Report (40) � NE
AccuSpec V4.22.2
Transaction #: 12764284
JOB TITLE: Reece (Tigard)
Date: 05/01/2019
Approved By:
Submittal review and approval required prior to listed unit(s) being released for
production and shipment. Unit(s) configured based on information provided. The
Approver is responsible for ensuring the units, options, and accessories meet the job
specifications.
MODINE
AccuSpec V4.22.2
SUBMITTAL SCHEDULE & DATA
Gas- and OH-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces
Job Name: Reece (Tigard) Date: 05/01/2019
Location: Engineer:
Submitted by: Kyle Cereghino Architect:
Contractor:
Unit Tag
UH-1, UH-2, UH-3
Model Number HD 30AS0111FBAN
Quantity of Units 3
Btu/Hr Input 30,000
Btu/Hr Output 24,600
CFM 505
Altitude 0-2000
Temperature Rise (degrees F) 45
External Static Pressure (E.S.P) 0.00
Total Static Pressure (T.S.P.) 0.00
Gas Type Natural
Gas Control Type Single Stage, Direct
Spark Ignition,
100% Shut-Off with
Continuous Retry
Supply Voltage 115/60/1
Control Voltage 24V
Motor HP 1/15
Motor RPM 1550
Blower RPM N/A
Heat Exchanger Type Aluminized Steel
Heat
Exchanger/Burner
Unit Efficiency % 82.0
Options & Accessories (See
Attached Pages)
Remarks
?ODINE
gib' AccuSpec V4.22.2
SUBMITTAL SCHEDULE & DATA
Gas- and Oil-Fired Unit Heaters and Infrared Heaters
Model Description Qty Tag
3 UH-1, UH-2,
HD 30A50111FBAN Propeller Unit Heater UH-3
3 UH-1, UH-2,
53140 HD 30A50111FBAN UH-3
4
,j OOINE
AccuSpec V4.22.2
HD MODEL NOMENCLATURE
1,2,3 4,5,6 i 7 8 9,10 11,12 13 14 15 16 I
HD 30 1 A S 01 11 F B A N j
1,2,3 - Product Type
HD - Power Vented Propeller Unit
4,5,6 - Furnace Input Rating
30 - 30,000 Btu/hr Input
7 - Heat Exchanger Type
A - Aluminized Steel Heat Exchanger and Burner
8 - Pilot Ignition
S - Direct Spark Ignition
9,10 - Motor and Drive Code (Power Code)
01 - 115V motor
11,12—Gas and Valve/Ignition Control Type (Control Code)
11 - Natural, Single Stage, Direct Spark Ignition, 100% Shut-Off with Continuous Retry
13 — Fan Guard Type
F - Finger Proof Fan Guard
14— Development Sequence
B - Current
15 — Future
A- For Future Use
16—Factory Installed Option
N - Click to See
?0DINE
AccuSpec V4.22.2
GENERAL PERFORMANCE DATA
c us
�, o
Intertek
General Performance Data
Model HD 30
At 0' Elevation
Btu/Hr. Input 30,000
Btu/Hr. Output 24,600
Entering Airflow (CFM) 505
Outlet Velocity 523
Air Temp. Rise (°F) 44
Mounting Height (Max Ft.)1 10
Heat Throw (Max. Mtg. Ft.)2 25
Unit Total Power (Amps) 3.75
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input 30,000
Btu/Hr. Output 24,600
Configured Air Temp Rise (°F) 45
Motor Data
Horse Power 1/15
RPM 1550
Type S.P.
Motor Amps at 115V 2.40
Clearances to Combustibles
Top and Bottom 1"
Vent Connector 4"
Access Side 18"
Non-Access Side 1"
Rear 18"
1 At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of
unit.
2 Heat Throws are calculated at 65°F ambient with a 45°F air temperature rise with the unit
mounted at a maximum mounting height of 10 feet.
f
?0DINE
AccuSpec V4.22.2
DIMENSIONS - UNIT
Model HD Dimensions
13.5 BETWEEN 3.8'16 MOUNTING HOLES
MOUNTING HOLES V)
ON
1N.W BETWEEN 3B"16 MOULHOLES (MODEL SIZES 1CO AND 125 ONLY)
TYP 3/8 ai"LONA (MODEL SIZES#DD AND 125 ONLY)
a
MOUNTING
6 r--_ f0' —POWER VENTER BRACfcST
ADIU3TASLE VENT PIPE SIZE 30 76
33" IA WENS j 1� CONNECTION
ELECTRIC AL
jlE CT NN ECTION
Iiiii
GAS
1 �' � � E _�.IEM,_,A
5� ill
COH NFL i1pN
_ q • t
Bp
pPEN1H6
. Y ik f�
1 � .YP'tP
IM
9
1 ' 1 r
�.;i ,._,✓,:. pay
•
C 6OPENINO w•—•—N
U ACCESS
PANEL
1
ACCESS VIEW REAR VIEW
Model Size HD30
Dimensions (in inches)
A 26.8
B 12.2
C 16.5
D 14.9
E 10.1
F 7.5
G 18.5
H 7.6
I 28
J 22
Vent Connector 3
Diameter
Gas Connection 1/2
Diameter
Fan Diameter 10
Approx. Shipping 55 lbs.
Weight
Standards
All unit(s) shall include:
C.S.A. (Canadian Standards Association) design certification for use in both the US and Canada to
the ANSI Z83.8 - latest revision, standard for "Gas Unit Heater and Gas-Fired Duct Furnaces" for
safe operation, construction, and performance
Mechanical Configuration
Furnace(s) section with 82% minimum efficiency provided by an indirect-fired tubular heat
exchanger with individually fired tubes for maximum heat transfer with minimal noise of flame
ignition/extinction.
Venting Arrangement
The venting shall be a power exhausted arrangement. The unit shall be tested to insure proper
ignition when the unit is subjected to 40 mile per hour wind velocities. The unit shall also include a
factory mounted differential pressure switch designed to prevent main burner ignition until positive
venting has been proven.
Unit Casing
The unit heater(s) casing shall be constructed of not less than 22 gauge aluminized steel with
minimization of exposed fasteners.
All exterior casing parts shall be cleaned of all oils and a phosphate coating applied prior to
painting. The exterior casing parts shall then be painted with an electrostatically applied baked-on
gray-green polyester powder paint (7-mil thickness) for corrosion resistance.
The unit shall be furnished with horizontal air deflectors. The deflectors are adjustable to provide
for horizontal directional airflow control (up or down).
Furnace Section
The heat exchanger(s) shall be made of 18 gauge aluminized steel tubes and headers.
The thermal efficiency of the unit(s) shall be a minimum of 82% efficient for all air flow ranges.
Each heat exchanger tube shall be individually and directly flame-fired. The heat exchanger tube
shall be crimped to allow for thermal expansion and contraction. The flue collector box shall be
made of 20 gauge aluminized steel.
The heat exchanger(s) seams and duct connections shall be certified to withstand 0.9" W.C.
external static pressure without burner flame disturbance.
The burner(s) shall be in-shot type, directly firing each heat exchanger tube individually and is
designed for good lighting characteristics without noise of extinction for both natural and propane
gas.
The ignition controller(s) shall be 100% shut-off with continuous retry.
The gas pressure shall be between 6-7" W.0 for natural gas.
The solid state ignition system shall directly light the gas by means of a direct spark igniter each
time the system is energized.
i I
The unit gas controls shall be provided with the following:
Single-stage gas controls with a single-stage combination gas control, an ignition control. The unit
fires at 100% full fire based on a call for heat from a room thermostat.
An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the
event of overheating.
A time delay relay that delays the start of the air mover to allow the heat exchanger a warm-up
period after a call for heat. The time delay relay shall also continue the air mover operation after
the thermostat has been satisfied to remove any residual heat in the heat exchanger.
The unit shall be orificed for 0-2000 feet elevation above sea level.
Electrical
All electrical components shall carry UL, ETL, or CSA certification.
A low voltage terminal board shall be provided for direct wiring connection to an external
thermostat.
A single 115V to 24V step down transformer shall be provided for all unit controls.
Air Mover
The motor horsepower shall be 1/15 H.P.
The motor wiring shall be in flexible metal BX conduit.
The motor shall be controlled by a time delay relay.
Propeller models shall meet the following requirements:
The motor type shall be Single-Speed, Open Drip Proof (ODP).
The air mover motor shall be a 115V motor.
Mounting
The unit shall be equipped with mounting brackets to allow for threaded rod suspension or to be
bolted directly to the ceiling support structure allowing 1" of top clearance.
Accessories
The following field installed accessory control devices shall be provided with the unit: