Scope of Work
Installation of the following devices for the fire alarm system
1. Install two smoke detectors, one on each landing at the elevator door
SYSTEM
$ SENSOR
k�
Smoke Detectors with
Sounder and Relay Option
/
System Sensor i3"sounder and relay smoke detectors
14t3
apply the guiding principles of installation ease,
intelligence,and instant inspection in a series of
specialty conventional devices.
Features Installation ease.I hroughout the P series,installation is simple
•85 d6 sounder with its installer-friendly base and plug-in design.The base
accommodates a broad range of back box and direct mounting
•Form C relay options and provides ample space for pre-wiring the device.To
•Isolated thermal sensor complete the installation,the i3 detector plugs into its base with a
simple Stop-Drop'N Lock action.
•Plug-in design(base included)
In-line terminals Intelligence.To reduce the likelihood of nuisance alarms,all
• i3 detectors are equipped with both drift compensation and
•Flexible mounting options smoothing algorithms.These capabilities minimize both short-and
•Stop-Drop'N Lock"attachment to the base long-term causes of nuisance alarms,such as RF interference and
dust accumulation.When connected to the 2W-MOD2 loop test/
•Removable cover and chamber maintenance module or an i3 Ready"panel,2-wire i3 detectors can
•Remote maintenance signaling generate a remote maintenance signal when in a maintenance or
freeze trouble condition.To measure the sensitivity of any i3 detector,
•Drift compensation and smoothing algorithms the SENS-RDR displays the reading,in terms of percent-per-foot
obscuration,within seconds.
•Simplified sensitivity measurement
•Dual-color LEDs Instant Inspection.i3 has red and green LEDs to simplify local
status indication during power-up,standby,alarm,maintenance,
and freeze trouble conditions.When in alarm,P sounder models
generate an 85 dB temporal tone.If connected to the RRS-MOD
reversing relay/synchronization module,all P sounders on the loop
will activate when one detector is in alarm.The RRS-MOD also
synchronizes P sounder output to ensure a clear audible signal.
Agency Listings
Should the application call for differentiating between a local and
w!„�! a general alarm,the i3 line offers an isolated thermal model,which
CD) ® MEA MSFM (ft) initiates a local alarm when smoke is detected,and a general alarm
�(E �/ U5 when the thermal sensor is activated.
LISTED APPROVED 11 approved approved \,,,,,,
3015195 7272-1653.16.1 3/2-02-E
•
�U Smoke Detector Specifications
Electrical Specifications LED Modes
Operating Voltage Nominal:12/24V non-polarized LED Mode Green LED Red LED Condition Duration
2-wire:8.5 V to 35 V Power up Blink every Blink every 10 Initial LED 80 seconds
4-wire:l 0 V to 35 V 10 seconds seconds status
Maximum Ripple Voltage 30%of applied voltage(peak to peak) indication
Standby Current 2-wire:50 pA maximum average Normal Blink every 5 off
4-wire:50 pA maximum average (standby) seconds
Peak Standby Current 2-wire:100 pA Out of off Blink every 5
4-wire:n/a sensitivity seconds
Maximum Alarm Current 2-wire:2WTR-B:130 mA limited by control Freeze off Blink every 10
panel trouble seconds
2WTA-B:130 mA** Alarm off Solid
4wire:4WTA B,4WTR-B:35 mA Power-Up Sequence for LED Indication
4WTAR-B,4WITAR-B:50 mA
**Direct Power(Non-Reverse Polarity):130 Condition Duration
mA limited by panel.Reverse Polarity Power: Initial LED 80 seconds
30 mA for the 2WTA-B in alarm;12 mA for all status
other 2WTA-B units on the loop.Add 25 mA indication
for the RRS-MOD reversing relay alarm current. Architect/Engineer Specifications
Alarm Contact Ratings 2-wire:n/a Smoke detector shall be a System Sensor i3 Series model number
4-wire:0.5 A @ 30 V AC/DC listed to Underwriters Laboratories UL 268 for Fire Protection Signaling
Form C Contact Ratings 2 A @ 30 V AC/DC Systems.The detector shall be a combination photoelectric/thermal
Physical Specifications equipped with a sounder(model 2WTA-B,4WTA-B),a Form C relay(model
Operating Temperature 32°F to 100°F(0°C to 37.8°C) 2WTR-B),a combination sounder/relay(model 4WTAR-B),or an isolated
Range thermaVsounder/relay(model 4WITAR-B).The detector shall include a
mounting base for mounting to 31/2-inch and 4-inch octagonal,single-gang,
Operating Humidity 0 to 95%RH non-condensing and 4-inch square back boxes with a plaster ring,or direct mount to the
Range ceiling using drywall anchors.Wiring connections shall be made by means
Thermal Sensor 135°F(572°C)fixed of SEMS screws.The detector shall allow pre-wiring of the base and the
Freeze Trouble 41°F(5°C) head shall be a plug-in type.The detector shall have a nominal sensitivity
Sensitivity 2.5%/ft.nominal of 25 percent per foot as measured in the UL smoke box.The detector
Input Terminals 14-22 AWG shall be capable of automatically adjusting its sensitivity by means of drift
compensation and smoothing algorithms.The detector shall provide dual-
Dimensions(including 53 inches(134 mm)diameter,2.0 inches color LED indication that blinks to indicate power-up,normal standby,out of
base) (51 mm)height sensitivity,alarm,and freeze trouble conditions.When used in conjunction
Approximate Weight 7.1 oz(200 g) with the 2W-MOD2 module,2-wire models shall include a maintenance
Sound Pressure Output 85 dBA(models 2WTA-B,4WTA-B,4WTAR-B, signal to indicate the need for maintenance at the alarm control panel and
and 4WITAR-B only) shall provide a loop testing capability to verify the circuit without testing each
Mounting 31/2-inch octagonal back box,4-inch octagonal detector individually.When used in conjunction with the RRS-MOD module,
back box,single-gang back box,4-inch square all i3 sounder models on a loop shall sound when one sounder alarms,all shall
back box with a plaster ring,direct mount to be synchronized,and all sounders may be silenced from the panel.
ceiling
Ordering Information
Model Thermal Wiring Alarm Current Model Description
2WTA-B Yes 2-wire 130 mA max limited by RRS-MOD Reversing relay/synchronization module
control panel 2W-MOD2 2-wire loop test/maintenance module
2VVTR-B Yes 2-wire 130 mA max.limited by SENS-RDR Sensitivity reader
control panel RT Removal/replacement tool
4WTA-B Yes 4-wire 35 mA A77-AB2 Retrofit adapter bracket
4WTR-B Yes 4-wire 35 mA
4WTAR-B Yes 4-wire 50 mA
4WFLAR-B Yes 4-wire 50 mA
*Th, SYSTEM ®2009 System Sensor.
3825 Ohio Avenue•St.Charles,IL 60174 Pma,;ts nonss„be<ttoaange withoutnoaevsrtsntemsen;«omfor
SENSOR® Phone:800-SENSOR2•Fax:630-377-6495 `went product inforrnattcrt induchng the Latest version°ft*us data sheet
005-0348-004.6/09-#2170
-Global Project Values:
SILENT Project Name: Landmark Ford Service Building Standby Hours: 24
KNIGHT' Project ID: Alarm Mins 5
Prepared By: Phillips Electronics Derating Factor
SK-5208 Calculations Date: Voltage Drop Warning
Version 02.26.09 Threshold%: 10
Panel ID: SK-5208 Model: SK-5208 Fire Alarm Control Panel Max NAC Current: 3.0 Amps
Location: Volts: 24 VDC Max Panel Current: 6.0 Amps
Ckt.# Circuit Name Qty Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Alarm &Type 1000 Ft. One-Way Ohms EOL p
SK-5208 SK-5208 Main Control 1 0.140 0.550
SK-5217 SK-5217 Zone Expdr 0.000 0.000
SK-5235 SK-5235 LCD Remote 0.000 0.000
SK-5280 SK-5280 Display Mod 0.000 0.000
SK-5220 SK-5220 Dir Con Mod 0.000 0.000
SK-7181 SK-7181 Zn Cnvtr 0.000 0.000
IDC-1 Initiating Device Ckt 1 0.000 NA**
IDC-2 Initiating Device Ckt 2 0.000 NA**
IDC-3 Initiating Device Ckt 3 0.000 NA**
IDC-4 Initiating Device Ckt 4 0.000 NA**
IDC-5 Initiating Device Ckt 5 0.000 NA**
IDC-6 Initiating Device Ckt 6 0.000 NA**
IDC-7 Initiating Device Ckt 7 0.000 NA**
IDC-8 Initiating Device Ckt 8 0.000 NA**
IDC-9 Initiating Device Ckt 9 0.000 NA**
IDC-10 Initiating Device Ckt 10 0.000 NA**
......................
.. . ....................
.. ....................
IDC-11 Inactive;;Add SK$2t7 0.000 NA**
......................
IDC-12 Inactive;:Add:SK-S2 t7: 0.000 NA**
IDC-13 Inactive, Add SK 52t7 0.000 NA**
IDC-14 Inactive odd$K$21.7. 0.000 0.000 NA**
......................
.......................
......................
IDC-15 Inactive, Add SK 52 7: 0.000 NA**
IDC-16 Inactive, AddiSK-52'.17:: 0.000 NA**
IDC-17 Inactive; Add SK 52 t7 0.000 NA**
......................
............ ..........
IDC-18 InactivAdd SK-5217::: 0.000 NA**
IDC-19 Inactive Add SK:52 E7 0.000 NA**
.. .....................
IDC-20 Inactive Add SK 5217;: 0.000 NA**
IDC-21 Inactive, AddSK 5217:: 0.000 NA**
IDC-22 Inactive;;Add SK-52`t7 0.000 NA**
............ .........
............. .........
............ .........
IDC-23 Inact ve, Add 5K-5217:. 0.000 NA**
IDC-24 Inactive add SK 5217 0.000 NA**
IDC-25 Inactive Add SK-5217.:: 0.000 NA**
. .....................
IDC-26 `Inactive ;AddSK52st7i 0.000 NA**
.......................
IDC-27 Inactive, Add:SK-52`t7 0.000 NA**
IDC-28 i active, Acid SK 5217 0.000 NA**
IDC-29 I act ve Add SK-5217: 0.000 NA**
IDC-30 Inactive;Add S.K.-5217 0.000 NA**
NAC-1 Notification Appl Ckt 1 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00%
NAC-2 Notification Appl Ckt 2 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00%
NAC-3 Notification Appl Ckt 3 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00%
NAC-4 Notification Appl Ckt 4 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00%
Aux Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00%
Total Standby Current(Amps) 0.140 0.550 Total Alarm Current(Amps)
Standby Time In Hours 24 0.083 Alarm Time In Minutes/60 (5 Mins)
Total Standby AH Required 3.362 0.046 Total Alarm AH Required
Total Combined AH Required 3.41 Command Shortcuts
Multiply By The Derating Factor 1.20
Minimum Battery AmpHours Required 4.09 Configure Circuits Print Page
** The SK-5208 and SK-5217 limits alarm current to 95mA per zone. The SK-5208 alarm current includes 10%of system zones in
alarm,but in no case less than three zones per UL 864.