4077 Airpark Dr. Standish, MI 48658 •989-846-4583•www.globesprinkler.com
FIRE SPRINKLER CORPORATION Technical Support•989-414-2600•techservice@globesprinkler.com
SPECIFIC APPLICATION MODEL "IC"
INTERSTITIAL COMBUSTIBLE CONCEALED SPACE
UPRIGHT SPRINKLER GL5608 RECEIVED
GENERAL DESCRIPTION
The Globe Series GL-SS/IC GL5608 Interstitial Combustible JAN 7 2020
Space Sprinkler is a quick response, upright, specific appli-
cation sprinkler designed to provide protection of light haz- ` CITY OF TIGARD
and combustible and non-combustible concealed spaces, dUILDING DIVISION
inclusive of interstitial (between floors) or attic spaces (with
slopes 2:12 or less). Each GL5608 sprinkler can be de-
signed for up to 16ft x 16ft (4.9m x 4.9m) spacing, providing
as much as 256 ft2 (23.8m2)of protection per sprinkler.
The GL5608 sprinkler meets the requirements of Under-
writers Laboratories UL 199H to comply with criteria for the
protection of combustible concealed spaces as described in -----
NFPA
—NFPA 13. <
When heat is absorbed, liquid within the glass bulb ex-
pands, increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule ex-
ceeds the strength of the glass causing the glass to shatter. GL 608
This results in water discharge which is distributed in an ap-
proved
V a!V
pattern.
•
APPLICATION SERIES GL—SS/IC UPRIGHT
The GL-SS/IC GL5608 can be designed for installation in SPRINKLER:
CPVC wet pipe sprinkler systems and steel wet pipe or
dry pipe sprinkler systems. The GL5608 can be used in The Globe GL-SS/IC GL5608 Interstitial Combustible Up-
concealed spaces having roof pitch of 2 in 12 or less con- right Sprinkler has been Listed to be used beyond the 36"
structed of wood truss, non-combustible bar joist, solid (914.4mm) height to a height of 60" (1.5m) to provide more
wood joists, or composite wood joists. The specific design functionality in installation specifically in areas where the
requirements for each type of piping system, and construc- height of the concealed space is both above and below the
tion materials can be found in the following sections of this height of 36" (914.4mm).
document.
NFPA 13 REQUIREMENTS TECHNICAL DATA
• cULus Listed for coverage areas up to 256 ft2 (23.8 m2)
Sprinklers shall be Listed for use in combustible concealed • 16 ft (4.9 m) maximum and 6 ft (1.8 m) minimum
spaces (with a slope not exceeding 2 in 12) with combus- Sprinkler Spacing
tible wood truss, wood joist construction, or bar joist con- • Maximum Open Space Height 60 in (1.5 m)
struction having a combustible upper surface and where the • Temperature Ratings- 175°F (79°C), 200°F (93°C)
depth of the space is less than 36" (914.4mm) from deck
to deck or with double wood joist and composite wood joist • Finish - Factory Bronze
construction with a maximum of 36" (914.4mm) between the • Water Working Pressure Rating - 175 psi (12 Bars)
top of the bottom joist and the bottom of the upper joist. • Maximum low temperature glass bulb rating -67°F
(-55° )
HYDRAULIC DESIGN AREA
• Materials of Construction, Frame - bronze, Deflector-
For all pipe and construction types the design area shall be brass, Screw- brass, Bulb seat- copper, Spring - nickel
1000 ft2 (92.9m2) except for Steel Pipe Systems with insula- alloy, Seal -teflon, Bulb -glass with alcohol based
tion filled joists, the design area shall be in accordance with solution, 3mm size
the Light Hazard Systems requirements of NFPA 13.
SPRINKLER COVERAGE
AREA
The coverage area of any single GL-SS/IC Sprinkler shall
. utilize the SxL rule for all sprinkler spacings (i.e. 16 x 10 =
160 sq. ft. X 0.10 = 16 gpm).
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 1 of 6
TABLE A GENERAL INSTALLATION ALLOWANCES
STEEL PIPING CPVC PIPING
OPEN SPACE HEIGHT TOTAL OPEN SPACE HEIGHT TOTAL COVERAGE DISTANCE
CONSTRUCTION TYPE ALLOWED ALLOWED AREA BETWEEN
SPACE SPACE Feet2 Meters2 SPRINKLERS
MINIMUM MAXIMUM HEIGHT' MINIMUM MAXIMUM HEIGHT' ( ) Feet(Meters)
Inches(mm) Inches(mm) Inches(mm) Inches(mm) Inches(mm) Inches(mm)
Unobstructed Wood Truss
6(152) 60(1524) 60(1524) 6(152) 60(1524) 60(1524) 1.8
Non-Combustible Bar Joist 6(1.8)
256(78.0) MINIMUM
Obstructed Wood Truss
6(152) 60(1524) 84(2134) N/A N/A N/A MAXIMUM 16(4.9)
Solid Wood Joist MAXIMUM
Insulation Filled Joist 6(152) 60(1524) 72(1829)2 6(152) 60(1524) 72(1829)"
NOTE:METRIC CONVERSIONS ARE APPROXIMATE.
WHEN TRUSS OR JOIST SPACE IS NONINSULATION FILLED, THE MAXIMUM ALLOWED TOP MEMBER DEPTH IS 12"(305 mm).
UP TO 12"(305mm)LOWER MEMBER SPACE.
TABLE B SPRINKLER SPECIFICATION AND APPROVALS
TEMPERATURE
RATING
NOMINAL MAX.LOW
STYLE SIN K" HAZARD' THREAD SPRINKLER FINISH PRESSURE TEMP.BULB cULus
MODEL FACTOR SIZE LENGTH 175°F 200°F RATING RATING
(79°C) (93°C)
UPRIGHT GL5608 5.6 LH 1/2"NPT 2 1/4" Factory X X 175 psi -67'F X
(80 metric) (15mm) (5.7cm) Bronze (12 Bars) (-55°C)
NOTE:
METRIC CONVERSIONS ARE APPROXIMATE.
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
OBSTRUCTION CRITERIA
For systems where the Globe "IC" Upright Sprinklers are the Globe "IC" Upright Sprinkler must use the obstruction
positioned with 15' (4.6m) or less between sprinklers the requirements for extended coverage upright sprinklers.
Globe "IC" Upright Sprinkler must use the obstruction re-
quirements for standard spray upright sprinklers. NOTE:
For systems where the Globe "IC" Upright Sprinklers are WEB MEMBERS AND GUSSETS SHALL NOT BE CONSIDERED OB-
STRUCTIONS PROVIDED THE MINIMUM 4-1/2 INCH LATERAL DISTANCE
positioned with greater than 15' (4.6m) between sprinklers REQUIRED BY THE SPECIFIC APPLICATION LISTING IS MAINTAINED.
CPVC DESIGN REQUIREMENTS
SYSTEM TYPE PARTITION REQUIREMENTS
The concealed space being protected must be broken up
Wet pipe system. into areas no greater than 1000 square feet either by full
height walls or by draft curtains.
ALLOWABLE CONSTRUCTION
TYPES DRAFT CURTAINS
• Unobstructed wood truss construction' When draft curtains are used they must be 8" (203.2mm)
in height or one third of the depth of the concealed
• Unobstructed bar joist construction' space, whichever is greater. Draft curtains must be
• Non-combustible insulation filled solid wood joist constructed of a material that will not allow for heat to
construction' escape through or above them.
• Non-combustible insulation filled composite wood joist
construction'
NOTE:
Upperjoist/truss cannot be more than 4"(101.6mm)in height.
2 The joist space in non-combustible insulation filled joist construction must be
completely filled with noncombustible insulation and secured in place by metal
wire netting to hold the insulation in place in the event of a fire.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 2 of 6
DEFLECTOR POSITION CPVC PIPE INSTALLATION
• 1 1/2 to 4 inches below the upper deck for unobstructed Horizontal runs of CPVC piping must be located with the
wood truss and bar joist constructions. Deflector must bottom of the piping not more than 6" (152.4mm) above the
be below the bottom of the top chord in trusses or below ceiling below or above ceiling insulation (if present), or one
bottom of joist. third depth of the combustible concealed space as mea-
- * 1 '/2 to 4 inches below the joists for non-combustible sured between the top surface of the ceiling below to the
insulation filled solid and composite wood joist bottom of the floor above or the bottom of the noncombus-
constructions. tible insulation above. Whichever is smaller.
_ * 4 '/2 inches away from trusses. When the lower joists are greater than 6"(152.4mm) in
height, CPVC piping is permitted to be attached directly to
CONCEALED SPACE SIZE the top of the joist. The CPVC piping can be used to supply
All spaces must have a minimum open space (from top of the Globe "IC" Upright Sprinklers as well as the sprinklers
Protecting the space below.
lower joist, cord, or truss to bottom of upper joist, cord, or
truss) of 6" (152.4mm). (see Figures 1 and 2) When using 1" (DN25) or larger pipe, a hanger must be
re-
Unobstructed wood truss and bar joist construction must not stralocated at the truss nearest a sprig for purposes of have a total bottom of floor to top of ceiling space height of (304.t. If using /b (D laterally19) piping, all sprigs methodsover 12"
more than 60" (1.5m). (see Figure 2) (304.8mm) must be braced using
described in the NFPA standards. Where CPVC piping must
Joist construction with noncombustible insulation in the be offset to go over an obstruction that will violate the hori-
upper deck must not have an open space (from top of lower zontal positioning requirements the CPVC piping must be
joist to bottom of upper joist) of greater than 60 inches in spaced not greater than 6 inches from that obstruction and
size. They must not have a total concealed space height of an additional Globe IC Upright Sprinkler must be provided
greater than 72" (1.8m). This allows for a maximum lower to protect the section of CPVC piping (see Figure 1 and 2).
joist space of 12" (304.8mm). CPVC piping must be kept a minimum of 18" (457.2mm) lat-
Solid wood joist and obstructed truss construction must erally away from heat sources such as heat pumps, fan mo-
not have an open space (from top of lower joist or truss to tors, and heat lamps.
bottom of upper joist or truss) of greater than 60"(1.5m) in
size. They must not have a total concealed space height of
greater than 84"(2.1m). The upper joist space must not be
greater than 12"(304.8mm) in depth (see Figure 2)
-.--4 1/2"(114mm)MIN.
38mm MIN. TO FACE OF WOOD TRUSS 6"(152mm)MAX.-••• f
1 172"
(38mm) OR TOP CHORD OF BAR JOIST FOR CPVC PIPE UPPER DECK
4"(102mm)MAX.
DEFLECTOR MUST BE L// /////////////////////////////////////////4j
BELOW BOTTOM OF TOP CHORD
TOP CHORD 4"(100mm)MAX.
FRAME ARMS MUST BE
i INSTALLED IN-LINE
WITH PIPE RUN �--6 (125mm)MAX.
GL560R L FOR CPVC PIPE
(MODEL IC SPRINKLER) 11
u,.0 U LI u
• 3• •� 0'i C• 6"(152mm)MIN.
12"(305mm)MIN. CI.CI o•CI"CI •
60"(1524mm)MAX. •❑ ❑ ❑I o`! �❑ • OBSTRUCTION
• 3•3.1 .11-
:1;30.3.iCST+
I
. .0 3• .'.0 3C.
0• O-o-o-io-o I
-
\' = \ \\ OPOF
CEILING COR �
DP
WHEN OFFSETTING CPVC PIPE OVER AN
"(152mm)MAX.ABOVE CEILING TO BOTTOM OF PIPE MUST BE INSTALLED DIRECTLY ON THE CPVC SPRINKLER
OR NON-COMBUSTIBLE CEILING INSULATION,OR 1/3 OVER THE OBSTRUCTION.
THE DEPTH OF CONCEALED SPACE(AS MEASURED
FROM TOP SURFACE OF CEILING TO BOTTOM SURFACE
OF DECK),OR WHICH EVER IS SMALLER.
FIGURE 1 : CPVC PIPE UNOBSTRUCTED WOOD TRUSS AND BAR
JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 3 of 6
INSULATION MUST BE HELD ON-COMBUSTIBLE
SOLID WOOD JOIST IN PLACE WITH METAL INSULATION
COMPOSITE WOOD JOIST
12"(305mm)MAX.DEPTH WIRE NETTING 12"(305rnm)MAX.DEPTH
WOOD TRUSS \\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\'`A\\\\\\\\\\\\\\`:Q\\`\\\\\\\\\\\\ UPPER DECK
TOP CHORD if /' %;/,r12"(305mm)MAX.DEPTH ��1 1/2"(38mm)MIN4"(102mm)MAXiI /� �j 0 _
A i. ../.10/1P
GL5608 •"(152mm)MAX.
II
n (MODEL IC SPRINKLER) FOR CPVC
FRAME ARMS MUST —�_,� •"(152mm)MAX. _
BE INSTALLED I FOR GPVC
IN-LINE WITH PIPE RUN I ■
6"(152mm)MIN. i F OBSTRUCTION 72
60"(1524mm)MAX. (1829mm)
MAX.
WOOD TRUSS D O D
WEB MEMEBER + O yj�0 0-W
,{1� •t CEILING
`lfi
ORME_1
BOTTOM OF PIPE/ I % MEW II
TOP OF CHORD `\\\\\\\\\\\\\\\\\\\\\\\CS"\ \\`\\\\\\\\\\\\\\\\\\\\\\\\\\\\"\\\
WHEN OFFSETTING CPVC PIPE OVER AN
OBSTRUCTION,A GL5608 MODEL'IC"SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE PIPE
OVER THE OBSTRUCTION.
6"(152mm)MAX.ABOVE CEILING OR NON-COMBUSTIBLE CEILING INSULATION.OR 1)3 THE DEPTH OF CONCEALED—
AREA(AS MEASURED FROM TOP SURFACE OF CEILING TO TOP SURFACE OF JOIST INSULATION ABOVE),OR WHICH
EVER IS SMALLER. WHEN THE LOWER JOIST IS GREATER THAN 6"(152mm)IN HEIGHT CPVC PIPING IS PERMITTED
TO BE ATTACHED DIRECTLY TO THE TOP OF THE JOIST.
FIGURE 2: CPVC PIPE NON-COMBUSTIBLE INSULATION FILLED
UPPER DECK SOLID WOOD, COMPOSITE WOOD JOIST, OR
WOOD TRUSS CONSTRUCTION
STEEL PIPING DESIGN REQUIREMENTS
SYSTEM TYPE DRAFT CURTAINS "
Wet pipe system and dry type systems. Draft Curtain for Unobstructed wood truss construction and
noncombustible bar joist construction must be 8" (203.2mm)
ALLOWABLE CONSTRUCTION in height or one third of the depth of the concealed space,
whichever is greater. Draft curtains must be constructed of
TYPES a material that will not allow for heat to escape through or
• Unobstructed wood truss construction' above them.
• Unobstructed bar joist construction' Draft Curtain for Obstructed wood truss and solid wood joist
• Solid wood joist construction2 construction must be 6" (152.4mm) in height or one third
of the depth of the concealed space, whichever is greater.
•
Obstructed wood truss construction2Draft curtains must be constructed of a material that will not
• Non-combustible insulation filled solid wood joist allow for heat to escape through or above them.
construction3
• Non-combustible insulation filled composite wood joist DEFLECTOR POSITION
construction3
• 1 1/2 to 4 inches below the upper deck for unobstructed
NOTE: wood truss and bar joist constructions. Deflector must
Upper joist/truss cannot be more than 4"(101.6mm)in height. be below the bottom of the top chord in trusses or below
2 Upper joist/truss cannot be more than 12"(304.8mm)in height. bottom of joist.
3 The joist space in non-combustible insulation filled joist construction must be
•
completely filled with noncombustible insulation and secured in place by metal 1 1/2 to 4 inches below the joists for noncombustible
wire netting to hold the insulation in place in the event of a fire. insulation filled solid and composite wood joist
construction.
PARTITION REQUIREMENTS • 1 1/2 to 2 inches below the joist or truss for solid wood
For unobstructed wood truss construction, unobstructed joist or obstructed truss construction.
bar joist construction, solid wood joist construction, and • 4 '/2 inches away from trusses
obstructed wood truss construction the concealed space
being protected must be broken up into areas no greater BLOCKING
than 1000 square feet either by full height walls or by draft For solid wood joist and obstructed wood truss construction
curtains.
blocking must be provided in each of the channels between
Noncombustible insulation filled joist construction is not re- the upper joists or trusses. The blocking must be located -
quired to be broken up into partitioned areas. where the draft curtains intersect the channels. The block-
ing must be installed to the full depth of the joists and be
installed as to not allow heat to escape through or above the
blocking. The blocking must be installed using either the -
same material as the joists or a noncombustible material.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 4 of 6
CONCEALED SPACE SIZE
All spaces must have a minimum open space (from top of size. They must not have a total concealed space height of
lower joist, cord, or truss to bottom of upper joist, cord, or greater than 72"(1.8m). This allows for a maximum lower
truss)of 6"(152.4mm) (see Figures 3,4, and 5). joist space of 12"(304.8mm) (see Figure 4).
Unobstructed wood truss and bar joist construction must not Solid wood joist and obstructed truss construction must
• have a total concealed space height of more than 60"(1.5m). not have an open space (from top of lower joist or truss to
(see Figure 3). bottom of upper joist or truss) of greater than 60"(1.5m) in
Joist construction with noncombustible insulation in the size. They must not have a total concealed space height of
- upper deck must not have an open space (from top of lower greater than 84"(2.1m). The upper joist space must not be
joist to bottom of upper joist) of greater than 60"(1.5m) in greater than 12"(304.8mm) in depth(see Figure 4).
4 1/2"(114mm)MIN.Ts UPPER DECK
FACE OF WOOD TRUSS OR 1 1/2"(38mm)MIN.
TOP CHORD OF BAR JOISTDEFLECTOR MUST BE
4"(100mm)MAX. BELOW BOTTOM OF TOP
��������`�`�`�`�����������`�����`�� CHORD
TOP CHORD % I e %
4"(100mm)MAX.
L5808 ;
(MODEL IC SPRINKLER)
FRAME ARMS MUST ��r� (1524mm)
BE INSTALLED MAX.
IN-LINE WITH PIPE RUN
11
6"
(15,2mm)
MIN.
1 2
% /-% EILING
FIGURE 3: STEEL PIPE UNOBSTRUCTED WOOD
TRUSS OR NON-COMBUSTIBLE BAR JOIST
CONSTRUCTION
2x FLOOR
SOLID WOOD JOISTS/OBSTRUCTED TRUSS UPPER DECK
16"(406mm)ON CENTER
-1---
i 1
12"(3005mm)
MAX / 1 1/2"(38mm)MIN.
r 2"(51mm)MAX.
L5608
FRAME ARMS MUST (MODEL IC SPRINKLER) 1 84"
BE INSTALLED I (2134mm)
IN-LINE WITH PIPE RUN : -Y- MAX.
I
I 6"(152mm)MIN.
EILING
60"(1524mm) MAX.
FRAMING
MINIM
%
i
CEILING
FIGURE 4: STEEL PIPE OBSTRUCTED WOOD TRUSS
OR SOLID WOOD JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 5 of 6
UPPER DECK NON-COMBUSTIBLE
2x FLOOR SOLID INSULATION COMPOSITE WOOD JOIST
WOOD JOIST
Itt✓irrlltltl Ht:71111f11r11rr,,,lf1 irli AY4n SIrtt 11 tVoii 7
u�%uuuuuu/luuu���u�/,�uu�uuu��'�.u��u��ur, ul
wi���rlrlrlrlrlt�r�rlrlti 1�rlt�rlrlrlt�tlr� erlld ItIrIrltltnrltlrltI,IIem erltltlw%11111 11/2°(38mm)MIN. -
111�/rrr/r1/t/H1t//tlttttt/ttt /ttt ttltfttl PI t11111M11) 'ft F 4"(102mm)MAX.
u. a,uu�uu�,. I,,,,,u,1,1,,,u%111u11uu141.w8uu,111,014”
EERErtl.rtt.tr:VLrrrr.tr,,11111/tr.reJ./J.t.G./,J..11111/.rrr.Nhoh,*
INSULATION MUST BE HELD L5608
IN PLACE WITH METAL _ (MODEL IC SPRINKLER) _
WIRE NETTING N. r i 6"(152mm)MIN. "
IN ill-Y- 60"(1524mm)MAX.
FRAME ARMS MUST
BE INSTALLED
I
72"
IN-LINE WITH PIPE RUN (1629mm)
MAX.
-Y-1, CEILING FRAMING 1
.\\\\`\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\C\\\\\\
CEILING
FIGURE 5: STEEL PIPE NON-COMBUSTIBLE
INSULATION FILLED UPPER DECK SOLID WOOD OR
COMPOSITE WOOD JOIST CONSTRUCTION
ORDERING INFORMATION GLOBE® PRODUCT
Quantity • SIN • Style • Orifice *Thread Size WARRANTY
Temperature • Finishes • Desired Quantity Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or work-
Wrench - P/N 325390 manship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Technical Support
Standish, MI 48658 1-800-248-0278 www.globesprinkler.com ,.•
.
Ph. 989-846-4583 techservice@globesprinkler.com :'
111.4
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 6 of 6
r
BE`1J1/ 4077 Airpark Dr. Standish, MI 48658•989-846-4583•www.globesprinkler.com
FIRE SPRINKLER CORPORATION Technical Support•989-414-2600•techservice@globesprinkler.com
SPECIFIC APPLICATION MODEL "IC"
INTERSTITIAL COMBUSTIBLE CONCEALED SPACE
UPRIGHT SPRINKLER GL5608 RECEIVED
GENERAL DESCRIPTION JAN 7 2020
The Globe Series GL-SS/IC GL5608 Interstitial Combustible
Space Sprinkler is a quick response, upright, specific appli- CITY OF TIGARD
cation sprinkler designed to provide protection of light haz- "T 3UILDING DIVISION
and combustible and non-combustible concealed spaces,
inclusive of interstitial (between floors) or attic spaces (with
slopes 2:12 or less). Each GL5608 sprinkler can be de-
signed for up to 16ft x 16ft (4.9m x 4.9m) spacing, providing
as much as 256 ft2 (23.8m2)of protection per sprinkler.
The GL5608 sprinkler meets the requirements of Under-
writers Laboratories UL 199H to comply with criteria for the
protection of combustible concealed spaces as described in 740-
NFPA 13. ' °
When heat is absorbed, liquid within the glass bulb ex-
pands, increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule ex-
-ceeds the strength of the glass causing the glass to shatter. GL 5608
-This results in water discharge which is distributed in an ap-
proved
V .!V
pattern.
APPLICATION SERIES GL-SS/IC UPRIGHT
The GL-SS/IC GL5608 can be designed for installation in SPRINKLER:
CPVC wet pipe sprinkler systems and steel wet pipe or
dry pipe sprinkler systems. The GL5608 can be used in The Globe GL-SS/IC GL5608 Interstitial Combustible Up-
concealed spaces having roof pitch of 2 in 12 or less con- right Sprinkler has been Listed to be used beyond the 36"
structed of wood truss, non-combustible bar joist, solid (914.4mm) height to a height of 60" (1.5m) to provide more
wood joists, or composite wood joists. The specific design functionality in installation specifically in areas where the
requirements for each type of piping system, and construc- height of the concealed space is both above and below the
tion materials can be found in the following sections of this height of 36" (914.4mm).
document.
NFPA 13 REQUIREMENTS TECHNICAL DATA
• cULus Listed for coverage areas up to 256 ft2 (23.8 m2)
Sprinklers shall be Listed for use in combustible concealed • 16 ft(4.9 m) maximum and 6 ft (1.8 m) minimum
spaces (with a slope not exceeding 2 in 12) with combus- Sprinkler Spacing
tible wood truss, wood joist construction, or bar joist con- • Maximum Open Space Height 60 in (1.5 m)
struction having a combustible upper surface and where the • Temperature Ratings- 175°F (79°C), 200°F (93°C)
depth of the space is less than 36" (914.4mm) from deck
to deck or with double wood joist and composite wood joist Finish• Factory Bronze
construction with a maximum of 36" (914.4mm) between the • Water Working Pressure Rating - 175 psi (12 Bars)
top of the bottom joist and the bottom of the upper joist. • Maximum low temperature glass bulb rating -67°F
(-55°C)
HYDRAULIC DESIGN AREA • Materials of Construction, Frame - bronze, Deflector-
For all pipe and construction types the design area shall be brass, Screw- brass, Bulb seat- copper, Spring - nickel
1000 ft2 (92.9m2)except for Steel Pipe Systems with insula- alloy, Seal -teflon, Bulb -glass with alcohol based
tion filled joists, the design area shall be in accordance with solution, 3mm size
the Light Hazard Systems requirements of NFPA 13.
SPRINKLER COVERAGE
AREA
The coverage area of any single GL-SS/IC Sprinkler shall
utilize the SxL rule for all sprinkler spacings (i.e. 16 x 10 =
160 sq. ft. X 0.10 = 16 gpm).
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 1 of 6
r.
TABLE A GENERAL INSTALLATION ALLOWANCES
STEEL PIPING CPVC PIPING
OPEN SPACE HEIGHT TOTAL OPEN SPACE HEIGHT TOTAL COVERAGE DISTANCE
CONSTRUCTION TYPE ALLOWED ALLOWED AREA BETWEEN
MINIMUM MAXIMUM SPACE MINIMUM MAXIMUM SPACE Feet2(Meters2) SPRINKLERS
Inches(mm) Inches(mm) HEIGHT' Inches(mm) Inches(mm) HEIGHT' Feet(Meters)
Inches(mm) Inches(mm)
Unobstructed Wood Truss
• 6(152) 60(1524) 60(1524) 6(152) 60(1524) 60(1524)
Non-Combustible Bar Joist 6(1.8)
Obstructed Wood Truss 256(78.0) MINIMUM
• 6(152) 60(1524) 84(2134) N/A N/A N/A MAXIMUM 16(4.9)
Solid Wood Joist MAXIMUM
Insulation Filled Joist 6(152) 60(1524) 72(1829)2 6(152) 60(1524) 72(1829)"
NOTE:METRIC CONVERSIONS ARE APPROXIMATE.
WHEN TRUSS OR JOIST SPACE IS NONINSULATION FILLED, THE MAXIMUM ALLOWED TOP MEMBER DEPTH IS 12"(305 mm).
2 UP TO 12"(305mm)LOWER MEMBER SPACE.
TABLE B SPRINKLER SPECIFICATION AND APPROVALS
TEMPERATURE
RATING
NOMINAL MAX.LOW
SINTHREAD SPRINKLER PRESSURE
STYLE MODEL K" HAZARD' SIZE LENGTH FINISH ° RATING TEMP.BULB cULus
FACTOR 175 F 200°F RATING
(79°C) (93°C)
UPRIGHT GL5608 5.6 LH 1/2"NPT 2 1/4" Factory x X 175 psi -67°F X
(80 metric) (15mm) (5.7cm) Bronze (12 Bars) (-55°C)
NOTE:
METRIC CONVERSIONS ARE APPROXIMATE.
2 SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
OBSTRUCTION CRITERIA
For systems where the Globe "IC" Upright Sprinklers are the Globe "IC" Upright Sprinkler must use the obstruction
positioned with 15' (4.6m) or less between sprinklers the requirements for extended coverage upright sprinklers.
Globe "IC" Upright Sprinkler must use the obstruction re-
quirements for standard spray upright sprinklers. NOTE:
For where the Globe "IC" Upright Sprinklers are WEB MEMBERS AND GUSSETS SHALL NOT BE CONSIDERED O8-
Fpor systemsed greater than (4.6m)C" beteen sprinklers STRUCTIONS PROVIDED THE MINIMUM 4-1/2 INCH LATERAL DISTANCE
REQUIRED BY THE SPECIFIC APPLICATION LISTING IS MAINTAINED.
CPVC DESIGN REQUIREMENTS
SYSTEM TYPE PARTITION REQUIREMENTS
The concealed space being protected must be broken up
Wet pipe system. into areas no greater than 1000 square feet either by full
height walls or by draft curtains.
ALLOWABLE CONSTRUCTION DRAFT CURTAINS
TYPES When draft curtains are used they must be 8" (203.2mm)
• Unobstructed wood truss construction in height or one third of the depth of the concealed
• Unobstructed bar joist construction' space, whichever is greater. Draft curtains must be
• Non-combustible insulation filled solid wood joist constructed of a material that will not allow for heat to
construction2 escape through or above them.
• Non-combustible insulation filled composite wood joist
construction2
NOTE:
Upper joist/truss cannot be more than 4"(101.6mm)in height.
2 The joist space in non-combustible insulation filled joist construction must be
completely filled with noncombustible insulation and secured in place by metal
wire netting to hold the insulation in place in the event of a fire.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 2 of 6
r A,
DEFLECTOR POSITION CPVC PIPE INSTALLATION
• 1 1/2 to 4 inches below the upper deck for unobstructed Horizontal runs of CPVC piping must be located with the
wood truss and bar joist constructions. Deflector must bottom of the piping not more than 6" (152.4mm) above the
be below the bottom of the top chord in trusses or below ceiling below or above ceiling insulation (if present), or one
bottom of joist. third depth of the combustible concealed space as mea-
• 1 1/2 to 4 inches below the joists for non-combustible sured between the top surface of the ceiling below to the
insulation filled solid and composite wood joist bottom of the floor above or the bottom of the noncombus-
constructions. tible insulation above. Whichever is smaller.
• 41/2 inches away from trusses. When the lower joists are greater than 6"(152.4mm) in
' height, CPVC piping is permitted to be attached directly to
CONCEALED SPACE SIZE the top of the joist. The CPVC piping can be used to supply
All spaces must have a minimum open space (from top of the Globe "IC" Upright Sprinklers as well as the sprinklers
lower joist, cord, or truss to bottom of upper joist, cord, or protecting the space below.
truss)of 6" (152.4mm). (see Figures 1 and 2) When using 1" (DN25) or larger pipe, a hanger must be
Unobstructed wood truss and bar joist construction must not located at the truss nearest a sprig for purposes of re-
have a total bottom of floor to top of ceiling space height of (304.t. If using /" (DN19) piping, all sprigs over 12"
more than 60" (1.5m). (see Figure 2) (304.8mm) must be laterally braced using methods
described in the NFPA standards. Where CPVC piping must
Joist construction with noncombustible insulation in the be offset to go over an obstruction that will violate the hori-
upper deck must not have an open space (from top of lower zontal positioning requirements the CPVC piping must be
joist to bottom of upper joist) of greater than 60 inches in spaced not greater than 6 inches from that obstruction and
size. They must not have a total concealed space height of an additional Globe IC Upright Sprinkler must be provided
greater than 72" (1.8m). This allows for a maximum lower to protect the section of CPVC piping (see Figure 1 and 2).
joist space of 12" (304.8mm). CPVC piping must be kept a minimum of 18" (457.2mm) lat-
Solid wood joist and obstructed truss construction must erally away from heat sources such as heat pumps, fan mo-
not have an open space (from top of lower joist or truss to tors, and heat lamps.
bottom of upper joist or truss) of greater than 60"(1.5m) in
size. They must not have a total concealed space height of
greater than 84"(2.1m). The upper joist space must not be
greater than 12"(304.8mm) in depth (see Figure 2)
• �4 1/2"(114mm)MIN.
1 1/2"(38mm)MIN. TO FACE OF WOOD TRUSS 6"(152mm)MAX-.- •�-
4" (38 m)MAX. OR TOP CHORD OF BAR JOIST FOR CPVC PIPE UPPER DECK
DEFLECTOR MUST AE V/ ///77777777/777/77 W /////////////,//'ate////!/97 I
BELOW BOTTOM OF TOP CHORD
TOP CHORD 4"(100mm)MAX.
FRNSTALLAME AED IRMS
N-MUST
LINE BE S - -
I
WITH PIPE RUN
GL5608 "(125mm)MAX.
FOR CPVC PIPE
(MODEL IC SPRINKLER)
.u.0 u u u,n.I,
�["� ���V } 6'(152mm)MIN.
12"(305mm)MIN. 0 00 0 o,�'`�C
60"(1524mm)MAX. 3 C/73 C- C3LV S V
C jCI DO�^��p O�C OBSTRUCTION
)0C.l3(D`1 ro.,309%
D D D D. C
�•6 re -D-o-D9 DSD:` ``\
\� I \\ \• \\��JJJJ \\\\
r
EILING `TOP OF CORD7 ii ii ii ii .iiI l/>l////j/
WHEN OFFSETTING CPVC PIPE OVER AN
"(152mm)MAX.ABOVE CEILING TO BOTTOM OF PIPE OBSTRUCTION A GL5608 MODEL"IC"SPRINKLER
OR NON-COMBUSTIBLE CEILING INSULATION,OR 1/3 MUST BE INSTALLED DIRECTLY ON THE CPVC
OVER THE OBSTRUCTION.
THE DEPTH OF CONCEALED SPACE(AS MEASURED
FROM TOP SURFACE OF CEILING TO BOTTOM SURFACE
OF DECK),OR WHICH EVER IS SMALLER.
FIGURE 1 : CPVC PIPE UNOBSTRUCTED WOOD TRUSS AND BAR
JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 3 of 6
INSULATION MUST BE HELD ON-COMBUSTIBLEI
SOLID WOOD JOIST IN PLACE WITH METAL NSULATION COMPOSITE WOOD JOIST
12"(305mm)MAX.DEPTH WIRE NETTING 12"(305mm)MAX.DEPTH
WOOD
TRUSS
%�������%4707A®A� � ®��, AAAA ' ��VA UPPER DECK
i
12"(305mm)MAX.DEPTH ; `ftt �"
1 1/2"(38mm) „4,4
MIN. ) 5'
41
4"(102mm "1v)MAX. � � 4 / '`11',"•"'
GL5608 ”(152mm)MAX.
(MODEL IC SPRINKLER) FOR CPVC
FRAME ARMS MUST
"(152mm)MAX.
BE INSTALLED FOR CPVC
IN-LINE WITH PIPE RUN
6"(152mm)MIN. OBSTRUCTION 1829mm
60"(1524mm)MAX. ( )
MAX.
WOOD TRUSS
WEB MEMEBER
CEILING
BOTTOM OF PIPE/J a° a
TOP OF CHORD
WHEN OFFSETTING CPVC PIPE OVER AN
OBSTRUCTION,A GL5608 MODEL'IC"SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE PIPE
OVER THE OBSTRUCTION.
6"(152mm)MAX.ABOVE CEILING OR NON-COMBUSTIBLE CEILING INSULATION.OR 1/3 THE DEPTH OF CONCEALED-
AREA(AS MEASURED FROM TOP SURFACE OF CEILING TO TOP SURFACE OF JOIST INSULATION ABOVE),OR WHICH
EVER IS SMALLER. WHEN THE LOWER JOIST IS GREATER THAN 6"(152mm)IN HEIGHT CPVC PIPING IS PERMITTED
TO BE ATTACHED DIRECTLY TO THE TOP OF THE JOIST.
FIGURE 2: CPVC PIPE NON-COMBUSTIBLE INSULATION FILLED
UPPER DECK SOLID WOOD, COMPOSITE WOOD JOIST, OR
WOOD TRUSS CONSTRUCTION
STEEL PIPING DESIGN REQUIREMENTS
SYSTEM TYPE DRAFT CURTAINS
Wet pipe system and dry type systems. Draft Curtain for Unobstructed wood truss construction and
noncombustible bar joist construction must be 8" (203.2mm)
ALLOWABLE CONSTRUCTION in height or. one third of the depth of the concealed space,
whichever is greater. Draft curtains must be constructed of
TYPES a material that will not allow for heat to escape through or
• Unobstructed wood truss construction' above them.
• Unobstructed bar joist construction' Draft Curtain for Obstructed wood truss and solid wood joist
• Solid wood joist construction2 construction must be 6" (152.4mm) in height or one third
• Obstructed wood truss construction2 of the depth of the concealed space, whichever is greater.
Draft curtains must be constructed of a material that will not
• Non-combustible insulation filled solid wood joist allow for heat to escape through or above them.
construction3
• Non-combustible insulation filled composite wood joist DEFLECTOR POSITION
construction3 • 1 1/2 to 4 inches below the upper deck for unobstructed
NOTE: wood truss and bar joist constructions. Deflector must
Upper joist/truss cannot be more than 4"(101.6mm)in height. be below the bottom of the top chord in trusses or below
2 Upper joist/truss cannot be more than 12"(304.8mm)in height. bottom of joist.
3 The joist space in non-combustible insulation filled joist construction must be
completely filled with noncombustible insulation and secured in place by metal •
1 1/2 to 4 inches below the joists for noncombustible
wire netting to hold the insulation in place in the event of a fire. insulation filled solid and composite wood joist
construction.
PARTITION REQUIREMENTS • 1 1/2 to 2 inches below the joist or truss for solid wood
For unobstructed wood truss construction, unobstructed joist or obstructed truss construction.
bar joist construction, solid wood joist construction, and • 4 '/2 inches away from trusses
obstructed wood truss construction the concealed space
being protected must be broken up into areas no greater BLOCKING
than 1000 square feet either by full height walls or by draft For solid woodjoist and obstructed wood truss construction
curtains. blocking must be provided in each of the channels between
Noncombustible insulation filled joist construction is not re- the upper joists or trusses. The blocking must be located _
quired to be broken up into partitioned areas. where the draft curtains intersect the channels. The block-
ing must be installed to the full depth of the joists and be
installed as to not allow heat to escape through or above the
blocking. The blocking must be installed using either the -
same material as the joists or a noncombustible material.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 4 of 6
CONCEALED SPACE SIZE
All spaces must have a minimum open space (from top of size. They must not have a total concealed space height of
lower joist, cord, or truss to bottom of upper joist, cord, or greater than 72"(1.8m). This allows for a maximum lower
truss) of 6"(152.4mm) (see Figures 3, 4, and 5). joist space of 12"(304.8mm) (see Figure 4).
Unobstructed wood truss and bar joist construction must not Solid wood joist and obstructed truss construction must
. have a total concealed space height of more than 60"(1.5m). not have an open space (from top of lower joist or truss to
(see Figure 3). bottom of upper joist or truss) of greater than 60"(1.5m) in
Joist construction with noncombustible insulation in the size. They must not have a total concealed space height of
. upper deck must not have an open space (from top of lower greater than 84''(2.1m). The upper joist space must not be
joist to bottom of upper joist) of greater than 60"(1.5m) in greater than 12"(304.8mm) in depth(see Figure 4).
4 1,2"(114mm)MIN.TO UPPER DECK
FACE OF WOOD TRUSS OR
TOP CHORD OF BAR JOIST 1 1/2"(38mm)MIN. DEFLECTOR MUST BE
4"(100mm)MAX. BELOW BOTTOM OF TOP
alh. `MN& IN CHORD
HORD 9
4"(100mof
TOP C MAX / 4 g
_ a
i .." 1' GL5608 ' -
(MODEL IC SPRINKLER) IIK '
FRAME ARMS MUST - ��r� (1524mm)
BE INSTALLED MAX.
IN-LINE WITH PIPE RUN
6"
052.)MIN.
III
/ i 4 CEILING
iiimmommoimmiiiimmoi
FIGURE 3: STEEL PIPE UNOBSTRUCTED WOOD
TRUSS OR NON-COMBUSTIBLE BAR JOIST
CONSTRUCTION
2x FOR
SOLLOID WOOD JOISTS/OBSTRUCTED TRUSS UPPER DECK
16"(406mm)ON CENTER
P
12"(305— Q
MAX. % 1 1/2"(3Bmm)MIN.i %
mm) 1
2"(51 mm)MAX.
L5608
FRAME ARMS MUST -- (MODEL IC SPRINKLER) . 84"
BE INSTALLED t (2134mm)
IN-LINE WITH PIPE RUN III MAX.
I
I 6"(152mm)MIN.
60"(1524mm)MAX.
FILING
—Y-J FRAMING
:AQAAAAAxVVAVVVVVVV\VAAAAAVAVVVVVVxxxxAVAAAAC\VAVVV.,,xx xxxx,
CEILING
FIGURE 4: STEEL PIPE OBSTRUCTED WOOD TRUSS
OR SOLID WOOD JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 5 of 6
UPPER DECK NON-COMBUSTIBLE
2x FLOOR SOLID INSULATION COMPOSITE WOOD JOIST
WOOD JOIST
VNANANNANANAN.ANNN.................................
W1'%iLtitititAtdiIY:PEIArddlbr:49 atiritu 'ddirAriri6r0 :1
Wiririt elt/tltltltititltl/rlMitMItM P/WiWIWAYMAYMMln�rlti r1 1/2"(38mm)MIN.
ht.w Inflttitltit/t/tlt r tntrrtttIt/t,IItit/r/tit/rir/rlt/111,r/t/r/rlrlt/rlr/r/r/r1t1171rIt/r/ F 4"(102mm)MAX.
• r.r.rrr.t.rtttta/,.........../r.r.rrr.�.trcrr.J��.rtrrrrrrr:/:.r
INSULATION MUST BE HELD L5608
IN PLACE WITH METAL _ (MODEL IC SPRINKLER)
WIRE NETTING t 6"(152mm)MIN. •
ill-Y- 60"(1524mm)MAX.
FRAME ARMS MUST
BE INSTALLED 72"
IN-LINE WITH PIPE RUN ' (1829mm)
MAX.
CEILING FRAMING
/-
VNA$ `.A A A A AANANA A A A A A A'NANSCVANAVONANANANAANNSNA
FILING
FIGURE 5: STEEL PIPE NON-COMBUSTIBLE
INSULATION FILLED UPPER DECK SOLID WOOD OR
COMPOSITE WOOD JOIST CONSTRUCTION
ORDERING INFORMATION GLOBE® PRODUCT
Quantity • SIN • Style • Orifice •Thread Size WARRANTY
Temperature • Finishes • Desired Quantity Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or work-
Wrench - P/N 325390 manship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Technical Support
Standish, MI 48658 1-800-248-0278 www.globesprinkler.com 41
Ph. 989-846-4583 techservice@globesprinkler.com
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 6 of 6
t t
7.71;„ BE
4077 Airpark Dr. Standish, MI 48658•989-846-4583•www.globespnnkier.com
FIRE SPRINKLER CORPORATION Technical Support•989-414-2600•techservice@globesprinkler.com
SPECIFIC APPLICATION MODEL "IC"
INTERSTITIAL COMBUSTIBLE CONCEALED SPACE
UPRIGHT SPRINKLER GL5608
GENERAL DESCRIPTION
The Globe Series GL-SS/IC GL5608 Interstitial Combustible
Space Sprinkler is a quick response, upright, specific appli-
cation sprinkler designed to provide protection of light haz-
ard
az and combustible and non-combustible concealed spaces,
inclusive of interstitial (between floors) or attic spaces (with
slopes 2:12 or less). Each GL5608 sprinkler can be de-
signed for up to 16ft x 16ft (4.9m x 4.9m) spacing, providing
as much as 256 ft2 (23.8m2)of protection per sprinkler.
The GL5608 sprinkler meets the requirements of Under- •11
writers Laboratories UL 199H to comply with criteria for the - e.
protection of combustible concealed spaces as described in
NFPA 13.
When heat is absorbed, liquid within the glass bulb ex-
pands, increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule ex-
ceeds the strength of the glass causing the glass to shatter. GL Cc08
This results in water discharge which is distributed in an ap-
proved
V .!V
pattern.
APPLICATION SERIES GL-SS/IC UPRIGHT
The GL-SS/IC GL5608 can be designed for installation in SPRINKLER:
CPVC wet pipe sprinkler systems and steel wet pipe or
dry pipe sprinkler systems. The GL5608 can be used in The Globe GL-SS/IC GL5608 Interstitial Combustible Up-
concealed spaces having roof pitch of 2 in 12 or less con- right Sprinkler has been Listed to be used beyond the 36"
structed of wood truss, non-combustible bar joist, solid (914.4mm) height to a height of 60" (1.5m) to provide more
wood joists, or composite wood joists. The specific design functionality in installation specifically in areas where the
requirements for each type of piping system, and construc- height of the concealed space is both above and below the
tion materials can be found in the following sections of this height of 36" (914.4mm).
document. TECHNICAL DATA
NFPA 13 REQUIREMENTS • cULus Listed for coverage areas up to 256 ft2 (23.8 m2)
Sprinklers shall be Listed for use in combustible concealed • 16 ft (4.9 m) maximum and 6 ft (1.8 m) minimum
spaces (with a slope not exceeding 2 in 12) with combus- Sprinkler Spacing
tible wood truss, wood joist construction, or bar joist con- • Maximum Open Space Height 60 in (1.5 m)
struction having a combustible upper surface and where the • Temperature Ratings- 175°F (79°C), 200°F (93°C)
depth of the space is less than 36" (914.4mm) from deck
to deck or with double wood joist and composite wood joist • Finish - Factory Bronze
construction with a maximum of 36" (914.4mm) between the • Water Working Pressure Rating - 175 psi (12 Bars)
top of the bottom joist and the bottom of the upper joist. • Maximum low temperature glass bulb rating -67°F
(-55°C)
HYDRAULIC DESIGN AREA
• Materials of Construction, Frame- bronze, Deflector-
For all pipe and construction types the design area shall be brass, Screw- brass, Bulb seat- copper, Spring - nickel
1000 ft2 (92.9m2) except for Steel Pipe Systems with insula- alloy, Seal -teflon, Bulb - glass with alcohol based
tion filled joists, the design area shall be in accordance with solution, 3mm size
the Light Hazard Systems requirements of NFPA 13.
SPRINKLER COVERAGE
• AREA
The coverage area of any single GL-SS/IC Sprinkler shall
utilize the SxL rule for all sprinkler spacings (i.e. 16 x 10 =
160 sq. ft. X 0.10 = 16 gpm).
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 1 of 6
t t
TABLE A GENERAL INSTALLATION ALLOWANCES
STEEL PIPING CPVC PIPING
OPEN SPACE HEIGHT TOTAL OPEN SPACE HEIGHT TOTAL COVERAGE DISTANCE
CONSTRUCTION TYPE ALLOWED ' ALLOWED AREA BETWEEN
MINIMUM MAXIMUM SPACE MINIMUM MAXIMUM SPACE Fee(Meters2) SPRINKLERS
Inches(mm) Inches(mm) HEIGHT' Inches(mm) Inches(mm) HEIGHT' Feet(Meters)
Inches(mm) Inches(mm)
Unobstructed Wood Truss
6(152) 60(1524) 60(1524) 6(152) 60(1524) 60(1524) 6(1.8)
Non-Combustible Bar Joist
256(78.0) MINIMUM
Obstructed Wood Truss
6(152) 60(1524) 84(2134) N/A N/A N/A MAXIMUM 16(4.9)
Solid Wood Joist
MAXIMUM
Insulation Filled Joist 6(152) 60(1524) 72(1829)2 6(152) 60(1524) 72(1829)"
NOTE:METRIC CONVERSIONS ARE APPROXIMATE.
WHEN TRUSS OR JOIST SPACE IS NONINSULATION FILLED. THE MAXIMUM ALLOWED TOP MEMBER DEPTH IS 12"(305 mm).
UP TO 12"(305mm)LOWER MEMBER SPACE.
TABLE B SPRINKLER SPECIFICATION AND APPROVALS
TEMPERATURE
RATING
NOMINAL MAX.LOW
SIN THREAD SPRINKLER PRESSURE
STYLE MODEL "K" HAZARD' SIZE LENGTH FINISH ° ° RATING TEMP. BULB cULus
FACTOR 175 F 200 F RATING
(79°C) (93°C)
UPRIGHT GL5608 5.6 LH 1/2"NPT 2 1/4° Factory X X 175 psi -67°F X
(80 metric) (15mm) (5.7cm) Bronze (12 Bars) (-55°C)
NOTE:
METRIC CONVERSIONS ARE APPROXIMATE.
2 SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
OBSTRUCTION CRITERIA
For systems where the Globe "IC" Upright Sprinklers are the Globe "IC" Upright Sprinkler must use the obstruction
positioned with 15' (4.6m) or less between sprinklers the requirements for extended coverage upright sprinklers.
Globe "IC" Upright Sprinkler must use the obstruction re-
quirements for standard spray upright sprinklers. NOTE:
OB-
For where the Globe "IC" Upright Sprinklers are WEB MEMBERS AND GUSSETS SHALL NOT BE CONSIDERED Fosystemsed greater than C"(4.6m) between sprinklersae STRUCTIONSPROVIDEDTHEMINIMUM4-1/2INCHLATERALDISTANCE
REQUIRED BY THE SPECIFIC APPLICATION LISTING IS MAINTAINED.
CPVC DESIGN REQUIREMENTS
SYSTEM TYPE PARTITION REQUIREMENTS
The concealed space being protected must be broken up
Wet pipe system. into areas no greater than 1000 square feet either by full
height walls or by draft curtains.
ALLOWABLE CONSTRUCTION
TYPES DRAFT CURTAINS
• Unobstructed wood truss construction' When draft curtains are used they must be 8" (203.2mm)
in height or one third of the depth of the concealed
• Unobstructed bar joist construction' space, whichever is greater. Draft curtains must be
• Non-combustible insulation filled solid wood joist constructed of a material that will not allow for heat to
construction2 escape through or above them.
• Non-combustible insulation filled composite wood joist
construction2
NOTE:
Upper joist/truss cannot be more than 4"(101.6mm)in height.
2 The joist space in non-combustible insulation filled joist construction must be
completely filled with noncombustible insulation and secured in place by metal
wire netting to hold the insulation in place in the event of a fire.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 2 of 6
DEFLECTOR POSITION CPVC PIPE INSTALLATION
• 1 1/2 to 4 inches below the upper deck for unobstructed Horizontal runs of CPVC piping must be located with the
wood truss and bar joist constructions. Deflector must bottom of the piping not more than 6" (152.4mm) above the
be below the bottom of the top chord in trusses or below ceiling below or above ceiling insulation (if present), or one
bottom of joist. third depth of the combustible concealed space as mea-
• 1 1/2 to 4 inches below the joists for non-combustible sured between the top surface of the ceiling below to the
insulation filled solid and composite wood joist bottom of the floor above or the bottom of the noncombus-
constructions. tible insulation above. Whichever is smaller.
• 4 1/2 inches away from trusses. When the lower joists are greater than 6"(152.4mm) in
height, CPVC piping is permitted to be attached directly to
CONCEALED SPACE SIZE the top of the joist. The CPVC piping can be used to supply
All spaces must have a minimum open space (from top of the Globe "IC" Upright Sprinklers as well as the sprinklers
lower joist, cord, or truss to bottom of upper joist, cord, or protecting the space below.
truss) of 6" (152.4mm). (see Figures 1 and 2) When using 1" (DN25) or larger pipe, a hanger must be
Unobstructed wood truss and bar joist construction must not located at the truss nearest a sprig for purposes of re-
have a total bottom of floor to top of ceiling space height of must be laterally bt. If using /" (DN19) piping,raaced using methods
all sprigs over 12"
more than 60" (1.5m). (see Figure 2) (304.8mm)
described in the NFPA standards. Where CPVC piping must
Joist construction with noncombustible insulation in the be offset to go over an obstruction that will violate the hori-
upper deck must not have an open space (from top of lower zontal positioning requirements the CPVC piping must be
joist to bottom of upper joist) of greater than 60 inches in spaced not greater than 6 inches from that obstruction and
size. They must not have a total concealed space height of an additional Globe IC Upright Sprinkler must be provided
greater than 72" (1.8m). This allows for a maximum lower to protect the section of CPVC piping (see Figure 1 and 2).
joist space of 12" (304.8mm). CPVC piping must be kept a minimum of 18" (457.2mm) lat-
Solid wood joist and obstructed truss construction must erally away from heat sources such as heat pumps, fan mo-
not have an open space (from top of lower joist or truss to tors, and heat lamps.
bottom of upper joist or truss) of greater than 60"(1.5m) in
size. They must not have a total concealed space height of
greater than 84"(2.1m). The upper joist space must not be
greater than 12"(304.8mm) in depth (see Figure 2)
�4 1/2"(114mm)MIN.
1 1/2"(38mm)MIN. TO FACE OF WOOD TRUSS 6"(152mm)MAX.—.- -� UPPER DECK
OR TOP CHORD OF BAR JOIST FOR CPVC PIPE
4"(102mm)MAX.
DEFLECTOR BOTTOMT \ ///////////////,z '///,
BELOW
TOP CHORD TOP CHORDS`\\
4"(100mm)MAX.
FRAME ARMS MUST BE
INSTALLED IN-LINE
WITH PIPE RUN �-6 (125mm)MAX.
(MODEL IC SPRINKLER) u [I 1 FOR CPVC PIPE
LLJJ u_u_ut,u_u_= 1
�[�57[�[ac
6"(152mm)MIN.
12"(305mm)MIN. _o_o_o,.o�o-c
60"(1524mm)MAX. 3c 3c
o'o 0 0 ❑_[ OBSTRUCTION
DCEJC
t;a)K ,7
-0:0-0"0 O_C
30 3C 30C 3C
ipm =°- - -„°,- -
• -
\� CEILING `TOP OFM OF CORD PIPE/
i/./. ���������7���� �I //7l-////7ii// //��///i// l>/1
WHEN OFFSETTING CPVC PIPE OVER AN
”(152mm)MAX.ABOVE CEILING TO BOTTOM OF PIPE
OBSTRUCTION,
BE INSTAL ED D RECTTLY ON THE CPVC ER
OR NON-COMBUSTIBLE CEILING INSULATION,OR 1/3 OVER THE OBSTRUCTION.
THE DEPTH OF CONCEALED SPACE(AS MEASURED
FROM TOP SURFACE OF CEILING TO BOTTOM SURFACE
OF DECK),OR WHICH EVER IS SMALLER.
FIGURE 1: CPVC PIPE UNOBSTRUCTED WOOD TRUSS AND BAR
JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 3 of 6
INSULATION MUST BE HELD O
IN COMBUSTIBLE
SOLID WOOD JOIST IN PLACE WITH METAL NSULATION COMPOSITE WOOD JOIST
12"(305mm)MAX.DEPTH WIRE NETTING 12"(305mm)MAX.DEPTH
WOOD TRUSS \\\\\\\\\\\\\\\\\\\\�\\\\\\\\\\\\\N:\`\\\\\\\\\\\\\�:Q�\\\\\\\\\\\\\\ UPPER DECK
TOP CHORD /1111111
%/�,� v�i12"(305mm)MAX.DEPTH
1 12"(38mm)MIN. ��4"(102mm)MAX. / i,, viii
GL5608 (152mm)MAX.
(MODEL IC SPRINKLER) AFOR CPVC
FRAME ARMS MUST r-Y_,� •"R CPVC)MAX.
B5 INSTALLED FOR CPVC
IN-UNE WITH PIPE RUNIII
6"(152mm)MIN. ST .
J
OBSTRUCTION 72
60"(1524mm)MAX. (1829mm)
MAX.
WOOD TRUSS
WEB MEMEBER
CEILING
=Mad...a LW=
BOTTOM OF PIPE/
J W�%
TOP OF CHORD \\\\\\\\\\\\\\\\\\\\\\\\\CS`\\\\\\\\\\N`\"\N\\\\\\\\\\\\\\\\\\\\\\\
WHEN OFFSETTING CPVC PIPE OVER AN
OBSTRUCTION A GL5608 MODEL"IC"SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE PIPE
OVER THE OBSTRUCTION.
6"(152mm)MAX.ABOVE CEILING OR NON-COMBUSTIBLE CEILING INSULATION.OR 113 THE DEPTH OF CONCEALED-
AREA(AS MEASURED FROM TOP SURFACE OF CEILING TO TOP SURFACE OF JOIST INSULATION ABOVE),OR WHICH
EVER IS SMALLER. WHEN THE LOWER JOIST IS GREATER THAN 6"(152rnm)IN HEIGHT CPVC PIPING IS PERMITTED
TO BE ATTACHED DIRECTLY TO THE TOP OF THE JOIST.
FIGURE 2: CPVC PIPE NON-COMBUSTIBLE INSULATION FILLED
UPPER DECK SOLID WOOD, COMPOSITE WOOD JOIST, OR
WOOD TRUSS CONSTRUCTION
STEEL PIPING DESIGN REQUIREMENTS _
SYSTEM TYPE DRAFT CURTAINS
Wet pipe system and dry type systems. Draft Curtain for Unobstructed wood truss construction and
noncombustible bar joist construction must be 8"(203.2mm)
ALLOWABLE CONSTRUCTION in height or one third of the depth of the concealed space,
whichever is greater. Draft curtains must be constructed of
TYPES a material that will not allow for heat to escape through or
• Unobstructed wood truss construction' above them.
• Unobstructed bar joist construction' Draft Curtain for Obstructed wood truss and solid wood joist
• Solid wood joist construction2 construction must be 6" (152.4mm) in height or one third
of the depth of the concealed space, whichever is greater.
• Obstructed wood truss construction2 Draft curtains must be constructed of a material that will not
• Non-combustible insulation filled solid wood joist allow for heat to escape through or above them.
construction3
• Non-combustible insulation filled composite wood joist DEFLECTOR POSITION
construction3 • 1 1/2 to 4 inches below the upper deck for unobstructed
NOTE: wood truss and bar joist constructions. Deflector must
Upper joist/truss cannot be more than 4"(101.6mm)in height. be below the bottom of the top chord in trusses or below
2 Upper joist/truss cannot be more than 12"(304.8mm)in height. bottom of joist.
3 The joist space in non-combustible insulation filled joist construction must be
•
completely filled with noncombustible insulation and secured in place by metal 1 1/2 to 4 inches below the joists for noncombustible
wire netting to hold the insulation in place in the event of a fire. insulation filled solid and composite wood joist
construction.
PARTITION REQUIREMENTS • 1 '/2 to 2 inches below the joist or truss for solid wood
For unobstructed wood truss construction, unobstructed joist or obstructed truss construction.
bar joist construction, solid wood joist construction, and • 4 '/2 inches away from trusses
obstructed wood truss construction the concealed space
being protected must be broken up into areas no greater BLOCKING
than 1000 square feet either by full height walls or by draft For solid wood joist and obstructed wood truss construction
curtains. blocking must be provided in each of the channels between
Noncombustible insulation filled joist construction is not re- the upper joists or trusses. The blocking must be located
quired to be broken up into partitioned areas. where the draft curtains intersect the channels. The block- -
ing must be installed to the full depth of the joists and be -
installed as to not allow heat to escape through or above the
blocking. The blocking must be installed using either the
same material as the joists or a noncombustible material.
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 4 of 6
CONCEALED SPACE SIZE
All spaces must have a minimum open space (from top of size. They must not have a total concealed space height of
lower joist, cord, or truss to bottom of upper joist, cord, or greater than 72"(1.8m). This allows for a maximum lower
truss) of 6"(152.4mm)(see Figures 3, 4, and 5). joist space of 12"(304.8mm) (see Figure 4).
Unobstructed wood truss and bar joist construction must not Solid wood joist and obstructed truss construction must
have a total concealed space height of more than 60"(1.5m). not have an open space (from top of lower joist or truss to
(see Figure 3). bottom of upper joist or truss) of greater than 60"(1.5m) in
Joist construction with noncombustible insulation in the size. They must not have a total concealed space height of
upper deck must not have an open space (from top of lower greater than 84"(2.1m). The upper joist space must not be
' joist to bottom of upper joist) of greater than 60"(1.5m) in greater than 12"(304.8mm) in depth(see Figure 4).
4 1/2"(114mm)MIN.TS UPPER DECK
FACE OF WOOD TRUSS OR 1 112"(38mm)MIN.
TOP CHORD OF BAR JOIST DEFLECTOR MUST BE
4"(100mm)MAX. BELOW BOTTOM OF TOP
IM.... N' CHORD
TOP CHORD % I e,
4"(100mm)MAX. % 2 e
' s L5608
- (MODEL IC SPRINKLER) 11‘ I
FRAME ARMS MUST - ��r� (1524mm)
BE INSTALLED
IN-LINE WITH PIPE RUN
(152mm)
MIN6" MAX..
�a�r
_ %. / / EILING
- FIGURE 3: STEEL PIPE UNOBSTRUCTED WOOD
TRUSS OR NON-COMBUSTIBLE BAR JOIST
CONSTRUCTION
2x FLOOR
SOLID WOOD JOISTS/OBSTRUCTED TRUSS UPPER DECK
16"(406mm)ON CENTER
T.12"(305 m)
Mr F1 2"(51 m8m)MAXN
L5608
FRAME ARMS MUST -- (MODEL IC SPRINKLER) 84"
BE INSTALLED I (2134mm)
IN-LINE WITH PIPE RUN MI MAX.
I
IMIMI
6"(152mm)MIN.
EILING
60"(1524mm) MAX.
V FRAMING
�V�I P
CEILING
FIGURE 4: STEEL PIPE OBSTRUCTED WOOD TRUSS
OR SOLID WOOD JOIST CONSTRUCTION
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 5 of 6
UPPER DECK
NON-COMBUSTIBLE
2x FLOOR SOLID INSULATION COMPOSITE WOOD JOIST
WOOD JOIST
Vein1uIIfuaY;1914WutIVA �u1uAZ>,'� tuVA kite
1tI//1lt 'rtt/r1t/1it� 1I. u.r.n. n . ttuun .r/•1
1 4!(21'0(23mmmm)
M)MAXIN.
.
INSULATION MUST BE HELD L5608 -
IN PLACE WITH METAL - (MODEL IC SPRINKLER) _ i
WIRE NETTING ir r i 6"(152mm)MIN.
NI -Y- 60"(1524mm)MAX.
FRAME ARMS MUST
BE INSTALLED ' 72'
IN-LINE WITH PIPE RUN (1829mm)
MAX.
CEILING FRAMING
�Y �+� i
x/_ A
,
VAAAAIVAAAAAA N.A A.\N N VAAAAAAA.AAAAAAAINNNO
CEILING
FIGURE 5: STEEL PIPE NON-COMBUSTIBLE
INSULATION FILLED UPPER DECK SOLID WOOD OR
COMPOSITE WOOD JOIST CONSTRUCTION
ORDERING INFORMATION GLOBE® PRODUCT
Quantity • SIN • Style • Orifice *Thread Size WARRANTY
Temperature • Finishes • Desired Quantity Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or work-
Wrench - P/N 325390 manship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Technical Support -
Standish, MI 48658 1-800-248-0278 www.globesprinkler.com
Ph. 989-846-4583 techservice@globesprinkler.com ""'
'.7..
NOV 2018 REV. B GFS-600 (Formerly A-40) Page 6 of 6
ir
GLBE 4077 Airpark Dr. Standish, MI 48658•989-846-4583•www.globesprinkler.com
0 Technical Support•989-414-2600•techservice@globesprinkler.com
SERIES GL-RES
RESIDENTIAL PENDENT AND RECESSED Pg-IgeT
K-FACTOR: 3.0, 4.1, 4.9, 5.6 ED
JAN 7 2020
GENERAL DESCRIPTION ,RCITY OF TIGARD
Uf
G IVISION
The series GL-RES pendent sprinklers are decorative fast
response glass bulb sprinklers specifically tested and List-
ed for use in residential applications such as homes, apart-
ments, hotels, and dormitories to provide control of these k: K
residential type fires and to improve the chance for occu-
pants to escape. They utilize a 3mm frangible glass bulb as
its heat sensing operating element. The recessed version
of each of these Residential Sprinklers is intended for use
in areas with finished ceilings. It employs a two-piece Re- SERIES GL-RES
cessed Escutcheon. The Recessed Escutcheon provides a GL3010, GL4110, GL4910, GL5610
total adjustment of 1/2 inch (12.7mm)from the flush ceiling
position or ±1/4 inch (6.4mm) of recessed adjustment. The
adjustment provided by the Recessed Escutcheon reduces TECHNICAL DATA
_ the accuracy to which the pipe drops to the sprinklers must
be cut. Approvals
• See TABLE A
-This sprinkler may be installed within dwelling occupancies Maximum Working Pressure
as allowed by NFPA 13, 13D, 13R and any other related • 175 psi (12 bar)
documents as appropriate. Temperature Rating
The GL3010 is typically utilized when maximum coverag- ° See TABLE A
es are not needed, thereby reducing flow demands. The K-Factor• " '/2
GL5610 is typically the sprinkler of choice when utilizing GL3010 K3.0 gpm/psi�2 (43.2 Ipm/bar/2)
•
Residential Sprinklers within an NFPA 13 Occupancy. The GL4110 K4.1 gpm/psis/2 (59.0 Ipm/bar��)
•
larger K-factor can be advantageous when needed to con • GL491 Q K4.9 gpm/psi��2 (70.6 Ipm/bars/2)
)
form to the NFPA 13 hydraulic Special Design Approach for GL5610 K5.6 gpm/psi {80.6 Ipm/bar
Residential Sprinklers. Thread Size
• 1/2" NPT(15 mm)
Length
• 2-1/2" (6.3 cm)
Materials of Construction
OPERATION • Frame- bronze • Deflector- brass • Screw - brass
Upon exposure to heat such as from a fire, the fluid in the • Lodgement Wire (GL5610 only)-stainless steel • Bulb
bulb expands, compressing the air bubble within the bulb. seat copper
When the air bubble can no longer compress, the fluid ex- ° Spring - nickel alloy • Seal -teflon
•
pansion causes breakage of the glass bulb, resulting in re- Bulb- glass with alcohol based solution, 3mm
lease of the water seat assembly, and discharge of water ° Escutcheon Assembly-carbon steel
from the sprinkler. FINISHES AND ACCESSORIES
Finishes
• Factory Bronze • Chrome •White Polyester
NOTE: • Black Polyester-special order
- Users should refer to Globe's web site (www.globesprinkler.com) Escutcheons
- to assure that the most recent technical literature is being utilized. • Brass•Chrome•White Polyester• Black Polyester
Wrenches
•Standard • Recess• 1/2" NPT
APRIL 2019 REV.A GFS-302 PAGE 1 of 4
DESIGN CRITERIA
The Globe Residential Pendent Sprinkler Series GL-RES is Hydraulic Design (NFPA 13)
cULus Listed for installation in accordance with this data The minimum required discharge from each design area
sheet as well as the applicable installation Standard being sprinkler shall be the greater of the following:
utilized. (1) In accordance with minimum flow rates indicated in
Globe Residential Sprinkler Installation Guide TABLE A.
(2) In rooms or compartments greater than 800 ft2
When conditions exist that are outside the scope of the pro- (74.3 m2), calculated based on delivering a minimum _
vided criteria, refer to the Globe Residential Sprinkler Instal- of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of
lation Guide (Document GFS-380) for recommendations each sprinkler, calculated in accordance with the
that may be acceptable to the authority having jurisdiction. S x L Rules for density area sprinklers.
Hydraulic Design (NFPA 13D and 13R) (3) In rooms or compartments 800 ft2 (74.3 m2) or less
(Defined as "Small Rooms") calculated based on de-
For systems designed to NFPA 13D or NFPA 13R, the min- livering a minimum of 0.1 gpm/ft2 (4.1 mm/min)over
imum required sprinkler flow rate is given in Table A for the the room or compartment using the area of the room
coverage areas shown. The sprinkler flow rate is the min- divided by the number of sprinklers in the room. (7psi
imum required discharge from each of the total number of minimum)
"design sprinklers" as specified in NFPA 13D or NFPA 13R.
TABLE A: NFPA 13, 13R, AND 13D
HYDRAULIC AND INSTALLATION DESIGN CRITERIA
DEFLECTOR TO MINIMUM
K TEMPERATURE MAX.AREA OF MINIMUM MINIMUM CEILING/ DISTANCE
FACTOR MOUNTING
SIN COVERAGE PRESSURE FLOW BETWEEN
GPM/PS/ SURFACE
(lpm ha7') FEET(m) PSI(bat) GPM(11min.) DISTANCE SPRINKLERS _
155°F 175°F 200°F INCHES(mm) FEET(m)
(68°C) (79°C) (93°C)
cULus cULus cULus 12(3.6)x 12(3.6) 7.1 (.49) 8.0(30.3)
3.0 EU`
GL3010
(43.2) cEUUus cULus cULus 14(4.3)x 14(4.3) 11.1 (.765) 10.0(37.8)
cULus cULus
EU()) EU(I) NA 12(3.6)x 12(3.6) 7.2(.5) 11.0(42)
Smooth Ceilings
41 cULus (4.3) ( ) ( ) Recessed 1/829
GL4110 (59) EUI NA NA 14x 14 4.3 8.6(.59) 12.0 45 (29)
to 1-5/8(41)
cULus
EU' cULus NA 16(4.9)x 16(4.9) 11.7(.81) 14.0(53)
Smooth Ceilings
cULus cULus Exposed
EU`
1) EUI NA 12(3.6)x 12(3.6) 7.0(.48) 13.0(49) Max.4(101.6)
cULus cULus Beamed Ceilings
EU�1) EU NA 14(4.3)x 14(4.3) 8.2(.57) 14.0(53) g
Adjacent 8(2.4)
4.9 cULus cULus per NFPA 13, 13D,
GL4910 (70 6) EU'1) EU'I NA 16(4.9)x 16(4.9) 8.2(.57) 14.0(53) or 13R
as appropriate
cULus cULus
Elio) Rim NA 18(5.5)x 18(5.5) 12.0(.83) 17.0(64) Beamed Ceilings
cULus cULus In Beam
EU"> EU") NA 20(6.1)x 20(6.1) 16.7(1.15) 20.0(76) 14"Max. Beam Depth
1-1/8(29)
cULus NA NA 12(3.6)x 12(3.6) 7.2(.5) 15.0(57) to 1-5/8(41)
5.6 cULus NA NA 16(4.9)x 16(4.9) 11.5(.79) 19.0(72)
GL5610
(80.6) cULus NA NA 18(5.5)x 18(5.5) 14.1 (.97) 21.0(79)
cULus NA NA 20(6.1)x 20(6.1) 18.4(1.27) 24.0(91)
NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R.
''LISTED BY UNDERWRITERS LABORATORIES,INC.FOR USE IN THE U.S.,CANADA, AND EUROPEAN UNION.
APRIL 2019 REV.A GFS-302 PAGE 2 of 4
INSTALLATION
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or
there is loss of liquid from the bulb. Sprinklers should be tightened
enough to obtain a leak-tight joint when water pressure is applied
and/or hydrostatic test is performed. Sprinklers should not be
overtightened as this can result in distortion and subsequent leak-
age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque FIGURE 1: STANDARD WRENCH
• for 1/2 inch NPT sprinkler threads. P/N 325390
Step1. Sprinklers must be properly oriented.
Step2. With pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprin-
kler fitting. Note:Do not grasp the sprinkler by ' t
the deflector.
Step3. Wrench-tighten the sprinkler using only thelort
appropriate wrench. Wrenches are only to be ,[
applied to the sprinkler wrench flats or wrench
hex as applicable. Note:Do not apply wrench to FIGURE 2: RECESSED WRENCH
frame arms.
P/N 325391
CARE AND MAINTENANCE
Prior to installation, it is important to read and follow the
"Sprinkler Caution" sheet (GFS-840) included within each
box of sprinklers. This sheet is available on Globe's web
site(www.globesprinkler.com).
- Always obtain permission from the proper authorities to 215/18"DIA
shut down the affected fire protection system and notify all
DIA
-personnel who may be affected by this action before closing HOLE INCELNG
a fire protection system main control valve for maintenance 29/32"DIA
work on the system that it controls. I I
Sprinklers should only be cleaned by means of gently dust-
ing with a feather duster; otherwise, non-operation in the /
event of a fire or inadvertent operation may result. / +°X112'REDUCER
ACE OF FTG.
Store sprinklers in a cool, dry place. Exposure to extreme _
heat will damage the thermal sensing element, possibly re- '`ikA,
�\ yr MAX.
suiting in premature activation.Avoid direct sunlight. .�� -\\1\�o any sprinkler that shows any corrosion, damage,
,' —
Replace t-,/e ELNG
or loss of liquid from the glass bulb. 1118"MN.(REF.)
RETANER 1 5/8"MAX.(REF.)*
Do not attempt to paint or alter the sprinkler's coating in any
manner after leaving the manufacturing plant. .
* (NNER RETANER FLUSH WITH CELNG)
Do not attach wiring, ropes, decorations or fixtures to a
sprinkler. FIGURE 3: 1/2"ADJUSTMENT RECESSED PENDENT
Absence of an escutcheon, used to cover a ceiling hole,
may delay sprinkler operation in a fire situation.
It is the owner's responsibility for inspection, testing and
maintenance of the fire sprinkler system with all components
and devices in accordance with the National Fire Protection
Association Pamphlet 25 as well as any other requirements
as set forth by the local Authority Having Jurisdiction (AHJ).
4077 Airpark Dr. Standish, MI 48658•989-846-4583•www.globesprinkler.com
Technical Support•989-414-2600•techservice@globesprinkler.com
APRIL 2019 REV.A GFS-302 PAGE 3 of 4
ORDERING INFORMATION
TABLE B: PART NUMBER SELECTION
PART NUMBER
SIN + TEMPERATURE + FINISH
XXXX XXX XX
SIN TEMPERATURE FINISH
GL3010 3010 155 155°F(68°C) 01 BRONZE
GL4110 4110 175 175°F(79°C) 02 CHROME
GL4910 4910 200 200°F(93°C) 03 WHITE POLYESTER
GL5610 5610 04 BLACK POLYESTER
Note:All combinations may not be available.
Refer to TABLE A for available listed combinations
TABLE C: ESCUTCHEONS
1/2"(13mm)ADJUSTABLE RECESSED ESCUTCHEON
FINISH FRICTION FIT 1/2"NPT THREADED 1/2"NPT
•
Chrome 332071 329301
White Polyester 332073-W 329303-W
Brass 332072 NA
Black Polyester 332073-B NA
SPECIFY:
• SPRINKLER
•Quantity•SIN•Temperature Rating• Finish
•Part Number(See TABLE B)
• ESCUTCHEON
•Quantity•Finish• Part Number (See TABLE C) GLOBO PRODUCT WARRANTY
• WRENCH
•Quantity•Part Number Globe agrees to repair or replace any of its manufactured
1/2"NPT Standard 325390 products found to be defective in material or workmanship
1/2"NPT Recess 325391 for a period of one year from date of shipment.
• PROTECTIVE CAPS
•Quantity•Part Number For specific details of our warranty please refer to Price List
Cap 327109-Cap Terms and Conditions of Sale (Our Price List).
APRIL 2019 REV.A GFS-302 PAGE 4 of 4