Series DS-1 Dry-Type Sprinklers
• 5.6K Pendent, Upright, and Horizontal Sidewall
Quick Response, Standard Coverage
General having jurisdiction. Failure to do so
may impair the performance of these ' i
Description devices.
The owner is responsible for maintain-
TYCO Series DS-1 Dry-Type Sprinklers, ing their fire protection system and
5.6K Pendent, Upright, and Horizontal devices in proper operating condi-
Sidewall,Quick Response(3 mm bulb) tion. Contact the installing contrac /,
-
and Standard Coverage are decora- tor or product manufacturer with any
tive glass bulb automatic sprinklers questions.
designed for commercial use.Dry-type The Series DS-1 Dry-Type Sprinklers )
sprinklers are typically used where: must only be installed in fittings that
• pendent sprinklers are required on meet the requirements of the Design
dry pipe systems that are exposed Criteria section.
to freezing temperatures (e.g.,
sprinkler drops from unheated Sprinkler
portions of buildings)
• sprinklers and/or a portion of the Identification
connecting piping are exposed to
freezing temperatures;for example, Numbers (SINS)
sprinkler drops from wet systems
into freezers, sprinkler sprigs 3/4 in.NPT:
into unheated TY3935 —Hors Pendent
from wet systems
TY3735 —HrizontalSidewall
• attics, or horizontal piping exten-
sions through a wall to protect an 1 in.NPT.
unheated areas such as loadingTY3235 —U
TY3135 —Uprightpright
endent
docks, overhangs, and building TY3335 -Horizontal Sidewall
exteriors
• sprinklers are used on systems that
Technical
are seasonally drained to avoid Data
freezing (e.g.,vacation areas)
Approvals
NOTICE UL and C-UL Listed Temperature Ratings
The Series DS-1 Dry-Type Sprinklers FM Approved Refer to Tables A and B
described herein must be installed NYC Approved under MEA 352-01-E Finishes
and maintained in compliance with this Previous New York City Approval and Sprinkler:Natural Brass,Chrome Plated,
document,as well as with the applica- MEA certification numbers apply to or Signal White
ble standards of the National Fire Pro- product as shown in this data sheet. Escutcheon:Signal White,Chrome Plated,
tection Association(NFPA),in addition In accordance with Section BC 3502 or Brass Plated
to the standards of any authorities of the Construction Code,current NYC
Approvals for use in the City of New Physical Characteristics
IMPORTANT York apply to all products that contain Inlet Copper
Refer to Technical Data Sheet UL or FM Approvals and Listings; Yok Copper
gPP g Yoke Stainless Steel
TFP2300 for warnings pertaining to therefore, not all products currently Casing Galvanized Carbon Steel
regulatory and health information. Approved for use in the City of New Insert Bronze
York will carry an actual MEA Certifi- Bulb Seat Stainless Steel
Always refer to Technical Data cation number. Bulb Glass
Sheet TFP700 for the `INSTALLER Compression Screw Bronze
WARNING" that provides cautions Refer to Tables A and B. Deflector Bronze
with respect to handling and instal- Maximum Working Pressure Frame Bronze
ration of sprinkler systems and corn- 175 psi(12,1 bar) Guidet Tube Stainless Steel
ponents. Improper handling and Inlet Thread Connections Spring Stainless Steel
installation can permanently damage 3/4 in.NPT Plug Spring' Stainless Steel
a sprinkler system or its compo- Sealing Assembly. Beryllium Nickel w/TEFLON
- nents and cause the sprinkler to fail 1 in.NPT or ISO 7-R 1 Escutcheon Carbon Steel
- to operate in a fire situation or cause Discharge Coefficient 'For 3/4 Inch NPT only
. ' it to operate prematurely. K=5.6 gpm/psi1/2(80,6 Ipm/bar1/2)
Page 1 of 10 AUGUST 2018 TFP510
TFP510
Page 2 of 10
PLUG WITH ? +P, INLET Operation
SEALING i -1
ASSEMBLY111111
t When the TYCO Series DS-1 Dry-Type
YOKE Sprinklers,5.6K Pendent, Upright,and
1 4 Horizontal Sidewall, Quick Response
PLUG VIM (3 mm bulb) and Standard Coverage
SPRING ( 'E� BAND are in service, water is prevented from
Ientering the assembly by the Plug with
mm, iii Sealing Assembly in the Inlet of the
WATER 1 SPRING Sprinkler.See Figures 1 and 2.
TUBE 1 CASING The glass bulb contains a fluid that
11111 a expands when exposed to heat.When
the rated temperature is reached, the
GUIDE 1� _, INSERT fluid expands sufficiently to shatter
TUBE 1 the glass Bulb, and the Bulb Seat is
released.
ULB
Ilk
SEATThe compressed Spring is then able
FRAME 'fe SEAT to expand and push the Water Tube as
�I,G0 well as the Guide Tube outward. This
3 mm BULB action simultaneously pulls inward on
VENT HOLE 1I� �i1 the Yoke, withdrawing the Plug with
lk ig Sealing Assembly from the Inlet and
— COMPRESSION allowing the sprinkler to activate and
DEFLECTOR ., SCREW flow water.
FIGURE 1 Design
SERIES DS-1, 3/4 INCH NPT, DRY-TYPE SPRINKLER
ASSEMBLY Criteria
The TYCO Series DS-1 Dry-Type Sprin-
PLUG WITH crkval INLET klers, 5.6K Pendent, Upright,and Hor-
SEALING / lir izontal Sidewall, Quick Response
ASSEMBLY ; ill' (3 mm bulb) and Standard Cover-
il•i4
YOKE age are intended for use in fire sprin-
kler systems designed in accordance
SPRING _ INLET with the standard installation rules
�� recognized by the applicable Listing
'.._.�4 BAND or Approval agency; for example,
WATER ti1111
iml t UL Listing is based on NFPA 13
requirements.
TUBE 1 CASING Sprinkler Fittings
Install the 3/4 or 1 inch NPT Series
GUIDE t INSERT DS-1 Dry-Type Sprinklers in the 3/4 or
TUBE k MI% 1 inch NPT outlet or run of the follow-
1 ing fittings:
�� SEAT • malleable or ductile iron threaded
FRAME 1pm tee fittings that meet the dimen-
kr �i sional requirements of ANSI B16.3
, (Class 150)
111.1 3 mm BULB
VENT HOLE ' II • cast iron threaded tee fittings that
meet the dimensional requirements
COMPRESSION of ANSI B16.4(Class 125)
DEFLECTOR __.___ SCREW Do not install the DS-1 Sprinklers
FIGURE 2 into an elbow fittings. The Inlet of the
SERIES DS-1, 1 INCH NPT AND ISO 7-R 1 DRY-TYPE SPRINKLER sprinkler can contact the interior of the
ASSEMBLY elbow, potentially damaging the Inlet
seal.
The unused outlet of the threaded tee is
plugged as shown in Figure 13.
You can also install the Series DS-1
Dry-Type Sprinklers in the 3/4 or 1 inch
NPT outlet of a GRINNELL Figure 730
Mechanical Tee. However, the use of
the Figure 730 Tee for this arrangement
is limited to wet pipe systems.
TFP510
Page 3 of 10
3/4 Inch NPT
TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Recessed Escutcheon with Standard Escutcheon Distance of 4 to 12 inches
(Figure 4) (Figure 3) (100 to 300 mm)
with Deep Escutcheon with Standard Escutcheon
(Figure 5) (Figure 8)
without Escutcheon with Deep Escutcheon
(Figure 6) (Figure 9)
without Escutcheon
(Figure 10)
Temperature Bulb Finish
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F(57°C) Orange
155°F(68°C) Red
175°F(79°C) Yellow 1,2 1,2 1*,2*
200°F(93°C) Green
286°F(141°C) Blue
Notes:
1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches)
Light and Ordinary Hazard occupancies only
TABLE A
3/4 INCH NPT SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
1 Inch NPT(and ISO 7-R 1)
TY3235 Pendent TY3235 Pendent TY3335 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Recessed Escutcheon with Standard Escutcheon Distance of 4 to 12 inches
(Figure 4) (Figure 3) (100 to 300 mm)
with Deep Escutcheon with Standard Escutcheon
(Figure 5) (Figure 8)
without Escutcheon with Deep Escutcheon
(Figure 6) (Figure 9)
TY3135 Upright without Escutcheon
without Escutcheons (Figure 10)
(Figure 7)
Temperature Bulb Finish
Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F(57°C) Orange
155°F(68°C) Red 1,2,3,4 1,2,4
175°F(79°C) Yellow 1,2,3,4 1,2,4 1*,2*,3**,4 1*,2*,4
200°F(93°C) Green
286`F(141°C) Blue 1,2,4
Notes:
1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches)
3. Approved by Factory Mutual Research Corporation(maximum order length of 48 inches)
4. Approved by the City of New York under MEA 352-01-E
5. The Upright Sprinkler without an Escutcheon(TY3135)is available in 1 inch NPT only
Light and Ordinary Hazard occupancies only
Light Hazard occupancies only
TABLE B
1 INCH NPT(AND ISO 7-R 1)SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP510
Page 4 of 10
SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)
FACE OF \ FACE OF \ FACE OF \
SPRINKLER \ SPRINKLER \ SPRINKLER \
FITTING }}} _ FITTING 'f FITTING }
• \ _ __ \ L -J I \ L
I
ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2" DIA.
2-3/4"to 48" 1-3/4" DIA. 3-3/4"to 48" 1/2"to 46" (88,9 mm)
(69,9 to 1219,2 mm) (44,5
44,5 mm) (95,3 to 1219,2 mm) (12,7 to 1168,4 mm) 2-1/2" DIA.
IN 1/4"(6,4 mm) IN 1/4"(6,4 mm) 2-1/4" DIA. IN 1/4" (6,4 mm)
INCREMENTS INCREMENTS (57,2 mm) INCREMENTS (63,5 mm...
(
____ 1 FACE OF I • • �
FACE OF CEILING . FACE OF'
CEILING rill I I ��IIIV CEILING ' .
. 4-1/4"t 1/8"
(108,0±3,2 mm)
2-3/16"±1/8" 3" DIA. 1-3/8"±1/8" 2-7/8" DIA.
(55,6±3,2 mm) (76,2 mm) (34,9±3,2 mm) (73,0 mm) l [tit
FIGURE 3 FIGURE 4 FIGURE 5
PENDENT TY3235 AND TY3935 PENDENT TY3235 AND TY3935 PENDENT TY3235 AND TY3935
WITH STANDARD WITH RECESSED WITH DEEP
ESCUTCHEON ESCUTCHEON ESCUTCHEON
SPRINKLER FITTING /
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR
FACE OF \
SPRINKLER
FITTING
ORDER LENGTHS:
5"to 48"
(127,0 to 1219,2 mm)
ORDER LENGTHS: IN 1/4"(6,4 mm)
• 5"to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4"(6,4 mm)
INCREMENTS FACE OF
1
SPRINKLER ow
FITTING
MINIMUM t - 71-3/4"(44,5 mm)
DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 6 FIGURE 7
PENDENT TY3235 AND TY3935 UPRIGHT TY3135
WITHOUT WITHOUT ESCUTCHEON
ESCUTCHEON 1 INCH NPT ONLY
TFP510
Page 5 of 10
ORDER LENGTHS: The configuration shown in Figure 12
2-3/4"to 48"(69,9 to 1219,2 mm) is only applicable for wet pipe systems
IN 1/4"(6,4 mm)INCREMENTS where the sprinkler fitting and water-
_ 2-3/8"t 1/8" filled pipe above the sprinkler fitting are
. (60,3±3,2 mm) not subject to freezing and where the
FACE OF FACE OF length of the Dry-Type Sprinkler has the
— SPRINKLER MOUNTING minimum exposure length depicted in
FITTING SURFACE \� Figure 11.Refer to the Exposure Length
section.
For wet pipe system installations of
[ 3" DIA. the 1 inch NPT Series DS-1 Dry-Type
(76,2 mm) Sprinklers connected to CPVC piping,
---,-,,,, -' ..--/‘
3.5° use only the following TYCO CPVC
SPRINKLER FITTING 1-3/4"DIA. fittings:
(REFER TO DESIGN (44,5 mm) CENTERLINE 5/16" • 1" x 1" NPT Female Adapter (P/N
CRITERIA SECTION) OF WATERWAY (7,9 mm) 80145)
FTY3335 AND TY3735 Adapter HORIZONAL SIDEWALL GURE 8 • x 1" x Sprinkler Head
Adapter Teee (P/N 80249)
WITH STANDARD ESCUTCHEON For wet Y pipe e system installations of the
the 3/4 inch NPT Series DS-1 Sprin-
ORDER LENGTHS: klers connected to CPVC piping, use
1/2"to 45-3/4"(12,7 to 1162,1 mm) in the 3/4"x 3/4" NPT Female Adapter
IN 1/4"(6,4 mm)INCREMENTS (P/N 80142).
I 4-1/4"t 1/8"
2-1/2" DIA. FACE OF (108,0 t 3,2 mm) For dry pipe system installations, use
FACE OF (63,5 mm) MOUNTING only the side outlet of maximum 2-112-
SPRINKLER , SURFACE inch reducing tee when locating the
FITTING \��\' S} the'es braDS-1 nch line. Otherrinklers wise,tluseelow
the
■`� _ configuration shown in Figure 13 to
3-1/2"DIA. assure complete water drainage from
IIIIIIIIIIIIII_`jJ (88,9 mm) above the Series DS-1 Dry-Type Sprin-
3.5° klers and the branch line. Failure to do
�` ! so may result in pipe freezing and water
10
SPRINKLER FITTING damage.
- (REFER TO DESIGN CENTERLINE 5/16"
CRITERIA SECTION) OF WATERWAY (7,9 mm) NOTICE
FIGURE 9 Do not install the Series DS-1 Dry-Type
• TY3335 AND TY3735 HORIZONAL SIDEWALL Sprinkler into any other type fitting
WITH DEEP ESCUTCHEON without first consulting the Technical
Services Department.Failure to use the
ORDER LENGTHS: appropriate fitting may result in one of
- 5-1/2"to 48"(139,7 to 1219,2 mm) _ the following:
IN 1/4"(6,4 mm)INCREMENTS MINIMUM • failure of the sprinkler to operate
2-1/4"(57,2 mm) properly due to formation of ice
FACE OF - - DEFLECTOR TO over the inlet Plug or binding of the
SPRINKLER MOUNTING Inlet Plug
FITTING SURFACE • insufficient engagement of the
Inlet pipe threads with consequent
leakage
Drainage
�, „ �� In accordance with the minimum
/ 3.5° 5/16„ requirements of the National Fire Pro-
(7,9 mm) tection Association for dry pipe sprin-
SPRINKLER FITTING
(REFER TO DESIGN CENTERLINE kler systems, branch, cross, and
CRITERIA SECTION) OF WATERWAY feed-main piping connected to Dry
Sprinklers and subject to freezing tern-
FIGURE 10 peratures must be pitched for proper
TY3335 AND TY3735 HORIZONAL SIDEWALL drainage.
WITHOUT ESCUTCHEON Exposure Length
When using Dry Sprinklers in wet pipe
sprinkler systems to protect areas
subject to freezing temperatures, use
TFP510
Page 6 of 10
/ -
_ RUN
FACE OF I I TO WET SIDE O OUTLET
SPRINKLER J SYSTEM OUTLET l PLUGGED '
FITTING PLUGGED \
\� , -y r-'' SPRINKLER •
HEATED TO DRY FITTING
HEATED EXPOSURE AREA (SEE DESIGN
AREA LENGTH SYSTEM CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA D8B-2 SPRINKLER AREA
INTENDED SECTION) INTENDED FITTING SUBJECT DSB-2
FOR FREEZER FOR FREEZER (SEE DESIGN TO INTENDED
STRUCTURES STRUCTURES CRITERIA FREEZING FOR FREEZER
SECTION) A,STRUCTURES
N --'\\ -)7
ir
FIGURE 11 FIGURE 12 FIGURE 13
EXPOSURE SPRINKLER FITTING SPRINKLER FITTING
LENGTH HEATED AREA UNHEATED AREA
STRAP TIES 1-3/4' DIA.
• (ENDS ON (44,5 mm)
7 OPPOSING CLEARANCE INSULATED
SIDES OF HOLE FREEZER WRENCH
BOOT) ADHESIVE STRUCTURE RECESS
/ /-DSB-2 BOOT
DSB-2\ /
ADHESIVE BOO., - i , \ IIIMEI il
Ail
__„_--ADHESIVE
CLEARANC1-3/45" DIA.EI WRENCH I �I
(44, mm) �III ��I III FLAT
I\ 10 ` v HOLE
INSULATED \ /I PUSH WRENCH
FREEZER 1INTO ENSURE
• � STRUCTURE I / ENGAGEMENT
STRAP TIES
MN
DS-1 (ENDS ON DS-1 WITH SPRINKLER
g`NO
SHOWN WITH OPPOSING SHOWN RIDH WRENCHING AREA
STANDARD SIDES OF ESCUTCHEON
ESCUTCHEON BOOT)
FIGURE 14 FIGURE 15 FIGURE 16
MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER W-TYPE 7
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES SPRINKLER
DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER WRENCH
TFP51O
Page 7 of 10
meet the requirements of the Design
Temperatures for Heated Areal Criteria section. Refer to the Design
Criteria section for other important
Ambient Temperature 40°F 50°F 60°F requirements regarding piping design
Exposed to (4°C) (10°C) (16°C) and sealing of the clearance space
Discharge End of Sprinkler Minimum Exposed Barrel Length2, around the Sprinkler Casing.
- Inches Do not install any bulb-type sprinkler
(mm) if the bulb is cracked or there is a loss
40°F of liquid from the bulb. With the sprin-
(4°C) 0 0 0 kler held horizontally,a small air bubble
should be present.The diameter of the
30°F air bubble is approximately 1/16 inch
(-1°C) 0 0 0 (1,6 mm)for the 135°F(57°C) rating to
20°F 4 1/8 inch(3,2 mm)for the 286°F(141°C)
(-7°C) (100) 0 0 rating.
10°F 8 1 • A leak-tight 3/4 inch NPT sprinkler
(-12°C) (200) (25) 0 joint should be obtained by applying
a minimum-to-maximum torque of
0°F 12 3 10 to 20 ft.-lbs. (13,4 to 26,8 Nm).
(-18°C) (305) (75) 0 • A leak-tight 1 inch NPT sprinkler
-10°F 14 4 1 joint should be obtained by applying
(-23°C) (355) (100) (25) a minimum-to-maximum torque of
20 to 30 ft.-lbs. (26,8 to 40,2 Nm).
-20°F 14 6 3 Higher levels of torque can distort the
(-29°C) (355) (150) (75) sprinkler Inlet with consequent leakage
-30°F 16 8 4 or impairment of the sprinkler.
(-34°C) (405) (200) (100) Do not attempt to compensate for
-40°F 18 8 4 insufficient adjustment in an Escutch-
(-40°C) (455) (200) (100) eon Plate by under or over-tightening
-50°F 20 10 6 the sprinkler. Re-adjust the position of
(-46°C) (510) (255) (150)(-46°C)
sprinkler fitting to suit.
Step 1. Install pendent sprinklers only
-60°F 20 10 6 in the pendent position, and install
(-51°C) (510) (255) (150) upright sprinklers only in the upright
position.The deflector of a pendent or
Notes: upright sprinkler must be parallel to the
1. For protected area temperatures that occur between values listed above,use the next ceiling.
_ cooler temperature.
2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). Install horizontal sidewall sprinklers in
the horizontal position with their cen-
TABLE C terline of waterway perpendicular to
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS the back wall and parallel to the ceiling.
MINIMUM RECOMMENDED LENGTHS Ensure the word"TOP"on the Deflector
faces the ceiling.
Table C to determine a sprinkler's build-up can occur that might damage Step 2. With a non-hardening pipe-
appropriate exposed barrel length to the dry-type sprinkler and/or prevent thread sealant such as TEFLON tape
prevent water from freezing in the con- proper operation in a fire situation. applied to the Inlet threads, hand-
necting pipes due to conduction. The Use of the Model DSB-2 Dry Sprin- tighten the sprinkler into the sprinkler
exposed barrel length measurement kler Boot, described in Technical Data fitting.
must be taken from the face of the Sheet TFP591 and shown in Figures 14
sprinkler fitting to the surface of the and 15,can provide the recommended Step 3. Wrench-tighten the sprinkler
structure or insulation that is exposed l using either:
sea.
to the heated area. Refer to Figure 11 • a pipe wrench on the Inlet Band or
for an example. the Casing (Ref. Figures 1 and 2)
Clearance Space Installation
• the W-Type 7 Sprinkler Wrench on
In accordance with NFPA 13, when The TYCO Series DS-1 Dry-Type Sprin- the Wrench Flat(Ref. Figure 16)
connecting an area subject to freez- klers,5.6K Pendent, Upright,and Hori-
ing and an area containing a wet pipe zontal Sidewall,Quick Response(3 mm Apply the Wrench Recess of the
sprinkler system, the clearance space bulb) and Standard Coverage must W-Type 7 Sprinkler Wrench to the
around the sprinkler barrel of Dry-Type be installed in accordance with this Wrench Flat.
Sprinklers must be sealed. Due to section.
temperature differences between two
areas,the potential for the formation of General Instructions
condensation in the sprinkler and sub- The Series DS-1 Dry-Type Sprinklers
sequent ice build-up is increased. If must only be installed in fittings that
• this condensation is not controlled,ice
TFP51O
Page 8 of 10
Note; if sprinkler removal becomes if they cannot be completely cleaned Ordering
necessary, remove the sprinkler using by wiping the sprinkler with a cloth or
the same wrenching method noted by brushing it with a soft bristle brush. Procedure
above.Sprinkler removal is easier when Care must be exercised to avoid
a non-hardening sealant was used damage to the sprinklers before, Contact your local distributor for avail-
and torque guidelines were followed. during, and after installation. Sprin- ability.When placing an order,indicate
After removal, inspect the sprinkler for klers damaged
damage. 9 by dropping, striking, the full product name and Part Number
wrench twist/slippage,or the like,must (P/N).
Step 4. After installing the ceiling or be replaced. Also, replace any sprin- DS-1 Dry-Type Sprinklers
wall and applying a ceiling finish, slide kler that has a cracked bulb or that has When ordering TYCO Series DS-1
on the outer piece of the escutcheon lost liquid from its bulb. (Ref. Installa- Dry-Type Sprinklers, 5.6K Pendent,
until it comes in contact with the ceiling tion Section.) Upright, and Horizontal Sidewall,
or wall. Do not lift the ceiling panel out The owner is responsible for the Quick Response(3 mm bulb)and Stan-
of its normal position. inspection,testing,and maintenance of dard Coverage, specify the following
When using the Deep Escutcheon, their fire protection system and devices information:
hold the outer piece in contact with the in compliance with this document, as • SIN:
mounting surface(ceiling or wall).Then well as with the applicable standards Pendent—TY3935 or TY3235
rotate the inner piece approximately 1/4 of the National Fire Protection Asso- Sidewall—TY3735 or TY3335
turn with respect to the outer piece, ciation (e.g., NFPA 25), in addition to Upright—TY3135
to hold the Deep Escutcheon firmly the standards of any other authorities
together. having jurisdiction.Contact the install- • 5.6 K-factor
ing contractor or product manufacturer • Deflector Style:
Care and with any questions. Upright, Pendent, or Horizontal
Automatic sprinkler systems are rec- Sidewall
Maintenance ommended to be inspected, tested, • Quick Response, Standard Cover-
and maintained by a qualified Inspec- Dry-Type a e, Sprinkler
The TYCO Series DS-1 Dry-Type Sprin- tion Service in accordance with local g
klers,5.6K Pendent,Upright,and Hori- requirements and/or national codes. • Order Length:
zontal Sidewall,Quick Response(3 mm Dry-Type Sprinklers are furnished
bulb)and Standard Coverage must be Limited based upon Order Length as
maintained and serviced in accordance measured per Figures 3 through
with this section. warranty 10. After taking the measurement,
Before closing a fire protection system round it to the nearest 1/4 inch
main control valve for maintenance For warranty terms and conditions,visit increment.
work on the fire protection system www.tyco-fire.com. • Inlet Connections:
that it controls, obtain permission to 3/4 in. NPT, 1 in. NPT, or ISO 7-R 1
• shut down the affected fire protection
systems from the proper authorities • Temperature Rating
and notify all personnel who may be • Sprinkler Finish
affected by this action. • Escutcheon Style and Finish, as
Absence of the outer piece of an applicable
escutcheon, which is used to cover a
• Part Number(P/N)from Table D
clearance hole, can delay the time to
sprinkler operation in a fire situation. The Upright Sprinkler without an
A Vent Hole is provided in the Bulb Escutcheon(TY3135)is available in
Seat(Ref. Figures 1 and 2)to indicate 1 in. NPT only.
if the Dry-Type Sprinkler is remaining Part Numbers are for 3/4 in.and
dry. Evidence of leakage from the Vent 1 in. NPT standard order sprin-
Hole indicates potential leakage past klers.Orders for all other sprinkler
the Inlet seal and the need to remove assemblies must be accompanied
the sprinkler to determine the cause of by a complete description. Refer to
leakage (e.g., an improper installation the Price List for a complete listing
or an ice plug). Close the fire protec of Part Numbers.
tion system control valve and drain the Sprinkler Wrench
system before removing the sprinkler. Specify: W-Type 7 Sprinkler Wrench,
Sprinklers which are found to be P/N 56-850-4-001
leaking or exhibiting visible signs of Sprinkler Boot
corrosion must be replaced. Specify: Model DSB-2 Dry Sprinkler
Automatic sprinklers must never be Boot, P/N 63 000 0 002
painted, plated, coated, or other- This Part Number includes one (1)
wise altered after leaving the factory. Boot, two (2) Strap Ties, and 1/3 oz.
Modified sprinklers must be replaced. of Adhesive (a sufficient quantity for
Sprinklers that have been exposed to installing one boot).
• corrosive products of combustion, but
have not operated,should be replaced
TFP51O
Page 9 of 10
P/N` 60 - XXX - X - XXX
i
- I SPRINKLER ESCUTCHEON
SIN FINISH FINISH.'
01 Pendent with Standard TY3935 SIGNAL WHITE
Escutcheon(3/4"NPT) (Figure 3) 0 CHROME PLATED
(RAL9003)
02 Pendent with Deep TY3935 1 NATURAL BRASS SIGNAL WHITE
Escutcheon(3/4"NPT) (Figure 5) (RAL9003)
03 Pendent with Recessed TY3935 2 NATURAL BRASS BRASS PLATED
Escutcheon(3/4" NPT) (Figure 4)
Pendent without TY3935 SIGNAL WHITE SIGNAL WHITE
04 Escutcheon(3/4" NPT) (Figure 6) 4 (RAL9003) (RAL9003)
9 CHROME PLATED CHROME PLATED
05 Sidewall with Standard TY3735
Escutcheon(3/4" NPT) (Figure 8)
06 Sidewall with Deep TY3735 TEMPERATURE SAMPLE
Escutcheon(3/4" NPT) (Figure 9) RATINGS ORDER
LENGTHS2
07 Sidewall without TY3735 0 135°F(57°C)
Escutcheon(3/4" NPT) (Figure 10) 055 5.50"
1 155°F(68°C) 082 8.25"
36 Pendent with Standard TY3235 2 175°F(79°C) 180 18.00"
Escutcheon(1"NPT) (Figure 3) 3 200°F(93°C)
187 18.75"
Pendent with Deep TY3235 -
- 33 Escutcheon(1"NPT) (Figure 5) 4 286°F(141°C) 372 37.25"
37 Pendent with Recessed TY3235 480 48.00" I
Escutcheon(1"NPT) (Figure 4)
32 Pendent without TY3235
Escutcheon(1" NPT) (Figure 6)
34 Sidewall with Standard TY3335
Escutcheon(1" NPT) (Figure 8)
Notes:
43 Sidewall with Deep TY3335 1. Escutcheon Finish applies to sprinklers provided with escutcheons.
Escutcheon(1" NPT) (Figure 9) 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured
per Figures 3 through 10,as applicable,and for each individual sprinkler
where it is to be installed.After the measurement is taken,round it to the
44 Sidewall without TY3335 nearest 1/4 inch increment.
Escutcheon(1" NPT) (Figure 10) Use Prefix"I"for ISO 7-R 1 Connection(e.g.,I-60-010-4-055).
38 Upright without TY3135
Escutcheon(1"NPT) (Figure 7)
TABLE D
SERIES DS-1 DRY-TYPE SPRINKLERS
PART NUMBER SELECTION