la3MULHERN+KULP
RESIDENTIAL
300 Brookside Avenue,Building 4,Ambler,PA 19002 p 215-646-8001 inulhernkulp.com
August 13,2019
Jeremy Hammon
DAVID WEEKLEY HOMES
1905 NW 169th Place Suite 210
Beaverton,OR 97006
SUMMERBROOK - LOT 13
7894 Model
JOIST BEARING
M+K Projed#: 211-18020
Reference
Structural plans,prepared by Mu/hem d Kulp
As-Built Photos,prowded by David Weekley Homes
Jeremy,
Pursuant to your request,we have prepared this letter to address the 1 nfloor T1I floor joist bearing at the above referenced lot in the
Summerbrook Community.It has been reported to our office that the 9 'h"T11110 series floor joists @ 32"o.c.were pocketed into the
foundation walls and have 2"-2.25"of bearing. Per PRSC R502.6 and the provided structural plans, 3"of bearing is required. Please
note that a representative from our office has not visited the site to confirm these conditions,but photos were provided.
Based on our evaluation.the as-built floor joists with 2"(min.)of bearing are adequate to support the code required loads tributary to
each joist.No further action is required.
Please feel free to call if you have any questions.
Respectfully, ��RED PRQPe`Sd'
,NGINEF /0
MULHERN &KULP STRUCTURAL ENGINEERING,INC. `, 3 9
93737PE
�
Nicholas J.Dastalfo Project Engineer 'Y 'WI r .
Nicholas J.Martignetti,P.E. Project Manager itk„ OREGON