SUBMITTAL DATA
Order#: Date: 06/20/2019
Project: Planet Fitness Tigard, OR
Project #:
RECEIVED
Submitter: Saul Diaz SEP 3 2019
UPG National Accounts CITY OF TIGARD
5005 York Dr, BUILDING DIVISION
Norman, Oklahoma 73069
405-419-6447
fi%14 )x''
IG�g5�� -35 �"
RpZ �SS, S
S101i14S
1�Cs.o4o �
�
µ nformation is subject to change wthout notice.Check local codes. Printed 06/20/2019
Date
06/20/20`19
Project Name
Planet Fitness Tigard,OR
Project Number
A'.lient/ Purchaser
Submittal Summary Page
Qty Tag # Model # Description
1 RTU-1 ZJ150N18R2D5EAA1A1 12.5 Ton, Single Packaged R-410A Air Conditioner, High Efficiency,
Two Stage Cooling, 12.0 EER, 180 MBH Input Aluminized Steel,
Two Stage Gas Heat, 208/230-3-60
• Dry Bulb Low Leak Economizer w/Barometric Relief and Power
Exhaust and Hoods (Bottom or Horizontal End Retum Only)with
Economizer Fault Detection &Diagnostic(Meets ASHRAE 90.1-
2013, IECC 2015, California Title 24, AMCA 511).
• 5 HP High Static Belt Drive Blower
• Standard 2"Throwaway Filters
• IntelliSpeed control of the VFD based on stages of cooling
(Provides Single Zone VAV Fan Operation as defined by ASHRAE
90.1 section 6.4.3.10)
• Smart Equipment Controller including Discharge Air, Return Air,
and Outdoor Air Temperature Sensors.
• Non-Powered Convenience Outlet
• HACR Circuit Breaker/Disconnect
• Return Air Smoke Detector(Bottom return only)
• Micro-Channel "all-aluminum" condenser coil, Copper
tube/aluminum fin evaporator coil
• Composite Drain Pan - Front Connection
RTU-1 1 RC04Roof Curb +� Irisulat • II Peter ed hocked Down
1 RTU-1 2AQ04700524 CO2 Space/Wall Mount Accessory
1, RTU-1 2EC0402 z. FC S uu1 g instilled
al a (Includes two tteetuees TWQ11 .....sensors)
1 RTU-2 ZJO78N12R2D5EAA1A2 6.5 Ton, Single Packaged R-410A Air Conditioner, High Efficiency,
Two Stage Cooling, 11.8 EER, 120 MBH Input Aluminized Steel,
Two Stage Gas Heat, 208/230-3-60
• Dry Bulb Low Leak Economizer w/Barometric Relief and Power
Exhaust and Hoods (Bottom or Horizontal End Return Only)with
Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-
2013, IECC 2015, California Title 24,AMCA 511).
• 2 HP High Static Belt Drive Blower
• Standard 2"Throwaway Filters
• IntelliSpeed control of the VFD based on stages of cooling
(Provides Single Zone VAV Fan Operation as defined by ASHRAE
90.1 section 6.4.3.10)
• Smart Equipment Controller including Discharge Air, Return Air,
and Outdoor Air Temperature Sensors.
• Non-Powered Convenience Outlet
• HACR Circuit Breaker/Disconnect
• Return Air Smoke Detector(Bottom return only)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Qty Tag# Model # Description
T -s
• Micro-Channel "all-aluminum" condenser coil, Copper
tube/aluminum fin evaporator coil
• Composite Drain Pan - Front Connection
4, 2 111-00471 -,
Roo Gut t �" �h Ftat U�r atat i, utt 1�
` oiled
1 RTU-2 2AQ04700524 CO2 Space/Wall Mount Accessory
RTU-2 2EC0402 al Et►thalpy l lt� talt � � �two4u m ity s r soil
a�� �..... �.�,� ._._._� �..... s s �;•
6 RTU- ZJ120N18R2D5EAA1A1 10 Ton, Single Packaged R-410A Air Conditioner, High Efficiency,
3,4,5,6,7,8 Two Stage Cooling, 12.0 EER, 180 MBH Input Aluminized Steel,
Two Stage Gas Heat, 208/230-3-60
• Dry Bulb Low Leak Economizer w/Barometric Relief and Power
Exhaust and Hoods (Bottom or Horizontal End Return Only)with
Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-
2013, IECC 2015, California Title 24,AMCA 511).
• 3 HP High Static Belt Drive Blower
• Standard 2"Throwaway Filters
• IntelliSpeed control of the VFD based on stages of cooling
(Provides Single Zone VAV Fan Operation as defined by ASHRAE
90.1 section 6.4.3.10)
• Smart Equipment Controller including Discharge Air, Return Air,
and Outdoor Air Temperature Sensors.
• Non-Powered Convenience Outlet
• HACR Circuit Breaker/Disconnect
• Return Air Smoke Detector(Bottom return only)
• Micro-Channel "all-aluminum" condenser coil, Copper
tube/aluminum fin evaporator coil
• Composite Drain Pan - Front Connection
3�4y5, RC �� " t� � � f
67,8
6 RTU- 2AQ04700524 CO2 Space/Wall Mount Accessory
3,4,5,6,7,8
:RTt 2EC� � I Etttrtalp Fuld lid •� !t�lty�SensGr
3,4 \
NOTES:
Notes
Equipment start-up and commissioning by a factory trained technician is recommended.
Contact your supplying distributor or sales representative for additional information &guidance.
tot
WARNING:Cancer and Reproductive Harm-www.P65Warnings.ca.gov
Information is subject to change without notice.Check local codes. Printed 06/20/2019
■ V RK® Predator 3-12.5 Ton Package Page:4
✓ York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
Cooling Performance
Total gross capacity 170.8 MBH
Sensible gross capacity 121.3 MBH
Total net capacity 155.3 MBH " ``
Sensible net capacity 105.8 MBH l
Efficiency(at ARI) 12.00 EER
Integrated eff.(at ARI) 15.00 IEER •
Ambient DB temp. 95.0 °F
Entering DB temp. 80.0 °F
Entering WB temp. 67.0 °F
Leaving DB temp. 57.5 °F
Leaving WB temp. 56.1 °Ft
Power input(w/o blower) 11.50 kW 4
Sound power 85 dB(A)
Refrigerant
Refrigerant type R-410A ,
Sys1 10 lbs 8 oz
Sys2 9 lbs 12 oz
Gas Heating Performance 12.5 Ton
Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and
Heating output capacity(Max) 144 MBH each rooftop is completely computer-run tested prior to shipment.
Supply air 5000 CFM Unit Features
Heating input capacity(Max) 180 MBH
Leaving DB temp. 86.7 °F • Two Stage Cooling
Air temp.rise 26.7 °F • 180 MBH Input Aluminized Steel,Two Stage Gas Heat
SSE 80.0 % • Full perimeter base rails with built in rigging capabilities
Stages 2 • Unit Cabinet Constructed of Powder Painted Steel, Certified At 750 Hours
Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards)
Supply air 5000 CFM • Scroll Compressor[s]
• Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and
Addl.Unit Losses(Options/Accessories) 0.82 IWG Hoods(Bottom or Horizontal End Return Only)with Economizer Fault
Blower speed 1508 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California
Max BHP of Motor(including service factor) 5.75 HP
Duct location Bottom Title 24,AMCA 511).
Motor rating 5.00 HP • Slide-Out Blower/5 HP Belt Drive Motor Assembly
Actual required BHP 4.87 HP • Solid Core Liquid Line Filter Driers
Power input 4.54 kW • Unit Ships with 2"Throwaway Filters
Elevation 0 ft. • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters.
Drive type BELT
Requires field-supplied drive true • Non-Powered Convenience Outlet
• Short Circuit Current:5kA RMS Symmetrical
Outside/Mixed Air • Through-the-Curb and Through-the-Base Utility Connections
Outside Air Cfm 320 CFM • Single Point Power Connection
• HACR Circuit Breaker/Disconnect
Electrical Data • Return Air Smoke Detector
Power supply 230-3-60 • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin
Unit min circuit ampacity 79.9 Amps evaporator coil
Unit max over-current protection 100 Amps • Composite Drain Pan-Front Connection
Dimensions&Weight • Tool-free maintenance with features like hinged doors for all-access panels,
Hgt 51 in. Len 120 in. Wth 59 in. slide-out blower and blower motor tray
Weight with factory installed options 1535 lbs.
Clearances BAS Controller
• IntelliSpeed control of the VFD based on stages of cooling.Provides Single
Right 12 in. Front 36 in. Back 36 in. Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10.
`Top 72 in. Bottom 0 in. Left 36 in. J • Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Note: Please refer to the tech guide for listed maximum static pressures Air Temperature Sensors.
,{��p�gy{ Standard Unit Controller: Smart Equipment Control Board
AMMAN 14J4IM£7Ud � 2
x�uI�CERTIFIE L� QUA�!nl t • Safety Monitoring-Monitors the High and Low-Pressure Switches,the
Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Failures, Safety Lockouts and Repeated Limit Switch Trips.
Warranty
• One(1)Year Limited Warranty on the Complete Unit
• Five(5)Year Warranty-Compressors and Electric Heater Elements
• Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger
Information is subject to change without notice.Check local codes. Printed 06/20/2019
ayoRK® Predator 3-12.5 Ton Package Page:5
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#: RTU-1 System: ZJ150N18R2D5EAA1A1
Factory Installed Options
ZJ150N18R2D5EAA1A1
Equipment Options Option(s) Selected
:40z �J Effeie� AA€r� .Prottt4' ategory"
120 EER �`
Nominal Cooling Capacity: 150 12.5 Ton
Two Stage Cooling
\. . t I ..._and N�na1 Heat C pac� nPut Alur ized Stee Two Stade Gas Heat
5 HP High Static Belt Drive Blower
Blower Option: R IntelliSpeed control of the VFD based on stages of
cooling (Provides Single Zone VAV Fan Operation as
defined by ASHRAE 90.1 section 6.4.3.10)
.,r
208/230-3-60
Dry Bulb Low Leak Economizer w/Barometric Relief and
Power Exhaust and Hoods (Bottom or Horizontal End
Outside Air Option: D Return Only)with Economizer Fault Detection &
Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,
California Title 24,AMCA 511).
• ion Powered Convenience Outlet
Opti \� a�
HAC ircuit Breaker .nnect.
Sensor Options: E
Return Air Smoke Detector(Bottom return only)
.......',,..... y .�
. • ;_....,��s �... ..Sensors,:.'..
Micro-Channel"all-aluminum"condenser coil, Copper
Refrigeration: A
tube/aluminum fin evaporator coil
Addoptions" F "�
„ > Sta A4 ThrowawayFilters
Cabinet Options: A Composite Drain Pan-Front Connection
71,47 _ g ::
du aeration*
,tea
Field Installed Accessories
O 1BD0408- Burglar Bars (32.0 lbs) 0 1CV0414 -Concentric 0 1FE0412 - Flue Exhaust
O 1CV0404- Concentric Diffuser,Side Discharge,18X32 Extension Kit (14.0 lbs)
Diffuser,Flush Mount,18X28 0 1CV0415 -Concentric 0 1FF0414 -2" Only Metal Filter
O 1CV0405- Concentric Diffuser,Side Discharge,18X36 Frame Kit (16.0 lbs)
Diffuser,Flush Mount,18X32 0 1CV0420-Concentric 0 1 FL0402- Permanent 2" only
O 1CV0406- Concentric Diffuser,Specialty,24X24 Filter Kit(Includes (4) Four Filters)
Diffuser,Flush Mount,18X36 0 1CV0421 -Concentric (2.2 lbs)
O 1CV0413- Concentric Diffuser,Specialty,28X28
Diffuser,Side Discharge,18X28 0 1CV0426 -Concentric
Diffuser,Specialty,24X24
Information is subject to change without notice.Check local codes. Printed 06/20/2019
lupoRK® Predator 3-12.5 Ton Package Page:6
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#: RTU-1 System: ZJ150N18R2D5EAA1A1
4 O 1 GP0405-Gas Piping Kit for 0 ASC Services- Charges for this 0 S1-03103518000 -Temp &
Bottom Gas Supply Connection Service are Applicable. humidity sensor, 120mm x 80mm,
with External Shut-Off(includes: Application, Startup& no display, modular jack,
- Internal gas pipe, fittings, gas cock Commissioning (ASC) Services warmer/cooler dial, JCI logo (0.4
& panel gaskets) (10.0 lbs) Available with Daily Fee Plus lbs)
O 1 HA0442- High Altitude Kit for Expenses. This Service Provides 0 S1-03103519000- CO2 sensor,
Natural Gas (1.0 lbs) a 90 Day DOA Benefit When 120mm x 80mm, no display, screw
O 1 HA0443- High Altitude Kit for Completed by a Factory Certified terminals or modular jack, no logo
Propane (1.0 lbs) Technician. Contact Your (0.2 lbs)
O 1 HG0425 - Hail Guard Kit- Distributor, Dealer, or Sales 0 51-MP-PRTKIT-OP- MAP
Diamond Pattern (37.0 lbs) Representative. Distributors Can (Multiple Access Portal) Gateway
O 1HG0434 - Hail Guard Kit- Call 1-877-874-7378 for an ASC Kit- Replacement MAP gateway
Provent Style (30.0 lbs) Quote. protective case, lanyard and
O 1 NP0459- Natural Gas to 0 S1-02812364700- Blower Sheave communication cable. Use only to
Propane Conversion Kit(2-Stage) for 12.5 Ton High Static Field replace worn or damaged
(2.0 lbs) Installed Drive (3.0 lbs) components. (0.3 lbs)
O 1RC0470 - Roof Curb- 8" High, 0 S1-03102529000 - Non- 0 51-SE-COM1001-0- Field
Flat, Uninsulated, Full Perimeter Networking Wall Sensor-Allows Installed Communication Card for
(Shipped Knocked Down) (135.0 remote sensing and control from Simplicity SE control. Can be field
lbs) single or multiple zones. (0.2 lbs) configurable for BACnet, N2 or
• 1 RC0471 - Roof Curb- 14" High, 0 S1-03102529004- Non- ModBUS MSTP (0.0 lbs)
Flat, Uninsulated, Full Perimeter Networking Wall Sensor with 0 S1-TBSU32P7S-Source 1
(Shipped Knocked Down) (135.0 Over-ride button-Allows remote Branded LX Series, Up to 4 Heat/
lbs) sensing and control from single or 2 Cool, Electronic 7 Day
r,
O 1 RC0472 - Roof Curb, Transition- multiple zones. Override allows Programmable (1.2 lbs)
Sunline 7.5T thru 12.5T to setpoint to be overridden for 2 0 51-YK-MAP1810-0P- MAP
Predator 3.0T thru 12.5T (Shipped hour time period. (0.2 lbs) (Multiple Access Portal) Gateway-
Assembled) (200.0 lbs) 0 S1-03102529006 - Non- For use with SimplicitySE Control.
O 1 RC0476- Roof Curb- 24" High, Networking Wall Sensor with (0.2 lbs)
Flat, Uninsulated, Full Perimeter Setpoint Adjustment and Over-ride 0 51-YK-MAP1810-0S-Stationary
(Shipped Knocked Down) (135.0 Button-Allows remote sensing MAP Gateway (Includes MAP
lbs) and control from single or multiple Gateway, Field Bus Adapter,
O 2AP0402 -Air Proving Switch (1.0 zones.Allows setpoint to be Mounting Bracket and 100 to 240
lbs) adjusted ±5° F. Override allows VAC Power Supply). US-
•
2AQ04700524- CO2 Space/Wall setpoint to be overridden for 2 compatible counties. (1.9 lbs)
Mount Accessory (5.0 lbs) hour time period. (0.2 lbs)
O 2AQ04700624- CO2 Unit Mount 0 S1-03103489000 -Temp sensor,
Accessory (4.6 lbs) 80mm x 80mm, LCD display,
O 2DF0403- Dirty Filter Switch (1.0 screw terminals, adjustable
lbs) setpoint, JCI logo (0.1 lbs)
O 2EC0401 - Kit, Single Enthalpy 0 S1-03103490000-Temp sensor
Field Installed (1.0 lbs) w/Economizer FDD, 120mm x
• 2EC0402- Kit, Dual Enthalpy 80mm, LCD display, screw
Field Installed (Includes two terminals, adjustable setpoint, no
humidity sensors) (1.0 lbs) logo (0.0 lbs)
O 2LA04702424- Low Ambient Kit 0 S1-03103516000 -Temp&
humidity sensor, 120mm x 80mm,
(3.2 lbs)
LCD display, screw terminals,
O 2SD04700824-Smoke Detector
warmer/cooler dial, JCI logo (0.4
Kit w/Mounting Hardware for lbs)
Supply Air(Horizontal/Downflow) 0 S1-03103517000-Temp sensor,
Only(9.4 lbs) 120mm x 80mm, no display, no
dial, screw terminals, no logo (0.4
lbs)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
. -
Predator 3-12.5 Ton Package , . Page:7
10 4 i y RK
York Single Package R-410A Air Conditioner
-----
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
Consolidated Drawing
3 4 5 15 2 8 9 10 II 12 13 14 15 15,
, .NOTES: I 0p66A716f,, CEN2ER OF 56414.17
4017 04)5008 11SE 017 14757-32.61 ----..- PONHAOE 7 7''7-- [SCAT 54$ 194SE UNIT: 4 POINT CORNER OARS 11.941 :BASE HNITI . .
. .
. „ I 2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS 1826,81 I . IFi6NT (1851
7 WA'. 177421 7 7 . ,
8 C IL
. .
i 4 i
! ' 1
3 MIN, CLEARANCES TO EE 653
. RIGHT SIDE: 12 1305) -. I
1113,5; . 1
114915 1443 6361 55 11295 41 25 3 )44' 71-1 755 .01 447 11577 ' 46.6 (2977 449 1-1541 [ 1
: .
1.1,51 SIR: 36 [915) i ir - _ 1.8,- 1 ,?..5 212.21K 1465 16461 5! 11255,41 25 5 1942,71 1 2(4 11231 393 1165) 471 12.51 355 1161) 1 1
.. 1 ,1
FRONT. 36 ISIS) 1158 1
,
. 12.5 Lips I2,0 15811 48 1121921 24 160,61 244 1!091 204 11n] 419 1173) 359 11561 I 1
: !
TOP: 72 11830] I-,L,- 18,00 r-- 12,5 DURO 1215 15511 46 1116841 26 4560,41 259 11187 27/71241 1 35, 1(591 1 328 1149) 1 1
BOTTOM, 0 [01 I:, 1457.211
6.621 10 riN 1469 16921 55 111431 25,5 1641.71 , 312 11421 314 11451 1 414 1199) 1 'I0 14411
I [
=4,
,
A. TO REMOVE THE SLIDE-ONT DRAIN PAIN A REAR CLEARANCE OF [173,31 --- - -1 12.5 7.$1,29 1478 16241 43.25 71263,21 24.5 1422,31 1 271 1123) 343 1156) 1 453 12.1i-h3TIM) 1 4 1
7 I DO in (15/B ,sol IS 8401118CP. IF SPACE IS ONAVAIIAHIE I'll ,
31818,81. ' i,-. i
, .
DRAIN PAN COO BE REMOVED THROUGH THE FRONT BY SEPARATING 1.1 i 18/ ALTERNATE CCNDENSATION DRAIN
5.31 I . . , .
THL CORNER WALL. A . e . .
. .
. .
5 FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES 1---, in:Hz!!,11! ,.11N r 10.so
...4 '18.26 . .
CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 2423 1 :s 1 1.266.fl 1 H43,61 5 .
. :
' 1 1 6. DOWNFLOW DUCES DESIGNED TO 111 ATTACHED TO ACCESSORY (61541 1 19 T
:11 1 11 allt 011111111:M 1/51:1111:1 IL
200 CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT FROM MI5 . I it, ,p 24.00 .• :
. .
.
. i 0 ,
1 H 1 IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED OF CROSS BRACES, FFAN6E3 I - :T-7 RH L, ,.„ ., 1 Alki I !!,-if-ii !.V1 HII!'If
,,,I,: , , 0,,,,o, ' !•,7•.,,,_1 74,:..',1,::C:t. .,,,,,y,,!1,,,,-, , 7
, 1 AS 3361 ON ACCESSORY ROOF CLTOS.
I 1 1, SIDE Ducr FLOUSES ARE 0.75' HIGH. .411- i :R(6'.i .•J.1 :1 i 1 611.14,,ielili! t,!J,11! !,
....., : :
, 1BOTTOM DUCTS 10 NOT HAVE 1LAN6ES. LEFT . . 01 i. • E 1 . .
. .
. .
. .
8. MINIMUM CONDENSATION TRAP 31 HT SHALL DE 1,5 TIMES ,_i_, • 1
T463,111 -..., .
101N111 !Ire,. r
. 11 . :
. ,
28.25 i i
, 71 i7H,Di , •
THE LOWEST NEGATIVE STATIC. 1. ‘,17
: i 1
0, DIMENSIONS IN f 1 ARE IN MILLIMETERS OP 74 ,,,614 , .1 1 ...,iii.. . . . . . 1. . ,
.
1 G : 10. OPTIONAL CCIL GUARDS, POWER EXHAUST, 6A2 NEAT, (.0.(5 / 19.14 ,, ,i lowiniai,iiir 1,,,H,1„I.ii,HI 1
. ...---f 2 .O.,'.. ;! .....;! ;;; ,:;U;.1,',!I ;- '
;ARL, :. ,1 , • '''
IN, T I(533,1J ;;; ; .1,,1,,,,1 1 II, . 1 ,,,,EF.,11111111.11111111111 I. ri
....... , , >
ECONOMIZER, DISCONNECT SWITCH, CONVENIENCE OUTLET, 1518.o)2:1 [4
-- 1486.21 11-14 1 \ ....7=. 5.PP'Y •
r.Mal '
5 : AND BAROMETRIC REUSE t FRESH AIR HOODS SHOWN, I [511.61 F435,41 I \ 1 1 IM01..!11r1F111!OLLII!,,16 :, iffii AJ" .1.
'''4€7'in..1), ,... , i - i
, ) IA.0f: 1 i
.41.... EXCEPT NP/AU :HEAT PUMP1 UNITS. 01 ,
\
\ FRONT C i . ,,--- i4W11
i4.41 •- i 1-10TTOM CAS ,nromminim 1 1 1
[367,6) 1 \
DIRECTION OF AIRFLOW 1 .--1,-16.39 , SUPPLY ENTRY 02.0 150,81 -..1 1.... 2
6.0G
. ,
L , I 141 '6 4/ 1 5 ,-Bull-09 DOPY
5.16 , 113,27 I v 1
f ..-Y ] :
1 I POWER 02.50 163.51 1131,11
1 S CENTER Or GRAVITY [436,81 ,.. .-1,
1 --
1 L;40; 11 CONTROL 371 011015 122,231 (317,61 1803,4)
, .
' 1 ' 1
FIEMLIPARTIALSEWk
I
i X1. 1
• 101!..,111Elt 11INTAKE HOOD NOT SHOWN IN THIS 41EW1
1 D!REONNECT TWITCH "1 4' . .
. .
1 i
301540 AIR--- (1 14086
118 SC ---55- „58.09 -I • •
1 I ! /NTAKE moon \ \
' • r
, , (SRI i ONAL) 5 414449 111187 0/.5 1611.51-5\ 1804B,31 114177,21
5 . . .
,
: .
ERES6 4117 H0007- "7 \/-
.: 1. ECONM.219 ',, '
\ 47077E9 ACCESS 15
• -:...... . . .
70157.0114U , :
IMPONNONOMMMMVII .,..., k,,,, \ ,-;,;FILTER/ , "2
.
[ :
: . :
. .
. . f653•31 • I irt,11. ?AWL) 55
COMPPE5 P. /
.1,01415117 SCOP 1 [
741.01 ENTP"00 875 12.2.231-`-- [,4- : 1 ADEDDA 1 1 4.r-VAS INC.7.4 ..= .
• ,
, . .
: D • I L. ACCESS
I D 1
.. 7 •
. . ,.... ,
I ,
.. . ..._....,_
_ .
. :
. .
: .
. .
. • . . ROWER ENTRY 02,50 (763,51- ,,,`•1
o - (1289.11
.-7-)7L5-2"---a----
ER:5[4 MP,- 1 -,...-,.....A---___-
.. .
. , ... .. . i>-,,,
,.
, ,-,
•-,,: 1-1524"SECTION PI 7-,
. . :
:
• / ' .. I REUSS 2- 1.7-5.
. . : .
I -411 DARC41171.1C RELIEF HOOD,-1
i C flkif
45154 q.2)232.91 5"7 9P44$HODER F.160.51 / 7 r.-. AL:2J, _ B.774c'7
„. i 5 [ [ , .., 45977
1021 i 06011 4
,/ /1
/ / 1.7-2/ 31 11 rI 13
. ,
UEFINEW CO119.1-41971CC OUTLET COVER---' / 1 1,6•23,4) 1 1 1:88 13
„
1281,1i HA98,6) \ 1 1
/OPT 118141 I / 1 Cl DETAIL A ran i , :•
Lou FPT / I DRAIN IOCATION T-r"APST \--COIL GUARD
/
5L/'I\ {OPTIONAL
,
CONVENIENCE 834181-44 ) [ ,
P [ he 1Th' POWER(21/531 00.875 122,231 1.7.- 43 OD
12260.611 Him
_1 . . ,
I T Mk ' . .
/ M, ' l'3' \ (OPTIONAL FRONT COIL GUARD NOI SHOWN 1N /HIS VIEW1
,7-.It 5 ' 1
1 kJt
1 1135,01 1 --, ZAFYY AND 1,1° q,,r DAT,:
CNARACTER,ST,O. iY•yi " RE01310A RECORD o DA 47 END MIL,,,, LL„ 77.noproe75777791:77111111,1 ItA111/1 el.or 11[111:1”,1:11 11,1f1:11111T1 il fr.0111 RI 111119.fi 1:11111:11i 5
i tC ti-: iN,t,,,:/i AMU M:11 NV 1,PI..AI Or OK 1.11.10911 MP:. W.,1g1 t::14,1.1:11Ellf III1A116 61 401:143 MIK:1,1 ,
1 ti 1' f"---','",'", ,I -21-13 WED 17314FLOW HOCD 1711 CRUSH 7.112 4 BAROMETRIC REI.IEF
G„ ' 2449/ SD 1ILP 17.1 152777598417777„741.3.
, , 'MEM
SCOMITTAL DWG, FRHATON, 17744 2.0•1 API/LICARI. ! I
. , ‘54-7 0 31105-24.181ADDED ET 724 01€45 70 TRUE I 45351 LOP 5M0 AC ",,A41(4""
A 1 m29,,,,, C 101-26-11 ADDED DC890 4440'I DIMENSION iN TOP 71471
10 BCE -7 e54 ,3'4, . W COIL, 50' CAB in.!NOT APPLICABLE 1 A 1
. . ' 1
fROJi.:Cle,:l + , , ,
DETPLA , 0 107-24-12 1:00415ED ACCESS PANEL 71071.5 4;13105 1,0 911 DOE 5. .67,777 .11e7.14 .1:PINSON CONTROLS '4'
: [ SCALE 0.300 777707 417 fa-- E L509-,4-2 31078 P21.1 41.117 !C5 TARS L;22311 40 DU Doc c..R. R Nkti$T411111 le
597.7477 2794.17.144515575 UST-PRED-V15 0i-1 1 1
i I iv -1,-- ----- fp's-n.-13 CHANGED 74!59 111,41)771.8473 1 43 35 10 RCP BOB 741,1 0_015 404474,01 3M 154.79 191
I 2 $ 4 5 0 7 3 4 10 ' II 12 i 3 54 15 .4 .
•
•
Information is subject to change without notice Check local codes. Printed 06/20/2019
YORK® Predator 3-12.5 Ton Package Page:8
. .24
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAAIA1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
■ Component Locations
Cooling With Gas Heat(6.5 Through 10 Tons)
Smart Equipment1n control board Filter drier
Disconnect location Filter access
w/screw connector for T-stat (2"or 4"filter options) (solid core)
wiring and network connections (optional disconnect switch)
Terminal block for Micro-Channel Aluminum
hi-voltage connection
Tube/Aluminum Fin
Condenser
Second model / ` €.a
nameplate r i ;
inside hinged Slide-out motor and
access panel ` a 1' blower assembly for
a^ �' easy adjustment
Dual stage ry ,' . and service
cooling for ® ,t
;g Belt-drive
maximum 1 ,( blower motor
comfortVC! TisPI,3 VFD location(optional)
\ Power ventor motor
Compressor#2 ;
access(high- € -,r t- a' 20-gauge aluminized
efficiencyiii t '�� „ r<'
f . �� steel tubular heat
compressor) -;;;:' •. exchanger for long life
''' S, ' a (stainless steel option)
r '
Two-stage gas
Base rails vv/forklift heating to maintain
slots(three sides) Slide out drainpan warm,comfortable
and lifting holes temperature
with 1"NPT,
Roof curbs in eight-and female connection Intelligent control
fourteen-inch heights.Roof..../"......../"....../ 74 board for safe and
curbs for transitioning from efficient operation
York SunlineTM footprint to Side entry power Compressor#1 access p
Toolless and control wiring (high-efficiency compressor)
the ZH/ZJ/ZR/ZU/ZW/ZK door latch
Series footprints knockouts
are also available(field installed accessory)
" Information is subject to change without notice.Check local codes. Printed 06/20/2019
Predator 3-12.5 Ton Package Page:9
yo
K York Single Package R-410A Air Conditioner
a
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
- Low Leak Downflow Economizer
_ Low Leak Downflow Economizer(shown with optional Power Exhaust)
{lfft¢
„! f`" -
- ' , Im o � ,--
I i I " ,
Fresh Air Hood
`` il II iL. - _ (included))y-,,,i i Ii � —j
41
", ' _. -----IS ,tY, �.
ri--
w.- ^-.�
Low Leak Economizer(included) i' ,°
Power Exhaust(optional)'
Barometric Barometric Relief
Relief Damper Hood (included)
(included)
Low leak economizers are capable achieving low
leakage rates of 3 cfm/sq. ft at 1"of static pressure,
meeting or exceeding the following standards:
ASHRAE 90.1-2010
ASHRAE 62
AMCA 511 (licensed as Class 1 A damper)
International Energy Conservation Code (IECC)
California Title 24
The outdoor intake opening shall be covered with a
rain hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is
also possible. Dampers shall fully close on power loss.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
tv yoRK® Predator 3-12.5 Ton Package Page: 10
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#: RTU-1 System: ZJ150N18R2D5EAA1A1
Factory Installed Power Exhaust
SP-in.-wg.
;51
0 0 0 0 0 0 0 0 0 0
•••.
0
0
NJ0
0
0
NJ
vi0
0
0
m
-n
c) el irn
Oic
r
m c
Lu
Ui00
on
00
0
x
ta
. . „ . . , . . .
o
o
BHP
- Information is subject to change without notice.Check local codes. Printed 06/20/2019
YO RK® Predator 3-12.5 Ton Package Page: 11
York Single Package R-410A Air Conditioner
Project Name:aPlanet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: I System: ZJ150N18R2D5EAA1A1
Seismic Certification
SPECIAL SEISMIC CERTIFICATION fdikt
Johnson zip!
((*)} DCL OF NON-STRUCTURAL
Controls
COMPONENTS AND SYSTEMS
CERTIFICATE OF COMPLIANCE
Dynamic Certification Laboratories has qualified the listed packaged rooftop units as CERTIFIED for seismic
applications in accordance with the following codes and standards:
CBC 2013, IBC 2012, ICC-ES AC-156 2012, ASCE 7-10
The following model designations are included in this certification. A complete list of certified models,options,
and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories,
provided by the equipment manufacturer upon request.
Unitary Product Group Packaged Rooftop Units (UPG)
Seismic Qualification Testing was conducted in accordance with and in strict adherence to the standards set
forth within the American Society of Civil Engineers(ASCE 7)by the independent approval agency,Dynamic
Certification Laboratories. The above referenced equipment is APPROVED for seismic applications when
properly installed and used as intended.
The basis of this certification is through testing of the active and energized components per AC156. This
certification covers multiple UPG brands,including York,Johnson Controls,Coleman, Luxaire,Evcon,Fraser-
Johnston and Ready Ship.
The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response
Acceleration,Sds„as determined by the ASCE 7 seismic maps. Various installation locations/isolation
configurations are covered under this certification,limited by the Sds value stated in the following table. A
seismic importance factor,ip,of 1.5 applies to this certification to include essential facility requirements and life
safety applications for post event functionality. The units are approved for both a rigid and flexible mount
configuration.
Maximum Design Stis Values of UPG Packaged Rooftop Units
Series Model Tons Sds(g) Fp/Wp
ZR/11/211/ZOZW/ZU/ZT/EA3* 037 3 2.5 1.88
ZR/Z.VZH/ZiqZW/ZUIZTtiA4* 049 4 2.5 1.88
ZR/2.1/21-i/ZirdZIN/ZU/27/.1A5* 061 5 2.5 1.88
ZR/Zi/ZiliZF/X13/Zicii2W/214125/XA/106* 078 6.5 2.5 1.88
ZR/ZJjZWZF/XP/ZK/ZW/ZU/ZS/XA/J07*/T" 090 7.5 2.5 1.88
ZR/21,1211/2F/XP/2K/ZW/ZU/ZS/XA/108* 102 8.5 2.5 1.88
ZR/Z1/214/Z.F/XP/EK/ZW/ZU/Z5MA/J10*/T* 120 10 2.5 1.88
ZRrLJ/ZH/ZF/XP/ZK/ZW/ZUJZ5/XA/J12 VT* 150 12.5 2.0 1.50
Page 1 of 2
iNnarnic Certification Laboratories 1315 Greg Street,Some 109,Sparks,NV 29431—Or 775-352-5065 www_shaketest.00rn
Information is subject to change without notice Check local codes. Printed 06/20/2019
YORK® Predator 3-12.5 Ton Package Page: 12
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
Seismic Certification
SPECIAL SEISMIC CERTIFICATION 010
Johnson
Re)) DCL OF NON-STRUCTURAL
COMPONENTS AND SYSTEMS Controls
CERTIFICATE OF COMPLIANCE
VdRageleNer MEM
Table of Seismic Design Parameters
Site Class F. 1, ap R z/h
D 1.0 1.5 2.5 6.0 1.0
Site and Project Requirements
it is the responsibility of the Design Professional of Record to:
• Provide engineering for the anchorage and restraint of the unit
• Validate Certification Design Parameters with actual site conditions
• Provide engineering of all equipment support structures
• Confirm component configuration
Certification Issued by: Dynamic Certification Laboratories
Document Control Number 90300-1107-A(rev.1)
Original Issue Date: 9/2/11
Revl.Issue Date: 3/26/14
5, S5220 Z.
3 id e#""'"'*—‘ .Faeorf Carter
t COONNeNue PNAKI Mertagef
or. =
mutwm,(0'004,Imovccoted
Dr.Ahmed itani,SE
Dynamic Certification Laboratories
Page 2 of 2
Dynamic Cierbikatibin Labrratories 1315 Greg Street,Suite los,Spat**,NV 99431- 775-356-5055 www.s.haketiest.com
Information is subject to change without notice.Check local codes Printed 06/20/2019
Predator 3-12.5 Ton Package Page: 13
K York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ150N18R2D5EAA1A1
Quantity: 1 Tag#:RTU-1 System: ZJ150N18R2D5EAA1A1
- 1RC0471 Roof Curb
RIGHT
80-5/8 INSULATED:}DECK UNDER
����"" ♦ �'�� CONDENSER SECTION
20
ll .1 ,-Iiii
SUPPLY
20 6 ��-�"�
4 *, ♦'r DUCT SIZES:
i Return 19.5 x?9.5
RETURN "' 5upply 19.5 x 29.5
2TYP. ���
ROOF OPENING:
� 4110°
y�'"� 48Long 30 Wide
50-112impoiINSULATED DECK UNDER
COht1PRESSC313 SECTION
FRONT
14"
*Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications.
For location of horizontal duct applications(On rear of unit),refer to Unit Dimensions details.
1RC0471 Roof Curb Dimensions
Information is subject to change without notice.Check local codes. Printed 06/20/2019
0463
yoRK® Predator 3-12.5 Ton Package Page: 14
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2
Cooling Performance
Total gross capacity 80.4 MBH
Sensible gross capacity 58.8 MBH
necapac75.5 MBH
Total � ��
Sensiblet net capityacity 53.9 MBH ,
Efficiency(at ARI) 11.80 EER ,€ �� ,�V
Integrated eff.(at ARI) 14.60 IEER �� �
Ambient DB temp. 95.0 °F a ti •,
Entering DB temp. 80.0 °F
Entering WB temp. 67.0 °F ,:
Leaving DB temp. 59.1 °F
Leaving WB temp. 57.2 °F i, ����l k'u "'`
Power input(w/o blower) 5.90 kW
Sound power 85 dB(A)
Refrigerant
Refrigerant type R-410A
Sys1 5 lbs 12 oz
Sys2 5 lbs 12 oz
Gas Heating Performance 6.5 Ton
Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and
Heating output capacity(Max) 96 MBH each rooftop is completely computer-run tested prior to shipment.
Supply air 2600 CFM Unit Features
Heating input capacity(Max) 120 MBH
Leaving DB temp. 94.2 °F • Two Stage Cooling
Air temp.rise 34.2 °F • 120 MBH Input Aluminized Steel,Two Stage Gas Heat
SSE 80.0 % • Full perimeter base rails with built in rigging capabilities
Stages 2 • Unit Cabinet Constructed of Powder Painted Steel, Certified At 750 Hours
Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards)
Supply air 2600 CFM • Scroll Compressor's]
- Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and
Addl.Unit Losses(Options/Accessories) 0.18 IWG Hoods(Bottom or Horizontal End Return Only)with Economizer Fault
Blower speed 937 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California
Max BHP of Motor(including service factor) 2.30 HP Title 24,AMCA 511
Duct location Bottom )
Motor rating 2.00 HP • 2 HP High Static Belt Drive Blower
Actual required BHP 1.54 HP • Solid Core Liquid Line Filter Driers
Power input 1.44 kW • Unit Ships with 2"Throwaway Filters
Elevation 0 ft. • Replacement Filters:4-(24"x 20").Unit accepts 2"or 4"wide filters.
Drive type BELT
Outside/Mixed Air • Non-Powered Convenience Outlet
• Short Circuit Current:5kA RMS Symmetrical
Outside Air Cfm 320 CFM • Through-the-Curb and Through-the-Base Utility Connections
Electrical Data • Single Point Power Connection
• HACR Circuit Breaker/Disconnect
Power supply 230-3-60
•
Unit min circuit ampacity 41.7 Amps Return Air Smoke Detector
Unit max over-current protection 50 Amps • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin
Dimensions&Weight evaporator coil
Hgt 51 in. Len 89 in. Wth 59 in. • Composite Drain Pan-Front Connection
Weight with factory installed options 1285 lbs. • Tool-free maintenance with features like hinged doors for all-access panels,
Clearances slide-out blower and blower motor tray
BAS Controller
Right 12 in. Front 36 in. Back 36 in. • IntelliSpeed control of the VFD based on stages of cooling.Provides Single
`Top 72 in. Bottom 0 in. Left 36 in. J Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10.
Note: Please refer to the tech guide for listed maximum static pressures • Smart Equipment Controller including Discharge Air, Return Air,and Outdoor
0 AMERICAN 'C lir4,-,,,,4-----)
�,�� Air Temperature Sensors.
.CERTIFIED} nuaury ® 1� �`j`2 j'
_ r'',C1 rag
_:: �� Standard Unit Controller: Smart Equipment Control Board
• Safety Monitoring-Monitors the High and Low-Pressure Switches,the
Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Failures,Safety Lockouts and Repeated Limit Switch Trips.
Warranty
• One(1)Year Limited Warranty on the Complete Unit
• Five(5)Year Warranty-Compressors and Electric Heater Elements
• Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page: 15
we Predator 3-12.5 Ton Package
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ078N12R2D5EAA1A2
Quantity: 1 Tag#:RTU-2 System: ZJ078N12R2D5EAA1A2
Factory Installed Options
ZJO78N12R2D5EAA1A2
Equipment Options Option(s) Selected
a ��� tngle PackagedR10A Air Condltgh
• Product Category Z< Eft "� �h�
�D a
Nominal Cooling Capacity: 078 6.5 Ton
Two Stage Cooling
Heat Tye,ar��' al Heat capacity: N 12' MB� tat Alum nized to S Gas Hem
2 HP High Static Belt Drive Blower
Blower Option: R IntelliSpeed control of the VFD based on stages of
cooling (Provides Single Zone VAV Fan Operation as
defined by ASHRAE 90.1 section 6.4.3.10)
1 t ge 2Q�30-3-6
, .,...�� � � .
Dry Bulb Low Leak Economizer w/Barometric Relief and
Power Exhaust and Hoods (Bottom or Horizontal End
Outside Air Option: D Return Only)with Economizer Fault Detection &
Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,
California Title 24,AMCA 511).
a`a`aa
o •
� � --Powered C•a enience utiet
CR circuit Br �fi< is i�d
Sensor Options: E
Return Air Smoke Detector(Bottom return only)
mart Equipt�rt �r oil chiding Discharge Air,
�\a ontrols: A � \ '
Atr, Temperature Sensors.
Micro-Channel"all-aluminum"condenser coil, Copper
Refrigeration: A
tube/aluminum fin evaporator coil
Additional d" T r awa r t \\
a
Cabinet Options: A Composite Drain Pan-Front Connection
Product
Field Installed Accessories
O 1 BD0408- Burglar Bars (32.0 lbs) 0 1 FL0402- Permanent 2"only 0 1 HA0443- High Altitude Kit for
O 1CG0420- Coil Guard (27.0 lbs) Filter Kit(Includes (4) Four Filters) Propane (1.0 lbs)
1 CV0403- Concentric (2.2 lbs) 0 1 HG0411 - Hail Guard Kit-
0Diffuser,Flush Mount,20RD 0 1 GP0405 -Gas Piping Kit for Diamond Pattern (37.0 lbs)
O
1CV0412- Concentric Bottom Gas Supply Connection 0 1HG0432- Hail Guard Kit-
Diffuser,Side Discharge,20RD with External Shut-Off(includes: Provent Style (25.0 lbs)
O 1FE0412- Flue Exhaust Internal gas pipe, fittings, gas cock 0 1NP0459 - Natural Gas to
Extension Kit (14.0 lbs) & panel gaskets) (10.0 lbs) Propane Conversion Kit (2-Stage)
0 1 FF0414-2" Only Metal Filter 0 1 HA0442 - High Altitude Kit for (2.0 lbs)
Frame Kit(16.0 lbs) Natural Gas (1.0 lbs)
Printed 06/20!2019
Information is subject to change without notice.Check local codes.
. 1.2yoRK. Predator 3-12.5 Ton Package Page: 16
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2
-O 1 RC0470 - Roof Curb- 8" High, 0 S1-03102529004 - Non- 0 S1-TBSU32P7S-Source 1
Flat, Uninsulated, Full Perimeter Networking Wall Sensor with Branded LX Series, Up to 4 Heat/
(Shipped Knocked Down) (135.0 Over-ride button -Allows remote 2 Cool, Electronic 7 Day
- lbs) sensing and control from single or Programmable (1.2 lbs)
• 1RC0471 - Roof Curb- 14" High, multiple zones. Override allows 0 S1-YK-MAP1810-0P- MAP
Flat, Uninsulated, Full Perimeter setpoint to be overridden for 2 (Multiple Access Portal) Gateway-
(Shipped Knocked Down) (135.0 hour time period. (0.2 lbs) For use with SimplicitySE Control.
lbs) 0 S1-03102529006- Non- (0.2 lbs)
O 1 RC0472- Roof Curb, Transition- Networking Wall Sensor with 0 S1-YK-MAP1810-0S-Stationary
Sunline 7.5T thru 12.5T to Setpoint Adjustment and Over-ride MAP Gateway (Includes MAP
Predator 3.0T thru 12.5T (Shipped Button-Allows remote sensing Gateway, Field Bus Adapter,
Assembled) (200.0 lbs) and control from single or multiple Mounting Bracket and 100 to 240
O 1 RC0476- Roof Curb-24" High, zones. Allows setpoint to be VAC Power Supply). US-
Flat, Uninsulated, Full Perimeter adjusted ± 5° F. Override allows compatible counties. (1.9 lbs)
(Shipped Knocked Down) (135.0 setpoint to be overridden for 2
lbs) hour time period. (0.2 lbs)
O 1 RC0479 -Transition Roof Curb- 0 S1-03103489000-Temp sensor,
8" High, Small Sunline to Predator 80mm x 80mm, LCD display,
O 1WC0412 -Wooden Crate (445.0 screw terminals, adjustable
lbs) setpoint, JCI logo (0.1 lbs)
O 2AP0402-Air Proving Switch (1.0 0 S1-03103490000 -Temp sensor
lbs) w/Economizer FDD, 120mm x
• 2AQ04700524- CO2 Space/Wall 80mm, LCD display, screw
Mount Accessory (5.0 lbs) terminals, adjustable setpoint, no
_0 2AQ04700624- CO2 Unit Mount logo (0.0 lbs)
Accessory (4.6 lbs) 0 S1-03103516000 -Temp&
O 2DF0403 - Dirty Filter Switch (1.0 humidity sensor, 120mm x 80mm,
lbs) LCD display, screw terminals,
0 2EC0401 - Kit, Single Enthalpy warmer/cooler dial, JCI logo (0.4
Field Installed (1.0 lbs) lbs)
• 2EC0402- Kit, Dual Enthalpy 0 S1-03103517000-Temp sensor,
Field Installed (Includes two 120mm x 80mm, no display, no
humidity sensors) (1.0 lbs) dial, screw terminals, no logo (0.4
O 2LA04702412- Low Ambient Kit lbs)
(2.2 lbs) 0 S1-03103518000-Temp&
O 2SD04700824-Smoke Detector humidity sensor, 120mm x 80mm,
Kit w/Mounting Hardware for no display, modular jack,
Supply Air(Horizontal/Downflow) warmer/cooler dial, JCI logo (0.4
Only(9.4 lbs) lbs)
O ASC Services- Charges for this O S1-03103519000-CO2 sensor,
Service are Applicable. 120mm x 80mm, no display, screw
Application, Startup & terminals or modular jack, no logo
Commissioning (ASC) Services (0.2 lbs)
Available with Daily Fee Plus 0 S1-MP-PRTKIT OP- MAP
Expenses. This Service Provides (Multiple Access Portal) Gateway
a 90 Day DOA Benefit When Kit- Replacement MAP gateway
Completed by a Factory Certified protective case, lanyard and
Technician. Contact Your communication cable. Use only to
Distributor, Dealer, or Sales replace worn or damaged
Representative. Distributors Can components. (0.3 lbs)
Call 1-877-874-7378 for an ASC 0 S1-SE-COM1001-0- Field
Quote. Installed Communication Card for
O S1-03102529000- Non- Simplicity SE control. Can be field
Networking Wall Sensor-Allows configurable for BACnet, N2 or
remote sensing and control from ModBUS MSTP (0.0 lbs)
- single or multiple zones. (0.2 lbs)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
; ® Predator 3-12.5 Ton Package e Page: 17
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAAIA2
Consolidated Drawing
NOTES: OPERATING CENTER OF GRAVITY 4 POINT CORNER LOADS LBS
1. FOR OUTDOOR USE ONLY. iTONNAGE UNIT WEIGHT (.LBS) LOCATION (BASE UNIT) _ (LBS) (BASE UNIT)
2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. UNIT)
3. MIN. CLEARANCES TO BE: (BASE U.,.IT X Y A B C D
8.5 ZF 1007,[458] 38 [965] 24 [610] 235 107 175 79 ' 255 116 342 155
RIGHT SIDE: 12 305 10 ZF 11103 [501] 38 (965 24 [610] 257 117 192 87 279 '127 375 170 ;
LEFT SIDE: 36 '915 8.5 ZH 1030 [467] 38 [9651 24 610 240 109 179 81 1261 118 350 -159
FRONT: 36 '915 10 ZH _. 1090 4941 38 965 24 610 254 115 189 86 276 125]1 371 168
REAR: 36 '915 6.5 23 1030 [467] 39[991 25 635: 245 111 191 87 260 `118 333 151'
TOP: 72 `1830] 7.5 23 1050 [476 39 991 25 635 250 113 195 89 ` 265 '120 340 154
BOTTOM: S '0] 32.67 - 8.5 23 1060 `481] 38 [965] , 24 610 247 112 184 84 268 4122 360 163, ;
4. TO REMOVE THE SLOE-OUT DRAIN PAN, A REAR CLEARANCE OF _ 830 10 ZJ 1070 48
60 in (1525 mm)) IS REQU�JIRED, IF SPACE IS UNAVAILABLE THE [830] [4� 39 [991 24 610] 245 111 191 87 278 '126 1 357 162
DRAIN AN CAN BE REMOVED THROUGH THE FRONT BY SEPARATING 6.83 -- 8.5 & 10ZR 1200 (544] 38 [965 25.5 [648] 297 135 221 100] 291 132 390 177
THE CORNER WALL. [173] 6.5 XP 1080 [490 38 [965 25 [635] ( 262 119 195 89 i 266 121 357 162
5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES 7.5 XP 1 1090,[494 38__965 1 23 584 243 110 181 82' i 284 129 381 173'
CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 24'38 `- • 8.5 . XP I. 1137 [516 38 1965 25.5 [648] .282 128 210 95` '276 125 , 370 168 i •
6. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY [619] y 10 XP 1135 [515] 38 [965] 25.5 j648L 281 127 209 95 1275 125 ( 369 167`.'
ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT 1"
IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY
CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 32.06- •---18 00 --•7.84
7. SIDE DUCT FLANGES ARE 0.75" HIGH. [814] 1 [457] [199]
BOTTOM DUCTS DO NOT HAVE FLANGES. 6.83
8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES
9. DIMENSIONS INTHE LOWEST G1T11EARE AINCMILLIMETERS OR KILOGRAMS. A [173] jlB 10,50 - - - 18.25
10. ECONOMIZER, DISCONNECTIC CONONAL COIL NNEC ASWITCH,R COIR HOODS GAS SHOWN. 616 n' \ • ALTERNATE CONDENSATION DRAIN
ECONOMIZER SWITCH, CONVENIENCE OU�CLET 24.24 T • �, ' __[267] +. [464]
•
lit EXCEPT XP (HEAT PUMP) UNITS. (FROM MTB. P00 �� � } ;NES „� 1 T.
E U >�i i1; n !„ll1l
FLANGE) T 27.50•. P 2610
��Q %I"�� = 1 1 [
-�' DIRECTION OF AIRFLOW 4_ ' i H [699] . L [ ] �!Y - I
50 CENTER OF GRAVITY LEFT N Y RIGHT 18.25 U 128.25
i ._,� ,,,,,,4;-. ,A,;,.,,,.',�\ [464) . a R [718]
314" FPT.._.:.� L yp �i _f - , N
518 486 17.14.. �.�, ]:140
21.00- a ( 1
20.39 [ ._ .. )
19 14 Y [533] i ,,
[ ] 24 [486] [435] ,SII �x\�� � '1 1.... .. =i SUPPLY 18.06
�.... '.._.. JP 1 [512]t.._... i_........ t '` _.!C ,as3 ' I [459]
r... D �'- ter...
532
5] r p 13687 ' 16.39 FRONT BOTTOM GAS 5,16 2.88
1 ] BOTTOM ENTRY: SUPPLY ENTRY 2,00 [51] rt-- 28.25 -4- 31.63 [73]
14591 - [416] [131] [718] [803]
[459] H- 18.89 POWER 2,50 [64]
OUTSIDE AIR DETAIL A ._ X [480] CONTROLTTO3X VIEW 00.875 [22] REAR (PARTIAL(INTAKE HOOD NOT SHOWNVINw THIS VIEW)
INTAKE HOOD
DISCONNECT SWITCH COVER - - 58.09 -
(OPTIONAL) (OPTIONAL) -
- 5._ w il," POWER ENTRY 02.50 [64] y ' i I [ - ....._
�»" 2261] [1475]
I
GAS INLET
25.72 " ` FRESH AIR HOOD( IN ,\ BLOWER ACCESS j 1 ___„4 .______i
653 ECONOMIZER(OPTIONAL) �I1 FILTER/ - ,� j - - +te
4_
[6n] CTL PANEL/ I �{ONPRESSOR I _..
COMPRESSO![ CONTROL ENTRY 00.875 [ 22] ACCESS ` .( 50.75
' aa. ACCESS r'- ',? i'H, III .; [1289]
• POWER ENTRY 2.50 [64j - "�
I" _ F e -
= k BAROMETRIC RELIEF HOOD/- Il j - t
E
9" POWER EXHAUST(OPTIONAL) �, ;
,`, ,..................A.,,;,=,_,2
__. .... st _ T- ,t .t °I t. i z.:',+ _.__. weal
CONVENIENCE OUTLET LAVER- ]` SEE DETLOCAIL TIFOR EXHAUST11.38
1 21.19 •
(OPTIONAL) 27.31 [538] [289] •
LEFT VIEW CONVENIENCE OUTLET [694] FLUE 11.,. [9.00
1499] -COIL GUARD
POWER ENTRY 0.875 [22] - 89.00[2261] - (OPTIONAL)
FRONT VIEW RIGHT VIEW
(OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
R�� Predator 3-12.5 Ton Package Page: 18
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ078N12R2D5EAA1A2
Quantity: 1 Tag#: RTU-2 System: ZJ078N12R2D5EAA1A2
Component Locations
Cooling With Gas Heat(6.5 Through 10 Tons)
Smart Equipment1PJ control board Filter access Filter drier
wtscrew connector for T-stat Disconnect location (solid core)
o tional disconnect switch) (2"or 4"filter options)
wiring and network connections ( P
Terminal block for Micro-Channel Aluminum
hi-voltage connection •- ` Tube/Aluminum Fin
�� Condenser
Second model
nameplate
inside hinged h Slide-out motor and
access panel " blower assembly for
easy adjustment
Dual stage and service
cooling for _ Belt-drive
maximum a 7 blower motor
comfort _ ` UFD location(optional)
" Power venter motor
Compressor#2 ) r � �
accesaccess(high-
sefficien(h �r 20-gauge aluminized
steel tubular heat
compressor) exchanger for long life(stainless steel option)
Two-stage gas
Base rails wlforklift heating to maintain
slots(three sides)
with 1"NPT,
3-- warm,comfortable
and lifting holes ; Slide-out drain pan temperature
Roof curbs in eight-and ..71: female connection Intelligent control
fourteen-inch heights.Roof , board for safe and
curbs for transitioning from operation
York SunlineTM footprint to Toolless and control wiring
Side entry power Compressor#1 access
the unlin RIZU/ZW/ZK (high efficiency compressor)efficient
door latch knockouts
Series footprints
are also available(field installed accessory)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
' 611111 YORK° Predator 3-12.5 Ton Package Page: 19
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#: RTU-2 System: ZJO78N12R2D5EAA1A2
Low Leak Downflow Economizer
_ Low Leak Downflow Economizer(shown with optional Power Exhaust)
--___
..„
----,
_------1
q . ,....
z..-- ------%-....,'-',:-..-"V( •--i ,.01 ii:I li, i,
Fresh Air Hood
_____,,______. _-_-:-/-7_ -j
si•-,„ ---------- - - - -- - - 1.
. , .--------7
.'''' •....-4,-4-4....
ilitill: 1,,,.6: 1, ::: ,x..:_iirtti.„ ': (::::ded)
—
..--.4,„.._. ......;,-,....,.....„. .,,,,..." •
..„4..........*,......,....4" ,,7.....„1:1 ,1)
I r
---------
,- .......„,-. ,
I 1 -
i,
.
1 Millint ,11:1,::11,
•,,,,
._
1 ,,--
--
1 -'---,, ---" --
Low Leak Economizer(included) / ' •,;:,---, ------;-‘---- -
. ,
Power Exhaust(optional)
, ,
Relief Damper
Barometric/ ,BarometricRelief
(included) Hood (included)
Low leak economizers are capable achieving low
leakage rates of 3 cfm/sq.ft at 1"of static pressure,
meeting or exceeding the following standards:
ASHRAE 90.1-2010
ASHRAE 62
AMCA 511 (licensed as Class 1A damper)
International Energy Conservation Code (IECC)
California Title 24
The outdoor intake opening shall be covered with a
rain hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is
also possible. Dampers shall fully close on power loss.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
104
K0
Predator 3-12.5 Ton Package Page:20
York Single Package R-410A Air Conditioner
y0
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#: RTU-2 System: ZJO78N12R2D5EAA1A2
Factory Installed Power Exhaust
SP-in.-wg.
0 0 0 0 0 0 0 0 0
NJ 1,1
C) a co
Un
0
NJ0
NJ
Un
0 w
,
Pao
o j
11 0
3 0 M
C X VI
o
c
"0
0
0
0
03
-0
-UT'
o • . . — . . . . . . . .
o
BHP
Information is subject to change without notice.Check local codes. Printed 06/20/2019
ayoRK* Predator 3-12.5 Ton Package Page:21
York Single Package R-410A Air Conditioner
Project Name:aPlanet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: I System: ZJO78N12R2D5EAA1A2
Seismic Certification
SPECIAL SEISMIC CERTIFICATIONi DCL Ake
Johnson *WO
OF NON—STRUCTURAL Controls
COMPONENTS AND SYSTEMS
CERTIFICATE OF COMPLIANCE
Dynamic Certification Laboratories has qualified the listed packaged rooftop units as CERTIFIED for seismic
applications in accordance with the following codes and standards:
CBC 2013, IBC 2012, ICC-ES AC-156 2012, ASCE 7-10
The following model designations are included in this certification, A complete list of certified models,options,
and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories,
provided by the equipment manufacturer upon request.
Unitary Product Group Packaged Rooftop Units (UPG)
Seismic Qualification Testing was conducted in accordance with and in strict adherence to the standards set
forth within the American Society of Civil Engineers(ASCE 7)by the independent approval agency,Dynamic
Certification Laboratories. The above referenced equipment is APPROVED for seismic applications when
properly installed and used as intended.
The basis of this certification is through testing of the active and energized components per AC156. This
certification covers multiple UPG brands,including York,Johnson Controls,Coleman, Luxaire,Evcon, Fraser-
Johnston and Ready Ship.
The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response
Acceleration,Sds,as determined by the ASCE 7 seismic maps. Various installation locations/isolation
configurations are covered under this certification,limited by the Sds value stated in the following table. A
seismic importance factor,ip,of 1.5 applies to this certification to include essential facility requirements and life
safety applications for post event functionality. The units are approved for both a rigid and flexible mount
configuration.
Maximum Design Sds Values of UPG Packaged Rooftop Units
Series model Tons Sds(g) I piWp
ZR/2.1121-1/2K/ZW/2111217.1A3* 037 3 2.5 1.88
ZR/D/ZH/ZictriAblZU/217.1A4* 049 4 2.5 1.88
ZR/2.1/214/ZKIZW/ZU/ZT/JA5* 061 5 2.5 1.88
ZR/Z.VZH/ZF/XP/ZK/ZW/ZUIZS/XA/106* 078 6.5 23 1.88
ZR/21/21-if2F/XP/ZKiZW/ZU/ZSieW.J07*/T* 090 7.5 2.5 1.88
ZR/Z3/211/2F/XP/ZOZW/ZU/73/XA/I08* 102 8.5 2.5 1.88
ZR/2.1/214/2FMNIKIZW/ZU/ZSMAti 10*11-* 120 10 2.5 1.88
ZIRIZI/ZI-1/2F/XPIZKIZW/ZU/ZSRA/112*./T* 150 123 2.0 1.50
Page 1 of 2
Dynamic Certificatien Laboratorres 1315 Greg Street,State 199,Sparks,NV 39431—ph:77S-353-5035 www,shakeress,cern
Information is subject to change without notice.Check local codes. Printed 06/20/2019
yORK® Predator 3-12.5 Ton Package Page:22
York Single Package R-410A Air Conditioner
Project NameT:aPlanet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: I System: ZJO78N12R2D5EAA1A2
Seismic Certification
SPECIAL SEISMIC CERTIFICATION
((a)} DCL OF NON-STRUCTURAL Johnson
Controls
COMPONENTS AND SYSTEMS
CERTIFICATE OF COMPLIANCE
Table of Seismic Design Parameters
Site Class F. ap R z/h
1.0 13 2.5 6.0 1.0
Site and Project Requirements
it is the responsibility of the Design Professional of Record to:
• Provide engineering for the anchorage and restraint of the unit
• Validate Certification Design Parameters with actual site conditions
• Provide engineering of all equipment support structures
• Confirm component configuration
Certification Issued by: Dynamic Certification Laboratories
Document Control Number: 90300-1107-A(rev.1)
Original issue Date: 9/2/11
Rev1.Issue Date: 3/26/14
t 55220
3 244 /04,rtn Cartes
COMMerelai FICKikrt Mariager
IntA#,ton Controls,incotponted
Dr.Ahmad itani,SE
Dynamic Certification Laboratories
Page 2 of 2
Dynamic Certification Laboratories 131S Greg Street,Suite 109,Sparks,NV 89431—0'775-35S-5085 www.stiaketest.cam
Information is subject to change without notice.Check local codes. Printed 06/20/2019
YORK® Predator 3-12.5 Ton Package Page:23
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJO78N12R2D5EAA1A2
Quantity: 1 Tag#:RTU-2 System: ZJO78N12R2D5EAA1A2
1RC0471 Roof Curb
RIGHT
80-5/8 r: INSULATED DECK UNDER
CONDENSER SECTION
-41(?":.
20
SUPPLY <},NA
20 6
4
# DUCT SIZES:
/ Return 19.5 x 29.5
-" ' Supply 19.5 x 29.5
RETURN
2P' ROOF OPENING:
46 Long
30 Wide
30
50'1!2 INSULATED DECK UNDER
COMPRESSOR SECTION
FRONT
14"
Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications.
For location of horizontal duct applications(On rear of unit), refer to Unit Dimensions details.
1 RC0471 Roof Curb Dimensions
Information is subject to change without notice.Check local codes. Printed 06/20/2019
yo ® Predator 3-12.5 Ton Package Page:24
RK York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
Cooling Performance
Total gross capacity 130.0 MBH t, fiew
p
Sensible gross capacity 96.0 MBH
Total net capacity 120.3 MBH
Sensible net capacity 86.3 MBH
Efficiency(at ARI) 12.00 EER
Integrated eff.(at ARI) 14.60 IEER ;
Ambient DB temp. 95.0 °F
Entering DB temp. 80.0 °F ,
Entering WB temp. 67.0 °F
Leaving DB temp. 57.8 °F ••
Leaving WB temp. 56.7 °F
Power input(w/o blower) 9.00 kW
Sound power 91 dB(A)
Refrigerant
Refrigerant type R-410A
Sys1 7 lbs 14 oz
Sys2 7 lbs 14 oz
Gas Heating Performance 10 Ton
Entering DB temp. 60 °F • York Predator units are manufactured at an ISO 9001 registered facility and
Heating output capacity(Max) 144 MBH each rooftop is completely computer-run tested prior to shipment.
Supply air 4000 CFM Unit Features
Heating input capacity(Max) 180 MBH
Leaving DB temp. 93.3 °F • Two Stage Cooling
Air temp.rise 33.3 °F • 180 MBH Input Aluminized Steel,Two Stage Gas Heat
SSE 80.0 % • Full perimeter base rails with built in rigging capabilities
Stages 2 • Unit Cabinet Constructed of Powder Painted Steel, Certified At 750 Hours
Supply Air Blower Performance Salt Spray Test(ASTM B-117 Standards)
Supply air 4000 CFM • Scroll Compressor[s]
-Ext.static pressure 0.8 IWG • Dry Bulb Low Leak Economizer w/Barometric Relief and Power Exhaust and
Addl.Unit Losses(Options/Accessories) 0.58 IWG Hoods(Bottom or Horizontal End Return Only)with Economizer Fault
Blower speed 1226 RPM Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,California
Max BHP of Motor(including service factor) 3.45 HP Title 24,AMCA 511).
_Duct location Bottom
Motor rating 3.00 HP • Slide-out Blower/3 HP Belt Drive Motor Assembly
Actual required BHP 3.06 HP • Solid Core Liquid Line Filter Driers
Power input 2.85 kW • Unit Ships with 2"Throwaway Filters
Elevation 0 ft. • Replacement Filters:4-(24"x 20"). Unit accepts 2"or 4"wide filters.
Drive type BELT • Non-Powered Convenience Outlet
Requires field-supplied drive true • Short Circuit Current:5kA RMS Symmetrical
Outside/Mixed Air • Through-the-Curb and Through-the-Base Utility Connections
Outside Air Cfm 100 CFM • Single Point Power Connection
• HACR Circuit Breaker/Disconnect
Electrical Data • Return Air Smoke Detector
Power supply 230-3-60 • Micro-Channel"all-aluminum"condenser coil,Copper tube/aluminum fin
Unit min circuit ampacity 57.2 Amps evaporator coil
Unit max over-current protection 70 Amps • Composite Drain Pan-Front Connection
Dimensions&Weight • Tool-free maintenance with features like hinged doors for all-access panels,
Hgt 51 in. Len 89 in. Wth 59 in. slide-out blower and blower motor tray
Weight with factory installed options 1325 lbs.
Clearances BAS Controller
• IntelliSpeed control of the VFD based on stages of cooling.Provides Single
Right 12 in. Front 36 in. Back 36 in. Zone VAV Fan Operation as defined by ASHRAE 90.1 section 6.4.3.10.
`Top 72 in. Bottom 0 in. Left 36 in. J • Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Note: Please refer to the tech guide for listed maximum static pressures Air Temperature Sensors.
Standard Unit Controller: Smart Equipment Control Board
AIMAI CERTIFIED QUALITY
��/•• ,l Safety Monitoring-Monitors the High and Low-Pressure Switches,the
€ J,eu9 •". ..3E "f':1 v S,
us * Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Failures, Safety Lockouts and Repeated Limit Switch Trips.
Warranty
• One(1)Year Limited Warranty on the Complete Unit
• Five(5)Year Warranty-Compressors and Electric Heater Elements
• Ten(10)Year Limited Warranty-Aluminized Steel Heat Exchanger
Information is subject to change without notice.Check local codes. Printed 06/20/2019
21FOR' s Predator 3-12.5 Ton Package Page:25
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
Factory Installed Options
ZJ120N18R2D5EAA1A1
Equipment Options Option(s) Selected
Sine a Air Corxtitianer; Hi.
•
\\ `` "ProductCategory:
10 Ton
Nominal Cooling Capacity: 120
Two Stage Cooling
Heat Type and Nominal Heat Capacity: N1$ 180 MBH Input Aluminized Steel,T , tage Gas Heat
3 HP High Static Belt Drive Blower
IntelliSpeed control of the VFD based on stages of
Blower Option: R
cooling (Provides Single Zone VAV Fan Operation as
defined by ASHRAE 90.1 section 6.4.3.10)
Dry Bulb Low Leak Economizer w/Barometric Relief and
Power Exhaust and Hoods (Bottom or Horizontal End
Outside Air Option: D Return Only)with Economizer Fault Detection &
Diagnostic(Meets ASHRAE 90.1-2013, IECC 2015,
California Title 24,AMCA 511).
\ \ \ No a eConvenience Outlet
ti �of ice Optitate: 5
\\ HACR rt < /Disconnect
Sensor Options: E
Return Air Smoke Detector(Bottom return only)
.urpment Controller including Drscha
..>.. .........:. ._�. ..... ......... • ....... Arend O...u...td:.a.oor Air Tempe-..rature
S.... n
c„Lam
.... -'
Micro-Channel"all-aluminum" condenser coil, Copper
Refrigeration: A
tube/aluminum fin evaporator coil
• Additional Options: Standard w ay ters
Cabinet Options: A Composite Drain Pan-Front Connection
, product • \t;� \ .
Field Installed Accessories
O 1BD0408- Burglar Bars (32.0 lbs) 0 1CV0413-Concentric 0 1FF0414 -2" Only Metal Filter
O 1CG0420 - Coil Guard (27.0 lbs) Diffuser,Side Discharge,18X28 Frame Kit (16.0 lbs)
O 1CV0403- Concentric 0 1CV0414-Concentric 0 1 FL0402 - Permanent 2" only
Diffuser,Flush Mount,20RD Diffuser,Side Discharge,18X32 Filter Kit (Includes (4) Four Filters)
O 1 CV0404- Concentric 0 1 CV0420-Concentric (2.2 lbs)
Diffuser,Flush Mount,18X28 Diffuser,Specialty,24X24 0 1GP0405- Gas Piping Kit for
O 1 CV0405- Concentric 0 1 CV0426-Concentric Bottom Gas Supply Connection
Diffuser,Flush Mount,18X32 Diffuser,Specialty,24X24 with External Shut-Off(includes:
O 1CV0412- Concentric 0 1 FE0412- Flue Exhaust Internal gas pipe, fittings, gas cock
Diffuser,Side Discharge,20RD Extension Kit(14.0 lbs) &panel gaskets) (10.0 lbs)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
LiyoRK. Predator 3-12.5 Ton Package Page:26
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
-O 1 HA0442- High Altitude Kit for 0 ASC Services-Charges for this 0 S1-03103518000-Temp&
Natural Gas (1.0 lbs) Service are Applicable. humidity sensor, 120mm x 80mm,
O 1 HA0443- High Altitude Kit for Application, Startup & no display, modular jack,
- Propane (1.0 lbs) Commissioning (ASC) Services warmer/cooler dial, JCI logo (0.4
O 1 HG0411 - Hail Guard Kit- Available with Daily Fee Plus lbs)
Diamond Pattern (37.0 lbs) Expenses. This Service Provides 0 S1-03103519000-CO2 sensor,
O 1 HG0432- Hail Guard Kit- a 90 Day DOA Benefit When 120mm x 80mm, no display, screw
Provent Style (25.0 lbs) Completed by a Factory Certified terminals or modular jack, no logo
O 1 NP0459- Natural Gas to Technician. Contact Your (0.2 lbs)
Propane Conversion Kit (2-Stage) Distributor, Dealer, or Sales 0 S1-MP-PRTKIT-OP- MAP
(2.0 lbs) Representative. Distributors Can (Multiple Access Portal) Gateway
O 1 RC0470- Roof Curb- 8" High, Call 1-877-874-7378 for an ASC Kit- Replacement MAP gateway
Flat, Uninsulated, Full Perimeter Quote. protective case, lanyard and
(Shipped Knocked Down) (135.0 0 S1-02815208000- Blower Sheave communication cable. Use only to
lbs) for 8.5 and 10 Ton High Static replace worn or damaged
O 1RC0471 - Roof Curb- 14" High, Field Installed Drive (2.8 lbs) components. (0.3 lbs)
Flat, Uninsulated, Full Perimeter O S1-03102529000- Non- 0 S1-SE-COM1001-0- Field
(Shipped Knocked Down) (135.0 Networking Wall Sensor-Allows Installed Communication Card for
lbs) remote sensing and control from Simplicity SE control. Can be field
O 1 RC0472- Roof Curb, Transition- single or multiple zones. (0.2 lbs) configurable for BACnet, N2 or
Sunline 7.5T thru 12.5T to O S1-03102529004- Non- ModBUS MSTP (0.0 lbs)
Predator 3.0T thru 12.5T(Shipped Networking Wall Sensor with 0 51-TBSU32P7S-Source 1
Assembled) (200.0 lbs) Over-ride button-Allows remote Branded LX Series, Up to 4 Heat/
O 1 RC0476 - Roof Curb- 24" High, sensing and control from single or 2 Cool, Electronic 7 Day
Flat, Uninsulated, Full Perimeter multiple zones. Override allows Programmable (1.2 lbs)
(Shipped Knocked Down) (135.0 setpoint to be overridden for 2 0 S1-YK-MAP1810-0P- MAP
lbs) hour time period. (0.2 lbs) (Multiple Access Portal) Gateway-
() 1WC0412 -Wooden Crate (445.0 O S1-03102529006- Non- For use with SimplicitySE Control.
lbs) Networking Wall Sensor with (0.2 lbs)
O 2AP0402 -Air Proving Switch (1.0 Setpoint Adjustment and Over-ride 0 S1-YK-MAP1810-0S- Stationary
lbs) Button-Allows remote sensing MAP Gateway(Includes MAP
• 2AQ04700524- CO2 Space/Wall and control from single or multiple Gateway, Field Bus Adapter,
Mount Accessory(5.0 lbs) zones.Allows setpoint to be Mounting Bracket and 100 to 240
O 2AQ04700624- CO2 Unit Mount adjusted ±5° F. Override allows VAC Power Supply). US-
Accessory (4.6 lbs) setpoint to be overridden for 2 compatible counties. (1.9 lbs)
O 2DF0403- Dirty Filter Switch (1.0 hour time period. (0.2 lbs)
0 S1-03103489000-Temp sensor,
lbs)
O 2EC0401 - Kit, Single Enthalpy 80mm x 80mm, LCD display,
screw terminals, adjustable
Field Installed (1.0 lbs)
• setpoint, JCI logo (0.1 lbs)
2EC0402- Kit, Dual Enthalpy
0 S1-03103490000-Temp sensor
Field Installed (Includes two
humidity sensors) (1.0 lbs) w/Economizer FDD, 120mm x
O 2LA04702412- Low Ambient Kit 80mm, LCD display, screw
(2.2 lbs) terminals, adjustable setpoint, no
logo (0.0 lbs)
O 2SD04700824-Smoke Detector 0 S1-03103516000-Temp&
Kit w/Mounting Hardware for humidity sensor, 120mm x 80mm,
Supply Air(Horizontal/Downflow) LCD display, screw terminals,
Only (9.4 lbs) warmer/cooler dial, JCI logo (0.4
lbs)
O S1-03103517000 -Temp sensor,
120mm x 80mm, no display, no
dial, screw terminals, no logo (0.4
lbs)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
YORK®
ORK Predator 3-12.5 Ton PackagePage:27
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAAIA1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAAIA1
Consolidated Drawing
NOTES: i I I OPERATING CENTER Of GRAVITY 4 POINT CORNER LOADS (LBS) (BASE UNIT)
1. FOR OUTDOOR USE ONLY. TONNAGE UNIT WEIGHT (LBS) LOCATION (BASE UNIT) 1
2. WEIGHTS SHOWN ARE FOR COOLING ONLY UNITS. (BASE UNIT) X 1 Y A B C D
3. MIN. CLEARANCES TO BE: 8.3 I ZF 1007 [458] 38 [965] 1 24 [610[ 235 107 175 79 ; 255 116 I 342 [155]1
RIGHT SIDE: 12 305 10 I ZF 1103 [501] 38 965] I 24 [610] 257 117 192 87 i 279 127 : 375[170],;
LEFT SIDE; 36 '915 8.5 ZH I 1030 [467] 38 965 I 24 610 240 109 179 81 1 261 118 1 35@_[159];
FRONT: 36 '915 10 ZH ! 1090494 38 965 24 610 254 115 189 86 276 125 371 1681i
REAR: 36 '915 6.5 23 1030 [4671 39_ 99125. 635 245 111_ 191 87 260 118 ` 333 151�i
TOP: 72 '1830] 7.5 23 1050 [476 39 991 `
25 635` 250 113 195 89 265 120 340 154
BOTTOM: 0 '0
4. TO REMOVE THE SL_D�-OUT DRAIN PAN, A REAR CLEARANCE OF [.- 32.67 H 8.5 Z) 1060 [481 38 9651 24 610 247 112 184 84 • 268 122 360 163`1
THE CORNER WALL. [173]83 6.5 ZR 1080 540 38965 25 664 245 111 1 - 291 132 139060 in (1525 mm)) IS REQUIRED. IF SPACE IS UNAVAILABLE THE [830] 10 73 1070 [4851 39 [9911 24P
pRAIN f1AM CAN 9E REMOVED THROUGH THE FRONT 8Y SEPARATING 8.5 & 1@ ZR . 1200 [544] 38�965 25.5 [648] 7 ...100J 291 132 390 177][ ] [635] 262 1189 266 121 357 162
5. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES 7.5 XP 1090 [494 38 965 23 [5841 243 1182 284 129 3813CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. 24.38 8.5 XP 1137 516 38 965 25.5 648 282 1295 276 125 370 16$6. DOWNFLOW DUCTS DESIGNED TO [619] 10 XP s 1135 [515] 38_[9651 25.5 [6481281 1295" j 275 125 369-`167'
ROOF CURB ONLY. IF UNIT IS MOUNTED SIDE SUPPLY, IT --- --- --------
IS RECOMMENDED THAT THE DUCTS ARE SUPPORTED BY
CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 32.06 1 1.--18.00-14--!.7.84
7. SIDE DUCT FLANGES ARE 0.75" HIGH. [814] I [457] , [199]
BOTTOM DUCTS DO NOT HAVE FLANGES. 6.83
8. MINIMUM CONDENSATION TRAP HEIGHT SHALL BE 1.5 TIMES
THE LOWEST NEGATIVE STATIC. , d i [173)
9. DIMENSIONS IN [ ARE IN MILLIMETERS OR KILOGRAMS. A
18. OPTIONAL COIL GUARDS, POWER EXHAUST GAS HEAT 1 R S 1 f, 'B ALTERNATE CONDENSATION DRAIN,-
10.50 18 25
ECONOMIZER DISCONNECT SWITCH CONVENIENCE OUTLET, 24.24 -----� ,..... e [267] [464]
AND BAROMETRIC RELIEF AND FRESH AIR HOODS SHOWN. [616 P ""---...
4 ] i �\ 11`i
Al,EXCEPT XP (HEAT PUMP) UNITS. (FROM MTBFLANG, 27.50! P I` Imr , IO ` I i
:E
DIRECTION OF AIRFLOW -4- R [699] L [ ) �ti �/g' ��i E
J
T 24.00 \\)'
610
LEFT ` % RIGHT 18.25 T/� [ 28.25
..5 I N [718]
1 T
t / [464] R ,
10 CENTER OF GRAVITY N 1-
jj p t
3/4' FPT ....; 20.39 [ i [ 21,00' «l ']�
[ ] 20.14 19!14
4 7.1 533 ti�y,
518 17.14 V `
[512] [486] [ ] II �\� � 1 + SUPPLY 1118.06
�..... t._ 7_..__._ 14.47_D. FRONT ¢ ''
�'. [459]
5. ft � ) SUPPLY ,- n ,�`__k �� I
[i 5J 368 16.39 BOTTOM GAS �-5 16 - 2.88
8.06 - -� [416) BOTTOM ENTRY: PLY ENTRY x02.00 [51] [131] - 28.25---- 31.63 [73]
[459] 18.89 POWER 2.50 [64] [718] [803]
OUTSIDE AIR DETAIL A k. X [460] j CONTROL OP VIEW 00.875 [22] BEAR (PARTIAL(INTAKE HOOD NOT SHOWNVINWTHIS VIEW)
INTAKE HOOD DISCONNECT SWITCH COVER
(OPTIONAL) (OPTIONAL} - 89.00 _ i_ 58.09
[2261] A [1475]
� - a POWER ENTRY 02.50 [64] o'"ir _„ ' -
„� v. i
FRESH A1R HOOD \ 4 _ _ GAS INLET
�.__. 25.12;� FRESH
ECONOMIZER(OPTIONAL)HOOD/OVAL) ' FILTER/ BLOWER ACCESS ��� -
3
Ta
653
( 1• UR PANEL I COMPRESSOR j� J,fMill -
�COMPRESSOR ; CONTROL ENTRY@.875 [ 22] .` ' ACCESS i , 50.75 __._._ __
ACCESS it w' ; [1289]
POWER ENTRY 2.50 [64] i. 8
i..• ,a [
xlro BAROMETRIC RELIEF HOOD/-/zi I ; . .__.....
4 �^ POWER EXHAUST(OPTIONAL) ,1.
x * 4-_, ..;x .mss rate....i ¢>,-s1 ...... t t r.(3 c),,A
CONVENIENCE OUTLET COVER 21.19 - 11.38
SEE DETAIL A FOR [538] [289]
(OPTIONAL) 27.31
[694] DRAIN LOCATION EXHAUST
LEFT VIEW CONVENIENCE OUTLET FLUE 1. 59.00 [1499] \--COIL GUARD
POWER ENTRY 00.875 [22] - 89.00[2261] -
FRONT VIEW RIGHT VIEW (OPTIONAL}
(OPTIONAL FRONT COIL GUARD NOT SHOWN IN THIS VIEW)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Predator 3-12.5 Ton Package Page:28
. LIYORK® York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
Component Locations
Cooling With Gas Heat(6.5 Through 10 Tons)
Smart Equipment'"'control board Filter access Filter drier
wlscrew connector for T-stat Disconnect location (solid core)
disconnect {2"or d"filter options)
wiring and network connections (optionalswitch)
}
Terminal block for Micro-Channel Aluminum
hi-voltage connection •
` Tube/Aluminum Fin
Condeensser
Second model %/ "
nameplate
inside hinged � Slide-out motor and
access panel / ,, blower assembly for
easy adjustment
Dual sta aand service
cooling for �`� � ..--0--;‘-'' 't z } , Belt drive
Art
maximum 1 ?
/ blower motor
comfort t VFD location(optional)
Power ventor motor
Compressor#2 �
access(high- `" '
efficiency g = 67::':1-: ;.'14' 'r;,,, 's eel tubularuheatzed
compressor) £ ; exchanger for long life
1a ) (stainless steel option}
K Two-stage gas
Base rails wlforktifti.„,.3,,,,34133,--,,,,•:,,;,-iIt tt'tft- '" g, heating to maintain
slots(three sides) warm,comfortable
and lifting holes *r Slide out drain pan temperature
with 1'NPT,
Roof curbs in eight-and toiti female connection Intelligent control
fourteen-inch heights.Roof�� board for safe and
curbs for transitioning from efficient operation
York SunlineT""footprint to !!! Side entry power Compressor#1 access
the ZH2J/ZR/ZU/ZW/ZK Toolless and control wiring (high-efficiency compressor)
door latch knockouts
Series footprints
are also available(field installed accessory)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Predator 3-12.5 Ton Package Page:29
aYORK York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
Low Leak Downflow Economizer
Low Leak Downflow Economizer(shown with optional Power Exhaust)
A
--- tz:;-::---7 -."-) -'''--
`""�� [ ,1-:7l h i k ` $ia Fresh Air Hood
� ,LW l� ill ,I 7-11',/,t'li
=`:J i (Included)
�,,,_ it t ,t I �'
1.
rio
j f jlppl I /j f y -'- .
lii,:,:„.4'
~
its 1 L \.
Low Leak Economizer(included) i
f , `j- "`
Power Exhaust(optional) .
Barometric -'
Relief Damper Barometric Relief
(included) Hood (included)
Low leak economizers are capable achieving low
leakage rates of 3 cfm/sq.ft at 1"of static pressure,
meeting or exceeding the following standards:
ASHRAE 90.1-2010
ASHRAE 62
AMCA 511 (licensed as Class 1A damper)
International Energy Conservation Code (IECC)
California Title 24
The outdoor intake opening shall be covered with a
rain hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is
also possible. Dampers shall fully close on power loss.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
YORK® Predator 3-12.5 Ton Package Page:30
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
Factory Installed Power Exhaust
SP-in.-wg.
0 o 0 o o o 0 o o o
in 01 U CO lD
O 0 O O O O O O O O
1.71
0
0
NJ
0
0
N
O
O
h o
3 oC K (r
d O
W
Irl
o
o
0
0
0
O
co
x
-o
0
0 0 0 0 0
0 0 0 0
BHP
Information is subject to change without notice.Check local codes. Printed 06/20/2019
ayoRK® Predator 3-12.5 Ton Package Page:31
York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D6EAA1A1
Quantity: 6 Tag#: RTU-3,4,5,6,7,8 System: ZJ120N18R2D6EAA1A1
Seismic Certification
SPECIAL SEISMIC CERTIFICATION
OF NON-STRUCTURAL V'Att(c"
Johnson -
Controls
COMPONENTS AND SYSTEMS
CERTIFICATE OF COMPLIANCE
Dynamic Certification Laboratories has qualified the listed packaged rooftop units as CERTIFIED for seismic
applications in accordance with the following codes and standards:
CBC 2013, IBC 2012, ICC-ES AC-156 2012, ASCE 7-10
The following model designations are included in this certification. A complete list of certified models,options,
and installation methods are detailed in report number 90300-1107 by Dynamic Certification Laboratories,
provided by the equipment manufacturer upon request.
Unitary Product Group Packaged Rooftop Units (UPG)
Seismic Qualification Testing was conducted in accordance with and in strict adherence to the standards set
forth within the American Society of Civil Engineers(ASCE 7)by the independent approval agency,Dynamic
Certification Laboratories. The above referenced equipment is APPROVED for seismic applications when
properly installed and used as intended.
The basis of this certification is through testing of the active and energized components per AC156. This
certification covers multiple UPG brands,including York,Johnson Controls,Coleman,Luxaire,Evcon,Fraser-
Johnston and Ready Ship.
The seismic values are obtained from the Maximum Considered Earthquake Short Period Spectral Response
Acceleration,Sds,as determined by the ASCE 7 seismic maps. Various installation locations/isolation
configurations are covered under this certification,limited by the Sds value stated in the following table. A
seismic importance factor,1p,of 13 applies to this certification to include essential facility requirements and life
safety applications for post event functionality. The units are approved for both a rigid and flexible mount
configuration.
Maximum Design Sds Values Of UPG Packaged Rooftop Units
Series Model Tons Sds(g) Fo/Wp
ZR/V/ZH/Zie,./ZW/Zii/ZT/JA3* 037 3 2.5 1.88
ZR/ZJ/ZH/ZK/ZW/ZU/ZT/JA4* 049 4 2.5 1.88
ZRIZ1/214,121V2INZU/ZT/JA5* 051 5 2.5 1.88
ZRPLI/ZiliZF/XP/ZVZVV/ZU,12S/XA/J06* 078 6.5 2.5 1.88
ZR/Zi/ZH/ZF/XP/ZK/ZW/ZWZS/XA/J07*/T* 090 7.5 2.5 1.88
ZR/71/21-1,12F/XP/ZX/ZW/ZU/25/XA/108* 102 8.5 2.5 1.88
ZR/ZJ/ZWZF/XP/ZK/ZW/ZU/ZS/XA/J10*/T* 120 10 2 5 1.88
2R/2_1/211/2F/XP/ZKIZWiZtVZSAA/112*/T* 150 12.5 2.0 1.50
Page 1 of 2
trimarnic Certification Laboratones 1313 Greg Street,Sone 109,Sparks,NV 39431 ib-3SSGOSS www.shaketest.COM
Information is subject to change without notice.Check local codes. Printed 06/20/2019
yoRKe Predator 3-12.5 Ton Package Page:32
, York Single Package R-410A Air Conditioner
Project Name:aPlanet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 System: ZJ120N18R2D5EAA1A1
Seismic Certification
SPECIAL SEISMIC CERTIFICATION 414
((*)) DCL ,.,-„.„,„ __ OF NON-STRUCTURAL Johnson
Controls
COMPONENTS AND SYSTEMS
CERTIFICATE OF COMPLIANCE
Table of Seismic Design Parameters
Site Class _ Fa to a, R, z/h
D 1.0 1.5 2,5 6.0 1.0
Site and Project Requirements
It is the responsibility of the Design Professional of Record to:
• Provide engineering for the anchorage and restraint of the unit
• Validate Certification Design Parameters with actual site conditions
• Provide engineering of all equipment support structures
• Confirm component configuration
Certification Issued by: Dynamic Certification Laboratories
Document Control Number: 903004107-A(rev.1)
Original Issue Date: 9/2/11
Rev1.Issue Date: 3/26/14
i
tartv
trt COMMettie:Pletitet M606666
htteet:O'r COOttiko OttO6e-PCiteled
Dr,Ahmed Rani,SE
Dynamic Certification Laboratories
Page 2 of 2
Dynamic Certfication Laboratorie5 MS Greg Street,Swte 109,Sparkt,NV 59431-ph 775-358-5025 www.s,haketest.com
- Information is subject to change without notice.Check local codes. Printed 06/20/2019
Predator 3-12.5 Ton Package Page:33
12YORK® York Single Package R-410A Air Conditioner
Project Name: Planet Fitness Tigard,OR Unit Model#: ZJ120N18R2D5EAA1A1
Quantity: 6 Tag#:RTU-3,4,5,6,7,8 System: ZJ120N18R2D5EAA1A1
1 RC0471 Roof Curb
RIGHT
80-5/8
'40.1°...7"<>.4..* INSULATED DECK UNDER
����� �"��� CONDENSER SECTION
20 ,-
,,,
/" SUPPLY <''�,►
,,,�, ,. [}UCT SIZES:
_ 6 ...,„,,,„
Return 19.5 x 9.5
RETURN _,,,,,
�� -- Supply 19.5 x 29.5
2 TYP.
ROOF OPENING:
\ 46 Long
•r 30 Wide
itii
50-1/2 �' INSULATED DECK UNDER
COMPRESSOR SECTION
FRONT
14"
"Supply and Return Air(Including duct support rails)as shown,are typical for bottom duct applications.
For location of horizontal duct applications(On rear of unit),refer to Unit Dimensions details.
1 RC0471 Roof Curb Dimensions
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:34
Date
06/20/2019
Project Name
Planet Fitness Tigard,OR
Project Number
Client/ Purchaser
Guide Specification Summary Page
Product Series Models and Unit Tags
3-12 Ton P e D5EAA1AIRTU-1
Z.IV 2 D EAA1A F
�� .. �.. ZJ120N18 , 2 ;EAA1AI ''11:1111;:3!,41,3,11:1#
Information is subject to
Printed 06120/2019
change without notice.Check local codes.
yrç Guide Specification for Page:35
York Predator
-GENERAL removing panels or creating bypass of the coils.
York Predator units are convertible single packages with Condensate pan shall be slide out design, constructed of
a common footprint cabinet and common roof curb for all anon corrosive material, internally sloped and
conforming to ASHRAE 62-B9 standards. Condensate
6-1/2 through 12-1/2 ton models. All have two connection shall be a minimum of g/<" I.D. female and be
compressors with independent R-410A refrigeration rigid mount connection.
circuits to provide 2 stages of cooling. The units were
designed for light commercial applications and can be INDOOR (EVAPORATOR) FAN ASSEMBLY
easily installed on a roof curb, slab, or frame. All units
are self contained and assembled on rigid full perimeter Fan shall be a belt drive assembly and include an
base rails allowing for 3-way forklift access and adjustable pitch motor pulley. Job site selected brake
overhead rigging. Every unit is completely charged with horsepower shall not exceed the motors nameplate
R-410A, wired, piped, and tested at the factory to horsepower rating plus the service factor. Units shall be
provide a quick and easy field installation. All units are designed to operate within the service factor. Fan wheel
convertible between side and down airflow. Independent shall be double inlet type with forward curve blades,
economizer designs are used on side and down dynamically balanced to operate smoothly throughout
discharge applications, as well as all tonnage sizes. the entire range of operation.Airflow design shall be
Predator®units are available in the following constant volume. Bearings shall be sealed and
configurations: cooling only, cooling with electric heat, permanently lubricated for longer life and no
cooling with gas heat, reheat only, reheat with electric maintenance. Entire blower assembly and motor shall be
heat and reheat with gas heat. Electric heaters are slide out design.
available as factory-installed options or field-installed
accessories. OUTDOOR(CONDENSER) FAN ASSEMBLY
DESCRIPTION The outdoor fans shall be of the direct drive type,
discharge air vertically, have aluminum blades riveted to
-Units shall be factory assembled, single package, corrosion resistant steel spider brackets and shall be
(Elec/Elec, Gas/Elec), designed for outdoor installation. dynamically balanced for smooth operation. The outdoor
They shall have built in field convertible duct connections fan motors shall have permanently lubricated bearings
for down discharge supply/return or horizontal discharge internally protected against overload conditions and
supply/return and be available with factory installed staged independently. A cleaning window shall be
options or field installed accessories. The units shall be provided on two sides of the units for coil cleaning.
factory wired, piped and charged with R-410A refrigerant
and factory tested prior to shipment.All unit wiring shall REFRIGERANT COMPONENTS
be both numbered and color coded. The cooling Compressors:
performance shall be rated in accordance with DOE and
AHRI test procedures. Units shall be CSA certified to a. Shall be fully hermetic type, direct drive, internally
ANSI 221.47 and UL 1995/CAN/CSA No. 236-M90 protected with internal high-pressure relief and over
standards. temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of+ or
UNIT CABINET — 10% of the unit nameplate voltage.
Unit cabinet shall be constructed of galvanized steel with b. Shall have internal spring isolation and sound
exterior surfaces coated with a non-chalking, powder muffling to minimize vibration and noise, and be
paint finish, certified at a 750-hour salt spray test per externally isolated on a dedicated, independent
ASTM-B117 standards. Indoor blower sections shall be mounting.
insulated with up to 1"thick insulation coated on the
airside. Either aluminum foil faced or elastometric rubber Coils:
insulation shall be used in the unit's compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with toolless
access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable
transit of equipment, overhead rigging, fork truck access
and proper sealing on roof curb applications. Disposable
2"filters shall be furnished as standard and be
accessible through hinged access door. Fan
performance measuring ports shall be provided on the
outside of the cabinet to allow accurate air
measurements of evaporator fan performance without
Information is subject to change without notice.Check local codes. Printed 06/20/2019
t ,
Guide Specification for Page:36
1.4
York Predator
..3YORK®
a. Evaporator coils shall have aluminum plate fins Heat exchanger and exhaust system shall be
mechanically bonded to seamless internally enhanced constructed of aluminized steel, and be designed with
copper tubes with all joints brazed. Special Phenolic induced draft combustion with post purge logic, energy
coating shall be available as a factory option. saving direct spark ignition, and redundant main gas
b. Evaporator coils shall be of the direct expansion, draw- valve. The heat exchanger shall be of the tubular type,
thrudesign. constructed of T1-40 aluminized steel for corrosion
resistance and allowing minimum mixed air entering
c. Condenser coils shall have aluminum plate fins temperature of 40 °F. Burners shall be of the in-shot
mechanically bonded to seamless internally enhanced type, constructed of aluminum-coated steel. Allgas
copper tubes with all joints brazed or Micro-Channel piping shall enter the unit cabinet at a single location,
aluminum tube, aluminum fins. through either the side or bottom,without any field
d. Condenser coils shall be of the draw-thru design. modifications. An integrated control board shall provide
timed control of evaporator fan functioning and burner
Refrigerant Circuit and Refrigerant Safety Components ignition. Heating section shall be provided with the
shall include: following minimum protection:
a. Independent fixed-orifice or thermally operated a. Primary and auxiliary high-temperature limit switches.
expansion devices. b. Induced draft pressure sensor.
b. Solid core filter drier/strainer to eliminate any moisture c. Flame roll out switch (manual reset).
or foreign matter. d. Flame proving controls.
c. Accessible servicegage connections on both suction e. All two stage gas units shall have two independent
and discharge lines to charge, evacuate, and measure stages of capacity(70% or 75% 1st stage, 100% 2nd
refrigerant pressure during any necessary servicing or stage) 3 through 5 ton and (60% 1st stage, 100% 2nd
troubleshooting,without losing charge.
stage)6-1/2 through 12-1/2 ton.
-d. The unit shall have two independent refrigerant
circuits, equally split in 50% capacity increments. UNIT OPERATING CHARACTERISTICS
_Unit Controls: Unit shall be capable of starting and running at 125 °F
outdoor temperature, exceeding maximum load criteria
a. Unit shall be complete with self-contained low-voltage of AHRI Standard 340/360. The compressor, with
control circuit protected by a resettable circuit breaker standard controls, shall be capable of operation down to
on the 24-volt transformer side. 0°F outdoor temperature. Unit shall be provided with fan
b. Unit shall incorporate a lockout circuit which provides time delay to prevent cold air delivery before heat
reset capability at the space thermostat or base unit exchanger warms up. (Gas heat only)
should any of the following standard safety devices trip
and shut off compressor: ELECTRICAL REQUIREMENTS -All unit power wiring
• Loss-of-charge/Low-pressure switch. shall enter unit cabinet at a single factory provided
location and be capable of side or bottom entry to
• High-pressure switch. minimize roof penetrations and avoid unit field
• Freeze condition sensor on evaporator coil. If any modifications. Separate side and bottom openings shall
of these safety devices trip, the LCD screen will be provided for the control wiring.
display the alarm message.
STANDARD LIMITED WARRANTIES -Compressor—5
c. Unit shall incorporate "AUTO RESET"compressor Years, Heat Exchanger— 10 Years, Elect. Heat Elem. —5
over temperature, over current protection. Years, Parts— 1 Year.
d. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy FACTORY INSTALLED OPTIONAL OUTDOOR AIR
hook-up. (Shall be made available by either/or):
e. Unit control board shall have on-board diagnostics and
fault message display. ADDITIONAL FACTORY INSTALLED OPTIONS
f. Standard controls shall include anti-short cycle and low • Alternate Indoor Blower Motor—For applications
voltage protection, and permit cooling operation down with high restrictions, units are available with optional
to a selectable value as low as 0°F. indoor blower motors that provide higher static output
g. Control board shall monitor each refrigerant safety and/or higher airflow.
switch independently.
GAS HEATING SECTION
r Information is subject to change without notice.Check local codes. Printed 06/20/2019
ayORK® Guide Specification for Page:37
York Predator
-• IntelliSpeedTM Supply Fan Control Option
(ASHRAE 90.1 compliant,section 6.4.3.10)—Units
configured with the IntelliSpeedTM Supply Fan Option
- will contain a VFD for variable volume supply fan
operation. This option allows the supply fan RPM to
vary based on the number of compressors or heating
stages energized. The economizer's minimum position
will also be configurable to vary based on the supply
fan VFD frequency output.
• Non-Powered Convenience Outlet—Unit is provided
with a non-powered 120VAC GFCI outlet with cover on
the corner of the unit housing the compressors.
• BAS Controls—Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• Smoke Detector—A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
FIELD INSTALLED OPTIONS
• Roof Curb— 14" high, full perimeter knockdown curb,
with hinged design for quick assembly.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:38
Date
06/20/2019
Project Name
Planet Fitness Tigard,OR
Project Number
Client/Purchaser
Control Summary Page
Control Models and Unit Tags
Standard im icity Control ° JI 5ON18R 15EAA1
�f•tk* RTU t
A*< � Z78N12R 1; 5EAA1
ZJI20N18R2a5 1AI RTL ,5 6,7,i
Information is subject to change without notice.Check local codes. Printed 06/20/2019
i
.
ra YORK® SSE Guide Spec Page:39
23 09 23 Direct-digital Control system for HVAC
23 09 23. 13 Decentralized,Rooftop Units:
23 09 23. 13.A. Unit Control Board
1. ASHRAE 62-2001compliant. BTL certified.
2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal.
3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non-
condensing),with a storage temperature range from-40F to 194F;5-95%RH(non-condensing).
4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board
and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs.
5. Controller shall accept the followinginputs: space temperature,return air temperature sensor,setpointadjustment,outdoor air
temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single
and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors,
FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality,
System purge.
6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and
be Demand Control Ventilation(DCV)ready.
7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/
exhaust/reversing valve/dehumidify/occupied.
8. Unit shall provide surge protection for the controller through a circuit breaker.
9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster.
10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation.
11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the
following standard safety devices trip and shut off compressor. If any of these safety devices trip,the LCD screen will display
alarm message indicating the specific safety device that caused the lockout.
a. Loss of charge/Low-pressure switch.
b. High-pressure switch.
c. Freeze condition sensor on evaporator coil.
12. Unit control board must support each usage case:
a. Conventional thermostat with low voltage input terminals for easy installation
b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control
board to compare with associated setpoints
c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building
automation/management system
13. Anti-short cycle and low voltage protection features included.
14. Internal occupied/unoccupied scheduling
15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F.
16. Shall allow for start-up, commissioning,troubleshooting, parameter adjustment, setpoint adjustment via onboard
display and navigable menu with no additional interface tool or controls technician required.
17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating
cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test.
18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between
them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up, commissioning,
troubleshooting, parameter adjustment, setpoint adjustment.
19. Local embedded trending and scheduling. Trending data and occupancy scheduling predefined from the factory.
Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device
(cellular phone, laptop,tablet)
20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable. These
include but are not limited to:
a. Demand Ventilation Mode—enable or disable
b. Operational Setpoint—display current value
c. Supply Air Temperature(SAT)—display current value
d. Return Air Temperature(RAT)—display current value
Information is subject to change without notice.Check local codes. Printed 06/20/2019
� E Guide Spec Page:40
YORK .7.7
• e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network
Sensor, or FC Bus communicated value
f. Return Air Humidity(RAH)—display current value
g. Operational outdoor Air Temperature (OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer
board and OprOAT only if economizer is present
h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards
OAH 0-10VDC input or FC Bus communicated value
i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer
boards OAQ 0-10VDC input or FC Bus communicated value
j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board
IAQ 0-10VDC input, SA Bus Network Sensor, or FC Bus communicated value
21. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone Fan
b. Cooling
c. Heating
d. Economizer
e. Demand Ventilation
f. Power Exhaust
g. Sensors
h. Network
22. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone—Occupied status
b. Indoor Fan status
c. Cooling status
d. Heating status
e. Economizer indication whether free-cooling is available or not
f. Enabling or disabling of Demand Ventilation
g. Power Exhaust
1) Enable/disable hot-gas reheat if available
2) Warmup/Cooldown
3) Title 24 Load Shed
4) Defrost
23. A menu shall display and allow modification to the following operations and settings:
a. Firmware version (of UCB, Economizer, other peripheral boards)
b. Setting time zone
c. Network information
1) Device name that will appear on the FC Bus
2) Selection of communication protocol
3) Operational Baud Rate
4) Device ID
24. A menu shall display and allow modification to the following operations and settings:
a. Version of firmware
b. Ability to Load new firmware
c. Create a backup file of the firmware and parameter setting via USB port
d. Restore factory default parameter values and setup
e. Full and Partial Cloning of parameter setpoints from or to other units
f. Data trend exporting
25. A menu shall display and allow modification to the following operations and settings:
Information is subject to change without notice.Check local codes. Printed 06/20/2019
YORK
SSE Guide Spec Page:41
a. Unit serial number, model number and name
b. bility to reset Lockouts
c. Controller name
d. Displays the current values of all setpoints in use
e. Displays all current values for the indoor and outdoor zones
f. Displays current values related to:
) Indoor Fan
2) Cooling
3) Heating
4) Heat Pump operation
5) Economizer operation
6) Power Exhaust
7) Demand Ventilation
8) Air monitoring station
9) Hot Gas Reheat
10) Smoke Control
g. Current information for inputs; including
1) Sensors
2) Coil Sensors
3) Thermostat
4) Binary Inputs
5) Unit Protection
6) Network Inputs
7) All outputs(relay and binary)
h. Self-Test
1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning
characteristics of the system at time of startup and commissioning.
23 09 23. 13.B. Auxiliary Control Boards
1. ASHRAE 62-2001 compliant. BTL certified.
2. Economizer controller CEC Title 24 Compliant
a. Display alarms if the following occur
1) Economizer is economizing when conditions do not support
2) Economizer is not economizing when conditions do support
3) Damper Stuck
4) Excess Outdoor Air
5) Failed Sensor
3. Refrigeration Fault Detection & Diagnostics
a. There is insufficient refrigerant in any circuit
b. There is excessive refrigerant in any circuit
c. There is excessive refrigerant flow
d. There is insufficient refrigerant flow(restriction)
e. Inefficient compressor
f. Insufficient High-side heat transfer
g. Excessive High-side heat transfer(low ambient control problem, low AP)
h. Insufficient Low-side heat transfer
i. Excessive Low-side heat transfer
Information is subject to change without notice.Check local codes. Printed 06/20/2019
SSE Guide Spec Page:42
a ®YORK®
j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if
refrigerant level is very low in the system)
k. Sensor fault-Sensor data is not available
I. The unit is off
m. The ambient temperature is too low
n. The ambient temperature is too high
o. The return air wet-bulb temperature is too low
p. The return air wet-bulb temperature is too high
q. Sensor fault-The condensing temperature is lower than the ambient temperature(Could also be triggered when
the condenser is wet)
r. The suction line temperature is less than the evaporator temperature
s. The evaporator temperature is greater than the ambient temperature
t. The liquid temperature is lower than the ambient temperature
u. Sensor fault-Suction temperature or ambient temperature is invalid
v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid
w. Sensor fault-The liquid pressure or suction pressure is invalid
x. Sensor fault-The suction line temperature is invalid
y. The return air dry-bulb temperature is too low
z. The return air dry-bulb temperature is too high
aa. The Efficiency Index is below 75%of ideal
bb. The Capacity Index is below 75%of ideal
23 09 23. 13.0 Remote Accessibility:
1. ASHRAE 62-2001 compliant. BTL certified.
2. Provide the ability to adjust parameter values, setpoints, limits remotely
3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS)
4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device
Information is subject to change without notice.Check local codes. Printed 06/20/2019
START-UP & SERVICE DATA INSTRUCTION Page:43
COMMERCIAL PACKAGE UNITS
3.0 To 40.0 TONS
START-UP CHECKLIST
Date:
Job Name:
Customer Name:
Address:
City: State: Zip:
Model Number: Serial Number:
Qualified Start-up Technician: Signature:
HVAC Contractor: Phone:
Address:
Contractor's E-mail Address:
Electrical Contractor: Phone:
Distributor Name: Phone:
WARRANTY STATEMENT This start-up sheet covers all startup check points common to all
package equipment.In addition it covers essential startup check
Johnson Controls/UPG is confident that this equipment will points for a number of common installation options. Depending
operate to the owner's satisfaction if the proper procedures are upon the particular unit being started not all sections of this startup
followed and checks are made at initial start-up.This confidence is sheet will apply.Complete those sections applicable and use the
supported by the 30 day dealer protection coverage portion of our notes section to record any additional information pertinent to your
standard warranty policy which states that Johnson Controls/UPG particular installation.
will cover parts and labor on new equipment start-up failures that Warranty claims are to be made through the distributor from whom
are caused by a defect in factory workmanship or material,for a the equipment was purchased.
period of 30 days from installation.Refer to current standard
warranty policy and warranty manual found on UPGnet for details. EQUIPMENT STARTUP
In the event that communication with Johnson Controls/UPG is
required regarding technical and/or warranty concerns,all parties Use the local LCD or Mobile Access Portal(MAP)Gateway to
to the discussion should have a copy of the equipment start-up complete the start-up.
sheet for reference.A copy of the original start-up sheet should be A copy of the completed start-up sheet should be kept on file
filed with the Technical Services Department. by the distributor providing the equipment and a copy sent to:
The packaged unit is available in constant or variable air volume Johnson Controls/UPG
versions with a large variety of custom options and accessories Technical Services Department
available.Therefore,some variation in the startup procedure will 5005 York Drive
exist depending upon the products capacity,control system, Norman,OK 73069
options and accessories installed.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:44
- SAFETY WARNINGS
The inspections and recording of data outlined in this procedure AWARNING
are required for start-up of Johnson ControlslUPG's packaged
products. Industry recognized safety standards and practices Lethal voltages are present during some start-up
must be observed at all times.General industry knowledge and checks.Extreme caution must be used at all times.
experience are required to assure technician safety. It is the
responsibility of the technician to assess all potential dangers
and take all steps warranted to perform the work in a safe AWARNING
manner. By addressing those potential dangers, prior to
beginning any work,the technician can perform the work in a
safe manner with minimal risk of injury. Moving parts may be exposed during some startup
checks. Extreme caution must be used at all times.
NOTE: Read and review this entire document before beginning
any of the startup procedures.
DESIGN APPLICATION INFORMATION
This information will be available from the specifying engineer full open position and the frequency drive is operating at 60 HZ.
who selected the equipment. If the system is a VAV system the Do not proceed with the equipment start-up without the
CFM will be the airflow when the remote VAV boxes are in the design CFM information.
Design Supply Air CFM: Design Return Air CFM:
Design Outdoor Air CFM At Minimum Position:
Total External Static Pressure:
_ Supply Static Pressure:
Return Static Pressure:
Design Building Static Pressure:
Outside Air Dilution:Economizer Position Percentage: _ CFM:
Supply Gas Pressure After Regulator W/o Heat Active — Inches
ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER:
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:45
REFERENCE
General Inspection Completed See Notes
Unit inspected for shipping,storage,or rigging damage 0 0
Unit installed with proper clearances 0 0
Unit installed within slope limitations 0 0
Refrigeration system checked for gross leaks(presence of oil) 0
Terminal screws and wiring connections checked for tightness 0 0
Filters installed correctly and clean 0 0
Economizer hoods installed in operating position 0 0
Condensate drain trapped properly,refer to Installation Manual 0 ❑
Economizer damper linkage tight 0 0
Gas Heat vent hood installed 0 0
All field wiring(power and control)complete 0 0
Air Moving Inspection Completed See Notes
Alignment of drive components 0 0
Belt tension adjusted properly 0 0
Blower pulleys tight on shaft, bearing set screws tight,wheel tight to shaft 0 0
Pressure switch or transducer tubing installed properly 0 0
Exhaust Inspection Powered 0 Barometric Relief 0 Com pleted See Notes
Check hub for tightness 0
Check fan blade for clearance 0 0
Check for proper rotation 0 0
Check for proper mounting(screen faces towards unit) 0 0
Prove operation by increasing minimum setting on economizer 0 0
Economizer Inspection Standard 0 BAS 0 Completed See Notes
CO2 sensor installed Yes 0 No 0 0 0
Check economizer setting(Reference SSE Control Board LCD menu location) 0 0
Prove economizer open/close through SSE Board Setting 0 0
Reheat Mode Normal 0 or Alternate 0 Not Applicable 0
Humidity Sensor(2SH0401)
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:46
Operating Measurements -Air Flow
Fan operates with proper rotation ID Fans Exh. Fans❑ Cond. Fans
Pressure drop across dry evaporator coil(At maximum design CFM)1 MC
External Static Pressure MC
Return Static Pressure MC
Supply Static Pressure IWC
Supply Air CFM Using Dry Coil Chart CFM
Final Adjusted Supply Air CFM2 CFM
1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential.
2. Was a motor pulley adjustment or change required to obtain the correct airflow?
Was it necessary to increase of decrease the airflow to meet the design conditions?
If the motor pulley size was changed,measure the outside diameters of the motor and blower pulleys and record those diameters here;
Blower Motor HP FLA RPM
Pulley Pitch Diameter Turns Out Final Turns Out
Blower Pulley Pitch Diameter Fixed Sheave
ELECTRICAL DATA
T1 -T2 Volts T2-T3 Volts
Control Voltage Volts T1 -T3 Volts
Measured
Device Nameplate
List All Three Amperages
Supply Fan Motors,2 AMPS AMPS
Exhaust Motor(Dampers 100%) AMPS AMPS
Condenser Fan#1 AMPS AMPS
Condenser Fan#2(if equipped) AMPS AMPS
Condenser Fan#3(if equipped) AMPS AMPS
Condenser Fan#4(if equipped) AMPS AMPS
Compressor#1 AMPS AMPS
Compressor#2(if equipped) AMPS AMPS
Compressor#3(if equipped) AMPS AMPS
Compressor#4(if equipped) AMPS AMPS
1. VAV units with heat section-simulate heat call to drive VAV boxes and VFDIIGV to maximum design airflow position.
2. VAV units without heat section-VAV boxes must be set to maximum design airflow position.
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:47
4 r
OPERATING MEASUREMENTS -COOLING
Discharge Discharge Liquid Line 2 Suction Suction
Stage Pressure Temp. Temp.1 Subcooling Pressure Temp. Superheat
First # 0 0 ° # 0 _ °
Second(if equipped) # 0 #
Third(if equipped) # 0 0 # 00
Fourth(if equipped) # 0 0 # ° °
Reheat 1st Stage # 0 0 # °
1. Liquid temperature should be taken before filter/drier.
2. Subtract 10 psi from discharge pressure for estimated liquid line pressure
Outside air temperature °F db °F wb %RH
Return Air Temperature 0F db °F wb %RH
Mixed Air Temperature °F db °F wb %RH
Supply Air Temperature °F db °F wb %RH
REFRIGERANT SAFETIES
Action Completed See Notes
Prove Compressor Rotation(3 phase only)by gauge pressure 0 0
Prove High Pressure Safety,All Systems 0 0
Prove Low Pressure Safety,All Systems 0 0
OPERATING MEASUREMENTS -GAS HEATING
Fuel Type: 0 Natural Gas 0 LP Gas
Action Completed See Notes
Check for gas leaks 0 0
Prove Ventor Motor Operation 0 0
Prove Primary Safety Operation 0 0
Prove Auxiliary Safety Operation 0 0
Prove Rollout Switch Operation 0 0
Prove Smoke Detector Operation 0 0
Stage 1 IWC 0
Manifold Pressure Stage 2(if Equipped) IWC 0
Stage 3(If Equipped) IWC 0
Supply gas pressure at full fire IWC 0
Check temperature risel 0 measured at full fire `F 0
j, Input X Eff.(BTU outputl
1.08 X Temp.Rise
Information is subject to change without notice.Check local codes. Printed 06/20/2019
Page:48
OPERATIONAL MEASUREMENTS -STAGING CONTROLS
Verify Proper Operation of Heating/Cooling Staging Controls
Create a cooling demand at the Thermostat, BAS System or Simplicity SE
Verify that cooling/economizer stages are energized. 0
Create a heating demand at the Thermostat, BAS System or Simplicity SE
Verify that heating stages are energized. 0
Verify Proper Operation of the Variable Frequency Drive(If Required)
Verify that motor speed modulates with duct pressure change. 0
FINAL -INSPECTION
Verify that all operational control set points have been set to desired value ❑
Scroll through all setpoints and change as may be necessary to suit the occupant requirements.
Verify that all option parameters are correct
Scroll through all option parameters and ensure that all installed options are enabled in the software and all 0
others are disabled in the software.(Factory software settings should match the installed options)
Verify that all access panels have been closed and secured 0
OBSERVED PRODUCT DIFFICIENCIES& CONCERNS:
Information is subject to change without notice.Check local codes. Printed 06/20/2019
FOR OFFICE USE ONLY-SITE ADDRESS:
This form is recognized by most building departments in the Tri-County area for transmitting information.
Please complete this form when submitting information for plan review responses and revisions.
This form and the information it provides helps the review process and response to your project.
City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT
III Transmittal Letter
,,\It n 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 • www.tigard-or.gov
TO: 1-0 f4'\ DATE RECEIVED:
DEPT: BUILDING DIVISION RECEIVED
SEP 3 2019
FROM: / v G CITY OF TIGARD
BUILDING DIVISION
COMPANY: PiE 0 Mr Pt SID G r
PHONE: £l)3 —671 -C/59 BY'
RE: /1 2 06 S c✓f -1 G /Ay /`'Te-c_Ac L y-10a5-5?
(Site Address) / (Permit Number)
Pc Pf
(Project name or subdivision name and lot number)
ATTACHED ARE THE FOLLOWING ITEMS:
Copies: Description: Copies: Description:
Additional set(s) of plans. Revisions:
Cross section(s) and details. Wall bracing and/or lateral analysis.
Floor/roof framing. Basement and retaining walls.
Beam calculations. Engineer's calculations.
sot Other(explain): C v T ,Ct