Loading...
Report (2) 9000 9/1) 1A/Nsh inj fon .Sci MfC2019 •0072,1 4111 -TAME" Weights RECEIVED OCT 9 2019 v‘cen COP:4 CITY OF TIGARD Of BUILDING DIVISION Table 87-1 Accessory Net Weights (Lbs)2,3 Oversize Hard' LPG All Highs Low' Economizer Outside Air Damper Unit Roof' Motor Start Conversion Zone Power' Static Static Model No, Net Motorized Manual Curb Adder Kit Kit Sensors Exhaust Drive Drive YC D036,048,060C 40 N/A 32 80 5 5 5 1 N/A N/A Y,C D037,049C re— OT5C,090C/D 1 - 40 35 32 82 5 N/A 5 1 ! 65 2 i C D061,074,086C,091 D,F0-21120k; ! , — Y C D1208,150C 40 35 32 165 5 N/A 5 1 75 2 — YCD103 YC D180B,210C 65 60 32 205 5 N/A 5 1 95 2 10 YCD121,151C YC D240B YCD181,211,241C 80 75 32 235 5 N/A 5 1 95 2 — YC D30013,301C 80 75 32 235 N/A 5 1 95 — 10 Y C 1048,060 40 N/A 32 N/A 5 5 5 1 N/A N/A — YCH049C Y C H075C,090C/D YC H061,074,086C,091D,102,120C40 35 32 N/A 5 N/A 5 1 N/A 2 — Y C H1208,150C 35 35 32 N/A 5 N/A 5 1 N/A 2 — YC H103, Y C H1808,210C 50 60 32 N/A 5 N/A 5 1 N/A 2 — YCH121,151C Y C H240B YCH181,211,241C 65 75 32 N/A 5 N/A 5 1 N/A 2 Y C H 300B,301C 65 75 32 N/A N/A 5 1 N/A — 10 NOTES: 1. Used on 1 phase only. 2. Net weight should be added to unit weight when ordering factory installed accessories. 3. Y C*102-300 factory installed options for economizers,multiply net capacity x.99,EER 0.97. For oversize motors,multiply net capacity n98,EER x.93.This is provided in compliance with A RI certification program. 4. Downflow only. 5. Not available on all models(See fan performance tables for specific models). 87 Weights Table 88-1 Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.) Unit Maximum Weights(Lbs)7 Corner Weights(Lbs)1 Center of Gravity(In.) Tons Model No. Shipping Net A B C D Length Width 3 YC D036C/YC D037C 782/811 621/651 209/217 158/159 116/124 138/151 37/36 19/20 4 YC*048C,/YC*049C 811/845 639/672 216/221 159/168 123/131 142/153 37/37 19/20 5 YC*060C,/YC*061C 831/901 659/713 219/230 163/176 126/137 152/170 36/38 20/21 61/4 YC*075C/YC*074C 938/956 750/767 238/240 192/199 144/151 176/177 39/40 21/21 YC*090C/YC*086C 982/965 793/777 262/246 203/199 151/151 177/180 39/39 21/21 71/2Single Compressor Y C*090 D/Y C*091 D 1044/1057 855/869 297/298 208/214 151/156 199/200 37/37 20/20 Dual Compressor '81/2 YC*102C/YC*103C 1169/1532 9621233 329/395 244/326 165/231 223/280 38/43 20/26 10 YC*120B/YC*120C 1546/1191 1247/984 425/334 331/252 215/171 276/227 41/38 25/20 YC*121C 1891 1523 516 391 266 351 46 29 121 YC*150C/YC*151C 1599/1915 1300/1547 430/523 342/383 234/271 294/370 42/45 26/30 15 YC*180B/YC*181C 1906/2476 1538/2017 535/693 387/507 259/345 357/472 45/52 29/35 171 YC*210C/YC*211C 1987/2547 1619/2088 553/701 415/538 279/369 372/480 46/53 29/35 20 YC*240B/YC*241C 2415/2645 1995/2186 656/751 503/568 352/373 459/494 53/53 35/34 25 Y C*300B/Y C*301 C 2525/2650 2105/2191 701/755 537/569 376/373 491/495 53/53 35/34 NOTE: 1. Corner weights are given for information only.0/-25ton units must be supported continuously by a curb or equivalent fra me support. 2. Weights are approximate,Horizontal and Downflow unit and corner weights may vary slightly. CENTER OF GRAVITY LENGTH } A �----S ------z 8 CENTER OF • G3tAVfTY O C;) WIDTH s /7- D _ C CENTER OF GRAVITY *Indicates both downflow and horizontal units. 88 Dimensions and Weights AWARNING Figure 2. Corner weights - Center of Gravity Heavy Objects! - Length Failure to follow instructions below or properly lift unit A — — — B could result in unit dropping and possibly crushing Center operator/technician which could result in death or Gravity serious injury,and equipment or property-only damage. W°th Ensure that all the lifting equipment used is properly '. rated for the weight of the unit being lifted. Each of the cables (chains or slings),hooks,and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings)may not be of the same length.Adjust as necessary for even unit lift. D C Center of Gravity AWARNING Improper Unit Lift! Failure to properly lift unit could result in unit dropping - and possibly crushing operator/technician which could result in death or serious injury,and equipment or property-only damage.Test lift unit approximately 24 inches to verify proper center of gravity lift point.To avoid dropping of unit,reposition lifting point if unit is not level. Table 3. Maximum unit and corner weights(lbs) and center of gravity dimensions(in.)-gas/electric models Maximum Model Unit Weights(a) Corner Weights(b) Center of Gravity(in.) Tons Model No. Shipping Net A B C D Length Width 3 YSC036G 577 472 193 178 45 55 33 9 4 YSC048G 598 492 205 183 46 58 33 9 5 YSC060G 627 522 214 193 52 63 33 10 6 YSC072H 805 710 222 217 121 150 41 22 7.5 YSC090H 853 760 206 237 127 190 36 22 7.5 YSC092H j 990 847 265 249 173 160 46 21 8.5 YSC102H 986 885 I 285 I 234 I 195 171 47 I 22 10 YSC120H 1156 1058 345 242 258 213 41 23 3 YHC036E 607 532 165 137 95 134 31 19 3 YHC037E 676 606 178 162 126 139 33 19 4 YHC048E/YHC047E 858 763 238 200 148 176 40 23 4 YHC048F 806 711 226 199 144 143 44 22 5 YHC060E/YHC067E 917 822 261 218 156 187 40 22 5 YHC060F t 1 850 755 239 214 152 151 44 21 6 YHC072E 1025 927 296 198 205 228 41 24 6 YHC072F 965 822 250 245 174 153 47 21 6 YHC074F 1114 1016 334 231 248 202 41 23 7.5 YHC092F 1124 1026 340 233 249 204 41 23 8.5 YHC102F I 1133 1035 341 236 253 205 49 23 10 YHC120F 1 1453 1259 356 371 289 242 54 27 (a)Weights are approximate. (b)Corner weights are given for information only. • RT-SVX21Y-EN 19 Dimensions and Weights Figure 3. Rigging and center of gravity '4- b. '''''''4141140„,. 1 4,4° ' --ai. . o , ill : uulluuu tunnuul ' i 4...,A 1111111111 ' ATTACH CHAIN OR �4 11011111111 CABLE Tr CLEVIS 1, 1111111111 ��.......... to lllllllllll 1tt11111�j.n ' llll�% • tl ��.T, I ,i ^• CENTER OF GRAVITY LENGTH CENTER OF G\ C , LENGTH \ /WIDTH V�,�1 CLEVIS - Table 4. Factory installed options(fiops)/accessory net weights (lbs)(a),(b) YHC047E-067E YSC036G-060G YHC048E-060E YSC072H-102H YSC120H YHC036E,YHC037E YHC048F-060F YHC072E/F YHC074F-102F YHC120F Net Weight Net Weight Net Weight Net Weight Net Weight Accessory 3 to 5 Tons 4 to 5 Tons 6 to 8.5 Tons 6, 7.5,8.5, 10 10 Barometric Relief 7 10 10 10 10 Belt Drive Option (3 phase only) 31 31 — — — Coil Guards 12 20 20 20 30 Economizer 26 36 36 36 36 Hinged Doors 10 12 12 12 12 Low Leak Economizer 68 93 1 93 93 93 Manual Outside Air Damper 16 26 26 26 26 Motorized Outside Air Damper 20 30 30 30 30 Novar Control 8 8 8 8 8 Oversized Motor 5 8 8 — — Powered Convenience Outlet 38 38 38 38 50 Powered Exhaust 40 40 80 80 80 Reheat Coil 12(C) 14 15 20(d) 30 Roof Curb 61 78 78 78 89 Smoke Detector, Supply 5 5 5 5 5 Smoke Detector, Return 7 7 7 7 7 Stainless Steel Heat Exchanger(e) 4 6 6 6 6 Through-the-Base Electrical 8 13 13 13 13 Through-the-Base Gas 5 5 5 5 5 Unit Mounted Circuit Breaker 5 5 5 5 5 Unit Mounted Disconnect 5 5 5 5 5 460V/575V(f) 29 29 — — — (a)Weights for options not listed are<5 lbs. (b)Net weight should be added to unit weight when ordering factory-installed accessories. (c)Reheat weight here is only applicable to YHC036E models. (d)Reheat weight for this value only applicable to 7.5 and 8.5 Ton High Efficiency"F"models. (e)Applicable to Gas/Electric units only. (f) Apply weight with all 460V and 575V 17 Plus Two-Stage Cooling units. 20 RT-SVX21Y-EN