Specifications ..FCE.\\I'Er la/so siv gzNn A✓6. FEB 4 2020 �CiTY Ic, ' rct AMERICAN HEATING VAV BOX ATTACHMENT TO CONCRETE OVER METAL DECK STRUCTURAL CALCULATIONS • • - MECHANICAL ATTACHMENT: MA 1-MA 13 SKETCHES: VAV IA-VAV1B , "-G Y,r ,.1 fJ rZI ,� All +`� ,�., (16 PAGES TOTAL INCLUDING COVER SHEET) , . .a-•"- 1 lief .uY,I. - 4s nYi--� rev.k' s` "�-�` ** LOWER UNITS ONLY Matt- k 4 .� L. August 15, 2019 PROJECT NUMBER: 190237.01 ExP .r : , .aj._ 41 CI _ ARCHITEC1ORE ENGINEERING PLANNING INTERIORS LANDSCAPE 15895 SW 72ND AVE SUITE 200 PORTLAND,OR 97224 PHONE:503.226.1285 FAX: 503.226.1670 INFO@C[DAINC.COM W W W.C[DA[NC.COM 444 ( CIDA Standard Mechanical unit Attachment RNH TEL: (503)226-1285 VAV Box 8/15/2019 FAX: (503)226 1670 MECHANICAL UNIT ATTACHMENT-LATERAL FORCES VAV Box Hung below floor framing Wp:= 1501b Weight of unit L:= 24in Length wm:= 18in Width of unit • hm := 18•in Height of unit SEISMIC PARTS AND PORTIONS (Portland, OR 97229) Mapped Ss:= 1.073 site class=D Adjusted Maximum Fa 1.07 Sms:= Fa'Ss Sins = 1.15 Design 2 SOS 3'Sms SDS =0.765 USE Sps:= 0.85 CONSERVATIVE FOR PORTLAND Mt IRO AND VANCOUVER WAAREAS h:= 10 z:= h•0.75 Assumes maximum 4-story building with box under 4th floor Ip:= 1.0 Values for air side HVAC per table 13.6-1 ASCE 7-10 ap:= 2.5 RP:= 6 0.4•ap•SDS'Ip / z Fp:= 1 + 2•-z •Wp Fp = 53.121b 0.7•Fp=37.191b Total seismic RP \ hl Fpmin 0.3 Sps•Ip Wp Fpmin =38.25 lb 0.7•Fpmin =26.77 lb Total seismic 0.2•Sps•Wp=25.5 lb E:\adcadd119100000-2019 Mechanical Units\0237.01 American Heating Standards 2019\Structural\VAV BOX \CONCRETE OVER METAL DECK A 2 CIDA Standard Mechanical unit Attachment RNH TEL: (503)226-1285 VAV Box 8/15/2019 FAX: (503)226 1670 VERTICALATTACHLENT OF VAV BOX TO UNDERSIDE OF CONCRETE DECK(PT or CIP) W corner= 4p "comer = 37.5 lb Vertical load to corner support from dead bad hm Mot:= Fp• 2 Mot Pseis= wm 2 Pseis= 13.28 lb Vertical load to corner support from seismic overturning ASD loads for attachment to unit 1.0D+0.7E, 0.6D-0.7E 0.2Sps•Wp PI Pcorner + 0.7 + Pseis PI = 51.26 lb Maximum vertical load 4 (0.2.SDs•Wp 1 P2:= 0.6•Pcorner —0.7. + Pseis I P2 = 8.74 lb Minimum vertical load>0 no compression in \ 4 111 vertical support Try(1)#10 SMS at box(20oa minimum 22ga hanging strap) P <1.0 OK Use hanging Va11ow:= 1041b U:_ U = 0.49 (1)#10 SMS at unit for vertical han m Val lowstrap attachment— Alternate:use 3/8"dia threaded rods for vertical support attach to unit per manufacturer LRFD loads for attachment to concrete 1.2D+1.0c E, 0.9D-1.0E ClcoNc 2.5 (0.2•SDs•Wp Pi tilt 1.2'Pcomer + 1.0. + S2CONC'Pseis Plult =84.58 lb Maximum verticalbad \ 4 l 0.2.Sps•Wp P2ult 0•9'Pcorner — I.0' + Pseis P2uit = 14.09 lb Minimum vertical load>0 no compres 4 l_ vertical support Try 3/8 x 1 5/8"embed Simpson Titen HD rod hanger at support E:\adcadd\19\00000-2019 Mechanical Units10237.01 American Heating Standards 2019\Structural\VAV BOX \CONCRETE OVER METAL DECK Nt43 CIDA Standard Mechanical unit Attachment RNH . TEL: (503)226-1285 VAV Box 8/15/2019 FAX: (503)226 1670 LATERAL BRACING OF VAV BOX Box is braced byy spllay wires at 45degrees vertical and horizontal each corner(4)total. Twire 2p', L'V z• Twire= 53.13 lb LRFD for attachment to concrete Tult:= nCONC'Twire Tuit = 132.81 lb • Tult Vert:_ Y— Vert =93.91 1b Vertical component of wire force Tult Horiz:= - Horiz=93.91 lb horizontal component of wire force 2 Try 3/8"x 1 7/8"embed Simpson Titan HD anchor at each wire ASD for attachment to unit(0.7E) TASD:= Twire'01 TASD=37.19 lb Vert_asd TASD Vert asd=26.3 lb Vertical component of wire force TASD Horiz_asd:= r Horiz_asd=26.3 lb horizontal component of wire force Try(1)#10 SMS at box(20da minimum) Vallow:= 1401b Tallow:= 661b Vert_asd Horiz_asd <1.0 OK Use U:_ + U=0.59 (1)#10 SMS at unit for wire attachment Vallow Tallow 1/8"ARCRAFTCABLE: TALLOW:= 340lb 0.7•Tw,ue Ucable:= Ucable=0.1 1 TALLOW E:\adcadd119100000-2019 Mechanical Units\0237.01 American Heating . Standards 2019\Structural\VAV BOX \CONCRETE OVER METAL DECK • Company: CIDA Date: 7/25/2019 SIMPSON Anchor Designerna *� Software Engineer: Rebekah Huschka Page: 1/5 Project: � Version 2.8.7094.26 Address: 15895 SW 72 Ave ® Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 1.Project information Customer company: Project description: Customer contact name: Location: Customer e-mail: Fastening description: Comment: 2.Input Data&Anchor Parameters ' General Base Material Design method:ACI 318-11 Concrete:Lower flute,Soffit of sand-lightweight Units: Imperial units concrete over metal deck(1-3/4"flute width) State:Cracked Anchor Information: Compressive strength,P.(psi):3000 Anchor type:Concrete screw 4P.,v: 1.0 Material:Carbon Steel Reinforcement condition:B tension,B shear Diameter(inch):0.250 Supplemental reinforcement:Not applicable Nominal Embedment depth(inch):1.625 Anchor installed offset:No Effective Embedment depth,hof(inch):1.190 Code report:ICC-ES ESR-2713 Anchor category:1 Anchor ductility:No hmin:See Figure 1 Cm!n(inch):2.38 Smin(inch):3.57 Recommended Anchor Anchor Name:Titen HD®Rod Hanger-THDB37158RH(1/4"shank&3/8"rod),hnom:1.625"(41mm) Code Report:ICC-ES ESR-2713 0 ( . ,, . - Omega of 2.5 is included in loads Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strang-Te Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com AA Company: CIDA Date: 7/25/2019 SIMPSON Anchor Designer' ' Engineer: Rebekah Huschka Page: 2/5 ,strinnotTie Software Project: `' Version 2.8.7094.26 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com Load and Geometry Load factor source:ACI 318 Section 9.2 Load combination:not set Seismic design:Yes Ductility section for tension:D.3.3.4.3(d)is satisfied Ductility section for shear:D.3.3.5.3(c)is satisfied 00 factor:not set Strength level loads: N.[lb]:85 V.[lb]:0 V.[lb]:0 Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Siro^y-Tie Company Inc 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com A4A .i SIMPSON Anchor Designer TM Company: CIDA Date: 7/25/2019 Engineer: Rebekah Huschka Page: 3/5 Strong-Tie Software Project: Version 2.8.7094.26 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com <Figure 1> f 0 [IN 6.00 [inch] _.1 c .1P/ 0 [lb] 7 / / ! i rf' - 6 4 3r /5 85 [lb] 1 =Min.3/4"(19 mm) 2=Min.3 1/4"(83 mm) 3=Min.1 1/2"(38 mm) 4=Min.20 gauge(0.889 mm)profile metal deck 5=Anchor 6=Max 1/4"(6 mm)offset 7=Lower flute(ridge) Min. 1 3/4"width 8=Upper flute(valley) Min.3 1/2"width Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Ssmnsan Strcng•T3e Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com • AVI 7 SIMPSON Anchor Designer Company: CIDA Date: 7/25/2019 Engineer: Rebekah Huschka Page: 4/5 strAnome Software Project: Version 2.8.709426 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 3, Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, N.(Ib) V.(lb) Vuay(lb) I(Vuax)2+(Vuay)2(Ib) 1 85.0 0.0 0.0 0.0 Sum 85.0 0.0 0.0 0.0 Maximum concrete compression strain(%o):0.00 Maximum concrete compression stress(psi):0 Resultant tension force(lb):0 Resultant compression force(lb):0 Eccentricity of resultant tension forces in x-axis,e'Nx(inch):0.00 Eccentricity of resultant tension forces in y-axis,e'Ny(inch):0.00 4.Steel Strength of Anchor In Tension(Sec.D.5.11 Nam(lb) t¢ ON.(lb) 5195 0.65 3377 6.Pullout Strength of Anchor in Tension(Sec.D.5.31 0.75gNpn=0.7595'Pc,PA5Np(fc/3,000)n(Sec. D.4.1,Eq.D-13&Code Report) 'Yc,P A Np(lb) fc(psi) n 0.750Npn(lb) 1.0 1.00 420 3000 0.50 0.65 205 Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-(is Company inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com SIMPSON Anchor Designer TM Company: CIDA Date: 7/25/2019 Engineer: Rebekah Huschka Page: 5/5 Software StroneleProject: Version 2.8.7094.26 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 11.Results 11.Interaction of Tensile and Shear Forces(Sec.0.71? Tension Factored Load,N.(lb) Design Strength,eN„(lb) Ratio Status Steel 85 3377 0.03 Pass Pullout 85 205 0.42 Pass(Governs) THDB3715BRH(1/4"shank&3/8"rod),hnom:1.625"(41mm)meets the selected design criteria. Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. S!n;pscn Strong-Tie Company Inn 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com MAR SIMPSON Anchor Designer TM Company: CIDA Date: 7/25/2019 Engineer: Rebekah Huschka Page: 1/5 st �)� Software Project: Version 2.8.7094.24 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 1.Proiect information Customer company: Project description: Customer contact name: Location: Customer e-mail: Fastening description: Comment: 2.Input Data&Anchor Parameters General Base Material Design method:ACI 318-11 Concrete:Lower flute,Soffit of sand-lightweight Units:Imperial units concrete over metal deck(4-1/2"flute width) State:Cracked Anchor Information: Compressive strength,1'.(psi):3000 Anchor type:Concrete screw 4a.,v: 1.0 Material:Carbon Steel Reinforcement condition:B tension,B shear Diameter(Inch):0.375 Supplemental reinforcement:Not applicable Nominal Embedment depth(inch):1.875 Anchor installed offset:No Effective Embedment depth,hof(inch):1.230 Code report:ICC-ES ESR-2713 Anchor category: 1 Anchor ductility:No hmin:See Figure 1 Cmi,(inch):2.46 Smin(inch):3.69 Recommended Anchor Anchor Name:Titan HD®-3/8"0 Titen HD,hnom:1.875"(48mm) Code Report:ICC-ES ESR-2713 Omega of 2.5 is included in loads Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong.T e Company Inc 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com • T t)V Company: CIDA Date: 7/25/2019 SIMPSON Anchor DesignerT"" Engineer: Rebekah Huschka Page: 2/5 strimmitTieSoftware Project: Version 2.8.7094.24 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com Load and Geometry Load factor source:ACI 318 Section 9.2 Load combination:not set Seismic design:Yes Ductility section for tension:D.3.3.4.3(d)is satisfied Ductility section for shear:D.3.3.5.3(c)is satisfied 00 factor:not set Strength level loads: N .(Ibj:94 V..z[lb]:0 Vuay(ibj:94 Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. 5iin,son Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925,847.3871 www.strongtie.com A441t SIMPSON Anchor DesignerTm Company: CIDA Date: 7/25/2019 Engineer. Rebekah Huschka Page: 3/5 S ong tie Software Project: Version 2.8.7094.24 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com <Figure 1> Q Oh] 1 / / 6.00 [inch] / 2 i i t 94 [lb] 7 / / ' f 8 / , / 6 4 / J/ 5 / 94 [lb] 1 =Min. 1/2"(12 mm)for Strong-Bolt 2 Min.3/4"(19 mm)for Titen HD,Titen HD Rod Hanger and BBMD 2=Min.1 1/2"(38 mm)for Strong-Bolt 2 Min. 1 1/2"(38 mm)for Titen HD and Titen HD Rod Hanger Min.3 1/4"(83 mm)for BBMD 3=Max.3"(76 mm) 4=Min.20 gauge(0.889 mm)profile metal deck 5=Anchor 6=Max 1"(25 mm)offset for Strong-Bolt 2 Max 1"(25 mm)offset for Titen HD and Titen HD Rod Hanger Max. 1 1/4"(32 mm)offset for BBMD 7=Lower flute(ridge) Min.4 1/2"width 8=Upper flute(valley) Min.4 1/2"width Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Simpson Strong-T e Company Inc. 5956 W.Las Positas Boulevard Pleasanton.CA 94588 Phone:925.560.9000 Fax:925.647.3871 www.strongtie.com /VIA !2 SIMPSON Anchor Designer' Company: ClDA Date: 7/25/2019 Engineer: Rebekah Huschka Page: 4/5 stranotTie Software Project: Version 2.8.7094.24 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 3.Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, Na„ (lb) Vuax(Ib) Vuay(lb) 1l(Vuax)2+(V ey)2(Ib) 1 94.0 0.0 94.0 94.0 Sum 94.0 0.0 94.0 94.0 Maximum concrete compression strain(%c):0.00 ' Maximum concrete compression stress(psi):0 Resultant tension force(Ib):0 Resultant compression force(lb):0 Eccentricity of resultant tension forces in x-axis,e'rix(inch):0.00 Eccentricity of resultant tension forces in y-axis,e'ry(inch):0.00 Eccentricity of resultant shear forces in x-axis,e'vx(inch):0.00 Eccentricity of resultant shear forces in y-axis,e'vy(inch):0.00 4.Steel Strength of Anchor in Tension(Sec.D.5.11 N.,e(Ib) 0 qNs,(Ib) 10890 0.65 7079 6.Pullout Strength of Anchor in Tension(Sec, D.5.31 0.750Npn=0.750Vc,P.i.eNp(fc/3,000)^(Sec. D.4.1, Eq.D-13&Code Report) Y'c,P A. Np(Ib) fc(psi) 0.750Npn(Ib) 1.0 1.00 375 3000 0.50 0.65 183 Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. Surnpsen Strong-Tie Company Inc. 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com MA Company: CIDA Date: 7/25/2019 SIMPSON Anchor Designer"" Engineer: Rebekah Huschka Page: 5/5 strangne Software Project: Version 2.8.7094.24 Address: 15895 SW 72 Ave Phone: (503)226-1285 E-mail: rebekahh@cidainc.com 8.Steel Strength of Anchor In Shear(Sec.D.6.1) V.(Ib) Avout 4grout0Vse(lb) 1434 1.0 0.60 860 11.Results Interaction of Tensile and Shear Forces(Sec.D.7.1 Tension Factored Load,N.(lb) Design Strength,eNn(Ib) Ratio Status Steel 94 7079 0.01 Pass Pullout 94 183 0.51 Pass(Governs) Shear Factored Load,V.(Ib) Design Strength,eVn(Ib) Ratio Status Steel 94 860 0.11 Pass(Governs) Interaction check Nue//Nn Vue/fbV Combined Ratio Permissible Status Sec.D.7..1 0.51 0.00 51.4% 1.0 Pass 3/8"0 Titen HD,hnom:1.875"(48mm)meets the selected design criteria. Input data and results must be checked for agreement with the existing circumstances,the standards and guidelines must be checked for plausibility. S nipson Strong-Tie Company Inc, 5956 W.Las Positas Boulevard Pleasanton,CA 94588 Phone:925.560.9000 Fax:925.847.3871 www.strongtie.com