Product Data For:
WAL-MART PICK UP MACHINE
7600 SW DARTMOUTH STREET
TIGARD, OR 97223
PREPARED BY:
FIRE PROTECTION
Viking Automatic Sprinkler Co.
3245 NW Front Ave Portland, OR 97210
24 Hrs 0: 503.227.1171 F: 503.227.1552
OR CCB #64837 • Metro Lic #2816 • CA C-16 LIC #279188
Boise • Longview • Medford • Portland • Seattle
Submittal Date: SEPTEMBER 19, 2019
Ker
TABLE OF CONTENTS
Sprinkler Heads
A. Victaulic, flexible sprinkler connection, 48"braided, AH2
B. Tyco, standard response, ELO pendent,TY525I
Victaulic° VicFlexTM Sprinkler Fittings
4taUIiC
Series AH2 and AH2-CC Braided Flexible Hoses 10.85
•
Vic
FIex'
1
Series AH2 Series AH2-CC
1.0 PRODUCT DESCRIPTION
Available Sizes by Component
• Series AH2 1"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830mm.
Note: length includes adapter nipple and 5.75"1140 mm straight reducer.
• Series AH2-CC 1"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 72/790, 915, 1220, 1525, 1830mm.
Note: length includes captured coupling and 5.757140 mm straight reducer.
• Sprinkler Reducers:
• Sprinkler Connections: /and 3/a"/15 and 20mm
• Straight Lengths: 5.75, 9, 137140, 230, 330 mm
• 90° Elbows:
• Short (typically used with concealed sprinklers)
• Long (typically used with recessed pendent sprinklers)
• Low Profile Short(for use with Style AB5, AB11, AB12, ABBA and ABMM Bracket)
• Low Profile Long(for use with Style AB5, AB11, AB12, ABBA and ABMM Bracket)
• Inlet Connections:
• 1725mm Grooved IGS
• 1"/25 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards.
• 4720mm NPT or BSPT adapter nipples available for VdS.
• 11/4"/32mm BSPT adapter nipples available for LPCB.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT.
System No. Location Spec Section j Paragraph
Submitted By Date Approved Date
victaulic.com •
victaulic.com
LO PRODUCT DESCRIPTION (Continued)
Brackets:
• Style AB1 for suspended and hard-lid ceilings and sidewalls, allows installation before most ceiling tiles in place
• Style AB2 for suspended and hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and
installation before most ceiling tiles in place
• Style AB3 for surface mount applications, wood, metal and block walls, or ceilings
• Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment
• Style AB5 for hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment
• Style AB7 for suspended and hard-lid ceilings
• Style AB7 Adjustable for suspended and hard-lid ceilings
• Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available)
• Style AB9 for hard-lid ceilings with hat furring channel grid systems
• Style AB10 for Armstrong®TechZonee^ ceilings
• Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low
profile installations(use only with 900 low profile elbows)
• Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low
profile installation down to 4"/100mm.
• Style ABBA bracket for suspended, exposed, and hard-lid ceilings
• Style ABMM bracket for surface mount and stand off-mount applications, wood, metal and block walls, or
ceilings and hard-lid ceilings
Maximum Working Temperature
• 2250F/107°C
Maximum Working Pressure
• 200 psi/1375 kPa (FM Approval)
• 175 psi/1206 kPa (cULus Listed)
• 1600 kPa/232 psi (VdS/LPCB Approved)
• 1.4 MPa (CCCf Approved)
Connections
• To adapter nipple (inlet)via
• 1"/25.4 mm Grooved IGS
• 1725.4 ram NPT or BSPT male thread
• 34720mm BSPT male thread (VdS only)
• 11/4'732 mm BSPT male thread (LPCB only)
• To sprinkler head (outlet) via 1/2" or 3/4715 mm or 20 mm
Minimum Bend Radius
• 7"/178 mm (FM/CCCf Approval)
• 2751 mm (cULus Listed)
• 3'776.2 mm (VdS/LPCB Approved)
Maximum Allowable Sprinkler K-Factors
• FM (1/2715 mm reducer) K5.6/8,1 (S.I.), (34720 mm reducer) K14.0/20,2 (S.I.)
• cULus (1/2"/15mm reducer) K8.0/11,5 (S.I.), (3/4720 mm reducer) K14.0/20,2 (S.I.)
• VdS/LPCB (1/2715 mm reducer) K5.6/8,1 (S.I.), (3/4720 mm reducer) K8.0/11,5 (S.I.)
10.85 5839 Rev AG Updated 07/2019 6>2019 Victautic Company.All rghts reserved.
victaulic.com
2.0 CERTIFICATION/LISTINGS •
VdS LPCB CCC
LISTED
NOTE
• The VicFiex Series AH2 Hose has been tested and evaluated by Spears@ for acceptable use with Spears®CPVC Products and is therefore covered under the
Spears@ FlameGaurd®Installer Protection Plan.
3.0 SPECIFICATIONS — MATERIAL
Series AH2
• Flexible Hose: 300-series Stainless Steel
• Collar/Weld Fitting: 300-series Stainless Steel
• Gasket Seal: Victaulic EPDM
• Isolation Ring: Nylon
• Nut and Nipple: Carbon Steel, Zinc Plated
• Reducer (1/2"/15 mm or 3/4"/20 mm): Carbon Steel, Zinc-Plated
• Low Profile Elbows: Ductile Iron, Zinc-Plated
Brackets: Carbon Steel, Zinc-Plated
Series AH2-CC
• Flexible Hose: 300-series Stainless Steel
• Collar/Weld Fitting: 300-series Stainless Steel
• Gasket Seal: Victaulic EPDM
• Isolation Ring: Nylon
• Coupling Retainer Ring: Polyethelene
• Nut and Nipple: Carbon Steel, Zinc Plated
• Reducer(1/2 715 mm or 3/4"/20 mm): Carbon Steel, Zinc-Plated
• Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395,
Grade 65-45-15, is available upon special request.
Coupling Housing Coating:
• Orange enamel (North America, Asia Pacific).
• Red enamel (Europe).
• Hot dipped galvanized.
Gasket:1
• Grade"E" EPDM (Type A)
FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of
Canada Limited, and Approved by Factory Mutual Research for wet and dry(oil free air) sprinkler services
within the rated working pressure.
Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference
should always be made to the latest Victaulic Gasket Selection Gums for specific gasket service guidelines and for a listing of services which arc not
compatible.
• Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of
ASTM A 449 and physical requirements of ASTM A 183.
• Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish
•
10,85 5839 Rev AG Updated 07/2019 2019 Viciviilit:Cnmpany All right reserved
i
. ,
victaulic.com
•
4.0 DIMENSIONS
Product Details - Series AH2 Braided Hose
Item Description
L . 1 , Flexible Hose
2 Isolation Ring I
l
3 Gasket
. _
_1:,i1._ .
,,,T......-,_
, ,,.1E US 11 ' -' 1
I- 5 t
6 I Nut
Adapter Nipple
Braid --1
;
Collar/Weld Fitting
,
• , . 8 Sleeve
Hose Length Dimensions
l
Hose Length A B
I
inches inches inches
mm mm mm
31/790 253/641 31/790
1
36/915 31.3/794 36/915 _I
48/1219 1
1 42.3/1073 48/1220 ;
60/1525 1 54.3/1378 60/1525 _I
72/1830 i 66.3/1683 72/1830
Series AH2-CC Braided Hose
,-
Item Description
e
7. 1 ,/ Ta-r4\ 1 Flexible Hose
--
io
"
P
2 Isolation Ring I - I .
-4 ' 4 ' 4. 1IIII,IIIIII H II " 1 3 Gasket
Of, I _____._; i ....__L. _LI. II HEli rii ,11 I,1.1i. ,+-- 4I Nut
• V
A / 1 1 5 Captured Coupling
,
6 Braid
I 7 Collar/Weld Fitting
1 ; 8 Sleeve
Hose Length A B
inches inches inches
mm I mm mm I
31/790 24.5/622 29.8/757
36/915 , 29.5/749 34.8/884 ;
48/1219 : 41.5/1054 46.8/1189
,-. ---4
60/1525 53.5/1359 58.8/1494
72/1830 = 65.5/1664 70.8/1798
. .
10.85 5839 RPV AG Updaipci 07/2019 (t)2019 Vrclaulir Cnmpany.All righl,rPsPrvPd
7
victaulic.com
•
4.0 DIMENSIONS (Continued)
Standard Reducer
—111mImmt iFIRTI IT
5.757140 mm straight reducer
Optional Reducers
lIf I moth
9.07229 mm straight reducer
l 1!111
C ; SII 1 -1
13.07330 mm straight reducer
2 627
66.5 mm
• to
='o
6577 E
5 1669mm
II
Short 90`elbow reducer Long 900 elbow reducer
NOTE
• The Short 90"elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent
sprinklers.
• FM?VdS Approved only.
Low Profile
r-�
-59`!
lr ninl
= 2.44.
c C
rrmern-gym
Short 90'elbow reducer Long 90'elbow reducer
NOTE
• Style AB11:When low profiles elbows are used with the Style AB11 bracket_the Low Profile Short Elbow is typically used with concealed sprinklers while the
Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers
•
•
10.85 5839 Rev AG Updated 07/2019 ee 2019 Victaulir.Company All rlghlc reserved
if
victaulic.cam
4.1 DIMENSIONS
VieFlex Brackets
Style AB1
• Suspended Ceilings
• Hard Lid Ceilings (FM Only) if.H .---„,„,
Item I Description it pwt . `,,
0
1 1 24"/610mm or48"/1219mm Square Bar '
2 I Patented Center Bracket
3 End Bracket •
NOTE
• Both saes FM/VdS/LPCB Approved,cULus listed :3
Style AB2
• Suspended Ceilings
• Hard-Lid Ceilings ,;;;
d
Item Description
i 1 24/610 mm or 48!1219 mm Square Bar_ � �
2 Patented Vertically Adjustable Center Bracket 1 I ?:_
L 3 _ End Bracket y7 /�
NOTE
1;
• Both sizes FM/VdS/LPCB Approved,cULus listed
r1:, 1
/9
Style AB3fes:
• Surface Mount Applications --
• FM/LPCB Approved ;. ;
P
10.85 5839 Rev AG Updated 07/2019 e)2019 Victautir Company.All nghl reserved
i
victaulic.com
•
4.2 DIMENSIONS
VicFlex Brackets
Style AB4 ` ,1
• Hard-Lid Ceilings with Hat furringro
channel grid system
3
Item Description i'"
1 24'/610 mm or 4871219mm Square Bar 3
Patented Vertically Adjustable Center Bracket
r
3 End Bracket for Hat Furring Channel R�1
NOTE -\t
• Both sues FM/VdS/LPCB Approved,cULus listed
Style AB5 r
• Hard-Lid Ceilings ,11
1 -
Item i Description
1 24"/610mmor48"/1219mmSquareBar 2'
2 Patented Vertically Adjustable Center Bracket , R
3 l End Bracket
', !
NOTE ' ',,
• Both sizes FM/VdS/LPCB Approved,cUlus listed-
''''',,,,,,,,,,„,04 3'
Style AB7
• Suspended Ceilings
• Hard-Lid Ceilings
— ,-,,<,,,,,,,,,
3 Item Description ",..
1 24"/610mmor48"/1219mmSquare Bar A t
I 2 Patented 1-Beer Center Bracket
3 End Bracket 1
NOTE *�
• Both sizes FMlVdStLPCB Approved.
R j
F
Style AB7 Adjustable
• Suspended Ceilings
• Hard-Lid Ceilings j
Item Description
1 700 mm or 1400 mm Square Bar "'
2 ! Patented 1-Beet"Center Bracket
3 End Bracket(adjustable) ' .,, \
NOTE �.
• Both sizes FM/VdS/LPCB Approved.
p 3`
•
• •
10.85 5839 Rev AG Updated 07/2019 CCr 2019 Victanlic Company_All rrghts reserved
if
victaulic.com
•
•
4.3 DIMENSIONS
VicFlex Brackets
Style ABB lit.
,irrw
• Hard-Lid Ceilings ....t544444444444.47fD .....
t ,
r))
, „...,,...,
' Item ' Description .,
1 1 j 700mm or 1400 rnm Square jar
2 Patented Vertically Adjustable Center Bracket 41411:::-'-1414,1%sissii44444,
3 I End Bracket
NOTE
• Both sizes FM/VdS/LPCB Approved
!IA'..11141411010
Style AB10
• Suspended ceilings ,
• Armstrong')TechZone–
Item Description
1 67152mm Square Bar ;
2 Patented 1-Bee2 Center Bracket I 0
3 End Bracket
NOTE
• FM/VdS/I_PCB Approved.LULus listed
Style AB11
• Suspended ceilings .
.,
• Hard-Lid ceilings
Item ; Description
1 I 247610mm or 4871219mm Square Bar
••-, ..g.
2 Patented 1-Beer Center Bracket
End Bracket I
,.___
' 3
NOTE .'
• F MiVdS Approved,cULus listed.
Style
5.4
Style AB12
• Suspended ceilings _.----s--,„„ .2
• Hard-Lid ceilings •••:- . • N''',, -
'% -%.• —3- .:-..=
• , .4il>-',,,,"
Item Description ' c,
. ' , ".•••!....... .- •
1 Style AB12 Bracket Body
1
2 #2 Square Drive Set Screw ,
NOTE
000
• FIANdS Approved
• •
10.85 5839 RPV AG Ur-rater;07/2019 C.2019 Victatilic Company Ail rightreserved
..
victauiic.com
4.3 DIMENSIONS (CONTINUED)
VicFlex Brackets
Style ABBA
• Floor-above mount
• Cantilever mount
• Temporary mount in exposed ceilings
Item Description
1 Style ABBA Mounting Plate
2 Style ABBA Square Bar
3 Cap Screw,Serated Flange,M6 x 1 x 20,
T25 Torx Drive Recessed
4 Style ABMM Bracket Body yr
5 7 Cap Screw,Serated Flange,M6 x 1 x 15.24,
T25 Torx Drive Recessed
Style ABMM
• Surface mount
• Stand-off mount '\,' •
Item Description
1 Style ABMM Bracket Body n,
2 Cap Screw,Serated Flange,M6 x 1 x 15.24,
T25 Torx Drive Recessed
10.85 5839 RPV AG Urdaied 07/2019 C,2019 Victaulic Company All rights rpservPd
i
victaulic.com
"
4.4 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB1 Bracket
A Bractet
1..e,(hurt .-'..� 4scemnh^ 2 J6O mn>
n,t
Style A1.11 1-ole
't l — 4 mi, •ofe mm
n '50 Mtn—.
Mtn
—mo n ole .n .,ole
jtt-r i t ,
c9rim srnm g M
1. Tvp,cal
yPIcal tering '
`
—r ceding tile t
1 "
grit i' _.t _ '' hl' ..=5 ' _ , eF,, L
.
4::' finished
ee note- erlinl face �c'
--- 24";h10 mm or --....--+k V27 V38
48"r12,9 mm a.,: Pendent
i".nt,
Hose Clearance Chart
Straight Reducer Long Elbow Short Elbow
V2707 V3802 V2707 V3802
3/4' 1/2" 3/a" 1/2" V2707 V3802 V2707 V3802
Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess 1/2"Max Recess 3/4"Max Recess 1/2"Max Recess
inches , inches inches inches i inches inches inches inches
mm mm mm mm ! mm mm mm mm
"R"Minimum 2.0 3.0 I 70
Bend Radius 50 80 175
"A"Minimum
Required 8.6 10.1 9.6 11.1 13.6 15.1 5.8 5.8
Installation 218 269 1 244 `; 281 - 345 383 147 147
Space j
1
NOTE
• Variations of ceiling grids,sprinkler heads.brackets,and hoses are permitted but may result in clearance differences from the figures above
i
• •
10.85 5839 Rev AG Updated 07/2019 C 2019Victaulic Company.All rights reserved-
victaulic.corn
•
4.5 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB2 Bracket ,
i
i R
A
a,1
ri
II
i
�—� n: y.1 S / rr m .twirl '
; ' les,
> t a
` F d
.1 ,S _ amw
3 ^
. r...
Hose Clearance Chart
Straight Reducer
V2707 V3802 V2709 V2707 V3802 ' V2709 V2707 r V3802 I V2709
Ms"I20mm ih"I13mm 3/."I20mm Ms"I20mm 1/2"I 13mm3/4"I 20mm 3/4"I20mm 1/2" 3/4"120mm
Max Recess" Max Recess Sidewall Max Recess Max Recess I Sidewall Max Recess Max Recess Sidewall
inches inches inches ,aches inches 1 inches inches inches inches
mm mm mm mm mm mm mm _ mm mm
1 "R"Minimum 2.0 3.0 7.0
Bend Radius SO 80 175
'A"Minimum
Required 6.2 7.6 6.1 I.2 8.6 7.1 11.2 12.6 11.1
Installation 158 193 155 183 218 180 285 i 320 282
Space
Hose Clearance Chart
Long Elbow Short Elbow
V2707 V2709 V3802
3/4"I20mm Ms"I20mm 1/2"I13mm
Max Recess Sidewall Max Recess
inches inches inches
mm mm mm
"R"Minimum
Bend Radius
.,A"Minimum ,
Required 3.3 3.6 3.3
Installation 84 91 84
Space
NOTE k
• Variations of ceiling grids.sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above.
i
• •
10.85 5839 Rev AG Updated 07/2019 tint 2019 Viclaulr Company_All rights recervest
If
victaulic.corn
• "
4.6 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB4 Bracket
-1
XR
ri mo
,V_ :=gt _ �, r
.wrr,
r
X
"
`Jr«i° . '
,.,;h
4111
.e' nq'oe_ �.
See rrole-- .
- ,-_
'cicat (- 16 mm - V27 V38
,..11(1/ -on s..r.,, - ` ,5,..'71,,, Pendent
Hose Clearance Chart
Straight Reducer Long Elbow Short Elbow
V2707 V3802 V2707 V3802
34" i/z" 3/a" 1/2" V2707 V3802 V2707V3802
Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess 1/2'Max Recess 3/4"Max Recessi3"Max Recess
inches inches inches inches inches inches inches i inches
mm mm mm mm mm mm mm 1 mm
"R"Minimum 2.0 2.0 3.0 i 3.0 7.0 7.0 _
Bend Radius 50 50 I 80 1 80 175 175
A"Minimum
Required 8.8 10.2 9.8 11.2 13.8 15.2 I 8.0 5.9
Installation 224 259 249 285 351 386 i
1 203 150
Space 1
NOTE
Variations of ceiling grids.sprinkler heads,brackets.and hoses are permitted hut may result in clearance differences from the figures above
10.85 5839 Rev AG Updated 07/2019 dd 2019 Victaulic Company_All rights reserved_
victaulic.corn
e •
4.7 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB5 Bracket
+ 8
n
Asyenlel�
(..1%, ti ,,e 1;t3�� i
_id
1I by --1.---'k'----kin,--.7 IS 'T
.'lr n.•Yt
`� rt
}1 l 11 It
1
4 P
rt rt t1 1 kj ,
11
D('d,•r:it,
a _..
V27 V38 V27
Pendent Sidewall
Hose Clearance Chart
Straight Reducer 1
"V2707 V3802 j V2709 V2707 V3802 V2709 V2707 V3802 V2709
3/4"I20mm 'h"I13mm 13 /a"I20mm 1'I20mm r "I13mm ;/4"I20mm ( 3/4"I20mm rh"I13mm 3/e"I20mm
Max Recess" Max Recess Sidewall Max Recess j Max Recess Sidewall Max Recess Max Recess Sidewall
• inches inches inches inches I inches I inches inches inches inches
mm mm mm mm mm mm mm mm mm
"R"Minimum 1 2.0 3.0 7.0
• Bend Radius 1 50 80 175
"A"Minimum i
Required 6.0 7 7 6.1 7.0 8.7 7.1 11.0 12.7 j 11.1
Installation 158 196 155 178 221 180 279 323 282
Space
Hose Clearance Chart
Low-Profile
Long Elbow ' Long Elbow Short Elbow
V2707 V3802 V2709 V3802 V3802
3/4"I20mm 1/2"I13mm 3/4"I20mm 1h"I13mm , lh"I 13mm
Max Recess ; Max Recess Sidewall Max Recess i Max Recess
inches ' inches inches I inches inches
mm mm i mm mm mm
"R"Minimum j —
Bend Radius
"A"Minimum
Required 3.5 4.9 3.6 2.9 3.3 I
Installation 89 124 91 74 84
Space
NOTE
• Variations of ceiling grids,sprinkler headsbrackets,and hoses are permitted hut may result in clearance differences from the figures above.
• •
10.85 5839 Rev AG 1,11 r s,1Sn 07/,...019 ft 2019 Viciaulic Company-All rights reserved,
I
victaulic.com
4.8 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION)
2",."/60 mm 1-.1_'768 mm
O.
tl ' .r n
rh.nle max hole
B-arket O'
Assembly ►il ') 'Sr5mm 2 /60 mm
A 4. Style A811 t f stir pole mm hole
See Chart
111111
it
1 ii V
I I it1,170.1/411
P
1/''lirrrn {! Fin-zhed
Typicel
54"/f59mm ceiling face
ceiling gr d typical
ceding tile <
See Note 4 ._. ?r."'d 10 run or _._._.____. V27 V38
48712199 mr,on center Pendent
Hose Clearance Chart
Low-Profile Low-Profile
Long Elbow Short Elbow
V2707 V3802
3/"I20mm 1/2"I13mm
Max Recess" Max Recess
inches inches
mm mm
"A"Minimum
Required 4.0 3.9
Installation 102 99
Space
NOTE
• Variations of ceiling grids.sprinkler heads,brackets,and hoses are permitted but may resadi in clearance differences from the figures above
• •
10.85 5839 RPV AG Updated 07/2019 (C)2019 Viclaulic Company.All rights recervnrl
victaulic.com
• •
4.9 DIMENSIONS
Clearances
Style AB12 and ABBA Bracket
Suspended Ceiling Grid with Recessed Sprinkler with Suspended Ceiling Grid with Recessed Sprinkler and
Low Profile Short Elbow Straight 5.75"1140 mm Reducer
1. r- / Vii.:i.,/� � k
T I
iii '
4 '-4- -4. . n' 0�' Ifs
. f
7
i f I i
_ � E
l
V270751'112.7 mm MAX.RECESS 52707,4-179 mm MAX.RECESS
Low Profile Low Profile Standard Standard Standard
Dimension Short Elbow Long Elbow Short Elbow Long Elbow Straight Reducer
3/4"719 mm 3/4119 mm 3/4719 mm 3/4719 mm 3/4719 mm
Recessed` Concealed Recessed Concealed Recessed Concealed Recessed Concealed Recessed Concealed
inches inches inches inches j inches inches inches inches inches inches
mm mm mm mm mm mm mm mm mm mm
A Minimum Required 4.0 5.5 5.6 7.2 5.9 7.5 7.7 9.3 15.0 16.6
Installation Space 101.6 139.7 1422 182.9 149.9 1905 195.6 236.2 381.0 421.6
I
Distance from Top of 0.5 2.0 1.5 1.5 15 15 3.0 3.0 3.0 3.0
B Typical Ceiling Tile to 12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2
Bottom of Gate f i I
Adjustability wit be limited
Style ABMM Bracket
Stand-off Dimensions
..., i r __ 028..• .
mm
I r
C,
• •
10.85 5839 Rev AG Updates 07/2019 4'i 2019 Victaulic Company.All rghls reserved
victaulic.com
4.10 DIMENSIONS
Clearances
Style AB3 and ABMM Bracket
Surface Mount Application with Recessed Sprinkler
A
R
C
Man MINIMID � A
33/4'/
ITi'--�-_... ..�-65.3 mm
x, _77 ®�
1.:2_1111:;"-- =_=..,,,L,...
7 I,/
AII
, . //:,
UM
two ,/,/./..i4,
mr.F.1.1_ r
4p�►
2,'s"/60 mm
max.hole
2'/51 mm
mm hole
Hose Clearances
inches 1 inches inches 'inches inches inches inches inches 1 mchesi inches'
Dimension mm mm mm mm mm mm mm mm mm mm
Wall Thickness 2 4 6 8 10 2 4 6 8 10
"A" 50 100 150 200 250 50 140 150 200 250
Outlet Length F 5.75 9 13 5.75. 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13
"B" 146.1[228.6:330.21146.1 228.6 330.2 228.6 330.21 330,2 330.2 146.1 228.6 330.2 146.1228.6;330.2(228.61330.2 L 330.2 1 330.2
Hose Clearance 11.6 14.8 18.8 9.6 1 12.8 16.8 1 10.8 ( 14.8 12.8 10.8 12.6 1 15.8 19.8' 10.6 13.8 1 17.8{ 11.8 115.8 I 13.8 ' 11.8
"C" 294 376 478 243 1 325 427 275 1 376 325 275 319 1 402 503 ; 268 351 1452 300 1 402 1 351 ' 300
i Bend Radius 7 8
"R" 175 200
NOTE
• Variations o1 ceding grids,sprinkler heads,brackets.and hoses are permitted but may result in c'earance differences from the figures above.
10.85 5839 Rev AG UpdaiFrl 07/2019 Z. 2019 VICtaUihC Company.AR nghis reserved
victaulic.com
5.0 PERFORMANCE — FRICTION LOSS DATA
Series AH2 and AH2-CC Braided Hoses with Straight 5.75'1140 mm Reducers
cOus
um Style AB1, AB2, AB4, AB5 and AB10 Brackets
Maximum
Equivalent Length Number of
of 1"/33.7 mm 90°Bends at 2751 mm
Sch.40 Pipe(C=120) Bend Radius
inches/mm inches/mm/type feet/meters
—
31/790 16715/Straight 16/4.9 4
34920/Straight .[---- 17/5.2 4
36/915 1/2715/Straight 21/6.4 5
W/20/Straight 23/7.0 5
48/1220 1/ /15/Straight 32/9,8 8 J
3/4720/Straight 1 37/11,3 8
60/1525
1/2715/Straight 46/14.0 10
1/4720/Straight 46/14.0 10
72/1830 . 1/2715/Straight 55/16.8
---i..- 12
1/4720/Straight 53/16.2 12
Series AH2 and AH2-CC Braided Hose with 90" Low Profile Elbows
COW
LISTED Style AB11 VicFlex Bracket
Maximum
Equivalent Length Number of
of 1733.7 mm 90°Bends at 2/51 mm
Sch.40 Pipe Bend Radius
inches/mm inches/mm feet/meters
1/2715 1 24/73 4
31/790
3/4720 24/73 4
4
16715 26/7.9 5.
36/915 .. •
W/20 28/8.5 5
r )
1 11/2715 43/131 i 8
48/1220 .1
1 3/4720 42/12.8 1 8
_
60/1525 1/2715 49/14.9 10
V4"120 50/15.2 10
'4715 65/19.8 12
72/1830
W/20 1 63/19.2 I 12
f
• •
10.85 5839 Rev AG Updated 07/2019 Ci 2019 Victatitic Cnrnrany.All rght,reserved
g
victaulic.com
•
5.0 PERFORMANCE— FRICTION LOSS DATA (CONTINUED)
Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide
Equivalent length values at various numbers of 90 degree bends at 2751 mm center line bend radius
Length of
Stainless;
Steel
Flexible Outlet 1 2 3 4 5 6 7 8 9 I 10 11 12
Hose Size Bend Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends
inches/ inches/ feet/ feet! feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/
mm mm meters meters meters meters meters meters meters meters meters meters meters meters
31/790 Eli/15 8.5/2.6 11.0/3.4 13.0/4. ' 16.0!4.9 NA NA NA NA N.A N,A I N.A N.A
3/4720 10.013.0 12.5!3.8 14.0/4.3 17.0/5•2 N.A NA N.A N.A N.A N.A NA ' NA
36/915 1/2715 13.5/4.1 16.0/4.9 ' 18.0/5.5 19 015.8 21.0/6.4 N.A N.A NA N.A N.A N.A N.A
3fy/20 / 14.0/43 17.0/5.2 19.5/5.9 f 20.0/6.1 23.0!7.0 { N.A N.A N.A N.A N.A N A N.A
48/1220 1/2715 15.5/4.7 17.0/5.2 19.5/5.9 20.0!6.1 21.0!6.4 122.0/6.7 ' 28.0/8.5 32.0/9.8 N A N A N.A N.A
W/20 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 ; 27.0/8.2 30.0/9.1 t 37.0/11.3 N.A N.A � N.A N.A
60/1525 '/2/15 21.5/6k 24.0/7.3 27M/8.2 28.5/8 7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13A 46.0/14–.0-1 N.A N A
' /20 23.0/7.0 24.0/7.3 28 0/8.5 29 5/9.0 30.5/9.3 31.0/9.4 38./11.6 42.0/12.8 44 0/13.4 46.0/14,0 N.A N.A
72/1830 W 2— '32 337,.55/11A
5 54..00//116..5
0/1 .53.0/16.2
%-0120 320/98 32.5/99 35.0/10.7'355/10.8 400/12.3's 40.5/12.3 41.0!12.5 46.0/140 50.0115.2 51.0/155 52.01158'53.0/16.2'
NOTES:
• Values for use with 5.75/140mm straight reducers.
How to use this Design Guide:
• For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the
maximum allowable number of bends.In this case,the designer may select a design number of bends for the iob and use the associated equivalent length
from the design guide to determine the system hydraulics.
• II is possible that the actual inqalled condition of some of the flexible drops may have more bends than the designer selected.When this happens.the design
guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydranfirs rare he
recalculated rising actual equivalent lengths to verify the performance of the system_
• •
10.85 5839 Rev AG Updated 07/2019 7 2019 Vietanlls Company.All rights reserved.
i I
victaulic.com
5.1 PERFORMANCE— FRICTION LOSS DATA
FM Series AH2 and AH2-CC Braided Hoses
Style AB1, AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB1O, AB12, ABBA and ABMM VicFlex Brackets
Maximum
Equivalent Number
Length of Length of of 90°Bends
Stainless Steel Outlet 1"/33.7mm at 7"/178mm
Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius
inches/mm Imperial/S.I. inches/mm/type feet/meters
C — 1/"115/Straight 13.8/4.2
31/790 5.6/8.1 �.. I. _-___, . , _ ____ � 2
Y2"/1 S/90°Elbow 1 23.5/7.1 a.
1/15/Straight ! 16.6/5.1
36/915 5.6/8.1 _. 2
/2/15/90"Elbow 25.6/7.8
1/2715/Straight 23.4/7.1
48/1220 5.6/8.11 3
1/2715/90'Elbow 30.7/9.3
h'/15/Straight 30.2/9.2
60/1525 5.618,1 4
I 'x'/15/90'Elbow 35.9/10.9
'/2'715/Strai9 ht ' 37.0/11.3
72/1830 5.6/8.1 . _ __ 4
1/2"!15/90 Elbow 41.1/12.5 1
i 3/4720/Straight i 16.8/5.1
31/790 I 8.0(11.5 1}/4"/20/90'Elbow 16.8/5.1 2
3 720/Straight 20/6.0
36/915 8.0/11.5 . 2
3 720/9D Elbow 19.7!6.0
1/4720/Straight 27.8/8A
i 48/1220 8.0/11.53
3.+"!20/90'Elbow 26.6/8.1
/4/20/Strai ht 357/109
3 .
60/1525 8.0/11.5 g. 4
3/4"/20/90`Elbow i 33.6/10.2
3/4C/20/Straight 433/13.2
72/1830 8,0/11.5 4
3/4"120/90' Elbow 40.6/12.2
3/4720/Straight i 16.5/5.0
31/790 11.2/16.1 — 2
34720/90"Elbow 17.8/5.4
3/4720/Straight 19_.5/5.9
36/915 11.2116.1 3!4"120/90Elbow 20.7!6.3 2
1/4720/Straight 26.7/8.1
48/1220 i 11.2116.1 //20/90'Elbow 27.9/8.5 3
314720/Straight 33.9/10 3
60/1525 11.2116.1 43/4"/20/90'Elbow 35/10.7
r 3/4'120/Straight 41.3/125 i
i 72/1830 11.2/16.1 — 4
3/4/20/90`Elbow -.. 42.2/128
31/790 14.0/20.2 3jJ4//2t
0/StrElblow 15.514472 2
i .
3/4"/20/Straight 19.415.9'
36/915 14.0/20-2 2 i
3/'/20/90'Elbow 19.6/5.9
314 120/Straight 30.3/9.2
48/1220 14.0/20.23
314"120/90`Elbow 29.5/8.9 =;
60/1525 14.0/20.2 3472015traight 33.9110.3
4
r 3/4'/20/90'Elbow 34.1/10.4
34720/Straight d 37.5/11.4
72/1830 14.0!20.2 /'/20/90 Elbow 38.6/11.7 4
FM NOTES:
• The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NEPA 13. 13R,and 130 and FM data sheets
2-0.2-5.and 2-8.FM 1637 standard for safety includebut are not lim ted topressure cycling,corrosion resistance.flow characterisitics,vibration resistance.
leafage,mechanical and hydrostatic strength
• EXAMPLE:A 48-inch hose installed with two 30' bends and two 90' bends is permitted and considered equivalent to the data in the table shown above.In
this example,the total number of degrees is 240'.which is less than the allowable 270'.
• •
10.85 5839 Rev AG Updated 07/2019 e)2019 Vrrlaulic Company_All rights reserved_
if
, . .
victaulic,tom
5.2 PERFORMANCE — FRICTION LOSS DATA
4). Series AH2 Braided Hose with 900 Low Profile Elbows
Style AB5, AB11, AB12, ABBA and ABMM VicFlex Bracket
Maximum
Equivalent Number
Length of Length of of 90"Bends
Stainless Steel Outlet 1"/33.7mm at 7.11.78mm
Flexible Hose K-Factor . Size Sch.40 Pipe Bend Radius
inches/mm l Imperial/S.1 inches/mm feet/meters
1 i .
31/790 5.6/8.1 1 W/15 ,
13.7/4.2 , 2
— 4-
36/91t5 5,6/8.1 1/2715 17.0/5.2 2
48/1220 5.6/8.1 1/2715 I 25.0/7.6 i 3
60/1525 56/81 1/2715 33.0/10.1 4
-i-- — ,
72/1830 5.6/8.1 W/15 41.1/125 4
-11
31/790 8.0/11.5 W/20 13.6/4.14 2
36/915 8.0/11.5 1/4720 16.9/52 2
, 1
48/1220 8.0/11.5 x 720 27.8/8.5 3
1
60/1525 8.0/11.5 W/20 i
32.6/9.9 4
72/1830 8.0/11.5 %"/20 40.6/12.4 4
_ --
'
31/790 11.2/16.1 1 W/20 13.7/4.2 2
1 : .
36/915 _ 1 11.2/16.1 W/20 17.0/5.2 2
.
I-
48/1220 11.2/16.1 W/20 24.9/7.6 3
60/1525 11.2/16.1 I 14'/20 32.9/10.0 4
4 1
72/1830 112/16.1 W/20 40.9/12.5 , 4
31/790 14.0/20.2 W/20 13.5/4.1 2
' —
--i ,
36/915 14.0/20.2 °/20 16.8/5.1 2
48/1220 14.0/20.2 3/4720 24.7/7.5 3
I 60/1525 14.0/20.2 W/20 32.7/9.9 4 1 .
1 1
, .
72/1830 14.0/20.2 3'Y/20 40.7/12A 4
, !
FM NOTES:
• The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R.and 13D and FM data sheets
2.0.2.5,and 2-8.FM 1637 standard for safety include.hilt are not limited to.pressure cycling,corrosion resistance,flow rharacterisitics,vibration resistance,
leakage,mechanical and hydrostatic strength
• EXAMPLE.A 48-inch hose installed with two 30bends and two 90 bends is permitted and considered equivalent to the data in the table shown above In
this example,the total number of degrees is 240,which is less than the allowable 270 .
• •
10.85 5839 Rev AG Updated 07/2019 ei 2019 Virtaillir Company Ail rights reserved
... ,
victaulic.com
5.3 PERFORMANCE— FRICTION LOSS DATA
(VdS Series AH2 and AH2-CC Braided Hose
l Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets
Equivalent Length of Maximum Number
Length of steel pipe according to of 90°Bends at
Stainless Steel Outlet EN 10255 DN 25 3"/76.2mm Bend
Flexible Hose Size (33,7 x 3,25) Radius
mm/inches mm/inches meters/feet meters/feet
15 mm/1/2" 1
31/79020mm/3/4" 5.5/18.0 3
15 mm/''z'
36/915 20 mm/ 6.4/21.0 3
15 mm//2"
48/1220 20mm!'!+" 8.5/27.9 3
. t .
60/1525 20 mm/ 10.7/35.1 4
15 mm/'h"
72/1830 20 mm/31a° 12.8/42.0 4
VDS CEILING MANUFACTURERS LIST
AB1,AB2,AB7,A610,AB11 AB4 ABS,AB8
1 AMI No specific approval 1.Hcti
2 Armstrong 2.Knauf
3 Chicago Metallic 3.Lafarge
4.Dipling 4 Lindner
5.Durlum 5 Rigips
6 Geipel
7 Gema-Armstrong
8 Hilti
9 Knauf
10 Lafarge
11 Linder
12.Odenwald
13.Richter
14.Rigips
15 Rockfon Pagos
16.Suckow&Fischer
17.USG Donn
Series AH2 and AH2-CC Braided Hose Series AH2 Braided Hose
LPCB Style AB1, AB2, AB3, AB4, AB5, AB7, AB8, Go Style AB1, AB2, AB3, AB4, AB5, AB7, AB8,
and AB10 Brackets AB10 and AB12 Brackets
Length of Equivalent Length Maximum
Stainless of steel pipe Number of
Steel according to 90°Bends at Length of
Flexible Outlet EN 10255 ON 25 3"/76.2mm Flexible Equivalent Length of
Hose Size (33,7 x 3,25) Bend Radius Hose 1"133.7mm Sch.40 Pipe
i mm
mm/inches mm/inches/type meters/feet inches Straight Configuration Bend Configuration
15 mm/Yz`/Straig ht 1 �. 790 0.87 2.70
790/31 , 1.8/6.0 2 I
20mm/N'/Straight , 31 2.9 8.9
15mm/' 7Straight 915 1.00 2.80
91 Sl36 3.6/1 1.9 3
20mm/V/Straight I 36 3.3 9.2
1Smm/1/2"/Straight 1220 2.23 4.66
4.3114.0 3
1220/48 20 ht
48 7.3 15.3
15 mm/1/2"/Straight I 1525 2.90 6.5
1525/60 4.1/13.6 3
20 mm/1/4"/Straight 60 9.5 21.3
15 mm/'"/Straight I 1830 3.31 7.16
1830/72 5.5/18.1 3 I
20mm/N"/Straight 72 i 10.9 23.5
CCCF NOTE
• Friction loss data is in accordance with G85135.16 tested at a flow rate
of 114 titers per minute(30 gallons per minute).
f •
10.85 5839 Rev AG Updated 07/2019 CO 2019 Vtciaulic Company.All rights reserved
victaulic.com
• •
6.0 NOTIFICATIONS
A WARNINGgrimomss
A51. n(
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping
products.
• Always verify that the piping system has been completely depressurized and drained immediately prior to installa-
tion, removal, adjustment, or maintenance of any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
A WARNING
• It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use
with the intended fluid media within the piping system and external environments.
• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,and flow rate on
300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be
acceptable for the intended service.
Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage.
i
10.85 5839 Rev AG Updatpd 07,2019 t0 2019 Vietahlir Compare All rcphl<rpservei.
victaulic.com
•
7.0 REFERENCE MATERIALS—CHARACTERISTICS
VicFlex Maximum Load Values
Series AH2 Hose with 24" Bracket
Actual Length Total Load 7- Max. Uniform Load
ft
Model Size m 1 lb N Ib/linear ft N/linear m
31/790 2.6
0.8 5.2 23 ! 2.6 38
i i
36/915 0 9 5.5 25 2.8 40
48/1220 1 2 6.3 28 1 3.1 46
60/1525 155 7.0 31 3.5 51
1
72/1830 1$ 7.7 34 3.9 57
Series AH2 Hose with 48" Bracket
Actual Length Total Load Max, Uniform Load
ft
Model Size m lb N lb/linear ft N/linear m
31/790
2.6 8 6.1 27 1.5 22
36/915 039 6 4 29 1.6 23
48/122012 7.2 32 1.8 26
60/1525 1 577.9 35 2.0 29
72/1830 1 88:7 I 39 22 32
1 I
Total Load is defined as the sum of the weights of the following:
• water-filled flexible sprinkler hose with threaded end fittings, including a typical fire sprinkler
• bracket assembly (any applicable Victaulic bracket model of the relevant associated size)
ASTM C 635: Suspension System Load-Carrying Capabilities (excerpted)
Actual Length I Min.Allowable Uniform Load
Suspension System ft/m ( lb/linear ft N/linear m
Light 5.0 75.7
Direct Hung Intermediate I 12.0 181.0
Heavy 16.0 241.7 I
SUMMARY: All direct-hung suspension system duty classifications per ASTM C 635 are able to withstand the
maximum water-filled weight of the VicFlex sprinkler hose and bracket.
• •
10.85 5839 Rev AG Updateri 07/2019 :ca 2019 Vrciaulic Company.All right,resarved.
victaulic.com
7.0 REFERENCE MATERIALS —CHARACTERISTICS (CONTINUED)
Flexible Hose In-Plane Bend Characteristics
One Bend Two Bends Three Bends
OR
I i
ra
Minimum OR
rand net tic
90'
NOTE
For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose.
Vtcflex-ABI;A52-AB10
VlcFlex-AB3
I V,r1lex-AB4
-VtcFlex-AB7
.Vu Flc;,x-AB8
VicFlee-A812
VicFIx-ABBA
I VicFIcx-ABMM
• •
User Responsibility for Product Selection and Suitability Note
Fach user hears final responsibility for making a determination as to the suitability pr This produr t shall the roam dactured by Victaufic or to Victauhc sees iticatiore. All prod'acts
Vh[antic protons for a particular end-use application,vi accordance with industry to be installed in accordance with current Victaulrc mstallabon/assembly instructions_.
standards and protect specificationsand the applicable hwiding cedes and related V ct„nkc rt.ewes the right to change product speciticetions_designs and standard
regulations as well as V'ctaulie performance,maintenancesafety.and warring, equipment without notice and without incurring nbegations.
instructions..Nothing in ibis or any other document,nor any verbal recommendation. Installation
advice or opinion from any Viclaulic employee.shall be deemed to alter.vary,supersede. Reference should always be made le I-VICF LCX.AB1-AB2-AI310, -VIII LEX-Ab�1.
m waiee any provision of Victaulrc Company's slaudard conditions of sale,installation I-VWCFLEX-AB7.or I-VICFLEX-A88 for the product you arc installing.Handbooks arc
guide,orthe disclaimerintoded with ea,I'shipment of Victaulrc products for complete installation arid assembly
Intellectual Property Rights data,and air available in PUF format en our webyde at wwer.wCJaulic.coin.
No statement contained t erein concerning a possible or suggested use of any material. Warranty
product,service,or design's intended.or should be constructed,to grant any license Refer to the Warranty sectian of the current Price List or contact Vic Wait for details
under any patent o!other intellectual properly right of Vietaulic or any of its suhsidanec •
or affiliates ceeenne such use or design,cr as a recommendation for the use of such Trademarks
material,produce service,or design or the infringement of any patent or other intettechral V'u'taotic and all other Victaulrc'narks are the trademarks or registered trademarks of
property right.The terms Patented"or'Patent Pending"refer to design or utility patent, VutauGr.Company antler its atfll aced entitie, in the U S.and/or other countries
or patent applications for articles anchor methods of use in the United States and/or other
countries
• •
10.85 5839 Rev AG Updated 07/2019 el 20)9 Vtctatdic Cnmpany All rights rnsPrved
ti,co
Worldwide www.tyco-fire.com
Contacts
Series ELO-231B - 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General for any given corrosive environment.
The effects of ambient temperature, te
Des cri tion concentration of chemicals, and gas/ •
p chemical velocity, should be consid-
ered,as a minimum,along with the cor '''_
TYCO Series ELO-231B 11.2K Standard rosive nature of the chemical to which
Response,Standard Coverage Upright the sprinklers will be exposed. ,t
and Pendent Sprinklers(Ref. Figure 1)
are automatic sprinklers of the frangible An upright intermediate level version
bulb type.They are standard response, of the Series ELO-231B Sprinklers for
spray sprinklers that produce a hemi- in-rack applications can be obtained by
spherical water distribution pattern utilizing the Series ELO-2318 Upright
below the deflector. Sprinkler with the WSG-2 Guard &
The 11.2 K-factor,ELO-2318 Sprinklers Shield, and a pendent intermediate - :--
level version of the Series ELO-2318 `'---'
were subjected to full-scale,high-piled
storage fire tests to qualify their use Sprinklers can be obtained by utilizing
in lieu of 5.6 or 8.0 K-factor standard the Series ELO-231B Pendent Sprinkler
spray sprinklers for the protection of with the WS-2 Shield. If there is a pos-
high piled storage. sibility of the pendent intermediate level
version being exposed to mechanical -
Higher flow rates can be achieved at damage,a G-2 Guard can be added.
much lower pressures with the 11.2
K-factor,ELO-2318 Sprinklers,making NOTICE
their use highly advantageous in high
density applications, such as the pro- The 11.2 K-factor, Series ELO-231B
lection of high-piled storage. Upright and Pendent Sprinklers • d -,.r,
described herein must be installed
Wax or lead coatings can be used and maintained in compliance with this •
'
to extend the life of the copper alloy document,as well as with the applica-
components used in Series ELO-231B ble standards of the National Fire Pro-
Sprinklers beyond that which would tection Association(NFPA), in addition
otherwise be obtained when exposed to the standards of any other authori-
to corrosive atmospheres. Although ties having jurisdiction.Failure to do so '
wax,lead,and polyester coated sprin- may impair the performance of these "
klers have passed the standard corro- devices.
sion tests of the applicable approval
agencies, the testing is not repre The owner is responsible for main-
sentative of all possible corrosive taming their fire protection system Sprinkler
atmospheres. Consequently, it is rec- and devices in proper operating con- identification
ommended that the end-user be con-
suited
Contact the installing contrac- �+•
suited with respect to the suitability
questions. Numbersfor or product manufacturer with any (.?►1�s)
of these corrosion resistant coatings
Installation of Series ELO-231B Pendent Refer to Table A for sprinkler identifica-
IMPORTANT Sprinklers in recessed escutcheons will tion numbers.
Refer to Technical Data Sheet void all sprinkler warranties, as well as
TFP2300 for warnings pertaining to possibly void the sprinkler's Approvals
regulatory and health information. and/or Listings.
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6 AUGUST 2018 TFP342
{
TFP342
Page 2 of 6
mm) Components:
NOMKE-IN 1 - Frame
..__:1/12,7
i 314" 2 - Seal
a affrrrft NPT 1 Assembly
3 - Ca
2
2-13/16" 2 4 - Bulb
An
�
(71,4 mm) WRENCH THREAD t -j i 5 - Compression
TYP. FLATS RELIEF j 3 I Screw
� 4 ,
6 - Deflector*
f 1/2" 3/4" 5 *Temperature
ratingis
1 NPT NPT .__, 6 _-- -- indicated on
A 7/16"(11,1 mm) + 1/2'(12,7 mm) deflector.
NOMINAL MAKE-IN NOMINAL MAKE-IN
UPRIGHT UPRIGHT PENDENT CROSS
TY5851 TY5151 TY5251 SECTION
FIGURE 1
SERIES ELO-231B 11.2K UPRIGHT 314 INCH NPT(TY5151), UPRIGHT 1/2 INCH NPT(TY5851),AND
PENDENT 3/4 INCH NPT(TY5251)SPRINKLERS, STANDARD RESPONSE
Technical Item Description
Data TY5151 -Upright 3/4 in.NPT
TY5251 -Pendent 3/4 in.NPT
Approvals TY5851 -Upright 1/2 in.NPT
UL and C-UL Listed Sprinkler Identification Number(SIN) TY5151 is a re-designation for Central SIN C5151.
FM Approved TY5251 is a re-designation for Central,Gem,and
Star SINs 65251.G1871,and S2531.respectively
NYC Approved TY5851 is a re-designation for Central SIN C5851.
Refer to Table C for specific details on K-factor,(gpm/psi)(Ipm/bar) 11.2 GPM/psis(161,4 LPM/bar')
laboratory and approvals, including
corrosion-resistant status.The approv- 155°F(68°C)1
als apply to the service conditions indi- Temperature Rating°F(°C)1 200°F(93°C)
cated in the Design Criteria section.) 286°F(141°C)
Finishes Thread Size 3/4 in.NPT or 1/2 in.NPT
Refer to Table C
Physical Characteristics Sprinkler Orientation Upright/Pendent
Frame Bronze
Cap Bronze Maximum Working Pressure,psi(bar) 175 psi(12,1 bar)
Sealing Assembly..Beryllium Nickel w/TEFLON Note:
Bulb(5 mm die.) Glass 1, Refer to Table C for laboratory listings and approvals.
Compression Screw Bronze
Deflector..... . ........... Bronze TABLE A
Additional Technical Data SERIES ELO-2318 11.2K UPRIGHT AND PENDENT SPRINKLERS
Refer to Table A for additional techni- TECHNICAL DATA
cal data.
Design and Group A plastics)with a minimum
Operation residual(flowing)pressure of 7 psi(0,5
p Criteria bar)for wet or dry pipe systems. Refer
The glass bulb contains a fluid that to Table B for additional information.
expands when exposed to heat.When UL and C-UL FM Approval Requirements
the rated temperature is reached, the Listing Requirements The 11.2 K-factor, Model ELO-231B
fluid expands sufficiently to shatter the TYCO Series ELO-231B 11.2K Standard Sprinklers are to be installed in accor-
glass bulb, allowing the sprinkler to Response,Standard Coverage Upright dance with the applicable control mode
activate and water to flow. and Pendent Sprinklers are to be density/area guidelines provided by FM
installed in accordance with NFPA 13 Global.
standard sprinkler position and area/ Note: FM Approval guidelines may
density flow calculation requirements differ from UL and C-UL Listing criteria.
for light,ordinary,or extra hazard occu-
pancies, as well as high-piled storage
occupancies (solid-piled, palletized,
rack storage,bin box,and shelf storage
including but not limited to Class l-IV
� k �
TFP342
Page 3 of 6
Storage Type NFPA FM Global
Sprinkler Type Standard Coverage Storage
Response Type SR SR
System Type Wet,Dry Wet,Dry
155°F(68°C)t 155°F(68°C)t
Temperature Rating°F("C)1 200"F(93"C) 200"F(93°C)
286"F(141 °C) 286"F(141 "C)
Open Frame(that is,no solid shelves)Single,Double,Multiple-
Row,or Portable Racj Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9
Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9
Plastics
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0.8-9,and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Rolled Paper Storage(Refer to the standard.) Refer to NFPA 13 Refer to FM 8-21
Flammable Liquid Storage(Refer to the standard.) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage(Refer to the standard.) Refer to NFPA 308 Refer to FM 7-31
Automotive Components in Portable Racks(Control mode only, Refer to NFPA 13 N/A
refer to the standard.)
Note:
Ref",Ic.Tattle C for laboratory listings and app'dvfi-s.
N •Not Applicable
TABLE B
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
SPRINKLER TEMPERATURE BULB SPRINKLER FINISH
TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
155"F(68`C) Red
UPRIGHT3
200°F(93°C) Green 1,2,3,4
(TY5151 &TY5851)
286"F(141°C) Blue 3 3,
155°F(68°C) Red
PENDENT3
(TY5251) 200°F(93°C) Green 1.2,3.4
286'F(141°C) Blue 3 3a
Notes:
Listen by Undervrtiters Laboratories Inc(UL:
2 Listed by Urrderwrfter,Laboratories,Ir.,:.for rise in Canada(C-UI.
.. Aporr:.ed try FM Global(FM App,ovalri
4 Approved dy the Grt;of Nec,York INYCi ur"der MEA 291-04-F
a Lvted'Approved fora mdximu r ceil:n❑temperature',of tSi)F t6B`Cl.
TABLE C
SERIES ELO-2316 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP342
Page 4 of 6
"FITTING SIDE" that an 8 in.or 10 in.adjustable wrench Care and
TOWARDS SPRINKLER is to be used for wax-coated sprinklers.
FITTING With reference to Figure 1,the W-Type Maintenance
3 Sprinkler Wrench or the adjustable
wrench,as applicable,is to be applied TYCO Series ELO-231B 11.2K Standard
� � to the wrench flats. Response,Standard Coverage Upright
When installing wax-coated sprinklers and Pendent Sprinklers must be main-
with the adjustable wrench, additional tained and serviced in accordance with
WRENCH care needs to be exercised to prevent this section.
RECESS damage to the wax coating on the
(END"A°) sprinkler wrench flats or frame arms Before closing a fire protection system
and, consequently, exposure of bare control valve for maintenance work on
FiGURE 2 metal to the corrosive environment. the fire protection system that it con-
W-TYPE 3 The jaws of the wrench should be trols, permission to shut down the
SPRINKLER WRENCH opened sufficiently wide to pass over affected fire protection system must
s
the wrench flats without damaging the ben obtained pens fnnerom whothh propermbeaaffected
wax coating.Before wrench-tightening and all personnel may affected
Installation the sprinkler,the jaws of the wrench are by this action must be notified.
TYCO Series ELO 231 B 11,2K to be adjusted to just contact the sprin- Sprinklers that are found to be leaking
TYCard Response, Standard ,2K Stan-akler wrench flats. After wrench-tight- or exhibiting visible signs of corrosion
Upright and Pendent SStandard
Coverage
must ening the sprinkler, loosen the wrench must be replaced.
be installed in accordance with this jaws before removing the wrench. Automatic sprinklers must never be
section. After installation, the sprinkler painted, plated, coated or other-
wrenchA leak tight 3/4 in. NPT sprinkler joint flats and frame arms must wise altered after leaving the factory.
A leak be obtained. byapplying na mint be inspected and the wax coating Modified sprinklers must be replaced.
retouched (repaired) whenever the Sprinklers that have been exposed to
imum-to-maximum torque of 10 to 20 coating has been damaged and bare corrosive products of combustion, but
lb-ft (13,4 to 26,8 N•m). A leak-tight metal is exposed.The wax coating on have not operated,should be replaced
1/2 in. NPT sprinkler joint should be the wrench flats can be retouched by if they cannot be completely cleaned
obtained by applying a minimum-to- gently applying a heated 1/8 in. diam- by wiping the sprinkler with a cloth or
maximum torque of 7 to 14 lb-ft (9,5 eter steel rod to the areas of wax that by brushing it with a soft bristle brush.
to 19,0 N•m). Higher levels of torque have been damaged, to smooth it
can distort the sprinkler inlet with con- Care must be exercised to avoid
back over areas where bare metal is
Sequent leakage or impairment of the damage to the sprinklers before,
sprinkler. exposed. during, and after installation. Sprin-
Notes: Do not install any type Notes: Only retouching of the wax klers damaged by dropping, striking,
Notes: if the is cracked bulbr there coating applied to the wrench flats wrench twist/slippage,or the like,must
sprinkler a if e bulb from the bulb. With and frame arms is permitted, and be replaced. Also, replace any sprin-
the loss of liquid held from
b a small h the retouching is to be performed kler that has a cracked bulb or that has
air bubblesprinkler should bpresent.horizontally, The only at the time of the initial sprinkler lost liquid from its bulb. For additional
diameter of the air bubble is approxi installation. information,refer to Installation section.
mately 1/16 in. (1,6 mm) for the 155°F The steel rod should be heated only Frequent visual inspections are rec-
(68°C) to 3132 in. (2,4 mm) for the to the point at which it can begin to ommended to be initially performed
286°F(141°C)temperature ratings. melt the wax, and appropriate precau- for corrosion resistant sprinklers,after
Do not attempt to up for insuf- tions need to be taken, when handling the installation has been completed,to
ficient make the escutcheon the heated rod, in order to prevent the verify the long term potential integrity
plate tby under-adjustment in heg escutcheon
utcheing on installer from being burned. of the sprinkler coatings. Thereafter,
orannual inspections per NFPA 25 should
sprinkler. Re-adjust the position of the If attempts to retouch the wax coating
sprinkler fitting to suit. with complete coverage are unsuc- suffice;howeverinof inspecting
cessful,additional wax can be ordered from the floor levvel,ainstead a random sampling
The Series ELO-231B Upright and in the form of a wax stick (the end of close-up visual inspections should
Pendent Sprinklers must be installed of which is color coded). Only the be made,so as to better determine the
in accordance with the following correct color-coded wax is to be exact sprinkler condition and the long
instructions. used, and retouching of wrench flats term integrity of the corrosion resistant
coating, as it may be affected by the
Note: Pendent sprinklers are to be and frame arms is only permitted at
installed in the pendent position; the time of initial sprinkler installation. corrosive conditions present.
upright sprinklers are to be installed in With the steel rod heated as previ- The owner is responsible for the
the upright position. ously described, touch the rod to the inspection,testing,and maintenance of
Step 1. With pipe thread sealant area requiring additional wax with the their fire protection system and devices
applied to the pipe threads, hand- rod angled downward, and then touch in compliance with this document, as
tighten the sprinkler into the sprinkler the wax stick to the rod approximately well as with the applicable standards
ti
ght1/2 in. away from the area requiring of the National Fire Protection Associ-
fitting. retouching. The wax will melt and run ation, such as NFPA 25, in addition to
Step 2. Tighten the sprinkler into the down onto the sprinkler. the standards of any other authorities
sprinkler fitting using only the W-Type 3 having jurisdiction.Contact the install-
Sprinkler Wrench(Ref.Figure 2),except ing contractor or product manufacturer
with any questions.
TFP342
Page 5 of 6
P/N 50 - XXX - X - XXX
SIN SPRINKLER TEMPERATURE
FINISH RATING
501 11.2K UPRIGHT(1/2 in.NPT) TY5851 1 NATURAL 155 155'F(68`C)
BRASS
510 11.2K UPRIGHT(3/4 in.NPT) TY5151 6 WAX COATED 200 200°F(93°C)
512 11.2K PENDENT(3/4 in.NPT) TY5251 7 CLEADED 286 286'F(141°C)
8 WAX-OVER-LEAD
COATED
9 CHROME
PLATED
TABLE D
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
PART NUMBER SELECTION
It is recommended that automaticWax Sticks
sprinkler systems be inspected,tested, Ordering (for retouching wrench-damaged wax
and maintained by a qualified lnspec- coating)
tion Service in accordance with local Procedure Specify: (specify Color) color coded
requirements and/or national codes. Sprinkler Assemblies with Wax Stick for retouching(specify tem-
Limited
NPT Thread Connection perature rating) temperature rated
Specify: Series ELO-231B 11.2K Stan- Series ELO-231B Sprinklers, P/N
Warrant dard Response (specify Pendent (specify):
�/ or Upright) Sprinkler, SIN (specify), Red for 155"F(68`CI . _ . .56-065-1-155
For warranty terms and conditions,visit (specify temperature rating), with Blue for 200`F(93-C)
2
(specify)finish,P/N(specify from Table and 86°F(141°C1 .. 56-065-1-286
www.tyco-fire.com.
D) Notes: Each wax stick is suitable for
Sprinkler Wrench retouching up to twenty-five sprinklers.
Specify: W-Type 3 Sprinkler Wrench, The wax used for 286°F(141°C)sprin-
P/N 56-895-1-001 klers is the same as for 200°F(93°C)
sprinklers, and, therefore, the 286°F
(141°C)sprinkler is limited to the same
maximum ceiling temperature as the
200°F(93°C)sprinkler, such as 150°F
(66°C).
e Y e
TFP342
Page 6 of 6
1400 Pennbrook Parkway,Lansdale,PA 19446 Telephone♦1-215-362-0700 ens /�
07018 n Johnson Controls.Alt rights reserved.Ali specifications and other information shown wecurrent as of document revision date and are sub}ect toehange without notice. Johnson �JJ���(�`�