Report
/YI t-026/9R-fid 759 ,5020 s SQ RECEIVED OCT 282019 CITY OF TIGARD COMcheck Software Version 4.1.1.0 BUILDING DIVISION Mechanical Compliance Certificate Section 1 : Project Information Energy Code:2014 Oregon Energy Efficiency Specialty Code Project Title:Embassy Center Project Type:Alteration Construction Site: Owner/Agent: Designer/Contractor: 9020 Sw Washington Square Rd Clint Latimer Tigard,OR 97223 Latimer HVAC LLC clint@latimerhvac.com Section 2: General Information Building Location(for weather data): Tigard,Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity. system Type&Description 1 HVAC System 1 (Single Zone w/Perimeter System): Heating:1 each-Duct Furnace,Electric,Capacity=17 kBtu/h No minimum efficiency requirement applies Fan System: FAN SYSTEM 1 --Compliance(Motor nameplate HP method):Fails:Fan system has no supply fan Fans: FAN 1 Terminal Unit,Constant Volume,1050 CFM,0.3 motor nameplate hp Section 4: Requirements Checklist In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks identify requirements that the applicant acknowledges are met or excepted from compliance.'Plans reference page/section'identifies where in the plans/specs the requirement can be verified as being satisfied. Requirements Specific To: HVAC System 1 : ❑ 1. Energy recovery ventilation systems.Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. Exception(s): ❑ Where energy recovery systems are prohibited by the International Mechanical Code. 1] Systems serving spaces that are not cooled and are heated to less than 60°F. ❑ Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy. ❑ Type 1 kitchen exhaust hoods. ❑ Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64°F(18°C). ❑ Systems requiring dehumidification that employ series-style energy recovery coils wrapped around the cooling coil when the evaporative coil is located upstream of the exhaust air stream. ❑ Systems exhausting toxic,flammable,paint exhaust,corrosive fumes,or dust. [j Laboratory fume hood systems that include qualifying features. � Plans reference page/section: )+1 Generic Requirements: Must be met by all systems to which the requirement is applicable: Project Title: Embassy Center Report date: 10/25/19 Data filename:C:\Users\Carlie\Documents\COMcheck\Embassy-incomplete.cck Page 1 of 5 Ai. Calculation of heating and cooling loads.Design loads are determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure, - 2. Equipment and system sizing.Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance with Section 503.2.1. Exception(s): - ❑ Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. at Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. Plans reference page/section: t`� *3.3. HVAC Equipment Performance Requirements.Reported efficiencies have been tested and rated in accordance with the applicable test procedure.The efficiency has been verified through certification under an approved certification program or,if no certification program exists,the equipment efficiency ratings are supported by data furnished by the manufacturer, f� 4. Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that ` ' respond to temperature within the zone. { Plans reference page/section: t!"' t 5. Set point overlap restriction.Where used to control both heating and cooling,zone thermostatic controls provide a temperature range T"` or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum. Exception(s): 3 Thermostats requiring manual change over between heating and cooling modes.i Plans reference page/section: Oil O 6. Optimum Start Controls.Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set point at time of occupancy. f Plans reference page/section: t"�) Q 1 4` r u 7. Off-hour controls.Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system. Exception(s): 13 Zones that will be operated continuously. [] Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff switch. Plans reference page/section: W I A- a 8. Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. Exception(s): 0 Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less.+ Plans reference page/section: 0 t z, 9. Freeze Protection and Snow melt system controls.Freeze protection systems,such as heat tracing of outdoor piping and heat exchangers,including self-regulating heat tracing,include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Plans reference page/section: O 10.Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions;or shall include supplementary control provisions so that the primary systems may be specifically controlled for comfort purposes only. Exception(s): a 1503.2.4.8+1 Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. Plans reference page/section: ' 'n" I i"5 C7 11.Humidity control.If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or zones,a humidity control device is provided. Plans reference page/section: N 1 1 o 12.Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative humidity in oxcocs of 30 percent.Whore a humidity control device is used for dehumidification.it is set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60 percent. Project Title: Embassy Center Report date: 10/25/19 ' Data filename:C:\Users\Carlie\Documents\COMcheck\Embassy-incomplete.cck Page 2 of 5 Exception(s): 0 Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity requirements outside this range. Plans reference page/section: N IA j 13.Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity where no ' active humidification or dehumidification takes place. Exception(s): 0 Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in `` section 503.2.3,HVAC equipment performance requirements. Plans reference page/section: N f A- 14.Ventilation.Ventilation,either natural or mechanical,is provided in accordance with Chapter 4 of the International Mechanical Code. /-` Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code. Plans reference page/section: Pt I O 15.Demand controlled ventilation(DCV).DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2 for multiple zone systems. Exception(s): O Systems with energy recovery complying with Section 503.2.6 0 Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan off,closes the ventilation damper,or closes the zone damper when the space is /unoccupied. 1'J 1 Plans reference page/section: I+ ❑ 16.Kitchen hoods.Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. Exception(s): Q Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. 0 Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. Plans reference page/section: 1\)IA. 0 17.Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling automobiles employs automatic carbon monoxide sensing devices. Plans reference page/section: N J Pr 18.Duct and plenum insulation and sealing.All supply and return air ducts and plenums are insulated with the specified insulation.When located within a building envelope assembly,the duct or plenum is separated from the building exterior or unconditioned or exempt spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams comply with Section 603.9 of the International Mechanical Code. Exception(s): O When located within equipment. (] When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F(8°C). 19.Low-pressure duct systems.All longitudinal and transverse joints,seams and connections of low-pressure supply and return ducts are securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or tapes installed in accordance with the manufacturer's installation instructions. Exception(s): Q Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification. � Plans reference page/section: 1. /t I lifi 20.Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed in accordance with Section 503.2.7.Pressure classifications� � lspecific to the duct system are clearly indicated on the construction documents. Plans reference page/section: t''t} ❑ 21.1 a gh-pressure duct systems.Ducts designed to operate at high-pressure are insulated and sealed in accordance with Section 503.2.7. In addition,ducts and plenums are leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Plans reference page/section: V I '22.Air system balancing.Each supply air outlet and zone terminal device is equipped with means for air balancing in accordance with the T' requirements of IMC 603.17.Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable volume fans with motors 10 horsepower. Project Title: Embassy Center Report date: 10/25/19 - Data filename:C:\Users\Cariie\Documents\COMcheck\Embassy-incomplete.cck Page 3 of 5 Plans reference page/section: u", `iz) 23.Manuals.The construction documents require that an operating and maintenance manual be provided to the building owner by the - mechanical contractor.See long descriptionAfor specifications. Plans reference page/section: s-k\ - o 24.Air System Design and Control.Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503.2.10.2. Plans reference page/section: N IA 25.Allowable fan floor horsepower.Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated in requirement details. Exception(s): Q Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. ID Individual exhaust fans with motor nameplate horsepower of 1 hp or less. Plans reference page/section: tyt' 1*26.Motor nameplate horsepower.For each fan,the selected fan motor is no larger than the first available motor size greater than the brake horsepower(bhp). Exception(s): D For fans less than 6 bhp,where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp,selection of the next larger nameplate motor size is allowed. D For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplateamotor size is allowed. Plans reference page/section: l A.I © 27.Large Volume Fan Systems.Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve single zones reduce airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code,whichever is greater. Exception(s): ❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity levels or supplying an exhaust system. Plans reference page/section: \\.) I P • 28.AII air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements. Exception(s): j Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity levels or supplying an exhaust system.y Plans reference page/section: \.r 1 Section 5: Compliance Statement Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application.The proposed mechanical alteration project has been designed to meet the 2014 Oregon Energy Efficiency Specialty Code,Chapter 8,requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the Requirements Checklist. j,V \,(A.h m - S a ( a( ti I Name-Title Signature Date Section 6: Post Construction Compliance Statement HVAC record drawings of the actual installation,system capacities,calibration information,and performance data for each equipment provided to the owner. ' HVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor. c Written HVAC balancing and operations report provided to the owner. The above post construction requirements have been completed. Project Title:Embassy Center Report date: 10/25/19 - Data filename:C:\Users\Carlie\Documents\COMcheck\Embassy-incomplete.cck Page 4 of 5 r 4- (7.1 Of \A nAtv Chr 2,,s7-71 Principal Mechanical Designer-Name Signature Date Project Title:Embassy Center Report date: 10/25/19 - Data filename:C:\Users\Carlie\Documents\COMcheck\Embassy-incomplete.cck Page 5 of 5 anK Construction Inc. Submittal General Contractors Job# 219089 Title Embassy Center Submittal Number: 15500-02 Date: 9/30/2019 Site 9200 SW Washington Sq Rd Tigard, OR 97223 Regarding: HVAC part 2 To: Woodblock REVIEWED ONLY AS TO GENERAL CONFORMITY WITH THE CONTRACT DOCUMENTS FOR DESIGN INTENT. THE DESIGN PROFESSIONAL DOES NOT WARRANT OR THESE ARE SUBMTITED as checked below: REPRESENT THAT THE INFORMATION ON THE SUBMITTAL/SHOP DRAWING IS EITHER ACCURATE OR OMPLETE. SOLE RES • SIBILITY FOR CONTRACT n For approval n For your use ESIVT1*(54ETtkiiklAND BON Ii5t1419a6WAlill Fa5MINkint ITH THE PARTY SUB' ING THE DRAWINGS OR SPECIFICATIONS. Remarks: PROVIDE FIRE PROTECTION @ ALL FIRE PARTITION WOODBLOCK-ARCHITECTURE, INC. PENETRATIONS (SUITE TO SUITE AND SUITE TO COMMON BY: MV DATE: 10.11.19 AREAS) PER OSSC CHAPTER 7. CONTRACTOR TO CONFIRM ❑ CONFORMS TO DESIGN INTENT REQUIREMENTS AT ALL WALL PENETRATIONS. ❑ CONFORMS TO DESIGN INTENT AS NOTED — ❑ NON-CONFORMINGREVIS€&RESUBMIT IX REVIEWED nApproved nRejected Revise/Resubmit [lApproved as Noted Vendor is entirely responsible for performance of their product(s). Corrections or comments made on the shot, drawings during this review do not relieve contractor from compiance with requirements of the drawings an, specifications. This check is only for review of general compliance with the informaiton given in the contra( documents. The contractor is responsible for conforming and correcting all quantities and dimension; selecti fabrication processes and techniques of construction; coordinating their work with that of all other trades; an performing their work in a safe and satisfactor manner. BnK Construction, Inc. General Contractors Phone: (503) 557-0866 Fax: (503) 557-1085 45 82nd Drive No. 53B, Gladstone, Oregon 97027 ph 503.557.0866 BnKconstruction.com wi TFB120-S - Damper Actuator BELIMO On/Off, Spring Return, 100 to 240 VAC Torque min.22 in-Ib,for control of air dampers. `/^ Application I Baia® r /O , e tol of daes Vs. tasiz shouldFobeffdone in safaccordanceconrwithmpthe rad per manufacturersystemAc's specificattoring Irtg-4":�m g' 5 ControlOn isOn/Offfail fromanauxiliarycontactin,orACamanualswitch.uTheactuatorionsis' mounted directly to a damper shaft from 1/4"up to 1/2"in diameter by means WARN! TY of its universal clamp,1/2"shaft centered at delivery.A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft. LISTED TEMP.D4DS IRE.B Operation C �t. DS NEG.Ep01°. The TF series actuators provide true spring return operation for reliable fail-safe Technical Data application and positive close off on air tight dampers.The spring return system Power Supply 100...240 VAC,-15%/+10%,50/60 Hz provides consistent torque to the damper with,and without,power applied Power Consumption Running 2.5 W to the actuator.The TF series provides 95°of rotation and is provided with a Power Consumption Holding 1.3 W graduated position indicator showing 0°to 90°.The actuator may be stalled anywhere in its normal rotation without the need of mechanical end switches. Transformer Sizing 5 VA Power consumption is reduced in holding mode.The actuator is double Shaft Diameter 1/4"to 1/2"round,centers on 1/2" insulated so an electrical ground connection is not necessary.The TF-S versions Electrical Connection (2)3ft[1m],18 GA appliance cables with are provided with one built-in auxiliary switch.This SPDT switch is provided 1/2"conduit connectors for safety interfacing or signaling,for example,for fan start-up.The switching Overload Protection electronic throughout 0°to 95°rotation function is adjustable between 0°and 95°. Electrical Protection actuators are double insulated Safety Note:Screw a conduit fitting into the actuator's bushing.Jacket the Angle of Rotation Max.95°,adjustable with mechanical stop actuator's input and output wiring with suitable flexible conduit.Properly Torque motor 22 in-lbs[2.5 Nm] terminate the conduit in a suitable junction box. Direction of Rotation(Motor) reversible with CW/CCW mounting Direction of Rotation(Fail-Safe) reversible with CW/CCW mounting Position Indication visual indicator,0°to 95° (0°is full spring return position) Dimensions(Inches[mm]) • Running Time(Motor) <75 sec 0.68" 17.3] Running Time(Fail-Safe) <25 sec @-4°F to 122°F[-20°C to 50°C], <60 sec @-22°F[-30°C] Ambient Humidity max.95%RH non-condensing ?_[ii�III� �■• Ambient Temperature -22.122°F[-30. 50°C]Storage Temperature -40.176°F[-40.80°C] II� Degree of Protection IP42,NEMA 2,UL Enclosure Type 2 6.28"[159.5] a Housing Material UL94-5VA r�� . e Agency Listingst cULus acc.to UL60730-1A/-2-14,CAN/CSA ; pc} L'' �E60730-1:02,CE acc.to 2004/108/EC and °° 2006/95/EC ' .s Noise Level(Motor) <50 dB(A) "' '\�..+`'• LII'III�I� " L Noise Level(Fail Safe) <62 dB(A) 0.77'[19.6] e MIll 0.39 [ss] 0 Servicing maintenance free Quality Standard ISO 9001 a u)• Weight 1.83 lb[0.83 kg] • Auxilliary switch 1 x SPDT,3A resistive(0.5A inductive)@ 250 N VAC,adjustable 0°to 95° N- ' tRated Impulse Voltage 4kV,Type of Action 1.AA.B,Control Pollution Degree 3. iv m R ci 800-543-9038 USA 866.805-7089 CANADA 203.791-8396 LATIN AMERICA/CARIBBEAN BELIMO TFB120-S - Damper Actuator On/Off, Spring Return, 100 to 240 VAC Accessories AV6-20 6.7"shaft extension for 1/4"to 3/4"diameter shafts. O� m IND-TF TF position indicator. 100 to 240 VAC K8 US Standard TFB(X)clamp(1/4"to 1/2"). KG10A Ball joint for 3/8"diameter rod,zinc plated. Line Wht N I-^Wht (1) Neutral KG8 Ball joint for 5/16"diameter rod,90°,galvanized steel. Volts Blk L �~i—Blk (2) Load KH8 Univ.crankarm,slot 21/64"w,for 3/8"to 11/16"dia.shafts. .. KH-TF US TFB(X)crankarm with 5/16"slot. On/Off KH-TF-1 US TFB(X)crankarm with 1/4"slot. KH-TF-1.1 US TFB(X)crankarm for Shafts with 1/4"slot. SB-TF TFB(X)mounting kit(T-bracket,bolts). /Z\//�\//� \ SH10 Push rod for KG10A ball joint(36"L,3/8"diameter). SH8 Push rod for KG6&KG8 ball joints(36"L,5/16"diameter). TF-P Anti-rotation bracket TF/NKQ/AM/NM/LM. I S1 TOOL-06 8 mm and 10 mm wrench. I S2 NC ZDB-TF Angle of rotation limiter for TFB(X). ZG-113 TFB(X)right angle bracket(4-1/2"H x 5-1/2"W x 2-1/2"0). I S3CNO 0°to 95° ZG-DC1 Damper clip for damper blade,3.5"width. Auxiliary Switches ZG-DC2 Damper clip for damper blade,6"width. ZG-LMSA-1 Shaft extension for 3/8"diameter shafts(4"1). ZG-LMSA-1/2-5 Shaft extension for 1/2"diameter shafts(5"L). ZG-TF112 TFB(X)crankarm adaptor kit(includes ZG-113). ZG-TF2 TFB(X)crankarm adaptor kit(T bracket included). ZS-100 Weather shield-galvaneal(13"L x 8"W x 6"D). ZS-101 Base plate for ZS-100. ZS-150 Weather shield-PC w/foam seal(16"L x 8-3/8"W x 4"D). P475 Shaft mount,non-Mercury aux.switch for 1/2"dia.shafts. P475-1 Shaft mount,non-Mercury aux.switch for 1"dia.shafts. PS-100 Actuator power supply and control simulator. TF-CC US Cable conduit connector,1/2". Typical Specification On/Off spring return damper actuators shall be direct coupled type which require no crank arm and linkage and be capable of direct mounting to a shaft up to a 1/2"diameter and center a 1/2"shaft.The actuators must be designed so that they may be used for either clockwise or counter clockwise fail-safe operation.Actuators shall be protected from overload at all angles of rotation. If required,one SPDT auxiliary switch shall be provided having the capability of being adjustable.Actuators with auxiliary switch must be constructed to E. meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings.Actuators shall be cULus listed,have a 5 year warranty,and be manufactured under ISO 9001 International Quality Control Standards.Actuators shall be as manufactured by Belimo. a 00 A N 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA/CARIBBEAN TFB120-S - Damper Actuator BELIMO On/Off, pring Return, 100 to 240 VAC Wirin' Dia 1 rams /'\ WARNING!LIVE ELECTRICAL COMPONENTS! During installation,testing,servicing and troubleshooting of this product,it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Meets cULus requirements without the need of an electrical ground connection. & Apply only AC line voltage or only UL-Class 2 voltage to the terminals of auxiliary switches.Mixed or combined operation of line voltage/safety extra low voltage is not allowed. OActuators with appliance cables are numbered. / '\ Provide overload protection and disconnect as required. A/� Actuators may be connected in parallel if not mechanically linked.Power A consumption and input impedance must be observed. AOne built-in auxiliary switch(lx SPDT),for end position indication, interlock control,fan startup,etc. a 0 0 0 0 E m 0 0, 0 r 0 d a cc, 0 N r N -c r. N U N 0 0 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA,CARIBBEAN • Model CSP-A Premium Inline Cabinet Fan ,, Model CSP-A Dimensions CSP-110-510,510-VG, F 710,710-VG,780 Model A B C D E F G Unit WeightI 12'/s 105/8 9 8 6 11'/a 73/e 16 G 110,125,190 (�` (327) (270) (229) (203) (152) (302) (187) (7) 200,250,290, 14 11'/8 11% 8 8 12'/8 10 23 � I/ 390 (356) (302) (286) (203) (203) (327) (254) (10) 18 14% 141/2 8 8 16'/e 13Ya >j, 410,510 (457) (365) (368) (203) (203 42g 36 ( ) (337) (1 6) Aral 700 235/8 11% 115/s 191/2 8 225) 1062 34 B..,,,::,. / (600) (295) (295) (495) (203) (575) (267) (15) 710,780 18 14% 141/2 10 8 16'/8 13Ya 36 (457) (365) (368) (254) (203) (429) (337) (16) CSP-700, hilik, 900,1050, 23% 14% 141/2 17'/s 8 22% 131/4 59 B.---'1 90 -3t i30 1410,1550 (603) (365) (368) (443) (203) (575) (337) (27) (��/� 1750,2150 35 14% 14% 28 6 323/4 13 68 (889) (375) (375) (711) (152) (832) (330) (31) l'- 101 I� `situ 3600 45Yz 16Yz 1662 4011431/4145/8 122I (1156) (419) (419) (1016) (279) (1099) (371) (55) G �� D All dimensions are in inches(millimeters)and weight in pounds(kilograms).Inlet and outlet 1 C connection widths are 1 in.(25 mm).Mounting bracket width is 11/2 in.(38 mm). \ For complete dimensional information,see CAPS submittal drawings. F inlet,/ -F r ''' ' ' ' :1' '' ' - ' y r ,,,,,,,,,'.--Yi.::''''''1;'''.‘f''''''''W'r':13,-;:::''' '''';:f-Sei:14-:::-.7.-'-'1°.'' d, �' j .. . , ,:- - ''' 'i 1:- - 1:-',.4. --,'-:,,,..: -Y -='. .i,'''''''';'?f:';',;- P 33 B , , ,, .., , :-.....,, ....-,-<:: §. 3 $� i1 ,":,,„.;',/,'..,:-',":;.'..:,„:',,,,.:,. r , y .0. . t "•. .+may *S'{J ?s P re i .. .. ,: ,. f 3snw #',tea 16 Model CSP-A **wow Earl Premium Inline Cabinet Fan y� PCa'Jft +sCf *Amp and Watt draw is approximate and may vary based on motor manufacturer.Below performance is for 115V. Model CSP-A Performance Max. CFM 1 Static Pressure in Inches wg Model RPM Amps* Input Watts* 0 0.1 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1.0 CFM 124 112 110 102 77 CSP-A110 950 0.62 20. Sones 0.8 0.8 0.8 0.9 0.9 Watts* 20.3 20.0 19.9 19.7 18.4 CFM 138 126 124 114 91 CSP-A125 1100 0.63 23 Sones 1.1 1.1 1.1 1.0 1.2 Watts" 22.5 22.3 22.2 22.1 21.3 CFM 215 202 198 180 159 121 CSP-A190 1400 1.10 55 Sones 2.0 1.5 2.0 2.0 2.5 2.5 Watts" 55.1 54.1 53.7 51.9 49.8 46.0 CFM 254 231 226 203 178 145 109 70 CSP-A200 900 0.43 58 Series 0.6 0.4 0.5 0.9 1.0 1.3 1.5 1.5 Watts* 57.9 57.3 57.1 56.1 54.6 52.5 50.3 48.0 CFM 266 246 241 221 205 187 165 132 CSP-A250 1000 0.79 67 Sones 0.9 1.0 1.0 2.0 2.5 3.0 2.5 2.5 Watts* 66.5 65.6 65.4 64.0 62.7 61.2 59.4 56.6 CFM 318 299 292 265 248 229 201 144 CSP-A290 1050 0.71 102 Sones 1.1 1.2 1.3 2.0 2.5 3.5 3.0 3.0 Watts* 102.2 100.9 100.4 98.3 96.9 95.0 90.5 81.3 CFM 412 400 397 382 363 339 324 309 CSP-A390 1350 1.33 161 Sones 2.0 2.0 2.0 2.5 3.0 4.0 4.5 4.5 Watts* 160.8 158.5 157.9 152.4 147.9 141.8 135.4 130.0 CFM 447 441 403 364 317 217 CSP-A410 1000 1.87 132 Sones 1.5 1.5 1.5 2.0 2.0 2.0 Watts* 132.2 131.7 128.7 125.6 120.5 112.4 CFM 545 514 506 464 405 324 CSP-A510 1070 3.11 218 Sones 2.5 2.0 2.0 2.0 2.0 2.5 Watts* 218.2 214.3 213.3 207.0 196.4 182.8 CFM 766 755 752 739 726 702 678 635 549 418 CSP-A700 1100 3.20 352 Sones 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 4.0 Watts* 352.1 350.7 350.3 348.7 346.3 340.7 332.6 315.5 289.1 256.1 CFM 737 698 688 635 567 475 334 CSP-A710 1080 4.40 333 Sones 2.5 2.5 2.5 2.5 2.0 2.0 2.0 Watts* 332.5 324.1 322.0 310.8 295.8 277.4 255.2 CFM 813 784 777 742 707 672 638 603 567 527 CSP-A780 1600 3.77 496 Sones 3.0 3.0 3.0 3.0 3.0 2.0 3.0 3.0 3.0 3.5 Watts* 496.4 493.0 492.2 488.0 467.5 453.1 441.8 423.1 407.2 CFM 908 852 841 782 715 631 CSP-A900 950 4.87 335 Sones 1.4 1.4 1.4 2.0 2.5 3.0 Watts* 335.0 288.6 286.0 272.7 259.9 245.5 CFM 1182 1110 1093 1013 922 832 743 CSP-A1050 1095 6.65 469 Sones 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Watts* 468.8 455.9 453.3 440.8 424.9 411.0 399.2 CFM 1584 1543 1533 1483 1439 1395 1345 1293 1238 1181 CSP-A1410 1450 7.80 871 Sones 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.0 4.0 Watts* 870.8 837.9 829.9 788.2 751.0 728.3 696.3 661.8 628.8 595.9 CFM 1672 1618 1604 1543 1484 1427 1367 1307 1240 1172 CSP-A1550 1610 8.32 913 Sones 5.0 4.5 4.5 4.5 4.5 4.0 4.0 4.5 4.5 4.5 Watts" 912.8 877.4 868.4 829.3 802.9 778.0 744.3 710.7 679.1 647.4 CFM 1842 1768 1749 1619 1464 1284 1032 772 484 CSP-A1750 1130 6.60 560 Sones 5.0 5.0 5.0 4.5 4.0 4.0 3.5 3.0 3.0 Watts* 599.8 570.5 563.0 515.0 470.9 420.3 366.1 317.2 276.5 CFM 2249 2175 2156 2044 1900 1701 1424 1114 CSP-A2150 1100 7.80 761 Sones 5.0 4.5 4.5 4.0 4.0 4.0 3.0 3.0 Watts* 760.8 731.5 724.0 679.7 622.7 544.0 459.7 382.3 CFM 3778 3653 3622 3460 3280 3091 2844 2551 2232 1750 CSP-A3600 1100 7.10 1314 Sones 5.0 5.0 5.0 5.0 4.5 4.0 4.0 4.0 3.5 3.5 Watts" 1313.7 1253.3 1238.3 1160.0 1084.0 1041.5 971.1 871.9 766.5 649.5 Performance certified is for model CSP inline for installation type D:Ducted inlet,Ducted outlet.Performance ratings include the effects of a backdraft damper. Speed(rpm)shown is nominal.Performance is based on actual speed of test.The sound ratings shown are loudness values in spherical fan sones at 5 ft(1.5m)in a spherical free field calculated per Annex B of AMCA 311.Values shown are for installation type D:ducted inlet spherical fan sone levels.Ratings do not include the effect of duct end correction.Ratings are based on 10 ft of insulated duct. 17 IN GREENHECK ESD-435 Stationary Louver Drainable Blade Application and Design411,1 amca ESD-435 is a weather louver designed to protect air intake and C RTIf ED WORIDWIDE exhaust openings in building exterior walls. Design incorporates ( ; Ramos drain gutters in the head member and horizontal blades to renETWnurionRTER channel water to the jambs where water is further channeled [:› PEgi°n®neR through vertical downspouts and out at the sloped sill. The ESD- 1/ n n 435 is an extremely efficient louver with AMCA LICENSED i RflDOOnT �0 ono conTnot °% PERFORMANCE DATA enabling designers to select and apply Z n'fcc'nT'pn ° InTEnnnTlOnn1.Inc.,°9 with confidence. J Standard Construction Frame Heavy gauge extruded 6063-T5 aluminum, 1 4 in.x 0.081 in. nominal wall thickness Blades Drainable design, heavy gauge extruded 6063- T5 aluminum, 0.081 in. nominal wall thickness, positioned at 37.5°angles on approximately [,o,6mm] 3 t/4 in. centers Construction Mechanically fastened Birdscreen 3/4 in.x 0.051 in.flattened expanded aluminum in . removable frame, inside mount(rear) Finish Mill Minimum Size 12 in. W x 9 in. H Maximum Single Section Size 120 in.W or 120 in. H (limited to 70 ft. sq.) D Options (at additional cost) ' - •A variety of bird and insect screens P A\ • Blank off panel P , ,� • Clip angles \ • Extended sill H / � . • Filter rack • Flanged frame • Glazing adaptor I, 1 • Hinged frame • Security bars •Welded construction • 0.125 nominal wall thickness •A variety of architectural finishes including: Clear anodize \: .'1 %**%%.N Integral color anodize Baked enamel paint W \ Kynar paint '''''''',,,,„,,,,,. :: *Width and height dimensions furnished approximately/a inch under size. PERFORMANCE DATA ESD-435 Stationary Louver Drainable Blade Free Area Chart (Sq. ft.) Extruded Aluminum Louver Louver Width in Inches Lo Loh1 amcci Greenheck Fan HeigInchgs 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 OE WORLDWIDE iT Ep E Corporation certifies - s"*'"c' that the ESD-435 9 0.15 0.25 0.35 0.44 0.54 0.64 0.74 0.81 0.91 1.01 1.10 1.20 1.30 1.37 1.47 1.57 1.67 1.76 1.86 suttuesTlitlouvers shown herein 12 0.30 0.49 0.68 0.87 1.07 1.26 1.45 1.59 1.79 1.98 2.17 2.36 2.56 2.70 2.89 3.08 3.28 3.47 3.66 > My, t are licensed to bear 18 0.54 0.88 1.23 1.58 1.93 2.28 2.62 2.88 3.23 3.58 3.93 4.28 4.62 4.88 5.23 5.58 5.93 6.28 6.62 m. , the AMCA Seal.The 24 0.79 1,30 1.81 2.32 2.83 3.33 3.84 4.23 4.74 5.25 5.76 6.27 6.78 7.16 7.67 8.18 8.69 9.20 9.71 ratings shown are ,rirenownon°.. based on tests and 30 1.04 1.71 2.38 3.06 3.73 4.40 5.08 5.58 6.26 6.93 7.60 8.28 8.95 9.45 10.13 10.80 11.47 12.15 12.82 procedures performed 36 1.29 2.13 2.97 3.81 4.65 5.49 6.33 6.96 7.80 8.64 9.48 10.31 11.15 11.78 12.62 13.46 14.30 15.14 15.98 in accordance with AMCA Publication 42 1.55 2.55 3.55 4.56 5,56 6.56 7.57 8.32 9.32 10.32 11.33 12.33 13.33 14.09 15.09 16.09 17.10 18.10 19.10 511 and comply with the requirements 48 1.82 3.01 4.19 5.37 6.55 7.74 8.92 9.81 10.99 12.17 13.35 14.54 15.72 16.61 17.79 18.97 20.16 21.34 22.52 of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal 54 2.08 3.44 4.79 6.14 7.49 8.85 10.20 11.21 12.56 13.92 15.27 16.62 17.97 18.99 20.34 21.69 23.04 24.40 25.75 applies to air performance and water 60 2.33 3.85 5.36 6.87 8.39 9.90 11.42 12.55 14.06 15.58 17.09 18.61 20.12 21.26 22.77 24.28 25.80 27.31 28.82 penetration ratings. 66 2.58 4.26 5.94 7.61 9.29 10.97 12.64 13.90 15.58 17.25 18.93 20.60 22.28 23.54 25.21 26.89 28.57 30.24 31.92 72 2.84 4,68 6.52 8.36 10.20 12,05 13.89 15.27 17.11 18.95 20.79 22.64 24.48 25.86 27.70 29.54 31.38 33.22 35.07 78 3.09 5.10 7.10 9.11 11.11 13.12 15.12 16.63 18.63 20.64 22.65 24.65 26.66 28.16 30.17 32.17 34.18 36.18 38.19 84 3.35 5.53 7.70 9.88 12,05 14.23 16.40 18.03 20.21 22.38 24.56 26.73 28.91 30.54 32.71 34.89 37.06 39.23 41.41 90 3.64 6.00 8.37 10.73 13.09 15.45 17.82 19.59 21.95 24.31 26.67 29.04 31.40 96 3.88 6.40 8.92 11.44 13.95 16.47 18.99 20.88 23.40 25.91 28.43 30.95 33.47 102 4.13 6.81 9.49 12.17 14.85 17,53 20.21 22.22 24.90 27.58 30.26 32.94 35.62 108 4.38 7.23 10.07 12.91 15.76 18.60,21.44 23.58 26.42 29.26 32.11 34.95 37.79 114 4.64 7.65 10.66 13.67 16.68 19.68 22.69 24.95 27,96 30.97 33.98 36.99 40.00 120 4.89 8.07 11.24 14.41 17.58 20.76 23.93 26.31 29.48 32.66 35.83 39.00 42.18 Airflow Resistance (Standard Air- .075 Ib/fel Water Penetration (Standard Air- .075 lb/ft3) Pe In.N'9 Test size 48 in.x 48 in. Test duration of 15 min. 1 0.9 I _. ml/m2 oz/ft2 200 - 0.8-- Teat She 48 In.z 48 in. 0.7- Stenderd Air-.078 lb/fl' 0.30 0.6. : . Teat Size 48 In.8 48 In. 0.5 N TestPeriod1Sminutes. 00- Air..075 IbFft , �0.25 ra: Stantlard100- 0,4 N } { I90 " y- 0.3 0.20 3 ao . .7 40 *° C 0.15 I.40 � 11tl 30- i`� 010 ;,. 0.1 - 0.09 - LL v1 20- 0.06 - __- --' -1 d 20- 1_^ 0.07 006 3 o.os 0.05 HIM_! l �-+ 10- 0.04 0- 0.00 . . . . • . . . . r . i r I t-. 1 it 9- 6 ft/min: 900 950 1000 1050 1100 1150 1200 7 0.03 I I m/s: 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6 Free Area Velocity 5- 0.02 ' ' The AMCA Water Penetration Test provides a method for comparing fern.re nt e e 4Peciv various louver models and designs as to their efficiency in resisting m/s 2 3 4 5 6 7 8 910 the penetration of rainfall under specific laboratory test conditions.The beginning point of water penetration is defined as that velocity where the Free Air Velocity water penetration curve projects through .01 oz. of water(penetration) Model ESD-435 resistance to airflow(pressure drop)varies per sq.ft. of louver free area. *The beginning point of water depending on louver application(air intake or air exhaust). penetration for Model ESD-435 is 989 fpm free area velocity. Free area velocities(shown)are higher than average These performance ratings do not guarantee a louver to be weather- velocity through the overall louver size.See louver selection proof or stormproof and should be used in combination with other factors information.(Test Figure 5.5) including good engineering judgement in selecting louvers. I ft GREENHECK INSTALLATION DETAILS ESD-435 Maximum Size and Installation Information Stationary Louver Drainable Blade Extruded Aluminum • Maximum single section size for model ESD-435 is 120 in.W x 84 in. H or 84 in.W x 120 in. H(70 sq.ft).Larger openings require field assembly of multiple louver sections to make up the overall opening size. Individual louver sections are designed to withstand a 25.PSF wind load(please consult Greenheck if the louvers must withstand higher wind-loads).Structural reinforcing members may be required to adequately support and install multiple louver sections within a large opening.Structural reinforcing members along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck.Options and accessories including,but not limited to,screens,filter racks,louver doors,and blank off panels are not subject to structural analysis unless indicated otherwise by Greenheck.Additional information on louver installation may be found in AMCA Publication #501, Louver Application Manual. SINGLE SECTION W/ SUPPORT ANGLES MULTIPLE SECTION W/ MULLION ;0 '0 1jiIi 0 �� ill®_ 0 (f) ...1.1111111111111111111 1111111.111111.11.11111.1.1 n S X CP =1111.11.11111111111111/11111..M.1 Q EIMIMINEMEMIll 1 EiiiIP E IM111111111111111111111MMI co R" P o z 11111111111111111111111111111111 r v N 7 I-- IIIMIIIIIMIIIIMMIMMIIIIIIIIIIIIIIIIIIIIIIIMMMIU IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII U C_ 7- IMMEMIIIMMEMII 111111.11111111.1=== ( 111M11.1.1111 1111.1111111.11111 M11.1.0111 01111111111111111.1.11= .11.111.1.1.1111 111111.111.1111111111. 1 1111111111111111111111.11=1=IMMERSION.. .11111.1.11.1.111111111111-- LI_____1 ® '® 20" [3048mm] MAX. W/1 SUPPORT SHIP SECTION SHIP SECTION UNLIMITED Minimum Single Section Size Maximum Single Section Size 12in.Wx9in.H 70 ft.sq. j MOREENHECK PRODUCT DETAILS ESD-435 Stationary Louver Drainable Blade �� A7 HEAD DETAIL \E OHEAD DETAIL Extruded Aluminum ri SEALANT AND BACKER ROD N ri SEALANT AND BACKER ROD NOT BY GREENHECK NOT BY GREENHECK • Vila .081 [2.tmm] EXTRUDED �I�l� .081 [2.1mm] EXTRUDED ALUMINUMHEAD ALUMINUMHEAD. 1 1 mEXTRUDEDA' A UIMWUMmHE]ADXTRUDED ALUMINUM HEAD III SUPPORT BRACKET III SUPPORT BRACKET I_ - IF REQ'D - IF REQ'D z o _CO /-II�. .081 [2.1mm] EXTRUDED z rill ALUMINUM BLADE z J All IIO STACK DETAIL = �ii�'to w `C .081 [2.1mm] EXTRUDED zIiI= ALUMINUM BLADE w "111_ SUPPORT BRACKET x wc� z . - 8> l -4" [101.6mm] 1z L ( II36" [914.4mm] LONG g' ofIV _- EXTRUDED ALUMINUMV a .081 [2.1mm] EXTRUDED z o 11SPLICE ANGLE - IFREQ•D Z It ALUMINUM BLADE I ("ii, �` SUPPORT BRACKET .081 [2.1 mm] EXTRUDED I - IF REQ'D VIII I ALUMINUM B ADEo _� '„ a ,--- to !_ 5/16" X 1" _ OPTIONAL BIRD w f l'il I HH ZP CS & NUT IAI OR INSECT SCREEN 0 1 1/2" X 1 1/2" X 1/8" 1 1/2" X 1 1/2" X 1/8" [3.2mm] EXTRUDED ALUMINUM (3.2mm] EXTRUDED ALUMINUM SUPPORT ANGLE SUPPORT ANGLE- IF REQ'D ir _ �� .081 [2.1mm] .087 [2.imm] iJ- EXTRUDED EXTRUDED ALUMINUM SILL - -- ALUMINUM SILL 4• � 'NONCOMPRESSIBLE NONCOMPRESSIBLE ro P DEAD LOAD SHIM, SEALANT 'co E DEAD LOAD SHIM, SEALANT N AND BACKER ROD ,N AND BACKER ROD NOT BY GREENHECK NOT BY GREENHECK B1 SILL DETAIL ®SILL DETAIL { 7,x.s.J1 I jl II t p J OPTIONAL EXTENDED SILL OPTIONAL FLANGE i 36" [914.4mm] LONG EXTRUDED ALUMINUM 1 1/2" X 1 1/2" SPLICE ANGLE - IF REQ'D OPTIONAL BIRD X 1/8" [3.2mm] _ EXTRUDED ALUMINUM I"_. 5/16" X 1" � �OR INSECT SCREEN SUPPORT ANGLE MI" HH ZP CS & NUT .081 [2.1mm] -- ;-- - __'__ EXTRUDED ALUMINUM JAMB .081 [2.1mm] EXTRUDED - SEALANT AND ALUMINUM BLADE � BACKER ROD SUPPORT BRACKET __ NOT BY GREENHECK ' .,s, dral SEALANT AND BACKER ROD NOT BY GREENHECK SECTION WIDTH - - SECTION WIDTH--..- - SECTION WIDTH c� 1/8" ACTUAL LOUVER WIDTH o- ....----ACTUAL LOUVER WIDTH--..- [3.2mm] - NOMINAL WIDTH ...I-NOMINAL WIDTH OJAMB DETAIL ®MULLION DETAIL 0SUPPORT DETAIL rid GREENHECK OPTION DRAWINGS ESD-435 Stationary Louver Drainable Blade Extruded Aluminum OPTIONAL 1 1/2" [38.1 mm] PERIMETER FLANGE �L OPTIONAL PERIMETER • .081 [2.1 mm] EXTRUDED �� CLIP ANGLES ALUMINUM FRAME �% i"- .081 [2.1mm] EXTRUDED ALUMINUM GLAZING ADAPTER (1" SHOWN) / OPTIONAL ISECURITY BARS .440 ,,,, ,, loo, !- /� OPTIONAL BIRD OR INSECT SCREEN IN REMOVABLE I I' ALUMINUM FRAME �/ ,--- , , i f jai�" % OPTIONAL OPTIONAL SINGLE SHEET, , �' EXTENDED SILL 1" (25.4mm) OR 2" (50.8mm) INSULATED BLANKOFF PANEL Ilki .,OPTIONAL ALUMINUM FILTER ' RACK AND FILTER(S) FINISHES Finish Type Description/Application Color Selection Standard Warranty (Aluminum) Standard Colors:Any of the 24 ar„ � 2-coat 70%KYNAR 5000/HYLAR 50000 AAMA 2605- "Best."The premier finish for extruded aluminum.Tough, 10 Years long-lasting coatinghas superior color retention and standard colors shown can be Dryfilm thickness 1.2 mil. AKA:Duranar®,Fluoro on®, g 9 (Consult Greenheck for ( P furnished in 70%or 50%KYNAR Trim®,Flouro of mer,Pol in lidene Fluoride,PVDF2) abrasive properties.Resists chalking,fading,chemical availability of extended P y y abrasion and weathering. 5000/HYLAR 5000®or Baked Enamel. warranty) 2-Coat Mica: 2-coat 50%KYNAR 5000/HYLAR 50000 AAMA 2604 "Better."Tough,long-lasting coating has excellent color Greenheck offers 9 standard 2- retention and abrasive properties.Resists chalking,fading, coat Mica colors.Other colors are 5 Years -Dry film thickness 1.2 mil.(AKA:Acroflur®,Acrynar®) chemical abrasion and weathering. available.Consult Greenheck for possible extra cost when selecting Baked Enamel AAMA 2603-Dry film thickness 0.8 mil. "Good."Provides good adhesion and resistance to non-standard colors or special 1 Year (AKA:Acrabond Plus®,Duracron®) weathering,corrosion and chemical stain. finishes. Integral Color Anodize AA-M10C22A42(>0.7 mil) "Two-step"anodizing is produced by following the normal Light,Medium or Dark Bronze; 5 years anodizing step with a second,colorfast process. Champagne;Black Clear Anodize 215 R-1 AA-M10C22A41(>0.7 mid Clear,colorless and hard oxide aluminum coating that resists Clear 5 years weathering and chemical attack. Clear Anodize 204 R-1 AA-M10C22A31(0.4-0.7 mil) Clear,colorless and hard oxide aluminum coating that resists Clear 1 Year weathering and chemical attack. Industrial coatin s Greenheck offers a number of industrial coatings such as Hi-Pro Polyester,Epoxy,and Permatector®. 9 Consult a Greenheck Product Specialist for complete color and application information. Consult Greenheck Mill Materials may be supplied in natural aluminum or galvanized steel finish when normal weathering is n/a acceptable and there is no concern for color or color change. Finishes meet or exceed AAMA 2605,AAMA 2604,and AAMA 2603 requirements.Please consult www.greenheck.com for complete information on standard and extended paint warranties.Paint finish warranties are not applicable to steel products. GREEIVIIECK Copyright©2018 Greenheck Fan Corporation • Greenheck Fan Corporation reserves the right P.O.Box 410•Schofield,WI 54476-0410•715.359.6171•greenheck.com to make product changes without notice. BnK Construction Inc. Submittal General Contractors Job# 219089 Title Embassy Center Submittal Number: 15500-03 Date: 10/11/2019 Site 9200 SW Washington Sq Rd Tigard, OR 97223 Regarding: HVAC Equipment To: Woodblock REVIEWED ONLY AS TO GENERAL CONFORMITY WITH THE CONTRACT DOCUMENTS FOR DESIGN INTENT. THE DESIGN PROFESSIONAL DOES NOT WARRANT OR REPRESENT THAT THE INFORMATION ON THE THESE ARE SUBMITTED as checked below: SUBMITTAL/SHOP DRAWING IS EITHER ACCURATE OR COMPLETE. SOLE RESPONSIBILITY FOR CONTRACT For approval C For your use U SIGN.14E DETAIL AND D ONigel3h�REMAIN nt `--v'►� Fir `�-�SUB IT UVl SPECIFICATIONS Remarks: MECHANICAL IS BIDDER DESIGNED. MECHANICAL WOODBLOCK ARCHITECTURE, INC. CONTRACTOR NEEDS TO ENGAGE A STRUCTURAL • ENGINEER TO COVER THE SCOPE OF THE BY: MV DATE: 10.18.1<: MECHANICAL WORK. WBA CAN PROVIDE A ❑ CONFORMS TO DESIGN INTENT REFERENCE IF NEEDED. ❑ CONFORMS TO DEStGN-1 0 NON-CONFORMING, REVISE&RESUBMIT ---------- -- -- --- ® REVIEWED nApproved Rejected ❑Revise/Resubmit nApproved as Noted Vendor is entirely responsible for performance of their product(s). Corrections or comments made on the shop drawings during this review do not relieve contractor from compiance with requirements of the drawings and specifications. This check is only for review of general compliance with the informaiton given in the contract documents. The contractor is responsible for conforming and correcting all quantities and dimension; selecti fabrication processes and techniques of construction; coordinating their work with that of all other trades; an performing their work in a safe and satisfactor manner. BnK Construction, Inc. General Contractors Phone: (503) 557-0866 Fax: (503) 557-1085 45 82nd Drive No. 53B, Gladstone, Oregon 97027 ph 503.557.0866 BnKconstruction.com TRANE® Submittal Prepared For: Date:October 4, 2019 Latimer HVAC Customer P.O. Number: Customer Project Number: Sold To: Job Number: Job Name: Embassy Commons Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed Kyle Wolf between submittal generation and equipment release,the product Trane performance and submittal data will need to be verified. It is the 7257 SW Kable Lane customer's responsibility to obtain such verification. Portland, OR 97224-7181 Phone: (503)620-8031 - Cell: (503)828-6788 Fax: (503)639-1454 J:IJOBSI124180110121Embassy Commons-submittal 01.doc Table Of Contents Product Summary 1 Variable Air Volume Fan Powered Terminal Units(Item Al) Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 4 Unit Dimensions 8 Accessory 9 Field Wiring 10 Embassy Commons October 4,2019 Tag Data -Variable Air Volume Fan Powered Terminal Units (Qty: 1) Item Tag(s) Qty Description Model Number Al No Tag 1 VAV Fan Powered Terminal Units VPEF1000Q**DD04AD210-L-WWD05021W-00 1 Product Data -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 Parallel with electric heat 10" (254 mm) 03 super quiet fan 1/2" [13mm] matte faced insulation Flanged connection 277/60/1 motor voltage Single speed motor w/SCR DDC with on/off electric heat control Standard actuator Left hand controls connection Duct temperature sensor Disconnect switch Power fuse 277 volt, 1 phase 5.0 kilowatt 2 stages of heat-equal increments 24vac magnetic contactors Electric heater air flow switch Performance Data -Variable Air Volume Fan Powered Terminal Units Tags No Tag Design cooling airflow(cfm) 650 Min cooling airflow(cfm) 400 Valve heating airflow(cfm) 400 Cooling inlet diameter(in) 10.000 Cooling inlet velocity(ft/min) 1192 APD @ cooling airflow(in H2O) 0.019 Fan airflow(cfm) 650 Downstream SP (in H2O) 0.250 Fan TSP (in H2O) 0.257 % of fan range (%) 47.00 Fan power(hp) 0.333 Plenum EAT(F) 70.00 Primary EDB (F) 80.00 Operating weight(Ib) 113.0 Hot water valves? None or Fld Prvd FloatingPoi nt Unit heating airflow(cfm) 1050 Coil heating capacity(MBh) 17.08 Room heat loss (MBh) 27.11 Room heating setpoint(F) 65.00 Coil EAT (F) 73.81 Unit LAT (F) 88.80 Coil LAT (F) 88.80 Full load amps (A) 19.65 Min circuit ampacity(A) 24.56 Max overcurrent protection (A) 25.00 Electric heater kW(kW) 5.00 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 11 Others Embassy Commons October 4,2019 Mechanical Specifications-Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 General Unit Information Casing-The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged. Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided. Filter-A filter is provided on the plenum inlet. Agency Listing -UL and Canadian UL listed as environmental air terminal unit. UL Control#9N65. All Trane terminal units are AHRI 880-98 certified. General Unit Clearance Leave a minimum of 36"on control box side of unit for adequate service access.Allow at least 12"on remaining sides for unit clearance.A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. Electrical Installation Information For electrical connections, consult field wiring section&equipment IOM. IMPORTANT: Field Wiring Most fan-powered VAV terminal units with electric reheat require a neutral connection from building power, however, some configurations do not. In order to prevent a building wiring issue once the boxes are installed,the wiring diagrams and field wiring installation for each unit MUST be checked to determine whether the neutral is required or not required. 1/2"Matte-Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2", 1.8 lb/cu.ft composite density glass fiber with high density facing. The insulation is UL listed and meets NFPA-90A and UL 181 standards. All insulation options will meet the 25/50 smoke developed and flame spread rating(per ASTM E 84 and UL 723 and CAN/ULC S102-M88) Meets NFPA-90B. The insulation R-value is 1.9.All cut edges of insulation are completely encapsulated in metal to prevent erosion. Air Valve &Fan Description (Parallel) (Series) The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct.A multiple point, averaging flow sensing ring is provided with balancing taps for measuring airflow within +/-5%of unit cataloged airflow. Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential.The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks.The damper blade assembly is connected through a cast zinc stub axle and shaft supported by self lubricating bearings.The shaft is cast with a damper position indicator.The valve assembly includes a mechanical stop to prevent over stroking. Air valve leakage <1% at 4". 1003SQ Air Valve/Fan Combination Size(Parallel) 10" Inlet designed for up to 1400.0 cfm. Fan is 1100.0 cfm for Std Motor and 1085.0 cfm for ECM Motor.. Fuse Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided. Factory Wired/Field Mounted Auxiliary Temperature Sensor The auxiliary temperature sensor is used in conjunction with the Trane DDC controller to sense duct temperature.When the DDC controller is used with a Building Automation System,the sensor temperature is reported as status only.When the DDC controller is used in a stand-alone configuration, the sensor determines the control action of the UCM in a heat/cool changeover system. The factory mounted option eliminates field wiring by providing the sensor pre-wired and zip-tied to the control box, where it can be easily cut loose and mounted in the duct. Motor Single Speed, direct drive induction, permanent split capacitor type.Thermal overload protection provided. Motors will be designed specifically for use with an open SCR which is standard. Motors will accommodate anti-backward rotation FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 11 Others Embassy Commons October 4,2019 at start up. Motor and Fan assembly are isolated from terminal unit. Electric Heat Coil Factory provided and mounted. Resistance open-type heater, a disc-type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel-chromium.The heater terminal box is provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators.All fan-powered units with electric reheat are single-point power connections. Magnetic Contactor An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.)or Analog Electronic VAV Controls. Transformer The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls. SCR-Variable Fan Speed Control Switch The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to achieve exact CFM requirements. Power Disconnect Switch (for VSEF&VPEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Power Fuse Fuses provided on all energized lines of incoming power to interrupt circuit overcurrent conditions. Flanged Connection A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection. System Communications The Controller is designed to send and receive data from a Central Control Panel or other Tracer family products, or a VariTrac CCP. Current unit status conditions and set points may be monitored and/or edited via this data communication feature. The network type is a twisted wire pair serial communication. Set points in Nonvolatile Memory(9 Thru 15) 9. Heating Set point Offset-This determines at what point the 1st. stage of reheat turns on. Expressed in degrees below cooling set point, only applicable when local thumb wheel is enabled. 10. Zone temperature, auxiliary temperature, and zone set point calibration corrections (+/- 10.0 F). 11. Flow measurement calibration correction (50- 150%). 12. Cooling Set point Low Limit-Applies low limit to programmed occupied cooling set point or zone sensor cooling set point(30.0 F- 100.0 F). 13. Heating Set point High Limit-Applies high limit to programmed occupied heating set point or zone sensor heating set point(30.0 F- 100.0 F). 14. RTD/Thermistor- Determines what type of zone temperature sensor will be used. 15. Occupied and Unoccupied Outside Air Requirements- Determines the percent of outdoor air required in the zone for air quality requirements. D.D.C. Floating Point Actuator Trane 3 wire, (open,close, common)26GA when 6-pos amp connector is used for Tracer UC210,W550,or VAV UCM, otherwise 18GA wires are used. 3.4 VA, 1.7W, 24 VAC, 50/60 Hz. Quarter turn control actuator with linkage release button.Actuator has a constant drive rate independent of load, a rated torque of 35 in-Ib, a 90-second drive time and is non-spring return. Travel is terminated by end stops at fully opened and closed positions.An integral magnetic clutch eliminates motor stall. An integral 3 screw terminal block is provided for field wiring. Operating temperature 32.0 F to 125.0 F. Additional Status Information (1 thru 8) In addition to the above set points,the following status information can be transmitted to the Command Control Unit and Tracer. 1. Active cooling temperature set point. 2: Active heating temperature set point. 3. Current unit primary airflow. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 11 Others Embassy Commons October 4,2019 4. Current zone temperature. 5. Re-heat status(On/Off). 6. Auxiliary Air Temperature-Available only if the unit has an auxiliary temperature sensor. 7: Failure Indicators-The U.C.M. will indicate the following: *Temperature Sensor Failure *Flow Sensor Failure *Local Zone Sensor Set point Failure 8. Ventilation Ratio. Direct Digital Controller The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a proportional integral control algorithm and direct control technology.The controller monitors zone temperature set points, zone temperature and its rate of change, and valve airflow, using a differential pressure signal. Optionally, the controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller and pressure transducer are installed and factory wired in an enclosure with 7/8"knockouts for remote control wiring.A Trane zone sensor is required. Override Commands The following override commands may be received by the Unit Control Module(U.C.M.)from the Tracer System. Control Mode,Action, &Offset(1 thru 12) 1. Control Mode-The U.C.M. Control Mode may be edited from occupied to unoccupied to accommodate night setback/setup. 2. Control Action-The Control Action may be edited from cooling to heating, changing the primary air damper to a heating source. This will accommodate a cooling/heating changeover system. 3. Control Offset-Enabling Control Offset will increase the cooling temperature set point and decrease the heating temperature set point by a control offset value stored at the U.C.M. This function facilitates demand limiting in the occupied mode. 4. Drive damper fully open. 5. Drive damper fully closed. 6. Drive damper to maximum airflow set point. 7. Drive damper to minimum airflow set point. 8. Disable unit fan. 9. Disable unit heat. 10. Reset- Enabling the reset function forces the controller and the flow sensor to recalibrate. ' 11. Programmable hot water valve drive time. 12. Programmable air valve drive time. Following Unit Set points The following unit set points reside in the U.C.M. in nonvolatile memory. These set points are editable from the Command Unit or Tracer via the communications link. Set points in Nonvolatile Memory(1 thru 8) 1. Occupied cooling temperature set point 60.0 F -80.0 F. 2. Occupied heating temperature set point 60.0 F - 80.0 F. 3. Unoccupied cooling temperature set point 60.0 F - 100.0 F. 4. Unoccupied heating temperature set point 30.0 F- 100.0 F. 5. Minimum cooling flow set point(0, 10 - 100%of unit equivalent cataloged airflow). 6. Minimum heating flow set point(0, 10- 100%of unit equivalent cataloged airflow). 7. Maximum flow set point(0,10- 100%of unit equivalent cataloged airflow). 8. Fan Control Offset-This determines at what operating point the fan in a parallel fan powered unit is energized.This can be specified as a function of temperature, degrees above heating set point, or primary airflow. 0.0 F - 10.0 F or 0, 10- 100%of unit equivalent cataloged airflow). Set points in Nonvolatile Memory(16 thru 21) 16. Series Fan Configuration-allows option of series fan powered box to shut off fan and close air valve when unit is unoccupied. Fan will operate in unoccupied mode if reheat is active. 17. Heating set point low limit. 18. Cooling set point high limit. 19. Local heating flow set point enable/disable&set point. 20. Auxiliary analog input mode select for either auxiliary temperature sensor or CO2 detector. 21.. Binary input mode select for either generic or occupancy detector. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 11 Others Embassy Commons October 4,2019 Additional Status Information (9 thru 12) 9. Fan Status (on/off) 10. Calibration Status (calibrating/not-calibrating) 1-1. BIP state 12. CO2 Concentration-available only if the unit has an auxiliary CO2 sensor. This mode and auxiliary air temperature are mutually exclusive. DDC Sequence of Operation The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as required to meet zone set points. Airflow is limited by minimum and maximum airflow set points. Parallel Unit Fan Energization As the zone temperature reaches the heating set point, the microprocessor controls airflow to the heating temperature set point and energizes the auxiliary fan when necessary. At or below the heating set point, reheat is energized. The heating minimum airflow set point is factory set,field adjustable, and is separate from the cooling minimum set point. Parallel unit fan energization is a function of primary airflow or zone temperature. 1. Primary Airflow-The fan energizes when primary airflow drops below the fan set point airflow.The fan automatically starts when the zone temperature drops to the heating temperature set point. 2. Zone Temperature-The fan energizes when the zone temperature drops to a selectable number of degrees above the heating temperature set point. DDC Controls Option DD04, DD14, DD44&DD74 Basic Operation: On/Off Staged Electric Heat(Normally Open Outputs)(DDC/UCM) (Parallel Units) A voltage signal from the zone sensor indicates the zone temperature is used by the unit controller to determine an error from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within minimum and maximum cooling airflow set points. As the zone temperature drops to the heating set point, primary airflow is controlled to minimum heating flow set point. The fan operation is intermittent in both modes. Staged electric heat is energized. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 11 Others Embassy Commons October 4,2019 Unit Dimensions -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 Unit Size VPEF1003SQ ..NH.........„..........F" Nominal 70"Dia.x 4"Depth Valve Size&Depth Nominal 03SQ Fan +4 • ' Fan Size •��Rv�$ N ,. Filter Size 16"x 20"X 1"(QTY 1) .;',Sg,���.�gteg., ;.j �tC. is.40111111111 TOP VIEW • 20" ► 5" o NOTES: z AIRFLOW 0 16 v2" A 1.Allow a minimum 6"plenum inlet clearance 0lii for un-ducted installations. 2.Filter is secured in filter frame located in unit inlet. 32 tit" 3.For Motor access,remove bottom screws on hanger brackets to slide panel as shown in drawing. 1 A 4.See Installation Documents for exact hanger z bracket location. 22 g 5.Air valve centered between top&bottom panel. co O 6.Heating coil un-insulated. External insulation may be field supplied and installed as required. HEATER o 6., 7.All high&low voltage controls have same-side PANEL SLIDES NEC jumpback clearance. FOR MOTOR ACCESS 8.Allow 48"of straight duct downstream of AIRFLOW unit before first runout and inside of the duct should DISCHARGE OUTLET be equal discharge size. 9.Terminal box access door is side hinged.Allow for clearance. 10.A 4 wire power supply required for 480\3&575\3 40" a single point connection units. I 16" 171/2" Approximate 113.0 lb Q Dry Weight Weights reflected may vary 20" ±5.0 lb based upon options DISCHARGE VIEW selected. • FLD=Furnished by Trane U.S.Inc.I Installed by Equipment Submittal Page 8 of 11 Others Embassy Commons October 4,2019 Accessory-Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 Notes: 1.When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance. VPCF and VPEF maximum Minimum 1-row coil maximum -•-•-.-•-•-. 2-row coil maximum Pa In,wg Parallel Fan Size 03SQ—PSC 199 0.80 s. N ', 174 0.70 .\\ 150 0.60 • 132 " �\ H C \ w 125 0.50 Ear �, u E ✓ u r , N 100 0.40 \\ t1) • 75 0.30is s � � p 50 0.20 \, \ 25 0.10 200 300 400 500 600 700 800 900 1000 1100 1200 1300 Cfm 94 142 189 236 283 330 378 425 472 519 566 614 Us Airflow • FLD=Furnished by Trane U.S.Inc.I Installed by Equipment Submittal Page 9 of 11 Others Embassy Commons October 4,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 277 Volt,1 Phase L1 N 41_ .7 Heater Control Wiring /N WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH /\CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED Customer Notes: TO ACCEPT OTHER TYPES OF 1. Factory installed, CONDUCTORS. FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others. DAMAGE TO THE EQUIPMENT. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 11 Others Embassy Commons October 4,2019 Field Wiring -Variable Air Volume Fan Powered Terminal Units Item: Al Qty: 1 HEATER TERMINAL DAMPER BOX WIRING ACTUATOR FAN CONTROL (.....--.A.---...\ WIRING BOX WIRING 7 ��� r TB,-, TB2-6 T633 7133-1 181-2 182-5 TB3-2 2ND STO HEAT 0 0 0 0 0 0 0 11 10 7 6 3 2 1 ,- 10o- Z DIGITAL DISPLAY ZONE SENSOR JACK 1STSTG HEAT s S W/COMM.REMOTE MTD. O ® S. OPTIONAL FIELD INSTALLED L DIGITAL DISPLAY ZONE SENSOR j R-FAN BR r TB2-8 TB3-1 Y T1325 T83-2 iil. K 24VAC BL 1834 > O % I — - r,D� 000000 , _� 0 0; 0 0 2(+) 1(-)J3 2 1 — L m ACT �-`- PRESSURE W COMM.JACK RIP GND 24V TRANSDUCER REMOTE MID. ADDRESS D.D.C.\U.C.M. Q Q SWITCHJ3 CONTROL BOARD = R + OPTIONAL FIELD URIHddl = GX VOUT L INSTALLED ZONE SENSOR J 1 ^ I-Q 3 o , �y�y - 7+ W TEL GRN — — {1I�"!�� 00(71 I 24V E (TBi-1)24V C_�— —�— ���� 0 ❑ � � �T � L.J SENSOR GND (n33-6)0N0 ZONE GND SET MCO2 GNO W.( V 083-S)AA:02 OPTIONAL FIELD INSTALLED L CO2 SENSOR J z Z $ D.D.C.\U.C.M. r BL 1 CONTROL BOX OPTIONAL f FACTORY INSTALLED Y WBtELESS SHIELDED TWISTED PAIR OPTIONAL FACTORY INSTALLED rTB3s -1 r TB3-6 , WIRELESS I I Y I COMMUNICATIONS WIRING I 24VAC r� 1 R�1�-----281-1124VAC ' OC�.OM_MONL—_(ISO-LIRE Cii< ORSNC CONTACT1-(151.1124VAC BK.RETURNL—-ITB1-2I GND OPTIOILN- GND 245 Y -NOT CONNECTED L ADX TEMP SENSOR L i' i' W550 80013 J OPTIONAL FIELD INSTALLED L OCCUPANCY SENSOR J NOTE: 1. FACTORY WIRING FIELD WIRING — — — — OPTIONAL OR ALTERNATE WIRING ®WARNING 2. 1/4'QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS. HAZARDOUS VOLTAGE! ZONE SENSOR TERMINALS 1(-)AND 2(+)REQUIRE SHIELDED TWISTED PAIR WIRING FOR DISCONNECT ALL ELECTRIC POWER COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION. INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. 4.I NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE(ON/CANCEL). FAILURE TO DISCONNECT POWER Cl THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1(BIP)AND 24VAC(HOT)FROM BEFORE SERVICING CAN CAUSE TRANSFORMER. INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIATHE COMMUNICATIONS SEVERE PINJUTRY OR DEATH INTERFACE. i /�EAA�RSONAL\CAU t ION S.I AS SHIPPED,THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT.THE AUX INPUT CAN BE USE COPPER CONDUCTORS ONLYI RECONFIGURED AS ACO2 SENSOR INPUT VIATHE COMMUNICATIONS INTERFACE. UNIT TERMINALS ARE NOT DESIGNED S TERMINAL NOT TO BE USED WITH VARITRANE. TO ACCEPT OTHER TYPES OF CONDUCTORS. 8.I ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR FAILURE TO DO SO MAY CAUSE WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK. DAMAGE TO THE EQUIPMENT. FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 11 of 11 Others