Report (29) PRIME E LE 'T' -,`. A L RECEIVED k SERVICES, LLC. JUL 1 2019 Electrical • Communications ♦ Life Safety♦ Security♦ CCTV CITY OF TIGARD PO Box 872395 Vancouver,WA 98687- Phone(503)318-5170 3UiLD?Nr DIVISION CCB#: 217825 FIRE ALARM SYSTEM SUBMITTAL Durham Elementary School 6960 SW Sandburd St. Tigard, OR 97223 June 26, 2019 Proposed by Prime Electrical Services PO 19-158 Project Manager: Oleg Primachenko B®SimplEx LifeAlarm Fire Alarm Controls UL, ULC, CSFM Listed; FM Approved; 4009 IDNet NAC Extender for Control with MEA (NYC)Acceptance* IDNet Communications or Conventional NACs Features . Provides additional notification appliance circuit ® 0 (NAC) capacity with flexible operation modes and power-limited design up to 8 NACs •• Four, Class B NACs are standard: Plag II.. • Rated 2 A each for conventional reverse polarity 4009 IDNet 24 VDC notification appliances and providing NAC Extender — multiple operation modes Minnilli ") MB • Can be selected to provide synchronization for Simplex®visible notification strobe flashes § • Capable of controlling TrueAlert non-addressable Optional IDNet ��,� IIER,EIo-,-.m. Channel Repeater notification appliances operating with SmartSync �• two-wire control mode** / `i• _-s a * I Input control options: • IDNet addressable communications from a Simplex , 2-Wire IDNet • ` model 4007ES,4010,4010ES,4100ES,or 4100U Fire Communications or Alarm Control Panel** ; Fiber Optic IDNet • Or from one or two conventional 24 VDC NACs with 1 Communications or multiple output control options • NAC Control INIItlW11Wtl1YIRYY4Ygo'.v II IDNet communications control benefits: - ' , • Provides status monitoring and individual NAC control IDNet Fiber using a single address per 4009 IDNet NAC Extender Optic Transmitter • Supports IDNet"Device Level"earth fault location moumwwunuaIwr • t �. � WALKTEST operation is available with either 4007ES,4010(shown), input choice 4010ES,4100ES,or 4100U Internal 8 A power supply/battery charger: Fire Alarm Control Panel • Charges internal batteries up to 12.7 Ah or up to 18 Ah Fire Alarm Control Panel with Conventional NACs batteries in external cabinet • Provides status monitoring of battery,input power,and 4009 IDNet NAC Extender Connection Reference Drawing earth faults Introduction • Rated 8 A for"Special Application"appliances; including Simplex 4901,4903,4904,and 4906 Series ADA Compliance.Complying with the notification horns,strobes,horn/strobes,and speaker/strobes requirements of ADA(Americans with Disabilities Act) • Rated 6 A for"Regulated 24 DC"appliance power may require more notification appliance power than is Optional 4009 IDNet NAC Extender modules: available within the fire alarm control panel.When • IDNet Communications Repeater provides Class B or additional power is required,a Simplex 4009 IDNet NAC Class A output Extender can provide up to 8 A of NAC power with up to eight,supervised reverse polarity NACs. • IDNet Communications Fiber Optic Receiver/Repeater, Location Flexibility.The 4009 IDNet NAC Extender available as Class B or Class X • Four additional Class B NACs,rated 1.5 A for Special can be mounted close to a compatible dedicated host Application appliances; 1 A for Regulated 24 DC panel or can be located remotely for convenient power appliance power distribution.Multiple operation modes and multiple connection options further increase location flexibility. • Class A,Two Circuit Adapter Module Additional Information. For additional operation detail UL Listed to Standard 864 and application information,refer to Installation External Accessories Instructions 574-181 and field wiring diagram 842-068. IDNet communication fiber optic transmitters: • ULC listed model is 4009-9202CA.This product has been approved by the California • For applications requiring the data integrity available State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and PP q g gSafety Code.See CSFM Listing 7300-0026:214 for allowable values and/or conditions with fiber optic communications concerning material presented in this document.Accepted for use—City of New York • Available as Class B or Class X Department of Buildings—MEA35-93E.Additional listings may be applicable;contact your local Simplex product supplier for the latest status.Listings and approvals under • Mounts in standard six-gang electrical box Simplex Time Recorder Co.are the property of Tyco Fire Protection Products. External battery cabinet for 18 Ah batteries ••4100U requires revision 11 software or higher for compatibility.4010 requires revision 2 software or higher for compatibility. S4009-0002-14 9/2015 Application and Operation Information IDNet Addressable Communications Compatible. Hardwire Control Applications. For applications Up to ten(10),4009 IDNet NAC Extenders can be where an existing(or new)conventional NAC needs controlled per 4007ES, 4010ES, 4100ES,or 4100U additional power,the 4009 IDNet NAC Extender can be IDNet communications channel;up to five(5)can be controlled directly from the NAC.Either one or two controlled on the 4010 IDNet communications channel. NACs,from either the same,or from different host fire Each output NAC can be individually controlled for alarm control panels,can be connected to control the 4009 general alarm or selective area notification requiring only IDNet NAC Extender output NACs.Multiple control one point address per Extender. Individual Extender selections provide flexible operation.(Refer to page 4 for NACs can also be manually controlled from the host more detail.)Alarms from the host panel will activate the panel.IDNet controlled extenders will inform the host four,4009 IDNet NAC Extender NACs(or optionally, panel of troubles via IDNet communications.4007ES, eight NACs)to extend the alarm. 4010ES,4100ES,and 4100U control panels control using The 4009 IDNet Extender monitors itself and each of its multi-point rules,refer to data sheet S4090-0011 for output NACs for trouble conditions,including earth details. faults.Extenders wired to conventional NACs will Optional IDNet Repeaters.IDNet communications can indicate a trouble by opening the path to the NAC's be repeated with the optional IDNet Repeater Module or end-of-line resistor,but retaining the ability to respond to with the optional Fiber Optic Receiver Module. Up to 100 alarms. Individual troubles are also annunciated by LEDs of the IDNet channel points can be repeated once(refer to located on the 4009 IDNet NAC Extender main circuit pages 3 and 5 for details).Repeated IDNet communications board.(Refer to page 7 for more diagnostic information.) also support the"device level"earth fault location utility of the host panel. Product Selection Standard Models Model Description 4009-9201"" 120 VAC input 4009-9202CA" 4009 IDNet NAC Extender with 4,Class B NACs and 8 A power supply 4009-9301 240 VAC input " ULC listed model ""4009-9201 has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019 Optional Modules (for on-site installation) Model Description Comments Additional four point NAC module,rated 1.5 A Special 4009-9807 Application appliances; 1 A for Regulated 24 DC appliance One maximum power, Class B 4009-9808 Dual Class A adapter(for two NAC outputs) Select as required(4 maximum) 4009-9809 IDNet Repeater,output is Class A or Class B Select either an IDNet Repeater or a Fiber 4009-9810 Class B Optic Receiver as required; one transmitter Fiber Optic Receiver can connect to one receiver 4009-9811 Class A(IDNet), Class X(fiber) 4009-9805 Red Appliqué for door Select if required 2975-9801 Beige trim 1-7/16"wide(78 mm), use if required for 2975-9802 Semi-Flush Trim Kit Red trim semi-flush installations Battery Selection (select battery size per system requirements) Model Description Comments ------>2081-9272 6.2 Ah Battery, 12 VDC 2081 9274 10 Ah Battery, 12 VDC Two batteries are required,24 VDC operation 2081-9288 12.7 Ah Battery, 12 VDC 2081-9275 18 Ah Battery, 12 VDC Requires external battery cabinet,two batteries are required,24 VDC operation External Accessories (select per system requirements) Model Description Comments 4090-9105 IDNet Fiber Optic Class B operation Mounts in six-gang electrical box, refer to 4090-9107 Transmitter Class X operation page 4 for mounting details 4009-9801 External battery cabinet for up to 18 Ah batteries,beige 16-1/4"W x 13-1/2"H x 5-3/4"D (413mmx343mmx146mm) 4081 Series End-of-Line Resistor Harnesses;see data sheet S4081-0003 for details 2 S4009-0002-14 9/2015 T •ical IDNet Connection Exam•le Typical ZDNet compatible devices (Refer to individual devices for actual wiring requirements,some wiring is not shown.) , . , . -7- 111i I IV ' iIDNet addressable communications channel, WILUQUitilitattUitabIT ...w..,..,7 shown Class B(Style 4) Output NACs,four standard, Conventional NAC operation(horns) eight with expansion option - —Select conventional L ; A or SmartSync f 4007ES,4010,4010ES, — 111111111 operation per NAC 4100ES(shown),or 41000 - - - Fire Alarm Control Panel ® C1 0 SmartSync operation(horns and strobes) 4009 IDNet NAC Extender with 11 i Mill ----1 i—o- Conventional NAC optional internal IDNet Repeater ��, operation(strobes) • Repeated IDNet Channel: '.3 up to 100 devices maximum on repeater output, /) 250 devices total on IDNet Channel .1. IDNet devices and additional 4009 IDNet NAC Extender(s) NOTE: Up to ten (10)4009 IDNet NAC Extenders may be connected per 4007ES, 4010ES,4100ES, or 4100U IDNet channel, up to five(5)on the 4010 IDNet channel. IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver). Typical Fiber Optic System Connections Two fiber cables,3000 ft Output NACs 4090-9105,Class B (914 m)maximum distance !'1,11„111.' (Style 4)Output Fiber IIIIIIIIIalllllll1111111111111111111111111111111UWllllll Optic Transmitter A:■ III [4 V 11L111E P n - 1pe-�MaL IDNet addressable communications 7 .,t..:.:1.4 --- channel Class B(Style 4)or Class A ' : (Style 6),Class B shown Repeated IDNet Channel:up to 100 devices maximum on repeater output,250 devices total on IDNet Channel Four fiber cables,3000 ft 4007ES,4010(shown), (914 m)maximum distance 4010ES 4100ES,or 4100U Fire Alarm Control Panel 11111111 II • 24 VDC power for wj fiber optic transmitters i111 4090-9107, p 4090-9107,Class A(Style 7) T 4n kg 6." Output Fiber Optic Transmitter 1_ErILI-1 LH ' 4009 IDNet NAC Extenders with optional Output NACs internal IDNet Fiber Receivers NOTE: Up to ten(10)4009 IDNet NAC Extenders may be connected per 4007ES, 4010ES,4100ES, or 4100U IDNet channel, up to five(5)on the 4010 IDNet channel. IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one receiver in a 4009 IDNet NAC Extender. 3 S4009-0002-14 9/2015 Hardwire Control Connection Information SmartSync Notification Appliance Control NAC Input Selections.The 4009 IDNet NAC The TrueAlert Notification Appliance product line Extender can be selected to: includes addressable and non-addressable operation. • Track input NAC operation or to provide a locally Non-addressable models are available with 2-wire generated code,selectable per NAC input SmartSync operation or conventional 4-wire operation. The following details apply to use with the 4009 IDNet • If selected for local coding,NAC outputs can be either NAC Extender: Temporal Coded or 60 Beats/min March Time Coded, one code selection per extender(input NACs must be on • TrueAlert non-addressable models with SmartSync continuous with Alarm) operation allow audible notification to be separately • Additionally,NAC outputs can be selected to provide controlled over the same wire pair that controls visible the Simplex strobe synchronization signal.This signal notification will synchronize the flashes of synchronized strobes but • 4009 IDNet NAC Extenders can be selected to provide will be ignored by free-run strobes and audible devices. SmartSync operation whether controlled by IDNet (Strobes are for operation by noncoded NACs.) communications or conventional NACs NAC input to NAC output control can be selected for • IDNet control allows output NACs to be individually standard and optional NACs per the following table: selected for conventional or SmartSync operation Conventional NAC Output Operation Options • With NAC input control,all output NACs are selected Input A B C for either conventional or SmartSync operation NAC 1 NACs 1 &2,5&6 NACs 1-4 NACs 1-8 • Refer to data sheet S4009-0003 for TrueAlert NAC 2 NACs 3&4,7&8 NACs 5-8 None Addressable operation details,contact your local SmartSync NAC Output Operation Simplex product supplier for further information on Input NAC Control Function specific TrueAlert notification appliances NAC 1 Strobe Control NAC 2 Horn Control All NAC outputs(1-8) Hardwire Control NAC Connection One-Line Reference Diagram Up to eight(8)output NACs total;hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements NAC 1 input • (see Note 1) Ai Conventional NACs I. Cj f-' With hardwire control, NAC outputs are all Output conventional or all ti ��� ___ ��#� ► NACs SmartSync operation 4009 IDNet NAC Extender C • Fire Alarm Control Panel p with Conventional NACs SmartSync operation Class A operation,either mode,requires NAC 2 input 4009-9808 Dual Class A Adapter (optional,see Note 1) To additional 4009 IDNet NAC Extenders(up to four(4), 4009 ZDNet NAC Extenders per NAC);see Note 2 Notes: 1.For separate audible and visible output NAC control,or SmartSync NAC output operation,two(2)input NACs are required. NAC 1 is"on-until-reset"and NAC 2 is"on-until-silenced." 2.To synchronize strobe flash outputs for up to four(4)4009 IDNet NAC Extenders,use the synchronized strobe output from a Synchronized Flash Module(4905-9914 for Class B operation,4905-9922 for Class A operation)or, if available,from a NAC selected to provide synchronized strobe flash output. NOTE:DO NOT USE a NAC selected for SmartSync operation for this function. Refer to Installation Instructions 574-181 for additional information and application guidance 4 S4009-0002-14 9/2015 4009 IDNet NAC Extender S•ecifications 120 VAC Input(4009-9201) 3A @ 102-132 VAC,60 Hz Input 240 VAC Input(4009-9301) 1.5A @ 204-264 VAC,50/60 Hz Ratings Hardwire Control from External Conventional reverse polarity operation NACs, Input Requirements 5 mA maximum; 16 to 33 VDC Total Rating 8 A, Special Application appliances 6 A, Regulated 24 DC appliance power Standard NACs 2 A each,Special Application or Regulated 24 DC appliance power Optional NACs 1.5 A each, Special Application appliances (requires 4009-9807) 1 A each, Regulated 24 DC appliance power Special Application Simplex non-addressable horns,strobes,and combination horn/strobes and Output Ratings Appliances speaker/strobes(contact your Simplex product representative for compatible appliances) Regulated 24 DC Power for other UL listed appliances; use associated external synchronization Appliances modules where required Strobe Operation Up to 33 strobes per NAC can be synchronized;output NACs configured for Simplex synchronized strobe operation are synchronized to each other Auxiliary Output 500 mA @ 24 VDC nominal Optional Modules Ratings Input Power 70 mA @ 24 VDC,system supplied IDNet Input,One Address Maximum distance from IDNet source is 2500 ft(762 m) IDNet Repeater Repeated IDNet output for up to 100 devices(total IDNet devices not to exceed Module 250 per channel) (4009-9809) IDNet Output Specifications Maximum distance to farthest device is 2500 ft(762 m) Total distance including"T-taps"is 10,000 ft(3048 m) Class A loop maximum distance is 2500 ft(762 m), no"T"taps Fiber Optic Receiver Modules Input Current 4009-9810,Class B,65 mA @ 24 VDC,system supplied 4009-9811,Class X, 80 mA @ 24 VDC,system supplied IDNet Output Specifications Same as those for Repeater Module(see above) Fiber Optic Transmission Distance 3000 ft(914 m)maximum General(LED status indicators are listed on page 7, dimensions and mounting details are on page 6) Operating Temperature 32°to 120° F(0°to 49°C) Operating Humidity Range 10%to 90%RH from 32° F to 104°F(0°C to 40°C) Wiring Connections* Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Fiber O•tic Transmitter S•ecifications Input Voltage 18.9-32 VDC from compatible listed fire alarm supply 4090-9105,Class B,30 mA @ 24 VDC Input Current 4090-9107,Class X,35 mA @ 24 VDC Multimode,graded index, 50/125pm,62.5/125 pm, 100/40 pm, or 200 pm Fiber Optic Connections and cable Type ST connectors requirements 4090-9105,Class B operation,two fiber cables required 4090-9107,Class X operation,four fiber cables required Module Size(with mounting bracket) 6-13/16"W x 3-3/4"H x 1-1/8"D(173 mm x 95 mm x 29 mm) Green LED flashing=transmit On-board Status Indicators Red LED flashing=receive Separate red LED on 4090-9107=Class X receive Communications Simplex IDNet Fiber Optic Transmission Distance 3000 ft(914 m)maximum Wiring Connections* Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Operating Humidity 10%to 90%RH from 32°to 104°F(0°to 40°C) Operating Temperature 32°F to 120°F(0°to 49°C) "Metric wire equivalents: 18 AWG=0.82 mm2; 12 AWG=3.31 mm2 5 S4009-0002-14 9/2015 4009 IDNet NAC Extender Mounting and Module Placement Information Cabinet depth [1 16-1/4"(413 mm) ► I4- 1/4"(108 mm) 1 6 10-29/32"(277 mm) d I Door,5/8" — —® © ® ® (16 mm)thick 00 0 i- i Optional Class A 4009-9807 Additional Four 13-1/2" adapter modules point module(shown with • (343 mm) Class A adapters) L Exposed cabinet / 1 II dimension for—*' +r$- i i I System Module / ® ®� semi-flush mount [1 \ \_ 1"(25.4 mm), Knockouts for screw IDNet repeater or 1-3/8"(35 mm)withor nail mounting holes Fiber optic receiver a semi-flush trim 8 lb a © 0 ®ILJU —© 0 0 - - 1 C II 1 I I I I �.. 12"(305 mm) r-I 1 I � p 1 I 7-------------- Battery location,no conduit entry or wiring in : I 1 I this area(12.7 Ah battery outline shown) I I I 11 O OI - .}.1- I 1 Semi-flush trim option Non-power limited wiring area(AC input) 1-3/16 wide(30 mm), —i 3/8"(9.5 mm)thick — Wall surface reference for semi-flush mount NOTE: Recommended conduit entrance varies with module selection. Refer to general installation instructions 574-181, specific module installation instructions, and to field wiring diagrams 842-068 before locating conduit entrance. 4009 IDNet NAC Extender Cabinet with Door Detail l r Optional red applique ' (4009-9805) 4009 IDNet'" NAC EXTENDER ',simplex 6 S4009-0002-14 9/2015 4090-9105/9107 IDNet Fiber Optic Transmitter Mounting Information i Surface mount box: _„, 0 0 0 0 000T0 - Simplex m(ordered ep rately) • • • •i_ se aratel Flush mount masonry box: I use 6-gang box, RACO#960,2-1/2"deep � . 0 o 0 0 0 0 I (64 mm), or RACO#965, 3-1/2"(89 mm) ii • • • • • •AMMEIMI7' I deep,or equal(supplied by others) t w cw• • `• Flush mount ganged boxes:\ _�= O ' use 6-gang box, 1-1/2"(38 mm) �a minimum depth;six, RACO#400 111 x !or equal, (supplied by others) .ILL., a v v u.. '0 �. JMJ 0 0 0 0 0 0 IDNet fiber optic transmitter: 4090-9107, Shown, Class A(Style 7)output 4090-9105, Not shown,Class B(Style 4)output INSTALLATION NOTE: Fiber optic cable bend radius should be 2"(51 mm) minimum, or per Manufacturer's specification. 0 0 0 0 0 0� Six-gang blank cover plate Mulberry Metal Products 97156 or equal(by others) Service Dia•nostic Features LED Status Indicators are provided for the following: Power-up Self-Diagnostics.Upon power-up,the • Each NAC(standard and optional)has a dedicated 4009 IDNet NAC Extender tests each module and yellow LED that: performs earth fault diagnostics.Trouble conditions are — During supervision provides a slow flash to indicate communicated to the host control panel and are also a short circuit condition and a fast flash to indicate displayed on diagnostic status LEDs in the 4009 IDNet an open circuit NAC Extender.When connected via IDNet — During an alarm,the LED follows the NAC output communications,detailed status information is available (on steady or flashing with coded output) at the host.When controlled with conventional NAC inputs,common troubles are signaled by providing a • Four, general status yellow LEDs provide nine polarized open circuit that disconnects the NAC wiring separate indications listed in priority of urgency.As a from its end-of-line resistor but still allows a reversed trouble is eliminated,any remaining trouble(s)will polarity alarm to be received. then be indicated until the 4009 IDNet NAC Extender is returned to normal operation. Door Mounted Reference Label.The 4009 IDNet NAC Extender has a detailed programming and • AC power status is indicated by a green LED that is diagnostic label inside the front door that provides a quick on when AC is normal.During low AC(brownout) reference for both installation and checkout. conditions or with no AC,the LED is off.Additional power and battery status is indicated by the general status LEDs. 7 S4009-0002-14 9/2015 4009 IDNet NAC Extender Current Calculation Chart Step 1. Calculate Basic Extender Battery Requirements(minus NAC loads) Panel, NAC Options,and Auxiliary Power(underlined model numbers are optional modules) Model Descript ion Supervisory Actual Alarm Current Actual Alarm Current Supervisory - — 4009-9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009-9301 240 VAC input 4009-9807 Additional Four Point NAC 40 mA + 40 mA + 4009-9808 Dual Class A Adapter(no additional current) – – – – Auxiliary Power Output (500 mA (500 mA maximum) + maximum) +[Al] Basic Panel Supervisory Current =[S1] Basic Panel Alarm Current =[A2] Step 2. Calculate ZDNet Output Module and Device Current(if used) 4009-9809 IDNet Repeater 70 mA 70 mA 4009-9810* Fiber Optic Receiver,Class B Select one per 65 mA + 65 mA + Extender 4009-9811* Fiber Optic Receiver, Class X 80 mA 80 mA IDNet Devices(connected to Repeater or Receiver above), Total devices + Total devices + 0.7 mA each, maximum of 100 x 0.7 mA each x 0.7 mA each *Note: IDNet Fiber Optic Transmitter ZDNet Module Supervisory Current [S2] = current is supplied from the host fire alarm control panel IDNet Module Alarm Current =[A3] Maximum Available Current =8 A* Step 2. Calculate Available NAC Current Subtract Auxiliary Power Output -[Al] Subtract IDNet Module Current -[A3] *8 A for Special Application Appliances;6 A for Regulated 24 DC Appliances Available NAC Current =[A4] Step 3. Calculate Actual NAC Loading(Limited to Available NAC Current per Step 2.) NAC Type NAC Circuit# NAC Ala Circuit 1 + Circuit 2 + Standard Panel NACS,2 A maximum per NAC Circuit 3 + Circuit 4 + Circuit 5 + Optional Four Point NAC Module, 1.5 A maximum Special Application rating, Circuit 6 + 1 A maximum Regulated 24 DC rating,per NAC Circuit 7 + Circuit 8 + Total Actual NAC Load Alarm Current =[A5] Step 4.Calculate Total Supervisory Current Total Supervisory Current=Basic Panel Current[S1]+ZDNet Module Current[S2]=I Step 5.Calculate Total Alarm Current Total Alarm Current=Basic Panel Current[A2]+IDNet Module Current[A3]+Actual NAC Current[A5]=I TYCO,SIMPLEX,and the product names listed in this material are marks and or registered marks.Unauthorized use is strictly prohibited. 5®S I rn p 1 EX Tyco Fire Protection Products•Westminster,MA•01441-0001•USA S4009-0002-14 9/2015 7� www.simplex-fire.com C 2015 Tyco Fire Protection Products.All rights reserved All.specifications and other information shown were current as of document revision date and are subject to change without notice. ftSimpIEx TrueAlarm Smoke Detectors UL, ULC, CSFM Listed; FM Approved; TrueAlarm Photoelectric Smoke Detectors MEA (NYC) Acceptance* for Two-Wire and Four-Wire Bases Features Photoelectric smoke detector with on-board TrueAlarm sensitivity drift compensation: Functional chamber enclosure: • Louvered design enhances smoke capture by directing III t fi= I 1 II flow to chamber • Entrance areas are minimally visible when ceiling mounted • Operation is for ceiling or wall mounting 4098-9601 TrueAlarm Photoelectric Multi-function indicator LED indicates normal Detector Mounted in Base and alarm conditions Magnetically operated functional test: • Initiates alarm and verifies performance • Identifies general sensitivity status using detector LED Models available in two sensitivity settings: S•ecifications • 4098-9601, Standard Sensitivity,nominal 2.8%/ft 15 to 32 VDC from Fire Alarm obscuration* Voltage Control Panel IDC • 4098-9605,Special Application Sensitivity,nominal Standby Current 100µA @ 24 VDC 3.5%/ft obscuration Alarm Current,2-Wire Up to 86 mA maximum,exact Available options: Operation current is determined by alarm current limiting of connected IDC • Bases for 2-wire or 4-wire operation Alarm Current • Auxiliary alarm relay output ,4-Wire 24 mA typical©24 VDC Operation • Remote alarm indicating LED Refer to page 2 under Product Auxiliary Relay Ratings Selection Designed for EMI compatibility UL listed to Standard 268 Air Velocity Range 0-2000 ft/min(0-610 m/min) UL Listed Temp. Range 32°to 100°F(0°to 38°C) Operating Temp. Range 15°to 122° F(-9°to+50°C) Descri•tion Storage Temp. Range 0°to 140°F(-18°C to 60°C) 10%to 95%RH from 32°to 122° Simplex®TrueAlarm photoelectric detectors Humidity Range F provide many of the proven TrueAlarm analog sensing (0°to 50°C)non-condensing features for applications where detectors are connected to Color Frost White conventional 2-wire or 4-wire initiating device circuits 4-7/8"Dia.x 1-7/8"H, mounted in (IDCs).Each TrueAlarm detector has an on-board Dimensions base(124 mm x 48 mm); refer to microprocessor that evaluates its photoelectric light page 3 for detail scattering chamber activity and makes an intelligent decision based on light obscuration history as to whether an alarm condition is present. * ULC listed model is 4098-9601.This product has been approved by the California State TrueAlarm detectors are packaged in a patented Fire Marshal(CSFM)pursuant to Section 13144.1 of the Califomia Health and Safety housing that minimizes the visibility of the air intake Code.See CSFM Listing 7272-0026:219 for allowable values and/or conditions concerning material presented in this document.Accepted for use—City of New York Department of louvers from the normal viewing locations while Buildings—MEA35-93E.Additional listings may be applicable;contact your local Simplex ..high p...S,-...__,..-,....smoke,. .Milt. product cunnlier for the latest static Listings and approvals under Simpler Time.Recorder maintaining a luso�cri�uuaucc arirvnc capture ability r..,.,.,.._..................__.__._._.__._._....,-_--��- ---..__._.._,.-.......-_----- Bases are available for remote alarm LED indicator Co.are the property of Tyco Fire Protection Products. connections and auxiliary relay outputs. S4098-0015-7 1/2015 TrueAlarm Smoke Detector Features Application Reference Intelligent Data Evaluation. Conventional smoke Detector Locations. Locations should be determined detectors will typically drift toward being too sensitive only after careful consideration of the physical layout and due to the accumulation of dust and dirt.With TrueAlarm contents of the area to be protected.Refer to NFPA 72, analog detection,data from the photoelectric chamber is the National Fire Alarm Code.On smooth ceilings, monitored and analyzed at the detector to provide a smoke detector spacing of 30 ft(9.1 m)may be used as a continuously shifting reference point. guide.For detailed installation information,refer to 4098 Drift Compensation.The data evaluation and its Detectors, Sensors, and Bases Application Manual shifting reference point provide a software filtering (574-709). process that compensates for environmental factors(dust, Sensitivity Selection. The 4098-9601 standard dirt,etc.)and component aging,establishing an accurate filtering, sensitivity detector is recommended for most applications. reference for evaluating new activity.With this the resulting drift compensation provides a significant When a special application for a reduced sensitivity detector is required,the 4098-9605 should be considered. reduction in the probability of false or nuisance alarms caused by shifts in sensitivity-either up or down. Consult your local Simplex product supplier for assistance in determining the proper selection. Magnetic Test Information. Status information is available by performing the magnetic test and observing the detector LED pulses.The LED will normally go directly into alarm with the magnetic test. If there is an off-normal condition,the LED pulses first to indicate the condition and then goes into alarm. (See page 3.) Product Selection Smoke Detectors Model Nominal Sensitivity Description Compatibility —"'—>4098-9601 2.8%/ft(standard) o TrueAlarm Photoelectric Detector Compatible with bases:4098-9788, 4098-9605 3.5/o/ft(special application sensitivity, 4098-9682,and 4098-9683 not ULC listed) Compatible Bases Model Description Details* 4098-9788 2-Wire Base with connections for IDC and LED connections are screw terminals for in/out wiring, Remote Alarm LED Indicator 18 to 14 AWG 4-Wire Base with Auxiliary Alarm Relay Ratings,Single Form"C", For Suppressed Loads: Relay Contacts and connections for Power limited, 3 A @ 28 VDC; Non-power limited,3 A @ 120 VAC 4098-9682 Remote LED Alarm Indicator Wiring Connections(In/Out where required): NOTE: Requires external 24 VDC for Relay contacts and IDC wiring,color coded 18 AWG leads; operation LED wiring,screw terminals for 18 to 14 AWG 2-Wire Base with Auxiliary Alarm Relay Ratings, Dual Form"C",For Suppressed Loads: Relay&connections for Remote LED Power limited, 1 A @ 28 VDC; Non-power limited, 1/2 A @ 120 VAC 4098-9683 Indicator NOTE:Must be connected as the only Wiring Connections(In/Out where required): device on the IDC to ensure relay Relay contacts and IDC(-),color coded 18 AWG leads; operation. IDC(-F)and LED wiring,screw terminals for 18 to 14 AWG Detector Accessories Model Description Details* Required for mounting to surface mounted 4"(102 mm)square or 4"octagonal boxes,and to 4"square flush mounted boxes 4098-9832 Adapter Plate May be used when retrofitting existing bases Compatible with detector bases 4098-9788,-9682,&-9683 4098-9830 Remote LED Indicator Mounted on single gang stainless steel plate 2098-9739 Encapsulated Dimensions:2-1/2"x 1-1/2"x 1" Required for 4-wire circuits using • 24 VDC (64 mm x 38 mm x 25.4 mm) 4098-9682 base,one per circuit; select End-of-Line Relay Mounted on single gang mounting type as required;wiring is color 2098-9735 Plate Mounted stainless steel plate coded 18 AWG wire leads *Refer to pages 3 and 4 for dimensions and additional mounting details; 18 AWG=0.82 mm2; 14 AWG=2.08 mm2 2 S4098-0015-7 1/2015 Detector Status LED Indications LED Indication Status Pulses approximately every 4 seconds Normal • Steady On Alarm LED Response to Magnetic Test* LED Indication Followed By Status Action LED turns ON Alarm is initiated Normal,sensitivity is within None compensation range LED pulses quickly, More sensitive,out of normal 6 times in 3 seconds, Alarm is initiated then turns ON compensation range Cleaning or other service is required LED pulses slowly, Alarm is initiated Less sensitive, out of normal 4 times in 8 seconds, compensation range then turns ON Does not initiate Alarm Detector is malfunctioning Service is required Testing requires placing a magnet at the designated location on the detector cover for 4 seconds.Refer to Application Manual 574-709 for further test and maintenance information. Dimensions and Reference Information 1/4" (6.4Imm) 6-3/8"(162 mm) ►I 4098-9832 Adapter Plate 14 4-7/8"(124 mm) ►� I V Base height IMIMI" 1-7/8" 11/16" MIMI= (48 mm) (17 mm) MMM • 1 •IIIM \IN\� 4/!/ LED Status Indicator (with clear lens) 4098-9601 &-9605 Dimensions Mounted on Base ALARM 0 t3 Simplex 4098-9830 Remote LED Indicator(not to scale) 3 S4098-0015-7 1/2015 Mountin• Information (Electrical boxes are supplied by others.) Electrical Box Requirements: Without relay(base 4098-9788): 4"octagonal or 4"square, 1-1/2"deep Single gang, 2"deep With relay(bases 4098-9682 and 4098-9683): 4"octagonal, 1-1/2"deep, with 1-1/2"extension ring 4"square, 1-1/2"deep,with 1-1/2"extension ring Surface mount reference 4"(102 mm) ��4" (102 mm) square box octagonal box 1-1/2"(38 mm) Flush mount reference, mount even with final minimum box depth surface, or with up to 1/4"(6.4 mm) maximum recess 4098-9832 Adapter Plate, required for mounting to surface mounted boxes and to 4"square flush mount boxes 4098-9682 and 4098-9683 include a relay module that mounts in base electrical box Smoke Detector Bases III' 4098-9788, 9682, &-9683 4098-9601, -9605 Smoke Detector TYCO,SIMPLEX,and the product names listed in this material are marks and or registered marks.Unauthorized use is strictly prohibited.NPPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association(NFPA). Et5 i m p I Ex Tyco Fire Protection Products•Westminster,MA•01441-0001•USA S4098-0015 7 1/2015 www.simplex-fire.com Ca 2015 Tyco Fire Protection Products.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. 5SimpIEx TrueAlarm Smoke Detectors UL, ULC, CSFM Listed; FM Approved, Duct Detector Housings with TrueAlarm Photoelectric MEA (NYC) Acceptance* Detector for 2-Wire or 4-Wire Operation Features 0 © L. . Compact air duct detector housing with clear • _ _-_ cover to monitor for the presence of smoke** 7-4,_27:71:5".f2L.,.?-"E`Includes factory installed TrueAlarm � 1 ° __.__ photoelectric smoke detector and features: 1 °°`°° 1 • On-board TrueAlarm sensitivity drift compensation o °u= and • Multi-function tracking °fimct on status LED indicator © ` f 0 _ J� • Magnetic test that initiates an alarm and provides detailed diagnostic information i _. • Clear cover allowing visual inspection I i=';------ -4,---- . ■� • Test ports provide functional smoke testing access with cover in place • UL listed to Standard 268A Model availability: Duct Detector Housing, Front and Bottom View • 4098-9685,2-Wire standard operation A A A • 4098-9688,2-Wire with supervised control for a single remote relay(relay included) 7 _ • 4098-9686,4-Wire operation with supervised control a "°"'0 °"� for multiple remote relays(includes one remote relay) 'q '= °s'"" A A ® Mounts to rectangular ducts or round ducts 4098-9830 4098-9834 4098-9835 • Minimum size is 8"(203 mm)square or 18" Remote Alarm Indicators and Test Stations (457 mm)diameter Introduction Magnetically operated functional test: • Initiates alarm and displays dirt accumulation status Operation.Simplex®air duct smoke detector housings using the detector status LED provide a TrueAlarm smoke detector for monitoring air conditioning or ventilating ducts.Sampling tubes are • Assists with maintenance priorities by categorizing installed into the duct allowing air to be directed to the detector status and identifying dirty detectors smoke detector mounted in the housing.These duct detector Sampling tubes(ordered separately): housings with smoke detectors are compatible with Simplex fire alarm control panels that provide conventional two-wire • Available in multiple lengths to match duct size or four-wire initiating device circuits(IDCs). • Installed and serviced with housing in place Model Details Remote module options (ordered separately): Each supports a remote red alarm LED or a remote test • Red alarm LED(4098-9830) station with LED(s).Models with relay output provide relay • Test stations with LED(s)and keyswitch(refer to page coil wiring supervision that will transfer a trouble to the DC 2 for compatibility) if supervision is lost. • Relays for remote control applications 2-Wire Model 4098-9685 provides basic smoke detection for applications that do not require a remote relay.Power is • These products have been approved by the California State Fire Marshal(CSFM)pursuant from the IDC. to Section 13144.1 of the California Health and Safety Code.See CSFM Listing 3240-0026.241 for allowable values and/or conditions concerning material presented in this 2-Wire Model 4098-9688 provides a supervised relay document.Accepted for use-City of New York Department of Buildings-MEA35-93E. output for connection to a single 4098-9841 relay.This Additional listings may be applicable;contact your local Simplex product supplier for the g latest status.Listings and approvals under Simplex Time Recorder Co.are the property of model is powered from the IDC and requires connection as Tyco Fire Protection Products. the only device to ensure relay operation. ** Please note that smoke detection in air ducts is intended to provide 4-Wire Model 4098-9686 provides a supervised relay notification of the presence of smoke in the duct.It is not intended control output that can control up to 15,4098-9843 control to,and will not,replace smoke detection requirements for open relays.Relay supervision troubles are indicated by a yellow areas or other non-duct applications. LED on the interface board.(Resettable 24 VDC is required, see page 4.)Remote test station 4098-9835 is available for use with this model to provide a test keyswitch,a red LED alarm indicator and a green power-on LED. S4098-0029-9 11/2014 Duct Detector Selection Chart Duct Smoke Detector Housing with Photoelectric Detector* Model Description Compatibility 4098-9685 2-Wire Duct Detector,standard operation No relay(s) 2-Wire Duct Detector with supervised single remote relay output; includes one 4098-9841 relay; NOTE: Must be only device on Supplied relay is required Remote LED 4098-9688 IDC for proper relay operation; (When used with the Simplex for proper operation indicator and - 4004 or 4005 fire alarm control panel,connect to"high current" test stations IDCs only) per below 4-Wire Duct Detector with supervised multiple remote relay output; Up to 15 total 4098-9843 �>'4098-9686 requires resettable 24 VDC fire alarm power and relay end-of-line relays(additional relays are resistor 4081-9008; includes one 4098-9843 relay ordered separately) LED Indicator and Remote Test Stations (Select one if required) Each assembly is on a single gang stainless steel plate,wiring is 18 AWG(0.82 mm2)color coded wire leads Model Description Compatibility Mounting 4098-9830 Red LED alarm indicator 4098-9685 Test Station with keyswitch and red LED alarm indicator 4098-9688 Use single gang box, ------->4098-98344098-9686 3"H x 2"W x 2"D (turning switch to"TEST"initiates alarm for system testing) (76 mm x 51 mm 4098-9835 Test Station with keyswitch, red LED alarm indicator,and green 4098-9686 only x 51 mm) power-on LED Epoxy Encapsulated Remote Relays and End-of-Line Resistor (wiring is 18 AWG(0.82 mm2)color coded wire leads) Model Description Compatibility Mounting 4098-9841 Relay,dual Form C(1/2 A @ 120 VAC); Refer to pages 3 4098 9688 only, Locate relays within included with 4098-9688 and 4 for one maximum 3 ft(1 m)of device Relay,single Form C(7 A @ 120 VAC);one additional relay 4098-9686 only, being controlled, per 4098-9843 included with 4098-9686 information connect up to 15 NFPA 72 4081 9008 End-of-Line Resistor Harness; 10 kO, 1/2 W; (ref.733-894); 4098-9686 At last relay location required to supervise remote relay coil connection *Each duct housing includes an internally mounted model 4098-9601 TrueAlarm photoelectric detector and an exhaust tube.A correctly sized sampling tube(ordered per application)is required,refer to chart below. Sampling Tube Selection Chart, Ordered Separately Per Duct Width, Select One Overall Duct Width Tube Required Suggested Cut Length 12"(305 mm) 4098-9854 1/2"(12.7 mm)longer than duct width 13"to 23"(330 mm to 584 mm) 4098-9855 1/2"(12.7 mm)longer than duct width 24"to 46"(610 mm to 1168 mm) 4098-9856 3 in"(76 mm)longer than duct width 46"to 71"(1168 mm to 1803 mm) 4098-9857 3 in"(76 mm)longer than duct width 71"to 95"(1803 mm to 2413 mm) — >4098-9858 3 in"(76 mm)longer than duct width TrueAlarm Detector Status LED Indications LED Indication Status Pulses approximately every 4 seconds Normal Steady On Alarm Detector LED Response to Magnetic Test** LED Indication Followed By Status Action LED turns ON Alarm is initiated Normal,sensitivity is within None compensation range LED pulses quickly, More sensitive,out of normal 6 times in 3 seconds, Alarm is initiated then turns ON compensation range Cleaning or other service is required LED pulses slowly, Alarm is initiated Less sensitive,out of normal 4 times in 8 seconds, compensation range then turns ON Does not initiate Alarm Detector is malfunctioning Service is required "*Testing requires placing a magnet at the designated location on the duct housing cover for 4 seconds and referring to the response from the red LED status indicator on the detector.Refer to Installation Instructions 574-776 for further test and maintenance information. 2 S4098-0029-9 11/2014 Duct Detector Housin• Detail Reference NOTE: Refer to Installation Instructions 574-776 for additional detail and maintenance information. 11-3/8"(289 mm) Ma•netic test area Exhaust tube access hole Conduit b others A 0 i- 0 U v „g Metal plate with dual holes for 3/4'(19 mm)conduit,plug m<� Status LED . OLi . supplied for unused hole • 11 . il (16�3mm) 'll - :4116 Li ri I Front View 4098-9601 Smoke detector r Yellow LED,relay control trouble' Sampling tube mounted in base(supplied)/, am. indicator(4098-9686 only) J access holeO •`i y I I iJ a _ Side of duct Wiring terminals ©� J 0 o 4 (Stationary baffle(built-in) (Captive fastening screws(4) NOTE:Orientation shown is for reference Transparent cover (Gasketed detector area) only,refer to General Location Notes and End View illustration below for alternate i / mounting reference. /- — 3-3/8" HI r �� 111 (86 mm) s- r" I — 1 k Bottom view Duct wall • 13/16" 7 Remote Relays (21 mm) Exhaust tube NOTE: Mount in separate electrical box within (supplied) 3 ft(1 m)of device being controlled per NFPA 72 Test ports(2)provided Sampling tube,ordered 1-3/16" 30 mm) )211i'n) oas ets(supp ie )separately per duct width � and for aerosol injection 1-1/2" 13/16" 1/2" (38 mm) '} i (21 mm) (13 mm) <X/ Square duct Alternate location ) T I"^ 2-3/8"(60 mm)� `eference outline, Of appropriate) J T 4098-9843 4098-9841 ail ll lin.i (7 A @ 120 VAC) (1/2 A @ 120 VAC) J 18"Round duct outline (minimum diameter) I 'Sampling tube,keyed for proper hole alignment with holes facing o into airflow(template is provided for proper tube installation). (Housing is shown as position 2 per note 2 below.) , I-1 General Location Notes: — • • • • I 1.Testing performed under the auspices of the Fire Detection I 0 1 Institute(FDI)recommended when sampling tubes are not R Duct located vertically,that they be positioned horizontally in the housing End View with upper half of the duct to account for possible stratification. Ducts and Tubes 2.Three duct side mounting options are available as shown below. Mount housing at 90°to airflow for all orientations. t Arrows indicate allowed airflow directions. Exhaust tube 1-. 7 iI -8"Square duct outline ° —. /'U1( (minimum width) —1 / I —1 'fes �/ 1P[A O DO NOT MOUNT ON BOTTOM OF DUCT / \ 3 S4098-0029-9 11/2014 Duct Detector Location Reference Duct Detector Location Considerations: 1. Proper duct smoke detection location must ensure .—Exhaust Damper Detector OK adequate airflow within the duct housing. K.—Exhaust 2. Duct air velocity rating is 300 to 4000 ft/min(91 to Exhaust-4— \ Return Air 1220 m/min).Pressure differential between intake and exhaust tubes is required to be between 0.015 to 1.55 • Do not locate inches of water(0.381 to 39.37 mm). detector here Return air 3. Ensure accessibility for test and service. damper /// 4. Proper Locations:downstream side of filters to detect fires in the filters;in return ducts,ahead of mixing areas;upstream of air humidifier and cooling coil. 5. Other locations and orientations may be required for Fresh air— L u Supply Air proper duct smoke detection depending on duct access, � X � system design,and duct airflow testing.Contact your Do not locate Filter bank \Detector OK local Simplex product supplier for assistance. detector here Locations to Avoid: Additional Information. Refer to NFPA 90A,Standard 1. Where dampers closed for comfort control would for the Installation of Air Conditioning and Ventilating interfere with airflow. Systems;NFPA 72,the National Fire Alarm and Signaling 2. Next to outside air inlets(unless the intent is to monitor Code;and the NEMA Guide for Proper Use of Smoke smoke entry from that area). Detectors in Duct Applications,and Installation Instructions 3. In return air damper branch ducts and mixing areas 574-776. where airflow may be restricted. S•ecifications Air Velocity Range(linear ft/min) 300 to 4000 ft/min(91 to 1220 m/min) UL Listed Temperature Range 32°F to 100°F(0°C to 38°C) Operating Temperature Range 32°F to 122°F(0°C to 50°C) General Storage Temperature Range 0°F to 140° F(-18°C to 60°C) Mechanical& Environmental Humidity Range 10%to 95%RH, non-condensing Wiring Connections Terminal blocks, 18 to 12 AWG(0.82 mm2 to 3.31 mm2) Housing Color and Material Black ABS base with clear polycarbonate cover Sampling and Exhaust Tube Material Black CPVC,custom extrusion;sampling tubes are pre-drilled Two-Wire Operation, Models 4098-9685 and 4098-9688 Operating Voltage 18-32 VDC,from compatible IDC • 4098-9685(no relay) Standby Current 100µA @ 24 VDC Alarm Current 40 mA maximum @ 24 VDC Standby Current 2 mA @ 24 VDC(includes relay supervision current) 4098-9688 Alarm Current 40 mA maximum @ 24 VDC (with single relay control) Relay Control 4098-9841 relay only,one maximum NOTE:Only one 4098-9688 Relay Rating Dual Form C, 1 A @ 28 VDC, 1/2 A @ 120 VAC, Resistive per IDC 100 ft(30 m)maximum to relay coil, relay must be within 3 ft(1 m)of device Relay Location being controlled per NFPA 72 Four-Wire Operation,Model 4098-9686,Requires Resettable and Fused 24 VDC from Fire Alarm Power Supply Operating Voltage 18-32 VDC(24 VDC nominal) Standby Current 12 mA @ 24 VDC;32 mA @ 24 VDC with 4098-9835 Test Station Alarm Current(one relay activated) 45 mA @ 24 VDC;65 mA @ 24 VDC with 4098-9835 Test Station Add 15 mA @ 24 VDC for each additional remote 4098-9843 relay Supervised Remote Relay Control For use with relay 4098-9843,quantity of 15 maximum,distance of 500 ft(152 m)maximum, requires 4081-9008(ref.733-894), 10 kO, 1/2 W end-of-line resistor 4098-9843 Relay Output Ratings,Single Form C, use with Model 4098-9686 Only Coil Current 15 mA @ 24 VDC, up to 15 maximum per relay control output Relay Contacts, Resistive Ratings 7 A at 0.35 PF @ 28 VDC& 120 VAC;250 pA @ 5 VDC Location Distance 500 ft(152 m)maximum to relay coils; relays must be within 3 ft(1 m)of device being • controlled per NFPA 72 Remote Alarm LED LED Current 1.7 mA, no impact to alarm current • &Test Stations Distance 250 ft(76 m)maximum from duct housing Models 4098-9830,4098-9834, &4098-9835 TYCO,SIMPLEX and the product names listed in this material are marks and or registered marks.Unauthorized use is strictly prohibited.NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association(NFPA). aSi m p 1 Ex Tyco Fire Protection Products•Westminster,MA•01441-0001•USA S4098-0029-9 11/2014 www.simplex-fire.com C�2014 Tyco Fire Protection Products.All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice. Wheelock° ExcederTM Series COOPER Notification Finally, Design and Safety Meet... E ,. Ili , Ceiling Wall Description: The Wheelock®ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation** The Wheelock®ExcederTA4 Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single 0 Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use • of a tool and are located behind the appliance to prevent tampering. tpj Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 1vDc Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a Li 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while g 8 Candela Settings*** it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra / Universal Mounting Base *** secure installation, while the ceiling models provide a captivated Ceiling and Wall Mounts to 5 Backbox Types screw to prevent the screw from falling during installation. Environmentally Friendly Low Current Draw Compatibility and Requirements -Synchronize using the Wheelock®Sync Modules or panels with built-in Wheelock®Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range *Compared to competitive models *"Patented "Compared to previous models • NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". - •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). •Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 ._-___..,.:..1.°1-1-.•-...:.,..,,:: 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 ti 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &UL 464 at 24 VDC UL Max Current*at 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.1760.197 0.242 0.282 0.125 UL Max Current*at 95 dBA • 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.1630.186 0.230 0.272 0.122 UL Max Current*at 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157184,,L.7:„.2..,. 0.226 0.267 0.120 Horn Ratings per UL 464 x' Model I Regulated Voltage 99 dB 95 dB 90 dB r Range VDC HN 16-33.00.064 0.044 0.022 N- HNC 16-33.0 0.084 0.044 0.022 HN 8.0-17.5 0.047 0.026 0.017 . HNC 8.0-17.5 0.047 0.026 0.017 •, . UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units). For audibles the max current is usually at the I'' maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Strobe Sync w/SM, Mounting Model Candela DSM or 12/24 VDC* Options PS-6&PS-8 to d Horn Strobes o .n • :A HSR 15/1575/30/75/95/110/135/185 X X To UMB** • O HSW 15/1575/30/75/95/110/135/185 X X o UMB*" ' C.) HSRC 15/30/60/75/95/115/150/177 X X v UMB** TD HSWC 15/30/60/75/95/115/150/177 X X °5 UMB** 1 m o Strobes V 0 —� STR > 15/1575/30/75/95/110/135/185 X X i. UMB** Q STW V 15/1575/30/75/95/110/135/185 X X (") UMB** E STRC r 15/30/60/75/95/115/150/177 X X tg UMB** w STWC o 15/30/60/75/95/115/150/177 X X v UMB** iHorn to c • HNR UMB*" N HNW *lat UMB*" • HNRC o rn UMB** CZ ILI HNWC CO X X r UMB** *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base Model Legend �� _j ' HN = Horn Lim... , _k. ST =Strobe "` %.& * HS = Horn Strobe " C = Ceiling Mount ` ` 1. W =White R = Red , • Example 1: STRC=Strobe, Red, Ceiling Mount Example 2: HSR= Horn Strobe, Red, Wall Mount Example 3: HSW= Horn Strobe, White, Wall Mount Example. Example: HSWC Pliiiiii":: ...1 '4791 Ire ...;,.x ... _' ;.. lei r1 n ...____„_... , ,_ R 1-- *UMB Contact Cover Voltage test points for quick 8 candela settings Common base for wall and ceiling with 5 troubleshooting and easy spot mounting options checking (wall models only) NOTE:Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock° ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3)audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock®'s SM, DSM Sync Modules,Wheelock®Power Supplies or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock®synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC • , WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder- Spec Sheet 11/09 NJ Location FL Location VA Location ' 273 Branchport Ave. 7565 Commerce Ct. 4401 Wilson Boulevard,Suite 220 Long Branch, NJ 07740 Sarasota,FL 34243 Arlington,VA 22203 P:800-631-2148 P:941-487-2300 P:877-459-7726 F:732-222-8707 F:941-487-2389 F:703-294-6560 www.coopernotification.com Cooper Notification is WheeIOCK° MEDC SAFEPATH° wnvEs, COOPER Notification