Report
tvt OF1-co875 1(0200 .u) ►°ICI i=cC,k1W'/ NNE S ASSOCIATES, INC. CONSULTINS ENGINEERS 6915 SW Macadam Avenue,Suite 200, Portland, OR 97219 Phone: 503-892-1188 FAX: 503-892-1190 SUBMITTAL DATA AND REVIEW SUMMARY Mechanical Todav's Date: September 10,2019 Project: Planet Fitness Tigard, OR Architect: Tiland/Schmidt Architects Job #: TS-5194 Submittal Name/#: 15 50 00 .2 Planet Fitness Tigard OR • Submittal Report Review Status Choices No Exception Taken Make Revisions Noted Revise&Resubmit Rejected Submit Specified Item Returned Without Action Section 23 74 12 —Packaged Outdoor Rooftop Units Products Review Status Comments RTU-1 No Exception Taken RTU-2 No Exception Taken RTU-3 No Exception Taken RTU-4 No Exception Taken RTU-5 No Exception Taken RTU-6 No Exception Taken RTU-7 No Exception Taken RTU-8 No Exception Taken MKE &Associates, Inc., has reviewed the above project submittal. The contractor shall take action appropriate to the review directives and the comments provided in the summary given above. Review is only for conformance with the general design concept of the project. Any action is subject to the requirements of the plans and specifications. Contractor is responsible for verification of all dimensions;fabrication and construction techniques; coordinating their work with other trades;and the satisfactory performance of their work in strict accordance with the contract documents. The review is undertaken solely to satisfy engineers obligation to owner and does not relieve contractor from their obligation fully to perform all contract requirements, nor shall such review give rise to any right of action of suit in favor of contractor or third person against engineer or owner Signed: John Thies—Mechanical Designer JT/heo 411 5194 MSub 2 2019-09-10 Div 23 doc 1 - � I SUBMITTAL DATA Order#: Date: 06/20/2019 Project: Planet Fitness Tigard, OR Project #: Submitter: Saul Diaz UPG National Accounts 5005 York Dr, Norman, Oklahoma 73069 405-419-6447 SUBMITTAL NO. 15 50 00-2 Reviewed by: Deacon Construction, LLC BY: SB DATE: 9/9/19 This check does not in any way relieve the Subcontractor or Supplier of their responsibility to verify accuracy of details„quantities and dimensions Information is subject to change without notice.Check local codes. Printed 06/20/2019 Date 06/26/2019 Project Name ALL Planet Fitness Tigard,OR Project Number Client/Purchaser Submittal Summary Page Qty Tag # Model# Description 1 RTU-1 ZJ150N18R2D5EAA1A1 12.5 Ton, Single Packaged R-410A Air Conditioner, High Efficiency, Two Stage Cooling, 12.0 EER, 180 MBH Input Aluminized Steel, Two Stage Gas Heat, 208/230-3-60 • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods (Bottom or Horizontal End Return Only)with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1- 2013, IECC 2015, California Title 24,AMCA 511). • 5 HP High Static Belt Drive Blower • Standard 2"Throwaway Filters • IntelliSpeed control of the VFD based on stages of cooling (Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) •Smart Equipment Controller including Discharge Air, Return Air, and Outdoor Air Temperature Sensors. • Non-Powered Convenience Outlet • HACR Circuit Breaker/Disconnect • Return Air Smoke Detector(Bottom return only) • Micro-Channel "all-aluminum"condenser coil, Copper tube/aluminum fin evaporator coil • Composite Drain Pan - Front Connection 1 RTU-1 1 RC0471 Roof Curb- 14"High, Flat, Uninsulated,Full Perimeter(Shipped knocked Down) 1 RTU-1 2AQ04700524 CO2 Space/Wall Mount Accessory 1 RTU-1 2EC040 t I Enthalpy Field Installed(Includes two humidity sensors) • 1 RTU-2 ZJ078N12R2D5EAA1A2 6.5 n, Single Packaged R-410AAir Conditioner, High Efficiency, Two Stage Cooling, 11.8 EER, 120 MBH Input Aluminized Steel, Two Stage Gas Heat, 208/230-3-60 • Dry Bulb Low Leak Economizer w/Barometric Relief and Power • Exhaust and Hoods (Bottom or Horizontal End Return Only) with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1- 2013, IECC 2015, California Title 24,AMCA 511). •2 HP High Static Belt Drive Blower •Standard 2"Throwaway Filters • IntelliSpeed control of the VFD based on stages of cooling (Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) • Smart Equipment Controller including Discharge Air, Return Air, and Outdoor Air Temperature Sensors. • Non-Powered Convenience Outlet • HACR Circuit Breaker/Disconnect • Return Air Smoke Detector(Bottom return only) Information is subject to change without notice.Check local codes. Printed 06/20/2019 Qty Tag # Model# Description t S • Micro-Channel "all-aluminum" condenser coil, Copper tube/aluminum fin evaporator coil • • Composite Drain Pan - Front Connection 1 RTU-2 1 RC0471 Roof Curb- 14"High, Flat, Uninsulated,Full Perimeter(Shipped Knocked Down) 1 RTU-2 2AQ04700524 CO2 Space/Wall Mount Accessory 1 RTU-2 2EC0402 Kit, Dual Enthalpy Field Installed (includes two humidity sensors) 6 RTU- ZJ120N18R2D5EAA1A1 10 Ton, Single Packaged R-410A Air Conditioner, High Efficiency, 3,4,5,6,7,8 Two Stage Cooling, 12.0 EER, 180 MBH Input Aluminized Steel, Two Stage Gas Heat, 208/230-3-60 • Dry Bulb Low Leak Economizer w/Barometric Relief and Power RTU` s 3 & 4 WILL HAVE Exhaust and Hoods (Bottom or Horizontal End Return Only)with OSA CM OF 320 PER Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1- SCHEDULE O MI w 0 2013, IECC 2015, California Title 24,AMCA 511). • 3 HP High Static Belt Drive Blower • Standard 2"Throwaway Filters • IntelliSpeed control of the VFD based on stages of cooling (Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) • Smart Equipment Controller including Discharge Air, Return Air, and Outdoor Air Temperature Sensors. • Non-Powered Convenience Outlet • HACR Circuit Breaker/Disconnect • Return Air Smoke Detector (Bottom return only) • Micro-Channel "all-aluminum"condenser coil, Copper tube/aluminum fin evaporator coil • Composite Drain Pan - Front Connection RT 1 Ct 4 \ 0 .Roof Curb 14"High,Flat, Uninsulated,Full Perimeter(Shipped 3,4,5,6,7,8 Yy Knocked Do ,.i.. .uF ...., .... ,.,.,..........:: .Qu ......... ..a..____c \........... .aa`..t:xw w...... ..... ..................tea..:. 6 RTU- 2AQ04700524 CO2 Space/Wall Mount Accessory 3,4,5,6,7,8 RTU- 2EC041 Kit, Dual EnthalpyF ���lled des two lumrdlty senso ``\` NOTES: Notes Equipment start-up and commissioning by a factory trained technician is recommended. Contact your supplying distributor or sales representative for additional information & guidance. WARNING:Cancer and Reproductive Harm-www.P65Warnings.ca.gov Information is subject to change without notice.Check local codes. Printed 06/20/2019 YPage:C)RK� Predator3-12.5 Ton Package4 ►i York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#: RTU-1 System: ZJ150N18R2D5EAA1A1 Cooling Performance Total gross capacity 170.8 MBH Sensible gross capacity 121.3 MBH Total net capacity 155.3 MBH , Sensible net capacity 105.8 MBH x a� Efficiency(at ARI 12.00 EER \ � �> AmIntebient DBrated ff.te(mpARI) 15.00 95.0 I EER � \\\\ ; Entering DB temp. 80.0 °F \ Entering WB temp. 67.0 °F \" Leaving DB temp. 57.5 °F • ;- � �" Leaving WB temp. 56.1 °F Power input(w/o blower) 11.50 kW Sound power 85 dB(A) Refrigerant R-410A Refrigerant type , Sysl 10 lbs 8 oz Sys2 91bs 12 oz Gas Heating Performance 12.5 Ton Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and Heating output capacity(Max) 144 MBH each rooftop is completely computer-run tested prior to shipment. Supply air 5000 CFM Unit Features Heating input capacity(Max) 180 MBH Leaving DB temp. 86.7 °F • Two Stage Cooling Air temp.rise 26.7 °F • 180 MBH Input Aluminized Steel,Two Stage Gas Heat SSE 80.0 % • Full perimeter base rails with built in rigging capabilities Stages 2 • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards) Supply air 5000 CFM • Scroll Compressor[s] Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Addl.Unit Losses(Options/Accessories) 0.82 IWG Hoods(Bottom or Horizontal End Return Only)with Economizer Fault Blower speed 1508 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California Max BHP of Motor(including service factor) 5.75 HP Title 24,AMCA 511). Duct location Bottom Motor rating 5.00 HP • Slide-Out Blower/5 HP Belt Drive Motor Assembly Actual required BHP 4.87 HP • Solid Core Liquid Line Filter Driers Power input 4.54 kW • Unit Ships with 2"Throwaway Filters Elevation 0 ft. • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters. Drive type BELT Requires field-supplied drive true • Non-Powered Convenience Outlet • Short Circuit Current:5kA RMS Symmetrical Outside/Mixed Air • Through-the-Curb and Through-the-Base Utility Connections Outside Air Cfm 320 CFM • Single Point Power Connection • HACR Circuit Breaker/Disconnect Electrical Data • Retum Air Smoke Detector Power supply 230-3-60 • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin Unit min circuit ampacity 79.9 Amps evaporator coil Unit max over-current protection 100 Amps • Composite Drain Pan-Front Connection Dimensions&Weight • Tool-free maintenance with features like hinged doors for all-access panels, Hgt 51 in. Len 120 in. Wth 59 in. slide-out blower and blower motor tray Weight with factory installed options 1535 lbs. Clearances —— BAS Controller • • IntelliSpeed control of the VFD based on stages of cooling. Provides Single Right 12 in. Front 36 in. Back 36 in. Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.100 Top 72 in, Bottom 0 in. Left 36 in. • Smart Equipment Controller including Discharge Air, Return Air,and Outdoor Note: Please refer to the tech guide for listed maximum static pressures Air Temperature Sensors. iumme AMERIc.N Y\ Standard Unit Controller: Smart Equipment Control Board iiima CERTIFIED.ouaurr ��® J(r• 3 • Safety Monitoring-Monitors the High and Low-Pressure Switches,the at us 'ku-a .-;.,.r. L\ ' Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition Failures,Safety Lockouts and Repeated Limit Switch Trips. Warranty • One(1)Year Limited Warranty on the Complete Unit • Five(5)Year Warranty-Compressors and Electric Heater Elements • Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger Information is subject to change without notice.Check local codes. Printed 06/20/2019 YORK° Predator 3-12.5 Ton Package Page:5 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Factory Installed Options ZJ150N18R2D5EAA1A1 Equipment Options Option(s) Selected irigle Packaged R-410A Air Conditioner,High %�' Product Cate : y':: ZJ Efficiency w 12.0 EER 12.5 Ton Nominal Cooling Capacity: 150 Two Stage Cooling Heat,Type and Nominal Heat Capacity: !N 8 180 MBH Input Aluminized Steel,Two Stage Gas Heat 5 HP High Static Belt Drive Blower IntelliSpeed control of the VFD based on stages of Blower Option: R cooling(Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) 208/230-3-60 Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods(Bottom or Horizontal End Outside Air Option: D Return Only)with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015, California Title 24,AMCA 511). m Service Options: 5 Non-Powered Convenience Outlet � • HACR Circuit Br ker/D s nect Sensor Options: E Return Air Smoke Detector(Bottom return only) Smart Equipment Controller including Discharge Air, Controls,: A Return.Air, and Outdoor Air Temperature Sensors. Micro-Channel"all-aluminum"condenser coil, Copper Refrigeration: A tube/aluminum fin evaporator coil • Additional Options: I Standard 2"Throwaway Filters Cabinet Options: A Composite Drain Pan-Front Connection ' Product Generation:111111 Field Installed Accessories O 1BD0408 - Burglar Bars (32.0 Ibs) 0 1CV0414- Concentric O 1FE0412- Flue Exhaust O 1 CV0404-Concentric Diffuser,Side Discharge,18X32 Extension Kit(14.0 Ibs) Diffuser,Flush Mount,18X28 0 1 CV0415- Concentric 0 1 FF0414-2"Only Metal Filter O 1CV0405 -Concentric Diffuser,Side Discharge,18X36 Frame Kit(16.0 Ibs) Diffuser,Flush Mount,18X32 0 1 CV0420- Concentric 0 1 FL0402 - Permanent 2"only O 1 CV0406 -Concentric Diffuser,Specialty,24X24 Filter Kit(Includes (4) Four Filters) Diffuser,Flush Mount,18X36 0 1CV0421 -Concentric (2.2 Ibs) O 1CV0413 -Concentric Diffuser,Specialty,28X28 Diffuser,Side Discharge,18X28 0 1CV0426- Concentric Diffuser,Specialty,24X24 Information is subject to change without notice.Check local codes. Printed D6/20/2019 ORI® Predator 3-12.5 Ton Package Page:6 , ' York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 • Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 O 1 GP0405-Gas Piping Kit for 0 ASC Services- Charges for this 0 S1-03103518000-Temp & Bottom Gas Supply Connection Service are Applicable. humidity sensor, 120mm x 80mm, with External Shut-Off(includes: Application, Startup & no display, modular jack, Internal gas pipe, fittings, gas cock Commissioning (ASC) Services warmer/cooler dial, JCI logo (0.4 &panel gaskets) (10.0 Ibs) Available with Daily Fee Plus Ibs) O 1HA0442 - High Altitude Kit for Expenses.This Service Provides O S1-03103519000- CO2 sensor, Natural Gas (1.0 Ibs) a 90 Day DOA Benefit When 120mm x 80mm, no display, screw O 1 HA0443 - High Altitude Kit for Completed by a Factory Certified terminals or modular jack, no logo Propane (1.0 Ibs) Technician. Contact Your (0.2 Ibs) O 1 HG0425- Hail Guard Kit- Distributor, Dealer, or Sales 0 S1-MP-PRTKIT-OP- MAP Diamond Pattern (37.0 Ibs) Representative. Distributors Can (Multiple Access Portal) Gateway O 1 HG0434- Hail Guard Kit- Call 1-877-874-7378 for an ASC Kit- Replacement MAP gateway Provent Style (30.0 Ibs) Quote. protective case, lanyard and O 1 NP0459 - Natural Gas to 0 S1-02812364700 - Blower Sheave communication cable. Use only to Propane Conversion Kit(2-Stage) for 12.5 Ton High Static Field replace worn or damaged (2.0 Ibs) Installed Drive (3.0 Ibs) components. (0.3 Ibs) O 1RC0470- Roof Curb- 8" High, O S1-03102529000 - Non- 0 S1-SE-COM1001-0- Field Flat, Uninsulated, Full Perimeter Networking Wall Sensor-Allows Installed Communication Card for (Shipped Knocked Down) (135.0 remote sensing and control from Simplicity SE control. Can be field Ibs) single or multiple zones. (0.2 Ibs) configurable for BACnet, N2 or • 1RC0471 - Roof Curb- 14" High, O S1-03102529004 - Non- ModBUS MSTP (0.0 Ibs) Flat, Uninsulated, Full Perimeter Networking Wall Sensor with 0 S1-TBSU32P7S-Source 1 (Shipped Knocked Down) (135.0 Over-ride button -Allows remote Branded LX Series, Up to 4 Heat/ Ibs) sensing and control from single or 2 Cool, Electronic 7 Day O 1 RC0472- Roof Curb, Transition- multiple zones. Override allows Programmable (1.2 Ibs) Sunline 7.5T thru 12.5T to setpoint to be overridden for 2 0 S1-YK-MAP1810-OP - MAP Predator 3.0T thru 12.5T(Shipped hour time period. (0.2 Ibs) (Multiple Access Portal) Gateway- Assembled) (200.0 Ibs) 0 S1-03102529006 - Non- For use with SimplicitySE Control. O 1 RC0476- Roof Curb-24" High, Networking Wall Sensor with (0.2 Ibs) Flat, Uninsulated, Full Perimeter Setpoint Adjustment and Over-ride 0 S1-YK-MAP1810-0S-Stationary (Shipped Knocked Down) (135.0 Button-Allows remote sensing MAP Gateway (Includes MAP Ibs) and control from single or multiple Gateway, Field Bus Adapter, O 2AP0402 -Air Proving Switch (1.0 zones.Allows setpoint to be Mounting Bracket and 100 to 240 Ibs) adjusted ± 5° F. Override allows VAC Power Supply). US- • 2AQ04700524- CO2 Space/Wall setpoint to be overridden for 2 compatible counties. (1.9 Ibs) Mount Accessory(5.0 Ibs) hour time period. (0.2 Ibs) O S1-03103489000 O 2AQ04700624- CO2 Unit Mount Temp sensor, Accessory (4.6 Ibs) 80mm x 80mm, LCD display, O 2DF0403 - Dirty Filter Switch (1.0 screw terminals, adjustable Ibs) setpoint, JCI logo (0.1 Ibs) O 2EC0401 - Kit, Single Enthalpy 0 S1-03103490000 Temp sensor Field Installed (1.0 Ibs) w/Economizer FDD, 120mm x • 2EC0402 Kit, Dual Enthalpy 80mm, LCD display, screw Field Installed (Includes two terminals, adjustable setpoint, no humidity sensors) (1.0 Ibs) logo (0.0 Ibs) O 2LA04702424 Low Ambient Kit O S1-03103516000 -Temp & humidity sensor, 120mm x 80mm, (3.2 Ibs) O 2SD04700824 Smoke Detector LCD display,screw terminals, warmer/cooler dial, JCI logo (0.4 - Kit w/ Mounting Hardware for Ibs) Supply Air(Horizontal/Downflow) Only(9.4 Ibs) O S1-03103517000 -Temp sensor, 120mm x 80mm, no display, no dial, screw terminals, no logo (0.4 Ibs) Information is subject to change without notice.Check local codes. Printed 06/20/2019 . r ' YORK® Predator 3-12.5 Ton Package Page:7 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Consolidated Drawing I 2 3 4 D 6 1 8 9 I0 II 32 1.3 =4 .5 '3 NOTES: a CENTER OF OPAVITE i. FOR OUTDOOR USE ONLY, 32-67 ---- TO2NA6E `y W Ip rT+l3, LOCATION 19ASF 39111 4 POINT CORNEA 10.595an< 'Ta E OMIT) 2 �. WEIGHTS H3WN ARE FOR COOLING Ok�Y UNITS. j ,,2,31 i 860) JM1f=T % T q ....-.A D _.. D 3. MIN CIL/LRAMS "O RE; 6,83 .�..d - t r 8 RIGHT SIDE: 12 13051 1E73,57 1 OWN 14113 10363 I s(1295,A 25.5?CS C59 Mel 341 11511 491 12111 4J 11541 Cl! SIDE- 36 1915.1 i i-•-•- 11.84 TA 146E:0653 51 11295,471 25.5 4947,13 270 4123T 363 11551 411 ( 15: 1 355 .E 11 FRONT. 36 [9157 m 1199,13 I 8 1111W 1299 158IT AP 11?-9,21 1 24 1607,5) 149 11991 201 11,81 419 31991 i 359 1591 REAR: 36 [913 TOP: 2 (0111830118.60 33U 1215 5513 1 A€311 0,41 26 16 r 4) 259 11181 211 11261 35 €1S91 28 31A31 .1 DO TOM: D 07 €407 27, 6.82 exS 19623 1 +5 T11411 25,9 5941,11 3I7 11421 3I9 11451 419 11191 i 918 31861 3 4. TO REMOVE THE SLIDE-OUT DRAIN PAIN A REAR CLEARANCE OF 24-38 �"�""�""""""""""-"; [113,3) 17, 114;'V (A,,,,' ':71 I49 15 11263 li3 24.5[6251,57 EH11231 343 11561 483( 191 26I 31131 60 IN 11525 rm3 i5 REQUIRED IF SPACE IS UNAVAILABLE, THE 6i9,2l DRAIN PAN CAN BE REMOVED THROUGH TUC Ei3ON( BY SEPARATING t2 1P� 4 ALTERNATE CONDENSATION DRAIN -I 1 THE CORNER WALL. A B 5: FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES • �i/'"wi �"P 18.50 '`"'_-.--...«•- 8,25 CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 24.23 -•- ,R.. i ;C j ..- IJu/111 e f 1266.11..,.,1 _. 1463,61 6 DOWNFLOW DUCTS 'DESIGNED TO BE ATTACHED TO ACCESSORY [615,41 ;E i ' 1 b 11 ROOD CURB ONLY F UNIT IS MOUNTED SIDE SUPPLY If tFROM M.G. 1 , ;P Zd.Ov �yp1� • _ a " IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED 3Y CROSS BRACES, €L3NGI:) =T 2.I 50 i IF €'04,6) •,4111$1i ( Ilk 6•;ia _, 1' .a1 3 AS DONE ON ACCESSORYROOFCURBS, LI111 Lo^S,SI. ;I. I �j��[�q" � a �� 7. SIDE. DO CI FLANGES ARE 0 75' HIGH. '�... FN I 1 lY Ir_ .INUA111w..... €.RIGHT �_. R 90) DM TIC DO NOT HAVE FLANGES. [.EFT - --- - _ j , 8. MINIMUM CONDENSATION TRAP HEIGHT SHALL fi'- 1.5 TIMES i t__. IN .: �d 7. "... : 28,25 HIT 61 THE LOWEST NEGA :VE STATIC 9. DIMENSIONS IN t l ARE IN MILLIMETERS OR KILOGRAMS, . - �21.09- .., - A .. - I0. OPTIONAL FOIL GUARDS, POWER EXHAUST, ,A NE/ 1t1.39 LS 14 +._ <: Y IC533,41 '. `� ' • cI G ECONOMIZER, DISCONNECT SWITCH, CONVENIENCE OUTLET, 20.14 :1.14 1i I:If3,D7 [d88 2. T ,! � d''" 'r - „�. �y�'"rtf'rq I F AND BAROMETRIC NIIItF 8 FRESH AIR ROODS_RUNN. ISII 6) , 14_5,41 k i � �T t. .. t 1Ghir,w: ,:_ .--. r:. kY.GT.PT >(Pf%A-iHkAi J4€r) ;;NCI;, - "' '_ -+tr� � '' c ;. --- _._ d a t 14.4T w \� 9.....,ar)TTS,M^A:1 ...._ _ _. rT n (367,6) 16 49 ,� SUPPLY ENTRY 0 2,0 1220,81 f r -PO DIRECTION OF AIRFLOW A 18 06 --:-___.__ [416,4 8C'TUM ENTRY: 5''.6 25 25 __ ?'.6S C=3,2T r 1458,81 j„ "o.iig C POWER 5U 16i 51 (133,17 i.'1 -,6) €303,A7 ii CENTER DP GRAVITY 14)9,411 CONTROL z%0111.875 122,231 REAR WAATIA�VIEWEL A I ...VIIWi f INTAKE. HOOD NOT SHOWN IN PH. S VIEW} Dlit3H9ECT SWITCH COVER-., OUTSIDE. A16-} IpPiriA€.1 \ r €NTAKE HOOD t ...._ .... .10 50 ....._ 1� ..... 58, 09 1 tOPTIONAL) c,Mr R ENTRY Pit 5 3E5,51-, ..,\ 13035 31 .......... j..... 141 51 .... .. -- - -......_fir fit tI AIR Nr'v)t ........ •• - -,aimiiii pi 23 T2 Iv r udAI.I . . 1653,3T . 1 ir i 1.4 PANEL,' 2G 1. 6 ur ar-„04 CONTROL FAT RT✓0.A35 t22:23T \ �'A EJ4 1 x f .,...,- _-_-_,-„,-,•,..„•_._ : r: tA1L a � � mo \ ;4, -54503353944/PmATPmm,me......535f ;� POWER ENTRY 2.50(63.51---- - ' s E 7 - - - Q I '_• "HEAT f _' _I Y' BAROMEHIC Rrl_i E[ NOOD_-` A E S * 'H y PJWEA %NAJSi - -' U rt -.0 C 4mr > � .m�-_l.!� ;OPTIMAI1 - l U..........., 4 = ...® KiCt �� .,,5£._ m yyy' Z LT 1± 1 G919/19 LT a Ea i�/� 2, TI I 1130177 q 3B �.. S9 ^0 € 'CI'0NA13 E693,69 j C !. 1:2.,a,:! �'.404,fb - - / I -SE DET„,L A FOR s.00" EAT-- DRAIN LOCATION FXI-Ai)>T 'DIL GUARD / I TIE: EtIE tT 1tErt ('01 IIf3Nki,l EKK CDN'rNErNLE OUT ET--1 1r 8 I ""`� POWER ENTRY 00.871 f22,291 89.00 r El/ \ [2260 6) Fg rt 1 THIS(OPTIONAL L2CNT COIL GUARD NOT SHOWN IN T1.. VILW • 5.3 t. _ _.. __..7.... _ ...._.... .......,-. .......... _ _ _ (.y^ f€! ? AOJ( 1. RN K 0 b51 S ft SW[3.ai 4h RI: i .......... ..... a 9L eEY R[v� 0dlt T REVISION RECORD ES N'f CA ...R 6N6 €xaf�e u€ aesen: M x e .gtaaa nWseema a t aat:'+sfs .:.e€.... [I 5.03 R R€'r.Tr!s [ ) eT B c MATE;(4 k i 1 yr q€sm m 1 i "26 I ADDED DC_�Xf{ry1 HAD BIF W fRE511 A:2 A WO/ETU(AEtfEr A 5 S H A4 ,__„_,,.,. 1 ... .. __ ... 5 'Er+{F=".ra SUBMITTAL DWG. PREDATOR, iec NOT e-111 f.- 1 .e.._ t l`� / Q ZA-18{FD fD/TM60") URI9161 J TAW _.. F 3.h ! N ?'; atA�-?., W CCl"1 CAD .NTT ArV!It RR... A A PHOEAM C C 26.11ADDES RirD WICTI[ RESIDN IN TOP VIEW _ .... I(r ...... .. .. ... 25-I 160934D 4 ES 4Nk....Y0T4 VIAL A qq A € �asu tsi sr A O4 245E U[5..... SCALE 0.300 Vera1oa 1412:EDT€) Bill UNIT TO TABLE _._. 326 r fiat 3M tix!tAa re a GSM - F� Jd,. p} __ __.._...__. ______......................... D , ._.......'[..._2@-I.CHANGE,SPISD(3?i'3 wars .__.._.. 1'•ti....._.. KT 066 vk( ;0,115 mAM rs MAI _........_.A.. I Q£ I ,_,_,_ 1 ) , 4 R 7 8 3 in 1t i2 13 - .. Information is subject to change without notice.Check local codes. Printed 06/20/2019 ; K® Predator 3-12.5 Ton Package Page:8 York Single Package R-410A Air Conditioner Project Name:• Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Component Locations • Cooling With Gas Heat(6.5 Through 10 Tons) Smart Equipment/ control board Filter access Filter drier w/screw connector for T-stat Disconnect location (solid core) o tional disconnect witch) itch (2"or 4"filter options) wiring and network connections ( P ) Terminal block for .,,,,,m1WitifiggiiiioNiielltil,",,,,..: Micro-Channel Aluminum ::::::: ti0n Tube/AluminumFin nameplate " a.4: . inside hinged04, Slide-out motor and access panel j blower assembly for 'r -� „ ` easy adjustment ve _� ` � �� �'�`� " and service Dual stage , cooling for ,. e R '' blower Belt-drmotormaximum comfort VFD location(optional) Power ventor motor Compressor#2 � �$�t'..',Ii.,,:i•i!igillti _access(high- efficiency 20-gauge aluminized .� p steel tubular heat compressor) ^> � d exchanger for Zang life g (stainless steel option) Two-stage gas Base rails w/forklift heating to maintain slots(three sides) warm,comfortable and lifting holes y Slide-out drain pan temperature with 1"NPT, Roof curbs in eight-and '� female connection Intelligent control fourteen-inch heights.Roof�� board for safe and curbs for transitioning from efficient operation York SunlineT" footprint to Side en Ilry power Compressor t?1 access the ZH/ZJ/ZR/ZU/ZW/ZK dToor and cons wiring (high-efficiency compressor) Series footprints door latch knock is are also available(field installed accessory) 1. Information is subject to change without notice.Check local codes. Printed 06/20/2019 �� yo R Kg Predator 3-12.5 Ton Package Page:9 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Low Leak Downflow Economizer Low Leak Downflow Economizer(shown with optional Power Exhaust) _ . i - i` ii i i_ Fresh Air Hood . 1 ' ( ' ; - - f (included) • i'l '. . 1 / N ii, _ _______-___ Low Leak Economizer(included) AI / l ,Power Exhaust(optional)' /t, Bariametric Relief Damper Barometric Relief (included) Hood (included) Low leak economizers are capable achieving low leakage rates of 3 cfmisq. ft at 1" of static pressure, meeting or exceeding the following standards: ASHRAE 90.1-2010 ASHRAE 62 • AMCA 511 (licensed as Class 1 A damper) International Energy Conservation Code (IECC) California Title 24 i The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Information is subject to change without notice.Check local codes. Printed 06/20/2019 yo RK9 Predator 3-12.5 Ton Package Page: 10 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Factory Installed Power Exhaust SP-in.-wg. © O O O o O 4 O 0 C7 O O 0 O O • 0 0 Q 0 0 U1 a C) 0 O U1 f, O 0 3 C k cn a) G et wI in O 0l 0 0 I v 0 0 0 0 0 0 0 0 BHP Information is subject to change without notice.Check local codes. Printed 06/20/2019 re • et yo R K® Predator 3-12.5 Ton Package York Single Package R-410A Air Conditioner Page:11 Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 • Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Seismic Certification . , SPECIAL SEI 3/4 IC CERTIFICATION 41 Johnson ((*)) DCL ,,,,„„C.45504.t.55 IS,5 x OF NO 6-STRUCTURAL 9 Controls COMPONE TS AND SYSTEMS CERTIFICAT OF COMPLIANCE ,,, , .,..,.... Dynamic Certification Laboratories has qualified the listed packaged rooftop units as CERTIFIED for seismic applications in accordance with the following codes and standards: CBC 2013, IBC 2012, 1CC-ES AC-156 2012, ASCE 7-10 The following model designations are included in this certification. A complete fist of certified models,options, and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories, provided by the equipment manufacturer upon request. Unitary Product Group Packaged Rooftop Units (UPG) Seismic Qualification Testing was conducted in acco 1 4'since with and in strict adherence to the standards set forth within the American Society of Civil Engineers I. CE 7)by the independent approval agency,Dynamic Certification Laboratories. The above referenced eq ipment is APPROVED for seismic applications when properly installed and used as intended. The basis of this certification is through testing oft •active and energized components per AC156. This certification covers multiple UPG brands,including ycrk,Johnson Controls,Coleman,Luxaire,Evcon,Fraser- Johnston and Ready Ship. The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response Acceleration,Sds,as determined by the ASCE 7 seismic maps. Various installation locations/isolation configurations are covered under this certification,limited by the Sds value stated in the following table. A seismic importance factor,ip,of 1.5 applies to this certification to include essential facility requirements and life safety applications for post event functionality. The units are approved for both a rigid and flexible mount configuration. Minimum Design Stigliatties of UPG Packaged Rooftop Units • Series Model Tons Sds(g) Fp/Wp ZR/ZJ/ZH/ZK/ZW/ZU/ZT/JA3* 037 3 2.5 1.88 ZR/21/ZH/ZIVZWIZU/2T/JA4* 049 4 2.5 1.88 • ZR/2J/ZH/ZIVZW/ZU/ZT/JA5* 061 5 2.5 1.88 ZR/Z.J/Z-H/ZF/XP/Z1V/ZU/ZiS/XA/106* 078 6.5 2.5 1.88 ZR/21/211/2F/XP/ZIC/ZW/ZU/28/XA/J07*/T* 090 7.5 2.5 1.88 ZR/21/ZIA/ZF/XP/ZOZW/ZUIZS/XA/J08* 102 8.5 2.5 1.88 Zitt7J/ZH/ZF/XP/ZK/ZW/ZU/ZS/XA/J10*/T* 120 10 2.5 1,88 ZR/ZJ/21-1/2F/XP/ZOZW/ZU/ZS/XA/112*/T* 150 12.5 2.0 1.50 Page 1 of 2 Dynamic Certi5cation Laboratories 1315 Greg Street,Suite 105,Sparks,NV 89431—ph:775-358-5085 WWw shaketr,st CCOTI Information is subject to change without notice.Check local codes. Printed 06/20/2019 , .. ' YORK Predator 3-12.5 Ton Package York Single Package R-410A Air Conditioner Page: 12 Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 • Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 Seismic Certification SPECIAL SEIS IC CERTIFICATION v(6)1. DCL ..-,,,,,.._,..—. OF NO STRUCTURAL Johnson Controls COM PONE S AND SYSTEMS CERTIFICATE F COMPLIANCE . ., .... ssewcwzwoownawwwwwwwmeunnrnan Table of Seismic Design Parameters Site Class Fe 1p a„, Re zih D 1.0 1,5 2.5 6.0 1.0 Site and Project Requirements It is the responsibility of the Design Professional of Record to: * Provide engineering for the anchorage and restraint of the unit a Validate Certification Design Parameters with actual site conditions a Provide engineering of all equipment support structures a Confirm component configuration Certification issued by: Dynamic Certification Labor[:tories Document Control Number: 90300-1107-A(rev.1) Original Issue Date: 9/2/11 Revl. Issue Date: 3/26/14 i.,,•!f; S5720 "i '''''a'\ '1....1 TXP 3 tel ,,,,,,,,e- 14$00 cariat ii Common:14i Prod ari uct anagai .."': "r 4,1\ ,..h,,,,,„„...„,.,,,,.....td - Dr.Ahmed ltant SE Dynamic Certification Laboratories Page 2 of 2 Dynamic Certification Laboratones 1315 1,eig Street,StUtie 1.09,spar*ei NV 85131—P9t 715-358-5085 www.shanetecticorn Information is subject to change without notice Check local codes. Printed 06/20/2019 Fl Predator 3-12.5 Ton Package Page: 13 3 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1 • Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1 1RC0471 Roof Curb RIGHT 80-5/8 *► INSULATED DECK UNDER 44. CONDENSER SECTION 24 *��' r 20 8 W DUCT SIZES: I Return 19.5 x 29.5 RETURN Supply 19.5 x 29.5 2 TYP. 440011y7` ROOF OPENING: .444410. 4�Nb ► 46 Long 30 Wide 30 50-1/2 ,i: INSULATED DECK UNDER COMPRESSOR SECTION .* FRONT 4 Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications. For location of horizontal duct applications(On rear of unit),refer to Unit Dimensions details. 1 RC0471 Roof Curb Dimensions Information is subject to change without notice.Check local codes. Printed 06/20/2019 YVORKe Predator 3-12.5 Ton Package Page: 14 0.4 } York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJ078N12R2D5EAA1A2 Cooling Performance Total gross capacity 80.4 MBH ' Sensible gross capacity 58.8 MBH \ x o Total net capacity 75.5 MBH Sensible net capacity 53.9 MBH i ` s Efficiency(at ARI) 11.80 EER a �?;l. s Integrate eff.(at ARI) 14.60 IEER \ Ambient DB temp. 95.0 °F � ' EnteringDB temp. 80.0 °F ] ^•• Entering WB temp. 67.0 °F t Leaving DB temp. 59.1 °F Leaving WB temp. 57.2 °F - Power input(w/o blower) 5.90 kW i r ro Sound power 85 dB(A) Refrigerant Refrigerant type R-410A 0 '""" - Sys1 5 lbs 12 oz Sys2 51bs 12 oz Gas Heating Performance 6.5 Ton Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and Heating output capacity(Max) 96 MBH each rooftop is completely computer-run tested prior to shipment. Supply air 2600 CFM Unit Features Heating input capacity(Max) 120 MBH Leaving DB temp. 94.2 °F • Two Stage Cooling Air temp.rise 34.2 °F • 120 MBH Input Aluminized Steel,Two Stage Gas Heat SSE 80.0 % • Full perimeter base rails with built in rigging capabilities Stages 2 • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards) Supply air 2600 CFM • Scroll Compressor[s] Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Addl.Unit Losses(Options/Accessories) 0.18 IWG ' Hoods(Bottom or Horizontal End Retum Only)with Economizer Fault Blower speed 937 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California Max BHP of Motor(including service factor) 2.30 HP Title 24,AMCA 511). Duct location Bottom Motor rating 2.00 HP • 2 HP High Static Belt Drive Blower Actual required BHP 1.54 HP + Solid Core Liquid Line Filter Driers Power input 1.44 kW • Unit Ships with 2"Throwaway Filters Elevation 0 ft. • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters. Drive type BELT • Non-Powered Convenience Outlet Outside/Mixed Air • Short Circuit Current:5kA RMS Symmetrical Outside Air Cfm 320 CFM • Through-the-Curb and Through-the-Base Utility Connections • Single Point Power Connection Electrical Data • HACR Circuit Breaker/Disconnect Power supply 230-3-60 • Return Air Smoke Detector Unit min circuit ampacity 41.7 Amps Unit max over-current protection 50 Amps • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin Dimensions&Weight evaporator coil Hgt 51 in. Len 89 in. Wth 59 in. • Composite Drain Pan-Front Connection Weight with factory installed options 1285 lbs. • Tool-free maintenance with features like hinged doors for all-access panels, Clearances slide-out blower and blower motor tray BAS Controller • Right 12 in. Front 36 in. Back 36 in. • IntelliSpeed control of the VFD based on stages of cooling. Provides Single Top 72 in. Bottom 0 in. Left 36 in. Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10. Note Please refer to the tech guide for listed maximum static pressures • Smart Equipment Controller including Discharge Air, Return Air,and Outdoor Air Temperature Sensors. nuau"rvtillAlum ti $�us i • Standard Unit Controller: Smart Equipment Control Board • Safety Monitoring-Monitors the High and Low-Pressure Switches,the Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition Failures,Safety Lockouts and Repeated Limit Switch Trips. Warranty • One(1)Year Limited Warranty on the Complete Unit • Five(5)Year Warranty-Compressors and Electric Heater Elements • Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger Information is subject to Change without notice.Check local codes. Printed 06/20/2019 YORK® Predator 3-12.5 Ton Package Page: 15 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 • Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 Factory Installed Options ZJO78N12R2D5EAA1A2 Equipment Options Option(s) Selected Single Packaged R-410A Air Conditioner,High Product Category: Efficiency 11.5 EER 6.5 Ton Nominal Cooling Capacity: 078 Two Stage Cooling Heat Type and Nominal Heat Capacity: 20 MBH Input Alup31,1ed Steel, Two Stage Gas He 2 HP High Static Belt Drive Blower IntelliSpeed control of the VFD based on stages of Blower Option: cooling(Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) Voltage: mEi 208/230 3 60 Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods(Bottom or Horizontal End Outside Air Option: D Return Only)with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015, California Title 24,AMCA 511). E r \\� Service{, . ion-Powered Convenience Outlet SCR Circuit BreakerfDisconnect Sensor Options: Return Air Smoke Detector(Bottom return only) • Controls: A Smart Equipment Controller t g Discharge Air, • Return Air and Outdoor Air Temperature Sensors Micro-Channel"all-aluminum"condenser coil, Copper Refrigeration: A tube/aluminum fin evaporator coil ditional O Standard 2"Throwaway Filters• Cabinet Options: I A Composite Drain Pan-Front Connection ()duct Genera r � , . � �': Field Installed Accessories O 1 BD0408 - Burglar Bars (32.0 Ibs) 0 1 FL0402- Permanent 2" only 0 1 HA0443 -High Altitude Kit for O 1CG0420- Coil Guard (27.0 lbs) Filter Kit(Includes (4) Four Filters) Propane (1.0 Ibs) O 1CV0403 - Concentric (2.2 Ibs) 0 1 HG0411 - Hail Guard Kit- Diffuser,Flush Mount,20RD 0 1 GP0405 - Gas Piping Kit for Diamond Pattern (37.0 lbs) O 1 CV0412 -Concentric Bottom Gas Supply Connection 0 1 HG0432- Hail Guard Kit- Diffuser,Side Discharge,20RD with External Shut-Off(includes: Provent Style (25.0 Ibs) O 1FE0412 Flue Exhaust Internal gas pipe, fittings, gas cock 0 1 NP0459 - Natural Gas to Extension Kit(14.0 Ibs) &panel gaskets) (10.0 Ibs) Propane Conversion Kit(2-Stage) O 1 FF0414 2"Only Metal Filter 0 1 HA0442- High Altitude Kit for (2.0 Ibs) Frame Kit(16.0 Ibs) Natural Gas (1.0 Ibs) Information is subject to change without notice.Check local codes. Printed 06/20/2019 ., El YrORK� Predator 3-12.5 Ton Package Page: 16 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 O 1RC0470- Roof Curb - 8" High, 0 S1-03102529004 - Non- 0 S1-TBSU32P7S -Source 1 Flat, Uninsulated, Full Perimeter Networking Wall Sensor with Branded LX Series, Up to 4 Heat/ (Shipped Knocked Down) (135.0 Over-ride button -Allows remote 2 Cool, Electronic 7 Day Ibs) sensing and control from single or Programmable (1.2 Ibs) • 1RC0471 - Roof Curb- 14" High, multiple zones. Override allows 0 S1-YK-MAP1810-OP- MAP Flat, Uninsulated, Full Perimeter setpoint to be overridden for 2 (Multiple Access Portal) Gateway- (Shipped Knocked Down) (135.0 hour time period. (0.2 Ibs) For use with SimplicitySE Control. Ibs) 0 S1-03102529006 - Non- (0.2 Ibs) O 1 RC0472- Roof Curb, Transition- Networking Wall Sensor with 0 S1-YK-MAP1810-OS- Stationary Sunline 7.5T thru 12.5T to Setpoint Adjustment and Over-ride MAP Gateway (Includes MAP Predator 3.0T thru 12.5T(Shipped Button-Allows remote sensing Gateway, Field Bus Adapter, Assembled) (200.0 Ibs) and control from single or multiple Mounting Bracket and 100 to 240 O 1 RC0476- Roof Curb-24" High, zones.Allows setpoint to be VAC Power Supply). US- Flat, Uninsulated, Full Perimeter adjusted ± 5) F. Override allows compatible counties. (1.9 Ibs) (Shipped Knocked Down) (135.0 setpoint to be overridden for 2 Ibs) hour time pe iod. (0.2 Ibs) O 1 RC0479-Transition Roof Curb- 0 S1-0310348 000 -Temp sensor, 8" High, Small Sunline to Predator 80mm x 80 m, LCD display, O 1WC0412 -Wooden Crate (445.0 screw termi als, adjustable Ibs) setpoint, JCI logo (0.1 lbs) O 2AP0402 -Air Proving Switch (1.0 0 S1-0310349 000 -Temp sensor Ibs) w/Economizer FDD, 120mm x • 2AQ04700524- CO2 Space/Wall 80mm, LCD;display, screw Mount Accessory (5.0 Ibs) terminals, adjustable setpoint, no O 2AQ04700624-CO2 Unit Mount logo (0.0 Ibs) Accessory (4.6 Ibs) 0 S1-03103516000 -Temp & O 2DF0403 - Dirty Filter Switch (1.0 humidity sensor, 120mm x 80mm, Ibs) LCD display,)screw terminals, O 2EC0401 - Kit, Single Enthalpy warmer/cooler dial, JCI logo (0.4 Field Installed (1.0 Ibs) lbs) • 2EC0402 Kit, Dual Enthalpy 0 S1-0310351 000 -Temp sensor, Field Installed (Includes two 120mm x 80 m, no display, no humidity sensors) (1.0 lbs) dial, screw t rminals, no logo (0.4 O 2LA04702412- Low Ambient Kit Ibs) (2.2 Ibs) 0 S1-03103516000 -Temp & O 2SD04700824-Smoke Detector humidity sensor, 120mm x 80mm, Kit w/ Mounting Hardware for no display, modular jack, Supply Air(Horizontal/Downflow) warmer/cooler dial, JCI logo (0.4 Only(9.4 Ibs) Ibs) O ASC Services- Charges for this O S1 0310351000 CO2 sensor, Service are Applicable. 120mm x 80mm, no display, screw Application, Startup & terminals or modular jack, no logo Commissioning (ASC) Services (0.2 Ibs) Available with Daily Fee Plus O S1-MP-PRTKIT-OP- MAP Expenses. This Service Provides (Multiple Access Portal) Gateway - a 90 Day DOA Benefit When Kit- Replacement MAP gateway Completed by a Factory Certified protective case, lanyard and Technician. Contact Your communication cable. Use only to Distributor, Dealer, or Sales replace worn or damaged Representative. Distributors Can components. (0.3 lbs) Call 1-877-874-7378 for an ASC 0 S1-SE-COMI1001-0 - Field Quote. Installed Co�munication Card for O S1-03102529000- Non- Simplicity S control. Can be field Networking Wall Sensor-Allows configurable for BACnet, N2 or remote sensing and control from ModBUS MSTP (0.0 Ibs) single or multiple zones. (0.2 Ibs) Information is subject to change without notice.Check local codes. Printed 06/20/2019 . • • I YORKe ,� Predator 3-12.5 Ton Package York Single Package R-410A Air Conditioner Page: 17 Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAAIA2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAAIA2 Consolidated Drawing NOTES: OPERATING CENTER OF GRAVITY i4 POINT CORNER LOADS {LBS) (BASE UNIT) 1. FOR OUTDOOR USE ONLY. TONNAGE UNIT !WEIGHT (LBS) LOCATION (BASE UNIT) 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. ;_(-BASE UNIT X Y A B C D 3. MIN. CLEARANCES TO BE: i 8.5 ZF 1007 1458 38 965 24 610 i 235 107 1175 79 255 116 342 155 RIGHT SIDE: 12 305 10 Zr 1103 [501 38 965 24 610 257 117 192 87 279 [127]1 375 1170 LEFT SIDE: 36 '915, 8.5 ZH 1030 [467 38 965 24 610 H 240 109 179 81 261 [118] 350 1551 FRONT: 36 915 I 10 ZH 1090 [494] 38 965 24 610 254 115 189 86 276 125 371 [168 REAR: 36 915' 6.5 2J 1030 [467] 39 991] 25 635 7 245 111 191 87 260 118 I 333- BOP: 72 1830] 32.67 8 S ZJ 1060 [48� 39 991 24 610 0 113 195 89' 265 120 BOTTOM: 8 '0r ,--- ] 38 965 24 610 247 112 184 84' 268 1 360 163 4. TO REMOVE THE SLIDE-OUT DRAIN PAN, A REAR CLEARANCE OF [830] 10 Z7 1070 [485] 245 111 191 87' 278 126 357 162 60 In (1525 mm) IS REQUIRED. IF SPACE IS UNAVAILABLE THE 6.83 -� 8 5 & 10 ZR1200 [544 DRAIN PAN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING --. ] 38 965 25.5 [6481I_..297 135 221 100 291 132 i 190 177 THE CORNER WALL. [173] 6.5 XP 1080 [490] 38 [965 25 [635] 262 1191 195 89 266 121 357 162 5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES i 7.5 XP 1090 [494]! 38 [965, 23 584 243 110 181 82 284 129 381 173 �_ CONTACT YOUR S DESIGNED ENGINEERING DEPARTMENT. 2419]38 .5 XP j_ 1137 [516], 38 [965,, 25.5 648 282 128 210 95 276 125 ' 370 1(i8.A 6. DOWNFIOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY [619] t 10 XP ; 1135 [515]; 38 [965 25.5 648 :281 127 ] 209 95 „ 275 125 369 167 # ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, I7 • IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY CROSS BRACES AS DONE ON ACCESSORY ROOF CURBS. 32.06 _ €'-18.00 ± 7.84 7. SIDE DUCT FLANGES ARE 0.75" HIGH. • [814] 1 [457] [199] BOTTOM DUCTS DO NOT HAVE FLANGES. -6.83 8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES . f 1 [ [173] THE LOWEST NEGL AAA IN rTIVE STATIC. T 10. OPTIIONI9. OLONALECOILIGUARD€, POWER ICEXHAUST, GAS ASCHHEAT, -.- 24.24 --ARE IN MILLIMETERS OR KILOGRAMS. ! A ^-. S �/ .�„ ^8 - ALTERNATE CONDENSATION DRAIN [464] y 10.50 E ## 267 AND BAROMETRIC RELIEF AND FRESH AIR HOODS SHOWN, [616] R U 'I �+,i�"."0 a� -T T_' " - J 11 ,11 EXCEPT XP (HEAT PUMP) UNITS. (FROM MTB. p ]I - -....�. DIRECTION OF AIRFLOW f_ ,, [699] L [4�.0� is: i �j E ) � r FLANGE) 27.50 610 50 CENTER OF GRAVITY LEFT N f Y RIGHT 18.25 s u [718] 1 [464) _ \ RN a` RT ¢ ` 374 FPT 1--- .. .- - 1 _, 21.00�-1 �a�" i .. i v M 2528] 19.14 17.14 \ y [533] ,j / [ , [512] [48I6] [435] p 1 1,`,W % SUPPLY 18.06 [459] 5.32 14.47 0� \\. FRONT 0 _..BOTTOM GAS - 2.88 [135] rr368 16.39 5.16 28.25 31.63 [73] + 38.0� - [416] -BOTTOM ENTRY: SUPPLY ENTRY 02.00 [51] [131] Q..._..... [459] -t 18.89 [718] [803] POWER 2.50 [64] OUTSIDE AIR DETAIL A r X [480] ,; CONTTOP VIEW 00.875 [22] BEAR (PARTIAL(INTAKE HOOD NOT SHOWNVINWTHIS VIEW) INTAKE HOOD DISCONNECT SWITCH COVER --\ 89 00 58.09 (OPTIONAL) (OPTIONAL) ,\ 2261 [1475] -__-.,-\ _ ■I. POWER ENTRY 02.50 [64] 4 .._. t ,� ------ I iu 6` ---25.72 , FRESH AIR HOOD/ - ..__.g, \ BLOWER ACCESS GAS INLET Gi3 ECONOMIZER OPT ONAL) FILTER/ [ ] TL PANEL)', OMPRES5OR" ii , OMPRESSOR ' CONTROL ENTRY 00.87S [ 221--_,,, _ ACCESS _ .4" 50.75 • C` ; [1289] ' POWER ENTRY 62,5@ [64J 1 r BAROMETRIC RELIEF HOW/ '"� (I t. • • • 7 POWER EXHAUST(OPTIONAL) • _• i CONVENIENCE OUTLET COVER 7'1 ----11, 21.19 '"---- `--11.38 \ . (OPTIONAL) / - 27.31 - SEE DETAIL A FOR i (538] [289] [694] DRAIN LOCATION ' EXHAUST I .'` - 59.00 LEFT VIEW CONVENIENCE OUTLET--' FLUE '11 [1499] `-COIL GUARD POWER ENTRY 00.875 [22] 89.00[2261] -; (OPTIONAL) FRONT VIEW RIGHT VIEW (OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW) Information is subject to change without notice.Check local codes. Printed 06/20/2019 RK® Predator -12.5- Page: 18 York Single Package R 410A Ton Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ078N12R2D5EAAIA2 Quantity: 1 Tag#:RTU-2 System: ZJ078N12R2D5EAA1A2 Component Locations Cooling With Gas Heat(6.5 Through 10 Tons) Smart EquipmentT"control board Filter drier Disconnect location Filter access wtscrew connector for T-stat (solid core) wiring and network connections (optional disconnect switch) (2"or 4"filter options) Terminal block for Micro-Channel Aluminum Tube/Aluminum Fin hi-voltage connection t Condenser Second model nameplate Slide-out motor and inside hinged blower assembly for access panel ` ] easy adjustment and service Dual stage blower ve cooling for t .- ,, .e'. .� . maximum 1 • / blower motor comfort 1 VFD location(optional) Compressor#2 Power ventor motor access(high- � :� ..20-gauge aluminized efficiency . "s .- steel tubular heat compressor) „ . exchanger for long life ** a • 'Fi rrlii (stainless steel option) 8 w � ip} • Two-stage gas Base rails w/forklift 1 heating to maintain slots(three sides) '3 M warm,comfortable and lifting holes u► Slide-out drain pan temperature with 1"NPT, Roof curbs in eight-and ,= I I female connection Intelligent control fourteen-inch heights.Roof r,,�'�� 7. board far safe and curbs for transitioning from efficient operation York SunlineTM footprint to J3 Side e power Compressor#1 access the ZH(ZJ/ZR2U/ZW/ZK doolreatch and co�i� •I wiring {high-efficiency compressor) Series footprints knock." are also available(field installed accessory) I 1I II l III Information is subject to.'•tenge without notice.Check local codes. Printed 06/20/2019 PORK® Predator 3-12.5 Ton Package Page: 19 ,, ' York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 Low Leak Downflow Economizer Low Leak Downflow Economizer I(shown with optional Power Exhaust) .may -- _ iR.aT. --. K , "�R,QKitltifl .. ��... /a7>W)iN r:. 1, .:. i1 i , i, Fresh Air Hood Ii 'I I[il ; (included) 1ti . � II 4x _ ------- r Low Leak Economizer(included) / �... J Power Exhaust(optional)' /'` Barometric%" Relief Damper Barometric Relief Hood (included) (included) Low leak economizers are capable achieving low leakage rates of 3 cfm/sq. ft at 1" of static pressure, meeting or exceeding the following standards: ASHRAE 90.1-2010 ASHRAE 62 AMCA 511 (licensed as Class 1 A damper) International Energy Conservation Code (IECC) California Title 24 The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Information is subject to change without notice.Check local codes. Printed 06/20/2019 yoRK. Predator 3- . g York Single Package 12 R5-410ATon Air Conditioner e Page:20 Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 Factory Installed Power Exhaust SP-in.-wg. O O O O O O O O O O o 0 0 0 0 0 0 0 0 0 O O 0 U1 _' O 0 Tin 3 o A rn • Ul so 0 • C rrr to O O 0 O CD i! CO 2 tri O O O O 0 O O O O 0 BHP Information is subject to change without notice.Check local codes. Printed 06/20/2019 yoRK® Predator 3-12.5 Ton Package Page:21 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 Seismic Certification SPECIAL SEISMIC CERTIFICATION Johnson dr/ (( )) DC L OF NON-STRUCTURAL Controls COMPONENTS AND SYSTEMS CERTIFICATE OF COMPLIANCE ,sM== Dynamic Certification Laboratories has qualified the I sted packaged rooftop units as CERTIFIED for seismic applications in accordance with the following codes a. d standards: CBC 2013, IBC 2012, !Cc-ES AC-156 2012, ASCE 7-10 The following model designations are included in this certification. A complete list of certified models,options, and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories, provided by the equipment manufacturer upon -equest. Unitary Product Group Packaged Rooftop Units (UPG) Seismic Qualification Testing was conducted in accordance with and in strict adherence to the standards set forth within the American Society of Civil Engineers(ASCE 7)by the independent approval agency,Dynamic Certification Laboratories. The above referenced equipment is APPROVED for seismic applications when properly installed and used as intended. The basis of this certification is through testing oft ctive and energized components per AC156. This certification covers multiple UPG brands,including 1c,Johnson Controls,Coleman,Luxaire,Evcon,Fraser- Johnston and Ready Ship. The seismic values are obtained from the Maximum nsidered Earthquake Short Period Spectral Response Acceleration,Sds,as determined by the ASCE 7 seis maps. Various installation locations/isolation configurations are covered under this certification,I ited by the Sds value stated in the following table. A seismic importance factor,1p,of 1.5 applies to this ification to include essential facility requirements and life safety applications for post event functionality. The its are approved far both a rigid and flexible mount configuration. Maximum Design Sds Values of UPG Packaged Rooftop Unita Series Model Tons Sds(g) Fri/Wp ZR/ZJ/ZH/ZK/2W/ZU/ZT/JA3* 037 3 2.5 1.88 ZR/ZJ/ZH/ZK/Z'iAf/ZU/ZT/JA4* 049 4 2.5 1.88 ZRIZI/ZH/ZKIZW/ZU/ZT/JA5* 061 5 2.5 1..88 ZR/23/Zii/ZF/XP/ZOZW/ZU/ZS/XA/.106* . 078 6,5 2.5 1.88 ZR/2J/ZWZF/XP/ZOZW/ZU/ZS/XA/107*/T* 090 7.5 2.5 1.88 ZR/ZJ/ZH/ZF/XP/ZK/ZW/ZU/ZS/XA/JOS* 102 8.5 2.5 1.88 ZR/ZJ/ZH/ZF/XP/2K/ZVV/ZU/ZS/XA/J10*/T* 120 10 2.5 1.88 ZR/ZJ/ZH/ZF/XP/ZK/ZW/ZU/ZS/XA/J12*/T* 150 12.5 2.0 1.50 Pagel of 2 Dynamic Certification Laboratories 1315 Greg Street,Suite 109,SparkS, V 59431—ph:77S-35S-50E5 www.shaketest.corn Information is subject to change without notice Check local codes. Printed 06/20/2019 -9 YORK Predator 3-12.5 Ton Package Page.22 9 York Sing le Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 Seismic Certification SPECIAL SEISMIC CERTIFICATION OF NON-STRUCTURALJohnson Controls COMPONENTS AND SYSTEMS CERTIFICATE OF COMPLIANCE Table of Seismic Design Parameters Site Class F. 1„ ap Rr, z/h Q 1.0 1.5 2.5 6.0 1.0 Site and Project Requirements It is the responsibility of the Design Professional of Record to: • Provide engineering for the anchorage and restraint of the unit • Validate Certification Design Parameters with actual site conditions • Provide engineering of all equipment support structures • Confirm component configuration Certification Issued by: Dynamic Certification Laboratories Document Control Number: 903110-1107-A(rev.1) Original Issue Date: 9/2/11 Revl.issue Date: 3/26/14 -p r 3 Id, s4mN%(Arun it € r et tcvts.incatporated Dr.Ahmed Itani,SE Dynamic Certification Laboratories Page 2 of 2 Gehamic Cert rtcatiura Laboratohes 1315 Greg Street,Suite 109,Sparks,.Pre 93431,'..ph.77S358-54989 +vww.uhaketest.crsm Information is subject to change without notice.Check local codes. ' Printed 06/20/2019 ilk Predator 3-12.5 Ton Package Page.23 �° Y�C3RK York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2 Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2 1RC0471 Roof Curb RIGHT 80-5f8 INSULATED DECK UNDER CONDENSER SECTION -----rv-------7-' 20 414; 1444S44•40. '� SUPPLY ' 20 6� DUCT SIZES: �� "'7 Return 19.5 x 29.5 tMIUiNI M�'�ll � Supply 19.5 x 29.5 RETURN2 TYP• ``���` :„."1,0Y-'''''' ROOF OPENING: / 40�,�' 30 Long 30 Wide \, 30 50-112 �''`' ► INSULATED DECK UNDER COMPRESSOR SECTION FRONT '''"--,„,,,,,,4" . ''Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications. For location of horizontal duct applications(On rear of unit),refer to Unit Dimensions details. 1RC0471 Roof Curb Dimensions Information is subject to change without notice.Check local codes. Printed 06/20/2019 cl 0 Predator 3-12.5 Ton Package Page:24 .' YORK1 ► York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 • Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Cooling Performance -k Total gross capacity 130.0 MBH • Sensible gross capacity 96.0 MBH ' Total net capacity 120.3 MBH ; Sensible net capacity 86.3 MBH Efficiency(at ARI) 12.00 EERt o Integrated eff.(at ARI) 14.60 IEER i Ambient DB temp. 95.0 °F � ti Entering DB temp. 80.0 °F k.i, w ` 1 Entering WB temp. 67.0 °F Leaving DB temp. 57.8 °F ,�.. Leaving WB temp. 56.7 °F „ —_, Power input(w/o blower) 9.00 kW Sound power 91 dB(A) m Refrigerant Refrigerant type R-410A 0"`""---- Sys1 7 lbs 14 oz Sys2 7 lbs 14 oz Gas Heating Performance 10 Ton Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and Heating output capacity(Max) 144 MBH each rooftop is completely computer-run tested prior to shipment. Supply air 4000 CFM Unit Features Heating input capacity(Max) 180 MBH Two Stage Cooling Leaving DB temp. 93.3 °F • Air temp.rise 33.3 °F • 180 MBH Input Aluminized Steel,Two Stage Gas Heat SSE 80.0 % • Full perimeter base rails with built in rigging capabilities Stages 2 • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards) Supply air 4000 CFM • Scroll Compressor[s] Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Addl.Unit Losses(Options/Accessories) 0.58 IWG Hoods(Bottom or Horizontal End Return Only)with Economizer Fault Blower speed 1226 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California Max BHP of Motor(including service factor) 3.45 HP Title 24,AMCA 511). Duct location Bottom Motor rating 3.00 HP • Slide-out Blower/3 HP Belt Drive Motor Assembly Actual required BHP 3.06 HP • Solid Core Liquid Line Filter Driers Power input 2.85 kW • Unit Ships with 2"Throwaway Filters Elevation 0 ft. • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters. Drive type BELT • Non-Powered Convenience Outlet Requires field supplied drive true • Short Circuit Current:5kA RMS Symmetrical Outside/Mixed Air • Through-the-Curb and Through-the-Base Utility Connections Outside Air Cfm 100 CFM • Single Point Power Connection • HACR Circuit Breaker/Disconnect Electrical Data • Return Air Smoke Detector Power supply 230-3-60 • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin Unit min circuit ampacity 57.2 Amps evaporator coil Unit max over-current protection 70 Amps • Composite Drain Pan-Front Connection Dimensions&Weight • Tool-free maintenance with features like hinged doors for all-access panels, Hgt 51 in. Len 89 in. Wth 59 in. slide-out blower and blower motor tray Weight with factory installed options 1325 lbs. Clearances BAS Controller • IntelliSpeed control of the VFD based on stages of cooling. Provides Single Right 12 in. Front 36 in. Back 36 in. Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10. Top 72 in. Bottom 0 in. Left 36 in. • Smart Equipment Controller including Discharge Air, Return Air,and Outdoor Note Please refer to the tech guide for listed maximum static pressures Air Temperature Sensors. yy Standard Unit Controller: Smart Equipment Control Board , ��1 Y�7ai Safety Monitoring-Monitors the High and Low-Pressure Switches,the �.:. us ,v-.'- -=- \^_- Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition Failures,Safety Lockouts and Repeated Limit Switch Trips. Warranty • One(1)Year Limited Warranty on the Complete Unit • Five(5)Year Warranty-Compressors and Electric Heater Elements • Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger Information is subject to change without notice.Check local codes. Printed 06/20/2019 YORK° Predator 3-12.5 Ton Package Page:25 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Factory Installed Options ZJ120N18R2D5EAA1A1 Equipment Options Option(s) Selected Single Packaged R 410AAirConditioner,High Product Category: ZJ Efficiency 10 Ton Nominal Cooling Capacity: 120 Two Stage Cooling Heat Type and Nominal Heat Ca : N98 180 MBH Input Aluminized Steel, Two Stage Gas Heat 3 HP High Static Belt Drive Blower IntelliSpeed control of the VFD based on stages of Blower Option: R cooling(Provides Single Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10) Voltage: 2 208/230-3-60 Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and Hoods (Bottom or Horizontal End Outside Air Option: D Return Only)with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015, California Title 24,AMCA 511). Service Opti Non-Powered Convenience Outlet ons: 5 HACR Circuit Breaker/Disconnect • Sensor Options: E Return Air Smoke Detector(Bottom return only) Smait Equipment Controller including Discharge Air, • Controls: A • .;•.• Return Air,and Outdoor Air Temperature Sensors_ Micro-Channel"all-aluminum"condenser coil, Copper Refrigeration: A tube/aluminum fin evaporator coil Additional Options: "I Standard 2"Throwaway Filters Cabinet Options: A Composite Drain Pan - Front Connection Product Generation: Field Installed Accessories O 1 BD0408 - Burglar Bars (32.0 Ibs) 0 1 CV0413- Concentric 0 1 FF0414-2"Only Metal Filter O 1CG0420- Coil Guard (27.0 Ibs) Diffuser,Side Discharge,18X28 Frame Kit(16.0 Ibs) O 1CV0403 -Concentric 0 1CV0414- Concentric 0 1 FL0402- Permanent 2"only Diffuser,Flush Mount,20RD Diffuser,Side Discharge,18X32 Filter Kit(Includes (4) Four Filters) O 1CV0404 -Concentric 0 1CV0420- Concentric (2.2 Ibs) Diffuser,Flush Mount,18X28 Diffuser,Specialty,24X24 0 1 GP0405 -Gas Piping Kit for O 1CV0405 -Concentric 0 1CV0426- Concentric Bottom Gas Supply Connection Diffuser,Flush Mount,18X32 Diffuser,Specialty,24X24 with External Shut-Off(includes: O 1CV0412 -Concentric 0 1FE0412-Flue Exhaust Internal gas pipe, fittings, gas cock Diffuser,Side Discharge,20RD Extension Kit(14.0 Ibs) & panel gaskets) (10.0 Ibs) Information is subject to change without notice.Check local codes. Printed 06/20/2019 514 YVORK® Predator 3-12.5 Ton Package Page:26 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 O 1 HA0442 - High Altitude Kit for 0 ASC Services- Charges for this 0 S1-03103518000 - Temp & Natural Gas (1.0 Ibs) Service are Applicable. humidity sensor, 120mm x 80mm, • Q 1HA0443 - High Altitude Kit for Application, Startup & no display, modular jack, Propane (1.0 Ibs) Commissioning (ASC) Services warmer/cooler dial, JCI logo (0.4 O 1HG0411 - Hail Guard Kit- Available with Daily Fee Plus Ibs) Diamond Pattern (37.0 Ibs) Expenses. This Service Provides 0 S1-03103519000 - CO2 sensor, O 1 HG0432- Hail Guard Kit- a 90 Day DOA Benefit When 120mm x 80mm, no display, screw Provent Style (25.0 Ibs) Completed by a Factory Certified terminals or modular jack, no logo O 1 NP0459 - Natural Gas to Technician. Contact Your (0.2 Ibs) Propane Conversion Kit(2-Stage) Distributor, Dealer, or Sales 0 S1-MP-PRTKIT-OP- MAP (2.0 lbs) Representative. Distributors Can (Multiple Access Portal) Gateway Q 1RC0470- Roof Curb- 8" High, Call 1-877-874-7378 for an ASC Kit- Replacement MAP gateway Flat, Uninsulated, Full Perimeter Quote. protective case, lanyard and (Shipped Knocked Down) (135.0 O S1-02815208000 - Blower Sheave communication cable. Use only to Ibs) for 8.5 and 10 Ton High Static replace worn or damaged • 1RC0471 - Roof Curb- 14" High, Field Installed Drive (2.8 Ibs) components. (0.3 lbs) Flat, Uninsulated, Full Perimeter 0 S1-03102529000 - Non- 0 S1-SE-COM1001-0 - Field (Shipped Knocked Down) (135.0 Networking Wall Sensor-Allows Installed Communication Card for Ibs) remote sensing and control from Simplicity SE control. Can be field O 1 RC0472- Roof Curb, Transition- single or multiple zones. (0.2 Ibs) configurable for BACnet, N2 or Sunline 7.5T thru 12.5T to O S1-03102529004 - Non- ModBUS MSTP (0.0 Ibs) Predator 3.0T thru 12.5T (Shipped Networking Wall Sensor with 0 S1-TBSU32P7S- Source 1 Assembled) (200.0 Ibs) Over-ride button -Allows remote Branded LX Series, Up to 4 Heat/ O 1 RC0476- Roof Curb-24" High, sensing and control from single or 2 Cool, Electronic 7 Day Flat, Uninsulated, Full Perimeter multiple zones. Override allows Programmable (1.2 Ibs) (Shipped Knocked Down) (135.0 setpoint to be overridden for 2 0 S1-YK-MAP1810-OP- MAP Ibs) hour time period. (0.2 lbs) (Multiple Access Portal) Gateway- o 1WC0412 -Wooden Crate (445.0 0 S1-03102529006 - Non- For use with SimplicitySE Control. Ibs) Networking Wall Sensor with (0.2 Ibs) O 2AP0402 -Air Proving Switch (1.0 Setpoint Adjustment and Over-ride 0 S1-YK-MAP1810-OS-Stationary Ibs) Button-Allows remote sensing MAP Gateway (Includes MAP • 2AQ04700524 CO2 Space/Wall and control from single or multiple Gateway, Field Bus Adapter, Mount Accessory(5.0 Ibs) zones.Allows setpoint to be Mounting Bracket and 100 to 240 O 2AQ04700624 CO2 Unit Mount adjusted ± 5° F. Override allows VAC Power Supply). US- Accessory (4.6 Ibs) setpoint to be overridden for 2 compatible counties. (1.9 Ibs) O 2DF0403 - Dirty Filter Switch (1.0 hour time period. (0.2 Ibs) Ibs) O S1-03103489000 -Temp sensor, O 2EC0401 Kit, Single Enthalpy 80mm x 80mm, LCD display, Field Installed (1.0 Ibs) screw terminals, adjustable setpoint, JCI logo (0.1 Ibs) • 2EC0402 Kit, Dual Enthalpy 0 S1-03103490000 -Temp sensor Field Installed (Includes two w/Economizer FDD, 120mm x humidity sensors) (1.0 Ibs) 80mm, LCD display, screw 0 2LA04702412- Low Ambient Kit terminals, adjustable setpoint, no (2.2 Ibs) logo (0.0 Ibs) O 2SD04700824 -Smoke Detector 0 S1-03103516000 -Temp & ' Kit w/ Mounting Hardware for humidity sensor, 120mm x 80mm, Supply Air(Horizontal/Downflow) LCD display, screw terminals, Only(9.4 Ibs) warmer/cooler dial, JCI logo (0.4 Ibs) 0 S1-03103517000 -Temp sensor, 120mm x 80mm, no display, no dial, screw terminals, no logo (0.4 Ibs) Information is subject to change without notice.Check local codes. Printed 06/20/2019 El V DI(® Predator 3-12.5 Ton Package Page:27 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAAIA1 Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120NI8R2D5EAAIA1 Consolidated Drawing NOTES: 1 OPERATING CENTER OF GRAVITY 4 POINT CORNER LOADS (LBS) (BASE UNIT) 1. FOR OUTDOOR USE ONLY. TONNAGE UNIT IWEIGHT (_LBS) LOCATION (BASE UNIT) 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. [(BASE UNNIT X Y A B C D 3. MIN. CLEARANCES TO BE: 8.5 2F ;• 1007 1458 38 965 24 610 i 235 107 175 79 255 [116] 342 [155 RIGHT SIDE: 12 305 i 10 ZF 1103 5011 38 965 24 610 257 117 1 192 87' 279 [127] 375 [170 LEFT SIDE: 36 915' 8.5 ZH 1030; [467] 38 965 24 610 240 109 179 81 261 [118] 350 [159 FRONT: 36 915 10 f ZH ....1090 [494] 38 965 24 610 1 254 115 j 189 86' 276 125 371 168_ REAR: 36 915 6.5 ZJ 1030 467]1 39 1991 25,..635 245 211 1191 87' 260 118 333 151- TOP: 72 18301 BOTTOM: 0 �@] � 7.5 27 ...1050476] 39 [991 25 635 250 113 195 89; 265 '120' 346- 154' 4. TO REMOVE THE SLOE-OUT DRAIN PAN, A REAR CLEARANCE OF 32.67 8.5 21 1060 481 38 465 24 610 247 112 184 84' 268 `122 360 163' 60 in (1525 mm) IS REQUIRED. IF SPACE IS UNAVAILABLE THE [830] T 10 23 1070 [485� 39 991 24 610 245 111 191 87 278 126' 357 162' Q 6,83 8.5 & 10 1 DRAIN PAN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING _ ZR 1200 [544] 38 965 25 5 [648] .297 135 221 C108] 291 [132] 390 [177] THE CORNER WALL. [173] 6.5 XP 1080 [490] 38 965 25 635 262 119 195 89 266 121 357 162] 5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES 24.38 l l - 7.5 XP 1090 [494] 38 •965' 23 [584 243 ID'1181 '82' 284 '129 381 '173 6. CONTACT YOUR APPLICATIOS DESIGNED TENGINEERINGGO BE ATTACHEDDEPARTMENT.ACCESSORY 8.5 XP 1137 [516] 38 '965' _25.5 648 282 128 1210 '95j 276 '125' 370 `16 ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, I7 10 XP 2135 [515] 38 `965: 25.5 648 :281 127 209;95 275 `125 1 369 '167 IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY 1 CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 32.06 -- -18 00 -- 7.84 7. SIDE DUCT FLANGES ARE 0.75" HIGH. [814] 1 [457] lj 1 [199] BOTTOM DUCTS DO NOT HAVE FLANGES. ; 6.83 8, MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES THE LOWEST NEGATIVE STATIC. , A [173] 9. NSIONS IN IN ETERS OR . A 1 ECONOMIZER DISCONIECTASD FRESHCONVENIENCE5OIXd�S R B 1067] [4.45 10. OPTIONAL COIL GUARDS, POWER EXHAUST GAS HEAT E y ALTERNATE CONDENSATION DRAIN [265] [464] ECONOMIZER, N. DISCONNECT SWITCH CONVENIENCE OUTLET, 24.24 S T [616] ,EXCEPT XP (HEAT PUMP) UNITS. (FROM MTB. P y ' U -�► DIRECTION OF AIRFLOW FLANGE) • U 27.50 p 24.00 � �J E ,gyp R [699] L [610] 1\ � r CENTER OF GRAVITYN Y 5 ' a��. 1 RIGHT 18.35 28.25 LEFT f � 464 c . R [718] 3/4" FPT.._.., l .... ��..:__ ....-.. :)--, .1 _ �+ 21.00� '� � 1 [ ) -lik..... N 't.._..._aE , NI 2589 19 14 d 533 �/ a1 \ [ ] [486] [435) \III � 3 ��} SUPPLY t 18.86 [518] �'14 17.1a Y [ 1 t 5.32 I 14.47 �) �x FRONT BOTTOM GAS 5.16 • • ,.....2.88 [135] ] r3681 16.39 • BOTTOM ENTRY: SUPPLY ENTRY 02.00 [51] 131 -- 28.25 31.63 [73] ._.__ _ r j [459] - 18.89 POWER 2.50 [64) [718] [603] DETAIL A [480] CONTROL 3X 00.875 [22] REAR (PARTIAL VIEW) OUTSIDE AIR X i TOP VIEW (INTAKE HOOD NOT SHOWN IN THIS VIEW) INTAKE HOOD DISCONNECT SWITCH COVER----- (OPTIONAL) (OPTIONAL) `, 2261 •I [1475] ._ ,'_... . ._ .. 1& POWER ENTRY 02.S0 [64]... • �.,._ _ - GAS INLET -- 25.72 __. _ j! [fiS3] FRESH AIR Up0♦ ) - \\. FILTER! BLOWER ACCESS C • ECONOMI2ER((OF ONAL r........ 3.::� TL PANEL,' \ OMPRESSOR i CONTROL ENTRY 00.87S [ 22] • OMPRES50R •�_ y „f_ 50•75 ACCESS _ [ ] • ACCESS �^ <` POWER ENTRY 02.50 [64] - _ __ ..T • h BAROMETRIC RELIEF H000/ ~� 11: ' `' __=___ „i POWER EXHAUST(OPTIONAL) '.,, -� _ ..._ 1_ 1 1LyY.. _Iis / �G_._.. ...__ ]r'u __ K?L!... _ _,my CONVENIENCE OUTLET COVER [694] SEE DETAIL A FOR 22.19 [289] L59.00 `„ :. uL� I (OPTIONAL) - 27 31 i_ 538 CONVENIENCE OUTLET-- / DRAIN LOCATION EXHAUST 4 LEFT VIEW POWER ENTRY 00.875 [221 - 89.00[2261] FLUE [1494] COIL GUARD FRONT VIEW RIGHT VIEW (OPTIONAL) (OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW) Information is subject to change without notice.Check local codes. Printed 06/20/2019 ,9 yoRK® Predator 3-12.5 Ton Package Page:28 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Component Locations Cooling With Gas Heat(6.5 Through 10 Tons) Smart EquipmentT'control board Filter drier Disconnect location Filter access w/screw connector for T-stat (solid core) wiring and network connections (optional disconnect switch) (2 or�}"filter options) Terminal block for Micro-Channel Aluminum hi-voltage connection Tube/Aluminum Fin ,� 4v Condenser Second model ` " nameplate inside hinged Slide-out motor and access panel ( --'� r\_ ; blower assembly for ,, ,r easy adjustment Dual stage and service cooling for Bett-drive � � ' � blower motor maximum comfort ,... a t lit it'ii _ VFD location(optional) „" Power ventor motor Compressor#2 °k . access(high- •• q efficiency 7, steel20-g t ge aluminized 1,C_ steel tubular heat compressor) �t Lit-.'-trt" •0 exchanger for long life �g t.. (stainless steel option) i �, � Two-stage gas Base rails w/forklift heating to maintain slots(three sides) warm,comfortable and liftingholes �. Slide-out drain pan # with 1"NPT, temperature Roof curbs in eight-and female connection Intelligent control fourteen-inch heights.Roof /� board for safe and curbs for transitioning from Com ressor#1 access efficient operation York SunlineC footprint to Side entry power p Toolless and control wirin (high-efficiency compressor) the ZH/ZJ/ZR/ZU/ZWiZK door latch g knockouts Series footprints are also available(field installed accessory) • Information is subject to change without notice.Check local codes. Printed 06/20/2019 ri yo R Kg Predator 3-12.5 Ton Package Page:29 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Low Leak Downflow Economizer Low Leak Downflow Economizer (shown with optional Power Exhaust) �`" •- j - 1 l I —i,i _ a Fresh Air Hood .` I i it i `' (included) ` 1 l .I j? � i�r f 1 / I it -- . ` ' J .. l ,. Low Leak Economizer(included) / � �F~! Power Exhaust(optional)/„/ Barometric/.,, Relief Damper Barometric Relief (included) Hood (included) Low leak economizers are capable achieving low leakage rates of 3 cfmisq. ft at 1"of static pressure, meeting or exceeding the following standards: ASHRAE 90.1-2010 ASHRAE 62 - AMCA 511 (licensed as Class 1 A damper) International Energy Conservation Code (IECC) California Title 24 The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Information is subject to change without notice.Check local codes. Printed 06/20/2019 ,.. yoRK® Predator 3- .5 ge Page:30 ., York Single Package 12 R 410ATon Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Factory Installed Power Exhaust SP-in.-wg. 0 P 0 0 0 0 0 0 0 0 O ..... N W -A U1 'al V CO UO O O O O O O 0 O O 0 U1 - O . . O N 0 . O O N U9 0 0 0 W r W (D Fy el O 3 Z in o o c K U1 - w al Q IA Ui 0 0 Ot -A O O O • co I -o Ut . . . . . . . . . . , . , , . . , . , O O O O O 0 O W in iD O O O O BHP Information is subject to change without notice.Check local codes. Printed 06/20/2019 Predator 3-12.5 Ton Package Page:31 York Single Package R-410A Air Conditioner Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Seismic Certification SPECIAL SEISMIC CERTIFICATION .3 OF NON-STRUCTURAL JohnsonControls COMPONENTS AND SYSTEMS CERTIFICATE OF COMPLIANCE Dynamic Certification Laboratories has qualified the listed packaged rooftop units as CERTIFIED for seismic applications in accordance with the following codes and standards: CBC 2013, IBC 2012, ICC-ES AC-156 2012, ASCE 7-10 The following model designations are included in this certification. A complete list of certified models,options, and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories, provided by the equipment manufacturer upon request. Unitary Product Group Packaged Rooftop Units (UPG) Seismic Qualification Testing was conducted in accordance with and in strict adherence to the standards set forth within the American Society of Civil Engineers(ASCE 7)by the independent approval agency,Dynamic Certification Laboratories. The above referenced equipment is APPROVED for seismic applications when properly installed and used as intended. The basis of this certification is through testing of the active and energized components per AC156. This certification covers multiple UPG brands,including York,Johnson Controls,Coleman,Luxaire,Evcon,Fraser- Johnston and Ready Ship. The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response Acceleration,Sds,as determined by the ASCE 7 seismic maps. Various installation locations/isolation configurations are covered under this certification,limited by the Sds value stated in the following table. A seismic importance factor,ip,of 1.5 applies to this certification to include essential facility requirements and life safety applications for post event functionality. The units are approved for both a rigid and flexible mount configuration. Maximum Design Sds Values of UPG Packaged Rooftop Units Series Model Tons Sds(g) Fp/Wp ZR/21/2/4/21</ZW/ZU/ZT/3A3* 037 3 2.5 1.88 ZR/211/21-1/2K/ZVV/ZU/DIJA4* 049 4 2.5 1.88 ZR/Z.J/2/4/ZIC./ZW/211/2713A5* 061 5 2.5 1.88 ZR/ZJ/21-1/2F/XP/Z.K/ZW/ZU/25/XA/J06* 078 6.5 2.5 1.88 ZR/11/211/2F/XP/ZKialsilZU/ZS/XA/J07*/T* 090 7.5 2.5 1.88 ZR/Z.J/ZHIZF/XP/ZIC/ZW/ZLI/ZS/XA/308* 102 &5 2.5 1.88 ZR/21/2F1/2F/XPIZK/ZW/ZU/ZS/XA/J10*/T* 120 10 2.5 1.88 ZR/D/Zhi/ZF/XP/ZIOZVVIZI.J/ZSRA/J12*.tr* 150 12.5 2.0 1.50 Page 1 of 2 Dynamic Certification Laboratories 1315 Greg Street,Suite 109,Sparks,NV 69431—Orr ii6-358-909S urkrw.straketest.corn Information is subject to change without notice.Check local codes. Printed 06/20/2019 f ••y YORK® Predator 3-12.5 Ton Package York Single Package R-410A Air Conditioner Page:32 Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1 • Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 Seismic Certification SPECIAL SEISMIC CERTIFICATION ij 0-ri DCL,,..„,,,,,_,,,,,-,„ OF NON-STRUCTURAL Johnson ,, Controls COMPONENTS AND SYSTEMS CERTIFICATE OF COMPLIANCE Table of Seismic Design Parameters Site Class F, I„ a, Rit z/h D LO 1,5 2.5 6.0 1.0 Site and Project Requirements it is the responsibility of the Design Professional of Record to: • Provide engineering for the anchorage and restraint of the unit • Validate Certification Design Parameters with actual site conditions • Provide engineering of all equipment support structures • Confirm component configuration Certification Issued by: Dynamic Certification Laboratories Document Control Number: 90300-1107-A(rev.1) Original Issue Date: 9/2/11 Revi. Issue Date: 3/26/14 ..--- , „--- ,.? S5220 -- 1r75 7- „_-- ,,,,, - ‘,,,,t`ii,, XP 3 id, akon Carter , \ it Cornrnerk kd Protioti MarraVer lokr mon Camtrois,locoman-1W • Dr.Ahmed ttani,SE Dynamic Certification Laboratories Page 2 of 2 Dynamic Cert,ftabon Labrrator es 1315 Geg Sreet,Su.re W9,Sparks, IV 9'3431' 133 775-358-5,085 www.shatetest.corn Information is subject to change without notice Check local codes Printed 06/20/2019 .94 yo R Kg Predator 3-12.5 Ton Package Page:33 York Single Package R-410A Air Conditioner Project Name. Planet Fitness Tigard,OR Unit Model#. ZJ120N18R2D5EAA1A1 - Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1 1RC0471 Roof Curb f_,%� RIGHT 80-5,8 ��'� + INSULATED DECK UNDER •r CONDENSER SECTION +1� ‹ l 'Al__ � '�SUPPLY �'IsF 20 6 +. DUCT SIZES: 'NI Return 19.5 x 29.5 4, RETURN *• Supply 19.5 x 29.5 2 TYP' ROOF OPENING: -,`„., 46 Long 30 Wide 30 4 50-1/2 �► INSULATED DECK UNDER �� COMPRESSOR SECTION FRONT 14" • *Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications. For location of horizontal duct applications(On rear of unit),refer to Unit Dimensions details. 1RC0471 Roof Curb Dimensions Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:34 Date 06/20/2019 Project Name Planet Fitness Tigard,OR Project Number Client/Purchaser Guide Specification Summary Page Product Series Models and Unit Tags Predator 3-12.5 Ton Package ZJ150N18R2D5EAA1A1 RTU-1 ZJO78N12R2D5EAA1A2 RTU-2 ZJ120N18R2D5EAA1A1 RTU 3,4,5,E 7 8 Information is subject to change without notice.Check local codes. Printed 06/20/2019 ® Guide Specification for Page:35 �Iy0 R' York Predator GENERAL removing panels or creating bypass of the coils. Condensate pan shall be slide out design, constructed of York Predator units are convertible single packages with a non corrosive material, internally sloped and a common footprint cabinet and common roof curb for all conforming to ASHRAE 62-B9 standards. Condensate 6-1/2 through 12-1/2 ton models.All have two connection shall be a minimum of 3/" I.D. female and be compressors with independent R-410A refrigeration rigid mount connection. circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be INDOOR (EVAPORATOR) FAN ASSEMBLY easily installed on a roof curb, slab, or frame. All units are self contained and assembled on rigid full perimeter Fan shall be a belt drive assembly and include an base rails allowing for 3-way forklift access and adjustable pitch motor pulley. Job site selected brake overhead rigging. Every unit is completely charged with horsepower shall not exceed the motors nameplate R-410A,wired, piped, and tested at the factory to horsepower rating plus the service factor. Units shall be provide a quick and easy field installation.All units are designed to operate within the service factor. Fan wheel convertible between side and down airflow. Independent shall be double inlet type with forward curve blades, economizer designs are used on side and down dynamically balanced to operate smoothly throughout discharge applications, as well as all tonnage sizes. the entire range of operation. Airflow design shall be Predator® units are available in the following constant volume. Bearings shall be sealed and configurations: cooling only, cooling with electric heat, permanently lubricated for longer life and no cooling with gas heat, reheat only, reheat with electric maintenance. Entire blower assembly and motor shall be heat and reheat with gas heat. Electric heaters are slide out design. available as factory-installed options or field-installed accessories. OUTDOOR(CONDENSER) FAN ASSEMBLY DESCRIPTION The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to Units shall be factory assembled, single package, corrosion resistant steel spider brackets and shall be (Elec/Elec, Gas/Elec), designed for outdoor installation. dynamically balanced for smooth operation. The outdoor They shall have built in field convertible duct connections fan motors shall have permanently lubricated bearings for down discharge supply/return or horizontal discharge internally protected against overload conditions and supply/return and be available with factory installed staged independently. A cleaning window shall be options or field installed accessories. The units shall be provided on two sides of the units for coil cleaning. factory wired, piped and charged with R-410A refrigerant and factory tested prior to shipment.All unit wiring shall REFRIGERANT COMPONENTS be both numbered and color coded. The cooling Compressors: performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be CSA certified to a. Shall be fully hermetic type, direct drive, internally ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 protected with internal high-pressure relief and over standards. temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of+ or UNIT CABINET — 10%of the unit nameplate voltage. Unit cabinet shall be constructed of galvanized steel with b. Shall have internal spring isolation and sound exterior surfaces coated with a non-chalking, powder muffling to minimize vibration and noise, and be paint finish, certified at a 750-hour salt spray test per externally isolated on a dedicated, independent ASTM-B117 standards. Indoor blower sections shall be mounting. insulated with up to 1"thick insulation coated on the airside. Either aluminum foil faced or elastometric rubber Coils: insulation shall be used in the unit's compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2"filters shall be furnished as standard and be accessible through hinged access door. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without Information is subject to change without notice.Check local codes. Printed 06/20/2019 w 4K® Guide Specification for Page:36 yroRKYork Predator a. Evaporator coils shall have aluminum plate fins Heat exchanger and exhaust system shall be mechanically bonded to seamless internally enhanced constructed of aluminized steel, and be designed with copper tubes with all joints brazed. Special Phenolic induced draft combustion with post purge logic, energy coating shall be available as a factory option. saving direct spark ignition, and redundant main gas b. Evaporator coils shall be of the direct expansion, draw- valve. The heat exchanger shall be of the tubular type, thru design. constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering c. Condenser coils shall have aluminum plate fins temperature of 40 °F. Burners shall be of the in-shot mechanically bonded to seamless internally enhanced type, constructed of aluminum-coated steel. All gas copper tubes with all joints brazed or Micro-Channel piping shall enter the unit cabinet at a single location, aluminum tube, aluminum fins. through either the side or bottom, without any field d. Condenser coils shall be of the draw-thru design. modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner Refrigerant Circuit and Refrigerant Safety Components ignition. Heating section shall be provided with the shall include: following minimum protection: a. Independent fixed-orifice or thermally operated a. Primary and auxiliary high-temperature limit switches. expansion devices. b. Induced draft pressure sensor. b. Solid core filter drier/strainer to eliminate any moisture c. Flame roll out switch (manual reset). or foreign matter. d. Flame proving controls. • c. Accessible service gage connections on both suction e. All two stage gas units shall have two independent and discharge lines to charge, evacuate, and measure stages of capacity(70% or 75% 1st stage, 100% 2nd refrigerant pressure during any necessary servicing or stage) 3 through 5 ton and (60% 1st stage, 100%2nd troubleshooting,without losing charge. stage)6-1/2 through 12-1/2 ton. d. The unit shall have two independent refrigerant circuits, equally split in 50% capacity increments. UNIT OPERATING CHARACTERISTICS Unit Controls: Unit shall be capable of starting and running at 125 °F outdoor temperature, exceeding maximum load criteria a. Unit shall be complete with self-contained low-voltage of AHRI Standard 340/360. The compressor,with control circuit protected by a resettable circuit breaker standard controls, shall be capable of operation down to on the 24-volt transformer side. 0 °F outdoor temperature. Unit shall be provided with fan b. Unit shall incorporate a lockout circuit which provides time delay to prevent cold air delivery before heat reset capability at the space thermostat or base unit exchanger warms up. (Gas heat only) should any of the following standard safety devices trip and shut off compressor: ELECTRICAL REQUIREMENTS -All unit power wiring • Loss-of-charge/Low-pressure switch. shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to • High-pressure switch. minimize roof penetrations and avoid unit field • Freeze condition sensor on evaporator coil. If any modifications. Separate side and bottom openings shall of these safety devices trip,the LCD screen will be provided for the control wiring. display the alarm message. STANDARD LIMITED WARRANTIES -Compressor—5 c. Unit shall incorporate "AUTO RESET"compressor Years, Heat Exchanger— 10 Years, Elect. Heat Elem.—5 over temperature, over current protection. Years, Parts— 1 Year. d. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy FACTORY INSTALLED OPTIONAL OUTDOOR AIR hook-up. (Shall be made available by either/or): e. Unit control board shall have on-board diagnostics and fault message display. ADDITIONAL FACTORY INSTALLED OPTIONS f. Standard controls shall include anti-short cycle and low • Alternate Indoor Blower Motor—For applications voltage protection, and permit cooling operation down with high restrictions, units are available with optional to a selectable value as low as 0 °F. indoor blower motors that provide higher static output g. Control board shall monitor each refrigerant safety and/or higher airflow. switch independently. GAS HEATING SECTION Information is subject to change without notice.Check local codes. Printed 06/20/2019 IGuide Specification for York Predator Page:37 • IntelliSpeedTM Supply Fan Control Option (ASHRAE 90.1 compliant,section 6.4.3.10) — Units configured with the IntelliSpeedTM Supply Fan Option will contain a VFD for variable volume supply fan operation. This option allows the supply fan RPM to vary based on the number of compressors or heating stages energized. The economizer's minimum position will also be configurable to vary based on the supply fan VFD frequency output. • Non-Powered Convenience Outlet—Unit is provided with a non-powered 120VAC GFCI outlet with cover on the corner of the unit housing the compressors. • BAS Controls—Include supply air sensor, return air sensor, dirty filter indicator and air proving switch. • Smoke Detector—A smoke detector can be factory mounted and wired in the supply and/or return air compartments. FIELD INSTALLED OPTIONS • Roof Curb— 14"high, full perimeter knockdown curb, with hinged design for quick assembly. Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:38 Date • 06/20/2019 Project Name Planet Fitness Tigard,OR Project Number Client/ Purchaser Control Summary Page Control Models and Unit Tags Standard Simplicity Control ZJ150N18R2D5EAA1A1 RTU-1 ZJO78N12R2D5EAA1A2 RTU-2 ZJ120N18R2D5EAA1A1 RTU-3,4,5,6,7,8 Information is subject to change without notice.Check local codes. Printed 06/20/2019 SSE Guide Spec Page:39 yo R K® 23 09 23 Direct-digital Control system for HVAC 23 09 23. 13 Decentralized,Rooftop Units: 23 09 23. 13.A. Unit Control Board 1. ASHRAE 62-2001compliant. BTL certified. 2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal. 3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non- condensing).with a storage temperature range from-40F to 194F;5-95%RH(non-condensing). 4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs. 5. Controller shall accept the followinginputs:space temperature,return air temperature sensor,setpointadjustment,outdoor air temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors, FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality, System purge. 6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and be Demand Control Ventilation(DCV)ready. 7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/ exhaust/reversing valve/dehumidify/occupied. 8. Unit shall provide surge protection for the controller through a circuit breaker. 9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster. 10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation. 11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor. If any of these safety devices trip.the LCD screen will display alarm message indicating the specific safety device that caused the lockout. a. Loss of charge/Low-pressure switch. b. High-pressure switch. c. Freeze condition sensor on evaporator coil. 12. Unit control board must support each usage case: a. Conventional thermostat with low voltage input terminals for easy installation b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control board to compare with associated setpoints c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building automation/management system 13. Anti-short cycle and low voltage protection features included. 14. Internal occupied/unoccupied scheduling 15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F. 16. Shall allow for start-up, commissioning,troubleshooting, parameter adjustment,setpoint adjustment via onboard display and navigable menu with no additional interface tool or controls technician required. 17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test. 18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up,commissioning, troubleshooting, parameter adjustment, setpoint adjustment. 19. Local embedded trending and scheduling.Trending data and occupancy scheduling predefined from the factory. Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device (cellular phone, laptop,tablet) 20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable.These include but are not limited to: a. Demand Ventilation Mode—enable or disable b. Operational Setpoint—display current value c. Supply Air Temperature(SAT)—display current value d. Return Air Temperature(RAT)—display current value Information is subject to change without notice.Check local codes. Printed 06/20/2019 .# PO R K SSE Guide Spec Page:40 e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network Sensor, or FC Bus communicated value f. Return Air Humidity(RAH)—display current value g. Operational outdoor Air Temperature(OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer board and OprOAT only if economizer is present h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards OAH 0-10VDC input or FC Bus communicated value i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer boards OAQ 0-10VDC input or FC Bus communicated value j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board IAQ 0-10VDC input, SA Bus Network Sensor, or FC Bus communicated value 21. A menu shall display and allow modification to the following operations and settings: a. HVAC Zone Fan b. Cooling c. Heating d. Economizer e. Demand Ventilation f. Power Exhaust g. Sensors h. Network 22. A menu shall display and allow modification to the following operations and settings: a. HVAC Zone—Occupied status b. Indoor Fan status c. Cooling status d. Heating status e. Economizer indication whether free-cooling is available or not f. Enabling or disabling of Demand Ventilation g. Power Exhaust 1) Enable/disable hot-gas reheat if available 2) Warmup/Cooldown 3) Title 24 Load Shed 4) Defrost 23. A menu shall display and allow modification to the following operations and settings: a. Firmware version (of UCB, Economizer, other peripheral boards) b. Setting time zone c. Network information 1) Device name that will appear on the FC Bus 2) Selection of communication protocol 3) Operational Baud Rate 4) Device ID 24. A menu shall display and allow modification to the following operations and settings: a. Version of firmware b. Ability to Load new firmware c. Create a backup file of the firmware and parameter setting via USB port d. Restore factory default parameter values and setup e. Full and Partial Cloning of parameter setpoints from or to other units f. Data trend exporting 25. A menu shall display and allow modification to the following operations and settings: Information is subject to change without notice.Check local codes. Printed 06/20/2019 YORK SSE Guide Spec Page:41 a. Unit serial number, model number and name b. Ability to reset Lockouts c. Controller name d. Displays the current values of all setpoints in use e. Displays all current values for the indoor and outdoor zones f. Displays current values related to: 1) Indoor Fan 2) Cooling 3) Heating 4) Heat Pump operation 5) Economizer operation 6) Power Exhaust 7) Demand Ventilation 8) Air monitoring station 9) Hot Gas Reheat 10) Smoke Control g. Current information for inputs; including 1) Sensors 2) Coil Sensors 3) Thermostat 4) Binary Inputs 5) Unit Protection 6) Network Inputs 7) All outputs(relay and binary) h. Self-Test 1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning characteristics of the system at time of startup and commissioning. 23 09 23. 13.B. Auxiliary Control Boards 1. ASHRAE 62-2001 compliant. BTL certified. 2. Economizer controller CEC Title 24 Compliant a. Display alarms if the following occur 1) Economizer is economizing when conditions do not support 2) Economizer is not economizing when conditions do support 3) Damper Stuck 4) Excess Outdoor Air 5) Failed Sensor 3. Refrigeration Fault Detection & Diagnostics a. There is insufficient refrigerant in any circuit b. There is excessive refrigerant in any circuit c. There is excessive refrigerant flow d. There is insufficient refrigerant flow(restriction) e. Inefficient compressor f. Insufficient High-side heat transfer g. Excessive High-side heat transfer(low ambient control problem, low OP) h. Insufficient Low-side heat transfer i. Excessive Low-side heat transfer Information is subject to change without notice.Check local codes. Printed 06/20/2019 PORKSSE Guide Spec Page:42 j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if refrigerant level is very low in the system) k. Sensor fault-Sensor data is not available I. The unit is off m. The ambient temperature is too low n. The ambient temperature is too high o. The return air wet-bulb temperature is too low p. The return air wet-bulb temperature is too high q. Sensor fault-The condensing temperature is lower than the ambient temperature (Could also be triggered when the condenser is wet) r. The suction line temperature is less than the evaporator temperature s. The evaporator temperature is greater than the ambient temperature t. The liquid temperature is lower than the ambient temperature u. Sensor fault-Suction temperature or ambient temperature is invalid v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid w. Sensor fault-The liquid pressure or suction pressure is invalid x. Sensor fault-The suction line temperature is invalid y. The return air dry-bulb temperature is too low z. The return air dry-bulb temperature is too high aa. The Efficiency Index is below 75%of ideal bb. The Capacity Index is below 75%of ideal 23 09 23. 13.0 Remote Accessibility: 1. ASHRAE 62-2001 compliant. BTL certified. 2. Provide the ability to adjust parameter values, setpoints, limits remotely 3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS) 4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page.43 START-UP & SERVICE DATA INSTRUCTION COMMERCIAL PACKAGE UNITS 3.0 To 40.0 TONS START-UP CHECKLIST Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician: Signature: HVAC Contractor: Phone: Address: Contractor's E-mail Address: Electrical Contractor: Phone: Distributor Name: Phone: WARRANTY STATEMENT This start-up sheet covers all startup check points common to all package equipment.In addition it covers essential startup check Johnson Controls/UPG is confident that this equipment will points for a number of common installation options. Depending operate to the owner's satisfaction if the proper procedures are upon the particular unit being started not all sections of this startup followed and checks are made at initial start-up.This confidence is sheet will apply.Complete those sections applicable and use the supported by the 30 day dealer protection coverage portion of our notes section to record any additional information pertinent to your standard warranty policy which states that Johnson Controls/UPG particular installation. will cover parts and labor on new equipment start-up failures that Warranty claims are to be made through the distributor from whom are caused by a defect in factory workmanship or material,for a the equipment was purchased. period of 30 days from installation.Refer to current standard warranty policy and warranty manual found on UPGnet for details. EQUIPMENT STARTUP In the event that communication with Johnson Controls/UPG is required regarding technical and/or warranty concerns,all parties Use the local LCD or Mobile Access Portal(MAP)Gateway to to the discussion should have a copy of the equipment start-up complete the start-up. sheet for reference.A copy of the original start-up sheet should be A copy of the completed start-up sheet should be kept on file filed with the Technical Services Department. by the distributor providing the equipment and a copy sent to: The packaged unit is available in constant or variable air volume Johnson Controls/UPG versions with a large variety of custom options and accessories Technical Services Department available.Therefore,some variation in the startup procedure will 5005 York Drive exist depending upon the products capacity,control system, Norman,OK 73069 options and accessories installed. Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:44 SAFETY WARNINGS • The inspections and recording of data outlined in this procedure AWARNING'' are required for start-up of Johnson Controls/UPG's packaged Lethal voltages are present during some start-up products.Industry recognized safety standards and practices must be observed at all times.General industry knowledge and checks. Extreme caution must be used at all times. experience are required to assure technician safety. It is the responsibility of the technician to assess all potential dangers and take all steps warranted to perform the work in a safe manner. By addressing those potential dangers, prior to AWARNING beginning any work,the technician can perform the work in a safe manner with minimal risk of injury. Moving parts may be exposed during some startup checks.Extreme caution must be used at all times. NOTE: Read and review this entire document before beginning any of the startup procedures. DESIGN APPLICATION INFORMATION This information will be available from the specifying engineer full open position and the frequency drive is operating at 60 HZ. who selected the equipment. If the system is a VAV system the Do not proceed with the equipment start-up without the CFM will be the airflow when the remote VAV boxes are in the design CFM information. Design Supply Air CFM: Design Return Air CFM: Design Outdoor Air CFM At Minimum Position: Total External Static Pressure: Supply Static Pressure: Return Static Pressure: Design Building Static Pressure: Outside Air Dilution:Economizer Position Percentage: _C,FM: Supply Gas Pressure After Regulator W/o Heat Active Inches _ ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER: Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:45 REFERENCE General Inspection Completed See Notes Unit inspected for shipping,storage,or rigging damage 0 0 Unit installed with proper clearances 0 0 Unit installed within slope limitations 0 ❑ Refrigeration system checked for gross leaks(presence of oil) 0 0 Terminal screws and wiring connections checked for tightness 0 0 Filters installed correctly and clean 0 0 Economizer hoods installed in operating position 0 0 Condensate drain trapped properly,refer to Installation Manual 0 0 Economizer damper linkage tight 0 0 Gas Heat vent hood installed ❑ 0 All field wiring(power and control)complete 0 0 Air Moving Inspection Completed See Notes Alignment of drive components ❑ ❑ Belt tension adjusted properly 0 0 Blower pulleys tight on shaft,bearing set screws tight,wheel tight to shaft 0 ❑ Pressure switch or transducer tubing installed properly 0 0 Exhaust Inspection Powered❑ Barometric Relief 0 Completed See Notes Check hub for tightness 0 0 Check fan blade for clearance ❑ ❑ Check for proper rotation ❑ 0 Check for proper mounting(screen faces towards unit) 0 0 Prove operation by increasing minimum setting on economizer 0 0 Economizer Inspection Standard 0 BAS 0 Com pleted See Notes CO2 sensor installed Yes 0 No 0 0 0 Check economizer setting(Reference SSE Control Board LCD menu location) 0 0 Prove economizer open/close through SSE Board Setting 0 0 Reheat Mode Normal O or Alternate❑ Not Applicable 0 Humidity Sensor(2SH0401) Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:46 � G Operating Measurements -Air Flow Fan operates with proper rotation ID Fans❑ Exh. Fans Cond. Fans 0 Pressure drop across dry evaporator coil(At maximum design CFM)1 jVVC External Static Pressure l%C Return Static Pressure IVVC Supply Static Pressure IVVC Supply Air CFM Using Dry Coil Chart CFM Final Adjusted Supply Air CFM2 CFM 1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential. 2, Was a motor pulley adjustment or change required to obtain the correct airflow? Was it necessary to increase of decrease the airflow to meet the design conditions? If the motor pulley size was changed,measure the outside diameters of the motor and blower pulleys and record those diameters here: Blower Motor HP FLA RPM Pulley Pitch Diameter Turns Out Final Turns Out Blower Pulley Pitch Diameter Fixed Sheave ELECTRICAL DATA T1 -T2 Volts T2-T3 Volts Control Voltage Volts T1 -T3 Volts Device Nameplate Measured List All Three Amperages Supply Fan Motors'2 AMPS AMPS Exhaust Motor(Dampers 100%) AMPS AMPS Condenser Fan#1 AMPS AMPS Condenser Fan#2(if equipped) AMPS AMPS Condenser Fan#3(if equipped) AMPS AMPS Condenser Fan#4(if equipped) AMPS AMPS Compressor#1 AMPS AMPS Compressor#2(if equipped) AMPS AMPS Compressor#3(if equipped) AMPS AMPS Compressor#4(if equipped) AMPS AMPS 1. VAV units with heat section-simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position. 2. VAV units without heat section-VAV boxes must be set to maximum design airflow position. information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:47 +. OPERATING MEASUREMENTS COOLING Stage Discharge Discharge Liquid Line Subcooling2 Suction Suction Superheat Pressure Temp. Temp. Pressure Temp. p First # ° 0 0 # 0 ° Second(if equipped) # 0 ° ° # 0 ° Third(if equipped) # 0 ° 0 # 0 ° Fourth(if equipped) # ° ° # ° ° Reheat 1st Stage # 0 0 # ° 0 1. Liquid temperature should be before filter/drier. 2. Subtract 10 psi from discharge pressure for estimated liquid line pressure Outside air temperature °F db °F wb %RH Return Air Temperature °F db °F wb %RH Mixed Air Temperature °F db °F wb %RH Supply Air Temperature °F db °F wb %RH REFRIGERANT SAFETIES Action Completed See Notes Prove Compressor Rotation(3 phase only)by gauge pressure 0 0 Prove High Pressure Safety,All Systems 0 0 Prove Low Pressure Safety,All Systems ❑ ❑ OPERATING MEASUREMENTS -GAS HEATING Fuel Type: 0 Natural Gas ❑ LP Gas Action Completed See Notes Check for gas leaks 0 0 Prove Ventor Motor Operation ❑ 0 Prove Primary Safety Operation 0 0 Prove Auxiliary Safety Operation 0 0 Prove Rollout Switch Operation 0 0 Prove Smoke Detector Operation ❑ 0 Stage 1 IWC 0 Manifold Pressure Stage 2(If Equipped) .IWC, 0 Stage 3(If Equipped) IWC 0 Supply gas pressure at full fire IWC 0 Check temperature risel 0 measured at full fire °F 0 1 Input X Eff.(BTU output) 1.08 X Temp.Rise • Information is subject to change without notice.Check local codes. Printed 06/20/2019 Page:48 s F OPERATIONAL MEASUREMENTS -STAGING CONTROLS Verify Proper Operation of Heating/Cooling Staging Controls Create a cooling demand at the Thermostat; BAS System or Simplicity SE Verify that cooling/economizer stages are energized. ❑ Create a heating demand at the Thermostat; BAS System or Simplicity SE Verify that heating stages are energized. ❑ Verify Proper Operation of the Variable Frequency Drive(If Required) Verify that motor speed modulates with duct pressure change. ❑ FINAL -INSPECTION Verify that all operational control set points have been set to desired value ❑ Scroll through all setpoints and change as may be necessary to suit the occupant requirements. Verify that all option parameters are correct Scroll through all option parameters and ensure that all installed options are enabled in the software and all ❑ others are disabled in the software. (Factory software settings should match the installed options) Verify that all access panels have been closed and secured ❑ OBSERVED PRODUCT DIFFICIENCIES & CONCERNS: Information is subject to change without notice.Check local codes. Printed 06/20/2019