Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report
lt/teczok - 00597 /42/0 Srt/ /31he/2c%S- £0 292458-YTG-A-0207 • 2 yro R K® EY.i St'fl YORK® Heating and Air Conditioning JUL 3 0 2018 DESCRIPTION TECHNICAL GUIDE YORK Sunline 2000TM units aNvertible single package air conditioners with a common Cabinet and a common roof curb for the 3,4, 5 and 6 ton sizes.The units were designed for light commercial and commercial applications.They can easily be installed on a roof curb, slab, roof jack or frame. SINGLE PACKAGE GAS/ELECTRIC UNITS All units include: • Powder Paint finish that meets ASTM-B-117 1000 hour AND SINGLE PACKAGE salt spray standards AIR CONDITIONERS • Permanently lubricated motors DICE, CG) 036, 048, 060 & 072 • Bottom or side air discharge configuration capability (field convertible) 3,4, 5&6 NOMINAL TONS • Manufactured under the quality standards of IS09001 10.0 SEER (3,4, &5 Ton), 9.0 EER (6 Ton) • Copper tube/aluminum fin coils • Easy access to all components • Rigging holes in base rails for lifting • Fork lift slots on three sides • Single point power connection Complete factory package-tested, charged and wired iji;li�'In I • *11111111111r l • CSA agency listing on all units -2----, �/ ', 11;11111;iil I WARRANTY • 0iiiii111111111111 iFactory Limited Parts Warranty hi • • I I One-year parts warranty -000 • A Five-year parts warranty on the compressor and "Ilt 000 electric heat elements. �s Ten-year parts warranty on the gas-fired heat exchangers. Pi ni -fir F ERFOR A CE Ccoo U w`v cERTIFIED CggFY tb cRn61t4 AM!ftwodetti 1 FOR DISTRIBUTION USE ONLY-NOT TO BE USED AT POINT OF RETAIL SALE 292458-YTG-A-.0207 TABLE OF CONTENTS DESCRIPTION 1 LIST OF TABLES PRODUCT NOMENCLATURE 3 Tbl.# Pg.# FEATURES 4 1 SOUND POWER RATING 7 FACTORY-INSTALLED OPTIONS 5 2 CAPACITY RATINGS- (ARI 210/240) 7 FIELD-INSTALLED ACCESSORIES 5 3 GAS HEAT RATINGS 7 GUIDE SPECIFICATIONS 39 4 D(CE, CG)036 COOLING CAPACITIES (3 TON) 8 5 D(CE, CG)048 COOLING CAPACITIES (4 TON) 9 LIST OF FIGURES 6 D(CE, CG)060 COOLING CAPACITIES (5 TON) . . . . 10 Fig.# Pg.# 7 D(CE, CG)072 COOLING CAPACITIES (6 TON) . . . . 11 1 UNIT CUTAWAY 5 8 SUPPLY AIR BLOWER PERFORMANCE(3 TON 2 TYPICAL FIELD POWER&CONTROL WIRING . . . .23 BELT DRIVE) SIDE DUCT APPLICATION 12 3 UNIT DIMENSIONS (3 6 TON COOLING ONLY/ 9 SUPPLY AIR BLOWER PERFORMANCE(4 TON ELECTRIC HEAT) FRONT VIEW 24 BELT DRIVE) SIDE DUCT APPLICATION 13 10 SUPPLY AIR BLOWER PERFORMANCE(5 TON 4 UNIT DIMENSIONS (3-6 TON COOLING/GAS HEAT) BELT DRIVE)-SIDE DUCT APPLICATION 14 FRONT VIEW 24 11 SUPPLY AIR BLOWER PERFORMANCE (6 TON 5 UNIT WITH ECONOMIZER RAINHOOD 25 BELT DRIVE)-SIDE DUCT APPLICATION 15 6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED 12 SUPPLY AIR BLOWER PERFORMANCE(3-6 TON DAMPER RAINHOOD 25 DIRECT DRIVE) -SIDE DUCT APPLICATION 16 7 UNIT DIMENSIONS (REAR VIEW) 26 13 BELT DRIVE BLOWER MOTOR AND DRIVE DATA. . 16 8 DISCONNECT/BLOWER ACCESS LOCATION 26 14 STATIC RESISTANCES 17 9 TYPICAL APPLICATIONS 27 15 ELECTRIC HEATER CFM LIMITATIONS 17 10 FOUR AND SIX POINT LOADING 28 16 ELECTRICAL DATA-D(CE, CG)036-072 DIRECT 11 ROOF CURB DIMENSIONS 29 DRIVE 18 12 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 17 ELECTRICAL DATA-D(CE, CG)036-072 BELT 208/230V AND 460V DIAGRAM 30 DRIVE 20 13 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 18 PHYSICAL DATA 22 575 VOLT DIAGRAM 31 19 ELECTRIC HEAT CORRECTION FACTORS 22 14 COOLING UNIT WITH ELECTRIC HEAT CONTROL 20 VOLTAGE LIMITATIONS 22 CIRCUIT 208/230V,460V AND 575V DIAGRAM . . . .32 15 COOLING UNIT POWER CIRCUIT 208/230-3-60 21 UTILITIES ENTRY 26 DIRECT DRIVE INDOOR BLOWER DIAGRAM 33 22 MINIMUM CLEARANCES 26 16 COOLING UNIT POWER CIRCUIT 208/230-3-60 23 D(CE, CG)4 AND 6 POINT LOADS WEIGHT BELT DRIVE INDOOR BLOWER DIAGRAM 34 DISTRIBUTION 28 17 COOLING UNIT POWER CIRCUIT 460-3-60 24 CENTER OF GRAVITY 28 DIRECT DRIVE INDOOR BLOWER DIAGRAM 35 25 OPERATING WEIGHTS (LBS.) 29 18 COOLING UNIT POWER CIRCUIT 460-3-60 BELT DRIVE INDOOR BLOWER DIAGRAM 36 19 COOLING UNIT POWER CIRCUIT 575-3-60 DIRECT DRIVE INDOOR BLOWER DIAGRAM 37 20 COOLING UNIT POWER CIRCUIT 575-3-60 BELT DRIVE INDOOR BLOWER DIAGRAM 38 2 Unitary Products Group • 292458-YTG-A-0207 PRODUCT NOMENCLATURE I ` I V I C E 0 3 6 n 2 5 PRODUCT CATEGORY D=Single Package Air Conditioner VOLTAGE CODE (Air Cooled) 25=208/230-3-60 46=460-3-60 58=575-3-60 PRODUCT GENERATION 3=3rd Generation 5=5th Generation FACTORY INSTALLED 6=6th Generation HEAT NOMINAL COOLING PRODUCT IDENTIFIER CAPACITY A=Cooling Only 036=3 Ton CE=Cooling 048=4 Ton 060=5 Ton 072=6 Ton [FM C G 0 3 6 [] 0 4 0 2 5 PRODUCT CATEGORY VOLTAGE CODE D=Single Package Air Conditioner 25=208/230-3-60 (Air Cooled) 46=460-3-60 58=575-3-60 PRODUCT GENERATION 3=3rd Generation NOMINAL GAS HEATING 8=8th Generation OUTPUT CAPACITY 9=9th Generation 040=40 MBH 060=60 MBH 079=79 MBH PRODUCT IDENTIFIER 099=99 MBH CG=Gas/Electric NOMINAL COOLING CAPACITY FACTORY INSTALLED 036=3 Ton HEAT 048=4 Ton N=Gas Heat Installed 060=5 Ton 072=6Ton Unitary Products Group 3 292458-YTG-A-D207 FEATURES alarm on ignition failures, compressor lockouts and repeated limit switch trips. All units are self-contained and assembled on full perimeter • Nuisance Trip Protection-To prevent nuisance base rails with forklift holes on three sides and holes for over- trouble calls,the control board uses a"three strikes, head rigging. Every unit is completely piped,wired, charged you're out"philosophy.The high and low-pressure and tested at the factory to simplify the field installation and to switches and the freezestats must trip three times provide years of dependable operation. within two hours before the unit control board will All models(including those with an economizer)are suitable for lock out the compressor. either bottom or horizontal duct connections. For bottom duct, • On Board Diagnostics-Each alarm will energize a remove the sheet metal panels from the supply and return air trouble light on the thermostat, if so equipped, and openings through the base of the unit. For horizontal duct, flash an alarm code on the control board LED. Each remove the supply and return air panels on the rear of the unit. high and low-pressure switch alarm as well as each All models are available with the"factory mounted"outdoor freezestat alarm has its own flash code.The control air damper option: board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. • Single enthalpy economizer Alarms and programmed values are retained Supply air blowers are equipped with either a direct drive or a through the loss of power. belt drive that can be adjusted to meet the exact require- All units have long lasting powder paint cabinets with 1000 ments of the job. hour salt spray test approval under ASTM-B117 procedures. All compressors are equipped with internal pressure relief. All models are CSA listed. Every refrigerant circuit includes a liquid line filter-drier,a high pressure switch and a suction line with a freezestat and low • Warranty -All models include a one-year limited parts pressure/loss of charge switch to protect all system compo- warranty on the complete unit. Compressors and electric nents. heater elements carry a five-year warranty. Gas heat • Control boards have standardized a number of features exchangers carry a 10 year parts warranty. previously available only as options or by utilizing addi- • Gas Heat Operation-All single phase models with gas tional controls. heat have minimum annual fuel utilization efficiency • Low Ambient-An integrated low-ambient control (AFUE)of 80%.All three phase models with°gas heat allows all units to operate in the cooling mode down have minimum steady state efficiency of 80%. Each sec- to 0°F outdoor ambient without additional assis tion includes a durable heat exchanger with aluminized tance. Optionally, the control board can be pro steel,a redundant gas valve, spark ignition, power vent- grammed to lockout the compressors when the ing, an ignition module for 100%shut-off and all of the outdoor air temperature is low or when free cooling safety controls required to meet the latest ANSI stan- is available. dards. • Anti-Short Cycle Protection-To aid compressor The gas supply piping can be routed into the heating life,an anti-short cycle delay is incorporated into the compartment through a hole in the base pan of the unit standard controls. Compressor reliability is further or through a knockout in the piping panel on the front of ensured by programmable minimum run times. For the unit. testing,the anti short cycle delay can be temporarily overridden with the push of a button. • Electric Heat Operation-All electric heat models are wired for a single power source and include a bank of • Fan Delays-Fan on and fan off delays are fully pro- nickel chromium elements mounted at the discharge of grammable and are independent of one another.All the supply air blower to provide a high velocity and uni- units are programmed with default values based form distribution of air across the heating elements. upon their configuration of cooling and heat. Every element is fully protected against excessive tem- • Safety Monitoring-The control board monitors the perature by thermal limit switches. high and low-pressure switches,the freezestats,the The power supply wiring can be routed into the control gas valve, if applicable, and the temperature limit box through a threaded pipe connection (field supplied) switch on gas heat units.The unit control board will in the base pan of the unit or through a knockout in the wiring panel on the side of the unit. 4 Unitary Products Group 292458-YTG-A-0207 20 GAUGE ALUMINIZED POWER VENTOR MOTOR STEEL TUBULAR HEAT WITH POST PURGE CYCLE EXCHANGER DIRECT OR BELT DRIVE HIGH EFFICIENCY ECONOMIZER COMPRESSOR HOOD BLOWER '_ affiiftr ,n\))))0 ----.kililif:allim..**ANO- .""illIgif i ili'll il r: I ..i ill 111 r III/11'1111i 1 i k\t'S. � ��l��lIlll� i,.i � COPPER TUBE/ � �p �i �, ALUMINUMFIN �,� ® d1! „ CONDENSINGA 4 OP ��� i'i�11li,1I ! � COIL A 1 ,lb t, IS1/1 I .' SLIDE-IN 1 0 ECONOMIZER I t ful ; / ./ I I 4,411t-41# �. \ Ilk I` `�` FULL PERIMETER •- fi s fi%' II jlii ,M�i BASE RAILS WITH SIDE RETURN , '� I "'1F I FORKLIFT SLOTS AIR DUCT OPENING \.*�" 'i�l'�P //v AND LIFTING HOLES •�� KNOCKOUT FOR SIDE ROETURN Si )-1:, *'�� GAS SUPPLY ENTRY AIR DUCT 3/4"PVC FEMALE `I OPENING CONDENSATE DRAIN LOW VOLTAGE CONTROL BOARD KNOCKOUTS FOR SIDE POWER AND CONTROL ENTRY FIGURE 1 - UNIT CUTAWAY FACTORY-INSTALLED OPTIONS FIELD-INSTALLED ACCESSORIES • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- • SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS- Includes a slide-in/plug-in damper assembly MIZERS- Includes a slide-in/plug-in damper assembly with fully modulating spring-return motor actuator capa- with fully modulating spring-return motor actuator capa- ble of introducing up to 100%outdoor air with nominal ble of introducing up to 100%outdoor air with nominal 1%leakage type dampers. 1%leakage type dampers. The enthalpy system contains one sensor that monitors The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must The rainhood is painted to match the basic unit and must be field-assembled before installing. be field assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER- • PHENOLIC COATED CONDENSER COILS-Special Includes a slide-in/plug-in damper assembly with a 2- coating process that utilizes Technicoat 10-1TM pro- position, spring return motor actuator which opens to cesses.Coating is applied by total immersion of the corn- some pre-set position whenever the supply air blower is plete coil for maximum protection. operating and will drive fully closed when the blower unit shuts down. • BELT DRIVE INDOOR FAN -Includes belt drive indoor fan and motor with unit access for belt adjustment and The rain hood is painted to match the basic unit and service. must be field assembled before installing. Unitary Products Group 5 292458-YTG-A-,0207 • ELECTRIC HEATERS wired for single point power sup- The power exhaust option can only be used on bot- ply. These nickel chromium heater elements are pro- tom duct configurations. vided with limit and automatic reset capability to prevent operation at excessive temperatures. • BAROMETRIC RELIEF DAMPER-This damper acces- sory can be used to relieve internal building air pressure • ROOF CURBS-Eight and fourteen-inch high roof curbs on units with an economizer without power exhaust.This provide a water-tight seal between the unit and the finished accessory includes a rain hood, a bird screen and a fully roof.These full perimeter curbs meet the requirements of assembled damper. With bottom duct connections,the the National Roofing Contractors Association(NRCA)and damper should be mounted over the opening in the are shipped knocked-down for field assembly. return air panel.With horizontal ductwork,the accessory should be mounted on the return air duct. Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct • ENTHALPY ACCESSORY CONTROL KIT-This kit hanger supports. contains the required components to convert a single • HIGH ALTITUDE NATURAL GAS-Burner orifices and enthalpy economizer to dual enthalpy. pilot orifices are provided for proper furnace operation at • BURGLAR BARS-Mount in the supply and return altitudes up to 6,000 feet. openings to prevent entry into the duct work. • PROPANE- Burner orifices, pilot orifices and gas valve • FLUE EXHAUST EXTENSION KIT- In locations with parts are provided to convert a natural gas furnace to wind or weather conditions which may interfere with propane. proper exhausting of furnace combustion products,this • HIGH ALTITUDE PROPANE Burner orifices and pilot kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. orifices are provided for proper furnace operation at alti- tudes up to 6,000 feet.This accessory supplements the • COIL GUARD-Customers can purchase a coil guard kit basic propane conversion kit. to protect the condenser coil from damage. This is not a • LOW NOX KIT-Required to reduce the emission of hail guard kit. nitrogen oxides below 40 nanograms per joule. • HAIL GUARD-Hail Guard Kit is available to prevent unit • POWER EXHAUST Our single input economizer from hail damage.This is a sloped hood that fits above the condenser coil. options are available with power exhaust.Whenever the outdoor air intake dampers are opened for free cooling, • GAS PIPING KIT-This kit supplies all necessary fittings the exhaust fan will be energized to prevent the condi- and shut off valve. tioned space from being over-pressurized during econo- mizer operation. 6 Unitary Products Group 292458-YTG-A-0207 TABLE 1: SOUND POWER RATING SOUND POWER(db 10"12 Watts) UNIT ESP BLOWER SIZE CFM Octave Band Centerline Frequency(Hz) SWL dB(A) d8(A) @ IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 10Ft.2 036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43 072 • 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower. TABLE 2: CAPACITY RATINGS-(ARI 210/240)1 TABLE 3: GAS HEAT RATINGS1 MODEL MBH EER2 SEERS MBH MBH AFUE TEMP MODEL INPUT OUTPUT (%) RISE°F D(CE,CG)036 36.0 9.1 10.0 D(CE,CG)048 47.4 9.0 10.0 DCG036N040 50 40 80.9 15-45 D(CE,CG)060 59.0 9.1 10.0 DCG036N079 100 80 80.5 40-70 D(CE,CG)072 72.0 9.0 DCG048N060 75 60 80.9 25-55 DCG048N099 125 100 80.3 45-75 1. 80/67°F Indoor and 95°F outdoor. DCGO6ON079 100 80 80.5 25-55 2. EER=Energy Efficiency Ratio at full load-the cooling DCGO6ON099 125 100 80.3 35-65 capacity in Btu's per hour(Btuh)divided by the power DCG072N079 100 80 80.5 25-55 input in watts,expressed in Btuh per watt(Btuh/watt). DCG072N099 125 100 80.3 35-65 3. SEER=Seasonal Energy Efficiency Ratio. 1. All units are single-stage heating. Unitary Products Group 7 292458-YTG-A,0207 , TABLE 4: D(CE,CG)036 COOLING CAPACITIES (3 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR COIL TOTAL POWER SENSIBLE CAPACITY' TOTAL POWER SENSIBLE CAPACITY' CAP.' ENTERING DRY BULB,°F CAP,' ENTERING DRY BULB,°F INPUTZ kW INPUTZ kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 45 3.1 35 30 26 21 17 - - 43 3.3 35 30 26 21 17 - - 1750 67 43 3.0 43 38 34 29 25 20 16 41 3.3 41 38 34 29 25 21 16 62 39 3.0 39 39 39 34 30 25 21 36 3.3 36 36 36 32 27 23 18 57 40 2.9 40 40 40 35 31 26 22 38 3.2 38 38 38 33 29 24 20 72 44 3.1 31 28 24 20 16 - - 42 3.3 31 27 23 20 16 - - 67 41 3.0 39 35 31 27 23 19 16 39 3.3 37 35 31 27 23 19 15 1475 62 38 3.0 38 38 37 33 29 25 21 36 3.3 36 36 35 31 27 23 19 57 39 2.9 39 39 39 35 31 27 23 37 3.2 37 37 36 32 28 25 21 72 42 3.1 28 25 22 18 15 - - 41 3.3 28 24 21 18 14 - - 1200 67 40 3.0 35 32 28 25 22 18 15 38 3.2 34 31 28 25 21 18 15 • 62 36 3.0 36 36 35 31 28 25 21 35 3.3 35 35 34 30 27 24 20 57 37 2.9 37 37 37 34 31 27 24 36 3.2 36 36 35 32 28 25 22 72 41 3.1 26 23 20 17 14 - - 39 3.2 26 23 20 17 14 - - 67 38 3.0 32 30 27 24 21 18 15 37 3.2 32 29 26 23 20 17 14 1050 62 35 3.0 35 35 33 30 27 24 21 33 3.2 33 33 31 28 25 22 20 57 36 2.9 36 36 35 32 29 26 23 34 3.2 34 34 32 30 27 24 21 72 39 3.1 24 21 19 16 14 - - 38 3.2 23 21 18 16 13 - - 900 67 37 3.0 30 27 25 22 20 17 15 36 3.2 29 26 24 21 19 16 14 62 34 3.0 34 33 30 28 25 23 20 32 3.2 32 31 29 26 24 21 19 57 34 2.9 34 34 33 30 27 25 22 33 3.1 33 33 30 27 25 22 20 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 105°F 115°F EVAPORATOR COIL TOTAL POWER SENSIBLE CAPACITY' TOTAL POWER SENSIBLE CAPACITY' CAP.' INPUTZ kW ENTERING DRY BULB,°F CAP.' INPUTZ kW ENTERING DRY BULB,°F CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 41 3.7 34 29 25 20 16 - - 39 4.1 33 28 24 19 15 - - 1750 67 38 3.7 38 37 33 28 24 19 15 36 4.0 36 36 32 27 23 18 14 62 34 3.7 34 34 34 30 25 21 16 32 4.0 32 32 32 27 23 18 14 57 35 3.6 35 35 35 31 26 22 17 33 4.0 33 33 33 28 24 19 15 72 40 3.7 30 26 23 19 15 - - 38 4.1 30 26 22 18 14 - - 1475 67 37 3.6 36 34 30 26 22 18 14 35 4.0 34 33 29 25 21 17 13 62 33 3.7 33 33 33 29 25 21 17 31 4.0 31 31 31 27 23 19 15 57 34 3.6 34 34 34 30 26 22 18 32 4.0 32 32 32 28 24 20 16 72 39 3.7 27 24 20 17 14 - - 37 4.1 26 23 20 16 13 - - 1200 67 36 3.6 34 30 27 24 20 17 14 34 4.0 33 30 26 23 20 16 13 62 32 3.6 32 32 32 29 25 22 19 30 4.0 30 30 30 27 24 20 17 57 33 3.6 33 33 33 29 26 23 19 31 3.9 31 31 31 27 24 21 17 72 37 3.6 25 22 19 16 13 - - 36 4.1 24 21 18 15 12 - - 1050 67 35 3.6 31 28 25 22 19 16 13 32 4.0 30 27 24 21 18 15 12 62 31 3.6 31 31 29 27 24 21 18 29 4.0 29 29 28 25 22 19 16 57 32 3.5 32 32 30 27 24 21 18 30 3.9 30 29 28 25 22 19 16 72 36 3.6 22 20 17 15 12 - - 34 4.0 21 19 16 14 11 - - 900 67 33 3.6 28 25 23 20 18 15 13 31 4.0 27 24 22 19 17 14 11 62 30 3.6 30 29 27 24 22 19 17 28 4.0 28 28 25 22 20 17 15 57 31 3.5 31 30 28 25 22 20 17 28 3.9 28 28 25 23 20 17 15 1.These capacities are gross ratings.For net capacity,determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table,multiply this value by 3.415 MBH/kW to determine the motor heat,and deduct this heat from the gross capacity of the unit. 2.These ratings include the compressor and the condenser fan motors but not the supply air blower motor.The total condenser fan motor power input is 0.36kW.Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 8 Unitary Products Group 292458-YTG-A-0207 TABLE 5: D(CE,CG)048 COOLING CAPACITIES (4 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR COIL TOTAL POWER SENSIBLE CAPACITY TOTAL POWER SENSIBLE CAPACITY' CAP z ENTERING DRY BULB,°F CAP.' 2 ENTERING DRY BULB,°F INPUT kW INPUT kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 1 74 71 68 72 60 4.1 44 39 33 28 23 - - 60 4.5 44 39 33 28 1 23 - - 2000 67 55 4.1 53 48 42 37 32 26 21 52 4.5 52 47 42 36 , 31 25 20 62 51 4.0 51 51 51 45 40 34 29 48 4.4 48 48 48 42 37 32 26 57 49 3.9 49 49 49 44 39 33 28 47 4.3 47 47 47 42 _ 36 31 26 72_ 58 4.1 41 36 31 26 21 - - 57 4.5 41 36 31 26 21 - - 1800 67 53 4.1 49 45 40 35 30 25 20 50 4.5 49 44 39 34 29 24 19 62 49 4.0 49 49 48 43 38 33 28 46 4.4 46 46 46 41 36 31 26 57 47 3.9 47 47 47 43 38 33 28 45 4.3 45 45 45 40 36 31 26 72 56 4.1 38 34 29 25 20 - - 55 4.6 38 33 29 24 20 - - 1600 67 51 4.1 46 41 37 32 28 24 19 48 4.5 45 40 36 31 27 23 18 62 47 4.0 47 47 45 41 36 32 27 44 4.4 44 44 44 40 35 31 26 57 46 3.9 46 46 46 41 37 32 28 44 4.4 44 44 44 39 35 30 26 72 54 4.1 35 31 27 23 19 - - 53 4.5 35 31 27 23 19 - - 1400 _ 67 49 4.1 42 38 34 30 26 22 19 47 4.5 41 38 34 30 26 22 18 62 45 4.0 45 45 42 38 34 30 26 43 4.4 43 43 41 37 33 29 25 57 44 3.9 44 44 43 39 35 31 27 42 4.3 42 42 41 37 33 29 25 72 52 4.1 32 29 25 22 18 - - 51 4.5 32 28 25 21 18 - - 1200 67 47 4.1 39 35 32 28 25 21 18 45 4.4 38 35 31 28 24 21 17 62 43 4.0 43 43 39 36 32 29 25 41 4.3 41 41 38 35 31 28 24 57 42 3.9 42 42 39 36 32 29 25 41 4.3 41 41 38 34 31 27 24 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 105°F 115°F EVAPORATOR COIL TOTAL SENSIBLE CAPACITY TOTAL SENSIBLE CAPACITY' CAP POWER ENTERING DRY BULB,°F CAP.' POWER ENTERING DRY BULB,°F INPUT'kW INPUT'kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 56 5.1 42 37 31 26 21 - _ - 53 5.6 40 35 29 24 19 - - 2000 67 49 5.0 49 46 40 35 29 24 19 46 5.5 46 44 39 33 28 23 17 62 45 4.9 45 45 45 39 34 28 23 41 5.4 41 41 41 36 30 25 20 57 44 4.9 44 44 44 39 33 28 22 41 5.4 41 41 41 35 30 25 19 72 55 5.0 39 34 29 24 20 - - 52 5.5 38 33 28 23 18 - - 1800 67 48 5.0 47 43 38 33 28 23 18 45 5.4 45 42 37 32 27 22 17 62 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 26 21 57 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 25 20 72 53 5.0 36 32 28 23 19 - - 51 5.5 35 31 26 22 17 - - 1600 67 46 4.9 44 40 35 31 26 22 17 44 5.4 44 39 35 30 26 21 17 62 42 4.9 42 42 42 37 33 28 24 39 5.3 39 39 39 35 30 26 21 57 41 4.8 41 41 41 37 32 28 23 39 5.3 39 39 39 34 30 25 21 72 51 5.0 33 29 26 22 18 - - 48 5.5 32 28 24 20 16 - - 1400 67 44 4.9 41 37 33 29 25 21 17 42 5.3 40 36 32 28 24 20 16 62 40 _ 4.8 40 40 39 35 31 27 23 37 5.3 37 37 36 32 28 24 20 57 40 4.8 40 40 38 34 30 26 22 37 5.3 37 37 36 32 28 24 20 72 49 4.9 30 27 23 20 16 - - 46 5.4 29 26 22 19 15 - - 1200 67 42 4.9 37 34 30 27 23 20 16 39 5.3 36 33 29 26 22 19 15 62 38 4.8 38 38 36 32 29 25 22 35 5.3 35 35 33 29 26 22 19 57 38 4.8 38 38 35 32 28 25 21 35 5.3 35 35 33 29 26 22 19 1.These capacities are gross ratings.For net capacity,determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table,multiply this value by 3.415 MBH/kW to determine the motor heat,and deduct this heat from the gross capacity of the unit. 2.These ratings include the compressor and the condenser fan motors but not the supply air blower motor.The total condenser fan motor power input is 0.36kW.Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 9 292458-YTG-A,0207 , TABLE 6: D(CE,CG)060 COOLING CAPACITIES(5 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 85°F 95°F EVAPORATOR COIL TOTAL SENSIBLE CAPACITY' TOTAL SENSIBLE CAPACITY CAP.' POWER ENTERING DRY BULB,°F CAP.' POWER ENTERING DRY BULB,°F INPUT kW INPUT2 kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - - 2500 67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 23 62 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 28 57 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 25 72 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - - 67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 22 2250 62 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 29 57 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 27 72 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - - 2000 67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 22 62 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 31 57 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 28 72 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - - 1750 67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 21 62 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 29 57 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 27 72 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - - 1500 67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 20 62 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 27 57 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 105°F 115°F EVAPORATOR COIL TOTAL SENSIBLE CAPACITY' TOTAL SENSIBLE CAPACITY' CAP' POWER ENTERING DRY BULB,°F CAP' POWER ENTERING DRY BULB,°F INPUT2 kW INPUT2 kW CFM WB°F MBH 86 83 80 77 74 71 I 68 MBH 86 83 80 77 74 71 68 72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - - 67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24_ 18 2500 62 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 19 57 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 17 72 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - - 2250 67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 18 - 62 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 _ 26 20 57 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 19 72 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - - 2000 67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 18 62 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 22 57 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 21 72 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - 1750 67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 17 62 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 21 57 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 _ 38 33 29 24 19 72 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - - 67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 16 1500 62 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 19 57 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18 1.These capacities are gross ratings.For net capacity,determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table,multiply this value by 3.415 MBH/kW to determine the motor heat,and deduct this heat from the gross capacity of the unit. 2.These ratings include the compressor and the condenser fan motors but not the supply air blower motor.The total condenser fan motor power input is 0.36kW.Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 10 Unitary Products Group 292458-YTG-A-0207 TABLE 7: D(CE, CG)072 COOLING CAPACITIES(6 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR 85°F 95°F COIL TOTAL POWER SENSIBLE CAPACITY TOTAL POWER SENSIBLE CAPACITY CAP. Z ENTERING DRY BULB,°F CAP.' ENTERING DRY BULB,°F INPUT kW INPUTZ kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 80 5.7 63 55 47 40 32 - - 77 6.3 63 55 47 40 32 - - 2700 67 80 5.7 76 68 60 53 45 37 30 77 6.3 75 68 60 53 45 37 30 62 70 5.5 70 70 70 62 55 47 39 71 6.3 71 71 71 63 56 48 40 57 68 5.6 68 68 68 60 52 45 37 71 6.3 71 71 71 63 56 48 40 - 72 82 5.7 60 53 46 38 31 - - 76 6.3 60 53 46 39 31 - - 2550 67 82 5.7 73 65 58 51 43 36 29 76 6.3 73 66 58 51 44 36 29 62 71 5.5 71 71 70 62 55 48 41 70 6.3 70 70 69 62 55 48 40 57 69 5.6 69 69 69 62 55 47 40 70 6.3 70 70 70 62 55 48 40 72 83 5.7 58 51 44 37 30 75 6.3 58 51 44 37 303 - - 2400 67 83 5.7 70 63 56 49 42 35 28 75 6.3 70 64 57 50 43 36 29 62 73 5.5 73 73 70 63 56 49 42 69 6.3 69 69 68 61 54 47 40 57 71 5.6 71 71 71 64 57 50 43 69 6.3 69 69 68 61 54 47 40 72 79 5.7 54 48 41 35 29 - - 73 6.3 53 47 41 35 29 - - 2100 67 79 5.7 65 59 53 47 40 34 28 73 6.3 65 59 52 46 40 34 28 62 69 5.5 69 69 66 60 54 47 41 67 6.3 67 66 63 57 51 45 38 57 67 5.6 67 67 67 61 54 48 42 67 6.3 67 66 63 57 51 45 39 72 74 5.6 50 44 39 34 28 - - 71 6.3 49 43 38 33 27 - - 1800 67 74 5.6 60 55 50 44 39 34 28 71 6.3 59 54 48 43 38 32 27 62 65 5.4 65 65 62 57 51 46 41 65 6.2 65 63 58 53 47 42 37 57 63 5.5 63 63 63 58 52 47 42 65 6.3 65 63 58 53 47 42 37 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON 105°F 115°F EVAPORATOR COIL TOTAL SENSIBLE CAPACITY TOTAL SENSIBLE CAPACITY CAP.' POWER ENTERING DRY BULB,°F CAP.' POWER ENTERING DRY BULB,°F INPUTZ kW INPUTZ kW CFM WB°F MBH 86 83 80 77 74 71 68 MBH 86 83 80 77 74 71 68 72 76 7.1 61 53 45 38 30 - - 75 7.9 59 51 _ 43 36 28 - - 67 71 7.1 70 66 58 50 43 35 27 65 7.8 65 64 56 48 41 33 25 2700 62 64 7.0 64 64 64 56 49 41 34 57 7.8 57 57 57 50 42 34 27 57 64 7.0 64 64 64 56 49 41 34 57 7.7 57 57 57 50 42 34__ 27 72 76 7.1 59 51 44 37 29 - - 76 7.9 57 49 42 35 27 2550 67 71 7.1 69 64 56 49 42 34 27 66 7.9 66 61 54 47 40 32 25 62 64 7.0 64 64 64 56 49 42 35 58 _ 7.8 58 58 58 51 43 36 29 57 64 7.0 64 64 64 56 49 42 34 58 7.7 58 58 58 50 43 36 29 72 75 7.1 56 49 43 36 29 - - 76 8.0 55 48 41 34 27 - - 2400 67 70 7.1 68 61 54 48 41 34 27 66 7.9 66 59 52 45 38 32 25 62 _ 64 7.0 _ 64 64 63 56 49 42 35 59 _ 7.8 59 59 59 52 45 38 31 57 _ 64 7.0 _ 64 64 63 56 49 42 35 59 7.7 59 59 58 51 - 44 37 30 72 73 7.1 52 45 39 33 27 - - 73 7.9 50 44 37 31 25 - - 2100 67 68 7.1 63 56 50 44 38 32 26 63 7.8 61 54 48 42 36 30 24 62 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 54 48 42 35 29 57 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 53 47 - 41 35 29 72 _ 70 7.1 47 41 36 31 25 - - 69 7.8 45 40 34 29 23 - - 1800 67 65 7.0 57 51 46 41 35 30 25 60 7.8 55 49 44 39 33 28 23 62 59 7.0 59 58 54 48 43 38 32 53 7.7 53 53 49 44 39 33 28 57 59 6.9 59 58 53 48 43 37 32 53 7.6 53 53 49 44 38 33 27 1.These capacities are gross ratings.For net capacity,determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table,multiply this value by 3.415 MBH/kW to determine the motor heat,and deduct this heat from the gross capacity of the unit. 2.These ratings include the compressor and the condenser fan motors but not the supply air blower motor.The total condenser fan motor power input is 0.36kW.Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 11 TABLE 8: SUPPLY AIR BLOWER PERFORMANCE(3 TON BELT DRIVE) -SIDE DUCT APPLICATION UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 835 705 880 745 923 795 969 860 1013 970 - - - - 1600 811 655 854 695 898 740 942 790 986 840 1029 900 - - 1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905 1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790 31.2 1300 - - - - 816 590 862 635 907 675 951 715 995 750 1200 - - - - - - 834 585 881 630 927 665 970 705 1100 - - - - - - 809 550 855 590 900 625 942 665 1000 - - - - - - 782 510 829 545 872 858 919 625 900 - - - - - - - - 797 500 843 540 890 580 UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.90 1.00 1.10 1.20 1.30 1.40 1.50 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 - - - - - - - - - - 1600 - - - - - - - - - - - - - - 1500 - - - - - - - - - - - - - 1400 1055 875 - - - - - - - - - - - 31.2 1300 1036 780 1066 850 - - - - - - - - - - 1200 1011 735 1047 765 1075 800 - - - - - - - - 1100 987 690 1028 720 1060 750 1084 775 - - - - - - 1000 963 655 1005 680 1040 695 1068 715 1089 735 - - - - 900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - - 1.230/460/575 Volts 2.For 208 Volts multiply values by 0.95. 3.Includes allowances for a wet evaporator coil, 1"filters,and the heat exchangers.Refer to STATIC RESISTANCE Table for resistance values on applications other than gas/electric units with side duct airflows. 12 Unitary Products Group 292458-YTG-A-0207 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) -SIDE DUCT APPLICATION UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 41,2 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730 UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.90 1.00 1.10 1.20 1.30 1.40 1.50 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 - - - - - - - - - - - - 1900 1085 1210 - - - - - - - - - - - - 1800 1064 1145 1102 1180 - - - - - - - - - 1700 1040 1075 1081 1115 1121 1140 - - - - - - - - 41.2 1600 1020 1005 1060 1050 1100 1085 - - - - - - - - 1500 1003 945 1044 995 1086 1035 - - - - - - - - 1400 982 880 1024 920 1067 965 1107 1000 - - - - - - 1300 970 835 1010 870 1053 920 1099 960 - - - - - - 1200 953 780 992 815 1034 855 1080 905 - - - - - - 1.230/460/575 Volts 2.For 208 Volts multiply values by 0.95. 3.Includes allowances for a wet evaporator coil,1"filters,and the heat exchangers.Refer to STATIC RESISTANCE Table for resistance values on applications other than gas/electric units with side duct airflows. Unitary Products Group 13 292458-YTG-A-,0207 TABLE 10: SUPPLY AIR BLOWER PERFORMANCE(5 TON BELT DRIVE)-SIDE DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 UNIT AIR FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 TONNAGE CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440 2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340 51,2 2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225 1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095 1800 - - - - 855 815 903 860 950 905 988 940 1022 970 1700 - - - - - - 884 815 925 850 964 880 1001 910 1600 - - - - - - 864 770 908 805 948 835 987 870 1500 - - - - - - - - 882 740 926 780 965 830 AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 UNIT AIR FLOW 0.90 1.00 1.10 1.20 1.30 1.40 1.50 TONNAGE CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 - - - - - - - - - - - - - - 2400 1193 1665 - - - - - - - - - - - - 2300 1170 1580 1202 1620 - - - - - - - - - - 2200 1148 1480 1180 1530 - - - - - - - - - - 2100 1121 1385 1155 1425 1190 1475 - - - - - - - _ 51,2 2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - - 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - - 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - - 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - - 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 1.230/460/575 Volts 2.For 208 Volts multiply values by 0.95. 3.Includes allowances for a wet evaporator coil,1"filters,and the heat exchangers.Refer to STATIC RESISTANCE Table for resistance values on applications other than gas/electric units with side duct airflows. 14 Unitary Products Group • 292458-YTG-A-0207 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE)-SIDE DUCT APPLICATION UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 1150 2325 1182 2425 1212 2525 - - - - - 3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - - 2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130 612 2600 985 1425 1015 1475 1045 1540 1075 - 1630 1103 1715 1135 1760 1163 1825 2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600 2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325 2000 - - - - - - 919 1025 950 1100 982 1130 1014 1160 1800 - - - - - - - - 909 925 939 1005 968 1030 UNIT AIR AVAILABLE EXTERNAL STATIC PRESSURE-IWG3 TONNAGE FLOW 0.90 1.00 1.10 1.20 1.30 1.40 1.50 CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 - - - - - 3000 - - - - - 2800 1245 2190 - - - - - - - - - - - - 612 2600 1193 1920 1222 1990 1250 2060 - - - - - - - - 2400 1142 1675 1173 1730 1205 1800 1234 1885 - - - - - - 2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - - 2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600 1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360 1.230/460/575 Volts 2.For 208 Volts multiply values by 0.95. 3.Includes allowances for a wet evaporator coil,1"filters,and the heat exchangers.Refer to STATIC RESISTANCE Table for resistance values on applications other than gas/electric units with side duct airflows. • Unitary Products Group 15 292458-YTG-A-4J207 , TABLE 12: SUPPLY AIR BLOWER PERFORMANCE(3-6 TON DIRECT DRIVE) -SIDE DUCT APPLICATION AVAILABLE EXTERNAL STATIC PRESSURE-IWG2 UNIT MOTOR SPEED 0.20 0.30 0.40 0.50 0.60 TONNAGE CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI - - - - 1699 825 1650 785 1570 755 31 MED 1684 800 1631 780 1582 750 1524 720 1410 690 LOW 1487 710 1464 690 1421 670 1367 650 1315 620 HI 1996 960 1933 936 1868 910 1795 880 1722 845 41 MED 1804 838 1765 810 1714 785 1650 765 1589 735 LOW 1681 760 1640 738 1604 715 1541 695 1490 670 HI 2400 1155 2338 1125 2274 1095 2167 1045 2096 1010 51 MED 2290 1105 2214 1065 2145 1030 2071 990 1990 950 LOW 2150 1020 2100 990 2029 950 1965 910 1905 880 61 HI 2461 1480 2402 1440 2361 1395 2260 1350 2178 1305 UNIT AVAILABLE EXTERNAL STATIC PRESSURE-IWG2 TONNAGE) MOTOR SPEED 0.70 0.80 0.90 1.00 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1430 725 1360 700 1280 680 1180 655 31 MED 1324 650 1260 630 1185 610 1100 590 LOW 1246 605 1185 590 1110 570 1020 545 HI 1635 820 1544 790 1419 765 1300 740 41 MED 1508 705 1407 675 1306 645 1195 625 LOW 1416 645 1337 620 1230 595 1120 575 HI 1990 980 1887 945 1771 905 1629 855 51 MED 1911 920 1828 885 1724 835 1604 798 LOW 1816 838 1724 800 1644 770 1531 710 61 HI 2101 1260 2000 1205 1914 1155 1830 1110 1.Side Duct application(230/460/575 Volts) 2.Includes allowances for a wet evaporator coil,1"filters,and the heat exchangers.Refer to STATIC RESISTANCES Table for resistance values. TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA MOTOR ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT MODEL BLOWER (NOTCHED) SIZE RANGE OUTSIDE PITCH OUTSIDE PITCH PITCH (RPM) HP FRAME DESIG- DIA. DIA. BORE DESIG- DIA. DIA. BORE DESIG- LENGTH QTY. NATION (IN.) (IN.) (IN.) NATION (IN.) (IN.) (IN.) NATION (IN.) 3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 4 TON 790/1120 11/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 5 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1 6 TON 900/1250 1 1/2 56 1VL44 3.1-4.1 2.8-3.8 7/8 AK56 5.4 5.2 1 A36 37.3 1 1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air,upstream of any heating device. 16 Unitary Products Group 292458-YTG-A-0207 TABLE 14: STATIC RESISTANCES RESISTANCE,IWG DESCRIPTION CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 ECONOMIZER'3 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30 ELECTRIC 7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22 HEATERS' 20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 BOTTOM DUCT CONNECTIONS' 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22 COOLING ONLY2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32 1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables. 2.Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables. 3.The pressure through the economizer is greater for 100%outdoor air than for 100%return air.If the resistance of the return air duct system is less than 0.25 IWG,the unit will deliver less CFM during full economizer operation. TABLE 15: ELECTRIC HEATER CFM LIMITATIONS MINIMUM SUPPLY AIR CFM UNITMODELSIZE NOMINAL VOLTAGE HEATER SIZE NOMINAL KW TONS 5 7 10 15 20 30 208/230-3-60 1100 1100 1200 1200 1300 - 3 460-3-60 - 1100 1200 1200 1300 - 575-3-60 - - 1200 1200 1300 - 208/230-3-60 1300 1300 1300 1300 1300 - 4 460-3-60 - 1300 1300 1300 1300 - 575-3-60 - - 1300 1300 1400 - 208/230-3-60 1600 1600 1600 1600 1600 1600 5 460-3-60 - 1600 1600 1600 1600 1600 575-3-60 - 1600 1600 1600 1600 1800 208/230-3-60 1800 1800 1800 1800 1800 1800 6 460-3-60 - 1800 1800 1800 1800 1800 575-3-60 - - 1800 1800 1800 1800 Unitary Products Group 17 292458-YTG-A-.0207 , TABLE 16: ELECTRICAL DATA-D(CE, CG)O36-072 DIRECT DRIVE COMPRESSORS ID MIN. MAX.FUSE/ OD FAN MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR1 TONNAGE VOLTAGE RLA LRA MOTOR MOTOR MODEL NO. KW AMPS AMPACITY SIZE EACH EACH FLA FLA (AMPS) (AMPS) None -- -- 16.6 20 2CE045105252 4.0 11.1 19.4 25 208-3-60 8.7 72.0 1.3 4.4 2CE045107252 5.6 15.5 24.9 25 2CE04511025 8.0 22.2 33.3 35 2CE04511525 11.9 33.0 46.8 50 2CE04512025 15.9 44.1 60.7 70 None -- -- 16.6 20 2CE045105252 5.3 12.7 21.4 25 230-3-60 8.7 72.0 1.3 4.4 2CE045107252 7.5 18.0 28.1 30 D(CE,CG) 2CE04511025 10.6 25.5 37.4 40 036 2CE04511525 15.9 38.2 53.3 60 (3.0) 2CE04512025 21.2 51.0 69.2 70 None -- -- 9.1 15 2CE045107462 6.8 8.2 13.0 15 460-3-60 4.9 45.0 0.8 2.2 2CE045110462 10.1 12.1 17.9 20 2CE045115462 13.6 16.4 23.2 25 2CE045120462 19.5 23.5 32.1 35 None -- -- 7.3 15 575-3-60 3.9 36.0 0.8 2.2 2CE04511058 10.6 10.2 14.9 15 2CE04511558 15.9 15.3 21.3 25 2CE04512058 21.2 20.4 27.7 30 None -- -- 23.9 30 2CE045105252 4 11.1 23.9 30 208-3-60 14.1 105.0 1.3 5.0 2CE045107252 5.6 15.5 25.7 35 2CE04511025 8 22.2 34 35 2CE04511525 11.9 33.0 47.5 50 2CE04512025 15.9 44.1 61.4 70 None -- -- 23.9 30 2CE045105252 5.3 12.7 23.9 30 230-3-60 14.1 105.0 1.3 5.0 2CE045107252 7.5 18.0 28.8 35 D(CE,CG) 2CE04511025 10.6 25.5 38.1 40 048 2CE04511525 15.9 38.2 54.1 60 (4.0) 2CE04512025 21.2 51.0 70 70 None -- -- 11.9 15 2CE045107462 6.8 8.2 13 15 460-3-60 7.1 55.0 0.8 2.2 2CE045110462 10.1 12.1 17.9 20 2CE045115462 13.6 16.4 23.2 25 2CE045120462 19.5 23.5 32.1 35 None -- -- 9.7 15 575-3-60 5.8 44.0 0.8 2.2 2CE04511058 10.6 10.2 14.9 15 2CE04511558 15.9 15.3 21.3 25 2CE04512058 21.2 20.4 27.7 30 18 Unitary Products Group , 292458-YTG-A-0207 TABLE 16: ELECTRICAL DATA-D(CE,CG)036-072 DIRECT DRIVE(CONT.) COMPRESSORS ID MIN. MAX.FUSE/ MODEL OD FAN BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR1 TONNAGE VOLTAGE RLA LRA MOTOR MOTOR MODEL NO. KW AMPS AMPACITY SIZE EACH EACH FLA FLA (AMPS) (AMPS) None -- -- 27.9 35 2CE045105252 4 11.1 27.9 35 2CE045107252 5.6 15.5 27.9 35 208-3-60 16.0 125.0 1.3 6.6 2CE04511025 8 22.2 36 40 2CE04511525 11.9 33.0 49.5 50 2CE04512025 15.9 44.1 63.4 70 2CE04513025 22.2 61.6 85.3 90 None -- -- 27.9 35 2CE045105252 5.3 12.7 27.9 35 2CE045107252 7.5 18.0 30.8 40 230-3-60 16.0 125.0 1.3 6.6 2CE04511025 10.6 25.5 40.1 45 D(CE,CG) 2CE04511525 15.9 38.2 56.1 60 060 2CE04512025 21.2 51.0 72 80 (5.0) 2CE04513025 29.6 71.2 97.3 100 None -- -- 14.1 20 2CE045107462 6.8 8.2 14.3 20 460-3-60 8.0 66.5 0.8 3.3 2CE045110462 10.1 12.1 19.3 20 2CE045115462 13.6 16.4 24.6 25 2CE045120462 19.5 23.5 33.4 35 2CE045130462 28.8 34.6 47.4 50 None -- -- 11.3 15 2CE04511058 10.6 10.2 16 20 575-3-60 6.4 50.0 0.8 3.3 2CE04511558 15.9 15.3 22.4 25 2CE04512058 21.2 20.4 28.8 30 2CE04513058 30.4 29.3 39.9 40 None -- -- 31.7 40 2CE045105252 4 11.1 31.7 40 2CE045107252 5.6 15.5 31.7 40 208-3-60 18.9 146.0 1.3 6.8 2CE04511025 8 22.2 36.3 50 2CE04511525 11.9 33.0 49.8 50 2CE04512025 15.9 44.1 63.7 70 2CE04513025 22.2 61.6 85.5 90 None -- -- 31.7 40 2CE045105252 5.3 12.7 31.7 40 2CE045107252 7.5 18.0 31.7 40 230-3-60 18.9 146.0 1.3 6.8 2CE04511025 10.6 25.5 40.4 50 D(CE,CG) 2CE04511525 15.9 38.2 56.3 60 072 2CE04512025 21.2 51.0 72.2 80 (6.0) 2CE04513025 29.6 71.2 97.5 100 None -- -- 16.3 25 2CE045107462 6.8 8.2 16.3 25 460-3-60 9.5 73.0 0.8 3.6 2CE045110462 10.1 12.1 19.7 25 2CE045115462 13.6 16.4 24.9 25 2CE045120462 19.5 23.5 33.8 35 2CE045130462 28.8 34.6 47.8 50 None -- -- 13 15 2CE04511058 10.6 10.2 16.3 20 575-3-60 7.6 58.4 0.8 3.6 2CE04511558 15.9 15.3 22.7 25 2CE04512058 21.2 20.4 29.1 30 2CE04513058 30.4 29.3 40.2 40 1. HACR Type per NEC. 2. These electric heaters do not include a fuse box.If a fuse box is required to meet a local code(i.e.Chicago),the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 19 292458-YTG-A-J207 TABLE 17: ELECTRICAL DATA-D(CE,CG)036-072 BELT DRIVE COMPRESSORS ID MIN. MAX.FUSE/ OD FAN MODEL BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR1 TONNAGE VOLTAGE RLA LRA MOTOR MOTOR MODEL NO. KW AMPS AMPACITY SIZE EACH EACH FLA FLA (AMPS) (AMPS) None -- -- 17.4 25 2CE045105252 4.0 11.1 20.4 25 208-3-60 8.7 72.0 1.3 5.2 2CE045107252 5.6 15.5 25.9 30 2CE04511025 8.0 22.2 34.3 35 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70 None -- -- 17.4 25 2CE045105251 5.3 12.7 22.4 25 230-3-60 8.7 72.0 1.3 5.2 2CE045107252 7.5 18.0 29.1 30 D(CE,CG) 2CE04511025 10.6 25.5 38.4 40 036 2CE04511525 15.9 38.2 54.3 60 (3.0) 2CE04512025 21.2 51.0 70.2 80 None -- -- 9.5 15 2C E045107461 6.8 8.2 13.5 15 460-3-60 4.9 45.0 0.8 2.6 2CE045110461 10.1 12.1 18.4 20 2CE045115462 13.6 16.4 23.7 25 2CE045120462 19.5 23.5 32.6 35 None -- -- 7.5 15 575-3-60 3.9 36.0 0.8 2.0 2CE04511058 10.6 10.2 15.2 20 2CE04511558 15.9 15.3 21.6 25 2CE04512058 21.2 20.4 28.0 30 None -- -- 24.1 35 2CE045105252 4 11.1 24.1 35 208-3-60 14.1 105.0 1.3 5.2 2CE045107252 5.6 15.5 25.9 35 2CE04511025 8 22.2 34.3 35 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70 None -- -- 24.1 35 2CE045105252 5.3 12.7 24.1 35 230-3-60 14.1 105.0 1.3 5.2 2CE045107252 7.5 18.0 29.1 35 D(CE,CG) 2CE04511025 10.6 25.5 38.4 40 048 2CE04511525 15.9 38.2 54.3 60 (4.0) 2CE04512025 21.2 51.0 70.2 80 None -- -- 12.3 15 2C E045107462 6.8 8.2 13.5 15 460-3-60 7.1 55.0 0.8 2.6 2CE045110461 10.1 12.1 18.4 20 2CE045115462 13.6 16.4 23.7 25 2CE045120462 19.5 23.5 32.6 35 None -- -- 9.9 15 575-3-60 5.8 44.0 0.8 2.0 2CE04511058 10.6 10.2 15.2 20 2CE04511558 15.9 15.3 21.6 25 2CE04512058 21.2 20.4 28 30 20 Unitary Products Group .292458-YTG-A-0207 TABLE 17: ELECTRICAL DATA-D(CE, CG)036-072 BELT DRIVE (CONT.) COMPRESSORS ID MIN. MAX.FUSE/ MODEL OD FAN BLOWER ELECTRIC HEATER HEATER HEATER CIRCUIT BRKR1 TONNAGE VOLTAGE RLA LRA MOTOR MOTOR MODEL NO. KW AMPS AMPACITY SIZE EACH EACH FLA FLA (AMPS) (AMPS) None -- -- 26.5 35 2CE045105252 4 11.1 26.5 35 2CE045107252 5.6 15.5 26.5 35 208-3-60 16.0 125.0 1.3 5.2 2CE04511025 8 22.2 34.3 40 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70 2CE04513025 22.2 61.6 83.5 90 None -- -- 26.5 35 2CE045105252 5.3 12.7 26.5 35 2CE045107252 _ 7.5 18.0 29.1 40 230-3-60 16.0 125 0 1.3 5.2 2CE04511025 10.6 25.5 38.4 40 D(CE,CG) 2CE04511525 15.9 38.2 54.3 60 060 2CE04512025 21.2 51.0 70.2 80 (5.0) 2CE04513025 29.6 71.2 95.5 100 None -- -- 13.4 20 2CE045107462 6.8 8.2 13.5 20 460-3-60 8.0 66.5 0.8 2.6 2CE045110462 10.1 12.1 18.4 20 2CE045115462 13.6 16.4 23.7 25 2CE045120462 19.5 23.5 32.6 35 2CE045130462 28.8 34.6 46.6 50 None -- -- 10.6 15 2CE04511058 10.6 10.2 15.2 20 575-3-60 6.4 50.0 0.8 2.0 2CE04511558 15.9 15.3 21.6 25 2CE04512058 21.2 20.4 28 30 2CE04513058 30.4 29.3 39.1 40 None -- -- 29.9 40 2CE045105252 4 11.1 29.9 40 2CE045107252 5.6 15.5 29.9 40 208-3-60 18.9 146.0 1.3 5.0 2CE04511025 8 22.2 34 45 2CE04511525 11.9 33.0 47.5 50 2CE04512025 15.9 44.1 61.4 70 2CE04513025 22.2 61.6 83.3 90 None -- -- 29.9 40 2CE045105252 5.3 12.7 29.9 40 2CE045107252 7.5 18.0 29.9 40 230-3-60 18.9 146.0 1.3 5.0 2CE04511025 10.6 25.5 38.1 45 D(CE,CG) 2CE04511525 15.9 38.2 54.1 60 072 2CE04512025 21.2 51.0 70 70 (6.0) 2CE04513025 29.6 71.2 95.3 100 None -- -- 15.2 20 2CE045107462 6.8 8.2 15.2 20 460-3-60 9.5 73.0 0.8 2.5 2CE045110462 10.1 12.1 18.3 20 2CE045115462 13.6 16.4 _ 23.6 25 2CE045120462 19.5 23.5 32.4 35 2CE045130462 28.8 34.6 46.4 50 None -- -- 12.1 15 2CE04511058 10.6 10.2 15.2 20 575-3-60 7.6 58.4 0.8 2.0 2CE04511558 15.9 15.3 21.6 25 2CE04512058 21.2 20.4 28 30 2CE04513058 - 30.4 29.3 I 39.1 40 1. HACR Type per NEC. 2. These electric heaters do not include a fuse box.If a fuse box is required to meet a local code(i.e.Chicago),the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 21 292458-YTG-A;0207. , TABLE 18: PHYSICAL DATA MODELS D(CE,CG) 036 048 060 072 Centrifugal Blower(Dia.x Wd.in.) 12 X 10 12 X 10 12 X 10 12 X 11 EVAPORATOR BLOWER Fan Motor HP(Direct Drive) 1/2 3/4 1 1 Fan Motor HP(Belt Drive) 1 1/2 1 1/2 1 1/2 1 1/2 EVAPORATOR Rows Deep 3 3 3 4 COIL Fins Per Inch 13 13 13 13 Face Area(Sq.Ft.) 3.6 4.3 5.1 5.1 Propeller Dia.(in.) 24 24 24 24 CONDENSER FANS Fan Motor Hp 1/4 1/4 1/4 1/4 Nom.CFM 3400 3400 3400 3400 CONDENSER Rows Deep 1 1 1 2 COILS Fins Per Inch 16 16 22 16 Face Area(Sq.Ft.) 17.1 17.1 17.1 16.7 COMPRESSOR Quantity/Type 1/Recip 1 /Scroll 1 /Scroll 1/Scroll (Qty.Per Unit) Quantity Per Unit(15"X 20"X 1"or 2") 2 2 2 2 AIR FILTERS Quantity Per Unit(14"X 25"X 1"or 2") 1 1 1 1 Total Face Area(sq.ft.) 6.3 6.3 6.3 6.3 CHARGE Refrigerant 22 5/8 6/8 6/8 10/0 (lbs./oz.) TABLE 19: ELECTRIC HEAT CORRECTION FACTORS TABLE 20:VOLTAGE LIMITATIONS1 NOMINAL VOLTAGE VOLTAGE kW CAP.MULTI- POWER SUPPLY VOLTAGE PLIER MIN. MAX. 208 208 0.75 208/230-3-60 187 253 240 230 0.92 460-3-60 414 506 480 460 0.92 575-3-60 540 630 600 575 0.92 1. Utilization Range"A"in accordance with ARI Standard 110. 22 Unitary Products Group • , 292458-YTG-A-0207 TYPICAL POWER WIRING CONTACTOR _E.'- OHO FIELD-SUPPLIED CONTACTOR ,,1 DISCONNECT I � r SINGLE SS dp FIELD-SUPPLIED -- I L -y--0-'1"O--r- PHASE _ -r (0 0 0 DISCONNECT L -, -0-"I"0--l-> POWER - r- I THREE GROUND L J SUPPLY i L L r -0-"I"Sr F_ PHASE LUG REFERTOTHEELECTRICALDATA -_- GROUNDL —I -p.-.'"o-_L> POWER TABLES TO SIZE THE DISCONNECT LUG I I SUPPLY SWITCH,OVERCURRENT PROTEC- L J TION AND WIRING. TYPICAL CONTROL WIRING COOLING ONLY (24 VOLT THERMOSTAT) COOLING/ HEATING (24 VOLT THERMOSTAT) THERMOSTAT' UNIT TERMINAL THERMOSTAT' TERMINALS STRIP TB1 TERMINALS RV Q RH UNIT TERMINAL STRIP TB1 24 VOLT ADD vc v1 TRANSFORMER JUMPER Rc Y2a Y' 24 VOLT ��\� 1 E TRANSFORMER GF ivl Y2 O 1 F W1 �J lE 124 VOLT THERMOSTAT 2TH07701024.TO CONTROL THE ECONOMIZER 0 ON SECOND STAGE COOLING,USE THE THERMOSTAT 2TH0401224. /\ O COOLING/ HEATING (ELECTRONIC THERMOSTAT) 0 MULTI STAGE 124 VOLT THERMOSTAT 2ET07701024 TO CONTROL THE ECONOMIZER ON THE SECOND COOLINGSTAGE N 0024 ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF THERMOSTAT1 HEAT,USE THERMOSTAT 2TH04 TERMINALS UNIT TERMINAL RC STRIP TB1 24 VOLT ADD JUMPER 111 H R TRANSFORMER COOLING/ HEATING (ELECTRONIC THERMOSTAT) Yl SINGLE STAGE Y2 2 Y2 W1 Wl .... r 4 W2 3 W2 THERMOSTAT TERMINALS UNIT TERMINAL G G STRIP TB1 RH B C ' I LED 1 X RC R ADD Y Y1 cOM COED 4 DCC JUMPER W W1r... r ADD Al G G Q JUMPER A2 T TO REMOTE SENSOR 24 VOLT T 2TH040702224 IF USED TRANSFORMER 'ELECTRONIC PROGRAMMABLE THERMOSTAT 2E1-04700224(INCLUDES SUBBASE). 'ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024(INCLUDES SUBBASE). TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING,USE THERMOSTAT SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER. 2TH04700224. 'SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER. REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR P6 ON UNITS WITH ECONOMIZER.TERMINALS Al AND A2 PROVIDE A RELAY OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET-BACK POSITION. FIGURE 2- TYPICAL FIELD POWER&CONTROL WIRING Unitary Products Group 23 292458-YTG-A,0207. r • FIELD-SUPPLIED CONTROL BLOWER • DISCONNECT SWRCH BOX ACCESS LOCATION ACCESS .g(Direct-Drive units) ____________ _ 4_, CONDENSER �.` SCROLL ail Iry�lll COMPRESSOR FILTER •r"�� n 11,0(11 ACCESS ACCESS 1( I I 32S/8 j sa • RETURN AIR i, ELECTRIC ll> FRONT VIEW HEAT CCESS \\ .., 82.1/4 • SUPPLY AIR • bt-'7/8 • j• \ 212 314^PVC FEMALE • CONDENSER AIR COND.DRAIN A.B (See Detail"A") ' WIRING ENTRY 11-12 •r (s»Dewl"e") j > r---s' OUTDOOR AIR �..." 17-1/2 /. %' (Economizer) s-a/.e ! t 612 � �� I7-12 / I NIII 7-7/e e X841 UNIT BASE WITH RAILS BOTTOM SUPPLY G Shown separately to illustrate 8 RETURN AIR bottom duct openings and OPENINGS(SEE NOTE) 0. power connection locations. B-POWER WIRING ENTRY I/ ' NOTE For curbirounted units, refer to the duct hanger dimensions A-CONTROL WIRING ENTRY & of the curb br the proper size of the 3/8 supply and return air duct connections. FIGURE 3- UNIT DIMENSIONS (3 -6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIELD-SUPPLIED CONTROL I3LOWER 'l VENT AIR ACCESS DISCONNECT SWITCH BOX OUTLET HOOD LOCATION ACCESS _ (Direct-Drive units) dG,� CONDENSER -- SCROLLCOMPR. \ NO ACCESS • \ I II �QI� COMBUSTION AIR FILTER r_ •r- ACCESS--- I 1101111 INLET HODO ACCESS 1'-)`I o )0IIIIIII 4..3/B 0 F' to --7 32-5/B ' AGAS HEA T ri> RETURN AIR FRONT VIEW 1-- J C ACCESS GAS SUPPLY ENTRY 17-,--,-- 7„40 ..:k_\1 ' /821/4 , (t/2'NPT IATGAS VALVE) • SUPPLY AIR \�\ 32--- / /2-12 • 3/4"PVC FEMALE 44718 4 - /� yf COND.DRAIN - CONDENSER AIR (See Detail"Al WIRING ENTRY _........ _11-t2 T OQ (See Detail"B") j &12 ..„.'x.„,,-,--/' OUTDOOR AIR 17-1/2 // L__ti% (Economizer) 5-DM /�i 8-112 -------- �p -- $"\ 77.12 �' GAS SUPPLY ENTRY 7-7/B >'&3r4 (V2"NPTI AT GAS VALVE) L(I4 '' BOTTOM SUPPLY 4 e .,X8.1/8 /� 8 RETURN AIR `` �32-1/4 UNIT BASE WITH RAILS OPENINGS(SEE NOTE) 7` �� Shown separately to illustrate B POWER WIRING ENTRY /, a bottom duct openings,power and O ��' gas piping connection locations. 1111..lak:k\ ��A-CONTROL WIRING ENTRY NOTE:For curb-mounted units, 8-3r8 refer tocurb duct hanger r size th �` 01 the curb for the proper size of the supply and return air duct connections. FIGURE 4- UNIT DIMENSIONS (3-6 TON COOLING/GAS HEAT) FRONT VIEW 24 Unitary Products Group • , ,2,9248-YTG-A-..,—.,, 1.... 27-1/2 .1 -4 1-5/8 t J imon A il 27-1/2 -...-19-3/4 ID 1 0 0 C ) ( ) 0 0 1 y =0 a o CI 44-7/8 "1 DETAIL"A" FIGURE 5- UNIT WITH ECONOMIZER RAINHOOD 7-1/4 i I CZ— I 1 iefa 27-1/2 -- - _ -- : ----- ----,,,,,;."--.7"-" 1 A 10-114 1 19-1/8 81/4 -17) 0 =--) ,,,C=') 0 01 i I •Irapimionsiamanarennio mi. I "A" AP-4--- 44-7/8 I%, 1 REAR VIEW LH.END VIEW 4-3/8 DIMENSION"A" FIXED OUTDOOR 12 AIR DAMPER DETAIL"B" MOTORIZED DAMPER 16-1/2 FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD Unitary Products Group 25 292458-YTG-A-,02Q7, , . 7• �_ DUCT COVERS Units are shipped with all air duct openings covered. ' I — For side duct applications; 1.Remove and discard the supply and return air duct % � covers. ««: 4:4 111�z 2.Connect ductwork to duct flanges on the rear of the a.: `y:: '. Iii L unit. �t IN pir----.-1-----...._0411:::,..-4.-___ For bottom duct applications; _ ` � 4 3 1.Remove the side supply air duct cover to gain access y to the bottom supply air knockout panel. III, 2.Remove and discard the bottom knockout panel. 171/2 , \� f• 3.Replace the side duct cover. 111'2 4.With filter section access panel removed from the unit,remove and discard the bottom return air s1�i X12 �\ v knockout panel. REAR VIEW SIDE SUPPLY AND RETURN AIRS 5.Replace the filter access panel. DUCT OPENINGS 77/8 FIGURE 7- UNIT DIMENSIONS (REAR VIEW) TABLE 22: MINIMUM CLEARANCES LOCATION CLEARANCE 24"(Cooling/Electric Heat) FILTER I Front 32"(Gas Heat) ACCESS BLOWER MOTOR I _,O� 12"(Less Economizer) ACCESSINI Rear 36"(With Economizer or Fixed DOT PLUGS 100111.0, Air/Motorized Damper) Left Side(Filter Access) 24"(Less Economizer) FIELD-SUPPLIED 36"(With Economizer) DISCONNECT SWITCH w• LOCATION �/ Right Side(Cond.Coil) 24" MOUNTING BRACKET FOR DICONNECT SWITCH Below Unit (blowertlatlachedto Ne /-1.`�� 72"(For the blower compartment) A,B Above Unit2 (See NG DeIAVB( CONT-OL BOX Condenser Air Discharge) (See Detail ENTRY ACCESS 9 ) DISCONNECT SWITCH LOCATION AND MOTOR ACCESS PANEL FOR 1. Units may be installed on combustible floors made UNIT WITH"BELT-DRIVE"OPTION from wood or class A, B,or C roof covering material. 2. Units must be installed outdoors. Overhanging struc- FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCA- tures or shrubs should not obstruct condenser air dis- TION charge outlet. TABLE 21: UTILITIES ENTRY HOLE OPENING SIZE(DIA.) USED FOR Side A 7/8"KO1 Control Wiring2 Bottom Side B 2"K01 Power Wring Bottom C 1-5/8"KO Gas Piping(Front) D 1-1/2"KO Gas Piping(Bottom) 1. Opening in the bottom to the unit can be located by the side in the insulation. 2. Do not remove the 2"knockout ring. 26 Unitary Products Group • , .2924,58-YTG-A-0207 ROOF JACK 7 INSTALLATION 4,1411 i aill. ( i I I LI I 1 1 L 4 ROOF CURB 1 1---"-- ./../ INSTALLATION • _ : i ......... . ._.. 1 I i 1 I 1 I I 1 1 I 1 I 1 E E 1 1 i filE .1 .1 .1 I I I ..,--L..„—.L....— T I 1 SLAB ON GROUND 1-1-17-1"— INSTALLATION --T— M—r— T I I r— IIIIIIIIIIIIIIIIIIIIIIII////XM Malliniaini , f) IIIIIIIIMFIINIEMIIIIIIIIIIIIIIIIIIIEIIIIIIIIIIIIIII EEE' 0 0 MIIIMIIIIIIIIIIIIIIIIIIMIIIIIIIIIIIIIIIIIIIIIIIIIIII 11111111,11/1/801111 I..I If SPIIIIIIIIIIIIIIIismassomemmil 111111111111111111111111111111111111111111 I i f'' *.•-"•-..asiiii&o. **.reo•400---.mw, . .. ,.. . .... FIELD-SUPPLIED '10'• - ,..., DISCONNECT SWITCH 0-4_0 ...,.., ...._., ... I ( — 10 • -., ' ' ... -'or ''lir''''..'! `..-* ''.•., I ..." 1 . . -. :: ........., I ,. I ..A.:': .,AE-".^ • t"'' 'Act,....t.,...:— . ' 1:.---, -- 1 I __ 10". -_, , ''' ..i...,,.---=. , ,.. ,,,...---....- a ,.. ,.., co: ;„,,,,:.-t, ,...„..-....„... -. „.„.„, ........ , , ...„-- ,,...,, ., ,...-..„..,.... . 1 it ,t) •—• I -- DRIP LEG ,--•..- .tit .... 4 . ". ot." ''''"*.' .''' ...% ' t a ',........ . 1 e ,-,- ,....— '01 , .,,,, 41 1 „..4 , mol i -, t, ' 0,:, ,,,,.. • .4..-...--eio,'''. -,-,- , ...' I ••. ' ', " 1 41..%0-'''l ' *-4..4..".....•'---7/7-- 1111 44 .11 . ' --' 11' MANUAL ...00,411.100.0111 I I, 0 GAS SHUT-OFF it.,. , •0VALVE - P- 1 "'" - ,----;:•' ' 00111•14111\4440.1.000.00000# 1111.11101. isaileatat;;$11.41-`11 . 1 ROOF CURS ..1.7,1 CONDENSATE I ,.. 70001. l'TRAP 14/ TO GAS SUPPLY LINE 4.,.., NTROL WIRING SUPPLY AIR V DUCT C A.-,,- TO TO INDOOR 1,"1..'4;fz RETURN AIR POWER SUPPLY THERMOSTAT .'f,'' DUCT FIGURE 9- TYPICAL APPLICATIONS 27 Unitary Products Group 292458-YTG-A-02x7• , • 447/8A BACK OF UNIT 447/, A BACK OF UNIT 821/4 , 821/4 D F B B E C APPROXIMATE APPROXIMATE CENTER OF GRAVITY C CONDENSER COIL CENTER OF GRAVITY D CONDENSER COIL FRONT OF UNIT END OF UNIT END OF UNIT \�Y FRONT OF UNIT �l Y FIGURE 10- FOUR AND SIX POINT LOADING TABLE 23: D(CE, CG)4 AND 6 POINT LOADS WEIGHT DISTRIBUTION 4-Point Loading(Ib) 6-Point Loading(Ib) UNIT TOTAL A B C D A B C D E F DCE036 Cooling/Electric 565 125 123 157 160 84 83 82 104 105 107 DCG036N040 605 134 132 168 171 90 89 88 112 113 114 DCG036N079 625 139 136 173 177 93 92 91 115 117 118 DCE048 Cooling/Electric 615 137 134 171 174 91 90 89 113 115 116 DCG048N060 665 148 145 184 188 99 98 96 123 124 126 DCG048N099 685 152 149 190 194 102 100 99 126 128 129 DCE060 Cooling/Electric 640 142 140 178 181 95 94 93 118 119 121 DCGO6ON079 700 155 153 194 198 104 103 101 129 131 132 DCGO6ON099 710 158 155 197 201 105 104 103 131 132 134 DCE072 Cooling/Electric 720 160 157 200 203 107 106 104 133 134 136 DCG072N079 780 173 170 216 220 116 114 113 144 146 147 DCG072N099 790 175 172 219 223 117 116 114 146 147 149 TABLE 24: CENTER OF GRAVITY DIMENSION 3-5 TON 6 TON X 40-3/4" 44" Y 19-3/4" 22" 28 Unitary Products Group 292458-YTG-A-0207 TABLE 25: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON 6 TON DCE(Cooling Only) 565 615 640 720 N040 605 - - - BASIC UNIT DCG N060 - 665 (Gas/Electric) N079 625 - 700 780 N099 - 685 710 790 Economizer 50 Motorized Damper 26 5-7 kW 18 OPTIONS Electric Heater 10-15 kW 23 OR ACCY. 20-30 kW 28 Roof Curb 92 Barometric Relief/Fixed Air Damper 10 Belt-Drive Blower 5 COMPRESSOR DUCT 2" TYP. AND CONDENSER SUPPORT RAILS END OF UNIT BACK / OF UNIT SUPPLY* AIA � 14" RETURN' ir:::.:!k„iii,„ / AIR �" 5.� 4%,.., --or :.. 10,,,.. "0' . .:'''. 1, \ 4 1/2" 19-1/2" �� 19-112" .� J FRONT ��� 7 " OF UNIT 37-1/4" 2\ 'Supply and Return Air(including duct support rails) shown are typical for bottom duct applications. DUCT SIZES: Supply Air = 19-1/4" X 19-1/4" For location of horizontal duct applications Return Air = 19-1/4" X 19-1/4" (on back of unit), refer to Unit Dimension details. FIGURE 11 - ROOF CURB DIMENSIONS 29 Unitary Products Group co -n 0 C) C m N C') 0 0 I— C) C COOLING UNIT W/GAS - CONTROL CIRCUIT 208/ 230V , 460V Z 1 A 1 8 1 C 1 D 1 E 1 F I G I H 1 3 1 K I I j N I N I p I 0 1 R I s 1 1 CONTROL BOARD LIMIT TBI PHS-I © �.�CBI O PRI G UCO P7 0— —•239/6 -OU E0-20 I/R-�J Lai-0-200/R— O Q IPS! S5 — 00000000 17, XI 7 53 -j 2 AMP TI T82 212/BL�B r P 1 C. ) 238/ QUBQ -0--r21;57,.\--Q--A202/BR O LP51 Ht 242/8K PHS-I _ C) 2I3/BL S © 1 �I 2� 4 115/BR •y, XP51 I I —299/w `..- _____422,13v. Cf) {i 210/O- SD L -NV J 1) 133/BL • 211/0--O IPSI I O • SD�241/R TBI 136/BK PIP3�III/P��RED ORED{�112/R�PII-B 137/8R Q I 237/R —P2.1 m ��i51//''��8L12- I� I • SDS RWI-I D r°21-3-(3— v� _R2 111/R--07 IQS P1-7�-135/PR 438/R—�P 2.2 -^^ BLK I Q 439/BK-�P2.3 ICB PI-4--132/BL $2 �FIW L _ J .112CI -� ID-231/1 MI 232/:R BLK 0 LS 0 BLK CTS/3//W-._PI-60 FS S PI•I- �i C v T. SPARK pi-2�/31/8R I Z I I t�--233/BR - 229/R �m IFR - LNSORp4' 7.1 elI L FAN J 3230/ Q®O — 228/BR O 514 P14 72 � 221/R //�I 901/Ri0—1 435/PR Q I— (12r ••512•• •ECONOMIZER - W1212 -1 225/R- $DSA. TO O -REDO • R� 231/p 'B) 7) 2-902/8�8 ' 131/BR Q SIMPLICITY-- u�i SI ^��� II NETWORKzis r1 6-OUT 1 1 101/GY TR So 151/Bx I II"" t s! 132/BL LAS 56 FO , ®� OCCUPANCY t� 216/GT 12J 101/PR 4IN IGY EF�I_..ESo...___ o.�—RELATIVE SENSOR HUMIDITY 3�903/R.7 - C 0 0-206/BL-(II riW OF I I 3) - 217/PR 3� �— OUTDOOR AIR 1-1905/Y1 I ALTERNATE YT I10::..��� GAS VALVE I AMBP6� TI-OUT I 105/Y I - 152/11 I _ • DETAIL 201/BL�2 _ YI I) 218/r / "' N I 71-ECON I © 81 IT 2 Sr ry SI P13 c Ord 1 1) 219/W 5� RELATIVE HUMIDITY ry 1 N 3C1 901/H I I CO I LOGIC 407/8 62051 SENSOR $DRA. I 220/0 8 10 �P1 Sr. RETURN AIR N ®WN I �t X902/BR-0Q) W109/0 P T BRN C IF RI L J --Ns-221/01 1° 03�-cg03/R 7 C • • C� 318/BR T82 � 215/BR�' 1� 402/BR TRI TI BRN DAS I El L ._ .-..-..-.. .._..-..-..-..—.._..J d © WHEN BAS CONTROLLED ECONOMIZER 05/Y.8 Z RNP ® IS INSTALLED - SEE APPROPRIATE CAUTION - OPEN ALL DISCONNECTS — ' Q 220/O 02,19./R1IR o?21/0 ACCESSORY ceAsf DIAGRAM BEFORE SERVICING THIS UNIT 26 REMOTE MINIMUM POST ION POTENTIOMETER DETAIL G I 7 2 7 9 0 A R E V B 0 C v_ D N) v G) 4 uY vCo ag -< n H n G) G-) o a IV c 0 -a -,-.-1 7 ^- �N) N C) _-,, T 8 Xm 0_ H c w 0 0 N I D O n o 0O o 8 -0 0 v r Z G) C COOLING UNIT W/GAS - CONTROL CIRCUIT 380V/ 415V & 575V Z I A 18 1 c I D 1 E I F ) G I H I JIK 1 i 1 M 1 N 1 P 1 o R I S I q TBI 4600 380 PRI PHS-I CONTROL BOARD LIMIT PHS-I © ,CBI 4 ISV• Q Q OCR P1 "—"—'239/R - U '-Q-201IR Lr —200/R TI 422/BR T82 LPSI SS — ODDODDDD ▪ 53 212/8N 2 AMP 202/8R • r3 H 1 24V SEC 212/BL�B p5I ©i ▪ ID-236/N QUBQ TS VA - ^ /-0-1_0----2 213/BL-(5 LPSI I CO I H2 I 2) 299/N I 415/BR O HP51 ©I{�-447/Y 0�0 444/BR > 210/0--(4 �0 L __.",n 1� INS 433/BL • N 211/0--03 I�P51 I O • SD -244/111) PI.3—{-441/R��-RETBI D RED-0.442/R P137/8R Q 436/BK:,:.1 I P2-I I —23T/R -P2.4 rn FSI R (L — — I • $D..• AUX RMI-1 > IFRZ 411/R7.1 fV ---"3/411771-2''' P2-2 PI-TN. 435/PR —I LK---0 —_ S2 0 439/8K P2-3 ICB Pt-4---432/BL O L J •..IRIS-P-- Cy-I II, 231/Y MI 232/:8 LS RS FS S P1 -I— �+' O BLK O 0 :LK 434/0 PI-8 Z I C ( ) SPARK PI-2�431/BR M. 2 233/BR 229/R X FIR L FAx J 3230/ Q®O —I 228/8R -."-F-- 0 O Y2 227/R S14P14 901/R-•�S I— IV,... �12( ..-..-.._..-.._ _.. 435/PR 0 S12 ECONOMfZER - M7212 -I 225/9/ SDSA. 0 (7 TO -• O- -RED® • R— 234/R :0 11) 2.--902/8R1(3).&: -902/BR-06 Q 431/BR Q SIMPLICITY-- r1 1 S4 401/GY TR So 451/BK 1 I 9 0 LAS NETWORK r4 GOUT 1 2� 216/GY 2 RELATIVE HUMIDITY' 3—�3/R 432/BL O 410/GY EF EFI S6 _- 1 OCCUPAHCT 404/PR N �—So. "'RELATIVE SENSOR ED _ C O 03--208/BL-(III �I 3) 211/PR 3 OUTDOOR AIR 1 mop, 4 I ALTERNATE LOM 452/M 905/Y•8 GAS VALVE IAMBPBI TI-OUT I 405/7 I I —"' DETAIL zoT/eL—tz D J z1e/r 4 ti 8Q 81' 51 P13 y CD I TI-ECON� 4l 219/M 15 40T/w Sr I I ~ I�9011R-O� CD- ) 620f RELATIVE HUMIDITY SENSOR SDRA. LOGIC I I 408/0 PI Sr. RETURN AIR ti 220/0 18 0�902/BR� < ®M�221/O y 409/0 P T BRN ; 903/R 17 IA 0 IIF KR1) (- — J TB2 1 DAS 1 C EDI ' �'{ • 1 • C 318/8R 4 215/BR L I 402/BR TRI Ti 8RX L..-..-.._..CON _..-. _..-..-.._..-..J v © WHEN BAS CONTROLLED ECONOMIZER 905/Y.e IS INSTALLED - SEE APPROPRIATE CAUTION - OPEN ALL DISCONNECTS — 5 uoio....9„wRMP ® ACCESSORT (BAS) DIAGRAM 26I/R 21/0 BEFORE SERVICING THIS UNIT X REMOTE MINIMUM POSITION POTENTIOMETER DETAIL G I 7 2 7 9 I A R E V B I> M W TI Ni 0 C 2.1M v0 D 0 2aI— > Z DZ g 0 C COOLING UNIT W/ ELECTRIC HEAT — CONTROL CIRCUIT 208/ 230V , 460V & 575V Z I A I B 1 c 1 o I E 1 E I o 1 X I 3 1 N I i I M I I N I P 1 o I B I s 1 C CON7UC8 BOARD P7 LIMIT.._ 219/R lir 4.02::V, O LPSI S5 — 00000000 S3 781 © PHS-I MP3 XI �`CBI TI 782 212/BL-Q8 r P1 ®I ID 299/w— O ••—••439/R••—• -OUI o- F201/R 2 LAMPXfo-200/R-- �- —202/BR I 24v SEC M 213/13L-0 IL=S1 I g'-- -----1-.12 B2 75 YA = . t I 21t/w HPSI I— 210/0--�1 ®D L _MY J 11) 243/Gy I ELECTRIC HEAT 302/BR 353 2/I/BR m NPS( TBI .PNS-I 0 211/O-0 I_ I ® • SD 214/R 216/81 1 303/w P31•®. ESI SD 29/8' I (L .122/BR. I LN 2 II • 2301/GT• • •SEE ELECTRIC HEATFRZ SI P10/R15-I (ACCESSORY DIAGRAM J LK-13 TBIO 115/8 D3OII 0 i L JCR1r27 I0---23I/T MI 232/.Rrn 2)301/BL !FR I C I 2)-233/BR 229/R — — n •i I L FAN J 3)-230/w email 228/BR y O 02 227/R (I P-1901/R Q Z R 1 F6-- -512 —.._.._ECONOM12ER - w7212''---_.., 25/R--JJ__ SDSA. TO --11 RED® • �- 234/R 6� �7� 2--902/8 R-�6 O SIMPLICITY-- ��� B r1 G-OU7-1 S1 I 101/GT TR So 151/BNI 111 NETWORK 0 ® 29 216/GT 2� RELATIVE HUMIDITY: 3 903/RI 1 110/GY EF EFI r LAS 208/01.—0 _— ry=� IOCCUPANCY�I 3� 211/PR 13� 404/PR N• I��So. I • 1 I SII Y OUTDOOR AIR EO LAAMB 61 152/w 905/T . 71-OUT 1 105/T - I 1 0 3�201/BL-{2 _ OI I� 218/T p 1 — ^��73 I YI-ECON I LP]' l 81 /T 2 X Sr I SI P13 l� 1� 218/w 1 5J 107/0 8208 RELATIVE HUMIDITY I N n I-90"-05 7 C I LOGIC SENSOR SDRA. ED I wR 220/0 I8� 108/0 PI Sr. RETURN AIR �2-902/BR-06 N IE RI L J ®0221/0 •9� 109/0 P 7 SRN (3 903/R 17 I Q C T82 I 402/BR TRI TI BRN OAS ED ' CO • • • 318/88 215/88 ' Ie 1 is...), ® WHEN BAS CONTROLLED ECONOMIZER - - -� 905/Y 18 W IS INSTALLED - SEE APPROPRIATE CAUTION - OPEN ALL DISCONNECTS —... RMP ® ACCESSORY (BAS) DIAGRAM BEFORE SERVICING THIS UNIT C 220/0 O 269,1L0,00_19 l/R M221/0 REMOTE MINIMUM POSITION POTENTIOMETER DETAIL G I 7 2 7 9 3 A R E V A O C D Ni Zco 03 p Ni (7T UT '7 V co 0CQ H c 0 n Cn 0 D -o O IV C D -D J cm N coN C a rn CO 1 a -I C 0 CT 0 C/1 I D G) C) o a Qo O ---.1 r z O c COOLING UNIT W/GAS or ELECTRIC HEAT - POWER CIRCUIT 208/ 230 - 3- 60 W/ I PH IDFAN Z I A I B I c I D I E I F I G 1 H I J I K I L I w I N I P I Q I R I s I "'I FLASH CODES DESCRIPTION LEGEND: 5 PHS ON STEADY CONTROL FAILURE -REPLACE CONTROL POWER SUPPLY CCH AUG AUXILIARY LIMIT SWITCH 208/230.3.80 SEE ELECTRIC -60 —���11�BIK� (Q �y . O HEART BEAT NORMAL OPERATION CB CIRCUIT BREAKER USE COPPER I I 9/BK-TO LI I FLASH NOT APPLICABLE CCH CRANKCASE NEATER CONDUCTORS ONLY HEAT DIAGRAM CS CENTRIFUGAL SNITCH I I NOTE 4 2 FLASHES CONTROL WAITING ASCD• I I ___� �, I - -120/BK-TO L2 3 FLASHES HPSI COMPRESSOR LOCKOUT DFS DIRTY FILTER SWITCH 1 FLASHES NOT APPLICABLE FSI SWITCH, LOWEVAPI I I I I12/BK -.....1-121/BK-TO mL I I MI.) L�.. L3 N 5 FLASHES LPSI COMPRESSOR LOCKOUT OH GROUND I DSI ICOMPR 6(LASHES NOT APPLICABLE Or GAS VALVE © 111/8 K•Y - - - - --- -•• l;p 101/BK Ijl NPS! HIGH PRESSURE SWITCH I I MI-2 i FLASHES FSI COMPRESSOR LOCKOUT TCB IGNITION CONTROL BOARD -I- I l -04..9,.115/BKI --• -•---- f 1F , 102/BL t 773 8 FLASHES NOT APPLICABLE LPSI LOW PRESSURE SWITCHV tS LIMIT SWITCH 1 I MI.3 .- 9 FLASHES IGNITION CONTROL LOCKED OUT/ IGNITION CONTROL FAILURE/LIMIT TRIP MI CONTACTOR, COMPRESSOR GNU yjcal.,lg/BK,••— I€ 103/Y 1� C 10 FLASHES COMPRESSORS LOCKED OUT ON LOW OUTDOOR TEMPERATURE• M1 CONTACTOR, ID FAN �i_ II FLASHES COMPRESSORS LOCKED OUT BECAUSE THE ECONOMIZER IS USING FREE COOLING•PHS PHASE 1055 MONITOR ` ODFAN ...4 12 FLASHES BONER OVERLOAD RELAY TRIP RCI-2 RUN CAPACITORS BLK RMP POTENTIOMETER, REMOTE MINIMUM POSITION ire 13 FLASHES COMPRESSOR HELD OFT DUE TO LOW VOLTAGE• RS ROLLOUT SNITCH O II FLASHES CEPRON STORAGE FAILURE RR! RELAY. HEAT YEL O SDSA SMOKE DETECTOR, SUPPLY AIR RCI O OFF NO POWER OR CONTROL FAILURE SDRA SMOKE DETECTOR, RETURN AIR 107/Y FO-BRN •THESE FLASH CODES DO NOT REPRESENT ALARMS TI TRANSFORMER, 75 VA N NOTES: TB! TERMINAL BLOCK. 24V M2-I AES !DEAN W I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL TO TERMINAL BLOCK. COMMON ID i0 104/R Q 4, O AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION UCB UNIT CONTROL BOARD L OF THIS UNIT, P1/SI SOCKET/PLUG CONNECTION,24V, 9 PIN ON IGNITION CONTROL BOARD PRP W 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN P2/52 SOCKET/PLUG CONNECTION,24V, 3 PIN ON IGNITION CONTROL BOARD I SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND P3/53 SOCKET/PLUG CONNECTION,24V, 4 PIN ON(YAP PARTITION RC2 O DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH P4/SI SOCKET/PLUG CONNECTION,2/Y, 2 PIN ON EVAP PARTITION 199/T CO I O BRN 41 0 THE UNIT MOST BE REMOVED, IT MUST BE REPLACED WITH TYPE P6/56 SOCKET/PLUG CONNECTION,21V, 4 PIN ON EVAP PARTITION 105 DEGREE C. 600 VOLT WIRE OR EQUIVALENT CLEARLY RENUMBERED PB/S8 SOCKET/PLUG CONNECTION,24V, 2 PIN ON EVAP PARTITION CD FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. P12/S12 SOCKET/PLUG CONNECTION.21v, 9 PIN AT ECONOMIZER 113/Y DRAFT_MTR 3. THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY P13/S13 SOCKET/PLUG CONNECTION,24V, 4 PIN AT SMOKE DETECTOR PIA/VA SOCKET/PLUG CONNECTION,21V, / PIN AT SMOKE DETECTOR TCB T SINGLE PHASE CONDITIONS. 110/BK��I--�—RE• N Q FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT, MOVE PIS/SIS SOCKET/PLUG CONNECTION, LINE VI T, 3 PIN ON ODFAN 'TND UCB PI/SI SOCKFI/PLUG CONNECTION,24V, 4 PIN ON UNIT CONTROL BOARD TTI [� I CRANKCASE SIRE TO 208V TERMINAL ON TI. UCB P2/S2 SOCKET/PLUG CONNECTION,21Y. 3 PIN ON UNIT CONTROL BOARD WHT p 3 HEATERS ARE NOT FOUND IN UNITS WITH SCROLL UCB P3/53 SOCKET/PLUG CONNECTION,21V, /PIN ON UNIT CONTROL BOARD 2pgy 128/W 111111 COMPRESSORS. 23OV —I 6. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P4/S/SOCKET/PLUG CONNECTION,24V, / PIN ON UNIT CONTROL BOARDGAS Q © SIZEREMOANE D MINIMPER UMRCIE RCUF OCCUPPEDISwITCH IS INSTALLED. UCB PS/SS SOCKET/PLUG CONNECTION,24V. 6 PIN ON UNIT CONTROL BOARD PRI 0 UNITSONLY UCB P6/56 SOCKET/PLUG COXNfCT10X,24V, 2 PIN ON UNIT CONTROL BOARD Q TI AFL OTHERWISE JUMPER MUST BE INSTALLED BETWEEN 'OCC' AND 'R', UCB P7/57 SOCKET/PLUG CONNECTION,21 V, 8 PIN ON UNIT CONTROL BOARD0-d-217-51?-(1) TEMPERATURE CONTROLS N WHEN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE _ - 24V SEC DEVICE OPERATING TEMPERATURE !DEG F•) < 816/T. -.,-„- FIELD WIRING 75 VA = SEE CONTROLOPEN •/- CLOSE •/- IF SHONE DETECTOR(S) IS (ARE) INSTALLED. REMOVE PLUG(S) 811TH OPTIONAL DEVICES AND WIRING CIRCUIT DIAGRAM MARED JUMPER WIRE. FACTORY WIRING LAS 55 5 45 5 WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED. DESIRED SPEED PRESSURE CONTROLS FSI 26 5 4! S Z REMOVE WIRE NUT IwN1 AND CONNECT WIRES AS SHOWN IN REMOTE MINIMUM POSITION POTENTIOMETER DETAIL. CONNECTION LEAD HIGH MED LOW DEVICE OPERATING PRESSURE (P510) O WIRE 20t/R IS CONNECTED TO TBI WHEN PHASE LOSS MONITOR IS REO'D AT 104 HIGH MED low MOTOR TERM BLUE TAPE a( HIGH HIGH HPSI 10 3000 OPEN +/- CLOSE +/- CAUTION - OPEN A L L DISCONNECTS ® NOT INSTALLED.!DEAN MOTOR WIRED FOR HIGH SPEED. FOR LOW OR MED SPEED, Q ® 1PU04/RE T�IP.S(SEEE UDESIRED SPEED CHART) BLOCK ORANGE TAP(OFf TAPE OFF MED LPSI 22 5 45 5 BEFORE SERVICING THIS UNIT S. X ON SOME UNITS, WIRES PRP AND BRN MAY BE REVERSED. G I 7 2 7 3 8 A R E V A co I- 0 O rn X a D G) X D w E co W -n Y/ C m 0) C) 0 0 I— G) c COOLING UNIT W/GAS or ELECTRIC HEAT - POWER CIRCUIT 208/ 230 - 3- 60 Z I A I B I C I D I E I F I G I H I J I K I L I M I N I P I ° 1 R I s I FLASH CODES DESCRIPTION LEGEND: POWER SUPPLY CCN PHS ON STEADY CONTROL FAILURE -REPLACE CONTROL AUS AUXILIARY LIMIT SWITCH Cs, (((���I O CB CIRCUIT BREAKER 2101SE2COPPERO �~ I I `}' HEART BEAT NORMAL OPCRA1lOM CCHMCRANKCASE HEATER SEE ELECTRIC BLK-IIIII BLK ! I 119/BK-TO LI I FLASK -NOT APPLICABLE CS CENTRIFUGAL SWITCH CONDUCTORS ONLY HEAT DIAGRAM DFS DIRT?FILTER SNITCH I I I NOTE I 2 FLASHES CONTROL WAITING ASCD• :_ �, 1120/BK-TO L2 3 FLASHES HPSI COMPRESSOR LOCKOUT DSI SNITCH, MAIM DISCONNECT M FSI SWITCH, LOw EVAP TEMP I I112/BK I 1 FLASHES NOT APPLICABLE GNO GROUND I l —.. 73 I121/BK—TO L3 5 FLASHES LPSI COMPRESSOR LOCKOUT OR GAS VALVE DSI MI-I L..._.. 6 FLASHES NOT APPLICABLE HPSI HIGH PRESSURE SWITCH ©I -II//BK -- - I I OI 101/BK COMPR n LCB IGNITION CONTROL MI-2 - 7 RASHES FSI COMPRESSOR LOCKOUT LPSI LOM PRESSURE SWITCH _ / B FLASHES NOT APPLICABLE LS LIMIT SWITCH GND I l -(3'. 11° `E"115/BKI - -- -©--II © 102/BL Ike 9 FLASHES IGNITION CONTROL LOCKED OUT/ IGNITION CONTROL FAILURE/LIMIT TRIP -MI CONTACTOR, COMPRESSOR 1 I ( MI-3 C RASHES CONTACTOR, ID FAN - { I ©,7,.116/BKi" I © 103/Y 10 ASNES COMPRESSORS LOCKED OUT ON LOW OUTDOOR TEMPERATURE• PHS PHASEE LOSS MONITOR II FLASHES COMPRESSORS LOCKED OUT BECAUSE THE ECONOMIZER IS USING FREE COOLING•RC RUN CAPACITOR L ODF AN -I 2 FLASHED BLOWER OVERLOAD RELAY TRIP RHG RELAY. HOT GAS m RLR RMP POTENTIOMETER, REBUTS MINIMUM POSITION c N IS FLASHES COMPRESSOR HELD OFF DUE TO LOW YOTAGE• RS ROLLOUT SWITCH 9. O 14 FLASHES EEPROM STORAGE FAILURE PWG SELEN, HEAT - - YEL 1110 O OFF NO POWER 011 CONTROL FAILURE SHG SOLENOID, HOT GAS I24V,NE. NC BCI SLL SOLENOID, LIQUID LIME, 240, NO •THESE FLASH CODES DO NOT REPRESENT ALARMS SDSA SMOKE DETECTOR, SUPPLY AIR 107/7 I-�BpN SDRA SMOKE DETECTOR, RETURN AIR M2-1 W NOTES: Ti TRANSFORMER. 75 VA ©-II 0 104/RN IDFAN O TBI TERMINAL BLOCK. 21V U2-2 I I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL TB2 TERMINAL BLOCK, COMMON A___' W AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION UCB UNIT CONTROL BOARD ©-II 0 105/BR io I OF THIS UNIT. PI/SI SOCKET/PLUG CONNECTION,24V, 9 PIN ON IGNITION CONTROL BOARD O 2. CAUTION, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN P2/52 SOCKET/PLUG CONNECTION,21V, 3 OR/ PIN ON IGNITION CNTRL ARD 106/Y© i O SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND P3/43 SOCKET/PLUG CONNECTION,21V. /PIN ON EVAP PARTITION DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH P4/S1 SOCKET/PLUG CONNECTION,24A. 2 PIN ON EVAP PARTITION ICBTHE UNIT M CO TYPE P6/S6 SOCKET/PLUG CONNECTION.24v. 4 PIN ON EVAP PARTITION LOS DEGREEUST C. 600RVOLTED.WIREITORU ST EQUBIVALENT WIACLEARLYH RENUMBERED P8/58 SOCKET/PLUG CONNECTION,21V, 2 PIN ON EVAP PARTITION 113/1 I OHN6g H BLK M FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. P12/512 SOCKET/PLUG CONNECTION,21V. 9 PIN AT ECONOMIZER ® r 3. THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY P13/513 SOCKET/PLUG CONNECTION,21V, 1 PIN AT SMOKE DETECTOR IIS/BR I OI ND REI SINGLE PHASE CONDITIONS. P14/511 SOCKET/PLUG CONMECTION,21Y, 4 PIN AT SNORE DETECTOR A FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT, MOVE PIS/S15 SOCKET/PLUG CONNECTION.LINE VOLT, 3 PIN ON ODFAN 128/W 112/BK WIRE TO 208V TERMINAL ON Ti. UCB P1/SI SOCKET/PLUG COMXECTION.21O, 4 PIN ON UNIT CONTROL BOARDUCB P2/52 SOCKET/PLUG CONNECTION.24v. 3 PIN ON UNIT CONTROL BOARD DRAFT MOTOR X0 © COMPRESSOR$CRANKCASEEATERS ARE NOT FOUND iN UNITS WITH SCROLL UCB D3/53 SOCKET/PLUG COXXECTION,21V, /PIN ON UNIT CONTROL BOARD 230v �2PR� 2 STAGE HEAT ONLY GAS HEAT - 6. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P4/54 SOCKET/PLUG CONNECTION,21V, 1 PIN ON UNIT CONTROL BOARD O UNITS ONLY TY. © REMOVESIZE ANJUMPERMINIMUM WIREIIFUOCCUPIEDCITI SWITCH IS INSTALLED. UCH P5/55 SOCKET/PLUG CONNECTION.24v. 6 PiN ON UNIT CONTROL BOARD UCB P6/56 SOCKET/PLUG CONNECTION,24V, 2 PIN ON UNIT CONTROL BOARD Q(LJWV'LA1 TEMPERE CONTROLS DEVICE OPERATING UTEMPERATURE IDEG F'I Ill ® OTHERWISE JUMPER MUST BE INSTALLED BETWEEN OCC' AND 'R'. UCB P7/57 SOCKET/PLUG CONNECTION,240. 8 PIN ON UNIT CONTROL BOARD 24V SEC Y1'' _ WHEN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE 75 VA OPEN •/- CLOSE •/- 818/1. SEE CONTROL CIRCUIT DIAGRAM LAS 55 5 45 5 Z ® IF SNORE DETECTORISI IS (ARE) INSTALLED. REMOVE PLUG(S) WITH - -FIELD WIRING DEVICES AND WIRING FSI 28 5 U 5 RED JUMPER WIRE. ® WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED, FACTORY WIRING REMOVE WIRE NUT (KIN) AND CONNECT WIRES AS SHOWN IN PRESSURE CONTROLS O REMOTE MINIMUM POSITION POTENTIOMETER DETAIL.WIRE 201/R IS CONNECTED TO TBI WHEN PHASE LOSS MONITOR IS DEVICE OPERATING PRESSURE IPSIGIOPEN CAUTION - OPEN A L L DISCONNECTS ZI A ONT SOMEALLED.UNITS, WIRES 105/BR AND 106/Y MAY BE REVERSED. HPSI 380 •10 CLOSE 300 •IO BEFORE SERV (CING THIS UNIT CO LPSI 22 5 45 5 GI72779A REV A I- 0 c m NJ '. 0 01 -o D c o (1) -< c Z1 H D 0 E D 0 0 C N 73 v c -n N C '01 CO m o H n -1 n 0 V in F D 0 0 N.) O O -c9 0 -1 1— z z 0 c COOLING UNIT W/GAS or ELECTRIC HEAT - POWER CIRCUIT 460- 3- 60 W/ I PH IDFAN Z I A I B I c j D I E IF1 G I H I J I K I L I M I N I P 1 o J R I S l -I FLASH CODES DESCRIPTION LEGEND: [-Pk-) ON STEADY CONTROL FAILURE -REPLACE CONTROL AUG AU%ILLARY LIMIT SWITCH POWER SUPPLY CCH Q f 13 CB CIRCUIT BREAKER 180-3-80 LK-1II1II-BLK Q-119/BK--TO O HEART BEAT NORMAL OPERATION CCH CRANKCASE HEATER 380/115.3-50 I+B I _ LI I FLASH NOT APPLICABLE CS CENTRIFUGAL SWITCH 380-3-60 SEE ELECTRIC 2 FLASHES CONTROL WAITING ASCD• DFS DIRTY FILTER SWITCH USE COPPER HEAT DIAGRAM f H - I -120/BK-TO L2 DSI SWITCH, MAIM DISCONNECT COM DOCTORS ONLY NOTE / _ M 3 FLASHES HP51[OPPRESSOR LOCKOUT F51 SWITCH. LOW EVAP TEMP I I I I 1 I12/BK - _ 73 1(LASHES HOT APPLICABLE UXD GROUND DSI I I MI-1 L L.. 'J 4-121/13K--TO L3 5 FLASHES LPSI COMPRESSOR LOCKOUT GV GAS VALVE ^ 1 COMPR • 6 FLASHES NOT APPLICABLE )(PSI HIGH PRESSURE SWITCH I I �/��I-II I//BN --• ••-••-• - -- --- F� 101/BK lil TCB IGNITION CONTROL BOARD I - 1� - - - MI-2 ' ▪ 7 FLASHES F51 COMPRESSOR LOCKOUT LPSI LOW PRESSURE SWITCH IIS/BN 10218E /� 8 FLASHES INOTGH TIONAPPLICABLE ONTR LS LIMIT SWITCH -0....,...,0'. ■- /� 9 FLASHES IGNITION CONTROL LOCKED OUT/ IGNITION CONTROL FAILURE /LIMIT TRIP MI CONTACTOR, DMFAESSOR - IIMI-3 35/:L `/ M1 CONTACTOR, ID FAN GND -'Il6/BK+ lit 103/7 .24111, C 10 FLASHES COMPRESSORS LOCKED OUT ON LON OUTDOOR TEMPERATURE• PHS PHASE LOSS MONITOR JJ my II FLASHES COMPRESSORS LOCKED OUT BECAUSE THE ECONOMIZER IS USING FREE COOLING•RCI-2 RUN CAPACITORS 1` ODFAN 12 FLASHES BLOWER OVERLOAD RELAY TRIP RMP POTENTIOMETER, REMOTE MINIMUM POSITION m BLM RS ROLLOUT SWITCH c 13 FLASHES COMPRESSOR HELD OFF DUE 10 LOW VOLTAGE• RNI RELAY, HEAT IRO 11 FLASHES EEPROM STORAGE FAILURE SUN SMOKE DETECTOR. SUPPLY AIR TEL TEL 0(( NO POWER OR CONTROL FAILURE SORA TRANSFORMEE R,ORS RETURN AIR 107/T RCI--�-ORN 0 •THESE FLASH CODES DO NOT REPRESENT ALARMS T/ TRANSFORMER, 150VA w TBI TERMINAL BLOCK, 24V M2-1 TDF AN L NOTES: T82 TERMINAL BLOCK, COMMON 0 10 101/R ©© M I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL UCB UNIT CONTROL BOARDII 411) C AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION PI/SI SOCKET/PLUG CONNECTION,21V, 9 PIN ON IGNITION CONTROL BOARD PRP OF THIS UNIT. P2/S2 SOCKET/PLUG CONNECTION,21V, 3 PIN ON IGNITION CONTROL BOARD 41 O 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN P3/53 SOCKET/PLUG CONNECTION,24V, 4 PIN ON EVAP PARTITION RC2 SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND P1/S/ SOCKET/PLUG CONNECTION,21V, 2 PIN ON EVAP PARTITION 199/T I O ORR 0 /73 DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH THE UNIT MUST BE REMOVED, IT MUST BE REPLACED WITH TYPE P6/S6 SOCKET/PLUG CONNECT10M,2/V, / PIN ON EVAP PARTITION P8/58 SOCKET/PLUG CONNECTION,21V, 2 PIN ON EVAP PARTITION M 105 DEGREE C. 600 VOLT WIRE OR EOUIVALENT CLEARLY RENUMBERED P12/512 SOCKET/PLUG CONNECTION,21V, 9 PIN AT ECONOMIZER 113/Y 110/BK n DRAFT_NTR FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING, PI3/S13 SOCKET/PLUG CONNECTION,24V. / PIN AT SMOKE DETECTOR ICg 3. THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY P11l511 SOCKET/PLUG CONNECTION.21V, 1 PIN AT SMOKE DETECTOR SINGLE PHASE CONDITIONS. PI5/515 SOCKET/PLUG CONNECTION, LINE VOLT, 3 PIN ON ODFAN 13R/Y !I I- - REI ® REMOVED UCB PI/51 SOCKET/PLUG CONNECTION,21V, /PIN ON UNIT CONTROL BOARD /BOY 230V FD UCB P2l52 SOCKET/PLUG COXMECTION,21V, 3 PIN ON UNIT CONTROL BOARD WHY ALX CRANKCASE HEATERS ARE NOT FOUND IN UNITS WITH SCROLL UCB P3/53 SOCKET/PLUG CONNECTION.24V. 1 PIN ON UNIT CONTROL BOARD IBOY XCOMPRESSORS. UCB P//S/SOCKET/PLUG CONNECTION,21V, /PIN ON UNIT CONTROL BOARD PRI 7/ GAS HEAT 6 SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P5/55 SOCKET/PLUG COXNECTION,21V, 6 PIN ON UNIT CONTROL BOARD • Q UNITS ONLY M• © REMOVE SIZE NJUMPERMWIRE UM IRIFUOCCUPIT IEDI SWITCH IS INSTALLED. UCB P7/S7 SOCKET/PLUG CONNECTION,21V, 8 PIN ON UNIT CONTROL BOARDONTROL BOARD Ti ® OTHERWISE JUMPER MUST BE INSTALLED BETWEEN OCC' AND •R•. - - —FIELD WIRING 2/V SEC _ TEMPERATURE CONTROLS Z WREN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE ------•OPTIONAL DEVICES AND WIRING 75 VA ® 816/T. DEVICE OPERATING TEMPERATURE (DEG F•) IF SMOKE R WIRE.OR(S) IS (ARE) INSTALLED. REMOVE PLUG(S) WITH FACTORY WIRING SEE CONTROL CIRCUIT DIAGRAM OPEN +/- CLOSE •/- O RED JUMPER DESIRED SPEED PRESSURE CONTROLS LAS 55 5 /5 5 O ® WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED, REMOVE WIRE NUT (WW) AND CONNECT WIRES AS SHOWN IN CONNECTION LEAD HIGH MED LOW DEVICE OPERATING PRESSURE IPS IG) PSI 26 5 /I 5 O�F�9 REM TE MINIMUMCPOSITION TOTENTIOMETERHDETALOSS MONITOR IS REO'D AT 101 HIGH MED LOW OPEN +/- CLOSE +/- CAUTION - OPEN ALL DISCONNECTS /v NOT INSTALLED. MOTOR TERM BLUE TAPE OF( HIGH HIGH MPSI 380 10 300 10 (DEAN MOTOR WIRED FOR HIGH SPEED. FOR LOW OR MED SPEED, BLOCK ORANGE TAPE OFF TAPE OFF MED LPSI 22 5 45 5 BEFORE SERVICING THIS UNIT W A ONVSOME/UNITS,L WIRES PRP TAP.ND BRNF MAYS BER DESIRED SPEED� G175337A REV A 0 m X1 v a 0 E co 01 o) -n (3) G) C m co 0 0 0 I— _ Z G) C COOLING UNIT W/GAS or ELECTRIC HEAT - POWER CIRCUIT 460 - 3- 60 Z l A I B I C I D I E I F I G I H I J I K I i I N I N I P .I 0 I R I 5 1 FLASH CODES DESCRIPTION LEGEND: POWER SUPPLY CCH PNS ON STEADY CONTROL FAILURE -REPLACE CONTROL AUR AUXILIARY LIMIT SWITCH CB CIRCUIT BREAKER 160-3-80 (� N ART BEAT NORMAL OPERATION CCH CRANKCASE HEATER 380/115-3-50 BLK-i�����BLK� :? T .119/BK—TO LI O I RASH NOT APPLICABLE CS CENTRIFUGAL SWITCH 380-3-60 SEE ELECTRIC FLASHES CONTROL BAITING ASCD. DFS DIRTY FILTER SWITCH USE COPPER HEAT DIAGRAM - NOTE 1 DSI SWITCH,MAIN DISCONNECT CONDUCTORS ONLY __ ,�., I -120/BK—TO L2 m FLASHES HPSI COMPRESSOR LOCKOUT USD SWITCH. LOW(YAP TEMP I 1 1 I F- 112/BK _ •_ FLASHES NOT APPLICABLE GND GROUND I • 121/BK—TO L3 �L FLASHES LPSI COMPRESSOR LOCKOUTI L — ~ HPSIALVE HIGHOH GAS SWITCH I DS I I 1 'I —I COMPR n FLASHES NOT APPLICABLE ICB IGNITION CONTROL BOARD I I �O."I'I I /8K --•— —..—..— -- — — I © 01/BK D FLASHES F51 COMPRESSOR LOCKOUT LPSI LOW PRESSURE SWITCH I MI-2 �R�R LS LIMIT ! -I IB/BK+-.--.---4..--.—.-�IT--(� 102/BE le C)^ FLASHES NOT APPLICABLE MS [OMIT SWITCH,COMPRESSOR 1 V�© / FLASHES IGNITION CONTROL LOCKED OUT/ IGNITION CONTROL FAILURE /LIMIT TRIP M2 CONTACTOR, ID FAN I 1 MI-3 PHS PHASEULOSS MONITOR — 1 ©-,1,1I6/BK+ — -- -(�--�I 0 103/7 VI C I FLASHES COMPRESSORS LOCKED OUT ON LOW OUTDOOR TEMPERATURE ,PC PHM CAPACITOR GND `�\ _J ``\' II FLASHES COMPRESSORS LOCKED OUT BECAUSE THE ECONOMIZER IS USING FREE COOLING•RAG RELAY,HOT GAS ODFAN It FLASHES BLOWER OVERLOAD RELAY TRIP 'AMP POTENTIOMETER.REMOTE MINIMUM POSITION S m RLR SD SNORE DT TECTOR lie I3 FLASHES COMPRESSOR HELD OFF DUE TO LOW VOLTAGE• RWI RELAY,MEAT TEL IA II FLASHES EEPROM STORAGE FAILURE SDSA SHOO DETECTOR.SUPPLY AIR - - Q OFF NO POWER OR CONTROL FAILURE SORA SMOKf DETECTOR.RETURN AIR RCI SHG SOLENOID,HOT GAS, 217,NC Cs-� M •THESE FLASH CODES DO NOT REPRESENT ALARMS SIL SOLENOID,LIOUID LINE,240,NO 101/Y I ti"RN W TI TRANSFORMER, 75 VA �M2�-I M NOTES: TI TRANSFORMER, 115 OR IOU vA -I I © 104/BK !DEAN TBI TERMINAL BLOCK. 217 F-�MI 2 O I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY. LOCAL T82 TERMINAL BLOCK.COMMON W AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OCR UNIT CONTROL BOARD - -- I�If 105/BR leOF THIS UNIT. USR UNIT SHUTDOWN RELAY m2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN PI/SI SOCKET/PLUG CONNECIIOX,210,9 PIN ON IGNITION CONTROL BOARD SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND P2/S2 SOCKET/PLUG CONNECT ION,21Y,3 OR 1 PIN ON IGNITION CONTROL BOARD 108/0 r DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH P3/S3 DOCKET/PLUG CONNGCTIAN,2/V, 1 PIN ON EVAP PARTITION ICB Fj PIN ON EVAP PARTITION THE UNIT MUST RE REMOVED, IT MUST BE REPLACED WITH TYPE p6/S6 DOCKET/PLUG CONMECIIAN,2/V, 1 PIN ON EVAP PARTITION 13/Y 110/BK ) OxMDH�B L K Go 105 DEGREE C. 800 VOLT WIRE OR EOUIVALEMT CLEARLY RENUMBERED p6/56 SOCKET/PLUG CONNECTION,21v, 2 PIN ON EMAP PARTITION 0 FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. PIZ/512 SOCK[I/PLUG CONNECIIOM,2IV, 9 PIN AT ECONOMIZER 38/7 RE 3 THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY P13/513 SOCKET/PLUG CONNECTION.21V, 1 PIN AT SMOKE DETECTOR �1600 PR� � I°IND /� SINGLE E DPHASE CONDITIONS. P11/511 SOCKET/PLUG CONNECTION,210, 1 PIN AT SMOKE DETECTOR v . 4600 2300 0 CH DRAFT MOTOR P15/515 SOCKET/PLUG CONNECTION.LINE VOLT. 3 PIN ON ODEAN < VCR PI/51 SOCKET/PLUG CONNECTION,2IR. 1 PIN ON UNIT CONTROL BOARD ® CRANKCASE HEATERS ARE NOT FOUND IN UNITS WITH SCROLL uC8 P2/52 SOCKET/PLUG CONNECTION,2IR. 3 PIN ON UNIT CONTROL BOARD �'mQ TI 2 STAGE HEAT ONLY COMPRESSORS. TI GAS HEAT 6. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P3/S3 SOCKET/PLUG CONNECTION,ICY. 1 PIN ON UN11 CONTROL BOARD 210 SEC - UNITS ONLY SIZE AND NIMIPLM CIRCUIT MAAMXIMUM FY, OCR PI/51 SOCKET/PLUG CONNECTION,2IV. 1 PIN ON UNIT CONTROL BOARD 75 VA Z A REMOVE JUMPER WIRE IF OCCUPIED SWITCH IS INSTALLED. UCB PS/S5 SOCKET/PLUG OCR P6/56 SOCKET/PLUG CONNECTION,21Y,2 PIN ON UNIT CONTROL BOARD 6 PIN ON UNIT CONTROL BOARD SEE CONTROL CIRCUIT DIAGRAM TEMPERATURE CONTROLS 0 OTHERWISE JUMPER MUST BE INSTALLED BETWEEN 'OCC' AND 'R'. UCB P7/57 SOCKET/PLUG CONNECT1011,2NV.6 PIN ON UNIT CONTROL BOARD DEVICE OPERATING TEMPERATURE (DEG F•> WHEN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE OPEN ./- CLOSE ./- O A 818/Y. RLAS 55 5 45 5 IF SMOKE DETECTORS) IS (ARE) INSTALLED, REMOVE PLUG(SI WITH O RED JUMPER WIRE. --FIELD WIRING FSI 26 5 41 5 XJ ® WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED, -----••--.•OPTIONAL DEVICES AND WIRING PRESSURE CONTROLS REMOVE WIRE NUT (WN) AND CONNECT WIRES AS SHOWN IN FACTORY WIRING DEVICE OPERATING PRESSURE IPSIG) W REMOTE MINIMUM POSITION POTENTIOMETER DETAIL. CAUTION OPEN A L L DISCONNECTS All WIRE 201/R IS CONNECTED TO TBI WHEN PHASE LOSS MONITOR IS OPEN ./- CLOSE H/"NOT INSTALLED. 0 1 BEFORE S E R V I C I N G THIS U N I T 0 ONSOME UNITS, WIRES 105/BR AND 106/Y MAY BE REVERSED. LPSI 225 150 IS G172782A REV A m 71 c 0 N D m CD G) -P CO g H n c 0 D 0 'o O Fes) C 0 a C -n N KS) IV C CO 73 m o H c o v) L D G) n o ° O o C O I- C) C COOLING UNIT W/GAS OR ELECTRIC HEAT - POWER CIRCUIT 575- 3- 60 W/ I PH IDFAN Z I A I B J C I D I E 3 F I 6 1 H 3 J I N I L I N I N I P IOIR I 5 1 -I FLASH CODES DESCRIPTION LEGEND, CCH L� ON STEADY CONTROL FAILURE -REPLACE CONTROL AUG AUXILLART LIMIT SWITCH POWER SUPPLY 575-3.60 F'-�BLK�IIIj l-'H - - -FIELD WIRING CB CIRCUIT BREAKER SEE ELECTRIC I +. _..—...OPTIONAL DEVICES AND WIRING O H ART BEAT NORMAL OPERATIONNEAT DIAGRAM CCH CRANKCASE HEATER USE COPPER5 FACTORY WIRING I FLASH NOT APPLICABLE CS CENTRIFUGAL SWITCH CONDUCTORS ONLY NOTE 4 FLASHES CONTROL WAITING ASCD• OMR! DRAFT MOTOR RELAY FLASHES MPSI CpIPR(SSOR LOCKOUT DFS DIRTY FILTER SWITCH I I I ' DSI MI-I COMPR DSI SWITCN, MAIN DISCONNECT I .0..........0... ' 1 m _.. IIA/RK-I.-.._.X1=3.-. _•.__CHI-0-II © 101/BK 1j1 `A FLASHES NOT APPLICABLE FSI GRIUNH, LOW EVAP TEMP NI 2 (LASHES LPSI COMPRESSOR LOCKOUT GND GROUND GV GAS VALVEPR ( I -�1 ®- -. 115/BK-•-----'----�1I © 102/0L tF� FLASHES NOT APPLICABLE HPSI HIGH PRESSURE SNITCH `'l� �W FLASHES FSI CONPRE SSOR LOCKOUT TCB IGNITION CONTROL BOARD 1` ©..._..I_I16/8K-4 - 103/Y 1� xi FLASHES NOT APPLICABLE LPSI LOW PRESSURE SWITCH -� 15 LIMIT SWITCH GND L. FLASHES IGNITION CONTROL LOCKED OUI/ IGNITION CONTROL FAILUR[/LIMIT TRIP MI CONTACTOR, COMPRESSOR BLK ODFAN C I FLASHES COMPRESSORS LOCKED OUT ON LOW OUTDOOR TEMPERATURE • M2 CONTACTOR. ID FAN `I- -ORT-7 II FLASHES COMPRESSORS LOCKED DUI BECAUSE THE ECONOMIZER IS USING FREE COOLING•NCS RUNSCAPACITOR RMP MONITOR o RCI TEL 1110 -I 2 FLASHES BLOWER OVERLOAD RELAY TRIP POTENTIOMETER, REMOTE MINIMUM POSITION I TO LI IS FLASHES COMPRESSOR HELD OFF DUE TO LOW VOLTAGE• RS ROLLOUT SWITCH al RMI RELAY. HEAT —I"TO' l2 108/BK )I-O-BHN V II FLASHES EEPROM STORAGE FAILURE MA SMOKE DETECTOR. SUPPLY AIR : I rM2•I tri OFF NO POWER OR CONTROL TAILORS SORA SMOKE DETECTOR, RETURN AIR I -�TO L3 10T/T © I I © 104/R ©© IDFAN •THESE FLASH CODES DO NOT REPRESENT ALARMS Ti TRANSFORMER, 75 VA W T2 TRANSFORMER, 575V I NOTES, FBI TERMINAL BLOCK, 24V PRP mill C) I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY. LOCAL TB2 TERMINAL BLOCK. COMMON RC2 0 AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OCR UNIT CONTROL BOARD OF THIS UNIT, PI/SI SOCKET/PLUG CONNECTION,24V, 9 PIN ON IGNITION CONTROL BOARD 199/Y— ey 7 I OA" • v 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN P2/52 SOCKET/PLUG CONNECTION,24V, 3 PIN ON IGNITION CONTROL BOARD SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND P3/53 SOCKET/PLUG CONNECTION,24v, 4 PIN ON EVAP PARTITION DMRI O7 DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH THE UNIT MUST DE REMOVED, IT MUST BE REPLACED WITH TYPE PA/SA SOCKET/PLUG CONNECTION,24Y, 2 PIN ON EVAP PARTITION P12/512 SOCKET/PLUG CONNECTION,24V, 9 PIN AT ECONOMIZERI II US REQ 41110 M ISO DEGREE C. 600 VOLT WIRE OR EOUIVALENT CLEARLY RENUMBERED P13/513 SOCKET/PLUG CONNECTION,24V, 4 PIN AT SMOKE DETECTOR WH 128/W 3. THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY PIS/SIS SOCKET/PLUG CONNECTION. LINE VOLT. 3 PIN ON ODFAN DRAFT MOTOR -I SINGLE PHASE CONDITIONS. UCB PI/SI SOCKET/PLUG CONNFCTION,24v, PIN ON UNIT CONTROL BOARD 2/BN GAS HEAT ALN REMOVED. UCB P2/52 SOCKET/PLUG CONNECTION.24V. 3 PIN ON UNIT CONTROL BOARD UNITS ONLY -113/O- AL CRANKCASE HEATERS ARE NOT FOUND IN UNITS WITH SCROLL UCB P4/54 SOCKET/PLUG CONNECTION,24V, 4 PIN ON OMIT CONTROL BOARD IIB/T � COMPRESSORS. UCB P5/SS SOCKET/PLUG CONNECTION,24V, 6 PIN ON UNIT CONTROL BOARD 6. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P6/S6 SOCKET/PLUG CONNECTION,24V, UINIT 2 PIN ON CONTROL BOARD -117/T- G SIIE AND MINIMUM CIRCUIT AMPACITY. UCB P7/S7 SOCKET/PLUG CONNECTION.24V, 8 PIN ON UNIT CONTROL BOARD IM LL1 REMOVE JUMPER WIRE IF OCCUPIED SWITCH ISE INSTALLED. DESIRED SPEED 460V PRI I N2 H3 NA XI 02 ® OTHERWISE ECONOMIZER1R IS INSTALLED MUST BE TREMOVEBPLUG C WITHN C JUMPER WC* AND IRE CONNECTION LEAD HIGH MED LOW C 110/• Z ® 6 SMOKE DETECTOR(S) IS (ARE) INSTALLED, REMOVE PLUG(S) WITH REO'D AT 104 HIGH MED LOW Ti T2 6/IPAX %4 O IFRED JUMPER WIRE. MOTOR TERM BLUE TAPE OFF HIGH HIGH 4V SEC 2 O ®WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED, BLOCK ORANGE TAPE 0(f TAPE 0(( MED 75 VA REMOVE WIRE NUT (WN) AND CONNECT WIRES AS SHOWN IN SEE CONTROL CIRCUIT DIAGRAM O REMOTE MINIMUM POSITION POTENTIOMETER DETAIL. TEMPERATURE CONTROLS PRESSURE CONTROLS ,77 WIRE IS CONNECTED TO TBI WHEN PHASE LOSS MONITOR IS DEVICE OPERATING TEMPERATURE IDES F ) DEVICE OPERATING PRESSURE (PSIG) CAUTION OPEN A L L DISCONNECTS La IDFAN MOTOR WIRED FOR HIGH SPEED. FOR LOW OR MED SPEED. OPEN •/- CLOSE •/- OPEN ./- CLOSE •/-- BEFORE SERVICING THIS UNIT CO- ® ONVSOMEE AUNITS.LWIIRES PRP AND BRN MAY DBEIREVERSEDSPEED CHART) FSI 26 5 45 5 051 220 15 450 0 15 G I 7 2 7 6 7 A R E V A 0I- 0 m xi v D G) w V W M CO G) C M m N O C) 0 0 I— Z G) C COOLING UNIT W/GAS OR ELECTRIC HEAT - POWER CIRCUIT 575- 3- 60 z 1 A I B I C I D I E I F I 0 1 H I J I K I I I M I N I P I o I R I 5 I I RASH CODES DESCRIPTION LEGEND, CCH 13 OH STEADY CONTROL FAILURE -REPLACE CONTROL CXICIRCUIT BREAKER RSWITCH BPOWER SUPPLY SEE ELECTRIC FIR -UK -OLA� HEART BEAT NORMAL OPERATION 575-3-60 HEAT DIAGRAM,- CCN CRANKCASE HEATER Q C I FLASH NOT APPLICABLE CS CENTRIFUGAL SWITCH CONDUCTORS ONLY NOTE 4 c m C 2 FLASHES CONTROL WAITING ASCD• DFS DIRTY FILTER SNITCH _ —-—, - �_ DNR1,2 DRAFT MOTOR RELAY D51 ' i MI-I 3 FLASHES HPSI COMPRESSOR LOCKOUT I -( ©•.-.�_IIUBK-I-- - -- - -- - -- �1 I © 101/BK M DSI SWITCH, MAIN DISCONNECT \ COMPR 4 FLASHES NOT APPLICABLE PSI SNITCH, LOW EVAP TEMP 5 FLASHES LPSI COMPRESSOR LOCKOUT GND GROUND I I MI-2 GO GAS VALVE �j� IIS/BK-'- 6 FLASHES NOT APPLICABLE XPSI HIGH PRESSURE SWITCH "�� I 't 102/BL Le 7 FLASHES FSI COMPRESSOR LOCKOUT ICB IGNITION CONTROL BOARD I MI-3 /73 6 FLASHES NOT APPLICABLE LPSI LOW PRESSURE SNITCH GND �`,v„v—116/8K-•,- _ Ijc 103/Y 14 9 FLASHES IGNITION CONTROL LOCKED OUT I IGNITION CONTROL FAILURE/LIMIT TRIP LS LIMIT SWITCH MI CONTACTOR. COMPRESSOR . BLN ODFAN C 10 FLASHES COMPRESSORS LOCKED OUT ON LOW OUTDOOR TEMPERATURE• M2 CONTACTOR, ID FAN II FLASHES COMPRESSORS LOCKED OUT BECAUSE THE ECONOMIZER IS USING FREE COOLING.PHS PHASE LOSS MONITOR co ire 12 FLASHED BLOWER OVERLOAD RELAY TRIP RC ROTH CAPACITOR TEL RHO RELAY, HOT GAS RCI (� 13 FLASHES COMPRESSOR HELD OFF DUE TO LOW VOLTAGE• RMP POTENTIOMETER. REMOTE MINIMUM POSITION - - yRS ROLLOUT SWITCH c M2-101/Y pN I/FLASHES EEPROM STORAGE FAILURE �/1- '” RWI RELAY, HEAT Ell OFF NO POWER OR CONTROL FAILURE USDA SMOKE DETECTOR, SUPPLY AIR I PHS _ I-0-101/BK qp TDF AN H .4111 •THESE FLASH CODES DO NOT REPRESENT ALARMS SDRA SMOKE DETECTOR. RETURN AIR SHG SOLENOID, HOT GAS, 2/V, NC IIIM2-2 NOTES: TI SOLENOID. LIQUID LINE, 240. NO .TO LI A_J IF III 105/Bfl TI TRANSFORMER, 75 VA I _ TO L2 !!YY �, O I. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL T2 TRANSFORMER, 575V AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION TBI TERMINAL BLOCK. 240 -TO 13 106/7 0 W OF THIS UNIT. TB2 TERMINAL BLOCK. COMMON :....2=7"..L=77.1. DT CT STAGE ONLY 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN OCR UNIT I BOARD IL 7--I 5 127/BK—J--�6LK m SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND PI/SI SOCKET/PLUG CONNEC710N,21V,9 PIN ON IGNITION CONTROL BOARD I 128/Y DM 1 !� DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH P2/52 SOCKET/PLUG CONNECTION,21v,3 OR/PIN ON IGNITION CONTROL BOARD Q O RE. fill THE UNIT MUST BE REMOVED. IT MUST BE REPLACED WITH TYPE P3/53 SOCKET/PLUG CONNECTION,21V, 1 PIN ON EVAP PARTITION WH ITS DEGREE C. 600 VOLT WIRE OR EQUIVALENT CLEARLY RENUMBERED P1/51 SOCKET/PLUG CONNE CTION,21Y, 2 PIN ON EVAP PARTITION 128/w--� 3. FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. P12/512 SOCKET/PLUG CONNECTION,2/V, 9 PIN AT ECONOMIZER 0 THREE PHASE MOTORS ARE INHERENTLY PROTECTED UNDER PRIMARY P13/513 SOCKET/PLUG CONNECTION,210, 4 PIN AT SMOKE DETECTORAll DRAFT MOTOR 11 XSINGLE PHASE CONDITIONS. P1//511 SOCKET/PLUG CONNECTION,21V, 4 PIN AT SMOKE DETECTOR 3/• GAS HEAT Q REMOVED. P15/515 SOCKET/PLUG CONNECTION, LINE VOLT, 3 PIN ON ODFAN 112/BN UNITS ONLY < UCB PI/SI SOCKET/PLUG CONNECTION,210, /PIN ON UNIT CONTROL BOARD M Q CRANKCASE HEATERS ARE NOT FOUND IN UNITS WITH SCROLL I OCR P3/S3 SOCKET/PLUG CONNECTON,210, 3 PIN ON UNIT CONTROL BOARD 117/Y COMPRESSORS. UCB P3/S3 SOCKET/PLUG CONNECON,21V, / PIN ON UNIT CONTROL BOARD N. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER UCB P1/S/ SOCKET/PLUG CONNECTION,21V, 1 PIN ON UNIT CONTROL BOARD IIA/T ZSIZE AND MINIMUM CIRCUIT AMPACITY. UCB PS/SS SOCKET/PLUG CONNECTION,21V, 6 PIN ON UNIT CONTROL BOARD Q REMOVE JUMPER WIRE IF OCCUPIED SWITCH IS INSTALLED. UCB P6/S6 SOCKET/PLUG CONNECTION,21V, 2 PIN ON UNIT CONTROL BOARD I H2 H3 HA XI 2 0 ® OTHERWISE JUMPER I ZERRISUST INSTALLE DTREMOVEBPLUGEN WITHCJUMPER WIRE UCB P7/51 SOCKET FIELD WIRINGT10N,21Y, 6 PIN ON UNIT CONTROL BOARDIRQIP T1 110/• T2 X INC 1 61/PR O0 ® IF BSMOKE DETECTOR'S) IS 'ARE) INSTALLED. REMOVE PLUG'S) WITH FACTORY LWIRING ES AND WIRING 21y SEC ® RED JUMPER WIRE. 75 VA = WHEN REMOTE MINIMUM POSITION POTENTIOMETER IS INSTALLED, TEMPERATURE CONTROLS PRESSURE CONTROLS SEE CONTROL CIRCUIT DIAGRAM REMOVE WIRE NUT 'WNL AND CONNECT WIRES AS SHOWN IN C A REMOTE MINIMUM POSITION TEN DETAIL. All RE20 /RSCONNECTD TOEBIWHEPHASELOSS MONITOR IS DEVICE OPERATING TEMPERATURE (DEG F•1 DEVICE OPERATING PRESSURE IPSIGI CAUTION - OPEN PEN ALL DISCONNECTS ISCONNECTS OPEN ./- CLOSE ./- OPEN ./- CLOSE ./- BEFORE SERVICING THIS UNIT el WIRES 105/BR AND 106/Y MAY BE REVERSED. LAS FSI 55 28 5 5 45 AI 5 XPSI 5 LPSI 380 22 IO 5 300 10 15 5 G I 7 2 7 8 5 A R E V B m X c 0 ry 3a CD iu G) rA CO aQ E H o o N D G) O O N C P] I . .22458-YTG-A-0207 GUIDE SPECIFICATIONS UNIT CABINET GENERAL Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered Units shall be manufactured by York International Unitary paint finish, certified at 1000 hours salt spray test per Products Group in an ISO 9001 certified facility. ASTMB117 standards. Indoor blower section shall be insu- lated with a minimum 1/2"thick insulation, coated on the air- York's Sunline 2000TH units are convertible single package- side.Aluminum foil faced insulation shall be used in the units.Although the units are primarily designed for curb furnace compartment and be fastened with ridged fasteners mounting on a roof,they can also be slab-mounted at ground to prevent insulation from entering the air stream. Cabinet level or set on steel beams above a finished roof. Cooling panels shall be"large"size, easily removable for servicing only and cooling with gas heat models are available with a and maintenance. Full perimeter base rails shall be provided wide variety of factory-mounted options and field-installed to assure reliable transit of equipment, overhead rigging and accessories to make them suitable for almost every applica- proper sealing on roof curb applications. Disposable 1"filters tion.All units are self-contained and assembled on full perim- shall be furnished and be accessible through a removable eter base rails with holes in the four corners for overhead access door, sealed airtight. Units filter track shall be rigging. Every unit is completely piped,wired, charged and designed to accommodate either 1"or 2"filters. Fan perfor- tested at the factory to simplify the field installation and to mance measuring ports shall be provided on the outside of provide years of dependable operation.All models(including the cabinet to allow accurate air measurements of evaporator those with an economizer)are suitable for either bottom or fan performance without removing panels or creating air by- horizontal duct connections. Models with power exhaust are pass of the coils. Condensate pan shall be internally sloped suitable for bottom duct connections only. For bottom duct, and conform to ASHRAE 62-89 self-draining standards. Con- remove the sheet metal panels from the supply and return air densate connection shall be a minimum of 3/4" I.D.female openings through the base of the unit. For horizontal duct, and be a ridged mount connection. remove the supply and return air panels on the rear of the INDOOR(EVAPORATOR) FAN ASSEMBLY unit. The indoor fan shall be direct drive, multi-speed,or a factory All non-Scroll compressors include crankcase heaters and all installed belt drive assembly that includes an adjustable pitch compressors have internal pressure relief. Every refrigerant motor pulley.Job site selected brake horsepower(B.H.P.)shall circuit includes a liquid line filter-drier,a discharge line high not exceed the motors nameplate horsepower rating, plus the pressure switch and a suction line with a freezestat and low service factor. Units shall be designed not to operate above pressure/loss of charge switch.The unit control circuit service factor. Fan wheel shall be double-inlet type with for- includes a 75 VA transformer,a 24-volt circuit breaker and a ward-curved blades,dynamically balanced to operate relay board with a compressor lockout circuit, a terminal strip smoothly throughout the entire range of operation.Airflow for thermostat wiring, plus an additional set of pin connectors design shall be constant air volume. Bearings shall be sealed to simplify the interface of additional field controls.All units and permanently lubricated for longer life and no maintenance. have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTMB117 procedures.All models OUTDOOR(CONDENSER) FAN ASSEMBLY are CSA listed.All models include a 1-year limited warranty The outdoor fan shall be of the direct-driven propeller type, on the complete unit. Compressors and electric heater ele- discharge air vertically, have aluminum blades riveted to a ments carry a 5-year warranty.Aluminized steel tubular heat corrosion resistant steel spider bracket and shall be dynami- exchangers carry a 10-year warranty. cally balanced for smooth operation.The outdoor fan motor DESCRIPTION shall be totally enclosed with permanently lubricated bear- ings, internally protected against overload conditions and Units shall be factory-assembled,single packaged, Electric staged independently. Cooling/Gas Heat, Electric Cooling/Optional Electric Heat REFRIGERANT COMPONENTS and designed for outdoor mounted installation. Compressor: The 3 thru 5 ton units shall have SEER ratings of 10.0 and the 6 ton unit shall have minimum EER ratings of 9.0.They a. Shall be internally protected with internal high pres shall have built-in field convertible duct connections for down sure relief and over temperature protection. discharge supply/return or horizontal discharge supply/return, b. Shall have internal spring isolation and sound muf- and be available with factory installed options or field installed fling to minimize vibration and noise, and be exter- accessories.The units shall be factory wired, piped, charged nally isolated on a dedicated, independent with R-22 refrigerant and factory tested prior to shipment.All mounting. unit wiring shall be both numbered and color coded.All units Coils: the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, a. Evaporator and condenser coils shall have alumi- classified to ANSI Z21.47, UL 1995/CSA No. 236 standards. num plate fins mechanically bonded to seamless Unitary Products Group 39 292458-YTG-A-0207. internally enhanced copper tubes with all joints GAS HEATING SECTION brazed. Special Phenolic coating shall be available Shall be designed with induced draft combustion with post as a factory option. purge logic, energy saving direct spark ignition, and redun- b. Evaporator and Condenser coils shall be of the dant main gas valve.Venter wheel shall be constructed of direct expansion,draw-thru, design. stainless steel for corrosion resistance.The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized Refrigerant Circuit and Refrigerant Safety Components shall steel for corrosion resistance and allowing minimum mixed include: air entering temperature of 25°F. Burners shall be of the a. Independent fixed-orifice expansion devices. inshot type, constructed of aluminum coated steel and con- tain air mixture adjustments.All gas piping shall enter the unit b. Filter drier/strainer to eliminate any moisture or for- cabinet at a single location through either the side or curb, eign matter. without any field modifications. Integrated control boards c. Accessible service gage connections on both suc shall provide timed control of evaporator fan functioning and tion and liquid lines to charge, evacuate, and mea burner ignition. Heating section shall be provided with the fol- sure refrigerant pressure during any necessary lowing minimum protection: servicing or troubleshooting without losing charge. a. Primary and auxiliary high-temperature limit d. The refrigeration system shall provide at least 15°F switches. of sub cooling at design conditions. b. Induced draft motor speed sensor. UNIT CONTROLS c. Flame roll out switch (manual reset). a. Unit shall be complete with self-contained low-volt- d. Flame proving controls. age control circuit protected by a resetable circuit breaker on the 24 volt transformer side. e. If any of the above safety devices trip,a LED (light- emitting diode) indicator shall flash a diagnostic b. Unit shall incorporate a lockout circuit which pro- code that indicates which safety switch has tripped. vides reset capability at the space thermostat or base unit, should any of the following standard ELECTRIC HEATING SECTION safety devices trip and shut off compressor. An electric heating section,with nickel chromium elements, c. Loss-of-charge/Low-pressure switch. shall be provided in a range of 5 thru 30 KW, offering two stages of capacity- 16 KW and above on 208/230 volt heat- d. High-pressure switch. ers and 20 KW and above on 460 and 575 volt heaters.The e. Freeze-protection thermostat, evaporator coil. heating section shall have a primary limit control(s)and auto- f. If any of the above safety devices trip, a LED(light- matic reset to prevent the heating element system from oper- emitting diode) indicator shall flash a diagnostic ating at an excessive temperature.The heating section code that indicates which safety switch has tripped. assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single g. Unit shall incorporate"AUTO RESET"compressor point power supply with branch circuit fusing (where over temperature,over current protection. required). h. Unit shall operate with conventional thermostat UNIT OPERATING CHARACTERISTICS designs and have a low voltage terminal strip for easy hook-up. a. Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum i. Unit control board shall have on-board diagnostics load criteria of ARI Standard 210/240. and fault code display. j. Standard controls shall include anti short cycle and b. The compressor,with standard controls, shall be low voltage protection, and permit cooling operation capable of operation down to 0°F outdoor tempera down to 0°F. ture. k. Control board shall monitor each refrigerant safety c. Unit shall be provided with fan time delay to prevent switch independently. cold air delivery before heat exchanger warms up (Gas heat only). I. Control board shall retain last 5 fault codes in non volatile memory,which will not be lost in the event of ELECTRICAL REQUIREMENTS a power loss. All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. 40 Unitary Products Group ,292458-YTG-A-0207 STANDARD LIMITED WARRANTIES • BAROMETRIC RELIEF DAMPER-Contains a rain hood, air inlet screen, exhaust damper and mounting • Compressor 5 Years hardware. Used to relieve internal air pressure through • Heat Exchanger 10 Years the unit. • Electric Heat Element 5 Years • PROPANE CONVERSION KIT-Contains new orifices and gas valve parts to convert from natural to L.P. gas. • Other Parts 1 Year One per unit required. OPTIONAL OUTDOOR AIR(Shall be made available by • HIGH ALTITUDE -NATURAL GAS-Contains orifices either/or): required for applications between 2000 and 6000 feet altitude. • ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER-Outdoor and return air dampers that are inter- • HIGH ALTITUDE-PROPANE GAS-Contains orifices locked and positioned by a fully-modulating, spring required for applications between 2000 and 6000 feet return damper actuator.The maximum leakage rate for altitude. Must be used with propane conversion kit. the outdoor air intake dampers shall not exceed 2% • LOW NOX-Required to reduce the emission of nitrogen when dampers are fully closed and operating against a oxides below 40 nanograms per joule. pressure differential of 0.5 IWG.A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return • GAS PIPING-Contains 1/2" pipe nipples,fittings and air damper assembly to take in CFM of outdoor air to gas cock(including panel assess gaskets) required for meet the minimum ventilation requirement of the condi- bottom gas supply connection with external shut off. tioned space during normal operation. During econo- • POWER EXHAUST OPTION -To work in conjunction mizer operation, a mixed-air temperature control shall with economizers. modulate the outdoor and return air damper assembly to • prevent the supply air temperature from dropping below ELECTRIC HEATERS 55°F. Changeover from compressor to economizer oper- • ECONOMIZER/MOTORIZED DAMPER RAIN HOOD- ation shall be provided by an integral electronic enthalpy Contains all hood panels and the hardware for assem- control that feeds input into the basic module.The out- bling. door intake opening shall be covered with a rain hood • MANUAL OUTDOOR AIR DAMPER that matches the exterior of the unit.Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- • COIL GUARD KIT-Guard for condenser coil. pressor operation is also possible. Dampers shall fully • HAIL GUARD close on power loss. • FLUE EXHAUST EXTENSION OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE • TECHNICOAT PHENOLIC COATED CONDENSER • ROOF CURB- 14"and 8" high,full perimeter curb with COIL wood nailer(shipped knocked-down). • ELECTRONIC SINGLE ENTHALPY ECONOMIZER Unitary Products Group 41 292458-YTG-A-p2O7. , 42 Unitary Products Group k2Q2458-YTG-A-0207 Unitary Products Group 43 ' , * Subject to change without notice. Printed in U.S.A. 292458-YTG-A-0207 Copyright<;2007 by Unitary Products.All rights reserved. Supersedes: 255040-YTG-A-0506 Unitary 5005 Norman Products York OK Group Drive 73069