Loading...
Specifications (21) t LC,°kt4d 'cue— . H, BRAD YOUNG & ASSOCIATES Inc. STRUCTURAL ENGINEERING Transmittal BYA Project#: 19300 Date: 8/7/2019 To: Lennox National Account Services Attn: Dave Whitten From: Lena Moses Subject: Men's Wearhouse - HVAC Replacement—Tigard, OR Comments: We have completed our assessment of the subject building's roof system capacity to the proposed HVAC loads. The new loads are resulting from replacing existing HVAC units with new units in the same location as the previous units. The existing HVAC units (RTU-2 and 3) are to be replaced with new units. An analysis of the existing roof framing showed that the new HVAC units with the existing curbs and accessories could be supported by the existing framing. Following this transmittal are structural calculations indicating that the existing roof framing meets applicable building code requirements for the new HVAC unit and curb loading. The existing curbs are to remain and the connection of the roof curb to the roof to resist overturning forces due to wind and seismic forces was not checked. These calculations are based on site survey information and HVAC information provided by Lennox. Please feel free to call me if you have any questions or if you need anything else. Thank You, Lena Moses, PE �.; a, gpeliA Staff Engineer r} c'4 71273 Brad Young, SE ` T" -_ .. _ . President ORl- r tel. 6 30 20 345 Pollasky Ave - Clovis, California 93612 • 559-323-9600 • 559-323-9633 Fax • www.byaengineering.com STRUCTURAL ENGINEERING CALCULATIONS (HVAC REPLACEMENT) MEN'S WEARHOUSE 16940 SW 72ND AVENUE TIGARD, OR BYA# 19300 August 7, 2019 Prepared For: 1-44 C 0 74. mem Lennox National Account Services I1/ /1' Branch- Seattle #191 11111, 2105 70th Ave. E, Suite 300 Fife, WA 98424 -30-ZO' BRAD YOUNG &ASSOCIATES, INC. STRUCTURAL ENGINEERING Men's Wearhouse Tigard, Oregon T.I. - New HVAC units replacing existing Design Parameters Code = 2014 OSSC (Based on 2012 IBC) Wind = 120-B, lw=1.0 Seismic = Site Class D SS= 0.962, S1 = 0.418 1=1.0 R=N/A Steel fy (W.F.)A992 = 50 ksi, UNO Steel fy (Tube)A500 Grade B =46 ksi, UNO Steel fy (Pipe)A53 Grade B = 35 ksi, UNO Steel fy (Misc.)A36 = 36 ksi, UNO Light gage studs fy = 50 ksi minimum, UNO High Strength Bolts =A325N Typical Bolts =A307 Concrete fc (Foundation) = 3000 psi, UNO Concrete-Pc (walls) = 3000 psi, UNO Concrete f'c (Columns) = 3000 psi, UNO Concrete f'c (Floor desks) = 3000 psi, UNO Rebar#3 bars = Gr. 40, fy =40,000 psi, UNO Rebar#4 and larger bars = Gr. 60, fy = 60,000 psi, UNO Welded Rebar =A706 Dimensioned Lumber = DF#2, UNO Glulam Beams = 24F-V4 @ simple spans, UNO = 24F-V8 @ Cantilever spans, UNO Wood Connectors = Simpson Strong Tie, UNO (Manufacture) (Equivalent may be used) Masonry f'm = 1500 psi, UNO - Allowable Soil Bearing Pressure = 1500 psf Note: The above material properties are typical properties and apply unless noted otherwise within this calculation package. The materials listed are not necessarily used in this design. Please see the following calculations for the actual types of materials used for this specific design. BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Follasky Ave. File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600(559)323-9633 Fax The following calculations will address the following: 1. Replacement of existing HVAC units in existing locations. All other work, if required or not addressed in this package, is by others. Loading Main Roof rDLroof� 1-1-roof) Component PSF Roofing 2.0 Rigid Insulation 1.5 Roof Sheathing 1.8 Roof Framing 4.0 Suspended Ceiling 1.8 MEP 1.0 Miscellaneous 1.9 Total Dead Load 14 Roof Live Load 20 DLroof := DLroof.psf DLroof = 14•psf LLroof LLroof'psf LLroof = 20•psf Note: When possible reduce roof live load for tributary area per ASCE 7-10 Section 4.8. When applicable live load reduction will be noted by R1. BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Poilasky Ave File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600(559)323-9633 Fax Snow Load pg := 2o•psf Ground Snow Load Ce := t.o Exposure Factor Ct := 1.0 Thermal Factor Is := 1.o Importance Factor pf.1 := o.7-Ce-Ct-Is-pg pf.1 = 14-psf pf.min Is•20•psf pf.min = 20-psf pf := max(pf 1 ,pf.min) pf = 20-psf Cs := 1.0 PS := Cs.pf Ps = 20•psf per 2014 OSSC SLroof Ps+ 5-psf SLroof = 25-psf add 5 PSF for rain on snow surcharge BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 File Name: 19300.xmcd 345 Pollasky Ave. Clovis,California,93612 Engineer: LM (559)323-9600(559)323-9633 Fax Snow Drift The parapet is -5'-0" max at the mechanical units that are getting replaced. Length of roof upwind of wall is 20' min. Length of low roof for windward is 175' max. Snow Loads pg = 2o•psf pf = 20.psf ps = 2o•psf Snow Drift- perASCE 7-10 Sections 7.7 7 := min(o.13-pg•ft + 14.pcf,3o•pcfl ,y = 16.6•pcf hp := s•ft existing parapet height Ps hb := s hb = 1.2osft non drift snow height -Y he := hp - hb he = 3.795ft max drift height lu.lee := 20 ft minimum Lu value for leeward case hd.lee := ,0.43.3 lu.lee'ft jPg • sf + 10- 1.s •ft p / hd.lee = 1.232 ft leeward drift height lu.wind := 175•ft Low Roof Length for windward case ( 3 1 ]Pg hdwind :_ 0.43• luwind• • • psf + 10- 1.5/•ft = 4.129ft windward drift height hd.wind hd1 := max(hd.lee,4'hd.windJ hd1 = 3.o97ft hd := min(hc,hd1) hd = 3.097ft drift height Pd := 7'hd pd = 51.4•psf maximum intensity of drift surcharge load - _. -- / l4. d1 2\ h w := min if hd1 <_ hc,4 hd1 , h ,8•hc w = 12.39ft drift width C J / BRAD YOUNG & ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 File Name: 19300.xmcd 345 Pollasky Ave. Clovis,California,93612 Engineer: LM (559)323-9600 (559)323-9633 Fax Item 1: There are (2) HVAC units being removed and replaced (RTU-2 & 3) in existing locations. The site survey found that the existing roof framing consists of glulam girders, glulam purlins at 8'-0" spacing, 2x6 sub-purlins @ 24" spacing and plywood roof sheathing. Check the existing roof framing for new mechanical loads. Per the information provided,the weight of the new mechanical units, including roof curbs and accessories, is as follows: WtRTU.2.new = 1209-Ib+ 297-lb+ 150 lb WtRTU.2.new = 1656lb WtRTU.3.new =- 722.Ib+ 306-Ib+ 75 lb WtRTU.3.new = llo3lb BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Pollasky Ave. File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600 (559)323-9633 Fax efr __\.-\()01,,.‘4-1 Y)A. J ' 111' ' .1.4" 1 jilliL." ' ' 1 ' ' , il' ailliit: ' " 717*-11* .,..iw.. ..J:rt: it i i dA-L+ „o-,oir 4. �,ty d,,,, ,v 1 r +; 4 0..., / 7. (�? A ICI `du �L r; ti I ifs,.,0,, -r ' • !! 9 Y s 7-`i aC i -1,14 t --^ itt ,,,1 ,, . 1 III r✓J ti '12. 3? , '" iv k ti4 , ' 1 • Member 1 - (E) 3 1/8 x 22 1/2 glulam purlins A RTU-2 Check existing roof purlin at RTU-2. L := 32.5-ft length of member w •= s ft+ 8-ft tributary 2 wtributary _ 8 ft Tributary width •` - 2 At := "tributaryAt = 26oft t At \\ R i := if At � 200•ft2,1 ,if At < 600•ft2,1.2— 0.001 ,0.6 R 1 = 0.940 ft i-I WDL DLroof'wtributary wDL - 112-plf wLL R1 'LLroof'`Ntributary wLL = 150-plf wSL := SLroof'wtributary wSL = 200•plf Half of the weight of the unit is supported by a girder and the other half is supported by 2 roof purlins. Divide the weight of unit by 4 to get point load on each purlin. P RTU.new 4_ WtRTU.2.new P RTU.new -- 414 lb at L= 7 ft Use (E) 3 1/8 x 22 1/5 GLB See attached BRAD YOUNG & ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Pollasky Ave. File Name: 19300.xrncd Clovis,California,93612 Engineer: LM (559)323-9600(559)323-9633 fax • Brad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: 559-323-9600 Project Descr: Arnted. 0 AUG 2019. 4 3:PIA Wood Beam File=O\drawings12019\193001dwg\Calcsu9300ec6 . Software copyright ENERCALC,INC 1983-2019,Build:1019 7 30 . fit:- :.#KtG0471 3: t4D Y{ N tltaf{It# . DESCRIPTION: Member 1 CODE REFERENCES Calculations per NDS 2012, IBC 2012, CBC 2013,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 2400 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 1850 psi Ebend-xx 1800 ksi Fc-Prll 1650 psi Eminbend-xx 950 ksi Wood Species : DF/DF Fc-Perp 650 psi Ebend-yy 1600ksi Wood Grade :24F-V4 Fv 265 psi Eminbend-yy 850 ksi Ft 1100 psi Density 31.21 pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(0.414) D(0.112)Lr(0.15)S(0.2) O d b b Q 3.125x22.5 Span=32.50 ft Applied Loads Service loads entered. Load Factors writ be applied for calculations. Uniform Load: D=0.1120, Lr=0.150, S=0.20, Tributary Width=1.0 ft,(Roof) Point Load: D=0.4140 k @ 7.0 ft,(RTU) DESIGN SUMMARY Desi•n OK Maximum Bending Stress Ratio = 0.745: 1 Maximum Shear Stress Ratio = 0.339 : 1 Section used for this span 3.125x22.5 Section used for this span 3.125x22.5 fb:Actual 1,941.28 psi fv:Actual = 103.25 psi FB:Allowable = 2,606.92 psi Fv:Allowable = 304.75 psi Load Combination +D+S Load Combination +D+S Location of maximum on span = 16.013ft Location of maximum on span = 0.000 ft Span It where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.946 in Ratio= 412>=240 Max Upward Transient Deflection 0.000 in Ratio= 0<240 Max Downward Total Deflection 1.534 in Ratio= 254>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 5.395 5.159 Overall MINimum 3.250 3.250 D Only 2.145 1.909 +D+Lr 4.582 4.347 +D+S 5.395 5.159 +D+0.750Lr 3.973 3.737 +D+0.750S 4.582 4.347 40.60D 1.287 1.146 Lr Only 2.438 2.438 S Only 3.250 3.250 rr` Member 2 - (E) 3 1/8 x 22 1/2 glulam purlins @ RTU-3 Check existing roof purlin at RTU-3. L := 32.5•ft length of member wtributary ._ 2 s ft+ s ft wtributary = s ft Tributary width •� 2 At := "tributaryAt = 26oft At \\ R1 := if At <_ 200•ft2,1 ,if At < 600•ft2,1.2—0.001--2 ,0.6 R 1 = 0.940 ft )) wDL := Di-roof wtributary wDL = 112•plf wLL := R1 'LLroof'wtributary wLL = 150•plf wSL := SI-roof wtributary wSL = 2oo•plf The weight of the unit is supported by 2 roof purlins. Divide the weight of unit by 4 to get point load at each support location. P P — RTU.new —WtRTU.3.new RTU.new 276 lb at L= 9 ft& 15 ft 4 Use (E) 31/8 x 22 1/5 GLB See attached BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Pollasky Ave. File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600(559)323-9633 Fax • Brad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: 559-323-9600 Project Descr: Pr,nled .2u'-1 43P"..n File=0\drawings120191193001dwg\Calcs119300 ec6. Wood Beam Software copyright ENERCALC,INC 1983-2019,Build:10.19.1.30 . ?* ;- 1t UDt479'3 -.;, :4 . :t * ,.rr,l f:; ,_.. ,. . 01WY jNa C:-Tit_ DESCRIPTION: Member 2 CODE REFERENCES Calculations per NDS 2012, IBC 2012, CBC 2013,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 2,400.0 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 1,850.0 psi Ebend-xx 1,800.0 ksi Fc-Pr!! 1,650.0 psi Eminbend-xx 950.0 ksi Wood Species : DF/DF Fc-Perp 650.0 psi Ebend-yy 1,600.0 ksi Wood Grade :24F-V4 Fv 265.0 psi Eminbend-yy 850.0 ksi Ft 1,100.0 psi Density 31210 pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling 0(0.276) D(0276) D(0.1112)Lr(0.15)S(0.2) b a a b a -) 3.125x22.5 Span=32.50 ft Applied Loads Service loads entered Load Factors will be applied for calculations Uniform Load: D=0.1120, Lr=0.150, S=0.20, Tributary Width=1.0 ft,(Roof) Point Load: D=0.2760 k @ 9.0 ft,(RTU) Point Load: D=0.2760 k @ 15.0 ft,(RTU) DESIGN SUMMARY . . Orsi.11 DK Maximum Bending Stress Ratio = 0.778 1 Maximum Shear Stress Ratio = 0.340 : 1 Section used for this span 3.125x22.5 Section used for this span 3.125x22.5 fb:Actual = 2,028.51 psi Iv:Actual = 103.75 psi FB:Allowable = 2,606.92 psi Fv:Allowable = 304.75 psi Load Combination +0+S Load Combination +D+S Location of maximum on span = 15.538ft Location of maximum on span = 0.000 ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.946 in Ratio= 412>=240 Max Upward Transient Deflection 0.000 in Ratio= 0<240 Max Downward Total Deflection 1.587 in Ratio= 245>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 5.418 5.274 Overall MINimum 3.250 3.250 D Only 2.168 2.024 +D+Lr 4.606 4.461 +D+S 5.418 5.274 +D+0.750Lr 3.996 3.852 +D+0.750S 4.606 4,461 +0.600 1.301 1.214 Lr Only 2.438 2.438 S Only 3.250 3.250 10 Member 3 - (E)4x12 blocking RTU-2 & 3 Check existing blocking at RTU-2 (highest weight). L := 8-ft length of member w _ 2 ft+ ft 4.5ft Tributary width tributary - 2 w tributary 2 At := "tributary At = 36ft ( i A R1 := if At _< 200•ft2,1 ,if At < 600•ft2,1.2—0.001.-2 ,0.6 R1 = 1.000 ft // wDL := DLroof'wtributary wDL = 63•pif wLL := R •LL roof'wtributary wLL = 90•plf WSL := SLroof'wtributary wSL = 113•pif To be conservative, apply half of the weight of the unit at midspan. Divide the weight of unit by 2 to get point load on the blocking. P - P RTU.new = WtRTU.2.new RTU.new •- 828 lb at L=4 ft 2 Use (E) 4x12 See attached BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Ponasky Ave. File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600{559)323-9633 Fax • Brad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: 559-323-9600 Project Descr: ;,,u(i 20 is 4 4317m _ I File=0 tdrawins120191193001dw\Caicsl19300 ec6 Wood Beam Software copyright ENERCALC,INC 1983-2019 Build 10191 30 t o E;f t 60t 4793 '= RAt YQUN�a1 A Qt T ; DESCRIPTION: Member 3 CODE REFERENCES Calculations per NDS 2012, IBC 2012, CBC 2013,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 1,000.0 psi E Modulus of Elasticity Load Combination ASCE 7-10 Fb- 1,000.0 psi Ebend-xx 1,700.0ksi Fc-Pr!' 1,500.0 psi Eminbend-xx 620.0 ksi Wood Species Douglas Fir-Larch Fc-Perp 625.0 psi Wood Grade : No.1 Fv 180.0 psi Ft 675.0 psi Density 31.210pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling 0(0.828) D(0.063)Lr(0.09)S(0.113) 0 0 a a 4x12 Span=8.Oft Applied Loads Service loads entered. Load Factors will be applied for calculations. Uniform Load D=0.0630, Lr=0.090, S=0.1130, Tributary Width=1.0 ft,(Roof) Point Load: D=0.8280 k @ 4.0 ft,(RTU) DESIGN SUMMARY Oea.n OK Maximum Bending Stress Ratio = 0,394 1 Maximum Shear Stress Ratio = 0.175 : 1 Section used for this span 4x12 Section used for this span 4x12 fb:Actual 498.02 psi fv:Actual 36.33 psi FB:Allowable = 1,265.00 psi Fv:Allowable = 207.00 psi Load Combination +D+5 Load Combination +0+S Location of maximum on span = 4.000ft Location of maximum on span = 7.066ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.015 in Ratio= 6470>=240 Max Upward Transient Deflection 0.000 in Ratio= 0<240 Max Downward Total Deflection 0.045 in Ratio= 2140>=180 Max Upward Total Deflection 0.000 in Ratio= 0<180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Overall MAXimum 1.118 1.118 Overall MINimum 0.452 0.452 D Only 0.666 0.666 +D+Lr 1.026 1.026 +D+S 1.118 1,118 +0+0.750Lr 0.936 0.936 +D+0.750S 1.005 1.005 +0.60D 0.400 0.400 Lr Only 0.360 0.360 S Only 0.452 0.452 fes. Member 4 - (E) 6 3/4 x 39 giuiam girder RTU-2 Check existing roof girder at RTU-2. L := 3o.5•ft length of member 32.5 ft+ 32.5-ft wtributary 2 wtributary = 32.s ft Tributary width At := "tributary At = 991 ft2 A \` R1 := if At <_ 200•ft2,1 ,if At < 600•ft2,1.2-0.001.-2 ,0.6 R 1 = 0.600 L ` ft // WDL DLroof'wtributary wDL = 455•pif WLL R1"1-1-roof wtributary wLL = 390•plf wSL := SLroof'wtributary wSL = 813 plf wSL.drift pd'wtributary from L= 0 to 12.5 ft wSL.drift = 1671•plf Apply all of the weight of the unit on this girder. Divide the weight of unit by 2 to get point load at each support location. WtRTU.2.new PRTU.new PRTU.new - 828 Ib at L= 20 ft& 25 ft 2 - Use (E) 6 3/4 x 39 GLB See attached BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young&Associates Print Date: 8/6/2019 STRUCTURAL ENGINEERING File Name: 19300.xmcd 345PollaakyAve. Engineer: LM Clovis,California,93612 (559)323-9600(559)323-9633 Fax ; � Brad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: _ Clovis,CA 93612 Project ID: 559-323-9600 Project Descr: Prated: 6 AUG 2019; 5 04P I File=02drawings12019N9300\dwglCalcs119300 ec6. ' Wood Beam Software copyright ENERCALCINC 1983-2019 Build:1019130. DESCRIPTION: Member 4 CODE REFERENCES Calculations per NDS 2012, IBC 2012,CBC 2013,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 2,400.0 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 1,850.0 psi Ebend-xx 1,800.0 ksi Fc-Prll 1,650.0 psi Eminbend-xx 950.0 ksi Wood Species :DF/DF Fc-Perp 650.0 psi Ebend-yy 1,600.0 ksi Wood Grade :24F-V4 Fv 265.0 psi Eminbend-yy 850.0 ksi Ft 1,100.0 psi Density 31.2100 Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(0.828) D(0.828) S 1.671,0' 455)Lr(0.39 S 0.813 6.75x39 A Span=30.50 ft Applied Loads Service loads entered. Load Factors will be applied for calculations. Uniform Load: D=0.4550, Lr=0.390, S=0.8130, Tributary Width=1,0 ft,(Roof) Varying Uniform Load: S=1.671->0.0 kilt,Extent=0.0—>>12.50 ft, Trib Width=1.0 ft,(Snow Drift) Point Load: D=0.8280 k @ 20.0 ft,(RTU) Point Load: D=0.8280 k @ 25.0 ft,(RTU) DESIGN SUMMARY ;ked- ' Maximum Bending Stress Ratio = 0.53& 1 Maximum Shear Stress Ratio - 0.374 : 1 Section used for this span 6.75x39 Section used for this span 6.75x39 fb:Actual = 1,235.78 psi fv:Actual = 113.95 psi FB:Allowable 2,299.07 psi Fv:Allowable = 304.75 psi Load Combination +D+S Load Combination +D+S Location of maximum on span = 14.471 ft Location of maximum on span = 0.000 ft Span#where maximum occurs = Span#1 Span#where maximum occurs = Span#1 Maximum Deflection Max Downward Transient Deflection 0.334 in Ratio= 1096>=240 Max Upward Transient Deflection 0.000 in Ratio= 0<240 Max Downward Total Deflection 0.502 in Ratio= 729>=180 _ Max Upward Total Deflection . , 0.000 in Ratio= _Lima_ . ,y Vertical Reactions Support notation:Far left is#1 Values In KIPS Load Combination Support 1 Support 2 Overall MAXimum — 28.788 21.985 Overall MINimum 21.415 13.825 D Only 7.373 8.160 +D+Lr 13.321 14.108 +D+S 28.788 21.985 +D+0,750Lr 11.834 12.621 +0+0.750S 23.435 18.529 +0,60D 4.424 4.896 • Brad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: 559-323-9600 Project Descr: Pi nted: S AUG 20'19, 5 04PM – — File=0:ldrawings120191193001dwg1Calcs119300.eo6 Wood Beam Software copyright ENERCALC,INC.1983-2019,Build:10.19.1.30 DESCRIPTION: Member 4 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Lr Only 5.948 _.._5.948--- --. ----- -----__..._– S Only 21.415 13.825 Member 5 - (E) 6 3/4 x 39 qlulam girder C . RTU-3 Check existing roof girder at RTU-3. L := 9•ft+4o•ft+9-ft length of member wtributary •— 2 32.5 ft+32.5•ft wtributary = 32.5 ft Tributary width At := "tributary At = 1885 ft2 1 A \ R1 := if At < 200.ft2,1 ,if At < 600•ft2,1.2- 0.001 2 ,0.6 R 1 = 0.600 ft ii WDL := Diroof-wtributary wDL = 455•plf wLL := R1LLroof'wtributary wLL = 390•plf wSL := SLroof'wtributary wSL = 813•plf Apply all of the weight of the unit on this girder. PRTU.new := WtRTU.3.new PRTU.new = 103 lb at L2 = 35 ft PRTU.exist 1500•Ib PRTU.exist = isoolb at L1 = 0 ft& L2 = 36 ft Point Load at cantilevered end (L1 =0 ft) Area _ (40•ft—2.9-ft w Area - 357 T1 cantilever — \ 2 tributary cantilever — PDL DLroof'Areacantilever PDL = 5005 lb PLL := R1•LLroof•Areacantilever PLL = 429o1b PSL := SLroof-Areacantilever PSL = 8937 lb Point Load at cantilevered end (L3 = ft) -from Member 4 reactions at Support#2 PDL := 8160•Ib PDL = 8160 lb PLL �-- 5948•1b _ . __ PLL = 59481b PSL := 13825•lb PSL = 13825 lb Use (E) 6 3/4 x 39 GLB See attached BRAD YOUNG &ASSOCIATES Copyright 2019 Brad Young &Associates STRUCTURAL ENGINEERING Print Date: 8/6/2019 345 Follasky Ave. File Name: 19300.xmcd Clovis,California,93612 Engineer: LM (559)323-9600 (559)323-9633 Fax 6 Bred Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: " 559-323-9600 Project Descr: Pnnted: 6 AUG 2019, 5{.':P M-1 " IW OOd BeamFile=Oldrawings120191193001dwg1Calcs119300 ec6 Software copyright ENERCALC INC 1983.2019 Build 10191 30 DESCRIPTION: Member 5 CODE REFERENCES Calculations per NDS 2012, IBC 2012,CBC 2013,ASCE 7-10 Load Combination Set:ASCE 7-10 Material Properties Analysis Method: Allowable Stress Design Fb+ 2,400.0 psi E:Modulus of Elasticity Load Combination ASCE 7-10 Fb- 2,400.0 psi Ebend-xx 1,800.0ksi Fc-Prll 1,650.0 psi Eminbend-xx 950.Oksi Wood Species :DF/DF Fc-Perp 650.0 psi Ebend-yy 1,600.0ksi Wood Grade :24F-V8 Fv 265.0 psi Eminbend-yy 850.0ksi Ft 1,100.0 psi Density 31.210pcf Beam Bracing : Beam is Fully Braced against lateral-torsional buckling D(5.005)IA41tt.229)S(8.937) D( 1130 D(8.16)Lr(5.948)S(13.825) D(0.455)Lr(039)S(0.813) r D(0.455)Lr(0.39)S(0.813) c I D(0.455) bLr(0.39)S(0.813) 6.75x39 ,, 6.75x39 6.75x39 Span=9.0ft Span=40.0 ft Span=9.0 ft Applied Loads Service loads entered. Load Factors will be applied for calculations. Load for Span Number 1 Uniform Load: D=0.4550, Lr=0.390, S=0.8130, Tributary Width=1.0 ft,(Roof) Point Load: 0=5.005, Lr=4.290, S=8.937 k @ 0.0 ft,(Roof) Point Load: D=1.50 k @ 0.0 ft,(RTU) Load for Span Number 2 Uniform Load: D=0.4550, Lr=0.390, S=0.8130, Tributary Width=1.0 ft,(Roof) Point Load: D=1.103 k @ 35,0 ft,(RTU) Point Load: 0=1,50 k @ 36.0 ft,(RTU) Load for Span Number 3 Uniform Load: D=0.4550, Lr=0.390, S=0.8130, Tributary Width=1.0 ft,(Roof) Point Load: D=8.160, Lr=5.948, S=13.825 k @ 9.0 ft,(Roof) DESIGN SUMMARY Desi'n Maximum Bending Stress Ratio - 0,781: 1 Maximum Shear Stress Ratio = 0.540 : 1 Section used for this span 6.75x39 Section used for this span 6.75x39 lb:Actual = 1,747,76 psi fv:Actual = 167.35 psi FB:Allowable = 2,237.57 psi Fv:Allowable = 304.75 psi Load Combination +D+S Load Combination +D+S .I rwation of maximum on span = _ 40.000ft Location of maximum on span = 40.000 ft Span#where maximum occurs = Span#2 Span#where maximum occurs = Span 4 2 Maximum Deflection Max Downward Transient Deflection 0.293 in Ratio= 736>=240 Max Upward Transient Deflection -0.056 in Ratio= 8644>=240 Max Downward Total Deflection 0.463 in Ratio= 466>=180 Max Upward Total Deflection -0.090 in Ratio= 5342>=180 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Support 3 Support 4 ---- Overall MAXimum 51.030 62.544 --------------- -----..... - Overall MINimum 31.414 38.502 Bad Young&Associates,Inc. Project Title: 345 Pollasky Avenue Engineer: Clovis,CA 93612 Project ID: " 559-323-9600 Project Descr: Printed: n AUG 2019. 5:03PM Wood BeamFile=0:1drawings120191193001dwg1Catcs119300.ec6. Software copyright ENERCALC,INC.1983-2019,Build:10.19.1.30. �L? QutCQT1, DESCRIPTION: Member 5 Vertical Reactions Support notation:Far left is#1 Values in KIPS Load Combination Support 1 Support 2 Support 3 Support 4 D Only 19.616 24,043 +D+Lr 34.842 41.674 +D+S 51.030 62.544 +D+0.750Lr 31.036 37.266 +D+0.750S 43.176 52.919 +0.60D 11.769 14.426 Lr Only 15.227 17.631 S Only 31.414 38.502