Loading...
Report /17eC ZO20 404D 6.9 Latimer HVAC HEATING•VENTILATION•AIR CONDITIONING g Carria e House Clubhouse � 8376 SW Pflaffle St Portland, OR JAN 2 9 1OZO Scope of Work BOLDING Latimer HVAC will perform the following scope of work: 1. Provide and install new gas furnace replacing existing. 2. Reconnect gas, controls, and recommission. Equipment Schedule F1-. Carrier 59SC5A080S17-16- 120/1/60, 13MCA, 15 MOCP. 0.75HP. 80,000 Btu input gas, 96%AFUE. 154#. On ground in mechanical room. Set for 1450 CFM for cooling. Mechanical General Notes: 1. Replacement unit is closest size replacement to existing. 2. All steel ducting will be 26 ga minimum galvanized. 3. Heating and cooling ducting to be designed to not exceed 0.5 wc positive(supply) and 0.5 wc negative (return). 4. Provide programmable thermostat.5 degree deadband minimum.7 day. Microprocessor.Set program for night energy savings. 5. Seal ducting with UL listed mastic or mastic tape. 6. Fan motor does not exceed allowable,first available above BHP. 7. Provide 0 and M to building owner. Ventilation Requirements-based on 2014 OMSC table 403.3 No changes to ventilation. GAS- Old furnace- 76,000 Btu. New furnace-80,000 Btu. Per OMSC Table C402.4(2) Less than 2Psi inlet pressure @ 0.5in WC pressure drop Max 50' developed length %" pipe adequate for 151,000 Btu Load- Water heater- 60,000 Btu F1- 80,000 Btu Total- 140,000 Btu l\/I 0 Latimer HVAC LLC,p.,.-..�,.�..-.,-.-...�, 11230 SW Morgen Ct. (503) 290-1085 Oregon CCB 220839 Tigard,OR 97223 info@latimerhvac.com Washington LATIMHL825K4 S 59SC5A ComfortTM Series Single—Stage 4—Way Multipoise (Carrie Condensing Gas Furnace Series 1 and 2 turn to the experts Product Data z �m � a v STANDARD FEATURES)AN 2 9 2020 • 4-way multipoise design for upflow,downflow or horizontals installation. J ,3 a s 11 S 1I O ,' • Installation flexibility with a 360-degree rotating elbow. O • More than twelve different venting options,including optional through-the-cabinet downflow and horizontal venting. 1 • Ideal condensing furnace height 35"(889 mm)cabinet:short enough for taller coils,but still allows enough room for service. • Silicon Nitride Power Heat"" Hot Surface Igniter. 4 ��Jt! • Aluminized-steel primary heat exchanger. fJ71 �I 1 I . Stainless-steel condensing secondary heat exchanger. f--- I • High-quality corrosion-resistant prepainted steel cabinet with hemmed edges for safety. • Factory-configured ready for upflow applications. • Direct-vent/sealed combustion,single-pipe venting or ventilated combustion air. • PSC blower motor,single-speed inducer motor,and single-stage gas valve. A11263 • Self-diagnostics with SuperBrite LED. • Approved for Twinning applications(060-10 through 120-20 The 59SC5 Multipoise Comfort Series Condensing Gas Furnace sizes,only). features energy efficiency up to 96.0% AFUE gas efficiency and • Propane convertible(See accessory list). workhorse PSC blower motor. This gas furnace also features • Approved for Manufactured Housing/Mobile Home applications 4-way multipoise installation flexibility,and is available in eleven model sizes. All sizes except the 26,000 BTUH model can be (except 26,000 and 140,000 Btuh input)with MH accessory kit. vented for direct vent/two-pipe, ventilated combustion air, or • Convenient Air Purifier and Humidifier electrical connections. single-pipe applications. The 26,000 BTUH model can use the • Residential installations may be eligible for consumer financing same 2—pipe venting system using outside air for combustion,but through the Retail Credit Program. is not considered direct—vent. All units meet California Air Quality • Cabinet air leakage less than 2.0%at 1.0 in.W.C.and cabinet air Management District emission requirements,are design certified in Canada,and are certified for mobile/manufactured home use. leakage less than 1.4%at 0.5 in.W.C.when tested in accordance with ASHRAE standard 193. E TM y i�.. iCERTIFIED- Olt to p www.ao,mbaaio¢o•.� C ComfortSER [ ES Use of theAIIRICertpation ntheMarkprdiratesa manufacturer's participation m the program.For U , verification of certification for individual products, ISO 9001 go to www.ahridirectory.org. groom Global 1 RATED ' CASING HEATING DIMENSIONS(IN.) OUTPUTt AFUE HEATING AIRFLOW COOLING ENERGY HEATING CFM SAP ORDERING uFFLowi STAR® ESP @ 0.5 ESP MOTOR HP NO. H D W (BTUH) HORIZONTAL DOWNFLOW CFM# (in.W.C.) (in.W.C.) SPEED TAPS 59SC5A026S14--08 35 29.5 14.2 25,000 96.0% 96.0% None 675 0.10 440-775 1/4-4 59SC5A040S14--10 35 29.5 14.2 39,000 96.0% 96.0% None 820 0.10 625-905 1/2-4 59SC5A040S17--12 35 29.5 17.5 39,000 96.0% 95.0% None 1000 0.10 650-1050 1/2-5 59SC5A060S14--10 35 29.5 14.2 58,000 95.5% 95.0% None 840 0.12 675-1130 1/2-4 59SC5A060S17--14 35 29.5 17.5 58,000 96.0% 96.0% None 980 0.12 650-1420 1/2-5 59SC5A080S17--16 35 29.5 17.5 78,000 96.0% 96.0% None 1040 0.15 810-1600 3/4-5 59SC5A080S21--20 35 29.5 21.0 78,000 96.0% 96.0% None 1695 0.15 1335-1970 1 -5 59SC5A100S21--14 35 29.5 21.0 97,000 96.0% 96.0% None 1510 0.20 915-1545 1/2-4 59SC5A100S21--20 35 29.5 21.0 97,000 96.0% 96.0% None 1680 0.20 1345-2065 1 -5 59SC5A120S24--20 35 29.5 24.5 117,000 96.0% 96.0% None 2245 0.20 1320-2105 1 -5 59SC5A140S24--20 35 29.5 24.5 135,000 96.0% 96.0% None 2175 0.20 1290-2035 1 -5 t Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate. #Heating CFM at factory default blower motor heating tap settings. ESP-External Static Pressure Q u) U) FEATURES AND BENEFITS rn Direct or Single-pipe Venting, or Optional Ventilated t) HYBRID HEAT®Dual Fuel system-This system can provide Combustion Air-All sizes except the 26,000 BTUH model can more control over your monthly energy bills by automatically be vented for direct vent/two-pipe, ventilated combustion air, or selecting the most economical method of heating.With HYBRID single-pipe applications. The 26,000 BTUH model can use the HEAT components,our system automatically switches between the same 2-pipe venting system using outside air for combustion,but gas furnace and the single-stage electric heat pump as outside is not considered direct-vent. This provides added flexibility to temperatures change to maintain greater efficiency and comfort meet diverse installation needs. than with any traditional single-source heating system. The heat Sealed Combustion System-This furnace brings in combustion pump also delivers high-efficiency cooling in the summer. air from outside the furnace, which results in especially quiet Power Heat'" Igniter-Carrier's unique SiN igniter is not only operation.By sealing the entire combustion vestibule, the entire physically robust but it is also electrically robust.It is capable of furnace can be made quieter,not just the burners. running at line voltage and does not require complex voltage Monoport Burners - The burners are specially designed and regulators as do other brands.This unique feature further enhances finely tuned for smooth, quiet combustion and economical the gas furnace reliability and continues Carrier's tradition of technology leadership and innovation in providing a reliable and operation. durable product. Bottom Closure - Factory-installed for side return; easily removable for bottom return. The multi use bottom closure can Reliable Heat Exchanger Design-The aluminised steel,clam also serve for roll-out protection in horizontal applications,and act shell primary heat exchanger was re-engineered to achieve greater efficiency out of a smaller size. The first two passes of the heat as the bottom closure for the optional return air base accessory. exchanger are based on the current 80% product, a design with Blower Access Panel Switch -Automatically shuts off 115-v more than ten years of field-proven performance and success. power to furnace whenever blower access panel is opened. These innovations, paired with the continuation of a crimped, Quality Registration - Our furnaces are engineered and no-weld seam create an efficient,robust design for this essential manufactured under an ISO 9001 registered quality system. component. Certifications-This furnace is CSA(AGA and CGA) design The condensing heat exchanger, a stainless steel fin and tube certified for use with natural and propane gases. The furnace is design, is positioned in the furnace to extract additional heat. factory-shipped for use with natural gas. A CSA listed gas S ainless steel coupling box componentry between heat exchangers conversion kit is required to convert furnace for use with propane has exceptional corrosion resistance in both natural gas and gas.The efficiency is AHRI efficiency rating certified.This furnace propane applications. meets California Air Quality Management District emission 4-Way Multipoise Design - One model for all applications- requirements. there is no need to stock special downflow or horizontal models when one unit will do it all. The new heat exchanger design allows these units to achieve the certified AFUE in all positions. 2 , SPECIFICATIONS The furnace should be sized to provide 100 percent of the design method to calculate heating load estimates and select the furnace. heating load requirement plus any margin that occurs because of Excessive oversizing of the furnace may cause the furnace and/or furnace model size capacity increments. None of the furnace vent to fail prematurely,customer discomfort and/or vent freezing. - model sizes can be used if the heating load is 12,000 BTUH or Failure to follow these guidelines is considered faulty installation lower. Use Air Conditioning Contractors of America (Manual J and/or misapplication of the furnace;and resulting failure,damage, and S); American Society of Heating, Refrigerating, and or repairs may impact warranty coverage. Air-Conditioning Engineers; or other approved engineering Heating Capacity and Efficiency 026-08 040-10 040-12 060-10 060.14 080-16 080-20 100-14 100-20 120-20 140-20 Input High (BTUH) 26,000 40,000 40,000 60,000 60,000 80,000 80,000 100,000 100,000 120,000 140,000 Heat Output High (BTUH)BTUH 25,000 39,000 39,000 58,000 58,000 78,000 78,000 97,000 97,000 117,000 135,000 Heat Certified Temperature High Heat 25-55 40-70 35-65 40-70 40-70 40-70 40-70 40-70 40-70 40-70 45-75 Rise Range °F(C) (14-31) (22-39) (19-36) (22-39) (22-39) (22-39) (22-39) (22-39) (22-39) (22-39) (25-42) Airflow Capacity and Blower Data 026-08 040.10 040-12 060-10 060-14 08016 080-20 100-14 100 20 120-20 140-20 Rated External Static Heating 0.10 0.10 0.10 0.12 0.12 0.15 0.15 0.20 0.20 0.20 0.20 Pressure(in.W.C.) Cooling 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 t�A Airflow Delivery High Heat 675 820 1000 840 980 1040 1695 1510 1680 2245 2175 U @ Rated ESP(CFM) Cooling 775 905 1050 1130 1420 1600 1970 1545 2065 2105 2035 ch Cooling Capacity(tons) 400 CFM/ton 1.5 2 2.5 2.5 3.5 4 5 4 5 5 5 to 350 CFM/ton 2 2.5 3 3 4 4.5 5.5 4.5 6 6 6 Direct-Drive Motor Type Permanent Split Capacitor(PSC) Direct-Drive Motor HP 0.25 0.5 0.5 0.5 0.5 0.75 1 0.5 1 1 1 Motor Full Load Amps 2.8 6.2 6.8 6.2 6.8 7.9 13.8 6.5 13.8 14.1 14.1 RPM Range 500-1150 Speed Selections 4 4 5 4 5 5 5 4 5 5 5 Blower Wheel Dia x Width in. 11 x 7 11 x 7 11 x 8 11 x 7 11 x 8 11 x 8 11 x 10 11 x 10 11 x 10 11 x 11 11 x 11 Air Filtration System Field Supplied Filter Used for Certified Watt Data* KGAWF**06UFR Electrical Data 026-08 040-10 040-12 060-10 060-14 080-16 080-20 100-14 100-20 120-20 140-20 Input Voltage Volts-Hertz-Phase 115-60-1 Operating Voltage Range Min-Max 104-127 Maximum Input Amps Amps 3.6 6.8 8.3 7.0 8.4 9.6 14.5 7.6 14.6 14.9 14.9 Unit Ampacity Amps 5.4 9.5 11.4 9.7 11.5 13.0 19.1 10.4 19.2 19.6 19.6 Minimum Wire Size AWG 14 14 14 14 14 14 12 14 12 12 12 Maximum Wire Length Feet 68 39 32 38 32 28 30 35 29 29 29 @ Minimum Wire Size (M) (20.7) (11.9) (9.8) (11.6) (9.8) (8.5) (9.1) (10.7) (8.8) (8.8) (8.8) Maximum Fuse/Ckt Bkr (Time-Delay Type Recom- Amps 15 15 15 15 15 15 20 15 20 20 20 mended) Transformer Capacity(24vac output) 40 VA External Control Power Heating 27.9 VA Available Cooling 34.6 VA Controls 026-08 040-10 04012 060-10 060-14 080-16 080-20 100-14 100-20 120-20 140-20 Gas Connection Size 1/2"-NPT Burners(Monoport) 2 2 2 3 3 4 4 5 5 6 7 Gas Valve(Redundant) Manufacturer White Rogers Minimum Inlet Gas pressure(in.W.C.) 4.5 Maximum Inlet Gas pressure(in.W.C.) 13.6 Ignition Device Silicon Nitride Limit Control 220 165 180 165 180 170 200 180 180 160 155 Heating Blower Control(Heating Off-Delay) Adjustable:90,120,150,180 seconds Cooling Blower Control(Time Delay Relay) 90 seconds Communication System none Thermostat Connections Com 24V,R,W,G,Y Accessory Connections EAC(115vac);HUM(24vac) *See Accessory List for part numbers available. 3 MODEL NUMBER NOMENCLATURE 1-2 3 4 5 6 7-9 10 11-12 13 14 15-16 Family Htg.Stages Tier Base Effy. Major Series Htg.Cap. Motor Width Voltage Minor Series Airflow 59 S C 5 A 060 S 17 - - 14 I I I I I I I I Family 08-800 CFM 10-1000 CFM 12-1200 CFM 14-1400 CFM 16-1600CFM 18-1800CFM 20-2000 CFM 22-2200 CFM S-Single Stage Minor Series T-Two Stage Vol e M-Modulati 14-14.2" C-Comfort 17-17.5" P-Performance 21-21.0" N-Infinity 24-24.5" 0-+90AFUE 2-+92AFUE 3-+93 AFUE 026=26,000 BTU 5-+95 AFUE 040=40,000 BTU S-Standard Q 6-+96 AFUE 060=60,000 BTU E-Energy Efficient Ln 7-+97AFUE 080=80,000 BTU V-VariableS.--• V 100=100,000 BTU N 120=120,000 BTU Ma'.r Series 140=140,000 BTU U7 A180005 FURNACE COMPONENTS HOT SURFACE IGNITER GAS BURNER MANUAL RESET ROLLOUT SWITCH FLAME It'.. O bwA w-` -/r`' '= SENSOR it i MANUAL RESET - -- ROLLOUT SWITCH • • GAS VALVE I� +, i Si Ifr' ..di , i 6 MAIN LIMIT SWITCH -—nv,� , (BEHIND GAS VALVE) OPERATING INSTRUCTIONS C °j-� NOT SHOWN(LOCATED ON ^O � MAIN FURNACE DOOR,SEE :•r OPERATING INSTRUCTIONS t '�O _•n� 1�(INSIDE DOOR FIGURE). p -'� 11.Oj(1 �tI. INDUCER MOTOR 0��� t` r�� ASSEMBLY ELECTRICAL JUNCTION Y G ? BOX(IF REQUIRED, 0 I �- I t�0 � LOCATION MAY VARY) I ,4 '1f"'"� � ccc...yyy s BLOWER DOOR (y( s W " � m W li!�e SAFETY SWITCH 11 "� . •-j " • - - -4-MEDIA CABINET r e _ ®no ,r''I O me FURNACE I _BLOWER AND CONTROL MOTOR BOARD -'= I �� 11 ®to tli A!/' I / CAPACITOR/ 1.1 , POWER CHOKE (IF USED) RATING PLATE NOT SHOWN (LOCATED ON BLOWER DOOR) -- -- - -- -- _. Y REPRESENTATIVE DRAWING ONLY,SOME MODELS MAY VARY IN APPEARANCE. A170154 4 ACCESSORIES DESCRIPTION PART NUMBER, 026-08 040-10 040-12 060-10 060-14 080-16 080-20 100-14 100-20 120-20 140-20 Venting Accessories Vent Kit-Through the Cabinet KGADC0101 BVC • • • • • • • • • • • ' Vent Terminal-Concentric-2"(51 mm) KGAVT0701 CVT Vent Terminal-Concentric-3"(76 mm) KGAVT0801 CVT Vent Terminal Bracket-2"(51 mm) KGAVT0101 BRA See Venting Tables Vent Terminal Bracket-3"(76 mm) KGAVT0201 BRA Vent Kit—Rubber Coupling KGAAC0101 RVC See Venting Tables Condensate Drainage Accessories Freeze Protect Kit—Trap Heater KGAHT0201 CFP • • • • • • • • • • • CPVC to PVC Drain Adapters-1/2"CPVC to 3/4"PVC KGAAD0110PVC • • • • • • • • • • • Horizontal Trap Grommet-Direct Vent KGACK0101 HCK All 2—Pipe Horizontal Condensate Neutralizer Kit P908-0001 • • • • • • • • • • • External Trap Kit KGAET0201 ETK • • • • • • • • • • • Ductwork Adapter Accessories Furnace Base Kit for Combustible Floors KGASB0201ALL • • • • • • • • • • • Coil Adapter Kits—No Offset KGADA0101ALL • • • • • • • • • • • Coil Adapter Kits—Single Offset KGADA0201ALL • • • • • • • • • • • Coil Adapter Kits—Double Offset KGADA0301ALL • • • • • • • • • • • Return Air Base(Upflow Applications)14.0—in.wide KGARP0301 B14 • • • Return Air Base(Upflow Applications)17.5—in.wide KGARP0301 B17 • • • Return Air Base(Upflow Applications)21.0—in.wide KGARP0301 B21 • • • Return Air Base(Upflow Applications)24.5—in.wide KGARP0301 B24 • • 0 IAQ Device Duct Adapters 20.0—in.IAQ to 16 in. KGAAD0101 MEC 20"x25"IAQ Devices Side Return to IAQ Device Duct Adapters 24.0—in.IAQ to 16 in. KGAAD0201 MEC 24"x25"IAQ Devices Side Return Gas Conversion Accessories Mobile Home Kit KGBMH0601KIT • • • • • • • • • Gas Conversion Kit-Nat to LP KGANP54011 SP • Gas Conversion Kit-LP to Nat KGAPN46011 SP • Gas Conversion Kit-Nat to LP KGBNP50011SP • • • • • • • • • • Gas Conversion Kit-LP to Nat KGBPN42011SP • • • • • • • • • • Gas Orifice Kit-#42(Nat Gas) LH32DB207 • • • • • • • • • • • Gas Orifice Kit-#43(Nat Gas) LH32D6202 • • • • • • • • • • • Gas Orifice Kit-#44(Nat Gas) LH32DB200 • • • • • • • • • • • Gas Orifice Kit-#45(Nat Gas) LH32DB205 • • • • • • • • • • Gas Orifice Kit-#46(Nat Gas) LH32D6208 • • • • • • • • • • Gas Orifice Kit-#47(Nat Gas) LH32D6078 • • • • • • • • • • Gas Orifice Kit-#48(Nat Gas) LH32DB076 • • • • • • • • • • Gas Orifice Kit-#54(LP) LH32DB203 • • • • • • • • • • Gas Orifice Kit-#55(LP) LH32DB201 • • • • • • • • • • Gas Orifice Kit-#56(LP) LH32DB206 • • • • • • • • • • Gas Orifice Kit-1.25mm(LP) LH32D8209 • • • • • • • • • • • Gas Orifice Kit-1.30mm(LP) LH32DB210 • • • • • • • • • • Gas Valve Adapter Gas Valve Tower Port Adapter Kit 92-1003 • • • • • • • • • • • Control Accessories Twinning Kit KGATW0701HS1 • • • • • • • IAQ Accessories Filter Rack—Side Return for 1"Filters KGAFRO201ALL • • • • • • • • • • • Filter Rack—Bottom Return for 1"Filters—14.2"wide KGBFRO401B14 • • • • • • • • Filter Rack—Bottom Return for 1"Filters—17.5"wide KGBFRO501617 • • • • • • • • Filter Rack—Bottom Return for 1"Filters—21.0"wide KGBFR0601621 • • • • • • • • Filter Rack—Bottom Return for 1"Filters—24.5"wide KGBFRO701824 • • • • • • • • Filter Pack(6 pack)—Washable-16x25x1 KGAWF1306UFR • • • • • • • • • • • Filter Pack(6 pack)—Washable-24x25x1 KGAWF1506UFR • • • • • • • • • • • EZ-Flex Filter-16"(406 mm) EXPXXFIL0016 Use with EZXCAB-1016 EZ-Flex Filter-20"(508 mm) EXPXXFIL0020 Use with EZXCAB-1020 EZ-Flex Filter-24" (610 mm) EXPXXFIL0024 Use with EZXCAB-1024 EZ-Flex Filter with End Caps-16"(406 mm) EXPXXUNV0016 Use with EZXCAB-1016 EZ-Flex Filter with End Caps-20"(508 mm) EXPXXUNV0020 Use with EZXCAB-1020 EZ-Flex Filter with End Caps-24"(610 mm) EXPXXUNV0024 Use with EZXCAB-1024 Cartridge Media Filter-16"(406 mm) FILXXCAR0016 Use with FILCABXL-1016 Cartridge Media Filter-20"(508 mm) FILXXCAR0020 Use with FILCABXL-1020 Cartridge Media Fitter-24"(610 mm) FILXXCAR0024 Use with FILCABXL-1024 EZ Flex Cabinet Side or Bottom Return 4"Filters— EZXCABCC0016 • • • • • • 16" EZ Flex Cabinet Side or Bottom Return 4"Filters— EZXCABCC0020 • • • 20" EZ Flex Cabinet Side or Bottom Return 4"Filters— FILCABXL0024 • • 24" •=Used with the model furnace 5 AIR DELIVERY - CFM (BOTTOM RETURN WITH FILTER) UNIT SIZE RETURN-AIR SPEED EXTERNAL STATIC PRESSURE(IN.W.C.)6 CONNECTION TAPS 2 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Black 1000 945 895 835 775 705 635 560 485 395 • 026-08 SIDE/BOTTOM Yellow 750 695 640 575 515 455 390 315 250 -7 Blue 675 620 560 500 440 380 310 245 -7 _7 Red 5 500 440 375 315 245 7 -7 -7 7 -7 Black 1100 1055 1010 960 905 850 795 740 685 620 SIDE OR Yellow 955 915 875 830 790 740 695 645 590 530 040-10 BOTTOM Blue 820 795 765 730 695 655 615 570 515 460 Red 730 710 680 655 625 595 555 515 465 400 Black 1245 1195 1150 1100 1050 1000 945 890 830 775 SIDE OR Yellow 1165 1120 1075 1030 980 925 870 815 760 710 040-12 BOTTOM Orange 1045 1015 965 925 885 840 790 740 695 640 Blue 1000 960 930 890 850 810 765 715 665 615 Red 735 725 700 680 650 625 590 555 515 470 Black 1340 1295 1245 1190 1130 1065 1005 895 815 725 SIDE OR Yellow 1035 1010 980 945 910 865 795 730 665 605 060-10 BOTTOM Blue 845 825 810 785 755 710 670 625 570 515 Red 5 770 750 730 710 675 640 600 560 510 455 U Black 1665 1615 1550 1485 1420 1345 1270 1190 1105 985 N Yellow 1340 1320 1295 1260 1215 1165 1110 1045 925 850 SIDE OR 060-14 Orange 1050 1045 1035 1015 995 960 915 845 785 725 BOTTOM Blue 985 980 975 950 930 900 845 795 740 690 Red 5 735 720 700 675 650 620 595 560 520 480 Black 1870 1810 1740 1670 1600 1525 1440 1355 1270 1180 SIDE OR Yellow 1525 1495 1460 1415 1365 1305 1240 1170 1090 990 080-16 BOTTOM Orange 1375 1355 1330 1300 1260 1210 1155 1090 1025 940 Blue 1045 1040 1030 1010 985 960 920 875 825 745 Red 5 880 865 850 835 810 785 750 715 665 605 Black 2360 2250 2160 2065 1970 1880 1785 1685 1580 1455 BOTTOM or Yellow 2100 2030 1960 1885 1805 1720 1635 1545 1440 1305 080-20 TWO-SIDES 3,4 Orange 1840 1810 1765 1725 1665 1590 1515 1430 1335 1240 Blue 1705 1685 1660 1615 1570 1510 1445 1370 1280 1135 Red 1425 1410 1385 1365 1335 1290 1245 1190 1120 1050 Black 1750 1705 1660 1605 1545 1475 1405 1305 1220 1140 SIDE OR Blue 1550 1510 1470 1430 1380 1320 1245 1170 1095 1015 100-14 BOTTOM Yellows 1290 1255 1220 1180 1130 1075 1020 960 885 800 Red 5 1085 1045 1010 960 915 865 805 740 665 595 Black 2415 2330 2245 2155 2065 1965 1865 1760 1645 1530 BOTTOM or Yellow 2130 2075 2010 1945 1865 1785 1695 1600 1490 1375 100-20 TWO-SIDES 3,4 Orange 1830 1815 1785 1740 1685 1625 1550 1470 1370 1255 Blue 1690 1680 1655 1620 1580 1530 1465 1385 1295 1185 Red 1415 1405 1390 1370 1345 1305 1260 1200 1125 1050 Black 2440 2360 2295 2215 2105 1975 1815 1710 1575 1405 BOTTOM or Blue 2300 2245 2185 2090 2005 1855 1745 1635 1505 1370 120-20 TWO-SIDES 3,4 Yellow 1805 1780 1750 1705 1650 1595 1515 1430 1330 1230 Oranges 1560 1550 1535 1505 1470 1420 1360 1285 1205 1130 Red 5 1390 1385 1370 1345 1320 1285 1230 1175 1105 1035 Black 2410 2325 2230 2135 2035 1930 1820 1700 1575 1445 BOTTOM or Blue 2250 2175 2100 2020 1930 1825 1715 1600 1485 1370 140-20 TW0-SIDES 3,4 Yellow5 1740 1725 1700 1660 1610 1550 1470 1390 1295 1190 Oranges 1500 1495 1485 1465 1435 1390 1335 1265 1185 1090 Red 5 1350 1345 1335 1315 1290 1255 1210 1150 1080 995 NOTE: 1. A filter is required for each return—air inlet. Airflow performance includes a 3/4—in.(19 mm)washable filter media such as contained in a factory—author- ized accessory filter rack. See accessory list. To determine airflow performance without this filter,assume an additional 0.1 in.w.c..available external static pressure. 2. Blower speed taps are not always in the same order. Factory default blower connections are as follows: a.Heating airflow—BLUE(also used for Continuous Fan) b.Cooling airflow—BLACK(enabled when the Y terminal is energized) ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION. 3. Airflows over 1800 CFM require bottom return,two—side return,or bottom and side return. A minimum filter size of 20"x 25"(508 x 635 mm)is required. 4. For upflow applications,air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return. 5. Highlighted areas indicate that this airflow range is below the range allowed for heating. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOL- ING. 6. All airflows that are shown in BOLD exceed 0.58 watts per CFM at the given external static pressure. 7. The"—"entry indicates an unstable operating condition. 6 MAXIMUM ALLOWABLE EXPOSED VENT LENGTHS IN UNCONDITIONED SPACE-FT. Unit Size 26,000*BTUH 0"Insulation 3/8"Insulation 1/2"Insulation Winter Pipe Dia. 1% 2 1% 2 1% 2 Design In. Temp 20 20 20 50 45 60 50 °F 0 5 5 25 20 30 25 -20 15 10 20 15 -40 10 5 15 10 40,000*BTUH 60,000 BTUH Unit Size Uninsulated 3/8-in.Insulation 1/2-in.Insulation Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 1% 2 2% 1'/* 2 2% 11/2 2 2% ' 1% 2 2% 3 1'/: 2 2% 3 1% 2 2% 3 Design in. Temp 20 20 20 20 20 50 45 20 60 50 20 30 30 25 20 75 65 60 20 85 75 65 °F 0 10 5 5 20 25 20 20 30 25 15 15 10 10 20 40 30 25 20 45 40 30 -20 5 20 15 10 20 20 15 10 5 20 25 20 15 20 30 25 20 -40 15 10 5 15 15 10 5 20 15 15 10 20 20 15 10 Unit Size 80,000 BTUH Uninsulated 3/8-in.Insulation 1/2-in.Insulation 4 Winter Pipe Dia. t17 1 /, 2 2/z 3 4 1 /: 2 2h 3 4 1%: 2 2/, 3 4 C.)Design in. to Temp 20 15 40 40 35 30 15 50 90 75 65 15 50 70 70 70 C) °F 0 15 20 15 10 5 15 50 45 35 30 15 50 50 40 35 -20 15 10 5 15 35 30 20 15 15 40 30 25 15 -40 10 5 15 25 20 15 5 15 30 25 20 10 Unit Size 100,000 BTUH Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 2 2% 3 4 2 2% 3 4 2 2% 3 4 Design in. Temp 20 20 50 40 35 20 80 95 80 20 80 105 90 °F 0 20 20 15 10 20 55 45 35 20 65 55 45 -20 15 10 5 20 35 30 20 20 45 35 25 -40 10 5 20 25 20 10 20 30 25 15 120,000 BTUH 140,000 BTUH Unit Size Uninsulated 3/8-in.Insulation 1/2-in.Insulation Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 2% 3 4 2% 3 4 2% 3 4 2% 3 4 2% 3 4 2% 3 4 Design in. Temp 20 10 50 40 10 75 95 10 75 105 5 55 50 5 65 105 5 65 125 °F 0 10 20 15 10 55 45 10 65 50 5 25 15 5 65 50 5 65 60 -20 10 10 10 35 25 10 45 30 5 10 5 5 45 30 5 50 40 -40 10 5 10 25 15 10 30 20 5 5 5 30 20 5 35 25 7 MAXIMUM ALLOWABLE EXPOSED VENT LENGTHS IN UNCONDITIONED SPACE- METERS Unit Size 26,000*BTUH 0"Insulation 3/8"Insulation 1/2"Insulation Winter Pipe Dia. 38 51 38 51 38 51 Design mm Temp -7 6.1 6.1 15.2 13.7 18.3 15.2 °C -18 1.5 1.5 7.6 6.1 9.1 7.6 -29 4.6 3.0 6.1 4.6 -40 3.0 1.5 4.6 3.0 Unit Size 40,000*BTUH 60,000 BTUH Uninsulated 3/8-in.Insulation 1/2-in.Insulation Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76 38 51 64 76 Design mm Temp -7 6.1 6.1 6.1 6.1 15.2 13.7 6.1 18.3 15.2 6.1 9.1 9.1 7.6 6.1 22.9 19.8 18.3 6.1 25.9 22.9 19.8 °C -18 3.0 1.5 1.5 6.1 7.6 6.1 6.1 9.1 7.6 4.6 4.6 3.0 3.0 6.1 12.2 9.1 7.6 6.1 13.7 12.2 9.1 -29 1.5 6.1 4.6 3.0 6.1 6.1 4.6 3.0 1.5 6.1 7.6 6.1 4.6 6.1 9.1 7.6 6.1 -40 4.6 3.0 1.5 4.6 4.6 3.0 1.5 6.1 4.6 4.6 3.0 6.1 6.1 4.6 3.0 Q 80,000 BTUH III Unit Size 0 Uninsulated 3/8-in.Insulation 1/2-in.Insulation CO Winter Pipe Dia. 38 51 64 76 102 38 51 64 76 102 38 51 64 76 102 ') Design mm Temp -7 4.6 12.2 12.2 10.7 9.1 4.6 15.2 27.4 22.9 19.8 4.6 15.2 21.3 21.3 21.3 °C -18 4.6 6.1 4.6 3.0 1.5 4.6 15.2 13.7 10.7 9.1 4.6 15.2 15.2 12.2 10.7 -29 4.6 3.0 1.5 , 4.6 10.7 9.1 6.1 4.6 4.6 12.2 9.1 7.6 4.6 -40 3.0 1.5 V 4.6 7.6 6.1 4.6 1.5 4.6 9.1 7.6 6.1 3.0 Unit Size 100,000 BTUH Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 51 64 76 102 51 64 76 102 51 64 76 102 Design mm Temp -7 6.1 15.2 12.2 10.7 6.1 24.4 28.9 24.4 6.1 24.4 32.0 27.4 °C -18 6.1 6.1 4.6 3.0 6.1 16.8 13.7 10.7 6.1 19.8 16.7 13.7 -29 4.6 3.0 1.5 6.1 10.7 9.1 6.1 6.1 13.7 10.7 7.6 -40 3.0 1.5 6.1 7.6 6.1 3.0 6.1 9.1 7.6 4.6 Unit Size 120,000 BTUH 140,000 BTUH Uninsulated 3/8-in.Insulation 1/2-in,insulation Uninsulated 3/8-in.Insulation 1/2-in.Insulation Winter Pipe Dia. 64 76 102 64 76 102 64 76 102 64 76 102 64 76 102 64 76 102 Design mm Temp -7 3.0 15.2 12.2 3.0 22.9 28.9 3.0 22.9 32.0 1.5 16.7 15.2 1.5 19.8 32.0 1.5 19.8 38.1 °C -18 3.0 6.1 4.6 3.0 16.8 13.7 3.0 19.8 15.2 1.5 7.6 4.6 1.5 19.8 15.2 1.5 19.8 18.3 -29 3.0 3.0 3.0 10.7 7.6 3.0 13.7 9.1 1.5 3.0 1.5 1.5 13.7 9.1 1.5 15.2 12.2 -40 3.0 1.5 3.0 7.6 4.6 3.0 9.1 6.1 1.5 1.5 1.5 9.1 6.1 1.5 35 7.6 8 • MAXIMUM EQUIVALENT VENT LENGTHS Table 1-Maximum Equivalent Vent Length -Ft. NOTE: Maximum Equivalent Vent Length(MEVL)includes standard and concentric vent termination and does NOT include elbows. Use Table 2-Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application. Unit Size 26,000 2 40,000 1 60,000 2 80,000 100,000 120,000 140,000 Pipe Dia. 1' 2 11/2 2 2' 11/2 2 21/2 3 1Y 2 21/2 3 4 2 21/2 3 4 21/2 3 4 21/2 3 4 (in) 0-2000 70 200 40 155 185 100 175 200 15 55 130 175 200 20 80 175 200 75 185 5 65 155 2001-3000 65 190 35 150 175 20 95 165 185 125 165 185 165 185 10 70 175 140 3001-4000 60 175 30 135 160 16 90 155 175 49 115 155 175 15 75 175 5 65 165 60 120 4001-4500 130 155 85 150 170 10 150 165 70 155 170 50 110 Altitude 55 160 25 44 110 160 4501-5000 125 145 15 80 145 165 145 160 150 165 60 45 100 (feet) 5001-6000 50 145 20 120 130 75 140 155 41 100 135 150 10 65 140 155 155 N/A 35 80 6001-7000 45 135 15 110 120 13 70 130 145 38 125 140 60 135 145 N/A 50 140 30 65 7001-8000 40 120 100 110 10 65 120 135 36 90 120 125 55 125 135 46 130 25 45 8001-9000 35 110 10 90 95 5 60 115 125 N/A 33 80 110 115 N/A 50 115 125 43 120 15 30 9001-1000 30 95 5 80 85 N/A 55 105 115 30 75 100 105 45 100 115 39 115 10 15 0 Maximum Equivalent Vent Length-Meters Unit Size 26,000 2 40,000 1 60,000 2 80,000 100,000 120,000 140,000 Pipe(m Dia. 38 51 38 51 64 38 51 64 76 38 51 64 76 102 51 64 76 102 64 76 102 64 76 102 Q 0-610 21.3 60.9 12.1 47.2 56.3 30.4 53.3 60.9 4.5 16.7 39.6 53.3 60.9 6.0 24.3 53.3 60.9 22.8 56.3 1.5 19.8 47.2 611-914 19.8 57.9 10.6 45.7 53.3 6.0 28.9 50.2 56.3 38.1 50.2 56.3 50.2 56.3 3'0 21.3 53.3 42.6 cn 14.9 4.5 22.8 18.2 915-1219 18.2 53.3 9.1 41.1 48.7 4.8 27.4 47.2 53.3 35.0 47.2 53.3 53.3 1.5 19.8 50.2 36.5 0) 1220-1370 39.6 47.2 25.9 45.7 51.8 3.0 45.7 50.2 21.3 47.2 51.8 15.2 33.5 U) Altitude 16.7 48.7 7.6 13.4 33.5 48.7 (meters) 1371-1524 38.1 44.1 4.5 24.3 44.1 50.2 44.1 48.7 3.0 19.8 45.7 50.2 18.2 13.7 30.4 1525-1829 15.2 44.1 6.0 36.5 39.6 22.8 42.6 47.2 12.4 30.4 41.1 45.7 42.6 47.2 47.2 NA 10.6 24.3 1830-2134 13.7 41.1 4.5 33.5 36.5 3.9 21.3 39.6 44.1 11.5 38.1 42.6 18.2 41.1 44.1 NA 15.2 42.6 9.1 19.8 2135-2438 12.1 36.5 30.4 33.5 3.0 19.8 36.5 41.1 10.9 27.4 36.5 38.1 16.7 38.1 41.1 14.0 39 6 7.6 13.7 NA 2439-2743 10.6 33.5 3.0 27.4 28.9 1.5 18.2 35.0 38.1 : 10.0 24.3 33.5 35.0 NA 15.2 35.0 38.1 13.1 36.5 4.5 9.1 2744-3048 9.1 28.9 1.5 24.3 25.9 NA 16.7 32.0 35.0 9.1 22.8 30.4 32.0 13.7 30.4 35.0 11.8 35.0 3.0 4.5 NOTES: 1. Inducer Outlet Restrictor disk(P/N 337683-401;1.25-in.(32 mm)Dia.)shipped in the loose parts bag or available through Replacement Components required under 10-ft.(3 M)TEVL in all orientations. Required for installations from 0-2000(0 to 610 M)above sea level. Failure to use an outlet restric- tor may result in flame disturbances or flame sense lock-out. 2. Inducer Outlet Restrictor disk(P/N 337683-401;1.25-in.(32 mm)Dia.) shipped in the loose parts bag or available through Replacement Components required for no greater than 5-ft.(1.5 M)TEVL in downflow and horizontal orientations only. Required for installations from 0-2000(0 to 610 M)above sea level. ELBOW CONFIGURATIONS VENTTERMINAL CONFIGURATIONS ge .... ..i_zs/___ D Concentric ri -(pa Long Medium Mitered /%T - \\ - I�/_ _ -10 Standard 2-in.,3-in.,or optional 4-in.termination. A13110 Table 2-Deductions from Maximum Equivalent Vent Length-Ft.(M) Pipe Diameter(in): 1-1/2 2 2-1/2 3 4 Mitered 90°Elbow 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) Medium Radius 90°Elbow 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5) Long Radius 90°Elbow 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) Mitered 45°Elbow 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) 4 (1.2) Medium Radius 45°Elbow 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) 2.5 (0.8) Long Radius 45°Elbow 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) 1.5 (0.5) Tee 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) 16 (4.9) NOTES: 1. Use only the smallest diameter pipe possible for venting. Over-sizing may cause flame disturbance or excessive vent terminal icing or freeze-up. 2. NA-Not allowed. Pressure switch will not close,or flame disturbance may result. 3. Vent sizing for Canadian installations over 4500 ft.(1370 M)above sea level are subject to acceptance by the local authorities having jurisdiction. 4. Size both the combustion air and vent pipe independently,then use the larger size for both pipes. 5. Assume the two 45°elbows equal one 90°elbow. Wide radius elbows are desirable and may be required in some cases. 6. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count. 7. The minimum pipe length is 5 ft.(2 M)linear feet(meters)for all applications. 8. Use 3-in.(76 mm)diameter vent termination kit for installations requiring 4-in.(102 mm)diameter pipe. 9 • Venting System Length Calculations The Total Equivalent Vent Length(TEVL)for EACH combustion air or vent pipe equals the length of the venting system,plus the equivalent length of elbows used in the venting system from Table 2. Standard vent terminations or factory accessory concentric vent terminations count for zero deduction. See vent system manufacturer's data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe. Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Table 1. Example 1 A direct-vent 60,000 BTUH furnace installed at 2100 ft.(640M).Venting system includes FOR EACH PIPE: 70 feet(22 M)of vent pipe,65 feet(20 M)of combustion air inlet pipe,(3)902 long-radius elbows,(2)45Q long-radius elbows,and a factory accessory concentric vent kit. Can this application use 2"(50 mm ND)PVC/ABS DWV vent piping? Measure the required linear length of air inlet and 70 ft. Use length of the longer of the vent vent pipe;insert the longest of the two here (22 M) or air inlet piping system Add equiv length of(3)90°long-radius elbows (use the highest number of elbows for either the 3 x (0 M) 7 M) From Table 2 9vent or inlet pipe) U Add equiv length of(2)45°long-radius elbows (use the highest number of elbows for either the 2 x cl) (0.5 M) = (p M) From Table 2 vent or inlet pipe) Add equiv length of factory concentric vent term 0 ft. From Table 2 Add correction for flexible vent pipe,if any 0 ft. From Vent Manufacturer's instructions;zero for PVC/ABS DWV Total Equivalent Vent Length(TEVL) (25 M) Add all of the above lines Maximum Equivalent Vent Length(MEVL) (9 M) For 2"pipe from Table 1 Is TEVL less than MEVL? YES Therefore,2"pipe MAY be used Example 2 A direct-vent 60,000 BTUH furnace installed at 2100 ft.(640M).Venting system includes FOR EACH PIPE: 100 feet(30 M)of vent pipe,95 feet(29 M)of combustion air inlet pipe,(3)90Q long-radius elbows,and a polypropylene concentric vent kit. Also includes 20 feet(6.1 M)of flexible polypropylene vent pipe,included within the 100 feet(30 M)of vent pipe. VERIFY FROM POLYPROPYLENE VENT MANUFACTURER'S INSTRUCTIONS for the multiplier correction for flexible vent pipe. Can this application use 60mm o.d.(2")polypropylene vent piping?If not,what size piping can be used? Measure the required linear length of RIGID air inlet and vent pipe;insert = 80 ft. Use length of the longer of the vent the longest of the two here:100 ft.Of rigid pipe—20 ft.Of flexible pipe (24 M) or air inlet piping system Add equiv length of (3)90°long-radius elbows (use the highest number of elbows for either the 3 x 5 ft. = 15 ft. vent or inlet pipe) (1.5 M) (4.6 M) Add equiv length of 45°long-radius elbows (use the highest number of elbows for either the 0 x = 0 ft Example from polypropylene vent vent or inlet pipe) (0 M) manufacturer's instructions,Verify from vent Add equiv length of factory concentric vent term 9 x 3.3 ft = 30 ft. manufacturer's instructions. (0.9 M) (9 M) Add correction for flexible vent pipe,if any 2* x 20 ft. = 36 ft. (6.1 M) (11 M) *VERIFY FROM VENT MANUFACTURER'S INSTRUCTIONS;For example only,assume 1 meter of flexible 60mm(2")or 80mm(3") polypropylene pipe equals 2.0 meters(6.5 ft.)of PVC/ABS pipe. Total Equivalent Vent Length(TEVL) (50 M) Add all of the above lines Maximum Equivalent Vent Length(MEVL) (29 M) For 2"pipe from Table 1 Is TEVL less than MEVL? NO Therefore,60mm(2")pipe may NOT be used;try 80mm(3") Maximum Equivalent Vent Length(MEVL) �575M� For 3"pipe from Table 1 Is TEVL less than MEVL? YES Therefore,80mm(3") pipe MAY be used 10 RETURN AIR TEMPERATURE This furnace is designed for continuous return—air minimum temperature of 60°F(15°C)db or intermittent operation down to 55°F(13°C) db such as when used with a night setback thermometer. Return—air temperature must not exceed 80°F(27°C)db. Failure to follow these return air limits may affect reliability of heat exchangers,motors and controls. SUPPLY AIR - I t MAX80°F /27°C -----0"- FRONT 32°F/0°C MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED RETURN - I f AIR MIN60°F /16°C Lo CD In A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0(0 mm) Front(Combustion air openings in furnace and in structure) I in.(25 mm) Required for service** 24 in.(610 mm)* All Sides of Supply Plenum** 1 in.(25 mm) Sides 0(0 mm) Vent 0(0 mm) Top of Furnace 1 in. (25 mm) *Recommended **Consult your local building codes COMBUSTION-AIR PIPE FOR NON-DIRECT (1-PIPE) VENT APPLICATION FIELD-SUPPLIED 2-IN. (51 mm) DIA. FIELD-SUPPLIED i"-* MITERED RADIUS 2-IN. (51 mm) DIA. PVC 90° ELBOW PVC PIPE al f 12" (300 mm) MINIMUM A12376 NOTE: See Installation Instructions for specific venting configurations. • 11 DOWNFLOW SUBBASE LOCATING TAB rt 1/4-IN.TYP - PLENUM II � OPENING r B / � i �` n LOCATING �D` y :- �� TAB a. i.- °%/mil FACTORY-SUPPLIED =� C FIELD-INSTALLED . INSULATION s.z° ,- ^° A97427 A88207 Assembled Disassembled Q DIMENSIONS(IN./MM) iC.) FURNACE FURNACE IN DOWNFLOW PLENUM OPENING* FLOOR OPENING HOLE NO.FOR rn CASING WIDTH APPLICATION A B C D WIDTH ADJUSTMENT In Furnace with or without Cased Coil 11-3/16 13-7/16 20-5/8 14-3/16(360) Assembly or Coil Box (322) 19( ) (341) (600) 4 Furnace with or without Cased Coil 15-1/8 16-3/4 20-5/8 17-1/2(445) Assembly or Coil Box (384) 19(4 ) (426) (600) 3 ) Furnace with or without Cased Coil 18-5/8 20-1/4 20-5/8 ( 21 533 Assembly or Coil Box (396) 19(` ) (514) (600) 2 24-1/2(622) Furnace with or without Cased Coil 22-1/8 19 O 23-3/4 20-5/8 1 Assembly or Coil Box (562) (603) (600) *The plenum should be constructed 1/4—in.(6 mm)smaller in width and depth than the plenum dimensions shown above. 1 Concentric Vent Kit Downflow Subbase A93086 A88202 A concentric vent kit allows vent and combustion—air pipes to One base fits all furnace sizes. The base is designed to be installed terminate through a single exit in a roof or side wall. One pipe between the furnace and a combustible floor when no coil box is runs inside the other allowing venting through the inner pipe and used or when a coil box other than a Carrier cased coil is used. It is combustion air to be drawn in through the outer pipe. CSA design certified for use with Carrier branded furnaces when installed in downflow applications. 12 MEDIA FILTER CABINET 25-5/8" (651 mm) 24-1/4" 23-5/8" I. (616mm) (600mm) Opening with Flanges Bent 23-3/8" 23-1/8" 4 IP- (594mm) (588mm) = O Opening I I I ' ; ' W II A o I , ' m , I I I J I I a I I ,I ' Furnace Side ' I Duct Side ' u I/ U I ' _( cn 0 — . 23-3/4" _ co (603mm) _ Centerline Screw Slots (146mm) Media Filter A B Cabinet 16"(406mm) 17" (432mm) 16" (406mm) 20"(508mm) 21"(533mm) 20" (508mm) 24"(610mm) 25"(635mm) 24" (610mm) NOTE: Media cabinet is matched to the bottom opening on furnace. May also be used for side return. A12428 TYPICAL WIRING SCHEMATIC ---- FIELD 24-V WIRING ---- FIELD 115-,208/230-,460-V WIRING FACTORY 24-V WIRING — FACTORY 115-V WIRING NOTE 2 THERMOSTAT FIVE WIRE Q Q Q Q Q TERMINALS FIELD-SUPPLIED THREE WIRE I DISCONNECT HEATING-ONLY + __ - - ___ 208/2 BLOWER DOOR SWITCH I -- --- 460-V 0-OR Nu ■1�J 460-V N :' THREE KV I i PHASE tl WH HT� C �-----f--� O 1 � N 1I -- 1■1 --- 208/230-V GND GND T I __ �� _=-1 SINGLE R 0- L fi I ♦I 1�1 I PHASE 115-V FIELD- AUXILIARY 0 __ 1 I ♦_ _ ___�__ _ SUPPLIED J-BOX L on I 1 r1 _GND DISCONNECT NOTE 1 ; 1 CONDENSING UNIT 24-V TWO TERMINAL WIRE BLOCK FURNACE NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation. 2. Some thermostats require a"C"terminal connection as shown. 3. If any of the original wire,as supplied,must be replaced,use same type or equivalent wire. A11387 13 59SC5A T C 0 0 01 01 0 0 0 0 0 0 Z 0 0 0 0 0 O O A X. 11 I I -, 1 I 1 I n N N N N O 111 615.116 NOTES: O O 0 D 0 W ? 0 N 0 Co N [IJ6.1] I23/10 N [98,41 1.Doors may vary by model. m 2.Minimum return air openings at furnace,based on metal duct.If flex duct is used, © . see flex duct manufacturer's recommendations for equivalent diameters. nail a.For 800 CFM-16-in.(406 mm)round or 141/2 x 12-in.(368 x 305 mm)rectangle. I © hTT b.For 1200 CFM-20-in.(508 mm)round or 141/2 x 19 1/2-in.(368 x 495 mm)rectangle. c.For 1600 CFM-22-in.(559 mm)round or 141/2 x 22 1/16-in.(368 x 560mm)rectangle. N y d.Return air above 1800 CFM at 0.5 in.w.c.ESP on 24.5"casing,requires one of the following p z 03 j configurations:2 sides,1 side and a bottom or bottom only.See Air Delivery table in this N W N ; n 6.21 AIR INTAKE j document for specific use to allow for sufficient airflow to the furnace. w Si w g 3.Vent and Combustion air pipes through blower compartment must _ 291/2 Co P. W O TOP VIEW 611/16 1170.11 use accessory''Vent Kit-Through the Cabinet".See accessory list for [74981 current part number. ,. 283/4 4.2611/16 1678.1] I73051 2611/16 4- 263/8 .4 [678.1] 1670.01 263/8 251/8 ..' 1669.9] IQ C 638.7 PO10 VI N N _ 235/16 � 21 �, I I 1 1 I 0 1592.91 15 7.416 \ G2 \ 1r� I21 1/1 tel CO CO OD Co N ^ 205/0 A 211/ib 1y, ,pp �I 1522.7) 153521 .Z CO N v CO �D " 20 518 y, = 148581� OUTLET WIDTH [522.]7 O 03 [76AIR INTAKE 1216 Cr AIRFLOW 013/4 [158] LLL� AIRFLOW 03 AIRFLOW t44.51 [76.21 S07/8 iA� GAS CONN AIR INTAKE !(jl 3/4 +. .{ t2221 ) © f[4451 0 N N O CONDENSATEON DRAIN TRAP p 21 /V'Y GAS CONN (��}}}���III VENT I dJ7/B CO A �_ �_ ;E II I101.6]- -.r^ A r 1 R21I E TAW W m �r� I7�631� (0222] w w -.1 1 N 2 * (22.2] 1 1 21/2 I I�Iyy [22.21 2 v2 1 I (63.57 Ly [6351 ,. 35 4 ,`yy �7/e 07/8 it 1.1 1889.01 1 I101A1 [2221 POWER CONN 283/16 325/e 1 {/i 7/8 R221 [715.91 [829.5] 1 I2227 POWER CONN D' 1 285/e 11J 2913/16 283/8 I --f- 1 rSIDE INLET 237/16 1726.41 [7511 [720A] SIDE INLET �7/8 �7� 201/4 [595.61 353/16 285/8 (222] Q221 169/16 131.91 [639.11 [726.91 [609.71 177/16 07/6 THERMOSTAT ENTRY [420.91 [442.3) 2215/16 122.21 N O W v V is 13/16 [3763 175/16 t581.91 201/4 169/16 THERMOSTAT ENTRY I CO I I [439.21 [513.9] I458.61 [420.9] A N A a W E O a> m _ _ 1 _ .4 A.8 r 1 I1 1rf I(BOTH SIDES) +1i C � 11/16 ��~ L. BOTTOM INLET I 125.41 11/ib 61/16 215/8 �1 22 SEE NOTE N3 [17.5] BOTTOM WRETURN 117.51 [154.01 [5493] 1658.311E0TH SIDES] 23 3/8 .. 21 I NOTE ALL DIMENSIONS IN INCH IMMI 15/16- (5920] [534.01 [3331 ' 265/16 .+ 4, 265/16 .... [66881 166881 SIR R. ''1 05024-4 1 E O m W W T p V W 62 2 WC WO in W W C p0 OCR� O (C7711 'O11 �`` g dV Obi ,Oif W O N O V 8 W g A N W W A O A i0 IV A ix, .- Co .4 • GUIDE SPECIFICATIONS General System Description Furnish a 4—way multipoise gas—fired Primary Heat Exchangers condensing furnace for use with natural gas or propane(factory— Primary heat exchangers shall be 3—Pass corrosion—resistant authorized conversion kit required for propane). aluminized steel of fold—and—crimp sectional design and applied Quality Assurance operating under negative pressure. Unit will be designed,tested and constructed to the current ANSI Z Secondary Heat Exchangers 21.47/CSA 2.3 design standard for gas—fired central furnaces. Secondary heat exchangers shall be of a stainless steel Unit will be third party certified by CSA to the current ANSI Z flow—through of fin—and—tube design and applied operating under 21.47/CSA 2.3 design standard for gas—fired central furnaces.Unit negative pressure. will carry the CSA Blue Star@ and Blue Flame@ labels. Unit Controls efficiency testing will be performed per the current DOE test Controls shall include a micro—processor—based integrated procedure as listed in the Federal Register. electronic control board with at least 16 service troubleshooting Unit will be certified for capacity and efficiency and listed in the codes displayed via diagnostic flashing LED light on the control,a latest AHRI Consumer's Directory of Certified Efficiency Ratings. self—test feature that checks all major functions of the furnace,and Unit will carry the current Federal Trade Commission Energy a replaceable automotive—type circuit protection fuse. Multiple Guide efficiency label. operational settings available including blower speeds for heating Q and cooling. Continuous fan speed is the same as the selected u, Delivery.Storage.and Handling heating speed. U to Unit will be shipped as single package only and is stored and Operating Characteristics ° handled per unit manufacturer's recommendations. Heating capacity shall be Btuh input; Warranty(for inclusion by specifying engineer) Btuh output capacity. U.S.and Canada only.Warranty certificate available upon request. Fuel Gas Efficiency shall be AFUE. Equipment Air delivery shall be cfm minimum at 0.50 in. Blower Wheel and PSC Blower Motor W.C.external static pressure. Galvanized blower wheel shall be centrifugal type,statically and Dimensions shall be: depth in. (mm); width dynamically balanced. Blower motor of PSC type shall be in. (mm);height in.(mm)(casing only). permanently lubricated with sleeve bearings, of hp, and Height shall be in. (mm) with NC coil and have multiple speeds from 500-1150 RPM operating only when in. (mm)overall with plenum. 115—VAC motor inputs are provided.Blower motor shall be direct Electrical Requirements drive and soft mounted to the blower housing to reduce vibration Electrical supply shall be 115 volts,60 Hz,single—phase(nominal). transmission. Minimum wire size shall be AWG;maximum fuse size Filters of HACR—type designated circuit breaker shall be Furnace shall have reusable—type filters.Filter shall be in. amps. (mm)X in.(mm). An accessory highly efficient Media Special Features Filter is available as an option. Media Filter. Refer to section of the product data identifying accessories and Casing descriptions for specific features and available enhancements. Casing shall be of.030 in.thickness minimum,pre—painted steel. Draft Inducer Motor Draft inducer motor shall be single—speed PSC design. 15 LO U U) to • Copyright 2018 Carrier Corp.• 7310 W.Morris St.• Indianapolis,IN 46231 Edition Date:1/18 Catalog No:59SC5A-11 PD Manufacturer reserves the right to change,at any time,specifications and designs without notice and without obligations. Replaces:59SC5A-10PD 16