Plans (35) Y SCOPE OF WORK: N.T.S PAGE 1 GENERAL NOTES. � 1. LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. COVER SHEET ROOF MOUNT PV SOLAR SYSTEM 2. NO SHEET METAL OR TECH SCREWS SHALL BE USED TO GROUND DISCONNECT ENCLOSURE WITH TIN-PLATED ALUMINUM LUGS;PROPER GROUNDING/GROUND BAR KITS SHOULD BE USED. a) ROOF TYPE : COMPOSITE SHINGLE M o cm 3. ALL EXTERIOR CONDUIT,FITTINGS,AND BOXES SHALL BE WITH RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS.(NEC 314.15A). 0 ARRAY : 18 MODULES . N. 4. ADEQUATE SPACING ARE MAINTAINED BETWEEN ANY PLUMBING VENTS EXTENDING THROUGH THE ROOF AND THE UNDERSIDE OF THE PHOTOVOLTAIC PANELS(6"MINIMUM RECOMMENDED OR 12" HAN Q.PEAK-G5-315 � WHA o c,4 11 HORIZONTAL). w w Gip w Z Z p O OI 5. BACK-FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES. JUL Q c) � 10MICRO-INVERTERS: U - } o Ui U 6. ALL CONDUCTORS EXPOSED TO SUNLIGHT ARE LISTED AS SUNLIGHT RESISTANT. APS YC5001 240V t3UILLYI t o L1 . m - C.) (.3 U 7. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED IN ACCORDANCE WITH UL1703 SECTION R902.4(IRC)&1509.7.4(IBC) LU ARRAY TILT 29° mCo HI- 0 8. THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC 110.26. U_ w~ Ili U V U AZIMUTH : 149°,241° L` 9. DRAWINGS ARE DIAGRAMMATIC ONLY.THE LOCATION AND ROUTING OF RACEWAYS SHALL BE DETERMINED BY THE CONTRACTOR UNLESS OTHERWISE NOTED OR STANDARDIZED. 2 STORIES BUILDING (nz cn 10. ALL EQUATIONS ACCOUNT FOR WORST CASE CONDITIONS. J 0 W Y Y Y 11. IF A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT,WIRE,EQUIPMENT DEVICES,OVER CURRENT PROTECTION,GROUNDING SYSTEMS,ETC.(ALL EQUIPMENT AND MATERIALS)THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIALS AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS IN THE SPECIFICATIONS OR NOTED ON THE PLANS TO ENSURE COMPLETE LISTED BY UNDERWRITERS 2 } co N r- COMPLIANCE WITH ALL CODES AND TO ENSURE THE LONGEVITY AND SAFETY OF THE OPERABLE SYSTEM. LABORATORIES FOR ELECTRICAL app (0 LU LU L AND FIRE SAFETY(CLASS A FIRE RATING) r- 12. ALL OUTDOOR EQUIPMENT SHALL BE MIN.NEMA 3R RATED. NOTE: Lt 13. METAL CONDUIT AND ENCLOSURES SHALL BE USED WHERE PV SOURCE OR OUTPUT CIRCUITS ARE RUN INSIDE A BUILDING. LIABILITY 1) NO DISCHARGE OF ANY POLLUTANTS The CitTO ANY STORM DRAIN SYSTEM. 0 14. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ANY AND ALL REQUIREMENTS GIVEN BY UTILITY COMPANIES. y of Tigard and Its 2) UL 1703 FOR MODULES & UL 1741 1 `n iY employees shall not be FOR INVERTERS PER CITY SOLAR 1 M 0 15. FOR ADDITIONAL EQUIPMENT SPECIFICATIONS,SEE PROVIDED CUT SHEETS. . C mresponsible for discrepancies REQUIRMENTS. OF 16. INSTALLER TO FOLLOW ALL LOCAL JURISDICTION GUIDELINES. whicI may appear herein. O Q a o a 6R cs CITY OF TIGARD OFFICE COPY VALIDITY OF PERMIT Z ° N THE ISSUANCE OF A PERMIT ct � Li_ Z REVIEWED FOR CODE COMPLIANCE BASED ON CONSTRUCTION 2017 OREGON SOLAR SPECIALTY CODE (OSSC) w m < 0 d N DOCUMENTS AND OTHER 2017 NATIONAL ELECTRICAL CODE (NEC) Approved: [ 2017OREGON SOLAR ELECTRICAL CODE OSEC cc ( ) Za) Q U Z OTC: DATA SHALL NOT PREVENT ORDINANCES OF THE CITY OF TIGARD a LI g 6 U it Permit#: THE CODE OFFICIAL FROM -3 CO I- O Q ,c'r 21k. 00 � Approved plans REQUIRING THE CORRECTION Address: 4`1 - �e_c i -t ,--!! -. ,,,_ �.. tl y OF ERRORS.ORSC 105.4 �� OFFICE COPD M J p suite #: � J By: Date: a� �9 VICINITY MAP O I- ` INDEX SHEET : F- 5 • SW Kenton Dr J i .' > - CO ' � 1. COVER PAGE O yZ lif s *�411 - 2. PLOT PLAN Z i N �`;.R.n _- ,'q. 3. ROOF PLAN CC U a z� 0 4. ELECTRICAL DIAGRAM w L Ly 9 Y ` rr- 5. RAFTER SIDE VIEW U 0 M. o * 6. MODULES SHEET O Q p �� .............O..O.O.. " IIIIIIIIIIIIIIIIIIIIIIII - " `;�. 7. MODULES FIRE RATING 0_ O 8049 Southwest r t I 8049-SW AsitfOrd'S.1% 0 Z CO Ashford Street 41} . I. 8. INVERTER SHEET , -- r ui 0 .m Solar Permit Services, Inc. Q y '4 9. RAILS/GROUNDING SHEET Z w OZ W m Prepared by (HT) -0 anti , Vin. 10. RAILS FIRE RATING o N I -1 H c, www.solarpermitservices.com SW Ashford St SW As* 4v: v , ty1, 11. ATTACHMENT SHEET X w �" 12. WARNING LABELS info@solarpermitservices.com '« DYNAMIC POWER •(949)872-8236 , INNOVATION LLC DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission.In the event that the Chninar or fanaral rnntrartnr falrc to nivc.ci irh notirsn hafnrr rnnctn irtinn anri/nr fahriration of tha work the flwnPr or(onPral C'.ontrartor will ha ham racnoncihJP to the rani iit of any Pn-orc riicrrananriac or omiccionc and tha rnct of rrrtifyinn therm 7-- SCALE --- N 1/16"=1'-0" PAGE 2 %j \ PLOT PLAN e °.O9-09Z o 50° ''LXn)) 017Z AZIMUTH 60" V o• \ OA .0£ 70° <Z 8pp°am in p/Orbv � . Vs � wpY Q° ' o..o�v� UN • • • Z (1) tl _ _ _ ..- ' �t../,-, 2/ Q V V V 9C' \ \ A/4 18 MODULES Q w N a 0 cS' \�0 ROOF TILT 29° W N 0 0 < POINT LOAD CALCULATION PER ARRAY (94, �' @ #OR WEIGHT TOTAL WEIGHT S AZIMUTH @ 149°,241° > N LIN FT PER(lbs) (lbs) /` \ -' O W Y Y ITEM w MODULES 18 41.1 lbs 740 lbs / S / 0 U W O 0o RAILS 120' 0.5 lbs 60 lbs LO N / \ co m 6 6 / / X RACKING PARTS 28 0.5 lbs 14 lbs LL TILT LEGS 0 3.5 lbs 0 lbs ® ® p_ / / / D MICRO INVERTERS ,n /POWEROPTIMIZER 10 5.5 lbs 55 lbs N. / ® 1 ® ® \ 0 TOTAL WEIGHT 869 lbs \ A CO 1.7) 0 MODULE DIMENSIONS(LxW) 66.34" x 39.37" = 18.1sq.ft �� :-'' -7-'-- =�diti WEIGHT PER MOUNT 869 / 28 = 31.0 lbs/Mount SUB zI w co O D w m / Acs N a (ApN � m WEIGHT PER SQ FT 869 / 326 sq.ft.= 2.7 lbs/sq.ft. / EMS Y / LU 2 rn o N WIND UPLIFT CALCULATION ((M x P)-.6x W)< L x ExQ GARAGE7 v Q ¢ O Q N w m a W=Module and racking weight 869 lbs QO I O Z ,t(;) = Z 10905 < 22960 M=Total Modules area 326.48 sq.ft.� �Cj a W 0 U a P=Wind pressure 35 psf / G / -7 03 P 0 Q L=Lag crew screw 328.05 hin / E=Lag screw embedment 2.5 Inch / � ¢ I Q=Quantity of lag screws 28 20 LU W �� > 15 _J � NOTES: CC P ijZ in -WORKING CLEARANCE FOR MAIN SERVICE PANEL AND AC DISCONNECT a 0 I- EXCEEDS 3' Q 5 Y -CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS WHEN �_ > PREPARING ROOF FOR ANCHOR POINT LOCATIONS. BUILDING STRUCTURE — — _ — w � Oi"J- z INTEGRITY IS THE RESPONSIBILITY OF THE INSTALLER. N -ADJUSTMENTS MAY BE REQUIRED DUE TO EXISTING ROOF LAYOUT. �r ur 7�� Z i U w_o -ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT 8049 SW ASHFORD ST Ct U 0 .7r O z v REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH LU W CC 9 Y v AS WINDOWS OR DOORS,AND LOCATED AT STRONG POINTS OF BUILDING 0 ti = CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT O Q min 0 0 -� CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS,WIRES 0 00 Q w NI- OR SIGNS. < Z U PV EQUIPMENT,SYSTEMS AND ALL ASSOCIATED WIRING AND J INTERCONNECTION SHALL ONLY BE INSTALLED BY QUALIFIED PERSONS. } o Ui 0 I- in v (NEC 690.4 E) a CV (1) d X w F o -PHOTOVOLTAIC SYSTEM CONDUTORS SHALL BE IDENTIFIED AND SCALE: THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY 0' 4' 10' 20' 30' 40' - SEPARATE COLOR CODING,MARKING TAPE,TAGGING OR OTHER 1/16"= Orr APPROVED MEANS.(NEC 690.4 B) - DYNAMIC POWER 2' INNOVATION LLC DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission.In the event that the nwnpr nr f;pnpral rnntrartnr fallc tn niva ci irh nntirp hpfnra rnnctn infirm anri/nr fahriratinn nf the wnrk tha flwnpr nr ripnpral rnntrartnr will ha halri racnnncihIc tn tha race ilt nf any arrnrc riicrrananripc nr nmiccinnc anri tha rnct nf rprtifvinn therm SCALE PAGE 3 ROOF PLAN q O�Nma T 9Ocnv �hopO ,y w .04'4 ^,yob Lo OSZOge 40° CO `50° ii.041 Aaru,x B0° CO 0£w 0° m0'080° '0o��.�� 0 � 2x8 @ 24" O.C. Q o d'\O /rn -'WaO % Y 0O_08..00j W N RAFTERS D_ c • 0 LEGEND = U J-BOX ON ROOF/ >- UNDER ARRAY 0 Z 4_ I / / i __ CHIMNEY Ind V CCI W n- U 1-- SKYLIGHT / / �I I W N 0 0 < J AIR CONDITION UNIT 1A/C1 w 0 W Y Y Y DORMER VENT ® �I `1r OA 1 I I,, l TURBINE VAV 18 MODULES / 2 .e 03 O I - '',- RMA RMA METER RMA ROOF TILT @ 29° INVERTER INV. AZIMUTH @ 149°,241 ° ® Loy " D AC DISCONNECT AC O Q' LOAD CENTER U> y I 0 Ail/illss SUB PANEL SUB r � yI � ! CO 4 4 --111.4_u_ Llai 444- 1_ 1itr��, U PERFORMANCE METER PM A w I— o CO Z W 0 O 0 MAIN ELECTRICAL PANEL MSP I r = r N CO U EXTERIOR 3/4"EMT CONDUIT I _ d W O N ~ N z = U1.5"3.5"ABOVE ROOF = z _ nUZ N— AND UNDER EAVES - i ': - QQ QSUB , N PV PANEL DIMENSIONS o co N.T.S. AC I I t Z w D 394-- f FI-1 cc QrnOUz MSvI , r , H a WgoUa 1I J1 � ao1= 0Q 66.34" . x ,i 0P7 J SCATTERED ROOF ATTACHMENT TYP. O_ [- PER MANUFACTURE AND SEE DATA SHEET - 8049 I— 5 Y 16°MAX OR CITY/COUNTY REQUIREMENTS SW ASHFORD ST < Cn T I f 4'-0"O.C. 7 4'-0"O.C. MAX > CO SOLAR STANDARD 0 >-- Z O N ow_ Z N LU FW RAIL WIi2' Q LU = v a o ° oo � UO ,r co -I n O 20 OCl_ <la- ccj O0 xt m U 2 in O ,, '"g U O U CO rn 2 _ -4'-0"O.r —'--4'_0"O. ° Q fY Z 1- �- I- 1 e. '1 i u1, u� END MOUNTING MID.MOUNTING N D x W H 0 CLIP,TYP. CLIP,TYP. 0' 2' 5' 10' 15' 20SCALE: PORTRAIT PANELS_DETAIL LAYOUT NOT TO SCALE 1/8"=1'-0" DYNAMIC POWER 1' INNOVATION LLC DISCLAIMER: If any Errors,Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer,in writing,of such error or omission.In the event that the flwnar nr nPnPraI C.nntrartnr falls to nivc cI Irh nntirp hafnm rnnctn Irtinn and/nr fahriratinn nf the wnrk the nwnPr nr C-ZPnPral rnntrartnr will hP hPlri mcnnncihlp to the raci Ilt nf any Prrnrc riicrrananniac nr nmiccinnc anr1 the rnct nf rir fifvinn therm SCALE PAGE 4 N.T.S. ELECTRICAL NOTES. ELECTRICAL DIAGRAM 1. ALL EQUIPMENT IS LISTED FOR USE. 2. ANY EQUIPMENT OR ELECTRICAL MATERIALS USED FOR THIS INSTALLATION SHALL BE NEW AND LISTED BY A RECOGNIZED ELECTRICAL c TESTING LABORATORY. IA 3. CONDUIT RUNS SHALL BE PROVIDED WITH SUFFICIENT WEATHER PROOF PULL BOXES OR JUNCTION BOXES/COMBINER BOXES PER (0 APPROPRIATE JURISDICTIONAL REQUIREMENTS. Y > 4. ALL PV ARRAYS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION. Q 5. ANY AC COMPONENT SHALL MEET OR EXCEED THE AVAILABLE FAULT CURRENT CALCULATED AT THAT COMPONENT. LU N a. 6. ALL MODULES AND ANY RELATED ROOF MOUNTED METALLIC EQUIPMENT SHALL BE PROPERLY GROUNDED. O c2 7. MARKINGS SHALL BE PROVIDED TO INDICATE THAT ALL CONTACTS OF THE DISCON NECT EQUIPMENT MIGHT BE ENERGIZED. 8. MICRO INVERTERS SHALL CONTAIN A GROUND FAULT DETECTION AND INTERRUPTION DEVICE. _ (-)) 9. THE POINT OF CONNECTION COMPLIES WITH APPLICABLE CEC/NEC. 10. BACKFED SOLAR BREAKER(S)SHALL BE INSTALLED AT THE OPPOSITE END OF THE CIRCUIT OR FURTHEST AWAY FROM THE MAIN BREAKER. Z U7 11. ALL EQUIPMENT SHALL BE GROUNDED, INCLUDING BONDING JUMPERS WHERE NECESSARY ACROSS RAIL SPLICE PLATES TO BOND -_= Q U U U 1 INDIVIDUAL PIECES OF RAIL THAT ARE CONNECTED AS AN EXPANSION SPLICE. 12. ALL WIRE,VOLTAGES,AMPERAGES AND EQUIPMENT IS SIZED ACCORDING TO TEMPERATURE DERATING AND LOCATION. CO (2 C/) a 0 13. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. Q W 14. ONLY COPPER(CU)CONDUCTORS SHALL BE USED.CONDUCTORS SHALL BE STRANDED OR SOLID WITH PROPERLY RATED CONNECTORS. J LU 0 0 0 N 0 0 Q 15. DISCONNECT SHALL BE WIRED SO NO BLADES ARE ENERGIZED. W 16. ALL MODULES AND RACKING SHALL BE GROUNDED USING 2703 UL LISTED RAIL INTEGRATED GROUNDING SYSTEM,OR WITHTINPLATED > DIRECT BURIAL RATED LAY IN LUGS USING STAINLESS STEEL HARDWARE,STAR WASHERS,AND THREAD FORMING BOLTS OR WEEBS. W O W Y Y Y #6 CU AWG BARE GROUND DtY H O O N N- AWND RAINS GEC WILEC 250), OLNDING MODULES 0 BE CONNECTED ,a Cn N O DIRECTLY TO THE PREMISE WIRING °r° - (q Lc) LO Lf) NEC 705.12(D)(2)(3)(c) ELECTRODE(TYP) CL 200A x 120%= 240A 15.6A x 125%+200A = 219.5A I � 240A >_ 220A J-BOX ON ROOF SEALED TIGHT- 17)r D TO UTILITY GRID lJ NON-FUSED-NEMA TYPE3 MIN. TERMINATOR CAP ON LAST Ct 120/240V r (N)30A 240V PV-AC DISCONNECT - SINGLE PHASE --V\-- NON-FUSIBLE 2POLE,LOCKABLE CABLE CONNECTOR OF AC Ln 0 KNIFE BLADE,NEMA 3R 6.3&NEC690.17 TRUNK CABLE(TYP) o CO NO CENTER MAIN BREAKER MAIN (ACTING AS RAPID SHUTDOWN INITIATING DEVICE) I- o 14 PANELS-BRANCH CIRCUIT#1 W Cij CO _ I ELECTRICAL PANEL AP SYSTEMS ECM WIRELESS I �;•• ZO a d O BI-DIRECTIONAL x- ,,____ p (E)200AMP 120/240V CONNECTED PV-MONITORING , I „:: ;........�?'CI I IIIA- , i'� p��N t�l d (n O N H m UTILITY METER o o (E)200AMP MCB (N)30A 2 POLE BREAKER ECM 7:::. ':.•'" .�`_' W LL } N ®� SHALL BE INSTALLED SUB-PANELD MAIN LUG PV / JJ - L - - MA - - U r AT OPPOSITE END OF • / Z = r- Q.L_� ®m MAIN CIRCUIT BREAKER (N)125A 240V Q Q O Q N 2® CO S MICRO-INVERTER MICR0.IN'°°'°°p> Q o 0 1-15A 1POLE BREAKERS W m 9® ®� \-\ \ MICRO-INVERTER APS-YC5WA(T'P.) $ ® ®- I O \\0 si CIRCUIT#2 z 2-20A 2POLE BREAKERS 4 PANELS-BRANCH CIRC 0i M� on ' I II I ��� 1 1�' Ili;:"*".:.1:mr4ITER �•.• � i;�l CO P 0 •=1 an ' - - - -o L - - - - �- ®4 - -L;CSOOIAC :S o B - - - - ®¢ 0 x MICR0.INVERTER MI MICROAM/ERTERp2 co ❑ O _i ,.- °? MOUNTS AND EQUIPMENT m ENCLOSURES GROUNDED EXTERIOR EMT 3/4"AC CONDUIT 0 to I 0 O H TO MAIN PANEL GROUND - (2)#10 CU THHN/USE-2 CONDUCTORS L - - 1 w (#12 CONDUCTORS): 1= 5 (E) UFER GND (1)#10 CU THHN/USE-2 NEUTRAL (MICRO INVERTER TRUNK CABLE, 1 PHASE Co (1)#6 BARE COPPER GROUND 35'EXTERIOR 3/4"EMT AC CONDUIT- 90°C, 600V, WET/DRY, 0 z a90°C 90°C WET&DRY (4)# 10 CU THHN CONDUCTORS WITH MICRO-INVERTER PRE-INSTALLED Z dd-- N (2)# 10 CU THHN NEUTRAL CONNECTORS, NOT IN A Z = I 13- uu)i o (1)# 6 CU GROUND CONDUIT. BLACK: L1, RED: L2,WITH 0 rn d• O w O 90°C WET&DRY NEUTRAL, GREEN: GROUND, 5 0 o� I UL1741, UL 746 C, Fl, IEC 60529 IP67(TYP). 0 < p coo 0 CALCULATIONS FOR CURRENT CARRYING (1)#6 COPPER GROUND (BONDING FOR ° a O p Z w CONDUCTORS: SOLAR MODULES AND RAIL) U O `n Q z O) AC REQUIRED CONDUCTOR AMPACITY Q Lo Et Z V -T, Utd • PTC RATING IS:292.2W ARRAY RATING MAXIMUM OUTPUT POWER=500W AC MAIN PANEL PV-CB SIZE=30A 2.08A x 9 x x1.25= 23.44AF >- o i 02 0 ~U 18 x 292.2 x 0.970 /1000= 5.102 KW-AC(CEC) ISC: 10.14 ADC 500W / 240V = 2.08 AMPS 8.3A x 1.25= 10.42A AWG#10 DERATED AMPACITY: ❑ N U) 0- X I j o rn 18 x 292.2 /1000= 5.260 KW-DC(PTC) IMP:9.55 ADC 2.08A x 4 = 8.33A PER BRANCH#1 7.3A x 1.25= 9.11A 40 X 0.91 X 1.0 = 36.40 A 2.08A x 4 = 7.29A PER BRANCH#2 TOTAL= 19.53A 36.40A >23.44A DYNAMIC POWER THEREFORE AC WIRE SIZE IS VALID INNOVATION LLC DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission.In the event that the flwnar nr flanaral(nntrartnr falls to niva CI Intl nntirp hafnra rnnctn Irtinn anri/nr fahriratinn nf tha wnrk tha Chiunar nr fanaral r.nntrantnr will ha halri racnnncihla to tha race Ilt nf any arrnrc rlicrrananciac nr nmiccinnc anri tha rnct nf rartifirinn therm Y N.T.S. I PAGE 5 RAFTER SIDE VIEW LU 1 PLY COMPOSITE SHINGLE M LU 0 1 EXISTING 1/2"CDX PLYWOOD 1 Y o SHT'G. w CV 5/16-18x1-1/4"S.S.FLANGE BOLT a. o d O 5/16-18 FLANGE NUT 1\ f �� Q U SNAPNRACK } COMPOSITION Z EL FLASHING _ UU U SNAPNRACK CHANNEL NUT A ,mr.n. 1_ F- WU ,slow QSTANDARD SNAPNRACK RAIL Jw N ❑ 1.----"" ,/ —1 0ZSNAPNRACK L-FOOT ;-II/I-I; � Lu 0UI— O O N } co NO o I i' / SNAPNRACK 1 -5/16"x 3-1/2"SS LAG BOLT @ 48"O.C. MAX. COMPOSITION OVER EXISTING SHT'G.AND L-FOOT BASE ROOF RAFTER AS SHOWN 0 MINIMUM 2-1/2" PENETRATION 0 M m 1 o F- o 2X8@ 24"O.C. RAFTERS I z di co 4"-6"PARALLEL TO ROOF O ❑ a. o Ia cnooNH0 1 5 A Z = r-- U , Q Q O Q N 1 c.> m o a- ser QrnQUZ SOLAR PANEL -'0101011.11111111. X a W g o U a. PORTRAIT Q N JM 1 Illk (-93 0 I— Y 1 z w Z Oa 2X8 @ 24"O.C. RAFTERS _. 111" - Z › c N Z = r co nV wo 157" - ccc� � � o zo in W w a o I 0 �� 2X10 @ 16"O.C.JOIST �, 179" -' o U O ,aQ� cn cp ULi 0_ a- c6 SO z z� , E I LOAD BEARING Q Z J'- 1 > cD 2 I W I-co 0NU) a. Xw �0 DYNAMIC POWER INNOVATION LLC A J DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer,in writing,of such error or omission. In the event that the flwnar nr nanaral r.nntrartnr falls tn niva ci irh nntirp hafnrm mnctn irtinn anri/nr fahriratinn nf tha wnrk tha flwnar nr nanaral r..nntrartnr will ha halri racnnncihla tn tha raci ilt nf any arrnrc riicrrpnanriac nr nmiccinnc anri tha rust nf rartifvinn therm N.T.S. PAGE 6 - powered by i MODULES SHEET Q.ANTUM /Duo/ Y � MECHANICAL SPECIFICATION Format 1685mm x 1000mm x 32mm(including frame) ,,,,,,,,, Ln Weight 18.7 kg °s°'"" 1 ss'.'"'" ErM I ,'!„; Front Cover 3.2 mm thermally pre-stressed glass with LA • anti-reflection technology (� Back Cover Composite film �"` I , �.� Frame Black anodised aluminium Q O W ® 000mm N � - `i Cell 6 x 20 monocrystalline Q.ANTUM solar half cells t , Junction boo 70-85mm x 50-70mm x 13-21 mm Ui O t i 1, - lt 1 Protection class IP67,with bypass diodes O ) \ Cable 4mm'Solar cable;(+)1100mm,(-)1100mm , ,,°„°,„,,, a8Daage es Q U F1 } k ' Ciiionnector Multi-Contact,MC4,IP65 and IP68 ) } Cip tz<.S�.1Ta.,� a 1. z o o o , ._ „..... ELECTRICAL CHARACTERISTICS I C/) }- I- W �{ ■P E = • . ' 315-33 t- POWER CLASS 315 320 325 330 Q W �) 0 e MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS,STC'(POWER TOLERANC:+5W/-0 W) 0 U 0 , ,s ., /" Y Power at MPP' Pr,P (Wl 315 320 325 330 -J W N ❑ ❑ Q ,�� - - Short Circuit Current* I. 1A] 10.04 10.09 10.14 10.20 C . > (/) Q.ANTUM SOLAR MODULE E Open v« [v] 39.87 40.13 40.40 40.66 Z L11 2 Y Y Current at MPP* I„p, (A] 9.55 9.60 9.66 9.71 -J 0 W Voltage at MPP* 11.,,, [V] 32.98 33.32 33.65 33.98 I- O O CV CD Efficiency' n [%] 318.7 i 19.0 z 19.3 >_19.6 O U (0 N N- ...- The new Q.PEAK DUO-G5 solar module from Q CELLS impresses thanks MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS,NBC' 2 .e u) LO LO LO to innovative Q.ANTUM DUO Technology, which enables particularly ' Power atMPP' P., 1W] 233.4 237.2 240.9 244.6 high performance on a small surface.Q.ANTUM's world-record-holding . • E Short Circuit Current* l. [A) 8.09 8.14 8.18 8.22 ct cell concept has now been combined with state-of-the-art circuitry 1 .E Open Circuit Voltage* V. (VI 37.30 37.54 37.79 38.04 7 j { * f Current at MPP* I,,,,, [A1 7.51 7.56 7.60 7.64 r- half cells and a six-bulbar design,thus achieving outstanding perfor- Voltage at MPP* v„ PP [VI 31.07 31.39 31.70 32.01 .- 0 mance under real conditions-bothwithlow-intensity solar radiation 0000W/m',25°C,spectrum AM 1.5G 'Measurement tolerances SIC n3%;NDC x5% '800W/mu,NOCT,spectrum AM1.5G 'typical values,actual values may differ Eh IY as well as on hot, clear summer days. Q CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE LU .... .. el . + , At least 98%of nominal power during err 1n r r n E� mi } ' W:a _ first year.Thereafter max.0.54% r O (} s ., 0. -' degradation per year.At least 93.1%of ,m ' W a CD Q.ANTUM TECHNOLOGY:LOW LEVELISED COST OF ELECTRICITY nominal power up to 10 years.At least i z ❑ di O t 1 ' :,� 85%of nominal power up to 25 years Higher yield per surface area, lower BOS costs,higher power IN r classes,and an efficiency rate of up to 19.9%. { } All data within measurement tolerances. 5 m r p (n 0 CO U = 0 Full warranties in accordance with the w { . } e m warranty terms of the Q CELLS sales W TM W �- CV INNOVATIVE ALL-WEATHER TECHNOLOGY Z f t organisation of your respective country. 1°° PP^ eP^ ZN �_r/^� U { # IRRADIANCE[W/M't L.L VJ r Optimal yields,whatever the weather with excellent low-lighti < 0 Z and temperature behaviour. „a a . m YEARS Typical module performance under low irradiance conditions in 0 m 121- a N comparison to STC conditions(25*C,1000W/m9. W-3 Z �> Et a- TEMPERATURE COEFFICIENTS Q O < U z W ENDURING HIGH PERFORMANCE Temperature Coefficient of[:r a 1%/Kl +0.04 Temperature Coefficient of V re _ III Long-term yield security with Anti LID Technology,Anti PID EUPD RESEARCH CELLS P a D t%/Kl -0.28 a W 0 a. Temperature Coefficient of P„,p v t%/K] -0.37 Normal Operating Cell Temperature NOCT CCI 45 r, ~ 0 < Technology', Hot-Spot Protect and Traceable Quality Tra.QTM. TOP BRAND PV ✓ m,[ax«« s MODULES PROPERTIES FOR SYSTEM DESIGN P MM /110,1M,MOULT OLI" EXTREME WEATHER RATING Maximum System Voltage v [v] 1000 Safety Class I 017 ✓„�;;,.,r -, High-tech aluminium alloy frame,certified for ,,carr Maximum Reverse Current I. IA] 20 Fire Rating c --1 co high snow(5400 Pa)and wind loads(4000 Pa). UL. Push/Pull Load (Pal 5400/4000 Permitted Module Temperature -40°C up to+85°C „ Z W (Test-load in accordance with IEC 61215) On Continuous Duty o O i- 0 A RELIABLE INVESTMENT V DE QUALIFICATIONS AND CERTIFICATES PARTNER d Inclusive 12-year product warranty and 25-year linear Quality:Tasted ,' .; VDE Quality Tested,(EC 61215(Ed.2);IEC 61730(Ed.i),Application clan,A j cp performance warranty2. � f This data sheet complies with DIN EN 50380. LI LI Z N O4 wxw.YDEinfo cmn -- •V STATE OF THE ART MODULE TECHNOLOGY o.400azea7 V �" E Q Z 2 rZ O 0 w o �'f Q.ANTUM DUO combines cutting edge cell separation D Emon ` ,, U O mr O z and innovative wiring with Q.ANTUM Technology. APT test conditions accordingm W _ to IEC/TS 62804-1:2015, t U co (n D method B(-1500v,168 h) 0 0- fm O z NOTE:Installation instructions must be followed.See the installation and operating manual or contact our technical service department for further information on approved installation 2 O OZ W See data sheet on rear and use of this product. for further information. d 0 0 co I _Q W THE IDEAL SOLUTION FOR: 3 Q L- O Z J 0 w Rooftop arrays on Rooftop arrays on - Hanwha I CELLS GmbH Z A w Q I- Liresidential buildings commercial/industrial Sonnenallee 17-21,06766 Bitterfeld-Wolfen,Germany I TEL+49(0)3494 66 99-23444 I FAX+49(0)3494 66 99-23000 I EMAIL sales®q-cells.com I WEB www.q-cells.com g QNoa Q U buildings x W rn Engineered in GermanyQ Engineered in Germany CELLS Q CELLS DYNAMIC POWER g , INNOVATION LLC DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer,in writing,of such error or omission- In the event that the ('u/nar nr C4cnpral Cs.nntrartnr falls to niva ct Ich nntirp hafnrc rnnctn infirm anri/nr fahriratinn nf tha v,inrlc tho fwnar nr(1.anesral C`.nntrarinr will ha hclri rccnnncihlc to the race If nf anu srrnrc rlicrrananrinc nr nmiccinnc and tha rrct nf rcrtifi/inn therm TOUGHER REQUIREMENTS v N.T.S. PAGE 7 ,CELLS TO GAIN VDE APPROVAL MODULES FIRE RATING YIELD}SECURITY •Double thermal cycling test in acc.with IEC{400 cycles) -- u7 ANTI PID TECHNOLOGY Longer testing cycles and the law ac fry perform nce •1.5 fold damp heat test in acc.with IEC{I,500 hours) ° C (APT) toss threshold of 5 l°make Quality Tested by VDE the most •Twice the amount of tested modules per test string u� HIIT-SPOT PROTECT comprehensive testing program for solar modules. „, + •Twice the amount of junction box tests (NSP) i •Additional dynamic load test following UV treatment o rr TRACEABLE QUALITY •Allowed performance loss after VDE testing is Q LU (TRA ) at most 5%(instead of 8% in acc.with LEC) a o O o E INSTRICTER PRODUCTIONQUALITY CONTROLS = 4 U v 0%elm w .. U �- 0 ' \ \ ••Wet leaks a test on ectroluminescenee 1%of alltest modulesfollowing lamination The additional tests protect against the risk of module Q F- •Daily test of grounding behavior damage and system failures thanks to high production W N UQ •Daily reverse current carrying capacity test consistency, > eij W � Y Y !G(NUNIQUEINTHEPV INDUSTRY: o REPEATED TESTS CO o co LU � L .1- r u �i •Quarterly testing for the accuracy of the power data on the tY �9i i�WHAQCELLSQUALITY module via remeasurement Continuous testing guarantees the production of solar •Quarterly recurrence of testing cycles on 20 modules from CC modules of the highest quality-every time and at all a running production production sites. '&7) 0 QUALITY T E S T E D • IVI O D U L E •Quarterly climatic testing on 4 modules from running production '7? U co m O L H The safest test standard for your ,- •nvestment Visitwww.vde.comforfurtherinformationontheQualityTested z W o program for solar modules. i CC0 N >- m 7 i. W \, 'Vol li' ...t ; CO IY + r w,. - . ...- I- Q Q Q N Hanwha Q.CELLS is the first solar module manufacturer to participate in the QualityD 4t : " w m i 11 Tested program of the German .module independent certification authorityVDE. Qualif ~,� ,r<> Q rn Q U Z Lij Tested by VDE considerably expands the well-known module tests of IEC 61215 a d v .. . ,,,,,,,, , i. _ ti `s , 11� ;= ai W dr C9 U a- 10 IEC 61730, in terms of the approval certification,the quality controls during the D ' -- _ _fr_ __ ,•. ._ oD F- 0 < production process and the frequency of the testing cycle.Unlike any other quality i, F.,, ____-- _..........„-- . �.. _ :' .1. program,Quality Tested by VDE ensures the continuously high safety and quality of Qr t n 100 — �_ . '�; z� our modules over the long term. - e '- Quality Tested - . " t✓ rte` ,-'. �-- I W -� 9UAt1TY TESTED MEANS THE ADVANTAGES FOR YOU ARE: high reliability .i Z optimized durability ,I,iiiiiir _TLAhe best modules on the market with •Reliable system performance low degradation T' •o i` �� ~ Y continuous line monitoring m Q independently confirmed: thanks to comprehensive approval ° _ ! i p Z certification. t f _ _ „ .m ' r N - r, •High reliability _ I ? 0 w_ •law relic ilitY optimized durability •thanks to additional t solarun tests. 'D• 400325/3i7 h ,' G :' Urn `dr_ o w _ w lit • fI o Y •Continuous line monitoring ry Q O J LU : :-. •Increased investment security • a a c O O thanks to testing repeated /" o quarterly. , 1:11' . 5 .<(-)2- rq Lll — w v •Increased bankability thanks to � r 1 Z c� w O U w o0 s 2 2 w independent certification by an - x " = ❑ N cn a _i < internationally recognized testing ',. `w * X w andcertifieattonauthority. 1 � ` `5 DYNAMIC POWER CELLS�� "auw" tim,SSGMBN INNOVATION LLC ffT Tttaiheim,Sonnenallee 17-21 TEL +4410}3494 66 49 23444 EMAIL sales®q-cells.com e 06766 Bitte fetd-Walfen,Germany FAX +4910}3494 66 49 23006 WEB www.q-cells com :a�CELLS J DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents,The Owner or General Contractor shall notify the Designer, in writing,of such error or omission. In the event that the r hnrnar nr C,anaral C nntractnr falls to niva ci ich nntirr� hafnra rnnctn ictinn anri/nr fahriratinn of tha work tha CTnrnar nr r�anaral C�nntractnr will ho ho lri racnnncihla to tha race ill of anv arrnrc rlicrrananciac nr nmiccinnc anri tha rnct of ractifirinn thorn v N.T.S. PAGE 8 1 _ INVERTER SHEET Ln cn IA APsystems YC500i EnergyMaxTM Microinverter Datasheet ¢ o Lu ,r p 1APsystems INPUT DATA (DC) C o ALTENERGY POWER MDPT Voltage Range- 22-45V Q in Leading the Industry in Operation Voltage Range 16V-52V = 0 Solar Microinverter Technology Maximum Input Voltage 55Vz CO Startup Voltage 22V Q W _ U U Maximum Input Current 12 H I— W W CO w U) fl O YC 5001 OUTPUT DATA (AC) -�--I w N 0 0 Q Nominal Output Voltage 2081 .___._ 24Au`-- with EnergyMaxTM Peak Output Power 548W 548W w > N � Z 2 Y Y Y w Maximum Continuous Output Power 500W 500W _I O W 1 High output microinverter_ O o g Nominal Output Current I— N p _ p 2.4A 2.08A 0 CO O �1e rated ground �' Default Output Voltage Range 183V-229V211V-264V"' O � �. (0 N � Y Peak Output Current 2.63A I 2,28A O O f!) LO LO LO Nominal Output Frequency 60Hz T T Single unit connects two solar modules=. i. • Integrated ground Default Output Frequency Range 59.3Hz-60,5Hz" CC Peak output power 548W • Maximum Units Per Branch 6 for 20A Breaker I 7 for 20A Breaker • Individual MPPT for each module 0 • PLC communication&free monitoring EFFICIENCY to fL' • Ideal for today's high output PV module Peak Efficiency 95,5% ro m o , CEC Weighted Efficiency 95% � > Nominal MPPT Efficiency 99.5% Z U) iii DIMENSIONS Night Power Consumption 120mW 0 0 0_ 0 _ N ›- m The APsystems YC500i with EnergyMaxTM is a grid-tied a W u_ >_ N _ e hecksr=t°m microinverter with intelligent networking and monitoring MECHANICAL DATA Z 2 U systems to ensure maximum efficiency. Highly dependable Operating Ambient Temperature Range 40°F to+149°F(-40°C to+65°C) and cost effective, the YC500i with EnergyMaxTm is optimized Storage Temperature Range -40°F to+185°F(-40°C to+85°C) W CO 0- a- to accommodate today's high output PV modules effectivelyDimensions(WxHxD)inches 8.75"x 6.5"x 1.1" CeQ PT(32tmm1 O) Q U with up to 548W output and dual MPPT,An integrated ground Dimensions(WxHxD)mm 221mm x 167mm x 29mm o_ W 8 Ur 0 a allows for rapid installation for installers who prefer trunk cable Weight 5.5 lbs(2.5kg) ap < architecture. Half the inverters and half the installation time AC Bus(trunk cable) 12AWG - Enclosure Rating NEMA 6 >n , means real cost savings for residential and commercial customers. '°. L Cooling Natural Convection -No Fans U c L0 I- -I o FEATURES & COMPLIANCE• O Iw— Communication(Inverter to ECU) Power line Communication Q Y Emissions&Immunity(EMC)Compliance FCC PART 15,ANSI C63.4,ICES-003 > - 0) w Safety&Grid Connection Compliance IEEE1547,CSA C22.2 No,1071-01,NEC 2014 z 500 N �.._� 90,12,NEC 2017 6 012 2 U emvn» 6 Z cD a w 9 Monitoring r- U 9 Via EMA Software U_ 0� O W \ WLtoZ U The default AC output is 240V mode.Programmable to 2O8V mode. Specifications subject to change without notice-please U Cl LO "Programmable per customer and utility requirements. ensure you are using the most recent version found at 0 a. 0 o ----. —Meets the standard requirements for Distributed Energy Resources °Oe APsystems.corn Cr) � � � (UL 1741)and identified with the ETL Listed Mark. Interteg I 0 0 EQ ZcTr 4-'~ •_l� -- 6.7377:c A//Rights Reserved Q Z 0 U W E 2 1�'• - 600 Ericksen Ave NE,Suite 200,Seattle,WA 98110 I 844.666.7035 1 APsystems.com p�4 APsystems = O U) CLu W ~U -.....:,.\i.,_...,.'_,_, Y" . ALTENERGY POWER N X W V CO DYNAMIC POWER INNOVATION LLC DISCLAIMER:If any Errors,Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission.In the event that the r)wnar or f;anaral r..nntrarinr fallq to niva cl Irh notirtc hafnrla r ngtn ir.Finn anri/or fahrirttinn of Hip work Hip flwnrr nr lanrral r..nntrarfor will ha halri ragnori ihla to fha raci ilt of any arrorc riicrrananniac nr nmiccionc anri tha rngt of rnri ifvinn therm --- ------- sCALE PAGE 9 N.T.S. RAILS SHEET Lor co Simple Ln = R1 = S 100 ,, --..A_ _.,,, • Quick assembly and clean aesthetic finish < >o • One wrench fits every bolt in the system w N ROOF V O J \ T SYSTV • Low profile installation on any roofCj• o Adaptable >- SnapNrack Residential PV Mounting Systems z _ _ • Compatible with virtually all 60 and 72 cell modules < 2 Q U U U • Unique"snap-in"channel nuts can be installed anywhere i rn H H W m fn a U on the rail on _J � W 0 0 0 • Rail channels provide improved wire management w N 0 0 < T {1 Strong J 0 W Y Y Y The SnapNrack line of solar mounting --� a. ��� � ':� ' 1rtril • Excellent seismic,wind,and snow-loading protection 0 0_ 0) CO N O systems is designed to reduce total . , z "• 3' . • Vertical and horizontal adjustments ensure superior fit oo installation costs. The system features = ; < Xry � w o -.. x a' r T., • Rain-tight metal flashing ensures waterproofing CC technical innovations proven on more than 100MW of solar projects to simplify �l ry Innovative Universal End Clamps } installation and reduce costs. • One size fits any standard L frame module lY -.r a u, CD -r Pitched Roof Arrays Simplified L • Clean look nothing extends beyond module frames A m Less waste-rail lengths match most modules f— o The SnapNrack Series 100 Roof Mount System is an w coo Y efficient,visually appealing,photovoltaic(PV)module z W O o d , installation system.Series 100 was developed in the ' gam . ' O N U ' N . :. ., Wwrn }, N field by a team of veteran solar engineers and installers. =- ar r M .a ., Z 2 („) Their goal was to ensure a quick,efficient installation. < < 0 CC Q N Series 100 has been tested on megawatts of real-world "ding w SnapNrack Series 100 Technical Data pat°nt P m p D_ Roof System in 4 Simple Steps: o z < Z residential and commercial installations. Industry Materials • 6000 Series aluminum cc Q rn < U Z a. leading installation times are achieved with unique • Stainless steel a Woo U < 1)IdentifygSite Conditions(Array Tilt,Building • -_ � oo P 0 Q Snap-in fasteners and fully adjustable components that Height,ht,Roof Type,Wind and Snow Loads) Galvanized steel make installation of roof mounted solar arrays easy Material Finish •Clear and black anodized aluminum 2)Determine Footing Span from Engineering while achieving lower installation costs. U co D Installation •Quick and efficient mounting —1 0 Tables(download at www.snapnrack.com) J ,— •Adjustable hardware to ensure clean and level finish z w • Up to 3"of height adjustability at roof connection 3)Choose color(Clear or Black)and roof •Worryfree waterproof flashing 0 I— • Waterproof full metal flashing at each roof penetration attachment type Calcs.&Certifications • Wind speeds up to 150 MPH and snow loads to 120 PSF Qu) R 4)Place Order with your distributor.Purchase >O z a , Electrical Equipment Bond(WEEK)or lay-fn lugs material for a single project or order in bulk Z N • Single wrench size for all system hardware for additional savings Warranty • 10 Year material and worksrnanship(download full details at snapnrack.com) Z = ti rD a o - Rail&Module Clamps U 0 w • Configures easily as low profile or tilt(0-60 Degrees) w v �-Roof Attachments U O r` • Rail channels provide excellent wire management Arra Accessories Snap rack,. OQ aw0o 0 0 m 0 w Q 0a 44Fti! t o Yti itt Q Z lii V v.•t,1- J— (877) 732-2860 www.SnapNrack.com } I X 0 H 0 m Patent Pending rack- (877) N co w o Moulc ,sterns r 0 printed on recycled paper using soy based inks. 0 2012 by SnapNrack PV Mounting System.All rights reserved, DYNAMIC POWER INNOVATION LLC DISCLAIMER: If any Errors,Discrepancies or Omissions appear in these drawings,specfications or other contract documents;The Owner or General Contractor shall notify the Designer,in writing,of such error or omission.In the event that the Clwnar nr f anaral(:nntractnr falls to nkia ci Joh nntir� hafnra rr'ncfn infirm anri/nr fahriratinn of tha work fha(�tninar nr C�anaral rnntrartnr will ha halri racnnncihla to tha vagi ill of any arrnrc riicerananriac or nmiccinnc and tha rrct of nar}firinn therm 40 ONLINE CERTIFICATIONS DIRECTORY N.T.S. PAGE 10 S \ AP \ RACK LL 2703 QIMS.E359313 1 RAIL FIRE CERTIFICATE Mounting Systems, Mounting Devices, Clamping Devices and Ground Lugs for 1.0 Use with Photovoltaic Modules and Panels - co 1R ___ c Ass / Fict\TioN I-0 Paoe Vo•-tom 0 . > Mounting Systems, Mounting Devices, Clamping Devices and Ground Lugs for < CD cr 5n.:)p?,4ack Solar Mounting Solutions Use with Photovoltaic Modules and Panels Cl- d g See General Infirrnation for MOuntino SYsterns. Mmint,no Devres.Cla•mbr,o Dev,-e•,orn.5m-M L,Ja.,Pop 1J-,..yr;;b PhomlIac m.x1ole.,.7,1 I LO EMMA 1 i 0 February 2015 "NRuNsaum"c'"As""411"7 F 35,313 Z ii(1) 775 Flero Ln < Suite 200 < 0 Sin Lots Obispo,SuCH AS 101401 USA . e/5 As of January 1st, 2015 many jurisdictions are H H LU Znyastlgated DO Cl) EL 0 now enforcing codes based upon updates to Investigated for System Flee < Ill - .......... .......... Cat. for Mechanical Gasalricatkm Li_ the International Building Code (IBC) and UL No. Bonding Loadme (A,•or C) Tested in Combination Vilds _I N Standards 1703 (modules) and 2703 (mounting Photovoltaic mounting system (l) > (,/) systems). The language included in the 2012 IBC Sends AN 3S0 N 14.L.Med PV Nodules: requires that the combination of roof mounted -410 REC Solar AS:REC214,REC.215,REC220,REC225,Rf:C230, REC235,REC240,RFC2a5.REC250,REC255,REC260,REC.26S, --1 0 D Et L.I..1 I-- 0 0 CV solar modules and racking components is to • 4 .....sogi , .. all(allowed by PF,PFOL8),PE-US,PF-L/S(91.P1),PF QT or P8Q3. 0 0 >_ CO (V N---• be considered a system (IBC Section 1509.7.2) ,-- Hy.,,d,,,Heavy industries Co Ltd: 2 2 cn 1.6 Lri LU • 4, _.--,, - . , co o Additionally, it requires that this system shall - HiS-Max..MG bares-HIS.M210PM,1415.14213/4G,HIS•M21514G, r r Of /° e.--C.77, MS-M2LEPMG,H.S.P121dalG,HIS-M22314G.HIS.142,25;MG,MS- meet or exceed the fire classification of the roof Arf ..- -4•A.-"-- 1122/3MG,1115-44230MG,HiS-P1233,4G,H.S.1s239.1G,liS-M2.38MG, .41F- _ H.S-M240MG,1115-P1243a1G,HIS-112 HIS M2404G,HIS- assembly. I ' 1129:04G,110544253mG,HIS-M255MG,MS-P4250MG,111S-14260HG, a: HIS.1426314G,11.5.14269M,HIS 11268110 HiS•s1220140; D 1.1+5.5xxxlv4 Senes•HTS.S2204 ,1115.5223110,1-14•5225MG, Y! 1145•5228110,1115-5230f4G,H15.52331.4,HiS42394G,HIS. I 0 The objective is to ensure that the PV system S238MG,HM-52401M,HiSS243M0,HIS•SZISMG,HIS•4248MG, Lo H•5•5250MG,H.S.S253MG,HlS-S2SSMG,HIS-5258m,m,s• is7) 0 does not adversely affect the fire rating of the roof. Roof surface fire ratings are classified either A, 5260MG,MS-5263MG,HiS-S26SMG,HIS-S268MG,HIS-S270MG, A HiS•5273MG,H.S-S275MG; co B, or C; Class A being the most resistant to the spread of flame. all may be followed by 9w Her.,Bl<or Mink. 0 LO Q FlEreiele rancisv LW'.11:1[1.04-24/013 Sena'-2c2074-74/00), 111 Cr) Lij C.0 Since the physical characteristics of the PV module (material, thickness of glass, etc) also JC205M-24/13b,1C.710M-271/Bb,JC21511-24/60,1C220m-24/ao, K.22514-24/0b,JC230M-24713b.JC-23514-24/15b,1C240M-24/Etb, Z 0 a potentially affect how a fire will act, modules are now tested and assigned a -type" based upon . - / , 2.2700144--2244,,1B5b11,1C2S5M-24713b,1C26014-24.05b, 2 _ (I) 0 C•I I- 0 No r.-- these characteristics and spread of flame test results. There are 15 total module types. Types 1, Surma Inc-MVX-235-60•5•701,MVX-240•60-5•70I,77NX•245-60- W Li_ (3) >7 C•1 5-7oi,NVX-250-60-5-701,WY-255-60-5-701,MVX.260-60-5-701. Z 1 0 .- 2 and 3 represent differences in the module composition and Types 4 - 15 are the same module Pnex-26s-60.5-701r2 (4 fX Z MVX•235-60.5-701,MVX•240-60-5-7131,MX-245.50-5-7BL reirx• H < < 0 ..... Cn compositions as Types 1 - 3 with differing fire test performance. 250-60-5-7B1,MVX-255-60.5-731,INVX-260-60-5.781,MVS-265. 0 50-5-701; W CC) if a- OPT.250.60.4.8130,097-255-84)-4.800,OPT•250-60-4-800,OPT. -, Z (1) Ct D 4t SnapNrack Series 100 has been Certified for a Class A fire rating with Type 1 and Type 2265•60-4-800,OPT•270•40.4-800,OPT•27S-60•4-800; OPT•250-150•4•71150,OPT•255-60-4•860,OPT•260-60•41-8150,OPT. 0 < 0) < 0 z modules, in accordance with the standards set forth in UL1703/2703 and IBC 2012. In order to 265-60-4-880,017-170-60-4-880,OPT-275-60-4-8410. 0-1 in 8 0 0 a_ 0 < maintain this classification, the SnapNrack mounting system must be installed per the UL-approved Yir41 Enemy(Ouna)Ca Ud•YLXXXP•29b Sense•YL215P•29b, TL220P-200,YL225P-29b,Y1.230P-29b.TL2-35P-29b,Y1.240P.Z9b, 11.245P•290,rasoP-?Rh riassa-no,V1.260P-29b; Installation Manual. Because the test was conducted with the modules at 5 inches from the roof yi.xxxA-290 Series-11.22DA-79b,YL 2.2511,29b,Ti230A-291:), Y1235A-29b,Ti240A-29B,YL245A-29b,Y1250.4-29b,51.255A-295. surface (worst case scenario), there is no restriction to the standoff height. 0 Pena Solar Ltd-ISM-215PA05,TSM-22011105,28e1-225P605.MN- __J c) 230PA0S,TSM-235PAOS,T5M•240PA05,TSM•245PAOS.TSM• __I '- Attachment 1 is the SnapNrack QIMS File which is accessed through the UL Online Certification 250FA05,7511.255FIMS,T51.1-260Pan TSM-215DA05.0S,TS11.220PA05,05,P5P1.225P0.05.0S,MM. Z u..1 0 Directory, or available here: SnapNrack QIMS File. 230PA05,05,15M•235PA05.05,T511•240PA05.05,194-245PA05-05, TOM P605.05.TSM•25SPA05.05,TSM•260PA05.05. I- - TSM-215PA05.41,TSM-12 'A02.09,TOM- P805.06,TSM- < (/) '2 Os-eS And P. , 130PA05,08,TSM-?35P605.06,TSP4-1e0PNOS.138.M14-245PN05.08. > - CO The full SnapNrack Series 100 UL Test Report is available by sending requests to 100 FS14-250PA05.86,TSM•255PA05.08,ISM•260PA05,06, 0 Z Lu 11 TSM-215P0OS,TSM-220P005,1511-2256005,TSM-2356005,TSM Q >-N appeng(cbsnapnrack.com. 235P005.ISM-24(0005,3011-2456005.TSM-250P005,TOM- •zr o 25511405.TP44601,005; Z 1L1J 0 TSH-2iSP008.88.Tsm-noP005.84, I- 3511-2256085.08,TOM- - N- CS) a. (/) - 2304,005.08,T144-235P00500,T501-27.09005.00,0511-245600506, fX 0 (3) '',71- 0 Z 0 Y LU TSM•250P005.00,n*255F005.08,TSM-260PCOS.08. w iT_ c. CD WTI.USied PV Modules; (5 0 CO 0 < 0- 0? o Hanwha Solar:Me.Models 141.60P6-P6-2-230Q,H51.10114-P6-2- a_ a. 45 235Q,14SLEOP6-P13-2-240Q,HSL60P6-PEI-2-245Q.HSLEOP6-P5-2- 0 c'") 250Q,HSLEOPb-P8-2-25SQ.HS1.60P6-1113-2-260Q,H$L60P6-113-2. (-) 0 F.) < CO.7 snap racii TM 765Q.HSL60P6-P0-2-210Q: '-' CO 77, Z a) 115L606-P8.-4--230Q,HSLEOP6-P0-4-235Q,115L6006-P13-4-240Q, LI i...7 Lij•cr H5L60P649-4-248Q,HS...60P6Pe.4-1500,HSLE064.8.4-25.4. < I-0 IX Z E 0 143 H5o565-P8-41-260Q,H5L80P648-4-265Q,HS1.80b6411-4-270Q; Z .1- in 0 coo LU&; may be follower!by adekbenal,.Maas >7 CD I I W H d '1 .( Sorra Inc-OPTXXX-60- 0 CN U) CL X 04-YTY: where*XX may Ise numbers 240 to 270 in Incsernon (0ts of 5; - 'Mere rev may be 100; 13177XXX.60-4-0Y5: (877) 732-2860 www.SnapNrack.com Stele 083 may be numbers 73550 255 IS.InaereePts of 5: DYNAMIC POWER where YYY may be 100. of SriapNr.sck, Sews H h A ?VIM 1 and Twe 2 PV Mockers INNOVATION LLC This listeamatiph.5 COnfICSOniAlArla PfOCCbtoVy Ally ftr,011.40.7.11 Cle,<IL..,.1...or USO thao,41,4 osp.revoy piohb.tec‘,y.,.t,out wrateri pwrrussron Lne 100 2015 by SnapNrack PV Mounti-rtg System All rrghts reserved , \ ) DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall nofify the Designer, in writing,of such error or omission. In the event that the nwnpr nr npnpral rnntrartnr fallc to nivp ci irh nntirp hpfnrca rnnctri iriinn anri/nr fahriratinn nf the wnr-k thp Clwnpr nr P.pnpral r.nntrartnr will hp hplri rpcnnncihlp to thp race lit nf any Prrnrc riicrrpnanripc nr nmiccinnc anri thP nnct nf rprtifvinn therm N.T.S. 1 PAGE 11 ATTACHMENT SHEET Y ch SRHS ] OO 1 0 w . D_ N FLASHED L FOOT /KIT � g Q 0 = U } SnapNrack Residential PV Mounting Systems ' . • z N QQvv — , cn f– 1 - w Al 0 QW wci_ U Flashed L Foot Kit Assembled(V spacer sold separately) Flashed L Foot Kit Parts(V spacer sold separtely) W W 0 0 Q > u) wZ 2Y Y Y J O w The SnapNrack line of solar mounting M Flashed L Foot Kit Assembly Flashed L Foot Kit Dimensions D r2 o Hoo c\1Co systems is designed to reduce total 2 2 N • • installation costs. The system featuress = r T ,:•-. - ". -94A7FR/CK 920Et7£El-r;Itlf,C1rM technical innovations proven on more •t5I �:sn than 200MW of solar projects to simplify x- ;«K° N. SwtAAAQt C9xP'31tC(x1 RAKING N installation and reduce costs. _ • iCD Flashed L Foot Simplified1 :•-• r 0° SnapNrack Series 100 Flashed L Foot Kit is an innovative `' EL20(7;) W C°o ❑ d �solution to provide a long lasting watertight seal over I N m w u_ ; >_ U the life of the system.The Flashed L Foot provides a Z 2 U `r (2W11- Z %-- single W Z %- single fastener flashed to an attachment composition Q Q U 0- N shingle roof with no required cutting of shingles.The L Flashed drillt in 3 rthree pilot hole �� I z ro < 0 Z Q rn Q O Z Foot is engineered for maximum adjustability for a clean 4" `R`F°` a -) c0 l 0 < level installation. 2)Prep and attach the base 3)Set the flashing and attach the L Foot SnapNrack Flashed L Foot Technical Data Patent Pending 0 o Materials • 6000 Series Aluminum L Foot&Base J `— • 1"slotted bolt connection z W • Stainless Steel Hardware 0 H • 1"spacers available for increased adjustability • Galvanized Steel Flashing i Material Finish • Clear and black anodized aluminum > U) rY • Clear or Black anodized aluminum components Place order through your SnapNrack > z a Weight • 0.16 lbs OZ 2 distributor, which can be found at N (both available with black flashing) Design Upright Load 200 lbs Uplift Z 2 co a w o www.snapnrack.cam contactry U rn 0 z 0 • No Cuttingof shingles Design Ultimate Load 1,000 lbs Uplift LT o Y w g Warranty • 10 Year material and worksmanshipO O 0 O O Z w $nciprack U5O � ¢ u Z co < w 94-' Q � � z ° 02 [/'�� f ting c r •t , ioz0 o m Snaprack. ❑ N co X w F o (877) 732-2860 www.SnapNrack.com Patent Pending DYNAMIC POWER 0 Printed on recycled paper using soy based inks ®2013 by SnapNrack PV Mounting System.All nights reserved. INNOVATION LLC } DISCLAIMER: If any Errors,Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission.In the event that the (Iwnar nr C�anaral rnntrartnr falls to nivs ci irh nntincs hafnra rnnctn u-tinn anri/nr fahriratinn of the work C. the owner nr C-IanPral nntrartnr will he horn racnnncihla to tha racl ilt of anv arrnm riicrrananriac nr nmiccinnc and tha rnct of rarfifvinn therm - - - _ _ \� N.T.S. PAGE 12 � WARNING LABELS in WARNING / NWARNING/ \ PHOTOVOLTAIC AC DISCONNECT 7 INVERTER OUTPUT 0 ' CONNECTIONS(S), DUAL POWER SUPPLY MAXIMUM OPERATING CURRENT 30 A Q o DO NOT RELOCATE THIS SOURCES: UTILITY GRID AND MAXIMUM AC OPERATING VOLTAGE 240 V w N OVERCURRENT DEVICE PV SOLAR ELECTRIC SERVICES 0 o PLACED ON MAIN ELECTRICAL PANEL 690.54 Q U PLACED ON MAIN PANEL PLACED ON MAIN ELECTRICAL PANEL > (i) q = cn F- I-U] CCI cn � U - w N 0 0 < > (n WARNING o w POWER TO THIS BUILDING IS PV SOLAR BREAKER 0 C I— r- o N CAUTION ALSO SUPPLIED BY THE DO NOT RELOCATE THIS ❑o v } CON o 1 PHOTOVOLTAIC SOLAR SYSTEM OVERCURRENT DEVICE SOLAR ELECTRIC SYSTEM CONNECTED coo cs " co ' "' `r) DO NOT TOUCH TERMINALS PLACED ON MAIN ELECTRICAL PANEL PLACED ON BREAKER PLACED ON MAIN PANEL o U) C CD om L o z � LJ co O 2 E❑ N m E O N U Z LLJ 2 U 1I QQOZcn p o CU PHOTOVOLTAIC SYSTEM THIS EQUIPMENT FED BY MULTIPLE SOURCES. WARN I ° < rn < 0 Z CL EQUIPPED WITH TOTAL RATING OF ALL OVERCURRENT DEVICE, WARNING co P O RAPID SHUTDOWN SHALL NOT EXCEED AMPACTIY OF BUSBAR. PHOTOVOLTAIC POWER SOURCE PLACED ON INVERTER PLACED ON MAIN PANEL NEC 705.12(D)(2)(3)(E) PLACED ON INTERIOR AND EXTERIOR DC CONDUIT, 0o CEC 690.56(C) RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES, z w JUNCTION BOXES, AND DISCONNECTS. MARKING 0 I— I=SHALL BE PLACED ON INTERIOR AND EXTERIOR DC up Y CONDUIT, RACEWAYS, ENCLOSURES AND CABLE > - r nUi ASSEMBLIES EVERY 10 FEET (3048MM), WITHIN 1 z FOOT OF TURNS OR BENDS AND WITHIN 1 FOOT cc v Tr,: 7 o Z 0 Lu ABOVE AND BELOW PENETRATIONS OF Lu vO o i ROOF/CEILING ASSEMBLIES, WALLS OR BARRIERS. p < o N o O o z w UOSn ¢ corn QLocz FE Jco > o = 1 (_) F-0 ❑ N U) 0... X w F0 u) DYNAMIC POWER INNOVATION LLC DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings,specifications or other contract documents;The Owner or General Contractor shall notify the Designer, in writing,of such error or omission. In the event that the flwnar nr nanaral rinntrartnr fallc to niva ci irh nntirp hafnra mnctn irtinn anri/nr fahriratinn nf tha work tha Chmnar nr Cdanaral rnntrartnr will ha halri racnnncihla to tha mac!ilt nf any arrnrc riicrrananniac nr nmiccinnc anri tha rnct of rar fifvinn therm