Report • PORTER " . , ( 960 e#4 ePet RECEIVED DEC 1 12019 ' ■ CITYBUILDING DIVISION 7320 NE St. Johns Road •Vancouver, WA 98665• 360-574-1366 • Lic# PORTEE1554DK • Fax 360-573-3723 Product Submittals: FPs2o1?-co152- Project: Hampton Inn & Suites 11799 SW 69th Ave Tigard Oregon System: Alarm System for RI Use Building Submittal Index: Page (2) FACP Specifications Page (6) BEP Specifications Page (8) Digital Cellular Communicator Specifications Page (10) RACP Specifications Page (12) Manual Pull Station Specifications Page (14) Common Area Smoke Detector Specifications Page(17) Common Are Heat Detector Specifications Page(20) Common Area Smoke/Heat Base Specifications Page(22) Common Area Ceiling Mount Horn/Strobe Specifications Page(26) Pool Area Wall Mount Horn/Strobe Specifications Page (30) ELEV/HVAC/FSD Control Module Specifications Page (32) Sprinkler/HVAC Monitoring Module Specifications Page (34) HA Unit Wall Mount Low Frequency Horn/Strobe Specifications Page (37) HA Unit Rest Room Strobe Specifications Page (41) Standard Unit Low Frequency Sounder Det. Base Specifications Page (43) Quest Room Smoke/CO Detector Specifications Page (45) Sprinkler Bell Specifications Submitted by: Bill Robinson BRobinson(aTORTERElectricInc.com 7320 NE St John's Rd Vancouver WA 98665 Office: 360-574-1366 Fax: 360-573-3723 Honeywell I Addressable Fire Alarm Control Panels • 0 SILENT' KNILGHT 6820 Addressable Fire Alarm Control Panel - - The 6820 is an addressable fire alarm control panel(FACP)and is a direct replacement for the 5820XL FACP.The 6820 can be configured to achieve a point capacity of 1110 points and connect up to 17 panels in a single communications link. The 6820 has one built-in signaling line circuit(SLC),which can support 159(SK)System Sensor°sensors and 159 SK modules or 127 (SD)Hochiki°devices per loop.To increase point capabilities,additional SLC loops can be added using the 6815 SLC expander for SK devices or the 5815XL expander for SD devices,increasing the point capacity to a 6820 maximum of 1110 points for SK devices and 635 points for SD devices. Three additional SLCs are needed to reach 1110 points(SK devices). The 6820 also has a form-C trouble relay,two Four additional SLCs are needed to reach 635 points(SD devices). programmable form-C relays,along with powerful A common communications and annunciation link allows up to 17 features such as drift compensation,pre trouble panels to be connected via copper or fiber optic cable.A designated maintenance alert,a built-in sensor test to panel is configured as the communicator for all panels in the link for comply with NFPA 72 calibration testing ® convenient single-point communications.It also has a built-in,dual- requirements,and calibration trouble alert. tine POTS and IP communicator with additional cellular options The 6820 supports a variety of devices,including available. the 6860,5860,and 6855 remote annunciators, The 6820 system can be enhanced by adding modules such as the 5824 serial parallel printer interface module(for 6860 remote annunciator which also has four programmable function printing system reports),the 5496 NAC expander, buttons to help automate tasks and reduce time spent at the panel. 5895XL power module,and SK or SD devices. SWIFT°wireless compatibility provides options for wireless detection through a Class A mesh network.It is ideal for hard-to-wire locations, buildings where new wiring is not allowed,or to provide an easy install fire system for new construction projects.SWIFT devices can be combined with other hard-wired 6820 compatible devices. FEATURES & B ENEFITS • Capable of providing • Connect up to 17 • Built-in dual path • Programmable date • Ftexput"circuits can up to 1110 points for panels on one site with POTS and IP setting for automatic be individually enhanced design convenient single- communications with and convenient programmed to flexibility.Additional point access using the optional cellular Daylight Saving Time function as Signal Line Circuits SK-NIC Network models available for changes notification circuits, can be added until Interface Card. reliable backup • Four user- auxiliary power maximum point levels Connected panels can reporting outputs,or initiating programmable are reached have mixed compatible . 6860 annunciator with buttons minimize circuits that support • Built-in USB interface FACP models a 4 x 40 large display time spent executing both 2-and 4-wire for convenient and • Convenient complex or routine smoke detectors • quick programming field-upgradeable art auto props• tasks programming reduces firmware installation time SIGNAL LINE CIRCUIT(SLC) system silenced and system power. waterflow,sprinkler supervisory(DACT 0 The 6815 signal line circuit(SLC) System operations include silencing non-coded)signaling services. supports multiple device types of SK alarms and troubles,resetting alarms • UL Listed:S2766 protocol,while the 5815XL signal line and the display of alarm troubles and • CSFM:7165-0559:0500 circuit(SLC)supports multiple device memory.The system's non-volatile types of SD protocol.You cannot mix SD event history buffer stores 1,000 • FDNY:COA#6249 and SK SLC devices on a FACP. events for viewing from the built- • FM approved The 6820 has one built-in signaling in or remote annunciator.System ORDERING INFORMATION line circuit(SLC)which supports multiple operations can be initiated with a 6820:Addressable Fire Alarm devices.Additional points mechanical firefighter's key or a valid Control Panel.(Red cabinet). can be added using the 6815 SLC 4-to 7-digit operator's code. expanders to increase overall capacity to COMPATIBLE ANNUNCIATORS PROGRAMMING 1,110 maximum points(SK devices)or by The 6820 system offers several options 6860:4x40 LCD remote fire annunciator adding up to four 5815XL SLC expanders to simplify and speed-up programming. (4 lines and up to 160 characters)per to reach 635 maximum points(SD JumpStart°AutoProgramming system;four programmable buttons devices).The number of SLCs which can 5860:4x20 LCD remote fire minimizes programming required to be used within one system is limited by annunciator.5860 is gray;5860R is red start a new system.The built-in keypad, point count.(See the Manual for or the 6860,5860 or 6855 remote 6855:4x20 LCD remote fire annunciator additional information.) 5865-3 or 5865-4:LED annunciators annunciators give you on-site access to The 6820 SLC loops support multiple current system programming. can display up to 30 LEDs(15 red and device types,maintenance alerts,and a Programming can also be accomplished 15 yellow).The 5865-4 has key switches built-in sensor test to comply with NFPA using the Windows°-based Honeywell for silence and reset,and a system 72 calibration testing requirements. Fire Software Suite(HFSS)program. trouble LED. S INDICATOR LIGHTS 5880:The 5880 LED/10 module SOFTWARE TOOLS has 40 programmable LED outputs and • General Alarm(Red):Flashes if in SKST:Silent Knight Selection Tool eight supervised dry contact inputs alarm;solid when alarm is silenced provides the installer or design architect which are useful for custom applications. • Supervisory(Yellow):Flashes if a with a Windows"software system You can use up to eight 5880 modules supervisory condition exists;solid configuration tool to create a detailed on one control panel for maximum when supervisory is silenced Bill of Material(BOM)and battery flexibility.Its compact size allows • System Troubles(Yellow):Flashes calculations. mounting inside the annunciator,or in if a trouble condition exists; HFSS:Honeywell Fire Software Suite an accessory cabinet. solid when trouble is silenced provides communication and panel 6820 COMPATIBLE DEVICES AND programming,detector status,event ACCESSORIES • System Silenced(Yellow): See the data sheets listed below for a history and additional data. Requires a complete listing when an alarm,trouble or P of the SK,SD or SWIFT PC running Microsoft'Windows". devices. supervisory condition has been 53623:SK Devices Data Sheet silenced but not yet cleared ADDITIONAL INFORMATION 53624:SD Devices Data Sheet • System Power(Green):Flashes Twisted-unshielded pair wire is 350614,350616&350618:SWIFT wireless devices for AC failure;solid when recommended.The 6820 also has 13 For a complete and current listing of power systems are normal preset notification cadence patterns compatible devices and accessories,visit USER INTERFACE www.silentknight.com (including ANSI 3.41) Important:You cannot mix SK and SD The 6820 built-in 4 x 20 annunciator AGENCY LISTINGS AND APPROVALS devices in the same fire alarm system. with 80 character LCD display NFPA 13,NFPA 15,NFPA 16,NFPA 70, and large easy-to-use tactile NFPA 72:Central station;remote touchpad can be used for system Signaling;Local Protective Signaling • operation,programming and Systems;Auxiliary Protected Premises maintenance.It has five LEDs for Unit;Water Deluge releasing service. alarm,supervisory,system trouble, Suitable for automatic,manual, Page 2 of 4—351610:B 9/26/2018 SK COMPATIBLE ADDRESSABLE B200S-LF:Low-frequency intelligent WSK-PHOTO-T:Wireless Multi-criteria • DEVICES sounder base photoelectric smoke detector with thermal SK-ACCLIMATE:Multi criteria B224RB(-IV,-WH):Relay base detection(135°F fixed temperature)and photoelectric smoke detector with thermal B224RB: Relay base B510W 4"base 135°F fixed temperature B224BI(-IV,-WH):Isolator base WSK-HEAT:Wireless Heat,(135°F fixed SK-BEAM:Reflected beam smoke detector B224BI: Isolator base temperature)and B510W 4"base without test feature WSK-HEAT-ROR:Wireless heat,ROR SK-BEAM-T:Reflected beam smoke SD COMPATIBLE ADDRESSABLE (135°F fixed temperature)and B510W 4" detector with test feature DEVICES base SK-CONTROL:Supervised control module SD505-6AB:Addressable 6"base WSK-MONITOR:Wireless monitor module SK-CONTROL-6:Six circuit supervised SD505-6IB:Addressable 6"short circuit WSK-RELAY:Wireless relay module control module isolator base W-USB:SWIFT Tools USB transceiver used SK-DUCT:Photoelectric duct smoke SD505-6RB:Addressable 6"relay base for communication with SWIFT devices detector with extended air speed range SD505-6SB:Addressable 6"sounder base SK-FIRE-CO:Four criteria fire and carbon SD500-AIM:Addressable input module SBUS ACCESSORIES monoxide detector (switch input) 6815:Each Single Line Circuit allows for SK-HEAT:Fixed thermal detector(135°F) SD500-ANM:Addressable notification an additional 159 SK modules and 159 SK SK-HEAT-W:Fixed thermal detector module sensors to be added to the system-up to (135°F),white SD500-ARM: Addressable relay module 1,110 total points.Supports System Sensor SK-HEAT-ROR:Fixed rate of rise detector SD505-DTS-K: Remote test switch and SK devices only. (135°F) LED indicator for the SD505-DUCTR 5815XL:Each Single Line Circuit provides SK-HEAT-ROR-W:Fixed rate of rise detector SD505-DUCT:Addressable Duct Smoke an additional 127 SD devices to be added to (135°F),white Detector. the system-for a maximum of 635 points. SK-HEAT-HT:Fixed high temperature SD505-DUCTR:Addressable Duct Supports SD devices only. thermal detector(190°F) Detector housing with relay base. 5496:A 6 amp notification power expander SK-HEAT-HT-W:Fixed high temperature SD505-HEAT:Absolute temperature heat with four power-limited notification thermal detector(190 F),white appliance circuit outputs. detector.Trip point range from SK-ISO:Fault isolator module 135°F-150°F(0°C-37°C). 5883:Relay Interface.Provides 10 Form C SK-MINIMON:Mini monitor module SD500-LIM:Addressable Line isolator relays. SK-MONITOR:Monitor module module 5824:Serial/Parallel Printer Interface SK-MONITOR-2:Dual input monitor SD500-MIM:Addressable Mini input Module for printer connection. ilomodule monitor module(switch input) 5895XL:Power Supply with six Flexput° SK-MON-10:10 input monitor module SD505-PHOTO:Photoelectric smoke circuits,and two Form C relays.Max.16 per SK-PHOTO:Photoelectric smoke detector detector system. SK-PHOTO-W:Photoelectric smoke SD500-PS/-PSDA:Addressable Single or 5815RMK:Remote mounting kit. detector,white dual action pull station Dimensions 10 3/8"W x 10-3/16"H x 3"D SK-PHOTO-T:Photoelectric smoke detector SD500-SDM:Addressable smoke detector COMMUNICATION OPTIONS with thermal(135°F fixed temperature) module CELL-CAB-SK:Cellular communicator, SK-PHOTO-T-W:Photoelectric smoke metal enclosure with lock/key* detector with thermal(135°F fixed AUDIBLE/VISIBLE DEVICES temperature),white These AV devices are all 2-wire.Color:"R" CELL-MOD:Cellular communicator,plastic indicates red;"W"denotes white.For a enclosure * SK-PHOTOR:Photoelectric detector with *Sole path,powered by panel. remote test capability complete listing of Silent Knight AV devices SK-PHOTO-R-W:Photoelectric detector go to www.silentknight.com. IPGSM-4G:Dual path fire alarm with remote test capability,white communicator,cellular and/or IP(primary CHSRL/CHSWL:Wall chime/strobe or backup,selectable) SK-PULL-SA:Addressable single action pull CHSCRL/CHSCWL:Ceiling chime/strobe station SK-IP-2:Remote reporting via the Internet. CHRL/CHWL:Wall chime Requires a VisorAlarm°receiver at the SK-PULL-DA:Addressable dual action pull HRL/HWL:Wall horn central station station P2RL/P2WL:Wall horn/strobe SK-RELAY:Addressable relay module PC2RL/PC2WL:Ceiling horn/strobe MISC.ACCESSORIES SK-RELAY-6:Addressable Six relay control SRL/SWL:Wall strobe SK-NIC:Network Interface Card.Provides a module SK-RELAYMON-2:Addressable Dual relay/ SCRL/SCWL:Ceiling strobe common communications link for the 6820. monitor module SPSCRL/SPSCWL:Ceiling speaker/strobe SK-NIC-KIT:Installation Accessory Kit SK-ZONE:Addressable zone interface SPSRL/SPSWL:Wall speaker/strobe SK-FML:Fiber-Optic Multi Mode, module SPRL/SPWL:Wall speaker transmitter and receiver SK-ZONE-6:Six zone interface module SPCRL/SPCWL:Ceiling speaker SK-FSL:Fiber-Optic Single Mode B300-6(-IV):6"base for SK-W Series RBB:Remote battery box accessory cabinet SWIFT WIRELESS DEVICES for batteries that are too large to fit in the B210LP:6"mounting base FACP cabinet.Dimensions:16"W x 10"H x B501(-WHITE,-IV,-BL):4"Flan eless base SWIFT is only compatible with g System Sensor(SK)devices.It is not 6"D(406mm W x 254mm H x 152mm D). 0 B501:4"Flangeless mounting base SK-SCK:Seismic Compliance Kit used to B200S(-IV,-WH):Intelligent sounder base compatible with Hochit (SD)devices. securely fasten batteries to the fire panel. B200S:Intelligent sounder base WSK-WGI:Wireless Gateway B200S-LF(-IV,-WH):Low-frequency WSK-PHOTO:Wireless Photoelectric smoke intelligent sounder base. detector Page 3 of 4—351610:139/26/2018 6820 Technical Specifications • PHYSICAL FLEXPUT CIRCUITS Flexput',Honeywell', Overall Dimensions:16.36"W x 26.37"H x 3.91"D Six programmable circuits which can be JumpStart',Silent Knight', Shipping Weight:32 lbs programmed individually as: SWIFT',and System Sensor are registered Color:Red Notification Appliance Circuits:3A @ 27.4VDC trademarks of Honeywell per circuit,power-limited(with a panel maximum International Inc. ENVIRONMENTAL current of 6A) Operating Temperature:32°F to 120°F (0°C to Auxiliary power circuits:3A @ 27.4VDC per circuit, Hochiki is a registered trademark of Hochiki 49°C) power-limited Corporation.Microsoft" Humidity:0 to 93°/o relative humidity(non- Initiating Circuits(Circuits 5 and 6 Only):100mA and Windows"are condensing) @ 27.4VDC per circuit,power limited registered trademarks of Microsoft Corporation. ELECTRICAL Supports Class B(Style 4)and Class A(Style 6) This document is not 6820 Primary AC:120AC @ 60Hz,3.3A Total configuration for SLC,SBUS,and Flexput circuits intended to be used for Accessory Load:6A @ 27.4VDC power-limited installation purposes.We Standby Current:190mA WIRING:See the product manual for wiring details try to keep our product information up-to Alarm Current:250mA Batteryan Charging Capacity:7 to 35AH date cannotc accurate.We 9 9 p Y� cover all specific Battery Size:18AH max.allowed in control panel applications or anticipate cabinet.Larger capacity batteries can be housed in all requirements.All specifications are subject RBB accessory cabinet. to change without notice. For Technical Support,call 800-446-6444 Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472 Hone e" 800-328-0103 351610 B I 09/18 ■•V www.silentknight.com t 2018 Honeywell International Inc. KNIGHTNA BEP - Horn/Strobe Power FIRE SYSTEM ACCESSORY Expansion Panel SILENT Model 5495 4011 Distributed Power Module KNIGHT In an emergency, by Honeywell you need maximum power The 5495 Distributed Power Module by Silent Knight is the most powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®,Gentex®,AMSECO®, Wheelock and Faraday—what you need to drive power- hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies.And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1-800-328-0103. Model 5495 accessories like magnetic door Distributed Power Module holders • The 5495 is a 6 amp notification power Built-in synchronization for expander that provides its own AC appliances from System power connection, battery charging Senso Gentex ,AMSECO®, circuit, and backup battery for use with Wheelock an Faraday fire and security controls such as the • Stand alone operation Silent Knight Model 5208 Fire Control Lightweight design adds to ease of /Communicator.The 5495 is the cost- installation and reduces shipping effective solution for powering costs notification appliances required by the • Operates with most polarized, UL Americans with Disabilities Act(ADA). Listed notification devices The 5495 has built-in ANSI cadence pattern,which can upgrade older • ANSI Cadence pattern output control panels that lack cadence capability built-in capability. Connection to Local Fire Control Imo'^� ; Features The 5495 may be connected to a local • UL Listed for 6 amps of notification fire control which utilizes Class A or Class B type notification circuits Model 5495 power operating between 9 and 32 VDC.The Distributed Power Module • Power supply's advanced switch control panel's notification circuit is mode design reduces damaging connected to one of the inputs on the Approvals heat and manages power up to 50% 5495.The control panel's notification • UL Listed more efficiently than other systems circuit end-of-line resistor is also • • Dip switches allow for easy connected across two terminals on the MEA 429-92-E Vol XII reconfiguration 5495,which provides supervision • CSFM 7300-0559:123 • 24 VDC filtered output voltage between the 5495 and the fire control • NFPA 72 • Four power-limited notification panel. Polarized audible and/or visual • OSHPD (CA)OSP-0065-10 outputs; 2 Class A or 4 Class B, or 1 notification devices are then connected (see accessories) Class A and 2 Class B to the 5495 signal circuits using the • Additional continuous auxiliary 4.7k1 end-of-line resistors provided. Since the 5495 draws very little power output from the control, it is possible to • 3 amps per output circuit connect one 5495 to each notification 41111 • 2 inputs; 2 Class B or 2 Class A circuit on the control panel and still • Ground fault detector/indicator provide full supervision of the • Independent trouble relay notification circuits all the way back to • AC loss delay option shuts off power the control panel. PN 350395 Rev G to non-essential high-current ©2015 Honeywell International Inc. FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power Trouble Output Local Fire Control (Alternative to notification circuit trouble.) Supervision •4 Class B(Style Y) Aux trouble: Yellow The 5495 supervises a variety of (1 Class A&2 Class B) Output troubles(1-4): Yellow functions including: Amps per output circuit: 3.0 (6.0 amps • Low AC power total) Ordering Information • Low battery condition Notification circuit output: 5495 Distributed Power Module • Earth ground fault Alarm Current(for typical voltages) Accessories: • Auxiliary output power limit condition drawn from main panel's notification • EOL supervision trouble or power appliance circuits. SK-SCK Seismic Compliance Kit limited condition at an output 12 VDC 6.5 mA When a trouble condition occurs, the 24 VDC One input circuit- 15 mA; 5495 creates a trouble condition on the Both input circuits-30 mA host control signal circuits to which it is No.of inputs: 2 connected.the 5495 still maintains the ability to be activated by the host Input configuration: 2 Class B or 2 control. In addition, the 5495 provides a Class A Form C trouble relay output as an Input voltage range: 9-32 VDC alternative to using the notification Battery charging capacity: 35.0 AH circuit trouble. Ambient temp.: 32°to 120° F Electrical Specification (0°to 49° C) AC input: 120 VAC at 2 amps Mechanical Output: 24 VDC at 6 amps Dimensions: Current: 12.25"W x 16" H x 3" D (30.88 cm W x Standby 75 mA 40.64 cm H x 7.62 D cm) Alarm 205 mA Auxiliary power circuit: 1 Indicator Lights AC power on : Green Notification circuits:4 Battery trouble: Yellow Output configuration: •2 Class A(Style Z) Ground fault: Yellow SILENT This document is not intended to be used for installation purposes.We try to No KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight by Honeywell 12 Clintonville Road, Northford,CT 06472-7161 Phone:(800)328-0103, Fax:(203)484-7118.For Technical Support,please call 800-446-6444. Assembled In America www.silentknight.com TG - 7FS CELLULAR ALARM • C I\IMU iCA OFF LTE-V FOP [._TE NETWORKS T E LG U A R D P/N: TG7LVFO1 6 COMMERCIAL FIRE PRODUCT FEATURES Certified for use on Verizon's LTE network for long, sunset- free installation. F• Meets UL 864 requirements for sole, primary or backup path communications. I- Minimizes false alarms by providing dual paths for self-tests. 1 � The Telguard TG-7FS LTE-V is the ideal cellular alarm communications solution for commercial fire systems. The TG-7FS LTE-V transmits alarm signals from the fire panel over the digital cellular network to the designated monitoring station. Compliant with the 2016 Edition of NFPA 72, the TG-7FS LTE-V can serve as the sole communications path for the fire alarm system. It • replaces all of the landlines currently dedicated to the master control unit. On average, cellular monitoring costs the end user significantly less than a dedicated landline. For each landline replaced with a TG-7FS LTE-V, the monthly communications bill decreases. By being able to signal failures to the central station within sixty minutes of an outage, the TG-7FS LTE-V can be installed as the sole path for commercial fire installations. For existing installations, all landlines can be swapped for a single TG-7FS LTE-V because of the new sixty minute supervision mode. The TG-7FS LTE-V can also be installed as a backup path and upgraded to sole path at a later date. Telguard Portal Telguard Cellular Service Advanced Reliability Telguard makes adopting cellular Telguard Cellular Service provides • Features the ability to utilize easy with a secure Internet portal. Verizon LTE network coverage multiple cellular technologies to The straightforward web interface for all Telguard units. Telguard's increase availability and reduce allows security dealers and central Communication Center is UL false alarms. stations to quickly and efficiently compliant and provides seamless • Automatic self-tests with central access Telguard based services 24/7. connectivity between the alarm station notification ensure the This advanced tool has multi-level panel, the Telguard family of cellular system is operating. user authorization and provides products and the central station. total account management of Telguard Technical Support provides ' Available relay output for tripping • UL Listed Telguard cellular alarm a single point of contact for both the alarm control panel when a communicators. cellular service and Telguard product trouble condition occurs. questions. • TG - 7FS T E L G U A R D P/N:LT E L Vol 011\») Power EL El ) • Transmit Power: liii 200mW in all bands. �P�wak ti Power Consumption: CI , 60mA(Standby) 250mA(Transmission). • Transformer: 12VAC,800mA UL listed plug-in. Telguard technology allows full data reporting for unlimited point-to-point signal details and maximum transmitting power Radio Transceiver for superior in-building penetration. • LTE Bands:4&13. • Antenna:9"dipole with 2dBi gain Telguard products are easy to install, economical, and UL Listed. 12 ft of cable and universal mounting bracket. Accessories • • FCC part 15,27 and 68 compliant. • ACD 12, ACD 35, ACD 50, ACD 100: 12/35/50/100 feet of low loss, high performance cable. Physical Details • HGDL-0: High gain directional antenna. • EXDL-0: External antenna. • TG-7FS LTE-V: 7,5"H x 11.5"W x 3,5"D. • Shipping Weight: 81bs. • Operating Environment: 0°C to+50°C;up to 95%humidity (non-condensing). Standard Features UL Listings Commercial Fire 864 Commercial Burglary Residential • Full data reporting. • Control units& 365 • Police Station 985 • Household fire accessories for connected warning systems • Automatic self test(60 min.&daily), fire alarm systems burglar alarm 1023 • Household burglar • Power supply with battery harness. units and systems alarm systems • Locking, red metal enclosure. 1610 • Central station burglar • Two programmable supervisory alarm units: trip outputs. Line security servcies • Supports virtually all alarm formats • For the most current product specifications and UL Listings visit www.Telguard.com. (Contact ID,SIA2,and others) using dial capture for universal SECURITY panel compatibility. SIGNALING CC)5 o ria _ /��� � '` • Telephone line monitor built-in, AI� EEEcrRowc ✓_ with Standard Line Security. ,...5, �AESORIry veriZQP CO �/ nssoclnnovM NETWORK LISTED r " NFPA' /Ih INTERNATIONAL CERTIFIED • Telguard,a Division of Telular Corporation •3225 Cumberland Blvd SE•Suite 300•Atlanta,GA 30339 • USA 800-229-2326,Option 5•www.Telguard.com •Copyright©2017 Telular Corporation •All Rights Reserved -----41"411119H/ Honeywell • ®SILENT. KNIGHT 5860 Remote Annunciator The 5860 remote annunciator,can be used to operate and program Honeywell Silent Knight fire alarm control panels(FACPs)from anywhere within the system. The 5860 features include an 80-character backlit LCD providing easy-to z ' rats 4 • cM - understand system messages.The annunciator is ergonomically designed e n with over-sized buttons for the most frequently used features,like Reset .a <, and Silence. ' , e 9 V , o a In addition to status messages displayed on the LCD,there are five LEDs for alarm,supervisory,trouble,silence,and AC power status. The 5860 annunciator is available in gray to match virtually any decor and 5860/5860R red for applications where the annunciator must stand out.The annunciator enclosure can be surface or flush mounted.A trim ring kit is available for surface mounting. COMPATIBILITY The 5860 is compatible with the following Honeywell Silent Knight FACPs: 6820:Addressable fire alarm control panel with up to 1,110 addressable points 6820EVS:Addressable fire alarm control panel with an emergency communication systems and up to 1,110 addressable points 6808:Addressable fire alarm control panel with up to 198 addressable points 6700:Addressable fire alarm control panel with up to 100 addressable points 5820XL:Addressable fire alarm control panel 5820XL-EVS:Addressable fire alarm control panel with an emergency communication systems 5808:Addressable fire alarm control panel 5700:Addressable fire alarm control panel FEATURES & BENEFITS • 80-character backlit • Support for • Five Status LEDs • Accommodates wiring • Accepts user codes or LCD display(4 lines simultaneous use of Available in red or light lengths up to 6000 ft. fire fighter's key •with 20 characters per multiple 5860s gray color from the control panel • Larger keypad buttons tine) • Easil view current for added design and y makes it easier to install flexibility • Tactile/audible status by alarms, maneuver for system feedback when a key is supervisories,or reset and silencing pressed on the troubles annunciator • Uses the RS-485 SBUS to interface with the panel 5860 Technical Specifications For a complete listing of all compliance approvals and certifications,please visit www.silentknight.com. Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Wire Runs Up to 6000 Feet From FACP Silent Knight'and Honeywell"are registered w e!1•_••••Re— v trademarks of Honeywell a t - a International,Inc. c G SBUS 1 1 *■ This document is not intended to be used for 6860 6860 6860 installation purposes.We try to keep our product •Up to Eight 5860s Per 5700 or 6700 System information up-to •Up to 12 5860s Per 5808,6808,5820XL,or 5820XL-EVS System date and accurate.We •Up to 16 5860s per 6820 or 6820EVS System cannot cover all specific Compatible Silent Knight FACP P applications or anticipate all requirements.All specifications are subject to change without notice. For Technical Support, 5860 Features call 800 446 6444. PHYSICAL ORDERING INFORMATION Dimensions:9.1"W x 7.4"H x 1.5"D(23.1W x 18.8H x 5860:Remote Annunciator,four line(4x20)LCD 3.8D cm) annunciator with 20 characters per line.Gray • Shipping Weight:2.8 lbs(1.3 kg) 5860R:Remote Annunciator,four line(4x20)LCD Color:5860R:Red;5860:Gray annunciator with 20 characters per line.Red ENVIRONMENTAL ACCESSORIES Operating Temperature:32°F to 120°F(0°C to 5860TR:Red Trim Ring for surface mounting 49°C) 5860TG:Gray Trim Ring for surface mounting Humidity:100/0-93%non-condensing) AGENCY LISTINGS AND APPROVALS ELECTRICAL UL listed Operating Voltage:24VDC CSFM approved Standby Current:20mA Meets NFPA 72 requirements Alarm Current:25mA FM approved MEA approved For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com • Honeywell Silent Knight Honeywell 12 Clintonville Road Northford,CT 06472 Doc 350224I RevJ 112/17 ell T'SILEN 800-328-0103 ©2017 Honeywell International Inc. KNIGHT Honeywell • SILENT r KNIGHT SK-PULL-SA / SK-PULL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to activate the station.The SK-PULL-DA is a dual action pull station requiring FIRE two motions to active the station.The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel(FACP). 1 D PULL OWN Extremely easy to operate,the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal.The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. Honeywell Z- 'lIF�7' I�JvlGlff INSTALLATION al The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O SK-PULL-SA surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13"(5.40 cm)or double gang or 4°(10.61 cm)square electrical box.You can also use the optional(System Sensor®PN BG-TR) FIRE trim ring if the station is being semi-flush mounted. 6 PUSH PULL DOWINN Honeywell 0 SK-PULL-DA FEATURES & BENEFITS • Installer can open • Key operated test and • Meets the Americans • Reliable analog • Handle latches in station without reset lock using lock with Disabilities Act communications for down position and the causing an alarm plate actuator Accessibility trouble-free operation word Activated condition Guidelines(ADAAG) appears,clearly • Key matches • Braille text on station controls and operating indicating the station • Dual-color LED is compatible FACP handle visible through handle locks mechanisms has been pulled of station blinks green guidelines(Section • Rotary address • Meets ADA switches for fast • UL Listed,including to indicate normal 4.1.3(13]) UL 38,Standard of requirement for 5 tbs installation operation and remains maximum pull force to • Shell,door,and handle Manually Actuated III steady red in an alarm active molded from durable Signaling System condition LEXAN • CSFM Listed • MEA Listed SK-PULL-SA / SK-PULL-DA Technical Specifications 1111 For a complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:5.5"H x 4"W x 1.45"D(14 x 10.2 x SK-Pull-SA:Single Action Pull Station 3.7cm) Microsoft,Windows,and SK Pull-DA:Dual Action Pull Station the Windows Logo are Housing Material:LEXAN polycarbonate resin registered trademarks Bi-Colored LED: ACCESSORIES or trademarks of Blinking Green:Normal BG-TR:Optional trim ring. Microsoft Corporation. Steady Red:Alarm SB-I/O:Surface backbox,indoor/outdoor. Silent Knight°,System Switch:Single pole,single throw(SPST)normally *Unless otherwise noted,specifications apply to Sensor"and Honeywell' open(N/O)switch which closes upon activation of SK-Pull-SA and SK-Pull-DA are registered the pull station trademarks of Honeywell COMPATIBILITY International,Inc. ELECTRICAL The SK-PULL-SA AND SK-PULL-DA are This document is not Operating Voltage:15-32VDC compatible with the following Honeywell Silent intended to be used for SLC Standby and Alarm Current:350µA Knight fire alarm control panels: installation purposes.We try to keep our product Wire Gauge:Up to 12AWG(3.1 mm2) 6820:Addressable fire alarm control panel information up-to 6820EVS:Addressable fire alarm control panel date and accurate.We ENVIRONMENTAL with an emergency voice system. cannot cover all specific Operating Temperature:32°F—120°F(0°C— 6808:Addressable fire alarm control panel applications or anticipate 49°C) 6700:Addressable fire alarm control panel all requirements.All specifications are subject Humidity:10%—93°/o non-condensing 5700:Addressable fire alarm control panel to change without notice. 5808:Addressable fire alarm control panel For Technical Su 5820XL:Addressable fire alarm control panel Support, ca11800-446-6444. 5820XL-EVS:Addressable fire alarm control panel with an emergency voice system For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell• Silent Knight Honeywell 12 Clintonville Road Northford,CT 06472 Doc 3501351 Rev El 11/17 ri SILENT' 800-328-0103 ©2017 Honeywell International Inc. KNIGHT Honeywell • ®SILENT" KNIGHT SK-PHOTO-W Series Intelligent Plug-In Photoelectric Smoke Detector Honeywell Silent Knight SK-PHOTO-W Series plug-in smoke detectors are designed for both performance and aesthetics.A new modern,sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The SK-PHOTO-W Series detector sensitivity can be programmed in the control panel software.Sensitivity is continuously monitored and reported to the panel.Point ID capability allows each detector's address to be set with rotary,decimal address switches,providing exact detector location for selective maintenance when chamber contamination reaches an .0 unacceptable level. Dual electronic thermistors add 135°F(57°C)fixed temperature thermal sensing on the SK-PHOTO-T-W.The SK-PHOTO-R-W is a remote test SK-PHOTO-W capable detector for use with DNR Series duct detector housings. FEATURES & BENEFITS • New modern profile for • Dual LED design • Expanded color • Optional relay, improved aesthetics provides 360°viewing options isolator,and sounder • Stable communication angle • SEMS screws for bases technique with noise • Remote test feature wiring of the separate • Plugs into separate immunity from the panel base base for ease of • Low standby current • Built-in functional test installation and • Two-wire SLC switch activated by maintenance connection external magnet • Optional remote, • Built-in tamper- single gang LED resistant feature accessory • Seated against back pressure DETECTOR SPACING AND INTELLIGENT BASES ACCESSORIES • APPLICATIONS B300-6:White,standard flanged CK300:Color Kit(includes cover and Honeywell recommends spacing low-profile mounting base. trim ring),white,10-Pack. detectors in compliance with NFPA 72. B300-6-BP:Bulk pack of B300-6, CK300-IV: Color Kit(includes cover In low airflow applications with smooth package contains 10. and trim ring),ivory,10-Pack. ceiling,space detectors 30 feet(9m). B300-6-IV:Ivory,standard flanged CK300-BL:Color Kit(includes cover For specific information regarding low-profile mounting base. and trim ring),black,10-Pack. detector spacing,placement,and B501-WHITE:White,standard M02-04-01:Detector test magnet. special applications refer to NFPA 72. European flangeless mountingbase.UL p 9 MO2-09-00:Telescoping test magnet. System Smoke Detector Application listed. Guide,document A05-1003,is available RAl00Z:Remote LED annunciator B501-BL:Black,standard European SMB600:Surface Mounting Kit at systemsensor.com flangeless mounting base.UL listed. (flanged). INSTALLATION 8501-IV:Ivory,standard European TR300:Replacement trim ring for The SK PHOTO W Series plug-in flangeless mounting base.UL listed. 6300-6,white. p g detectors use a separate base to B200S-WH:White,Intelligent, TR300-IV:Replacement trimring for simplify installation,service,and programmable sounder base. B300-6-IV,ivory. maintenance.Installation instructions B200S-IV:Ivory,Intelligent, are shipped with each detector. programmable sounder base. B200SR-WH:White,Intelligent sounder Mount base(all base types)on an base for retrofit applications. electrical backbox which is at least 1.5" B200SR-IV:Ivory,Intelligent sounder (3.81 cm)deep. base for retrofit applications. NOTE: B200S-LF-WH:White,Low Frequency 0Intelligent,programmable sounder •Because of the inherent supervision base. provided by the SLC loop,end-of-line resistors are not required.Wiring B200S-LF-IV:Ivory,Low Frequency "T-taps"or branches are permitted for Intelligent,programmable sounder Style 4(Class"B")wiring. base. B200SR-LF-WH:White,Low •When using relay or sounder bases, Frequency Intelligent sounder base for consult the installation sheet for device retrofit applications. limitations between isolator modules B200SR-LF-IV:Ivory,Low Frequency and isolator bases. Intelligent sounder base for retrofit applications. ORDERING INFORMATION B224RB-WH:White,plug-in System SK-PHOTO-W:Photoelectric smoke Sensor relay base. detector,white. B224RB-IV:Ivory,plug-in System SK-PHOTO-R-W:Photoelectric smoke Sensor relay base. detector,remote test capable,for use B224B1 WH:White,plug-in System with DNR(W)duct smoke detectors, Sensor isolator detector base. white. B224BI-IV:Ivory,plug-in System SK-PHOTO-T-W:Photoelectric smoke Sensor isolator detector base. detector with thermal sensing,white. SK-PHOTO-W Series Detector Technical Specifications ID PHYSICAL COMPATIBILITY For a complete listing of all compliance approvals and Height:2.0"(51mm)installed in B300-6 base The SK-PHOTO-W series detectors are certifications,please visit Diameter:6.2"(156mm)installed in B300-6 compatible with the following Honeywell Silent www.silentknight.com. base 4.1"(104 mm)installed in B501 base Knight fire alarm control panels: Microsoft,Windows,and the Windows Logo are Weight:3.4 oz(95 g) 6820:Addressable fire alarm control panel registered trademarks oof 6820EVS:Addressable fire alarm control panel Microsofttr Corporation.or ENVIRONMENTAL M with an emergency voice system. Silent Knights,System Operating Temperature range: 9 y 6808:Addressable fire alarm control panel Sensor°and Honeywell° Photo:32°F to 122°F(0°C to 50°C) are registered 6700:Addressable fire alarm control panel trademarks of Honeywell Photo with Thermal:32°F to 100°F(0°C to International,Inc. 38°C) 5700:Addressable fire alarm control panel 5808:Addressable fire alarm control panel This document is not UL listed Velocity range:Photo/Photo with intended to be used for 5820XL:Addressable fire alarm control panel installation purposes.We Thermal:0 to 4,000 fpm(0 to 20 m/sec) try to keep our product (suitable for installation in ducts) 5820XL-EVS:Addressable fire alarm control information up-to date and accurate.We Humidity:10%to 93%non-condensing panel with an emergencyvoice system cannot cover all specific applications or anticipate Thermal Ratings:Fixed Temperature Set point: AGENCY LISTINGS AND APPROVALS all requirements.All 135°F(57°C) For exact certification listings for each model, specifications are subject please reference the respective agency Web site. to change without notice. ELECTRICAL RATINGS UL listed:S6173 For Technical Support, Voltage Range:15 to 32VDC peak FM approved call 800 446 6444. CSFM:7272-0559:0523 Operating Current®24VDC:200µA(one communication every 5 seconds with green LED 411 blink on communication) Maximum Current:4.5mA®24VDC(one communication every 5 seconds with amber LED solid on). For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3516341 RevA 104/18 ri SILENT 800-328-0103 ©2018 Honeywell International Inc. KNIGHT Honeywell • ® SILENT' KNIGHT SK-HEAT-W Series Intelligent Thermal (Heat) Detector Honeywell Silent Knight SK-HEAT-W Series intelligent thermal detectors are designed for both performance and aesthetics.A new modern,sleek, contemporary design and advanced thermal technologies make the SK-HEAT-W Series ideal for both system operation and building design. The point ID address,set using rotary decimal switches,provide specific detector locations.The series includes a 135°F/57°C fixed temperature, rate-of-rise and a 190°F/88°C fixed high-temperature detectors.These thermal detectors provide effective,intelligent property protection in a ' variety of applications. ' SK-HEAT-W • FEATURES & BENEFITS • Sleek and stylish • High temperature • 360°-field viewing • Built-in functional test • Sealed against back contemporary design model(SK-HEAT- angle of the visual switch activated by pressure • Advanced thermal W-HT)factory preset alarm indicators(two external magnet • Plugs into separate technology for fast to 190°F(88°C) bi-color.LEDs).LEDs • Walk test with address base for ease of response • Addressable by device blink green in Normal display(an address of installation and condition and turn on 121 will blink the maintenance • Fixed temperature • Two-wire SLC steady red in Alarm. model(SK-HEAT-W) connection detector LED 12 • SEMS screws for • Integral (pause)-1) factory preset to . Visible LEDs"blink" wiring of the separate 135°F(57°C) communications and • Low standby current base every time the unit is built-in device-type 0 • Rate-of-rise model addressed identification • Designed for • Optional remote, (SK-HEAT-W-ROR), , guilt-in tam er- directsurface or single-gang LED 15°F(8.3°C)per p • Remote test feature electrical box accessory resistant feature from the panel minute mounting APPLICATIONS INTELLIGENT BASES ACCESSORIES Use thermal detectors for protection of B300-6:White,standard flanged CK300:Color Kit(includes cover and property.For further information,refer low-profile mounting base. trim ring),white,10-Pack. to manual 156-6541,Applications B300-6-BP:Bulk pack of B300-6, CK300-IV: Color Kit(includes cover Manual for System Smoke Detectors, package contains 10. and trim ring),ivory,10-Pack. which provides detailed information on B300-6-IV:Ivory,standard flanged CK300-BL:Color Kit(includes cover detector spacing,placement,zoning, low-profile mounting base. and trim ring),black,10-Pack. wiring,and special applications B300A-6-IV:Ivory,standard flanged M02-04-01:Detector test magnet. low-profile mounting base.UL listed. M02-09-00:Telescoping test magnet. INSTALLATION B501-WHITE:White,standard RA100Z:Remote LED annunciator The SK-HEAT-W Series plug-in European flangeless mounting base.UL SMB600:Surface Mounting Kit intelligent thermal detectors use a listed. (flanged). separate base to simplify installation, B501-BL:Black,standard European TR300:Replacement trim ringfor service,and maintenance.Installation P flangeless mounting base.UL listed. B300-6,white. instructions are shipped with each detector 8501-IV:Ivory,standard European TR300-IV:Replacement trim ring for flangeless mounting base.UL listed. B300-6-IV,ivory.. Mount base(all base types)on an B200S-WH:White,Intelligent, electrical backbox which is at least 1.5" programmable sounder base. (3.81 cm)deep. B200S-IV:Ivory,Intelligent, programmable sounder base. NOTE: B200SR-WH:White,Intelligent sounder •Because of the inherent supervision base for retrofit applications. provided by the SLC loop,end-of-line B200SR-IV:Ivory,Intelligent sounder 0 resistors are not required.Wiring base for retrofit applications. "T-taps"or branches are permitted for Style 4(Class"B")wiring. 6200S-LF-WH:White,Low Frequency Intelligent,programmable sounder •When using relay or sounder bases, base. consult the installation sheet for device B200S-LF-IV:Ivory,Low Frequency limitations between isolator modules Intelligent,programmable sounder and isolator bases. base. NOTE:Detectors must be mounted to one B200SR-LF-WH:White,Low of the Intelligent Bases listed below. Frequency Intelligent sounder base for ORDERING INFORMATION retrofit applications. SK-HEAT-W:Thermal heat detector, 6200SR-LF-IV:Ivory,Low Frequency 135°F fixed,white. Intelligent sounder base for retrofit SK-HEAT-ROR-W:Thermal heat applications. detector,135°F rate of rise,white. B224RB-WH:White,plug-in System SK-HEAT-HT-W:Thermal heat detector, Sensor relay base. 190°F high temp,white. B224RB-IV:Ivory,plug-in System Sensor relay base. B224B1-WH:White,plug-in System Sensor isolator detector base. B224BI-IV:Ivory,plug-in System Sensor isolator detector base. SK-HEAT-W Series Detector Technical Specifications PHYSICAL COMPATIBILITY For a complete listing of all compliance approvals and Height:2.0"(51mm)installed in B300-6 base The SK-HEAT-W series detectors are certifications,please visit Diameter:6.2"(156mm)installed in B300-6 compatible with the following Honeywell Silent www•silentknight.com. base 4.1"(104 mm)installed in B501 base Knight fire alarm control panels: Microsoft,Windows,and the Windows Logo are Weight:3.4 oz(95 g) 6820:Addressable fire alarm control panel registered trademarks or trademarks of 6820EVS:Addressable fire alarm control panel ENVIRONMENTAL Microsoft Corporation. with an emergency voice system. Operating Temperature range: Silent Knight',System 6808:Addressable fire alarm control panel Sensor®and Honeywell" Heat-Fixed temperature:-4°F to 100°F(-20°C are registered 6700:Addressable fire alarm control panel trademarks of Honeywell to 38°C) 5700:Addressable fire alarm control panel International,Inc. Heat-Rate of Rise(ROR):-4°F to 100°F(-20°C This document is not ° 5808:Addressable fire alarm control panel to 38°C) intended to be used for o ° ° 5820XL:Addressable fire alarm control panel installation purposes.We Heat-High Temperature:-4°F to 150 F(-20 C try to keep our product to 66°C) 5820XL-EVS:Addressable fire alarm control information up-to panel with an emergency voices stem date and accurate.We Humidity:10%to 93%non-condensing g y y cannot cover all specific applications or anticipate Thermal Ratings:Fixed Temperature Set point: AGENCY LISTINGS AND APPROVALS all requirements.All 135°F(57°C) For exact certification listings for each model, specifications are subject please reference the respective agency Web site. to change without notice. Rate-of-Rise Detection:15°F/min.(8.3°C/min UL listed:S2101 For Technical Support, High Temperature Heat:190°F(88°C)Electrical FM Approved call800-446-6444, Ratings CSFM:7270-0559:0511 ELECTRICAL RATINGS Voltage Range:15 to 32VDC peak Standby current(max.avg.):200uA®24 VDC (one communication every 5 seconds with LED enabled). LED current(max.):4.5mA @ 24 VDC("ON"). For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com • Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 351637 I Rev AI04/18 SILENT 800-328-0103 ©2018 Honeywell International Inc. ®KNIGHT INSTALLATION AND MAINTENANCE INSTRUCTIONS SYSTEM I SENSOR® B300-6 and B300-6-1V 3825 Ohio Avenue,St.Charles,Illinois 60174 1-800-SENSOR2,FAX:630-377-6495 6" Plug-In Detector Bases www.systemsensor.com SPECIFICATIONS Base Diameter: 6.1 inches(155 mm) Base Height: 0.76 inches(19 mm) Operating Temperature: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com. Electrical Ratings: Operating Voltage: 15 to 32 VDC Standby Current: 170 µA Listings:UL268 BEFORE INSTALLING FIGURE 2.MOUNTING DETECTOR TO BOX Please read the System Smoke Detectors Application Guide, which provides detailed information on detector spacing,placement,zoning,wiring,and spe- cial applications.Copies of this application guide are available from System Sensor.NFPA 72 guidelines should be observed. DECOR DECORATIVE RING NOTICE:This manual should be left with the owner/user of this equipment. IMPORTANT:The detector used with this base must be tested and maintained t regularly following NFPA 72 requirements.The detector should be cleaned at 1 4 'WA.) least once a r' year. et I �\ GENERAL DESCRIPTION , '®/io qj The B300-6 and B300-6-IV are plug-in detector bases intended for use in an ,\ intelligent system, with screw terminals provided for power (+ and-), and ..\ 1/,�_ ; / remote annunciator connections. Communication takes place over the power i, DETECTOR lines(+ and-). � BASE BASE TERMINALS 6 NO. FUNCTION 1 Power(-),Remote Annunciator(-)2 Power(+) 40 o 3 Remote Annunciator(+) 4I a m� FIGURE 1.TERMINAL LAYOUT ��m�� TERMINAL 2 C2036-01 eo IIIIIIII TERMINAL I TERMINAL3 "'" INSTALLATION AND WIRING GUIDELINES(SEE FIGURE 8)�� , All wiring must be installed in compliance with all applicable local codes �«i r; \ and any special requirements of the authority having jurisdiction.Proper wire ,�' C1• gauges should be used.The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the' il Qo �/ like- lihood of wiring errors. Improper connections can prevent a system from re- TERMINAL 4 /1 m O sponding properly in the event of a fire. e For signal wiring(the wiring between interconnected detectors),it is recom- mended that the wire be no smaller than 18 AWG(0.823 mm2).Wire sizes up Co127-07 to 12 AWG(3.31 mm2)may be used with the base. MOUNTING This detector base mounts directly to 4-inch square(with and without plaster Make electrical connections by stripping about 3/8 inch(10 mm)of insulation rings),4-inch octagon,31/2-inch octagon,and single gang junction boxes.To from the end of the wire(use strip gauge molded in base).Then slide the wire mount,remove the decorative ring by turning it in either direction to unhook under the clamping plate and tighten the clamping plate screw.Do not loop the snaps,then separate the ring from the base. Install the base on the box the wire under the clamping plate.(See Figure 4.) using the screws supplied with the junction box and the appropriate mounting Check the zone wiring of all bases in the system before installing the detec- slots in the base. tors.This includes checking the wiring for continuity,correct polarity,ground Place the decorative trim ring on the base and rotate it in either direction until fault testing and performing a dielectric test. it snaps into place.(See Figure 2.) The base includes an area for recording the zone,address,and type of detec- tor being installed. This information is useful for setting the detector head address and for verification of the detector type required for that location. Once all detector bases have been wired and mounted, and the loop wiring IIIIIhas been checked,the detector heads may be installed in the bases. 1 I56-6566-001 11/17/2017 TAMPER-RESIST FEATURE FIGURE 5A.ACTIVATE TAMPER-RESIST FEATURE NOTE:Do not use the tamper-resist feature if a removal tool will be used. PLASTIC LEVER • The detector base includes a tamper-resist feature that prevents removal of the detector without using a small screwdriver or similar tool. To activate this feature,use needle-nose pliers to break the tab on the detector base as shown in Figure 5A.Then,install the detector. To remove the detector from the base once the tamper-resist feature has been activated, remove the decorative ring by rotating it in either direction and BREAK TAB AT DOTTED LINE BY pulling it away from the base.Then,insert a small screwdriver into the notch, TWISTING TOWARD CENTER OF BASE as indicated in Figure 5B, and press the plastic lever toward the mounting C0130-00 surface before rotating the detector counterclockwise for removal. FIGURE 5B.DETECTOR REMOVAL The tamper-resist feature can be defeated by breaking and removing the plas- USE SMALL-BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW tic lever from the base. However, this prevents the feature from being used v again. rill + REMOTE ANNUNCIATOR remote (RA100Z) / \ Connect the remote annunciator between terminals 1 and 3 using the spade lug terminal included.The spade lug terminal is connected to the base termi- CO130-00 nal as shown in Figure 6. FIGURE 6.CONNECTION TO REMOTE ANNUNCIATOR TERMINAL It is not acceptable to have three stripped wires under the same wiring ter- STRIPPED WIRE minal unless they are separated by a washer or equivalent means.The spade , U lug supplied with the model RA100Z is considered an equivalent means.See Figure 3 for proper installation. FIGURE H.TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP REMOTE CAUTION:DO NOT LOOP WIRE ANNUNCIATOR UNDER TERMINAL 1 OR 2. / \\\ _ \�2 \\\\� _- BREAK WIRE RUN TO PROVIDE \ \\\\OF CONNECTIONS. tu / ---t WIRE WITH SPADE LUG co w ' CO116-00 aZ00piq � �V ‘kr4 v. ,. OJ �. �"epr 0 iLli IC; ‘1 ccoO I ' • 71U / I I —1 (—) CLASS A OPTIONAL WIRING / I D (-0 / CO129-02 FIGURE 4.TERMINAL WIRE INSTALLATION THIS NOT THIS 0 0 0 C0473-00 Please refer to insert for the Limitations of Fire Alarm Systems THREE-YEAR LIMITED WARRANTY System Sensor warrants its enclosed smoke detector base to be free from defects in ma- 12220 Rojas Drive,Suite 700,El Paso TX 79936 USA.Please include a note describing the terials and workmanship under normal use and service for a period of three years from malfunction and suspected cause of failure.The Company shall not be obligated to repair date of manufacture. System Sensor makes no other express warranty for this smoke or replace units which are found to be defective because of damage,unreasonable use, detector base.No agent,representative,dealer,or employee of the Company has the au- modifications,or alterations occurring after the date of manufacture.In no case shall the thority to increase or alter the obligations or limitations of this Warranty.The Company's Company be liable for any consequential or incidental damages for breach of this or any 0 obligation of this Warranty shall be limited to the repair or replacement of any part of other Warranty,expressed or implied whatsoever,even if the loss or damage is caused by the smoke detector base which is found to be defective in materials or workmanship the Company's negligence or fault.Some states do not allow the exclusion or limitation of under normal use and service during the three year period commencing with the date of incidental or consequential damages,so the above limitation or exclusion may not apply manufacture.After phoning System Sensor's toll free number 800-SENSOR2(736-7672) to you.This Warranty gives you specific legal rights,and you may also have other rights for a Return Authorization number,send defective units postage prepaid to:Honeywell, which vary from state to state. System Sensors is a registered trademark of Honeywell International,Inc. 2 I56-6566-001 ©2017 System Sensor. 11/17/2017 GCS / GCC Series • Selectable Candela Evacuation Signals 24 VDC Commander4 Strobe and Horn/Strobe 24 units per carton,29 pounds per carton Applications I R fi The Commander4 Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The GCS/GCC offers tamperproof field selectable candela options of 15,30,75,95,115 1 and 150 candela. The GCC horn offers a continuous or synchable temporal three in 2400Hz and mechanical tones. All tones are easy for the professional to change in the field by using switches. ,R The Commander4 Series comes standard with the 4"mounting plate which c+ ,. incorporates the popular Super-Slide®feature that allows the installer to easily test , I for supervision. The product also features a locking mechanism which secures the I product to the bracket without any screws showing. The Commander4 also features 4 the patented Checkmate instant voltage verification feature which allows the ; installer to check the voltage drop draw and match it to the blueprint. The GC Series appliances are ANSI/UL 464,ANSI/UL 1971,CAN/ULC S525 and/or CAN/ULC S526 listed for use with fire protective systems and are warranted for three 414Y years from the date of purchase. • Standard Features Product Listings • Nominal voltage 24 VDC SIGNALING 47 • Tamperproof field selectable candela options of 15,30,75,95,115&150 ' • Unit Dimensions:6"(15.24 cm)x 2.6"(6.604 cm) `i�+ (4) UaS • Super-Slide®Bracket,Ease of Supervision Testing APPROVED ,. Checkmate Instant Voltage Verification LISTED Prewire entire system,install mounting bracket,then install signals • ANSI/UL 464 and ANSI/UL 1971 Listed Documented lower installation and operating costs • CAN/ULC S525 and/or CAN/ULC S526 Listed Input terminals 12 to 18 AWG • FM Approved • Horn/strobe switch selection for high or low dBA • CSFM:7135-0569:122(GCC) • Horn/strobe switch selection for 2400Hz or mechanical tone 7125-0569:123(GCS) • Horn/strobe switch selection for continuous or temporal 3 • MEA: 285 91 E • Synchronize strobe and/or horn with Gentex AVSM Control Module • Silence audible while visual appliance will remain flashing Patents • Tamperproof re-entrant grill • Surface mount with the GCSB(Gentex Ceiling Surface Mount Box) • 7,375,617 May 20,2008 • Faceplate available in red or off-white • Ceiling mount Product Compliance • NFPA 72 • Americans with Disabilities Act(ADA) • IBC/IFC/IRC • City&State ordinances/Laws/Regulations • Quality Management System is certified to: ISO 9001:2008 CENTEX rr'"�'S= Assembled CORPORATION in the USA GCS 24VDC Selectable Candela,Low Profile Evacuation Strobe • Model Part Number Voltage(VDC) Candela GCS24CR 904-1213-002 24 15,30,75,95,115,150 GCS24CW 904-1215-002 24 15,30,75,95,115,150 GCS24PCR 904-1214-002 l 24 , 15,30,75,95,115,150 GCS24PCW 904 1216 002 i 24 15 30 75,95,115,150 GCC 24VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Reverberant Anechoic Room Model Part Number Voltage(VDC) Candela dBA @ 10ft. dBA @ 10ft. GCC24CR i 904-1209-002 24 15,30,75,95,115,150 81-86 dBA 90 dBA GCC24PCR I 904-1210-002 ', 24 15,30,75,95,115,150 81-86dBA 90 dBA GCC24CW 904-1211-002 i 24 15,30,75,95,115,150 ! 81-86 dBA 90 dBA GCC24PCW 904-1212-002 1 24 15,30,75,95,115,150 , 81-86 dBA 90 dBA R=Red Faceplate,W=White Faceplate. All units are available in plain(no lettering). Plain units are not returnable. ALERT and AGENT bezels available for order. GCS/GCC 24 VDC Strobe Current Ratings(mA) 24 VDC(16-33 Volts) Candela 24VDC ULMax 15Cd 97mA 120mA IIII 30 Cd 97 mA 120 mA 75 Cd 143 mA 200 mA 95 Cd 148 mA 220 mA 115 Cd 201 mA 290 mA 150 Cd 205 mA 1 321 mA GCC24 Product Horn Decibel(dBA)and Current Ratings(mA) Minimum SPL Minimum SPL @ 10ft.per @ 10ft.per UL Max 24 VDC ANSI/UL 464 ANSI/UL 464 Operating Current Horn Mode (HIGH) (LOW) (HIGH) Temp 3 2400Hz I 83 dBA 75 dBA 23 mA Temp 3 Mechanical l 81 dBA 73 dBA* 22 mA Continuous 2400Hz 86 dBA 78 dBA 23 mA Continuous Mechanical 1 84 dBA I 76 dBA 22 mA *Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone. The chime tone is always private mode). S GCS/GCC- Selectable Candela Evacuation Signals • A 0 INIVd JCN 00 I II II 4" III 15.24 cm r ` 6.0" 2.6" 15.24cm /1 III-6.6cm • Gentex Super-Slide® Mounting Bracket III Allows the installer to prewire the system,test for system UL ListedControl Panel Signal Signal supervision,remove the signal head until occupancy,switch out s+ s+ s- H+ H- S+ s+ S- H+ H- Gentex signals without changing mounting brackets and has Supervised S S S S (31 9 1 S ® S locking edge connector for snap-in-place installation. Signal Circuit , \ - END OR UNE RESISIS TOR Gentex Checkmate® Instant Voltage -�' Verification It is often necessary to confirm the voltage drop along a line of , devices.The access holes are provided in the back of the terminal DO NOT PANTblock to allow the voltage to be measured directly without zhi o �„ removing the device.Typically this would be done at the end of theg) (� \) o line to confirm design criteria.Most measurements will be taken (�� a using the S+and S-locations although access is provided to other �J locations.Notice:Care should be taken to not short the test probes. 1 r l', n. Notes iNo ° s¢ s. o • Operating temperature:32°to 120°F(0°to 49°C) 0Ci 3- FO+ • The GCS/GCC Series is not listed for outdoor use I C�� ° 1e i— • For nominal and peak current across ANSI/UL regulated voltage s "^" range for filtered DC power and unfiltered(FWR[Full Wave .1 0 110 Rectified])power,see installation manual • The sound output for the temporal 3 tone is rated lower since o co-60 0 the time the horn is off is averaged into the sound output rating. `� o o While the horn is producing a tone in the temporal 3 mode,its • sound pressure is the same as the continuous mode. , , • This appliance is not recommended for use on coded or pulsing 1 1( signaling circuits GCSIGCC Series 1111/ Selectable Candela Evacuation Signals Architect & Engineering Specifications The audible and/or visible signal shall be Gentex model GCS,GCC or approved equal and shall be listed by Underwriters Laboratories(ANSI/ UL)for use with fire protective signaling systems(ANSI/UL 1971 and/or ANSI/UL 464)and with CAN/ULC S526 and/or CAN/ULCSS25 with intended use in fire alarm systems. The notification appliance(GCC)shall produce a peak sound output of 90 dBA or greater as measured at 24 VDC in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2Hz regardless of power input voltage. The strobe appliance shall have an operating current of 97 mA or less at 24 VDC for the 15 candela strobe circuit.The unit shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate.The GC Series shall be mounted on the ceiling. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. S GENTEX Fire Protection Products Group 1 10985 Chicago Drive 1 Zeeland,MI 49464 551-0051-07 CORPORATION gentex.com 1 Phone:616.392.7195 1 Toll-free:800.436.8391 1 Fax:616.392.42.19 Important Notice:These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules.The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to particular fact patterns.Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. � t ° u• s, .�. 7t . s WGES / WGEC Series Outdoor Evacuation Signals 24 VDC Outdoor Commander Strobe and Horn/Strobe 1 unit per carton,3 pounds per carton Applications The Outdoor Commander Series is a outdoor listed strobe and horn/strobe n comination that offers dependable visible and/or audible alarms for all outdoor " ' needs. �, The WGE Series offers a fixed 75 candela strobe. The WGEC horn/strobe offers a continuous or synchable temporal 3 in 2400Hz,mechanical and chime as well as a whoop tone.All tones are easy for the professional to change in the field by the use of switches. Included with the WGE Series is the GOE or GOELP outdoor enclosure.The enclosure is made of high quality Lexan®material,providing protection from weather related ' 1 conditions and allowing the necessaryfull candela output.This highly constructed p 9 Y - - enclosure meets various installation requirements including deterring moisture from entering the enclosures. The Outdoor Commander Series is equipped with a standard 4"mounting plate which incorporates the Super-Slide®feature that allows the installer to easily test for supervision.The product also features a locking mechanism which secures the )"a product to the bracket without any screws showing. The WGE Series also features the Checkmate®instant voltage verification feature which allows the installer to check the • voltage drop draw and match it to the blueprint. The WGE Series appliances are ANSI/UL 464,ANSI/UL 1638, CAN/ULC 5525 and/or CAN/ULC S526 listed for use with fire protective systems and are warranted for three years from date of purchase. Product Listings SIGNALING Standard Features -^ • Nominal voltage 24 VDC C (00 uSt. • Fixed 75 candela LISTED I ( • GOE Unit Dimensions:5.84"(14.83 cm)high x 4.81"(12.22 cm)wide x 4.22"(10.72 cm)deep • ANSI/UL 464 and ANSI/UL 1638 Listed • GOELP Unit Dimensions:5.84"(14.83 cm)high x 4.81"(12.22 cm)wide x • CAN/ULC 5525 and/or CAN/ULC 5526 Listed 3.25"(8.255 cm)deep • CSFM:7135-0569:122(WGEC) • Super-Slide®-Ease of Supervision Testing 7125-0569:127(WGES) • Checkmate®Instant Voltage Verification 7300-0569:124(ENCLOSURE) • Prewire entire system,install mounting bracket,then install signals • MEA: 285-91E-XVI • Input terminals accept 12 to 18 AWG • Horn/strobe switch selection for high or low dBA Product Compliance • Horn/strobe switch for 2400 Hz,mechanical,chime and whoop tones • Horn/strobe switch for continuous or temporal 3(not available on whoop tone) • NFPA 72 • Synchronize strobe and/or horn by using Gentex AVSM Control Module ▪ Americans with Disabilities Act(ADA) • Silence audible while visual appliance will remain flashing • IBC/IFC/IRC • Tamperproof re-entrant grill and locking screw(optional use) • Quality Management System is certified to: • GOE/GOELP made of clear Lexan®-provides maximum visibility and reliability for ISO 9001:2008 effective visible signaling-allowing full 75cd output • Faceplate available in red or off-white • Wall mount GENTEX •�' = .`/��� in USA CORPORATION GEH Low Profile Evacuation Horn IPReverberant Anechoic Room Model Part Number Voltage(VDC) dBA at 10ft. dBA at 10ft. GEH24-R 904-1205-002 24 'II 70-82 dBA 100 dBA GEH24-W 904-1207-002 24 70-82 dBA 100 dBA NOTE:Must order the GOE or GOELP(sold separately)when using the GEH24 in an outdoor application. WGES24 Evacuation Outdoor Strobe Model Part Number Voltage(VDC) Candela WGES24-75WR 904-1219-002 24 75 WGES24-75WW 904-1220-002 24 j 75 WGES24-75WRLP 904-1261-002 24 I 75 WGES24-75WWLP 904-1263-002 24 75 WGEC24 Evacuation Outdoor Horn/Strobe Reverberant Anechoic Room Model Part Number Voltage(VDC) Candela dBA at 10ft. dBA at 10ft. WGEC24-75WR 904-1217-002 24 75 70-82 dBA 100 dBA WGEC24-75WW 904-1218-002 ' 24 75 70-82 dBA 100 dBA WGEC24-75WRLP 904-1257-002 24 75 70-82 dBA 100 dBA WGEC24-75WWLP i 904-1259-002 I 24 75 70-82 dBA 100 dBA R=Red Faceplate,W=White Faceplate LP=Low Profile(GOELP Enclosure) All units are available in plain(no lettering) Plain units are not returnable IIIWGES/WGEC is shipped with the GOE or GOELP Outdoor Enclosure WGE 24 VDC Series Strobe Current Ratings Candela 24VDC ULMax 75 cd 112mA 170 mA WGE 24 VDC Horn Decibel(dBA)and Current Ratings(mA) Horn Decibel Horn Current Levels(dBA) Ratings(mA) UL MAX Minimum Minimum Regulated SPL at 10ft. SPL at 10ft. 24 VDC per per Operating ANSI/UL 464 ANSI/UL 464 Current Horn Mode (HIGH) (LOW) (HIGH) Temp 3 2400Hz 78 dBA 71 dBA* 28 mA Temp 3 Mechanical 76 dBA 70 dBA* 25 mA Temp 3 Chime 70 dBA* 66 dBA* 15 mA Continuous 2400Hz 81 dBA 74 dBA* 28 mA Continuous Mechanical 80 dBA 72 dBA* 25 mA Continuous Chime 70 dBA* 66 dBA* 15 mA Whoop 82 dBA 69 dBA* 56 mA *Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm • use. Use the high dBA setting for public mode application(not applicable when using the chime tone. The chime tone is always private mode). WGES/WGEC -Outdoor Evacuation Signals • K� Mir rillMll1111111 5.84" A11111111, � 111 11[4 14.83 cm 1---71--) V 441411I�iI� [4 12 4.8221cm [4 4.22" 10.7 cm Gentex Super-Slide® Mounting Bracket UL Listed Allows the installer to prewire the system,test for system Control Signal Signal supervision,remove the signal head until occupancy,switch out Panel s+ s+ s- H+ H- s+ s+ s- H+ H- Gentex signals without changing mounting brackets and has Supervised 9 S 0 0 0 0 . 0 S Signal Circuit III locking edge connector for snap-in-place installation. \ / MI111/ RESISTOR Gentex Checkmate® Instant Voltage O END OF ONE Verification It is often necessary to confirm the voltage drop along a line of devices.The access holes are provided in the back of the terminal1. block to allow the voltage to be measured directly without TOP 0 removing the device.Typically this would be done at the end of the ®���/// line to confirm design criteria.Most measurements will be taken �� using the 5+and S-locations although access is provided to other locations.Notice:Care should be taken to not short the test probes. G= R It ti /,O\� Notes E E 1 - • The WGE Series is listed for outdoor use. Indoor operating I 411 temperature:32°to 120°F(0°to 49°C). Outdoor operating I [�11 �.. temperature:-31°to 150°F(-35°to 66°C) = ( ; III- • For nominal and peak current across ANSI/UL regulated voltage A r� l ti V� T ' range for filtered DC power and unfiltered(FWR[Full Wave I L j CiJ l Rectified])power,see installation manual F> • The sound output for the temporal 3 tone is rated lower since �0 the time the horn is off is averaged into the sound output rating. DO NOT While the horn is producing a tone in the temporal 3 mode,its ® 0 PAINT 0 sound pressure is the same as the continuous mode. • This appliance is not recommended for use on coded or pulsing signaling circuits • Fps Zbtg_cc,ts2 /pts WGES / WGEC Series Outdoor Evacuation Signals Architect & Engineering Specifications The audible and/or visible signal shall be Gentex WGES,WGEC Outdoor Evacuation Signal Series or approved equal and shall be listed by Underwriters Laboratories Inc.per ANSI/UL 1638 and/or ANSI/UL 464 and CAN/ULC S526 and/or CAN/ULCS525. The notification appliance (WGEC)shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/ visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 170mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela requirements of the ADA(75cd). The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models. The appliance shall be capable of testing supervision without disconnecting wires.Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit. The appliance has extended temperature range of-31°to 150°F(-35°to 66°C). The appliance shall satisfy virtually all outdoor and severe environment applications. The GOE Enclosure is includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to allow for drainage,the seal on the GOE Enclosure is not water tight. The GOELP Enclosure includes a weather seal for mounting to wall and intended for use with universal electrical box. To allow for drainage,bottom edge of enclosure is not water tight. GENTEX Fire Protection Products Group 110985 Chicago Drive I Zeeland,MI 49464 551-0047-04 CORPORATION gentex.com I Phone:616.392.7195 I Toll-free:800.436.8391 I Fax:616.392.4219 Important Notice:These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules.The materials do not address all legal considerations as there is inevitable uncertainty regarding Interpretation of laws,regulations and rules and the application of such laws,regulations and rules to particular fact patterns.Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. Honeywell • ®SILENT' KNIGHT SK-RELAY Intelligent Relay Module The SK-RELAY is an addressable relay module for use with Honeywell Silent Knight Series fire alarm control panels(FACPs).The SK-RELAY allows a Silent Knight FACP to switch discrete contacts by code command.The relay contains two isolated sets of Form C contacts,which operate as a DPDT switch.No supervision is provided for the notification appliance circuit. Honeywell Si11 VT The SK-RELAY contacts can be used for virtually any normally open or ®'�`�t4tir normally closed application.Each SK-RELAY is programmed with a unique signaling line circuit(SLC)loop address.When an event occurs that C+i controls the SK-RELAY,the relay is triggered by the FACP. cat loh INSTALLATION The SK-RELAY mounts directly into a 4"square electrical box.The box must SK-RELAY have a minimum depth of 2-1/8".A surface mount electrical box(System Sensor®PN SMB500)is available from Silent Knight. FEATURES & BENEFITS • Two sets of Form C • Panel controlled • Polling LED visible contacts status LED that through the cover • Rotary address flashes green in plate switches for fast normal state and is • SEMS screws for easy installation solid red in alarm wiring • Contacts are rated for • Relay programming is • UL Listed a variety of amps(see completely flexible— Specifications) can be mapped to zone conditions • SK-RELAY Technical Specifications I. Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.sitentknight.com. 4.675"H x 4.275"W x 1.4"D SK-RELAY:Relay Module Microsoft,Windows,and Shipping Weight:6.3 oz(196 g) the Windows Logo are ACCESSORIES. registered trademarks ELECTRICAL SMB500:4"Square Surface Mount Electrical Box or trademarks of Operating Voltage:15-32 VDC CB500:Module Barrier Microsoft Corporation. End-of-Line Resistance:Not used tem SLC Standby&Alarm Current:.255mA max @ COMPATIBILITY Silentsr°K and H Sneywe Sensor"and Honeywell' 24VDC(one communication every 5 sec with LED The SK-RELAY is compatible with the following are registered enabled) Honeywell Silent Knight fire alarm control panels: trademarks of Honeywell 6820:Addressable fire alarm control panel International,Inc. ENVIRONMENTAL 6820EVS:Addressable fire alarm control panel This document is not Operating Temperature:32°F-120°F(0°C- with an emergency mass notification system. intended to be used for 49°C) installation purposes.We 6808:Addressable fire alarm control panel Humidity:10%-93%non-condensing 6700:Addressable fire alarm controlpanel try to keep our product information up-to RELAY CONTACT RATINGS 5700:Addressable fire alarm control panel date and accurate.We 3.OA @ 30VDC resistive 5808:Addressable fire alarm control panel cannot cover all specific 5820XL:Addressable fire alarm control panel applications or anticipate 0.9A @ 110VDC resistive all requirements.Alt 0.9A @ 125VAC resistive 5820XL-EVS:Addressable fire alarm control panel specifications are subject with an emergency mass notification system. to change without notice. 0.5A @ 125VAC inductive(PF=.35) 0.7A @ 75VAC inductive(PF=.35) For Technical Support, call 800-446-6444. S For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell411) Silent Knight Honeywell 12 Clintonville Road Northford,CT 06472 Doc 3501271 Rev GI 11/17 MI SILENT' 800-328-0103 ©2017 Honeywell International Inc. MA KNIGHT ----""1111119 Honeywell • SILENT. 13 KNIGHT SK-MONITOR-2 Addressable Dual Monitor Module The SK-MONITOR-2 module is capable of monitoring two separate Class B circuits simultaneously,making it idealfor water-flow tamper switch and flow switch monitoring. if 40 % 110 The SK-MONITOR-2 is an addressable monitor module with two initiating - j circuits for use with Honeywell Silent Knight series fire alarm control panels x (FACPs).The SK-MONITOR-2 acts as an interface to contact devices,such as waterflow switches and pull stations. a!""."".' The SK-MONITOR-2 supports Class B supervised wiring to the toad device. it" (]T, f�91 Conventional 4-wiresmoke detectors can be monitored for alarm and ` f • trouble conditions.. INSTALLATION SK-MONITOR-2 mounts directly into a 4"square electrical box.The box SK-MONITOR-2 must have a minimum depth of 2-1/8".A surface mount electrical box 41110 (System Sensor''part number SMB500)is available from Silent Knight. FEATURES & BENEFITS • Monitor two circuits, • Panel controlled • Rotary address with unique status LED that switches for fast addresses, flashes green in installation simultaneously normal state and is • SEMS screws for easy • Support for Class B solid red in alarm wiring wiring • Attractive ivory cover • Fully supervised plate • SK-MONITOR-2 Technical Specifications i To Next Device ' 4 For a complete listing of all compliance approvals and n fl certifications,please visit www.silentknight.com. d ° o Olb . 7 , Microsoft,Windows,and ��1 -- " the Windows Logo are TT11 trademarks o:... Microsofttrademarks Corporation. 0 't,u) tf Mooft Corporation. ` , O 00 Compatible FRCP Silent Knight®,System Two initiating device circuits NFPA U u Sensor®and Honeywell® Stlye B Power limited 230NA Max C are registered 12VDC max r1 n SLC trademarks of Honeywell Out IN I International,Inc. ti? e O s r This document is not __ ___ + intended to be used for TT " u ` installation purposes.We jj "� ' try to keep our product �-''�-' � information up-to K'- 0 - .O Jll date and accurate.We (( �� CC//�� cannot cover all specific LI IJ applications or anticipate all requirements.All Wiring SK-Monitor-2 Modules specifications are subject to change without notice. PHYSICAL AGENCY LISTINGS AND APPROVALS For Technical Support, call 800-446-6444. Height:4.5"H x 4"W x 1.25"D ULListed Shipping Weight:6.3 oz(196 g) CSFM Approved City of New York Approved ELECTRICAL 0 Operating Voltage:15-32 VDC COMPATIBILITY Standby and Alarm Current:750pA max @ 24VDC The SK-MONITOR-2 is compatible with the (one communication every 5 sec with 47K EOL) following Honeywell Silent Knight fire alarm End-of-Line Resistance:47K12 control panels: 6820:Addressable fire alarm control panel ENVIRONMENTAL 6820EVS:Addressable fire alarm control panel Operating Temperature:32°F-120°F(0°C- with an emergency mass notification system. 49°C) 6808:Addressable fire alarm control panel Humidity:10%-93%non-condensing 6700:Addressable fire alarm control panel 5700:Addressable fire alarm control panel ORDERING INFORMATION 5808:Addressable fire alarm control panel SK-Monitor-2:Dual Monitoring Module 5820XL:Addressable fire alarm control panel ACCESSORIES. 5820XL-EVS:Addressable fire alarm control panel SMB500:4"Square Surface Mount Electrical Box with an emergency mass notification system. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com III S 2 Knight Honeywell 12 Clintonville Road Northford,CT 06472 Doc 3501241 Rev E 111/17 0 SILENT' 800-328-0103 ©2017 Honeywell International Inc. KNIGHT GHSLF Series 24 VDC,520 Hz square wave audible and fixed candela strobe 24 units per carton Applications The GHSLF is a high quality,low profile,low frequency audible and visible appliance that offers a dependable audible and visual alarm.The GHSLF is ideal for any occupancy that requires notification appliances. The GHSLF horn offers a 520 Hz square wave,temporal 3 tone.A jumper selection is available for normal or loud decibel tone.A temporal 4 pattern is available when used with the Gentex GTSM Synchronization Control Module. The GHSLF is available in a fixed 15,110 and 177 candela strobe. - The GHSLF is shipped with a standard 4"metal mounting plate which incorporates the popular Super-Slide®feature that allows the installer to easily test for supervision. 7-7 The product also features a locking mechanism which secures the product to the s 1 '= _ bracket without any screws showing. — mm— The GHSLF also features the patented Checkmate-Instant Voltage Verification ry feature which allows the installer to check the voltage drop and match it to the blueprint. The GHSLF is listed to ANSI/UL 1971,ANSI/UL 464, CAN/ULC S525 and CAN/ULC S526, and is listed for use with fire protective systems and is warranted for three years from date of purchase. • Standard Features Product Listings Nominal voltage 24 VDC SIGNALING • Unit Dimensions:6-1/2"(16.5 cm)high x 5-1/2"(14.0 cm)wide x 2"(5.0 cm)deep • Produces a 520 Hz square wave,temporal 3 tone Cr (2) US • Fixed candela options:15,110 and 177 LISTED • Jumper selection for normal or loud dBA • Super-Slide'Bracket-Ease of Supervision Testing • ANSI/UL 1971 and ANSI/UL 464 Listed • Checkmate'-Instant Voltage Verification • CAN/ULC S525 and CAN/ULC 5526 Listed • Prewire entire system,install mounting bracket,then install signals • CSFM:7135-0569:0148 • Input terminals accept 12 to 18 AWG • Synchronize horn/strobe with Gentex GTSM Synchronization Control Module Product Compliance • Temporal 4 pattern available when used with Gentex GTSM Synchronization Module • NFPA 72 • Temporal 4 520 Hz measured per ANSI/UL 2075 • IBC/IFC/IRC • Tamperproof re-entrant style grill and locking screw(optional use) • Americans with Disabilities Act(ADA) • Faceplate available in red or off-white • Quality Management System • Wall mount is certified to:ISO 9001:2008 Model Part Number Nominal Voltage(VDC) Candela GHSLF15R 904-0620-002 24 VDC 15 Cd GHSLF15W 904-0618-002 24 VDC 15 Cd GHSLF110R 904-0537-002 24 VDC 110 Cd GHSLF110W 904-0536-002 24 VDC 110 Cd GHSLF177R 904-0533-002 24 VDC 177 Cd GHSLF177W ! 904-0532-002 24 VDC '.. 177 Cd R=Red Faceplate,W=White Faceplate.All units are plain(no lettering). ALERT and FIRE bezels available for order. GENTEX •�`"�_��� Assembled in the USA CORPORATION GHSLF 24 VDC Series 0 [ Yi,',.' '' r e 0 t','e',,IC 1,' l'...;. "t e;i L'x'. 0 a 11 I:!' V IS I I LI; :;,,Km a[ Horn Decibel Levels:Reverberant Room(dBA) Minimum SPL at 10ft.Per Minimum SPL at loft.Per Horn Mode ANSI/UL 464(NORMAL) ANSI/UL 464(LOUD) Temporal 3 520 Hz 76.3 dBA 78,8 dBA Temporal 4520Hz* " 80.6 dBA 82.0dBA *Temporal 4 520 Hz measured per ANSI/UL 2075 24 VDC Nominal Horn/Strobe Current Horn/Strobe Current Ratings Ratings(mA) Over Input Voltage Range of 16-33V(mA) ULMAX ULMAX 24 VDC 24 VDC Regulated 24 VDC Regulated 24 VDC Operating Current Operating Current Operating Current Operating Current Candela Horn Mode (NORMAL) (LOUD) (NORMAL) (LOUD) 15 Temporal 3 520 Hz 112.0 mA 144.0 mA 124.0 mA 182.0 mA 15 Temporal 4 520 Hz 158.0mA 175.0 mA j 195.0 mA 291.0 mA 110 Temporal 3 520 Hz 193.0 mA 223.0 mA 280.0 mA 326.0 mA 110 Temporal4 520 Hz 241.0 mA 291.0 mA 384.0 mA 474.0 mA 177 :Temporal 3 520 Hz 268.0 mA 293.0 mA 365.0 mA 393.0 mA 177 I Temporal 4 520 Hz 337.0 mA 391.0 mA 427.0 mA 525.0 mA • Notes UL Listed Control Signal Signal • Operating temperature:32°to 120°F(0°to 49°C) Panel S+ S. S- H+ H- S+ S+ 5- H+ H- • The GHSLF is not listed for outdoor use Supervised 9 6 Seel I9 6 S S e • For nominal and peak current across ANSI/UL regulated voltage Signal Circuit range for filtered DC power and unfiltered(FWR[Full Wave \ 0 F--- END OFLINE RESISTOR Rectified])power,see installation manual O ,y • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating • This appliance is not recommended for use on coded or pulsing , �J �a signaling circuits LI*NOT PANT • The four pulse temporal pattern(temporal 4)can only be /� ° obtained on this product when used in conjunction with the o o 0 Gentex GTSM synchronization module C 0 I • See GTSM control module manual(550-0632,manual issue date (02-01-15)for synchronization module wiring diagrams.GTSM —-- 1 manual can be obtained at www.gentex.com/fire,or call Gentex Red Wires Vic;»] `,o TIJ -i -1_, lr�ia S4 Corporation at 1-800-436-8391 ~ Stral 0 0 Black Wires MI S- LI --•► H¢ ZE 1J I Optional Loud 411il'• H_ _ _ s Decibel Install l�\I t III Jumper 111 \ I, b v r-Thl / ) 0/7 • � � GHSLF 24 VDC Series • Low Frequency Audible DO w.run 6.5" } �� •-�� 16.5 cm wv A 1 �... 116, I 1 14 cm HH 411 Gentex Super-Slide® Mounting Bracket Architect & Engineering Specifications Allows the installer to prewire the system,test for system The audible and visible appliance shall be Gentex model GHSLF. supervision,remove the signal head until occupancy,switch out The appliance shall be listed with Underwriters Laboratories(ANSI/ Gentex signals without changing mounting brackets and has UL)for use with fire protective signaling systems(ANSI/UL 1971 locking edge connector for snap-in-place installation. and ANSI/UL 464)and with CAN/ULC 5526 and CAN/ULC 5525 with intended use in fire alarm systems.The GHSLF will produce a Gentex Checkmate® Instant Voltage peak sound output of at least 75 dBA as measured in an anechoic chamber.The GHSLF shall also maintain a minimum flash rate of Verification 1 Hz or up to 2 Hz regardless of power input voltage. The strobe It is often necessary to confirm the voltage drop along a line of appliance shall have an operating current of 365 mA or less for the devices.The access holes are provided in the back of the terminal 177 candela strobe circuit with the horn set at the NORMAL setting. block to allow the voltage to be measured directly without The appliance shall be polarized to allow for electrical supervision removing the device.Typically this would be done at the end of the of the system wiring.The unit shall be provided with a mounting line to confirm design criteria.Most measurements will be taken bracket with terminals and barriers for input/output wiring and using the 5+and S-locations although access is provided to other be able to mount to a single gang or double gang box or double locations.Notice:Care should be taken to not short the test probes. workbox without the use of an adapter plate.The GHSLF shall be mounted on the wall.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC.The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. GENTEX Fire Protection Products Group 110985 Chicago Drive I Zeeland,MI 49464 GHSLF-01 CORPORATION gentex.com I Phone:616.392.7195 I Toll-free:800.436.8391 I Fax:616.392.4219 Important Notice:These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules.The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to particular fact patterns,Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. GES3 / GEC3 Series • Selectable .. niela Evacuation Sionals 12 VDC and 24 VDC Commander3 Strobe and Horn/Strobe 24 units per carton,28 pounds per carton Applications The Commander3 Series is a low profile strobe and horn/strobe combination that 1 c t`,t1 offers dependable audible and visual alarms and the absolute lowest current t.. available. .., The GE3 Series 24 VDC offers tamperproof field selectable candela options of 15, 30,60,75,and 110 candela.The 12 VDC offers tamperproof field selectable candela options of 15,30,60,and 75 candela. The GEC3 horn/strobe offers a continuous or synchable temporal 3 in 2400Hz,mechanical and chime as well as a whoop tone.All tones are easy for the professional to change in the field by the use of switches. +�+►- Ipgommovi qW t3 . The Commander3 Series is shipped with a standard 4"metal mounting plate which ;+ incorporates the popular Super-Slide®feature that allows the installer to easily test Inv for supervision.The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander3 also features the patented Checkmate®instant voltage verification feature which allows the installer to check the voltage drop draw and match it to the blueprint. The GE3 Series appliances are ANSI/UL 464,ANSI/UL 1971,CAN/ULC S525(24 VDC ..., only)and/or CAN/ULC 5526(24 VDC only),is listed for use with fire protective systems and are warranted for three years from date of purchase. • Product Listings Standard Features SIGNALING • Nominal voltage 12 VDC and 24 VDC (0) • 24 VDC field selectable candelas:15,30,60,75&110 C (1 US • 12 VDC field selectable candelas:15,30,60&75 LISTED 1 I • Unit Dimensions:5"(12.7 cm)high x 4.5"(11.43 cm)wide x 2.5"(6.35 cm)deep • Super-Slide®Bracket,Ease of Supervision Testing • ANSI/UL 464 and ANSI/UL 1971 Listed • Checkmate®Instant Voltage Verification • CAN/ULC 5525 and/or CAN/ULC 5526 Listed • Prewire entire system,install mounting bracket,then install signals (24 VDC only) • Documented lower installation and operating costs • CSFM:7135-0569:122(GEC3-24&GEH-24) • Input terminals accept 12 to 18 AWG 7125-0569:123(GES3-24) • Horn/strobe switch selection for high or low dBA 7125-0569:129(GES3-12) • Horn/strobe switch for 2400 Hz,mechanical,chime and whoop tones 7135-0569:130(GEC3-12&GEH-12) • Horn/strobe switch for continuous or temporal 3(not available on whoop tone) • MEA: 285-91-E(GEC3-24&GES3-24) • Synchronize strobe and/or horn with Gentex AVSM Control Module 580-06-E(GEC3-12&GES3-12) • Silence audible while visual appliance will remain flashing • Tamperproof re-entrant style grill and locking screw(optional use) Patents • Surface mount with the GSB(Gentex Surface Mount Box) • 7,375,617 May 20,2008 • Faceplate available in red or off-white • Wall mount � Product Compliance • NFPA 72 • Americans with Disabilities Act(ADA) • IBC/IFC/IRC • Quality Management System is certified to: ISO 9001:2008 GENTEX F� 4_ - _"'� Assembled 111 CORPORATION 3ntheUSA • GES3 12 VDC/GES 24 VDC Selectable Candela,Low Profile Evacuation Strobe Model Part Number Voltage(VDC) Candela GES3-12W8 904-1235-002 12 15,30,60,75 GES3-12WW 1 904-1237-002 1_ 12 15,30,60,75 i GES3-24WR i 904-1321-002 241.. 15,30,60,75,110 GES3-24WW 904-1319-002 24 15,30,60,75,110 GEC3 12VDC/GEC3 24VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Reverberant Anechaic Room Model Part Number Voltage(VDC) Candela dBA at 10ft. dBA at 10ft. GEC3-12WR i 904-1231-002 12 15,30,60,75 62-82 dBA 100 dBA GEC3-12WW I 904-1233-002 12 15,30,60,75 62-82 dBA 100 dBA GEC3-24WR i 904-1317-002 24 1 15,30,60,75,110 62-82 dBA 100 dBA GEC3-24WW 1 904-1315-002 24 15,30,60,75,110 1 62 82 dBA 100 dBA R=Red Faceplate,W=White Faceplate All units are available in plain(no lettering) Plain units are not returnable ALERT and AGENT bezels available for order GE3 12 VDC/24 VDC Strobe Current Ratings(mA) 12 VDC(8-17.5 Volts) 24 VDC(16-33 Volts) Candela I 12 VDC I UL Max 24 VDC UL Max 15cd 106 mA 1 92 mA 30 mA 42 mA • 30cd 131 mA ! 141 mA 42 mA 58 mA 60cd 86 mA 260 mA 66 mA 97 mA 75cd 237 mA 312 mA I 80 mA 116 mA 110cd 103 mA 161 mA GE3 12 VDC/24 VDC Horn Decibel(dBA)and Current Ratings(mA) 12 VDC(8-17.5 Volts) 24 VDC(16-33 Volts) Horn Decibel Horn Current Horn Decibel Horn Current Levels(dBA) Ratings(mA Levels(dBA) Ratings(mA) UL MAX UL MAX Minimum Minimum Regulated Minimum Minimum Regulated SPL at 10ft., SPL at 10ft., 12 VDC SPL at 10ft., SPL at 10ft., 24 VDC per per Operating per per Operating ANSI/UL464 ANSI/UL464 Current ANSI/UL464 ANSI/UL464 Current Horn Mode (HIGH) (LOW) (HIGH) (HIGH) (LOW) (HIGH) Temporal 3 2400 Hz 76 dBA 69 dBA' 29 mA 78 dBA 71 dBA* 28 mA Temporal 3 Mechanical 75 dBA 68 dBA* 26 mA 76 dBA 70 dBA* 25 mA Temporal 3 Chime 62 dBA' 60 dBA* 13 mA 70 dBA" 66 dBA* 15 mA Continuous 2400 Hz 79 dBA L 74 dBA* 29 mA 81 dBA 74 dBA* 28 mA Continuous Mechanical i 78 dBA 72 dBA* 26 mA 80 dBA 72 dBA* 25 mA Continuous Chime 63 dBA* 1 61 dBA* 13 mA 70 dBA* 66 dBA* 15 mA Whoop 78 dBA 71 dBA* 55 MA 82 dBA 69 dBA* 56 mA *Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone. The chime • tone is always private mode). GES3/GEC3 - Selectable Candela Evacuation Signals 0 1/' ( `...____. III 1 1 t 6 ,.A01111P.-- i I .I_,_ x_, ,,,,, I� ■. IPMII 12.7 mI i "_ l CI I) __, ■ .■ IN ,PI ■■ ,_ \ li ►_ II�i ...._ 1.1 DO „� ,, I r II' 4.5"11.4cm 6.35cm Id Gentex Super-Slide® Mounting Bracket UL Listed Allows the installer to prewire the system,test for system Control Signal Signal supervision,remove the signal head until occupancy,switch out Panel s+ s+ s- H+ H- s+ S. s- H+ H- Gentex signals without changing mounting brackets and has Supervised 9 S S 0 S . . Is 0 S Signal Circuit II locking edge connector for snap-in-place installation. \ / • RESISTOR Gentex Checkmate® Instant Voltage O END OF LINE 1.11 Verification It is often necessary to confirm the voltage drop along a line of devices.The access holes are provided in the back of the terminal % - - �• - - , _,,,,, block to allow the voltage to be measured directly without (� removing the device.Typically this would be done at the end of the 111/// line to confirm design criteria.Most measurements will be taken �� using the S+and S-locations although access is provided to other n locations.Notice:Care should be taken to not short the test probes. 4—r II R 0 Notes .E 1 4; �. '.- • Operating temperature:32°to 120°F(0°to 49°C) --- (:),] • The GES3/GEC3 Series is not listed for outdoor use PE �_ • For nominal and peak current across ANSI/UL regulated voltage N • 1���'�I� - range for filtered DC power and unfiltered(FWR[Full Wave t C:,D, O Rectified])power,see installation manual L11 • The sound output for the temporal 3 tone is rated lower since /r the time the horn is off is averaged into the sound output rating. E3 CD C30 While the horn is producing a tone in the temporal 3 mode,its sound pressure is the same as the continuous mode. 0 • This appliance is not recommended for use on coded or pulsingMN ME\ j! signaling circuits • GES3 / GEC3 Series Selectable Candela Evacuation Signals Architect & Engineering Specifications The audible and/or visible signal shall be Gentex GES3,GEC3 Series or approved equal and shall be listed by Underwriters Laboratories(ANSI/ UL)for use with fire protective signaling systems(ANSI/UL 1971 and/or ANSI/UL 464)and with CAN/ULC S526(24 VDC only)and/or CAN/ULC 5525 (24 VDC only)with intended use in fire alarm systems. The notification appliance(GEC3)shall produce a peak sound output of 100 dBA or greater at 12 VDC or 24 VDC as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2 Hz regardless of power input voltage.The strobe appliance shall have an operating current of 42 mA or less at 24 VDC for the 15 Cd strobe circuit and 92 mA or less at 12 VDC for the 15 Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The GE3 Series shall be mounted on the wall. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power at 24 VDC or a voltage range of 8-17.5 volts at 12 VDC. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. • GENTEX Fire Protection Products Group 110985 Chicago Drive I Zeeland,MI 49464 551-0050-07 CORPORATION gentex.com Phone:616.392.7195 I Toll-free:800.436.8391 I Fax:616.392.4219 Important Notice:These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gentex makes no representations and warranties,express or implied,that these materials are complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules.The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to particular fact patterns.Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules. Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. INTELLIKNIGHT ACCESSORY SILENT KNIGHT B200S/B200S-LF Intelligent Sounder Base by Honeywell The B200S sounder base series is designed for new and existing commercial dwelling unit applications. It offers maximum flexibility in installation, configuration, and operation to meet or exceed UL 268 and UL 464 requirements. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. B200S/B200S-LF The sounder base "listens in" to the communication between the attached sensor head and the fire alarm control panel (FACP)to adopt the same address as the detector, but as a unique device type on the loop. The ,/' u, 44% FACP can then use that address to command an individual - -- • sounder—or a group of sounders—to activate. In (.' ` addition, the FACP's will enable custom tone patterns. • III 1 The B200S series sounder bases recognize the System f., • Sensor synchronization protocol. This enables it to be used „?' ���+++••• as a component of the general evacuation signal—along • with other System Sensor horns, horn strobes, and chimes —when connected to a FACP output programmed as B200S-LF B200S sounder base power. The B200S-LF low frequency sounder base is designed to Compatibility meet the NFPA 72 sleeping space requirement to produce a fundamental frequency of 520 Hz +/- 10%with a square The B200S series is compatible with the wave or its equivalent. Studies show that a lower frequency, following SK-series detectors programmed for centered around 520 Hz, is the most ideal to awaken System Sensor protocol (Firmware version of sleeping occupants, even those with mild to severe hearing 13.0 or higher): loss. • SK-Fire-CO Addressable Combination Fire and Features CO Detector • Addressability for maximum configuration flexibility • SK-Photo Photoelectric Smoke Detector and • Supports Continuous,ANSI Temporal 3,ANSI Temporal 4, SK-Photo-T Photoelectric Smoke Detector with and March Time tones Thermal • Custom tone capability with some FACP models • SK-Acclimate Multicriteria Photoelectric Smoke • Ability to synchronize with other System Sensor Detector notification devices • SK-Ion Ionization Smoke Detector • UL 268 and UL 464 compliant • SK-Heat Fixed Temperature Thermal Detector, • Pre-wire mounting plate fits various junction box sizes SK-Heat-ROR Rate-of-Rise Detector with • Uses a mechanical locking feature that prevents the Thermal, and SK-Heat-HT Fixed High removal of the attached sensor head Temperature Thermal Detector • No external relays and input modules needed to The B200S/B200S-LF are compatible with the supervise the Aux power following IntelliKnight FACP's: • 520 Hz +/— 10% square wave tone (B200S-LF ) Installation 5808 5808 • The B200S series sounder bases can be mounted directly 5820XL to 4" (10.16 cm) square, 4" (10.16 cm) octagon, 3 1/2" (8.9 5820XL-EVS cm) octagon, single-gang or double-gang junction boxes. P/N 351565 Rev A ©2014 Honeywell International Inc. INTELLIKNIGHT ACCESSORY O Model B200S/B200S-LF Sounder Base '- - - ;_—OPTIOWLRBINOTE A11NJNCIAOHYODELAA oZ/IOOZ i 1 (—)WO / i (.)ac / i u 1 u I, ,) IL! i —Ixa� 61 I " ' IR ig x ea (f)Sounder Base Power (-)Sounder Base Power (.)NAC --4 Yf---i+�—� 11 L157E� (-)NAC d 4 4RESISTOR 4.7N Wiring B200S/B200S-LF Specifications Sound Output • Physical Volume Greater than 85 dBA minimum Height: 2.0" (5.08 cm)less sensor measured in a UL reverberant room at 10 feet, 24 Volts(in continuous Width: 6.875" (17.46 cm) tone). Shipping Weight: B200S- .50 lb. (227gm) B200S-LF-.60 lb. (272gm) Ordering Information B200S Intelligent Sounder Base Electrical B200S-LF Intelligent Low Frequency Sounder Aux Power Voltage 16 to 33 VDC(VFWR) Base Aux Power Standby M02-04-01 Detector Test Magnet Current .55 mA maximum Aux Power Alarm M02-09-01 Telescoping Test Magnet Current B200S 35 mA maximum Aux Power Alarm Current B200S-LF 140 mA maximum SLC Operating Voltage 15 to 32 VDC SLC Standby/Alarm Current 300 pA max (base only) Environmental Operating Temperature: 32°F— 120°F (0°C—49°C) Humidity: 10%—93% non- condensing SILENT �j This document is not intended to be used for installation purposes.We try to Pit • keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight 12 by Honeywell Clintonville Road, Northford,CT 06472-1610 Phone: (800)328-0103, Fax:(203) mimmininimm 484-7118.For Technical Support,Please call 800-446-6444. Assembled In America www.silentknight.com ---14.11111111911 Honeywell I Acdressable Devices 0 Elv Sn�i SK-FIRE-CO-W Multi-Criteria Fire/CO Detector General Description SK-FIRE-CO-W is a plug-in,addressable device that provides both fire and carbon monoxide(CO)detection.The detector combines four separate sensing elements to sense multiple components of a fire:smoke,CO,light/flame,and heat.This approach enables enhanced sensitivity to real fire with heightened immunity to nuisance particulates.For CO,the detector's electrochemical sensing cell creates a separate ' signalsafety for life CO detection. a ., Multiple sensors and communication can greatly reduce nuisance alarms compared to single sensing methods.Sophisticated algorithms maximize the advantages of all y h 4 yttOr four sensor types creating our best detection strategy offering heightened immunity to nuisance particulate and enhanced sensitivity to real fire. SK-FIRE-CO-W in B200S-WH sounder base • Photoelectric sensors detect airborne particles associated with smoke. • Thermal sensors detect heat and rate-of-rise(135°F fixed temperature threshold). • Infrared sensors discern tight patterns in the environment as an additional data • point for alarm determination. This ability to reject certain nuisance alarm triggers,such as theater smoke,supports the use of the fire/CO detector in applications where moderate to heavy nuisance conditions exist that might cause single sensing detectors to false alarm. UL models meet UL 268 7th edition and UL 521 listing requirements for fire detection and UL 2075 standard for system-connected life safety carbon monoxide detection. Released through the incomplete burning of various fuels,CO is a colorless,odorless and deadly gas that is virtually impossible to detect with the human senses.Because the potential exists for dangerous levels of CO to accumulate in almost any building, legislation mandating the use of CO detection in commercial spaces continues to grow. B200S series intelligent sounder bases are recommended for use with SK-FIRE-CO-W.These bases can generate either a Temp 3 pattern for fire or a Temp 4 pattern for CO alarm indication.The B200S series bases recognize the System Sensor synchronization protocol for use as a component of the general evacuation signal—along with other System Sensor Audible/Visible devices—when connected to a power supply or Fire Alarm Control Panel(FACP)output capable of generating the System Sensor synchronization pulses. FEATURES & BENEFITS • Detects all four major • Separateaudibtesignal • Automatic drift • New modern profile • UL 268 7th edition,UL elements of a fire for fire or CO alarm compensation for with expanded color 521,and UL 2075 when used with a smoke and CO sensors options listed el • Separate CO detection B200S series base signal • ReatTest"CO testing • Uses only one address • 10-year CO cell with • Highest nuisance capability on the SLC loop end-of-life warning alarm immunity SK-FIRE-CO-W Technical Specifications 0 PHYSICAL/OPERATING ORDERING INFORMATION Silent Knight®andRealTest' Dimensions: SK-FIRE-CO-W:Advanced multi-criteria fire/C0 detector, aHoneywellre registeredInternati tradeonalmarksInc.of Height:2.7'(69 mm)installed in B200S series sounder white ©2019.All rights reserved. base Bases Unauthorized use of this Diameter:6.875"(175 mm)installed in B200S series B501-WHITE:4"Mounting base,white document is strictly sounder base B501-WHITE-BP:4"mounting base,white,10-pack prohibited. Weight:3.4 oz.(95 g) B501-IV:4'Mounting base,ivory This document is not intended Operating Humidity Range:15%to 90%Relative B501-BL:4"Mounting base,black to be used for installation Humidity,Non-condensing purposes.We try to keep our B300-6:6"Flanged mounting base,white -to- Operating Temperature Range:32°F to 100°F(0°C to B300-6-BP:6"Flanged mounting base,white, date and acocurate.We rmation cannot38°C) B300-6-IV:6'Flanged mounting base,ivory cover all specific applications Air Velocity:0 to 4000 ft./min.(0 to 1219.2 m/min.) B200S-WH:Intelligent addressable sounder base,white or anticipate all requirements. Alt specifications are subjectto ELECTRICAL SPECIFICATIONS B200S-IV:Intelligent addressable sounder base,ivory change without notice. Operating Voltage Range:15 to 32 VDC B200S-LF-WH:Intelligent addressable sounder base, Operating Current @ 24 VDC:200 uA(one low-frequency,white Country of origin:Mexico communication every 5 seconds with green LED blink on B200S-LF-IV:Intelligent addressable sounder base,tow- communication) frequency,ivory Maximum Alarm Current:2 mA®24 VDC(one B224BI-WH:Isolator base,white communication every 5 seconds with red LED solid on) B224B1-IV:Isolator base,ivory Maximum Current:4.5 mA®24 VDC(one B224RB-WH:Relay base,white communication every 5 seconds with amber LED solid B224RB IV:Relay base,ivory on) Isolator Load Rating:0.0063 Accessories SMB600:Surface mounting kit(flanged) CO MONITORING UL STANDARD REFERENCE TR300:Trim ring,white Alarm thresholds(in parts per million)are as follows for: TR300-IV:Trim ring,ivory 70±5ppm:Detector response time 60—240 min. CK300-IR:IR color kit(includes cover and trim ring),white, 0 150±5ppm:Detector response time 10—50 min. 10 pack 400±lOppm:Detector response time 4—15 min. CK300-IR-IV:IR color kit(includes cover and trim ring), STANDARDS ivory,10 pack Per UL standard 2075,the SK-FIRE-CO-W has have been CK300-IR-BL:IR color kit(includes cover and trim ring), tested to the sensitivity limits defined in UL Standard black,10 pack 2034. RA100Z:Remote LED annunciator UL Standard:UL 268 7th Edition M02-04-00:Detector test magnet M02-09-00:Telescoping test magnet AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the SK-FIRE- CO-W.In some cases,certain modules may not be listed by certain approval agencies,or listing may be in process. Consult the factory for the latest listing status. UL:S6173 CSFM:7272-0559:0517 Honeywell Silent Knight ill Clintonville Road Northford, Honeywell orthford,CT 06472-1610 203.484.7161 SK-62001 I A 105/19 ®SILENT' www.silentknight.com ©2019 Honeywell International Inc. KNIGHT • P POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm General Signaling A t';R. Burglar Alarm -17 Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires ® Q 0 "" DC Bells-Terminal strip * t Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel I. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in • an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA126 1750070 .12A 85 76 8(200) 12VDC MBA128 1750080 .12A 90 77 10(250) 12VDC MBA1210 1750060 .12A 92 78 6(150) 24VDC MBA246 1750100 .06A 87 77 8(200) 24VDC MBA248 1750110 .06A 91 79 ---> 10(250) 24VDC MBA2410 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. • Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y PAGE 1 OF 2 5/08 POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. I Fig.3 A.C.BELLS 10 WHITE(IN) WHITE(OUT) [ 1, (250) 8„ —1^—�— FROM CONTROL ri (2�) 6" I PANEL OR (150) PRECEDING BELL BLACK(IN) I/ '_ BLACK(OUT) CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. 2 11/16" (68) DWG#776-I NOTES: I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2 END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWG#776-3 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance ill 0 III • ,-, 5 3/4" O _ 3 3/8" 5" r To Next (146) (86) (127) Device or End-of-Line Resistor _ 4 3 3/8" 1 5/8" (86) (41) ..f 4 1/4" (108) Installation DWG#776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. o )111 :3'410 3. Comove wi gong. 3. Connect wiring(see Fig.3). it: • 4. Mount bell mechanism to backbox(bell mechanism must be 0Dmounted with the striker pointing down). / 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). 6. Test all bells for proper operation and observe that they can �5`l BBx-1 ti be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. 4111 PRINTED IN USA MFG.#5400776-REV Y PAGE 2 OF 2 5/08