Report Ai CZO/9-OO8(eF
/252o scd &8f
RECEIVED
DEC 162019
CITY OF TGARD
RIIII D BUILDING TIGARD
Date: Dec 12 2019
Job: ALL STATE
RUUD
Equipment list for project:ALL STATE - Dated: Dec 12 2019
Units
Tag No Model No Qty Description
RGEA14: 14 SEER gas heat and electric cool residential
RTU- 1 RGEA14042AJT101AA 1 packages
Voltage: 208-230V- 1PH-60Hz
Factory Options: None
RGEA14: 14 SEER gas heat and electric cool residential
RTU -2 RGEA14042AJT081AA 1 packages
Voltage:208-230V- 1PH-60Hz
Factory Options: None
Accessories
Tag No Field Model Description
RTU- 1 AXRF-FAA1 Manual Fresh Air Damper
RTU-2 AXRF-FAA1 Manual Fresh Air Damper
Notes
Dec 12 2019
Performance Summary
Tag: RTU -1 Model No: RGEA14042AJT101AA AHRI Ref: 7493371
Project: ALL STATE City: PORTLAND INTL ARPT State: OR
Altitude: 108 Air Discharge: Downflow/Horizontal
Cooling Performance
AHRI Rating-Capacity:40,000 EER: 12 SEER: 14
Gross Cap @ AHRI Rating Conditions(btuh)-Capacity: 41,092
Ambient Air(F)-Dry Bulb:87.5 Wet Bulb:66.5
Airflow(CFM)-CFM: 1,462 SCFM: 1,462
System Entering Air(F)-Dry Bulb:80 Wet Bulb: 67 % RH: 51.1
System Leaving Air(F)-Dry Bulb: 60.1 Wet Bulb: 57.8
Air Enthalpy(btu/lb)-Entering: 31.4 Leaving: 24.9
Design Net Cooling Capacity (btuh) -Total: 42,800 Sensible: 31,400 Latent: 11,400
Design Gross Capacity(btuh)-Capacity: 44,700 Sensible:33,300
Total Power-Watts: 3,286.5 KW:3.3
Heating Performance
Gas Heating Values(btuh)-Input: 100,000 Output: 81,000
Heating Airflow(CFM)-CFM: 1,462
Air Dry Bulb (F)-Outdoor: 29.5 Entering Air: 70 Leaving Air: 121.3
Air Temperature Rise (F)-Rise: 51.3
Air Moving System Characteristics
External Static Pressure(inches WG)-ESP: 0.5
Blower Speed or Speed Tap-Tap: Next Higher Drive: Direct
Motor Characteristic(watts&BHP)-Power: 538.2
Electrical Supply
Power Supply(Volt/Hz/Ph)-Volt/Hz/Ph: 208-230/60/1
Minimum Ampacity(amps)-Ampacity: 30
Max Overcurrent Protection (amps)-Fuse: 45 HACR Breaker: 45
Dimensions, Weight & Clearances
Dimensions-Length: 52-7116 Width: 47-112 Height: 41
Weight(lb)-Weight: 446
Clearances(inches)-Front:48 Cond. Coil: 18 Duct Side: 12
Clearances(inches)-Evap End: 36 Top:60
Product Submittal#: 5ad192f2-cbce-437a-826c-a772a2724123
RVVg, Submittal Printed on: 12/12/2019 7:01:22 PM
�^'"``�� For Model: RGEA14042AJT101AA
In keeping with its policy of continous progress and product improvement reserves the right to make changes without notice.
Gross capacity does not include the effect of motor heat.AHRI rating is net capacity and includes the effect of fan motor heat.All net capacities also accounts for the effect of motor
heat.
ASHRAE Weather Data®2009 American Society of Heating,Refrigerating and Air-Conditioning Engineers,Inc.,Atlanta,GA,USA.wonv.ashrae.org All rights reserved.Used by
permission in this program.
Model: RG EA14042AJT1 01 AA
1 TOP VIEWI
r.III I BOTTOM
VIEW
it �=M
1DUCT
_
sew GPENNG
fettz
aorroM
11111
SUPPLY
DUCT
OPENNG
IE � _411111 1011
-
---
OUTDOOR FAN IFFFI I �PPM
GRILLE 8
COMPRESSOR ACCESS
[ ]Designates Metric Conversions „now
FEATURES
1. All models feature Scroll®compressors for maximum 10. Inside the easily accessible furnace compartment is the
efficiency and quiet operation.5 Ton RGEA15 models draft inducer motor.This motor is specially designed for
feature UltraTech`"Scroll 2-Stage compressors with quiet reliable operation.In addition to the draft inducer
Comfort Alert'"diagnostics(see below),high/low pressure motor,the in-shot gas burners and manifold efficiently
switches,and hard start kits, regulate the flow of gas for combustion.These new
2. Louvered condenser compartment for protecting the coil gas/electric units also feature direct-spark ignition and
against yard hazards and/or weather extremes. remote flame sensors for added reliability and efficiency.
3. One-piece top with a deep flange to help keep water out 11.All units feature an internal trap on the condensate line
of the unit- eliminating the need for installing an on-site external trap.
4. Supply and return air openings feature a one-inch tall 12. Easily accessible control box.
flange to prevent water migration into the ductwork. 13. Single point wiring simplifies installation.
5. Access panels have"weep holes"and channels to further 14. Our gas/electric package units feature a tubular heat
help manage water run-off. exchanger design.Tubular heat exchangers are more
6. Side and down discharge options available on all models. efficient and durable than older-style clamshell heat
All models are shipped ready for horizontal application. exchangers.
7. Easily accessible blower section complete with slide-out 15.Thermal expansion valve standard on all models for
blower.The RGEA15 comes standard with variable speed superior superheat control,reliability,and energy
motor with adjustable airflow in heating and cooling.The efficiency at all operating conditions.
variable speed motor also comes with a interface that 16. Filter drier standard on all models(not shown).
allows for dehumidification when used in continuous 17. Rugged baserail included for improved installation and
humidistat.The variable speed system is capable of 1 handling
inch external static. 18. Complete factory charged,wired and run tested.
8. Refrigerant connections are conveniently located for easy 19. Molded compressor plugs.
service diagnostics.
9. Condenser and evaporator coils feature enhanced fins for
better heat transfer and rifled copper tubing for greater
efficiency.
FIELD INSTALLED ACCESSORIES
Roof Curb(8'[203.2 mm],14"[355.6 mm] Low Pressure Control ❑
&24"[609.6 mm) High Full Platform) ❑ Economizer(Enthalpy Controlled)Downflow Only ❑
Roof Curb(14"[355.6 mm&24"[609.6 mmj Manual Fresh Air Damper ❑
Sloped Platform) ❑ L.P.(Propane)Kit ❑
Filter Accessory ❑ Transition(Rectangular-Round)Downflow/Sideflow ❑
Lift Kit(For Rigging) LI Concentric Diffuser and Grille ❑
Time Delay Relay ❑ High Pressure Control El
Start Assist ❑ Thermostat Cl
Low Ambient Control ❑
Before proceeding with installation,refer
to installation instructions packaged
with each model,as well as complying
with all Federal,State,Provincial,end Rhein Sales Company Inc.
Local codes,regulations,and practices. 90,Box 17010,Fon Smith,AR 72917
"In keeping with its policy of continuous progress and product improvement,Rheem reserves the right to make changes without notice."
PRINTED IN U.S.A. 5-16 OG FORM NO.X33-1565
AXRF-FAA1 - Manual Fresh Air Damper
FRESH AIR DAMPER
AXRF-FAA1 (Fixed-0-35%)
The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No
drilling or damper assembly is required.The amount of outside air(0-35%)is controlled by sim-ply
adjusting the side damper.
AXRF-FA81(Motorized-0-35%)
The 0-35% motorized outside Air Damper is designed to replace the unit return air duct cover. No
drilling or damper assembly is required. The control motor opens the adjustable slide damper
when the unit blower motor is energized.
,,',,',,,,:?:;-,,,A
S,T
. may
CAULK INSIDE OF CORNERS �
(TYP.4 PLACES)(304112)MATERIAL , 'ems
\ " ,/ [521 mm] /,
SHIP HOOD REMOVED ����;i�
\ / i 15'IB
y/i� [384 mm]
` :_ ale(304101)GASKET "13.18 mm x 1/2"[12.7 mm]
``. ele"[15.87 mml FLANGE ON BACK SIDE
13S1n" '�.
[349 mm]���` 1
12"
�'-,.,� [305 mm]
Dec 12 2019
Performance Summary
Tag: RTU -2 Model No: RGEA14042AJT081AA AHRI Ref: 7493371
Project: ALL STATE City: PORTLAND INTL ARPT State: OR
Altitude: 108 Air Discharge: DownflowlHorizontal
Cooling Performance
AHRI Rating-Capacity:40,000 EER: 12 SEER: 14
Gross Cap @ AHRI Rating Conditions(btuh)-Capacity:41,092
Ambient Air(F)-Dry Bulb:87.5 Wet Bulb:66.5
Airflow(CFM)-CFM: 1,462 SCFM: 1,462
System Entering Air(F)-Dry Bulb:80 Wet Bulb:67 % RH: 51.1
System Leaving Air(F)-Dry Bulb:60.1 Wet Bulb:57.8
Air Enthalpy(btu/lb)-Entering: 31.4 Leaving: 24.9
Design Net Cooling Capacity(btuh)-Total:42,800 Sensible: 31,400 Latent: 11,400
Design Gross Capacity(btuh)-Capacity:44,700 Sensible: 33,300
Total Power-Watts: 3,286.5 KW: 3.3
Heating Performance
Gas Heating Values(btuh)-Input: 80,000 Output: 65,000
Heating Airflow(CFM) -CFM: 1,462
Air Dry Bulb(F)-Outdoor:29.5 Entering Air:70 Leaving Air: 111.2
Air Temperature Rise(F)-Rise: 41.2
Air Moving System Characteristics
External Static Pressure(inches WG)-ESP: 0.5
Blower Speed or Speed Tap-Tap: Next Higher Drive: Direct
Motor Characteristic(watts&BHP) -Power: 538.2
Electrical Supply
Power Supply(Volt/Hz/Ph)-Volt/Hz/Ph: 208-230/60/1
Minimum Ampacity(amps)-Ampacity: 30
Max Overcurrent Protection(amps)-Fuse: 45 HACR Breaker: 45
Dimensions, Weight & Clearances
Dimensions-Length:52 -7/16 Width: 47-1/2 Height: 41
Weight(lb)-Weight:441
Clearances(inches)-Front: 48 Cond. Coil: 18 Duct Side: 12
Clearances(inches)-Evap End: 36 Top:60
Product Submittal#: 667130b2-bcc8-472d-b22d-855a94d26c2c
RUUD Submittal Printed on: 12/12/2019 7:01:22 PM
'--"W For Model: RGEA14042AJT081AA
In keeping with its policy of continous progress and product improvement,reserves the right to make changes without notice.
Gross capacity does not include the effect of motor heat.AHRI rating is net capacity and includes the effect of fan motor heat.All net capacities also accounts for the effect of motor
heat.
ASHRAE Weather Data m 2009 American Society of Heating,Refrigerating and Air-Conditioning Engineers,Inc.,Atlanta,GA,USA.wnxw.ashrae.org All rights reserved.Used by
permission in this program.