Report (75) COMcheck Software Version 4.1.1.0
Interior Lighting Compliance ``' '�'
Certificate r :- ..�
��\°fi1'c',«( , 1,)IVIS 90 `.
Section 1: Project Information
Energy Code: 2014 Oregon Energy Efficiency Specialty Code
Project Title: BOX LUNCH
Project Type:Alteration
Construction Site: Owner/Agent: Designer/Contractor:
Portland,OR 97223
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B x C)
Retail:Sales Area(Ceiling Height 11 ft.) 1825 1.5 2738
Allowance:Furniture,clothing,cosmetics highlighting/Fix. ID:C 799(a) 1.4 1119(b)
Allowance:Furniture,clothing,cosmetics highlighting/Fix.ID:C 740(a) 1.4 1036(b)
Common Space Types:Restrooms:Exempt(Ceiling Height 8 ft.)
Common Space Types:Active Storage:Exempt(Ceiling Height 11 ft.)
Common Space Types:Corridor/Transition:Exempt(Ceiling Height 10 ft.)
Total Allowed Watts= 4892
(a)Area claimed may exceed total floor area when Retail Merchandise Highlighting allowance(s)are specified.
(b) Allowance is(B x C)or the actual wattage of the fixtures given in Section 2,whichever is less.
Area Category Exemption Qualifications
Total Wattage Total Pre-Alt #Fixtures
Activity Area Pre-Alt. Post-Alt. Fixtures Repl./Added
Common Space Types:Restrooms(57 sq.ft.): Exemption:Less than 100 100 N/A 0
10 fixtures replaced.
Common Space Types:Active Storage(284 sq.ft.): Exemption:Less 320 320 N/A 0
than 10 fixtures replaced.
Common Space Types:Corridor/Transition(99 sq.ft.): Exemption: 64 64 N/A 0
Less than 10 fixtures replaced.
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Retail:Sales Area(1825 sq.fL) i
Track lighting 1:C:SALES TRACK:Wattage based on circuit breaker capacity(15 amps x 0 0 1800 1800
120 volts)
- 1— 6- _
Track lighting 2:C:DISPLAY TRACK:Wattage based on circuit breaker capacity(15 0 0 1800 1800
amps x 120 volts)
Common Space Types:Restrooms(57 sq.ft.):Exempt
Incandescent 2:EXIST:FAN/LIGHT COMBO:Incandescent 100W: 1 1 100 100
Common Space Types:Active Storage(284 sq.ft.):Exempt
Linear Fluorescent 2:EXIST:4'STRIP:48"T8 32W:Electronic: 2 5 64 320
Common Space Types:Corridor/Transition(99 soft):Exempt
Linear Fluorescent 3:EXIST:4'STRIP:48"T8 32W:Electronic: 2 1 64 64
Total Proposed Watts= 4500
Section 4: Requirements Checklist
Project Title: BOX LUNCH Report date: 07/23/19
Data filename:J:\Box Lunch\190400\Docs\MEP\190400 COMCHECK.cck Page 1 of 4
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
Li 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Wattage:4892 Proposed Wattage:4500
Complies:YES
Mandatory Requirements:
Li 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section:
❑ 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
Exception(s):
❑ Retail spaces adjacent to vertical glazing(retail spaces under overhead glazing are not exempt).
❑ Display,exhibition and specialty lighting
❑ HID lamps 150 watts or less.
❑ Spaces required to have occupancy sensors.
Plans reference page/section:
❑ 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Exception(s):
LI Lighting systems serving areas designated as security or emergency areas that must be continuously lighted.
❑ Lighting in public areas such as concourses,stairways or corridors that are elements of the means of egress with switches that
are accessible only to authorized personnel.
❑ Lighting for warehouses,parking garages or spaces using less than 0.5 watts per square foot.
❑ Lighting for contiguous,single-tenant retail spaces.
Plans reference page/section:
❑i 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section:
❑ 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Exception(s):
❑ Building exits as defined in Section 1002 of the Oregon Structural Specialty Code.
Plans reference page/section:
❑ 7. Additional controls.Each area that is required to have a manual control shall have additional controls that meet the requirements of
Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section:
• $ Light reduction controls. aah space required toliave a manual control also aliowsTor reduang the coririected lighiing'loadFy atre`ast
50 percent by either
1)controlling(dimming or multi-level switching)all luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
Exception(s):
Li Only one luminaire in space.
❑ An occupant-sensing device controls the area.
❑ The area is a corridor,storeroom,restroom,public lobby or sleeping unit.
LI Electrical and mechanical room.
Project Title: BOX LUNCH Report date: 07/23/19
Data filename:J:\Box Lunch\190400\Docs\MEP\190400 COMCHECK.cck Page 2 of 4
❑ Areas that use less than 0.6 Watts/sq.ft.
Plans reference page/section:
❑ 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:
1)a scheduled basis,using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area is unoccupied.
Exception(s):
❑ Sleeping units,patient care areas;and spaces where automatic shutoff would endanger safety or security.
Plans reference page/section:
❑ 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section:
❑ 11.An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Exception(s):
❑ Classrooms and lecture halls.
❑ Conference,meeting and training rooms.
❑ Employee lunch and break rooms.
❑ Rooms used for document copying and printing.
❑ Office spaces up to 300 square feet.
❑ Restrooms.
❑ Dressing,fitting and locker rooms.
Plans reference page/section:
❑ 12.Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Plans reference page/section:
❑ 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that:1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Exception(s):
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,where captive-key override is
utilized,override time is permitted to exceed 2 hours.
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,the area controlled shall not exceed
20,000 square feet.
Plans reference page/section:
❑ 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Exception(s):
❑ Retail stores and associated malls,restaurants,grocery stores,places of religious worship,theaters and exterior lighting zones.
❑ Single zone electronic time control devices and self-contained wall box preset lighting controls.
Plans reference page/section:
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section:
❑ 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Project Title: BOX LUNCH Report date: 07/23/19
Data filename:J:\Box Lunch\190400\Docs\MEP\190400 COMCHECK.cck Page 3 of 4
Exception(s):
Where electronic high-frequency ballasts are used.
p Luminaires on emergency circuits.
D Luminaires with no available pair in the same area.
Plans reference page/section:
17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section:
❑ 18.Each dwelling unit in a building is metered separately.
Plans reference page/section:
Interior Lighting PASSES
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the i.ndatory requirements in the Requirements
Checklist. /
f 7. a5.. I
Name-Tit a Si. ature ) Date
Project Title: BOX LUNCH Report date: 07/23/19
Data filename:J:\Box Lunch\190400\Docs\MEP\190400 COMCHECK.cck Page 4 of 4