Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report
ff S2ozb- eao3 . 1265 SW' Ddrbno-4 44i SoL ADT Commercial 9350 S.W. Nimbus Ave Beaverton, OR 97008 503-235-4000 FEB 2 Reference: Fire Alarm System — FACP upgrade National Retail 7255 S.W. Dartmouth Street Tigard, OR 97223 • Device Data Sheets February 2020 ID DF-60953:C ES-50X ® Fire•uTe Alarms Intelligent Addressable FACP • with Communicator by Honeywell Addressable Fire Alarm Control Panels General The ES-50X is the latest intelligent addressable fire alarm control panel (FACP)from Fire•Lite Alarms and is a direct replacement for the MS-9050UD/LS. The ES-50X comes with a pre-installed communi-cator and supports up to 50 addressable devices in any combination of detectors or modules. With an extensive list of powerful features, the ES-50X programs just like Fire•Lite's other ,adiaf '" addressable panels, yet fits into applications previously served only by - conventional panels. ® s The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator.The POTS transmits system status(alarms,troubles, - AC loss, etc.)to a Central Station via the public switched telephone °^ _• ^ network.The IP communicator's intemet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedi- cated business telephone lines.Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-FL. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel's USB port(and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file,walk-test data, current status and system volt- • Maintenance alert warns when smoke detector dust accumula- ages by means of a USB flash drive. tion is excessive The power supply and all electronics are contained on a circuit • One-person audible or silent walktest with walktest log&printout • board supported on a new quick install chassis and housed in a • System alarm verification selection per detector point metal cabinet. Available accessories include local and remote • PAS (Positive Alarm Sequence)and Pre-signal per point(NFPA upload/download software, remote annunciators, and reverse polar- 72 compliant) ity/city box transmitter(4XTMF). • Up to 16 ANN-BUS annunciators-8 per each ANN-Bus Features • Remote Acknowledge, Alarm Silence, Reset and Drill via • Listed to UL Standard 864, 10th edition addressable modules or remote annunciator • Pre-installed IPOTS-COM Ethernet IP and POTS(Plain Old Tele- • Upload/Download of program and data via USB with optional FS- phone Service)Central Station Communicator Tools Programming Utility • Optional CELL-MOD or CELL-CAB-FL GSM Central Station SLC COMMUNICATION LOOP Communicator overAlarmNet® • Supports LiteSpeed TM and CLIP protocols • Compatible with SWIFT®wireless devices • SLC operates up to 10,000 ft. (3,000 m)in LiteSpeed mode with • Auto-programming (learn mode) reduces installation time. twisted,unshielded wire Reports two devices set to the same address • Single addressable SLC loop which meets NFPA Class B and • Two independently programmable, built-in Style Z (Class A) or Class A requirements Style Y(Class B)NAC circuits • 50 addressable device capacity(any combination of addressable • Selectable strobe synchronization for System Sensor,Wheelock, detectors and modules) and Gentex devices • Compatible with Fire•Lite's addressable devices (refer to the • Notification Appliance Circuit End of Line resistor matching SLC Wiring Manual) • Four programmable function keys for ease of maintenance NOTIFICATION APPLIANCE CIRCUITS(NAGS) • Two programmable relays and one fixed trouble relay • Two independently programmable output circuits. Circuits can be • Built-in Programmer configured for the following outputs: • Integral 80-character LCD display with backlighting —Style Y(Class B) • Real-time clock/calendar with automatic daylight savings control —Style Z(Class A) • History file with 1,000 event capacity • Silence Inhibit and Autosilence timer options • Addressable sounder base • Continuous, March Time, Temporal, or California code for main • Multi-criteria detector (smoke, heat, CO) with programmable circuit board NACs with two-stage capability response • Selectable strobe synchronization per NAC • Control module delay timer • 2.5 A special application,250mA regulated,total power for NACs • Automatic detector sensitivity testing(NFPA 72 compliant) NOTE:Maximum or total 24VDC system power shared between all NAC • • Automatic device type-code verification circuits and the ANN-BUS is 2.7 A • Point trouble identification PROGRAMMING AND SOFTWARE • Waterfiow selection per module point • Alarm verification selection per detector point • Autoprogramming(learn mode)reduces installation time DF-60953:C•7/16/2018—Page 1 of 4 • Custom English labels (per point) may be manually entered or OPTIONAL MODULES selected from an internal library file 4XTMF Reverse Polarity Transmitter Module: Provides a super- • Two programmable Form-C relay outputs vised output for local energy municipal box transmitter, alarm and • • 50 software zones trouble.Includes a disable switch and disable trouble LED. • Continuous fire protection during online programming • Program Check automatically catches common errors not linked COMPATIBLE ANNUNCIATORS to any zone or input point ANN-80: Remote, red LCD annunciator mimics the information dis- • OFFLINE PROGRAMMING: Create the entire program in your played on the FACP LCD display. Recommended wire type is un- office using FS-Tools,a Windows®-based software package,and shielded. upload/download system programming locally. Offline program- ANN-100: Remote LCD annunciator mimics the information dis- ming requires an ethernet connection. FS-Tools is available on played on the FACP LCD display. Recommended wire type is un- www.firelite.com. shielded.For use in FM applications only. User interface ANN-I/O: LED Driver Module provides connections to a user sup- LED INDICATORS plied graphic annunciator.(See DF-52430.) ANN-LED:Annunciator Module provides three LEDs for each zone: • Fire Alarm(red) Alarm,Trouble,and Supervisory.Ships with red enclosure.(See DF- • CO Alarm(red) 60241.) • AC Power(green) ANN-RLED:Provides alarm(red)indicators for up to 30 input zones • Supervisory(yellow) or addressable points. (See DF-60241.) • Trouble(yellow) ANN-RLY:Relay Module provides 10 programmable Form-C relays. • Ground fault(yellow) Can be mounted inside the cabinet. (See DF-52431.) • Battery fault(yellow) ANNS/PG: Serial/Parallel Printer Gateway module provides a con- nection for a serial or parallel printer.(See DF-52429.) • Disabled(yellow) ADDRESSABLE DEVICES • Maintenance(yellow) • Communication(yellow) All feature a polling LED and rotary switches for addressing. • Alarm Silenced(yellow) SD365:Addressable low-profile photoelectric smoke detector. Lite- • F1-F4 Programmable Function Keys(yellow) Speed only. SD365-IV: Addressable low-profile photoelectric smoke detector. KEYPAD Ivory.LiteSpeed and CLIP mode. • 16 key alpha-numeric pad SD365T:Addressable low-profile photoelectric smoke detector with • Acknowledge thermal sensor.LiteSpeed only. • • Alarm Silence SD365T-IV: Addressable low-profile photoelectric smoke detector • Drill(Manual Evacuate) with thermal sensor.Ivory.LiteSpeed and CLIP mode. • Four(4)programmable function keys SD365R: Remote test capable addressable photoelectric smoke detector for use with DNR(W)duct detector housing.LiteSpeed only. • Reset(lamp test) SD365R-IV: Remote test capable addressable photoelectric smoke Product Line Information detector for use with DNR(W) duct detector housing. Ivory. Lite- Speed and CLIP mode. ES-50X:Addressable Fire Alarm Control Panel with one SLC loop. H365:Low-profile 135°F fixed thermal sensor.LiteSpeed only. Includes main circuit board with display, pre-installed IPOTS-COM communicator, chassis with transformer, backbox with door, plastic H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed bag containing screws,cables,key,etc. (For ES-50XC,refer to DF- and CLIP mode. 60954.) H365R: Low-profile, intelligent, rate-of-rise thermal sensor. Lite- FS-Tools: Programming software for Windows®-based PC corn- Speed only. outer.Available for download at www.firelite.com. H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. CELL-CAB-FL/CELL-MOD:Optional GSM communicators. LiteSpeed and CLIP mode. IPOTS-COM: Dual technology (POTS and IP) communicator. H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor. (replacement board) LiteSpeed only. DP-ES-R:Optional dress panel for the ES-50X. H365HT-IV:Low-profile intelligent 190F/88°C fixed thermal sensor. TR-CE:Optional trim ring for semi-flush mounting. Ivory. LiteSpeed and CLIP mode. BB-2F:Optional cabinet for one or two modules. Legacy Devices BB-6F: Optional cabinet for up to six modules mounted on CHS-6 SD355:Addressable low-profile photoelectric smoke detector. chassis. SD355T:Addressable low-profile photoelectric smoke detector with BB-26:Battery backbox,holds up to two 25 AH batteries&CHG-75. thermal sensor. BB-55F: Battery box,houses two 55 AH batteries SD355R: Remote test capable addressable photoelectric smoke CHS-6:Chassis,mounts up to six multi-modules in a BB-6F cabinet. detector for use with DNR(W)duct detector housing. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to SD355CO•Addressable, low-profile device that provides fire, heat, 75 AH. CHG-120F: Remote battery charging system for lead-acid batteries and carbon monoxide(CO)detection. with a rating of 55 to 120 AH.Requires additional BB-55F for mount- H355:Fast-response,low-profile heat detector. ing. H355R: Fast-response, low-profile heat detector with rate-of-rise BAT Series:Batteries,see data sheet DF-52397. option. PRN Series: UL listed compatible event printer. Uses tractor-fed H355HT: Fast-response, low-profile heat detector that activates at paper. 190°F/88°C. Page 2 of 4—DF-60953:C•7/16/2018 AD355: Low-profile, intelligent, "Adapt" multi-sensor detector W-BG12LX:LiteSpeed Intelligent wireless pull station. (B350LP base included). WAV-RL,WAV-WL,WAV-CRL,WAV-CWL:LiteSpeed Intelligent AV B200S: Programmable,addressable sounder base bases. • B200SR:Addressable sounder base. W-USB: Wireless USB radio/antenna dongle that plugs into the BEAM355:Intelligent beam smoke detector. USB port of a PC running SWIFT Tools. BEAM355S: Intelligent beam smoke detector with integral sensitiv- SWIFT Tools: Programming and diagnostic utility for the Wireless ity test. Gateway and devices.Available for download from firelite.com. InnovairFlex low-flow non-relay duct detector housing; NOTE: For more information on Compatible Addressable Devices for D355PL: I includes SD355R. use with the ES-50X, see the following data sheets (document num- bers): SD365 Series (DF-61010), H365 Series (DF-61011), AD355 DNR: InnovairFlex low-flow non-relay duct-detector housing.(Order (DF-52386), BG-12LX(DF-52013), CMF-300-6(DF-52365), CRF-300-6 SD355R/SD365R separately.) (DF-52374), CMF/CRF Series (DF-52130), CP355 (DF-52383), H355 DNRW: InnovairFlex low-flow non-relay duct-detector housing, with Series (DF-52385), /300 (DF-52389), ISO-6 (OF 60485), MMF-300 NEMA-4 rating.Watertight. (Order SD355R/SD365R separately.) Sertes/MDF300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), S0355/SD355T (DF-52384), and SLC Wiring Manual Addressable Modules (51309). MMF-300: Addressable Monitor Module for one zone of normally- NOTE:Legacy 300 Series detection devices such as the CP300/CP350, open dry-contact initiating devices. Mounts in standard 4.0" (10.16 SD300(T)/SD350(T)and older modules such as the M300, M301, M302, cm.)box. Includes plastic cover plate and end-of-line resistor. Mod- C304, and BG-10LX are not compatible with LiteSpeed polling. If the ule may be configured for either a Style B(Class B)or Style D(Class SLC contains one of these devices, polling must be set for standard A)IDC. CLIP protocol. Please consult factory for further information on previous MDF-300: Dual Monitor Module. Same as MMF-300 except it pro- 300 Series devices. vides two Style B(Class B)only IDCs. ADDRESSABLE DEVICE ACCESSORIES MMF-301: Miniature version of MMF-300. Excludes LED and Style Endof-Line Resistor Assembly (R-47K and R-3.9K): The D option.Connects with wire pigtails.May mount in device backbox. 47k ohm assembly supervises the MMF-300, MDF-300, MMF-301, MMF-302:Similar to MMF-300.Addressable Monitor Module for one and CMF-300 module circuits. The 3.9k ohm assembly supervises zone of conventional two-wire detectors. Requires resettable 24 the MMF-302 module circuit.These resistors are included with each VDC power. Refer to the Device Compatibility Document for listed module. compatible devices and quantity limitation. Power Supervision Relay: Supervises the power to 4-wire smoke CMF-300: Addressable Control Module for one Style Y/Z (Class B/ detectors and notification appliances. A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires Wiring Requirements external 24 VDC to power notification appliances. CRF-300:Addressable relay module containing two isolated sets of While shielded wire is not required, it is recommended that all SLC contacts,which operate as a DPDT switch. Mounts directly wiring be twisted pair to minimize the effects of electrical interfer- Form-C4111 to a 4.0"(10.16 cm.)box,surface mount using the SMB500. ence.Refer to the panel manual for wiring details. BG-12LX: Addressable manual pull station with interface module mounted inside. 1300:This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). ISO-6: Six-fault isolator module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SMB500: Used to mount all modules except MMF-301 and M301. MMF300-10:Ten-input monitor module. Mount one or two modules in a BB-2F cabinet(optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. MMF-302-6:Six-zone interface module. Mount one or two modules in a BB-2F cabinet(optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6: Six-circuit supervised control module.Mount one or two modules in a BB-2F cabinet(optional).Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module(Form-C relays).Mount one or two modules in a BB-2F cabinet(optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SWIFT Wireless Devices W-GATE:LiteSpeed Wireless Gateway W-SD355:LiteSpeed intelligent,wireless photo detector. W-H355R: LiteSpeed intelligent wireless rate of rise (135°) heat detector. W-S13355T:intelligent wireless photo/heat detector. W-H355: LiteSpeed intelligent wireless fixed-temperature (135°) heat detector. 41) W-MMF: LiteSpeed Intelligent wireless monitor module. W-CRF:LiteSpeed Intelligent wireless relay module. DF-60953:C•7/16/2018—Page 3 of 4 SYSTEM SPECIFICATIONS System Capacity Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0—49°C/32 • Intelligent Signaling Line Circuits 1 —120°F and at a relative humidity 93%±2%RH(noncondensing)at • Addressable device capacity 50 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's • Programmable software zones 50 standby batteries and the electronic components may be adversely • Annunciators 16 affected by extreme temperature ranges and humidity.Therefore,it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15—27°C/60- Electrical Specifications 80°F. AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing- no switch required. Wire size: minimum 14 AWG NFPA Standards (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. The ES-50X complies with the following NFPA 72 Fire Alarm Sys- Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger terns requirements: Capacity: 7-18 AH (ES-50X cabinet holds maximum of two 18 AH —LOCAL(Automatic, Manual, Waterflow and Sprinkler Supervi- batteries.) sory). Communication Loop: Supervised and power-limited. —AUXILIARY (Automatic, Manual and Waterflow) (requires Notification Appliance Circuits: Terminal Block provides connec- 4XTMF). tions for two NACs, Style Y(Class B)or Style Z (Class A). Special —REMOTE STATION (Automatic, Manual and Waterflow) Application power. Power-limited, supervised circuitry. Maximum (Where a DACT is not accepted,the alarm,trouble and supervi- signaling current per circuit: 2.5 amps special application, 250mA sory relays may be connected to UL 864 listed transmitters.For regulated. End-of-Line Resistor: 4.7k ohm, % watt (P/N 71252 UL reverse polarity signaling of alarm and trouble, 4XTMF is listed)for Style Y(Class B)NAC;system capable of 1.9 kS2-22 kl2 required.) ELR range.Refer to the Fire-Lite Device Compatibility Document for —PROPRIETARY(Automatic,Manual and Waterflow). listed compatible devices. —CENTRAL STATION (Automatic, Manual and Waterflow, and Two Programmable Relays and One Fixed Trouble Relay: Con- Sprinkler Supervised). tact rating:2.0 A @ 30 VDC(resistive),0.5 A @ 30 VAC(resistive). —OT, PSDN (Other Technologies, Packet-switched Data Net- Form-C relays,non-power-limited,non-supervised. work) Cabinet Specifications —IBC 2012,IBC 2009,IBC 2006,IBC 2003, IBC 2000(Seismic). • —CBC 2007(Seismic) Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.)deep. Backbox: 19.00"(48.26 cm.)high x 16.65"(42.29 Agency Listings and Approvals cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.)high x 19.65"(49.91 cm.)wide. The listings and approvals below apply to the basic ES-50X control panel. In some cases, certain modules may not be listed by certain Shipping Specifications approval agencies, or listing may be in process. Consult factory for latest listing status. Weight: 26.9 lbs. (12.20 kg.)Dimensions: 20.00"(50.80 cm.)high • UL: S624 x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. • FM approved • CSFM: 7165-0075:0500 • FDNY: COA#6261 NOTE:See DF-60954 for ULC-listed model. AlannNet®, Fire-Cite®Alarms,SWIFT®,and System Sensor®are registered trademarks of Honeywell International Inc.Microsoft®and Windows®are registered trademarks of the Microsoft Corporation. ®2018 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. • ISO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. C E R T I F r E U All specifications are subject to change without notice. MINDIMIEWMILIMME QUALITY SYSTEMS For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. Country of Origin:USA www.firelite.com Page 4 of 4—DF.60953:C•7/1612018 DF-61012:C ANN-I 00 80 Character LCD @well-re Alarms iRemote Fire Annunciator by Honeywell Annunciators General The ANN-100 annunciator is a backlit,80-character LCD fire annun- ciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory,and Alarm Silenced conditions. ANN SON The ANN-100 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. Con- nected devices are powered,via two additional wires, by either the host FACP or a remote UL-listed,filtered power supply. + The ANN-100 displays English-language text of system point infor- siLENCE AL.? A mation including device type,zone,independent point alarm,trouble or supervisory status, as well as any custom alpha labels pro- wEsZT `' grammed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents i F'FEALAFM ANNUNCIATOR unauthorized operation of the control switches.) °^a AtanInS °Nw•ry"el Up to eight ANN-100s may be connected to each ANN-BUS of a FACP. No programming is required,which saves time during system commissioning. Features • Listed to UL Standard 864,9th Edition • Backlit 80-character LCD display(20 characters x 4 lines) Specifications • Mimics all display information from the host panel PHYSICAL • Control switches for Signal Silence,System Acknowledge,Reset, • and Drill • Flush Mount: (Outside wall) 12.25"W x 11.5"H x 0.875"D(31.1W • Control switches can be independently enabled or disabled at the x 29.2H x 2.2D cm), (Inside wall) 9.375 W x 8.375"H x 2"D FACP (23.8W x 21.3H x 5.1 D cm) • • Keyswitch enables/disables control switches and mechanically Surface Mount: (Including Trim Ring) 12.25"W x 11.5"Hx 3"D locks annunciator enclosure (31.1 W x 29.2H x 2.2D cm) • Keyswitch can be enabled or disabled at the FACP ELECTRICAL: • Enclosure supervised for tamper • Operating Voltage:24VDC • System status LEDs for AC Power,Alarm,Trouble, Supervisory, • Standby Current:20mA and Alarm Silence • Alarm Current:25mA • Local sounder can be enabled or disabled at the FACP • Wiring Distance:Up to 6,000 ft max.from FACP • ANN-100 connects to the ANN-BUS terminal on the FACP and " All connections are power-limited and supervised. requires minimal panel programming • For use indoors in a dry location. • Displays device type identifiers, individual point alarm, trouble, supervisory,zone,and custom alpha labels ENVIRONMENTAL • Time-and date display field • Ambient temperature:32°F to 120°F(0°C to 49°C). • Surface-mount or flush-mount installation options • Relative humidity:93%±2%RH(non-condensing)at 32°C t 2°C • Optional trim ring for a more finished look (90°F±3°F) • Can be remotely located up to 6,000 feet (1,800 m) from the Agency Listings and Approvals panel • Backlight turns off during AC loss to conserve battery power but The listings and approvals below apply to the ANN-100. In some will turn back on if an alarm condition occurs cases,certain modules may not be listed by certain approval agen- • May be powered by 24 VDC from the host FACP or by remote dies, or listing may be in process. Consult the factory for the latest power supply(requires 24 VDC) listing status. • Up to eight ANN-100s can be connected on the ANN-BUS ULIULC:S2424 FM approved Controls and Indicators CSFM: 7165-0075:0500 • AC Power FDNY:COA#6261 • Alarm • • Trouble Ordering Information • Supervisory ANN-100:80 character remote fire annunciator;red • Alarm Silenced TR-ANN-R:Optional trim ring for surface-mount applications; red DF-61012:C-1/22/2019—Page 1 of 2 • • Fire-Lite®Alarms is a registered trademark of Honeywell International Inc. 02019 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO Wetry to keep our product information up-to-date and accurate.411 We cannot cover all specificapplications nr anticipate all requirements.® All specifications are subject to change without notice. EN6INEEAINI t;MANIFA TERlNC QUALITY SYSTEMS For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. Country of Origin:USA www.firelite.com Page 2 of 2—DF-61012:C•1122/2019 DF-52013:D•E-100 BG-12LX Flre•LITeALarms • Addressable Manual Pull Station by Honeywell General The Fire•Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that / includes an addressable interface (mounted inside) for FIRE Fire•Lite's addressable f le fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station.This leads fire personnel quickly to the location of the alarm. Features 1 PUSH IN I • Maintenance personnel can open station for inspection and PULL DOWN address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station,flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to Fireure®alarms SLC loop(accepts up to 12 AWG/3.25 mm2 wire). by Honeywell • Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- 3 $ gang,double-gang,or 4"(10.16 cm)square electrical box. • Smooth dual-action design. F • Meets ADAAG controls and operating mechanisms guide- LL • lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. usually needed for semi-flush mounting with 4° (10.16 cm) or • Attractive shape and textured finish. double gang boxes(not with single gang boxes). • Key reset. Operation • Includes Braille text on station handle. • Optional trim ring(BG12TR). Pushing in,then pulling down on the handle causes it to latch in the down/activated position. Once latched,the word"ACTI- • Meets UL 38, Standard for Manually Actuated Signaling VATED" (in bright yellow) appears at the top of the handle, Boxes. while a portion of the handle protrudes from the bottom of the station.To reset the station,simply unlock the station with the Construction key and pull the door open.This action resets the handle;clos- Shell, door, and handle are molded of durable polycarbonate ing the door automatically resets the switch. material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch.Two rotary decimal switches allow address settings (1 —159 with Breakaway Tab removed for MS-9600 Series,1 — • Shipping Weight:9.6 oz.(272.15 g) 99 and MS-9200ODLS, 1 —50 for MS-9050UD). • Normal operating voltage:24 VDC. • Maximum SLC loop voltage:28.0 VDC. Architectural/Engineering • Maximum SLC standby current:375 pA. Specifications • Maximum SLC alarm current:5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- • Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key.An operated sta- • For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of Installation red-colored polycarbonate material with clearly visible operat- The BG-12LX will mount semi-flush into a single-gang,double- appear instructions provided on the cover. The word FIRE shall gang,or standard 4"(10.16 cm)square electrical outlet box,or appear on the front of the stations in white letters, 1.00 inches • will surface mount to the model SB-10 or SB-I/O surface back- (2.54 cm) or larger. Stations shall be suitable for surface box. If the BG-12LX is being semi-flush mounted, then the mounting on matching backbox SB-10 or SB-I/O;or semi-flush optional trim ring (BG12TR) may be used. The BG12TR is mounting on a standard single-gang, double-gang, or 4°(10.16 cm) square electrical box, and shall be installed OF-52013:D•4/13/2012—Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations • shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10:Surface backbox;metal. SB-I/O:Surface backbox;plastic. BG12TR:Optional trim ring. 17003:Keys,set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess.Consult factory for latest listing status. • UL/ULC Listed: S711 (listed for Canadian and non-Cana- dian applications). • MEA:67-02-E. • CSFM:7150-0075:0184. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. • FireLite®Alarms®is a registered trademark of Honeywell International Inc. ®2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes.ISO 9001 We try to keep our product information up-to-date and accurate. • C E RT.F E IN HUMMING&UNWIRING We cannot cover all specific applications or anticipate all requirements. 1 •110,0•1•10111MOMIIIIII All specifications are subject to change without notice. r_� QUALITY SYSTEMS Made in the U.S.A. For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. www.firefde.com Page 2 of 2-DF-52013:D•4/13/2012 OF-52347:A•E-900 M M F-300-1 0(A) Flre•LiTe°Alarms • Ten-Input Monitor Module by Honeywell Addressable Devices General .0100 ..... 16..0.0.. The MMF-300.10 ten-input monitor module is an interface between a control panel and normally open contact devices • ::: �s� �A; a�u, F in intelligent alarm systems such as pull stations, security . e. ,• contacts,or flow switches. The first address on the MMF-300-10 is set from 01 to 150 r ® • . � and the remaining modules are automatically assigned to the v ' next nine higher addresses. Provisions are included for dis- ® •® ��.d abling a maximum of two unused addresses. , •: The supervised state (normal, open, or short) of the moni- „' tored device is sent back to the panel.A common SLC input .`.•:•- =_ • is used for all modules,and the initiating device loops share a €t=_ common supervisory supply and ground — otherwise each monitor operates independently from the others. ® •I �, ®i Each MMF-300-10 module has panel-controlled green LED '':= ' •in: , indicators. The panel can cause the LEDs to blink, latch on, .:; •.. a or latch off. •�� x .Etf,`� NOTE:Unless otherwise specified, the term MMF-300-10 is used in this data sheet to refer to both the MMF-300-10 and the MMF- 300-10A(ULC-listed version). Features Mounting options: • Listed to UL Standard 864,9th edition. —CHS-6 chassis: Up to 6 modules. • • Ten addressable Class B or five addressable Class A initi- ating —BB-6F cabinet:Up to 6 modules. device circuits. —BB-2F cabinet:One or two modules. • Removable 12 AWG (3.25 mm2) to 18 AWG (0.9 mm2) Wire gauge: 12 AWG(3.25 mm2)to 18 AWG(0.9 mm2). plug-in terminal blocks. Power-limited circuits must employ type FPL, FPLR, or • Status indicators for each point. FPLP cable as required by Article 760 of the NEC. • Unused addresses may be disabled. MMF-300-10 is shipped in Class S position; remove shunt • Rotary address switches. for Class A operation. • Class A or Class B operation. Maximum SLC wiring resistance: 40 or 50 ohms, panel • Flexible mounting options. dependent. • Mounting hardware included. Maximum IDC wiring resistance: 1500 ohms. Specifications Maximum IDC voltage: 10.2 VDC. Standby current: 3.5 mA (SLC current draw with all Maximum IDC current:240 NA. addresses used; if some addresses are disabled, the standby current decreases). Alarm current:55 mA(assumes all ten LEDs solid ON). Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications;—10°C to+55°C for EN54 applications. Humidity: 10% to 85% noncondensing for UL applications; 10%to 93%noncondensing for EN54 applications. Dimensions: 6.8" (172.72 mm) high x 5.8' (147.32 mm) wide x 1.25"(31.75 mm)deep. Shipping weight: 0.76 lb. (0.345 kg)including packaging. • DF-52347:A•05/15/2009—Page 1 of 2 Agency Listings and Approvals The listings and approvals below apply to the MMF-300- • 10(A)Ten-Input Monitor Module. In some cases, certain mod- ules or applications may not be listed by certain approval agencies,or listing may be in process. Consult factory for lat- est listing status. • UL Listed:S2424 • ULC Listed:S2424 • CSFM approved:7300-0075:205 • FM approved • MEA approved:55-02-E Product Line Information MMF-300-10:Ten-input monitor module. MMF-300-10A:Same as above with ULC Listing. BB-2F: Optional cabinet for one or two modules. Dimen- sions, DOOR:9.234" (23.454 cm)wide(9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm)deep; BACKBOX:9.0" (22.860 cm)wide(9.25" [23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHASSIS(installed):7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high interior overall x 2.156"(5.4762 cm)deep overall. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis (below). Dimensions, DOOR:24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep,hinged at bottom; BACKBOX:24.0"(60.96 cm)wide x 12.550"(31.877 cm)high x 5.218" (13.2537 cm)deep. CHS-6:Chassis,mounts up to six modules in BB-6F. 411 FireLite®Alarms®and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ®2009 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. I S`7 We try to keep our product information up-to-date and accurate. • We cannot cover all specific applications or anticipate all requirements. OIEFIVIrlIFIEEP ENUNEEUINC 8 MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. Made in the U.S.A. www.firelite.com Page 2 of 2—DF-52347:A•05/15/2009 DF-61010:B SD365 Series kTE)) Fire•trre Alarms Addressable Photoelectric Smoke Detectors • by Honeywell Addressable Devices The Fire•Lite® Alarms SD365(A), SD365R(A), and SD365HT(A) intelli-gent plug-in smoke detectors are designed for both performance and aesthetics, and are direct replacements for the g, SD355 Series. A new modem, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. Exclusively for use with Fire•Lite's addressable fire alarm control , panels, the SD365(A) Series point ID capability allows each detec- tor's address to be set with rotary,decimal address switches,provid- ing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious res- ,' cue time while also reducing property damage.Two LEDs on each sensor light to provide a local,visible sensor indication. The SD365(A) Series also offers 135°F (57°C) fixed temperature thermal sensing on the SD365T(A)and a remote test capable detec- tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings. Features • Plugs into separate base for ease of installation and maintenance SLC LOOP: • Separate base allows interchange of photoelectric,ionization and • Two-wire SLC loop connection thermal sensors • Unit uses base for wiring OPTIONS: • Compatible with LiteSpeedn'and CLIP protocol systems • Optional relay,isolator,and sounder bases • Stable communication technique with noise immunity Installation • ADDRESSING: SD365 Series plug-in intelligent smoke detectors use a detachable • Addressable by device base to simplify installation, service and maintenance. Installation • Rotary,decimal addressing instructions are shipped with each detector. (Refer to the Fire•Lite panel manuals for device capacity.) Mount detector base(all base types)on an electrical backbox which ARCHITECTURE: is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes,see DF-60059. • Sleek,low-profile,stylish design • Unique design to respond quickly and dependably NOTE:Because of the inherent supervision provided by the SLC loop, to a broadiqe single-source range r end-of-line resistors are not required. Wiring "T-taps"or branches are permitted for Style 4(Class"8')wiring only. • Integral communications and built-in device-type identification When using relay or sounder bases, consult the 1300(A) installation • Built-in tamper resistant feature sheet 156-3626 for device limitations between isolator modules and iso- lator bases. • Remote test feature from the panel • Walk test with address display (an address on 121 will blink the Construction detector LED: 12-[pause]-1(LiteSpeed systems only) These detectors are constructed of fire-resistant plastic. The SD365 • Built-in functional test switch activated by external magnet Series plug-in intelligent smoke detectors are designed to commer- • Removable cover and insect-resistant screen for simple field cial standards and offer an attractive appearance. cleaning • Expanded color options Operation Each SD365 Series detector uses one of the panel's addresses OPERATION: (total limit is panel dependent)on the Fire•Lite Signaling Line Circuit • Designed to meet UL 268 7th Edition (SLC). It responds to regular polls from the control panel and reports • Factory preset at 1.5% nominal sensitivity for panel alarm thresh- its type and the status. If it receives a test command from the panel old level (or a local magnet test), it stimulates its electronics and reports an • LED"blinks"when the unit is polled(communicating with the fire alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The SD365 Series offers features and panel)and latches in alarm. performance that represent the latest in smoke detector technology. • Low standby current MECHANICALS: Detector Sensitivity Test fibEach detector can have its sensitivity tested(required per NFPA 72, • Sealed against back pressure Chapter 14 on Inspection, Testing and Maintenance)when installed/ • SEMS screws for wiring of the separate base connected to an Fire•Lite addressable fire alarm control panel. The • Designed for direct-surface or electrical-box mounting results of the sensitivity test can be printed for record keeping, DF-61010:B•71/2019—Page 1 of 3 Product Line Information B200SA-WH:Same as B200S-WH,ULC listing NOTE:"-IV"suffix indicates CLIP and LiteSpeed device. B200SA-IV:Same as B200S-IV,ULC listing • NOTE:A"suffix indicates Canadian version. B200SCOA-WH: White, Intelligent, programmable sounder base in Enired in SD365:White,low-profile intelligent photoelectric sensor, LiteSpeed Segles detector appl(reqications Canada for ULC applications with CO only SD365A:Same as SD365 but with ULC listing B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO SD365-IV:Ivory,low-profile intelligent photoelectric sensor Series detector applications,ULC listing SD365A-IV:Same as SD365-IV but with ULC listing B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- SD365T:White,same as SD365 but includes a built-in 135°F(57°C) 10% with a square wave or its equivalent; designed to meet the fixed-temperature thermal device,LiteSpeed only NFPA 72 sleeping space requirement.(CSFM:7300-1653:0238) SD365TA:Same as SD365T but with ULC listing B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable SD365T-IV: Ivory, same as SD365T but includes a built-in 135°F sounder base. Produces a fundamental frequency of 520 Hz +/- (57°C)fixed-temperature thermal device 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement.(CSFM:7300-1653:0238) SD365TA-IV:Same as SD365T-IV but with ULC listing B200SR-WH: White, Intelligent sounder base capable of producing SD365R: White, low-profile intelligent photoelectric sensor, remote sound output with ANSI Temporal 3 or continuous tone. Intended for test capable,for use with DNR/DNRW,LiteSpeed only retrofit applications.(CSFM:7300-1653:0213) SD365RA: Same as SD365R but with ULC listing, for use with B200SR-IV: Ivory, Intelligent sounder base capable of producing DNRA sound output with ANSI Temporal 3 or continuous tone. Intended for SD365R-IV:Ivory,low-profile intelligent photoelectric sensor,remote retrofit applications.(CSFM:7300-1653:0213) test capable,for use with DNR/DNRW B200SRA-WH: Same as B200SR-WH with,ULC listing SD365RA-IV:Same as SD365R-IV but with ULC listing,for use with B200SRA-IV:Same as B200SR-IV in Ivory color,ULC listing DNRA B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- INTELLIGENT BASES 10% with a square wave or its equivalent; designed to meet the NOTE:For details on intelligent bases,see DF-60059. NFPA 72 sleeping space requirement. Intended for retrofit applica- B300-6:White,6"base,standard flanged low-profile mounting base tions.(CSFM:7300-1653:0238) (CSFM: 7300-1653:0109) B200SR-LF4V: Ivory, Low Frequency Intelligent, programmable B300-6-IV: Ivory,6" base, standard flanged low-profile mounting sounder base. Produces a fundamental frequency of 520 Hz +l- • base(CSFM: 7300-1653:0109) 10% with a square wave or its equivalent; designed to meet the Same as 6300 6, ULC listed NFPA 72 sleeping space requirement. Intended for retrofit applica- B300A-6: tions.(CSFM:7300-1653:0238) B300A-6-IV: Ivory, 6" standard flanged low-profile mounting base,ULC listed MOUNTING KITS AND ACCESSORIES B300-6-BP:Bulk pack of B300-6,package contains 10 TR300:White,replacement flange for 6210LP(A)base B501-WHITE: White, 4" standard European flangeless mounting TR300-IV: Ivory,replacement flange for B210LP(A)base base. UUULC listed(CSFM:7300-1653:0109) RA100Z(A): Remote LED annunciator.3-32 VDC. Mounts to a U.S. B501-BL: Black, 4" standard European flangeless mounting base. single gang electrical box.For use with B501(A)and B300-6(A). UUULC listed(CSFM:7300-1653:0109) M02-04-00:Test magnet B501-IV: Ivory color, 4" standard European flangeless mounting M02-09-00:Test magnet with telescoping handle base. UUULC listed(CSFM:7300-1653:0109) CK300:Color Kit(includes cover and trim ring),white, 10-pack B501-WHITE-BP:Bulk pack of B501-WHITE contains 10 CK300-IV:Color Kit(includes cover and trim ring),ivory, 10-pack B224RB-WH:White,relay base(CSFM:7300-1653:0216) CK300-BL:Color Kit(includes cover and trim ring), black, 10-pack B224RB-IV: Ivory,relay base(CSFM:7300-1653:0216) B224RBA-WH:White,relay base,ULC listing B224RBA-IV: Ivory,relay base,ULC listing B224BI-WH:White,isolator detector base(CSFM:7300-1653:0216) B224BI-IV:Ivory isolator detector base(CSFM:7300-1653:0216) B224BIA-WH:White,isolator detector base,ULC listing B224BIA-IV: Ivory isolator detector base,ULC listing B200S-WH:White,Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol.(CSFM:7300-1653:0213) B200S-IV: Ivory, Intelligent addressable sounder base capable of • producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol.(CSFM:7300-1653:0213) Page 2 of 3—DF-61010:13-71/2019 SYSTEM SPECIFICATIONS • Sensitivity: Listings and Approvals • UL Applications:0.5%to 4.0%per foot obscuration. Listings and approvals below apply to the SD365 Series detectors. • ULC Applications:0.5%to 3.5%per foot obscuration In some cases, certain modules may not be listed by certain Size:2.0"(5.3 cm)high;base determines diameter approval agencies, or listing may be in process. Consult factory for —B300-6:6.1"(15.6 cm)diameter latest listing status. • —B501:4"(10.2 cm)diameter UL/ULC Listing:S1059 • For a complete list of detector bases see DF-60983 FM Approved • CSFM:7272-0075:0502 Shipping weight:3.4 oz.(95 g) Operating temperature range: • SD365: 32°F to 122°F(0°C to 50°C) • SD3657 Series:32°F to 100°F(0°C to 38°C) • SD365R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70°C) UL/ULC Listed Velocity Range: 0-4000 f/min. (1219.2 m/min.), suitable for installation in ducts Relative humidity: 10%—93%non-condensing Thermal ratings:fixed-temperature set point 135°F(57°C),rate-of- rise detection 15°F(8.3°C)per minute,high temperature heat 190°F (88°C) ELECTRICAL SPECIFICATIONS Voltage range: 15-32 volts DC peak Standby current(max.avg.):200pA @ 24 VDC(one communica- tion every 5 seconds with LED enabled) Max current:4.5 mA @ 24 VDC("ON") DETECTOR SPACING AND APPLICATIONS • Fire•Lite recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet(9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document A05-1003, is avail- able at www.systemsensor.com. LiteSpeedu" is a trademark, and Fire•Lite® Alarms and System Sensor® are registered trademarks of Honeywell International Inc. ©2019 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. • ISO We try to keep our product information up-to-date and accurate. 9001We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. ENCIM:EMN6 8 MANIFACTIRINB 11111111 T I' SYSTEMS For more information,contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. Country of Origin:Mexico www.firelite.com Page 3 of 3—DF-61010:B•71/2019 HWF2 - COM SERIES • LTE / IP Single or Dual Path Commercial Fire Communicators The HWF2-COM Series LTE / IP fire communicators are single or dual path commercial fire alarm communicators that offer Contact ID reporting with any FACP (fire HWF2A-COM alarm control panel) with a built-in dialer. INE Models include: HWF2A-COM(AT&T LTE&IP) HWF2V-COM(Verizon LTE&IP) Both models connect directly to the primary or secondary communication ports of a fire panel's digital alarm communicator transmitter(DACT). Three selectable reporting paths include:LTE cellular only,IP only,or IP primary with LTE cellular backup.All signals from the HWF2-COM Series are delivered to the AtarmNet•' network control center which routes highly encrypted,cybersecured Ethernet data packets via a customer-provided Internet connection or LTE cellular network to the appropriate central station.The AlarmNet®network control center is fully redundant and monitored 24/7.Installation and programming are easy using the handheld 7720P Programming • tool. HWF2V-COM INN . do FEATURES AND BENEFITS • LTE and IP connection tested every day connection(LAN or WAN),DSL model or • Diagnostic LEDs indicate signal strength • Three selectable reporting paths:LTE cable modem and status cellular only,IP only,or IP Primary with LTE • Data transmits over standard Contact ID • cellular backup protocol but is secured with the industry's Choice of LTE provider services • • Requires no change to the existing FACP advanced encryption standard(AES 256 QOS:Quality of Service diagnostics via AlarmNet conveys vital communicator configuration bit) information including signal strength, • Connects directly to the primary and • Supports both dynamic(DHCP)or public message path used,and when the message secondary telephone ports of a DACT and private Static IP addressing was received • Plan choices range from 5 minute,60 • Reliable connection:IP and cellular • 7720P Handheld programmer for easy minute,6 hour,and 24 hour supervision connection tested every day setup intervals • Built-in,standalone power supply module. • Operates overthefollowing communication • Onboard charging circuit design protocols:LTE,HSPA+(4G)HSPA(3G) accommodates battery backup.Includes • Works over any type of customer provided primary power and battery supervision Ethernet 10/100 based network Honeywell The HWF2-COM LIE/IP fire communicators operate over the most • Primary Subscriber ID(four digits),obtained from your monitoring modern and common cellular networks including LTE,4G and3G. station • • Communication Module MAC ID,and MAC CRC number located on They connect to any customer provided Ethernet 10/100 base the outside of the box and inside of the module network connection(LAN or WAN),DSL or cable modem.Selectable All parameters are assigned by the monitoring station. reporting path feature allows the radios to be configured for a single or dual path,while providing appropriate supervision intervals ALARMNET based on NFPA 72 requirements.Selectable paths and supervision AlarmNet communications technology provides a highly reliable timing intervals include: alternative for the transmission of alarm signals.The network SELECTABLE DESCRIPTION SUPERVISION provides extensive coverage in the United States and Canada.The PATH TIMES AlarmNet Network Control Center processes signals from powerful 1111 servers in multiple locations equipped with 24/7 infrastructure 2010 Cell Single path,cellular 5 Minutes support.Redundant hardware servers,real-time backup databases, 2010 IP Single path,IP 5 Minutes and generators with battery backup at all locations ensure 2010 IP&Cell Dual path,IP and cellular 24 Hours continuity of service.Signals from AlarmNet are transmitted to 2013 Cell Single path,cellular 60 Minutes central station receivers using multiple communication paths consisting of the Internet,LTE radio network,or toll free plain old 2013 IP Single path,IP 60 Minutes telephone service(POTS).Visit AtarmNet.com to learn more. 2013 IP&Cell Dual path,IP and cellular 6 Hours INSTALLATION REQUIREMENTS,UL COMPLIANCE OPERATION To meet UL864/NFPA requirements,ensure the following: When an event occurs,the FACP goes off-hook to dial the central station.The HWF2-COM Series dialer capture module detects the • HWF2-COM Series must be installed in accordancewith the National off-hook condition and provides the fire panelwith a dialtone.When Fire Protection Association(NFPA)standards 70 and 72 the fire panel detects the dial tone,it begins dialing the central • HWF2-COM Series must be mounted in the same room and within station. 20 feet of the fire panel. • HWF2-COM Series and all equipment used for the IP connection After the dialing is completed,the dialer capture module returns a (e.g.,router,hub,modem,etc)must be UL-listed,powered from an signal to the fire panel.The fire panel then sends the Contact ID unswitched branch circuit,and be provided with appropriate standby reports to the dialer capture module,which in turn sends a signal power. after the report is successfully received from the fire panel.The • HWF2-COM Series must use the 7AH battery(not included)to dialer capture nodule sends the Contact ID reports to the HWF2- provide 24 hour backup capability COM Series communications module.When allthe reports are sent, the fire panel goes on-hook.The HWF2-COM Series communications module then transmits the messages to the central station either over the LTE network or the Internet (depending on configuration). FIRE COMMUNICATOR/PANEL CAPABILITY The HWF2-COM Series is compatible with fire alarm control panels that use the Contact ID communications format as described in the SIA DC-05 standard. EASY TO PROGRAM The HWF2-COM communicator can be pre-programmed using the 7720P programmer to enter all central station information.This is saved to the HWF2-COM communicator panel memory.When the HWF2-COM is installed at the site and connected to the Internet/ Intranet,it registers with the AlarmNet Receiver. For most installations,the only required parameters are: • • Primary City ID(two digits),obtained from your monitoring station • Primary Central Station ID(two digits),obtained from your monitoring station Page 2 of 3—DH-62010:B•6/27/2019 HWF2-COM SERIES TECHNICAL SPECIFICATIONS ELECTRICAL Both models include: Transformer: • Red cabinet with key and lock Alarm Net' is a registered • Primary:12OVAC,60Hz,0.5A • Wall outlet box trademarks of Honeywell • Secondary:18VDC,5OVA • Dialer capture module International Inc. Battery: • LIE communications module ©2019 by Honeywell International • One 12 V 7.0 AH lead-acid battery:(not • Antenna and mounting adapter Inc.All rights reserved. supplied) • PowerBoostl power supply Unauthorized use of this document • Battery charging current:l Amp maximum • LED display board is strictly prohibited. • Battery discharge current:Standby 230mA, • Transformer Active 950mA • Manual and required screws This document is not intended to be • Cables,etc. used for installation purposes.We CABINET SPECIFICATIONS try to keep our product information ANTENNA AND EXTERNAL up-to-date and accurate.Wecannot • Dimensions:14.875"H x 12.75"W x 3.0'D HARDWARE t37.8cm H x 32.4cm W x 7.6cm D) cover all specific applications or • Color:Red CELL-ANT3DB:3dBA gain antenna anticipate all requirements.All WA7626-CA:SMAto N adapter cable specifications are subjectto change SHIPPING DIMENSIONS 7626-50HC:50 ft.antenna cable,low loss without notice. • Weight:5.3 lbs(6.94kg) • Dimensions:15.625"H x 13.79'W x 9.25'D Note:The WA7626-CA adapter cable and Country of origin:USA (39.7cm H x 34.9cm W x 23.9cm D) 7626-50HC antenna cable are only required when installing the CELL-ANT3DB TEMPERATURE AND HUMIDITY antenna remotely. RANGES This system meets NFPA requirements for OTHER ACCESSORIES operation at 0-49°C/32-120°F and at a 7720P:HWF2V-COM,HWF2A-COM and relative humidity 93°/a+-2%RH(non- IPGSM-4G handheld programmer condensing at 32°C+-2°C(90°F+-3°F). HPTCOVER:Plug-in transformer box for However the useful life of the system's HWF2V-COM,HWF2A-COM,and IPGSM- standby batteries and the electronic 4G communicators components may be adversely affected by BAT-1270:Battery 12 Volts,7AH,sealed extreme temperature ranges and humidity. AGENCY LISTINGS AND Therefore,it is recommended that this APPROVALS system and its peripherals be installed in an environment with a normal room The listings and approvals below applyto temperature of 15-27°C/60-80°F. the HWF2-COM Series communicators.In some cases,certain modules may not be PRODUCT LINE INFORMATION listed by certain approval agencies,or listing HWF2V-COM:LTE Digital Cellular Fire may be in process.Consult the factoryfor Alarm Communicator and Internet Panel, latest listings. Verizon LTE/IP UL Listed:S789 HWF2A-COM:LTE Digital Cellular Fire CSFM:7300-1645:0511 Alarm Communicator and Internet Panel, FDNY:Approved AT&T LTE/IP THE FUTURE IS 1111 Honeywell Power Products WHAT 12 Clintonville Road WE MAKE IT Northford,CT 06472-1610 203.484.7161 off-62010 I B 106/19 www.honeywellpower.com e2019 Honeywell International no Honeywell