Loading...
Report (2) /q2/0 s6(/ 84.7agowi iZo R � / cizni INSTALL CONFIDENCE SUBMITTAL DATARECE1VED For: Quotation JUL 302018 Order#: Date: 07/10/2018 CITY OF-TIG -D Project: Barrows Rd BUILDING DIVISION Project#: Location: Beaverrton OR Purchaser: Hunter Davisson Submitter: Dolan Miles Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 Date Project07/10/2018 Name J YORK* Barrows Rd Project Number INSTALL CONFIDENCE Client/ Purchaser Hunter Davisson Submittal Summary Page Qty Tag # Model# Description 1 ZE060H12A2C1AAA1A1 5 Ton, York Small Sunline Single Packaged R-410A Air Conditioner, Single Stage Cooling, 11.8 EER/ 14.0 SEER, Single Stage Gas Aluminum Steel, 125 MBH Input, 208/230-3-60, Direct Drive • Dry Bulb Economizer and Hood (No Barometric Relief Damper) with Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015, California Title 24, AMCA 511) • 1 HP Direct Drive Blower • 1"Throwaway Filters • Smart Equipment Controller including Discharge Air, Return Air, and Outdoor Air Temperature Sensors. • Microchannel All Aluminum Condenser Coil, Copper tube/Aluminum fin Evaporator Coil • Galvanized Steel Drain Pan • Standard Access Doors 1 RD Barometrric"Relief Damper with Hood Kit(Downflow Unit or Duct , .Mounted) 1 2SD04701724 Smoke Detector Kit w/Mounting Hardware for Supply or Return Air (Horizontal/Downflow) Equipment start-up and commissioning by a factory trained technician is recommended. Contact your supplying distributor or sales representative for additional information &guidance. Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 Kfi Small Sunline (3-6 Ton , layoR Package) N543 Page:3 Single Package R-410A Air Conditioner Project Name: Barrows Rd Unit Model#: ZE060H12A2C1AAA1A1 Quantity: 1 System: ZE060H12A2C1AAA1A1 Cooling Performance y „ Total gross capacity 61.1 MBH , = ,„ Sensible gross capacity 45.4 MBH „, ,` Seasonal Efficiency(at ARI) 14.00 SEER ,,, Efficiency(at ARI) 11.80 EER Ambient DB temp. 95.0 °F ' !i�1�� . . Entering DB temp. 80.0 °F Gl Entering WB temp. 67.0 °F Leaving DB temp. 59.0 °Fr Leaving WB temp. 57.3 °F Power input(w/o blower) 4.28 kW ;:,01 , -ww, '�'' Sound power 82 dB(A) :- , ,.,'. Refrigerant type R-410A Sys1 6 lbs 6 oz Gas Heating Performance 1, Entering DB temp. 60 °F Heating output capacity(Max) 100 MBH 5 Ton Supply air 2000 CFM Heating input capacity(Max) 125 MBH • York Units are Manufactured at an ISO 9001 Registered Facility and Each Leaving DB temp. 106.3 °F Rooftop is Completely Computer-Run Tested Prior to Shipment. Air temp.rise 46.3 °F Unit Features SSE 80.0 % •Stages 1 Single Stage Cooling Supply Air Blower Performance -, • Single Stage Gas Aluminum Steel • 125 MBH Input Supply air 2000 CFM • Unit Cabinet Constructed of Powder Painted Steel,Certified At 1000 Hours Ext.static pressure 0.64 IWG Addl.Unit Losses(Options/Accessories) 0.11 IWG Salt Spray Test(ASTM B-117 Standards) Blower speed 1103 RPM • Either Supply and/or Return can be Field Converted from Vertical to Duct location Bottom Horizontal Configuration without Cutting Panels. Motor rating 1.00 HP • Full Perimeter Base Rails with Built in Rigging Capabilities Actual required BHP 1.02 HP • Scroll Compressor Power input03 kW 2 Elevation 203 ft. • Dry Bulb Economizer and Hood(No Barometric Relief Damper)with Drive type DIRECT Economizer Fault Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC Speed tap 5 2015,California Title 24,AMCA 511) Outside/Mixed Air • 1 HP Direct Drive Blower Outside Air Cfm 400 CFM • Solid Core Liquid Line Filter Driers • Unit Ships with 1"Throwaway Filters Electrical Data • Replacement Filters:2-(15"x 20"x 1"or 2")and 1 -(14"x 25"x 1"or 2"). Power supply 208-3-60 Unit accepts 1"or 2"wide filters. Unit min circuit ampacity 32 Amps • Single Point Power Connection Unit max over-current protection 40 Amps • Short Circuit Current:5kA RMS Symmetrical Dimensions&Weight • Through-the-Curb and Through-The-Base Utility Connections Hgt 33 in. Len 83 in. Wth 45 in. • Microchannel All Aluminum Condenser Coil,Copper tube/Aluminum fin Weight with factory installed options 757 lbs. Evaporator Coil Clearances • Galvanized Steel Drain Pan • Right 24 in. Front 32 in. Back 36 in. Standard Access Doors .fop 72 in. Bottom 0 in. Left 36 in. J Standard Unit Controller: Smart Equipment Control Board Note: Please refer to the tech guide for listed maximum static pressures •• An Integrated Low-Ambient Control,Anti-Short Cycle Protection,Lead-Lag, Fan On and Fan off Delays, Low Voltage Protection,On-Board Diagnostic .AMERMAN and Fault Code Display.Allows all units to operate in the cooling mode down ~ CERTIFIED,';auauty � � m, - to 0°F outdoor ambient without additional components or intervention. • Safety Monitoring-Monitors the High and Low-Pressure Switches,the Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition Failures,Safety Lockouts and Repeated Limit Switch Trips. BAS Controller • Smart Equipment Controller including Discharge Air,Return Air,and Outdoor Air Temperature Sensors. Warranty • One(1)Year Limited Warranty on the Complete Unit • Five(5)Year Warranty-Compressors and Electric Heater Elements • Ten(10)Year Warranty-Aluminized Heat Exchanger Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 'AYORK' Small Sunline (3-6 Ton Page:4 Package) N543 Single Package R-410A Air Conditioner Project Name: Barrows Rd Unit Model#: ZE060H12A2C1AAA1A1 Quantity: 1 System: ZE060H12A2C1AAA1A1 Factory Installed Options ZE060H12A2C1AAA1A1 York Small Sunline Single Packaged R-410A Air Product Category: ZE Conditioner17, 11.8 EER/14.0 SEER 1l1 2 g Nominal Cooling Capacity: 060 5 Ton Single Stage Cooling Single Stage Gas Aluminum Steel h� Heat Type and Nominal Heat Capacity: H12 125 MBH Inputk 1 HP Direct Drive Blower Blower Option: A Direct Drive Voltage: 2 208/230-3-60 Dry Bulb Economizer and Hood (No Barometric Relief Damper)with Economizer Fault Detection& Diagnostic Economizer/Damper: C (Meets ASHRAE 90.1-2013, IECC 2015, California Title 24,AMCA 511) i s Service Options: 1 Sensor Options: A Smart Equipment Controller including Discharge Air, Controls: A ; Return Air, and Outdoor Air Temperature Sensors Microchannel All Aluminum Condenser Coil, Copper Refrigeration: A tube/Aluminum fin Evaporator Coil dditional Options: 1 1"Throwaway Filters Galvanized Steel Drain Pan Cabinet Options: A Standard Access Doors Product Generation.• _ Field Installed Accessories • 1 RD0410 - Barometric Relief Damper with Hood Kit(Downflow Unit or Duct Mounted) (6.0 lbs) • 2SD04701724 -Smoke Detector Kit w/Mounting Hardware for Supply or Return Air (Horizontal/Downflow) (16.5 lbs) Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 ray RYOR ( Small Sunline (3-6 Ton Package) N543 Page: Single Package R-410A Air Conditioner • Project Name: Barrows Rd Unit Model#: ZE060H12A2CIAAAIA1 Quantity: 1 System: ZE060H12A2CIAAAIA1 Consolidated Drawing NOT1.ES FOR OUTDOOR USE ONLY. N OPERATING CENTER OF GRAVITY 4 POINT CORNER LOADS (LBS) (BASE UNIT) 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. TONNAGE I WEIGHT (LBS) LOCATION (BASE UNIT) 3. MIN. CLEARANCES TO BE: T (BASE UNIT) X Y A B C D RIGHT SIDE: 24 [609,6] 3 ZE 470 [213] 34.5 [876,3] 18.25 [463,6] 111 [50] 80 [36] 117 [53] 162 [73] LEFT SIDE: 24609,6 (LESS ECONOMIZER) 4 ZE 598 271 36 €914,4] (WITH ECONOMIZER) [ ] 36 [914,4] 18.50 [469,9] 139 [63] 108 [49] 154 [70] 198 [90] FRONT: 24 609,6] (COOLING/ELECTRIC HEAT) 5 ZE 632 [287] 37.5 [952,5] 18.2 [462,3] 139 [63] 117 [53] 171 [78] 204 [93] 32 ]]€812,8] (GAS HEAT) REAR: 12 304,8 (LESS ECONOMIZER) 3 ZF 468 [212] 33 [838,2] 18.25 [463,6] 114 (52] 76 [35] 111 [50] 167 [76] 36 914,4[[ (WITH ECONOMIZER OR FIXED 4 ZF 541 [245] 31.50 [800,1] 18.50 [469,9] 138 [63] 85 [39] 122 [55] 196 [89] AIR/MOTORIZED DAMPER) 5 ZF 569 [258] 37 [939,8] 15 [381] 105 [48] 86 [39] 170 [77] 208 [94] TOP: 72 11828,8] 31.62 6 ZF 640 290 37 [939,8] 15 [381] 118 (54] 96 [44] 192 [87] 234 106 BOTTOM: 0 0 [ ] [ ] 4. FOR CONTACTYOUR LLER SAPPLICATION ENGINEERINGERV CE AND OPERATIONAL DEPARTMENT. [803,3] _ 6.12 3 ZR 575 [261] 40 [1016] 20 [508] 132 [60] 125 [57] 155 [70] 164 [74] 5. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY [155,5] 4 ZR 585 [265] 40 [1016] 20 [508] 134 [61] 127 [58] 158 [72] 167 [76] ROISOF RECURB ONLY. IF OMMENDED THATUNIT IS THE DUCTSUAREDSIDE SUPPORTEDPBY' IT 7.25 18.26[184,0] [463,7] 5 ZR 590 [268] 40 [1016] 20 [508] 135 [61] 128 [58] 159 [72] 168 [76] CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 3 XN 610 [277] 38.3 [972,8] 18.75 [476,3] 136 [62] 119 [54] 165 [75] 190 [86] 6. SIDE DUCT FLANGES ARE 0.875" [22,2] HIGH. 1.80 27.54 -- 4 XN 616 [279] 38.2 [970,3] 18.4 [467,4] 135 [ ] [ ] [ ] BOTTOM DUCTS DO NOT HAVE FLANGES. [45,8] [699,6] [61] 117 53 169 77 195 88 7. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES 5 XN 620 [281] 38.6 [980,4] 18 [457,2] 132 [60] 117 [53] 174 [79] 197 [89] THE LOWEST NEGATIVE STATIC. + REAR 8. DIMENSIONS IN 1 1 ARE IN MILLIMETERS OR KILOGRAMS. 3 XP 575 [261] 39 [990,6] 20 [508] 135 [61] 121 [55] 151 [69] 168 [76] 9. OPTIONAL COIL GUARD, GAS HEAT, ECONOMIZER HOOD, -5.89 4 XP 585 [265] 39 (990,6] 20 [508] 137 [62] 124 [56] 154 [70] 171 [78] DISCONNECT OUTLET/INLETWHOOD'SHOWN. 5.51 OUTLET, AND 5.51 [149,6] 5 XP 590 [268] 39 [990,6] 20 [508] 138 [63] 125 [57] 155 [70] 172 [78] iti EXCEPT XN& XP(HEAT PUMP) UNITS. (140,0] A^ B - DIRECTION OF AIRFLOW f f 12.26— r 115 S CENTER OF GRAVITY �[3113]� 2 J,1],� �` NM 11.50 POWER WIRING BOTTOM ENTRY 3.00 02.00 [50,8] (I�}i `ib� RIGHT IIIIIIIIIIII E 0/A / , [76,2] [292,1] T _I 17'50 ��0 '� iiIII i 4.00 s[ ,5] \� -_��j� = IIIIIIIIIIII [101,6] 1 1 "` IIIIIIIIIIII RETURN / u 11.50 19.08 Y SUPPLY 0/A (292 1] 484,6] V IIIIIIIIIIII �., [ 8.23 �� ��� [209,2] ! ii1.e���1��0 MI } f D 11.06 6.48 C [1656.51)• 4.58[116,3] [281,0] [164,7] 17.50 7.62 [31 CONTROL WIRING BOTTOM ENTRY 32.09 - AS SUPPLY BOTTOM ENTRY 01.50 [38,1] K.O. 17.50 . 2] [193,6] 62 00.88 [22,2] [815,2] (0.50 [12,7] NPT AT GAS VALVE ECONOMIZER HOOD 01.97 K.O. X - VENT AIR OUTLET HOOD [44444,, 35] [803,2] (OPTIONAL) [50,' COMBUSTION AIR INLET HOOD REAR TASHIWN IIET) DISCONNECT SWITCH (RAIN HOOD NOT SHOWN IN THIS VIEW) COVER (OPTIONAL) 4 1 ACCESS F � COMP. Il 11 BLOWER CONVENIENCE OUTLET BLOW ACCES ACCESS27.35 32.55 ACCESS COVER (OPTIONAL) ;� ACCESS ° [826,7] L[694,7] 1 - 2,2] K.O. .. —I Mil--•Ik— .. 3.78 I 4.38 6.94 ---- 18.58 --- [96,0] [111,1] [176,2] 44.88 [471,9] 4.42 31.89 GAS SUPPLY ENTRY [1139,8] COIL GUARD 0.75 PVC P ]FPT 19.67 [112,3] [810,0] X1.63 [41,4] (OPTIONAL) COND. DRAIN [499,7] 2.55 — 82.19 - RIGHT VIEW LEFT VIEW [64,7] [2087,6] FRONT VIEW Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 ayoRK. Small Sunline (3-6 Ton Page:6 Package) N543 Single Package R-410A Air Conditioner Project Name: Barrows Rd Unit Model#: ZE060H12A2C1AAA1A1 Quantity: 1 System: ZE060H12A2C1AAA1A1 Typical Application ROOF JACK / / INSTALLATION f i () o 1 1 .. b. a °"11 1 t II ' „ }} ' ROOF CURB t i f INSTALLATION I I i I 1 I1 ; I 1 I I ; I 4 I II I 1 I [ r11 .._,_-1_,„,„—L.---,4 11 d I SLAB ON GROUND --t----f- INSTALLATION 1 1 1 / c— . e a a FIELD-SUPPLIED t s ._,�. DISCONNECT SWITCH .,, 1 "� , lk b ii 4 qrk • 4. - - -0`?‘ ' _ 1 i ...a . r „ ''-^* -.."'., i ------ - •-- , ,1. „.......;.,...1*. " , 1 i. .4}`''•,,.. i : .-'i .- DRIP LEG - 'r'- • � iiat a � , , ` I tit t 1,.. . "'``'+ !6 ( M MANUAL ' ” " . I.`� li . .,err riper t GAS SHUT-OFF C i tr-ve t,I wa" rr •�M r a VALVE MMtt : �e si M�I! q>wA t/ ROOF CURB 1 I CONDENSATE TRAP0411 TO GAS SUPPLY LINE 1 SUPPLY AIR DUCT TO CONTROL WIRING POWER TO INDOOR4sr::1 RETURN AIR SUPPLY THERMOSTAT DUCT Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 rillIFORIC Small Sunline (3-6 Ton Package) N543 Page:7 Single Package R-410A Air Conditioner Project Name: Barrows Rd Unit Model#: ZE060H12A2C1AAA1A1 Quantity: 1 System: ZE060H12A2C1AAA1A1 Typical Field Power and Control Wiring TYPICAL POWER WIRING CONTACTOR — L] 0 0FIELD-SUPPLIED CONTACTOR cP34 DISCONNECT SINGLE a.. FIELD-SUPPLIED 4 — P L DISCONNECT -I--0--,"s}-r-› PHASE 4 c) 0 0 L. r r'- 1 7 -41--0' 0--oI"> POWER 1 1 1 1 i GROUND L J SUPPLY _1_, L •..... I 1 i C7fr.".r:j.:> ir> THREE = I L 1 -0--,-.30--,-> PHASE LUG REFER TO THE ELECTRICAL DATA GROUND L —J _0..'I—0——t-> POWER TABLES TO SIZE THE DISCONNECT LUG I I SUPPLY SWITCH,OVER CURRENT L J PROTECTION AND WIRING, TYPICAL COOL/HEAT CONTROL WIRING COOLING ONLY (24 VOLT THERMOSTAT) COOLING/ HEATING (24 VOLT THERMOSTAT) THERMOSTATUNIT TERMINAL THERMOSTAT' TERMINALS STRIP TEl TERMINALS -0 UNIT TERMINAL ADD —€ STRIP TEl -0 TRANSFORMER 24 VOLT JUMPER 0 0 E0_ 0 24 VOLT TRANSFORMER -0 .111. 0 0 -o 1 E 124 VOLT THERMOSTAT.TO CONTROL THE ECONOMIZER ON SECOND 0 STAGE COOLING,USE A 2 STAGE COOLING THERMOSTAT. -0 0 COOLING /HEATING (ELECTRONIC THERMOSTAT) MULTI STAGE 124 VOLT THERMOSTAT.TO CONTROL THE ECONOMIZER ON THE SECOND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO THERMOSTAT 1 STAGES OF HEAT,USE A 2 STAGE COOL AND HEAT THERMOSTAT. TERMINALS UNIT TERMINAL RC STRIP TB1 24 VOLT ADD 1 RH JUMPER R TRANSFORMER COOLING I HEATING (ELECTRONIC THERMOSTAT) 1 Yl SINGLE STAGE Y2 2- Y2 .1. ... WI VV1 4. THERMOSTAT' 4 w2 3' W2 TERMINALS UNIT TERMINAL c c STRIP TEl RH B C LED I X Y ADD 4 RC R Vi . LED 2 USEDNOTW W1, OCC JUMPER N. COM 4. ... G G .1. ADD 1 Al JUMPER A2 T TO REMOTE SENSOR 24 VOLT T IF USED TRANSFORMER ,ELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL IELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL,TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING,USE A 2 STAGE COOL AND SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER. HEAT THERMOSTAT. I SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRC HEATER OR 2 STAGE GAS HEAT. REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR P6 ON UNITS WITH ECONOMIZER,TERMINALS Al AND A2 PROVIDE A RELAY OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET-BACK POSITION. Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 Date 07/10/2018 Project Name YoRKs. Barrows Rd Project Number INSTALL CONFIDENCE Client/ Purchaser Hunter Davisson Guide Specification Summary Page Product Series Models and Unit Tags Small Sunline(3-6 Ton Package)N643 ZE66OH12A2CIAAA1A1 Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 • 'ba y0 Guide Specification for Page:9 York Sunline GENERAL DOE and AHRI test procedures. Units shall be CSA listed, Units shall be manufactured by Johnson Controls Unitary staandardndards. to ANSI Z21.47, UL 1995/CSA No. 236 st Products in an ISO 9001 certified facility. York Sunline units are convertible single package units. Although the UNIT CABINET units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on Unit cabinet shall be constructed of galvanized steel, with steel beams above a finished roof. Cooling only, cooling exterior surfaces coated with a non-chalking, powdered with gas heat and cooling with electric heat models are paint finish, certified at 1000 hours salt spray test per available with a wide variety of factory-mounted options ASTMB117 standards. Indoor blower section shall be and field-installed accessories to make them suitable for insulated with a minimum 1/2" thick insulation, coated on almost every application. All units are self-contained and the airside. Aluminum foil faced insulation shall be used in assembled on full perimeter base rails with holes in the the furnace compartment and be fastened with ridged four corners for overhead rigging. Every unit is fasteners to prevent insulation from entering the air completely piped, wired, charged and tested at the stream. Cabinet panels shall be "large" size, easily factory to simplify the field installation and to provide removable for servicing and maintenance. Full perimeter years of dependable operation. All models (including base rails shall be provided to assure reliable transit of those with an economizer) are suitable for either bottom equipment, overhead rigging and proper sealing on roof or horizontal duct connections. Models with power curb applications. Disposable 1"filters shall be furnished exhaust are suitable for bottom duct connections only. and be accessible through a removable access door, For bottom duct, remove the sheet metal panels from the sealed airtight. Units filter track shall be designed to supply and return air openings through the base of the accommodate either 1" or 2" filters. Fan performance unit. For horizontal duct, remove the supply and return measuring ports shall be provided on the outside of the air panels on the rear of the unit. cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air All non-Scroll compressors include crankcase heaters and by-pass of the coils. Condensate pan shall be internally all compressors have internal pressure relief. Every sloped and conform to ASHRAE 62-89 self-draining refrigerant circuit includes a liquid line filter-drier, a standards. Condensate connection shall be a minimum of discharge line high pressure switch and a suction line with 3/4" I.D. female and be a ridged mount connection. a freezestat and low pressure/loss of charge switch. The INDOOR(EVAPORATOR) FAN ASSEMBLY unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor The indoor fan shall be a factory installed direct-drive or lockout circuit, a terminal strip for thermostat wiring, plus belt-drive assembly that includes an adjustable pitch motor an additional set of pin connectors to simplify the interface pulley. Job site selected (B.H.P.) brake horsepower shall of additional field controls. All models are CSA listed. All not exceed the motors nameplate horsepower rating, plus models include a 1-year limited warranty on the complete the service factor. Units shall be designed not to operate unit. Compressors and electric heater elements carry a 5- above service factor. Fan wheel shall be double-inlet type year warranty. Aluminized steel and Stainless steel tubular with forward-curved blades, dynamically balanced to heat exchangers carry a 10-year warranty. operate smoothly throughout the entire range of operation. DESCRIPTION Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and Units shall be factory-assembled, single packaged, no maintenance. Electric Cooling/Gas Heat, Electric Cooling/Optional OUTDOOR(CONDENSER) FAN ASSEMBLY Electric Heat, Heat Pump/Optional Electric Heat are designed for outdoor mounted installation. The outdoor fan shall be of the direct-driven propeller type, The 3 ton, 4 ton and 5 ton units shall have minimum SEER discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be rating of 13.0 with heat pumps having a 7.7 H.S.P.F. The 6 Ton Cooling only or Cooling with Electric Heat shall have dynamically balanced for smooth operation. The outdoor 11.2 EER, 6 Ton Cooling with Gas Heat shall have 11.0 fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload EER. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal conditions and staged independently. discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 alyoRK Guide Specification for Page: 10 York Sunline REFRIGERANT COMPONENTS f. Unit shall incorporate"AUTO RESET" compressor Compressors: over temperature, over current protection. a. Shall be internally protected with internal high- g. Unit shall operate with conventional thermostat pressure relief and over temperature protection. designs and have a low voltage terminal strip for b. Shall have internal spring isolation and sound easy hook-up. muffling to minimize vibration and noise, and be h. Unit control board shall have on-board diagnostics externally isolated on a dedicated, independent and fault code display. mounting. i. Standard controls shall include anti-short cycle and Coils: low voltage protection, and permit cooling operation down to 0°F. a. Evaporator coils shall have aluminum plate fins j. Control board shall monitor each refrigerant safety mechanically bonded to seamless internally switch independently. enhanced copper tubes with all joints brazed. Special k. Control board shall retain last 5 fault codes in non Phenolic coating shall be available as a factory volatile memory which will not be lost in the event of a option. power loss. b. Evaporator coils shall be of the direct expansion, draw-thru design. GAS HEATING SECTION c. Condenser coils shall have aluminum plate fins Shall be designed with induced draft combustion with mechanically bonded to seamless internally post purge logic, energy saving direct spark ignition, and enhanced copper tubes with all joints brazed or redundant main gas valve. Venter wheel shall be Micro-Channel aluminum tube, aluminum fins. constructed of stainless steel for corrosion resistance. d. Condenser coils shall be of the direct expansion, The heat exchanger shall be of the tubular type, draw-thru design. constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering Refrigerant Circuit and Refrigerant Safety Components temperature of 25°F. Burners shall be of the inshot type, shall include: constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit a. Independent fixed-orifice or thermally operated cabinet at a single location through either the side or expansion devices. curb without any field modifications. Integrated control b. Filter drier/strainer to eliminate any moisture or boards shall provide timed control of evaporator fan foreign matter. functioning and burner ignition. Heating section shall be c. Accessible service gage connections on both suction provided with the following minimum protection. and liquid lines to charge, evacuate, and measure a. Primary and auxiliary high-temperature limit switches. refrigerant pressure during any necessary servicing or troubleshooting, without losing charge. b. Induced draft motor speed sensor. d. The refrigeration system shall provide at least 15°F of c. Flame roll out switch. sub-cooling at design conditions. d. Flame proving controls. Unit Controls: e. If any of the above safety devices trip, a LED (light- emitting diode) indicator shall flash a diagnostic code a. Unit shall be complete with self-contained low-voltage that indicates which safety switch has tripped. control circuit protected by a resettable circuit breaker on the 24-volt transformer side. NOTE: All 2 Stage Gas Heat, 60% Capacity 1st Stage, b. Unit shall incorporate a lockout circuit which provides 40% Capacity 2nd Stage. reset capability at the space thermostat or base unit, UNIT OPERATING CHARACTERISTICS should any of the following standard safety devices trip and shut off compressor. Unit shall be capable of starting and running at 125°F c. Loss-of-charge/Low-pressure switch. outdoor temperature, exceeding maximum load criteria of AHRI Standard 210/240. The compressor, with d. High-pressure switch. standard controls, shall be capable of operation down to e. Freeze-protection thermostat, evaporator coil. 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only). Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 MIFORK Guide Specification for Page: 11 York Sunline ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES • Compressor 5 Years • Heat Exchanger 10 Years • Electric Heat Element 5 Years • Other Parts 1 Year OPTIONAL OUTDOOR AIR • Economizer—Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. ADDITIONAL FACTORY INSTALLED OPTIONS • BAS Controls FIELD INSTALLED OPTIONS • Barometric Relief Damper—This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 • Date 07/10/2018 Project Name J ■�/OC Barrows Rd Project Number INSTALL CONFIDENCE Client/ Purchaser Hunter Davisson Control Summary Page Control Models and Unit Tags Standard Simplicity Control ZEO6OHI2A2CIAAA1Al Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 • SSE Guide Spec Page: 13 YO 23 09 23 Direct-digital Control system for HVAC 23 09 23. 13 Decentralized,Rooftop Units: 23 09 23. 13.A. Unit Control Board 1. ASHRAE 62-2001compliant. BTL certified. 2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal. 3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non- condensing),with a storage temperature range from-40F to 194F;5-95%RH(non-condensing). 4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs. 5. Controller shall accept the followinginputs:space temperature,return air temperature sensor,setpointadjustment,outdoor air temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors, FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality, System purge. 6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and be Demand Control Ventilation(DCV)ready. 7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/ exhaust/reversing valve/dehumidify/occupied. 8. Unit shall provide surge protection for the controller through a circuit breaker. 9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster. 10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation. 11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor. If any of these safety devices trip,the LCD screen will display alarm message indicating the specific safety device that caused the lockout. a. Loss of charge/Low-pressure switch. b. High-pressure switch. c. Freeze condition sensor on evaporator coil. 12. Unit control board must support each usage case: a. Conventional thermostat with low voltage input terminals for easy installation b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control board to compare with associated setpoints c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building automation/management system 13. Anti-short cycle and low voltage protection features included. 14. Internal occupied/unoccupied scheduling 15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F. 16. Shall allow for start-up, commissioning,troubleshooting, parameter adjustment, setpoint adjustment via onboard display and navigable menu with no additional interface tool or controls technician required. 17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test. 18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up, commissioning, troubleshooting, parameter adjustment, setpoint adjustment. 19. Local embedded trending and scheduling.Trending data and occupancy scheduling predefined from the factory. Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device (cellular phone, laptop,tablet) 20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable.These include but are not limited to: a. Demand Ventilation Mode—enable or disable b. Operational Setpoint—display current value c. Supply Air Temperature(SAT)—display current value d. Return Air Temperature(RAT)—display current value Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 • MYORK. SSE Guide Spec Page 14 e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network Sensor, or FC Bus communicated value f. Return Air Humidity(RAH)—display current value g. Operational outdoor Air Temperature(OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer board and OprOAT only if economizer is present h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards OAH 0-10VDC input or FC Bus communicated value i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer boards OAQ 0-10VDC input or FC Bus communicated value j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board IAQ 0-10VDC input, SA Bus Network Sensor,or FC Bus communicated value 21. A menu shall display and allow modification to the following operations and settings: a. HVAC Zone Fan b. Cooling c. Heating d. Economizer e. Demand Ventilation f. Power Exhaust g. Sensors h. Network 22. A menu shall display and allow modification to the following operations and settings: a. HVAC Zone—Occupied status b. Indoor Fan status c. Cooling status d. Heating status e. Economizer indication whether free-cooling is available or not f. Enabling or disabling of Demand Ventilation g. Power Exhaust 1) Enable/disable hot-gas reheat if available 2) Warmup/Cooldown 3) Title 24 Load Shed 4) Defrost 23. A menu shall display and allow modification to the following operations and settings: a. Firmware version (of UCB, Economizer, other peripheral boards) b. Setting time zone c. Network information 1) Device name that will appear on the FC Bus 2) Selection of communication protocol 3) Operational Baud Rate 4) Device ID 24. A menu shall display and allow modification to the following operations and settings: a. Version of firmware b. Ability to Load new firmware c. Create a backup file of the firmware and parameter setting via USB port d. Restore factory default parameter values and setup e. Full and Partial Cloning of parameter setpoints from or to other units f. Data trend exporting 25. A menu shall display and allow modification to the following operations and settings: Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 ayoRic SSE Guide Spec Page: 15 a. Unit serial number, model number and name b. Ability to reset Lockouts c. Controller name d. Displays the current values of all setpoints in use e. Displays all current values for the indoor and outdoor zones f. Displays current values related to: 1) Indoor Fan 2) Cooling 3) Heating 4) Heat Pump operation 5) Economizer operation 6) Power Exhaust 7) Demand Ventilation 8) Air monitoring station 9) Hot Gas Reheat 10) Smoke Control g. Current information for inputs; including 1) Sensors 2) Coil Sensors 3) Thermostat 4) Binary Inputs 5) Unit Protection 6) Network Inputs 7) All outputs(relay and binary) h. Self-Test 1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning characteristics of the system at time of startup and commissioning. 23 09 23. 13.B. Auxiliary Control Boards 1. ASHRAE 62-2001 compliant. BTL certified. 2. Economizer controller CEC Title 24 Compliant a. Display alarms if the following occur 1) Economizer is economizing when conditions do not support 2) Economizer is not economizing when conditions do support 3) Damper Stuck 4) Excess Outdoor Air 5) Failed Sensor 3. Refrigeration Fault Detection& Diagnostics a. There is insufficient refrigerant in any circuit b. There is excessive refrigerant in any circuit c. There is excessive refrigerant flow d. There is insufficient refrigerant flow(restriction) e. Inefficient compressor f. Insufficient High-side heat transfer g. Excessive High-side heat transfer(low ambient control problem, low AP) h. Insufficient Low-side heat transfer i. Excessive Low-side heat transfer Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018 .. ,____,_ YOR SSE Guide Spec Page: 16 j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if refrigerant level is very low in the system) k. Sensor fault-Sensor data is not available I. The unit is off m. The ambient temperature is too low n. The ambient temperature is too high o. The return air wet-bulb temperature is too low p. The return air wet-bulb temperature is too high q. Sensor fault-The condensing temperature is lower than the ambient temperature(Could also be triggered when the condenser is wet) r. The suction line temperature is less than the evaporator temperature s. The evaporator temperature is greater than the ambient temperature t. The liquid temperature is lower than the ambient temperature u. Sensor fault-Suction temperature or ambient temperature is invalid v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid w. Sensor fault-The liquid pressure or suction pressure is invalid x. Sensor fault-The suction line temperature is invalid y. The return air dry-bulb temperature is too low z. The return air dry-bulb temperature is too high aa. The Efficiency Index is below 75%of ideal bb. The Capacity Index is below 75%of ideal 23 09 23. 13.0 Remote Accessibility: 1. ASHRAE 62-2001 compliant. BTL certified. 2. Provide the ability to adjust parameter values, setpoints, limits remotely 3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS) 4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 07/10/2018