Report (2) 4487-2019-00Y5Ce
1562O *1 E-Mregf YE-PRAC -
Sheet RECEIVED
Enphase Microinverters
Region:AMERICAS DEC 1 2019
CITY OF TIGARD
BUILDING DIVISION
Enphase The high-powered smart grid-ready
P Enphase IQ 7X Micro" dramatically simplifies the
IQ 7X M icroi nverter installation process while achieving the highest
system efficiency for systems with 96-cell modules.
Part of the Enphase IQ System,the IQ 7X Micro
integrates with the Enphase IQ Envoy", Enphase IQ
Battery'",and the Enphase Enlighten" monitoring
and analysis software.
The IQ Series Microinverters extend the reliability
standards set forth by previous generations and
undergo over a million hours of power-on testing,
enabling Enphase to provide an industry-leading
warranty of up to 25 years.
Easy to Install
• Lightweight and simple
I 1101
• Faster installation with improved,lighter two-wire cabling
el • Built-in rapid shutdown compliant(NEC 2014&2017)
Efficient and Reliable
• Optimized for high powered 96-cell*modules
• Highest CEC efficiency of 97.5%
• More than a million hours of testing
• Class II double-insulated enclosure
ENPHASE. s ®IQ • UL listed
=
E------
„...,1,9..-?1(-=.- Smart Grid Ready
nil � 9 !i I (a. • Complies with advanced grid support,voltage and
®mll CL ^..)i ! frequency ride-through requirements
• Remotely updates to respond to changing
grid requirements
• Configurable for varying grid profiles
• Meets CA Rule 21 (UL 1741-SA)
*The IQ 7X is required to support 96-cell modules.
SAFEPY US-G
E341165
EN PHASE
E
To learn more about Enphase offerings,visit enphase.com a
En phase IQ 7X Microinverter
INPUT DATA(DC) IQ7X-96-2-US
Commonly used module pairings' 320 W-460 W+
Module compatibility 96-cell PV modules
Maximum input DC voltage 79.5 V
Peak power tracking voltage 53 V-64 V
Operating range 25 V-79.5 V
Min/Max start voltage 33 V/79.5 V
Max DC short circuit current(module Ise) 10 A
Overvoltage class DC port II
DC port backfeed current 0 A
PV array configuration 1 x 1 ungrounded array;No additional DC side protection required;
AC side protection requires max 20A per branch circuit
OUTPUT DATA(AC) @ 240 VAC @ 208 VAC
Peak output power 320 VA
Maximum continuous output power 315 VA
Nominal(L-L)voltage/range° 240 V/211-264 V 208 V/183-229 V
Maximum continuous output current 1.31 A(240 VAC) 1.51 A(208 VAC)
Nominal frequency 60 Hz
Extended frequency range 47-68 Hz
AC short circuit fault current over 3 cycles 5.8 Arms
Maximum units per 20 A(L-L)branch circuits 12(240 VAC) 10(208 VAC)
Overvoltage class AC port III
AC port backfeed current 18 mA
Power factor setting 1.0
Power factor(adjustable) 0.85 leading...0.85 lagging
EFFICIENCY @240 VAC @208 VAC
GEC weighted efficiency 97.5% 97.0
MECHANICAL DATA
Ambient temperature range 40°C to+60°C
Relative humidity range 4%to 100%(condensing)
Connector type(IQ7X-96-2-US) MC4(or Amphenol H4 UTX with optional Q-DCC-5 adapter)
Dimensions(WxHxD) 212 mm x 175 mm x 30.2 mm(without bracket)
Weight 1.08 kg(2.38 Ibs)
Cooling Natural convection-No fans
Approved for wet locations Yes
Pollution degree PD3
Enclosure Class II double-insulated,corrosion resistant polymeric enclosure
Environmental category/UV exposure rating NEMA Type 6/outdoor
FEATURES
Communication Power Line Communication(PLC)
Monitoring Enlighten Manager and MyEnlighten monitoring options
Compatible with Enphase IQ Envoy
Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break
disconnect required by NEC 690.
Compliance CA Rule 21 (UL 1741-SA)
UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class 8, ICES-D003 Class B,
CAN/CSA-C22.2 NO.107.1-01
This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and
NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC
and DC conductors,when installed according manufacturer's instructions,
1.No enforced DC/AC ratio.See the compatibility calculator at https://enohase com/en-us/support/module-comoatibility.
2.Nominal voltage range can be extended beyond nominal if required by the utility.
3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area.
To learn more about Enphase offerings,visit enphase.com e EN P H A S E
h 2019 Enphase Energy All rights reserved.All trademarks or brands used are the property of Enphase Energy,Inc.
2019-3-26