CARRIER' ; AMERICAN HEf, k STANDARDS 3120.01
Pwind(lateral)= 52.74 psf
Pwind(vert)= 41.64 psf
Fp= 0.425'Welght
UNIT SIZE MAX.WEIGHT MIN.WEIGHT LENGTH WIDTH HEIGHT 0.6(WIND) NET VERTICAL 0.7(SEIS)
(LB) (LB) (IN) (IN) (IN) LATERAL 0.6(W)+0.6(D) LATERAL
(LB) (LB) (LB)
2.0 TON 340 330 _ 48.1875 32.625 42.125 446 _ -75 101
2.5 TON 348 342 48.1875 _ 32.625 44.125 467 -68 104
3.0 TON ^_ 432 376 48.25 44.1875 46.125 489 -145 129
3.5 TON 477 463 48.25 44.1875 48.75 517 -93 142
4.0 TON 495 452 74.375 46.75 33.375 545 -310 147
5.0 TON 580 506 74.375 46.75 41.375 676 -300 173
6.0 TON 610 597 74.375 46.75 41.375 676 -246 181
10 TON 1050 1050 88.125 - 59.5 49.375 956 -280 312
-
12.5 TON 1370 1370 115.875 63.375 57.375 1,461 -398 408
14 TON 1775 1775 127.875 86.375 49.375 1,387 -852 528
15 TON 1824 1907 127.875 86.375 48.25 1,356 -822 543
17 TON 2100 2100 141.5 86.375 49.375 1,535 -1,200 625
17.5 TON 2102 1839 141.5 86.375 48.25 1,500 -1018 625
20 TON 2247 _ 2072 141.5 86.375 48.25 1,500 -878 668
25 TON 2292 2118 157.75 86.375 57.375 1,989 -2118 682
27.5 TON 2640 2640 157.75 _ 86.375 57.375 1,989 -781 785
UNIT TOTAL
OT MOMENT' RES.MOMENT LATERAL Fup OT MOMENT RES.MOMENT LATERAL Fup
UNIT SIZE 1.0(W) 1.0(D) 0.6(WIND) 0.6(W)-0.6(D) 1.0(W) 1.0(W)t0.9(D) 1.0(WIND) 1.0(W)-0.9(D)
(LB-FT) (LB-FT) - (LB) (LB) (L8-FT) (LB-FT) (LB) (LS)
2TON 1,306 449 447 355 2,317 449 595 601
2.5 TON 1,432 465 468 382 2,485 465 616 638
3.OTON 1,567 693 490 347 2,662 693 638 538
3.5 TON 1,751 853 517 - 352 2,900 853 667 553
4.0 TON 1,265 955 546 363 2,548 955 775 574
5.0 TON 2,208 932 581 420 3,481 932 730 642
6.0 TON 1,944 1,163 677 443 3,481 1,163 906 696
10 TON 3.279 2,604 957 558 5,402 2,604 1,228 829
12.5 TON 5,822 _ 3,859 1,462 882 9,010 3,859 1,818 1,256
14 TON 4,758 6,389 1,388 837 7,839 6,389 1,782 1,103
-
15 TON 4,544 6,565 1,356 804 7,563 6,565 1,750 1,065
-
17 TON 5,265 5,525 1,536 1,055 8,674 5,525 1,971 1,349
17.5 TON 5,028 6,619 1,501 943 8,369 6,619 1,936 1,232
20 TON 5.028 7,457 1,501 873 8,369 7,458 1,936 1,162
25 TON 7,926 7,623 1,990 1,232 12,265 7,623 2,475 1,606
-
27.5 TON 7,926 9,502 1,990 1,075 12,265 9,502 2,475 1,450
1 OF 1 1.-\.
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-CARRIER 2 TON UNIT
Wp:= 3301b Weight of unit W,:= 100lb Weight of(E)curb
Wt:= Wp+ We Wt=430 lb
L:= 48.1875in Length of unit L,:= 48in Length of Curb
wm:= 32.625in Width of unit we:= 29.625in Width of curb/curb adapter
hm:= 42.125•in Height of unit
he:= 14•in Height of curb
hmc:= hm + he hmc= 56.13 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
SDS:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVERAREA
h := I Oft 1p:= 1.0 ay:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4•a •SDS•I zl
FPunit Rp p l + 2• I•Wp F 140.25lb 0.7•F 98.17 lb
J Pu»it= Punit =
0.4-ap SDS•Ip \
. Fp:= R I + 2•Z/
h I•NW( Fp = 182.75 lb 0.7•Fp= 127.92 lb
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KZt:= 1.0 GC,:= 1.9 GCr vert= 1.5
qz:= 0.00256.Kh•KZi 1(d-V3,2-psf
F:= GC,qZ F=52.74 psf
Pwind_unit F•L•hm Pwind unit =743.52 lb
Pwind F•L•hme Pwind = 990.62 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert ci GC,_vert Fvert=41.64 psf
Pwind unit vert Fvert'L'wm Pwind unit vert =454.61 lb
Pven_ASD 0.6Wp—0.6Pwind_unit_vert Pvert_ASD = —74.77 lb
Pvert_LRFD 0.9Wp— I.OPwihd_unit yen Pvert_LRFD=—157.61 lb
E:\adcadd119100000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\CARRIER\WOOD1lateraIMECH RTU
Ga3
CIDA RTU RNH ,
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB •
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
Mot_wind unit Pwind_unit'tt2 Mot_seismic_unit FPunit'I 2m�
Mot wind unit= 1305.02 lb ft Mot seismic unit =246.17 lb ft
(0.7•Mot_seismicunit) (0.6—0.7.0.2•SDs).Wp
(0.6Mot_wind unit) Pvert_ASD Fup_seismic_unit +
Fup_wind_unit '- we 2
we 2
Fup_seismic_unit = 149.I6Ib
Fup_wind_unit =354.55 lb
0.7.FPunit =98.17 lb
0.6•Pwind unit =446.11 lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 447 sliding and 3551b tension at unit to curb connection—18GAcurb
0.6• =446.11 lb F =354.55 lb
Pwind,unit up_wind_unit SCREW 4
Try 18GAx 6"clip with(4)#10 screws per clip
VCLIP:= 401 Ib 0.6Pwind unit =446.11 lb VCLIP= 401 lb
0.6Pwind_unit
USHEAR USHEAR=0.556
2•VCLIP
Fup_wind_unit
UUPLIFT VCLIP VUPLIFT 0.88
I'
Use(1)clip per side—(4)total
E:\adcadd\19100000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\CARRIER\WOOD\IateraIMECH RTU
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670 ,
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
_ WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc\ hmc
Mot_wind_total wind 2 ' Mot seismic_total FP' 2
Mot_wind_total =2316.6 lb ft Mot seismic total =427.37 lb ft
0.6Mot_wind_total Pven ASD 0.7•Mot_seismic total (0.6—0.7.0.2•SDS)'Wt
Fup_wind_total — Fup_sesmic_total :- —
we 2 we 2
F 600.41 lb
Fup_seismic_total 17.76lb
up wind total =
0.6•Pwind = 594.371b 0.7Fp = 127.92 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 5951b sliding and 601 b uplift at curb to roof connection
0.6•Pwind= 594.37 lb Fup_wind_total =600.41 lb
Try#12x3"WOOD SCREWS EACH SIDE—Long side to take tenson, shortsiies to take shear
'screw:= 3in length of screw
LP 'screw - 8 i
= n Lp =2.38 in
screw length-Sheathing-tapered tip d 2 thread length
thread 'screw 3
dscrew 0.216in Screw diameter
LP Nthread 154.lb withdrawal capacity per inch
Cr,p:= Cp= I.1 in
10•dscrew
Cp:= if(Cp > 1.0,1.0,Cp) Cp= 1
Vallow I.6.I561b•Cp Vallow=249.6 lb
Tallow:= I.6•dthread'Wthrcad Tallow=492.8 lb
0.6•Pwind
USHEAR:= USHEAR= 0.595
4"Vallow
Fup_wind_total
UUPLIFT UUPLIFT=0.61
2'Tallow
Use(2)#12x3"screws per side—(8)screws total
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
1CARRIER\WOOD\lateraIMECH RTU
(,Gt5
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-CARRIER 5 TON UNIT
Wp:= 5061b Weight of unit W,:= 1001b Weight of(E)curb
Wt:= Wp+ W, Wt=606 lb
L:= 48.25in Length of unit L,:= 48in Length of Curb
wm := 44.1875in Width of unit we:= 41.1875 in Width of curb/curb adapter
hm:= 54.75-in Height of unit
he:= 14•in Height of curb
hme:= hm + h, hmc=68.75 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
Sps:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVERAREA
h:= 10ft 1p:= 1.0 ap:= 2.5 Rp:= 6 z:= h Air side HVAC component
0.4•ap•SDs'Ip z'
FPunit= I + 2•—z •W F 215.05lb 0.7•F
Rp h� p Punit = Punit = 150.53lb
0.4•a •Sps•I z
Fp:= p p• I + 2•— •Wt Fp=257.55 lb 0.7.Fp = 180.28 lb
Rp h
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
V3s:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kzt:= 1.0 GCr:= 1.9 GCr vert= 1.5
qZ:= 0.00256•Kh•Kri Kd•V3,2•psf
F:= GCS qz F=52.74 psf
Pwind unit= F•L•hm Pwind unit =967.6 lb
Pwind F•L hmc Pwind = 1215.03 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert qz GCr vert Fven = 41.64 psf
Pwind unit vert Fvert•1-•wm Pwind unit vert =616.52 lb
Pvert_ASD 0.6Wp-0•--wind unit_vert Pvert ASD =-66.31 lb
Pvert LRFD:= O.9Wp- 1.0Pwind_untt vert FvertLRFD 16I.12 lb
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\StructuralRTU
\CARRIER\WOOD\lateratMECH RTU
CIDA RTU RNCIA
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overtuminq at unit to curb SEISMIC-Overturning at unit to curb
hm (hm�
Mot_wind unit Pwind_unit'2 Mot_seismic unit FPunit' 2
Mat_wind_unit = 2207.34lbft Mot seismic unit =490.58 lb ft
(0.7•Mot_seismic_unit) (0.6—0.7.0.2•SDS)'Wp
(0.6Mot_wind unit Pvert ASD Fup_seismic_unit +
Fup_wind_unit _ � We 2
We 2
Fup seismic unit = 221.75 lb
Fup wind_unit =419.02 lb
0.7•Fpunit = 150.53 lb
0.6•Pwind unit = 580.56 lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 581 sliding and 420b tension at unit to curb connection—18GAcurb
0.6•Pwind_unit = 580.56 lb Fup_wind_unit =419.02 lb SCREW 4
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP 401Ib 0.6Pwind unit =580.56 lb
0.6Pivind unit
USHEAR USHEAR=0.362
4•VCLIP
Fup_wind_unit
UUPL1Fr UUPLIFT=0.52
2•VCLIP
Use(2)clip per side—(8)total
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\CARRIER\WOOD\IateraIMECH RTU
a7
CIDA RTU RNH ,
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF -
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc� hmc
Mot_wind_total Pwind' 2 Mot_seismic_totat FP'2
nd_total =3480.5lbft
Mot_wi Mot seismic_totat =737.77 lb ft
(0.6Mot_wind_total) Pvert_ASD 0.7.Mot_seismic_total (0.6-0.7.0.2•SDS)'Wt
Fup_wind_total w — 2 Fup seismic_total w 2
c c
Fup wind_total =641.59lb
Fup_seismic_total =4.72 lb
0.6•Pwind=729.02 lb 0.7Fp= 180.28 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 7301b sliding and 642b uplift at curb to roof connection
0.6•Pwind= 729.02 lb Fup wind total =64 L59lb
Try#12x3"WOOD SCREWS EACH SIDE—Long side to take ension, shortsides to take shear
lscrew:= 3 in length of screw
LP !screw - 8 in Lp =2.38 in
screw length-Sheathing-tapered tip 2
dthread lscrew'3 thread length
dscrew 0.216in Screw diameter
LP Wthread 154•Ib withdrawal capacity per inch
Cp:= Cp= 1.1 in
10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallo%v 1.6.1561b•Cp Vatlow=249.6 lb
Tallow= 1.6'dthread'Wthread Tallow=492.8 lb
0.6•Pwind
USHEAR USHEAR=0.487
6•Vallow
Fup_wind_total
UUPLIFT UUPLIFT=0.43
3.I allow
Use(3)#12x3"screws per side—(12)screws total
E:\adcadd\19100000-2019 Mechanical
Units\0237.01 American Heating -
Standards 2019\Structural\RTU
\CARRIER\WOOD1lateraIMECH RTU
Gus
CIDA RTU LAJ
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-CARRIER 12.5 TON UNIT
WP:= I461 lb Weight of unit We:= I00lb Weight of(E)curb
Wt:= WP+ We WI= 1561 lb
L:= 115.875 in Length of unit Lc:= 115in Length of Curb
wm:= 63.375in Width of unit we:= 61.375in Width of curb/curb adapter
hm := 57.375-in Height of unit
hc:= 14-in Height of curb
hmc:= hm + he hmc= 71.38in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
SDS:= 0.85 CONSERVATIVE FOR PORTLANDWANCOUVER AREA
h := 10fi Ip:= 1.0 aP:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4.a •SDS•i z
FPunit I + 2.— •W =620.92 lb 0.7•F 434.65 lb
P• P
Rp h P PunitPunit =
0.4•a •SDS'I / zl
Fp:= R P I 1 + 2•h .Wt Fp=663.421b 0.7•Fp=464.41b
P \\ J
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KZt:= 1.0 GC,:= 1.9 GC, vert:= 1.5
qz:= 0.00256•Kh•KZi Kd•V3s2•psf
F:= GCc qz F=52.74 psf
Pwind unit F•L•hm Pwind unit = 2435,16 lb
Pwind F'L'hmc \'wind = 3029.36 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert qi GCr vert Fven=41.64 psf
Pwind unit vert = Fvert'L'wm Pwind unit vert =2123.54 lb
Pvert_ASD:= 0.6WP—0.6Pwind unit vert Pvert_ASD =—397.53 lb
Pven_LRFD= 0.9Wp — LOPwind_unit_vert Pvert_LRFD=—808.64 lb
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating
Standards 20191Structural\RTU
\CARRIER\WOOD\IateraIMECH RTU
;1uR
CIDA RTU
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hm
m Mot seismic unit •= FPunit'
Mot wind_unit= Pwind_unit 2 - 2
M 582i.561bft Mot_seismic_unit = 1484.4lbft
of wind unit-
wm
Mres:= tiVp' Mres =3858Ibft
2
(0.6Mot yvind unit) Pvert_ASD
Fup_windunit = (0.7•Mot_seismic_unit - 0.64Mres)
we 2 Fupseismic_unit
we
Fup_wind_unit =881.7lb Fup_seismic_unit = -249.42 lb
0.6•Pwind_unit = 1461.1 lb 0.7•Fpunit =434.65lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 1462 sliding and 8821b tension at unit to curb connection-18GAcurb
0.6•Pwind„unit = 1461.1 lb Fup_wind-unit =881.7 lb nscREw := 4
Try 16GAx 6"clip with(4)#10 screws per clip
VcLIp:= 401Ib 0.61)wind unit = 1461.1 lb
0.6Pwind unit
USHEAR _ USHEAR = 0.607
6.VcLIp
Fup_wind_unit
UUPLIFT UUPLIFT=0.73
3•VcuP
Use(3)dip per side-(12)total
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 20191Structural\RTU
\CARRIER\WOOD1lateralMECH RTU
Gu(0
CIDA RTU LAJ
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturninq at unit to curb SEISMIC-Overturninq at unit to curb
hmcl hmc
Mot_wind total :_ Pwind'2 lJ Mot_seismic_total FP'2
Mot_windtotal =9009.2 lb ft Mot seismic total = 1973 lb ft
(0.6Mot_wind_total) Pvert ASD 0.7'Mot seismic_total (0.6—0.7.o,2.s s).Wt
Fup wind total we — 2 Fup_seismic_total µ — — 2
Fupwind_total = 1255.65 lb Fup_seismic_total =—105.39 lb
0.6•Pwi„d= 1817.62 lb 0.7Fp=464.4 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 18181b sliding and 1256b uplift at curb to roof connection
0.6•Ptvind= 1817.62 lb Fup wind total = 1255.65 lb
Try#12x3"WOOD SCREWS EACH SIDE—Lang side to take naon, short s des to tale shear
lscrew:= 3 in length of screw
LP:= lscrew — 8 in Lp =2.38 in
screw length-Sheathing-tapered tip 2
dthread lscrew'3 thread length
dscrew := 0.216in Screw diameter
Lp 'thread 154'16 withdrawal capacity per inch
Co:= Cp-- 1.1 in
10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallow 1.6.1561b•Cp Vallow=249.6 lb
Tallow:= 1.6•dthread'Wthread Tallow= 492.8 lb
0.6•Pwind
USHEAR USHEAR= 0.9I
8•Vallow
Fup_wind_total
UUPLIFT= UUPLIFT= 0.64
4•Tauow
Use(4)#12x3"screws per side—(16)screws total
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 20191Structural\RTU
\CARRIER\WOOD\lateralMECH RTU
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-CARRIER 25 TON UNIT
WP:•
= 2118Ib Weight of unit We:= 10016 Weightof(E)curb
Wt:= Wp+ We WE= 2218 Ib
L:= 157.75in Length of unit Lc:= 157in Length of Curb
wm:= 86.375in Width of unit we:= 83.375in Width of curb/curb adapter
hm:= 57.375•in Height of unit
he:= 14.in Height of curb
hmc:= hm+ he hmc= 71.38 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
Sim:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVERAREA
h:= I Oft 1p:= 1.0 ap•:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4•aP SDs.Ip z
Fp"n,t . I + 2 W F 900.15 lb 0.7•F 630.1 lb
RP ) Punit= Punit =
0.4•a •SDs• z11
Fp:= R �•�1 + 2•hl.Wt Fp =942.65lb 0.7•Fp =659.85lb
P JJ
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kit:= 1.0 GCr:= 1.9 GCr vert:= 1.5
qz:= 0.00256•Kh•Kzi Kd.V3s2.psf
F:= GC;qz F= 52.74 psf
Pwind unit F•L•hm Pwind unit =3315.18 lb
Pwind F'L•hmc wind = 4124.12 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert qi GCr vert Fven =41.64 psf
wind unit_vert = Fvert•L•wm Pwind unit_vert =3940.13 lb
Fvert ASD 0.6Wp—0.6Pwind_unit_vert Pvert_ASD =—1093.28 lb
Pvert_LRFD= 0.9Wp- I.OPwind unit_vert Pvert_LRFD=—2033.93 lb
E:\adcadd\19\00000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\StructuraRRTU
\CARRIER\WOODltateratMECH RTU
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hm (h \
m
Mot wind unit Pwind-unit'- Mot_seismic unit FPunit•
2 2 �
Mot_wind_unit = 7925.36 lb ft Mot seismic unit =2151.92 lb ft
Mot_seismicun t) (0.6-0.7.0.2•SDs)•Wp
(0.6Mot_wind_unit) Pvert_ASD Fup_seismic_unit t= +
Fup_wind_unn — we 2
we 2
Fup_seismic_unit = 726.18lb
Fup_wind_unit = 1231.05 lb
0.7.Fpunit =630.1 lb
0.6-Pwind unit = 1989.11 lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 1990 sliding and 12321b tension at unit to curb connection-18GAcurb
0.6•Pwind_unit = 1989.11 lb Fup wind unit = 1231.05 lb
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP:= 4011b 0.6Pwind unit= 1989.11 lb
0.6Pwind_unit
USHEAR:= USHEAR=0.62
8•VCLIP
Fup wind unit
UUPLIFT:= UUPLIFT= (.77
4•VCLIP
Use(4)clip per side-(16)total
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\CARRIER MOOD\IateraIMECH RTU
Lu/3
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb -
M - := (P hmc) hmc
ot_wind tote! wind' 2 Mot seismic total := FP'2
- -
Mot wind_total = 12265 lb ft Mot seismic total =2803.4 lb ft
(0.6Mot wind_total) Pven_ASD 0.7'Mot_seismic-total (0.6 -0.7.0.2-Sos)•Wt
Fup_wind_total ` Fup_seismic total
we 2 we 2
Fup_wind_total = 1605.8lb
Fup_seismic total =-250.99 lb
0.6•13wind =2474.47 lb 0.7Fp=659.85 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 24751b sliding and 1606b uplift at curb to roof connection
0.6•PNi„d =2474.47 lb Fup_wind_total = 1605.8 lb
Try#12x3"WOOD SCREWS EACH SIDE-Long side to take bnson, short sdes to take shear
'screw:= 31n length of screw
5,
LP:= 'screw " 8 In Lp =2.38 in
screw length-Sheathing-tapered tip 2 -•
dthread = 'screw'3 thread length
dscrew 0.216in Screw diameter
Lp wthread 154.lb withdrawal capacity per inch
CD p:= Cp = 1.1 to
10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallow:= 1.6•I561b•Cp Vallow= 249.6 lb
Tallow 1.6'dthread'wthread Tallow= 492.8 lb
0.6•Pwind
USHEAR:= USHEAR=
12 V 0.826
allow
Fup_wind_total
UUPLIFT UUPLIFT= 0.54
6•Tat low
Use(6)#12x3"screws per side-(24)screws total
E:\adcadd\19\00000-2019 Mechanical
Units10237.01 American Heating •
Standards 2019\Structural\RTU
\CARRIER\WOOD\lateralMECH RTU
AMERICAN HEATING STANDARDS 7/22/2019
Wind(tat)= 52.74 psf
Wind(vert)= 41.64 psf �j
Fp= 0.43'weight Lenno-c LI h/
2
UNIT SIZE WEIGHT LENGTH WIDTH HEIGHT 0.7'Fp P_WIND P_WIND_VERT P_WIND_TOT
(LBS) (IN) (IN) (IN) (LBS) (LBS) (LBS) (LBS)
2 TON 502 85.25 45 38.875 176.76 1213.79 1109.32 1650.91 _
2.5 TON 505 85.25 45 38.875 177.67 1213.79 1109.32 1650.91
3 TON 497 85.25 45 38.875 175.26 1213.79 1109.32 1650.91
4 TON 527 85.25 45 38.875 184.29 1213.79 1109.32 1650.91
5 TON 565 85.25 45 46.875 195.73 1463.57 1109.32 1900.69
6 TON 620 85.25 45 46.875 212.28 1463.57 1109.32 1900.69
7.5 TON 1212 124.375 60.125 46.875 402.25 2135,27 2162.40 2773.00
8.5 TON 890 101.25 45 46.875 298.37 1736.26 1317.52 2257.42
10 TON 1222 124.375 60.125 46.875 405.26 2135.27 2162.40 2773.00
12.5 TON 1232 124.375 60.125 46.875 408.27 2135.27 2162.40 2773.00
13 TON 17B5 107.75 91.125 54.25 569.72 2140.89 2839.25 2693.38
15 TON 1950 129.5 91.125 54.25 625.93 2573.04 3412.37 3237.05
17.5 TON 2090 120.1875 91.125 54.25 665.27 2388.01 3166.98 3004.27
20 TON 2997 132.375 90.75 65 941.94 3151.35 3473.77 3830.11
25 TON 2997 132.375 90.75 65 941.94 3151.35 3473.77 3830.11
30 TON 2997 132.375 90.75 65 941.94 3151.35 3473.77 3830.11
35 TON 6100 286 66 90 1922.19 9427.28 5623.71 10893.74
40 TON 6100 286 68 90 1922.19 9427.28 5623.71 10893.74
45 TON 6500 286 68 90 2042.59 9427.28 5623.71 10893.74
50 TON 6550 286 68 90 2057.64 9427.28 5623.71 10893.74
UNIT TO CURB CONNECTION Curb to roof connection(14"std curb)
LC#7:0.60+0.6W LC#6 0.6D+0.6W
Mot(1.0W) Pvert W 0 6D) 0.6'Pwind Mot(1.OW) (O.6D 0 6W) (Q 6D}
(LB-FT) (LBS) 0.6'Pwind
UNIT (0.6D-0.6W
) (0 6(LB) (LBS) (LBS) (LB FT) (LB) (LBS) (LBS)
2TON 1966.08 -182.19 212.44 728.27 3637.2 -161,2 217.15 728.3
2.5 TON 1966.08 -181.29 211.54 728.27 3637.2 -160.3 216.25 728.3
3 TON 1966.08 -183.69 213.94 728.27 3637.2 -162.7 218.65 728.3
4 TON 1966.08 -174.69 204.94 728.27 3637.2 -153.7 209.65 728.3
5 TON 2858.53 -163.29 207.27 878.14 4821.0 -142.3 216.46 878.1
6 TON 2858.53 -146.79 190.77 878.14 4821.0 -125.8 199.96 878.1
7.5 TON 4170.44 -285.12 839.90 1281.16 7033.6 -259.6 1498.6 1281.2
8.5 TON 3395.03 -128.25 755.03 1042.95 5725.8 -102.8 1111.3 1043.0
10 TON 4170.44 -282.12 836.90 1281.16 7033.6 -256.6 1495.6 1281.2
12.5 TON 4170.44 -279.12 833.90 1281.16 7033.6 -253.6 1492.6 1281.2
13 TON 4839.31 -316.27 725.59 1284.53 7659.3 -290.8 1433.7 1284.5
15 TON 5816.15 -438.71 930.65 1543.83 9205.4 -413.2 1786.9 1543.8
17.5 TON 5397.90 -323.09 779.66 1432.81 8543.4 -291.6 1566.5 1432.8
20 TON 8534.91 -143.03 868.12 1890.81 12607.4 -117.5 1656.1 1890.8
25 TON 8534.91 -143.03 868.12 1890.81 12607.4 -117.5 1656.1 1890.8
30 TON 8534.91 -143.03 868.12 1890.81 12607.4 44.5 1494.1 1890.8
35 TON 35352.28 142.89 3962.54 5656.37 47206.2 330.4 3715.9 5656.4
40 TON 35352.28 142.89 3962.54 5656.37 47206.2 330.4 3715.9 5656.4
45 TON 35352.28 262.89 3842.54 5656.37 47206.2 450.4 3595.9 5656.4
50 TON 35352.28 277.89 3827.54 5656.37 47206.2 465.4 3580.9 5656.4
1 OF 1
l-Gt y
CIDA RTU RNH
TEL: (503) 226-1285 AMERICAN HEATING STANDARDS 7/24/2019 "
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-LENNOX 3 TON UNIT
W,:= 497Ib Weight of unit We:= 701b Weight of(E)curb
Wt:= WP+ We Wt= 567Ib
L:= 85.25in Length of unit Lc:= 79.75in Length of Curb
vim:= 47in Width of unit we:= 41.5in Width of curb/curb adapter
hm := 38.875•in Height of unit
h,:= 14•in Height of curb
hmc:= hm + he hmc= 52.88 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR 97227)
Mapped Adjusted Maxmum Design
2
S,:= 1.043 site Gass=D Sms:= 1.126 Fa:= SS ss Fa= 1.08 Sns 3•Sms Sias =0.751
s
SEISMIC PARTS AND PORTIONS (BEAVERTON, OR 97005)
Mapped Adjusted Maximum Design
S
Ss:= 1.076 site class=D Sms:= 1.151 Fa:= S ss Fa= 1.07 Sps 3 Sms SDs =0.767
s
SEISMIC PARTS AND PORTIONS (VANCOUVER, WA 98663)
Mapped Adjusted Maximum Design
Ss 2
:= 1.016 site class=D Sms:= 1.107 Fa:= Ss ss Fa= t.09 SDS 3•Sms SDs =0.738
s
BEAVERTON AREA GOVERNS
USE SDS:= 0.8 CONSERVATIVE FOR PORTLAND-VANCOUVER Mb i KO AREA
h := 30ft IP:= 1.0 aP:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4•a •Sps•1 z
_ P P _
Fp°mt . 1 + 2 W F 198.81b 0.7•F 139.16 lb
RP h P Punit = Punit =
0.4-aP•SDS'IP z
Fp:= . I + 2•_).Wt Fp=226.81b 0.7•Fp= 158.76 lb
JJ
E:ladcadd119100000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\LENNOX Mood llateraIMECH RTU curb
LU3
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX:(503)226 1670
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
WIND SPEED FOR WASHINGTON COUNTY= 120 MPH
1MND SPEED FOR CLACKAMAS COUNTY=120 MPH
WIND SPEED FOR MULTNOMAH COUNTY=120 MPH
WIND SPEED FOR VANCOUVER,WA=135 MPH VANCOUVER,WA GOVERNS
vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KZt:= 1.0 GCr:= 1.9 GCr vert 1.5
q2:= 0.00256•Kh•Kr Kd•V3,2.psf
F:= GC;q F= 52.74 psf
Pwind_unit F'2 'hm Pwind_unit=606.95 lb
Pwind F'2'hmc Pwind=825.53 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert qi GCr vent Fvert =41.64 psf
Pwind unit vert Fvert'L'wm Pwind unit vert = 1158.63 lb
Pvert_ASD 0.6Wp—0.6Pwind_unit_vert Pvert_ASD = 396.98 lb
Pven_LRFD 0.9Wp— 1.0Pwind_unit_vert Pvert_LRFD= 711.33 lb
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.60+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hn Mot seismic unit FPunit' m
Mot_wind_unit= Pwind unit'2 — 2
Mot seismic i• = 322.01 lbft
Mot_wind_unit =983.13 lb ft -
unt
Mres Wp'— Mres =973.3 lb ft
2
(0.6Mot wind unit Pvert ASD
Fup_wind_unit (01'Mot_seismic unit — 0.6•Mres)
we 2 Fup_seismic_unit •—
we
Fup_wind_unit = 369.06 lb Fup_seismic_unit =—103.68 lb
0.6•Pwind_unit =364.17 lb 0.7•Fpunit = 139.16 lb
E:\adcadd\19100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\Wood\IateralMECH RTU curb
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Desgn attachment for 364 lb sliding and 369 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit =364.17 lb Fup_wind_unit =369.06 lb SCREW := 4
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP:= 4011b 0.6Pwind unit =364.17 lb
0.6Pwind unit
USHEAR:_ USHEAR =0.454
2'VCLIP
Fup_wind_unit
UUPLIFT:= UUPLIFT= 0.92
I'VCLIP
Use(1)dip per side—(4)total
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
b � bmc
Mot vind total:= Pwind' m2c Mot_seismic_total := PVT
Mot wind total = 1818.7 lb ft Mot seismic total =499.67 lb ft
we Mres = 973.31bft
(0.6Mot_wind_total) Pvert_ASD Mies Wt' 2
Fup_wind_total :_ w'c 2
(0.7'Mot_seismic_total —0.6'Mres)
Fup_seismic_totat
we
Fup_wind_total = 514.03 lb Fupseismic_total =—68.96lb
0.6•Pwind=495.32 lb 0.7Fp = I58.76lb
WIND GOVERNS CURB TO ROOF
E:tadcadd\19100000-2019 Mechanical
Units10237.01 American Heating Standards 20191Structural\RTU
\LENNOX\Wood\IateraIMECH RTU curb
UA5
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 495 lb sliding and 514 lb uplift at curb to roof connection
0.6•Pwind=495.32 lb Fup_wind_total = 514.03 lb
Try#12x3"WOOD SCREWS EACH SIDE-Long side to take Anson, shortsdes to take shear
'screw 3 m length of screw
LP:= !screw - 8 in Lp = 2.38 in
screw length-Sheathing-tapered tip 2
dthread = 'screw'3 thread length
dscrew:= 0.216in Screw diameter
Lp Wthread:= 154•lb withdrawal capacity per inch
C := C = 1.1 in
p 10.dscrew p
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallow:= 1.6•1561b•Cp Vallow=249.6 lb
Tallow:= I.6'dthread'Wthread Tallow= 492.8 lb
0.6•Pwind
USHEAR:= USHEAR=0.496
4.Vallow
Fup wind total
UUPLIFT:= UUPLIFT= 0.52
2'Tallow
Use(2)#12x3"screws per side-(8)screws total
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX1Wood\IateralMECH RTU curb
C�t/v
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX:(503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-LENNOX 5 TON UNIT
WP:= 565Ib Weight of unit w,:= 701b Weight of(E)curb
Wt:= Wp+ We Wt=635 lb
L:= 85.25in Length of unit L,:= 79.75in Length of Curb
wm:= 47in Width of unit we:= 41.5in Width of curb/curb adapter
hm := 46.875•in Height of unit
h,:= 14•in Height of curb
hmc:= hm + he hmc= 60.88in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR 97227)
Mapped Adjusted Maximum Design
S
Ss:= 1.043 site class=D Sms := 1.126 Fa:= 5—55 F8= 1.08 Sips2'Sms SDS =0.751
s
SEISMIC PARTS AND PORTIONS (BEAVERTON, OR 97005)
Mapped Adjusted Maximum Design
Sms 2
SS:= 1.076 site class=D Sms:= 1.151 Fa:= — Fa= 1.07 SDS 3•Sms SDS =0.767
8
s
SEISMIC PARTS AND PORTIONS (VANCOUVER, WA 98663)
Mapped Adjusted Maximum Design
SS:= 1.016 site class=D Sms:= 1.107 Fa:= Ss s5 Fa= 1.09 SDS 3'Sms SDs =0.738
s
BEAVERTON AREA GOVERNS
USE SDS:= 0.8 CONSERVATIVE FOR PORTLAND-VANCOUVER METRO AREA
h := 30ft Ip:= 1.0 ap:= 2.5 Rp:= 6 z:= h Air side HVAC component
0.4•a •SDS•1 Z
P P
FPunit 1 + 2•— •W F 226 lb 0.7•F 158.21b
Rp h P Punit = Punit=0.4•aP SDS.Ip ( zl
Fp: R •I 1 + 2• I•Wt Fp =2541b 0.7•Fp= 177.81b
l J
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating Standards 2019\Structural\RTU
\LENNOX\WoodMateralMECH RTU curb
LU7
CIDA RTU RNH
TEL: (503) 226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
WIND SPEED FOR WASH NGTON COUNTY=120 MPH
WIND SPEED FOR CLACKAMAS COUNTY=120 MPH
WIND SPEED FOR MULTNOMAH COUNTY=120 MPH
WIND SPEED FOR VANCOUVER,WA=135 MPH VANCOUVER,WA GOVERNS
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kz1:= 1.0 GC,:= 1.9 GCr vert 1.5
qz:= 0.00256•Kh'K1tKd•V3s2•psf
F:= GCr qz F= 52.74 psf
Pwind_unit:= F'Z'hm Pwind unit =731.85 lb
Pwind F•2'hmc kind=950.43 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert 9i GCr vert Fvert =41.64psf
Pwind_unit_vert Fvert'lLwm Pwind unit vert = 1158.63 lb
Pvert_ASD 0.6Wp 0.6Pwind_unit_vert Pvert_ASD =—356.18 lb
Pvert_LRFD 0.9Wp 1.0Pw,ind_unit_vert Pvert_LRFD=—650.13 lb
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hm\
Mot_wind_unit= Pwind_unii 2 Mot_seismic_unit FPunit' 2
Mofwindunit 1429.39lbft Mot_seismic_unit =441.41lbft
—
w
}} Mres•= Wp'2
0.6 Mres = 1106.5lbft
( Mot_wind_unit) Pvert_ASD
Fup_wind_unit Nc 2 Fup_seismic_unit :_ `0 7 Mot seismic unit 0.6•Mres)
we
Fup_wind_unit =426.08 lb Fup_seismic_unit =—102.62 lb
0.6•Pwind_unit =439.11 lb 0.7•Fpunit = 158.21b
E:\adcadd119\00000-2019 Mechanical
Un1ts10237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\WoodilateralMECH RTU curb
LGtg
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 439 lb sliding and 426 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit =439.11 lb Fup_wind_unit =426.08 lb nSCREW:= 4
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIp:= 401lb 0.6Pwind unit =439.11 lb
0.6Pwind unit
USHEAR USHEAR =0.274
4•VCLIP
Fup wind unit
UUPLIFT UUPLIFT=0.53
2•VCLIP
Use(2)clip per side—(8)total
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc� bmc
Mot wind total = Pwind" 2 Mot seismic total := FP'2
Mot wind total =2410.7lbft Mot seismic total =644.26 lb ft
we Mres = 1106.5►b ft
(0.6Mot wind_total� Pven_ASD Mres'= 4Vt. 2
Fup_wind_total " we — 2
(0.7•M ot_seism ic_total 0.6•Mres)
Fup_seismic_total
we
Fup wind total =596.33 lb Fup_seismic_total =—60.1 lb
0.6•P„ind=570.26 lb 0.7Fp = 177.81b
WIND GOVERNS CURB TO ROOF
E:\adcadd\19100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\Wood\lateralMECH RTU curb
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 570 lb sliding and 596 lb uplift at curb to roof connection
0.6'Pwind= 570.26 lb Fup_wind total = 596.33 lb
Try#12x3"WOOD SCREWS EACH SIDE—Long side to take fznson, shorts ties to take shear
!screw 3 in length of screw
5
Lp:= !screw — 8 in Lp = 2.38 in
screw length-Sheathing-tapered tip 2
dthread !screw 3 thread length
dscrew 0.216in Screw diameter
Lp wthread:= 154•lb— withdrawal capacity per inch
C C = 1.1 in
p 10•dscrew p
Cp:= if(Cp> 1.0,1.0,Cp) Cp= I
Vallow I.6.1561b•Cp Val low=249.6 lb
Tallow 1.6•dthread'wthread Tallow=492.8 lb
0.6•Pwind
USHEAR= USHEAR=0.571
4•Vail„
Fup_wind_total
UUPLIFT UUPLIFT=0.61
2'Tallow
Use(2)#12x3"screws per side—(8)screws total
E:ladcadd119100000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\LENNOX\WoodllateraIMECH RTU curb
LUI0
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX:(503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-LENNOX 15 TON UNIT
Wp:= 195016 Weight of unit W,:= 105Ib Weight of(E)curb
Wt:= Wp+ We Wt= 2055 lb
L:= I29.5in Length of unit L,:= 102in Length of Curb
wm:= 91.1251n Width of unit w,:= 86.125in Width of curb/curb adapter
hm:= 54.25•in Height of unit
h,:= 14.in Height of curb
hmc:= hm + h, hmc= 68.25 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR 97227)
Mapped Adjusted Maximum Design,
Ss:= 1.043 site class=D Sms:= 1.126 Fa:= S ss Fa= 1.08 SDs 3•Sms SDs =0.751
S
SEISMIC PARTS AND PORTIONS (BEAVERTON, OR 97005)
Mapped Adjusted Maximum Design
Ss:= 1.076 site class=D Sms := 1.151 Fa= —s Fa= 1.07 Sias3•Sms SDs =0.767
S,
SEISMIC PARTS AND PORTIONS (VANCOUVER,WA 98663)
Mapped Adjusted Maximum Design
S, := 1.016 site class=D Sms := 1.107 Fa:= Ss ss Fa= 1.09 SDs:= 3•Sms SDS =0.738
s
BEAVERTON AREA GOVERNS
USE Sips := 0.8 CONSERVATIVE FOR PORTLAND-VANCOUVER METRO AREA
h:= 30ft 1p:= 1.0 ap:= 2.5 Rp:= 6 z:= h Air side HVAC component
0.4•a P•Sp Ds•l PFpunt
l + 2•—z W P FPunt =780 lb 0.7•Fp„„ =546 lb
0.4•ap SDS•lp z
Fp:_ . 1 + 2•-z •Wt Fp =822 lb 0.7•Fp=575.4 lb
RP h
E:\adcadd\19V00000- 2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\WoodllateraIMECH RTU curb
t•Ltti
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
WIND SPEED FOR WASH INGTON COUNTY=120 MPH
WIND SPEED FOR CLACKAMAS COUNTY=120 MPH
WIND SPEED FOR MULTNOMAH COUNTY=120 MPH
WIND SPEED FOR VANCOUVER,WA=135 MPH VANCOUVER,WA GOVERNS
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KZ1:= 1.0 GCr:= 1.9 GCr ven 1.5
qz:= 0.00256•Kh'Kzi Kd•V3,2•psf
F:= GC;qz F= 52.74 psf
Pwind unit F'L'hm Pwind unit =2573.27 lb
Pwind:= F'1-'hmc kind= 3237.34 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fven qi GCr vert Fart = 41.64 psf
'wind_unit vert 0.6Wp— 0.6Fvert'L'Wm Pwind unit vert =—877.44 lb <0,Uplift
Pwind_total_vert = 0.6Wt— 0.6•Fvert'L'wm —P 814.44lb <0,Uplift
wind total vert - p
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
h hm
nt Mat seismic unit FPunit'
Mat_wind_unit Pwind_unit'2 - - 2
M 5816.661b ft Mot_seismic_unit = 1763.12 lb ft
of wind unit
(0.6Motwind unit) Pwind_unit_vert (0.7'Mot_seismic_unit) (0.6-0.7.0.2•SDs)•Wp
Fup wind_unit w — 2 Fup_seismic_unit t„ 2
c c
Fup_wind_unit =924.99 lb Fup_seismic_unit =—303.84 lb
0.6•Pwind_unit = 1543.96 lb 0.7•Fpuni1 = 546 lb
WIND GOVERNS RTU UNIT TO CURB
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\Wood\IateralMECH RTU curb
Lu17_
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 1,544 lb sliding and 925 lb tension at unit to curb connection—18GAcurb
0.6'Pwind_unit = 1543.96 lb Fup_wnd_unit =924.99 lb nSCREW := 4
Try 16GAx 6"clip with(4)#10 screws per clip
VCL1p:= 4011b 0.6Pwind unit = 1543.96 lb
0.6Pwind_unit
USHEAR USHEAR=0.642
6•VCLIP
Fup_wind_unit
UUPLIFT UUPLIFT=0.77
"3.VCLIP
Use(3)clip per side—(12)total
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc hmc"
Mot_wind_total := Pwind' 2 Mot—seis_total FP. z
Mot wind total =9206.18 lb ft Mot seistotal = 2337.56 lb ft
0.6(Mot wind_total) Pwind_total_yen (0.7-Mot_seis_mtai) (0.6— 0.7.0.2•Sps)•(Wt)
Fup_wind_total Fup_seis_total
W w — 2
c 2
Fup_wind_.total = 1176.85 lb Fup_seis_totai = —273.43 lb
0.6•P 1942.4 lb
0.7•Fp = 575.4lb
wind =
WIND GOVERNS CURB TO ROOF
E:\adcadd119100000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
1LENNOX\Wood\ateraIMECH RTU curb
0.4.13
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 1,942 b sliding and 1,177 lb uplift at curb to roof connection
0.6•P.,yind= 1942.4 lb Fupwind_total = 1176.85 lb
Try#12x3"WOOD SCREWS EACH SIDE-Lang side to take neon, shortsdes totals shear
'screw 3 in length of screw
Lp:= 'screw 8 in Lp = 2.38 in
screw length-Sheathing-tapered tip 2
dthread Iscrew'3 thread length
dscrew i= 0.216in Screw diameter
Lp wthread:= 154•lb withdrawal capacity per inch
Cp:= Cp= I.I in
10•dscrew
Cp:= if(Cp> 1.0,I.O,Cp) Cp= I
Vallow 1.6.1561b•Cp Vallow= 249.6 lb
Tallow 1.6•dthread*wthread Tallow=492.8 lb
0.6-Pwind
USHEAR USHEAR=0.973
8'Vallow
Fup_wind_total
UUPLIFI- UUPLIFT=0.6
4•Tallow
Use(4)#12x3"screws per side—(16)screws total
E:ladcadd11 9100000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\WoodMateralMECH RTU curb
Lu►
CIDA RTU RNH
TEL:(503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019 •
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURS-LENNOX 20 TON UNIT
Wp:= 29971b Weight of unit W,:= 105Ib Weight of(E)curb
Wt:= Wp+ W, Wt= 3102Ib
Ltop:= 145in Top Length of unit
Lbonom 119.75in Bottom Length of unit Lc:= 115.125 in Length of Curb
wm:= 90.75in Width of unit w,:= 86.125 in Width of curb/curb adapter
hm:= 65•in Height ofunit
h�:= 14•in Height ofcurb
hmc:= hm + h, hmc= 79 in Total heghtof unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR 97227)
Mapped Adjusted Maximum Design
Ss:= 1.043 site class=D Sms:= 1.126 Fa:= Sms Fa= 1.08 SDS= 3•Sms SDS =0.751
SEISMIC PARTS AND PORTIONS (BEAVERTON, OR 97005)
Mapped Adjusted Maximum Design
Ss:= 1.076 site class=D Sms:= 1.151 Fa:= Ss ss Fa= 1.07 SDS 3'SimSDS=0.767
s
SEISMIC PARTS AND PORTIONS (VANCOUVER,WA 98663)
Mapped Adjusted Maximum Design
Ss:= 1.016 site class=D Sms:= 1.107 Fa:= Ss s5 Fa= 1.09 SDS 3'Sms SDS =0.738
s
BEAVERTON AREA GOVERNS
USE SDS := 0.8 CONSERVATIVE FOR PORTLAND-VANCOUVER METRO AREA
h := 30ft IP:= 1.0 a9:= 2.5 Rp:= 6 z:= h Air side HVAC component
0.4.aP SDS•IP / z\
FPunit • 1 + 2.- •W F 1198.81b 0.7•F 839.161b
RP k h P Pumt = Punit =
0.4•aP SDS'IP /
Fp:_ • 1 + 2•— •Wt Fp = 1240.8 lb 0.7-Fp =868.56 lb
Rp h
E:ladcadd119100000-2019 Mechanical
Units10237.01 American Heating Standards 2019\Structural\RTU
1LENNOX1WoodllateralMECH RTU curb
LI 15
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
WIND SPEED FOR WASHNGTON COUNTY=120 MPH
WIND SPEED FOR CLACKAMAS COUNTY=120 MPH
WIND SPEED FOR MULTNOMAH COUNTY=120 MPH
WIND SPEED FOR VANCOUVER,WA=135 MPH VANCOUVER,WA GOVERNS
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kzt:= i.0 GCr:- 1.9 GCr vert:= 1.5
qz:= 0.00256•Kh•Kn•Kd•V3,2.psf
F:= GCr qz F=52.74 psf
P _ F Ltop + Lbottom•h P 3151.63 lb
wind_unit.— 2 m wind_unit —
P F Ltop + Lbottom h P 3830.44lb
wind 2 me wind=
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert gz•GCr vert Fven =41.64 psf
Pwind_unit_ven 0.6Wp— 0.6Fvert'Ltop'wm Pwind_unit_vert = —484.87lb
Pwind_total_ven 0.6Wt—0.6•Fvert•Ltop•wm
Pwind_total_vert =—421.87 lb
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hm
hm Mot seismic unit FPunit' —
Motµwind unit = Pwind_unit'2 -
M ofwind unit —— 8535.66lbft Mot_seismic_unit = 3246.75lbft
(0.6Mot_wind_unit) Pwind_unit_ven (0.7•Mot_seismic_unit) (0.6 —0.7.0.2•Sps)•Wp
Fup_wind_unit w — 2 w Fup seismic_unit -
c c 2
Fup_wind_unit =956.01 lb Fup seismic._unit =—414.6 lb
0.6•13wind_unit = 1890.98 lb 0.7•FPunit = 839.16 lb
WIND GOVERNS RTU UNIT TO CURB
• m aA11s a1-\IT
E:\adcadd\19\00000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\LENNOX\Wood\lateraIMECH RTU curb
CIDA RTU RNH
TEL: (503)226-12B5 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
Al IA1.4-1III1GN I
Design attachment for 1,891 lb sliding and 956 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit = 1890.98 lb Fup_wind_unit =956.01 lb nSCREw:= 4
Try 16GAx 6"Op with(4)#10 screws per clip
VCLIP= 40I lb 0.6Pwind unit = 1890.98 lb
0.6Pwind_unit
USHEAR:= USHEAR= 0.786
6•VCLIP
Fup_wind_unit
UUPLIFT:= UUPLIFT=0.79
3•VCLIP
Use(3)clip per side—(12)total
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hInc hmcl
Mot_wind_total wind Z Mot_seis_total FP' —
2 J
Mot wind total = 12608.53 lb ft Mot seis totai = 4084.3 lb ft
O.6(Mot_wind total Pwind_total_vert (0.7•Mot_seis_totai) (0.6—0.7.0.2.Sps).(W)
Fup_wind total := — Fup_seistotal :-
W —
c 2 w c 2
Fup_wind total = 1265 lb Fup_seis total =—358.54 lb
0.6•Ptvit,d=2298.26 lb 0.7•Fp = 868.56 lb
WIND GOVERNS CURB TO ROOF
E:\adcadd119\00000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\Wood\IateralMECH RTU curb
LM 17
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 2,153 lb sliding and 1,136 b uplift at curb to roof connection
0.6•Pwind=2298.26 lb Fup_wind_total = 1265 lb
Try#12x3"WOOD SCREWS EACH SIDE—Long side to take bnson, shortsdes to take shear
'screw 3 in length of screw
LP 'screw —Bin Lp= 2.38 in
screw length-Sheathing-tapered tip 2
dthread 'screw'3 thread length
dscrew:= 0.216in Screw diameter
Lp "'thread 154•lb withdrawal capacity per inch
Cp:= Cp= 1.1 in
10•dscrew
Cp:= if(Cp> I.O,1.O,Cp) Cp=
Vallow I.6.1561b•Cp Vanow,=249.61b
Tallow:= 1.6•dthread'�thread Tallow=492.8 lb
0.6•Pwind
USHEAR 10 V USHEAR=0.921
allow
Fup_wind_total
UUPLIFT UUPLIFT=0.51
5•Tallow
Use(5)#12x3"screws per side—(20)screws total
E:\adcadd019100000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
1LENNOX\Wood'1ateralMECH RTU curb
LIAir"
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-LENNOX 35 TON UNIT
W,:= 61001b Weight of unit W,:= 6251b Weight of(E)curb
Wt:= Wp+ We Wt=6725 lb
L:= 286in Length of unit L,:= 282.375 in Length of Curb
wm:= 90in Width of unit w,:= 80.125in Width of curb/curb adapter
hm:= 68•in Height of unit
h�:= 14•in Height of curb
hmc:= hm + h, hmc= 82 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND,OR 97227)
Mapped Adjusted Maximum Design
Sm
S,:= 1.043 site class D Sms:= 1.126 Fa:= S 55 Fa= 1.08 SOS:= 3•Sms Sips =0.751
s
SEISMIC PARTS AND PORTIONS (BEAVERTON, OR 97005)
Mapped Adjusted Maximum Design
2
S,:= 1.076 site class=D Sms:= 1.151 Fa:= Ss ss Fa= 1.07 SDS 3'Sms SDS =0.767
s
SEISMIC PARTS AND PORTIONS (VANCOUVER, WA 98663)
Mapped Adjusted Maximum Design
5,:= 1.016 site class=D 5ms:= 1.107 Fa:= Ss ss Fa= 1.09 SDS 3'Sms SDS =0.738
s
BEAVERTON AREA GOVERNS
USE SOS:= 0.8 CONSERVATIVE FOR PORTLAND-VANCOUVER METRO AREA
h:= 30ft Ip:= 1.0 ap:= 2.5 RI,:= 6 z:= h Air side HVAC component
0.4 a •SDS.I
P P Fpunit•= Rp 1 + 2 _ •WP FPunit =2440 lb 0.7•Fpunit = 1708 lb
0.4•a •Spg•I z
Fp:= P P• 1 + 2— •Wt Fp =2690 lb 0.7•Fp = 1883 lb
Rp h
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU
1LENNOX\Wood\IateralMECH RTU curb
Lull
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
WIND SPEED FOR WASH IN GTON COUNTY=120 MPH
WIND SPEED FOR CLACKAMAS COUNTY= 120 MPH
WIND SPEED FOR MULTNOMAH COUNTY=120 MPH
WIND SPEED FOR VANCOUVER,WA=135 MPH VANCOUVER,WA GOVERNS
Vas:= 135 Exposure B
Kd:= 0.85 Kb:= 0.7 Kzt:= LO GCr:= 1.9 GCr Vert•= I
qz:= 0.00256•Kh•Kzt•Kd•V3,2.psf
F:= GC1 qz F= 52.74 psf
Pwind_unit F•L•hm Pwind unit =7123.45 lb
Pwind F'�•'hmc Pwind = 8590.05 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Pvert qi GCr vert Fven =41.64 psf
Pwind_unit_vert 0.6Wp—0.6Fvert'L'wm Pwind unit ven =—805.94 lb
Pwind_total ven:= 0.6Wt—0.6•Fvert'L'wm
Pwind total vert =—430.94 lb
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
h hm
Mot_setsmic unit •= Fpunit' 2
Mot_wind_unit Puind_unit' 2
M — 20183.1I lb Mot seismic_unit =6913.3316ft
of wind unit — }
(0.6Mot_wind_unit) Pwind_unit vert (0.7•Mot )seismic unit (0.6 —0.7.0.2•Sps)•Wp
Fup_wind_unit = w — 2 Fup_seismic_unit W — 2
Fup wind unit =2216.62 lb Fup_seismic._unit =—763.63 lb
0.6•Pwind_unit =4274.07 lb 0.7•Fpunit= 1708 lb
WIND GOVERNS RTU UNIT TO CURB
E:\adcadd\19100000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU
\LENNOX\WoodllateraIMECH RTU curb
LAO
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachmentfor 4,274 b sliding and 2,217 lb tension at unit to curb connection—18GAcurb
0.6'Pwind_unit=4274.07 lb Fup_wind_unit =2216.62 lb SCREW= 4
Try 16GAx 6"clip with(4)#10 screws per dip
VCLIP:= 401 Ib 0.6Pwind unit=4274.07 lb
0.6Pwind_unit
USHEAR 12 USHEAR =0.888
V CLIP
Fup_wind_unit
UUPLIFT UUPLIFT=0.92
6•VCLIP
Use(6)clip per side—(24)total
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc htoe` -
Mot wind total Pwind'— Mot_seis total FP' —
2 \ 2
Mot_wind_total =29349.32lbft Mot_seis coral = 9140.8316ft
"(Mot wind_total) Pwind_total_yen (0.7'Mot_seis_total) (0.6-- 0.7.0.2•SDs)'(W)
Fup_wind total — Fup_seis_total
w — 2
c 2 w c
Fup_wind_total =2852.79 lb
Fup_seis_total =—677.37 lb
0.6.['wind=5154.03 lb 0.7•Fp = 1883 lb
WIND GOVERNS CURB TO ROOF
E:\adcadd119100000-2019 Mechanical
Units10237.01 American Heating
Standards 2019\Structural\RTU
\LENNOX\Wood\IateralMECH RTU curb
L-U2I
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
ATTACHMENT
Design attachment for 5.154 b sliding and 2,853 lb uplift at curb to roof connection
0.6•Pwind= 5154.03 lb Fup wind_total = 2852.79 lb
Try#12x3"WOOD SCREWS EACH SIDE—Lang side to take bnaon, sh ort s'd es to take shear
Iscrew 3in length of screw
Lp Iscrew — 8 in Lp=2.38 in
screw length-Sheathing-tapered tip 2
dthread 'screw 3 thread length
dscrew:= 0.216in Screw diameter
Lp Wthread:= 154•lb withdrawal capacity per inch
Cp:= Cp= 1.1 in
10•d screw
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Valhi„ 1.6.1561b•Cp Vaitow= 249.6 lb
Tallow 1.6•dth read'Wthread Teo,=492.8lb
0.6•Pwind
USHEAR USHEAR= 0.86
24 V
avow
Fup_wind_total
UUPLIFT UUPLIFT=OAS12•Taoo v
Use(12)#12x3"screws per side—(48)screws total
E:\adcadd11 9100000-2019 Mechanical
Units\0237.01 American Heating
Standards 20191Structural\RTU
\LENNOX\Wood\lateraIMECH RTU curb
TRANE UP AMERICAN HEA ;STANDARDS .120.01
Pwlnd(lateral)= 52.74 psf
Pwlnd(vert)= 41.64 psf
Fp= 0.425•Weight
MAX.WEIGHT MIN.WEIGHT LENGTH WIDTH HEIGHT
0.6(WIND) NET VERTICAL 0.7(5E15)
UNIT SIZE (LB) (LB) (IN) (IN) (IN) LATERAL 0.6(W)40.6(D) LATERAL
(LB) (L8) (LB)
3 TON 615 481 69.875 44.25 36.25 557 -248 183
4 TON 763 511 88.625 53.25 40.875 796 -434 227
5 TON 854 561 88.625 53.25 40.875 796 -412 254
6 TON 845 667 88.625 53.25 40.875 796 -419 251
7.5 TON 928 686 88.625 53.25 40.875 796 -408 276
8.5 TON 987 856 88.625 53.25 40.875 796 -306 294
r
10 TON 1199 960 _ 99.6875 63.1875 50.875 1,114 -374 357
12.5 TON 2191 _ 1413 121.6875 84.1875 64.125 1,715 -591 652
15 TON 2197 1822 121.6875 84.1875 64.125 1,715 -685 654
17.5 TON 2277 1863 121.6875 84.1875 64.125 1,715 -660 677
20 TON 2107 1925 121.6875 84.1875 64.125 1,715 -623 627
25 TON 2062 1878 121.6875 84.1875 64.125 1,715 -651 613
-
UNIT _ TOTAL
OT MOMENT RES.MOMENT LATERAL Fup OT MOMENT RES.MOMENT LATERAL Fup
UNIT SIZE LOW) 1.0(D) 0.6(WIND) 0.6(W)-0.6(0) 1.0(W) LO(W)+0,9(D)- 1.0(WIND) L0(W)-0.9(D)
(LB-FT) (LB-FT) (Ls) (is) (LB-FT) (LB-FT) (LB) (LB)
3 TON 1,402 887 557 369 2,693 887 772 594
4 TON 2,260 1,425 797 535 4,074 1,425 1,069 789
5 TON 2,260 1,507 797 524 4,073 1,507 1,069 778
6 TON 2,260 1,480 797 527 4,073 1,480 1,069 782
7.5 TON 2,260 1,523 797 522 4,073 - 1,523 1,069 776
8.5 TON 2,260 1,900 797 471 4,073 1,900 1,069 725
10 TON 3,938 3,157 1,115 651 6,404 3,157 1,422 941
12.5 TON 7,637 6,939 1,715 973 11,336 6,939 2,090 1,301
15 TON 7,637 6,392 _ 1,715 _ 1,020 11,336 6,392 2,090 1,348
17.5 TON 7,637 6,536 1,715 1,008 11,336 6,536 2,090 1,336
20 TON 7,637 6,753 1,715 989 11,336 6,753 _ 2,090 1,317
25 TON 7,637 6,588 1,715 1,003 11,336 6,588 2,090 1,331
I
1 OF 1 .8/10/2015
TUZ
CIDA RTU RNH
TEL:(503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-TRANE 3 TON UNIT
WP:= 48I Ib Weight of unit We:= 100Ib Weight of(E)curb
Wt:= Wp+ We Wt= 581 lb
L:= 69.875in Length of unit L,:= 69.0in Length of Curb
wit,:= 44.25in Width of unit w,:= 41.25in Width of curb/curb adapter
hm:= 36.25•in Height of unit
h,:= 14•in Height ofcurb
hmc:= hm + hp hmc = 50.25 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND,OR)
Design
SDS:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVER AREA
h:= 10ft 1p:= 1.0 ap:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4•a •SDS•l z
FP°"n.— 1 + 2 W F =204.42lb 0.7•F 143.1 lb
_ p P _
RP h P Fp,„,, Punit =
0.4•aPSDS 1P �
Fp:_ I + 2•-z •W, Fp =246.92 lb 0.7•Fp = 172.85 lb
RP h,
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
V3,:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kn:= 1.0 GC,:= 1.9 GC, vert:= 1.5
qZ:= 0.00256.Kh.Kzt'Kd.V3,2.psf
F:= GC;qz F= 52.74 psf
Pwind unit F L•hm Pwind unit = 927.78 lb
Pwind F'L'hmc Pwind= 1286.1 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fven qi GCr vert Fven=41.64 psf
Pwind unit vert := Fvert'L'wm Pwind unit vert = 894.1 lb
Punit_ven 0.6WP - 0.6Pwind_unit_vert Punit-vert =-247.86 lb
Pvert ASD 0.6Wt-0.6Pwind unit vert Pven ASD =—187.86lb
Pvert LRFD:= 0.9Wt— 1.OPwind unit ven Pvert LRFD 371.2Ib
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU\TRANE
\WOOD\IateralMECH RTU curb 3
G u3
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
h (hml
m Mot_seismic unit Fpunit' —
Mot_wind_unit = Pwind_unit'2 - \ 2 ,
M — 1401.341bft Mot_seismic_unit = 308.77Ibft
of wind unit
F — (0.6Mot_wind_unit) — Punit_vert (0.7•Mot_seismic_unit) _ (0.6— 0.7.0.2•Sps)•Wp
upwind unit •= u seismic_unit
w •= We
c 2 Fp_ 2
unit =368.53 Ib
Fup_wind Fup seismic_unit ——52.8 lb
0.6•Pwind_unit =556.671b 0.7•Fpunit = 143.1 lb
WIND GOVERNS RTU UNITTO CURB
ATTACHMENT
Design attachment for 557 lb sliding and 369 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit =556.67 lb Fup_wind_unit =368.53 lb
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP:= 401Ib 0.6Pw,ind unit =556.67 lb
0.6Pwind_unit
USHEAR USHEAR=0.694
2'VCLIP
Fup wind_unit
UUPLIFT UUPLIFT=0.92
I•VCLIP
Use(1)dip per side—(4)total
E:\adcadd\19\00000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU\TRANE
\WOOD\IateralMECH RTU curb 3
-rue
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc (hmcl
Mot_wind_total Fwind'2 Mot_seis_total= Fp'l -
2
Mot wind_total =2692.76Ibft Mot seis total = 517 lbft
0.6(Mot_wind_total) 1'vert_ASD (0.7'Mot_seis_total) (0.6— 0.7.0.2•SW.(WO
Fup_wind total — Fup_sets_total —
wc 2 we 2
Fup windtotal =563.94 lb Fup_seis_totai _ --34.45lb
0.6•P771.66 lb
0.7•Fp= 172.85lb
wind=
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 772 lb sliding and 564 lb uplift at curb to roof connection
0.6•Pwind= 771.66 lb Fup_wind_total =563.94 lb
Try#12x3"WOOD SCREWS EACH SIDE—Ling side to take tnsion, shortsdestotals shear
!screw 3 in length of screw
5.
Lp iscrew —8 Lp =2.38 in
screw length-Sheathing-tapered tip 2
dthread I thread length
` screw'3
dscrew 0.216in Screw diameter
LP Wthread 154•lb withdrawal capacity per inch
Cp:= Cp= l.1 in
10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallow I.6.1561b•Cp Vallow=249.6 lb
Tallow I.6•d thread'Wthread Tallow,= 492.8 lb
0.6.Pwind
USHEAR USHEAR=0.773
4•Vallow
Fupwind_total
UUPLIFT UUPLIFT= 0.57
2'Tallow
Use(2)#12x3"screws per side—(8)screws total
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structurai\RTU\TRANE
\WOODUateraIMECH RTU curb 3
Yus.
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-TRANE 4 TON UNIT
WP:= 642Ib Weight of unit We:= 100Ib Weight of(E)curb
Wt:= WP+ We Wt= 742 lb
L:= 88.625in Length of unit Le:= 88in Length of Curb
wm:= 53.25in Width of unit wt:= 51.25in Width of curb/curb adapter
hm:= 40.875•in Height of unit
tic:= 14•in Height of curb
hmc:= hm + he hme=54.88 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND,OR)
Design
SOS:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVERAREA
h := 1 Oft IP:= 1.0 aP:= 2.5 RP.= 6 z:= h Air side HVAC component
0.4•a •SDs'1 z
FPunit= RP P•4 1 + 2• )•WP FPunit =272.85 lb 0.7•Fpunit = 190.99 lb
0.4.8p.SDS•I ( `\\ zl
Fp:= P. 1 + 2•h i•Wt Fp=315.35 lb 0.7•Fp=220.74lb
P ` J
WIND LOAD: BASED ON 2012 IBC/ 2014 OSSC
V3s:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KzL:= 1.0 GCr:= 1.9 GCr vert 1.5
9z:= 0.00256•Kh•Ke Kd•V3$2•psf
F:= GCS qz F= 52.74 psf
Pwind unit F•L•hm Pwindunit = 1326.87 lb
Pwind F•L•hmc Pwind= 1781.34 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fvert:= gz'GCr vert Fvert=41.64 psf
Pwind unit vert Fvert'L'Wm Pwind unit vert = 1364.67 lb
Punit_vert 0.6WP 0.6Pwind_unit vert Punit_vert =—433.6lb
Fvert ASD 0.6Wt 0.6Pwind unit vert Pven ASD =—373.61b
Fvert LRFD 0.9Wt— 1.0Pwind unit vert Fvert RFD =—696.87 lb
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\StructuraI\RTU\TRANE
\WOOD\lateralMECH RTU curb 4
Tub
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hm\
hm
Mot_wind_unit Pwind_uni seismic unit ••= FP Mot_t'2 2
Mofwindunit —
— 2259.83 lb ft Mot_seismic_unit =464.71b ft
(0.6Mot_wind unit Punit_vert (0.7•Mot seismic_unit) (0.6-0.7•0.2•Sps).Wp
Fup_wind unit — Fup_seismic_unit :_
w w '•
c 2 2
Fup_wind_unit =534.28 lb Fup seismic_unit =—78.24 lb
0.6•Pwind_unit = 796.12lb 0.7•Fpunit = 190.99 lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 797 lb sliding and 535 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit =796.12 lb Fup_wind,_unit =534.28 lb
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP 4011b 0.6Pwind unit 796.12 lb
0.6Pwind unit
USHEAR:= USHEAR= 0.496
4•Vcup
Fup_Wind unit
UUPL1FT UUPLIFr=0.67
2'VCLIP
Use(2)clip per side—(8)total
E:\adcadd119100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU\TRANE
\WOOD\lateralMECH RTU curb 4
Tu•7
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc hmc`
Mot_wind_total wind 2 Mot seis_total := FP' 2
l
Mot wind total =4072.96 lb ft Mot seis total =721.03 lb ft
0.6(Mot wind_total) Pvert_ASD (0•7Mot_sets total) (0.6- 0.7.0.2.SDs).(W)
Fup wind_total — 2 Fup_seis_total w _ 2
c
Fup_wind_total =759 lb Fup_seis_total =—60.27 lb
0.7•Fp=220.74 lb
0.6•Pwind= 1068.8 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 10691b sliding and 789b uplift at curb to roof connection
0.6•Pwind= 1068.8 lb Fup_wind_total =759 lb
Try#12x3"WOOD SCREWS EACH SIDE—Long side to take tension, short sides to take shear
(screw:= 3 to length of screw
LP:= 'screw - 8 in Lp =2.38 in
screw length-Sheathing-tapered tip 2
dthread:= screw'3 thread length
dscrew:= 0.216in Screw diameter
LP Wthread 154.Lb withdrawalcapacity per inch
C := C = 1.1 in
p I0•dscrew p
Cp:= if(Cp> 1.0,1.0,Cp) CP= 1
Vallow:= 1.6.1561b•Cp Vallow= 249.6 lb
Tallow:= I.6•dthread'Wthread Tallow=492.8 lb
0.6•Pwind
USHEAR:= USHEAR = 0.714
6•Vallow
Fuptvind total
UUPLIFT:= UUPLIFT=0.51
3'Tallow
Use(3)#12x3"screws per side-(12)screws total
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 20191Structural\RTU\TRANE
\WOOD\lateraIMECH RTU curb 4
TUF
CIDA RTU RNH
TEL: (503) 226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNITATTACHMENT LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-TRANE 12.5 TON UNIT
Wp:= 19781b Weight of unit We:= 100lb Weight of(E)curb
Wt:= Wp+ We Wt=2078 lb
L:= 121.6875in Length of unit Lc:= 121 in Length of Curb
wm := 84.1875 in Width of unit we:= 81.18754-Width of curb/curb adapter
hip:= 64.125•in Height of unit
hc:= 14•in Height of curb
hmc:= hm+ he hmc= 78.13 in Total heightof unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
SDS:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVERAREA
h := l Oft Ip:= 1.0 ay•:= 2.5 RP:= 6 z: h Air side HVAC component
0.4•a •Sps•I z
__ P P
FP°n't. 1 + 2 W F840.65 lb 0.7•F 588.45 lb
Rp h Punit = Punit=
0.4•ap SDS'Ip z
Fp := R 1 + 2•z)•Wt Fp = 883.15 lb 0.7•Fp=618.21b
)J
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
Vas: 135 Exposure B
Kd:= 0.85 Kh:= 0.7 Kzt:= 1.0 GCr:= 1.9 GCr ven= 1.5
qz:= 0.00256•Kh•Kn•Kd•V3,2•psf
F:= GCr qz F= 52.74 psf
Pwind_unit F'L'hm Pwind unit = 2858.18 lb
kind F'L'hmc Pwind = 3482.18 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fven qz GCr ven Fvert =41.64 psf
Pwind_unit_vert Fven'L'wm wind unit vert =2962.42 lb
Punit_vert 0.6Wp-0.6Pwind_unit_vert Punit_vert =-590.65 lb
Pvert_ASD 0.6Wt -0.6Pwind_unit_ven PvertASD=-530.65 lb
Pvert_LRFD 0.9Wt- LOPwind unit vert Pvert LRFD=-1092.22 lb
E:1adcadd\19100000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU\TRANE
\WOOD\IateralMECH RTU curb 12.5
TU'
CIDA RTU RNH
TEL: (503) 226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
Chm�
hm Mot seismic unit '= Fpunit'
Mot_wind_unit Pwind_unit-2 2 ,j
M — 7636.691bft Mot_seismic_unit = 2246.11 Ibft
of wind unit —
(0.6Mot_wind_unit) Punit_ven (0.7•Mot seismic unit) (0.6— 0.7.0.2•SD4 Wp
Fup wind_unit Fup seismic_unit
w 2
c 2 w c
Fup_wind_unit =972.58 lb Fup_seismic_unit 243.32 lb
0,6•Pwind unit = 1714.91 lb 0.7.Fpunit = 588.45 lb
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 1,715 lb sliding and 973 lb tension at unit to curb connection—18GAcurb
0.6•Pwind_unit = 1714.91 lb Fup_wincLumt =972.58 lb
Try 16GAx 6"clip with(4)#10 screws per cep
VCLIP:= 401 lb 0-6Pwind unit = 1714.91 lb
0.6Pwind_unit
USHEAR USHEAR=0.713
6•VCLIP
Fup—wind_unit
UUPLIFT UUPLIFT=0.81
3 VCL1P
Use(3)clip per side—(12)total
E:\adcadd119\00000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU\TRANE
\WOODllateraIMECH RTU curb 12.5
CIDA RTU TN
RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturninq at unit to curb SEISMIC-Overtuminq at unit to curb
hmc (hmc�
Mot_wind_total:= kind*z Mot_seis_totai FP. —
2
Mot_wind_total = 11335.23lb ft Mot leis_total =}}2874.84 lb ft
0.6(Mot_wind_total) Pvert ASD (0.7•Mot_seis_total) (0.6 — 0.7.0.2.s ).(W)
Fup_wind_total — Fup_seis_total _
we 2 we 2
= 1270.58 lb Fup_seis_total =—202.32lb
Fup_wind_total
0.6•P =2089.31 lb
0.7•Fp = 618.216
wind
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 2090Ib sliding and 1301Ib uplift at curb to roof connection
0.6•Pwind=2089,31 lb Fup_wind_total = 1270.58 lb
Try#12x3"WOOD SCREWS EACH SIDE—Lang side to take bnson, shortsdes to tale shear
(screw l= 3 in length of screw
Lp:= 'screw — 8—in Lp =2.38 in
screw length-Sheathing-tapered tip 2
dthread !screw•3 thread length
dscm,v := 0.216in Screw diameter
LP `"thread:= 154•lb withdrawal capacity per inch
Cp:= Cp= 1.1 in
10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= 1
Vallow` 1.6.1561b•Cp Va11ow= 249.6 lb
Tallow I.6•dthread'w'thread Tallow=492.8 lb
0.6•Pwind
USHEAR•= USHEAR= 0.837
10•V
allow
Fup_wind_total
UUPLIFT UUPLIFT=0.52
5'Tallow
Use(5)#12x3"screws per side—(20)screws total
E:\adcadd119\00000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU\TRANE
\WOOD\lateralMECH RTU curb 12.5
Ti{if
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
RTU DESIGN ON 14"CURB-TRANE 25 TON UNIT
Wp:= 18781b Weight of unit We:= 10016 Weight of(E)curb
Wt:= Wp+ We Wt= 1978113
L:= 121.6875in Length of unit Le:= 121 in Length of Curb
Wm:= 84.1875 in Width of unit we:= 81,1875 inWidth of curb/curb adapter
hm:= 64.125•in Height of unit
he:= 14.in Height of curb
hmu:= hm+ he hme=78.13 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (PORTLAND, OR)
Design
SDS:= 0.85 CONSERVATIVE FOR PORTLANDNANCOUVER AREA
h := l 0ft 1p:= 1.0 ap:= 2.5 RP:= 6 z:= h Air side HVAC component
0.4•aP SDS•lp /
Fpunit= RP \1 + 2' •Wp Fpunit =798.15 lb 0.7•Fpunit= 558.71b
0.4ap SDS•Ip / zl
Fp:_ • 1 + 2•— •Wt Fp = 840.65 lb 0.7.Fp= 588.45 lb
RP h,
WIND LOAD: BASED ON 2012 IBC/2014 OSSC
Vas:= 135 Exposure B
Kd:= 0.85 Kh:= 0.7 KZt:= 1.0 GCr:= 1.9 GCrven:= 1.5
qz:= 0.00256.Kh•KZt•Kd•V3,2.psf
F:= GCr qZ F= 52.74 psf
Pwind unit F•L•hm Pwind_unit = 2858.18 lb
Pwind:= F•L•hme Pwind= 3482.18 lb
WIND LOAD: BASED ON 2012 IBC/ASCE7-10-VERTICAL
Fven qi GCr ven Fvert= 41.64 psf
Pwind unit vert ` Fvert•L•Wm Pwind_unit_vert =2962.42 lb
Punit_vert = 0.6Wp-0.6Pwind_unit_vert Punit_vert =-650.65 lb
Pvert_ASD 0.6Wt-0.6Pwind_unit_vert Pvert_ASD = -590.65lb
Fvert LRFD 0.9Wt - 1.0Pwind_unit_ven Pvert_LRFD=-1182.22 lb
E:\adcadd\19\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU\TRANE
\WOOD\lateralMECH RTU curb 25
CIDA RTU TGIZ
TEL: (503)226-1285 AMERICAN HEATING STANDARDS RNH
7/24/2019
FAX: (503)226 1670
OVERTURNING-RTU UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.60+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
h
m
Mot_wind_untt Pwind_unit' m Mot_seismic_unit FPumt" 2
M 7636.69lbft Mot-seismic-unit = 2132.56 Ibft
of wind unit = 1 }}
F (0.6Mot wind_unit) _ Punit_vert (0.7•Mot_seismic_unit) (0.6—0.7.0.2SoS).Wp
up wind_unit Fup_s _u eismicnit •—
2 —
We we 2
Fup_wind_unit = 1002.58 lb Fup_seismic_unit = -231.02 lb
0.6•Pwind_unit = 1714.91 lb 0.7.FPunit =558.71b
WIND GOVERNS RTU UNIT TO CURB
ATTACHMENT
Design attachment for 1,715 lb sliding and 1,003 lb tension at unit to curb connection-18GAcurb
0.6•Pwind_unit = 1714.91 lb Fup_wind_unit = 1002,58 lb nSCREW 4
Try 16GAx 6"clip with(4)#10 screws per clip
VCLIP 401 Ib 0.6Pwind unit = 1714.91 lb
0.6Pwind_unit
USHEAR USHEAR =0.7I 3
6•VCLIP
Fup_wind_unit
UUPLIFT••- UUPLIFT=0.83
3•VCLIP
Use(3)clip oerside-(12)total
E:\adcadd119\00000-2019 Mechanical
Units10237.01 American Heating
Standards 20191Structural\RTU\TRANE
\WOOD1lateraIMECH RTU curb 25
11413
CIDA RTU RNH
TEL: (503)226-1285 AMERICAN HEATING STANDARDS 7/24/2019
FAX: (503)226 1670
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at unit to curb SEISMIC-Overturning at unit to curb
hmc hmc\
Mot wind total Pwind' 2 Mot_seis_total Fp' 2
Mot wind total = 11335.23 lb ft Mot secs total = 2736.49 lb ft
0.6(Mot_wind_total) Pven_ASD (0.7'Mot_seis_total) (0.6- 0.7.0.2•S124(W)
Fup_wind total w - 2 Fup sets_total W 2
c
Fop wind_total = 1300.58 lb Fup seis_total = —192.58 lb
0.6•P 2089.31 lb
0.7.Fp = 588.45lb
wind =
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 20901b sliding and 13311b uplift at curb to roof connection
0.6•Pwind=2089.31 lb Fup_wind_total = 1300.58 lb
Try#12c3"WOOD SCREWS EACH SIDE—Long side to take tension, thortsdes to take shear
!screw 3 in length of screw
LP ` 'screw — 8[n Lp =2.38 in
screw length-Sheathing-tapered tip 2
dlhread= 'screw'3 thread length
dscrew 0.216in Screw diameter
LP Wthread 154•lb withdrawal capacity per inch
C := C = 1.1 in
p 10•dscrew
Cp:= if(Cp> 1.0,1.0,Cp) Cp= I
Vallow:= 1.6.1561b•Cp Vallow= 249.6 lb
Tallow= 1•6'dthread'"'thread Tallow=492.8 lb
0.6•Pwind
USHEAR 10•V USHEAR= 0.837
al low
Fup wind_total
UUPLIFT UUPLIFT=0.53
5•Tallow
Use(5)#12x3"screws per side—(20)screws total
E:\adcadd119\00000-2019 Mechanical
Units\0237.01 American Heating
Standards 2019\Structural\RTU\TRANE
\WOOD\IateratMECH RTU curb 25