Plans A HECEIVED
Scope of Work JAN 2 8 2020 '
*Replace 5 ton RTU with new 5 ton RTU, Like for Like. �a�v f r r,,
Pa Y;(cu.cl Lo+' 1 , ._.
�t Ff ov 7 En!h-}i *Reconnect existing, ductwork, electrical, gas and
` controls. NOTE: Existing RTU weight with/out
economizer is 512 lbs. New RTU weight
•
with/out economizer= 533 lbs. Code
_ --J11-
Av
allows for up to 10%additional weight
r
without having structural calculations.
.. 70
-
—CI.rYOTGARa ; We are <+0.4%> higher in weight.
REVIEWED FOR CODE COMPLIANCE
Approved: I
GI
OTC: [ I l
s i'
Permit#: 1
Address: j r, C. _ [fir - :--"- y,,ty
Z it Ventilation Requirements
Suite#� ;' p IMC 2015 Chapter 4,Table 403.3.1.1
By' Date: �-._Z' 9 ' ! Area Served: Retail 1400 sq. ft. =21
i.
p { t I— —
Occupants @ 7.5 cfm = 158 CFM, delivered by
I RTU-1 using economizer. Set OSA at 170 CFM,
ii i E i
5 i I-- 1 ` — J Minimum.
[E1 r 1 ii �® �EJ
Lr_ , r- - i
E r
E L 1T —� `� J LA Ow P.o0 I:
I' Equipment Schedule
EWW.�T I 7 .A. 1
TAG RTU-1 Existing RTU
TV, 0 7 a 4-iX t,5 -De, } c Manufacture Daikin Goodman
: Model DP14MG6108043A GPG10600901A
li i
Cooling BTUH 57 56
Heating BTUH 80 90
li l SEER 14 10
ii E CFM-Cooling 1750 Nom.
ii I Voltage 208/230, 3ph 208/230, 3ph
i1 MOCP 45
ll i1 j Weight 533 lbs. 512 lbs.
11 Location On Roof On Roof
a(�' �1. Like for Like,set on existing curb.
' 1' Accessories:Add Economizer.
,... �____._ . .________�__ __ �...-_--- __._.. A , ,. -4 _ Notes Note: Existing duct smoke detector&
�.-_. ..__ -_ �_ _.�_ thermostat.
il VALIDITY OF PERMIT
i,
THE ISSUANCE OF A PERMIT
I' BASED ON CONSTRUCTION Project: Tigard Towne Square - Suite G1 -RTU Replacement
c- DOCUMENTS AND OTHER CITY OF TIGAR
DATA SHALL NOT PREVENT Approved by Planning �/
THE CODE OFFICIAL FROM �_��� Location: 16200 SW Pacific Hwy., Suite Cl Tigard Or. 97123 Tigard Or. 97223
REQUIRING THE CORRECTION Date: 0\ Replacement of (1) 5 ton RTU
OF ERRORS.OSSC 105.4 L
Initials: Scale: 3/32y
" = 1'0" Plan Sheet
Drawn By: Date: 1/24/2020 'Rey. M-1