Report (74) e‘Ve- • ® JamesHardie HardiePaneI®7L . Vertical Siding Commercial DECEMBER 2015 MULTI-FAMILY/COMMERCIAL INSTALLATION REQUIREMENTS-PRIMED&COLORPLUS® PRODUCTS Visit www.JamesHardieCommercial.com for the most recent version. SMOOTH • CEDARMILL® • SELECT SIERRA 8 • STUCCO • IMPORTANT FAILURE TO INSTALL AND FINISH THIS PRODUCT IN ACCORDANCE WITH APPLICABLE BUILDING CODES AND JAMES HARDIE WRITTEN APPLICATION INSTRUCTIONS MAY LEAD TO PERSONAL INJURY,AFFECT SYSTEM PERFORMANCE,VIOLATE LOCAL BUILDING CODES,AND VOID THE PRODUCT ONLY WARRANTY.BEFORE INSTALLATION,CONFIRM THAT YOU ARE USING THE CORRECT HARDIEZONE®INSTRUCTIONS.TO DETERMINE WHICH HARDIEZONE PRODUCT APPLIES TO YOUR LOCATION,VISIT WWW.HARDIEZONE.COM OR CALL 1-866-942-7343(866 9HARDIE) D STORAGE&HANDLING: A CUTTING INSTRUCTIONS* Store flat and keep dry and OUTDOORS equipped with a HardieBlade®saw INDOORS JUL6 2019 covered prior to installation.Installing 1.Position cutting station so that wind blade and vacuum dust extraction 1.NEVER cut with power saws indoo product wet or saturated may result will blow dust away from user and c.Good: Circular saw with a 2.Cut only using score and snacq r GARD in shrinkage at butt joints.Carry others in working area. HardieBlade saw blade(for low to electric or pneumatic). �`I ' I product on edge. Protect edges and 2.Use one of the following methods: moderate cutting volume) 3.Position cutting station in n�'i J 4I,tiid`a� DIVISION corners from breakage.James Hardie a.Best: i.Score and snap ii.Shears is not responsible for damage caused (manual,electric or pneumatic)* *Shears and score/snap methods may not by improper storage and b.Better: Dust reducing circular saw be suitable for products thicker than 1/2 in. NEVER dry sweep Use wet suppression or vacuum handling of the o product. NIOSH-approved respirators can be used in conjunction with above cutting practices to further reduce dust exposures.Additional exposure information is available at www.jameshardie.com to help you determine the most appropriate cutting method for your job requirements.If concern still exists about exposure levels or you do not comply with the above practices,you should always consult a qualified industrial hygienist or contact the manufacturer for further information. 61x163105 GENERAL REQUIREMENTS: •Refer to table 1 for James Hardie's multifamily/commercial drainage requirements. •HardiePanel®vertical siding can be installed over braced wood or steel studs spaced a maximum of 2 ft.(610mm)o.c.Irregularities in framing and sheathing can mirror through the finished application. •Consult ESR1844 for fastener schedule as well as additional technical information at www.jameshardiecommercial.com. •A water-resistive barrier is required in accordance with local building code requirements.The water-resistive barrier must be appropriately installed with penetration and junction flashing in accordance with local building code requirements.James Hardie will assume no responsibility for water infiltration.James Hardie does market HardieWrap®Weather Barrier,a non-woven non-perforated housewrapt,which complies with building code requirements. - •Information on installing James Hardie®products over foam can be located in JH Tech Bulletin 19 at www.jameshardie.com. •Do not install James Hardie products,such that they may remain in contact with standing water. •HardiePanel vertical siding may be installed on vertical wall applications only. •DO NOT use HardiePanel vertical siding in Fascia or Trim applications. •The designer and/or architect shall take into consideration the coefficient of thermal expansion and moisture movement of the product in their design.These values can be found in the Technical Bulletin#8"Expansion Characteristics of James Hardie®Siding Products"at www.jameshardiecommercial.com. Table 1:HardiePanel®Siding—Wall Drainage Requirements xterior Wall Drainage Requirement-. ich Eave Overhang Wi' it a Minimum 12-inch Eave Overhang Vertical Joints Vertical Joints Vertical Joints Vertical Joints formed by: formed by formed by: formed by Building Height Board and Batten; Expressed Seam Board and Batten; Expressed Seam (Stories) Moderate Contact; Joints Moderate Contact; Joints Caulk Caulk James Hardie 7 story building 6 story building Panel Products> 6 story building Rainscreen min.3/8 in.air gap)3 30%of Building's 4 story building ( 9 p) Total Exterior Wall 3 story building 2 story building Covering 1 story building WRB' James Hardie 7 story building 6story building 6, Rainscreen(min.3/8 in.air gap)3 rarj6i rroaucts< 5 story building 30%of Building's 4 story building Drainage Plane(e.g.drainable WRB) Total Exterior Wall 3 story building 2storybuilding with 90%drainage Covering 1 story building WRB' efficiency2 'Water-resistive Barrier and drainage requirements as defined by building code. 'Water-resistive Barrier as defined by local building code that is manufactured in a manner to enhance drainage,must meet minimum 90%drainage efficiency when tested in accordance with ASTM E2273 or other recognized national standards. 3 Water-resistive Barrier(WRB)as defined by building code and a minimum 3/8 in.(10mm)air space between the WRB and the panel siding(formed by minimum 3/8 in.furring). 'DANGER:Do not breathe dust Fiber cement is nota health hazard when handled or stored in Sr original,unaltered condition.The hazard associated with fber cement arises from crystalline silica present in the dust generated by activities such as cutting,rebating,drilling, from this product.Respirable routing,sawing,croshing,or otherwise shooing fber cement,and when cleaning tp,disposing of or moving the dust When doing any of these activities In a manner that generates dust:(1)follow James Hardie insbuctiars and best practices to reduce or limit the release of dust;(2)warn others in the area to avoid the dust;(3)when using mechanical saw or high speed cutting tools,work outdoors and use dust collection equipment;and(4)if no other dust controls are available,wear a Crystalline Silica Dust causes NIOSH-approved dust mask or respirator(e.g.,the N 95 dust mask). damage to lungs and respiratory Refer to the product Safety Data Sheet before use.Do not handle product until all safety precautions have been read and understood.Wash hands and face thoroughly after handling.If exposed to dust or concerned,get medical advice.If shortness system through prolonged of breath or other health concerns develop after exposure to dust from the product,seek medical attention.Dispose of product in accordance with local,state and national regulations.If there are no applicable regulations,dispose of in a secure Or repeated inhalation. landfill,or In a way met will not expose others to dust. WARNING:This product contains a chemical known to the Slate of California to cause cancer.For more information go to wrwr.P65Wantlngs.ca.gw/product. For more information contact:James Hardie Building Products,Inc.,231 S.LaSalle St.,Suite 2000,Chicago,IL 60604 USA 1-888 JHARDIE www.jameshardie.com www.jhsafesite.com C0M1302-P1/4 f2/15 P� JamesHardie ® V Commercial y �9_ INSTALLATION: •HardiePanel vertical siding must be joined on stud. •Position fasteners 3/8 in.(9.5mm)from panel edges and no closer than 2 in.(50mm)away from corners. JOINT TREATMENT •Vertical Joints-Install panels in moderate contact(fig.1);alternatively joints may also be covered with battens or caulked(Not applicable to ColorPlus®Finish)(fig.2). •Horizontal Joints-Provide positive slope Z-flashing at all horizontal joints(fig.3). Refer to Table 1 for correct installation condition Water Resistive Barrier Condition Figure 2 water-resistive _ii, stud barrier*** Figure 1 water-resistive `` `stud stud ,- Figure 3 barrier*** /� - ,re_ 9 water-resistive lb-'1/4r-c-714'="--7:....-- lit- tp barrier*** ............._........---00"_l water-resistive water-resistive HardiePanel barrier**' barrier . o o siding keep nails 3/8 in.(9.5mm)min. Batten Joint leave appropriate gap between .4-upper panel upper panel from panel panels,then caulk* edges moderate Caulk Joint ® ~Don not caulk D in.not caulk concert (Not applicable to ColorPlus Finish) ( )9aP ` Z-flashing Z-flashing plate o o decorative 3/8 in. I IIII Figure 4 band board ■ (9.5mm)--' o lower panel lower panel mom� .m•mmmo Recommendation:When i �. MPI installing Sierra 8,provide keep fasteners 2 in.(50mm) a double stud at panel away from corners joints to avoid nailing through grooves. Drainage Plane/Wrap Condition Figure 2 drainage wrap*** a.. stud g drainage 0,11:411 v stud Figure 1 stud wrap"` , Figure 3 �� riti_OLI ,��..■� 9drainage wrap*** ��� , 0 0 Sli 1 �1,.�� ,, drainage wdrraai a e oHardiePanel siding keep nails Batten Joint leave appropriate gapbetween upper panel 3/8 in.(9.5mm)min. panels,then caulk' f wuprpaeppanel from panel edges Caulk Joint Do not caulk �.Do not caulk (Not applicable to ColorPlus®Finish) ''h in.(6mm)gap %in.(6mm)gap contact Z-flashing Z-flashing plate ° _decorative 3/8 i". iihmoderate , Figure 4 band board (9.5mm())—� o -4--lower panel lower panel ■ �� � Recommendation:When �� •PI installing Sierra 8,provide keep fasteners 2 in.(50mm) a double stud at panel away from corners joints to avoid nailing through grooves. Furring/Rainscreen Condition Figure 2 Figure 1 furring strip** water-resistive water-resistive 9 barrier*** stud barrier*** water-resistive !� `-stud stud barrier*" = `" '! Figure 3 ciii- „,„..- str p* 9 '�> HardiePanel furring strip” la keep nails o o siding 3/8 in.(9.5mm)min. from panel edges moderate ten Joint leave appropriate gap between upper panel upper panel panels,then caulk* cCaulk Joint - o ._- onot caul plate o 1ontact ; (Not applicable to ColorPlus®Finish) la(6mm)caulk gap I II ,AD in.n-(6mm)gap 3/8 in. Z-Dflashingnot Zflashingk 111111 (9.5mm)�' o decorative o Figure 4 band board —4. -lower panel lower panel • r---' I Recommendation:When keep fasteners 2 in.(50mm) away from corners ,4___-, ' _: installing Sierra 8,provide \1111 % a double stud at panel Apply caulk in accordance with caulk manufacturer's written joints to avoid nailing application instructions. ', , through grooves. **Furring as prescribed in Table 1. ***WRB or Drainage Plane as prescribed in Table 1. COM1302-P2/412/15 ® JamesHardie >o Commercial Ii .? CLEARANCES At the juncture of the roof Maintain a 1/4 in.(6mm) ' Install siding and trim products in Maintain a minimum Maintain a minimum 1-2 in. and vertical surfaces, clearance between the compliance with local building code 1-2 in.(25-50mm) (25-50mm)clearance between flashing and counterflashing bottom of James Hardie requirements for clearance between clearance between James Hardie products and shall be installed per the products and horizontal the bottom edge of the siding and James Hardie*products deckingmaterial. roofing manufacturer's flashing.Do not caulk the adjacent finished grade. 9aP and paths,steps and instructions.A minimum (refer to figure 3 on page 1) Figure 5 driveways Figure 7 _` 1-2 in.(25-50mm) Maintain a minimum 1 in. S'd'°' M . clearance between the lir Figure 6 siding roofing and the bottom (25mm)gap between gutter bottom 1-2 in. edge of the siding and trim. end caps and siding&trim. Die (25 50mm deck material I i 1-2 in. A min •11 5-50mm) Figure 8 Figure 9 lt min- ( 1-2 in. flashing t� (25-50mm) concrete Jo\ 47ist HIV' mm E 1 siding f'' roundaten `6 in(152mm)ren -M2 i; leder Do not bridge floors with HardiePanel siding.Horizontal joints 11174"4"' A (215mm) , should always be created between floors(fig. 10). . lira rascla Figure 10 flashing gutter and end cap • ,' KICKOUT FLASHING Honzontal4 ,,,., Floixing , ,�/ ..,, Because of the volume of water that can pour down a sloped T roof,one of the most critical flashing details occurs where a .' �,' �' roof intersects a sidewall. The roof must be flashed with step I 1--____ flashing. Where the roof terminates,install a kickout to deflect 4 water away from the siding.It is best to install a self-adhering membrane on the wall before the subfascia and trim boards are nailed in place,and then come back to install the kickout. Sheathing_ e Figure 11,Kickout Flashing' To prevent water from Stir' �, dumping behind the siding and the end of the roof PT tliePanel siding I intersection,install a"kickout"as required by IRC code 11905.2.8.3:"...flashing shall be a min.of 4 in.high and 4 in. wide."James Hardie recommends the kickout be angled . between 100°-110°to maximize water deflection Note:Furring shown is as a best practice or as prescribed per Table 1. GENERAL FASTENING REQUIREMENTS PNEUMATIC FASTENING Fasteners must be corrosion resistant,galvanized,or stainless steel. James Hardie products can be hand nailed or fastened with a pneumatic Electro-galvanized are acceptable but may exhibit premature corrosion.James tool.Pneumatic fastening is highly recommended.Set air pressure so Hardie recommends the use of quality,hot-dipped galvanized nails. James that the fastener is driven snug with the surface of the siding. A flush Hardie is not responsible for the corrosion resistance of fasteners.Stainless mount attachment on the pneumatic tool is recommended. This will steel fasteners are recommended when installing James Hardie products near help control the depth the nail is driven.If setting the nail depth proves the ocean,large bodies of water,or in very humid climates. difficult,choose a setting that under drives the nail.(Drive under driven Note:When utilizing express seam joints ensure adequate nailable nails snug with a smooth faced hammer;does not apply for installation substrate width is available. to steel framing). •Consult applicable code compliance report for correct fastener type and CUT EDGE TREATMENT placement to achieve specific design wind loads. Caulk,paint or prime all field cut edges.James Hardie touch-up kits are •NOTE:Published wind loads may not be applicable to all areas where Local Building Codes have specific jurisdiction.Consult James Hardie Technical Services required to touch-up ColorPlus products. if you are unsure of applicable compliance documentation. •Drive fastenemperyendicullar to aiding-and-framing. CAULKING •Fastener heads should fit snug against siding(no air space).(fig.A) •Do not over-drive nail heads or drive nails at an angle. C920 Grade NS,Class 25 or higher,such as Quad Mae or a Latex Joint •If nail is countersunk,fill nail hole and add a nail.(fig.B) Sealant complying with ASTM C834.Caulking/Sealant must be applied in •For wood framing,under driven nails should be hit flush to the plank with a accordance with the caulking/sealant manufacturer's written instructions. hammer(for steel framing,remove and replace nail). Note:DO NOT caulk nail heads when using ColorPlus products,refer •NOTE:Whenever a structural member is present,HardiePanel siding should be to the ColorPlus touch-up section. fastened with even spacing to the structural member.The tables allowing direct PAINTING to OSB or plywood should only be used when traditional framing is not available. For best results use an Elastomeric Joint Sealant complying with ASTM •Do not use aluminum fasteners,staples,or clipped head nails. DO NOT use stain on James Hardie products.James Hardie products must be painted within 180 days for primed product and 90 days for Snug Flush unprimed.100%acrylic topcoats are recommended.Do not paint when ' Countersunk, ill 411.- wet.For application rates refer to paint manufacturers specifications. `Pk 't `,L. add nail �� Back-rolling is recommended if a paint sprayer is used. do not under DO NOT Figure A i Figure B drive nails STAPLE COM1302-P3/4 12/15 1-1110, • COLORPLUS®TECHNOLOGY CAULKING,TOUCH-UP & LAMINATE • Care should be taken when handling and cutting James Hardie ColorPlus products. • • Laminate sheet must be removed immediately after installation of each course.Gently wipe any residue or construction dust left on the product using a soft cloth. •Touch up nicks,scrapes and nail heads using the ColorPlus Technology touch-up applicator.Touch-up should be used sparingly.If large areas require touch-up,replace the damaged area with new HardiePanel siding with ColorPlus Technology. •Terminate non-factory cut edges into trim where possible,and caulk.Color matched caulks are available from your ColorPlus product dealer. •Treat all other non-factory cut edges using the ColorPlus Technology edge coaters,available from your ColorPlus product dealer. Note:Use of touch-up on fasteners on the face of ColorPlus panels should be avoided.Do not caulk joint between ColorPlus panels. Note:James Hardie does not warrant the usage of third party touch-up or paints used as touch-up on James Hardie ColorPlus products. Problems with appearance or performance arising from use of third party touch-up paints or paints used as touch-up that are not James Hardie touch-up,will not be covered under the James Hardie ColorPlus Limited Finish Warranty. Not all designs will be suitable for every application. PAINTING JAMES HARDIE SIDING AND TRIM PRODUCTS WITH COLORPLUS TECHNOLOGY When repainting ColorPlus products,James Hardie recommends the following regarding surface preparation and topcoat application: •Ensure the surface is clean,dry,and free of any dust,dirt,or mildew •Repriming is normally not necessary • 100%acrylic topcoats are recommended •DO NOT use stain or oil/alkyd base paints on James Hardie products •Apply finish coat in accordance with paint manufacturer's written instructions regarding coverage,application methods,and application temperature RECOGNITION:In accordance with ICC-ES Evaluation Report ESR-1844,HardiePanel vertical siding is recognized as a suitable alternate to that specified in:the 2006.2009,&2012 International Residential Code for One-andTwo-Family Dwellings and the 2006,2009,&2012 International Building Code.HardiePanel vertical siding is also recognized for application in the following:City of Los Angeles Research Report No.24862, State of Florida listing FL#889,Dade County,Florida NOA No.02-0729.02,U.S.Dept.of HUD Materials Release 1263c,Texas Department of Insurance Product Evaluation EC-23,City of New York MEA 223-93-M,and • California DSA PA-019.These documents should also be consulted for additional information concerning the suitability of this product for specific applications. ©2015 James Hardie Building Products Inc. All rights reserved. Additional Installation and TM,SM,and 0 denote trademarks or registered trademarks of James Hardie Technology Limited.The QUAD mark is a registered Warranty information available at JamesHardie trademark owned by Henkel Corporation. www.jameshardle.com Commercial COM-I302-P4/4 12/15