Pps2(30- is 7730 SW RVIl12..i _= t m , Honeywell I Farenhyt Series ` # ` DEC 1 0 2019 CITY OF TK3ARD Intelligent Fire Alarm ContRitLD G DIVISION - - Panel IFP-300 / IFP-300B The IFP-300(red)and IFP-300B(black)are intelligent analog/addressable Fire Alarm Control Panels(FACP).The basic IFP-300 panel contains one built in signaling line circuit(SLC),which can support 159 IDP/SK sensors and 159 IDP/SK modules or 127 SD devices per loop.Additional SLC loops can be added using the model 6815 SLC expander for System Sensor devices to increase the overall point capacity to a maximum of 300 points per panel,or model 5815XL for Hochiki devices to increase the overall point capacity to a maximum of 254 points per panel. IFP-300 has the interconnection capability for up to 32 panels.The system has two modes of operation,multiple panels covering one larger building,or multiple independent buildings.To network panels together IFP-300B use the SK-NIC network interface card.Copper wire or fiber optic cable panel connectivity can be used within the same networked system. IFP-300 has a built-in dual phone line,digital alarm communicator/ transmitter(DACT),IP or optional cellular technologies,Form C trouble relay,and two programmable Form C relays.IFP-300 has powerful features such as detector sensitivity,day/night thresholds,drift compensation,pre-trouble maintenance alert,and calibration trouble alert. The IFP-300 supports a variety of devices,including RA- 2000,RA-1000 or RA-100 remote annunciator,5824 serial/ parallel printer interface module(for printing system reports), FEATURES & BENEFITS • Network support for • IFP-300 can be • Network card allows • JumpStart • Supports Class B up to 32 Sites surface or flush copper network AutoProgramming` (Style 4)and Class A • Built-in support for up mounted connection with a feature for easy (Style 6 or Style 7 to 159 IDP/SK • Built-in USB interface multi-mode or programming configuration for SLC, detectors- programming • Supports forsingle-mode fiber and SBUS. up to four I DP/SK modules or connection option SWIFT wireless • Built in 127 SD SLC devices ' Firmware can be • Built-in dualhone upgraded in the field P gateways.Each synchronization for • Four line LCD display tine,digital alarm gateway can have up appliances from • Renewable license on communicator/ to 49 wireless devices AMSECO,Gentex, with 40 characters per downloadin software tine g transmitter(DACT),IP System Sensor,and helps inhibit or optional cellular Wheelock • Available in a red or unauthorized technologies black cabinet programming - 1 IFP-300 Technical Specifications SPECIFICATIONS ORDERING INFORMATION For a complete listing of all Physical: IFP-300-Intelligent Fire Alarm Control Panel. compliance approvals and Overall Dimensions:26.4"H x 16.4"W x 4.11"D Red certifications,please visit www.farenhyt.com. Weight:45 tbs. IFP-300B-Intelligent Fire Alarm Control Panel Color:Red or Black Black Microsoft,Windows,and the Windows Logo are Environmental Operating Temperature:32°F to SBUS ACCESSORIES registered trademarks 120cF (0°C to 49°C) or trademarks of Humidity:0 to 93%relative humidity(non- RA 2000,RA 1000, RA-1000R, RA-100, Microsoft Corporation. condensing) RA-2000GRAY-Remote annunciators 6815-Signal Line Circuit(SLC)Expander for All other trademarks IDP/SK devices are the property of their ELECTRICAL: IFP-300 Primary AC:120 VAC @ 60 Hz,3.3A Total 5815XL-Signal Line Circuit(SLC)Expander for respective owners. Accessory Load:6A @ 24 VDC power-limited SD devices This document is not RPS-1000-Power Supply intended to be used for Standby Current:190 mA PP y installation purposes.5496-NAC Expander p poses.We Alarm Current:250 mA try to keep our product Battery Charging Capacity:17 to 55 AH 5824 Serial/Parallel Module information up-to Battery Size:18 AH max.allowed in control panel 5880-LED I/O Module date and accurate.We 5865-3/-4-LED Annunciator cannot cover all specific cabinet.Larger capacity batteries can be housed in applications or anticipate RBB accessory cabinet. 5883-Relay Interface all requirements.All specifications are subject APPROVALS MISCELLANEOUS ACCESSORIES to change without notice. NFPA 13,NFPA 15,NFPA 16,NFPA 70,&NFPA SKSS-3-Software Suite.Provides 72:Central Station;Remote Signalling;Local programming,upload/download and event For Technical Protective Signalling Systems;Auxiliary Protected reporting Support,Please call 800-446-6444. Premises Unit;&Water Deluge Releasing Service RBB-Remote Battery Box Cabinet.Use for Other Approvals: backup batteries up to 35 AH. UL Listing;CSFM(pending);COA(pending); Dim:16"W x 10"H x 6"D OSHPD(CA)(pending),FM(pending) SK-SCK-Seismic Compliance Kit SK-NIC-Network Interface Card APPROVED RELEASING SOLENOIDS SK-NIC-KIT-Network Interface Card in Cabinet Asco T8210A107 24 VDC 3 A max 0 Hz SK-FML-Multi Mode Fiber Card Asco 8210G207 24 VDC 3 A max 0 Hz SK-FSL-Single Mode Fiber Card CELL-MOD-Cellular Communicator in Plastic COMPATIBLE DEVICES Enclosure See the data sheets listed below for a complete CELL-CAB-SK-Cellular Communicator in listing of the IDP,SK,SWIFT or SD devices. Metal Enclosure with lock and key 350361-IDP Device Protocol data sheet 53623 - SK Device Protocol data sheet 350360-SD Device Protocol data sheet 350615&350617-SWIFT devices data sheet For more information www.farenhyt.com Honeywell 12 Clintonville Road Northford,CT 06472 800-328-0103 ` DocIRevAI05/17 Honeywell www.farenhyt.com ©201717Honeywell International Inc. *Th, SYSTEMSENSOR 5600 Series Mechanical Heat 5601P Detectors System Sensor's 5600 series mechanical heat detectors offer a low-cost means for property protection against fire, and for non-life-safety installations where smoke detectors are inappropriate. [} .135 F15 t ' 5621 Features Multiple configurations.The 5600 series offers a full-line of configurations to accommodate a broad range of applications.Both • Multiple configurations for installations: single-and dual-circuit models are available for low-and high- -Single-and dual-circuit models —Fixed temp and combination fixed-temp/rate-of-rise temperature ratings with either fixed temperature or combination 135°F or 194°F ratings. fixed temperature/rate-of-rise(ROR)activation.The ROR element of • the fixed/ROR models is restorable to accommodate field-testing. • Plain housing for residential installations(Model 5601P) • Easy-to-use terminal screws Installation flexibility.To satisfy a variety of installation needs, • A broad range of back box mounting options: the 5600 series easily mounts to single-gang and octagonal back boxes.And these models accommodate four-square back boxes, —Single gang when used with a square to round plaster ring.The reversible —3.5"and 4"Octagonal mounting bracket permits both flush-and surface-mount back box —4"square with square to round plaster ring installations. • Reversible mounting bracket Visual identification.The 5600 series provides clear markings on the exterior of the unit to ensure that the proper detector is being used.Alphanumeric characters identify the activation method,as well as the temperature rating,in Fahrenheit and Celsius degrees. Fixed temperature models are identified FX,while combination fixed/ rate-of-rise units are marked FX/ROR.The 5600 series also provides a post-activation indicator in the form of a collector.When the detector is activated,the collector drops from the unit,making it easy to identify the unit in alarm. Agency Listings LISTED APPROVED S2101 3016008 CS630 7270-1653.0167 Specifications Architectural/Engineering Specifications Mechanical heat detector shall be a System Sensor 5600 series model number ,listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire Protective Signaling Systems.The detector shall be either a single-circuit or a dual-circuit type,normally open.The detector shall be rated for activation at either 135°F(57°C)or 194°F(90°C),and shall activate by means of a fixed temperature thermal sensor, or a combination fixed temperature/rate-of-rise thermal sensor.The rate-of-rise element shall be activated by a rapid rise in temperature, approximately 15°F(8.3°C)per minute.The detector shall include a reversible mounting bracket for mounting to 31/2-inch and 4-inch octagonal,single gang,and 4-inch square back boxes with a square to round plaster ring.Wiring connections shall be made by means of SEMS screws that shall accommodate 14-22AWG wire.The detector shall contain alphanumeric markings on the exterior of the housing to identify its temperature rating and activation method.The rate-of-rise element of combination fixed temperature/rate-of-rise models shall be restorable,to allow for field-testing.The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm. Physical/Operating Specifications Maximum Installation Temperature 5601P,5603,5621,and 5623: 100°F(38°C) 5602,5604,5622,and 5624: 150°F(65.6°C) Operating Humidity Range 5 to 95%RH non-condensing Dimensions with mounting bracket Diameter:4.57 inches(11.6cm) Height: 1.69 inches(4.3cm) Alarm Temperature 5601P,5603,5621,and 5623: 135°F(57°C) 5602,5604,5622,and 5624: 194°F(90°C) Weight 6 oz.(170 grams) Rate-of-Rise Threshold 15°F(8.3°C)rise per minute(models 5601P,5602,5621,and 5622 only) Mounting 31/2-inch octagonal back box 4-inch octagonal back box Single gang back box 4-inch square back box with a square to round plaster ring Electrical Specifications Operating Voltage/Contact 6-125VAC/3A Ratings 6-28VDC/1A 125VDC/0.3A 250VDC/0.1A Input Terminals 14-22 AWG 4 X01 ftIt Amok .. rats n� � 5601 P 5602,5622 5603,5623 5604,5624 5621 Ordering Information Identification Method Temperature UL Protected Spacing-10 Foot Model Circuit on Exterior Rating Activation Ceiling* 5601P Single None 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) 5602 Single Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) 5603 Single Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5604 Single Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5621 Dual Lettering 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) 5622 Dual Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(15.24m x 15.2m) 5623 Dual Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5624 Dual Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) *NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet. SYSTEM 3825 Ohio Avenue•St.Charles, IL 60174 02013 System Sensor. Phone:800-SENSOR2•Fax 630-377-6495 Productspedfications subjecttc change withoutnotice.Usit systemsensor.com SEw/COR'" tc current product information,including the latest version of this data sheet. ��/J www.systemsensor.com SPDS30001•7/13 Honeywell HPFF12, HPFFI2CM, HPFFI 2E, HPFFI 2CME NAC Expander/Power Supply ' Description • The Honeywell HPFF12(E) and HPFF12CM(E) are Notifica- tion Appliance Circuit (NAC) Expander Power Supplies designed to extend the power capabilities of existing NACs • • and provide power for auxiliary devices. The HPFF12 and — HPFF12CM connects to any 12 or 24V Fire Alarm Control Panel(FACP)or operates stand-alone. HPFF12 They provide regulated and filtered 24VDC power to four NAC's and an auxiliary output. The NAC outputs are rated at 3.0 amps each and the auxiliary output is rated at 2.0 amps (this output is continuously supplied,even in alarm,and there- fore must be taken into account for power supply loading and battery size calculations).The combined output cannot exceed 12.0 amps. The HPFF12 and HPFF12CM provide independent output cir- cuit supervision so in the event of a NAC fault they can notify the attached FACP. In addition they have a trouble memory ;" feature that displays past troubles(by NAC)for rapid diagnos- tics.Synchronization is built in for five appliance brands. The HPFF12 and HPFF12CM have two fully independent supervised initiating circuits that can be used for synchronized strobes and coded horns. Their NAC outputs may be config- • ured as any of the following: • four Class B(Style Y) ;; • • two Class A(Style Z) • two Class B and one Class A • • four Class A with the optional HPP31076 Class A adapter • ' These power supplies contain an internal Battery charger s� capable of charging up to 26.0 amp-hour(AH)batteries. The HPFF12 is mounted in a lockable wall cabinet that can HPFFI2CM: accommodate up to two 18AH batteries. The HPFF12CM is Three modules in EQBB-D4 designed to mount in Honeywell's large equipment enclosure (EQBB-D4; order separately). Up to three HPFF12CM sup- plies can be mounted in a D-sized EQ cabinet in positions 2,3, —Two Class B&one Class A. and 4. Each HPFF12CM can accommodate two 12AH batter- _Two Class A(Style Z). ies. —Four Class A(requires the HPP31076 Class A adapter). One of the most challenging aspects of a retrofit application is •locating the existing End-of-Line(EOL)resistor.In these appli Four field programmable operational modes: cations that have EOL values other than the 3.9k normally —Pass-through. used with the HPFF12, a single resistor matching the existing —Temporal generator. EOL can be used as a reference for all the outputs. This fea- —Sync generator. ture speeds installation and system checkout because the actual EOL does not need to be located and changed in the —Pass-through Filtered. circuit.The reference resistor must be within the range of 1.9k • Temporal coding and sync protocols compatible with the fol- to 25k. lowing notification appliance brands: NOTE:4 separate programming resistors for the HPFF12 are pro- —System Sensor. vided in the hardware kit shipped with each HPFF12(E) and —Faraday. HPFF12CM(E). They are 3.9K(5 of these are provided,need only —Amseco. 1 for programming),2.2K(1 each),4.7K(1 each)and 10K(1 each) —Cooper-Wheelock. Features -Gentex. • Listed to UL Standard 864,9th edition. • Protocol pass-through for synchronizing large systems. • Four (4) power limited supervised notification application • Two fully independent supervised input/output control circuits. circuits (NAC's) capable of supplying +24VDC at 3.0 amp • Redundant activation operation for survivability. maximum each. • Supports FACP's Selectable Silence ability. • NAC output circuits may be configured as any of the follow- • 2.0 amp auxiliary continuously supplied output. ing: • Eight status LEDs. —Four Class B(Style Y). • Supervised AC input,battery voltage,auxiliary output,char- Cabinet Dimensions: ger,and earth ground faults. • HPFF12 Cabinet: 16.65"W x 19.0" H x 5.2" D (42.29 W x • Trouble indication for supervision of the following: 48.26 H 13.23 D cm) -NAC circuits. • Large equipment enclosure(EQBB-D4): 24"W x 45.9" H -Auxiliary output. x 5.15" D(60.96 W x 116.52 H x 13.1 D cm) -AC input. -Battery charger voltage. Product Line Information -Earth ground faults. HPFF12: 12.0A fire rated power supply. Unit includes red • Optional two-hour delay for AC loss. enclosure, battery cable and installation instructions. 120VAC/ • Separate Trouble and AC Fail Form-C relay contacts. 60Hz. • The Trouble Form-C relay contacts selectable for immediate HPFF12E: 240VAC/50Hz version of HPFF12. or a 2 hour delay with AC failure. HPFF12CM: 12.0A fire rated power supply(chassis mounted). • 26 AH battery charger capability: Unit includes mounting hardware, battery cable and instruc- -HPFF12(E)supports two 12V 18AH batteries tions for installation in large equipment enclosure. 120VAC/ 60Hz. -HPFF12CM(E)supports two 12V 12AH batteries per unit. HPFF12CME:240VAC/50Hz version of HPFF12CM. • NAC Overload protection and indication. • Provision for mounting single or 6 circuit addressable con- HPP31076: Class A (Style Z) NAC Adaptor. Increase Class A trol or relay modules inside the enclosure. (Use mounting circuits from 2 to 4. kit PN 90475.) Large Equipment Enclosure:EQ series cabinet for mounting HPFF12CM power supplies consists of a backbox(EQBB-D4) Specifications and a locking door(EQDR-D4 or FCI-VDR-D4B). Order sepa- rately. Primary Input Power: 120VAC, 60Hz, 5.4A standard; CMF-300-6: Six-circuit supervised addressable control mod- 240VAC,50Hz,3.2A on units with E suffix. ule activated through FACP programming on a select basis to Secondary Power: 24 volt operation:two 7-26 AH batteries. control power supply activation or output. Battery Charging Capacity: Up to 26 AH batteries. CMF-300: Supervised addressable control module activated HPFF12 Cabinet: Holds up to two 18AH batteries. through FACP programming to activate power supply. HPFF12CM: Holds up to two 12AH batteries. BAT-12120: Battery, 12 volt, 12.0 AH (two required). Total Output Current: 12.OA max. BAT-1270: Battery, 12 volt,7.0 AH (two required). Standby Current:0.075 A. 90474: Mounting kit; required to attach an addressable mod- ule onto the control circuit board(included with supply). Auxiliary Power Output:2.0A under all conditions. NAC Output Ratings: 24VDC fully regulated, 3.0A max per Listings and Approvals circuit(12.0A total). Listings and approvals below apply to all. In some cases,cer- End-of-Line Resistor Range: 1.9K to 25k ohm,1/2 watt. Prod- tain modules may not be listed by certain approval agencies, uct ships with 4 separate programming resistors. They are or listing may be in process.Listed under UL 864 9th Edition. 3.9K(5 each-only need one for programming),2.2K(1 each), 4.7K(1 each)and 10K(1 each) UL Listed:S24562 • Common Trouble: 2.0A at 30VDC. FM Approved Relay Fail Relay: 2.0A at 30VDC. Input Control Circuits: compatible with 12 and 24 VDC con- trol panel NACs. Input Control Current (alarm): 5.68 mA @ 12 VDC, 12.28 mA @ 24 VDC. Temperature Rating:32°F to 120°F(0°C to 49°C). Relative Humidity: 10%to 93%non-condensing. This document is not intended to be used for installation purposes.We try to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. System Sensor®is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. Automation and Control Solutions Honeywell Honeywell 12 Clintonville Road 1(877) HPP-POWR Northford,CT 06472-1610 hpp_techsery@honeywell.com www.honeywellpower.com DH-60547:C1 �. AugustISO 9001 Madeadein in thehe U.S.A. ,U.S.Registered Trademark ©2010 Honeywell International Inc. ENGINEERING IMANIMCIDIPI; Page2of2 QUALITY SYSTEMS SILENT Fa ren h y t la KNIGHT by Honeywell Intelligent Device Addressable Monitor Module Agency Listings IDP-Monitor MEA The IDP-Monitor is an addressable monitor module for use with JO 386-0-E-Vol 2 Silent Knight IFP-series fire alarm control panels (FACPs). The '•� IDP-Monitor acts as an interface to contact devices, such as waterflow switches and pull stations. . The IDP-Monitor supports Class A supervised or Class B supervised wiring to the load device. Conventional 4-wire ` � a smoke detectors can be monitored for alarm and trouble conditions. Features • Single contact monitor . • Support for Class A and Class B wiring IDP-Monitor • Fully supervised Compatibility • Panel controlled status LED that flashes green in normal state The IDP-Monitor is compatible with the and is solid red in alarm following FACPs: • Attractive ivory cover plate • Rotary address switches for fast installation • IFP-2000 / RPS-2000 Intelligent Fire Panel • SEMS screws for easy wiring • IFP-2000ECS Emergency Communication • UL Listed System with Fire Panel • IFP-1000 / ECS Intelligent Fire Panel Installation • IFP-100 / ECS Intelligent Fire Panel The IDP-Monitor mounts directly into a 4" square electrical box. • IFP-50 Intelligent Fire Panel The box must have a minimum depth of 2-1/8".A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. P/N 350288 Rev J Copyright©2015 Honeywell International Inc. -1 TO NEXT FROM PANEL OR DEVICE + ����+���VW\ /�������`� h PREVIOUS DEVICE I I MONITOR , ' ANY NUMBER OF UL LISTED CONTACT n MODULE (--1 CLOSURE DEVICES MAY BE USED.DO NOT MIX I , CONNECT MODULES TO LISTED COMPATIBLE FIRE ALARM INTIATING,SUPERVISORY,OR ��O Q gb , / CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MODULE. j ° o 1 , a t) 0 i • "_�/ (+) 41011 47KEOL l .fx4 T I `J RESISTOR lY7i�1 . ELR-47K i - no a I [Su. /, ? ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED INITIATING DEVICE CIRCUIT(IDC)-NFPA STYLE B POWER LIMITED:450pA MAX.@ 11 VDC MAX INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. Typical Wiring for IDP-Monitor Module, NFPA Style B TO NEXT FROM PANEL OR DEVICE - �in....480. —in..1....\ 0�....... —4".—'SW I- PREVIOUS DEVICE MONITOR , , I I ANY NUMBER OF UL LISTED CONTACT MODULE CLOSURE DEVICES MAY BE USED.DO NOT MIX n n II CONNECT MODULES TO LISTED COMPATIBLE FIRE ALARM INTIATING,SUPERVISORY,OR C2 4.D a Doll v I , CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MODULE. ® n CAMINIED I I ) 0 T EOL RESISTOR IS fII(� WM 411 CM i INTERNAL AT � „AALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED TERMINALS 8&9 111 LJ U INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. Typical Wiring for IDP-Monitor Module, NFPA Style D Specifications Environmental Physical Operating Temperature: 32°F— 120°F (0°C—49°C) Height: 4.5" (11.4 cm) Humidity: 10%—93% non-condensing Width: 4" (10.2 cm) Ordering Information Depth: 1.25" (3 cm) IDP-Monitor Monitoring Module Shipping Weight: 6.3 oz (196 g) Accessories Electrical SMB500 4" Square Surface Mount Electrical Box Operating Voltage: 15—32 VDC SLC Standby and Alarm Current Draw: 350 pA End-of-Line Resistance: 47K 0 Max. IDC wiring resistance: 1,500 S2 Max. IDC Voltage: 11 Volts Max. IDC Current: 450 pA SLC Loop Resistance: 40 Q max. SILENT This document is not intended to be used for installation purposes.We try to keep our product information up-to- dIliti ate and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are KNIGHT subject to change without notice. For more information,contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103,Fax:(203)484-7118. by Honeywell For Technical Support, Please call 800-446-6444. www.farenhyt.com F:: a r e n Fi t Addressable Photoelectric Smoke Detector & Photoelectric Smoke with Thermal IDP-Photo & IDP-Photo-T The IDP-Photo is a photoelectric smoke detector and the IDP-Photo-T is a photoelectric smoke detector with thermal. TheseUL MEA plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with 225-02-E vol.v Silent Knight IFP-series fire alarm control panels (FACPs). Detector sensitivity can be programmed from the FACP software. Sensitivity is continuously monitored and reported to the FACP. Point ID capability allows each detector's address to be set with a' rotary address switches, providing exact detector locations for selective maintenance when chamber contamination reaches unacceptable levels. t e } IDP-Photo and IDP-Photo-T have a unique optical sensing chamber amt that is engineered to sense smoke produced by a wide range of combustion sources. In the IDP-Photo-T, dual electronic thermistors add 135°F (57°C) thermal technology to maximize detection. IDP-Photo(Base Not Included) Features • Sleek, low-profile design • Reliable analog communications for trouble-free operation • Age resistant polymer housing • Dual electronic thermistor design on the IDP-Photo-T • Superior EMI resistance for reliability e • Simple field cleaning for code compliance 11111a • Variety of mounting options to meet any application • Dual LED indicators for 360°visibility • Detector transmits signal to indicate maintenance is required IDP-Photo-T(Base Not Included) • Optional remote LED annunciator (PN SSRA400Z) Compatibility • Plug-in mounting provides ease of installation The IDP-Photo and IDP-Photo-T are • Tamper-proof feature available on mounting bases compatible with the following IDP-series • Listed for use in duct applications detector bases: • Rotary address switches for fast installation • IDP6AB 6" Mounting Base • SSB501 4" Mounting Base • UL Listed • SSB224BI 6" Isolator Base • SSB224RB 6" Relay Base Installation The IDP-Photo and IDP-Photo-T plug into a compatible IDP-series • SSB501 BHT 6" Temporal Sounder Base detector base. The IDP-Photo and IDP-Photo-T are compatible with the following FACPs: • IFP-1000 Intelligent Fire Panel • IFP-100 Intelligent Fire Panel • IFP-50 Intelligent Fire Panel SILENT 7550 Meridian Circle Maple Grove,Mn 55369-4927 KNIGHT 763-493-6455 P/N 350280 Rev B,04/10/06 1-800-328-0103 Copyright©2006 Silent Knight Fax:763-493-6475 by Honeywell www.farenhyt.com SLC OUT IN Compatible FACP + — + — RA400Z(Optional) IIMMIllpillilill .. ri..:,:. ev--: ..�.. tai ..r. eiv .,41. ..�,. 0. i;/ 0. �"� �• 7 i. LJ / Class A Optional Wiring / Wiring IDP-Series Detector Mounting Bases Specifications* Ordering Information Physical IDP-Photo Photoelectric Smoke Detector - Height. 2.0" (5.0 cm) IDP-Photo-T Photoelectric Smoke Detector with Diameter: 4.1" (10.4 cm) Thermal (135°F) Shipping Weight: 5.2 oz. (147 g) Accessories Electrical SSRA400Z Remote LED Annunciator. Operating Voltage. 15-32 VDC SSRMK400 Recessed Mounting Kit. Provides low Standby Current: profile for use with SSB501. 250 pA @ 24 VDC (no communication; LED off) SSXR2B Detector Removal Tool.A removal and 300 pA @ 24 VDC (one communication every 5 sec with replacement tool for IDP plug-in detectors. LED enabled) Includes the SST55-127-000. Alarm Current: 6.5 mA @ 24 VDC max(with LED on) SSM02-04-01 Detector Test Magnet. Environmental SSM02-09-00 Test Magnet with Telescoping Handle. Operating Temperature SSXP-4 Extension Pole for SSXR2B. Extends from IDP-Photo: 32°— 120°F (0°C—49°C) 5— 15 ft. IDP-Photo-T: 32°— 100°F (0°C—38°C) SST55-127-000 Detector Removal Head. Humidity: 10%—93% non-condensing SSBCK-200B Black Detector Kit. For IDP-series Other Ratings detectors. IDP-Photo-T Thermal: Fixed temperature setpoint 135°F (57°C) *Unless otherwise noted, specifications apply to IDP-Photo and Velocity: 0-4000 fpm (0-20 m/sec) IDP-Photo-T. IDP-Photo Insect Screen Hole Size: 0.016" (0.41 mm) nominal SILENT This document is not intended to be used for installation purposes.We try to keep our - • KNIGHT product information up-to-date and accurate.We cannot cover all specific applicationsti _ or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight 7550 Meridian Circle Suite 100, Maple byHoneywell Grove, Mn 55369-4927. Phone:(800)328-0103, Fax: (763)493-6475. Y Made in the U.S.A. SILENT F a r e n h y t gro KNIGHT by Honeywell Addressable Single Action and Dual Action Agency Listings Pull Stations MEA IDP-Pull-SA & IDP-Pull-DA 67-02-E Vol.IX The IDP-Pull-SA is a single action pull station requiring only one •j For IDP-Pull-DA motion to activate the station. The IDP-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight IFP-series fire alarm control panels (FACPs). FIRE Features II' • Installer can open station without causing an alarm condition 1 DOWN • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locksSILENT �. KNIGHT • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) IDP-Pull-SA • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN® FIRE • Reliable analog communications for trouble-free operation • Braille text on station handle • Handle latches in down position and the word Activated l PUSH .IN appears, clearly indicating the station has been pulled ♦ PULL DOWN • Rotary address switches for fast installation • UL Listed, including UL 38, Standard of Manually Actuated Signaling System Installation 4t4 SILENT ti KNIGHT The IDP-Pull-SA and IDP-Pull-DA can be surface mounted to an SB-I/O surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13"(5.40 cm) or double- IDP-Pull-DA gang or 4" (10.61 cm) square electrical box. You can also use the Compatibility optional (System Sensor® PN BG-TR) trim ring if the station is The IDP-Pull-SA and IDP-Pull-DA are being semi-flush mounted. compatible with the following FACPs: • IFP-2000/ RPS-2000 Intelligent Fire Panel • IFP-1000 / ECS Intelligent Fire Panel • IFP-100 / ECS Intelligent Fire Panel • IFP-50 Intelligent Fire Panel P/N 350286 Rev F ©2013 Honeywell International Inc t Class A L . SLC , t.-....- • + OUT = 7 • Class B Compatible FACP Et o Idee 1 p 640 . Class A Wiring: - Class B Wiring: Li f ' Wiring IDP-Pull-SA&IDP-Pull-DA Pull Stations Specifications* Ordering Information Physical IDP-Pull-SA Single Action Pull Station Height: 5.5"(14 cm) IDP-Pull-DA Dual Action Pull Station Width:4"(10.2 cm) Depth: 5.4 oz. (3.7 cm) Accessories BG-TR Optional trim ring. Housing Material: LEXAN polycarbonate resin SB-I/O Surface backbox, indoor/outdoor. Bi-Colored LED: Blinking Green: Normal *Unless otherwise noted,specifications apply to IDP-Pull-SA and IDP-Pull-DA. Steady Red:Alarm Switch: Single pole, single throw(SPST) normally open (N/O) switch which closes upon activation of the pull station Electrical Operating Voltage: 15-32 VDC Operating Current(LED flashing): 300 pA Wire Gauge: Up to 12 AWG (3.1 mm2) Environmental Operating Temperature 32°— 120°F (0°C—49°C) Humidity: 10%—93% non-condensing 0 SILENT This document is not intended to be used for installation purposes.We try to keep our KNIGHT product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight 12 Clintonville Road, Northford, CT 06472- immoimm. n by Honeywell 1610 Phone:(800)328-0103, Fax:(203)484-7118. For Technical Support, Please call 800-446-6444. www.farenhyt.com Made in the U.S.A. SILENT Farenhyt KNIGHT by Honeywell Addressable Relay Module Agency Listings IDP-Relay MEA C)`�-!)' (13 386-02-E Vol II The IDP-Relay is an addressable relay module for use with , Silent Knight IFP-series fire alarm control panels (FACPs). The IDP-Relay allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The IDP-Relay contacts can be used for virtually any normally open or normally closed application. Each IDP-Relay is programmed with a unique signaling line circuit (SLC) loo tt.�� � ~`"� address. When an event occurs that controls the IDP-Relay, the the relay is triggered by the FACP. �. Features • Two sets of Form C contacts IDP-Relay • Contacts are rated for a variety of amps (see Specifications) Compatibility • Panel controlled status LED that flashes green in normal The IDP-Relay is compatible with the state and is solid red in alarm following FACPs: • Relay programming is completely flexible—can be mapped • IFP-2000 / RPS-2000 Intelligent Fire Panel to zone conditions • Polling LED visible through the cover plate • IFP-2000ECS Emergency Communication System with Fire Panel • Attractive ivory cover plate • IFP-1000 / ECS Intelligent Fire Panel • Rotary address switches for fast installation • IFP-100 / ECS Intelligent Fire Panel • SEMS screws for easy wiring • IFP-50 Intelligent Fire Panel • UL Listed • IFP-25 Intelligent Fire Panel Relay Contact Ratings Current Load Installation Max Voltage Description Application Rating P The IDP-Relay mounts directly into a 4" 3 A 30 VDC Resistive Noncoded square electrical box. The box must have a minimum depth of 2-1/8". A surface mount 2 A 30 VDC Resistive Coded electrical box (System Sensor® PN SMB500) 0.7 A 70.7 VDC PF =0.35 Noncoded is available from Silent Knight. 0.9 A 125 VAC Resistive Noncoded 0.46 A 30 VDC L/R=20 ms Noncoded 0.5 A 125 VAC PF =0.75 Noncoded 0.3 A 125 VAC PF = 0.35 Noncoded 2 A 25 VAC PF=0.35 Noncoded P/N 350290 Rev J ©2015 Honeywell International Inc. CONNECT MODULES TO LISTED COMPATIBLE (-) CONTROL PANELS ONLY. (-)-wit FROM PANEL TO NEXT OR PREVIOUS DEVIE 11�����4.����` �4 OR t (+) (+) DEVICE RELAY CONTROL I - MODULE - If any wiring to Terminals 4-10 is Nonpower limited,The CB500 barrier it. O O (� is required.The CB500 includes a v I Nonpower limited label,which ' o e o ' must be placed over the Power - Illi,111 © �- , Limited terminal information on (_) the name plate label. Relay Common 2 Ij},rtoTI j� ' Normally Closed 2 tT9 Tz,_;II Normally Open 2 le,Ta T3 Relay Common 1 II},-r7 7 : . 7 T Unused Normally Closed 1 lj},Ta ` 4" "-A- _rs Normally Open 1 ma +o 10 rim 0 ows Clilo El *NOTE:ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN �s n A SEPARATE ZONE. 11111 1111 Specifications Ordering Information Physical IDP-Relay Relay Module 4.675" H x 4.275" W x 1.4" D Shipping Weight: 6.3 oz (196 g) Accessories Environmental SMB500 4" Square Surface Mount Electrical Box Operating Temperature: 32°F— 120°F (0°C—49°C) CB500 Module Barrier Humidity: 10%—93% non-condensing Electrical Operating Voltage: 15—32 VDC End-of-Line Resistance: Not used SLC Standby&Alarm Current: .255mA max @ 24 VDC (one communication every 5 sec with LED enabled) SILENT This document is not intended to be used for installation purposes.We try to keep our product information up-to-date and accurate.We cannot cover all specific applications or KNIGHT anticipate all requirements.All specifications are subject to change without notice. For more , information,contact Silent Knight 12 Clintonville Road, Northford,CT 06472-1610 Phone: imilmoi (800)328-0103, Fax:(203)484-7118. For Technical Support, Please call by Honeywell 800-446-6444. www.farenhyt.com Assembled U.S.A.