw. - ',PRINTED IN USA MFG.tt 5401086-REVU PAGE 2OF2 5/08 [ r 000 Single Inlet Connection for Residential Systems, �« UL Listed Description Designed specifically residential sprinkler systems, the Single Specifications Inlet Connection features all brass construction with an inte- grally cast mounting/identification plate. The connection comes Material: equipped with a single 1 1/2" NST gasketed female threaded Brass swivel inlet and a 1 1/2" NST plug to protect the threaded swivel Type: from damage or the introduction of foreign materials when not in Single Outlet PL use. The out let is 1 1/2" NPT female thread for connect to the end of 1 1/2" threaded male pipe. The integrated identification Sizes: plate has three drilled mounting holes for attachment to 1.5" FNPT x 1.5" FNST a mounting surface such as an exterior wall of a building or other structure. Fasteners used should be suitable for the material to Other Specifications: Integral Identification which the connection is being attached. sign "Auto Sprinkler" with mounting holes. Installation Install according to applicable ing Paste with PTFE or PTFE codes using customary instal- thread Sealant Tape should lation methods for the installa- be used. Where required, a tion of threaded connections. check valve should be used to A suitable threaded sealant maintain system pressure. such as PipeFit Thread Seal- . Fire Protection Products, Inc ' 6241 Yarrow Dr.,Suite A,Carlsbad,CA 92011-1541 91996-2007 Fire Protection Products,Inc(FPPp F.p P.P,:: For questions: 1 800 344-1822•1 800 344-3775 fax•www.fppi.com • ..ZY'ffi@§Z P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 511 SIDE MOUNT CPVC - COPPER HANGER al 1 6 SIZE-3/4"thru 2"pipe. �t MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. Side View-For LISTING/APPROVAL- Drawings Below e*. 203-EX 4231,EX 2551 FUNCTION- Hanger on CPVC and Copper pipe. INSTALLATION-Per NFPA 13, 13R, 13D and CPVC manufacturers instructions on top or bottom of beam. Space by pipe type SPECIAL NOTE: When installing on CPVC sprinkler system pipe: ►ale Verify that all assembly components are cleaned of any surface oil. FASTENERS-UL Listed per NFPA 13. in WOOD: 3/4"-2"CPVC pipe-#905 screw- no pre-drill. 3/4" -2"Copper pipe-#905 screw- no pre-drill. l r in STEEL-min. 18 GA. �J 3/4"-2"CPVC pipe- 1/4"or#14 Tek Screw. 3/4" -2"Copper pipe- 1/4"or#14 Tek Screw. FEATURES *Offset edge eliminates abrasion. Hanger-Wood Stud Hanger-Metal Stud *Retainer dimples secure hanger to pipe during installation. *Required AFCON#905 screw has 5/16"hex head- included. ORDERING-Part#and pipe size. a Specific AFCON products are exclusively designed to be compatibk ONLY with other AFCON pnuhaN including parts and Fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any eveumstarren whatsoever for any director indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 1/08 •• P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org w• 514 OFFSET CPVC HANGER #905 300 1i - - SIZE-3/4"tiro 3"pipe. Y MATERIAL-Carbon Steel. minimm FINISH-Mil.Galvanized.. LISTING/APPROVAL- S., 203-EX 4231,EX 2551 111, PATENT-No.6,648,278. FUNCTION- 3/4"-2" Hanger/restrainer for horizontal CPVC,Copper or Steel pipe. Listed hanger/restrainer in all 3 mounting positions,i.e.vertical surface and both top and bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward movement of pipe that supplies a pendent sprinkler below a ceiling. moo mg" Size 2'A" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions. i.e.vertical surface and both top and bottom of horizontal surface. I ' Size 3" Hanger for horizontal CPVC pipe in two mounting positions,side and bottom. i.e.vertical surface and bottom of horizontal surface. Stabilizes vertical piping by providing horizontal restraint INSTALLATION- Per NFPA 13, 13R and 13D. l C ' .�— Space by pipe type. Install on wood,concrete or steel-See Drawings. I "- Snap over pipe then squeeze strap back allowing pipe to slide freely. listed Restraint When #905 threads are exposed in wood,install#906 backing nut. 3/4"thru 2" F= SPECIAL NOTE: When installing on CPVC sprinkler system pipe: --_ Verify that all assembly components are cleaned of any surface oil. FASTENERS-UL Listed per NFPA 13 III) WOOD- 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4" -2"Copper pipe- #905 screw- no pre-drill. 3/4" -2" Steel pipe- 1/4"xl 1/2"lag screw- no pre-drill. Thru 5/8"gypsum board- 1/4" x 2" lag screw. • STEEL-min. 18 GA.- 3/4"-3"CPVC pipe- 1/4"or#14 Tek Screw_ 3/4"-2"Copper pipe- 1/4"or#14 Tek Screw. 3/4"-2" Steel pipe- 1/4"or#14 Tek Screw. A • CONCRETE:Required minimum load each fastener= 5(wt)+2501bs. 2 FEATURES p * 1 1/2"Offset-loose fit allows pipe to slide. *3/4"and 1"pipe size made with common center-line. J Listed Restraint *Patented design for superior strength. 3/4"thru 2" *Offset edge eliminates abrasion. *AFCON#905 screw has 5/16"hex head- included. ORDERING-Part#and pipe size. AFCON#906 backing nut sold separately. Specific AFCON products arc exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed away brace,restrainer or hanger assembly. Be advised the following warranty reaviction will apply. DISCLAIMER-AFCON will NOT warrant against the failure ofita products when used in combination with other products,parts or systems not manufactured or sold by AFCON AFCONshall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages ofany kind,including but not bruited to buss of business or profit,when non-AFCON products have been,or are uses. 6/08 • • P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 515 DOUBLE OFFSET C.P.V.C. HANGER j • „.../7/ A 0 • SIZE-3/4" and 1"pipc. MATERIAL-Carbon Steel. FINISH-Mil. Galvanized. LISTING/APPROVAL- c0as 203-EX 4231 PATENT-No.6,702,236 FUNCTION-Hanger/restrainer for horizontal CPVC pipe. INSTALLATION- Per N.EFA 13, I3R and 13D. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS-UL Listed per NFPA 13. WOOD: #904 screw- no pre-drill. STEEL: 1/4" or#14 Tek Screw in min.20 GA. FEATURES *Double 1 1/2"offset-loose fit allows pipe to slide. * Center line matches AFCON#514. * 3/4" and 1" pipe size have common center-line. * Offset edge eliminates abrasion. • * Required AFCON#904 screw has 3/8"hex head- included. ORDERING-Part#and pipe size. • • Spec AFT ON trododualc.ale excluslieiy designed m be cnmiwlble ONLY with other AFCON products including part,and nasteners,resulting in a listed sway brace,restrainer of hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,pans or systems not illalladtlilred or sold by AFCON. A FCON,shall NOT be liable under any c¢cumsnmces whaluever for any direct or indirect.incidental or consequential damages of any kind,including but riot limited to Ices of business or profit,when non-AFCON products have been,or are used. • • A sr 8/07 .. f'