Report 11 Project Name: Planet Fitness Standby Hours:124 1 ��J����ion (Salem,OR 1 Alarm Mins:15 1 Potter AFC-1000 Installed By:1M&E Electric,Inc. Batt Efficiency:180% 1 Battery&Voltage Drop Designed By: Donald Allen SLC Type:1Class B i Calculations Date: 4/11/2019 NAC Source Voltage:120.4 i Model 5: AFC-1000 Max Panel Current(amps): 10 Panel ID:I I User assumes all responsibility to ensure the quantities and " -- -"- "" current draw values in this worksheet are accurate prior to Location:` 1 --__-" _ ._.--. -- submittal. F ACP Standby(amps) Alarm(amps) Qty Part A Description Each Total Each Total 1 AFC-1000 Analog Addressable FACP 0.130 0.130 0.220 0.220 Panel Standby: 0.130 Panel Alarm: 0.220 P-LNK(RS-485)(Both P-Link Circuits Combined) Standby Alarm 1 UD-1000 DACT Card 0.016 0.016 0.023 0.023 1 RA-6075 LCD Annunciator 0.020 0.020 0.025 0.025 RA-6500F Flush Mount LCD Annunciator 0.020 0.050 LED-16F Flush Mount LED Annunciator 0.025 0.025 LED-16F LED Annunciator LED Power* 0.015 0.210 CA-6500 Class A Module 0.060 0.100 PSN-1000(E) Power Expander 0.015 0.015 NOHMI-SLCE-127° SLC Expander(9 Max) 0.060 0.060 PAD100-SLCE-127 SLC Expander(9 Max) 0.060 0.060 RLY-5 Relay Expander 0.025 0.035 RLY-5 Relay Expander Power* 0.010 0.135 DRV-50 LED Driver Module 0.025 0.025 DRV-50 LED Driver Module LED Power* 0.010 0.215 FCB-1000 Fire Communications Bridge 0.025 0.025 FIB-1000 Fiber Interface Board 0.030 0.030 MC-1000 Multi-Connect Expander 0.010 0.010 SPG-1000 Serial Parallel Gateway 0.040 0.040 *REQUIRED IF USING NOHMI PROTOCOL SIC DEVICES (Maximum current draw is 1 Amp per P-Link circuit,with 2 amps total) P-LINK Standby: 0.036 P-LINK Alarm: 0.048 *Only enter quantity if PLINK power is being used to power devices SLC Devices Standby Alarm 1 PAD100-PD Analog Photo Smoke 0.000300 0.000300 0.000300 0.000300 PAD100-PHD Analog Photo Smoke/Heat 0.000300 0.000300 PAD100-HD Analog Fixed Temp Heat 0.000300 0.000300 PAD100-CD Analog Carbon Monoxide Detector 0.000300 0.000300 PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000 PAD100-DUCT Addressable Duct Detector 0.000300 0.000300 PAD100-DUCTR* Addressable Duct Detector w/Relay 0.000500 0.000500 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.000200 PAD100-MIM Micro Input Module 0.000200 0.000200 PAD100-SIM Single Input Module 0.000240 0.000240 6 PAD100-DIM Dual Input Module 0.000240 0.001440 0.000240 0.001440 6 PAD100-RM Relay Module 0.000240 0.001440 0.000240 0.001440 PAD100-OROI One Relay One Input Module 0.000240 0.000240 PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240 PAD100-2M* Conventional Zone Module 0.000240 0.000240 PAD100-NAC° Notification Appliance Circuit 0.000200 0.000200 PAD100-SM Speaker Module 0.000200 0.000200 PAD100-IM Isolator Module 0.000150 0.000150 PAD100-LED LED Module 0.000240 0.000240 PAD100-LEDK Addressable LED w/Key Switch 0.000200 0.000200 PAD100-SB* Addressable Sounder Base 0.000260 0.000200 PAD100-RB Addressable Relay Base 0.000200 0.000200 PAD100-IB Addressable Isolator Base 0.000150 0.000150 PSA Analog Photo Smoke 0.000325 0.000325 PSHA Analog Photo Smoke/Heat - 0.000325 0.000325 RHA Analog Rate of Rise Heat 0.000325 0.000325 FHA Analog Fixed Temp Heat 0.000325 0.000325 DDA Addressable Duct Detector 0.000325 0.000325 APS-SA/APS-DA Addressable Pull Station Single/Dual Action 0.000325 0.000325 MCM Mini Contact Input Module 0.000325 0.000325 SCM-4 Single Contact Input Module 0.000325 0.001000 DCM-4 Dual Contact Input Module 0.000325 0.001000 TRM-4 Twin Relay Output Module 0.000325 0.001000 CIZM-4* Conventional Zone Input Mod 0.000325 0.001000 MOM-4* Monitored Output Module 0.000325 0.001000 ARB* Detector Base w/Relay 0.000325 0.000325 J ASB* Detector Base w/Sounder 0.000325 0.000325 SCI on Short Circuit Isolator(Class Al 0.000325 0.002340 F AIB*0 Detector Base w/lsolator(Class A) 0.000325 0.002340 IM/I8/SCI/AIB Class B** Current Draw from Install Manual SLC Loop Alarm LED Current 0.000000 0.000000 0.036000 0.036000 * Requires Aux Power(Configure Below) SIC Standby: 0.003180 SIC Alarm: 0.039180 ** See the installation manual for special considerations when installing IM,IB,AIR, SCI devices on Class B loops. Potter Electric Signal(C)2017 1 of 5 AFC-4000 Battery and Voltage Drop Calculation t NAC Circuits(See NAC Configuration.below) Standby(amps) Alarm(amps) Ckt Use Description Total Total 1 Notification Circuit#1,First Floor 0.00000 0.28600 2 Circuit#2.Second Floor 0.00000 0.28600 3 Notification Cirt.#3,Third Floor 0.00000 0.28600 4 Cirt.#4,Fourth Floor 0.00000 1.84000 5 Notification Cirt.#5,Fifth Floor 0.00000 0.28600 6 Notification Outdoor H-5 0.00000 0.14000 NAC Standby: 0.00000 NAC Alarm: 3.12400 I/O Circuits(See I/O Configuration below) Standby(amps) Alarm(amps) Ckt Use Description Total Total 1 Notification Cellular Monitor 0.00000 0.00000 2 0.00000 0.00000 3 0.00000 0.00000 4 Emergency Comm Monitor 0.00000 0.00000 I/O Standby: 0.00000 I/O Alarm: 0.00000 Battery Calculation Summary Standby(amps) Alarm(amps) Panel Current: 0.13000 0.22000 P-Link Current: 0.03600 0.04800 SLC Device Current: 0.00318 0.03918 NAC Circuit Current: 0.00000 3.12400 I/O Circuit Current: 0.00000 0.00000 SLC Loop Type: Class B Total Standby: Total Alarm: Device Addresses Used: Standby Hours: 24 Alarm Mins: 5 Device Addresses Available: 127 AH Required: 4.07 AH Required: 0.29 Total Combined Standby&Alarm AmpHours Required: 4.36 Efficiency Factor: 80% Required Battery AmpHours: 5.45 Battery AmpHours Provided: 7 Note:The cabinet will house two 8 AH or 18 AN batteries. The charging circuit is rated for up to two 55 AH batteries. 1 Potter Electric Signal(0)2017 2 of t AFC-4000 Battery and Voltage Drop Calculation P OTTER .Diho SY'�INRglatim NAC Circuit Configuration&Voltage Drop Planet Fitness 4/11/2019 NAC 1 : MAX Circuit Current(amps): 3 Source Voltage Used(VDC): 20.4 Usage:INotification I Description:'Circuit#1,First Floor Wire Type Ohms/10110ft Length 1-Way Actual'Ohms Max Load(amps) Volts @ FOI lYlirt VoltsFieq't( #14 Solid 2.5 220 1.100 I 0.286 20.09 16 Circuit Devices Standby(amps). Alarm(amps) Qty Lookup Type Description Each Total Each Total 2 Horn Strobes Potter CHS-24,30cd Hi db 0.000000 0.000000 0.143000 0.286000 Total Standby: 0.00000 Total Alarm: 0.28600 NAC 2 MAX Circuit Current(amps). 3 Source Voltage Used(VDC): 20.4 Usage:) I Description:'Circuit#2.Second Floor Wire Type Ohms/1000ft Length 1-Way l Actual Ohms Max Load lamps( Volts @.EuL Min Volts Req'd #14 Solid 2.5 230 1.150 0.286 20.07 16 Circuit Devices Standby(amps) Alarm(amps) Qty Lookup Type .Description;- Each. Total Each. Total 2 Horn Strobes Potter CHS-24,30cd,Hidb 0.000000. 0.000000 0.143000 0.286000 _ f Total Standby: 0.00000 Total Alarm: 0.28600 NAC 3 MAX Circuit Current(amps): 3 Source Voltage Used(VDC): 20.4 Usage:'Notification I Description:'art.#3,Third Floor Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load(amps).,. Volts 0 FOL. Mm Volts Req'd #14 Solid 2.5 240 1.200 0.286 20.06 16 Circuit Devices Standby(amps} Alarm(amps) Qty Lookup Type Description Each Total Each Total 2 Horn Strobes Potter CHS-24,30cd,Hi db 0.000000 0.000000 0.143000 0.286000 Total Standby: 0.00000 Total Alarm: 0.28600 Potter Electric Signal(C)2017 3 of 5 AFC-4000 Battery and Voltage Drop Calculation F TheTTFIZ NAC Circuit Configuration&Voltage Drop(cont'd) NAC 4 MAX Circuit Current(amps): 3 Source Voltage Used(VDC): 20.4 Usage: ( Description: Girt.#4,Fourth Floor Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load(amps) Volts 0'EOL NM)p Volts Req'd.. #14 Solid 2.5 250 1.250 1.840 18.10 16 Circuit Devices Standby{amps) Alarm(amps), Qty Lookup Type Description Each Total Each Total 2 Horn Strobes Potter CHS-24A,30cd,Hidb 0.000000 0.000000 0.920000 1.840000 Total Standby: 0.00000 Total Alarm: NAC 5 MAX Circuit Current(amps): 3 Source Voltage Used(VDC): 20.4 Usage:I Notification ( Description:ICirt.#5,Rfth Floor I Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load lamps) Volts @ FOL Min Volts Req'd #14 Solid 2.5 270 1.350 0.286 20.01 16 Circuit Devices Standby(amps) Alarm(amps) Qty Lookup Type Description Each Total Each Total 2 Horn Strobes Potter CHS-24,30cd,.Hi db 0.000000 0.000000 0.143000 0.286000 Total Standby: 0.00000 Total Alarm: 0.28600 NAC 6 MAX Circuit Current(amps): 3 Source Voltage Used(VOC): 20.4 Usage:I Notification I Description:(OutdoorH-5 Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load(amps) Volts @ EOL Min Volts Req d #16 Solid 4 30 0.240 0.140 20.37 16 Circuit Devices Standby(amps) Alarm lamps) Qty Lookup Type Description Each.. Total.. . Each Total 1 Horn Strobes W-P,Potter WGEC24-75WR,Hi db 0.000000 0.000000 0.140000 0.140000 Total Standby: 0.00000 Total Alarm: 0.14000 Potter Electric Signal(C)2017 4 of 5 AFC-4000 Battery and Voltage Drop Calculation POILF & al ROW. I/O Circuit Configuration&Voltage Drop Planet Fitness 4/11/2019 I/O 1 MAX Circuit Current(amps): 1 Source Voltage Used.(VDC): 20.4 Usage:INotification ) Description:(Cellular Monitor Wire Type Ohms/10OOft Length 1-Way Actual Ohms Max Load(amps) : Volts @ EOL f,., #14, €: #18 Solid 6.4 20 0.256 0.000 20.40 16 Circuit Devices Standby(amps) Alarm(amps) Qty Lookup Type Description Each Total Each Total 1 User Defined Dry Contact 0.000000 0.000000 0.000000 0.000000 Total Standby: 0.00000 Total Alarm: 0.00000 I/O 2 MAX Circuit Current(amps): 1 Source Voltage Used(VDC): 20.4 Usage:I I Description:I Wire Type Ohms/100 ; ,lit 1-Way Actual Ohms Max Load(arnpsl Volts @ EOL Min Volts Req'd #18 Solid 6.4 30 0.384 0.000 20.40 16 Circuit Devices Standby(amps) Alarm(amps) Qty Lookup Type Description Each Total Each Total 1 ' User Defined Dry Contact 0.000000 0.000000 0.000000 0.000000 Total Standby: 0.00000 Total Alarm: 0.00000 Planet Fitness 4/11/2019 I/O 3 MAX Circuit Current(amps): 1 Source Voltage Used(VDC): 20.4 Usage:1 ( Description: Wire Type Ohms/.000ft Length 1-Way .:Actual Ohms. Max Load(amps( Volts @ EOL .Mu Volts Req:'d. #14 Solid 2.5 0.000 0.000 IIIMEE111111 16 Circuit Devices. Standby(amps)_ Alarm(amps) Qty Lookup Type Description Each Total Each Total Total Standby: 0.00000 Total Alarm: 0.00000 I/O 4 MAX Circuit Current(amps): 1 Source Voltage Used(VDC): 20.4 Usage:I I Description:!Emergency Comm Monitor Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load lamps) Volts 4)EOL Min'.VoltsReq'd #14 Solid 2.5 80 0.400 0.000 20.40 16 Circuit Devices Standby(amps) Alarm(amps) Qty Lookup Type Description Each Total Each Total Total Standby: 0.00000 Total Alarm: 0.00000 Potter Electric Signal(C)2017 Sof 5 AFC-4000 Battery and Voltage Drop Calculation Tigard Storage (Tigard, OR) Operational System Matrix ori w o F qac v � - o ,o 4' - . o 45) ra p w k yoQ 2� v v Waterflow (Wet) (6) • IN M Valve Tamper(8) • • Smoke Detector(13) • III • Pull Station (2) • System Wiriing Fault - • MI AC Power Fault III MI Telephone/Communication Fault I • P POTTER AFC-1000 The Symbol of Protection Fire Alarm Control Panel Features �SEnne�F • 1,270 addresses available on this analog addressable system • • Additional system capacity achieved via multi-point SLC modules •'2 54 THS J • 1500 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built-In AFC-000 • System Operates as Class A or Class B for SLC,P-Link and NACs • 10 Amp Power Supply,Expandable to 315 amps • 6 NACS,Regulated,Rated at 3 Amps each,expandable to 192 • 4 Input/Output(I/O)Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort • Strobe Synchronization and System Wide Sync for Gentex®, AMSECO®,Cooper Wheelock®and System SensorO strobes • Dedicated Alarm,Supervisory and Trouble Relays • 4,000 Event History Buffer • Optional two line DACT with UD-1000 that can report General,Zone or Point Information • Built in IP communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status,Reports and Event Information min • Product includes 5 year warranty NYC Fire Dept. Certificate of Approval ) 6256 ; LISTED 7165-0328:0509 S735 Description Technical Specifications The AFC-1000 is an expandable analog/addressable releasing fire Dimensions 1815/16"W x 27 5/i6"H x 4 7/16"D alarm system with a total system capacity of 1270 addresses.Additional 5.0 Amps CP 120 VAC 50/60 HZ capacity on the system is achieved using multi-point SLC modules AC Mains 3.0 Amps @ 240 VAC 50/60 HZ The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules.The system is expandable with ai nclosure 16 gauge cold rolled steel with removable total of nine additional addressable Signaling Line Circuits(SLC)each locked door with Lexan viewing window with a maximum of 127 devices.Each SLC may be comprised of any Standby Current-130 mA combination of smoke sensor,heat detectors or modules and allows for a Alarm Current-200 mA total of 50 ohms of impedance and may use any wire compliant with the • 10 Amps power for NACs,I/O,and P-Link National Electrical Code(NEC). • 3 Amps per NAC,regulated Battery The AFC-1000 has a 10 Amp power supply with six Notification • 1 Amp per I/O circuit,regulated Appliance Circuits (NACs) and four Input/Output (I/O) circuits. The • Battery Charger range 8-55 Ah • NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Battery Charger voltage 27.3 VDC • Each output is regulated and power limited.In addition,each output is P-Link maximum current of 1 Amp uniquely programmable and may be configured for steady signal,strobe Temperature and 32°to 120°(0°C to 49°C)with a maximum synchronization, constant power, door holder power, or releasing. The Humidity Range humidity of 93%non-condensing. strobe synchronization includes Gentex,AMSECO, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power,2 additional input circuits and the AFC-1000 will support up to 31 power supplies.The system will synchronize the strobes system wide. In addition,the PSN- 1000E has space to allow the installation of up to six PAD 100-SLCE SLC - loop expansion cards.The cards mount on a stacker bracket that allows access to all SLC circuit connections. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830135-REV B • 01/I8 PAGE 1 OF 4 P POTTER AFC-1000 The Symbol of Protection Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 1,270 addressable devices or modules in any combination.The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description ` ,X E PAD!00-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PADIOQ-PHD Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135°Fahrenheit heat detector. PAD 10C1-11D Analog Fixed(135d-185dF)or Rate-of-Rise Heat Detector(software selectable) PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay.Addressable Duct Smoke Detector with Form C relay rated at 10a @ 250/120VAC or 8amps at 30VDC. PAD 100-DUCT Addressable Duct Smoke Detector. PAD I00-6B 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD!00-4B 4"round base that may be mounted to an electrical box and wired for connection to the above sensors. PARI 00-18 Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD 100-RB Addressable Relay Base that contains one relay controlled by the SLC.Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. PAD!00-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. PAD 100-CD Addressable CO gas detector. PAD100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. Modules `;1114144,0: DeseriPtion PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD!00-PSSA Single Action Addressable Pull Station. PAD 100-PSDA Dual Action Addressable Pull Station. PADI00-SIM Single Input Module is a standard contact module with an LED that mounts into a 4"square electrical box. PADI00-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PADI00 l RTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel.Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.Also provides two contact inputs. PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel.Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD100-LED Module provides a single addressable LED that is controlled by the control panel. PAD100-SM Speaker Module provides switching for two audio channels. PAD100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD100-DRYS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.For use with the PAD100-DUCTR only. ' PAD100-OROI One Relay One Input Module provides one form C relay and one input.The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830135-REV B • 01/18 PAGE 2 OF 4 PPOTTER AFC-1000 The Symbol of Protection Fire Alarm Control Panel SLC Features RA-6075R—2 x 16 LCD annunciator with a key pad in a locked The Potter protocol is a digital protocol with a proven design for metal enclosure. reliability and noise immunity.The system does not require special RA-6500R(F)—4 x 40 LCD annunciator with a key pad in a locked cable or conductors for connection of the Signaling Line Circuit metal enclosure.Flush mount version available. as long as the cable is compliant with NFPA 70 and NFPA 72. LED-16(F)—16 LED annunciator with common indicators in a The system allows for Class A or Class B installations as well as locked metal enclosure.Flush mount version available. "T Taps."Each loop is capable of 127 points,with a max wiring PSN-1000(E)—10 amp,remote intelligent power supply with distance of 10,000 ft. 6 NACs,2 I/Os and a P-Link repeater.This panel is listed in conjunction with the AFC-1000 as releasing circuits. Sensor Features CA-6500—Class A convertor that converts the SLC,NACs and The sensors through the fire alarm control panel provide a real P-Link connection time status as to the condition of the system.The smoke detector UD-1000—UL listed,Dual line telephone alarm communicator sensitivity,heat detector temperature level and drift compensation DRV-50—LED driver expander,used to connect up to 50 LEDs in a are all programmable options.The system also allows for a day/night graphic display mode where the panel automatically adjusts the sensitivity depending FCB-1000—Fire communication bridge,provides remote mounting on the time of day.To assist in the reduction of false alarms,the of the Ethernet connection smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer FIB-1000—Fiber interface module,used to extend P-Link to multi- maintain the programmed sensitivity. mode fiber(2 required) RLY 5—Relay module,provides 5 form C relay contacts rated at 3.0 User Interface amps 24VDC/125AC The fire alarm control panel has a 4 x 40 LCD display to provide SPG-1000—Serial parallel gateway,allows for the connection to a information to the system status.The keypad has navigation keys serial or parallel printer to allow manipulation of the Menu on board the panel.The panel is The FIB-1000,FCB-1000 and the SPG-1000 may be installed in the shipped standard with the following LEDs: stacker bracket or ordered with the optional rack mount enclosure. • AC Power-Green MC-1000 Multi-Connect allows up to sixty-three AFC series panels • Alarm-Red to share a single reporting technology. • Earth Fault-Amber AE-2—Two card expansion cabinet • Supervisory-Amber AE-8—Eight card expansion cabinet • Silenced-Amber AE-14—Fourteen card expansion cabinet • Trouble-Amber • Pre-Release-Amber Ethernet/I.P. Connection • Release-Red The AFC-1000 is shipped standard with an Ethernet connection. The common buttons include a Silence,Reset,Acknowledge,and This connection is the programming port and may be connected Drill.All of the buttons are accessible once the locked door is to a building Wide Area Network(WAN)or Local Area Network opened. (LAN).Once connected to the Internet,the panel may be selectively programmed to e-mail alarm conditions,trouble conditions, P-Link supervisory conditions,test,Event History and detector status.An The AFC-1000 has a proprietary communication protocol that e-mail may be sent to the panel and the panel will e-mail the event history,detector status,configuration file or server status to an communicates through a RS-485 connection to field devices.Up authorized E-mail account.In addition,reminders may be set to send to 64 devices may be connected to a single P-Link connection.The P-Link includes the communication terminals and regulated 24 VDC an e-mail for service,testing or other conditions. connection for the field devices.The field devices may be any of the In addition,the Ethernet connection is UL listed as an IP following: communicator.The IP communicator is listed to report to the UL PAD100-SLCE-Analog/Addressable loop expansion module listed Sur-Gard III IP receiver.The IP communicator replaces the (maximum of 9 per AFC-1000) traditional less reliable alarm communicator transmitter that utilized SLCE-127-Nohmi addressable loop expansion module for retrofit telephone lines.The IP communicator is an active method of applications. connection and communication to the monitoring station. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 • www.pottersignal.com 8830135-REVB • 01118 PAGE3OF4 . . P POTTER AFC-1000 The Symbol of Protection Fire Alarm Control Panel • Dimensions 18.91" 17.60" Q 0 0 TOP . • o 4.41" 3.75" y DEPTH I b it a ] ! ! 0 0 j 0 S. 0 I 0 I 1 II I ) LEFT SIDE RIGHT SIDE t _ 1 BOTTOM • o Ordering Information Model Description Stock No. AFC-1000 Fire Alarm Control Panel 3992754 Potter Electric Signal Company, LLC • St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830135-REV B • 01/18 PAGE 4 OF 4 P POTTER RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Features Standby Current 20 mA Alarm Current 25 mA Operating Temperature 0°C-49°C(32°F-120°F)10%-93% @ 30°C(86°F)non-condensing ' ! humidity Maximum Wire Length 6500 FT Maximum Annunciators 31 Size(WxHxD) 8"x 6-1/4"x 1-5/8" Wire Gauge 14 AWG-22 AWG Via' a jar LISTED lUAW S2930 7165-0328:0195 Description Installation The RA-6075 is a LCD remote annunciator for the PFC-6075 and The RA-6075 is connected to the PFC-6075 using a four wire RS-485 PFC-6030 addressable fire control panel.The RA-6075 communicates connection.The connection is power limited and supervised.Up to using a RS-485 connection to the main panel providing common thirty-one(31)RA-6075 LCD annunciators can be connected using indication of Alarms,Supervisory,Trouble and other system status and Class B or Class A wiring.Class A wiring requires an optional CA- control functions. 6075 Class A Expander. The RA-6075 features a 16x2 LCD display with LED's for Power, Alarm,Supervisory,Trouble,and Silenced conditions.It can be NOTICE mounted on a single gang electrical box or a two square electrical box. The annunciator is enclosed in a sheet metal enclosure and has a Potter Install in accordance with installation manual,#5403593. lock securing the keypad. Figure 1:RA-6075 Class B Wiring Example Figure 2:RA-6075 Class A Wiring Example Ta the next annunciator dim.. IC�171C�ICt7lln Mk.. co II !j 4 tli < 111113IAIII. a Panel IMI MI •Annunciator I 1 I818II anneetlon 'IRemote Panel Remote Q © Panel ,71111.1111111 itilligia . ram .0 kiri : 1411 <1 Q Q O �^ Remote ( 1 Remote ----` Annunciator AnAe + r Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5406077-REV B PAGE 1 OF 2 9/11 . . The Symbol of Protection A-6075 P POTtERLCD ANNUNCIATOR INSTALLATION ' Address Settings The RA-6075 address is set by dip switch Si located on the back of the RA-6075.The address must he set in the range of 1 to 31 to be recognized by the control panel. Figure 3:RA-6075 Class A(back panel view) N .N �J O o \\ C) DIP SWITCH J LI 0 II*' IA I(1,4 . e (t+-,I 0 0f/ ` Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings AddressSW_1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On .. 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On MFG #5406077-REV B PAGE 2 OF 2 PRINTED IN USA 9111 PAD100-PSSA/PSDA PPOTTER.. Addressable Pull Station The Symbol of Protection Single/Dual Action - Features • Single or Dual Action versions �' • Durable die-cast construction O • Reset key matches the fire alarm control panels - • Compatible with IPA Series panels • SLC Class A,Class X&Class B • Product includes a 5 year warrantyI 1 I M ,4„...H p �� � 55�MQ1U Description Technical Specifications * The PAD100-PSSA (Single Action) is activated by simply pulling Operating Voltage '4.0VDC the white "T" bar handle down. The PAD100-PSDA(Dual Action) Max SLG Standby Current 200uA is activated by lifting the front cover and then pulling the white"T" bar handle down.Once activated,the"T"bar cannot be reset without Max SLC Alarm Current 200uA opening the front cover.Opening the front cover will also activate the32°F-120°F(0°-49°C) pull station.To reset the PAD100-PS Series,use the Potter WS-93 key Environmental Limitations Indoor Only to unlock and open the front cover. Once the cover is open,push the Dimensions 4.75"H x 3.25"W x 1.75"D "T"bar back into the normal position and re-secure the front cover. Relative Humidity umidity Range 0-93%(non-condensing) ApplicationSingle gang box or Mounting Option The PAD100-PSSA/PSDA is compatible with Potter's IPA and AFC/ Potter P32-BBIDBB ARC series addressable fire alarm control panels. It is a non-coded APS-SA-1.22 lbs. addressable pull station available in either a single or dual action Shipping Weight APS-DA-1.46 lbs. model and installs on a single gang box or surface mounts using the P32-BB or P32-DBB(deep)back box. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com _________..__________________.._______..._ 8830097-REV C • 3/18 PAGE 1 OF 2 POTTER PAD100-PSSA/PSDA Addressable Pull Station The Symbol of Protection Single/Dual Action Setting the Address - The PAD100-PS Series uses one SLC address assigned to the device.The address is set using the DIP switch located on the back of the PAD100-PS device. • Pull Station Front View Fig I 711:11W0 �- `i [) ALARM«««' L 0 T 1/ PIU- pip , ; 1 ,1,P'U-I,L, �;ILIH . XVIII; LILI II 1 ITo ,,,. ._ „.„,_ , iNb,,,,. , il puLdepos TTER , ,„i .e., ,,.,,,t, epoTTER ,,.........„, PAD 100-PSDA PAD 100-PSSA Pull Station Back View and Wiring Fig 2 O Mint 0 ._- r. ...) \ FACTORY WIRED CONTACTS FROM FACP OR PREVIOUS DEVICE TO NEXT DEVICE Ordering Information Model Description Stock No. PAD100-PSSA Addressable Pull Station,Single Action 3992721 t PAD100-PSDA Addressable Pull Station,Dual Action 3992720 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830097-REV C • 3718 PAGE 2 OF 2 PAD100-PD PPO ��� The Symbol of Protection Photoelectric Smoke Sensor Features • Low profile,less than 2 inches with the base • am. • Wide selectable sensitivity range of 1.0 to 3.7"/0/foot • Sensor communicates sensitivity to control panel • UL listed smoke calibration and sensitivity { f` �6 • Optional locking tab to prevent unwanted removal • Simple DIP switch address setting,no programming tool required • LED alarm indicator • Product includes a 5 year warranty moo (511' l LISTED Description Technical Specifications The Photoelectric Smoke Sensor is a listed Analog Addressable smoke Operating Voltage 24 VDC sensor compatible with fire alarm control panels that utilize the Potter Addressable Device(PAD)protocol.The PAD100-PD is a low profile Detector Current Draw 300µA smoke sensor with a wide sensitivity range.The sensor and base(not Alarm indicator I LED included)are made of a durable plastic in an off-white color to blend Alarm set-point range 1.0 to 3.7%/ft 3.6-12%/m in with the ceiling. % Installation temperature 32 to 120°F/ 0 to 49°C The PAD100-PD has a sensitivity range of 1.0 to 3.7per foot and range is UL. The PAD100-PD features drift compensation and has built in dirty detector warning as well as. The PAD100-PD and the control Operating relative 0%to 93%(Non-condensing) panel communicate over a proven and robust digital communication humidity range path and the system analyzes the information at the particular device. Start-up time Max. 1 sec. The total polling speed is less than five(5)seconds,well under the UL Maximum number of requirements. addresses per loop 127 The sensor is compatible with any of the PAD series sensor bases and Maximum number of simply twists on. The PAD100-PD is addressed using DIP switches lighted indicators in 30 in the rear of the sensor and can be easily programmed in the field alarm per loop. without special tools. Color Eggshell White Setting the Address Weight(without base) lolg(3.56oz) Each addressable device on the SLC loop must have a unique address Dimensions(w ithout Height: 1.35 in(34mm) from 1 to 127 to function properly. The address is set using DIP base) Diameter:3.93 in(100 mm) switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device.Verify the following: 1. Power to the device is removed ' 2. Field wiring is correctly installed. - 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830108-REV C • 3/18 PAGE 1 OF 2 P POTTER PAD100-PD The Symbol of Protection Photoelectric Smoke Sensor Air Velocity Ratings The PAD 100-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously.If the system already has 30 LEDs on,the PAD 100-PD will operate even though the LED may not illuminate. Operation The PAD100-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status.The polling LED can be turned off if desired for less conspicuous operation. The PAD100-PD with the PAD100-4DB or PAD100-6DB has a low profile of less than two(2)inches to blend into the surrounding environment.The sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector. Sensor Sensitivity The PAD100-PD and the compatible control panel work in tandem to keep the sensitivity consistent.As the sensor is installed over time,the sensor compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty sensor.The sensor will then have to be cleaned or replaced. The PAD100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs. NOTE:As required by NFPA,do not install the sensors until all construction is complete and the work area has been thoroughly cleaned.If the sensors have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service. Spacing The PAD 100-PD is UL listed with a recommended maximum spacing of 30 feet.Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. Compatible Bases All bases will mount on a single gang,double gang, octagon,4"square or mud ring electrical box. Device Description Stock No. PAD 100-4DB 4"Standard Base 3992731 PAD 100-6DB 6"Standard Base 3992732 PAD 100-IB 6"base with an isolator module included. 3992730 PAD100-RB 6"base with one Form-C relay contact. 2A @ 30VDC,0.5A @ 125VAC 3992728 PAD100-SB 6"base with sounder module included.Sound pattern is provided from external source. 3992729 PAD100-SPKB 6"base with speaker included 3992762 Ordering Information Model Description Stock No. PAD100-PD Photoelectric Smoke Sensor 3992733 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 • www.pottersignal.com 8830108-REV C • 3/18 PAGE 2 OF 2 P® PAD1 00-DIM The Symbol of Protection Dual Input Module Features Q` sma4F0 • Single module with dual contact monitoring inputs . • 'i ,�/ • Two(2)Class B or one(I)Class A monitoring inputs �, • SLC Class A,Class X&Class B r ; ' ;"` ii l , • Mounts in a standard 4"or double gang box • Wiring terminals accessible when mounted in box ''' ,4%1!PNig:11i;i44-,'!Ailier • All wiring terminals accept 22 to 12 AWG Ufa • Product includes a 5 year warranty �� � x' NOTE:This addressable module does not support 2-wire smoke detectors. rP h -'1 Description Technical Specifications The PAD100-DIM uses one (1) SLC loop address when monitoring Operating Voltage 24 OV two(2)Class B circuits or one(1)Class A circuit.The module mounts on either a 4" square or double gang box. The module is capable Max SLC Standby 240µA of monitoring two (2) separate class B circuits making it ideal for urgent - monitoring sprinkler waterflow and valve tamper switches when they Max SLC Alarm 240µA are located in the same proximity.The PAD 100-DIM includes one red Current LED to indicate the module's status. In normal condition, the LED Max Wiring Resistance 10052 flashes when the device is being polled by the control panel.When an of IDC input is activated,the LED will flash at a fast rate. Max Wiring IµF F Capacitance of IDC Application EOL Resistor 5.1K SZ The PAD100-DIM is compatible with Potter's IPA and AFC/ARC Operating Temperature 32 to 120°F(0 to 49°C) series addressable fire alarm control panels. The PADI 00-DIM is an Range interface module used to monitor dry contact devices such as sprinkler Operating Humidity 0 to 93%(non-condensing) waterflow, valve tamper switches, or conventional pull stations.The Range module is capable of monitoring two separate Class B or one Class A Max no.of Module Per 127 units circuits. Loop 4.17"(I 06mm)L x 4.17" Setting the Address Dimensions (106mm)W x 1.14"(29mm)D Each addressable SLC device must be assigned an address. The Standard 4"Square or address is set using the DIP switch located on the PAD100-DIM.When Mounting Options Double Gang Box the PAD100-DIM is used to monitor two individual Class B circuits a single device address is assigned, each input is then identified as a Shipping Weight 0.6 lbs sub-point of the module address. For example, if the address number is assigned as"8", the first input will be"8.1" and the second input will be"8.2". Before connecting a device to the SLC loop, take the following precautHns to prevent potential damage to the panel or device: I. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830082-REV C • 3/18 PAGE 1 OF 2 . . 1 P POTTER PAD100-DIM ® The Symbol of Protection Dual Input Module I P Installation Using Compatible Electrical Box Fig 1 �- w 0II .,, 0 , Q ® tl s , MFnO ;: O _0 I p , -�LMJ'T 11\ Wiring Diagrams PADI00-DIM With One Class A Circuit Fig 2 MOVE THE"CL-A"DIP SWITCH TO"UP"POSITION 10 cD0 V7/0 FOR CLASS A WIRING FROMFACPOR / el PREVIOUS MODULE \ OI �III�� r\ TO NEXT MODULE nc 60 s C3 II l O Ali J O 4 \ _ —Thr--- F.) (::, . -a-73 P - - NOTE- END-OF-LINE RESISTOR /"„ IS NOT REQUIRED PAD100-DIM With Two Class B Circuits Fig 3 MOVE THE"CL-A"DIP SWITCH TO"DOWN"POSITION FOR CLASS B WIRING 4 CD 0 OUP 10 FROM FAC POR \ ' i PREVIOUS MODULE _ l l I i I'I'I' I -1 TO NEXT MODULE '��ll ;ac ZX71 END-OF-LINE -----Y-Th1.�. 5 RESISTOR 1111 I� 5.1K OHM3 W _•' Part# IR� c■► 0 cz, P END-OF-LINE RESISTOR - - 5.1KOHM}fW Part#3005013 Ordering Information - Model Description Stock No. PADI00-DIM Dual Input Module 3992703 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830082-REV C • 3/18 PAGE 2 OF 2 CS/CHS P® , SELECTABLE CANDELA a The S mbol of Protection CEILING MOUNT . .,._.nom ... . :..,. ._ . ,.. VIROSONNOMMTONXIMMINIIIMMI Features • Nominal voltage 24 VDC • Tamperproof field selectable candela options 15,30,75,95, 115, & 150 • Super-Slides Bracket-Ease of Supervision Testing • Checkmates-Instant Voltage Verification • Synchronize strobe and/or horn with Gentex AVSM Control Module Lu . - 44, • Prewire entire system,install mounting bracket,then install signals Documented lower installation and operating costs ,v ' • Input Terminals 12 to 18 AWG • Switch Selection for High or Low dBA cfsitit Switch Selection for 2400Hz or mechanical Tone • Switch Selection for Continuous or Temporal 3 • Tamperproof re-entrant grill • Surface mount with the CLNGBB(Ceiling Surface Mount Back Box) • Silence audible while visual appliance will remain flashing(for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature: U` • 32°F to I20°F(0°C to 49°C).The CS Series is not listed for outdoor use. LISTED Unit Dimensions S3247 Product includes a 5 year warranty • 6"(15.24 cm)x 2.6"(6.604 cm) Description The Potter CS/CHS Series is a ceiling mount strobe or horn/strobe The Ceiling Mount Series comes standard with the 4" mounting plate combination that offers dependable audible and visual alarms and the which incorporates the popular Super-Slides feature that allows the lowest current consumption. installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without The CS/CHS offers tamperproof field selectable candela options of 15, any screws showing. 30,75,95, 115 and 150 candela. The CS/CHS also features the patented Checkmate®-Instant Voltage The CHS horn offers a continuous or synchable temporal three in Verification feature which allows the installer to check the voltage drop 2400Hz and mechanical tone.All tones are easy for the professional to draw without removing the signal. change in the field by using switches.The models are shipped from the factory in the temporal three alarm mode. The CS Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use with fire protective systems. The CS Series has a very minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA*Cust Service.866-572-3005•Tech Support:866-956-0988•Canada 888-882-1833•www.pottersignat corn PRINTED IN USA MFG.#8830051-REV A PAGE 1 OF 4 06/13 CS/CHS D POTTER SELECTABLE CANDELA ® The S mbol of Protection CEILING MOUNT Mounting Super-Slide® 3.Snap Cover Over Assembly 2.Insert Locking Screw i . 1I ' 1 _ 4 11C11111immunimimr_,_ Adel. kl .n. rAllithH6. 41 _ 1111 I,' �`• .,- =----�-, w 111 ® mow / et r. I.Slide Onto Bracket r Checkmate®Instant Voltage Verification Switch Locations f 1 1 � 12345 T PPM , U DO( c-7) a Q, Q O o 9 i a7 Ir` [IF e I St = �Ic ,,,. animma c_ — . ' 8+ -i 15 Q O111111111111 ICI MEIwooss - A �,.��� 0 0 �y1�� _ O CO •0 • l , (MERMEN#} ii: 1 (4 iii O The access holes are provided in the back of the terminal block to Switch positions I and 2 in the down position to select isolated horn allow the voltage to be measured directly without removing the and strobe power inputs.Switch 3 selects between temporal or non- device.Typically this would be done at the end of the line to confirm temporal tone.Up is temporal.Switch 4 selects between mechanical or design criteria.Most measurements will be taken using the S+and high frequency tone.Up is mechanical.Switch 5 selects between high S-locations although access is provided to other locations.NOTICE: or low dBA.Up is high dBA. - CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. Potter El ectric S ignal Company,LLC•St Louis,MO 63042 USA•CustService.866-572-3005•TechSupport:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830051-REV A PAGE 2 OF 4 06/13 CS/CHS POTTER SELECTABLE CANDELA The Symbol of Protection CEILING MOUNT CS Series 24 Volt Ceiling Mount Selectable Strobe Model Part Nominal Number Number Voltage Candela CS-24R 4890020 24 VDC 15,30,75,95, 115, 150 CS-24W 4890021 24 VDC 15,30,75,95, 115, 150 CS-24PR 4890022 24 VDC 15,30,75,95, 115, 150 CS-24PW 4890023 24 VDC 15,30,75,95, 115, 150 CHS Series 24 Volt Ceiling Mount Selectable Horn/Strobe Model Part Nominal Reverberant dBA @ In Anechoic Room Number Number Voltage Candela 10 ft.per ANSIIUL 464 dBA @ 10 ft. CHS-24R 4890040 24 VDC 15,30,75,95, 115, 150 81-86 90 CHS-24W 4890041 24 VDC 15,30,75,95, 115, 150 81-86 90 CHS-24PR 4890042 24 VDC 15,30,75,95, 115, 150 81-86 90 CHS-24PW 4890043 24 VDC 15,30,75,95, 115, 150 81-86 90 Model Designations: C=Ceiling Mount S=Strobe HS=Horn/Strobe R=Red Faceplate W=White Faceplate All units are available in plain(no lettering). Plain units are non-returnable. CS24 Product Strobe Current Ratings(mA) - Candela 15 cd 30 cd 75 cd 95 cd 115 cd 150 cd 24 VDC 24 VDC 72 mA 101 mA 167 mA 200 mA 214 mA 286 mA (16-33 Volts) UL Max' 120 mA 120 mA 200 mA 220 mA 290 mA 321 mA CHS24 Product Horn Decibel and Current Ratings(mA) Horn Minimum dBA @ 10 ft. Minimum dBA @ 10 ft. Regulated 24 VDC Mode per ANSI/UL 464 per ANSI/UL 464 Max.Operating (HIGH) (LOW) @ High Setting(mA) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical 81 73* 22 Continuous 2400Hz 86 78 23 Continuous Mechanical 84 76 22 NOTES: • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power, see installation manual. • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. • Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use.Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). • RMS current ratings are per UL average RMS method.UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units).For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units).For audibles the max current is usually at the maximum listed voltage.For unfiltered FWR ratings,see installation manual. PotterElectricSignalCompany,LLC•St.Louis,MO 63042 USA•CustService:866-572-3005•Tech Support:866-956-0988•Canada888-882-J 833•www.pottersignal.corn PRINTED IN USA MFG.#8830051-REV A PAGE 3 OF 4 06113 P POTTs,�H� SELECTABLE CANDELA e The Symbol of Protection CEILING MOUNT • Architect&Engineering Specifications The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc.per ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC.The notification appliance shall also be listed with the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible units and audible units only)shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. Conventional CS/CHS Series Wiring Diagrams UL Listed UL Listed Control Control Signal Signal Panel Signal Signal Panel S+ S+ S- H+ H- 5+ s+ S- H+ H- , s+ $+ S- H+ H- S+ S+ S- H+ H- Supervised4.11. ME Supervised g 0 B o . 2 q 0 Signal Circuit ""'t 111„ y Signal© i Circuit " 111 \ © Illy \ END OF UNE IIID ERESI TORE 0 la RESISTOR O mill " \ Q 0 END OR LINE RESISIS TOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage.Strobes should not be used on coded or pulsing signaling circuits.However,use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe,horn and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. 4 PotterElectric Signal Company,LLC•St.Louis,MO 63042 USA•CustService:866-572-3005.Tech Support:866-956-0988•Canada 888-882-1833•wwwpottersignal.corn PRINTED IN USA MFG.#8830051-REV A PAGE 4 OF 4 06/13 GENTEX - CORPORATION Outdoor Commander Series w G E C 2 4 / Evacuation Signals W G E S 2 4 Applications The Outdoor Commander Series offers dependable visible and/or audible SERIES alarms for all outdoor needs. Included with the WGE Series is the GOE or GOELP outdoor enclosure. The Q enclosure is made of high quality Lexan°material, providing protection from weather related conditions and allowing the necessary full candela output. = .�• This highly constructed enclosure meets various installation requirements including deterring moisture from entering the enclosures. ft ',. The Outdoor Commander Series is equipped with the 4"mounting plate which incorporates the Super-Slide®feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The WGE Series also features the Checkmate°- Instant Voltage Verification feature which allows the installer to check the voltage drop draw and match it toiifi, t } ten blueprint. .,, The WGE Series strobe has a minimal operating current and has a minimum fi) F flash rate of 1Hz regardless of input voltage. _ The WGE Series appliances are ANSI/UL 464 and ANSI/UL 1638 listed for use -zR; .; with fire protective systems and are warranted for three years from date of purchase. GOELP GOE Standard Features WGES24 and WGEC24 Shipped • Nominal voltage 24VDC with the GOE or GOELP • Unit is shipped with ANSI/UL1638 listed WGES24-75 candela strobe Outdoor Enclosure or WGEC24-75 candela horn/strobe Product Listings • GOE Unit Dimensions:5.75"(14.605 cm) high x 4.75"(12.065 cm) wide x SIGNALING 4.18"(10.617 cm) deep _ _ GOELP Unit Dimensions:5.75"(14.605 cm) high x 4.75"(12.065 cm) wide x U 3.25"(8.255 cm) deep ®L (^O • To obtain outdoor listed horn, must order GEH24 and GOE/GOELP LISTED 1 �► separately • Super-Slide®- Ease of Supervision Testing • ANSI/UL 464 and ANSI/UL 1638 Listed • Checkmate®- Instant Voltage Verification • CSFM 7135-0569:122(WGEC) • Switch selection for high or low dBA 7125-0569:127(WGES) • Switch for mechanical and 2400Hz tone 7300-0569:124(ENCLOSURE) • Switch for continuous tone or temporal 3 (not available on whoop tone) • MEA#285-91E-XVI • Tamperproof re-entrant grill Product Compliance • Prewire entire system, install mounting bracket, then install signals • NFPA 72 • Separate horn and strobe functions • Americans with Disabilities Act(ADA) • Synchronize strobe and/or horn by using Gentex AVSM Control Module • IBC/IFC/IRC • Listed to ANSI/UL1638 when used with the GOE or GOELP enclosure • Quality Management System is certified • GOE/GOELP made of clear Lexan°-provides maximum visibility and to:ISO 9001:2008 reliability for effective visible signaling- allowing full 75cd output • Input terminals accept 12 to 18 AWG • Faceplate available in red or off-white \ MEMBER ,� ASSEMBLED IN THE USA GEH24 - 24 Volt Low Profile Evacuation Horn — Model Number Part Number Nominal Reverberant dBA at In Anechoic Room Voltage 10 ft.per ANSI/UL 464 dBA at 10ft. GEH24-R 904-1205-002 24 VDC 70-82 100 GEH24-W 904-1207-002 24 VDC 70-82 100 NOTE:Must order the GOE or GOELP separately when using the GEH24 in an outdoor application. WGES24 - 24 Volt Low Profile Evacuation Outdoor Strobe — Model Number Part Number Nominal Candela Voltage (ANSI/UL 1638) WGES24-75WR 904-1219-002 24 VDC 75 WGES24-75WW 904-1220-002 24 VDC 75 WGES24-75PWR 904-1247-002 24 VDC 75 WGES24-75PWW 904-1248-002 24 VDC 75 WGES24-75WRLP 904-1261-002 24 VDC 75 WGES24-75WWLP 904-1263-002 24 VDC 75 WGES24 and WGEC24 shipped WGES24-75PWRLP 904-1262-002 24 VDC 75 with the GOE or GOELP WGES24-75PWWLP 904-1264-002 24 VDC 75 Outdoor Enclosure WGEC24 - 24 Volt Low Profile Evacuation Outdoor Horn/Strobe Model Number Part Number Nominal Candela Reverberant dBA 0 10ft In Anechoic Room Voltage (ANSI/UL 1638) Per ANSI/UL 464 dBA @ 10ft. VT -iEC24-75WR 904-1217-002 24 VIJC 75 70-82 100 V' -iEC24-75WW 904-1218-002 24 VDC 75 70-82 100 VT -iEC24-75PWR 904-1245-002 24VDC 75 70-82 100 ►r 7EC24-75PWW 904-1246-002 24 VDC 75 70-82 100 VT EC24-75WRLP 904-1257-002 24 VDC 75 70-82 100 - ►T EC24-75WWLP 904-1259-002 24 VDC 75 70-82 100 VT 1 C24-75PWRLP 904-1258-002 24 VDC 75 70-82 100 • WGEC24-75PWWLP 904-1260-002 24 VDC 75 70-82 100 • Model Designations: "W"=Wall Mount "R" = Red Faceplate "W° =Off-White Faceplate "P" = Plain (no lettering) NOTE:Plain units are non-returnable. LP"=Low Profile(GOELP Enclosure) Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 24VDC Horn Mode at 10 feet per at 10 feet per Max.Operating ANSI/UL 464(HIGH) ANSI/UL 464(LOW) at High Setting WGE Series Product emp 3 2400Hz 78 dBA 71*dBA 28mA Strobe Current Ratings emp 3 Mechanical 76 dBA 70*dBA 25mA Candela 75cd emp 3 Chime 70*dBA 66*dBA 15mA 24 VDC 112mA Continuous 2400Hz 81 dBA 74*dBA 28mA UL Max' 170mA Continuous Mechanical 80 dBA 72*dBA 25mA Continuous Chime 70*dBA 66*dBA 15mA I hoop 82 dBA 69*dBA 56mA NOTES: • The WGE Series is listed for outdoor use. Indoor Operating Temperature:32°to 120°F(0°to 49°C). Outdoor Operating Temperature:-31'to 150°F(-35°to 66°C). • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. • Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products(see Technical Bulletin Number 014). • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is _ producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. *Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level required for public mode fire protection Sservice. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). 1 RMS current ratings are per ANSI/UL average RMS method. ANSI/UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units)(8-17VDC for 12VDC units). For strobes the ANIS/UL max current is usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation manual. Tone Switch Locations TONE SWITCH POSITION 3 4 5 Mechanical Temporal 3 ON ON ON =1"illi Mechanical-Continuous OFF ON ON [ —ENE:101 2400Hz-Temporal 3 ON OFF ON c[ _� • 2400Hz-Continuous OFF OFF ON _ Chime-Temporal 3 ON ON OFF i=r occo - Chime-Continuous OFF ON OFF ct,t,.EKTI ,b Whoop ON OFF OFF -., Whoop OFF OFF _ OFF cEc"EffE NOTE: EO • Switch Positions 1 and 2 in the OFF position to ® �" select isolated horn and strobe power inputs -61- • Switch Position 6 ON=HIGH dBA 1 • Switch Position 6 OFF=LOW dBA 01E,.- l plEt" ) ay iih Gentex Super-Slide® Gentex Checkmate® Instant Mounting Bracket ir _ ' Voltage Verification P It is often necessary to confirm the Allows the installer to pre-wire _. voltage drop along a line of devices.The the system, test for system 1 access holes are provided in the back of supervision, remove the signal ' 1114 :� r+ the terminal block to allow the voltage to be head until occupancy, switch I measured directly without removing the out Gentex signals without device.Typically this would be done at the changing mounting bracketsJo <_; end of the line to confirm design criteria. and has locking edge '- i Most measurements will be taken using the connector for snap-in-place -. .... .„.._1411r11.111 ., i installation. '+�� S+and S-locations although access is provided to other locations. NOTE:Care should be taken to not short the test probes. Mounting Outdoor Enclosure Super-Slide®Mounting Plate: Super-Slide®Mounting Plate: Mounts to GOE Outdoor Enclosure Mounts to GOELP Outdoor Enclosure .51:( ,,-., ,/ /Pi _ -----_- _ _ j pi, r-____ - ;., ,,,% ) ' ..,....: . ---1 yJj " 1 j iJ,� �0 I '� 3 �( i `,,- ! ii, , , , , , , _- ' . -t , 1 , ;II! r---r ti c, :-,-.% , ‘ , � ,1 5 r. d (;-: 0„-:_q !. 441111 5 ,__ 41t4. 6-,g,,,44- 'I L'-')1, • WGEC24 / WGES24 SERIES Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Control Panel Signal Signal Panel Signal Signal S+ S+ 5- H+ H- S+ S+ S- H+ H- S+ S+ S- H+ H- S+ S+ S- H+ H- Supervised O O ►+ O Q Supervised O - y ® 0 y e 0 Signal Circuit 111" 111111 Signal Circuit " " \ © I't' HogENOOE LINE ORESISTOR MEND RE STORE \ O END OF LINE O � RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET(551-0031) AND/OR AVSM CONTROL MODULE MANUAL(550-0284) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.gentex.com OR CALL GENTEX CORPORATION AT 1-800-436-8391. Architect & Engineering Specifications The audible and/or visible signal shall be Gentex WGE Series or approved equal and shall be listed by Underwriters Laboratories Inc.per ANSI/UL 1638 and/or ANSI/UL 464.The notification appliance shall also be listed with the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 170mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela requirements of the ADA(75cd). The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models. The appliance shall be capable of testing supervision without disconnecting wires.Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit. The appliance has extended temperature range of-31°to 150°F(-35°to 66°C). The appliance shall satisfy virtually all outdoor and severe environment applications. The GOE Enclosure is includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to allow for drainage,the seal on the GOE Enclosure is not water tight. The GOELP Enclosure includes a weather seal for mounting to wall and intended for use with universal electrical box. To allow for drainage,bottom edge of enclosure is not water tight. 1 unit per carton 3 pounds per carton Important Notice: 551-0047-03 G E N T E X These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarilyily summary,and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties,express or implied,that these materials are complete and CORPORATION accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to Fire Protection Products Group•www.gentex.com particular fact patterns.Each person's activities can differently affect the obligations that exist under 10985 Chicago Drive •Zeeland, Michi an 49464 applicable laws,regulations or rules.Therefore,these materials should be used only for informational g purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion.