Reliable® Model G Automatic Sprinklers
Spray Upright, Spray Pendent,
And Conventional D
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of construc-
tion. The fusible alloy is captured in the cylinder of the =
solder capsule by a stainless steel ball. When the fusible
alloy melts, the ball moves into the cylinder allowing the �
cylinder to fall away from the sprinkler.When this happens, J; -
the lever is released to spring free from the sprinkler so rtsca-
that all of the operating parts clear from the waterway al-
lowing the deflector to distribute the discharging water.
Except for the parts in the cylinder as mentioned above, Upright Pendent
the sprinkler components are made from copper based
alloys for maximum corrosion protection.Lead plated,wax
coated or wax over lead plated sprinklers are available for .nr*
specially severe environments. Chrome plated sprinklers
are available for decorative purposes. , _'
All sprinklers are individually hydrostatically tested. All me
sprinklers are identified as to their fusing point by mark
ings that appear on several of the operating parts and by
an identifying color that appears on the frame.
Sprinkler Types
Standard Upright—This deflector configuration is normal-
ly used with exposed piping installations. Water is distrib Small Orifice Upright Conventional
uted laterally and downward in a wide pattern approximat-
ing a hemisphere which is completely and uniformly filled
with water in the form of small drops or spray.
Standard Pendent—This deflector configuration is nor- Application and Installation
mally used where the space above the piping is limited Standard sprinklers are used in fixed fire protection sys-
or where a concealed piping installation is employed. tems: Wet, Dry, Deluge or Preaction. Care must be exer-
The discharge characteristics of the standard pendent cised that the orifice sizes, temperature ratings, deflector
are virtually identical to the standard upright as de- styles and sprinkler spacings are in accordance with the
scribed above. latest published standards of the National Fire Protection
Association or the approving authority having jurisdiction.
Large and Small Orifice —By varying the orifice size, a The sprinklers must be installed with the Reliable Model
large or small orifice sprinkler is created that will distrib- D Sprinkler Wrench. Any other type of wrench may dam-
ute as much as 40% more water or 65% less water than age the sprinkler.
the normal 1/2" (15mm) orifice sprinkler. The approvals or listings of Reliable Automatic Sprin-
klers by major approving organizations are shown in the
Conventional —This deflector configuration is used pri- tabulated list provided on the back of this bulletin.
marily in those countries where the LPC installation rules
have precedence. The sprinkler is designed to distribute
a portion of its water discharge upward against the ceil-
ing with the balance downward. It may be installed in
either the upright or the pendent position. Sprinklers with
• conventional deflectors are available with orifice sizes
corresponding to light, ordinary and extra—high hazard
installations.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Technical Data
"K"Factor Sprinkler Sprinkler Identification Number
Sprinkler Type Height Approvals _ (SIN)
US Metric SSU SSP
Standard—Upright(SSU)and Pendent(SSP) ,
Deflectors Marked to Indicate Position
1/2"(15 mm)Standard Orifice with 1/2"NPT(R1/2)Thread 5.62 81.0 2'/8"(73 mm) 1,2,3,4,5,6 R1025 R1015
7/16"(11 mm)Small Orifice with NPT(R1/2)Thread 4.24 61.0 2'/e"(73 mm) 1 R1023 R1013 ti
3/a"(10 mm)Small Orifice with 1/2"NPT(R1/2)Thread 2.82 40.6 2'/8"(73 mm) 1,2, R1021 R1011
5/16"(8 mm)Small Orifice with 1/2"NPT(R'/2)Thread 1.98 28.5 2'/e"(73 mm) 1,5 R1022 R1012
17/32"(20 mm)Large Orifice with 1/2"NPT(R1/2)Thread 7.96 114.7 2'/8"(73 mm) 1,2, R1026 R1016
17/32"(20 mm)Large Orifice with 3/4"NPT(R3/4)Thread 8.20 118.2 2 t5/16"(75 mm) 1,2, R1027 R1017
20 mm XHH with 20 mm Thread
10 mm XLH with 10 mm Thread 8.20 118.2 75.4 mm 3,4, R1027 R1017
4.10 59.1 73 mm 3,4, R1024 R1014
Conventional—Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10 59.1 73 mm 4 R1074
15mm Standard Orifice with(R1/2) Thread 5.62 81.0 73 mm 3,4,6 R1075
20mm XHH with(R3/4)Thread 8.20 118.2 75.4 mm 3,4 R1077
Temperature Ratings Maintenance
Sprinkler Maximum Model G Sprinklers should be inspected and the sprinkler
Classification Rating Ambient Frame ' system maintained in accordance with NFPA 25. Do not clean
Temperature Color sprinklers with soap and water, ammonia or any other clean-
°F °C °F °C
Ordinary 135 57 100 38 Black ing fluids. Remove any sprinkler that has been painted (other
Ordinary 165 74 100 38 Uncolored than factory applied)or damaged in any way.A stock of spare
Intermediate 212 100 150 66 White sprinklers should be maintained to allow quick replacement of
High 286 141 225 107 Blue damaged or operated sprinklers. Prior to installation,sprinklers
1)Frame color does not apply to painted or plated sprinklers should be maintained in the original cartons and packaging un-
-Use sprinklert rating as identified on operating parts. til used to minimize the potential for damage to sprinklers that
Finishes would cause improper operation or non-operation.Use only the
Standard Finishes Model D Sprinkler Wrench for sprinkler removal and installation.
Bronze —All Temperature Ratings
Chrome —All Temperature Ratings Any other type of wrench may damage the sprinkler.
White(2) —All Temperature Ratings Approval Organizations
Only Frame and Deflector are Painted 1. Underwriters Laboratories,Inc.and UL Certified for Can-
Special Application Finishes ada(cULus).
Bright Brass Plated —Only frame,deflector and cap are plated.135°F 2. Factory Mutual Research Corporation
(57°C),165°F(74°C),212°F(100°C)Temp.Rating.
Black Plated —Only frame,deflector and cap are plated.All 3. Loss Prevention Council
Polyester Coated 12H4) Temp.Ratings. 4. Pleniere ASsemblee
Lead Plated —Only frame and deflector are coated. 5. N.Y.C. BS&A No.587-75—SA or
Wax-Coated(3) —165°F(74°C),212°F(100°C)and 286°F(141°C) N.Y.C. MEA 258-93 E
Wax-Coated Over Temp.Ratings.
Lead Plated'3) —165°F(74°C)Clear Wax,212°F(100°C) Brown 6. EC Certificate: 1438-CPD-0054(R1015)
Wax. 1438-CPD-0053(R1025)
—165°F(74°C)Clear Wax,212°F(100°C) Brown 1438 CPD 0052(R1075)
Wax. 1438-CPD-0056(R1077)
(1) Other colors and finishes are available.Consult factory for details. Ordering Information
(2) UL listed and NYC MEA Approved only. Specify:
(3) 212°F(100°C)brown wax may be used on 286°F(141°C) 1. Model G
sprinklers when maximum ambient temperatures do not exceed 150°F 2. Deflector
(66°C).UL Listed,FM Approved,NYC MEA 258-93-E. • Upright
(4) FM Approved for R1027 only.
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory w,'
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. *I.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years.
Manufactured by
Reliable Automatic Sprinkler Co.,Inc. ® Recycled
IlleliiibIl ® (800(800)4 31-1588 848 6051-2042 Sales Offices Paper
Sales Fax Revision lines indicate updated or new data.
(914)829 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.08/19 P/N 9999970005