Specifications (27) page
Project:22199 SOLSTICE CUSTOM HOMES 1111 Patrick J. Burke
Location: Fl 8R-TYP ISOLATED BR'G PAD(ROUND) Alan Mascord Design
Footing INK 2187 NW Reed St.Ste 100 or
[2015 International Building Code(2015 NDS)] _v--'i.44„,ik ..
Portland. OR 97210
Footing Size: 1.5 FT Round Diameter X 8.00 IN Deep
Section Footing Design Adequate StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
CAUTIONS I
I
*Footing has been designed without reinforcement
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Diameter: Dia.= 1.5 ft
Effective Depth to Top Layer of Steel: d= 6 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 3.5 in
Column Depth: n= 3.5 in
FOOTING CALCULATIONS 1 3.5 in-
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1400 psf
Effective Allowable Soil Bearing Pressure:Qe= 1400 psf
Required Footing Area: Areq= 1.77 sf
Area Provided: A= 1.77 sf
Baseplate Bearing: 1
Bearing Required: Bear= 3464 lb sin l
Allowable Bearing: Bear-A= 28634 lb i
Beam Shear Calculations(One Way Shear):
Beam Shear: Vu1 = 429 lb Sin
Allowable Beam Shear: Vc1 = 3509 lb
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 38 inAsn
Punching Shear: Vu2= 2235 lb
Controlling Allowable Punching Shear: vc2= 16678 lb
Bending Calculations: FOOTING LOADING
Factored Moment:
Mu= 6906 in-lb Live Load: PL= 0 lb Nominal Moment Strength: Mn= 13160 in-lb Dead Load: PD= 2474 lb
Total Load: PT= 2474 lb
Ultimate Factored Load: Pu= 3464 lb
Footing plus soil above footing weight: Wt= 114 lb
, Project:22199 SOLSTICE CUSTOM HOMES page
EtLocation: F20-TYP ISOLATED BR'G PAD Patrick J. Burke
Footing Alan Mascord Design
Et[2015 International Building Code(2015 NDS)] 2187 NW Reed St.Ste 100 or
Portland, OR 97210
Footing Size: 1.667 FT x 1.667 FT x 10.00 IN --`''�� ���'•~-
Section Footing Design Adequate
StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
CAUTIONS
*Footing has been designed without reinforcement
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 1.67 ft
Length: L= 1.67 ft
Depth: Depth= 10 in
Effective Depth to Top Layer of Steel: d= 8 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 3.5 in
Column Depth: n= 3.5 in E-3.5in-1
FOOTING CALCULATIONS —
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1375 psf
Effective Allowable Soil Bearing Pressure:Qe= 1375 psf
Required Footing Area: Areq = 2.78 sf
Area Provided: A= 2.78 sf 10 in
Baseplate Bearing:
Bearing Required: Bear= 5347 lb
Allowable Bearing: Bear-A= 28634 lb
Beam Shear Calculations(One Way Shear):
Beam Shear: ! 3 i
Vu1 = 535 lb —
Allowable Beam Shear: Vc1 = 5867 lb j —
Punching Shear Calculations(Two Way Shear): 1.6667 ft
Critical Perimeter: Bo= 46 in
Punching Shear: Vu2= 3579 lb FOOTING LOADING
Controlling Allowable Punching Shear: vc2= 26919 lb
Bending Calculations: Live Load: PL= 0 lb
FactoredDead Load: PD= 3819 lb
Moment:
Mu= 13367 in-lb Total Load: PT= 3819 lb
Nominal Moment Strength: Mn= 29334 in-lb
Ultimate Factored Load: Pu= 5347 lb
Footing plus soil above footing weight: VVt= 224 lb
Project:22199 SOLSTICE CUSTOM HOMES Patrick J.Burke
Location:F24-TYP ISOLATED BR'G PAD
Alan Mascord Design
Footing
2187 NW Reed St.Ste 100 page of
t �
[2015 International Building Code(2015 NDS)] _ jr+ Fkr�� Portland, OR 97210
Footing Size:2.0 FT x 2.0 FT x 12.00 IN
Section Footing Design Adequate StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
CAUTIONS
"Footing has been designed without reinforcement
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2 ft
Length: L= 2 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 10 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 3.5 in I-3.5in--I
Column Depth: n= 3.5 in
FOOTING CALCULATIONS
I
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1350 psf
Effective Allowable Soil Bearing Pressure:Qe= 1350 psf
Required Footing Area: Areq= 4 sf
12 in
Area Provided: A= 4.00 sf
i j
Baseplate Bearing:
Bearing Required: Bear= 7560 lb ; T
Allowable Bearing: Bear-A= 28634 lb i Sin
Beam Shear Calculations(One Way Shear): j
Beam Shear: Vu1 = 630 lb
Allowable Beam Shear: Vc1 = 8800 lb 2 rt I
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 54 in
Punching Shear Vu2= 5168 lb FOOTING LOADING
= 0 lb
Controlling Allowable Punching Shear: vc2= 39501 lb Live Load: PLPD= 5400 lb
Bending Calculations: Dead Load:
Factored Moment:
Mu= 22680 in-lb Total Load: PT= 5400 lbNominal Moment Strength: Mn= 55000 in-lb Ultimate Factored Load: Pu= 7560 lb
Footing plus soil above footing weight: Wt= 387 lb
Project:22199 SOLSTICE CUSTOM HOMES page
Patrick J. Burke
Location: F28-TYP ISOLATED BR'G PADAlan Mascord Design
Footing 2187 NW Reed St. Ste 100
[2015 International Building Code(2015 NDS)] °f
Footing Size:2.333 FT x 2.333 FT x 14.00 IN Portland, OR 97210
Section Footing Design Adequate StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
CAUTIONS
*Footing has been designed without reinforcement
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.33 ft
Length: L= 2.33 ft
Depth: Depth= 14 in
Effective Depth to Top Layer of Steel: d= 12 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 3.5 in
Column Depth: n= 3.5 in H3.5 in—
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1325 psf
Effective Allowable Soil Bearing Pressure:Qe= 1325 psf
Required Footing Area: Areq = 5.44 sf
Area Provided: A= 5.44 sf is in'
Baseplate Bearing:
Bearing Required: Bear= 10095 lb
Allowable Bearing: Bear-A= 28634 lb
Beam Shear Calculations(One Way Shear):
Beam Shear: 3 in
Vu1 = 720 Ib
Allowable Beam Shear: Vc1 = 12318 lb — —
Punching Shear Calculations(Two Way Shear): — Z333 ft
Critical Perimeter: Bo= 62 in
Punching Shear: Vu2= 7001 lb FOOTING LOADING
Controlling Allowable Punching Shear: vc2= 54424 lb Live Load: PL= 0 lb
Bending Calculations: Dead Load: PD= 7211 lb
Factored Moment: Mu= 35329 in-lb Total Load: PT= 7211 lb
Nominal Moment Strength: Mn= 92387 in-lb Ultimate Factored Load: Pu= 10095 lb
Footing plus soil above footing weight: Wt= 614 lb
page
Project:22199 SOLSTICE CUSTOM HOMES IIIII Patrick J. Burke
Location: F30-TYP ISOLATED BR'G PAD EN Alan Mascord Design
Footing 2187 NW Reed St. Ste 100 of
[2015 International Building Code(2015 NDS)] - > .._Portland,OR 97210
Footing Size:2.5 FT x 2.5 FT x 15.00 IN
Section Footing Design Adequate StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
CAUTIONS
Footing has been designed without reinforcement
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 2.5 ft
Length: L= 2.5 ft
Depth: Depth= 15 in
Effective Depth to Top Layer of Steel: d= 13 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 3.5 in H3.5in-,
Column Depth: n= 3.5 in
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1312 psf
Effective Allowable Soil Bearing Pressure:Qe= 1313 psf
Required Footing Area: Areq= 6.25 sf 15 in,
Area Provided: A= 6.25 sf
Baseplate Bearing:
Bearing Required: Bear= 11484 lb
Allowable Bearing: Bear-A= 28634 lb
Beam Shear Calculations(One Way Shear): 13 in
Beam Shear: Vu1 = 766 lb Allowable Beam Shear: Vc1 = 14300 lb 2.5 ft
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 66 in
Punching Shear: Vu2= 8010 lb FOOTING LOADING
Controlling Allowable Punching Shear: vc2= 62763 lb Live Load: PL= 0 lb
Bending Calculations: Dead Load: PD= 8203 lb
Factored Moment: Mu= 43066 in-lb Total Load: PT= 8203 lb
Nominal Moment Strength: Mn= 116188 in-Ib Ultimate Factored Load: Pu= 11484 lb
Footing plus soil above footing weight: Wt= 755 lb
Project;22199 SOLSTICE CUSTOM HOMES page
Ell Patrick J. Burke
Location: F36-TYP ISOLATED BR'G PAD Alan Mascord Design
Footing Ell 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] of
' .. Portland, OR 97210
Footing Size: 3.0 FT x 3.0 FT x 12.00 IN
Reinforcement:#4 Bars @ 9.00 IN. O.C. E/W/(4)min. StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: Fc= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE -3.5 in-
Width: W= 3 ft
Length: L= 3 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE 12 in'
Column Type: Wood
Column Width: m= 3.5 in I ? f' n n
9 i T
Column Depth: n= 3.5 in
� i f3in
FOOTING CALCULATIONS
I aft 1
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1350 psf E 3.51n
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf —
Required Footing Area: Areq= 9 sf
Area Provided: A= 9.00 sf
Baseplate Bearing:
Bearing Required: Bear= 17010 lb 121n
Allowable Bearing: Bear-A= 33841 lb
P-
Beam Shear Calculations(One Way Shear):
Beam Shear: Vu1 = 4607 lb 3 in
Allowable Beam Shear: Vc1 = 22275 lb
Punching Shear Calculations(Two Way Shear): 3 ft
Critical Perimeter: Bo= 47 in
Punching Shear: Vu2= 15198 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 87244 lb Live Load: PL= 0 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 131175 lb Dead Load: PD= 12150 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 58163 lb Total Load: PT= 12150 lb
Controlling Allowable Punching Shear: vc2= 58163 lb Ultimate Factored Load: Pu= 17010 lb
Bending Calculations: Footing plus soil above footing weight: Wt= 870 lb
Factored Moment: Mu= 76545 in-lb
Nominal Moment Strength: Mn= 336668 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.62 in
Steel Required Based on Moment: As(1)= 0.17 in2
Min.Code Req'd Reinf. Shrink./Temp. (ACI-10.5.4):As(2)= 0.78 in2
Controlling Reinforcing Steel: As-reqd= 0.78 in2
Selected Reinforcement: #4's @ 9.0 in. o.c. e/w(4)Min.
Reinforcement Area Provided: As= 0.79 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 15 in
Note:Plain concrete adequate for bending,
therefore adequate development length not required.
Project:22199 SOLSTICE CUSTOM HOMES Patrick J. Burke page
Location:F42-TYP ISOLATED BR'G PAD Alan Mascord Design
Footing gum 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] _, �,.� _,:.Portland.OR 97210
Footing Size: 3.5 FT x 3.5 FT x 12.00 IN
Reinforcement:#4 Bars @ 8.00 IN.O.C. E/W/(5)min. StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
Section Footing Design Adequate
FOOTING PROPERTIES . LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 3.5 ft
Length: L= 3.5 ft ,3.5 in-
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE I i
Column Type: Wood 1
12in
Column Width: m= 3.5 in
Column Depth: n= 3.5 in e'
3in
FOOTING CALCULATIONS — n
3.5 ft 1
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1350 psf i3.5 in;
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf I—
Required Footing Area: Areq= 12.25 sf
Area Provided: A= 12.25 sf
Baseplate Bearing:
Bearing Required: Bear= 23152 lb 12 in
Allowable Bearing: Bear-A= 33841 lb P ,; T
Beam Shear Calculations(One Way Shear): 3in
Beam Shear: Vu1 = 7028 lb _ 1 --
Allowable Beam Shear: Vc1 = 25988 lb 3.5 ft I
Punching Shear Calculations(Two Way Shear):
Critical Perimeter: Bo= 47 in
Punching Shear: Vu2= 21340 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 87244 lb Live Load: PL= 0 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 131175 lb Dead Load: PD= 16537 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 58163 lb Total Load: PT= 16537 lb
Controlling Allowable Punching Shear: vc2= 58163 lb Ultimate Factored Load: Pu= 23152 lb
Bending Calculations: Footing plus soil above footing weight: Wt= 1184 lb
Factored Moment: Mu= 121547 in-lb
Nominal Moment Strength: Mn= 419670 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.66 in
Steel Required Based on Moment: As(1)= 0.28 in2
Min.Code Req'd Reinf. Shrink./Temp. (ACI-10.5.4):As(2)= 0.91 in2
Controlling Reinforcing Steel: As-reqd= 0.91 in2
Selected Reinforcement: #4's @ 8.0 in. o.c.e/w(5)Min.
Reinforcement Area Provided: As= 0.98 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 18 in
Project:22199 SOLSTICE CUSTOM HOMES page
En Patrick J. Burke
Location:F54-TYP ISOLATED BR'G PAD Alan Mascord Design
Footing 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] Portland, OR 97210
of
_,11040./.014,(..,
Footing Size:4.5 FT x 4.5 FT x 12.00 IN
Reinforcement:#4 Bars @ 9.00 IN. O.C. E/N/(6)min. StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 60000 psi
Concrete Reinforcement Cover: c= 3 in
FOOTING SIZE
Width: W= 4.5 ft
Length: L= 4.5 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d= 8.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 5.5 in
Column Depth: n= 5.5 in
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1350 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 20.25 sf F 5.5 in-'
Area Provided: A= 20.25 sf 1
Baseplate Bearing:
Bearing Required: Bear= 38272 lb
Allowable Bearing: Bear-A= 83566 lb 12 in
Beam Shear Calculations(One Way Shear): _ ' n
Beam Shear: Vu1 = 13289 lb 3 in
Allowable Beam Shear: Vc1 = 33413 lb
Punching Shear Calculations(Two Way Shear): 4.5 ft
Critical Perimeter: Bo= 55 in
Punching Shear: Vu2= 35790 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-35): vc2-a= 102094 lb Live Load: PL= 0 lb
Allowable Punching Shear(ACI 11-36): vc2-b= 136125 lb Dead Load: PD= 27337 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 68063 lb Total Load: PT= 27337 lb
Controlling Allowable Punching Shear: vc2= 68063 lb Ultimate Factored Load: Pu= 38272 lb
Bending Calculations: Footing plus soil above footing weight: Wt= 1958 lb
Factored Moment: Mu= 258335 in-lb
Nominal Moment Strength: Mn= 505002 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a= 0.62 in
Steel Required Based on Moment: As(1)= 0.59 in2
Min. Code Req'd Reinf. Shrink./Temp.(ACI-10.5.4):As(2)= 1.17 in2
Controlling Reinforcing Steel: As-reqd= 1.17 in2
Selected Reinforcement: #4's @ 9.0 in. o.c.e/w(6)Min.
Reinforcement Area Provided: As= 1.18 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup= 24 in
page
Project:22199 SOLSTICE CUSTOM HOMES 111111 Patrick J. Burke
Location:FC1 -TYP MAX BR'G FTG COLUMN UP TO F36 Alan Mascord Design
Column sol 2187 NW Reed St.Ste 100 or
[2015 International Building Code(2015 NDS)] —„,...,140-01W....Portland,OR 97210
3.5INx3.5INx4.OFT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
Section Adequate By: 0.0%
VERTICAL REACTIONS ' LOADING DIAGRAM
Live Load: Vert-LL-Rxn= 0 lb
Dead Load: Vert-DL-Rxn= 14550 lb
Total Load: Vert-TL-Rxn= 14550 lb
COLUMN DATA B
Total Column Length: 4 ft
Unbraced Length(X-Axis)Lx: 4 ft
Unbraced Length(Y-Axis)Ly: 4 ft
Column End Condition-K(e): 1
Axial Load Duration Factor 1.00
COLUMN PROPERTIES
#2-Douglas-Fir-Larch
Base Values Adiusted
Compressive Stress: Fc= 1350 psi Fc'= 1188 psi
Cd=0.90 Cf=1.15 Cp=0.85
Bending Stress(X-X Axis): Fbx= 900 psi Fbx'= 0 psi
Cd=0.90 CF=1.50 a ft
Bending Stress(Y-Y Axis): Fby= 900 psi Fby'= 0 psi
Cd=0.90 CF=1.50
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Column Section(X-X Axis): dx= 3.5 in
Column Section(Y-Y Axis): dy= 3.5 in
Area: A= 12.25 in2
Section Modulus(X-X Axis): Sx= 7.15 in3
Section Modulus(Y-Y Axis): Sy= 7.15 in3
Slenderness Ratio: Lex/dx= 13.71 1
Ley/dy= 13.71 A
Column Calculations(Controlling Case Only): AXIAL LOADING
Controlling Load Case:Axial Dead Load Only(D) Live Load: PL= 0 lb
Actual Compressive Stress: Fc= 1188 psi Dead Load: PD= 14539 lb
Allowable Compressive Stress: Fc'= 1188 psi Column Self Weight: CSW= 11 lb
Eccentricity Moment(X-X Axis): Mx-ex= 0 ft-lb Total Axial Load: PT= 14550 lb
Eccentricity Moment(Y-Y Axis): My-ey= 0 ft-lb
Moment Due to Lateral Loads(X-X Axis): Mx= 0 ft-lb
Moment Due to Lateral Loads(Y-Y Axis): My= 0 ft-lb
Bending Stress Lateral Loads Only(X-X Axis):Fbx= 0 psi
Allowable Bending Stress(X-X Axis): Fbx'= 0 psi
Bending Stress Lateral Loads Only(Y-Y Axis):Fby= 0 psi
Allowable Bending Stress(Y-Y Axis): Fby'= 0 psi
Combined Stress Factor: CSF= 1
III
Project:22199 SOLSTICE CUSTOM HOMES Page
Location:FC2-TYP MAX BR'G FTG COLUMN @ F42 Patrick J. Burke
Column Alan Mascord Design
111111 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] Portland,OR 97210
5.5 INx5.5INx4.0FT .0°
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By: 0.0% StruCalc Version 10.0.1.6 11/8/2018 3:47:33 PM
VERTICAL REACTIONS LOADING DIAGRAM
Live Load: Vert-LL-Rxn= 0 lb
Dead Load: Vert-DL-Rxn= 18547 lb
Total Load: Vert-TL-Rxn= 18547 lb
COLUMN DATA
Total Column Length: 4 ft B
Unbraced Length(X-Axis)Lx: 4 ft
Unbraced Length(Y-Axis)Ly: 4 ft
Column End Condition-K(e): 1
Axial Load Duration Factor 1.00
COLUMN PROPERTIES
#2-Douglas-Fir-Larch
Base Values Adjusted
Compressive Stress: Fc= 700 psi Fc'= 613 psi
Cd=0.90 Cp=0.97
Bending Stress(X-X Axis): Fbx= 750 psi Fbx'= 675 psi
Cd=O.90 CF=1.00 4 ft
Bending Stress(Y-Y Axis): Fby= 750 psi Fby'= 675 psi
Cd=0.90 CF=1.00
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
Column Section(X-X Axis): dx= 5.5 in •'
Column Section(Y-Y Axis): dy= 5.5 in
Area: A= 30.25 in2
Section Modulus(X-X Axis): Sx= 27.73 in3
Section Modulus(Y-Y Axis): Sy= 27.73 in3
Slenderness Ratio: Lex/dx= 8.73
Ley/dy= 8.73
A
Column Calculations(Controlling Case Only):
Controlling Load Case:Axial Dead Load Only(D) AXIAL LOADING
Actual Compressive Stress: Fc= 613 psi Live Load: PL= 0 lb
Allowable Compressive Stress: Fc'= 613 psi Dead Load: PD= 18521 lb
Eccentricity Moment(X-X Axis): Mx-ex= 0 ft-lb Column Self Weight: CSW= 26 lb
Eccentricity Moment(Y-Y Axis): My-ey= 0 ft-lb Total Axial Load: PT= 18547 lb
Moment Due to Lateral Loads(X-X Axis): Mx= 0 ft-lb
Moment Due to Lateral Loads(Y-Y Axis): My= 0 ft-lb
Bending Stress Lateral Loads Only(X-X Axis):Fbx= 0 psi
Allowable Bending Stress(X-X Axis): Fbx'= 675 psi
Bending Stress Lateral Loads Only(Y-Y Axis):Fby= 0 psi
Allowable Bending Stress(Y-Y Axis): Fby'= 675 psi
Combined Stress Factor: CSF= 1
Project:22199 SOLSTICE CUSTOM HOMES Patrick J. Burke
Location:FC4-TYP MAX BR'G FTG COLUMN @ F54&F60 Alan MaNW Reedscord DesSt.ipage
inE 2187gn
Column Ste 100 of
[2015 International Building Code(2015 NDS)] Portland.OR 97210
5.25 IN x 5.25 IN x 4 FT
1.8E Parallam Column-iLevel Trus Joist StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:0.0%
VERTICAL REACTIONS LOADING DIAGRAM
Live Load: Vert-LL-Rxn= 0 lb
Dead Load: Vert-DL-Rxn= 60094 lb
Total Load: Vert-TL-Rxn= 60094 lb
COLUMN DATA B
Total Column Length: 4 ft
Unbraced Length(X-Axis)Lx: 4 ft _
Unbraced Length(Y-Axis)Ly: 4 ft
Column End Condition-K(e): 1
Axial Load Duration Factor 1.00
COLUMN PROPERTIES
1.8E Parallam Column-iLevel Trus Joist
Base Values Adjusted
Compressive Stress: Fc= 2500 psi Fc'= 2180 psi
Cd=0.90 Cp=0.97
Bending Stress(X-X Axis): Fbx= 2400 psi Fbx'= 2368 psi Oft
Cd=0.90 CF=1.10
Bending Stress(Y-Y Axis): Fby=2400 psi Fby'= 2368 psi
Cd=0.90 CF=1.10
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi
Column Section(X-X Axis): dx= 5.25 in
Column Section(Y-Y Axis): dy= 5.25 in
Area: A= 27.56 in2
Section Modulus(X-X Axis): Sx= 24.12 in3
Section Modulus(Y-Y Axis): Sy= 24.12 in3
Slenderness Ratio: Lex/dx= 9.14 A
Ley/dy= 9.14 A
Column Calculations(Controlling Case Only): AXIAL LOADING
Controlling Load Case:Axial Dead Load Only(D) Live Load: PL= 0 lb
Actual Compressive Stress: Fc= 2180 psi Dead Load: PD= 60060 lb
Allowable Compressive Stress: Fc'= 2180 psi Column Self Weight: CSW= 34 lb
Eccentricity Moment(X-X Axis): Mx-ex= 0 ftIb Total Axial Load: PT= 60094 lb
Eccentricity Moment(Y-Y Axis): My-ey= 0 ft-lb
Moment Due to Lateral Loads(X-X Axis): Mx= 0 ft-lb
Moment Due to Lateral Loads(Y-Y Axis): My= 0 ft-lb
Bending Stress Lateral Loads Only(X-X Axis):Fbx= 0 psi
Allowable Bending Stress(X-X Axis): Fbx'= 2368 psi
Bending Stress Lateral Loads Only(Y-Y Axis):Fby= 0 psi
Allowable Bending Stress(Y-Y Axis): Fby'= 2368 psi
Combined Stress Factor: CSF= 1
Project:22199 SOLSTICE CUSTOM HOMES page
IRELocation: M1 -SIDE FRONT ENTRY BM Patrick J. Burke
Multi-Loaded Multi-Span Beam iims Alan Mascord Design
2187 NW Reed St.Ste 100 or
[2015 International Building Code(2015 NDS)] Portland,OR 97210
3.5 INx7.25INx5.OFT --_4?
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By:65.2% StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/2286
Dead Load 0.02 in
Total Load 0.04 IN L/1359
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 777 lb 661 lb
Dead Load 531 lb 454 lb
Total Load 1308 lb 1115 lb
Bearing Length 0.60 in 0.51 in
BEAM DATA Center rRt TR2
Span Length 5 ft
Unbraced Length-Top 0 ft A- 5 ft
Unbraced Length-Bottom 5 ft --B
—
Unbraced
Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 6 plf
Bending Stress: Fb= 900 psi Fb'= 1170 psi Total Uniform Load 6 plf
Cd=1.00 CF=1.30
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
•
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Live Load 595 lb
Min. Mod.of Elasticity: E—min= 580 ksi E_min'= 580 ksi Dead Load 397 lb
Comp. to Grain: Fc---= 625 psi Fc-1'= 625 psi Location 1.5 ft
TRAPEZOIDAL LOADS-CENTER SPAN
Controlling Moment: 1809 ft-lb Load Number One Two
1.75 Ft from left support of span 2(Center Span) Left Live Load 76 pif 203 plf
Created by combining all dead loads and live loads on span(s)2 Left Dead Load 50 plf 135 plf
Controlling Shear: 1308 lb Right Live Load 101 plf 203 plf
At left support of span 2(Center Span) Right Dead Load 67 plf 135 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft 1.5 ft
Load End 1.5ft 5ft
Comparisons with required sections: Req'd Provided Load Length 1.5 ft 3.5 ft
Section Modulus: 18.56 in3 30.66 in3
Area(Shear): 10.9 in2 25.38 in2
Moment of Inertia(deflection): 19.63 in4 111.15 in4
Moment: 1809 ft-lb 2989 ft-lb
Shear: 1308 lb 3045 lb
Project:22199 SOLSTICE CUSTOM HOMES Patrick J.Burke
Location:M2-FRONT ENTRY BM Alan Mascord Desipage gn
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] �41,14rrigk,Z:�
Portland,OR 97210
3.5 IN x 5.5 IN x 8.5 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By:27.2%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.15 IN L/668
Dead Load 0.11 in
Total Load 0.26 IN L/392
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A
Live Load 429 lb 429 lb
Dead Load 302 lb 302 lb
Total Load 731 lb 731 lb
Bearing Length 0.33 in 0.33 in
BEAM DATA Center
Span Length 8.5 ft s.5 ft B
Unbraced Length-Top 0 ft A
Unbraced Length-Bottom 8.5 ft
Live Load Duration Factor 1.15
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 101 plf
#2-Douglas-Fir-Larch Uniform Dead Load 67 plf
Base Values Adjusted Beam Self Weight 4 plf
Bending Stress: Fb= 900 psi Fb'= 1346 psi Total Uniform Load 172 plf
Cd=1.15 CF=1.30
Shear Stress: Fv= 180 psi Fv'= 207 psi
Cd=1.15
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp.1-to Grain: Fc--t = 625 psi Fc--I-'= 625 psi
Controlling Moment: 1555 ft-lb
4.25 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -732 lb
8.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 13.87 in3 17.65 in3
Area(Shear): 5.3 in2 19.25 in2
Moment of Inertia(deflection): 29.73 in4 48.53 in4
Moment: 1555 ft-lb 1979 ft-lb
Shear -732 lb 2657 lb
Project:22199 SOLSTICE CUSTOM HOMES �� page
Location: M3-16/0 O.H. GARAGE DR HDR Patrick J. Burke
Multi-Loaded Multi-Span Beam Alan MDesign
NEM 2187 NWW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] Portland, OR 97210
5.5 IN x 11.5 IN x 16.0 FT
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By:23.5% StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.20 IN L/937
Dead Load 0.16 in
Total Load 0.36 IN L/528
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 1008 lb 1008 lb
Dead Load 782 lb 782 lb
Total Load 1790 lb 1790 lb
Bearing Length 0.52 in 0.52 in
BEAM DATA Center
Span Length 16 ft
Unbraced Length-Top 0 ft A is ft
Unbraced Length-Bottom 16 ft B
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 126 plf
#2-Douglas-Fir-Larch Uniform Dead Load 84 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 224 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
Min.Mod.of Elasticity: E_min= 470 ksi E_min'= 470 ksi
Comp.J-to Grain: Fc- = 625 psi Fc--i-'= 625 psi
Controlling Moment: 7159 ft-lb
8.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 1790 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 98.18 in3 121.23 in3
Area(Shear): 15.79 in2 63.25 in2
Moment of Inertia(deflection): 317.14 in4 697.07 in4
Moment: 7159 ft-lb 8840 ft-lb
Shear: 1790 lb 7168 lb
Project:22199 SOLSTICE CUSTOM HOMES 1111 Patrick J. Burke
Location:M4-MAIN GARAGE BM. Alan Mascord Design page
II
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] _,- Sy :-Portland.OR 97210
5.125 IN x 21.0 IN x 21.5 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By:2.0%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.56 IN L/463
Dead Load 0.38 in
Total Load 0.93 IN L/277
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240 1
2
REACTIONS A B
Live Load 8762 lb 7830 lb
Dead Load 5906 lb 5289 lb
Total Load 14668 lb 13119 lb
Bearing Length 4.40 in 3.94 in
BEAM DATA Center ,
Span Length 21.5 ft _ 2isrt B
Unbraced Length-Top 0 ft .111M11.1.111111111A--
Unbraced Length-Bottom 21.5 ft
Live Load Duration Factor 1.15
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.38 Uniform Live Load 285 plf
Notch Depth 0.00 Uniform Dead Load 172 plf
MATERIAL PROPERTIES Beam Self Weight 23 plf
24F-V4-Visually Graded Western Species Total Uniform Load 480 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One* Two*
Fb_cmpr= 1850 psi Fb'= 2604 psi Live Load 1477 lb 1187 Ib
Cd=1.15 Cv=0.94 Dead Load 993 lb 800 lb
Shear Stress: Fv= 265 psi Fv'= 305 psi Location 14.5 ft 17.5 ft
Cd=1.15 *Load obtained from Load Tracker. See Summary Report for details.
Modulus of Elasticity: E= 1800 ksi E= 1800 ksi
Min.Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.-I-to Grain: Fc--I-= 650 psi Fc--i-'= 650 psi Load Number One Two
Left Live Load 517 plf 76 plf
Controlling Moment: 80145 ft-lb Left Dead Load 345 plf 50 plf
10.97 Ft from left support of span 2(Center Span) Right Live Load 517 plf 76 plfight Dead Load 345 plf 50 Of
Created by combining all dead loads and live loads on span(s)2 Right
Start 5 ft 1 50 ft
Controlling Shear: 14669 lb
At left support of span 2(Center Span) Load End 14.5 ft 21.5 ft
Created by combining all dead loads and live loads on span(s)2
Load Length 14.5 ft 4 ft
Comparisons with required sections: Reo'd Provided
Section Modulus: 369.38 in3 376.69 in3
Area(Shear): 72.2 in2 107.63 in2
Moment of Inertia(deflection): 3432.2 in4 3955.22 in4
Moment: 80145 ft-lb 81730 ft-lb
Shear 14669 lb 21866 lb
Project:22199 SOLSTICE CUSTOM HOMES page
Location:M5-BM BTWN GARAGE/STORAGE Patrick J. Burke
Multi-Loaded Multi-Span Beam Alan Mascord Design
111111 2187 NW Reed St. Ste 100 of
[2015 International Building Code(2015 NDS)] Portland,OR 97210
5.5 IN x 11.5IN x 11.5 FT
-- + � -
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By: 37.6% StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.13 IN L/1059
Dead Load 0.04 in
Total Load 0.17 IN L/818
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A_
Live Load 1725 lb 1725 lb
Dead Load 510 lb 510 lb
Total Load 2235 lb 2235 lb
Bearing Length 0.65 in 0.65 in
BEAM DATA Center
Span Length 11.5 ft _.
Unbraced Length-Top 0 ft A 11.5 ft
Unbraced Length-Bottom 11.5 ft B_
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 300 plf
#2-Douglas-Fir-Larch Uniform Dead Load 75 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 389 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
Min. Mod.of Elasticity: E_min= 470 ksi Emin'= 470 ksi
Comp.J-to Grain: Fc--t-= 625 psi Fc-1'= 625 psi
Controlling Moment: 6426 ft-lb
5.75 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2235 lb
12.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 88.13 in3 121.23 in3
Area(Shear): 19.72 in2 63.25 in2
Moment of Inertia(deflection): 236.87 in4 697.07 in4
Moment: 6426 ft-lb 8840 ft-lb
Shear: -2235 lb 7168 lb
Project:22199 SOLSTICE CUSTOM HOMES no Patrick J. Burke
Location:M6-MULT JSTS BY STAIRS Alan Mascord Design page
Multi-Loaded Multi-Span Beam no 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] Portland,OR 97210
(2)1.51Nx11.25INx11.17FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By:430.9%
Controlling Factor: Moment
ICAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/5450
Dead Load 0.01 in
Total Load 0.04 IN L/3803
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 223 lb 223 lb
Dead Load 97 lb 97 lb
Total Load 320 lb 320 lb
Bearing Length 0.17 in 0.17 in
BEAM DATA Center
Span Length 11.17 ft 11.17 ft B
Unbraced Length-Top 0 ft A
Unbraced Length-Bottom 11.17 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 40 plf
#2-Douglas-Fir-Larch Uniform Dead Load 10 plf
Base Values Adiusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 900 psi Total Uniform Load 57 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp.-L to Grain: Fc-1= 625 psi Fc-1'= 625 psi
Controlling Moment: 894 ft-lb
5.59 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -320 lb
11.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 11.92 in3 63.28 in3
Area(Shear): 2.67 in2 33.75 in2
Moment of Inertia(deflection): 23.51 in4 355.96 in4
Moment: 894 ft-lb 4746 ft-lb
Shear -320 lb 4050 lb
Project:22199 SOLSTICE CUSTOM HOMES page
111111 Patrick J. Burke
Location:M7-BM ACROSS FOYER Alan Mascord Design
Multi-Loaded Multi-Span Beam 116
2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] /___41440,..01.0„(... Portland,OR 972103.5 IN x 11,25 IN x 8.0 FT
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By: 13.6% StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.07 IN L/1463
Dead Load 0.03 in
Total Load 0.09 IN L/1052
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A B
Live Load 2024 lb 1479 lb
Dead Load 758 lb 632 lb
Total Load 2782 lb 2111 lb
Bearing Length 1.27 in 0.97 in
BEAM DATA Center
Span Length 8 ft
Unbraced Length-Top 0 ft A aft B_.
Unbraced Length-Bottom 8 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 210 plf
#2-Douglas-Fir-Larch Uniform Dead Load 103 plf
Base Values Adjusted Beam Self Weight 9 plf
Bending Stress: Fb= 900 psi Fb'= 990 psi Total Uniform Load 322 plf
Cd=1.00 CF=9.10
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One *
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 223 lb
Min. Mod.of Elasticity: E_ _
min= 580 ksi Emin'= 580 ksi Dead Load 97 lb
Comp.1-to Grain: Fc-1-= 625 psi Fc--L'= 625 psi Location 5 ft
*Load obtained from Load Tracker.See Summary Report for details.
Controlling Moment: 5360 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
3.84 Ft from left support of span 2(Center Span) Load Number One
Created by combining all dead loads and live loads on span(s)2 Left Live Load 320 plf
Controlling Shear: 2781 lb Left Dead Load 80 plf
At left support of span 2(Center Span) Right Live Load 320 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 80 plf
Load Start 0 ft
Comparisons with required sections: Reo d Provided Load End 5 ft
Section Modulus: 64.97 in3 73.83 in3 Load Length 5 ft
Area(Shear): 23.18 in2 39.38 in2
Moment of Inertia(deflection): 102.16 in4 415.28 in4
Moment: 5360 ft-lb 6091 ft-lb
Shear: 2781 lb 4725 lb
Project:22199 SOLSTICE CUSTOM HOMES Patrick J. Burke page •
Location:M8 FLUSH BM @REAR POCH Alan Mascord Design
Multi-Loaded Multi-Span Beam sim 2187 NW Reed St. Ste 100 of
[2015 International Building Code(2015 NDS)] ____4140,19,a:.,_Portland,OR 97210
5.5 INx11.51Nx12.OFT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By: 1.3%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.12 IN L/1251
Dead Load 0.13 in
Total Load 0.24 IN L/588
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A
Live Load 1293 lb 1293 lb
Dead Load 1480 lb 1480 lb
Total Load 2773 lb 2773 lb
Bearing Length 0.81 in 0.81 in
BEAM DATA Center
Span Length 12 ft �2 n
Unbraced Length-Top 0 ft
Unbraced Length-Bottom 12 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 202 plf
#2-Douglas-Fir-Larch Uniform Dead Load 224 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 440 plf
Cd=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 162 lb
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi Dead Load 108 lb
Comp.1 to Grain: Fc- = 625 psi Fc--- = 625 psi Location 6 ft
Controlling Moment: 8725 ft-lb
6.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2773 lb
At right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 119.65 in3 121.23 in3
Area(Shear): 24.47 in2 63.25 in2
Moment of Inertia(deflection): 284.5 in4 697.07 in4
Moment: 8725 ft-lb 8840 ft-lb
Shear: -2773 lb 7168 lb
Project:22199 SOLSTICE CUSTOM HOMES page
1111 Patrick J. Burke
Location:M9-FLUSH BM 0/KIT.CABINETS Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] , or
Portland, OR 97210
5.51Nx11.51Nx10.0FT
#2-DouglasFir Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By:25.4%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.11 IN L/1099
Dead Load 0.03 in
Total Load 0.14 IN L/857
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A_
Live Load 2200 lb 2200 lb
Dead Load 619 lb 619 lb
Total Load 2819 lb 2819 lb
Bearing Length 0.82 in 0.82 in
BEAM DATA Center
Span Length 10 ft
:°r . _., MZ , .
Unbraced Length-Top 0 ft A ion
Unbraced Length-Bottom 10 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 440 plf
#2-Douglas-Fir-Larch Uniform Dead Load 110 plf
Base Values Adjusted Beam Self Weight 14 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 564 plf
Cd=1.00 CF=1.00
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi
Comp.-L to Grain: Fc-1= 625 psi Fc-L'= 625 psi
Controlling Moment: 7046 ft-lb
5.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2819 lb
At right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 96.64 in3 121.23 in3
Area(Shear): 24.87 in2 63.25 in2
Moment of Inertia(deflection): 228.42 in4 697.07 in4
Moment: 7046 ft-lb 8840 ft-lb
Shear: -2819 lb 7168 lb
page
Project:22199 SOLSTICE CUSTOM HOMES 11111 Patrick J.Burke •
Location:M10-SMALL BM BTWN GREAT RM/DINING Alan Mascord Design
Multi-Loaded Multi-Span Beam int 2187 NW Reed St.Ste 100 or
[2015 International Building Code(2015 NDS)] r � ¢, ,_Portland,OR 97210
3.125 IN x 9.0 IN x 7.5 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:32.4%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.15 IN L/600
Dead Load 0.04 in
Total Load 0.19 IN L/477
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A
Live Load 2700 lb 2700 lb
Dead Load 698 lb 698 lb
Total Load 3398 lb 3398 lb
Bearing Length 1.67 in 1.67 in
BEAM DATA Center
Span Length 7.5 ft
Unbraced Length-Top 0 ft
A
Unbraced Length-Bottom 7.5 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.04 Uniform Live Load 720 plf
Notch Depth 0.00 Uniform Dead Load 180 plf
MATERIAL PROPERTIES Beam Self Weight 6 plf
24F-V4-Visually Graded Western Species Total Uniform Load 906 plf
Base Values Adjusted
Bending Stress: Fb= 2400 psi Controlled by:
Fb_cmpr= 1850 psi Fb'= 2400 psi
Cd=1.00
Shear Stress: Fv= 265 psi Fv'= 265 psi
Cd=1.00
Modulus of Elasticity: E= 1800 ksi E= 1800 ksi
Min.Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi
Comp.-I-to Grain: Fc- I = 650 psi Fc--L'= 650 psi
Controlling Moment: 6371 ft-lb
3.75 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -3398 lb
8.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Red Provided
Section Modulus: 31.85 in3 42.19 in3
Area(Shear): 19.23 in2 28.13 in2
Moment of Inertia(deflection): 113.89 in4 189.84 in4
Moment: 6371 ft-lb 8438 ft-lb
Shear: -3398 lb 4969 lb
page
Project:22199 SOLSTICE CUSTOM HOMES nun
Patrick J. Burke
Location: M11-BM BTWN GREAT RM/DINING No Alan Mascord Design
Multi-Loaded Multi-Span Beam NM 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] of
5.25 INx11.25INx19.OFT
Portland, OR 97210
2.0E Parallam-iLevel Trus Joist
Section Adequate By: 3.5% StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Controlling Factor: Deflection
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.61 IN L/373
Dead Load 0.20 in
Total Load 0.81 IN L/281
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 1498 lb 2209 lb
Dead Load 556 lb 740 lb
Total Load 2054 lb 2949 lb
Bearing Length 0.52 in 0.75 in
BEAM DATA Center
Span Length 19 ftanwilmir
Unbraced Length-Top 0 ft A 19 ft
13-
Unbraced Length-Bottom 19 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 53 plf
2.0E Parallam-iLevel Trus Joist Uniform Dead Load 13 plf
Base Values Adjusted Beam Self Weight 18 plf
Bending Stress: Fb= 2900 psi Fb'= 2921 psi Total Uniform Load 84 plf
Cd=1.00 CF=1.01
Shear Stress: Fv= 290 psi Fv'= 290 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 2000 ksi E'= 2000 ksi Live Load 2700 lb
Comp. L to Grain: Fc- L= 750 psi Fe- = 750 psi Dead Load 698 Ib
Location 12 ft
Controlling Moment: 18539 ft-lb *Load obtained from Load Tracker. See Summary Report for details.
11.97 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2948 lb
At right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 76.16 in3 110.74 in3
Area(Shear): 15.25 in2 59.06 in2
Moment of Inertia(deflection): 601.71 in4 622.92 in4
Moment: 18539 ft-lb 26955 ft-lb
Shear: -2948 lb 11419 lb
page
Project:22199 SOLSTICE CUSTOM HOMES 11111 Patrick J. Burke
Location:M12-BM OVER MID GREAT RM. Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St. Ste 100 of
[2015 International Building Code(2015 NDS)] f Portland.OR 97210
5.125 IN x 13.5IN x 19.0 FT
24F-V4-Visually Graded Western Species-Dry Use StruCaic Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:32.0%
Controlling Factor: Deflection
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.33 IN L/683
Dead Load 0.39 in
Total Load 0.72 IN L/317
Live Load Deflection Criteria: 0360 Total Load Deflection Criteria:L/240
REACTIONS A B 1
Live Load 2080 lb 2000 lb 2
Dead Load 2387 lb 2330 lb
Total Load 4467 lb 4330 lb
Bearing Length 1.34 in 1.30 in TRI TR3
TR2
BEAM DATA Center , w. -40
Span Length 19 ft 19 n
Unbraced Length-Top 0 ft A
Unbraced Length-Bottom 19 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 1 UNIFORM LOADS Center
Camber Required 0.39 Uniform Live Load 0 plf
Notch Depth 0.00 Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 15 plf
24F-V4-Visually Graded Western Species Total Uniform Load 15 plf
Base Values Adiusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by: Load Number One" Two" Three
Fb_cmpr= 1850 psi Fb'= 2396 psi Live Load 355 lb 355 lb 162 lb
Cd=1.00 Cv=1.00 Dead Load 244 lb 244 lb 108 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Location 5.5 ft 10.5 ft 5.5 ft
Cd=1.00 *Load obtained from Load Tracker. See Summary Report for details.
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Min. Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi
Comp.-L to Grain: Fc--L= 650 psi Fc-1'= 650 psi Load Number One Two Three
Left Live Load 202 plf 76 plf 202 plf
Controlling Moment: 20872 ft-lb Left Dead Load 224 plf 140 plf 224 plf
10.45 Ft from left support of span 2(Center Span) Right Live Load 202 plf 76 plf 202 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 224 plf 140 plf 224 plf
Controlling Shear: 4467 lb Load Start 0 ft 5.5 ft 10.5 ft
At left support of span 2(Center Span) Load End 5.5 ft 10.5 ft 19 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 5.5 ft 5 ft 8.5 ft
Comparisons with required sections: Read Provided
Section Modulus: 104.55 in3 155.67 in3
Area(Shear): 25.28 in2 69.19 in2
Moment of Inertia(deflection): 796.11 in4 1050.79 in4
Moment: 20872 ft-lb 31079 ft-lb
Shear: 4467 lb 12223 lb
Project:22199 SOLSTICE CUSTOM HOMES page
11111 Patrick J.Burke
Location:M13-GREAT RM WINDOW HDR Alan Mascord Design
Multi-Loaded Multi-Span Beam 111111 2187 NW Reed St. Ste 100
of
[2015 International Building Code(2015 NDS)] Portland, OR 97210
3.51N x 11.25 IN x 3.0 FT � ''
#2 Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By: 5.3%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/6322
Dead Load 0.01 in
Total Load 0.01 IN L/3128
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A_
Live Load 1887 lb 2367 lb
Dead Load 1978 lb 2098 lb
Total Load 3865 lb 4465 lb
Bearing Length 1.77 in 2.04 in
TR1
BEAM DATA Center
Span Length 3 ft
Unbraced Length-Top 0 ft A aft -Q
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 9 plf
Bending Stress: Fb= 900 psi Fb'= 990 psi Total Uniform Load 9 plf
Cd=1.00 CF=1.10
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One" Two*
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 1293 lb 2000 lb
Comp.-I-to Grain: Fc- = 625 psi Fc--1-'= 625 psi Dead Load 1480 lb 2330 lb
Location 1.5 ft 1.5 ft
Controlling Moment: 5787 ft-lb *Load obtained from Load Tracker. See Summary Report for details.
1.5 Ft from left support of span 2(Center Span) TRAPEZOIDAL LOADS-CENTER SPAN
Created by combining all dead loads and live loads on span(s)2 Load Number One
Controlling Shear: -4464 lb Left Live Load 640 plf
At right support of span 2(Center Span) Left Dead Load 160 plf
Created by combining all dead loads and live loads on span(s)2 Right Live Load 640 plf
Right Dead Load 160 plf
Comparisons with required sections: Reo'd Provided Load Start 1.5 ft
Section Modulus: 70.14 in3 73.83 in3 Load End 3 ft
Area(Shear): 37.2 in2 39.38 in2 Load Length 1.5 ft
Moment of Inertia(deflection): 31.87 in4 415.28 in4
Moment: 5787 ft-lb 6091 ft-lb
Shear: -4464 lb 4725 lb
page
Project:22199 SOLSTICE CUSTOM HOMES 11111 Patrick J.Burke •
Location: M14-FOYER ENTRY DR HDR Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] _�4 ,_Portland,OR 97210
3.5 IN x 9.25 IN x 6.34 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:43.3%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.04 IN L/2084
Dead Load 0.02 in
Total Load 0.06 IN L/1239
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 1176 lb 1176 lb
Dead Load 802 lb 802 lb
Total Load 1978 lb 1978 lb TR1
Bearing Length 0.90 in 0.90 in N,
BEAM DATA Center .. ..-...a..... . —
Span Length 6.34 ft 6.34 e
B
Unbraced Length-Top 0 ft
Unbraced Length-Bottom 6.34 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 220 plf
#2-Douglas-Fir-Larch Uniform Dead Load 55 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 282 plf
Cd=9.00 CF=1.20 TRAPEZOIDAL LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=9.00 Left Live Load 151 plf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Left Dead Load 191 plf
Comp.-I-to Grain: Fc-1= 625 psi Fc-1'= 625 psi Right Live Load 151 plf
Right Dead Load 191 plf
Controlling Moment: 3135 ft-lb Load Start 0 ft
3.17 Ft from left support of span 2(Center Span) Load End 6.34 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 6.34 ft
Controlling Shear: -1978 lb
6.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Red Provided
Section Modulus: 34.84 in3 49.91 in3
Area(Shear): 16.48 in2 32.38 in2
Moment of Inertia(deflection): 44.72 in4 230.84 in4
Moment: 3135 ft-lb 4492 ft-lb
Shear: -1978 lb 3885 lb
, Project:22199 SOLSTICE CUSTOM HOMES page
III Patrick J. Burke
Location:M15-FRONT DEN FLUSH BM Alan Mascord Design
Multi-Loaded Multi-Span Beam Ilin 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] °f
�� 9f Portland,OR 97210
5.125 IN x 10.5 IN x 12.5 FT
_
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:21.7%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.30 IN L/493
Dead Load 0.18 in
Total Load 0.49 IN L/307
Live Load Deflection Criteria: 0360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 2987 lb 3094 lb
Dead Load 1795 lb 1868 lb
Total Load 4782 lb 4962 lb TRI
Bearing Length 1.44 in 1.49 in
BEAM DATA Center w
Span Length 12.5 ft '
Unbraced Length-Top 0 ft A 12.5 n
Unbraced Length-Bottom 12.5 ft B
Live Load Duration Factor 1.00
Camber Adj. Factor 0
Camber Required 0 UNIFORM LOADS Center
Notch Depth 0.00 Uniform Live Load 320 plf
Uniform Dead Load 170 plf
MATERIAL PROPERTIES Beam Self Weight 12 plf
24F-V4-Visually Graded Western Species Total Uniform Load 502 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by:
Fb_cmpr= 1850 psi Fb'= 2400 psi Load Number One
Cd=1.00 Live Load 81 Ib
Shear Stress: Fv= 265 psi Fv'= 265 psi Dead Load 54 lb
Cd=1.00 Location 4 ft
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.1 to Grain: Fc-1= 650 psi Fc--L'= 650 psi Load Number One Two
Left Live Load 126 plf 50 plf
Controlling Moment: 15474 ft-lb Left Dead Load 84 plf 34 plf
6.25 Ft from left support of span 2(Center Span) Right Live Load 126 plf 50 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 84 plf 34 plf
Controlling Shear: -4962 lb Load Start 0 ft 4 ft
12.0 Ft from left support of span 2(Center Span) Load End 12.5 ft 12.5 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 12.5 ft 8.5 ft
Comparisons with required sections: Req'd Provided
Section Modulus: 77.37 in3 94.17 in3
Area(Shear): 28.09 in2 53.81 in2
Moment of Inertia(deflection): 386.05 in4 494.4 in4
Moment: 15474 ft-lb 18834 ft-lb
Shear: -4962 lb 9507 lb
page
Project:22199 SOLSTICE CUSTOM HOMES imn Patrick J. Burke
Location: M16-SIDE BM AT REAR PATIO mg Alan Mascord Design
Multi-Loaded Multi-Span Beam 111111. 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] f Portland,OR 97210
5.5 IN x 9.5 IN x 11.5 FT -
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By:80.2%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.09 IN L/1581
Dead Load 0.07 in
Total Load 0.15 IN L/894
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A B
Live Load 691 lb 549 lb
Dead Load 526 lb 433 lb
Total Load 1217 lb 982 lb
Bearing Length 0.35 in 0.29 in TR1
TR2
BEAM DATA Center —`..
Span Length 11.5 ft 11.5 ft
Unbraced Length-Top 0 ft A
Unbraced Length-Bottom 11.5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 11 plf
Bending Stress: Fb= 875 psi Fb'= 875 psi Total Uniform Load 11 plf
Cd=1.00 CF=1.00 TRAPEZOIDAL LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One Two
Cd=1.00 Left Live Load 126 plf 126 plf
Modulus of Elasticity: E= 1300 ksi E= 1300 ksi Left Dead Load 84 plf 84 plf
Min.Mod.of Elasticity: E_min= 470 ksi E_min'= 470 ksi Right Live Load 126 plf 50 plf
Comp.-L to Grain: Fc--t-= 625 psi Fc--1-'= 625 psi Right Dead Load 84 plf 34 plf
Load Start Oft 6 ft
Controlling Moment: 3348 ft-lb Load End 6 ft 11.5 ft
5.52 Ft from left support of span 2(Center Span) Load Length 6 ft 5.5 ft
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 1217 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 45.92 in3 82.73 in3
Area(Shear): 10.74 in2 52.25 in2
Moment of Inertia(deflection): 105.47 in4 392.96 in4
Moment: 3348 ft-lb 6032 ft-lb
Shear: 1217 lb 5922 lb
Project:22199 SOLSTICE CUSTOM HOMES page
111111 Patrick J. Burke
Location: M17-BM AT REAR PATIO Alan Mascord Design
Multi-Loaded Multi-Span Beam 111111 2187 NW Reed St. Ste 100
[2015 International Building Code(2015 NDS)] °{
5.125 IN x 15.0 IN x 16.0 FT
.. ,_ Portland, OR 97210
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:34 PM
Section Adequate By: 16.7%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.32 IN L/592
Dead Load 0.25 in
Total Load 0.58 IN L/332
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A B 1
Live Load 2974 lb 5778 lb 2 s
Dead Load 2478 lb 4165 lb
Total Load 5452 lb 9943 lb
Bearing Length 1.64 in 2.98 in
BEAM DATA Center
Span Length 16 ft
Unbraced Length-Top 0 ft 16 ft B�
Unbraced Length-Bottom 16 ft
Live Load Duration Factor 1.00
Camber Adj. Factor 0
Camber Required 0 UNIFORM LOADS Center
Notch Depth 0.00 Uniform Live Load 0 plf
Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 17 plf
24F-V4-Visually Graded WesternSpecies Total Uniform Load 17 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by:
Fb_cmpr= 1850 psi Fb'= 2400 psi Load Number One * Two * Three *
Cd=1.00 Live Load 1293 lb 1335 lb 1631 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi Dead Load 1480 lb 900 lb 1098 lb
Cd=1.00 Location 6 ft 10 ft 13.5 ft
*Load obtained from Load Tracker. See Summary Report for details.
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi
Min. Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Comp.-L to Grain: Fc--I-= 650 psi Fc--1'= 650 psi Load Number One Two Three Four
Left Live Load50 plf 240 plf 50 plf 505 plf
Controlling Moment: 32948 ft-lb Left Dead Load 34 plf 150 plf 34 plf 337 plf
9.28 Ft from left support of span 2(Center Span) Right Live Load 126 plf 240 plf 101 plf 505 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 84 plf 150 plf 67 plf 337 plf
Controlling Shear: -9942 lb Load Start Oft 6 ft 6 ft 13.5 ft
At right support of span 2(Center Span) Load End 6 ft 16 ft 10 ft 16 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 6 ft 10 ft 4 ft 2.5 ft
Comparisons with required sections: R. eo'd Provided
Section Modulus: 164.74 in3 192.19 in3
Area(Shear): 56.28 in2 76.88 in2
Moment of Inertia(deflection): 1042.24 in4 1441.41 in4
Moment: 32948 ft-lb 38438 ft-lb
Shear: -9942 lb 13581 lb
page
Project:22199 SOLSTICE CUSTOM HOMES 111111 Patrick J.Burke
Location:M18-HDR OVER WDWS @ DINING(4 PT BRG HDR) an Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] $skeZ Portland.OR 97210
3.5 INx9.25INx9.99FT(3.3+3.3+3.3)
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By:26.6%
Controlling Factor: Shear
DEFLECTIONS Left Center Right LOADING DIAGRAM
Live Load 0.01 IN L/7967 0.00 IN L/MAX 0.00 IN L/MAX
Dead Load 0.00 in 0.00 in 0.00 in
Total Load 0.01 IN L/5691 0.00 IN L/8911 0.00 IN L/MAX
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A B C D
Live Load 1373 lb 3744 lb 2539 lb 600 lb
Dead Load 729 lb 2186 lb 1259 lb 215 lb
Total Load 2102 lb 5930 lb 3798 lb 815 lb TR1 TRI
Uplift(1.5 F.S) 0 lb 0 lb 0 lb -13 lb w w w
Bearing Length 0.96 in 2.71 in 1.74 in 0.37 in
BEAM DATA Left Center Right 3.33 ft 3.33 n
Span Length 3.33 ft 3.33 ft 3.33 ft A 3.33 ft D
Unbraced Length-Top O ft O ft O ft
Unbraced Length-Bottom 3.33 ft 3.33 ft 3.33 ft
Live Load Duration Factor 1.00 UNIFORM LOADS Left Center Right
Notch Depth 0.00 Uniform Live Load 380 plf 380 plf 380 plf
MATERIAL PROPERTIES Uniform Dead Load 185 plf 185 plf 185 plf
#2-Douglas-Fir-Larch Beam Self Weight 7 plf 7 plf 7 plf
Base Values Adjusted Total Uniform Load 572 plf 572 plf 572 plf
Bending Stress: Fb= 900 psi Fb'= 1074 psi TRAPEZOIDAL LOADS-LEFT SPAN
Cd=1.00 CI=0.99 CF=1.20 Load Number One
Shear Stress: Fv= 180 psi Fv'= 180 psi Left Live Load 557 plf
Cd=1.00 Left Dead Load 371 plf
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Right Live Load 557 plf
Min.Mod. of Elasticity: E_min= 580 ksi E_min'= 580 ksi Right Dead Load 371 plf
Comp.-I-to Grain: Fc-1= 625 psi Fc--I-'= 625 psi Load Start 0 ft
Load End 3.33 ft
Controlling Moment: -1905 ft-lb Load Length 3.33 ft
Over right support of span 1 (Left Span) CENTER SPAN
Created by combining all dead loads and live loads on span(s)1,2 Load Number One
Controlling Shear: -3070 lb Left Live Load 557 plf
3.0 Ft from left support of span 1 (Left Span) Left Dead Load 371 plf
Created by combining all dead loads and live loads on span(s)1,2 Right Live Load 557 plf
Right Dead Load 371 plf
Comparisons with required sections: Req'd Provided Load Start 0 ft
Section Modulus: 21.28 in3 49.91 in3 Load End 3.33 ft
Area(Shear): 25.58 in2 32.38 in2 Load Length 3.33 ft
Moment of Inertia(deflection): 10.43 in4 230.84 in4
Moment: -1905 ft-lb 4468 ft-lb --- -
Shear: -3070 lb 3885 lb
Project:22199 SOLSTICE CUSTOM HOMES page
EN Patrick J. Burke
Location:M19-WINDOW HDR AT KITCHEN mg Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100
of
[2015 International Building Code(2015 NDS)] Portland,OR 97210
3.5 IN x 7.25 IN x 4.0 FT
___41,040-910(,....
#2 Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By: 0.2%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/1589
Dead Load 0.02 in
Total Load 0.05 IN L/994
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A_
Live Load 1866 lb 1866 lb
Dead Load 1117 lb 1117 lb
Total Load 2983 lb 2983 lb TR1
Bearing Length 1.36 in 1.36 in
BEAM DATA Center
Span Length 4 ft
Unbraced Length-Top 0 ft A Oft B_
Unbraced Length-Bottom 4 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 380 plf
#2-Douglas-Fir-Larch Uniform Dead Load 185 plf
Base Values Adjusted Beam Self Weight 6 plf
Bending Stress: Fb= 900 psi Fb'= 1170 psi Total Uniform Load 571 plf
Cd=1.00 CF=1.30
Shear Stress: Fv= 180 psi Fv'= 180 psi TRAPEZOIDAL LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Left Live Load 553 plf
Min. Mod.of Elasticity: E—min= 580 ksi E_min'= 580 ksi Left Dead Load 368 plf
Comp.1 to Grain: Fc-1= 625 psi Fc-1'= 625 psi Right Live Load 553 plf
Right Dead Load 368 plf
Controlling Moment: 2983 ft-lb Load Start 0 ft
2.0 Ft from left support of span 2(Center Span) Load End 4 ft
Created by combining all dead loads and live loads on span(s)2 Load Length 4 ft
Controlling Shear: 2983 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Rend Provided
Section Modulus: 30.59 in3 30.66 in3
Area(Shear): 24.86 in2 25.38 in2
Moment of Inertia(deflection): 26.84 in4 111.15 in4
Moment: 2983 ft-lb 2989 ft-lb
Shear: 2983 lb 3045 lb
page
Project:22199 SOLSTICE CUSTOM HOMES IIM Patrick J. Burke
Location:M20-SIDE DEN WINDOW HDR Alan Mascord Design
Multi-Loaded Multi-Span Beam NM 2187 NW Reed St. Ste 100 or
[2015 International Building Code(2015 NDS)] ---/.14 ,9a,..._Portland,OR 97210
3.5 IN x 9.25 IN x 3.0 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Section Adequate By: 12.7%
Controlling Factor: Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/5048
Dead Load 0.00 in
Total Load 0.01 IN L/3050
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A B 1
Live Load 2105 lb 1110 lb
Dead Load 1342 lb 804 lb
Total Load 3447 lb 1914 lb
Bearing Length 1.58 in 0.87 in TR1 rRz
BEAM DATA Center ;.. :
Span Length 3 ft
---- - 3 ft
Unbraced Length-Top 0 ft A B
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 7 plf
Cd=1.00 CF=1.20 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One*
Cd=1.00 Live Load 2987 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 1795 lb
Comp.1 to Grain: Fc-1-= 625 psi Fc-l'= 625 psi Location 1 ft
Load obtained from Load Tracker. See Summary Report for details.
Controlling Moment: 3352 ft-lb
1.02 Ft from left support of span 2(Center Span) TRAPEZOIDAL LOADS-CENTER SPAN
Created by combining all dead loads and live loads on span(s)2 Load Number One Two
Controlling Shear: 3448 lb Left Live Load 76 plf 76 plf
At left support of span 2(Center Span) Left Dead Load 50 plf 140 plf
Created by combining all dead loads and live loads on span(s)2 Right Live Load 76 plf 76 plf
Right Dead Load 50 plf 140 plf
Comparisons with required sections: Req'd Provided Load Start 0 ft 1 ft
Section Modulus: 37.24 in3 49.91 in3 Load End 1 ft 3 ft
Area(Shear): 28.73 in2 32.38 in2 Load Length 1 ft 2 ft
Moment of Inertia(deflection): 18.16 in4 230.84 in4
Moment: 3352 ft-lb 4492 ft-lb
Shear: 3448 lb 3885 lb
Project:22199 SOLSTICE CUSTOM HOMES mg page
Patrick J. Burke
Location:M21 -LAUNDRY RM WINDOW HDR Alan Mascord Design
Multi-Loaded Multi-Span Beam a 2187 NW Reed St.Ste 100
/
[2015 International Building Code(2015 NDS)] of
. Portland,OR 97210
3.51Nx9.251Nx3.0FT
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By: 19.7% StruCalc Version 10.0.1.6 11/8/2018 3:47:35 PM
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/6122
Dead Load 0.00 in
Total Load 0.01 IN L/3633
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
1
REACTIONS A B
Live Load 1927 lb 1085 lb
Dead Load 1319 lb 756 lb
Total Load 3246 lb 1841 lb TR1
Bearing Length 1.48 in 0.84 in
BEAM DATA Center "
Span Length 3 ft ,..
Unbraced Length-Top 0 ft 3 ft
Unbraced Length-Bottom 3 ft B
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 180 plf
#2-Douglas-Fir-Larch Uniform Dead Load 135 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 322 plf
Cd=1.00 CF=1.20
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 1751 lb
Comp.1 to Grain: Fc-1= 625 psi Fc-1'= 625 psi Dead Load 1168 lb
Location 1 ft
Controlling Moment: 2657 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
1.02 Ft from left support of span 2(Center Span) Load Number One Two
Created by combining all dead loads and live loads on span(s)2 Left Live Load 494 plf 126 plf
Controlling Shear: 3246 lb Left Dead Load 330 plf 84 plf
At left support of span 2(Center Span) Right Live Load 494 plf 101 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 330 plf 67 plf
Load Start 0 ft 1 ft
Comparisons with required sections: Req'd Provided Load End 1 ft 3 ft
Section Modulus: 29.52 in3 49.91 in3 Load Length 1 ft 2 ft
Area(Shear): 27.05 in2 32.38 in2
Moment of Inertia(deflection): 15.25 in4 230.84 in4
Moment: 2657 ft-lb 4492 ft-lb
Shear: 3246 lb 3885 lb
page
Project:22199 SOLSTICE CUSTOM HOMES 11111 Patrick J.Burke
Location:STUDS AT STAIRS Alan Mascord Design
Column MEI 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] __,- i }, ' `Portland,OR 97210
1.5 INx5.5lNx18.0FT@120.C.
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By: 12.7%
DEFLECTIONS LOADING DIAGRAM
Deflection due to lateral loads only: Defl= 1.06 IN=L/203
Live Load Deflection Criteria: L/180
VERTICAL REACTIONS
Live Load: Vert-LL-Rxn= 324 lb B
Dead Load: Vert-DL-Rxn= 248 lb
Total Load: Vert-TL-Rxn= 572 lb
HORIZONTAL REACTIONS
•
Total Reaction at Top of Column: TL-Rxn-Top= 135 lb
Total Reaction at Bottom of Column: TL-Rxn-Bottom= 135 lb
COLUMN DATA
Total Column Length: 18 ft
Unbraced Length(X-Axis)Lx: 9 ft
Unbraced Length(Y-Axis)Ly: 0 ft
Column End Condition-K(e): 1
Axial Load Duration Factor 1.00 18ft w
Lateral Load Duration Factor(Wind/Seismic) 1.33
STUD PROPERTIES
#2-Douglas-Fir-Larch
Base Values Adjusted
Compressive Stress: Fc= 1350 psi Fc'= 1019 psi
Cd=1.33 Cf=1.10 Cp=0.52
Bending Stress(X-X Axis): Fbx= 900 psi Fbx'= 1790 psi
Cd=1.33 CF=1.30 Cr-1.15 CI=1.00
Bending Stress(Y-Y Axis): Fby= 900 psi Fby'= 1790 psi
Cd=1.33 CF=1.30 Cr=1.15
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi A
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
AXIAL LOADING
Stud Section(X-X Axis): dx= 5.5 in Live Load: PL= 324 plf
Stud Section(Y-Y Axis): dy= 1.5 in Dead Load: PD= 216 plf
Area: A= 8.25 in2 Column Self Weight: CSW= 32 plf
Section Modulus(X-X Axis): Sx= 7.56 in3 Total Axial Load: PT= 572 plf
Section Modulus(Y-Y Axis): Sy= 2.06 in3
Slenderness Ratio: Lex/dx= 19.64 LATERAL LOADING (Dy Face)
Ley/dy= 0 Uniform Lateral Load: wL-Lat= 15 psf
Stud Calculations(Controlling Case Only):
Controlling Load Case:Axial Dead Load and Lateral loads(D+W or E)
Actual Compressive Stress: Fc= 30 psi
Allowable Compressive Stress: Fc'= 1019 psi
Eccentricity Moment(X-X Axis): Mx-ex= 0 ft-lb
Eccentricity Moment(Y-Y Axis): My-ey= 0 ft-lb
Moment Due to Lateral Loads(X-X Axis): Mx= 608 ft-lb
Moment Due to Lateral Loads(Y-Y Axis): My= 0 ft-lb
Bending Stress Lateral Loads Only(X-X Axis): Fbx= 964 psi
Allowable Bending Stress(X-X Axis): Fbx'= 1790 psi
Bending Stress Lateral Loads Only(Y-Y Axis): Fby= 0 psi
Allowable Bending Stress(Y-Y Axis): Fby'= 1790 psi
Combined Stress Factor: CSF= 0.55
Project:22199 SOLSTICE CUSTOM HOMES page
Patrick J. Burke
Location:U1-WINDOW HDR AT MASTER BATH Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100
[2015 International Building Code(2015 NDS)] or
_r , ,,.e ,. Portland,OR 97210
3.5 IN x 9.25 IN x 6.0 FT
#2-Douglas-Fir-Larch-Dry Use
Section Adequate By:20.0% StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.04 IN L/1843
Dead Load 0.03 in
Total Load 0.07 IN L/1096
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A_
Live Load 1485 lb 1485 lb
Dead Load 1011 lb 1011 lb
Total Load 2496 lb 2496 lb
Bearing Length 1.14 in 1.14 in
BEAM DATA Center
Span Length 6 ft
Unbraced Length-Top O ft A 611—
Unbraced Length-Bottom 6 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 495 plf
#2-Douglas-Fir-Larch Uniform Dead Load 330 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 832 plf
Cd=1.00 CF=1.20
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp. to Grain: Fc--L= 625 psi Fc- = 625 psi
Controlling Moment: 3744 ft-lb
3.0 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2496 lb
At right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 41.6 in3 49.91 in3
Area(Shear): 20.8 in2 32.38 in2
Moment of Inertia(deflection): 50.54 in4 230.84 in4
Moment: 3744 ft-lb 4492 ft-lb
Shear: -2496 lb 3885 lb
page
Project:22199 SOLSTICE CUSTOM HOMES Patrick J. Burke
Location:U2-WINDOW HDR AT BR.2 no Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] —:r: ¢,ks .;Portland.OR 97210
3.5 INx3.5INx5.0FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By:7.3%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.10 IN L/601
Dead Load 0.07 in
Total Load 0.17 IN L/356
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 355 lb 355 lb
Dead Load 244 lb 244 lb
Total Load 599 lb 599 lb
Bearing Length 0.27 in 0.27 in
BEAM DATA Center issamowilasom
Span Length 5 ft
Unbraced Length-Top 0 ft A
Unbraced Length-Bottom 5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 142 plf
#2-Douglas-Fir-Larch Uniform Dead Load 95 plf
Base Values Adjusted Beam Self Weight 3 plf
Bending Stress: Fb= 900 psi Fb'= 1350 psi Total Uniform Load 240 plf
Cd=9.00 CF=1.50
Shear Stress: Fv= 180 psi Fv'= 180 psi
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp.-L to Grain: Fc- = 625 psi Fc- = 625 psi
Controlling Moment: 749 ft-lb
2.5 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -599 lb
At right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 6.66 in3 7.15 in3
Area(Shear): 4.99 in2 12.25 in2
Moment of Inertia(deflection): 8.42 in4 12.51 in4
Moment: 749 ft-lb 804 ft-lb
Shear: -599 lb 1470 lb
page
. Project:22199 SOLSTICE CUSTOM HOMES
1111 Patrick J. Burke
Location: U3-REAR MSIR BR WIN. HDR Elm Alan Mascord Design
Multi-Loaded Multi-Span Beam 111.1 2187 NW Reed St.Ste 100 of
[2015 International Building Code(2015 NDS)] _41.440,..:04,,(...Portland,OR 97210
3.5INx9.251Nx3.0FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By:42.3%
Controlling Factor: Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/5220
Dead Load 0.00 in
Total Load 0.01 IN L/3123
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A B
Live Load 1335 lb 1631 lb
Dead Load 900 lb 1098 lb
Total Load 2235 lb 2729 lb
Bearing Length 1.02 in 1.25 in
TR2
BEAM DATA Center
Span Length 3 ft
Unbraced Length-Top O ft -A
3 ft B
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adjusted Beam Self Weight 7 plf
Bending Stress: Fb= 900 psi Fb'= 1080 psi Total Uniform Load 7 plf
Cd=1.00 CF=1.20 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=1.00
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 2038 lb
Comp.--to Grain: Fc--L= 625 psi Fc--I-'= 625 psi Dead Load 1358 lb
Location 1.5 ft
Controlling Moment: 3139 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
1.5 Ft from left support of span 2(Center Span) Load Number One Two
Created by combining all dead loads and live loads on span(s)2 Left Live Load 101 plf 505 plf
Controlling Shear: -2729 lb Left Dead Load 67 plf 337 plf
At right support of span 2(Center Span) Right Live Load 126 plf 505 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 84 plf 337 plf
Load Start Oft 1.5 ft
Comparisons with required sections: Req'd Provided Load End 1.5 ft 3 ft
Section Modulus: 34.88 in3 49.91 in3 Load Length 1.5 ft 1.5 ft
Area(Shear): 22.74 in2 32.38 in2
Moment of Inertia(deflection): 17.74 in4 230.84 in4
Moment: 3139 ft-lb 4492 ft-lb
Shear: -2729 lb 3885 lb
page
Project:22199 SOLSTICE CUSTOM HOMES Ell Patrick J. Burke •
Location: U4-GAMES RM FRONT WINDOW HDR mill Alan Mascord Design
Multi-Loaded Multi-Span Beam 2187 NW Reed St. Ste 100 of
[2015 International Building Code(2015 NDS)] �. ,a!,._Portland.OR 97210
3.5INx7.251Nx3.OFT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 10.0.1.6 11/8/2018 3:47:36 PM
Section Adequate By:7.9%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/2833
Dead Load 0.01 in
Total Load 0.02 IN L/1695
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:L/240
REACTIONS A B 1
Live Load 1477 lb 1187 lb
Dead Load 993 lb 800 lb
Total Load 2470 lb 1987 lb
Bearing Length 1.13 in 0.91 in TR1
BEAM DATA Center
Span Length 3 ft
—_ — -
Unbraced Length-Top 0 ft A 3 ft
Unbraced Length-Bottom 3 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Douglas-Fir-Larch Uniform Dead Load 0 plf
Base Values Adiusted Beam Self Weight 6 plf
Bending Stress: Fb= 900 psi Fb'= 1170 psi Total Uniform Load 6 plf
Cd=1.00 CF=1.30 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=1.00 Live Load 1751 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 1168 lb
Comp.1 to Grain: Fc-1-= 625 psi Fc-1'= 625 psi Location 1.5 ft
Controlling Moment: 2770 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
1.5 Ft from left support of span 2(Center Span) Load Number One Two
Created by combining all dead loads and live loads on span(s)2 Left Live Load 495 plf 126 plf
Controlling Shear: 2469 lb Left Dead Load 330 plf 84 plf
At left support of span 2(Center Span) Right Live Load 495 plf 101 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 330 plf 67 plf
Load Start Oft 1.5 ft
Comparisons with required sections: Req'd Provided Load End 1.5 ft 3 ft
Section Modulus: 28.41 in3 30.66 in3 Load Length 1.5 ft 1.5 ft
Area(Shear): 20.58 in2 25.38 in2
Moment of Inertia(deflection): 15.73 in4 111.15 in4
Moment: 2770 ft-lb 2989 ft-lb
Shear: 2469 lb 3045 lb