Loading...
Report (21) 05 GI S-Wash SE . RECEIVED JUN 24 2019 ITY OF TIGARD YATLDING DIVISION FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 FOOT LOCKER WASH 9585 SW WASHINGTON SQ RD A14 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL tti CO® Worldwide www.tyco-fire.com Contacts Series RFII — 5.6 K-factor "Royal Flush I1" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General The Series RFII Sprinklers are shipped with a Disposable Protective Cap.The Description Protective Cap is temporarily removed p during installation and replaced to help The TYCO Series RFII 5.6 K-factor, protect the sprinkler during ceiling "Royal Flush II" Concealed Pendent installation or finish.The tip of the Pro Sprinklers Quick Response (3-mm tective Cap can be used to mark the center of the ceiling hole into plaster bulb) and Standard Response (5-mm bulb), are decorative sprinklers fea board or ceiling tiles by gently pushing turing a flat cover plate designed to the ceiling product against the Pro conceal the sprinkler.These sprinklers tective Cap. When ceiling installa are optimal for architecturally sensi- tion is complete,the Protective Cap is tive areas such as hotel lobbies, office removed and the Cover Plate/Retainer buildings, churches, and restaurants. Assembly is installed. Each sprinkler includes a Cover Plate/ As an option,the Series RFII Standard Retainer Assembly and a Sprinkler/ Response(5 mm bulb)"Royal Flush II" Support Cup Assembly. The separa Concealed Pendent Sprinklers can be ble, two-piece assembly design pro- fitted with a silicone Air and Dust Seal. Technical vides the following benefits: (Refer to Figure 5.) The Air and Dust Seal is intended for sensitive areas Data • Allows installation of the sprinklers where it is desirable to prevent air and and pressure testing of the fire pro- dust from the area above the ceiling to Sprinkler Approvals tection system prior to installation of pass through the cover plate. Approvals apply only to the service a suspended ceiling or application of conditions indicated in the Design Criteria the finish coating to a fixed ceiling. NOTICE section. • Permits the removal of suspended The Series RFII Concealed Pendent • TY3531 (3 mm Bulb)is UL Listed,C-UL ceiling panels for access to building Sprinklers described herein must be Listed and NYC Approved(MEA 353- service equipment without having installed and maintained in compliance 01-E)as Quick Response. to first shut down the fire protection with this document and with the appli- • TY3531 (3 mm Bulb)is VdS Approved system and remove sprinklers. cable standards of the NATIONAL FIRE (Certificate No.G4090007). • Provides for 1/2 in. (12,7 mm)of ver- PROTECTION ASSOCIATION (NEPA), • TY3531 (3 mm Bulb)is FM and tical adjustment to allow a measure in addition to the standards of any authorities having jurisdiction. Failure LPCB Approved(Ref.No.094a110)as of flexibility in determining the length Standard Response. to do so may impair the performance of fixed piping to cut for the sprinkler of these devices. Note:FM and LPCB do not approve drops. concealed sprinklers for quick The owner is responsible for maintain- response. ing their fire protection system and devices in proper operating condition. • TY3551 (5 mm Bulb)is UL Listed,C-UL The installing contractor or sprinkler Listed, FM Approved, LPCB Approved manufacturer should be contacted with (Ref. No.094a/9),and NYC Approved any questions. (MEA 353-01-E)as Standard Response. IMPORTANT Approvals for Air and Dust Seal Refer to Technical Data Sheet Sprinkler UL and C-UL Listed for use with the RFII TFP2300 for warnings pertaining to Standard Response Concealed Sprinkler regulatory and health information. Identification (TY3551) Always refer to Technical Data Maximum Working Pressure Sheet TFP700 for the "INSTALLER Number (SIN) Maximum 250 psi(17,3 bar)by UL, WARNING" that provides cautions C-UL,and NYC with respect to handling and instal- TY3531 — 3 mm bulb Maximum 175 psi(12,1 bar)by FM,VdS, lation of sprinkler systems and com- TY3551 — 5 mm bulb and LPCB ponents. Improper handling and Temperature Rating installation can permanently damage a sprinkler system or its compo- 155°F(68°C)Sprinkler with CoverPlate nents and cause the sprinkler to fail 139°F(59°C) to operate in a fire situation or cause 200°F(93°C)Sprinkler with it to operate prematurely. 165°F(74°C)Cover Plate Page 1 of 4 SEPTEMBER 2018 TFP181 TFP181 Page 2 of 4 Discharge Coefficient K=5.6 GPM/psi1/2(80,6 LPM/barl'2) 1/2"NPT SEALING Adjustment ASSEMBLY 1/2 inch(12,7 mm) Finishes FRAME ►I / \ r' See the Ordering Procedure section �' l CAP Physical Characteristics I, 1 Frame Bronze Support Cup Plated Steel SUPPORT Guide Pins Stainless Steel CUP WITH BULB Deflector Bronze ROLL FORMED Compression Screw Brass THREADS Bulb Glass Cap Bronze or Copper R Sealing Assembly..Beryllium Nickel w/TEFLON I I COM PRESSION Cover Plate Brass i SCREW Retainer Brass GUIDEAiridm Ejection Spring Stainless Steel PINS(2) t ,- i Design _ DEFLECTOR (DROPPED Criteria DEFLECTOR _ J ]� POSITION) The TYCO Series RFII 5.6 K-factor, "Royal Flush II" Concealed Pendent SPRINKLER/SUPPORT CUP Sprinklers are intended for fire protec- ASSEMBLY tion systems designed in accordance I with the standard installation rules THREAD INTO i recognized by the applicable Listing SUPPORT ) WTHTHREAD or Approval agency; for example, UL CUP UNTIL \ O 0 % DIMPLES Listing is based on NFPA 13 and VdS MOUNTING Approval is based on the CEA 4001. SURFACE IS EJECTION FLUSH WITH SPRING For more information on LPCB and VdS CEILING Approvals,contact Johnson Controlss at the following office: Enschede, Netherlands -, ____ �f Telephone:31-53-428-4444 Fax:31-53-428-3377 SOLDER COVER The Series RFII Concealed Pendent TABS(3) COVER PLATE/RETAINER PLATE Sprinklers are only listed and approved ASSEMBLY with the Series RFII Concealed Cover FIGURE 1 Plates having a factory applied finish. MODEL RFII CONCEALED SPRINKLER NOTICE ASSEMBLY Do not use the Series RFII in applica- Installation Do not attempt to compensate for tions where the air pressure above the insufficient adjustment in the Sprinkler ceiling is greater than that below.Down The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- drafts through the Sprinkler/Support "Royal Flush II" Concealed Pendent kler/Support Cup Assembly.Re-adjust Cup Assembly can delay sprinkler Sprinklers must be installed in accor- the position of the sprinkler fitting to operation in a fire situation, dance with this section. suit. Step 1. Install the sprinkler only in the Operation General InstructionsDo not install any bulb-type sprinkler pendent position with the center-line if the bulb is cracked or there is a loss of the sprinkler perpendicular to the When exposed to heat from a fire, the mounting surface. Cover Plate, normally soldered to the of liquid from the bulb.With the sprin- Retainer at three points, falls away to kler held horizontally,a small air bubble Step 2. Remove the Protective Cap. expose the Sprinkler/Support Cup should be present.The diameter of the Step 3. With pipe thread sealant Assembly. air bubble is approximately 1/16 inch applied to the pipe threads, hand- (1,6 mm)for the 155°F(68°C)and 3/32 tighten the sprinkler into the sprinkler The Deflector — supported by the inch(2,4 mm)for the 200°F(93°C)tem- fitting. Guide Pins — then drops down to its perature ratings. Step 4. Wrench-tighten the sprinkler operational position. A leak tight 1/2 inch NPT sprinkler using only the RFII Sprinkler Wrench. The glass bulb contains a fluid that joint should be obtained by applying a (Refer to Figure 3.) Apply the RFII expands when exposed to heat.When minimum to maximum torque of 7 to 14 Sprinkler Wrench to the Sprinkler as the rated temperature is reached, the ft.-lbs. (9,5 to 19,0 Nm). Higher levels shown in Figure 3. fluid expands sufficiently to shatter the of torque can distort the sprinkler Inlet glass bulb,activating the sprinkler and with consequent leakage or impairment allowing water to flow. of the sprinkler. • TFP181 Page 3 of 4 • FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER DIAMETER HOLE 1 FITTING I DIMENSION C SPRINKLER ) CMN fk SUPPORT CUP JJ 1 ASSEMBLY I �1/2"(12,7 mm)THREADED DADJUSTMENT ' � hI1iTI ,,MI FACE ��� OF CEILING, o RETAINING RING / �,,,,,a,, / MOUNTING t' 1 °� SURFACE\ d f I FIGURE 4 , DISPOSABLE PROTECTIVE CAP r -'-----' Z• Step 5. Replace the Protective Cap i by pushing it upwards until it bottoms E_ �_ L__� out against the Support Cup. (Refer T _t to Figure 4.)The Protective Cap helps 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE prevent damage to the Deflector and (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER Arms during ceiling installation and/or REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY finish.You can also use the Protective Cap to locate the center of the clear- COVER PLATE COVER PLATE ance hole by gently pushing the ceiling -PROFILE DEPTH DIAMETER material up against the center point of DIMENSION B DIMENSION A the Protective Cap. A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) NOTICE B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) As long as the Protective Cap remains in place,the system is considered "Out FIGURE 2 of Service". SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Step 6. After the ceiling has been completed with the 2-1/2 in.(63,5 mm) diameter clearance hole and in prep- aration for installing the Cover Plate/ Retainer Assembly,remove and discard , AWOL�_ FRAME ►tel` the Protective Cap. Verify that the MN ,/ ARM % �1 Deflector moves up and down freely. If the Sprinkler is damaged and the f I' Deflector does not move up and down SUPPORT IR ) freely, replace the entire Sprinkler. - CUP ) Do not attempt to modify or repair a > �I��� iii 11_4 ? damaged sprinkler. A...., Step 7. When installing an Air and I■Ii�� Dust Seal,refer to Figure 5;otherwise, --------- proceed to Step 8. To attach the Air Amiii 7/8"(23 mm) and Dust Seal, verify the angle of the SQUARE outside edge of the seal is oriented according to Figure 5.Start the edge of , s _ the Retainer in the grooved slot of the ALIGN /./.1-*** J �. Air and Dust Seal and continue around ARROWS WITH (/ `\ the retainer until the entire Air and Dust FRAME ARMS � Seal is engaged. -1 r ACCEPTS \ ` 0 1/2"SOCKET �–rte DRIVE FIGURE 3 RFII SPRINKLER WRENCH TFP181 Page 4 of 4 Step 8. Screw on the Cover Plate/ SUPPORT — SPRINKLER FACE OF ORIENT Retainer Assembly until the Retainer CUP CEILING �_ SEAL (shown in Figure 2)or the Air and Dust BEVEL AS Seal (shown in Figure 5) contacts the ;j��L___ SHOWN ceiling.Do not continue to screw on the 1 COVER j� '',) Cover Plate/Retainer Assembly so that ( PLATE it lifts a ceiling panel out of its normal l f ) RETAINER — position. If you cannot engage the 1� i�; ASSEMBLY r I% Cover Plate/Retainer Assembly with 1, :\ the Support Cup or you cannot engage (j the Cover Plate/Retainer Assembly suf- ficiently to contact the ceiling,you must ; � Ih r / AIR reposition the Sprinkler Fitting. /� oo l .r__ _ �� AND DUST �•—�_- _ , • SEAL �� LIP OF COVER Care and RETAINER PLATE FIGURE 5 Maintenance OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) The TYCO Series RFII 5.6 K-factor, Care must be exercised to avoid "Royal Flush II" Concealed Pendentdamage to the sprinklers before, Ordering Sprinklers must be maintained and during, and after installation. Sprin- serviced in accordance with this klers damaged by dropping, striking, Procedure section. wrench twist/slippage,or the like,must Before closing a fire protection system be replaced. Also, replace any sprin- Contact yourW local cintributor for main control valve for maintenance kler that has a cracked bulb or that has availability.ttWhen placingta an order, work on the fire protection system lost liquid from its bulb. (Ref. Installa- that the full product name. that it controls, obtain permission to tion Section.) Sprinkler/Support Cup Assembly shut down the affected fire protection Specify: Series RFII (specify SIN), s stem from the proper authorities Exercise care to avoid damage to sprnatal K=5.6, "Royal Flush II" Pendent Sprin- g P P klers before, during, and after instal- and notify all personnel who may be lation. Replace sprinklers damaged klers(specify)temperature rating, P/N* affected by this action. by dropping, striking, wrench twist- (specify): Absence of the Cover Plate/Retainer ing, wrench slipping, or the like. Also, 155°F(68°C) 200°F(93°C) Assembly can delay sprinkler opera- replace any sprinkler that has a cracked TY3531 51-792-1-155 51-792-1-200 • tion in a fire situation. bulb or that has lost liquid from its bulb. TY3551 51-790-1-155 51-790-1-200 (Refer to the Installation section.) When properly installed, there is a * Use Suffix'1"for ISO 7-1 connection;for example. nominal 3/32 in. (2,4 mm) air gap If you must remove a sprinkler, do not 51-792-1-155-I between the lip of the Cover Plate and reinstall it or a replacement without Separately Ordered Cover Plate/ the ceiling, as shown in Figure 2. reinstalling the Cover Plate/Retainer Retainer Assembly: Assembly. If a Cover Plate/Retainer rating from This air gap is necessary for proper Assembly becomes dislodged during below)Specify:S (temperaturees RFIi Concealed Coverrm operation of the sprinkler. If the ceiling service, replace it immediately. s, P/N finish (specify). requires repainting after sprinkler Plate with The owner is responsible for the (finish), ( P y). installation, ensure that the new paint inspection,testing,and maintenance of 139°F(59°C)(a) 165°F(74°C)(b) does not seal off any of the air gap. their fire protection system and devices Grey White Y (RAL9002) 56-792-0-135 56-792-0-165 Do not pull the Cover Plate relative to in compliance with this document, as Brass 56-792-1-135 56-792-1-165 the Enclosure. Separation may result. well as with the applicable standards Pure White(c) Sprinklers which are found to be of the NATIONAL FIRE PROTECTION (RAL9010) 56-792-3-135 56-792-3-165 exhibiting visible signs of ASSOCIATION,for example, NFPA 25, Signal White leaking leaking orn must be replaced. in addition to the standards of any other (RAL9003) 56-792-4-135 56-792-4-165 corrosiauthorities having jurisdiction.Contact Jet Black Automatic sprinklers must never be the installing contractor or sprinkler (RAL9005) 56-792-6-135 59-792-6-165 painted, plated, coated, or other- manufacturer regarding any questions. Brushed wise altered after leaving the factory. p Chrome 56-792-8-135 56-792-8-165 - Automatic sprinkler systems should be Chrome 56-792-9-135 56-792-9-165 Modified sprinklers must be replaced. inspected,tested,and maintained by a Custom 56-792-X-135 56-792-x-165 Sprinklers that have been exposed to qualified Inspection Service in accor- corrosive products of combustion, but dance with local requirements and/or (a) For use with 155°F(68°C)sprinklers. - have not operated,should be replaced national code. (b) For use with 200°F(93°C)sprinklers. if they cannot be completely cleaned (c) Eastern Hemisphere sales only. by wiping the sprinkler with a cloth or Limited by brushing it with a soft bristle brush. Sprinkler Wrench Specify: RFII Sprinkler Wrench, Warranty P/N 56-000-1-075 For warranty terms and conditions,visit Air and Dust Seal www.tyco-fire.com. Specify:Air and Dust Seal, • P/N 56-908-1-001 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 ® �.r /'��,'2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson �/ ,(`I NAI IONAL FIRE PROTECTION ASSOCIATION and NI-PA are registered trademarks of National Are Protection Association; Controls TEFLON is a registered trademark of DuPont Eddyth read 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS 1 ‘-g,4-3.--;, 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 ; 2.547 1.654 44 2 ' 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL t . .. _° 1 1.00 1.00 t 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 x Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems n- •� 1819 Clarkson Road For additional information, ( v�SU Mme+/' Chesterfield, MO 63017 contact your salesperson today at s L O us p� II BULL MOOSE TUBE COMPANY 06 (800)325-4467 or(636)537-2600 LISTED FAX:(80)(636)32544 537-7 2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 41> A LFFRO company e-mail:sales@bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 #'C T Yr. t . '4/ 'air i -Ili / £.,. l e�/-i { i J 0 ' — ', } } gg Elmo 2 NW d ' { 1 `/ Oxy x a € - ii. , . „4,„: Plit: -- Pi:: , ,CZri 7` {Y tea: 0 � �� ', a via+&` t,ti J ry " 0044444444 ,,,,,s .2' 't 1' &Mill 14 i'fi4,.........',', . .' VPI.V.e' .0." f ,` '1, r 1 ,,,,,,, ,,,,,,,,._ ,, „1„,„ 4- 1 1 _ / Y Sa r� r- sn i : !`„ ,, ,„.- , v ' 1!, 4 --,g . A �/ , - - - '• _. s . r.. .,, ^� To- ` r. • SMITI-! COPE INTERNATIONAL • Ductile Iron Threaded Fittisgn specifications • branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP 02) • Ductile iron castings conform to ASTM A536 C US -,, LISTED w ,..,,,,,..,,,,!,,,,,,,,41 • Fitting dimensions conform to ASME B16.3 :,. • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 _ • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings . -20 to 100 500 150 500 200 480 460t 3 _,. :250 rt . 300 440 ,.,;. av, 350 420 ., , 400 400 450 Etre 380 500 30t mo....- ° 550 340 4 600 320 .,, 650 + 300 T 9t � r k ,r ' ° ar z r a €x^ a "fin 1 ''' on,e,." '. 1 r,-,:':. o ,. say �Z, ..,.w...r' r.ri ; wse�M,. . „ - � w. Ductile Iron Fittings- ass I I I ' ?I c ® us 41> APPROVED Fig. 35E 3-90° Elbow LISTED A Size A Packing Weight Part Number in in Inner Master lb ---1-'444^ 1/2 35E 3004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 A 1 3.5[_3010 1.50 40 80 0.5 limihi 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 358 3024 2.70 4 8 32 Fig. 35RE3-90°Reducing Elbow B Size A B Packing Weight in Part Number in in Inner Master lb 1 . 3/1 x 1/2 358E3006004 1.20 1.22 80 160 0.3 I- 1 x 1/2 35RE3010004 1.2E 1.36 70 140 0.4 1 x 3/4 35813010006 38 1.45 50 00 0.4 I 1 A 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35813012006 1.45 1.63 35 70 0.6 111_1111111-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 358E_3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 358E3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 358E3090004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 - 1.97 18 36 1.0 2 x 1 35813020010 1.73 2.02 16 3% 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 33R83020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 ra 2-1/2 x 2 35883024020 2.39 2.60 6 1? 2.5 Fig. 35F 3-45°Elbow Size Part Number A Packing Weight A in in Inner Master lb 7� �, 1/2 351- 3004 0,88 160 300 0.2 03/4 35F 3006 0.98 80 160 0.3 4 -� 1 3513010 1.13 40 80 0.5 1-1/4 35F 3012 1.29 25 50 0.7 -1/? 35F 3014 44 20 40 0 a�i IA 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 27 Fig. 35T 3- Tee Size A Packing Weight Part Number -- in in Inner Master lb .EllA 1/7 35' 3004 1.13 80 160 0.3 (- I 1 3/4 35T 3006 1.31 30 60 0.5 • =�=I 1 35113010 1.50 25 50 0.7 1-1/4 35T 3012 1.75 10 20 1.1 A '1 1-1/2 351 3014 1.04 10 20 1.5 A 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 • 111 SI\IITH-COOPER IN"I'RRN VI'IONAL° • 'l'OI.I. FREE, 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com ) Ductile Iron Fittings- Class 300 UL/FM • i i �4 , CCOus APPROVED Fig. 35RT3-Reducing Tee LISTED Size A B C Packing Weight Iplr in Part Number in in in Inner Master lb 1 C 3/4 x 1/2 35013006004 1.20 1.20 1,22 60 120 0.4 I 1 x 1/2 35013010004 1.26 1.26 1.36 30 60 0.6 -1.-- I�-- �I- 'x 1/2 x 1 35013010004010 1.50 1.36 1.50 30 60 0.6 1 x 3/4 35013010006 1.38 1.38 1,45 25 50 0.6 *----_.4 i r 1 x 3/4 x 3/4 35013010006006 1.38 1 31 1.45 35 70 0.6 B A 1x3/4x 1 35013010006010 1,50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 350T3112004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x1-1/4 3501.3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4x3/4 35813012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35R13012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x ` 35013012010 1.58 1 58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35813012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35R F3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35013012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35013012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35813014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35013014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35013014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 3501'3014006 1.52 1.52 1.75 16 32 1.1 1-1/2 x 314 x 1-1/4 35813014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35013014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 35013014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1,2 350T3014010004 1.44 1.25 1,69 20 40 0.8 1-1/2 x 1 x 3/4 35013014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35013014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 350113014010011 1.94 1.80 1.94 12 21 1.3 1-1/2x 1-1/4 35813014012 1.82 1,82 1.88 12 24 1.4 ii 1 1-1i2 x 1-1/1x 112 35013014012004 1.41 1.34 1.66 16 32 0.9 1-1/2 x 1-1/4 x 3/4 35013014012006 1.52 1.45 1.75 16 32 1.0 1-1/2x 1-1/4x 1 35813014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35013014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 351/13014012014 1.94 1.88 1.94 14 28 1.4 2 x 1/2 35013020004 1.49 1.49 1.88 10 20 1.5 2 x 3/4 350113020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35813020010 1.73 1.73 2.02 8 16 1,7 2 x 1 x 2 35813020010020 2.25 2.02 2.25 8 16 ' 9 2 x 1-1/4 35013020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1'4 x 2 35013020012020 2,25 2.10 2.25 8 16 2.0 2 x 1-1/2 35013020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 12 35013020014004 1.49 1. 1 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35013020014006 1,60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 3,51/130200 14010 1.73 1.65 2.02 8 16 1.5 Allk 2 x 1-1/2 x 1-1/4 35813020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee 1 Size A B C j��; Packing Weight in in in in Inner Master lb �C Part Number 3/4x 1 35813006010 1.45 1,45 1.37 30 60 0.6 1 all 1 x 1-1/4 35813010012 1.67 1.67 1.58 20 40 0.9 � 11 x 1-1/2 35/313010914 1.80 1.80 1.61 13 30 1.0 IF > 1-1/4x 1 x 1-1/2 35813012010014 1.88 1.80 1.82 15 30 1.2 A B �T 11'i4x1-1/2 35�i3012011 1.88 1.88 1.8_ i5 30 1-1/4 x 2 358 13012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35013014012020 2.16 2.10 2.02 10 20 .8 1-1/2x2 35613014020 2.16 2.16 2.02 8 16 1.8 SMITH-COOPER INTERNATIONAL® • 'POLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 112 a '` 1 ucti e ron ittings- ass I I 1 v U.... LITYFLUS- c ® us 41> APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED 0 , Size Part Number A Packing Weight iIiI in in Inner Master Ib _ 3(4 1/2 35043004 1.38 200 400 0.1 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35043014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35083074 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 11111 Size Part Number A Packing Weight Ni A in in Inner Master lb ® 1 x 1/2 3500301000-11. 69 80 160 0.3 1 x 3(4 358G3010006 1.69 60 120 0.4 80 0.6 j���i 1/4 x 3/4 35RC3012006 2.06 40 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master lb 1 x 1/2 35H03010004 1.06 180 360 0.2 mI 1 x 3/4 35HB3010006 1,06 180 360 0.1 j I rA 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1i1-1/2 x 1 35H83014010 1.25 75 150 0.4 1-1/7 x 1-1/1 350133014012 126 75 150 0.3 2 x 1 35HB3020010 1.38 40 80 0.6 2 x 1-1/4 35 183020012 1.38 40 80 0.6 li} 2 x 1-1/2 35HB3020014 1.38 40 80 0.6 1 Fig. 35SP3 -Square Head Plug .. Size Part Number A Packing Weight in in Inner Master lb 1/2 35S43004 0.94 600 1200 0.07 1 It il3/4 35SP3006 1.12 350 700 0.1 b 1 , I IA 1 35S1 3010 1.25 200 400 0.1 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3011 1,44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3- Union with Brass Seat A Size A Packing Weight Part Number aain in Inner Master lb 1 35113010 2.19 20 40 0 m) 1-1/4 35U 3012 2.50 15 30 1.2 20 1-1/2 35113014 2.62 0 1.7 kI 2 35U 3020 3.12 6 12 I 2.4 113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(333)890-4456 • www.srnithcooper.com : I ' Ductile Iron ittings- ass I I 1 - I QUALtlYittIS c ® us 11> APPROVED Fig. 35X 3- Cross LISTED A )I�� Size A Packing Weight Part Number 11/1111in in Inner Master lb _ I A 1 35X 3010 1.50 2C 40 0.9 1-1/4 35X 3012 1.75 12 24 1.4 �_ I _, A 1-1/2 35X 31314 1.94 8 16 1.8 Nil 1 2 35X 3020 2.25 6 12 2.8 B B Fig. 35RX3-Reducing Cross ` '` ' Size A B Packing Weight 'NENE in Part Number in in Inner Master lb 1-1 J4 x 1 35RX3012010 1.67 1.58 II 1 1-1/2 x 1 35RX3014010 15 30 1.2 1.80 1.65 12 24 1.4 �A 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3- Cap Size Part Number A Packing Weight ®1 in in Inner Master lb A 1 i2 35C 3004 0,87 300 600 0.1 ":. 3/4 35C 3006 0.97 200 400 0.1fA- 350 3010 1.16 110 220 0.2 ` 1-1/4 350 3012 1.28 70 140 0.4 I" 1-1/2 350 3014 1.33 50 100 0.5 $: 2 350 3020 1.45 25 50 0.8 2-1/2 35C 3024 1,70 18 36 1.6 Fig. 35BC3-Beam Clamp 1Size A Packing Weight AIIII in 3/8 35BC3003 Part Number in 0.75 Inner 100 Master 200 lb �� 0.3 in 1/2 35BC3004 0.75 80 160 0.5 maim SNIITII-COOPER INTERNATIONAL® • "COLE FREE: 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114 Pipe Hangers OTOLCO- Fig.200 - "Trimline" Adjustable Band Hanger (B-Line Fig. B317ONF) Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) c Fig. 200C- "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) LISTED Fig.200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications Function: For fire sprinkler and other general piping purposes. Knurled -- swivel nut design permits hanger adjustment after installation. � Features: • (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily B , installed around pipe. ! A For hanger with non captured nut order Fig. 200S. zi °, • (21/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it securely in * /> hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) -- Fig.200-1/2.200-3/4 in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and f Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Factory Mutual Engineering Approved (FM) (3/4" (20mm)thru 8" (200mm)). Conforms to Federal Specifications WW-H-171 E &A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, < ;. Type 10. Maximum Temperature: 650°F(343°C) Finish: Pre-Galvanized. Stainless Steel materials will be supplied with (21 hex nuts E in place of a knurl nut. Order By: Figure number and pipe size Designed to meet or exceed requirements of FM DS 2-0. ' Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 ,,,,,,Z, Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) 200-1/2 1/2" (15) -, " 3/8"-16 '"7"--., 31/8" 179.4) 25/8" (66.7) 11 15.0) 200-3/4 3/4' (20) 3/8"-16 31/8' (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8" (66.7) 12 15.5) - 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8' (73.0) 13 (5.9) 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8" (73.0) >I 14 (6.4) 200-2 2' (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9) W 200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8 (104.7) 27 112.3) F, 200-3 3" (75) 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S 200-31/2 31/3' (90) ', 3/8%16 73/8" (187.3151/4" (133.31 34 115.6) 200-4 4' (100) 3/8"-16 73/8" (187.3) 5' (127.0) 35 (16.01 200-5 5" 1125) /';'-'-',-, /2"-13 91/8" (231.8) 61/4" (158.71 „ 66 (30,2) 200-6 6" (150) 1/2"-13 101/8" (257.21 63/4" (171.4) 73 (33.4) 200-8 8" (2001 ,dl'` 1/2"-13 131/8" 1333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Protection Solutions 21 by E `l *Ii Threaded Accessories B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig. 103) - B3205L - Threaded Rod (right& left hand threads) / TL Size Range: 3/8"-16 thru 3"-4 rod Specify Length '` ` Material: Steel ,,--- 1U, Function: Recommended for use as a hanger support in hanger assemblies. -< TL 0 Rod is threaded on both ends with right hand threads of the length shown.Also '� ���� A available with left and right hand threads-specify Fig. B3205L when ordering. �� Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain. Contact B-Line for alternative finishes and materials. Order By: Part number, rod size, length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) lbs. (kN) B3205-3/8 x'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-112 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) B3205-3/4 x'L' 314"-10 3" (76.2) 3230 (14.37) 2530 (11.25) ' 03205-7/8 x'1' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) 83205-1 x1..' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) 83205-11/8 x'L' 11/8%7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205-11/4 x'L' 1114"-7 5" (127.0) 9500 (42.25) 7440 (33.09) 63205-11/2 x'1' 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) B3205-13/4 x'L' 13/4'-5 7 (177,8) 18600 (82.73) 14566 (64.79) B3205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) 83205-21/4 x'L' 21/4"-41/2 9 (228.6) 32300 (143.67) 25295 (112.51) • B3205-2112 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig. 100) Fig. 99 - All Threaded Rod Cut To35) ATR • Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length 01 Material: Steel x`/011" H L Maximum Temperature: 750°F(399°C) o Finish: Plain.Contact B-Line for alternative finishes and materials. cu ch s u • Order By: Part number, rod diameter and finish r- o Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. AIR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) ATR 1/4"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44) ATR 3/8"x 120 99-3/8"x length 16 730 (3.24) 29 (13.15) ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04) ATR 5/8"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37) ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79) AIR 7/8"x 120 99-7/s"x length 9 4480 (19.93) 170 (77.11) ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Hangers&Supports 236 Revised 4/28/2014 by. EA** 4 VERTICAL MOUNT SAMMYS® SAMMYS® for Steel !/sr hs L Ai L`r ,ri . oftam c . -- ----'' -1 quick/ Product Feature's K j k L n0 •Made with Teks®self-drilling fasteners- Pre'dr 1"'quired t- no pre-drilling required. •Install into steel range from 22 gauge-1/2"thicknesses. Saves time from traditional methods. ` irta Reduces installation cost. 4444 � �i7''''....41::':lel : I I , „se ' Quick to install using the Sammy Nut T Driver with an 18V cordless drill/driver. tPart Screw! bUltimate4'4Case .. . ; "aZe Nuri Descriptions Pullout Pultatt - # r, .. . _, — a 114" 8024957` DSTR 100* 1/4-20 x l"TEKS 3 1510(20 ga.) .036"-20 ga 3/16" 25 125 1/4" 8025957 DST 100 114-14 x 1 TEKS 3 446 (20 ga.) .036"-20 ga 3/16" 25 125 1/4" 8026957 BST 150 1/4-14 x 1-1/2"TEKS 3 970(16 ga.), .036"-20 ga 3/16" 25 125 1/4" 8027957 DST 200 1/4-14 x 2"TEKS 3 446 (20 ga.) .036"-20 ga 3/16" 25 125 1/4" 8030957 TEK 500 12-24 x 1-1/2"TEKS 5 3125 (3116") .187"-3/16" 1/2" 25 125 1c?„<> 3/8" 8038957 DSTR 1* 1/4-20 x 1"TEKS 3 1510 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125 — ° v 3/8" 8037957 DSTR 1-1/2* 12-24 x 1-1/2"TEKS S 1510(3/16") 1500 1475 060"-16 ga. 1/2" 25 125 „c-..:,,,,,,,<> 3/8" 8039957 DSTR 516* 5/16-18 x 1-1/4"TEKS 3 2200 (20 ga.) 1500 1475 .036"-20 ga 1/8" 25 125 446(20 ga.) #14 Black 3/8" 8040957 DST 10 114-14 x 1"TEKS 3 .036"-20 ga 3/16" 25 125 970(16 ga.) Nut Driver 446 (20 ga.) Part#8113910 4 3/8" 8077925 DST 10-SS 1/4-14 x 1'TEKS 3 .036"-20 ga 3/16" 25 125 ( 9a) t 970 16 3/8" 8041957' DST 15 1/4-14 x 1-1/2"TEKS 3 4467 (16 ga.) a j .036"-20 ga 3/16" 25 125 ..." 446 (20 ga.) t 3/8" 8078925 DST 15-SS 1/4-14 x 1-1/2"TEKS 3970 446 (16 ga.) 036"-20 ga 3/16" 25 125 446 (20 ga.) r 3/8" 8042957 DST 20 1/4-14 x 2 TEKS"3 .036"-20 ga 3/16" 25 125 970(16 ga.) 3/8" 8043957 DST 25 1/4-14 x 2-1/2"TEKS 3 970 (16 ga) .036"-20 ga 3/16" 25 125 446 (20 ga.) 3/8" 8044957 DST 30 1/4-14 x 3"TEKS 3 970{16 ga.) .036"-20 ga 3/16" 25 125 Q 3/8" 8045957 DST 516 5/16-18 x 1-1/4"TEKS 3 1500 (3/16") 1500 1475 .12Y-1/8" 1/8" 25 125 . Q, 3/8" 8046957 TEK 50 12-24 x 1-1/2"TEKS 5 3125(3/16") 1500 1475 .187'-3/16" 1/2" 25 125 _ 1/2" 8031925 DST 2.0 1/4-14 x 2"TEKS 3 446 (20 ga.) .188"-3/16" 114" 25 125 970 (16 ga.) .; 1/2" 8033925 DSTR 1.0* 1/4-20 x 1"TEKS 3 1510(20 ga.) .036"-20 ga 3/16" 25 125 1/2" 8034925 DSTR 5.16* 5/16-18 x 1-1/4"TEKS 3 2220 (20 ga.) .036"-20 ga 1/8" 25 125 1/2" 8035925 DST 5.16 5/16-18 x 1-1/4"TEKS 3 1500(3/161 .12F-1/8" 1/8" 25 125 `` " 1/2" 8036925 TEK 5.0 12-24 x 1-1/2"TEKS 5 3125 (3/16") .18T-3/16" 1/2" 25 125 _#14 SW Red w Nut Driver *Includes retaining nut Part#8114910 SAMMY Swivel Head® for Steel .--:-....,, . .. , /r r,,, ,,,t , ,T 1 o: r/;,rr,, Product Features t �. •Eliminates distortion of threaded rod in •Installs into angled Z-Purlin;Allows sloped roof applications. threaded rod to hang plumb. `: •Accommodates 3-1/2 x 12 pitch. •Mows 17°deflection from vertical. A 54< Rod Part Screw Ultimate tit. FM Test Min Max Box �,n Approvals Model �" .i- _ Size Number Descriptions Pullout(lbs) Load(lbs) Load(lbs) Thick Thick Qty s v".3J8"', xE 7:1;_.. _ 4 ,, ;;'4 6' ( -. ' v V" 7-„-0:2-,777-- ---3116*- 25/ 1255„. D (Does not comply with ROHS requirements) #14 Black *Includes retaining nutNut Driver SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910 contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.sammysuperscrew.comw 6 •