Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report
Bulletin 157 Rev.hit M MIN ® Model F3QR56 Dry Reliabi K5.6 (80 metric) Quick-Response, Standard Spray Sprinklers Features 1. Available in the following configurations: • Pendent with standard escutcheon • Pendent with Model HB extended escutcheon • Pendent with Model FP recessed escutcheon t f • Pendent with Model F1 recessed escutcheon • Concealed Pendent with Model CCP cover plate , • Horizontal Sidewall with Standard escutcheon • Horizontal Sidewall with Model HB extended es- cutcheon Pendent Pendent/HB • Horizontal Sidewall with Model FP recessed es- (See Fig. 1) (See Fig.2) cutcheon (FM Standard Response) • Horizontal Sidewall with Model F1 recessed es- cutcheon (FM Standard Response) 2. Available with 1" NPT, ISO7-1R1, 3/4" NPT, or IS07- 1 R3/4 inlet fitting. 3. 3/4" NPT inlet fittings permit replacement of older 3/4" inlet dry sprinklers without changing to a larger sprin- -- kler fitting. `-< 4. Sprinklers, escutcheons, and cover plates are avail- able in a wide variety of standard and special appli- Recessed FP Pendent Concealed cation finishes. (See Fig.3) (See Fig.4) 5. White polyester, black polyester, and Electroless Nickel PTFE (ENT) finish sprinklers are cULus Listed as Corrosion Resistant. yL 6. Available with cULus Listed 250 psi (17.2 bar) pres- sure rating for Dry Pendent and select HSW configu- rations. FM Approved for 175 psi (12 bar). Product Description 4 : Model F3QR56 Dry sprinklers are quick-response, stan- dard coverage sprinklers with a nominal K-Factor of 5.6(80 Recessed F1 Pendent Horizontal Sidewall metric). Available in Dry Pendent or Dry Horizontal Sidewall (See Fig. 5) (See Fig.6) configurations, Model F3QR56 Dry sprinklers all use a 3 mm glass bulb operating element. See the Temperature Rat- 4 ings table in this Bulletin for available temperature ratings. Model F3QR56 Dry sprinklers are intended for installation r: on wet-pipe, dry-pipe, or preaction sprinkler systems in ac- cordance with NFPA 13, FM Property Loss Prevention Data Sheets,and other applicable installation standards. Model F3QR56 Dry sprinklers are available with a vari- Horizontal Sidewall/HB ety of escutcheon options as illustrated in Figs. 1 through (See Fig.7) 3 and Figs. 5 through 9. In addition, Model F3QR56 Dry Pendent sprinklers are also available with the Model CCP conical concealed cover plate as illustrated in Fig. 4. Avail- able sprinkler, escutcheon, and cover plate finishes are identified in the Finishes table in this Bulletin. The Model F1 escutcheon, Model FP escutcheon, and Model CCP cover plate are the only recessed escutcheons and cover plate listed for use with Model F3QR56 Dry sprinklers; the use of Recessed FP Recessed F1 any other recessed escutcheon or cover plate with Model Horizontal Sidewall Horizontal Sidewall F3QR56 Dry sprinklers will void all guarantees, warranties, (See Fig. 8) (See Fig.9) listings and approvals. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Inlet fittings are available with 1"NPT, ISO 7-1 R1,3/4"NPT, See the Available Configurations, Listings, and Approvals or IS07-1 R3/4 threads. Sprinklers with 3/4" NPT and IS07- table in this Bulletin for further information on Model F3QR56 1R3/4 inlet fittings are intended primarily for replacement of Dry sprinklers. existing 3/4"or IS07-1 R3/4 inlet dry sprinklers, but may also be used in new installations. Available Configurations, Listings, and Approvals Available Sprinkler Sprinkler Escutcheon or Listings and Inlet Identification Model Cover Plate Length Approvals()) Threads Number (See Figs. 1-9) (SIN) Standard 2" to 36" Escutcheon (50 to 900 mm) HB Extended Escutcheon El Recessed cULus, NYC 3/4" NPT or Escutcheon 3-1/2"to 36" ISO7-1 R3/4 (90 to 900 mm) FP Recessed Escutcheon F3QR56 Dry CCP Cover Plate R5714 Pendent Standard 2" to 48" Escutcheon (50 to 1200 mm) HB Extended Escutcheon 1" NPT F1 Recessed cULus, FM, NYC or Escutcheon 3-1/2"to 48" IS07-1 R1 (90 to 1200 mm) FP Recessed Escutcheon CCP Cover Plate Standard 2" to 48" Escutcheon (50 to 1200 mm) HB Extended Escutcheon cULus(2), NYC(2) 3/4" NPT or F1 Recessed 3-1/2" to 48" IS07-1 R3/4 Escutcheon (90 to 1200 mm) FP Recessed F3QR56 Dry Escutcheon Horizontal R5734 Sidewall Standard 2" to 48" Escutcheon (50 to 1200 mm) cULus(2) FM(3), NYC(2) HB Extended 3-1/2"to 48" Escutcheon (90 to 1200 mm) 1" NPT or F1 Recessed IS07-1R1 Escutcheon 3-1/2"to 48" cULus(2), FP Recessed (90 to 1200 mm) FM(3)(4), NYC(2) Escutcheon t')For available temperature ratings and finishes see the Temperature Ratings and Finishes tables,respectively,in this Bulletin. (2)cULus Listing and NYC for Light Hazard and Ordinary Hazard only. 0)FM Approved for Light Hazard only. 0)Model F3QR56 Dry Horizontal Sidewall with Model F1 or Model FP recessed escutcheon are FM Approved as Standard Response. 2. Patents I Model F3QR56 Dry series sprinklers may be covered by one or more of the following patents: US Patent No. 5,775,431 US Patent No. 5,967,240 Listing and Approval Agencies See the Available Configurations, Listings, and Approvals table in this Bulletin for listings and approvals applicable to each available configuration. 1. Listed by Underwriters Laboratories, Inc. and UL Certified for Canada(cULus) 2. Certified by FM Approvals(FM) 3. Permitted in New York City based on UL Listing per Local Law 33/2007 (NYC) Technical Data Nominal K-Factor: 5.6 gpm/psi'12(80 L/min/bar'/2) Sprinkler Listing or Approval Deflector to Ceiling Distance Maximum Working Pressure F3QR56 Dry cULus,NYC -- 250 psi(17,2 bar) Pendent FM -- 175 psi(12 bar) 4"to 6" 250 psi(17.2 bar) F3QR56 Dry cULus,NYC Horizontal Sidewall 6"to 12" 175 psi(12 bar) FM -- 175 psi(12 bar) Temperature Glass Bulb Sprinkler Cover Plate Maximum Ceiling Listings and Classification Color Temperature Rating Temperature Rating Temperature Approvalso) Orange 135°F(57°C) Ordinary 135°F(57°C) 100°F(38°C) cULus,FM,NYC Red 155°F(68°C) Intermediate Yellow 175°F(79`C) 165°F(74°C) 150°F(66°C) cULus,NYC Intermediate Green 200°F(93°C) 165°F(74°C) 150°F(66°C) cULus, FM,NYC None 225°F(107°C) cULus,FM(2),NYC High Blue 286°F(141°C) 165°F(74°C) 150°F(66°C) cULus,NYC C')For listed and approved sprinkler,escutcheon,and inlet configurations see the Available Configurations,Listings,and Approvals table in this Bulletin. (2)High temperature classification is FM Approved with Standard and Model HB escutcheons only. Finishes Component Sprinkler Escutcheon)') Cover Plate Bronze Brass") White Paint Standard Finishes White Polyester«) White Polyester Chrome Chrome Chrome Electroless Nickel PTFE°21 Satin Chrome Electroless Nickel PTFE Special Application Finishes Black Polyester° Black Polyester Black Paint Customer Color Polyester Custom Color Paint Custom Color Polyester Black Plating "l Standard and Model HB escutcheons are supplied with both the can and escutcheon finished.Model F1 escutcheons are supplied with both the collar and escutcheon finished.Model FP escutcheons are supplied with the escutcheon finished;the cup is galvanized steel with no further finish. I (2)cULus Listed as a Corrosion Resistant Sprinkler. Is)Brass finish available for standard,Model F1,and Model FP escutcheons only. 3. I Model F30R56 Dry Pendent Sprinkler with Standard Escutcheon (SIN R5714) "A"Dim. 2"to 48"(51mm to 1219mm)in 1/4"(6mm)increments for 1"connections or I— 2"to 36"(51mm to 914mm)in 1/4"(6mm)increments for 3/4"connections - I l .i-- - ' — T- -,...,,- II I I , System Fitting i _ " Inlet Fitting 2-1/8" �— s [54mm] Dia. "A" Dimension Hole in Ceiling 1-1/2" [38 mm] I 1-21/32" Dia. i IN I Total Adjustment [42 mm] 1-- 1-1/4"[32 mm] Sprinkler Can i Ceiling iling Escutcheon Adjustment 1/4"[6 mm] Escutcheon — Escutcheon ��Ceiling i I\ r Ceiling Adjustment Nominal Escutcheon t 1 Position 1/4"[6 mm] 1 Protrusion at Nominal Escutcheon Position 1-5/8" _ 3 [76 mm] [41 mm] DIA. 153FG01-G Fig. 1 Note:The sprinkler can protrudes'A"when escutcheon is in nominal position. Escutcheon adjustment provides'/<"(-6mm)to+1'/4" (+32mm)"A" dimension adjustment range. Sprinkler Guard: Model C2 4. I Model F3QR56 Dry Pendent Sprinkler with Model HB Extended Escutcheon (SIN R5714) "A"Dim. 31/2'to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2°to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections System Fitting UI 2-1/2"[64 mm]Dia. _ ` — Inlet Fitting Hole in Ceiling "A"Dimension 3-1/2"[89 mm] Escutcheon Dia. 1/2"[12.5mm] ' Escutheon Adjustment • Ceiling i 1"[25 mm]Total 0 Escutcheon Adjustment ---\--1— Escutcheon —___ � 1/2'[12.5mm] Escutheon Adjustment Sprinkler Can Nominal Position of Escutcheon /1-1/4"[32 mm] ' Protrusion at 1.5/8" Nominal Escutcheon Position r • [41 mm] i 157FG02B 2-3/16"[56 mm]Dia. - - ...11 Fig. 2 Note: The sprinkler can protrudes 114"when escutcheon is in nominal position. Escutcheon adjustment provides-'/"(-12.7mm)to+Ye"(+12.7mm) "A"dimension adjustment range. Sprinkler Guard: Model C2 5. Model F3QR56 Dry Pendent Sprinkler with Model FP Recessed Escutcheon (SIN R5714) "A"Dim. 3'/2'to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections r, I h I011 .d I I 1 ' b J I _. I— II — \; I. L System Fitting Inlet Fitting 2-1/2" [64 mm] Dia. — IAN— Hole in Ceiling "A" Dimension I 2-9/32" [58 mm] Dia. 7— Nominal Sprinkler 1 Escutcheon I Cup Position ` ---- wor."-N Escutcheon Ceiling 11 �1� _____-.Ceiling i, 1/4" [6 mm]Escutcheon Adjustment 1/4" [6 mm] 3 7/32" Escutcheon Adjustment [82 mm] Dia. —1.---1 1/2" [12 mm] - - Total Escutcheon Adjustment 153FG02-F Fig. 3 Note:Do not install the Model F3QR56 Dry Pendent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space i above. 6. I Model F3QR56 Dry Pendent Sprinkler with Model CCP Cover Plate (SIN R5714) "A"Dim. 3'h"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections I IN 1 11I IIII �`� Iil II,I"I" I I System Fitting MUMInlet Fitting I _ 2-1/2"[64 mm] Dia. Hole in Ceiling 'A' Dimension 2-9/32"[58 mm] Dia. ' Nominal Sprinkler Cover Plate i Cup Assembly Position 1 _= Model CCP 1/2 Cover Plate Assembly Ceiling j djustment Limited to 3!8"[10 mm]) {tee _ �, --� 1 Ceiling 1 i 3/16"[5 mm] I -$- Cover Plate Adjustment 3/16"[5 mm] Cover Plate Adjustment 3-5/16" [84 mm] Dia. 3/8" [10 mm] 153FG03-F Total Cover Plate Adjustment Fig.4 Note:Do riot install the Model F3QR56 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have positive pressure in the space above. 7. • I Model F3QR56 Dry Pendent Sprinkler with Model F1 Recessed Escutcheon (SIN R5714) "A"Dim. 3/'- to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 313""to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections. F z s L - _ 7 I i�l� li 11�0 I I I II, I 1' 1 1 � II II 1 Ii 1I I1 it ply! I !4'1 IlL I I r-�1 f�� r 1 L. \ L- System Fitting Inlet Fitting 2-1/4" [57 mm] Dia. ' Hole in Ceiling h 1-15/16' [49mm] Dia. "A" Dimension I I Nominal 11 Escutcheon 11 Position 11 \ \1 Ceiling 1/8" Ceiling [3 mm] 1/4" [6mm] Escutcheon Adjustment \ --f 1/4" [6 mm] - Escutcheon Adjustment Escutcheon 1/2" [12 mm] Adjustment 2-27/32" 157FG05B [72 mm] Dia. Fig.5 8. 1 Model F3QR56 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon (SIN R5734) "A"Dim. 2"to 48"(51mm to 1219mm)in 114"(6mm)increments for 1"connections or 2"to 36"(51mm to 914mm)in 1/4"(6mm)increments for 3/4"connections 1-1/2" [38 mm] Total Escutcheon Adjustment Ceiling 1 m i 4"[102 mm] Min. 1-1/4" [32 mm] ,►i 12" [305 mm] Max. Escutcheon Adjustment 1/4" [6 mm] System Fitting Escutcheon Adjustment Inlet Fitting _ j i 2 [5 3 mm] ' (111/1 /ram 1' I' rr= -' fi lnllt' 5/8" [16 mm] fIi - 1 I•1'1111 — 3,� [76 mm] � 1 I 2-1/8" T 1� J [54 mm] Dia. — I Hole in Wall I 1/4"[6mm] Protrusion Sprinkler Can ---' �' at Nominal Escutcheon Position Nominal Escutcheon Position "A'Dimension r► 157FG06B Fig. 6 Note:The sprinkler can protrudes 1/4"when escutcheon is in nominal position. Escutcheon adjustment provides'/a"(-6mm)to+11" (+32mm)"A" dimension adjustment range. 9. 1 Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model HB Escutcheon (SIN R5734) "A"Dim. 31/z"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections 1" [25.4mm] h. Total Adjustment Ceiling it 1/2"[12.7mm] Escutcheon Adjustment 4' [101.60mm] Min. 12"[304.80mm]Max. 1/2" [12.7mm] - Escutcheon Adjustment I 2 3/32" • — System Tee [53.18mm] ', Inlet Fitting 1 r t ��IIIIIIIII uNNuu Alt i��l [2-13/64" 3-1/2" ��INIIIY�II, II I 55.D8 8mm] [88.9mm] A--_-,_—: � ' .r_ Escutcheon Dia. \.i , I I 2 1/2" Dia. , 1 [63.5mm] \, Hole in Wall I 1-1/4"[31.75mm]Nominal Protrusion \ I Sprinkler Can "A"Dimension — `- Escutcheon \` Nominal Position 157FG07B of Escutcheon Fig. 7 Note: The sprinkler can protrudes 11/4"when escutcheon is in nominal position. Escutcheon adjustment provides'h"(-12.7mm)to+'h"(+12.7mm) "A"dimension adjustment range. 10. Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model FP Recessed Escutcheon(SIN R5734) "A"Dim. 31/2'to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 31/2"to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling 1-13/32' Escutcheon -- [36 mm] 4"[102 mm] Min. System Fitting Cup cULus, NYC:6"[152 mm] Max. FM: 12" [305 mm]Max, • Inlet Fitting ` . I //// �c� 5/8"[16 mm] 3-7/32" [82 mm] Dia. l y 2-1/2" V 1 [64 mm] Dia. • Hole in Wall - Nominal Escutcheon Position 2-19/64" [58 mm] Dia. 1/4"[6mm] scutcheon Adjustment 1/2"[12 mm] 157FG08B - "A"Dimension ' Total Escutcheon Adjustment 'I� --- 1/4"[6 mm] Escutcheon Adjustment Fig.8 Note:Do not install the Model F30R56 Dry Horizontal Sidewall sprinkler with the Model FP escutcheon in walls which are positively pressurized with respect to the protected space. 11. Model F3QR56 Dry Horizontal Sidewall Sprinkler with Model Fl Recessed Escutcheon (SIN R5734) "A"Dim. 37"to 48"(89mm to 1219mm)in 1/4"(6mm)increments for 1"connections or 3' "to 36"(89mm to 914mm)in 1/4"(6mm)increments for 3/4"connections Ceiling Escutcheon [3 mm] I 1 4" [102 mm] Min. System Fitting m icULus, NYC:6"[152 mm] Max. FM: 12"[305 mm] Max. , Inlet Fitting I I , 5/8•[16 mm] n Y\\` i i y I 2-27/32" [72 mm] Dia. 2-1/4" [57 mm] Dia. I �, 1 y_ Hole in Wall rls 1-15/16'[49 mm] Dia. Nominal Position [—Iof Escutcheon ■ 41f— 1/4" [6 mm] Escutcheon Adjustment lam— 1/2"[12 mm] 157FG096 �__ A"Dimension Total Escutcheon Adjustment --- jf 1/4" [6 mm] Escutcheon Adjustment Fig.9 12. • RECOMMENDED EXPOSED MINIMUM BARREL LENGTH WHEN CONNECTED TO WET PIPE SPRINKLER SYSTEM (DRY PENDENT SPRINKLER WITH STANDARD ESCUTCHEON SHOWN) WET PIPE EXPOSED BARREL IS HARGE EN' OED MII MINIMUM M TOP LEILING (-1 __I �� IP �1 AMBIENT AMBIENT TEMPERATURE __ Tt ___ _ __ _ BARREL TH- TEMPERATURE 40°HA'C 50°F110'C 60'FH6°C ---1` - - 1F EXPOSED TO I-- - 1--- ---' -II1H_-IL, DISCHARGE END I EXPOSED (FACE )"' --I ;y tc==�, I IN.(MM) IN.IMM) IN.(MM) r-= HUMIDIFY AND ILMPLRAIURL DIFFLRLNIIAL 40°F(4°C) 0 0 0 r = % CAUSES CONDENSATION CN THE EXPOSED DRY 30°F ERG) 0 0 0 �„ / BARRELL WITH IER, ON ULATION, FOAM NSIDER C INSULATING GRE SED 20°F(-T'C( 4(100) 0 0 TAPE OR EQUIVALENT. 10°F(-12°C) 6(200) 1(25) 0 0°F(-18°C) 12(300) 3(75) 0 MINIMUM (HEATED AREA) SEAL THE CLEARANCE SPACE EXPOSED -10°F(-23°C) 14(350) 4)100) 1(25) BARREL AROUND THE SPRINKLER TO AVOID LENGTH LEAKAGE OF AIR INTO THE PROTECTED -20°F(-29'C) 14(950) 0 1150) I 3(T5) AREA AND CONSEQUENT FORMATION OF ---- - -- - --- CONDENSATE AROUND THE FRAME,WHICH 30°F(3P0) , 16(4001 61200) 4(100) COULD INHIBR OPERATION OR CAUSE PREMATURE OPERAT,ON.SEE BELOW FOR -40°F(-40°C) 18(450) 3(200) 4(1001 RECOMMENDED METHODS. 'A" CLEARANCE -50°F(.46'C) 20(5001 10(25) 61150) DIMENSION HOLE A0°F(-51°C) 201500) 10(250) 6(150) I 'FOR AMBIENT TEMPERATURES EXPOSED TO THE DISCHARGE END / OF THE SPRINKLER THAT OCCUR BETWEEN THE VALUES LISTED.USE I I THE NEXT MINIMUM BARREL Pr "THE MINIMUM EXPOSED BARREL LENGTH IS NOT THE SAME AS THE I 'A.DIMENSION.THE MINIMUM EXPOSED BARREL LENGTH IS BASED ON A PROPERLY SEALED PENETRATION WRH A MAXIMUM WIND VELOCITY HI PN THE EXPOSED SPRINKLER OF 30 MPH(49 KMM).LONGER EXPOSED / BARREL LENGTHS WILL HELP AVOID FREEXING OF THE WET PIPING ! ESCUTCHEON WHERE HIGHER WIND VELOCITY IS EXPECTED. CEILING) `Ii11,nI "'THE MINIMUM EXPOSED BARREL LENGTH IS MEASURED FROM THE I II 14, FACE OF THE FITTING TO THE INSIDE FACE OF THE WALL FOR DRY (PROTECTED AREA) � DISCHARGE END OF SPRINKLER HORLZONTAL SIDEWALL SPRINKLERS. I.--.-3'DIA. RECOMMENDED EXPOSED MINIMUM BARREL LENGTHS ALSO APPLY TO DRY HORIZONTAL SIDEWALL SPRINKLERS RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS WET PIPE (DRY SPRINKLER WITH STANDARD ESCUTCHEON SHOWN) WET PIPE f-- F --- -r -11 - p I I I I 1I --�111 L__ k1t -- l � Lr-I 1L,"-1r-ti L-� 1 I' (HEATED AREA) EMI(HEATED AREA) MINIMUM MINIMUM EXPOSED _. EXPOSED BARREL 4 iiiNiNiiii.. BARREL LENGTH : Ko INSIDE FACE /SEAL(BEE ABOVE) / (6EE ABOVE) ED) , / am- CLEARANCE HOLE / = INSULATED FREEZER,II! /r) I1 OR COOLER STRUCTURE (\F OR EXTERIOR FRAMING _ = • 1 _ n wym (PROTECTED AREA) DISCHARGE END OF (PROTECTED AREA) II DISCHARGE END OF n• I DRY SPRINKLER I _1 DRY SPRINKLER IN COLA AREA \AO IN COLD AREA 157FG10C Fig. 10 13. *CAUTION* RELIABLE DRY PENDENT AND DRY HORIZONTAL SIDEWALL SPRINKLERS MAY BE INSTALLED IN A LISTED CPVC SPRINKLER FITTING, ONLY UPON VERIFICATION THAT THE FITTING DOES NOT INTERFERE WITH THE SPRINKLER'S INLET. Do not install dry sprinklers with standard inlets into CPVC fittings that have an internal obstruction;this will damage the sprinkler,the fitting, or both. Short inlet("PL")versions of Reliable dry sprinklers are available that mayor may not be compatible with fittings having internal obstructions in existing installations. Sprinklers with the short inlet("PL")should only be installed in CPVC fittings of wet-pipe systems. In all cases, verify sprinkler and fitting dimensions prior to installation to avoid interference. Internal No Internal Obstruction Obstruction Female Female Pipe Pipe Thread Thread - CPVC Fitting with Internal Obstruction CPVC Fitting No Internal Obstruction Shorter Longer Inlet ' Inlet Male Male Pipe Pipe Thread— Thread Dry Sprinkler Dry Sprinkler Short Inlet ("PL") Standard Inlet BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION 076FG08C Fig. 11 14. «& 7 » : t d \ . . « , . . Fig. 2-Model oe Model F3RWrench \�.. » < . : , < : 2�\: , . \§ , \ .. § } ^ «w« . . a«© « «. « « a , « � am � « --- -- m2 3-Model x o Wrench 15. MATERIAL SPECIFICATIONS ,- ,� ITEM 4 DESCRIPTION MATERIAL SPECIFICATION • 13 1 FRAME BRASS PER UNS C83600 2 DEFLECTOR BRONZE PER UNSC51000 I,� 3 LOAD SCREW BRASS PER UNS C22000 r/ 4 SEAT ADAPTOR BRASS ALLOY PER UNS C36000 n ! 5 BULB INSERT COPPER ALLOY PER UNS C31400 6 GLASS BULB GLASS W/GLYCERIN SOLUTION 111 il �/ E 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL NJ 4_ 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLET BRASS ALLOY PER UNS C35330 12 CAP BRASS ALLOYPERUNSC54400 0 ' 13 SPRING WASHER/SEAL PTFE COATED BERYLLIUM NICKEL 11 5 14 FLIP DISK BRASS ALLOY PER UNS C54400 j 15 CAN/ESCUTCHEON PAINTED OR PLATED MILD STEEL 0 ' 110 � ,-®(PIPE WRENCH MAY ONLY BE USED ON OUTER STEEL PIPE OF SPRINKLER) I © 016fg10 _I 153fg16 0 157fg16 3 ,� ( APPEARANCE OF DEFLECTOR MAY VARY DEPENDING ON MODEL mom, ,. Fig. 16 16. Installation Instructions Model F3QR56 Dry sprinklers must only be installed in the sprinkler assembly other than the wrench boss.When following fittings: inserting or removing the wrench from the sprinkler, 1. The side outlet of an ANSI B 16.3 class 150(malleable care should be taken to prevent damage to the sprin- or ductile) or ANSI B16.4 class 125 (cast) iron pipe kler.The sprinkler is then tightened into the pipe fitting tee to achieve a leak free connection.The recommended 2. The run outlet of an ANSI B 16.3 class 150(malleable minimum to maximum installation torque is 22 -30 lb- or ductile) or ANSI B16.4 class 125 (cast) iron pipe ft (30 —40 N-m) for 1" NPT and IS07-1R1 sprinklers, tee, with the side outlet plugged (wet-pipe systems and 14-20 lb-ft(19—27 N-m)for 3/4" NPT and IS07- only) 1 R3/4 sprinklers. 3. Spears Manufacturing Company Brass Thread In- 3a.Alternatively, where access to the outer tube of sert Style or Special Reinforced Plastic Thread Style the sprinkler is available, the Model F3QR56 Dry Listed adapter or tee(wet-pipe systems only) (gasket sprinkler may be installed using a pipe wrench. sealed outlets shall not be used) The pipe wrench shall only be permitted to inter- 4. Any Listed CPVC sprinkler adapter or tee only in ac- face with the galvanized steel outer tube portion of cordance with Fig. 11 and upon verification that the the sprinkler (Item #8 in Fig. 16). Do NOT wrench CPVC adapter or tee does not interfere with the sprin- any other portion of the sprinkler assembly.A pipe kler's inlet (wet-pipe systems only) (gasket sealed wrench can install the sprinkler into the fitting with outlets shall not be used) a large amount of torque; consideration should be Model F3QR56 Dry sprinklers must not be installed into el- given to the need for future removal of the sprin- bows,welded outlets,or gasket sealed outlets. Installation of kler because the installation torque will have to be the Model F3QR56 Dry sprinkler is not recommend in cop- matched or exceeded to remove the sprinkler.The per pipe systems, as this may reduce the life expectancy of recommended minimum to maximum installation the sprinkler. torque is 22 - 30 lb-ft (30 — 40 N-m) for 1" NPT In all dry-pipe system installations,the Model F3QR56 Dry and IS07-1 R1 sprinklers, and 14-20 lb-ft(19—27 sprinkler must be installed with protrusion into the fitting in N-m)for 3/4" NPT and IS07-1 R3/4 sprinklers. accordance with Fig. 1 through Fig.9 in this Bulletin. Do not 4. Standard and Model HB escutcheons can be in- install Model F3QR56 Dry sprinklers with the standard(long) stalled by slipping the escutcheon over the can until inlet fitting into CPVC fittings that have an internal obstruc- the escutcheon is seated against the ceiling or wall. tion (see Fig. 11); this will damage the sprinkler, the fitting, Model F1 escutcheons are installed by pressing the or both. Model F3QR56 Dry sprinklers are available with a escutcheon onto the collar until the escutcheon is short"PL" inlet fitting for installation on CPVC fittings of wet- seated against the ceiling or wall. The Model FP es- pipe sprinkler systems only. cutcheon is installed by pressing or threading the es- Model F3QR56 Dry sprinklers connected to wet-pipe sys- cutcheon into the cup by hand; the escutcheon can tems must be installed with the Exposed Minimum Barrel be tightened against the ceiling or wall by turning the Length required by Fig. 10 located in a Heated Area. escutcheon in a clockwise direction and removed by An orange protective clip is factory installed on the sprin- turning the escutcheon in a counter-clockwise direc- kler to protect the glass bulb thermal element from dam- tion.To install the Model CCP cover plate,first remove age. The clip should remain in place during installation of the protective clip. Install the Model CCP cover plate the sprinkler and be removed when the sprinkler system is on the sprinkler by pressing or threading the cover placed in service. Sprinklers with 3/4" NPT and IS07-1 R3/4 plate into the cup by hand; the cover plate can be inlets are supplied with a protective cap on the inlet that tightened against the ceiling by turning the cover must be removed before installation. plate in a clockwise direction and removed by turning Use the following steps for installation: the cover plate in a counter-clockwise direction. 1. Cut a hole in the wall or ceiling directly in-line with 5. Remove the orange protective clip when placing the the outlet of the fitting. See the Installation Data table sprinkler system in service. for the recommended hole diameter based on the es- cutcheon or cover plate option selected. 2. Apply pipe joint compound or PTFE tape to the male threads of the sprinkler's inlet fitting. 3. Install the sprinkler in the fitting using the installation wrench specified in the Installation Data table. The Model F3 and F3R wrenches are designed to be in- serted into the groves in the sprinkler's wrench boss as shown in Fig. 12. The Model XLO2 wrench is de- signed to fit into the cup and engage the wrench boss as shown in Fig. 13. Do NOT wrench any part of the 17. Installation Data Required Centerline of Sprinkler Sprinkler Suggested Hole Diameter in • Installation Model Escutcheon or Cover Plate Wall or Ceiling Tube/Inlet to Finished Ceiling Wrench Vertical Dimension" Standard Escutcheon 2-1/8"(54 mm) F3 or F3R HB Extended Escutcheon 2-1/2"(64 mm) F3QR56 Dry Not F1 Recessed Escutcheon 2-1/4"(57 mm) Pendent Applicable FP Recessed Escutcheon XLO2 2-1/2"(64 mm) CCP Cover Plate Standard Escutcheon 2-1/8"(54 mm) 4-5/8"to 12-5/8" HB Extended Escutcheon 2-1/2"(64 mm) (116 mm to 321 mm) F3 or F3R F3QR56 Dry F1 Recessed Escutcheon 2-1/4"(57 mm) cULus,NYC Horizontal 4-5/8"to 6-5/8" Sidewall FP Recessed Escutcheon 2-1/2"(64 mm) (118 mm to 168 mm) XLO2 F1 Recessed Escutcheon 2-1/4"(57 mm) FM 4-5/8"to 12-5/8" FP Recessed Escutcheon 2-1/2"(64 mm) (118 mm to 321 mm) * Based on 5/8" (16 mm)centerline of sprinkler tube/inlet to defector vertical distance. Maintenance Ordering Information The Model F3QR56 Dry Sprinklers should be inspected Specify: and the sprinkler system maintained in accordance with 1. Sprinkler: [Model F3QR56 Dry Pendent SIN R5714] NFPA 25. Do not remove the factory applied thermally sen- [Model F3QR56 Dry Horizontal Sidewall SIN R5734] sitive wax fillet between the bulb supporting cup and the 2. Escutcheon/Cover Plate: [None][Standard escutch- wrenching boss. Do not replace this wax with a substitute eon][Model HB extended escutcheon][Model F1 substance. recessed escutcheon][Model FP recessed escutch- An Alternate substance may interfere with proper operation eon][Model CCP cover plate—pendent only] of the sprinkler. Do not clean sprinklers with soap and water, 3. Inlet Threads: [1" NPT][IS07-1 R1][3/4" NPTI[ISO7- ammonia or any other cleaning fluids. Remove dust by us- 1 R314] ing a soft brush or gently vacuuming. Replace any sprin- 4. Inlet Fitting: [Long—Standard Inlet Fitting][Short "PL" kler which has been painted (other than factory applied)or —Wet Pipe Systems only] damaged in any way.A stock of spare sprinklers should be 5. Sprinkler Temperature Rating: See Temperature Rat- maintained to allow quick replacement of damaged or op- ings table erated sprinklers. Prior to installation, sprinklers should be 6. Sprinkler Finish: See Finishes Table maintained in the original cartons and packaging until used 7. Escutcheon/Cover Plate Finish: See Finishes Table to minimize the potential for damage to sprinklers that would 8. Length: "A" Dimension (face of tee to face of ceiling cause improper operation or non-operation. or wall) in 1/4" (6 mm) increments—See Fig. 1 through Fig. 9 Note: The "A" dimension is based on a nominally gauged pipe thread "make-up" of.600" (15mm) per ANSI B2.1 [approxi- mately 7 1/2 threads]. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years,. Manufactured by Reliable Automatic Sprinkler Co.,Inc. ® Recycled Reliable® (800)431-1588 Sales Offices Paper (800)848 6051 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.10/16 P/N 9999970175 FPS2022 - /9 4450 SU) 97" 41/C Bulletin 016 Rev,H Model DH56 HSW W Reliable ® Model DH56 HSW Recessed �. Model DH56 HSW Concealed Quick Response, Extended Coverage Dry Sprinklers For coverages up to 28 feet wide and 10 feet long'1). 250 psi (17,2 bar) rated. Features: . 1. Coverage for long and narrow spaces such as hallways, " ' � " corridors, decks and rooms up to 28 feet wide and 10 , feet long." 2. Deflector to ceiling dimensions are: 4"(102mm)min.to 12"(305mm)max. DH56 HSW(See Fig.4) 3. Minimum spacing between sprinklers 16 feet(4.9m).(1) 4. Polyester Coated or Electroless Nickel PTFE (Teflon)* .. Plated Corrosion Resistant Sprinklers. *Concealed Sprinkler is not corrosion resistance. 5. UL Listed for extended coverage,light hazard applications. { 6. 5.6 K Factor. 7. Sprinkler is approved for 250 psi(17,2 bar)applications. 8. Quick response performance. 9. 1/2" (13mm)adjustment of escutcheon and cover. DH56 HSW/HB(See Fig.5) 10.Concealed cover plate can prevent the sprinkler from being used for unintended purposes.No exposed thermal element with the concealed version. 40, 11.Push-on/thread-off sturdy convenient escutcheon for recessed and cover for concealed. ,14 12.Factory assembled sprinkler&cup,shipped complete with bulb protector for concealed and FP recessed versions. 13.Sprinkler & cup assembly and escutcheon or cover are separately packaged. DH56 HSW FP Recessed(See Fig.6) 14.Available in a variety of plated and painted finishes j1>See Fig. 9. Approval Organizations �- 1. Listed by Underwriters Laboratories Inc. ands 4 UL certified for Canada(cULus) Pr . 2. NYC MEA 258-93-E Patents US Patent No. 7,841,418 DH56 HSW Concealed Other Patents Pending with SWC coverplate(See Fig. 7) The SWC cover plate and FP recessed escutcheons have Products Description 1/2" adjustment. The SWC cover plate is attached with 135 The Model DH56 are quick response extended cover- & 165 degree solder. In the event of a fire the rising ambient age sidewall dry sprinklers for use in light hazard applica- temperature melts the solder and the cover plate is ejected tions. The Model DH56 dry sprinkler with SWC cover plate away by springs exposing the 3mm frangible glass bulb. is a concealed sprinkler that uses Reliable's push on/thread The use of a 3mm bulb allows quick response which enables off sidewall cover.This sprinkler has the cup factory mounted the sprinkler to apply water to a fire sooner than standard and is shipped with a bulb protector that protects the 3mm response sprinklers of the same temperature rating . frangible glass bulb during shipping and post installation fin- Model DH56 dry sprinklers are intended for use in dry ishing operations. The DH56 can be combined in the field and preaction systems to protect areas subjected to freez- with the FP Escutcheon to make a recessed dry sprinkler. ing temperatures and unheated portions inside and outside buildings. See Fig. 1 for guidelines on using dry sprinklers in 'DuPont Registered Trademark wet systems. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Environments wherein dry sprinklers are employed can DH56 HSW Recessed with FP Escutcheon be corrosive. For this reason, Model DH56 dry sprinklers To install the DH56 HSW dry sprinkler with the FP Escutch- have a special wax fillet placed in the gap between the eon as a recessed sprinkler cut a 25/8" diameter hole in the cup that supports the bulb and the wrenching boss. This wall as shown in Fig.6. Temporarily remove the plastic pro- wax will not interfere with the operation of the sprinkler,and tective cap, and then use the Model XLO2 wrench' (see it prevents contaminants from entering the internal portion Fig. 2)to tighten the sprinkler until it is secured in the sprin- of the drop nipple. The wax must not be removed. kler fitting. Note:The Model XL02 wrench has a notch in it to accommodate the deflector top. This wrench can only Application be inserted one way. Care must be taken not to damage The Model DH56 is a horizontal sidewall dry sprinkler the deflector during tightening. Apply a Teflon"based seal- intended for installation in light hazard occupancies in ac- ant to the sprinkler threads before installing in the sprinkler. cordance with NFPA 13. These sprinklers are designed to It is recommended that the sprinkler be protected during provide fire protection in long and narrow spaces such as plastering and painting operations by reinstalling the plastic hallways, corridors, decks and rooms up to 28 feet(8,5m) protective cap. Installation is completed by removing the wide and 10 feet(3m)long. They are rated for 250 psi(17,2 protective cap and inserting the push-on escutcheon. Turn bar) and can be mounted between 4 and 12 inches (102 clockwise to adjust the escutcheon against the wall. and 305mm)down from the ceiling. DH56 HSW Concealed with SWC Cover Plate General Installation Instructions To install the DH56 HSW dry sprinkler with the SWC cover- Model DH56 dry sprinklers must be installed only in stan- plate as a concealed sprinkler,cut a 21/8" diameter hole into dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) the wall as shown in Fig. 7. Temporarily remove the plastic pipe tees in the horizontal position,even at branch line ends. protective cap,and then use the Model XL02 wrench' (see They should not be installed into elbows or pipe couplings Fig. 2)to tighten the sprinkler until it is secured in the sprin- located on drop nipples to the sprinklers. For these and kler fitting. Note:The Model XLO2 wrench has a notch in it other fittings including CPVC, the dry sprinkler should be to accommodate the deflector top. This wrench can only installed into a fitting to allow protrusion into the fitting in ac- be inserted one way. Care must be taken not to damage cordance with the diagrams. The "A" dimension of the dry the deflector during tightening. Apply a Teflon*based seal- sprinkler,which extends into a freezing zone from wet pipe ant to the sprinkler threads before installing in the sprinkler. systems, should be selected to provide, as a minimum,the It is recommended that the sprinkler be protected during specified lengths in inches shown in Fig. 1. plastering and painting operations by reinstalling the plastic Caution: protective cap. Installation is completed by removing the Do not install Model DH56 HSW Dry sprinklers into CPVC protective cap and inserting the coverplate. Coverplate as- adapter fittings or tees that have an internal obstruction. semblies provide 1" (13mm) of adjustment. Final adjust- This will damage the sprinkler and/or the fitting. Refer to ment is made by turning the coverplate clockwise until the Fig. 8 skirt flange makes full contact with the wall surface. Cover DH56 HSW removal requires turning in the counter-clockwise direction. Concealed coverplate assemblies are listed only for use To install the DH56 HSW dry sprinkler cut a 21/8" diameter with specific sprinklers.The use of any other concealed wall hole in the wall as shown in Fig.4. Use the Model F3 instal- sprinkler or the use of the SWC coverplate on any sprinkler lation wrench(see Fig. 3)on the square boss to tighten the with which it is not specifically listed will void all guarantees, sprinkler until it is secured in the sprinkler fitting'. Apply a warranties, listings and approvals. Teflon*based sealant to the sprinkler threads before install- Note: DH56 and DH56 Recessed Sprinklers have orange ing in the sprinkler. Installation is completed by removing bulb protectors to minimize bulb damage during shipping, the orange glass bulb-protector and assembling the slip-on handling, and installation. REMOVE THIS PROTECTION AT escutcheon to the sprinkler's can. THE TIME THE SPRINKLER SYSTEM IS PLACED IN SER- VICEDH56 HSW/HB FOR FIRE PROTECTION. Removal of the protectors To install the DH56 HSW/HB dry sprinkler cut a 21/2" di- before this time may leave the bulb vulnerable to damage. ameter hole in the wall as shown in Fig. 5. Use the Model RASCO wrenches are designed to install sprinklers when F3 installation wrench (see Fig. 3) on the square boss to covers are in place. REMOVE PROTECTORS BY UNDO- tighten the sprinkler until it is secured in the sprinkler fitting'. ING THE CLASP BY HAND. DO NOT USE TOOLS TO RE- Apply a Teflon" based sealant to the sprinkler threads be- fore installing in the sprinkler. Installation is completed by removing the orange glass bulb-protector and assembling the slip-on escutcheon to the sprinkler's can. ' Installation Wrenches. Throughout this technical bulletin,Reliable has specified specific installation wrenches for use on each version of our sprinklers.A pipe wrench may also be used to install a dry sprinkler provided that it only interfaces with the steel outer tube of the assembly(Item#8 on fig 10).Keep in mind that a pipe wrench will incorporate a large amount of toraue into the final assembly.This torque will have to be matched or exceeded upon the sprinkler's removal at a later date "DuPont Registered Trademark 2. , • RECOMMENDED MINIMUM EXPOSED BARREL LENGTH BASED ON AMBIENT TEMPERATURE IN THE PROTECTED AREA (STANDARD DH56 HSW DRY SPRINKLER SHOWN) EXPOSED BARREL AMBIENT AMBIENT TEMPERATURE TEMPERATURE OF PROTECTED 407/4-C I 50F/10°C I 60'F/16"C IAEA.AT THE DIEDswim END EXPOSED MINIMUM BAFREL LENGTH'. or INE smoto•EN (FACE OF TEE TO TOP OF CEILING) IN.(IMO IN.NM) IN.(1.0.1) 40V(EC) 0 0 0 30F(-EC) 0 0 0 2WF(-7C) 4(101) 0 0 10'F(-17C) 8(203) 1 (25.1) 0 DDIENSION OT(-ICC) 12(305) 3(73) 0 MINIMUM CLEARANCE -10T(-2.3•C) 14(356) 4(101) 1 (25.1) -20F(-2WC) 14(356) 6(152) 3(75) r.".` ---'' ''''‘<.....:4°LE:!:,•:.•'.1::..:,.:.:11•,..•:!.:....• !i! :i '. !'ii'.'• iiii -30V(-34T) 16(406) 8(203) 4(101) ... . .... ... ..... . ..... ..... . ....... -40V(-4CFC) 18(457) 8(203) 4(101) .....:.•:i:.::i:i:.:::.:,.'.•,:.•..:.•.:.•::,:...:: -50V(-EEC) 20(505) 10(254) 6(152) '.••.'..•-.'.•'.'.'."•.'.'.'.•..'.'.'.'. •......•...,.....•••••••.•...•.•,•. ... ........ ..... . -DOT(-5EC) 20(508) 10(254) 6(152) FXsARRELPOSED LENGTH .....L.„.it} (HEATED AREA) ..,•.••.•.-.........,•...,...•.•.. :::.::::.;.:.:.::: ::::::;:;:: ISCUTC14EON •-•' •THE PROTECTED AREA REFERS TO THE AREA BELOW THE GOURD. I THE AMBIENT TEMPERATURE IS THE TEMPERATURE AT THE DISCHARGE —Ii14 ------------ ------- I DA. END OF THE SPRINKTER. '\. FOR PROTECTED AREA TEMPERATURES THAT OCCUR BETMEEN THE VALUES ,1 LISTED,USE THE NUT COINER TEMPERATURE - :'0!;M:gM.M.r'i :i .THE MIN.REQUIRED BARREL LENGTH IS NOT THE SANE AS THE'.A.0114ENSION. WET NOTE:EXPOSED MINIMUM BARREL LENGTHS ARE INGUJSIVE UP TO 30MPH PIPE (PROTECTED,, VAPID VELOCITIES IN THE PROTECTED AREA INSTALL 1 INCH NPT THREADED ENO OF DRY PENDENT SPRINKLER i:,i''•::ii:..',:.,:''''',],'''::: INTO O THE 1 INCH NPT OUTLET OF A NAMEABLE IRON nzE Hum. PER ANSI B 16.3(CLASS 160) WALL OR CAST RON THREADED TEE FITTING PER ANSI 16.4(CLASS 125)ONLY. INSUIATED FREEZER OR COOLER STRUCTURE IF 15241DITY AND TEMPERATURE DIFFERENTIAL OR EKTEMOR FRAMING CAUSES CONDENSATION ON THE EXPOSED DRY SPRDELER,CONSIDER WRAPPING THE EXPOSED BARREL WITH INSULATION,FOAM INSULATING TAPE OR EQUIVALENT, SEAL THE CLEARANCE SPACE AROUND THE SPRINKLER TO AVOID LEAKAGE OF AIR INTO THE PROTECTED AREA AND CONSEQUENT FORMATION 17 CONDENSATE AROUND THE FAME,WHICH COULD INHIBIT OPERATION OR CAUSE PREMATURE OPERATION,SEE BELOW FOR RECOMMENDED METHODS RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS (STANDARD DH56 HSW DRY SPRINKLER SHOWN) MINIMUM EXPOSED CLEARANCE MINDIUM BARREL ' '-• HOLE EXPOSED LENGTH BARREL (SEE ABOVE) LENGTH (SEE ABOVE) INSIDE I INSIDE FACE FACE . IN COLD SPRIMER 41, .,. :, ! ....i -:. N COLD AREA OEATED AREA) i:1,:::il (HEATED AREA) e I' jiMil MI _______ II..,.*:, Ai • ..41.1 I I I Wili.k . k'' I al 1-,... •,, 11011110 , ,... k"., 111111=11 111111.10" \ I i': ': i';'',ii'iM!!'.. !1 WET PIPE qi .:.;i ;i:ii .:.i.i :: *::'.:Liti WET PIPE SEAL 111 :7::::H: :!i:.::!:::::::::3 1111 :' " ': (PROTECTED AREA) liji..ii :-:*i;i:i:i*:::i::•.•1.; !jii:i:.i!::i...:i.::i::.::.-:ii::::;.ii , 111:::::''.••,-.::;:::,.''':::•••:::1.. DECKTITE FLASHING RASCO 14003910 INSULATED FREEZER, (RECOMMENDED) OR COOLER STRUCTURE OR EXTERIOR FRAMING O 16F011A Fig. 1 3. Y Technical Data: Maintenance Temperature Sprinkler Model DH56 Quick Response Dry Sprinklers should be in- K Factor Rating Maximum Identification spected and the sprinkler system maintained in accordance Thread Ambient Size Ir Temperature Number with NFPA 25. Do not remove the factory applied thermally SWC Tem US Metric; Sprinkler Cover p (SIN) sensitive wax fillet between the bulb supporting cup and the 155°F 135'F 100°F wrenching boss. Do not replace this wax with a substitute (68°C) (57°C) (38°C) substance. An alternate substance may interfere with proper 175°F 165°F 150°F operation of the sprinkler. Do not clean sprinklers with soap 5.6 80 1 (79°C) (74°C) (66°C) i RA1664 and water, ammonia or any other cleaning fluids. Remove 200°F 165 F 150°F dust by using a soft brush or gentle vacuuming. Remove any (93°C) 1(74 C) (66°C) sprinkler which has been painted(other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or Coverage area ', operated sprinklers. Prior to installation, sprinklers should be Maximum Coverage Flow Rate Pressure maintained in their original cartons and packaging until used Area Width x Length gpm(umin) psi(bar) to minimize the potential for damage to sprinklers that would ftxft(mxmZ 28 x 8(8,5 x 2,4) 23(87,1) ss(t,2) cause improper operation or non-operation. 28 x 10(8,5 x 3) 28(106) 25(1,7) Model DH56 Quick Response Approval Type: Extended Coverage Horizontal • Quick Response, Extended Coverage. Sidewall Dry Sprinkler Specification • Approved for installation in accordance with NFPA 13 Sprinklers shall be a [quick response -cULus Listed] ex- for light hazard occupancies. tended coverage horizontal sidewall sprinkler for light hazard occupancies. Sprinklers to be of bronze frame construction Step 1 1 with a special deflector capable of providing a discharge over a coverage area of 28 ft. (8,5m)wide, and 10 ft. (3m) long horizontal throw.Water seal assembly shall consist of a Teflon" coated Belleville spring washer. Installation shall permit sprin- kler deflectors to be positioned 4" (102mm)to 12" (305mm) At below the ceiling. Sprinklers shall have a nominal K-factor Step 2 of 5.6(80), and 1" NPT thread. Sprinkler temperature rating shall be [155°F(68°C)] and [200°F(93°C)]. Rated working pressure shall be 250 psi (17.2 bar). Standard finish: [white] [chrome][bronze][Special finish- specify]. Quick response extended coverage horizontal sidewall dry sprinklers shall be Reliable Model DH56,SIN RA1664(Bulletin 016). Step 3 For recessed EC horizontal sidewall sprinklers: Replace "horizontal sidewall"with"recessed horizontal sidewall." Add: ] (1)Recessed escutcheon assembly shall be a two-piece es- cutcheon of push-on and thread off design with (13mm) '.r adjustment.Standard finish shall be chrome,white and brass. Quick response recessed horizontal sidewall sprinklers shall Fg.2-XL02 Wrench be Reliable Model DH56,SIN RA1664(Bulletin 016). For concealed EC horizontal sidewall sprinklers: Replace "horizontal sidewall" with "concealed horizontal sidewall." Add: Cover plate assembly shall consist of a brass cover r plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a '/2" (13mm) cover plate adjust- ment. Cover plate temperature rating shall be 135°F(57°C) for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F (93°C) dry sprinkler. A bulb protector shall be provided and factory installed inside the sprinkler cup to protect the glass bulb from damage, which could occur during construction before the cover plate is installed.Standard cover plate finish: [white] [Custom Color- specify]. Quick response extended Fig.3-F3 Wrench coverage concealed horizontal sidewall dry sprinklers shall *DuPont Registered Trademark be Reliable Model DH56,SIN RA1664(Bulletin 016). 4. *CAUTION* DO NOT INSTALL MODEL F3, MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLERS INTO CPVC ADAPTER FITTINGS OR TEES THAT HAVE AN INTERNAL OBSTRUCTION. THIS WILL DAMAGE THE SPRINKLER AND/OR THE FITTING. CPVC ADAPTER FITTINGS AND TEES WITH INTERNAL OBSTRUCTIONS ARE ALSO COMMONLY FOUND DURING THE RETROFITTING PROCESS OF RELIABLE'S OLDER MODEL G3 DRY SPRINKLERS. INTERNAL NO OBSTRUCTION INTERNAL OBSTRUCTION irr "'Er FEMALE 10 FEMALE 0� PIPE %�t �/ PIPE l` i0 THREAD � . THREAD ' INCORRECT CORRECT CPVC ADAPTER CPVC ADAPTER FITTING OR TEE FITTING OR TEE SHORTER = LONGER R INLET f mum MALE MALE PIPE PIPE THREAD =. THREAD = PIP - -= MODEL F3-PL MODEL F3QR-PL OR STANDARD MODEL DH56 HSW-PL MODEL F3. DRY SPRINKLER MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLER BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION O f 6fg08A Fig.8 7. Ordering Information Installation Wrench' Specify: Model XLO2 Sprinkler Wrench (Recessed &Concealed) 1. Sprinkler Type(select one): Model F3 Sprinkler Wrench (a)Model DH56 Dry EC HSW Note: A leak tight 1" NPT sprinkler joint can be obtained (b)Model DH56 Dry EC HSW/HB with a torque of 20-30 ft-lbs (27.1 - 40.7 N-m). Do not (c)Model DH56 Dry Recessed EC HSW/FP tighten sprinklers over maximum recommended torque. (d)Model DH56 Dry Concealed EC HSW It may cause leakage or impairment of the sprinklers. 2. Sprinkler Temperature Rating. Escutcheon Data: 3. Sprinkler Finish. 4. Cover Plate/Escutcheon Finish. FP cup/escutcheon assembly-1/2"(13mm) adjustment 5. Length: "A" Dimension (face of tee to face of ceiling or Finishes (1) wall) in VI" (6mm) increments. Standard Finishes t't Notes: l Sprinkler Escutcheon r Cover Plate 1. The "A" dimension is based on a nominally gauged pipe White or Black Polyester pi Brass"2 thread "make-up" of 0,600" (15mm) per ANSI B2,1 [71/2 Chrome White White threads approximately]. I - Bronze Chrome 2. All platings and paintings are decorative and intended for — interior use. Special Application Finishes • Sprinkler HSW/HSW HB • U Sprinklers, p i kler Listing Category Sa is dr Open. ( eons • EIectroless Nickel Other colors andfinishes eare avail'able.ctroless ConsuEtNackoryPTFE(Tells nI)"I Quick Response p cULus listed Corrosion Resistant (2 Not available for HB escutcheons. Note:Paint or any other coatings applied over the factory finish will void all approvals and warranties. ill', v-... 76' [4.9m] Minimum Spacing 28' [B.Sm] Maximum Spacing \ \\ �''''-- MODEL DH56 DRY SPRINKLER I \ I I r WALL i I 4 \ \ . 1 40/ / Ay 4" /.100mm] rain.From Ceiling 7 /%�;��� i ;2" [305mmI max, From Geiiino \max % .\ \� //' 28' f8_,5m] A \ 10' !3m] 016FG09A Fig.9 ' Installation Wrenches: Throughout this technical bulletin,Reliable has specified specific installation wrenches for use on each version of our sprinklers.A pipe wrench may also be used to install a dry sprinkler provided that it only interferes with the steel outer tube of the assembly(item#8 on fig 16).Keep in mind that a pipe wrench will incorporate a large amount of torque into the final assembly.This torque will have to be matched or exceeded upon the sprinkler removal at a later date. 'DuPont Registered Trademark 8. MATERIAL SPECIFICATIONS ITEM# DESCRIPTION MATERIAL SPECIFICATION Gar - - 1 FRAME BRASS PER UNS C83600 2 DEFLECTOR BRONZE PER UNS C51000 3 LOAD SCREW BRASS PER UNS C22000 4 SEAT ADAPTOR BRASS ALLOY PER UNS C36000 5 BULB INSERT COPPER ALLOY PER UNS C331400 6 GLASS BULB GLASS W/GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLET BRASS ALLOY PER UNS C35330 12 CAP BRASS ALLOY PER UNS C54400 • 13 SPRING WASHER/SEAL TEFLON COATED BERYLLIUM NICKEL 14 FLIP DISK BRASS ALLOY PER UNS C54400 15 CAN/ESCUTCHEON PAINTED OR PLATED MILD STEEL Fig. 10 9. f tilers Fire & Building Products Technical Services: Tel: (800) 381-9312/Fax: (800)791-5500 Series DS-1 — 5.6 K-factor Dry Type Sprinklers Standard & Quick Response, Extended Coverage General manufacturer should be contacted with any questions. Description The Series DS-1 Dry Type Sprinklers .., must only be installed in fittings that The Tyco® Series DS-1, 5.6 K-factor, meet the requirements of the Design Ar ., Quick Response(3 mm Bulb)and Stan- Criteria section. if 4 v , dard Response (5 mm Bulb), Extend- ' ed Coverage Horizontal Sidewall, Dry Model/Sprinkler Type Sprinklers are decorative glass ' / bulb automatic sprinklers.They are in- i # .) tended for use in applications where Identification the sprinklers and/or a portion of the Numbers connecting piping may be exposed to freezing temperatures (e.g., horizontal TY3338-(3 mm Bulb Type) piping extensions through a wall to TY3358-(5 mm Bulb Type) protect an unheated area of a build- ing). The Series DS-1 Extended Cov- Water Tube Stainless Steel erage Horizontal Sidewall Sprinklers Technical Spring Stainless Steel are designed for extended cover- Sealing age use in light hazard occupancies Data g Assembly (ECLH). Beryllium Nickel w/Teflon* Approvals Escutcheon Carbon Steel WARNINGS UL and C-UL Listed. NYC Approved. *Registered Trademark of DuPont The Series DS-1 Dry Type Sprinklers (Refer to Table A) Patents described herein must be installed Maximum Working Pressure U.S.A. Patent No.5,188,185 and maintained in compliance with 175 psi(12,1 bar) this document, as well as with the Operation applicable standards of the National Inlet Thread Connection p Fire Protection Association, in addi- 1 inch NPT When the Series DS-1 is in service, tion to the standards of any other au- Discharge Coefficient water is prevented from entering the thorities having jurisdiction. Failure to K=5.6 GPM/psi"2 assembly by the Plug&Belleville Seal- do so may impair the performance (80,6 LPM/bar12) ing Assembly (Ref. Figure 1) in the of these devices. Temperature Ratings Inlet of the Sprinkler. The glass Bulb The owner is responsible for maintain- Refer to Table A contains a fluid that expands when ing their fire protection system and de- exposed to heat.When the rated tern- vices in proper operating condition. Finishes perature is reached,the fluid expands The installing contractor or sprinkler Sprinkler: Natural Brass, Chrome sufficiently to shatter the glass Bulb, Plated,White Polyester and the Bulb Seat is released. The Escutcheon:White Coated or Chrome compressed Spring is then able to ex- Plated, Brass Plated pand and push the Water Tube as well IMPORTANT Physical Characteristics as the Guide Tube outward.This action Always refer to Technical Data Inlet Copper simultaneously pulls inward on the Sheet TFP700 for the "INSTALLER Plug Copper Yoke,withdrawing the Plug&Belleville WARNING" that provides cautions Yoke Stainless Steel Seal from the Inlet allowing the sprin- with respect to handling and instal- Casing . . . . Galvanized Carbon Steel sprin- kler to activate and flow water. lation of sprinkler systems and corn- Insert Bronze ponents.Improper handling and in- Bulb Seat Stainless Steel stallation can permanently damage Bulb Glass a sprinkler system or its compo- Compression Screw Bronze nents and cause the sprinkler to fail Deflector Bronze to operate in a fire situation or cause it to operate prematurely. Frame Bronze Guide Tube Stainless Steel Page 1 of 6 JANUARY, 2008 TFP520 Page 2 of 6 TFP52O SPRINKLER FINISH TY3338 HSW (3 mm Bulb Type) w/Standard Escutcheon (Ref.Fig.2) TY3358 HSW (5 mm Bulb Type) w/Standard Escutcheon (Ref.Fig.2) Temperature Bulb Color Natural Chrome White Rating Code Brass Plated Polyester 135"F/57`C Orange 1,2,3 155"F/68°C Red 1,2.3 Notes 1. Listed by Underwriters Laboratories, Inc. (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches). 3.Approved by the City of New York under MEA 352-01-E. TABLE A SERIES DS-1, EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVAL Coverage 01 Min Min Top Of Deflector To APPLICATION W x L Flow Pressure Temperature Ceiling Distance«1 Ft.x Ft.(m x m) GPM(LPM) PSI(bar) Rating°F(C°) Inches(mm) 16 x 16(4,9 x 4,9) 26(98) 21.6(1,49) TY3338 HSW (3 mm Bulb Type) 16 x 18(4,9 x 5,5) 29(110) 26.8(1,85) For Quick Response 135&155 4 to 12 Light Hazard 16 x 20(4,9 x 6,1) 32(121) 32.7(2,25) (57&68) (100 to 300) Extended Coverage Per NFPA 13 18 x 16(5,5 x 4,9) 29(110) 26.8(1,85) Coverage 01 Top Of Deflector To APPLICATION W x L Min Flow Min Pressure Temperature Ceiling Distance 1') Ft.x Ft.(m x m) GPM(LPM) PSI(bar) Rating"F(C°) Inches(mm) 16 x 16(4,9 x 4,9) 26(98) 21.6(1,49) TY3358 HSW For(5 mm Bulb Tye)Standa d Response 16 x 18(4,9 x 5,5) 29(110) 26.8(1,85) 135&155 4 to 12 Light Hazard 16 x 20(4,9 x 6,1) 32(121) 32.7(2,25) (57&68) (100 to 300) Extended Coverage Per NFPA 13 18 x 16(5,5 x 4,9) 29(110) 26.8(1,85) Notes: 1.The minimum allowable spacing between sprinklers to prevent cold soldering is 14 feet(4,3 m). 2.To meet the deflector-to-ceiling distance of 4 to 12 inches(100 to 300 mm),the centerline of the sprinkler waterway must be 4-7/16 to 12-7/16 inches below the ceiling. TABLE B SERIES DS-1,EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS UL AND C-UL INSTALLATION CRITERIA • TFP520 Page 3 of 6 PLUG WITH YOKE CASING INSERT FRAME 3 or 5 mm GASKETED SPRING BULB DEFLECTOR PLATE SEAL 11 COMPRESSION WATER GUIDE BULB VENT SCREW INLET 1"NPT SP ING TUBE TUBE SEAT HOLE FIGURE f TY3338(3 mm BULB) TY3358(5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY Design ORDER LENGTHS: Criteria 2-1/2"to 48" (63,5 to 1219,2 mm) 4 t 1/8 TheTyco®SeriesDS-1 Sprinklers are in- IN 1/4"(6,4 mm) [(101,6±3,2 mm) tended for use in fire sprinkler systems INCREMENTS FACE OF designed in accordance with the ex- ..___-MOUNTING tended coverage installation guide- FACE OF 1.3/4"DIA. SURFACE lines provided by NFPA 13 and the in- ,L_1__s SPRINKLER (44,5 mm) \\ stallation criteria provide by Table B. �l FITTING L H The 1 inch NPT Series DS-1 Sprin- CI IIII 1 klers are to be installed in the 1 inch +I � r (76,2DIA. m) NPT outlet or run of malleable or duc- tile iron threaded tee fittings that meet .`I the dimensional requirements of ANSI `T �SPRINKLER FITTING B16.3(Class 150)or cast iron threaded -_! (REFER TO DESIGN CENTERLINE 7/16" tee fittings that meet the dimension- CRITERIA SECTION) OF WATERWAY (11,1 mm) al requirements of ANSI B16.4 (Class 125). The Series DS-1 Sprinklers may FIGURE 2 also be installed in the 1 inch NPT out- TY3338(3 mm BULB) TY3358(5 mm BULB) let of a Grinnell Figure 730 Mechani- EXTENDED COVERAGE HORIZONTAL SIDEWALL cal Tee. w/STANDARD ESCUTCHEON Typically, the end sprinkler fitting on a branch line is plugged as shown in Figure 2. The DS-1 Sprinklers cannot be installed into an elbow fitting. For wet pipe systems,the DS-1 Sprin- klers may also be installed in the fol- lowing Tyco® CPVC fittings: (P/N WRENCH 80145) 1"x 1" NPT Female Adapter or FLAT (P/N 80249) 1"x 1"x 1"NPT Sprinkler WRENCH Head Adapter Tee. RECESS NOTE PUSH WRENCH All,111 lib) Do not install the Series DS-1 into any IN TO ENSURE other type fitting without first con- ENGAGEMENT suiting the Technical Services De- WITH SPRINKLER IL t partment. Failure to use the appro- WRENCH FLATS �l priate fitting may result in: failure of the sprinkler to properly operate due to formation of ice over the inlet Plug FIGURE 3 or binding of the inlet Plug; or, insuf- W-TYPE SPRINKLER WRENCH ficient engagement of the inlet pipe threads with consequent leakage. Branch, cross, and feedmain piping connected to Dry Sprinklers and sub- ject to freezing temperatures must be pitched for drainage in accordance with the minimum requirements of the Page 4 of 6 TFP52O National Fire Protection Association il EXPOSURE Installation for dry pipe sprinkler systems. LENGTH When Dry Sprinklers are to be used in ~(SEE DESIGN The Tyco®Series DS-1 Dry Type Sprin- wet pipe sprinkler systems protecting CRITERIA SECTION) klers must be installed in accordance areas subject to freezing temperatures with the following instructions: (e.g., sprinkler drops into freezers), FACE OF consideration must be given to the SPRINKLER NOTES appropriate length of the sprinkler that FITTINGri The Series DS-1 must only be installed will prevent freezing of the water in the in fittings that meet the requirements connecting pipes due to conduction. i r- on of the Design Criteria section. When the temperature surrounding I Refer to the Design Criteria section for the wet pipe sprinkler system is main- other important requirements regard- DSB-2 tained at a minimum temperature of IWOing piping design and sealing of the IN 40°F/4°C, the following are the mini- R FREED clearance space around the Sprinkler mum recommended lengths between FOR FREEZER Casing. the face of the sprinkler fitting and the STRUCTURES Do not install any bulb type sprinkler outside surface of the protected area if the bulb is cracked or there is a loss (i.e., length exposed to minimum am- HEATED of liquid from the bulb. With the sprin- bient of 40°F/4°C-Ref. Figure 4): AREA W kler held horizontally, a small air bub- • 12 inches(300 mm)when the tern- ble should be present. The diameter perature within the protected area FIGURE 4 EXPOSURE LENGTH of the air bubble is approximately 1/16 is-20°F/-29°C inch(1,6 mm). • 18 inches(450 mm)when the tern- A 1 inch NPT sprinkler joint should be perature within the protected area obtained with a minimum to maximum is-40°F/-40°C torque of 20 to 30 ft. lbs. (26,8 to 40,2 1-3/4"DIA. Nm). Higher levels of torque may dis- •24 inches(600 mm)when the tem- (44,5 mm) tort the sprinkler inlet with consequent perature within the protected area CLEARANCE INSULATED leakage or impairment of the sprinkler. is-60°F/-51°C HOLE FREEZER in- For protected area temperatures be- ADHESIVE STRUCTURE sufficient not attempt to compensatecu forhtween thosegiven above,the minimum Plae under-or t n an Escutcheon he Plate by under-or over-tightening the recommended length from the face of DSB-2 i Sprinkler. Readjust the position of the the fitting to the outside of the protect- BOOT i Aink, sprinkler fitting to suit. ed area may be determined by interpo- �i lating between the indicated values. II- 'I I __� Step 1. Horizontal sidewall sprinklers The 2007 edition of NFPA 13, Sec- • III—* are to be installed in the horizontal 1 position with their centerline of water- tion 8.4.10.2 requires that dry sprin- way perpendicular to the back wall klers connected to wet pipe sprinkler and parallel to the ceiling. The word systems protecting insulated freezer "TOP" on the Deflector is to face to- structures have the clearance space wards the ceiling. around the sprinkler barrel be sealed. STRAP TIES DS-1 The use of the Model DSB-2 Dry Sprin- (ENDS ON Step 2. With pipe thread sealant ap- kler Boot described in Technical Data OPPOSING SHOWN WITH plied to the inlet threads, hand tighten Sheet TFP591,and illustrated in Figure SIDES OF STANDARD the sprinkler into the sprinkler fitting. 5,will meet the intent of NFPA 13. BOOT) ESCUTCHEON Step 3.Wrench tighten the sprinkler by wrenching on the Casing with a pipe FIGURE 5 wrench whenever the casing is readily MODEL DSB-2 SPRINKLER accessible.Otherwise,use a W-Type 7 BOOT WITH SIDEWALL SERIES Sprinkler Wrench (Ref. Figure 3). The DS-1 DRY SPRINKLER wrench recess of the W-Type 7 is to be applied to the sprinkler wrench flats (Ref. Figure 3). Step 4. After the wall has been in- stalled/finished, slide on the outer piece of the Escutcheon until it comes in contact with the ceiling/wall. TFP520 Page 5 of 6 Care and The owner is responsible for the in- spection, testing, and maintenance Maintenance of their fire protection system and de- Warranty vices in compliance with this docu- The Series DS-1 Dry Type Sprin- ment, as well as with the applicable Products manufactured by Tyco Fire klers must be maintained and ser- standards of the National Fire Protec- & Building Products (TFBP) are war- viced in accordance with the following tion Association (e.g., NFPA 25), in ranted solely to the original Buyer for instructions: addition to the standards of any oth- ten(10)years against defects in mate- er authorities having jurisdiction. The rial and workmanship when paid for lli nstang contractor or sprinkler manu- and properly installed and maintained Absence of the outer piece of an es- facturer should be contacted relative under normal use and service. This cutcheon, which is used to cover a to any questions. warranty will expire ten(10)years from clearance hole, may delay the time to Automatic sprinkler systems should date of shipment by TFBP. No warren- sprinkler operation in a fire situation. be inspected, tested, and maintained ty is given for products or components Before closing a fire protection system by a qualified Inspection Service in manufactured by companies not affili- main control valve for maintenance accordance with local requirements ated by ownership with TFBP or for work on the fire protection system that and/or national code. products and components which have it controls, permission to shut down been subject to misuse, improper in- the affected fire protection systems stallation, corrosion, or which have must be obtained from the proper au- not been installed, maintained, modi- thorities and all personnel who may fied or repaired in accordance with be affected by this action must be applicable Standards of the Nation- notified. al Fire Protection Association, and/or the standards of any other Authorities A Vent Hole is provided in the Bulb Having Jurisdiction. Materials found Seat (Ref. Figure 1) to indicate if the by TFBP to be defective shall be either Dry Sprinkler is remaining dry. Evi- repaired or replaced, at TFBP's sole dence of leakage from the Vent Hole option. TFBP neither assumes, nor is an indication that there may be authorizes any person to assume for weepage past the Inlet seal and that it, any other obligation in connection the sprinkler needs to be removed with the sale ofproducts or parts of for determining the cause of leakage products. TFBP hall not be es on- (e.g. an improper installation or an P ice plug). The fire protection system sible for sprinkler system design er- control valve must be closed and the rors or inaccurate or incomplete infor- system drained before removing the mation supplied by Buyer or Buyer's sprinkler. representatives. Sprinklers that are found to be leaking In no event shall TFBP be liable, in or exhibiting visible signs of corrosion contract, tort, strict liability or under must be replaced. any other legal theory, for incidental, indirect,special or consequential dam- Automatic sprinklers must never be ages,including but not limited to labor painted, plated, coated, or other- charges, regardless of whether TFBP wise altered after leaving the factory. was informed about the possibility of Modified sprinklers must be replaced. such damages, and in no event shall Sprinklers that have been exposed TFBP's liability exceed an amount to corrosive products of combustion, equal to the sales price. but have not operated,should be com- pletely cleaned by wiping the sprinkler The foregoing warranty is made in with a cloth or by brushing it with a lieu of any and all other warranties. soft bristle brush. express or implied, including warran- Care must be exercised to avoid dam- ties of merchantability and fitness for age -before, during, and after instal- a particular purpose. lation. Sprinklers damaged by drop- This limited warranty sets forth the ex- ping, striking, wrench twist/slippage, clusive remedy for claims based on or the like, must be replaced.Also,re- failure of or defect in products,materi- place any sprinkler that has a cracked als or components, whether the claim bulb or that has lost liquid from its is made in contract,tort, strict liability bulb(Ref. Installation Section). or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Page 6 of 6 TFP520 P/N 60 - XXX - X - XXX ORDER LENGTH(1) (EXAMPLES) 055 5.50" SPRINKLER ESCUTCHEON MODEL/SIN FINISH FINISH 082 8.25" 350 EC Sidewall 3 mm Bulb TY3338 1 NATURAL BRASS WHITE 180 18.00" (1"NPT),135°F/57°C 4 WHITE POLYESTER WHITE 187 18.75" 351 EC Sidewall 3 mm Bulb TY3338 (1"NPT),155°F/68°C 9 CHROME PLATED CHROME PLATED 372 37.25" 0 CHROME PLATED WHITE 480 48.00" EC Sidewall 3 mm Bulb 3 WHITE(RAL9c10)* WHITE(RAL9010)* 950 TY3358 (1"NPT),135°F/57°C 2 NATURAL BRASS BRASS PLATED EC Sidewall 3 mm Bulb 951 TY3358 (1"NPT),155°F/68°C NOTES (1).Dry Type Sprinklers are furnished based upon"Order Length"as measured per Figure 2 After the measurement is taken,round it to the nearest 1/4 inch increment. Eastern Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES DS-1 EXTENDED COVERAGE HORIZONTAL SIDEWALL DRY TYPE SPRINKLERS (Use Prefix`I"for ISO 7-RI Connection, e.g., 1-60-361-1-180) Ordering • 1 Inch NPT Inlet Connection. •Temperature Rating. Procedure •Sprinkler Finish. Dry Sprinklers: •Standard Escutcheon and Finish. Contact your local distributor for • Part Number from Table C. availability, and please specify the 2.W-Type 7 Sprinkler Wrench. following: Refer to the Price List for complete 1. Sprinkler. listing of Part Numbers. • Model/SIN. Model DSB-2: • Bulb Size(3 or 5 mm) Specify: Model DSB-2 Dry Sprinkler • Extended Coverage Horizontal Boot*, P/N 63-000-0-002. Sidewall Dry Type Sprinkler. * Includes one Boot, two Strap Ties, •5.6 K-factor. and 1/3 oz. of Adhesive (quantity of •Order Length. adhesive is sufficient for installing one Boot) Dry Type Sprinklers are furnished based upon Order Length as mea- sured from the face of the wall to the face of the sprinkler fitting(Ref. Figure 2). After the measurement is taken, round it to the nearest 1/4 inch increment. ©2007-2008 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446 ♦ Bulletin 148 Rev.H Model F1FR QREC Series •11Reliable° K8.0 (1Eiended .1 Quick co ers A complete line of UL Listed and FM Approved quick response extended coverage sprinklers for light hazard applications. Horizontal Sidewall Sprinklers are approved for installation 4" - 12" (102mm - 305mm) below the ceiling. Model F1FR QREC Sprinkler Types - w Extended Coverage Pendent Extended Coverage Horizontal Sidewall Extended Coverage Recessed Extended • EC-9 Deflector Pendent Coverage Pendent Model F1FR QREC Recessed Sprinkler Types Recessed Extended Coverage Pendent } Recessed Extended Coverage Horizontal gI Sidewalk - ; • EC-9 Deflector �.k For Model F1FR QREC '/2" K 5.6 (80) Sprinkler Types refer to Bulletin 028. Extended Coverage Recessed Extended Horizontal Sidewall EC-9 Coverage Horizontal Sidewall Approval Organizations EC-9 1. Underwriters' Laboratories, Inc. (UL) 2. Underwriters Laboratories of Canada(ULC) 3. Factory Mutual Approvals (FM) 4. NYC MEA 258 93 E The glass bulb consists of an accurately controlled amount UL Listing Category of special fluid hermetically sealed inside a precisely manu- Sprinklers,Automatic & Open factured glass capsule. This glass bulb is specially con- Quick Response Extended Coverage Sprinkler structed to provide fast thermal response. The balance of UL Guide Number parts are made of brass,copper and beryllium nickel. VNIV The temperature rating of the sprinkler is identified by the Note: Consult appropriate FM Installation Standards color of the glass bulb. regarding limitations of room size,ceiling height and Application minimum wall fire resistance rating. Quick response sprinklers are used in fixed fire protec- Product Description tion systems: Wet, Dry, Deluge or Preaction. Care must be Reliable Models F1FR QREC and F1FR QREC Recessed exercised that the orifice size, temperature rating, deflector Sprinklers are quick response sprinklers which combine the style and sprinkler type are in accordance with the latest durability for a standard sprinkler with the attractive low pro- published standards of the National Fire Protection Asso- file of a decorative sprinkler. ciation or the approving authority having jurisdiction. Quick The Models F1FR OPEC and F1FR QREC Recessed Auto- response sprinklers are intended for installation as specified matic Sprinklers utilize a 3.0mm frangible glass bulb. These in NFPA 13. sprinklers have demonstrated response times in laboratory tests which are five times faster than standard response sprinklers. This quick response enables these sprinklers to apply water to a fire faster than standard response sprinklers of the same temperature rating. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 I. . * Model F1 FR QREC Pendent Sprinkler Deflector: EC Installation Wrench: Model D Sprinkler Wrench or Model W2 Sprinkler Wrench Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy traivriel Installation Data: — i Nominal Sprinkler Nominal Thread K-Factor Sprinkler Temperature Approval Identification 11010.. Orifice Size Length Rating Organizations US ' Metric Number(SIN) "/32" 3/4'NPT 8.0 115 2.2" 135°F(57°C) 1,2,3,4 R4342 (20mm) (Rs/4) (56.1mm) 155°F(68°C) i. r. ..� , Model F1 FR QREC Recessed Pendent Sprinkler Deflector: EC Installation Wrench: Model GFR2 Sprinkler Wrench Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy Installation Data: Nominal Sprinkler Nominal Thread K-Factor Sprinkler Temperature Approval"1 ! Identification Orifice Size Length Rating Organizations Number(SIN) US Metric '132" 3/4"NPT 2.2" 135°F(57°C) (20mm) (R3/4) 8.0 115 (56.1mm) 155°F(68°C) 1,2,3,4 R4842 l'l Refer to escutcheon data table for dimensions. Model F1 FR QREC Pendent and Recessed Pendent Required Minimum Flow/Pressure Maximum Flow Rate Pressure Coverage Area 2 1/4'- gpm(Umin) psi(bar) Width x Length 26 (98.4) 10.6(0,7) 16 x 16 (4.9 x 4.9) r -' _ 33 (125.0) 17.0(1,2) 18x18 (5.5x5.5) _ 40 (151.4) 250(1,7) 20 x 20 (6.0x60)`21 'oen ,,;Ae — � T r V'' .21 UL/ULC Listed for both Pendent and Recessed Pendent at All IS :P, kcc= 135°F(57°C)only. , �..1_ - L 1_ )_ i (11 „L IL i --1 \ fj 2 27452 DIA. i7223mniJ ' 3cFto2B 2. .4 Model Fl FR QREC Horizontal Sidewall Sprinkler Deflector: EC-9 1 Installation Wrench: Model D Sprinkler Wrench of Model W2 Sprinkler Wrench Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy Installation Data Nominal Sprinkler Nominal Thread K-Factor Sprinkler Approval)') Temperature p , „, ' Orifice Size Length Organizations Rating identification Number , US Metric (SIN) 1 • "(ai' 3/a"NPT 2.85 135°F (57°C) �y (20mm) (R8/4) 8.0 115 (724mm) 1,2,3,4 155°F (68°C) R4862 175°F (79°C) Model F1FR QREC Recessed Horizontal Sidewall Sprinkler Deflector: EC-9 Installation Wrench: Model GFR2 Sprinkler Wrench Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy Model Fl FR QREC Horizontal Sidewall and Recessed Horizontal Sidewall Required Minimum Flow/Pressure Flow Rate Pressure Maximum Approval(') Deflector to Ceiling gpm(Lhnin) I psi(bar) Coverage Area Temperature Organizations Dimension UL FM UL FM WidthxLength Mingo) - Min.-Max ft x ft(m x m) Fl Inches mm 26 (98.4) - 10.6 (0,7) - 16x16 (4.9x4.9) .. ( 05) 135°F (570 C) 4-12 (102-305) 29 (109.8) 32 (121.1) 13.1 (0,9) 116.0 (1.1) , 18x16 (4,9x4.9) 4-12 (102-305) 29 (109.8) 36 (136.3) 13.1 (0,9) 20.2 (1,4) 16x18 (4.9x5.5) 155°F (68°C) 1,2,4 1,2,3,4 4-12 (102-305) 32 (121.1) 40 (151.4) 16.0 (1,1) ' 25.0 (1,7) ', 16x20 (4.9x6.0) 4-12 (102-305) 36 (136.3) 44 (166.6) 20.2 (1,4) 30.2 (2,1) 16x22 (4.9x6.7) 75°F (79°C) 4-12 (102-305) 39 (147.6) 48 (1817) 23.8 (1,6) 36_0 (2,5� 16x24 (4.9x� __..._..: .._...__ 4-12 (102-305) 33(124.9) 17.0(1,2) 18 x 18(5.5 x 5.5) 135°F (57°C) 4- 12(102-305) 39(147.6) 23.8(1,6) 14 x 26(4.3 x 7.9) 135°F (57°C) 4-6(102-153) 40(151.4) 25.0(1,7) 18 x 22(5.5 x 6.7) 135°F (57°C) 4- 12(102-305) 46(174.1) 33.1 (2,25) 14 x 26(4.3 x 7.9) 135°F (57°C) 1,2 1,2 6- 12(153-305) 33(124.9) 17.0(1,2) 18 x 18(5.5 x 5.5)' 155°F (68°C) 4-12(102-305) 40( L ( ) 18x22(5.5x6.7), 155°F (68°C) 4- 12(102-305) 46 FM (17 .1) of recessed sprinkler(�12 5)° 14 x 26(4.3 x 7.9)j 155°F (68°C) 6- 12(153-305) 15t4) 25.0 1,7 ") Approvalp F(57°C)and 155°F(68°C)only. :a Refer to escutcheon data table for dimensions. • ME Or arnvo locv r fir 4'TO If' RAN SPRING COLLAR _ OMR Rd?MOST SPRINKLER wREINGH -1-1 ears. 1 15/Iw' OK 3 21/I$'OK 1 RECOMMENDED 2 ]/4'CCmIET£R 1- Kw.nartxrOU 1 3. Installation Sprinkler Types Quick response sprinkler are intended for installation as Extended Coverage Pendent specified in NFPA 13. Quick response sprinklers and stan- Extended Coverage Sidewall dard response sprinklers should not be intermixed. • EC-9 HSW Deflector The Model Fl FR QREC Recessed Sprinklers are to be in- Recessed Extended Coverage Pendent stalled as shown. The Model El or F2 Escutcheons illus- Recessed Extended Coverage Sidewall trated are the only recessed escutcheons to be used with • EC-9 HSW Deflector the Model F1FR QREC Sprinklers. The use of any other Finishesf'I recessed escutcheon will void all approvals and negate all 'Standard Finishes))) warranties. Sprinkler Escutcheon When installing Model F1FR QREC Sprinklers, use the Bronze Brass Model D Sprinkler Wrench or Model W2 Sprinkler Wrench. Chrome Chrome When installing Model FIER QREC Recessed Pendent or White&Black Polyesterj3m White Recessed Sidewall Sprinklers, use the Model GFR1 Sprin- Special Application Finishes kler Wrench. Any other type of wrench may damage these Sprinkler(2) Escutcheon Electroless Nickel PTFE13i Electroless Nickel PTFE sprinklers. Bright Brass Bright Brass Glass bulb sprinklers have orange bulb protectors to Black Plating Black Plating minimize bulb damage during shipping, handling and in- Black Paint Black Paint stallation. REMOVE THIS PROTECTION AT THE TIME THE Off White Satin Off White SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE Chrome Chrome Dull PROTECTION. Removal of the protectors before this time ("Other colors and finishes are available on special order. Consult mayleave the bulb vulnerable to damage. RASCO wrench- factory for details. FM Approval limited to bronze,bright and satin chrome plated, es are designed to install sprinklers when covers are in and polyester coated only. place. REMOVE PROTECTORS BY UNDOING THE CLASP e cULus Listed Corrosion Resistant Sprinkler BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- TECTORS. Escutcheon Data - Maintenance Escutcheon "A" Face of Fitting Model Adjustment Dimension to Ceiling or The Models F1FR QREC and F1FR QREC Recessed Sprin- Wall Dimension klers should be inspected and the sprinkler system main- Fi ; (19mm) 33'°(19mm)(1� (s'(5mm)- tained in accordance with NFPA 25. Do not clean sprinklers 1/'(35mm) he'(24mm any other cleaning F2 /2. (13mm) 11" ((Omm("� Vic,"(5mm)- with soap and water, ammonia or other fluids. 1 Remove dust by gentle vacuuming. Replace any sprin- r,8 (18mmlJ kler which has been painted (other than factory applied) or :"ECEC Pendent damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or op- Ordering Information erated sprinklers. Prior to installation, sprinklers should be Specify: maintained in the original cartons and packaging until used 1. Sprinkler Model: El FR QREC to minimize the potential for damage to sprinklers that would 2. Sprinkler Type cause improper operation or non-operation. 3. Temperature Rating 4. Sprinkler Finish Temperature Ratings 5. Thread Type: [3/4"NPT] [ISO 7-1 R3/a] Sprinkler Maximum Bulb 6. Escutcheon Type Classification ! RatingAmbient Tern 7. Escutcheon Finish (where applicable) 'F 7 'C of ,C Color y— Ordinary 135 57 100 38 Orange Note: When Model F1 FR Recessed sprinklers are or- Ordinary 155 68 100 38 Red dered,the sprinklers and escutcheons are pack- Intermediate 175 79 150- 66 Yellow aged separately. Maximum Working Pressure 175 psi (12 bar) SIN R4842&R4862 cULus listed for 250 psi (17 bar) 100%Factory tested hydrostatically to 500 psi (34.5 bar) The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. Recycled ® ( Sales Offices Paper II e''ab le (800)80D)431-15 848-6051 8 8-2042 Sales Fax Revision lines indicate updated or new data. (914)829 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.03/17 P/N 9999970142 • Bulletin 014 Rev. E co Reliable® Model Fl FR56 Series k able Quick Response o Standard Spray 3 m Model F1FR56 Sprinkler Types Standard Upright r'- .'" Standard Pendent' Conventional Vertical Sidewall ,, 4' In Horizontal Sidewall k Model Fl FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Upright Pendent Horizontal Sidewall Model F1FR56 Concealed Sprinkler Types Standard Pendent Oki Listing & Approvals 1. Underwriters Laboratories Inc. and Certified for 1 '* Canada(cULus). 2. Factory Mutual Approvals (FM) Vertical Sidewall Conventional 3. Loss Prevention Council (LPCB, UK) 4. VdS Schadenverhutung GmbH s, UL Listing Category - -- Sprinklers,Automatic&Open(VNIV) = Quick Response Sprinkler ` Product Description Reliable Models F1FR56 Series Sprinklers are quick re- " sponse sprinklers which combine the durability of a stan- Horizontal Sidewall Recessed dard sprinkler with the attractive low profile of a decorative Pendent/F1/F2 sprinkler. The Models F1FR56 Series Recessed automatic sprin- ,, klers utilize a 3.0 mm frangible glass bulb. These sprin- �, a � klers have demonstrated response times in laboratory tests / , i,T which are five to ten times faster than standard response . �. sprinklers. This quick response enables the Model F1FR56 w. 7. Series sprinklers to apply water to a fire much faster than N standard sprinklers of the same temperature rating. . The glass bulb consists of an accurately controlled amount Recessed Recessed of special fluid hermetically sealed inside a precisely menu Horizontal dewall Pendent/FP factured glass capsule. This glass bulb is specially con- structed to provide fast thermal response. At normal temperatures, the glass bulb contains the fluid Application in both the liquid and vapor phases. The vapor phase can Quick response sprinklers are used in fixed fire protec- be seen as a small bubble. As heat is applied, the liquid tion systems:Wet, Dry, Deluge or Preaction. Care must be expands,forcing the bubble smaller and smaller as the liq- exercised that the orifice size, temperature rating, deflec- uid pressure increases. Continued heating forces the liquid tor style and sprinkler type are in accordance with the lat- to push out against the bulb, causing the glass to shatter, est published standards of the National Fire Protection As- sociation or the approving Authority Having Jurisdiction. ute the discharging water. Quick response sprinklers are intended for installation as specified in NFPA 13.Quick response sprinklers and stan- dard response sprinklers should not be intermixed. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model Fl FR56 Quick Response Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Sprinkler Identification Number Nominal Thread Nominal K Factor Sprinkler Approval (SIN) Orifice Size Height Organization US Metric Upright Pendent Standard-Upright(SSU)and pendent Deflectors Marked to Indicate Position Yz"(15mm) � 1/2"NPT(RY2) 5.6 I 80 1 2.25" (57mm) 1 1,2 3,4 RA14251') 1 RA14141rn21 Conventional-Install in Upright or Pendent Position 15mm11 /"NPT(RY2) 5.6 80 57mm I 3,4 RA1475 0)cULus listed corrosion resistant(Polyester coated)sprinkler. `2)Polyester coated FM approved sprinkler. Upright Pendent Conventional Model Fl FR56 Quick Response Recessed Pendent Sprinkler Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Thread K Factor Sprinkler Sprinkler Identification Number Orifice Size US Metric Height (SIN) Yz'(15mm) 1/2"NPT(R1/2) 5.6 80 -J 2,25"(57mm) RA1414 Refer to escutcheon data table for approvals and dimensions. .'.—2 5/8"DIP. CEILING "'--- HOLE IN CEILING - : —2.5/16"DIA. [58.7mm] CUP L __x__==4 I 1"X 1/2"REDUCER I ,A, I t `, s I i f f CEILING � 4 - �l I FACE OF FITTING -/� f i CIll4 moo TO FACE OF CEILING r : h `\ III '' roN(I) .,- �✓ m ��: :9� n) .,, ___... ____. --f_. ADJUSTMENT ill • ]N1. .........�.... (1)REFER TO FP ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS. Model F1FR56/F1 or F2 Model F1FR56/FP 2. Model F1 FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: Nominal Nominal K Factor Sprinkler Approval Sprinkler Orifice Thread Size Height Organizations Identification US Metric gNumbers(SIN) 1"(15mm) V2"NPT(R1/2) 5.6 8.0 2.25' (57mm) 1 1 3,4 RA1485 15mm 1/2"NPT(R1/2) 5.6 8,0 2.25" (57mm) 401 0"LPC Approval is for pendent position only. Sprinkler Type Deflector to Ceiling Distance " (Min. -Max.) .10 Upright 4 (102r m) 12"(305mm) Pendent 4"(102mm)- 12"(305mm) Vertical Sidewall Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler Deflector: HSW Installation Wrench:Model D Sprinkler Wrench Installation Data: Horizontal Sidewall Nominal K Factor Sprinkler Approval Organizations Height and Type of Approval Sprinkler Nominal Orifice Thread Size Identification US Metric Light Hazard Ordinary Numbers(SIN) 1 Hazard I 1/2' (15mm) 1/2"NPT(R1/2) 5 6__._..._ 80 2.63"(67mm) 1,2 l 1 RA1435 A. FACE FACE OF FITTING(I) TO FACE OF CEILING DIMENSION 1 1/4"MIN 2 1/4" HOLE DIA. [31.8mm] [57.2mm] [1,/.2mm8"] (101.6m [3LING 5 T 4mmJ CEILING TO ?"X 1/2"REDUCER DEFLECTOR s. 1 1 _If lifl I 15/16" GW.1 I°II [49.2mm] 1en7- - ---� 2 27/32" OL4. i Lmil J [72.2mm] Horizontal Sidewall TURN COLLAR UNTIL l TIGHT AGAINST SPRINKLER L WRENCH BOSS. '—ADJUSTMENT 013FG03 (1) REFER TO ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS. Note: For Recessed HSW Sprinklers use installation wrench GFR2. 3. Model Fl FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: "K"Factor Temp.Rating Max. Bulb Sprinkler Nominal Thread Orifice Size Model Ambient Color Approvals Identification US Metric Sprinkler Cover Temp �Number(SIN) I 1/2"(15mm) 5.6 80 1/2" NPT F1FR 135'F/57°C 135°F/57°C 100°F/38°C Orange 1,2 RA1414 1/2"(15mm) 5.6 80 1" NPT F1FR 155°F/68°C ' 135°F/57°C 100 F/38 C Red 1, 2,4'" RA1414 1/2"(15mm) 5.6 80 /2" NPT F1FR 175°F/79°C 165°F/74°C 100 F/38°C Yellow 1,2 RA1414 /2"(15mm) 5.6 80 1/2"NPT F1FR 200°F/93°C 165'F/74°C 1 100°F/38°C Green 1,2 RA1414 ri)For VdS only= 155°F!68°C Norbulb and 1/2"[12,7mm]adjustment. I — /� is �� -:i .i . — yr ,� r _ "'_ C�5tl4 1 1 .. � 1 r x t r d ,/ / / 1 1/2" ADJUSTMENT .—. 5/16" AUJUSIMENTTTT . �. Figure 1 Figure 2 Installation Aid A protective cap is included for use during installation. Sprinkler with a threaded Model CCP cup which is fac- Important:The F1FR56 Sprinkler with Model CCP cover tory attached to the sprinkler. The assembly is complet- plate is not an FM Approved combination. ed by the installation of the attractive, low profile, 135°F Installation (57°C) or 165°F (74°C) rated Model CCP push on cover Quick response sprinklers are intended for installation plate assembly. The cover plate and sprinkler cup as- as specified in NFPA 13. Quick response sprinklers and semblies are joined using a cover plate skirt with flexible standard response sprinklers should not be intermixed. tabs for threaded engagement. A choice of two cover The Model F1FR56 Recessed Quick Response Sprin- plate assemblies provide either '/2" (13mm)or She" (8mm) klers are to be installed as shown.The Model F1 or F2 Es- of cover adjustment. cutcheons illustrated are the only recessed escutcheons Do not install these sprinklers in ceiling which have to be used with the Model F1FR56 Sprinklers. The use positive pressure in the space above. of any other recessed escutcheon will void all approvals After a 25/e" (67mm) diameter hole is cut in the ceil- and negate all warranties. ing, the sprinkler is easily installed with the Model RC1 When installing Model F1FR56 Sprinklers, use the Mod- Wrench. A Teflon* based thread sealant should be el D Sprinkler Wrench. Use the Model GFR2 Wrench for applied to the sprinkler threads only. The Model RC1 installing F1FR56 Recessed Pendent Sprinklers. Any Wrench is then used to engage the sprinkler wrenching other type of wrench may damage these sprinklers. surfaces and to install the sprinkler in the fitting. When NOTE: A leak tight 1/2" NPT (R1/2) sprinkler joint can inserting or removing the wrench from the sprinkler/cup be obtained with a torque of 8-18 ft-lbs(10,8-24,4 N-m). assembly, care should be taken to prevent damage to Do not tighten sprinklers over maximum recommended the sprinkler. DO NOT WRENCH ON ANY OTHER PART torque. It may cause leakage or impairment of the sprin- OF THE SPRINKLER. The cover plate is then pushed klers. onto the cup. Final adjustment is made by hand turning The Model F1FR56/CCP Concealed Sprinkler uses the the cover plate until the skirt flange makes full contact 1/2" orifice, 1/2" NPT (R1/2), 135°F (57°C), 155°F (68°C) with the ceiling. Cover plate removal requires turning in 175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent the counter clockwise direction. "DuPont Registered Trade Mark 4. After installation, inspect all sprinklers to ensure that Sprinkler Types there is a gap between the cover plate and ceiling and Standard Upright that the four cup slots are open and free from any air flow Standard Pendent impediment to the space above. Conventional Concealed cover plate/cup assemblies are listed only Recessed Pendent . for use with specific sprinklers. The use of any other con- Vertical Sidewall cealed cover plate/cup assembly with the Model F1FR56 Horizontal Sidewall Pendent Sprinkler or the use of the Model CCP Concealed Recessed Horizontal sidewall cover plate assembly on any sprinkler with which it is not Concealed pendent specifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Maximum Working Pressure Glass bulb sprinklers have orange bulb protectors to 175 psi (12 bar) minimize bulb damage during shipping, handling and 100% Factory tested hydrostatically to 500 psi (34.5 bar) installation. REMOVE THIS PROTECTION AT THE TIME Finishes (1) THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION.Removal of the protectors before this Standard Finishes time may leave the bulb vulnerable to damage. RASCO Sprinkler Escutcheon __. Coverplate Bronze Brass wrenches are designed to install sprinklers when covers Chrome Plated Chrome Chrome are in place. REMOVE PROTECTORS BY UNDOING THE , White Polyester Plated , White CLASP BY HAND. DO NOT USE TOOLS TO REMOVE _Coated nnsr White Painted Special Application Finishes THE PROTECTORS. p Sprinkler HT- 1 Escutcheon Cover plate..._.... Temperature Ratings Bright Brass r31 Bright Brass Bright Brass Sprinkler Black Plated Black Plated Satin Max.Ambient Black Paint Black Paint Off White Classification 1 Temperature 1 Bulb Color Off White ' Off White Black Paint °C of---, Temp. Satin Chrome Satin Chrome Black Plated Ordinary 57 135 100°F(38°C) I Orange a Ordinary 68 155 100°F(38°C) Red Consther lithe and colors are available on special order. Consult the factory for details. Intermediate 79 175 150°F(66'C) Yellow ''; cULus Listed only. Intermediate 93 200 150°F(66°C) Green 13 200°F(93°C)maximum. Hi h(" 141 286 225'F(107°C) Blue.._._ (4) cULus listed"corrosion resistance'applies to SIN Numbers 0:Not available for recessed sprinklers. RA1425(Upright)and RA1414(Pendent)in standard black or white. 0') FM Approvals finish as"Polyester coated"applies to SIN Number Escutcheon Data t') RA1414(Pendent)in standard black or white. • • Face of Fitting to EscutcheonModel Approvals' Adjustment CeilingorWall Ordering Information Dknension Dimension __.. Specify: Fi 1 3 4 Max RPr.°s 11/2"(38.1mm) i 31,e"-'s/he" 1. Sprinkler Model Min Recess '(4"(19.1mm)_ (5mn-24nrn) 2. Sprinkler Type Max Recess 1'/i'(38.1mn) 3/1 -''/+a'. F2 1,2,3,4 ' MinRPc 1`(25mm) (5inr17nnn)_ 3. Orifice Size FPPush-on/ 1 Max Recessed{ 7/1"(11mm) 1!5" (38.1mm) 1 4. Deflector Type , Thread-off 1'4 j Min Recessed h5/,5(24mm) 1"(25.4mm) 5. Temperature Rating '151N:RA1435-cULus and FM permits use with FlorF2 escutcheons for light 6. Sprinkler Finish hazard only 7. Escutcheon Type 8. Escutcheon Finish (where applicable) Maintenance 9. Cover plate Model The Models F1FR56 and F1FR56 Recessed Sprinklers 10. Cover plate Thread size should be inspected quarterly and the sprinkler system 11. Cover plate Temperature maintained in accordance with NFPA 25. Do not clean 12. Cover plate Adjustment sprinklers with soap and water, ammonia or any other 13. Cover plate Finish cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has Note:When Model F1FR56 Recessed sprinklers are ordered,the sprin- been painted (other than factory applied) or damaged klers and escutcheons are packaged separately. in any way. A stock of spare sprinklers should be main- tained to allow quick replacement of damaged or oper- ated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging to mini- mize the potential for damage to sprinklers that would cause improper operation or non-operation. 5. s Bulletin 136 January 2019 Model F1 FR LO CO ®Reliable K8.0 (115metric) Quick Response Sprinklers N 0 Model Fl FR LO Sprinkler Types Standard Spray Upright Standard Spray Pendent Conventional all, Model Fl FR LO Recessed Sprinkler Types Recessed Standard Spray Pendent For Model F1FR1/2" K 5.6 (80), 4.2 (60) &2.8 (40) Sprin- Upright Pendent kler Types refer to Bulletin 014 for technical specifica- tions and approvals. Listings &Approvals 1. Listed by Underwriters Laboratories, Inc. (UL) , 2. Listed by Underwriters'Laboratories of Canada(ULC) 3. Factory Mutual Approvals (FM) 4. Loss Prevention Council (LPCB, UK) • 5. Verband der Schadenversicherer Gmbh 6. EC Certificate: 1438-CPD-0049 (R3612) Conventional Recessed Pendent 1438-CPD-0048 (R3622) (Model FP Shown) 1438-CPD-0047 (R3672) to push out against the bulb, causing the glass to shatter, UL Listing Category opening the waterway and allowing the deflector to distrib- Sprinklers, Automatic& Open ute the discharging water. Quick Response Sprinkler The temperature rating of the sprinkler is identified by the ULGuide Number color of the glass bulb. VNIV Application Product Description Quick response sprinklers are used in fixed fire protec- Reliable Models F1FR LO and HER LO Recessed Sprin- tion systems: Wet, Dry, Deluge or Preaction. Care must be klers are quick response sprinklers which combine the du exercised that the orifice size,temperature rating, deflector rability of a standard sprinkler with the attractive low profile style and sprinkler type are in accordance with the latest of a decorative sprinkler. published standards of the National Fire Protection Asso- The Models El FR LO and F1FR LO Recessed automatic ciation or the approving Authority Having Jurisdiction.Quick sprinklers utilize a 3.0 mm frangible glass bulb.These Sprin response sprinklers are intended for installation as specified iklers have demonstrated response times in laboratory tests n erN apPA 1 s FM Global Loss Prevention Data Sheet 2-0 or which are five to ten times faster than standard response other applicable standards. Quick response sprinklers and sprinklers.This quick response enables the Model F1FR LO standard response sprinklers should not be intermixed. and F1FR LO Recessed sprinklers to apply water to a fire Installation much faster than standard sprinklers of the same tempera- The Model F1FR LO Recessed Quick Response Sprin- ture rating. klers are to be installed as shown. The Model F1 or F2 Es- The glass bulb consists of an accurately controlled amount cutcheons illustrated are the only recessed escutcheons to of special fluid hermetically sealed inside a precisely man- be used with the Model F1FR LO Sprinklers. The use of ufactured glass capsule. This glass bulb is specially con- any other recessed escutcheon will void all approvals and structed to provide fast thermal response. The balance of negate all warranties. parts are made of brass,copper and beryllium nickel. When installing Model F1FR LO Sprinklers, use the Model At normal temperatures, the glass bulb contains the fluid D Sprinkler Wrench or Model W2 Sprinkler Wrench. When in both the liquid and vapor phases. The vapor phase can installing Model F1FR LO Recessed Pendent or Sidewall be seen as a small bubble. As heat is applied, the liquid Sprinklers, use the Model GFR2 Sprinkler Wrench. Any expands,forcing the bubble smaller and smaller as the liq- other type of wrench may damage these sprinklers. uid pressure increases. Continued heating forces the liquid Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 DEFLECTOR LOAD SCREW BULB WASHER CUP FRAME or„. 1E8FG02 Technical data: Deflector Nominal Thread Max. Min. Temperature Models Response Finish Orientation K-Factor Size Working Working Rating Pressure Pressure Upright 3/4" NPT See See F1FR LO Quick Pendent K 8.0 or 175 psi m 7 psi "Temperature "Finish Response Conventional (115 metric) IS07-1 R3/4 Ratings"Table Table" Material Data: Frame Deflector Load Screw Cup Washer Bulb DZR Brass CDA Alloy 210,220,314,316,360 CDA Alloy 314 Nickel Alloy 440 or Alloy 360 QM Brass CDA Alloy 510 or or coated with PTFE Adhesive Tape Glass GDA Alloy 544 CDA Alloy 353 See"Installation Data"tables for additional information on each sprinkler model. Model F1FR LO Pendent, Recessed Pendent, and Upright sprinklers (SIN R3612 and R3622) are cULus Listed for 250 psi (17 bar). 2. Model Fl FR LO Quick Response Upright, Pendent &Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench or Model W2 Sprinkler Wrench Installation Data: Nominal Sprinkler Sprinkler Type K-Factor Sprinkler Approval Identification Height Organization Numbers(SIN) US Metric SSU SSP Standard-Upright(SSU)and pendent(SSP)Deflectors Marked to Indicate Position 17/32"(20mm)Large Orifice with 3/4"NPT(R3/4)Thread 8.0 115 I 2.3" (58mm) I 1,2,3,4,5,6 I R3622(1)(3)(3) I R3612(3)(3) Conventional-Install in Upright or Pendent Position 20mm Large Orifice with 3/4"NPT(R3/4)Thread 8.0 I 115 58mm 4 I R3672 ())Polyester coated upright UL and ULC listed corrosion resistant R3622. (3)FM Approved for polyester coated sprinkler.R3622,R3612. (3)Electroless Nickel PTFE Plated-FM Approved/cULus Listed Corrosion Resistant .. Upright Pendent Conventional Model Fl FR LO Quick Response Recessed Pendent Sprinklerf'I Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Approvals') Sprinkler Nominal Orifice Thread Size"T" K-Factor Sprinkler Organization Identification US Metric Height Fl F2 FP Numbers(SIN) 17/32"(20mm) 3/4" NPT(R3/4) 8.0 115 2.3"(58mm) 1,2 1,2,3 1,2 R36122m (')Refer to escutcheon data table for dimensions. j2)Electroless Nickel PTFE Plated-FM Approved/cULus Listed Corrosion Resistant '/-M - ,_h---z 1- _, —r r .=4 I ' OLE u.[FILM 1 r �- i r 0 Cr9,9 h'bh 1. I RtcE- / ' . OO}tle -- ro 9co 09 a C v mm / 9m r err (n, arm_s= n m(3m„ '� l rL55 J/e 5-m 92 rscurc+For+ ram( :1 I 03 tl8 ` JI ;t' c ✓ n /,( mmJ yu0Rm' 1 � I , � / nwMUM*ECM 9/e[a.om,,,\ / I /F6lOnO£5 b 3m L \ �UAVIAUM REnES 115 r nr uxucuunxmnn -:— n- xE__ss=L3/27 a.,,.,j l t'22,9'9d RECESSED PENDENT W/FP ESCUTCHEON ,,,e,,,c .Hr4SL e NO]ne 35Cea✓Co WISH(F ESaJTc5EW' RECESSED PENDENT W/F1 OR F2 ESCUTCHEON __ ..nnx,ra wn FM 9555rvro m.v EScnm„m, 3. Finisheso)(2) Note:A leak tight 1/2" NPT(R1/2) sprinkler joint can be ob- Standard Finishes tained with a torque of 8 - 18 ft-lbs (11 - 24 N-m). Do not Sprinkler Escutcheon tighten sprinklers over maximum recommended torque. It Bronze Brass may cause leakage or impairment of the sprinklers. Chrome Plated Chrome Plated°' White Polyester CoatedI4)ts> White Painted° Glass bulb sprinklers have orange bulb protectors to Special Application Finishes minimize bulb damage during shipping, handling and in- Sprinkler Escutcheon stallation. REMOVE THIS PROTECTION AT THE TIME THE Electroless Nickel PTFEIN Electroless Nickel PTFE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE Bright Brass Bright Brass PROTECTION. Removal of the protectors before this time Black Plated Black Plated mayleave the bulb vulnerable to damage. RASCO wrench- Black Pain's Black Paint g Off White�sl Off White es are designed to install sprinklers when covers are in Satin Chrome Chrome Dull place. REMOVE PROTECTORS BY UNDOING THE CLASP III Other finishes and colors are available on special order. BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- Consult the factory for details. TECTORS. (2) FM Approvals is limited to bronze and brass,chrome or black plated finishes only. Temperature Ratings (3) FP Push-onfThread-off escutcheon. (4) cULus listed corrosion resistance. Maximum SIN R3622. Sprinkler Ambient Bulb "I FM Approved for SIN R3622,R3612 Classification Temperature IBI cULus listed corrosion resistant SIN R3622&R3612 Temperature Color °F °C °F °C Note: For 1/2"orifice pendent FM approved white polyester coated, Ordinary 135 57 100 38 Orange cULus listed white and black polyester and Electroless Nickel Ordinary 155 68 100 38 Red PTFE Plated corrosion resistant sprinklers refer to bulletin 014. Intermediate 175 79 150 66 Yellow Intermediate 200 93 150 66 Green Maximum Working Pressure Highm 286 141 225 107 Blue 175 psi(12 bar) III Not Available for recessed sprinklers. SIN R3612&R3622 cULus listed for 250 psi (17 bar) 100%Factory tested hydrostatically to 500 psi (34.5 bar) Maintenance The Models F1FR LO and F1FR LO Recessed Sprinklers Ordering Information should be inspected and the sprinkler system maintained in Specify: accordance with NFPA 25. Do not clean sprinklers with soap 1. Sprinkler Model and water, ammonia or any other cleaning fluids. Remove 2 Sprinkler Type dust by using a soft brush or gentle vacuuming. Replace 3. Orifice Size any sprinkler which has been painted(other than factory ap 4. Deflector Type plied) or damaged in any way. A stock of spare sprinklers 5. Temperature Rating should be maintained to allow quick replacement of dam- 6. Sprinkler Finish aged or operated sprinklers. Prior to installation, sprinklers 7 Escutcheon Type should be maintained in the original cartons and packaging 8 Escutcheon Finish (where applicable) until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Note: When Model F1FR LO Recessed sprinklers are ordered, the Sprinkler Types sprinklers and escutcheons are packaged separately. Standard Upright Standard Pendent Conventional Recessed Pendent The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years. Manufactured by Reliable Automatic Sprinkler Co.,Inc. • Recycled ) Sales Offices M Paper Reliable (80(8000 4 )848-6051 31-158 8 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.rellablesprinkler.com Internet Address so.Printed In U.S.A.01/19 P/N 9999970027