Report Worldwide
www.tyco-fire.com
tyca Contacts
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The TYCO Series TY-FRB Sprinklers i ,
Description described herein must be installed A
and maintained in compliance with
The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the '
Upright (TY313) and Pendent (TY323) applicable standards of the National
Sprinklers described in this data sheet Fire Protection Association,in addition
are quick response,standard coverage, to the standards of any other authori
decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so
sprinklers designed for use in light or may impair the performance of these
ordinary hazard,commercial occupan- devices. ;:,
cies such as banks, hotels, and shop- =
ping malls. The owner is responsible for main- •-
taining their fire protection system
The recessed version of the Series and devices in proper operating con-
TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac-
applicable, is intended for use in areas tor or product manufacturer with any
with a finished ceiling. This recessed questions.
pendent sprinkler uses one of the1,., ":''''f*::::::'* ,,
,
following: Sprinkler
• A two-pEscutcheon
Stylehr15 Recessed Identification
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
Number
the flush pendent position. (SIN)
• A two-piece Style 20 Recessed TY313. . . . Upright 5.6K, 1/2 in. NPTA.,%11,-
Escutcheon with recessed adjust-
TY323. . . .Pendent 5.6K, 1/2 in. NPT .7-------w,:,'
ment up to 1/2 in. (12,7 mm) from
the flush pendent position. Technical
The adjustment provided by the Data Operation
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops The glass bulb contains a fluid which
to the sprinklers must be cut. Approvals expands when exposed to heat.When
Intermediate level versions of Series Refer to Table A the rated temperature is reached, the
TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently to shatter the
Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to
kler guards and shields are described 250 psi(17.2 bar)* activate and water to flow.
in Technical Data Sheet TFP78O. "The maximum working pressure of 250 psi(17.2 bar) Design
only applies to the listing by Underwriters Laborato-
ries,Inc.(UL).
Discharge Coefficient Criteria
IMPORTANT K=5.6 GPM/psi'/=(80,6 LPM/bar's) The TYCO Series TY FRB,5.6 K-factor,
Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323)
TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec-
regulatory and health information. tion systems designed in accordance
Always refer to Technical Data Finishes with the standard installation rules
Sheet TFP700 for the "INSTALLER Sprinkler:Refer to Table B recognized by the applicable Listing or
WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing
with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA
lation of sprinkler systems and com- Plated 13, and FM Approval is based on the
ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention
installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style
a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used
nents and cause the sprinkler to fail Sealing Assembly...Stainless Steel w/TEFLON for recessed pendent installations.
to operate in a fire situation or cause Bulb Glass
- it to operate prematurely, Compression Screw Bronze
Deflector Bronze
Page 1 of 4 AUGUST 2018 TFP172
TFP172
Page 2 of 4
Components: *Temperature rating is ** Pipe thread connections per ISO 7-1
1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request.
• 2 - Button 5 - Compression STYLE 15 or 20
3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED
- Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON
6* 7z!Z.. I
—� 7/16" 1 R
5 cl (11,1 mm) } ��1 c
4 I NOMINAL 2" II I,� 0
m MAKE-IN (50,8 mm) e
iiiiir
2 D' '�j 2" Ni 1:17
1-3/8" IJ
�1 (50,8 mm) (34,9 mm)
____
1 3 1 WRENCH
F FLATS
1/2" NPT** DEFLECTOR* r 2-7/8"(73,0 mm)DIA. -
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation Step 2. With pipe-thread sealant
L. applied to the pipe threads, hand-
RENCH RECESS
The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler
WUpright (TY313) and Pendent (TY323) fitting.
(USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the
END"A") dance with this section. sprinkler fitting using only the W-Type
^
�� General Instructions 6 Sprinkler Wrench(Figure 2).With ref-
FIGURE 2 Do not install any bulb-type sprin- erence to Figure 1,apply the W-Type 6
W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats.
SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 Ib ft (9,5 to
sprinkler held horizontally, a small air 19,0 N•m).
bubble should be present. The diam- Recessed Pendent Sprinklers
WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent
RECESS 1/16 in.(1,6 mm)for the 135°F(57°C)and Sprinklers must be installed in accor-
3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions.
q: temperature ratings. Step A. After installing the Style 15
A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the
should be obtained by applying a sprinkler threads,and with pipe-thread
minimum to maximum torque of 7 to sealant applied to the pipe threads,
., 14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the
ii..., of torque can distort the sprinkler Inlet sprinkler fitting.
with consequent leakage or impairment
PUSH WRENCH of the sprinkler. Step B. Tighten the sprinkler into the
IN TO ENSURE sprinkler fitting using only the W-Type
ENGAGEMENT Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure
WITH SPRINKLER insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the
WRENCHING AREA eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench
the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque
FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m).
' W-TYPE 7 RECESSED
SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and
The Series TY-FRB Upright and finishing, slide on the Style 15 or Style
Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB
in accordance with the following Sprinkler and push the Closure over the
instructions. Mounting Plate until its flange comes in
Step 1.Install Pendent sprinklers in the contact with the ceiling.
pendent position. Install upright sprin-
klers in the upright position.
TFP172
Page 3 of 4
- Care and 2-7/8" DIA. -
(73,0 mm)
Maintenance 2-1/4" DIA.
• The TYCO Series TY-FRB,5.6 K-factor, FACE OF ~ (57,2 mm) —
Upright (TY313) and Pendent (TY323) SPRINKLER
Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm)
viced in accordance with this section. + 1 — ' FLUSH
Before closing a fire protection system 3/8±5/16"
main control valve for maintenance (9,5±7,9 mm) % Al al '� i t
work on the fire protection system } /
that it controls, obtain permission to /8i
shut down the affected fire protection MOUNTING '
systems from the proper authorities SURFACE (3,2mm)
and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
affected by this action.
TY-FRB PLATE 3/4"(19,1 mm)
Absence of the outer piece of an
escutcheon, which is used to cover FIGURE 4
a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only - 2-7/8" DIA. _
cleaned by means of gently dusting (73,0 mm)
with a feather duster; otherwise, non- FACE OF
operation in the event of a fire or inad- SPRINKLER r 2-1/4" DIA. _
vertent operation may result. FITTING (57,2 mm)
Sprinklers which are found to be 5/16±1/4"
leaking or exhibiting visible signs of (7,9±6,4 mm) 1/2"(12,7 mm)
- corrosion must be replaced.
Automatic sprinklers must never be _ ..-taL —� �I
- painted, plated, coated, or other-
wise altered after leaving the factory. } ��� i 1
Modified sprinklers must be replaced. MOUNTING 1/8
Sprinklers that have been exposed to SURFACE (3,2 mm)
corrosive products of combustion, but
have not operated,should be replaced I
if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm)
by brushing it with a soft bristle brush. FIGURE 5
Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323)
damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
during, and after installation. Sprin- RECESSED ESCUTCHEON
klers damaged by dropping, striking,
wrench twist/slippage,or the like,must Recessed Escutcheon
be replaced. Also, replace any sprin- Limited Specify: Style 15 Recessed Escutch-
kler that has a cracked bulb or that has warrant eon with(specify')finish,P/N(specify')
lost liquid from its bulb. (Ref. Installa- Y Specify: Style 20 Recessed Escutch-
tion Section.) For warranty terms and conditions,visit eon with(specify*)finish, P/N(specify`)
The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770
inspection,testing,and maintenance of
their fire protection system and devicesSprinkler Wrench
in compliance with this document, as Ordering Specify: W-Type 6 Sprinkler Wrench,
_ well as with the applicable standards Procedure P/N 56-000-6-387
of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench,
ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001
the standards of any other authorities ability.When placing an order, indicate
having jurisdiction.Contact the install- the full product name and Part Number
ing contractor or product manufacturer (p/N).
with any questions.
Sprinkler Assemblies with NPT
Automatic sprinkler systems are rec- Thread Connections
ommended to be inspected, tested, Specify: Series TY-FRB Upright or
and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN
tion Service in accordance with local (specify), K=5.6, Quick Response,
requirements and/or national codes. (specify) temperature rating, (specify)
finish, P/N (specify,refer to Table A).
TFP172
Page 4 of 4
SPRINKLER FINISH(See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERC
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
UPRIGHT 155°F(68°C) Red
(TY313)
and 175°F(79°C) Yellow 1,2,3,4,5,6
• PENDENT•
• (TY323) 200°F(93°C) Green
5.6 286°F(141°C) Blue
1/2 in.NPT
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 1,2,3,4
(TY323) 175°F(79°C) Yellow
Figures 4a and 5b
200°F(93°C) Green
Notes:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 — XXX — X — XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C)
371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C)
POLYESTER
Notes: SIGNAL WHITE(RAL9003) 79°C
a. Use suffix"I"for ISO 7-1 connection;for example, 4 175 175°F POLYESTER ( )
77-370-4-175-I
5 JET BLACK(RAL9005) 200 200°F(93°C)
POLYESTER
9 CHROME PLATED 286 286°F(141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway,Lansdale,PA 19446(Telephone+1-215-362-0700
0 2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association', Controls
TEFLON is a registered trademark of DuPont
Eddythread 40
A Lightweight Schedule 40 Replacement Pipe
That Has a Corrosion Resistance Ratio of 1.0
Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe
products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our
customers have an option to buy a carefully designed replacement for Schedule 40 that:
• Has a Corrosion Resistance Ratio of 1.0
• Has a Pressure Rating of 300 psi
• Is Lighter Weight Than Schedule 40
• Is Approved by Factory Mutual and Listed by Underwriters Laboratories
• Is Produced in Accordance to ASTM A-135 and A-795
• Can be Used With Standard Schedule 40 Threaded Fittings,
Couplings and Valves
• Is Produced From Steel With Excellent Properties of
Strength and Threadability
• Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems*
• Offers Lower Freight Costs
EDDYTHREAD 40 SPECIFICATIONS
1 1.461 1.083 70
1 1/4 2.070 1.418 51
1 1/2 2.547 1.654 44
2 3.308 2.123 30
CORROSION RESISTANCE RATIOS
1 1.00 1.00
1 1/4 1.00 1.00
1 1/2 1.00 1.00
2 1.00 1.00
Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems
�• 1819 Clarkson Road For additional information, C U� us
( v�rSU /) Chesterfield,MO 63017 contact your salesperson today at
J 8 BULL MOOSE TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED
(�
V FAX:(636)537-2645 in the USA,or from Canada 441›..
www.bullmoosetube.com call(800)882-4666
A L fl O company e-mail:sales(&,,bullmoosetube.com
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.
8/08
Cin
0 „,,,,,,,,,,,i,*,,*,,„ . „,4.A.0. 4,4,,.„,„,,„'pp',++;`,„,..' . ,
0 P.114
q ,
p w t.n
r }} s , N4.*YaY �.
r tt n •,,,�'Mi'*w Y '�i s N}t x$�y#"" �
,* 1'0,,I,'4',,, ,"':''.,',.1 r',,,f. j7,,,,,,,''' ,r, ,,thi.',,e, ,, ' ,,' 3' /1;101 , "r1‘.,''4'''* '1,i‘4,,A
t� � {L ,Y 7 ' q j "'� 4
PI::: , ,' ; * 4 r , , it,."1,,4'.4.,, ‘,
t ya
rIJ
V
CyyUI
r F;. �dya i iw ar; „. yy”fro a.
,..:
EN-4 $ ,.„,,. 4,,„
�,&� { CF :�', 666 1 i' a'7NM"'
.,,,,
,:::..'
rR Y N
Nr y fi 'ffi ;,.1..,..!,,,,,,„ t�ti;Y
„ ,
µ ah M �` *', k '1 �,,= i' ',,..1„:%,,g.,, , , ,,;,,,,„e ,,„;...*, , , " 1"I a a :
Pffilisi
f � t „ r4tt$ 4f
v > Y rn 1,
%
'Timmi
— d
C
" MI TH „co
ezEt- ' I INTERN E R N -T. O N A L
�1
Ductile Iron Threaded Fittings
Specifications
• 4, branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi
• Rated to 300 WSP
• Ductile iron castings conform to ASTM A536 C US
LISTED
• Fitting dimensions conform to ASME B16.3
• Bushings and plugs conform to ASME B16.14 4111>*
• Fittings are 100% air tested APPROVED
• NPT threads on all fittings conform to ASME B1.20.1
• Independent lab verification that fittings meet applicable chemical &physical properties
• Manufacturing facilities are ISO 9001:2008 and ISO 14001
Temperature Working Pressure, Nonshock psiG
Degrees F 300# Class Threaded Fittings
-20 to 100 500
150 " 500
200 480
+j 250 460
300 440
350 T 420
400 400
450
VI 711,-TM- 380
500 360
; 550 340
600 320
650 ;, = 300
-2- Ductile Iron Fittings- Class 300 UL/FM
..
• c ® us
APPROVED
Fig. 35E 3-90°Elbow LISTED
A Size A Packing Weight
in Part Number in inner Master lb
+� 02 35F 3004 1.13 100 200 0.2
3/4 35E 3006 1.31 70 140 0.3
A 1 35E 3010 1,50 40 80 0.5
SE* 1-1/4 351_3012 ? .1.75 25 50 0.8
rill 1-112 351_3014 1.94 18 36 11
2 35E 3020 '2.25 10 20 1.8
2-1/2 3513024 2.70 4 8 32
Fig. 35RE3-90°Reducing Elbow
B Size A B PackingWeight
< > in Part Number in in Inner Mster lb
le it1 :A
3/4x 12 35RE3006004 1.20 122 80 160 03
1 x 1/2 358E3010004 1.26 1.36 70 140 0.4
x3/4 3oRE3010006 1.38 1.45 50 100 04
1-1/4 x 1/2 358E3012004 1.34 1.53 35 70 0.5
1-1/4 x 3/4 3501_3012006 1.45 1.63 35 70 0.6
1-1/4 x 1 35813012010 ,! 1.58 1.67 30 60 0.7
1-1/2 x 1/2 350E3014004 1.52 1.75 30 60 0.6
1-1/2 x 3/4 358E3014006 �'`1.52 1.75 25 50 0.7
1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8
1-1/2x 1-1/4 358E3014012 1, 1.82 1.88 18 36 1.0
' 2 x 1/2 350E3070004 1.60 1.97 18 36 1.0
2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0
2 x 1 350E3020010 1.73 2.02 16 32 1.2
2 x 1-1/4 358E3020012 Ai 1.90 2.10 12 24 1.3
,I 2x1-1/2 350E3020014 2.02 2.16 10 20 1.5
21/2x1-1/2 35RE3024014 r 2.116 2.51 6 12 2.2
}, 2-1/2 x 2 35013024020 2.39 260 6 12 2.5
Fig. 35F 3-45°Elbow
Size Part Number A Packing Weight
in in Inner Master lb
. \. 1/2 35F 3004 0.88 150 300 0.2
i�� 3/4 3513006 0.98 80 160 0.3
lik4 1 351 3010 1.13 40 80 0.5
1 1/4 35F3012 � ;. 1.29' 25 50 0,7
1-1/2 351 3014 1.44 20 40 1.0
bill IA 2 35F 3020 --� 1.69 10 20 1.6
2-1/2 35F 3074 1.95 4 8 2.7
Fig. 35T 3- Tee
Size A Packing Weight
• Part Number
in in Inner Master lb
� 2 3513004 1.13 80 160 0 3
A
3I4 35T 3006 �1. 1.31 30 60 0.511,
III ill
1 351 3010 1 50 25 50 0 7
1-1/4 35T3012 z' 1,75 10 , 20 1.1.
A a e A ) ?_ 35 3014 94 01. 20 1 5
2 35T 3020 {' 2.25 6 =12 2.4 <<
2-1/2 35T 3024 2.70 4 8 4.3
111 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com
' `' Ductile Iron Fittings- Class 300 UL/FM
cCO us
APPROVED
Fig. 35RT3-Reducing Tee LISTED
111111 , ,
Size Part Number A B C Packing Weight
in in in in Inner Master lb
3 _t C, ,
3/4 x 1/2 35613006004 1.20 20 1,22 60 120 0 4
1 x 1/2 35813010004 1.26 1.26 1.36 30 60 0.6
1 x 1/2 x 1 350(3010004010 50 1.36 1.50 30 60 0.6
1 x 314 350 13010006 1.38 1.38 1.45 25 50 0.6
1( -j 1 x 3/4 x 3/4 35073010006006 1.38 1.31 1.45 35 70 0.6
B A 1 x 3/4 x 1 35R13010006010 1.50 1.45 1.50 25 50 0.7
1-1/4 x 1/2 350(3012004 1.34 1,34 1,53 20 40 0.8
1-1/4 x 1/2 x 1-1/4 35813012004012 1.75 1.53 1.75 25 50 0.9
1-1/4 x 3/4 35613012006 1.45 1.45 1.62 15 30 0.9
1-1/4 x 3/4 x 1-1/4 35813012006012 1.75 1.62 1.75 20 40 1.0
1-114 x 1 35613012010 1.58 1.58 1.67 15 30 1.0
1-1/4 x 1 x 1/2 35813012010004 1.34 1.26 1.53 25 50 0.7
1-1/4 x 1 x 3/4 35073012010006 1.45 1,38 1.63 20 40 0.8
1-1/4 x 1 x 1 35813012010010 1.58 1.50 1.69 20 40 0.9
1-1/4 x 1 x 1-1/4 35013012010012 1.75 1.69 1.75 15 30 1.0
1-1/2x1/2 35813014004 1.41 1.41 1.66 16 32 1.0
1-1/2 x 1/2 x 1-1/4 35813014004012 1.81 1.56 1.88 24 48 1.1
1-1/2 x 1/2 x 1-1/2 3501-3014004014 1.94 1.66 1.94 12 24 1.2
1-1/2 x 3/4 35813014006 1.52 1.52 1.75 16 32 1.1
1-1/2 x 3/4 x 1-1/4 35813014006012 1.94 1.66 1.88 20 40 1.1
1-1/2 x 3/4 x 1-1/2 35813014006014 1.94 1.75 1.94 18 36 1.2
1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2
1-1/2 x 1 x 1/2 35013014010004 1.44 1.25 1.69 20 40 0.8
1-1/2 x 1 x 3/4 35R-13014010006 1.50 1.44 1.75 16 32 0.9
1-1/2 x 1 x 1 35813014010010 1.65 1.50 1.80 16 32 1.0
1-1/2 x 1 x 1-1/4 35813014010012 1.82 1.67 1.88 12 24 1.2
1-1/2 x 1 x 1-1/2 35873014010014 1.94 1.80 1.94 12 24 1.3
1-1/2 x 1-1/4 35813014012 1.82 1.82 1.88 12 24 1.4 I
1 1/2 x 1-1/4 x 1/2 35813014012004 1.41 1.34 1.66 16 32 0.9
1-1/2 x 1-1/4 x 3/4 35013014012006 1.52 1.45 1.75 16 32 1.0
1-1/2 x 1-1/4 x 1 35813014012010 1.65 1-58 1.80 16 32 1.1
1-1/2 x 1-1/4 x 1-1/4 35813014012012 1.82 1.75 1.88 14 28 1.3
11/2x 1-114 x 1-1/2 35013014012014 1.94 1.88 1,94 14 2.8 1.4
2 x 1/2 35813020004 1.49 1.49 1.88 10 20 1.5
2 x 3/4 35813020006 1.60 1.60 1.97 10 20 1.6
2 x 1 35813020010 1.73 1.73 2.02 8 16 1.7
2 x 1 x 2 35013020010020 2.25 2.02 225 8 16 1.9
2 x 1-1/4 35813020012 1.90 1.90 2.10 8 16 1.9
2 x 1-1/4 x 2 35813020012020 2.25 2.10 2.25 8 16 2.0
2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1
2 x 1 1/2 x 1/2 35813020014004 1.49 1.41 1 88 10 20 1.3
2 x 1-1/2 x 3/4 35813020014006 1.60 1.52 1.97 10 20 1.4
2 x 1 1/2 x 1 35813020014010 1.73 1.65 2.02 8 16 i.5
2 x 1-1/2 x 1-1/4 35013020014012 1.90 1.82 2.10 8 16 1.7
2x 1-1/2x 1 1/2 35813020014014 2.02 1.94 2.16 8 16 1.8
Fig. 35BT3-Bull Head Tee
Size A B C Packing Weight
�■■; inPart Number in in in Inner Master lb
�C 3/<1 x 1 35873006010 1.45 1 45 1.37 30 60 0.6
• *Mk 1 x 1-1/4 35B13010012 1.67 1.67 1,58 20 40 0.9
1 x 1-1/2 35813010014 1.80 1.80 1.65 15 30 1.0
A I( B > 1-1/4 x 1 x 1-1/2 35B13012010014 1.88 1.80 1.82 15 30 1.2
1-1/4 x 1-1/2 35813012014 1.88 1.88 1.82 15 30 1.3
1-1/4 x 2 35813012020 2.10 2,10 1.90 10 20 1.6
1-1/2 x 1-1/4 x 2 35813014012020 2.16 2.10 2.02 10 20 1.8
1-1/2 x 2 351313014020 2.16 2.16 2.02 8 16 1.8
S\IITII-COOPER INTERNAFIONAL® • "COLE FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcoopet.com 112
Ductile Iron Fittings- Class 300 UL/FM
c (21us ®"
APPROVED
A
Fig. 35CP3 -Straight Coupling with Ribs
LISTED
Size 0 Part Number A Packing Weight
IIIin in Inner Master lb
1/._ 35CP3004 38 200 400 0.1
3/4 35CP3006 1.63 100 200 0.2
1 35CP3010 1.75 60 120 0.4
1-1/4 35CP3012 2.00 35 70 0.5
1-1/2 35CP3014 2.19 25 50 0.7
2 35CP3020 2.62 15 30 1.2
2-1/2 35CP3024 3.00 9 18 2.2
Fig. 35RC3 -Hex Reducing Coupling
" Size A Packing Weight
Part Number
in in Inner Master lb
1 x 1/2 35003010004 1.69 80 160 0.3
Algai A 1 x 3/4 35RC3010006 1.69 60 120 0.4
4.t." x. 1 1-1/4 x 3/4 35003012006 2.06 40 80 0.6
>. '* 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0
Fig. 35HB3 -Hex Bushing
Size Part Number A Packing Weight
_ in in Inner Master lb
B
--,, . " '` t 1 x 1/2 35H93010004 1.06 180 360 0 2
1 x 3/4 35HB3010006 1.06 180 360 y 0.1 0441),
1 1 r...A
1-1/4 x 1 35HB3012010 1.19 90 180 0.2
i 1 1-1/2 x 1 35H83014010 1.25 75 150 4, 0.4 '
1-1/2 x 1-1/4 35HB3014017 1.25 75 150 0.3
2x 1 35HB3020010 1.38 40 80 ,:0.6 -
xti 2 x 1-1/4 351B3020012 138 40 80 0.6
2 x 1.1/2 35HB3020014 1.38 40 80 ;ta0.6_.; .w
Fig. 35SP3 -Square Head Plug
Size Part Number A Packing Weight
in in Inner Master lb
1/2 35SP3004 0.94 600 1200 0 07
IA
3/4 35SP3006 1.12 350 700 0.1`,
_ 1 Jill 1 • ..
1 1
35SP3010 17.5 200 400 01
1-1/4 35S93012 1.37 100 200 0.34,`
1-1/2 35S03014 1.44 80 160 0.4
2 35SP3020 1.50 45 90 0.6
Fig. 35U 3- Union with Brass Seat
A Size A Packing Weight
Part Number
in in Inner Master lb
1111
1 35U 30102.192040 G
1-1/4 35U 30122.50 15 30 1.2 2 35U 3014 2.62 10 20 1.7
6521164704258 2 35U 3020 3.12 6 12 2.4
ilwar
113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com
Ductile Iron Fittings - Class 300 UL/FM
414 >
C ® US
APPROVED
Fig. 35X 3-Cross LISTED
I A ' A Size A Packing Weight
Part Number
111
i-2-111/2
n in Inner Master lb
0
1 1.50 20 40 .9
1 IA 1 357 3010 1-1/4 35X 3012 1.75 12 24 1.4
wlIA
1-1%2 35X 3014 1.94 8 16 1.8
2 35X 3020 2.25 6 12 2.8
B B Fig. 35RX3-Reducing Cross
(---'` ' Size A B Packing Weight
gimp. Part Number
1IA in in in Inner Master lb
I 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2
- --- 111 � -- 1-1/2x1 35RX3014010 1.86 1.65 12 - 24; 1,4
1 A 2 x 1 35073020010 2.02 1.73 8 16 2.0
ii i
Fig. 35C 3- Cap
• . Size Part Number A Packing Weight
® in in Inner Master lb
A 2 35C 3004 0 87 300 600 0 1
1 I 1 3/4 350 3006 0.97 200 400 0.1 g;
1
35C 3010 1.16 110 220 0.2_ vI
1-114 35C 3012 `,1.28` 70 140 ' �4,4.
1-1/2 3503014 1.33 50 100 0.5
2 35C 3020 t'1.45 , 25 50 ..
2-1/2 35C 3024 1.70 18 36 1.6
Fig. 35BC3-Beam Clamp
Size A Packing Weight
111 Part Number
AI in in Inner Master lb
■ 3/8 33803003 0.75 100 200 0.3
781 ■i 1/2 35B03004 0.75 80 160 0.5
ii
am
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114
c �L us FM wds LPCB
FireLock® Outlet-7rUSTEo 491x/27
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
' STYLE 922
The Style 922 Outlet-T provides a convenient method of incorporating/,3/4,and 1715,20 555
and 25 mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and
other outlet products.Available for 1'A through 76.1 mm/32 to 76.1 mm piping systems,Style
922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS
Approved for direct sprinkler connection only on wet and dry systems.
The locating collar engages into the hole prepared in the pipe.When tightened,the assembly
compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up
to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire
protection systems.
Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.*
Contact Victaulic for other optional coatings.
*Consult Section 10.01 for specific listings/approvals.
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to
ASTM A-395,grade 65-45-15,is available upon special request.
Gasket:
• Grade"E"EPDM-Type A
(Violet color code).FireLock products have been Listed by Underwriters Laboratories Inc.and
Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the
rated working pressure using the Grade"E"Type A Gasket System.
Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
Housing Coating:
• Orange enamel(North America, Latin America,Asia Pacific)
• Red enamel(Europe)
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
uctaulic
VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.B 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. -
REV_G 10.52.1
IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52
STYLE 922
DIMENSIONS Nominal Size Hole Approx.
inches/mm Diameter Dimensions-inches/millimeters Weight Each
Y .-Z-1
1'/0 '1 13/16 1.30 1.83 1.10 3.87 2.56 1.0
V ��� r r 1 32 X 15 30.2 33.0 46.5 279 98.3 65.0 0.45
: �■ T 320 1 3/16 1.28 1.83 1.10 3.87 2.56 1.1
P III 3/4
30.2 32.5 46.5 27.9 98.3 65 0 0.50.
•j 1
Fl.
��6/ iI�i 1 1 3/16 1.52 2.18 1.10 3.87 2.56 1.2
1 ii 25 30 2 38.6 55.4 27.9 98.3 65.0 0 54
11/21 13/16 1.42 1.95 1.22 4.08 2.56 1.2
40 X 15 30.2 36.1 495 31.0 103.6 65.0 0.54
3/4 .-.13/16 1.40 1.95 1.22 _._ 4.08 2.56 1.2
20 30.2 35.6 49.5 31.0 103.6 65.0 0.54
1 I 13/16 1.64 2.30 1.22. 4.08 2.56 1.3
25 I 30.2 41.7 58.4 31.0 103.6 65.0 0.59
2 Yz 13/16 1.66 2.19 1.46 4.60 2.56 1.3
50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59
3A 1 3/16 1.64 2.19 1.46 4.60 2.56 1.4
20 30.2 41.7 55.6 37.1 116.8 65.0 0.64
1 13/16 1.88 2.54 1.46 4.60 2.56 . 1.5
25 30.2 47.8 645 37.1 116.8 65.0 0.68
2'1 1 13/16 1.91 2.44 1.71 5.40 2.56 1.6
65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73
34 13/16 1.89 2.44 1,71 5.40 2.56 1.6
20 30.2 48 0 62.0 43.4 137.2 65.0 0.73
1 13/16 2.13 2.79 1.71 5.40 2.56 1.6
25 30.2 54.1 70.9 43.4 137.2 65.0 0.73
76.1 mm X 'h 1 3/16 1.91 2.44 1.71 5.50 2.56 1.6
,. 15 I 30.2 48.5 62.0 43.4 139.7 65.0 0.73
3/n i 13/16 1.89 2.44 1.71 5.50 . 2.56 1.6
- 20 i 30.2 48.0 62.0 43.4 139.7 65.0 0.73
1 7 13/16 2.13 2.79 1.71 5.50 2.56 1.7
25 1 30.2 54.1 70.9 43.4 139.7 65.0 0.80
t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional)
male pipe threads only.Use of male threaded products with special features,such as probes,dry pen-
dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify
suitability in advance may result in assembly problems or leakage.
*Center of run to engaged pipe end for NPT threads(dimensions are approximate).
i.
www.victaulic.com
VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.C 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �Ct�UI1C"
10.52_2 REV_G
IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52
FireLock° Outlet-1"
" STYLE 922
PERFORMANCE
Equivalent Length of 1 inch
Schedule 40 Steel Pipe(per UL
Run Size x Outlet Size 213,Section 16)(C=120)*,FT
;-';i:.E,EigL''-EL*****ii;EILE!,E:LVELAYILEEEEE-ZEVt*KAVOLLB1YLL
11/4 8.5
32 X 25 . 2.6
11/2
X
40 25 2.6
2 x 1 8.5
50 25 2.6
65 x 25 2.6
76.1 mm X 25
82:6
*Hazen-Williams coefficient of friction is 120
www.victaulic.com jctaulie
VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
REV G 10,52_3
STYLE 922
•
INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data,and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the
right to change product specifications,designs and standard equipment without notice and without
incurring obligations.
For complete contact information,visit www.victaulic.com
10.52 3355 REV G UPDATED 12/2009 ICtauIIC'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
10,52
Pipe Hangers
Fig.200- "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) "
Fig.200F- "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF)
Fig.200C- "Trimline"" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED
iFig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut
Size Range:
Fig. 200 - 1/2" (15mm)thru 8" (200mm) pipe
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurled -- J
swivel nut design permits hanger adjustment after installation. �!
4tl
Features:
- • 11/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe
types and protect CPVC plastic pipe from abrasion. Captured design ;
keeps adjusting nut from separating with hanger. Hanger is easily �0 ; �', B i' ��.
installed around pipe. A �'
For hanger with non captured nut order Fig. 200S. ;i
• 121/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it securely in _= '
hanger before installation.Adjusting nut is easily removed.
Approvals: Underwriters Laboratories listed 11/2" (15mm)thru 8" (200mm)) ! Fig.200-1/2.200-3/4
in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and
Fig.200-1 to 200-2 Fig.200-21/2 to 200-8
Factory Mutual Engineering Approved(FM) (3/4" (20mm)thru 8" (200mm)).
Conforms to Federal Specifications WW-H-171 E &A-A-1 192A,Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69 &SP-58,
Type 10.
,..
Maximum Temperature: 650°F 1343°CI
Finish: Pre-Galvanized. Stainless Steel
materials will be supplied with (2) hex nuts
in place of a knurl nut. 1` AP .44 :.': _fir
Order By: Figure number andpipe size
9
r
Designed to meet or exceed requirements of .
FM DS 2-0. ��
Fig.200
Fig.200C Fig.200E
Pipe Size Rod Size A B Approx.Wt./100
Part No. in. (mm) in. (mm) in. 1mm) lbs. (kg)
200-1/2 1/2" (15) 3/8'-16 ; 31/8" (79.4) 25/8" (66.7) 11 15.0) ' '
200-3/4 3/4" (20) 3/8"-16 31/8" 179.4) 21/2" (63.5) 11 (5.0)
200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 (5.51
200-11/4 11/4" 132) 3/8"-16 33/4" (94.01 27/8" (73.0) 13 (5.9)
200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8" (73.0) 14 (6.4)
200-2 2" (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9)
200-21/2 21/2" (65) 3/8"-16 55/8 (142.9) 41/8" (104.7) 27 (12.3)
200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.31 Fig.200S
200-31/2 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 '(15.6)
200-4 4" (100) 3/8"-16 73/8" (187.3) 5" (127.0) 35 (16.0)
200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2)
200-6 6" (1501 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.41
200-8 8"; (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 ; (62.3)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line
Fire Protection Solutions
21 by k ,
Threaded Accessories
B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig.103)
B3205L - Threaded Rod (right& left hand threads) TL ll��
Size Range: 3/8"-16 thru 3"-4 rod Specify Length l�lll1111�
Material: Steel .--\- 10.
Function: Recommended for use as a hanger support in hanger assemblies. TL
Rod is threaded on both ends with right hand threads of the length shown.Also
available with left and right hand threads-specify Fig. B3205L when ordering. iliVll A Thread Size
Maximum Temperature: 750°F(399°C)
Finish: Plain. Contact B-Line for alternative finishes and materials.
Order By: Part number, rod size, length and finish
Standard Design Load
Thread Size Thread Length IL 650°F(343°C) 750°F(399°C)
Part No. A in. (mm) Lbs. (kN) Lbs. (kN)
83205-3/8x'1' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54)
B3205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70)
B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52)
B3205-314 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25)
B3205-7l8X'1.' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60)
B3205-1 x`L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55)
83205-1118x'L' 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93)
B3205-11/4 x11.1 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09)
B3205-11/2 X'L' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07)
B3205-13I4 x'L' 11/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79)`
B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29)
k
B3205-21/4 x'L' 21/4"-41/2 9" (228:6)'` 32300 (143.67) 25295 (112.51)
B3205-21/2 x11.' 272"-4 10" (254.0) 39800 (177.03) 31169 (138.64)
133205-23/4 x1L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08)
B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35)
ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100)
Fig. 99 - All Threaded Rod Cut To Length
Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length v 01)
���l�j��l���
Material: Steel 'fid` "�`
Maximum Temperature: 750°F(399°C) R o
„
Finish: Plain.Contact B-Line for alternative finishes and materials. s 0
Order By: Part number, rod diameter and finish ! a
Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft.
ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg)
ATR'1/4"x 120f- 99-1/4'x length: 20 240 (1.07) 12 (5.44)
ATR 310 X 120 `9.3/e"X length- 16 730 (3.24) 29 (13,15)
ATR 1/2"x 120 99-'/2"x length 13 1350 (6.00) 53 (24.04)
AIR x 120 /8"x length 11 2160 (9.60) 89' (40.37)
- ,. ATR 3/4"x 120 99-110 x length`' 10 3230 (14.37) 123 (55.79)
' Mr x 120 ; x_99-1/&"x length 9 4480 (19.93) 170 (77.11)
ATR 1'x 120 99-'' x length.,; 8 5900 (26.24) 225 (102.06)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
B
e
Pipe Hangers&Supports 236 Revised 4/28/2014 -L
11N
by A.
VERTICAL MOUNT SAMMYS '
SAMMYS° for Wood --, _ .-, v_ r _ 1 _ :4--r _ ., 1. _ _ .. _
Not less than ,_:
Wood Flooring
2'nominal width Product Fed{„,.
,: 3 (1-1/2") a"= ..�.».ate;- - -
�� •No pre-drilling required.
it
-- F `- Not less than i •Quick to install using the Sammy
�� 3"nominal
I
thickness(2-1/7') ;y r') Nut Driver with an 18V cordless
-' `' (depth or side Wood Joist < drill/driver.
of vertical member) --
I •Saves time from traditional
a Double Sheetrock methods.
ceiling
nsta(tkr •Reduces installation cost.
Minimum 2"embedment into base
material for NFPA13compliance. . Composite/Truss - •Made in the U.S.A.
Consult truss manufacfurer for
recommended installation paint.
- - *Pre-drilling maybe required for GST
25.360.Tool available on page 10.
r"`x
Igt I
''
VRod Part Screw Ultimate UL Test FM Test Box Cason
Approvals Model
Size Number Descriptions Pullout(lbs) Load(lbs) Load(lbs) Qty City
1/4" 8002957 GST 100 1/4 x 1" a't°, ' c5
6714 t;
1/4" 8003957 GST 200 1/4 x 2" 1760(Fir) 25 125
liar 1/4" 8004957 GST 300 1/4 x 3" 2060(Fir) b•, ` Cr itc.45 *-4 1 f ,;_
3/8 8006957 GST.75 1/4 x 3/4" 564 (3/4"Ply) 25 125
� ' 210(7/1 t4
3/8' 8007957 GST 10 1/4 x 1" ' s '4
670(3/4 :
'� 3/8" 8008957 GST 20 1/4 x 2" 1760 (Fir) 850 1475 25 125
Q. 3/8" 8068925 GST20-SS 1/4xF 1760(Fir) , .-!q w K>n
Q., 3/8" 8009925 GST 25-380 3/8 x 2-1/2" 2113 (Fir) 1500 25 125
°° 3/8" 8010957 GST 30 1/4 x 3" 2060(Fir) - :; 14
Nut DBlackriver
3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 Part#8113910
P
3/8" 8011925 Gf+ ; a 1/4 x 4 ;z` 2180(Fir) . 1 a,` .
3/8" 8012925 GST 60 1/4 x 6 2230 (Fir) 25 125 _
k 1/2" 8013925 ,'- 1/4 x 2° ° 1760(Fir) +- ¶'—
`" ' - 1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125
. , -. . ¢.,
' 015925 GST 3 1/4 x 3" 2275(Fir) Y g , $ —
w
1/2" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125
`ZW ` . o's 7 u 1/4x6" 2230(Fir) #14 SW Red
Nut Driver
Part#8114910
F SAMMY Swivel Head° for Wood
' Product Features
•Eliminates distortion of threaded rod. •Saves time from traditional methods.
•Accommodates up to 3'/i"x 12 pitch roof. •Reduces installation cost.
•Allows 17°deflection from vertical. •Made in the U.S.A.
IIIIIIIIApprovals Rod Part Model Screw Ultimate UL Test FM Test Min Box Case
Size Number Descriptions Pullout(lbs) Load(lbs) Load(lbs) Thickness Qty Qty
6 ° ' 3/8° 8139957 SH-GST 20 1/4x2" 1257(Fir) 1050 1475 25 125 125 a
0.•Q 3/8" 8141957 SH-GST 30 1/4 x 3" 1720(Fir) 1500 1475 25 125
#14 Black
Nut Driver
SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into part#8113910
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.