MARTIN BUILDING HVAC
PORTLAND, OR
STRUCTURAL.. CALCULATIONS
MECHANICAL UNIT SUPPORT AND ATTACHMENT: MA1-MA5
SKETCHES: SK1-SK3
RECE1 fF
JAN 13 20210
CITY of k:Afil3
c
0.,:truR.it BUILDING 1:,141I.Ri :
, ,O.Vh O/� r { (9 PAGES TOTAL INCLUDING COVER SHEET
ires. , 63 E ,....
SON
December 20 2019
IS D. GN R i
(Ev rS�",I zi PROJECT NUMBER: 190406.01
V,'.4.:.:0
4
0 WI.;x
ARCHITECTURE
MN
ENGINEERING
UPLANNING
INTERIORS
LANDSCAPE -
15895 SW 72ND AVE
SUITE 200
PORTLAND,OR 97224
PHONE:503.226.1285
FAX:503.226.1670
INFO a CIDAENC.COM
WWW.CIDAENC.COM
U.S. Seismic Design Maps Page 1 of 3
Pi t4-I
AN OSHPD
Martin Bldg
9430 SW Coral St, Portland, OR 97223, USA
Latitude, Longitude: 45.4475898, -122.77428959999997
Crescent Grove
Cemeter & Mausoleum
Red Robin Gourmet
c0 a SW Coral St SW word St
Burgers and Brews yy pp
4 !�
Double-Tree #.71r 7 lil(C3 1 's
c t _t.i.i Tigard Baker& [?er Allerl gAsthma v
y
SW Locust St9SWLocust St
Panera Bread
Bridgetivell Resources
'O` gie • Map data 02019
Date 12/19/2019,3:50:35 PM
Design Code Reference Document ASCE7-16
Risk Category II
Site Class D-Stiff Soil
Type Value Description
Ss 0.866 MCER ground motion.(for 0.2 second period)
S1 0.397 MCER ground motion.(for 1.0s period)
SMS 0.999 Site-modified spectral acceleration value
SMI null-See Section 11.4.8 Site-modified spectral acceleration value
Sos 0.666 Numeric seismic design value at 0.2 second SA
Sol null-See Section 11.4.8 Numeric seismic design value at 1.0 second SA
Type Value Description
SDC null-See Section 11.4.8 Seismic design category
Fa 1.154 Site amplification factor at 0.2 second
F„ null-See Section 11.4.8 Site amplification factor at 1.0 second
PGA 0.394 MCEG peak ground acceleration
FPGA 1.206 Site amplification factor at PGA
PGAM 0.475 Site modified peak ground acceleration
TL 16 Long-period transition period in seconds
SsRT 0.866 Probabilistic risk-targeted ground motion.(0.2 second)
SsUH 0.977 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration
SsD 1.5 Factored deterministic acceleration value.(0.2 second)
S1RT 0.397 Probabilistic risk-targeted ground motion.(1.0 second)
S1 UH 0.458 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration.
S1D 0.6 Factored deterministic acceleration value.(1.0 second)
PGAd 0.5 Factored deterministic acceleration value.(Peak Ground Acceleration)
httneq/ceicmicmanc.nra/ 17/19/2(11 A
MA2
CIDA Martin Bldg CDG
TEL: (503)226-1285 RTU 12/19/2019
FAX: (503)226 1670 190406.01
MECHANICAL UNIT ATTACHMENT-LATERAL FORCES RTU
ROOFTOP UNIT ON C URB
New 40ton unit to replace(e)30 ton unit with same cabinet dimensions on existing curb
• W exist=46001b W new=6290Ib
Wp:= 62901b Weight of unit We:= 2501b Weight of(E)curb Wt:= Wp+ We Wt=6540 lb
L:= 255in Length of unit Lc:= 234in Length of Curb
wm:= 92in Width of unit we:= 86in Width of curb
hm:= 68•in Height of unit
he:= 14•in Height of curb
hmc:= hm + he hmc= 82 in Total height of unit on curb
SEISMIC PARTS AND PORTIONS (Portland, OR)
Mapped SS:= 0.866 site class=D
Adjusted Maximum Sms:= 0.999
Design SDs:= 0.666
h:= 30ft Ip:= 1.0 ap:= 2.5 Rp:= 6.0 z:= h Air side HVAC component
0.4•ap Sips Ip / z
FPunit 1 + 2.—}WP F 2094.5716 0.7 F 1466.216
RP \ Punit= Punit=
0.4.ap•SDS•Ip zl
FPcurb R • I + 2• .kWp+ Vs/c) FPcurb=2177.82 lb 0.7•FPcurb= 1524.47 lb
P
\ J
WIND LOAD: BASED ON 2018 IBC/2019 OSSC
Vas:= 98 Exposure B
Kd:= 0.85 Kh:= 0.7 Kzt:= 1.0 GC,:= 1.9 GCr vert:= 1.5
9z:= 0.00256•Kh•Kn•Ktd•V3s2•psf
F:= GCS qZ F= 27.79 psf
'wind unit F•L hm 'wind unit=3346.95 lb
'wind_curb F•L•(hm + hc) 1wind_curb=4036.03 lb
G:\adcadd\19\00000-2019 Mechanical
Units\0406.01 Martin Building HVAC
\IateraIMECH RTU curb(ASD-
WOOD).mcd
CIDA Martin Bldg CDG
TEL: (503)226-1285 RTU 12/19/2019
FAX: (503)226 1670 190406.01
WIND LOAD: BASED ON 2018 IBC/ASCE7-16-VERTICAL
Fvert Qi GCr vert Fvert =21.94 psf
Pwind unit vert Fvert•L'wm Pwind unit vert= 3574.92 lb
•
Fvert_unit 0.6Wp—0.6Pwind_unit_vert Fvertunit= 1629.05 lb <0,Net Uplift
Pvert_curb:= 0.6(Wp+ Wc) —0.6Pwind_unit_vert Fvertcurb= 1779.05 lb <0, Net Uplift
OVERTURNING-UNIT TO CURB
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturninq at unit to curb SEISMIC-Overturning at unit to curb
/hm\
Mot_,wind_unit Pwind_unit'h2 Mot_seismic_unit= Fpunit'\2/
Mofwindunit—9483.03 lb ft Mot seismic unit= 5934.61 Ib ft
—
0.6Mot_wind_unit) Pvert_unit (0.7•Mot_seismicunit) (0.6 •-0.7.0.2•Sim)•Wp
Fup_wind_unit = W — 2 Fup_seismic_unit w — 2
c c
Fup_wind__unit =—20.6 lb Fup_seismic_unit=—1014.1 lb
0.6•Pwind unit=2008.17 lb 0.7•Fpunit= 1466.2 lb
WIND GOVERNS UNIT TO CURB CONNECTION
ATTACHMENT
Design attachment for 2009 lb sliding and 0 lb tension at unit to curb connection-18GAcurb
0.6•Pwind_unit=2008.17 lb Fup_wind_unit =—20.6 lb
Try 16GAx5'CLIPS WITH(4)#10 SCREWS TO UNITAND(4)#10 SCREWS TO CURB
VCLIP 471 lb Per dip
0.6•Pwind unit
Ushear
6 VCLIP Ushear= 0.711
Use(3) 16GAx6"clip per side with(4)#10 SMS to unit,and(4)#10 SMS to curb—(12)clips total
G:\adcadd\19\00000-2019 Mechanical
Units\0406.01 Martin Building HVAC
\lateraIMECH RTU curb(ASD-
WOOD).mcd
CIDA Martin Bldg CDG
TEL: (503)226-1285 RTU 12/20/2019
FAX: (503)226 1670 190406.01
OVERTURNING-CURB TO ROOF
LC#7 0.6D+0.6W LC#8 0.6D+0.7E
WIND-Overturning at curb to roof SEISMIC-Overturning at curb to roof
halt (halt
Mot_wind curb:= Pwind curb'— Mat_seismic c:= FPcurb'
2 — 2
Mot_wind_curb= 13789.76 lb ft Mot seismic c=7440.88 lb ft
(0.6Mot_wind_curb) Pvert curb (0.7'Mot_seismicc) (0.6—0.7.0.2SDS)'(W)
Fup_wind_curb = — 2 Fup,seismic_c:=
W w 2
c c
Fup_wind_curb= 264.97 lb Fup_seismic_c = -930.32 lb
0.6•Pwindcurb -— 2421.62 lb 0.7'FPcurb= 1524.47 lb
WIND GOVERNS CURB TO ROOF
ATTACHMENT
Design attachment for 2422 lb sliding and 265 lb uplift at curb to roof connection
0.6 Pwind_curb = 2421.62 lb Fup_wind_curb =264.97 lb
Try#10x2.5"WOOD SCREWS EACH SIDE-Long side to Coke tension,short sides b take shear
'screw= 2.5in length of screw
5.
LP:= 'screw— $to Lp= 1.88 in
screw length-Sheathing-tapered tip , 2
d thread length
thread:= screw'3
dscrew:= 0.I9in Screw diameter
Lp Wthread:= 135•—lb withdrawal capacity per inch
C := C =0.99 to
p
10-dscrew p
Cp:= if(Cp> 1.0,1.0,Cp) Cp=0.99
Vallow= 1.6.901b•Cp Vallow= 142.11 lb
Tallow:= 1.6•dthread'Wthread Tallow= 360 lb
0.6•Pwind_curb
USHEAR:= USHEAR=0.947
18 V
allow
Fup_wind_curb
UUPLIFT:= UUPLIFT=0.08
• 9•Tallow Use(9)#10 Screws each side
G:\adcadd119100000-2019 Mechanical
Units10406.01 Martin Building HVAC
\IateralMECH RTU curb(ASD-
WOOD).mcd
15895 SW 72ND AVENUE,SUITE 200
Q PORTLAND,OREGON 97224
TEL:503.226.1285 FAX:503.226.1670
0 E-MAIL:info@cidainc.com J
PROSECT NAME: PEOI.No. St+EE''
TITLE:- BY: DATE: -
FT 7--- 7 T^ ( 1 AwfV� if/
p$50 ( Pg .
E 7, _ _
i /le ' 1 , _ , ;
C 4' r , Tete- !
4
i, 1
jj
is
•
,- 3 t
.
`l
L
n
_. _w.w__ . . p
ta/k,,,, 6290 a t-150/- )4, 7 '� 17 .2" Pg;
I4/4i,. --... . _..2 SPsr' 7, 6 0- / pr/Z/fi.T
s / L. //i
b S T1---
V.- (2,2-//2,/ /3 Z 3 /1/"-)
h---- ., 3`/ /1.// 1 t/''7 1 /'2,e! 35a
/1i /// f 7)3c7; i'fiZZ 7 M ®,k
S rimed.. TSL /
-50 )/Oii/3 4 Za 4,0400
z L. & d
1,,/%., (20Z4 i//Zz3 ppf�
m z , 9L /.//( ; 55) i sL /z) i/2 ZS At 4 ti 414
Oait'
IVED
Johnson
Controls JAN 13 2020
ARD
JOHNSON CONTROLS PORTLAND
MEDFORD OR CB -ON58
4011 SE INTERNATIONAL WAY STE 605
• Proposal MILWAUKIE OR 97222-8826
PH: (866) 635 1302
FAX: (503) 654 1158
TO: AMERICAN HEATING Date: 10/23/2019
5025 SE 24TH AVE
Quote Ref: 1-15FXOLU1
PORTLAND, OR 97202-4765 Project Name: THE MARTIN BUILDING
Site: AMERICAN HEATING
5035 SE 24TH AVE
PORTLAND, OR 97202-4765
ATTN: Ryan Haggerty
We propose to furnish the materials and/or perform the work below for the net price of:
For the above price this proposal includes:
Proposal to provide equipment replacement only Z4N524ABE5A4BBCDA1.York Millennium, 40 Ton, Four Stage
Cooling, Single Package R-410A Air Conditioner, 10.7 EER, Natural Gas - 533 MBH Input- Aluminized Steel, 460-
3-60
• Major Components Have Hinged and Latched Access Doors
•VAV(Factory Installed VFD)
• Economizer, Low Leak Seals with Single Enthalpy Sensor with Economizer Fault Detection & Diagnostic (Meets
ASHRAE 90.1-2013, IECC 2015, California Title 24, AMCA 511)
• Factory Installed Power Exhaust with Modulating Damper Blades (0 to 100% Exhaust)
• 10 HP Hi-Efficiency Exhaust Motor
• Forward Curve Blades - Class II Blower
• Bottom Return, Bottom Supply Configuration
•25 HP High Efficiency Indoor Blower Motor(Not Available on 25 Ton)
•2" Deflection Springs Under Supply Air Blower& Motor
•2" Pleated Filters (Mery 8)
•Smart Equipment Controller including Discharge Air, Return Air, and Outdoor Air Temperature Sensors.
BACNet MS/TP, Modbus and N2 Communication Card.
• Copper Tube/Aluminum Fin Condenser Coil
•Copper Tube/Aluminum Fin Evaporator Coil
•Stainless Steel Drain Pan
• Head Pressure Control & Hot Gas Bypass
No Labor, start up or Install included. YORK 40 Ton, Four Stage Cooling, Single Package R-410A Air
Conditioner. No Curb adapter required per customer.
This proposal DOES NOT include:
1. Labor or material not specifically described above is excluded from this proposal.
2. Unless otherwise stated, any and all overtime labor is excluded from this proposal.
3. Applicable taxes or special freight charges are excluded from this proposal.
Important: This proposal incorporates by reference the Terms and Conditions attached
This proposal is hereby accepted and
Johnson Controls is authorized to proceed This proposal is valid through: 02-02-2020
with the work, subject to credit approval by
Johnson Controls, Inc. Milwaukee, WI.
Page I1
Johnson 14*#
Controls
SUBMITTAL DATA
Order#: Date: 08/27/2019
Project: Martin Building
Project #: CSL08261901
Submitter: Chris LaDue
NorthWest Branch Region(UST/IPA)
3985 70th Ave East,
Fife, Washington 98424
2533444639
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Date
08/27/2019 Opi
Project NameJohnson
Martin Building Controls
Project Number
CSL08261901
Client/Purchaser
Submittal Summary Page
Qty Tag # Model # Description
1 Z4N524ABE5A4BBCDA1 York Millennium, 40 Ton, Four Stage Cooling, Single Package R-
410A Air Conditioner, 10.7 EER, Natural Gas- 533 MBH Input-
Aluminized Steel, 460-3-60
• Major Components Have Hinged and Latched Access Doors
•VAV (Factory Installed VFD)
• Economizer, Low Leak Seals with Single Enthalpy Sensor with
Economizer Fault Detection & Diagnostic (Meets ASHRAE 90.1-
2013, IECC 2015, California Title 24, AMCA 511)
• Factory Installed Power Exhaust with Modulating Damper Blades
(0 to 100% Exhaust)
• 10 HP Hi-Efficiency Exhaust Motor
• Forward Curve Blades - Class II Blower
• Bottom Return, Bottom Supply Configuration
• 25 HP High Efficiency Indoor Blower Motor(Not Available on 25
Ton)
• 2" Deflection Springs Under Supply Air Blower& Motor
• 2" Pleated Filters (Mery 8)
• Smart Equipment Controller including Discharge Air, Return Air,
and Outdoor Air Temperature Sensors. BACNet MS/TP, Modbus and
N2 Communication Card.
• Copper Tube/Aluminum Fin Condenser Coil
• Copper Tube/Aluminum Fin Evaporator Coil
• Stainless Steel Drain Pan
• Head Pressure Control & Hot Gas Bypass
Equipment start-up and commissioning by a factory trained technician is recommended.
Contact your supplying distributor or sales representative for additional information & guidance.
WARNING:Cancer and Reproductive Harm-www.P65Warnings.ca.gov
�.....•...• Information is subject to change without notice.Check local codes. Printed 08/27/2019
, aii ® Millennium 25-40 Ton Page:3
YORK Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#: Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Cooling Performance 1
Total gross capacity 507.9 MBH
Sensible gross capacity 376.3 MBH
Total net capacity 469.8 MBH ,,;,, -• r_
• Sensible net capacity 338.2 MBH
Efficiency(at ARI) 10.70 EER
Integrated eff.(at ARI) 13.60 !EER 4r � • �` •
Ambient DB temp. 86.1 °F
Entering DB temp. 80.0 °F °
Entering WB temp. 67.0 °F le- ' ° v F
Leaving DB temp. 58.2 °F '
Leaving WB temp. 56.9 °F r ,-r; �,"N
Power input(w/o blower) 39.26 kW i
Sound power 88 dB(A)
Refrigerant
Refrigerant type R-410A
Sys1 21 lbs
Sys2 18 lbs 8 oz
Sys3 18 lbs 8 oz 40 Ton
Sys4 20 lbs • Introducing the Millennium 40 ton rooftop line-units designed to provide
Gas Heating Performance peak performance and value both today and for years to come.Millennium
units are manufactured at an ISO 9001 registered facility and each rooftop is
Entering DB temp. 60 °F completely computer-run tested prior to shipment.
Heating output capacity(Max) 426 MBH
Supply air 16000 CFM Unit Features
Heating input capacity(Max) 533 MBH • Four Stage Cooling
Leaving DB temp. 84.7 °F • Natural Gas-533 MBH Input-Aluminized Steel
SSSSE 80.0 temp. rise 24.7 % • Major components have hinged and latched access doors
Stages 2 • Sloped unit roof with drip lip
Supply Air Blower Performance • Double Wall Cabinet Construction Provides Superior Cleanability and
Supply air 16000 CFM Structural Integrity
Ext.static pressure 0.6 IWG • Unit Cabinet Constructed of Powder Painted Steel,Certified at 750 Hours
Addl. Unit Losses(Options/Accessories) 1.24 IWG Salt Spray Test(ASTM B-117 Standards)
Blower speed 728 RPM • VAV(Factory Installed VFD)
Motor rating 25.00 HP • Industrial Duty Scroll Compressors Each Has An!dependent Refrigeration
Actual required BHP 13.74 HP Circuit
Power input 11.18 kW
3
_ Elevation 30 ft. • Standard Mechanical Cooling from 40`F to 125*F
Drive type BELT • Economizer,Low Leak Seals with Single Enthalpy Sensor with Economizer
Electrical Data Fault Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,
Power supply 460-3-60 California Title 24,AMCA 511)
• Unit min circuit ampacity 127 Amps • Factory Installed Power Exhaust with Modulating Damper Blades(0 to 100%
Unit min over-current protection 150 Amps Exhaust)
Unit max over-current protection 150 Amps • 10 HP Hi-Efficiency Exhaust Motor
Dimensions&Weight • Forward Curve Blades-Class II Blower
Hgt 64 in. Len 276 in. Wth 92 in. • 25 HP High Efficiency Indoor Blower Motor
Weight with factory installed options 6290 lbs. • Bottom Return,Bottom Supply Configuration
Clearances • 2"Deflection Springs Under Supply Air Blower&Motor
Right 60 in. Front 60 in. Rear 60 in. •
2"Pleated Filters(Mery 8)
Top 120 in. Bottom 0 in. Left 60 in. J • Replacement Filters:4-(16"x 25")AND 6-(20"x 25")
•
Note: Please refer to the tech guide for listed maximum static pressures Short Circuit Current:5kA RMS Symmetrical
• Single Point Power Connection
� AMERICAN ^ r ' j ^\ • Copper Tube/Aluminum Fin Condenser Coil
ii. CERTIREEL OU5LrTY �us (E) ) • Angled Condenser Coils Protect from Hail,Shipping,and Handling Damage
toic �✓ • Copper Tube/Aluminum Fin Evaporator Coil
• Intertwined Evaporator Coils Provide Larger Heat Transfer at Part Load
• Through-the-Curb and Through-The-Base Utility Connections
• Sloped Stainless Steel Drain Pan
• Head Pressure Control&Hot Gas Bypass
• High and Low Refrigerant Pressure Protection
Standard Unit Controller: Smart Equipment Control Board
• Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Air Temperature Sensors. BACNet MS/TP, Modbus and N2 Communication
Card.
Warranty
• One(1)Year Limited Parts-Only Warranty on the Complete Units
• One(1)Year Warranty on Compressors and Electric Heater Elements
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Millennium 25-40 Ton Page:4
YORK® Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#: Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Factory Installed Options
Z4N524ABE5A4BBCDA1
•
Equipment Options Option(s) Selected
: . ork ri it
a
gas s t s s
40 Ton
Basic Unit: 4 Four Stage Cooling
10.7 EER
Air Volume: 2 VAV(Factory Installed VFD)
Configuration: A Bottom Return, Bottom Supply Configuration
Major . Access
Doors
� '.3 Stainless Steel
Forward Curve Blades-Class II Blower
ID Blower: E 2" Deflection Springs Under Supply Air Blower& Motor
ID Motor 25 HP High Efficiency Indoor Blower Mot,
s Available on.25 Ton). `-
Copper Tube/Aluminum Fin Condenser Coil
Coils: A
Copper Tube/Aluminum Fin Evaporator Coil
fri
R$ �erattoneSSControl
4 Head Pressure &Hot Gas Bypass
Filters: B 2" Pleated Filters(Mery 8)
Economizer,Low Leak Seals with Single Enthalpy's
�' Sensor with Economizer Fault Detection&Diagno
ornizer:otins
poB
(Meets ASHRAE 90.1-2013, IECC 2015,California a '
24 AMCA 511)
Factory Installed Power Exhaust with Modulating
Exhaust: C
Damper Blades(0 to 100% Exhaust)
ErMilit Motor: D 10 HP i= ci
x h a
Smart Equipment Controller including Discharge Air,
Return Air, and Outdoor Air Temperature Sensors.
Controls: A •
BACNet MS/TP, Modbus and N2 Communication Card.
Generation
Field Installed Accessories
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Millennium 25-40 Ton Page:5
`' YORK® Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#: Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
O 1BD0407 - Burglar Bars Kit- 0 S1-03102529004 - Non- 0 S1-NSB8BHN241-0 -Wall
Includes supply and return air Networking Wall Sensor with Temperature and 3% Relative
opening anti-intrusion screens. For Over-ride button —Allows remote Humidity Combined Sensor, Full
Bottom Supply/Bottom Return duct sensing and control from single or Display, WHITE, NO JCI LOGO,
opening configurations only. (84.0 multiple zones. Override allows NS8000 Series (0.4 lbs)
" lbs) setpoint to be overridden for 2 0 S1-NSB8BHN243-0-Wall
O 1 HA0421 - High Altitude Kit for hour time period. (0.2 lbs) Temperature and 3% Relative
Natural Gas- Contains orifices 0 S1-03102529006 - Non- Humidity Combined Sensor, Full
required for applications between Networking Wall Sensor with Display, BLACK, NO JCI LOGO,
2,000 and 6,000 ft. (1.5 lbs) Setpoint Adjustment and Over-ride NS8000 Series (0.4 lbs)
O 1NP0438 - Natural Gas To Button—Allows remote sensing 0 S1-NSB8BPN240-0 -Wall
Propane Conversion Kit and control from single or multiple Temperature and 2% Relative
O 1 RC0455P - Roof Curb- 14" High, zones. Allows setpoint to be Humidity Combined Sensor, Full
Flat, Uninsulated, Partial adjusted ± 5° F. Override allows Display, WHITE, JCI LOGO,
Perimeter(Shipped Knocked setpoint to be overridden for 2 NS8000 Series (0.4 lbs)
Down)- Condenser Section hour time period. (0.2 lbs) 0 S1-NSB8BPN241-0 -Wall
Supported by a Separate Channel 0 S1-03103519000 - CO2 sensor, Temperature and 2% Relative
(included) (385.0 lbs) 120mm x 80mm, no display, screw Humidity Combined Sensor, Full
O 2AQ04700324B -Space CO2 terminals or modular jack, no logo Display, WHITE, NO JCI LOGO,
Sensor(To maintain CO2 levels in (0.2 lbs) NS8000 Series (0.4 lbs)
a conditioned space.) (2.0 lbs) 0 S1-MP-PRTKIT-OP - MAP 0 S1-NSB8BPN243-0 -Wall
O 2EC0401 - Kit, Single Enthalpy (Multiple Access Portal)Gateway Temperature and 2% Relative
Field Installed (1.0 lbs) Kit- Replacement MAP gateway Humidity Combined Sensor, Full
O 2EC0402 - Kit, Dual Enthalpy protective case, lanyard and Display, BLACK, NO JCI LOGO,
Field Installed (Includes two communication cable. Use only to NS8000 Series (0.4 lbs)
humidity sensors) (1.0 lbs) replace worn or damaged 0 S1-NSB8BTN041-0 -Wall
O 2ET077001124 - Honeywell components. (0.3 lbs) Temperature Sensor, No Display,
T7350, 2 Heat/4 Cool, Auto/Man 0 S1-NSB8BHN041-0 -Wall WHITE, NO JCI LOGO, NS8000
Changeover, Electronic 7 Day Temperature and 3% Relative Series (0.4 lbs)
Programmable (2.0 lbs) Humidity Combined Sensor, No 0 S1-NSB8BTN043-0 -Wall
O 2PM04700124- Phase Monitor Kit Display, WHITE, NO JCI LOGO, Temperature Sensor, No Display,
- Includes Control and associated NS8000 Series (0.4 lbs) BLACK, NO JCI LOGO, NS8000
wiring. This accessory provides 0 S1-NSB8BHN043-0 -Wall Series (0.4 lbs)
protection against phase reversal, Temperature and 3% Relative 0 S1-NSB8BTN141-0 -Wall
loss or unbalance. (13.0 lbs) Humidity Combined Sensor, No Temperature Sensor,
O ASC Services -Charges for this Display, BLACK, NO JCI LOGO, Warmer/Cooler Display, WHITE,
Service are Applicable. NS8000 Series (0.4 lbs) NO JCI LOGO, NS8000 Series
Application, Startup & 0 S1-NSB8BHN141-0 -Wall (0.4 lbs)
Commissioning (ASC) Services Temperature and 3% Relative 0 S1-NSB8BTN143-0 -Wall
Available with Daily Fee Plus Humidity Combined Sensor, Temperature Sensor,
Expenses. This Service Provides Warmer/Cooler Display, WHITE, Warmer/Cooler Display, BLACK,
a 90 Day DOA Benefit When NO JCI LOGO, NS8000 Series NO JCI LOGO, NS8000 Series
Completed by a Factory Certified (0.4 lbs) (0.4 lbs)
Technician. Contact Your 0 S1-NSB8BHN143-0 -Wall 0 S1-NSB8BTN240-0 -Wall
Distributor, Dealer, or Sales Temperature and 3% Relative Temperature Sensor, Full Display,
Representative. Distributors Can Humidity Combined Sensor, WHITE, JCI LOGO, NS8000
Call 1-877-874-7378 for an ASC Warmer/Cooler Display, BLACK, Series (0.4 lbs)
Quote. NO JCI LOGO, NS8000 Series 0 S1-NSB8BTN241-0 -Wall
O S1-03102529000 - Non- (0.4 lbs) Temperature Sensor, Full Display,
Networking Wall Sensor—Allows 0 S1-NSB8BHN240-0 -Wall WHITE, NO JCI LOGO, NS8000
remote sensing and control from Temperature and 3% Relative Series (0.4 lbs)
single or multiple zones. (0.2 lbs) Humidity Combined Sensor, Full 0 S1-NSB8BTN243-0 -Wall
Display, WHITE, JCI LOGO, Temperature Sensor, Full Display,
NS8000 Series (0.4 lbs) BLACK, NO JCI LOGO, NS8000
Series (0.4 lbs)
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Millennium 25-40 Ton Page:6 ,
iliYORK® Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#: Z4N524ABE5A4BBCDA1
Quantity: 1 System: Z4N524ABE5A4BBCDA1
O S1-SE-COM1001-0- Field 0 S1-TEC3023-16-000 - 7 DAY 0 S1-TEC3613-16-000 - 7 DAY
Installed Communication Card for PROGRAMMABLE PROGRAMMABLE
Simplicity SE control. Can be field THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
configurable for BACnet, N2 or WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
ModBUS MSTP (0.0 lbs) FCUNAV, 0-10VDC PROP, OCC FCUNAV, ON/OFF OR
O S1-TEC3012-14-000 - 7 DAY & DEHUMID, FULL COLOR, FLOATING, OCC & DEHUMID,
PROGRAMMABLE WHITE, NO LOGO FULL COLOR, WHITE, NO LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3030-14-000 - 7 DAY 0 S1-TEC3622-14-000 - 7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, ON/OFF OR THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
FLOATING, DEHUMID, FULL WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
COLOR, WHITE, JCI LOGO RTU/HEAT PUMP WITH FCUNAV, 0-10VDC PROP,
O S1-TEC3012-16-000 - 7 DAY ECON,FULL COLOR, WHITE, JCI DEHUMID, FULL COLOR,
PROGRAMMABLE LOGO WHITE, JCI LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3030-16-000 - 7 DAY 0 S1-TEC3622-16-000 - 7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, ON/OFF OR THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
FLOATING, DEHUMID, FULL WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
COLOR, WHITE, NO LOGO RTU/HEAT PUMP WITH ECON, FCUNAV, 0-10VDC PROP,
O S1-TEC3013-14-000 - 7 DAY AND FULL COLOR, WHITE, NO DEHUMID, FULL COLOR,
PROGRAMMABLE LOGO WHITE, NO LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3031-14-000 - 7 DAY 0 S1-TEC3623-14-000 -7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, ON/OFF OR THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
FLOATING, OCC & DEHUMID, WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
FULL COLOR, WHITE, JCI LOGO RTU/HEAT PUMP WITH ECON, FCUNAV, 0-10VDC PROP, OCC
O S1-TEC3013-16-000 - 7 DAY OCC SENSOR, FULL COLOR, & DEHUMID, FULL COLOR,
PROGRAMMABLE WHITE, JCI LOGO WHITE, JCI LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3031-16-000- 7 DAY 0 S1-TEC3623-16-000 - 7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, ON/OFF OR THERMOSTAT, ZIGBEE PRO THERMOSTAT, OPTIONAL MSTP
FLOATING, OCC & DEHUMID, WIRELESS COMMUNICATION, OR N2 COMMUNICATION,
FULL COLOR, WHITE, NO LOGO RTU/HEAT PUMP WITH ECON, FCUNAV, 0-10VDC PROP, OCC
O S1-TEC3022-14-000 - 7 DAY OCC SENSOR, FULL COLOR, & DEHUMID, FULL COLOR,
PROGRAMMABLE WHITE, NO LOGO WHITE, NO LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3612-14-000 - 7 DAY 0 S1-TEC3630-14-000 -7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, 0-10VDC PROP, THERMOSTAT, OPTIONAL MSTP THERMOSTAT, OPTIONAL MSTP
DEHUMID, FULL COLOR, OR N2 COMMUNICATION, OR N2 COMMUNICATION,
WHITE, JCI LOGO FCUNAV, ON/OFF OR RTU/HEAT PUMP WITH
O S1-TEC3022-16-000 - 7 DAY FLOATING, DEHUMID, FULL ECON,FULL COLOR, WHITE, JCI
PROGRAMMABLE COLOR, WHITE, JCI LOGO LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3612-16-000 - 7 DAY 0 S1-TEC3630-16-000 - 7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, 0-10VDC PROP, THERMOSTAT, OPTIONAL MSTP THERMOSTAT, OPTIONAL MSTP
DEHUMID, FULL COLOR, OR N2 COMMUNICATION, OR N2 COMMUNICATION,
WHITE, NO LOGO FCUNAV, ON/OFF OR RTU/HEAT PUMP WITH
O S1-TEC3023-14-000 - 7 DAY FLOATING, DEHUMID, FULL ECON,FULL COLOR, WHITE, NO
PROGRAMMABLE COLOR, WHITE, NO LOGO LOGO
THERMOSTAT, ZIGBEE PRO 0 S1-TEC3613-14-000 - 7 DAY 0 S1-TEC3631-14-000 - 7 DAY
WIRELESS COMMUNICATION, PROGRAMMABLE PROGRAMMABLE
FCUNAV, 0-10VDC PROP, OCC THERMOSTAT, OPTIONAL MSTP THERMOSTAT, OPTIONAL MSTP
& DEHUMID, FULL COLOR, OR N2 COMMUNICATION, OR N2 COMMUNICATION,
WHITE, JCI LOGO FCUNAV, ON/OFF OR RTU/HEAT PUMP WITH ECON, .
FLOATING, OCC & DEHUMID, OCC SENSOR, FULL COLOR,
FULL COLOR, WHITE, JCI LOGO WHITE, JCI LOGO
Information is subject to change without notice.Check local codes. Printed 08/27/2019
•
Millennium 25-40 Ton Page:7
alifORK. Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#: Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
O S1-TEC3631-16-000 - 7 DAY
PROGRAMMABLE
THERMOSTAT, OPTIONAL MSTP
OR N2 COMMUNICATION,
RTU/HEAT PUMP WITH ECON,
OCC SENSOR, FULL COLOR,
WHITE, NO LOGO
O S1-YK-MAP1810-0P - MAP
(Multiple Access Portal) Gateway-
For use with SimplicitySE Control.
(0.2 lbs)
O S1-YK-MAP1810-0S - Stationary
MAP Gateway (Includes MAP
Gateway, Field Bus Adapter,
Mounting Bracket and 100 to 240
VAC Power Supply). US-
compatible counties. (1.9 lbs)
O YCCP40000MP060 -40 TON
2nd-5th Year Compressor
Warranty
Information is subject to change without notice.Check local codes. Printed 08/27/2019
ium
11111YORK® rn»ien Package v on f CIyG.
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
30-40 ton Millennium Unit Drawings
30 AND 40 TON MILLENNIUM OVERHEAD VIEW
1 2,12
s..2
A
j
•
240 0 I-
30 AND 40 TON MILLENNIUM MAJOR COMPONENT LAYOUT
1 _.. 'NlrO/Tit�lu�� i _._ {. _ .
•
C
_ 1 A
'�„� is , ii
.---; 73.
•
,..,,..�L! o ,4 7 1 A j •
L 4,i i,. o 41 +'1-I 'e }P .J- .
Information is subject to change without notice.Check local codes. Printed 08/27/2019
ayoRK® mittennium Package u Ion ,Qy..
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Component Locations
111rN�k — : tg
�r Hinged, Optional Hinged,
Ire IMEi - Tool-Free Hinged, Tool-Free
1[ Door Tool-Free Door
= = ��• iiI
{_Door s
9.1 /I ,«i_ #.Al i l' . Hinged,Tool-Free
.. i 1 ,
I €l \N.!' ; t w/PE Option,
, : 1 f . 'kx 1 i 2 to 3 4 /'°
, wr . -*' ' ' w I.
. . ... i : : -03 , . : : . , (: :
BACK VIEW
( _
]LHinged, Optional Hinged. I Hinged, xr I �
Tool-Free Hinged, Tool-Free Tool-Free 4
Door Tool-Free Door wiGas ;
� _ Door or Other Z f l :i k e t1711:
Heat Source f
/ Hinged,Tool-Free `' }
wiPE Option 1 ix •
5 6 7 8 9 {
, S1 I ,
.
FRONT VIEW
1. STD Cabinet Option includes Hinged.Tool-Free 4. Doors 1.2,3,6,7.8&9 are 56.31 inches high by
Doors#1.3.6.8. 27.33 inches wide.
2. Premium Cabinet Option includes Hinged,Tool-Free 5 Doors 4&5 are 26.5 inches high by 33.63 inches
Doors#1,2.3,6,7,8. wide.
3. Doors#4,5,9 are dependent upon unit Heating
and Power Exhaust Options.
CABINET DOOR CONFIGURATION
Information is subject to change without notice.Check local codes. Printed 08/27/2019
2 yoRK® mmennium ZD-4U ion
Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Component Locations
EVAPORATOR COIL
AND DRAIN PAN ACCESS
FILTER ACCE S POWER &CONTROL WIRING
COMPRESSOR ACCESS
—
REAR ,---_ -------
-- -.-• - ----- . _ _ - ,._.
-•-:: .1
____ _ weir ',,•-7, --•,---09 ! i
11111111 AmP--- •-••,,,,,•ri loo ill .
........„ , ,
. . F#i r iffsu i
- 101110 O'111.1110
11W. _•••• '' 11111111-0311011 11 1
104 r0e114-1'' RIGHT
•- 00.,.'•:Igoe.1! i
\ . im. 0w, .. .
001"do-, :, END
„.._ .
--..,... , ..ii.Y..--•
, ,.....,..,_,
Lillit-lilliii0 2„1
. . ,
• it.... . , P. 10.11-1" 101111111111111111 EAT SECTION
--....„.,...., FRONT
-_.•• OPTIONAL POWER
LEFT END OUTLET(115V)
POWER EXHAUST ACCESS
HEAT SECTION
EVAPORATOR COIL
FILTER DRIERS AND DRAIN PAN ACCESS
— FILTER ACCESS •
_....._
ittri:
lilL440R1I ---
i
\ 1 ir*Viftil . _,
19111041k II 41 4 • -- -rr ,._ ,,-
11.41V-iiiiiii#11 ii \
,n4141,,,ttiglif' . 1 .1.,.... --- -----
I iThrtit winatakis t ' ili..,-- :-_ .;'‘..
0-----rftwairfk *k
II ,-.,,: I ,
IttatIOARN.:!1._ I .
Otigi,,ftfilit,
REAR ••:,...,,,,. 41 -*•••^^*"*-'''.-
SUPPLY BLOWER & MOTOR
Information is subject to change without notice.Check local codes. Printed 08/27/2019
rayc. ,
RK® m►uen ium Package u ion
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Construction Features and Center of Gravity
PITCHED ROOF
f
ANGLED CONDENSER 1
COILS ,' SOLID, CLASS II FAN CONSTRUCTION
\ r—V. ' INTERTWINED COIL
:w
,t
T
1111111 1114; 1110111-
[ :1,1II tdllFn:is41'Iyt / _ _1 11111 .ilii lit lin ty I a ' I1IINNiI S�111�4R� -±tl 4,1,
11 ) ►_ �1 -1 �.�•� 4141 4f / � I,
DOUBLE WALL CONSTRUCTION ' . Li1 .
ik
`'
f ,4 HINGED, LATCHED
LOW LEAK DAMPERS ACCESS DOORS
UNIT CENTER OF GRAVITY
MODEL 25 TON 30 TON 40 TON
CENTER OF X Y X Y X Y
GRAVITY C RIGHT END
• REAR —^ CONDENSER BASIC UNIT 99" 48" 100" 47" 96" 46"
B COILS BASIC UNIT/W
D ECON.
110" 48" 110" 47" 100" 46"
— BASIC UNIT/W
X ECON.&GAS OR
nw '�` ELECT,HEAT, 104" 48" 104" 46" 99" 45"
`�N A ✓ FRONT STEAM OR HOT
240>, WATER HEAT
BASIC UNIT 1W
ECON,&GAS OR 118` 47" 114" 46" 111" 45.
ELECT,HEAT,&
POWER EXHAUST
UNIT CORNERWEIGHT
UNIT 25 TON 30 TON 40 TON
DESCRIPTION A B C D A B C D A B C 0
BASIC UNIT 870 949 1352 1239 950 972 1360 1303 969 969 1464 1454
BASIC UNIT WITH 1018 1111 1313 1203 1076 1124 1328 1272 1058 1058 1482 1482
ECONOMIZER
BASIC UNIT WITH
ECONOMIZER AND 994 1084 1418 1300 1073 1073 1403 1403 1102 1055 1503 1570
GAS OR ELECTRIC
HEAT
BASIC UNIT WITH
ECONOMIZER.AND
GAS OR ELECTRIC 1220 1275 1318 1262 1275 1275 1410 1410 1335 1278 1485 1551
HEAT AND POWER
EXHAUST
NOTES:Basic Unit=cooling only,10hp FC fan.
+Econ=+23516
+Heat=single stage gas,180 lb
+Power Exhaust=modulating 7 5h
Printed 08!27/2019
Information is subject to change without notice.Check local codes.
2 YO R K® mutermium zo-4U ion
Package r ClyV. AL.
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDAI
Quantity: 1 System: Z4N524ABE5A4BBCDAI
Dimensions&Clearances
r> RETURN AIR
SUPPLY AIR
REik!! .------:- e---
-- -----' -
1.,
::: ' -'-',.40 '.- , RIGHT
---,,,,,,,_, ------
--•` ,_------ SE ---lk,410,--''',4 ,OS,,,:,,,: END
SEE DETAIL
64" ' DETAIL C,
72.25'
Nick.
\\,...:,..:, f-
. .....--
,
.'-' - ----:'—'--- FRONT 1 .......-----"---131.5" I
92",,,,,,,
LEFT ,r.--------------RIGHT
END -REAR - .,,,, END
.4000.".... -
4
1%. OPEN
,--
80.93"- --, *!,...,...„.„,. 03 625" .,... _---
L%----7 12"
-------SEE 71.61' 4-26" _...,, _"---m IN
I 4'5" —0101111104* DETAIL ----,,,..„... c'.....-- >
.71r
6.46" 0 15.89"
88.7"
83"
LEFT -------...„.„,_____.<__-
END 4.5" 't
TO GAS VALVE
MANIFOLD
2-1/2"
DA.HOLES
• 1---, *-- •._ \
+ -.......,
N tC ' calk,"
+ III 1111 : BASE RAIL lialk
1 2.31" 6.45" 28'
--- *0
BASE RAIL
11
2" ,i/
1-1/2k FPT 0 2-1/
1-1/4"NPT
DETAIL A DETAIL B
DETAIL C _
(DRAIN CONNECTION) (ELECTRICAL CONNECTION)
(GAS CONNECTION
FOR COOLING ONLY AND ALL HEATING APPLICATIONS THROUGH CURB)
Information is subject to change without notice.Check local codes. Printed 08/27/2019
. yoRK® mmennium Z3-4U ion
Package
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDA1
Quantity: 1 System: Z4N524ABE5A4BBCDA1
Dimensions&Clearances
CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - SIDE
REQUIRED CLEARANCES
10'
ENDS ENDS
60-40-
1 ;f„,
60" MEIN
REAR FRONT
* Front is the side with access to the Electrical/Gas Controls.
* Right is the side with the Condenser Coils.
LEFT 60"
RIGHT 60"
REAR 60" NOTE: DO NOT use the unit roof to support any type of
FRONT 60" structure or bracing.
TOP 10'
CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - FRONT & END
LEFT END
FRONT SIDE
15.93 . 79.0 I.- 15.93
4 • II
V(71 :11S1 .01A9.6
4411111 HOOD FOR
OPTIONAL
EXHAUST AIR
RAIN HOOD FOR t \END OT RAEVTAul LRANBOL ER Wvv IITTHH
FIXED OUTSIDE AIR 33.90 33.90 29.36
FIXED OUTSIDE AIR)
OR ECONOMIZER
/ 4 59.52
7.94
RAIN HOOD FOR
OPTIONAL POWER EXHAUST
OR BAROMETRIC RELIEF
(NOT AVAILABLE WITH
END RETURN OR WITH
FIXED OUTSIDE AIR)
Information is subject to change without notice.Check local codes. Printed 08/27/2019
e yo R K. millenniumPackage v ion „..,.,
York Single Package R-410A Air Conditioner
Project Name: Martin Building Unit Model#:
Z4N524ABE5A4BBCDA1
Quantity: 1 System: Z4N524ABE5A4BBCDA1
Fan Curve
40TonForward Curve
7.0 "
s au u n aam rlitUal
u urnir�i�
galllia • r wn� Bi an
wai65 inir nilnrinn> nnr nnn n
`uu� 111111111/1111111111101111111111111111111111=11110111 i I
6.0 k`l esimes aI a irsamo eiis r
��.
r it inset
IMOInaluesuuramon-
irrn iiieaiei
i aisenione
i r ria � na i 5.5 SG . N rNH rNanaii n
.n
mmentaimminemairugmantionnieseee
. _ �� _ .n8i
.
SA naunnina _ vise- . itis
lipiriMMIIIMftal
ELII
a / '' i a y'ttt �nn rrit1 i
t I ,. t. ; "
4.5 mmeees
i, iraga iiiilliii im itinll►
URIBUSIIIIMUNIMI
4.0 am.mnin rrNNMh if ►' s/nliii lrnni►`
I. awari wilil
t.n iriii aas iwI
a3.5
BSIBIZMUMNIUSIII111111111111111111111111111111111111MMIMMainninlillibunonai
t . io
r
1,101
74
' ".� mm,,5030 _ Illillngsig ,-mil
slu i11
. M11011§'
Swlrs nnriese_
R nnn 1 uain
25 i , ninui i�
iii ■Nt iiiir ►
nkilli
2.0 r nen _l ""
r
i ""rte m� "ss.`e
rias I1
allLo i
`au...
i�.S l wow 71 i�ii i nisi I-snc :`Tfit41 , Unit't.rtlC`,
.5 fir` t region.-Add to FSP atts)
additional lc»wes(OPtinii's
.- '1CCenbtiYic,) ,
0.0 - ,.
0 2 4 6 8 1 12 14 16 18 20
(F\!(x1000)
NOTE: All areas below the"A"curve are fixed,internal cabinet losses and should be considered when determining total sys-
tem static and plotting unit fan performance.
NOTE: Standard Unit includes wet evaporator coil,clean 2"throwaway filters,system and cabinet effects at standard air den-
sity and 0'elevation.
FIGURE 25- FAN PERFORMANCE-40 TON
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page: 15
Date
08/27/2019 �f
Project Name
Johnson ,�
Martin Building Controls
Project Number
CSL08261901
- Client/ Purchaser
Guide Specification Summary Page
•
Product Series Models and Unit Tags
i#enn�
Information is subject to change without notice.Check local codes. Printed 08/27/2019
YORK® Guide Specification for Page: 16
York Millennium
GENERAL interior. Floor shall be 18 gauge, and 24 gauge. All
serviceable sections shall have hinged access doors with
Introducing the York 25, 30, and 40 ton Millennium latches on both sides of the unit. All access doors shall be
rooftop line- units designed to provide peak constructed of 20 gauge steel on the outside, with 24
performance and value both today and for years to gauge on the inside. Each door shall seal against a rubber .
come. Each rooftop unit is completely computer-run gasket to prevent air and water leakage. The roof shall be
tested prior to shipment. The unit is designed to be double wall, with 18 gauge on the external surface and 24
flexible enough to meet your needs today and in the gauge on the interior. The roof shall be formed with a 45
future. The true value of this unit is that it can be degree drip lip overhanging the sidewalls to prevent
designed to fit any need, from cooling only, constant precipitation drainage from streaming down the side of the
volume applications to variable air volume systems with unit. Roof sections shall be connected together via integral
variable frequency drive. channels fastened with screws and sealed with rubber
DESCRIPTION gasketing. Each fastened seam shall be further protected
by a sheet metal channel covering the full length of the
Supply York Millennium packaged rooftop system in gasket surface, making a completely water tight seal.
accordance with the capacities in the plans. Units shall SUPPLY AIR SYSTEM
be rated by the manufacturer at a minimum 10.5 EER
according to AHRI 360. Units shall be shipped in a single SUPPLY AIR FAN
package, fully charged with R-410A refrigerant. The
manufacturing facility shall be registered under ISO 9001 Fans shall be centrifugal type - Class I or Class II or
Quality Standards for Manufacturing. Units shall carry backward inclined airfoil type statically and dynamically
both ETL and CGA safety approval ratings. Tags and balanced in the factory. Fan wheels shall be designed for
decals to aid in the service or indicate caution areas continuous operation at the maximum rate of fan speed
shall be provided. Installation and maintenance manuals and motor HP. The fan and motor assembly shall be
shall be supplied with each unit. Units shall be capable mounted on a common base to allow consistent belt
of providing mechanical cooling down to 40°F (0°F with tension with no relative motion between the fan and motor
low ambient kit). Unit shall be capable of starting and shafts. The entire assembly shall be isolated from the unit
running at 125°F. Unit electric and gas connections shall base with (optional 1", 2" deflection springs or rubber
be either through the curb or the side of the unit. isolators). The fan discharge shall be connected to the
cabinet through a reinforced neoprene flexible connection
CONSTRUCTION to eliminate vibration transmission from the fan to the unit
Base casing. Fans shall be double-width, double-inlet with
forward curved blades.
The base rail shall be constructed of 12 gauge galvanized OPTIONAL
steel, extending the full perimeter of the unit. All
components shall be supported from the base, and the Units equipped with variable frequency drive on supply fan
base shall include integral lifting lugs. The unit base rail must be controlled by a duct static transducer providing a
shall overhang the roof curb for water runoff and shall 2- 10 VDC signal to the drive. Supply fan variable
have a fabricated recess with a continuous flat surface to frequency drives shall have factory option of being
seat on the roof curb gasket, providing a positive, weather equipped with a manual drive bypass.
tight seal between the unit and the curb.
BEARINGS AND DRIVES
Casing
Bearings shall be self-aligning pillow-block regreasable
The unit cabinet shall be double wall construction to ball bearings with an average life expectancy of 200,000
provide both maximum resistance to bacterial growth in hours. Grease fittings shall be accessible through access
the air stream and superior structural integrity. All sheet doors. Fan motors shall be NEMA designed, Standard
metal shall be G90 mill galvanized sheet metal, formed efficiency (option, Hi-efficiency) ball bearing type with
and reinforced to provide a rigid assembly. Sheet metal electrical characteristics and horsepower as specified.
shall be cleaned in an alkaline and zinc phosphate bath, Motors shall be 1750 RPM, open drip proof type. The
and the exterior surfaces shall be coated with a 1.5 mil motor shall be located within the unit on an adjustable,
powder paint, capable of withstanding 750 salt spray heavy steel base. All fan motor drives shall be selected for -
hours in accordance with ASTM B-117. The unit shall be a minimum service factor of 1.2 and have fixed pitched
insulated with 1-1/2," 1 pound fiberglass insulation sheaves.
between the two sheet metal skins. Insulation shall meet
NFPA-90A regulations for smoke and flame spread AIR FILTERING SYSTEM
ratings. The cabinet corner post and the intermediate side All filter holding frames shall be of heavy duty construction
supports shall be 16 gauge steel. All access doors shall be designed for industrial applications. All filters shall be
18 gauge on the exterior surfaces, and 20 gauge on the either side accessible or front loading with access doors
Information is subject to change without notice.Check local codes. Printed 08/2712019
YORK® Guide Specification for Page: 17
York Millennium
provided on both sides of the filter section. All filter media the unit. Non-modulating Exhaust- Units with non-
, shall be Class II listed under UL Standard 900. Filter modulating power exhaust shall have a barometric relief
efficiencies shall be rated in accordance with ASHRAE damper to prevent outside air from entering in the off
Standard 52-76 2"Throwaway Filters with fiberglass cycle. The fans shall cycle on and off with building
media multiple shall be standard. pressure. Modulating Operation -The fans shall be
capable of modulating the amount of air from 0% to
OPTIONAL 100% of nominal CFM. Modulation shall be through
Two inch pleated, throwaway filters with 30% efficiency. discharge dampers or variable frequency motor speed
Rigid filters shall be high performance, expanded area, modulation. Dampers or VFD shall be controlled by static
disposable type filters. Rigid filter sections shall be pressure in the conditioned space or return air duct.
preceded by a 2 throwaway prefilter assembly. Filter HEATING SYSTEM
efficiency shall be 95% MERV 14 or optional 65% (MERV
8) based on ASHRAE Standard 52-76. Gas-fired Heating Section
AIR INLET SYSTEM One or more gas-fired heating modules shall be installed
General to provide the heating requirements per the schedule
shown on the plans. The heat exchanger shall be of
Outside Air inlet openings shall be covered by a factory tubular design. Tubes shall be 2-1/4" OD and
installed rain hood permanently attached to the cabinet to constructed of minimum 20 gauge, G160 aluminized
prevent windblown precipitation from entering the unit. The steel (1.6 mil aluminum silicone alloy)for corrosion
rain hoods on the front and back of the unit shall be resistance (Optional: 409 Stainless Steel). Flue baffles
rotated into the cabinet and secured for shipment so that shall be made of 430 stainless steel. Each gas fired heat
upon installation they need only be rotated upwards and module shall have an induced draft combustion fan with
screwed into place. The outside air hood shall contain a energy efficient intermittent pilot spark ignition and
removable and cleanable filter with an efficiency rating of redundant main gas valves with pressure regulator. Units
50% based on ASHRAE 52- 76. All damper assemblies with standing pilot ignition shall not be acceptable. An
shall be of low leak design. Damper blades shall be induced draft fan shall be provided to maintain a positive
fabricated from a minimum of 16 gauge galvanized steel. flow of air through each tube, to expel the flue gas and to
Blade ends and edges shall be covered with vinyl seals. maintain a negative pressure within the heat exchanger
Damper shafts shall be fabricated from solid steel and relative to the conditioned space. Induced draft fans shall
mounted in the frame with bronze bearings. be direct-drive. One (1) high limit controller per heating
module, with automatic reset to prevent the heat
Economizer(Optional) exchanger from operating at an excessive temperature
An economizer shall have outdoor air and return air will be installed. A pressure switch on the combustion
- dampers that are interlocked and positioned by fully section must be provided to prevent ignition until
modulating, solid state damper actuators. The actuators sufficient air flow is established through the heat
shall be spring loaded so that the outside air damper will exchanger. Secondary airflow safety shall be provided by
close when power to the unit is interrupted. The roll-out switch protection. The rollout switch shall
operation of the economizer shall be fully integrated into discontinue furnace operation if the flue becomes
the cooling control system. The economizer shall be restricted. Units shall ship with an external flue to be
available for control via a dry bulb sensor(Optional: shipped in the unit and mounted on the job site. The flue
single or dual enthalpy sensors). shall discharge products of combustion above the unit,
preventing recycling of corrosive combustion gases back
Relief System (Optional) through the heat exchanger. Gas heating sections shall
be both ETL and CGA approved to both US and
All units with relief must have an economizer. On all units Canadian safety standards.
not equipped with an economizer, an option shall be
available for a manually adjustable outside air damper Optional Modulating Furnace control or Single Stage
that shall be capable of admitting 0-25% outside air. control available.
REFRIGERATION SYSTEM
Exhaust Air Fans (Optional) Units shall have four independent refrigerant circuits for
General -forward curved centrifugal fan(s) shall be maximum load-matching capability. Each refrigerant
installed in the return air plenum for positive power circuit shall be controlled with a balance-port thermal
exhaust. Fans shall be on a common shaft, driven by a expansion valve for maximum control at low load
single motor. The fans, motors and drives shall be of the conditions.
same quality and design as specified for the Supply Air Evaporator Coils
Fan, except the fans shall be Class I. Fans shall be
capable of exhausting up to 100% of the nominal CFM of
Information is subject to change without notice.Check local codes. Printed 08/27/2019
YORK® Guide Specification for Page: 18
York Millennium
Evaporator coils shall be direct expansion type with circuit shall also have both high and low pressure
intertwined circuiting to assure complete coil face activity switches installed on either side of the compressor and
during part load operation. Coil fins shall be enhanced include shrader depressors for replacement of the
aluminum type. Coil types shall be 3/8" OD copper, pressure switches without removing charge. All small
internally enhanced and mechanically expanded to bond diameter distributor tubing to the evaporator coil shall be
with the fins. Coil casing shall be fabricated from heavy protected by polyurethane sleeves over the length of the
gauge galvanized steel. All coils shall be pressure tested tubing to prevent the tubes from copper-to-copper
at a minimum of 450 PSIG. A galvanized powder painted contact during shipment or operation.
steel drain pan shall be provided under the entire length CONTROLS
and width of the evaporator coil, including all return
bends. The main drain pan shall be sloped a total of 1/4" GENERAL DESCRIPTION
per foot towards the drainage point. Main drain pan shall
be easily cleanable in the field. The condensate drain Equipment with Smart Equipment®as standard shall be
opening shall be flush with the bottom of the drain pan to factory run-tested through the control, after the test is
allow complete drainage. Coils in excess of 48 inches complete; there will be no wires to re-connect. All control
high shall have an intermediate drain pan, also wiring points shall be tested and verified through
fabricated of galvanized powder painted steel extending communication.
the entire finned length of the coil to provide better water The control shall be UL or CSA recognized. The control
drainage. Drainage from the intermediate drain pan shall shall be manufactured in a manufacturing facility that is
be to the primary drain pan. OPTIONAL: Drain pans certified to ISO 9001.
shall be constructed of stainless steel.
Compressors
COMPRESSOR CONTROL
Units shall have four industrial duty hermetic scroll
compressors, independently piped and charged. The control shall have a five-minute Anti-Short Cycle
Compressors shall have an enlarged liquid carrying Delay to prevent excessive compressor cycling. The
capacity to withstand rugged operating conditions. control shall have a three-minute minimum run time to
Compressor frame shall be cast iron, with cast iron fixed insure that oil gets returned to the compressor each time
and orbiting scrolls. Each compressor shall feature a it starts. The minimum runtime shall be programmable
solid state protection module, designed to protect the up to 10 minutes.
compressor from over temperature and overcurrent The control shall monitor the High Pressure switch, the
conditions. Each compressor shall include the following Low Pressure switch, and the Compressor Overloads
safety and convenience devices: replaceable suction separately for each refrigeration circuit. The control shall
screen, discharge line check valve, and oil sight glass. have a 30 second Low Pressure Switch bypass when it
Compressors shall be vibration isolated from the unit, starts any compressor.
and installed in an easily accessible area of the unit.
A hard compressor lockout shall occur if the control
Condenser Coils detects the same switch trip three times in a two-hour
Condenser coils shall have 3/8" seamless copper tubes, window, which starts when the first trip occurs. On the
arranged in staggered rows, mechanically expanded into first and second trips, the control will turn the
aluminum fins. Coils shall be protected from hail damage compressor off and wait five-minutes after the switch re-
with a V configuration, with individual flat coils rotated 30 closes, before restarting the compressor.
from the vertical plane for each condensing circuit. The control shall be capable of operating both
Condensing coils shall have an integral subcooler for compressors and the economizer when there is a call for
more efficient, stable operation. both stages of cooling.
Condenser Fans and Motors The control shall have a means of locking out
Condenser fans shall be direct drive, propeller type, mechanical compression below a programmable low
discharging vertically. Condenser fan motors shall be 3 ambient trip point. This must be done without adding
phase, totally enclosed air over(TEAO)type, with built in extra components to the unit.
thermal overload protection. The control shall have a means of locking out the
Refrigerant Piping mechanical compression when the economizer is
operating in free cooling mode without additional
All interconnecting piping between refrigeration components.
components shall be copper tubing with brazed joints.
Each refrigerant circuit shall be equipped with liquid line
filter drier, and moisture indicating sight glass. Each
Information is subject to change without notice.Check local codes. Printed 08/27/2019
I " iGuide Specification for Page: 19
York Millennium
The control shall have a means of starting the
_ compressor before the indoor Fan comes on when
operating with a Thermostat in the AUTO FAN mode.
FAN CONTROL
The control shall have fully adjustable Fan ON and Fan
OFF delays for both Heating and Cooling settable at the
control or via communication.
The control's default Fan OFF delay for Cooling shall be
30 seconds to take advantage of the remaining capacity
in the coil after the compressor has been turned off.
The control shall lock on the Fan if the high temperature
limit trips three times in one hour of operation.
The control will have a software programmable Fan
Mode Switch for Auto operation or Continuous operation.
When the Fan is in the Continuous mode, it will run
continuously during the occupied schedule and in the
Auto mode when in an unoccupied schedule.
The control shall be capable of operating the fan without
a G or fan signal from the thermostat.
AVAILABLE ACCESSORIES
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:20
Date
08/27/2019
Project Name 'I ,(
Johnson ,���
Martin Building Controls
Project Number
CSL08261901
- Client/ Purchaser
Control Summary Page
•
Control Models and Unit Tags
'1m; usTptviab Nt 0 E5A
Information is subject to change without notice.Check local codes. Printed 08/27/2019
121YORK® SSE Guide Spec Page:21
23 09 23 Direct-digital Control system for HVAC
23 09 23. 13 Decentralized,Rooftop Units:
23 09 23. 13.A. Unit Control Board
1. ASHRAE 62-2001 compliant. BTL certified.
2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal.
3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non-
condensing),with a storage temperature range from-40F to 194F;5-95%RH(non-condensing).
4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board
and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs.
5. Controller shall accept the followinginputs: space temperature,return air temperature sensor,setpointadjustment,outdoor air
temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single
and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors,
FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality,
System purge.
6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and
be Demand Control Ventilation(DCV)ready.
7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/
exhaust/reversing valve/dehumidify/occupied.
8. Unit shall provide surge protection for the controller through a circuit breaker.
9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster.
10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation.
11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the
following standard safety devices trip and shut off compressor. If any of these safety devices trip,the LCD screen will display
alarm message indicating the specific safety device that caused the lockout.
a. Loss of charge/Low-pressure switch.
b. High-pressure switch.
c. Freeze condition sensor on evaporator coil.
12. Unit control board must support each usage case:
a. Conventional thermostat with low voltage input terminals for easy installation
b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control
board to compare with associated setpoints
c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building
automation/management system
13. Anti-short cycle and low voltage protection features included.
14. Internal occupied/unoccupied scheduling
15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F.
16. Shall allow for start-up, commissioning,troubleshooting, parameter adjustment,setpoint adjustment via onboard
display and navigable menu with no additional interface tool or controls technician required.
17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating
cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test.
18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between
them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up, commissioning,
troubleshooting, parameter adjustment,setpoint adjustment.
19. Local embedded trending and scheduling.Trending data and occupancy scheduling predefined from the factory.
Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device
(cellular phone, laptop,tablet)
20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable.These
include but are not limited to:
a. Demand Ventilation Mode—enable or disable -
b. Operational Setpoint—display current value
c. Supply Air Temperature(SAT)—display current value
d. Return Air Temperature(RAT)—display current value
Information is subject to change without notice.Check local codes. Printed 08/27/2019
[ SSE Guide Spec Page:22
yo R K
e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network
Sensor,or FC Bus communicated value
f. Return Air Humidity(RAH)—display current value
g. Operational outdoor Air Temperature(OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer
board and OprOAT only if economizer is present
h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards
OAH 0-10VDC input or FC Bus communicated value
i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer
boards OAQ 0-10VDC input or FC Bus communicated value
j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board
IAQ 0-10VDC input, SA Bus Network Sensor,or FC Bus communicated value
21. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone Fan
b. Cooling
c. Heating
d. Economizer
e. Demand Ventilation
f. Power Exhaust
g. Sensors
h. Network
22. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone—Occupied status
b. Indoor Fan status
c. Cooling status
d. Heating status
e. Economizer indication whether free-cooling is available or not
f. Enabling or disabling of Demand Ventilation
g. Power Exhaust
1) Enable/disable hot-gas reheat if available
• 2) Warmup/Cooldown
3) Title 24 Load Shed
4) Defrost
23. A menu shall display and allow modification to the following operations and settings:
a. Firmware version (of UCB, Economizer,other peripheral boards)
b. Setting time zone
c. Network information
1) Device name that will appear on the FC Bus
2) Selection of communication protocol
3) Operational Baud Rate
4) Device ID
24. A menu shall display and allow modification to the following operations and settings:
a. Version of firmware
b. Ability to Load new firmware
c. Create a backup file of the firmware and parameter setting via USB port
d. Restore factory default parameter values and setup
e. Full and Partial Cloning of parameter setpoints from or to other units
f. Data trend exporting
25. A menu shall display and allow modification to the following operations and settings:
Information is subject to change without notice.Check local codes. Printed 08/27/2019
a YORK® SSE Guide Spec Page:23
a. Unit serial number, model number and name
b. Ability to reset Lockouts •
c. Controller name
d. Displays the current values of all setpoints in use
e. Displays all current values for the indoor and outdoor zones
f. Displays current values related to:
1) Indoor Fan
2) Cooling
3) Heating
4) Heat Pump operation
5) Economizer operation
6) Power Exhaust
7) Demand Ventilation
8) Air monitoring station
9) Hot Gas Reheat
10) Smoke Control
g. Current information for inputs; including
1) Sensors
2) Coil Sensors
3) Thermostat
4) Binary Inputs
5) Unit Protection
6) Network Inputs
7) All outputs(relay and binary)
h. Self-Test
1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning
characteristics of the system at time of startup and commissioning.
23 09 23. 13.B. Auxiliary Control Boards
1. ASHRAE 62-2001 compliant. BTL certified.
2. Economizer controller CEC Title 24 Compliant
a. Display alarms if the following occur
1) Economizer is economizing when conditions do not support
2) Economizer is not economizing when conditions do support
3) Damper Stuck
4) Excess Outdoor Air
5) Failed Sensor
3. Refrigeration Fault Detection &Diagnostics
a. There is insufficient refrigerant in any circuit
b. There is excessive refrigerant in any circuit
c. There is excessive refrigerant flow
d. There is insufficient refrigerant flow(restriction)
e. Inefficient compressor
f. Insufficient High-side heat transfer
g. Excessive High-side heat transfer(low ambient control problem, low AP)
h. Insufficient Low-side heat transfer
i. Excessive Low-side heat transfer
Information is subject to change without notice.Check local codes. Printed 08/27/2019
R YORK® SSE Guide Spec Page:24
j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if
refrigerant level is very low in the system)
k. Sensor fault-Sensor data is not available
I. The unit is off
• m. The ambient temperature is too low
n. The ambient temperature is too high
o. The return air wet-bulb temperature is too low
p. The return air wet-bulb temperature is too high
q. Sensor fault-The condensing temperature is lower than the ambient temperature(Could also be triggered when
the condenser is wet)
r. The suction line temperature is less than the evaporator temperature
s. The evaporator temperature is greater than the ambient temperature
t. The liquid temperature is lower than the ambient temperature
u. Sensor fault-Suction temperature or ambient temperature is invalid
v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid
w. Sensor fault-The liquid pressure or suction pressure is invalid
x. Sensor fault-The suction line temperature is invalid
y. The return air dry-bulb temperature is too low
z. The return air dry-bulb temperature is too high
aa. The Efficiency Index is below 75%of ideal
bb. The Capacity Index is below 75%of ideal
23 09 23. 13.0 Remote Accessibility:
1. ASHRAE 62-2001 compliant. BTL certified.
2. Provide the ability to adjust parameter values, setpoints, limits remotely
3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS)
4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:25
START-UP & SERVICE DATA INSTRUCTION
COMMERCIAL PACKAGE UNITS
3.0 To 40.0 TONS
START-UP CHECKLIST
Date:
Job Name:
Customer Name:
Address:
City: State: Zip:
Model Number: Serial Number:
Qualified Start-up Technician: Signature:
HVAC Contractor: Phone:
Address:
Contractor's E-mail Address:
Electrical Contractor: Phone:
Distributor Name: Phone:
WARRANTY STATEMENT This start-up sheet covers all startup check points common to all
package equipment.In addition it covers essential startup check
Johnson Controls/UPG is confident that this equipment will points for a number of common installation options. Depending
operate to the owner's satisfaction if the proper procedures are upon the particular unit being started not all sections of this startup
followed and checks are made at initial start-up.This confidence is sheet will apply.Complete those sections applicable and use the
supported by the 30 day dealer protection coverage portion of our notes section to record any additional information pertinent to your
standard warranty policy which states that Johnson Controls/UPG particular installation.
will cover parts and labor on new equipment start-up failures that Warranty claims are to be made through the distributor from whom
are caused by a defect in factory workmanship or material,for a the equipment was purchased.
period of 30 days from installation.Refer to current standard
warranty policy and warranty manual found on UPGnet for details. EQUIPMENT STARTUP
In the event that communication with Johnson Controls/UPG is
required regarding technical and/or warranty concerns,all parties Use the local LCD or Mobile Access Portal(MAP)Gateway to
to the discussion should have a copy of the equipment start-up complete the start-up.
sheet for reference.A copy of the original start-up sheet should be A copy of the completed start-up sheet should be kept on file
filed with the Technical Services Department. by the distributor providing the equipment and a copy sent to:
The packaged unit is available in constant or variable air volume Johnson Controls/UPG
versions with a large variety of custom options and accessories Technical Services Department
available.Therefore,some variation in the startup procedure will 5005 York Drive
exist depending upon the products capacity,control system,
options and accessories installed. Norman,OK 73069
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:26
SAFETY WARNINGS
The inspections and recording of data outlined in this procedure AWARNING
are required for start-up of Johnson Controls/UPG's packaged
products. Industry recognized safety standards and practices Lethal voltages are present during some start-up
must be observed at all times.General industry knowledge and checks. Extreme caution must be used at all times.
experience are required to assure technician safety. It is the
responsibility of the technician to assess all potential dangers
and take all steps warranted to perform the work in a safe
manner. By addressing those potential dangers, prior to AWARNING
beginning any work,the technician can perform the work in a
safe manner with minimal risk of injury. Moving parts may be exposed during some startup
checks. Extreme caution must be used at all times.
NOTE: Read and review this entire document before beginning
any of the startup procedures.
DESIGN APPLICATION INFORMATION
This information will be available from the specifying engineer full open position and the frequency drive is operating at 60 HZ.
who selected the equipment. If the system is a VAV system the Do not proceed with the equipment start-up without the
CFM will be the airflow when the remote VAV boxes are in the design CFM information.
Design Supply Air CFM: Design Return Air CFM:
Design Outdoor Air CFM At Minimum Position:
Total External Static Pressure:
Supply Static Pressure:
Return Static Pressure:
Design Building Static Pressure:
Outside Air Dilution:Economizer Position Percentage: _ CFM:
Supply Gas Pressure After Regulator W/o Heat Active Inches
ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER:
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:27
REFERENCE
General Inspection Completed See Notes
Unit inspected for shipping,storage,or rigging damage ❑ ❑
Unit installed with proper clearances 0 ❑
Unit installed within slope limitations ❑ 0
Refrigeration system checked for gross leaks(presence of oil) ❑ ❑
Terminal screws and wiring connections checked for tightness 0 0
Filters installed correctly and clean 0 ❑
Economizer hoods installed in operating position 0 0
Condensate drain trapped properly, refer to Installation Manual 0 0
Economizer damper linkage tight ❑ 0
Gas Heat vent hood installed 0 0
All field wiring(power and control)complete 0 0
Air Moving Inspection Completed See Notes
Alignment of drive components ❑ 0
Belt tension adjusted properly ❑ 0
Blower pulleys tight on shaft, bearing set screws tight,wheel tight to shaft ❑ ❑
Pressure switch or transducer tubing installed properly ❑ ❑
Exhaust Inspection Powered 0 Barometric Relief 0 Completed See Notes
Check hub for tightness 0 0
Check fan blade for clearance ❑ 0
Check for proper rotation 0 ❑
Check for proper mounting (screen faces towards unit) 0 0
Prove operation by increasing minimum setting on economizer ❑ 0
Economizer Inspection Standard❑ BAS 0 Completed See Notes
CO2 sensor installed Yes 0 No 0 0 ❑
Check economizer setting(Reference SSE Control Board LCD menu location) 0 0
Prove economizer open/close through SSE Board Setting 0 0
Reheat Mode Normal El or Alternate 0 Not Applicable 0
Humidity Sensor(2SH0401)
Information is subject to change without notice.Check local codes. Printed 08/27/2019
•
Page:28
Operating Measurements -Air Flow
Fan operates with proper rotation ID Fans❑ Exh. Fans❑ Cond. Fans 0
Pressure drop across dry evaporator coil (At maximum design CFM) 1 IWC
External Static Pressure IWC
Return Static Pressure IWC •
Supply Static Pressure IWC
Supply Air CFM Using Dry Coil Chart CFM
Final Adjusted Supply Air CFM2 CFM
1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential.
2. Was a motor pulley adjustment or change required to obtain the correct airflow?
Was it necessary to increase of decrease the airflow to meet the design conditions?
lithe motor pulley size was changed,measure the outside diameters of the motor and blower pulleys end record those diameters here;
Blower Motor HP FLA RPM
Pulley Pitch Diameter Turns Out Final Turns Out
Blower Pulley Pitch Diameter Fixed Sheave
ELECTRICAL DATA
T1 -T2 Volts T2-T3 Volts
Control Voltage Volts T1 -T3 Volts
Device Nameplate Measured
List All Three Amperages
Supply Fan Motors°2 AMPS AMPS
Exhaust Motor(Dampers 100%) AMPS AMPS
Condenser Fan#1 AMPS AMPS
Condenser Fan#2(if equipped) AMPS AMPS
Condenser Fan#3(if equipped) AMPS AMPS
Condenser Fan#4(if equipped) AMPS AMPS
Compressor#1 AMPS AMPS
Compressor#2(if equipped) AMPS AMPS
Compressor#3(if equipped) AMPS AMPS
Compressor#4(if equipped) AMPS AMPS
1. VAV units with heat section-simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position.
2. VAV units without heat section-VAV boxes must be set to maximum design airflow position.
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:29
OPERATING MEASUREMENTS -COOLING
Stage plressu�re Discharge Liquid Line SubcoolingZ presSucsure Tempon n Superheat
First • # 0 ° • # 0 °
• Second(if equipped) # # °
Third(if equipped) # ° # °
Fourth(if equipped) # # °
Reheat 1st Stage # #' °
1. Liquid temperature should be taken before filter/drier.
2. Subtract 10 psi from discharge pressure for estimated liquid line pressure
Outside air temperature °F db °F wb %RH
Return Air Temperature °F db °F wb %RH
Mixed Air Temperature °F db °F wb %RH
Supply Air Temperature °F rib °F wb %RH
REFRIGERANT SAFETIES
Action Completed See Notes
Prove Compressor Rotation(3 phase only)by gauge pressure 0 0
Prove High Pressure Safety, All Systems 0 0
Prove Low Pressure Safety,All Systems 0 0
OPERATING MEASUREMENTS -GAS HEATING
Fuel Type: 0 Natural Gas 0 LP Gas
Action Completed See Notes
Check for gas leaks 0 0
Prove Ventor Motor Operation 0 0
Prove Primary Safety Operation 0 0
Prove Auxiliary Safety Operation 0 0
Prove Rollout Switch Operation 0 0
Prove Smoke Detector Operation 0 0
Stage 1 IWC 0
Manifold Pressure Stage 2(If Equipped) IWC 0
Stage 3(If Equipped) IWC 0
Supply gas pressure at full fire IWC 0
Check temperature'risel 0 measured at full fire °F 0
j, Input X Eff.(BTU output)
1.08 X Temp.Rise
Information is subject to change without notice.Check local codes. Printed 08/27/2019
Page:30
OPERATIONAL MEASUREMENTS -STAGING CONTROLS
Verify Proper Operation of Heating/Cooling Staging Controls
Create a cooling demand at the Thermostat, BAS System or Simplicity SE
Verify that cooling/economizer stages are energized. 0
Create a heating demand at the Thermostat, BAS System or Simplicity SE
Verify that heating stages are energized. 0
Verify Proper Operation of the Variable Frequency Drive(If Required)
Verify that motor speed modulates with duct pressure change. 0
FINAL -INSPECTION
Verify that all operational control set points have been set to desired value ❑
Scroll through all setpoints and change as may be necessary to suit the occupant requirements.
Verify that all option parameters are correct
Scroll through all option parameters and ensure that all installed options are enabled in the software and all 0
others are disabled in the software. (Factory software settings should match the installed options)
Verify that all access panels have been closed and secured 0
OBSERVED PRODUCT DIFFICIENCIES & CONCERNS: