Loading...
Specifications (43) r\s7.-acs ► 5 -- ootS`� STRUCTURAL INTEGRITY. LLC Design Memorandum To: Matt Greiner, LX Design From: Shane Earp, RE Project: Knez Residence Remodel Project Location: 14980 SW 100th Ave., Tigard, OR Project No.: 19192 Re: Floor Joists Calculation It is my understanding a non-loadbearing wall is to be moved on the main floor level. The wall supports ceiling joists only, there is not any snow or floor live load on the ceiling joists. The new wall bears on floor joists approximately 8"from the support. The joists span 10'-0"and are 2x12's @ 16" o/c. Attached is a calculation for the subject floor joists. The floor joists are adequate to support floor live load, floor dead load and the wall above. Please contact my office if you have any questions or comments. flop PRO ph,* �5 � GINE 410 44' w 58521PE .A. .. ..: r OREGON 4*. 14, t° 4 BANE R. 0 EXPIRES: 12-31-2019 724 MAIN ST.,SUITE 214, KLAMATH FALLS,OR 97601 541.884.1081 Project:19192 \Nip StruCalc 9.0 Lp/ageof / Location:JST1 Floor Joist [2015 International Building Code(2015 NDS)] �r 1.5 IN x 11.25 IN x 10.0 FT @16O.C. #2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 9/3/2019 12:36:03 PM Section Adequate By: 136.6% Controlling Factor:Shear DEFLECTIONS Center LOADING DIAGRAM Live Load 0.04 IN L/2848 Dead Load 0.03 in Total Load 0.07 IN L/1608 Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240 REACTIONS A a Live Load 267 lb 267 lb Dead Load 589 lb 144 lb Total Load 856 lb 411 lb Bearing Length 0.91 in 0.44 in SUPPORT LOADS A B Live Load 200 plf 200 plf _._..._.. . , Dead Load 442 plf 108 plf to ft Total Load 642 plf 308 plf MATERIAL PROPERTIES #2-Douglas-Fir-Larch JOIST DATA Center Base Values Adjusted Span Length 10 ft Bending Stress: Fb= 900 psi Fb'= 1035 psi Unbraced Length-Top 0 ft Cd=1.00 CF=1.00 Cr=1.15 Unbraced Length-Bottom 0 ft Shear Stress: Fv= 180 psi Fv'= 180 psi Floor sheathing applied to top of joists-top of joists fully braced. Cd=1.00 Floor Duration Factor 1.00 Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Comp.-to Grain: Fc--= 625 psi Fc--'= 625 psi JOIST LOADING Uniform Floor Loading Center Controlling Moment: 1151 ft-lb Live Load LL= 40 psf 4.4 Ft from left support of span 2(Center Span) Dead Load DL= 15 psf Created by combining all dead loads and live loads on span(s)2 Total Load TL= 55 psf Controlling Shear: 856 lb TL Adj.For Joist Spacing wT= 73.3 plf At left support of span 2(Center Span) Wall Loading Created by combining all dead loads and live loads on span(s)2 Wall One Live Load(-to Joists): L1 = 0 plf Comparisons with required sections: Req'd Provi ed Dead Load(-to Joists)D1 = 400 plf Section Modulus: 13.35 in3 31.64 in3 Load Location X1 = 0.83 ft Area(Shear): 7.13 in2 16.88 in2 Moment of Inertia(deflection): 26.57 in4 177.98 in4 Moment: 1151 ft-lb 2729 ft-lb Shear: 856 lb 2025 lb