Report 142.2.00 suJplciFre b / t2 '/g-0U .,-
_ •
What Ithe RE DN
T T-J-1
Drive-fhru is Wearing
?rc �-r 'pry � t, r � a z 04 a" ;k:4 � �� �
THE ACCESS AIR 100 12,
22 4111".
,.._
PASS-THRU AIR CURTAIN ` NOW NNW
SYSTEMTM
For use with any Flushmount Style Window
The Ready Access AA100 Pass-Thru Air Curtain
System is designed to be an integral part of your drive-
thru operation by protecting your workplace against 1
the entry of insects and exhaust fumes, while
increasing energy efficiency by reducing air
conditioning losses. Also satisfies health department
codes for fly fan applications
Features and Benefits
Satisfies health department requirements for"Fly Fan" Fully Assembled, Ready to Install
applications while it reduces and deflects the amount The Access Air 100 system is shipped completely pre-
of outside wind blowing into the building. This also assembled and ready for installation, lowering
reduces air-conditioning loss as well as reducing installation costs. Normal installation for new store
unwanted environmental factors such as dust and construction ordinarily takes less than two hours.
exhaust fumes from entering the building.Acts as a fly
fan to deter insects from entering the building during
warm weather conditions.
Warranty and Service Support
Unique Design Your Access Air 100 System comes with a one year
The AA100 installs directly into the frame work of the limited warranty on parts and labor. In addition, each
building providing a more pleasing appearance than Pass-Thru Air Curtain System is backed by a worldwide
outside mountable units. Its quiet operation helps service organization.
provide a pleasant work environment.
Quality Construction AVAILABLE OPTIONS
The exterior housing of the Ready Access air curtain Powder Coat painting is available upon request for a
system is manufactured using statuary bronze or"clear" wide range of custom colors.
anodized aluminum finish.
1815 Arthur Drive, West Chicago, Illinois 60185- Direct(630) 876-7766-Toll Free (800)621-5045-Fax(630)876-7767
E-mail: ready@ready-access.com-Web site: www.ready-access.com-Members: CSI, NRA, NAFEM, CFESA
ARRIVES READY FOR INSTALLATION
Your Ready Access window is shipped completely assembled and ready for installation. Comes with instructions.
Installation Details for the AA100 Pass-thru
Air Curtain System
III
ROUGH OPENING ,,,
43-3/4" II 11-3/4"(299mm)
(1111 mm) I;
`r r 2"(si mm)
mJIb1
(z1s m)`II6,lorr * % 77-3/4"(1975 mm)
:`� k...°104' ROUGHOPENING 1
;:IIID! 12"
I 36'(915
�; ` I/ (305 mm)
tii...t. .4.40:040...:
i/
110
/ v...:1.:.,'' '
22" 13"
(559 mm) (330 mm)
11-3/4"
-------\ 11111 [ (29"m)
I' Q NOMINAL 60"11524 mm1II
0 0
% A
REINSTALLED SMALLER
TRANSOM GLASS ^�
OUTSIDE VIEW
KNOCK-OUT FOR
ELECTRICAL ENTRY
UNIT SPECIFICATIONS:
• 104/120 Volts I
• 3 Actual Unit Amps
• 60 Hz
• 600 FPM Air Velocity
R/L Window Shown INSIDE VIEW
Window must be installed square and plumb.
RE IMN Installation illustrations are for reference only. Construction
CCESSand local codes will determine proper installation of window.
Contact Ready Access for more information on installation.
O
1815 Arthur Drive, West Chicago, Illinois 60185-Direct (630) 876-7766 -Toll Free (800)621-5045- Fax(630) 876-7767 a
E-mail: ready@ready-access.com -Web site: ww .ready-access.com -Members: CSI, NRA, NAFEM, CFESA N
w
N
N
0
3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Job Information
Job01
TRANS'
Tag Y4C-1
Quantity 1 Model number YHC092F3
Unit Information
Tonnage 7.5 Ton Dual compressor Unit function DX cooling,gas heat
Min.unit operating weight 1026.0 lb Max.unit operating weight 1291.0 lb
Design Airflow 3000 cfm Elevation 1500.00 ft
Cooling Information
Gross Total Capacity 91.06 MBh Gross Sensible Capacity 64.76 MBh
Gross Latent Capacity 26.30 MBh Net Total Capacity 87.29 MBh
Net Sensible Capacity 60.99 MBh Net Sensible Heat Ratio 0.70 Number
Cooling Entering DB 80.00 F Cooling Entering WB 67.00 F
Cooling Leaving Unit DB 60.55 F Cooling Leaving Unit WB 57.81 F
Ambient Temp 95.00 F
Heating Information
Heating capacity Low gas heat 3ph Input Heating Capacity 120.00 MBh
Output Heating Capacity 96.00 MBh Heating EAT 70.00 F
Heating LAT 99.90 F Heating Delta T 29.90 F
Motor/Electrical Information
Voltage 208-230/60/3 Design ESP 1.100 in H2O
Indoor Motor Power 0.97 kW Component SP 0.140 in H2O
Indoor RPM 1265 rpm Indoor mtr operating power 1.30 bhp
Compressor Power 6.12 kW Outdoor Motor Power 0.71 kW
MCA 41.90 A System Power 7.80 kW
Compressor 1 RLA 10.00 A MOP 50.00 A
Condenser fan FLA 0.00 A Evaporator fan FLA 0.00 A
Total Static Pressure 1.240 in H2O
Acoustics
Sound Power Level.-Lw" 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 dHz 4 kHz 8 kHz
Ducted Discharge Heating 92 dB 90 dB 94 dB 86 dB 84 dB 83 dB 82 dB 75 dB
Ducted Inlet Heating 80 dB 80 dB 76 dB 67 dB 57 dB 57 dB 57 dB 48 dB
Outdoor Noise Heating 90 dB 86 dB 90 dB 85 dB 80 dB 77 dB 74 dB 66 dB
Notes:
Ducted Inlet and Ducted Discharge Sound Power Levels are in accordance with AHRI 260.
Outdoor Sound Power Levels are in accordance with AHRI 270.
Electrical values provided are estimated only and are subject to change without notice and may differ from nameplate values.
Field installed low or high static drive kits may be needed. Please check the fan performance tables in the product catalog for application ranges.
3/28/2019 Product Version 2002.09.04.1
Page 1 of 2
3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
Job Information
Job01
TRANS"
Tag Y4C-1
Quantity 1 Model number YHC092F3
Information for LEED Projects
ASHRAE 90.1 Yes SEER/IEER 15.00
Refrig charge(HFC-410A)-ckt 1 5.5 lb Compressor Power 6.12 kW
Refrig charge(HFC-410A)-ckt 2 4.2 lb Outdoor Motor Power 0.71 kW
Rated capacity(AHRI) 89.00 MBh Indoor mtr operating power 1.30 bhp
EER @ AHRI Conditions 12.6 EER Exhaust fan power 0.65 kW
Note: This product meets the minimum equipment efficiency requirements of ASHRAE Standard 90.1-2007 and-2010(which are based on
AHRI standard rating conditions)and,therefore,also meets the LEED'Minimum Energy Performance"prerequisite in the Energy
and Atmosphere section.The power data listed above is at actual user-entered conditions.Refer to the product catalog for
performance at AHRI standard rating conditions.
The LEED Green Building Rating SystemTM,developed by the U.S.Green Building Council,provides independent,third-party verification that a building project
meets green building and performance measures.
Electrical values provided are estimated only and are subject to change without notice and may differ from nameplate values.
Field installed low or high static drive kits may be needed. Please check the fan performance tables in the product catalog for application ranges.
3/28/2019 Product Version 2002.09.04.1