Report (22) TRANE® REC - Cekx- C1 - -'0/ED JUN .26 2019 CITY OTIGARD 0 BUILDING DIVISION Packaged Gas/Electnc RooftoUnits ...a, ,...,. PrecedentTM 3 - 10Tons - 60 Hz : s'P-4- „.,,., , ',. '''''''' I% , ,,,f 1,.x u ',"' -"Ill 1111111111111 ki e }� � SS y yy 7Jy�p,� ., February 2004 RT PRC006-EN _. 0 TRANE' Introduction r. Wim.,, 21 Ili : .".i ' ,.:, '' ilk- %1 w Precedentm: . . .The sameTrane With its sleek compact cabinet,rounded quality... with added flexibility. corners and beveled top,it may just be Precedent is a flexible line of packaged the most aesthetically pleasing units that covers a wide variety of packaged unit on the planet.And,of applications. course,Precedent carries theTrane Electromechanical controls are available reputation for excellence,quality,and for simpler applications,and for the reliability. more sophisticated, ReliatelTM From simple applications,to the most microprocessor controls. In addition to complex,Precedent has the solution. controls,Precedent offers many other outstanding features and option choices. CO 2004 American Standard Inc.All rights reserved RT-PRC006-EN TRANE'' Contents Introduction Features and Benefits Application Considerations c Selection Procedure 11 Model Number Description 1 General Data 1 z Performance Data -2; Cooling Performance 2; Fan Performance 3E Heat Performance 7z Controls ' 7( Electric Power 7E Dimension and Weights 8E Mechanical Specifications 9 RT-PRC006-EN 3 0 TRAHE° Features and Benefits Easy Access Panels ' 4x Remove two screws for access to the ''„'„ ' v standardized internal components and a r ' wiring. Easy- Adjust Idler Arm f , I 4 With the Easy-Adjust Idler Arm,the belt ,�/�,r. ke and sheaves on belt drive units can be r quickly adjusted without moving the ; mounted fan motor.The result is a major Patented Condenser Coil savings in time and money. Precedent boasts a patented 1+1+1 , f Hybrid coil,permanently gapped for Unit Cabinet Aj ( easy cleaning. The compact cabinet with rounded corners takes up less room and is less y costly to ship. The beveled and ribbed ' top is not only aesthetically pleasing it is t ” desi ned to revent water from oolin Single Point Power 0r A single electrical connection powers the "" unit. Colored And Numbered Wring You save time and money tracing wires f 5 * and diagnosing the unit I Convertible Units f The units ship in a downflow Sloped Drain Pans r = configuration.They can be easily Every Precedent unit has anon- converted to horizontal by simply corrosive, removable,double sloped moving two panels. drain pan that's easy to clean and ,` r reversible to allow installation of drain Units come complete with horizontal trap on either side of the unit. Compressors duct flanges so the contractor doesn't Through the Base Condensate have to field fabricate them.These g PrecedentTM contains the best duct flanges are a time and cost saver. Every unit includes provisions for compressor technology available to thrugh the base condensate drain achieve the highest possible �� connections. This allows the drain to performance. Our compressor line be connected through the roof curb includes Trane built Climatuff® ;�,�,9instead of a roof penetration. reciprocating and scrolls. '/,44•-.'! " "'A Easy Access Panels Foil-Faced Insulation All panels in the Evaporator section of Easy access panels reduce the number of the unit have cleanable foil faced possible water entry points. , # •insulation.All edges are either Low Ambient Cooling i captured r sealed to ensure no fibers All Precedent microprocessor units have { get into the airstream. cooling capabilities down to 0°F as standard. Electromechanical models ` have cooling capabilites to 40°F as built, or to 0°F by adding the optional low Unit Base ambient control (Frostat). For added water integrity,Precedent has a raised 1'/S"lip around the unit's downflow supply and return to prevent water from blowing into the ductwork. 4 RT-PRC006-EN TRANE® Features and Benefits Standardized Components Progressive Tubular Heat Exchanger • Components are placed in the same The compact cabinet features a tubular location on all PrecedentTM units. heat exchanger in low,medium and high Familiarize yourself with one Precedent heat capacities. and you are familiar with every The heat exchanger is fabricated using Precedent. stainless steel burners and corrosion- IIrresistant aluminized steel tubes as '' standard on all models.It has an induced draft blower to pull the gas mixture through the burner tubes. The heater has a direct spark ignition system which doubles as a safety device to prove the ''./ ie 41,1'it 4' F flame. Gas electric Precedent models exceed all California seasonal efficiency ` requirements.They also perform better • than required to meet the California NOx emission requirments. Flexible Applications Easy Access Low Voltage Terminal Board • Only two roof curbs for the 3-10 ton Precedent line. . .simplifies curb Precedents Low Voltage Terminal Board selection. is external to the electrical control • Standard or High Efficiency Cooling. cabinet. It is extremely easy to test • Electromechanical or ReliaTel operation of all unit functions. This is microprocessor controls to meet either another cost and time saving installation the simple or the more complex feature. application. • Low,medium or high gas heat capacities. f , • Airflow is outstanding.The Precedent can replace an older machine with old f ductwork and,in many cases,improve comfort throw h better air distribution. • Belt or direct drive —standard or oversized supply fan motors meet a wide airflow range. Low Voltage Connections • Precedent offers ultimate flexibility. The wiring of the low voltage Options and components are not pre connections to the unit and the zone packaged at the factory. Units are built sensors is as simple as 1-1,2t-2,and 3-3. to order in our standard"shortest in This simplified system makes it easy for the industry"ship cycle time. the installer to wire. Single- ry Single-sideSide serviceSeice is standard on all Precedent units. 5 RT-PRC006-EN TRAIVE° Features and Benefits • Eliminates the need for field-installed components with its built-in anti-short- �, � ' � cycle timer,time delay relay and minimum "on"time controls.These t �� ' tool t � controls are factory tested to assure proper operation. • Requires no special tools to run the 44' Precedent unit through its paces 4 4N, � during testing. Simply place a jumper betweenTest 1 andTest 2 terminals on the Low VoltageTerminal Board and the unit will walk through its Micro Controls operational steps.The unit automatically returns control to the Several years ago,Trane was the first to zone sensor after stepping through the introduce microprocessor controls into test mode a single time,even if the the Light Commercial Market.That jumper is left on the unit. design,along with immeasurable experience,has provided the technology • As long as the unit has power and the forTrane's second-generation ReliaTel LED is lit,the Micro is operational.The microprocessor controls. light indicates that the Micro is functioning properly. ReliaTel Micro: • Features expanded diagnostic • Provides unit control for heating, capabilities when used withTrane's cooling,and ventilating by utilizing Integrated Comfort Systems. input from sensors that measure • As an energy benefit,softens electrical outdoor and indoor temperature. "spikes"by staging on fans, compressors and heaters. • Improves quality and reliability through the use of time tested • The Intelligent Fallback or Adaptive microprocessor controls and logic. Control is a benefit to the building occupant. If a component goes astray, •Prevents the unit from short cycling, the unit will continue to operate at considerably improving compressor predetermined temperature set points. life. • Intelligent Anticipation is a standard • Ensures that the compressor will run feature of the Micro. Functioning for a specific amount of time,which constantly,the Micro and zone sensors allows oil to return for betterwork together in harmony,to provide lubrication,enhancing the reliability of tight comfort control. the compressor. Electromechanical Controls • Reduces the number of components required to operate the unit,thereby ▪ For the simpler job that does not reducing possibilities for component require a building automation system, failure. or expanded diagnostics capabilities, Precedent offers electromechanical controls.This 24-volt control includes the control transformer and contactor pressure lugs for power wiring. 6 RT-PRC006-EN TRANE® Features and Benefits Factory-installed Options Economizer Trane Communication Interface Dehumidification(Hot Gas Reheat) Equipped with either dry bulb,reference Available factory or field-installed.This Option or comparative enthalpy sensing,this module,when applied with ReliaTelTM feature provides free cooling as the easily interfaces" nteerfaces withTrane's Integrated This option allows for increased outdoor air ventilation. It reduces humidity levels outdoor temperature and/or humidity ComfortTM System. decreases. Economizers,correctly while increasing comfort level in the air installed,offer valuable energy savings. space.Cooling can operate without a Factory-installed economizers save time . demand for dehumidification.The hot and ensure proper installation. �f : gas reheat coil is designed to deliver maximum reheat temperatures and Through the Base Utility Access pivot to allow for easyaccess cleaning.9• Factory provided through the base '��/� . openings simplify electrical wiring i and gas piping. Because these utility � .: openings frequently minimize the � �, number of roof penetrations,the integrity f� of roofing materials is enhanced. Phase Monitor q l° Phase monitor shall provide 100% , protection for motors and compressors 4',Til':1-1A':7:7/A4 against problems caused by phase loss, of �� phase imbalance,and phase reversal. 9 Phase monitor is equipped with an LED that provides an ON or FAULT indicator. Clogged Filter/Fan Fail Switches These sensors allow a zone sensor Hinged Access Doors ��' service light or Integrated Comfort , These doors permit easy access to the System to indicate a dirty filter or a fan + filter,fan/heat,and compressor/control that's not working.The field installation � �, sections.They reduce the potential roof charges for these valuable feedback damage from screws or sharp access devices often eliminate them from door corners. consideration.Factory installation can make such features a good investment. Unit Mounted Disconnect or Circuit Breaker Codes require a method of assured unit r F. shutdown for servicing.Field-installed disconnects sometimes interfere with ��' service access.Factoryinstallation of unit I „ disconnects reduces costs,assures y � a proper mounting and provides the f� % opportunity to upgrade to unit circuit /i ,7%"”` "J * '� breaker protection. Unit Disconnect Switch Convenience Outlet RT-PRC006-EN 7 TRANE' Features and Benefits The following options round-out the complete line of PrecedentTM' options: — 0-50%Manual or Motorized Outside Air — Electric Heaters — Discharge Air Sensor — Hail Protection Quality Coil Guards — Supply and/or Return Smoke Detectors — High Pressure Cutout (standard on 3 phase models with scroll compressor and all standard efficiency 3-ton models) — Thermal Expansion Valve for a wider range of applications — Wide array of Zone Sensors and Thermostats — Liquid Propane Conversion Kits — Factory built Roof Curb — Power Exhaust — LonTalk Communications Interface One of Our Finest Assets: Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much more Precedent has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers,its airflow performance is outstanding. Precedent...The same Trane qualiity...with added flexibility. 8 RT-PRC006-EN TRANE° Features and Benefits Quality And ReliabilityTesting • We perform a 100%coil leak test at the • All PrecedentTM designs were factory.The evaporator and condenser rigorously rain tested at the factory to coils are leak tested at 200 psig and ensure water integrity. pressure tested to 450 psig. • Actual shipping tests were performed • All parts are inspected at the point of to determine packaging requirements. final assembly. Sub-standard parts are Units were test shipped around the identified and rejected immediately. country to determine the best • The requirement for cycle testing of packaging. heat exchangers is 10,000 cycles by • Factory shake and drop tests were ANSI Z21.47. This is the standard used as part of the package design required by both UL and AGA for cycle process to help assure that the unit test requirments. Trane requires the arrives at the job site in top condition. design to be tested to 21/2 times this current standard. • Rigging tests include lifting a unit into the air and letting it drop one foot, • Every unit receives a 100%unit run test assuring that the lifting lugs and rails before leaving the production line to hold up under stress. make sure it lives up to rigorousTrane requirements. We test designs at our factory not on our customers! VariTracTM I Roof Top Unit VariTrac 7_ WhenTrane's changeover VAV System �� 1 for light commercial applications is coupled with Precedent,it provides the - latest in technological advances for - comfort management systems and can allow thermostat control in every zone served by VariTrac. l 11_41 RT-PRC006-EN 9 TRANE® Application Considerations Application of this product should be NOTE:THE EFFECTIVENESS OF within the cataloged airflow and cooling BAROMETRIC RELIEF DAMPER considerations. DURING ECONOMIZING OPERATION Low Ambient Cooling IS SYSTEM RELATED. PRESSURE DROP OFTHE RETURN AIR SYSTEM The Precedent' line features,as SHOULD BE CONSIDEREDTO standard,low ambient cooling down to CONTROL BUILDING 0°F with the ReliaTelTM microprocessor PRESSURIZATION. controls and 40°F with electromechanical controls. Contact Condensate Trap your localTrane Representative for more The evaporator is a draw-thru assistance with low ambient cooling configuration.A trap must be field applications. provided prior to start-up on the Barometric Relief cooling cycle. This product offers an optional Clearance Requirements barometric relief damper for use in The recommended clearances conjunction with economizer option. identified with unit dimensions should This option consists of gravity dampers be maintained to assure adequate which open with increased pressure.As service,maximum capacity and peak the building air pressure increases,the operating efficiency.Actual clearances pressure in the unit return air section which appear inadequate should be also increases,opening the dampers and reviewed with the localTrane sales relieving the conditioned space. personnel. Heating Operation Unit Pitch The heat exchanger is manufactured These units have reversible sloped with aluminized steel.To prevent condensate drain pans. Units must be condensation within the heat exchanger, installed level;any unit slope must be do not exceed 50%outside air. toward side of unit where condensate drain is connected. 10 RT-PRC006-EN TRANE' Selection Procedures Cooling Capacity Step 4 Heating Capacity Step 1 In order to select the correct unit which Step 1 — Calculate the building heating Calculate the building's total and sensible meets the building's requirements,the load using theTrane calculation form or cooling loads at design conditions.Use fan motor heat must be deducted from other standard accepted method. theTrane calculation methods or anythe gross cooling capacity.The amount of heat that the fan motor generates is Step 2— Size the system heating other standard accepted method. capacity to match the calculated dependent on the effort by the motor building heating load.The following are cfm and static pressure.To determine the buildingheatingrequirements:follo Factors used in unit selection: total unit static pressure: A a. Total heating load of 60.0 MBh Total Cooling Load:58 MBh External Static(duct system) b. 2000 cfm 13 0.52 wg c. Fuel-Natural gas Sensible Cooling Load:40 MBh For the YSC060A4 there are three C Standard Filter 1 in. 0.06 wg heating capacities available,60 MBh,80 Airflow:2000 cfm fromTable PD 89 MBh and 130 MBh input models shown D Economizer 0.18 wg inTable PD-91.The output capacities of Electrical Characteristics: 460/60/3 (100%Outside Air) fromTable these furnaces are 48 MBh,64 MBh E PD 89 and 104 MBh respectively.The medium Summer Design Conditions:Entering heat model with 64 MBh best matches Evaporator Coil:80 DB,67WB Outdoor the building requirements, indicating a Ambient:95 Total Static Pressure 0.76 wg YHC060A4*M should be selected. F Air Delivery Selection External Static Pressure:0.52 in.wg G Note:The Evaporator Fan Performance External static pressure drop through Downflow Configuration Table PD 64 has deducted the pressure the air distribution system has been H drop for a 1 in.filter already in the unit calculated to be 0.7 inches of water. High Efficiency (see note belowTable PD 64).Therefore, Enter Table PD-64 for aYHC060A4*M at the actual total static pressure is 0.76- 2000 cfm and 0.70 static pressure.The Economizer 0.06(fromTable PD 89)=0.70 wg. standard motor will give the desired airflow with 1.07 bhp and 1094 rpm. Step 2 With 2000 cfm and 0.70 wg. Accessory Selection As a starting point,a rough determination Table PD-64 shows 1.07 bhp for this unit. Select accessories needed to must be made of the size of the unit.The Note below the table gives a formula to accommodate the application. final selection will be made after calculate Fan Motor Heat, examining the performance at the given 2.829 x bhp+.4024=MBH. conditions.Divide the total cooling load by 2.829 x 1.07+.4024=3.43 MBH. nominal BTUH per ton(12 MBh per ton); then round up to the nearest unit size. Now subtract the fan motor heat from 58 MBh/12 MBh=approx.5 tons the gross cooling capacity of the unit: NetTotal Cooling Capacity Step 3 =62.4 MBH- 3.43=58.97 MBH. Table PD-13 shows that aYHC060A4 has Net Sensible Cooling Capacity a gross cooling capacity of 62.4 MBh and =48.4 MBH-3.43=44.97 MBH. 48.4 MBh sensible capacity at 2000 cfm and 95 DB outdoor ambient with 80 DB, Step 5 67WB air entering the evaporator. If the performance will not meet the required load of the building's total or To Find Capacity at Intermediate sensible cooling load,try a selection at Conditions Not in theTable the next higher size unit. When the design conditions are between two numbers that are in the capacity table,interpolation is required to approximate the capacity.Note: Extrapolation outside of the table conditions is not recommended. RT-PRC006-EN 11 TRAIIE® Selection Procedure Dehumidification Selection Step 3:Determine reheat Typical 10 tonYHC120A temperature rise 3200 cfmTotal Supply airflow Go to PD-92 for reheat temperature rise: 1280 cfm Outside Air(40%) 21 1920 cfm Return Air 0.35" External Static Pressure OA Conditions OA 66°F DB, Part load day and raining 67°F w6 68°F dbRA• 75°F DB, ' ' ' 4 67°F wb 52%RH MA' 72.2°F DB RA conditions 65°F w6 10A 75°F db SAS 53°F DB o • ' 63°F wb SA 74°F DB itA• Step 1: Determine the mixed/ "n entering air condition(MA) S REHEAT —* Ag , MA=(%outside air*outside air dry-bulb temperature)+(% return air*return air . ; dry-bulb temperature) ,A '° • in Nit ari `* es `• elf "' MA= (0.40°*68°F)+ (0.60*75°F) Chart C-1 t � MA=72.20 F db Note:Repeat for wet-bulb temperature(wb). Plot on psychrometric chart. Note:Reheat temperature rise is based Step 5:Determine static pressure MA' on supply airflow and leaving evaporator drop add for reheat 72.2°F db coil temperature. Table PD-61 shows a static pressure drop 65°F wb of 0.09"wc 0.35"+0.09"=0.5"wc Step 4:Determine leaving unit Step 2 Determine leaving unit temperature Table PD-54 indicates that a standard temperature Reheat temperature(obtained in step 3) motor and field installed low static drive Leaving UnitTemperature=SA' +SA' kit is needed for this airflow and static Utilize theTOPSST" program to 21°F db+53°F=74°F db pressure range. determine the leaving unit temperature. SA=74°F 53.8°F db Consider Chart C-1.If the space relative 52.7°F wb humidity is equal to or above the space 51.8°F dp relative humidity setpoint,the Dehumidification Option will: • Energize compressor or both compressors(2 stage compressor units). • Hot gas reheat valve is energized and hot gas is diverted to the reheat coil. • Dehumidification/reheat is terminated when space humidity is reduced to 5% below relative humidity setpoint. At MA,air enters the RTU.The RTU filters, cools,and dehumidifies the air as it moves through the evaporator coil.Air leaves the evaporator coil saturated at the preset dew point condition(SA')and is reheated by the hot gas reheat coil to deliver 74°F(SA)supply air to the space. 12 RT-PRC006-EN TRANE��� Model 0 Number Description YSC 036 A 3 R L A ** C 0 0 0 C 1 0 0 0 1 A 1 1 2 3 4,5,6 7 8 9 10 11 12,1314 15 16 17 18 19 20 21 22 23 24 25 DIGIT 1 - Unit Function DIGIT 14-Fresh Air Selection DIGIT 20-Convenience Outlet Y = DX Cooling,Gas Heat 0 = No Fresh Air 0 = No Convenience Outlet A = Manual Outside Air Damper 0-50% A = Unpowered Convenience Outlet DIGIT 2-Efficiency B = Motorized Outside Air Damper 0-50% B = Powered Convenience Outlet S = Standard Efficiency C = Economizer,Dry Bulb 0-100% (3 phase only) without Barometric Relief H = High Efficiency D = Economizer,Dry Bulb 0-100% DIGIT 21-Communications Options with Barometric Relief 0 = No Communications Interface DIGIT3-Airflow E = Economizer,Reference Enthalpy C = Convertible 0-100%without Barometric Relief 1 = Trane Communications Interface F = Economizer,Reference Enthalpy 2 = LonTalk® Communications Interface DIGITS 4,5,6-Nominal Gross Cooling0-100%with Barometric Relief 3 = Novar 2024 Controls 4 = Novar 3051 Controls G = Economizer,Comparative Enthalpy Capacity(MBh) 0-100%without Barometric Relief 036 = 3-Ton H = Economizer,Comparative Enthalpy DIGIT 22-Refilgeration System Option 048 = 4-Ton 0-100%with Barometric Relief 0 = Standard Refrigeration System 060 = 5-Ton A = Thermal Expansion Valve(TXV) 072 = 6-Ton DIGIT 15-Supply Fan/Drive Type/Motor B = Dehumidification(Hot Gas Reheat Coil) 090 = 71/2-Ton,Single Compressor 092 = 71/2-Ton,Dual Compressors 0 = Standard Drive 102 = 81/2-Ton 1 = Oversized Motor DIGIT 23 Refrigeration Controls 120 = 10-Ton 2 = Optional Belt Drive Motor 0 = No Refrigeration Control 1 = High Pressure Control III DIGIT 7-Major Design Sequence DIGIT 16-Hinged Service AccessFilters 2 = Frostat 0 = Standard Panels/Standard Filters 3 = Crankcase Heater A = First 4 = High Pressure Control and Frostat A = Hinged Access Panels/Standard Filters 5 = High Pressure Control and Crankcase B = Standard Panels/2"Pleated Filters DIGIT8-UnitVoltageC = Hinged Access Panels/2"Pleated Filters Heater 1 = 208-230/60/1 6 = Frostat and Crankcase Heater 3 = 208-230/60/3 7 = High Pressure Control,Frostat and 4 = 460/60/3 DIGIT 17-Condenser Coil Protection Crankcase Heater W= 575/60/3 0 = Standard Coil K = 380/60/3 1 = Standard Coil with Hail Guard DIGIT 24-Smoke Detector 2 = Epoxy Coated Condenser Coil 0 = No Smoke Detector DIGIT -Unit Controls 3 = Epoxy Coated Condenser Coil with A = Return Air Smoke Detector Hail Guard B = Supply Air Smoke Detector E = Electromechanical C = Supply and Return Air Smoke R = ReliaTel Microprocessor DIGIT 18-Through the Base Provisions Detectors DIGIT 10-Heating Capacity 0 = NoThrough the Base Provisions A = Through the Base Electric DIGIT 25-Monitoring Controls L = Low B = Through the Base Gas Piping 0 M= Medium _ C = Through the Base Electric and Gas = Co Meditotng Control 1 H = High Piping 1 = Clogged Filter Switch 2 = Fan Failure Switch 3 = DischargeAir Sensing Tube DIGIT 11-Minor Design Sequence DIGIT 19 - Disconnect/Circuit Breaker/ 4 = Clogged Filter Switch and Fan Fail A = First Sequence Phase Monitor(3 phase only) Switch 0 = No Disconnect/NoCircuit Breaker/No 5 = Clogged Filter Switch and Discharge DIGITS 12, 13-Service Sequence Phase Monitor Air SensingTube **= Factory Assigned 1 = Unit Mounted Non-Fused Disconnect 6 = Fan Fail Switch and Discharge Air 2 = Unit Mounted Circuit Breaker Sensing Tube 3 = Phase Monitor 7 = Clogged Filter and Fan Fail Switches 4 = Phase Monitor & Non-Fused and Discharge Air SensingTube Disconnect Switch 8 = Novar Return Air Sensor 5 = Phase Monitor & Circuit Breaker Example: Model number YSC036A3RLA**C000C 10001 A10 describes a unit with the following characteristics:DX Cooling with natural gas heating,3 ton nominal cooling capacity,208-230/60/3 power supply, ReliaTelr^^controls,low heat model.0-100%dry bulb economizer without barometric relief,standard direct drive motor,standard access panels,standard condenser coil with no coil protection, through the base electric and gas access,non-fused disconnect,no convenience outlet or communications interface,standard refrigeration coil,high pressure control,return air smoke detector,and clogged filter switch. RT-PRC006-EN 13 TRAIVE' General OF Data . ,f t -- - Table GD-1 - General Data 3-Ton Convertible Units 4-Ton Convertible Units YSC036A1 YSC036A3,A4,AW YSC048A1 YSC048A3,A4,AW Cooling Performance' Gross Cooling Capacity 37,400 37,400 50,300 49,200 SEER2 10.5 10.7 10.1 10.0 Nominal CFM/ARI Rated CFM 1,200/1,200 1,200/1,200 1,600/1,600 1,600/1,600 ARI Net Cooling Capacity 36,000 36,000 48,000 47,000 System Power(ION) 3.91 3.79 5.28 5.40 Heating Performance° Heating Models Low Medium High Low Medium High Low Medium High Low Medium High Heating Input(Btu) 60,000 80,000 120,000 60,000 80,000 120,000 60,000 80,000 120,000 60,000 80,000 120,000 Heating Output(Btu) 47,000 63,000 95,000 48,000 64,000 96,000 47,000 63,000 95,000 48,000 64,000 96,000 ed AFUE%5 80 80 80 81 81 81 80 80 80 81 81 81 Steady State Efficiency(%) 80 80 80 81 81 81 80 80 80 81 81 81 No.Burners 2 2 3 2 2 3 2 2 3 2 2 3 No.Stages 1 1 1 1 1 1 1 1 1 1 1 1 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Compressor No./Type 1/Climatuff Hermetic 1/Climatuff Hermetic 1/Climatuff Scroll 1/Climatuff Scroll Outdoor Sound Rating(dB)6 83 83 86 82 Outdoor Coil-Type Lanced Lanced Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 0.3125 0.3125 Face Area(sq ft) 719 7.19 6.17 9.59 Rows/FPI 2/17 2/17 2/17 1/17 Indoor Coil-Type Lanced Lanced Lanced Lanced Tube Size(in.) 0.3125 0.3125 0.3125 .3125 Face Area(sq ft) 5.67 5.67 6.68 6.17 Rows/FPI 2/16 2/16 3/16 3/16 Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/3/4 NPT 1/3/4 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller Propeller Propeller No.Used/Diameter(in.) 1/22 1/22 1/22 1/22 DriveType/No.Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM 2,550 2,550 2,850 3,610 No.Motors/HP 1/0.20 1/0.20 1/0.33 1/0.33 Motor RPM 1,075 1,075 1,075 1,075 Direct Drive Indoor Fan-Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/10 x 10 1/10 x 10 1/11 x 11 1/11 x 11 DriveType/No.Speeds Direct/2 {3irect/2 D6tict/2 Direct/2 No.Motors 1 1 1 1 Motor HP(Standard/Oversized) 0.33/0.50 0.33/0.50 0.60/0.80 0.60/0.80 Motor RPM(Standard/Oversized) 950/1,1009 930/1,1008 1,000/1,100 1,000/1,100 Motor Frame Size(Standard/Oversized) 48/48 48/48 48/48 48/48 14 RT-PRC006-EN TRANE' General Data Table GD-1 — Continued 3-Ton Convertible Units 4-Ton Convertible Units YSC036A1 YSC036A3,A4,AW YSC048A1 YSC048A3,A4,AW Belt Drive Indoor Fan-Type — FC Centrifugal — No.Used/Diameter(in.) — 1/11 x 11 — 1/11 x 11 DriveType/No.Speeds — Belt/Variable Sheave — No.Motors — 1 — 1 Motor HP(Standard/Oversized) — 1.00/— — 1.00/— Motor RPM(Standard/Oversized) — 1,750/— — 1,750/— Motor Frame Size(Standard/Oversized) — 56/— — 56/— Filters-Type Furnished 10 Throwaway Throwaway Throwaway Throwaway (No.)Size Recommended (2)20 x 25 x 18 (2)20 x 25 x 18 (2)20 x 25 x 18 (2)20 x 25 x 18 Refrigerant Charge(Lbs of R-22)7 3.8 3.8 4.4 3.8 NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm.Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,which is based on ARI Standard 210/240 exceptAK l380V/60 Hz). 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.Fora more precise value,see unit nameplate and service instructions. 8. 20 x 25 filter on medium and low heat models.20 x 30 filter on high heat models 9.Motor RPM shown is low speed.High speed RPM is 1,060/1,145. 10.Optional 2"pleated filters also available. • RT-PRC006-EN 15 0 TRANE' General ' Tons) Data . = alli'd "Eft: t Table GD-2— General Data 5-Ton Convertible 6-Ton Convertible YSC060A1 YSC060A3,A4,AW,AK YSC072A3,A4,AW,AK Cooling Performance' Gross Cooling Capacity 63,100 63,100 72,000 SEERIEER2 9.90/— 10.20/— —/10.212 Nominal CFM/ARI Rated CFM 2,000/2,000 2,000/2,000 2,400/2,100 ARI Net Cooling Capacity 60,000 60,000 69,000 Integrated Part Load Value' — — — System Power(KW) 6.86 6.78 6.77 Heating Perfonnance4 Heating Models Low Medium High Low Medium13 High Low Medium" High Heating Input(Btu) 60,000 80,000 130,000 60,000 80,000 130,000 80,000 120,000 150,000 Heating Output(Btu) 47,000 63,000 103,000 48,000 64,000 104,000 64,800 97,200 121,500 AFUE%5 81 81 80 81 81 80 81 81 81 Steady State Efficiency(%) 81 81 80 81 81 80 81 81 81 No.Burners 2 2 3 2 2 3 2 3 3 No.Stages 1 1 1 1 1 1 1 1 2 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 Compressor No./ Type 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll Outdoor Sound Rating(dB)6 84 84 88 Outdoor Coil-Type Lanced Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 0.3125 Face Area(sq ft) 8.81 8.81 13.88 Rows/FPI 2/17 2/17 2/17 Indoor Coil-Type Lanced Lanced Lanced Tube Size(in.) 0.3125 0.3125 0.3125 Face Area(sq ft) 5.00 5.00 9.89 Rows/FPI 3/16 3/16 2/16 Refrigerant Control Short Orifice Short Orifice Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/34 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller Propeller No.Used/Diameter(in.) 1/22 1/22 1/26 DriveType/No.Speeds Direct/1 Direct/1 Direct/1 CFM 3,470 3,470 6,100 No.Motors/HP 1/0.33 1/0.3315 1/0.7014 Motor RPM 1075 1,075 1,075 Direct Drive Indoor Fan-Type FC Centrifugal FC Centrifugal N/A No.Used/Diameter(in.) 1/11 x 116 1/11 x_118 N/A Drive Type/No.Speeds Direct/2 Direct/2 id/A No.Motors 1 1 N/A Motor HP(Standard/Oversized) 0.90/1.00 0.90/1.0016 N/A Motor RPM(Standard/Oversized) 985/1,0809 985/1,080' N/A Motor Frame Size(Standard/Oversized) 48/48 48/48 N/A 16 RT-PRC006-EN TRANS" General Data � $ Table GD-2 - Continued 5-Ton Convertible 6-Ton Convertible YSCO60A1 YSC060A3,A4,AW,AK YSC072A3,A4,AW,AK Belt Drive Indoor Fan-Type - FC Centrifugal FC Centrifugal No.Used/Diameter(in.) - 1/11 x 11 1/12 x 12 DriveType/No.Speeds - BeltNariable Sheave BeltNariable Sheave No.Motors - 1 1 Motor HP(Standard/Oversized) - 1.00/- 1.00/2.0017 Motor RPM(Standard/Oversized) - 1,750/- 1,750/1,750 Motor Frame Size(Standard/Oversized) - 48/- 56/56 Fitters-Type Furnished 11 Throwaway Throwaway Throwaway (No.)Size Recommended (2)20 x 25 x 110 (2)20 x 25 x 110 (4)16 x 25 x 2 Refrigerant Charge(Lbs of R-22)7 4.7 4.9 7.1 NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm.Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK(380V/60 Hz)units. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 8. YSC060A1,3,4,W Oversized Motor and YSCO6OAK Standard Motor Fan Diameter is 12 x 11. 9. Motor RPM shown is low speed.High speed RPM is 1100/1135. 10.Filter size shown is for low and medium heat models.High heat model filter size recommended is 20 x 30 x 1. 11.Optional 2"pleated filters also available. 12.YSC072A when used in a horizontal application has an EER of 10.1 and System Power(kW)of 6.83. 13.Medium heat is not available for AK(380V/60 Hz)units. 14.Outdoor motor is 0.75 hp for AK(380V/60 Hz)units. 15.Outdoor motor is 0.40 hp for AK(380V/60 Hz)units. 16.Standard Motor is 1.00 hp for YSCO6OAK(380V/60 Hz)units. 17.Standard Motor is 2.00 hp for the YSC072AK(380V/60 Hz)units. RT PRC006-EN 17 0 TRAIVE" General Data . Table GD-3 — General Data 71/2-Ton Convertible 81/2-Ton Convertible Single Compressor Dual Compressor YSC090A3,A4,AW,AK YSC092A3,A4,AW YSC102A3,A4,AW,AK Cooling Performance' Gross Cooling Capacity 95,000 92,000 105,000 EER2 10.1 10.48 10.1 Nominal CFM/ARI Rated CFM 3,000/2,625 3,000/2,625 3,400/3,000 ARI Net Cooling Capacity 90,000 87,000 100,0009 Integrated Part Load Value3 — 11.08 11.89 System Power(KW) 8.91 8.378 9.99 Heating Performance Heating Models Low Medium" High Low Medium High Low Medium" High Heating Input(Btu) 120,000 150,000 200,000 120,000 150,000 200,000 120,000 150,000 200,000 Heating Output(Btu) 97,200 121,500 162000 97,200 121,500 162000 97,200 121,500 162000 AFUEOS 81 81 81 81 81 81 81 81 81 Steady State Efficiency(%) 81 81 80 81 81 80 81 81 81 No.Burners 3 3 4 3 3 4 3 3 4 No.Stages 1 2 2 1 2 2 1 2 2 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 3/4 3/4 1/2 3/4 3/4 1/2 3/4 3/4 Compressor No./ Type 1/Trane Scroll 2/Climatuff Scrolls 2/Climatuff Scrolls Outdoor Sound Rating(dB)6 90 87 86 Outdoor Coil-Type Lanced Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 0.3125 Face Area(sq ft) 170 17.0 19.83 Rows/FPI 3/17 2/17 2/17 Indoor Coil-Type Lanced Lanced Lanced Tube Size(in.) 0.3125 0.3125 0.3125 Face Area(sq ft) 9.89 9.89 12.36 Rows/FPI 3/16 3/16 3/16 Refrigerant Control Short Orifice Short Orifice Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/3/4 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller Propeller No.Used/Diameter(in.) 1/26 1/26 1/26 DriveType/No.Speeds Direct/1 Direct/1 Direct/1 CFM 6200 6500 7100 No. Motors/HP 1/0.7012 1/0.70 1/0.75 Motor RPM 1075 1,075 1,075 18 RT-PRC006-EN TRANE" General 4 Data standard n Table GD-3 — Continued 71/2-Ton Convertible 81/2-Ton Convertible Single Compressor Dual Compressor YSC090A3,A4,AW,AK YSC092A3,A4,AW YSC102A3,A4,AW,AK Belt Drive Indoor Fan-Type FC Centrifugal FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/12 x 12 1/12 x 12 1/15 x 15 DriveType/No.Speeds BeltNariable Sheave BeltNariable Sheave BeltNariable Sheave No.Motors 1 1 1 Motor HP(Standard/Oversized) 2.00/3.00 2.00/3.00 2.00/3.00 Motor RPM(Standard/Oversized) 1,750/1,750 1,750/1,750 1,750/1,750 Motor Frame Size(Standard/Oversized) 56/56 56/56 56/56 Filters-Type Furnished 10 Throwaway Throwaway Throwaway (No.)Size Recommended (4)16 x 25 x 2 (4)16 x 25 x 2 (4)20 x 25 x 2 Refrigerant Charge(Lbs of R-22)7 11.9 6.2 Circuit 1/3.4 Circuit 2 7.9 Circuit 1/4.0 Circuit 2 NOTES: 1.Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm.Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,which is based on ARI Standard 210/240 except AK(380V/60 Hz)units. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 8. YSC092Awhen applied in a horizontal configuration has a 10.1 EER,10.7 Integrated Part Load Value,and 8.61 System Power(KW). 9. YSC102A when applied in horizontal configuration has an 11.3 Integrated Part Load Value,9.8 System Power IKVV)and 99,000 ARI Net Cooling Capacity. 10.Optional 2"pleated filters also available. 11.Medium heat is not available for AK(380V/60 Hz)units. 12.Outdoor motor is 0.75 hp for AK(380V/60 Hz)units. RT-PRC006-EN 19 TRANE® General ( sRs- Data Table GD-4 — General Data 10-Ton Convertible YSC120A3,A4,AW,AK Cooling Performance' Gross Cooling Capacity 118,000 EER2 10.28 Nominal CFM/ARI Rated CFM 4,000/3,200 ARI Net Cooling Capacity 114,0008 Integrated Part Load Value' 11.38 System Power(KW) 11.188 Heating Performance° Heating Models Low Medium10 High Heating Input(Btu) 150,000 200,000 250,000 Heating Output(Btu) 121,500 162,000 202,500 AFUE%5 81 81 81 Steady State Efficiency(%) 81 81 81 No. Burners 3 4 5 No.Stages 2 2 2 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 LP(minimum/maximum) 10.0/14.0 Gas Connection Pipe Size(in.) 3/4 3/4 3/4 Compressor No./Type 2/Climatuff Scrolls Outdoor Sound Rating(dB)' 86 Outdoor Coil-Type Lanced Tube Size(in.)OD 0.3125 Face Area(sq ft) 19.83 Rows/FPI 2/17 Indoor Coil-Type Lanced Tube Size(in.) 0.3125 Face Area(sq ft) 12.36 Rows/FPI 4/16 Refrigerant Control Short Orifice Drain Connection No./Size(in.) 13/4NPT 20 RT-PRC006-EN 0 TRANE' General Data Table GD-4 — Continued 10-Ton Convertible YSC120A3,A4,AW,AK Outdoor Fan-Type Propeller No.Used/Diameter(in.) 1/26 DriveType/No.Speeds Direct/1 CFM 7000 No.Motors/HP 1/0.75 Motor RPM 1,075 Belt Drive Indoor Fan-Type FC Centrifugal No.Used/Diameter(in.) 1/15 x 15 Drive Type/No.Speeds Belt/Variable Sheave No.Motors 1 Motor HP(Standard/Oversized) 3.00/5.00 Motor RPM(Standard/Oversized) 1,750/3,450 Motor Frame Size(Standard/Oversized) 56/56 Filters-Type Furnished 9 Throwaway (No.)Size Recommended (4)20 x 25 x 2 Refrigerant Charge(Lbs of R-22)7 7.2 Circuit 1/5.3 Circuit 2 NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,which is based on ARI Standard 210/240 except AK(380V/60 Hz). 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. a Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 8. YSC120Awhen applied in a horizontal configuration hasa 10.1 EER,112,000 ARI Net Cooling Capacity,10.7 Integrated Part Load Value and 11.09 System Power(KW). 9. Optional 2"pleated filters also available. 10.Medium heat is not available for AK(380V/60 Hz)units. RT-PRC006-EN 21 TRANE' General Table GD-5 — General Data 3-Ton Convertible Units 4-Ton Convertible Units YHC036A1,A3,A4,AW YHC048A1,A3,A4,AW Cooling Performance' Gross Cooling Capacity 38,000 49,800 SEER2 12.50 12.0 Nominal CFM/ARI Rated CFM 1,200/1,200 1,600/1,600 ARI Net Cooling Capacity 36,600 47,500 System Power(KW) 3.33 4.48 Heating Performance3 Heating Models Low Medium High Low Medium High Heating Input(Btu) 60,000 80,000 120,000 60,000 80,000 120,000 Heating Output(Btu)7 48,000 64,000 96,000 48,000 64,000 96,000 AFUE%48 81 81 81 81 81 81 Steady State Efficiency(%)8 81 81 81 81 81 81 No.Burners 2 2 3 2 2 3 No.Stages 1 1 1 1 1 1 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 1/2 1/2 1/2 1/2 1/2 Compressor No./Type 1/Climatuff Scroll 1/Climatuff Scroll Outdoor Sound Rating(dB)5 83 85 Outdoor Coil-Type Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 Face Area(sq ft) 719 9.59 Rows/FPI 2/17 3/17 Indoor Coil-Type Lanced Lanced Tube Size(in.) 0.3125 0.3125 Face Area(sq ft) 6.68 6.68 Rows/FPI 3/16 4/16 Refrigerant Control Short Orifice Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller No.Used/Diameter(in.) 1/22 1/22 DriveType/No.Speeds Direct/114 Direct/114 CFM 2,550 3,050 No.Motors/HP 1/0.20 1/0.33 Motor RPM 1,075 1,075 22 RT-PRC006-EN TRA/VE' General Data Table GD-5 — Continued 3-Ton Convertible Units 4-Ton Convertible Units YHC036A1,A3,A4,AW YHC048A1,A3,A4,AW Direct Drive Indoor Fan-Type FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/10 x10 1/11 x 11 DriveType/No.Speeds Direct/2 Direct/2 No.Motors 1 1 Motor HP(Standard/Oversized) 0.33/0.50 0.60/0.80 Motor RPM(Standard/Oversized) 950/1,1006 930/1,0009 Motor Frame Size(Standard/Oversized) 48/48 48/48 Belt Drive Indoor Fan-Type FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/11 x 11 1/11 x 11 DriveType/No.Speeds Belt/Variable Sheave 12 BeltNariable Sheave 12 No.Motors 1 1 Motor HP(Standard/Oversized) 1.00/— 1.00/— Motor RPM(Standard/Oversized) 1,750/— 1,750/— Motor Frame Size(Standard/Oversized) 56/— 56/— Filters-Type Furnished 13 Throwaway Throwaway (No.)Size Recommended (2)20 x 25 x 11p (2)20 x 25 x 110 Optional Hot Gas Reheat Coil-Type Lanced Lanced Tube Size(in.)OD 0.375 0.375 Face Area(sq.ft.) 2.22 2.22 Rows/FPI 1/16 1/16 Refrigerant Charge(Lbs of R-22)6 Standard 5.311 7.711 Optional Hot Gas Reheat Coil 5.3 8.5 NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm.Certified in accordance with the Unitary Air-Conditioner Equipment certification program,which is based on ARI Standard 210/240. 2. SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 4. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 6. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 7. YHC036A1 and YHC048A1 Heating Output(Btu)is Low 47,000,Medium 63,000,High 95,000. 8. YHC036A1 andYHC048A1 AFUE(%)and Steady State(%)isLow,Medium and High 80.0. 9. Motor RPM shown is low speed.High speed Motor RPM is:YHC036A 1,060/1,145,YHC048A 1,000/1,100. 10.Filter size shown is for low and medium heat models. High heat model filter size recommended is 20 x 30 x 1. 11.Refigerant charge shown is for three phase.YHC036A1 Refrigerant Charge is 4.5,YHC048A1 refrigerant charge is 8.1. 12.Belt Drive motor is not available for YHC036A1,YHC048A1 13.Optional 2"pleated filters also available. 14.With Dehumidification(Hot Gas Reheat)option:Direct/2. RT-PRC006-EN 23 • 0 TRAIN' General '. -' �- Data > . a,,,.` Table GD-6 - General Data 5-Ton Convertible Units 6-Ton Convertible Units YHC060A1 YHCO60A3,A4,AW YHC072A3,A4,AW Cooling Performance' Gross Cooling Capacity 62,100 62,400 73,000 SEER/EER2 11.8/- 12.0/- -/11.510 Nominal CFM/ARI Rated CFM 2,000/2,000 2,000/2,000 2,400/2,100 ARI Net Cooling Capacity 59,000 59,500 70,000 System Power(KW) 5.73 5.56 6.0910 Heating Performance4 Heating Models Low Medium High Low Medium High Low Medium High Heating Input(Btu) 60,000 80,000 130,000 60,000 80,000 130,000 80,000 120,000 150,000 Heating Output(Btu) 48,000 64,000 103,000 48,000 64,000 104,000 64,800 97,200 121,500 AFUE%5 81 81 80 81 81 80 81 81 81 Steady State Efficiency(%)5 81 81 80 81 81 80 81 81 81 No.Burners 2 2 3 2 2 3 2 3 3 No.Stages 1 1 1 1 1 1 1 1 2 Gas Supply Line Pressure Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 Compressor No./Type 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll Outdoor Sound Rating(dB)6 84 84 89 Outdoor Coil-Type Lanced Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 0.3125 Face Area(sq ft) 10.96 10.96 17.00 Rows/FPI 3/17 3/17 3/17 Indoor Coil-Type Lanced Lanced Lanced Tube Size(in.) 0.3125 0.3125 0.3125 Face Area(sq ft) 771 7.71 9.89 Rows/FPI 4/16 4/16 3/16 Refrigerant Control Short Orifice Short Orifice14 Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/3/4 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller Propeller No.Used/Diameter(in.) 1/22 1/22 1/26 Drive Type/No.Speeds Direct/1 Direct/113 Direct/1 CFM 3,170 3,370 6100 No.Motors/HP 1/0.33 1/0.33 1/0.70 Motor RPM 1,075 1,075 1,075 24 RT-PRC006-E N TRANE" General4 444 ry^1 Data Table GD-6 — Continued 5-Ton Convertible Units 6-Ton Convertible Units YHC060A1 YHC060A3,A4,AW YHC072A3,A4,AW Direct Drive Indoor Fan-Type FC Centrifugal FC Centrifugal N/A No.Used/Diameter(in.) 1/11 x 118 1/11 x 118 N/A DriveType/No.Speeds Direct/2 Direct/2 N/A No.Motors 1 1 N/A Motor HP(Standard/Oversized) 0.90/1.00 0.90/1.00 WA Motor RPM(Standard/Oversized) 985/1,0809 985/1,0809 N/A Motor Frame Size(Standard/Oversized) 48/48 48/48 N/A Belt Drive Indoor Fan-Type FC Centrifugal FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/11 x 11 1/11 x 11 1/12 x 12 DriveType/No.Speeds Belt/Variable Sheave 11 BelWariable Sheave" BeltNariable Sheave No.Motors 1 1 1 Motor HP(Standard/Oversized) 1.00/— 1.00/— 1.00/2.00 Motor RPM(Standard/Oversized) 1,750/— 1,750/— 1750,1750 Motor Frame Size(Standard/Oversized) 56/— 56/— 56/56 Filters-Type Furnished Throwaway Throwaway Throwaway (No.)Size Recommended (2)20 x 30 x 112 (2)20 x 30 x 112 (4)16 x 25 x 212 Optional Hot Gas Reheat Coil-Type — Lanced — Tube Size(in.)OD — 0.375 — Face Area(sq.ft.) — 2.22 — Rows/FPI — 2/16 — Refrigerant Charge(Lbs of R-22)7 Standard 79 8.4 10.7 Optional Hot Gas Reheat Coil — 10.7 — NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 8. YHC060A Oversized Motor Fan Diameter is 12 x 11. 9. Motor RPM shown is low speed.High speed Motor RPM is 1,100/1,135. 10.YHC072Awhen applied in a horizontal configuration has an 11.3 EER and 6.2 System Power(kW). 11.Belt Drive Motor is not available for YHC060A1. 12.2"pleated filters is a factory installed option.2"pleated filters is standard with the Dehumidification(Hot Gas Reheat)option. 13.With Dehumidification(Hot Gas Reheat)option:Direct/2. 14.TXV is supplied from the factory as standard with the Dehumidification(Hot Gas Reheat)option. RT-PRC006-EN 25 0 TRANEJ GeneralI , 4� Data > rye/ Table GD-7 - General Data 71/2-Ton Convertible 81/2-Ton Convertible 10-Ton Convertible YHC092A3,A4,AW YHC102A3,A4,AW YHC120A3,A4,AW Cooling Performance' Gross Cooling Capacity 94,000 103,000 117,000 EER2 11.58 11.59 11.210 Nominal CFM/ARI Rated CFM 3,000/2,625 3,400/3,000 4,000/3,200 ARI Net Cooling Capacity 90,0008 98,0009 109,00010 Integrated Part Load Value3 11.88 1189 11.71° System Power(KW) 7.838 8.529 9.7310 Heating Performance' Heating Models Low Medium High Low Medium High Low Medium High Heating Input(Btu) 120,000 150,000 200,000 120,000 150,000 200,000 150,000 200,000 250,000 Heating Output(Btu) 97,200 121,500 162000 97,200 121,500 162000 121,500 162,000 202,500 AFUEo5 81 81 81 81 81 81 81 81 81 Steady State Efficiency(%) 81 81 80 81 81 80 81 81 81 No.Burners 3 3 4 3 3 4 3 4 5 No.Stages 1 2 2 1 2 2 2 2 2 Gas Supply Line Pressure Natural(minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 LP(minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 Gas Connection Pipe Size(in.) 1/2 3/4 3/4 1/2 3/4 3/4 3/4 3/4 3/4 Compressor No./Type 2/Climatuff Scrolls 2/Climatuff Scrolls 2/Climatuff Scrolls Outdoor Sound Rating(dB)6 91 89 88 Outdoor Coil-Type Lanced Lanced Lanced Tube Size(in.)OD 0.3125 0.3125 0.3125 Face Area(sq ft) 17.5 19.83 2721 Rows/FPI 3/17 3/17 3/17 Indoor Coil-Type Lanced Lanced Lanced Tube Size(in.) 0.3125 0.3125 0.3125 Face Area(sq ft) 12.36 12.36 12.36 Rows/FPI 3/16 4/16 5/16 Refrigerant Control Short Orifice Short Orifice Short Orifice Drain Connection No./Size(in.) 1/3/4 NPT 1/3/4 NPT 1/3/4 NPT Outdoor Fan-Type Propeller Propeller Propeller No.Used/Diameter(in.) 1/26 1/26 1/26 DriveType/No.Speeds Direct/1 Direct/1 Direct/1 CFM 6200 6600 7000 No.Motors/HP 1/0.70 1/0.75 1/0.75 Motor RPM 1075 1,075 1,075 Belt Drive Indoor Fan-Type FC Centrifugal FC Centrifugal FC Centrifugal No.Used/Diameter(in.) 1/15 x 15 1/15 x 15 1/15 x 15 DriveType/No.Speeds BeltNariable Sheave BeltNariable Sheave Belt/Variable Sheave No.Motors 1 1 1 Motor HP(Standard/Oversized) 2.00/3.00 2.00/3.00 3.00/5.00 Motor RPM(Standard/Oversized) 1,750/1,750 1,750/1,750 1,750/3,450 Motor Frame Size(Standard/Oversized) 56/56 56/56 56/56 Filters-Type Furnished" Throwaway Throwaway Throwaway (No.)Size Recommended (4)20 x 25 x 2 (4)20 x 25 x 2 (4)20 x 25 x 2 Optional Reheat Coil-Type Lanced Lanced Lanced Tube Size(in.)OD 0.375 0.375 0.375 Face Area(sq.ft.) 5.19 5.19 5.19 Rows/FPI 2/16 2/16 2/16 Refrigerant Charge(Lbs of R-22)7 6.4 Circuit 1/6.2 Circuit 2 74 Circuit 1/7.1 Circuit 2 11.0 Circuit 1/7.3 Circuit 2 NOTES: 1. Cooling Performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb.Gross capacity does not include the effect of fan motor heat.ARI capacity is net and includes the effect of fan motor heat.Units are suitable for operation to±20%of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,which is based on ARI Standard 210/240. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360.Units are rated at 80°F ambient,80°F entering dry bulb,and 67°F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratorytest conditions using American National Standards Institute standards.Ratings shown are for elevations up to 2000 feet.For elevations above 2000 feet,ratings should be reduced at the rate of 4%for each 1000 feet above sea level. 5. AFUE is rated in accordance with DOE test procedures. 6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.For additional information refer to Table PD-90. 7. Refrigerant charge is an approximate value.For a more precise value,see unit nameplate and service instructions. 8. YHC092Awhen applied in a horizontal configuration has an 11.3 EER,89,000 ARI Net Cooling Capacity,11.4 Integrated Part Load Value,and 7.88 System Power(KW). 9. YHC102A when applied in horizontal configuration has an 11.3 EER,11.3 IPLV,97,000 ARI Net Cooling Capacity and 8.58 System Power(KW). 10.YHC120Awhen applied in a horizontal configuration has an 10.7 EER,11.2 IPL,108,000 ARI Net Cooling and 10.09 System Power(KW). 11.Optional 2"pleated filters also available. 26 RT-PRC006-EN TRANS' Performance Data Table PD-1-Gross Cooling Capacities(MBH) 3-Ton Single/Three Phase YSCO36A1,A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 378 12.9 25.1 24.1 29.6 18.2 35.5 11.9 1080 80 35.6 35.0 38.8 273 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 273 273 29.9 23.5 35.6 17.5 85 376 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0 90 39.3 39.3 39.7 376 42.0 29.2 37.8 37.8 379 376 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4 75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1 1200 80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3 85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2 90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 371 371 37.0 370 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0 75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 377 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4 1320 80 37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0 85 39.4 39.4 40.2 35.2 42.1 25.9 379 379 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3 90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 371 31.5 75 37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6 80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7 1440 85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 370 26.4 90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 376 33.0 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3 SHC=Sensible Heat Capacity RT-PRC006-EN 27 TRANE' Performance Data Table PD-2 - Gross Cooling Capacities (MBH) 4-Ton Single Phase YSC048A1 AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SI-IC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8 1440 80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 4.3.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4 85 50.3 50.3 53.0 45.1 574 34.9 470 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0 90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6 75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3 1600 80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7 85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0 90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3 75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7 1760 80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8 85 53.6 53.6 54.8 49.8 58.6 371 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9 90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9 75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 370 42.2 28.1 50.1 17.0 1920 80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9 85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 376 45.5 45.5 45.5 45.5 50.5 36.6 90 57.1 571 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity Table PD-3 - Gross Cooling Capacities (MBH) 4-Ton Three Phase YSC048A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MR-I SHC MBH SHC MBH SHC MR+-SHC MBH-SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 176 33.4 32.7 39.6 25.2 471 16.0 80 46.0 46.0 51.6 37.4 56.5 279 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6 1440 85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1 90 52.5 52.5 52.9 52.2 572 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 472 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 477 38.6 75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 278 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5 80 48.1 48.1 52.4 39.3 572 29.0 44.9 44.9 49.2 379 54.7 277 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8 1600 85 51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0 90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3 75 472 43.5 52.8 32.3 573 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 271 48.5 16.8 80 49.7 49.7 53.1 41.0 578 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 274 39.7 39.7 41.8 36.3 48.7 25.9 1760 85 52.8 52.8 53.8 49.7 58.1 377 50.3 50.3 51.0 49.1 55.6 370 472 472 47.2 472 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9 90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 476 47.6 47.6 47.6 49.5 43.8 75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2 80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9 1920 85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6 90 56.6 56.6 56.6 56.6 59.3 470 54.6 54.6 54.5 54.5 56.8 471 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity 28 RT-PRC006-EN TRANE'' Performance Data Table PD-4 - Gross Cooling Capacities (MBH) 5-Ton Single/Three Phase YSC060A1,A3,A4,AW,AK AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 672 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2 1800 80 59.0 59.0 65.1 471 69.8 35.0 55.6 55.6 62.0 45.7 676 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6 85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9 90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0 75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 379 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6 2000 80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0 85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9 90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7 75 60.3 552 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 378 65.4 23.6 477 477 54.5 35.4 61.8 22.0 2200 80 63.1 63.1 66.8 512 70.8 379 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3 85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 573 57.3 62.5 43.8 90 69.4 69.4 69.3 69.3 72.2 54.6 673 673 673 673 70.1 54.9 64.6 64.6 64.6 64.6 671 54.8 61.2 61.2 61.2 61.2 63.2 54.2 75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4 2400 80 64.5 64.5 675 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3 85 677 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5 90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 677 56.8 62.4 62.4 62.4 62.4 63.9 56.5 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3 SHC=Sensible Heat Capacity Table PD-5 - Gross Cooling Capacities (MBH) 6-Ton Three Phase YSC072A3,A4,AW,AK AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SME MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6 80 67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 378 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9 2160 85 71.4 71.4 74.2 61.9 78.6 474 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 673 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0 90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 772 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8 75 67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0 80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 379 578 57.8 62.6 49.6 71.3 36.3 2400 85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 772 479 674 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 470 90 76.2 76.2 76.5 74.3 79.9 571 74.3 74.3 74.3 74.3 779 57.4 71.7 71.7 71.7 71.7 75.5 577 68.5 68.5 68.4 68.4 72.2 57.5 75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4 80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 377 2640 85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 673 778 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7 90 774 774 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8 75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 273 56.2 56.2 64.7 41.9 71.7 25.8 80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 578 773 41.8 66.5 66.5 70.1 571 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5 2880 85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 678 677 67.7 72.9 50.1 90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity RT-PRC006-EN 29 TWE' Performance � � Data fi o F� Table PD-6 - Gross Cooling Capacities(MBH) 7/-Ton Single Compressor Three Phase YSC090A3,A4,AW,AK AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8 80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 872 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0 2700 85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9 90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5 75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5 80 92.2 92.2 97.5 70.9 100.3 50.4 874 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1 3000 85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1 90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 777 75 91.5 82.5 977 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2 80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1 3300 85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 975 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8 90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 972 97.2 972 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4 75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8 80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 971 775 101.0 55.7 876 876 92.5 772 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6 3600 85 99.0 99.0 99.7 88.7 101.8 62.7 978 978 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 673 89.1 89.1 89.1 89.1 96.3 68.3 90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity Table PD-7 - Gross Cooling Capacities(MBH) 71/2-Ton Dual Compressors Three Phase YSC092A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SI-IC MBH SHC MBH SHC MBH SHC MBH SHC MB-1 SHC MBH SHC MBH SHC MBH SHC 75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2 80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3 2700 85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 776 79.0 76.1 89.9 59.3 90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0 75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9 80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4 3000 85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6 90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 971 77.5 88.0 88.0 88.0 88.0 92.2 77.4 75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5 80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 879 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5 3300 85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5 90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3 75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2 80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 774 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5 3600 85 97.8 978 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 679 86.9 86.9 86.9 86.9 93.1 68.2 90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity 30 RT-PRC006-EN 0 TWINE' Performance Data Table PD-8- Gross Cooling Capacities(MBH) 8'/z Ton Three Phase YSC102A3,A4,AW,AK AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) NBH SHC NBFi SHC NEH SHC NEH SHC NEH SHC MBH SHC NEH SHC NBH SHC NBH SHC NE-I SHC NEH SHC MBH SHC 75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 575 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8 3060 80 98.0 98.0 107.2 771 113.7 570 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5 85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 876 89.9 85.7 103.1 67.1 90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3 75 98.7 872 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5 3400 80 10t6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 779 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8 85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7 90 111.0 111.0 111.0 111.0 1170 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0104.8 110.7 874 99.8 99.8 99.7 99.7 105.2 87.1 75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 775 91.3 59.4 104.6 372 374080 1041 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 870 92.2 78.5 105.1 56.0 85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9 90 112.8 112.8 112.8 112.8 1178 872 111.8 111.8 111.8 111.2 116.0 90.0 107.7 1077 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4 75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1 4080 80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 1074 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2 85 110.5 110.5 111.9 102.3 1172 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8 90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 1078 95.4 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity Table PD-9- Gross Cooling Capacities(MBH) 10 Ton Three Phase YSC120A3,A4,AW,AK AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MB-I SHC SHC NBH SHC NB-I SI-IC NB-I SHC NB-I SI-IC NB-I SHC NBH SHC NB-I SHC NB-I SHC NBFI SHC MB-I SHC 75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 1072 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9 3600 80 112.8 112.8 121.2 89.2 1275 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 978 79.7 113.6 574 85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 1177 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6 90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5 75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8 4000 80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3 85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4 90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 1171 100.0 75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 971 971 111.3 72.3 121.3 40.2 88.6 88.6 100.9 677 115.1 39.7 4400 80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 973 126.3 69.2 107.7 1077 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2 85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 1279 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0 90 1279 1279 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7 75 116.1 113.8 123.1 77.6 1278 48.5 108.9108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6 4800 80 121.4 121.4 124.5 98.6 129.4 66.4 1173 1173 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 975 116.5 65.7 85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 875 112.1 112.1 112.1 112.1 1178 873 90 129.1 129.1 129.1 129.1 132.5 100.4 1272 1272 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity RT-PRC006-EN 31 TRANE® Performance Data Table PD-10- Gross Cooling Capacities(MBH)3-on YHC036A1,A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6 1080 80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5 85 379 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2 90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0 75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9 1200 80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4 85 39.6 39.6 41.1 36.3 44.6 274 37.1 371 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 371 24.8 90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 376 37.6 37.6 376 40.4 32.1 34.7 34.7 34.7 34.7 374 31.1 75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 372 12.2 1320 80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 271 374 19.2 85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 272 32.9 32.9 32.9 32.9 376 26.2 90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1 75 371 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 275 275 31.5 21.0 37.5 12.5 1440 80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 378 20.1 85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 373 373 373 373 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6 90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 375 375 375 375 38.6 34.9 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity Table PD-11- Gross Cooling Capacities(MBH)4-Ton YHC048A1,A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MB-I SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 174 33.2 33.2 39.3 24.6 47.8 16.0 1440 80 47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 479 24.1 85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2 90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2 75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 178 34.7 34.7 40.2 26.2 48.6 16.4 1600 80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 375 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4 85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 470 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3 90 54.5 54.5 54.8 54.8 574 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 474 474 474 49.6 43.0 75 47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8 1760 80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7 85 53.1 53.1 54.2 50.9 570 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3 90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7 75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 373 373 41.7 29.3 49.6 172 1920 80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 476 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 279 85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1 90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity 32 RT-PRC006-EN TRANE" Performance Data Table PD-12 - Gross Cooling Capacities (MBH)5-Ton Single Phase YHC060A1 AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SFIC MBH SHC MBH SHC MBH SHC MBH SFIC MBH SHC MBH SHC 75 56.2 48.2 64.3 378 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1 1800 80 576 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6 85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0 90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5 75 57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 4E2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7 2000 80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1 85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5 90 676 67.6 676 676 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8 75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 677 24.3 49.6 49.4 576 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1 2200 80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5 85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7 90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6 75 60.6 574 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5 240080 64.0 64.0 670 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8 85 672 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 572 572 57.2 62.9 45.6 90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 675 573 62.2 62.2 62.2 62.2 63.9 57.2 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity Table PD-13 - Gross Cooling Capacities (MBH)5-Ton Three Phase YHC060A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bulb(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 56.6 49.0 64.4 37.5 677 24.7 52.0 46.8 60.9 35.7 66.2 23.3 470 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0 1800 80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8 85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 677 42.3 55.6 55.6 573 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5 90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1 75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 376 66.6 23.8 48.6 47.7 572 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5 2000 80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 578 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4 85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 678 43.0 58.4 58.4 59.2 575 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0 90 677 677 677 677 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3 75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 670 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0 2200 80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 679 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9 85 66.4 66.4 672 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 442 90 68.7 68.7 68.7 68.7 71.2 52.8 671 671 671 671 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 6t0 61.0 61.0 61.0 62.9 55.3 75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 673 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 472 53.4 36.6 61.7 21.4 2400 80 64.5 64.5 670 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 575 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3 85 673 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 626 46.2 90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 579 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity RT-PRC006-EN 33 TRANE' Performance Data r$ f Table PD-14 - Gross Cooling Capacities(MBH) 6-Ton Three Phase YHC072A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5 80 68.7 68.2 73.8 51.7 75.4 370 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5 2160 85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 678 60.9 75.0 46.2 59.5 59.5 61.3 577 71.7 45.4 90 74.7 74.7 75.3 70.6 770 51.9 73.4 73.4 73.7 73.2 777 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8 75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 376 72.0 24.0 80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 374 56.7 56.7 61.9 49.8 72.4 36.1 2400 85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 771 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7 90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0 75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 577 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6 80 72.3 72.3 74.5 53.9 75.4 374 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7 2640 85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 773 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7 90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 572 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7 75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0 80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 670 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6 2880 85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 774 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5 90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 772 61.3 72.9 72.9 72.9 72.9 74.8 64.1 NOTES: 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity a SHC=Sensible Heat Capacity Table PD-15 - Gross Cooling Capacities (MBH) 71/2-Ton Dual Compressors Three Phase YHC092A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 85.7 72.4 95.8 56.8 99.9 371 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2 80 875 870 96.2 68.5 101.1 50.4 81.8 81.8 92.4 674 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8 2700 85 92.8 92.8 970 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 970 60.9 779 779 80.3 75.4 92.3 59.4 90 972 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7 75 879 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 3E4 74.9 70.5 87.8 53.4 96.9 34.8 674 674 80.5 50.2 92.8 32.8 80 90.5 90.5 974 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 479 3000 85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 873 873 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5 90 99.4 99.4 99.9 98.1 104.1 74.1 972 972 972 972 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9 75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 371 770 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4 80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 776 82.8 69.5 94.1 49.9 3300 85 976 97.6 99.4 88.0 103.3 679 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 673 85.2 85.2 85.1 85.1 94.7 65.2 90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 777 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7 75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 375 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0 80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4 3600 85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 879 879 95.6 678 90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 979 979 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1 NOTES 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity 34 RT-PRC006-EN TRANS' Performance Data Table PD-16 - Gross Cooling Capacities (MBH) 81-Ton Three Phase YHC102A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MB-I SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6 80 96.9 96.9 106.2 776 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6 3060 85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5 90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6 75 96.6 872 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5 80 100.9 100.9 1077 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 1073 55.7 81.8 81.8 86.8 73.4 101.4 53.1 3400 85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 976 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8 90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 978 97.8 97.8 97.8 102.8 879 75 98.9 92.5 1074 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 1075 38.7 76.9 76.9 875 58.4 102.2 36.2 80 103.7 103.7 108.8 84.0 113.3 577 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 973 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5 3740 85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4 90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7 75 100.9 973 108.1 674 112.5 42.9 93.1 93.1 104.7 679 111.5 41.4 86.2 86.2 978 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9 80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 578 4080 85 110.2 110.2 110.9 103.4 115.1 79.5 1076 107.6 107.6 1076 114.1 76.6 103.0 103.0 103.0 103.0 109.9 776 96.6 96.6 96.6 96.6 104.2 777 90 112.9 112.9 112.9 112.9 116.5 875 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 970 NOTES. 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity Table PD-17 - Gross Cooling Capacities (MBH) 10-Ton Three Phase YHC120A3,A4,AW AmbientTemperature(F) 85 95 105 115 Enter. Dry Entering Wet Bu b(F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 75 1070 94.4 1174 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 1072 65.3 118.6 42.2 82.3 78.8 978 61.1 113.6 39.6 3600 80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 875 123.4 62.3 977 977 1078 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3 85 1176 1176 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 1070 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5 90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3 75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5 4000 80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 1170 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1 85 120.5 120.5 122.3 1079 125.9 76.4 1170 1170 118.6 110.2 125.0 78.8 111.6 111.6 11t8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7 90 125.2 125.2 124.2 124.2 1276 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 1177 98.6 75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 1171 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2 4400 80 117.6 1176 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8 85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 1074 1172 83.2 90 126.0 126.0 1271 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3 75 113.4 113.4 121.8 76.2 125.0 48.4 1076 104.0 118.5 770 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9 4800 80 119.5 119.5 123.2 970 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 1172 66.8 85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 1175 1175 1176 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4 90 1275 1275 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 1075 NOTES. 1. All capacities shown are gross and have not considered indoor fan heat.To obtain net cooling subtract indoor fan heat. 2. MBH=Total Gross Capacity 3. SHC=Sensible Heat Capacity RT-PRC006-EN 35 0 TRANE' Performance Data ___ r rk f�tff$ ,, s»ra.AV,Z'J:��✓.G r A¢?"+.vL.9 Table PD-18-Direct Drive Evaporator Fan Performance 3,4,and 5 Ton YSC036A,YSC0484,YSC060A - Low and Medium Heat External Static Pressure(Inches of Water)&Motor Power(Bhp)1 Standard Motor Oversized Motor' High Speed Low Speed High Speed Low Speed Unit Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP 960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35 1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47 1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39 1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40 3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41 Horizontal Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42 1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44 1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45 1440 0.44 0.43 - - 0.64 0.52 0.54 0.48 1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56 1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58 1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60 1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63 4 YSC048A**L,M 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64 Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66 1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68 1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70 1920 0.22 0.57 - - 0.70 0.85 0.20 0.73 1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85 1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89 1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91 1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94 5 YSC060A**L,M3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95 Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96 2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96 2300 0.25 0.97 - - 0.55 1.17 0.10 0.97 2400 0.15 1.00 - - 0.43 1.20 - - 960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35 1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47 1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39 1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40 3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41 Downflow Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42 1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44 1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45 1440 0.44 0.43 - - 0.64 0.52 0.54 0.48 1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56 1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58 1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60 1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63 4 YSC048A**L,M 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64 Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66 1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68 1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70 1920 0.27 0.57 - - 0.75 0.85 - - 1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85 1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89 1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91 1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94 5 YSC060A**1_,M3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95 Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96 2200 0.40 0.95 0.05 0.67 0.70 1.12 0.35 0.96 2300 0.30 0.97 - - 0.60 1.17 0.15 0.97 2400 0.20 1.00 - - 0.48 1.20 - - Fan motor heat(MBH)=3.72 x Fan Bhp+.24. Trane's factory supplied motors,in commercial equipment,are definite purpose motors,specifically designed and tested to operate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure.Our product's warranty will not be affected. NOTES: 1. Data includes pressure drop due to wet coil and filters. 2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel. 3. YSC060AK*uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel.Refer to oversized motor column for the standard motor performance data. 36 RT-PRC006-EN 0 TRANE' Performance Data Table PD-19- Direct Drive Evaporator Fan Performance 3,4 and 5 Ton YSC036A,YSC048A,YSC060A -High Heat External Static Pressure(Inches of Water)&Motor Power(Bhp)1 Standard Motor Oversized Motor2 High Speed Low Speed High Speed Low Speed Unit Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP 960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35 1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47 1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39 1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40 3 YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41 Horizontal Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42 1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44 1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45 1440 0.39 0.4.3 - - 0.59 0.52 0.49 0.48 1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56 1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58 1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60 1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63 4 YSC048A**H 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64 Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66 1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68 1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70 1920 0.22 0.57 - - 0.70 0.85 0.20 0.73 1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85 1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89 1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91 1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94 5 YSC060A**H3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95 Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96 2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96 2300 0.25 0.97 - - 0.55 1.17 0.10 0.97 2400 0.15 1.00 - - 0.43 1.20 - - 960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35 1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47 1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39 1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40 3 YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41 Downflow Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42 1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44 1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45 1440 0.39 0.43 - - 0.59 0.52 0.49 0.48 1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56 1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58 1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60 1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63 4 YSC048A**H 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64 Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66 1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68 1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70 1920 0.27 0.57 - - 0.75 0.85 - - 1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85 1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89 1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91 1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94 5 YSC060A**H3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95 Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96 2200 0.40 0.95 0.00 0.67 0.70 1.12 0.35 0.96 2300 0.30 0.97 - - 0.60 1.17 0.15 0.97 2400 0.20 1.00 - - 0.48 1.20 - - Fan motor heat(MBH)=3.72 x Fan Bhp+.24. Trane's factory supplied motors,in commercial equipment,are definite purpose motors,specifically designed and tested to operate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure.Our product's warranty will not be affected. NOTES: 1. Data includes pressure drop due to wet coil and filters. 2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel. 3. YSC060AK*uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel.Refer to oversized motor column for the standard motor performance data. RT-PRC006-EN 37 0 TRANE® Performance T Data s � � Table PD-20 - Belt Drive Evaporator Fan Performance - 3-Ton -YSC036A3,A4,AW*L,M- Low and Medium Heat-Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 - - 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52 1080 537 0.14 606 0.18 669 0.23 724 0.27 I 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58 1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65 1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73 1440 673 0.29 728 0.34 1780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop due to other motor failure.Our product's warranty will not be affected. options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt may be necessary. Table PD-20 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1000 0.57 1037 0.63 1072 0.69 1106 0.75 1139 0.81 1080 1022 0.64 1058 0.70 1093 0.76 1127 0.82 1161 0.89 1200 1047 0.71 1083 0.77 1117 0.83 1150 0.90 1183 0.97 1320 1075 0.79 1108 0.85 I 1141 0.92 1174 0.99 1206 1.06 1440 1104 0.88 1137 0.95 1170 1.02 1201 1.09 1231 1.16 1-HP Standard Motor& Field Supplied High Static Drive(2) Table PD-21 - Belt Drive Evaporator Fan Performance -3-Ton -YSC036A3,A4,AW*L,M- Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60 1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69 1200 645 0.22 720 0.28 I 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79 1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 I 1135 0.89 1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00 1-HP Standard Motor&Field Supplied High Static Drive(2) For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-21 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90 1080 1090 0.75 I 1123 0.81 1154 0.87 1185 0.93 1215 0.99 1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12 1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26 1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41 1-HP Standard Motor& Field Supplied High Static Drive(2) 38 RT-PRC006-EN 0 TRANE° Performance Data Table PD-22- Belt Drive Evaporator Fan Performance - 3-Ton - Y5C036A3,A4AW*H - High Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52 1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59 1200 593 0.19 657 0.23 716 0.28 ( 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66 1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74 1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature No accessories or options are included in pressure drop data. Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt maybe necessary. 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt may be necessary. Table PD-22 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1005 0.58 1041 0.64 1076 0.70 1110 0.76 1142 0.82 1080 1029 0.65 1064 0.71 1099 0.77 I 1133 0.83 1166 0.90 1200 1053 0.72 1089 0.78 1123 0.85 1156 0.91 1189 0.98 1320 1082 0.80 1116 0.87 1150 0.93 1182 1.00 1214 1.07 1440 1113 0.90 1146 0.97 1178 1.04 1209 1.11 1240 1.18 1-HP Standard Motor& Field Supplied High Static Drive(2) Table PD-23 - Belt Drive Evaporator Fan Performance - 3-Ton -YSC036A3,A4,AW*H - High Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 563 0.13 . 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60 1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70 1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80 1320 711 0.29 I 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90 1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02 1-HP Standard Motor&Field Supplied High Static Drive(2) For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose - - NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature No accessories or options are included in pressure drop data. Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH) 2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt maybe necessary. Table PD-23 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&Field Motor&Drive Supplied High Static Drive(2) 960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90 1080 1096 0.76 I 1128 0.82 1159 0.88 1190 0.94 1220 1.00 1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13 1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28 1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43 RTPR0006-EN 39 0 TRANE® Performance . u Data . Table PD-24 - Belt Drive Evaporator Fan Performance -4-Ton -YSC048A3,A4,AW*L,M- Low and Medium Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 604 0.21 666 0.25 724 0.30 778 0.36 826 0.41 870 0.47 911 0.52 952 0.58 990 0.63 1026 0.69 1440 665 0.29 720 0.34 773 0.38 824 0.44 I 872 0.51 916 0.57 956 0.63 994 0.69 1030 0.75 1065 0.81 1600 726 0.38 777 0.44 826 0.49 I 873 0.54 919 0.61 961 0.68 1002 0.75 1039 0.82 1074 0.89 1109 0.95 1760 789 0.50 I 836 0.56 881 0.61 924 0.67 967 0.73 1008 0.81 1048 0.89 1085 0.97 1120 1.04 1154 1.12 1920 851 0.63 896 0.70 938 0.76 978 0.82 1018 0.88 1057 0.96 1095 1.04 1131 1.13 1167 1.21 1199 1.30 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standardfilters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK61 required.Field Supplied Belt maybe necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-24 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1062 0.76 1097 0.82 1130 0.88 1163 0.95 1195 1.02 1440 1100 0.88 1133 0.94 1166 1.01 1198 1.08 1228 1.15 1600 1141 1.02 1173 1.09 1205 1.16 1235 1.23 1265 1.31 1760 1185 1.19 1215 1.26 1246 1.33 I 1275 1.41 1304 1.49 1920 1230 1.37 1 1260 1.45 - - - 1-HP Standard Motor&Field Supplied High Static Drive(2) Table PD-25 - Belt Drive Evaporator Fan Performance - 4-Ton -YSC048A3,A4,AW*L„M- Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 669 0.25 744 0.31 805 0.37 860 0.44 911 0.50 959 0.56 1003 0.63 1045 0.70 1082 0.77 1119 0.85 -1448 733 0.34 803 0.41 I 864 0.48 916 0.55 965 0.62 1011 0.69 1055 0.76 1096 0.83 1134 0.91 1171 0.99 1buIJ- 800 0.45 I 864 0.53 923 0.60 974 0.68 1021 0.75 1064 0.83 1106 0.91 1147 0.99 1185 1.07 1221 1.15 1760 868 0.58 926 0.67 982 0.75 1033 0.83 1079 0.92 1121 1.00 1161 1.08 1199 1.17 1237 1.26 11273 1.35 1920 937 0.74 989 0.83 1042 0.92 1092 1.01 1138 1.10 1179 1.19 1217 1.28 11254 1.38 1290 1.47 - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES 1 Data includes pressure drop due to standard filters and wet coils. 1-HP Standard Motor&Field No accessories or options are included in pressure drop data. Supplied High Static Drive(2) Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. Table PD-25 - Continued 1. Field Supplied Fan SheaveAK61 required.Field Supplied Belt maybe necessary. External Static Pressure(Inches of Water) 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt 1.10 1.20 1.30 1.40 1.50 may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Trane's factory supplied motors,in commercial equipment,are definite purpose 1-HP Standard motors,specifically designed and tested to operate reliably and continuously at Motor&Drive all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature 1280 1154 0.92 1187 1.00 1218 1.07 1248 1.14 1277 1.21 motor failure.Our product's warranty will riot be affected. 1440 1205 1.07 1237 1.15 I 1270 1.24 1300 1.32 1330 1.40 1600 1256 1.23 1290 1.33 1322 1.42 - - - - 1760 1307 1.43 - - - - - - - - 1920 - - - - - - - - - - I 1-HP Standard Motor&Field Supplied High Static Drive(2) 40 RT-PRC006-EN TRANE° Performance . r Data Table PD-26 - Belt Drive Evaporator Fan Performance - 4-Ton - YSC048A3,A4,AW*H - High Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 618 0.22 678 0.26 735 0.31 788 0.37 835 0.42 879 0.48 920 0.53 960 0.59 997 0.65 1034 0.71 1440 680 0.30 735 0.35 787 0.40 1 838 0.46 884 0.52 926 0.59 966 0.64 1004 0.70 1040 0.77 1075 0.83 1600 744 0.40 794 0.45 1 842 0.50 888 0.56 933 0.64 975 0.71 1015 0.78 1051 0.84 1086 0.91 1120 0.97 1760 808 0.52 I 854 0.58 899 0.64 941 0.69 984 0.76 1024 0.84 1063 0.92 1099 1.00 1134 1.07 1167 1.14 1920 873 0.66 916 0.73 957 0.79 997 0.85 1037 0.92 1075 0.99 1112 1.08 1148 1.17 1183 1.25 1214 1.33 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included In pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH)=2.829x Fan BHP+.4024. 1. Field Supplied Fan SheaveAK61 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt maybe necessary. Table PD-26 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1069 0.77 1104 0.83 1137 0.90 1169 0.96 1202 1.04 1440 1109 0.89 1142 0.96 1174 1.03 1205 1.10 1236 1.17 1600 1153 1.04 1184 1.11 1214 1.18 1244 1.26 I 1275 1.33 1760 1197 1.22 1228 1.29 I 1258 1.36 1287 1.44 - - 1920 1245 1.41 1274 1.49 - - - 1-HP Standard Motor& Field Supplied High Static Drive(2) Table PD-27- Belt Drive Evaporator Fan Performance - 4-Ton - YSC048A3A4,AW*H - High Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 686 0.27 758 0.33 817 0.39 871 0.45 922 0.51 968 0.58 1013 0.64 1053 0.72 1091 0.79 1127 0.86 1440 753 0.36 821 0.43 I 878 0.50 930 0.57 977 0.63 1022 0.70 1066 0.78 1107 0.85 1145 0.93 1180 1.01 1600 821 0.48 I 884 0.55 941 0.63 990 0.70 1035 0.78 1078 0.86 1120 0.93 1160 1.02 1197 1.10 1234 1.18 1760 891 0.62 949 0.70 1004 0.78 1052 0.87 1096 0.95 1137 1.03 1176 1.12 1214 1.20 11251 1.29 1287 1.38 1920 962 0.78 1015 0.87 1067 0.97 1115 1.06 1158 1.15 1198 1.24 1235 1.33 1271 1.42 - 1-HP Standard Motor&Field Supplied High Static Drive(2) For Standard Evaporator Fan Speed IRPMI,reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. Table PD-27 - Continued 1. Held Supplied Fan SheaveAK61 required.Field Supplied Belt may be necessary. External Static Pressure(Inches of Water) 2. Field Supplied Fan Sheave AK41 required.Feld Supplied 1.10 1.20 1.30 1.40 1.50 Belt may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1160 0.94 1194 1.01 1224 1.08 1254 1.15 1283 1.22 1440 1214 1.09 1247 1.18 1 1278 1.26 1308 1.34 1338 1.43 1600 1268 1.26 1300 1.35 1331 1.44 1760 1321 1.47 - - - - - 1920 - 1-HP Standard Motor&Field Supplied High Static Drive(2) RT-PRC006-EN 41 TRANE° Performance Data �.,� .y rk �%'i¢��. °. s ;tip Table PD-28 - Belt Drive Evaporator Fan Performance - 5-Ton -YSCO6OA3,A4,AW*L,M- Low and Medium Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1600 747 0.40 797 0.46 846 0.51 893 0.57 938 0.64 981 0.72 1020 0.79 1056 0.85 1091 0.92 1125 0.99 1800 828 0.56 873 0.62 I 917 0.68 960 0.74 1002 0.81 1042 0.89 1081 0.97 1118 1.05 1152 1.13 1185 1.20 2000 909 0.75 951 0.82 992 0.89 1031 0.95 1069 1.01 1107 1.09 1144 1.18 1179 1.27 1213 1.37 1246 1.45 2200 992 0.98 1031 1.06 1068 1.13 1104 1.20 1139 1.27 1175 1.35 1209 1.43 - - - - - - 2400 1075 1.26 1111 1.34 1145 1.42 1179 1.50 - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt may be necessary. Table PD-28 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1158 1.05 1190 1.13 1221 1.20 1251 1.27 1281 1.35 1800 1216 1.28 1246 1.35 1276 1.43 I - - - - 2000 - - - - - - - - - - 2200 - - - - - - - - - - 2400 - - - - - - - - Table PD-29 - Belt Drive Evaporator Fan Performance - 5-Ton -YSCO6OA3,A4,AW*L,M- Low and Medium Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor &Field Supplied Low Static Drive(1) 1-HP Standard Motor&Drive 1600 825 0.48 889 0.56 946 0.64 996 0.71 1041 0.79 1084 0.87 1126 0.95 1166 1.03 1204 1.11 1240 1.20 1800 913 0.66 971 0.75 1025 0.84 1074 0.92 1117 1.01 1158 1.09 1197 1.18 1235 1.27 1272 1.36 1307 1.45 2000 1003 0.89 1054 0.98 1105 1.08 1153 1.18 1196 1.27 1235 1.37 1272 1.46 1308 1.50 - 2200 1094 1.16 1140 1.26 1187 1.37 1232 1.48 I - - - - - - - - - - - - 2400 1185 1.48 1 - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt maybe necessary. Table PD-29 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1274 1.28 1307 1.37 1338 1.46 - - 1800 - - - - - - - - 2000 - - - - - - - - 2200 - - - - - - 2400 - - - - - - - - 42 RT-PRC006-EN TRANE9 Performance Data Table PD-30 - Belt Drive Evaporator Fan Performance -5-Ton -YSC060A3A4,AW*H- High Heat-Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1600 764 0.42 814 0.47 862 0.53 909 0.60 953 0.67 994 0.74 1032 0.81 1069 0.88 1103 0.94 1136 1.01 1800 848 0.58 892 0.65 I 936 0.70 978 0.77 1020 0.84 1059 0.92 1098 1.01 1132 1.09 1166 1.16 1198 1.24 2000 932 0.79 973 0.86 1013 0.92 1051 0.98 1090 1.06 1127 1.14 1163 1.23 1197 1.32 1231 1.42 1262 1.50 2200 1017 1.03 1055 1.11 1091 1.18 1127 1.25 1162 1.32 1196 1.40 1231 1.49 I - - - - - - 2400 1103 1.32 1138 1.41 1171 1.49 I - - - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor Refer to Table PD-89 to determine additional static pressure drop failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan SheaveAK56 required.Field Supplied Belt may be necessary. Table PD-30 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1168 1.08 1201 1.15 1231 1.22 1261 1.30 1290 1.37 1800 1229 1.31 1259 1.39 1288 1.46 I - - - - 2000 - - - - - - - - - - 2200 - - - - - - - - 2400 - - - - - - - - Table PD-31 - Belt Drive Evaporator Fan Performance - 5-Ton -YSC060A3A4,AW*H- High Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor &Field Supplied Low Static Drive(1) 1-HP Standard Motor&Drive 1600 847 0.51 910 0.59 964 0.66 1011 0.74 1056 0.82 1098 0.89 1140 0.97 1179 1.06 1217 1.14 1252 1.23 1800 938 0.70 995 0.79 1047 0.87 1093 0.96 1135 1.05 1175 1.13 1213 1.22 1251 1.31 1287 1.40 1323 1.49 2000 1030 0.94 1082 1.03 1131 1.13 1176 1.23 1217 1.32 1255 1.42 1292 1.50 I - - - - - - 2200 1123 1.23 1170 1.33 1216 1.44 I - - - - - - - - - - - - - - 2400 - - - - - - - - - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt may be necessary. Table PD-31 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 CFM RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1285 1.31 1317 1.40 1348 1.49 I - - 1800 - - - - - - - - 2000 - - - 2200 - - - - - - 2400 - RT-PRC006-EN 43 • 0 TRANS` Performance Data Table PD-32 - Belt Drive Evaporator Fan Performance - 6-Ton -YSC072A3,A4,AW*L,M- Low and Medium Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 - - 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88 2160 - - 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01 2400 - - 597 0.46 647 0.54 695 0.62 I 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15 2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32 2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied FanSheaveAK84andBeltAX34required. Table PD-32 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HP Standard Motor &Drive 1HP Standard Motor&High Static Drive Kit (or 2 HP Oversized Motor&Drive) 1920 931 0.96 965 1.04 999 1.12 1030 1.20 1062 1.29 1092 1.37 1120 1.45 1150 1.54 1177 1.63 1204 1.71 2160 951 1.10 984 1.19 I 1018 1.29 1049 1.37 1080 1.46 1 1110 1.55 1139 1.65 1168 1.74 1196 1.84 1222 1.93 2400 973 1.25 1006 1.35 1039 1.45 I 1070 1.55 1100 1.65 1129 1.76 1158 1.86 1186 1.96 1213 2.06 1241 2.16 2540 996 1.42 1029 1.52 1060 1.63 1091 1.74 1121 1.85 1150 1.96 1178 2.07 1206 2.18 1233 2.30 - - 2880 1023 1.62 1054 1.72 1085 1.83 1114 1.95 1143 2.06 1172 2.18 1200 2.30 - - - - - - 2 HP Oversized Motor&Drive Table PD-33 - Belt Drive Evaporator Fan Performance - 6-Ton -YSC072A3,A4,AW*H- High Heat - Down flow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor &Field Supplied Low Static Drive(1) 1-HP Standard Motor&Drive 1920 - - 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93 2160 - - 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08 2400 594 0.46 644 0.53 692 0.61 1 741 0.70 786 0.79 826 0.88 - 864 0.97 900 1.05 936 1.15 971 1.24 2640 643 0.60 691 0.67 I 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43 2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66 2-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are NOTES: definite purpose motors,specifically designed and tested to operate Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions.Using the full No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure.Our due to other options/accessories product's warranty will not be affected. 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-33 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&High Static Drive Kit (or 2 HP oversized Motor&Drive) 1920 952 1.01 985 1.09 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77 2160 977 1.17 1010 1.26 1043 1.36 1073 1.44 I 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00 2400 1004 1.34 1037 1.44 I 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26 2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20 - - - - - - 2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 - - - - - - - - - - 2-HP Oversized Motor&Drive 44 RT-PRC006-EN 0 TRAIVE® Performance , ;, r 4f Data f Table PD34 - Belt Drive Evaporator Fan Performance - 6-Ton -YSC072AK*L - Low Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 1920 - - - - 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88 2160 - - 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01 2400 - - 597 0.46 647 0.54 695 0.62 I 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15 2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32 2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are NOTES: definite purpose motors,specifically designed and tested to operate Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions.Using the full No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure.Our due to other options/accessories product's warranty will not be affected. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-34 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor &Drive 2 HP Standard Motor&High Static Drive) 1920 931 0.96 965 1.04 999 1.12 1030 1.20 1062 1.29 1092 1.37 1120 1.45 1150 1.54 1177 1.63 1204 1.71 2160 951 1.10 984 1.19 I 1018 1.29 1049 1.37 1080 1.46 1110 1.55 1139 1.65 1168 1.74 1196 1.84 1222 1.93 2400 973 1.25 1006 1.35 1039 1.45 1070 1.55 1100 1.65 1129 1.76 1158 1.86 1186 1.96 1213 2.06 1241 2.16 2640 996 1.42 1029 1.52 1060 1.63 1091 1.74 1121 1.85 1150 1.96 1178 2.07 1206 2.18 1233 2.30 - - 2880 1023 1.62 1054 1.72 1085 1.83 1114 1.95 1143 2.06 1172 2.18 1200 2.30 - - - - - - 2 HP Standard Motor&High Static Drive Table PD-35 - Belt Drive Evaporator Fan Performance - 6-Ton -YSC072AK*H- High Heat- Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Std.Motor&Field Supplied Low Static Drive 2 HP Standard Motor&Drive 1920 - - 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93 2160 - - 600 0.42 654 0.49 705 0.57 I 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08 2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24 2640 64.3 0.60 691 0.67 I 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43 2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: Data includes pressure drop due to standard filters and wet coils. 2 HP Standard Motor &High Static Drive Trane's factory supplied motors,in commercial equipment,are definite purpose motors,specifically designed and tested to operate reliably and continuously at all cataloged conditions.Using the full No accessories or options are included in pressure drop data. Anditiordisimin, horsepower range of our fan motors as shown in our tabular data Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure.Our due to other options/accessories product's warranty will not be affected. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-35 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor&Drivel 2-HP Standard Motor&High Static Drive 1920 952 1.01 985 1.09 I 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77 2160 977 1.17 I 1010 1.26 1043 1.36 1073 1.44 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00 2400 1004 1.34 1037 1.44 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26 2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20 - - - - - - 2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 - - - - - - - - - - RT-PR C006-E N 45 TRANE® Performance rh Data Table PD-36 - Belt Drive Evaporator Fan Performance - 6-Ton - YSC072A3,A4,AW*L,M - Low and Medium Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 - - 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95 2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10 2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27 2640 684 0.63 721 0.71 1 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1 1027 1.45 2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67 2-HP Oversized Motor and Drive For Standard Evaporator Fan Speed(RPM),reference Table P0-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 2-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories F1-HP Fan Motor Heat(MBH(=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000. 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-36 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&High Static Drive Kit Motor&Drive (or 2 HP Oversized Motor&Drive) 1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88 2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 I 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 - - 2400 1029 1.37 1063 1.47 1 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 - - - - 2540 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 - - - - - - 2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 - - - - - - - - - - 2-HP Oversized Motor&Drive Table PD-37 - Belt Drive Evaporator Fan Performance - 6-Ton -YSC07243A4,AW*H- High Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00 2160 608 0.41 661 0.48 714 0.56 I 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17 2400 667 0.55 710 0.62 1 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1 1027 1.37 2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 11031 1.47 11063 1.58 2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82 2-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 2-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 1-HP Fan Motor Heat(MBH(=2.829x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan SheaveAK84 and Belt AX34 required. Table PD-37 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&High Static Drive Kit(or 2 HP Oversized Motor&Drive) 1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 - - 2160 1032 1.26 1068 1.36 1102 1.46 1 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 - - - - 2400 1061 1.47 1 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 - - - - 2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 - - - - - - - - 2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 - - - - - - - - - - - - 2-HP Oversized Motor&Drive 46 RT-PRC006-EN TRAIVE® Performance ' on Data Standard, Efficiency Table PD-38 - Belt Drive Evaporator Fan Performance - 6-Ton -YSCO72AK*L - Low Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor&Low Static Drive 2 HP Standard Motor&Drive 1920 522 0.27 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95 2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10 2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27 2640 684 0.63 721 0.71 I 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 11027 1.45 2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67 2 HP Standard Motor &High Static Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: Trane's factory supplied motors,in commercial equipment,are definite purpose Data includes pressure drop due to standard filters and wet coils. motors,specifically designed and tested to operate reliably and continuously at No accessories or options are included in pressure drop data. all cataloged conditions.Using the full horsepower range of our fan motors as Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature duets otheroptions/accessories motor failure.Our product's warranty will not be affected. 2-HP Fan Motor Heat)MBH)=3.000 x Fan BHP+.5000. 1. Field Supplied Fan SheaveAK84 and BeltAX34 required. Table PD-38 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard 2 HP Standard Motor&High Static Drive Kit Motor&Drive 1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88 2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 - - 2400 1029 1.37 1063 1.47 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 - - - - 2640 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 - - - - - - 2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 - - - - - - - - - - Table PD-39 - Belt Drive Evaporator Fan Performance - 6-Ton - YSCO72AK*H - High Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor&Field Supplied 2 HP Standard Motor&Drive Low Static Drive(1) 1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00 2160 608 0.41 661 0.48 714 0.56 1 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17 2400 667 0.55 710 0.62 I 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.271 1027 1.37 2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 11031 1.47 1063 1.58 2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82 2 HP Standard Motor&High Static Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-39 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2 HP Standard Motor&High Static Drive 1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 - - 2160 1032 1.26 1068 1.36 1102 1.46 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 - - - - 2400 1061 1.47 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 - - - - 2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 - - - - - - - - 2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 RT-PRC006-EN 47 'WANE' Performance Data Table PD-40 - Belt Drive Evaporator Fan Performance - 71/2-Ton - YSC090,092A3,A4,AW,AK*L - Low Heat-Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 - - - - 676 0.59 726 0.67 773 0.77 815 0.85 854 0.94 891 1.03 928 1.12 963 1.22 2700 - - 682 0.68 727 0.76 770 0.85 814 0.95 1 856 1.06 895 1.16 931 1.25 965 1.35 998 1.45 3000 693 0.79 738 0.89 780 0.97 819 1.07 ( 858 1.18 898 1.29 936 1.40 '972 1.52 1006 1.63 1038 1.73 3300 753 1.03 795 1.14 834 1.23 I 871 1.33 906 1.45 942 1.56 978 1.69 1014 1.81 1048 1.94 1080 2.06 3600 814 1.31 I 853 1.44 890 1.55 925 1.65 958 1.76 991 1.88 1023 2.01 1057 2.14 1088 2.28 I 1121, 2.41 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane'sfactory supplied motors,in commercial equipment,are definite purpose I 3-HP Oversized Motor NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Motor Sheave 1VL4OL x 7/8 and Fan Sheave AK71 required. Table PD-40 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2-HP Standard Motor&High Static Drive Kit(or 3-HP Oversized Motor&Drive) 2400 996 1.32 1028 1.42 1061 1.52 1092 1.63 1122 1.73 1151 1.83 1180 1.93 1207 2.03 1235 2.14 1261 2.24 2700 1031 1.56 1062 1.66 1093 1.78 I 1123 1.89 1153 2.00 1181 2.12 1209 2.23 1236 2.35 I 1262 2.47 1288 2.58 3000 1070 1.85 1099 1.95 I 1128 2.07 1158 2.19 1185 2.31 1213 2.43 1240 2.55 1267 2.68 1293 2.81 1319 2.94 3300 1110 2.18 1139 2.29 I 1167 2.42 1195 2.54 1222 2.66 1248 2.79 1274 2.92 1301 3.05 1325 3.18 1351 3.33 3600 1151 2.55 1181 2.68 1208 2.81 1236 2.95 1261 3.07 1287 3.21 1311 3.33 - - - - - - 3-HP Oversized Motor&Drive Table PD-41 - Belt Drive Evaporator Fan Performance - 71/2Ton -YSC090,092A3,A4,AW*M- Medium Heat -Down flow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 - - 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29 2700 676 0.67 721 0.75 764 0.84 809 0.94 1 851 1.04 891 1.14 927 1.24 961 1.34 994 1.44 1027 1.54 3000 741 0.89 783 0.98 822 1.08 I 861 1.19 901 1.30 939 1.41 975 1.52 1009 1.64 1041 1.74 1071 1.85 3300 807 1.17 1 846 1.26 882 1.37 917 1.48 953 1.60 989 1.72- 1024 1.85 1058 1.97 1089 2.09 11119 2.21 3600 874 1.50 910 1.60 944 1.71 976 1.83 1008 1.95 1041 2.08 1074 2.22 1107 2.35 1138 2.49 1168 2.62 3-HP Oversized Motor &Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 3-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Motor Sheave 1VL40Lx 7/8 and Fan Sheave AK71 required. Table P0-41 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&High Static Drive Kit 2-HP Standard Motor&Drive (or 3-HP Oversized Motor&Drive) 2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 1278 2.31 2700 1058 1.65 1089 1.76 I 1120 1.87 1149 1.99 1178 2.10 1205 2.21 I 1232 2.33 1259 2.45 1284 2.56 1310 2.68 3000 1101 1.96 I 1131 2.08 1160 2.20 I 1187 2.31 1215 2.44 1243 2.57 1269 2.69 1295 2.82 1321 2.95 1346 3.08 3300 1147 2.33 1176 2.45 1204 2.58 1230 2.70 1256 2.82 1282 2.96 1308 3.09 1333 3.23 1358 3.36 - - 3600 1196 2.75 1223 2.88 1250 3.02 1276 3.15 1301 3.28 1325 3.41 - - - - - - - - 3-HP Oversized Motor&Drive 48 RT-PRC006-EN 0 TRANS® Performance Data Table PD-42 - Belt Drive Evaporator Fan Performance - 7/2-Ton -YSC090,092A3,A4,AW,AK*H - High Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 - - 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 906 1.07 941 1.16 976 1.26 1009 1.36 2700 717 0.74 760 0.83 804 0.93 1 847 1.03 887 1.13 922 1.23 958 1.33 991 1.43 1024 1.53 1055 1.64 3000 787 0.99 826 1.09 I 865 1.20 905 1.31 943 1.42 979 1.54 1012 1.64 1044 1.76 1075 1.87 1105 1.98 3300 858 1.30 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 1068 2.01 1099 2.13 11129 2.25 11157 2.37 3600 930 1.66 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 1126 2.43 1157 2.57 1185 2.70 1212 2.83 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 3-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Motor Sheave 1VL40Lx 7/8 and Fan Sheave AK71 required. Table PD-42 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2-HP Standard Motor&High Static Drive Kit(or 3-HP Oversized Motor&Drive) 2400 1042 1.46 1073 1.56 1104 1.67 1134 1.77 1163 1.87 1190 1. 7 121 2.08 1244 2.18 1271 2.2 1296 2.38 2700 1086 1.75 1117 1.86 1146 1.97 1174 2.09 1203 2.21 1230 2.32 1255 2.44 1282 2.55 1308 2.67 1333 2.78 3000 1134 2.09 1163 2.21 11191 2.33 1218 2.45 1245 2.58 1272 2.70 1298 2.83 1323 2.96 1348 3.09 1372 3.22 3300 1185 2.49 1212 2.61 1238 2.74 1265 2.87 1292 3.01 1316 3.13 1341 3.27 1366 3.41 - - - - 3600 1239 2.96 1265 3.09 1290 3.22 1316 3.36 - - - - - - - - - - - - 3-HP Oversized Motor&Drive Table PD-43 - Belt Drive Evaporator Fan Performance - T1/2-Ton -YSC090,09243,A4,AW,AK*L- Low Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 653 0.53 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 911 1.03 948 1.13 982 1.23 1017 1.34 2700 725 0.73 760 0.80 801 0.88 I 847 0.98 889 1.09 927 1.19 963 1.28 997 1.38 1030 1.48 1061 1.60 3000 798 0.98 830 1.06 1 862 1.15 902 1.24 943 1.35 981 1.48 1017 1.60 1050 1.70 1081 1.80 1111 1.90 3300 872 1.28 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 1071 1.93 1104 2.07 I 1135 2.19 1164 2.30 3600 946 1.65 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 1125 2.31 1158 2.46 1189 2.61 \1219 2.75 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as 2-HP Standard Motor&High Static No accessories or options are indluded in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Drive(or 3-HP Oversized Motor) _ -Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Motor Sheave 1VL4OL x 7/8 and Fan Sheave AK71 required. Table PD-43 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2-HP Standard Motor&High Static Drive Kit(or 3-HP Oversized Motor&Drive) 2400 1053 1.44 1087 1.55 1121 1.65 1153 1.76 1185 1.86 1217 1.98 1246 2.08 1277 2.20 1306 2.32 1334 2.44 2700 1093 1.71 I 1124 1.83 1156 1.95 1187 2.06 1218 2.18 1248 2.30 I 1277 2.42 1306 2.53 1333 2.65 1361 2.78 3000 1141 2.02 1170 2.15 1198 2.28 I 1227 2.41 1255 2.54 1283 2.67 1311 2.79 1339 2.93 1365 3.05 1391 3.18 3300 1192 2.41 1220 2.52 1247 2.65 1272 2.78 1299 2.92 1325 3.07 1350 3.21 1376 3.36 - - - - 3600 1246 2.87 1272 2.99 1298 3.11 1323 3.24 1348 3.37 - - - - - - - - - - _ 3-HP Oversized Motor&Drive RT-PRC006-EN 49 0 TWINE Performanceu Data Table PD-44 - Belt Drive Evaporator Fan Performance - 71/2-Ton -YSC090,092A3,A4,AW*M- Medium Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41 2700 756 0.79 795 0.87 I 841 0.97 884 1.08 923 1.18 959 1.27 992 1.36 1025 1.47 1057 1.58 1089 1.70 3000 833 1.07 1 865 1.16 906 1.25 946 1.36 985 1.49 1020 1.61 1052 1.71 1083 1.81 1114 1.91 1143 2.03 3300 910 1.41 938 1.50 972 1.60 1010 1.70 1047 1.84 1081 1.97 1 1114 2.11 1144 2.22 11173 2.33 1200 2.44 3600 988 1.81 1014 1.91 1042 2.01 1076 2.12 1110 2.25 1143 2.39 1175 2.54 1205 2.69 1234 2.82 1260 2.94 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor&High Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Static Drive(or 3-HP Oversized No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Motor) Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Motor Sheave 1VL4OL x 7/8 and Fan Sheave AK71 required. Table PD-44 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor 2-HP Standard Motor&High Static Drive Kit &Drive (or 3-HP Oversized Motor&Drive) 2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 1325 2.40 1353 2.52 2700 1120 1.82 1152 1.93 1183 2.05 1214 2.17 1243 2.28 11273 2.40 1302 2.52 1330 2.64 1357 2.76 1385 2.89 3000 1172 2.15 1201 2.29 1 1229 2.42 1257 2.55 1285 2.68 1312 2.80 1340 2.93 1367 3.06 1395 3.19 1421 3.33 3300 1227 2.56 1255 2.69 1281 2.83 1307 2.97 1333 3.11 1359 3.26 1384 3.40 - - - - - - 3600 1287 3.06 1312 3.18 1337 3.31 1361 3.45 - - - - - - - - - - - - 3 HP Oversized Motor&Drive Table PD-45 - Belt Drive Evaporator Fan Performance - 71/2-Ton -YSC090,092A3,A4,AW,AK *H- High Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2400 713 0.62 764 0.71 811 0.81 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 1031 1.38 1067 1.48 2700 790 0.86 837 0.96 880 1.07 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 1086 1.69 1 1117 1.80 3000 869 1.16 910 1.26 950 1.38 989 1.50 1023 1.62 1056 1.72 1086 1.82 11116 1.92 1146 2.04 1175 2.17 3300 949 1.53 985 1.63 1023 1.75 1058 1.88 1092 2.02 1 1124 2.15 1154 2.26 11182 2.37 1210 2.48 1237 2.60 3600 1029 1.97 1061 2.07 1096 2.19 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 1276 3.01 1302 3.13 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 3-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750_ 1. Field Supplied Motor Sheave 1VL4OL x7/8 and Fan Sheave AK71 required. Table PD-45 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard 2-HP Standard Motor&High Static Drive Kit Motor&Drive (or 3-HP Oversized Motor&Drive) 2400 1101 1.59 1134 1.69 1166 1.80 1197 1.90 1229 2.02 1259 2.13 1287 2.25 1317 2.37 1344 2.48 1373 2.61 2700 1148 t92 1180 2.04 1210 2.15 1241 2.27 I 1269 2.39 1299 2.51 1326 2.62 1354 2.74 1383 2.88 1409 3.00 3000 1204 2.30 I 1232 2.43 1260 2.56 1287 2.69 1316 2.82 1344 2.95 1370 3.07 1397 3.20 1423 3.34 - - 3300 1264 2.74 1290 2.87 1316 3.02 1342 3.16 1367 3.30 1393 3.45 - - - - - - - - 3600 1327 3.26 1352 3.39 - - - - - - - - - - - - - - - - 3-HP Oversized Motor&Drive 50 RT-PRC006-EN TRANE' Performance Data Table PD-46 - Belt Drive Evaporator Fan Performance - 81/2-Ton -YSC102A3,A4,AW,AK*L,M - Low and Medium Heat -DownflowAirflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BFP FFM BFP FPM BHP RPM BHP RPM BHP FPM BHP RPM BHP RPM BHP FPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2720 - - - - 608 0.59 649 0.70 689 0.82 728 0.94 764 1.06 798 1.19 829 1.33 859 1.46 3060 - - 615 0.65 654 0.75 692 0.87 728 0.99 764 1.13 1799 1.26 833 1.39 864 1.53 894 1.68 3400 625 0.72 665 0.83 702 0.95 736 1.06 770 1.19 1804 1.34 836 1.49 868 1.63 899 1.78 928 1.93 3740 681 0.93 716 1.05 752 1.18 784 1.31 I 815 1.44 846 1.58 876 1.74 906 1.90 935 2.06 963 2.22 4080 737 1.19 769 1.31 1802 1.45 833 1.60 862 1.73 891 1.87 919 2.03 947 2.20 974 2.37 1001 2.55 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor Refer to Table PD-89 to determine additional static pressure drop failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-46 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM 8-F RPM 8-F RPM BHP RPM BFP RPM BI-P FPM BFP RPM BHP RPM BHP FPM BHP 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive 2720 .•: 1.61 916 1.76 943 1.91 970 2.07 996 2.22 1021 2.37 1046 2.53 1071 2.69 1096 2.86 1119 3.02 3060 922 1.82 949 1.98 976 2.14 11001 2.31 1026 2.47 1051 2.65 1074 2.81 1098 2.99 1120 3.16 1144 3.34 3400 957 2.08 984 2.24 11011 2.41 1035 2.58 1060 2.75 1083 2.93 1106 3.11 1128 3.29 - - 3740 992 2.39 1018 2.55 1045 2.72 1070 2.90 1095 3.08 1117 3.25 1140 3.44 - - - - - - 4080 1028 2.73 1053 2.90 1079 3.07 1104 3.26 1128 3.44 - - - - - - - - - - Table PD47 - Belt Drive Evaporator Fan Performance - 81/2-Ton -YSC10243,A4,AW,AK*H- High Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2720 - - - - 619 0.62 661 0.74 700 0.85 738 0.97 773 1.09 807 1.23 838 1.36 868 1.51 3060 586 0.58 629 0.68 667 0.79 705 0.91 741 1.04 776 1.17 I 810 1.30 843 1.44 874 1.58 904 1.72 3400 642 0.76 681 0.88 717 1.00 751 1.12 785 1.25 1 817 1.40 849 1.55 881 1.69 911 1.84 940 1.99 3740 698 0.99 735 1.12 769 1.25 I 800 1.37 831 1.51 862 1.66 892 1.82 920 1.98 950 2.14 977 2.30 4080 756 1.26 I 789 1.40 821 1.54 851 1.68 879 1.82 908 1.97 936 2.13 964 2.30 991 2.48 1017 2.66 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. _ - . - -- ---- ` all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat)MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-47 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive 2720 896 1.65 923 1.80 950 1.95 977 2.11 1003 2.26 1029 2.42 1053 2.57 1078 2.74 1102 2.90 1124 3.06 3060 932 1.88 959 2.04 985 2.20 I 1010 2.36 1034 2.53 1058 2.70 1082 2.87 1105 3.05 1129 3.22 1151 3.39 3400 969 2.15 I 996 2.31 1020 2.48 1045 2.65 1070 2.83 1093 3.00 1116 3.19 1138 3.37 - - - - 3740 1005 2.47 1032 2.64 1058 2.81 1083 2.99 1106 3.16 1129 3.35 - - - - - - - - 4080 1044 2.83 1069 3.01 1095 3.19 1119 3.37 - - - - - - - - - RT-PRC006-EN 51 • 0 TRAIVE® Performance : Hifi . .,e d dj Data Table PD-48- Belt Drive Evaporator Fan Performance - 8/2-Ton -YSC102A3,A4,AW,AK*4M- Low and Medium Heat-Horizontal Airflow External Static Pressure(Indies of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM FFM BHP RPM BHP RFM BHP FFM EI-IP RPM BHP RPM BHP RPM BHP RPM 8HP RPM BHP FFM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2720 607 0.59 655 0.69 697 0.80 744 0.93 791 1.07 834 1.21 871 1.34 904 1.46 933 1.58 962 1.70 3060 672 0.81 715 0.92 755 1.04 I 792 1.16 834 1.31 876 1.47 917 1.63 953 1.78 985 1.93 1013 2.06 3400 739 1.09 776 1.20 I 814 1.34 849 1.47 882 1.61 920 1.77 958 1.94 996 2.12 1030 2.29 11063 2.47 3740 807 1.43 839 1.54 875 1.69 907 1.83 938 1.98 969 2.13 1003 2.30 11037 2.49 1072 2.69 1106 2.88 4080 875 1.83 903 1.95 935 2.10 968 2.26 99/ 2.42 1025 2.58 1053 2.74 1084 2.93 1116 3.13 1148 3.34 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan SheaveAK79 and Belt AX38 required. Table PD-48 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive 2720 988 1.81 1013 1.93 1037 2.05 1061 2.17 1084 2.28 1106 2.40 1128 2.52 1150 2.64 1172 2.76 1192 2.88 3060 1040 2.19 11065 2.33 1090 2.46 1113 2.59 1136 2.72 1158 2.86 1179 2.99 1199 3.12 1220 3.25 1239 3.38 3400 1091 2.62 1117 2.78 1141 2.92 1165 3.07 1188 3.22 1210 3.37 - - - - - - - - 3740 1137 3.07 1166 3.27 1193 3.44 - - - - - - - - - - - - - - 4080 - - - - - - - - - - - - - - - - - - - - Table PD-49 - Belt Drive Evaporator Fan Performance - 8/2-Ton -YSC10243,A4,AW,AK*H- High Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2720 625 0.63 671 0.73 713 0.84 762 0.98 807 1.12 849 1.26 883 1.38 915 1.50 944 1.62 971 1.74 3060 692 0.86 734 0.98 772 1.10 811 1.23 854 1.38 896 1.54 934 1.70 969 1.85 997 1.99 1026 2.12 3400 760 1.15 799 1.28 834 1.41 I 868 1.55 903 1.70 942 1.87 980 7.04 1016 2.22 11049 2.39 1079 2.56 3740 828 1.50 I 863 1.64 898 1.79 929 1.94 960 2.08 993 2.25 I1027 2.44 1062 2.63 1096 2.82 1127 3.02 4080 898 1.92 929 2.07 962 2.23 992 2.39 1020 2.55 1048 2.71 1078 2.89 1110 3.09 1142 3.30 - - 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed IR PMI,reference Table PD 86 Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-49 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive 2720 998 1.86 10221.97 1046 2.09 1069 2.21 1092 2.33 1115 2.45 1136 2.56 1158 2.69 1179 2.80 1200 2.93 3060 1052 2.26 I 1077 2.39 1101 2.52 1124 2.66 1146 2.79 1167 2.92 1188 3.05 1209 3.18 1229 3.31 1249 3.45 3400 1106 2.71 1131 2.86 1155 3.01 1179 3.16 1202 3.31 1222 3.45 - - - - - - - 3740 1157 3.21 1185 3.39 - - - - - - - - - - - - - - - - 4080 - - - - - - - - - - - - - - - - - - - - 52 RT-PRC006-EN 0 ?WANE® Performance 0,1 DataStandartiyhaenCy Table PD-50- Belt Drive Evaporator Fan Performance - 10-Ton -YSC120A3,A4,AW,AK*L,M- Low and Medium Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BI-P RPM BHP RPM BI-P RPM BI-P RPM BFP RPM BHP RPIV1 BHP RPM BHP 3-HP Standard Motor&Field Supplied Low Static Drive(1) 3200 - - - - - - 727 1.00 763 1.14 798 1.28 832 1.42 863 1.56 895 1.71 924 1.86 3600 - - 717 1.03 751 1.15 784 1.28 816 1.42 848 1.57 879 1.73 I 910 1.89 940 2.05 968 2.20 4000 746 1.21 780 1.35 813 1.49 843 1.62 873 1.76 902 1.92 I 931 2.09 959 2.26 986 2.43 1014 2.61 4400 814 1.57 845 1.73 876 1.88 905 2.03 I 932 2.18 959 2.34 985 2.51 1012 2.69 1037 2.88 1063 3.07 4800 883 2.02 911 2.18 940 2.35 967 2.52 993 2.68 1018 2.84 1042 3.01 1067 3.20 1091 3.39 1115 3.59 3-HP Standard Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 5-HP Oversized Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Motor&Drive No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1VM50 x 7/8",Fan Sheave AK89 and Belt AX40 required. Table PD-50 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BI-P RPM BHP RPM BHP RPM BHP RPIVI BHP RPM BHP RPM BI-P RRM BHP RPM BI-P 3-HP Standard Motor&Drive 3200 952 2.01 979 2.18 1004 2.34 1029 2.51 1053 2.68 1078 2.86 1101 3.04 1124 3.23 1146 3.41 1169 3.59 3600 996 2.37 1023 2.53 1049 2.71 1073 2.88 1097 3.07 1120 3.25 1142 - 3.43 11164 3.63 1186 3.83 1207 4.02 4000 1041 2.79 1067 2.96 1092 3.14 1117 3.33 I 1141 3.51 1164 3.70 1186 3.90 1208 4.10 1228 4.30 1249 4.51 4400 1088 3.26 1113 3.45 I 1137 3.64 1162 3.84 1185 4.04 1207 4.23 1229 4.43 1252 4.65 1273 4.85 1293 5.06 4800 1139 3.80 1161 4.00 1185 4.22 1208 4.43 1230 4.63 1253 4.85 1275 5.06 1295 5.27 1317 5.49 1337 5.71 5-HP Oversized Motor&Drive Table PD-51- Belt Drive Evaporator Fan Performance - 10-Ton -YSC120A3,A4,AW,AK*H- High Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied Low Static Drive(1) 3200 - - - - 723 0.99 759 1.12 793 1.26 827 1.40 860 1.55 891 1.69 921 1.84 949 2.00 3600 721 1.04 755 1.17 787 1.29 820 1.44 851 1.59 882 1.75 I 913 1.90 942 2.06 971 2.22 999 2.39 4000 793 1.40 824 1.54 854 1.67 883 1.82 ( 913 1.98 941 2.15 969 2.32 997 2.50 1024 2.67 1050 2.85 4400 866 1.83 895 1.98 I 923 2.13 949 2.28 976 2.45 1003 2.63 1029 2.81 1054 3.00 1079 3.20 1104 3.39 4800 939 2.34 967 2.51 992 2.67 1017 2.84 1042 3.01 1066 3.19 1090 3.38 1114 3.58 1138 3.79 1161 4.00 3-HP Standard Motor&Drive 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: Iserr motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1VM50 x 7/8",Fan Sheave AK89 and Belt AX40 required. Table PD-51 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 3200 976 2.16 1001 2.32 1027 2.49 1051 2.66 1075 2.84 1098 3.02 1120 3.19 1143 3.38 1166 3.57 1189 3.75 3600 1025 2.55 1052 2.73 1076 2.90 1100 3.09 1122 3.27 I 1145 3.46 1167 3.66 1188 3.85 1210 4.05 1230 4.25 4000 1076 3.03 1101 3.20 1126 3.40 I 1149 3.58 1172 3.77 1194 3.97 1216 4.18 1236 4.38 1257 4.59 1277 4.80 4400 1129 3.58 1153 3.77 1176 3.97 1200 4.17 1222 4.37 1244 4.57 1266 4.78 1286 4.99 1307 5.21 1326 5.43 4800 1184 4.21 1207 4.42 1229 4.63 1252 4.84 1274 5.06 1295 5.27 1315 5.48 1336 . 5.70 - - - - 5-HP Oversized Motor&Drive RT-PRC006-EN 53 TRANE Performance Data t „.; Table PD-52 - Belt Drive Evaporator Fan Performance - 10-Ton -YSC120A3,A4,AW,AK*L,M- Low and Medium Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP PPM BHP PPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied 3-HP Standard Motor&Drive Low Static Drive(1) 3200 - - 761 1.10 798 1.22 834 1.35 875 1.51 916 1.68 955 1.85 991 2.01 1022 2.16 1050 2.31 3600 799 1.35 836 1.48 872 1.63 904 1.77 I 936 1.91 972 2.09 1009 2.28 1045 2.47 1079 2.66 1111 2.84 4000 881 1.81 913 1.96 I 947 2.12 977 2.28 1006 2.44 1035 2.60 1066 2.78 1100 2.99 1133 3.20 1165 3.41 4400 963 2.39 992 2.54 1023 2.71 1052 2.89 1079 3.06 1106 3.23 1132 3.41 11160 3.61 1189 3.82 1219 4.05 4800 1045 3.07 1072 3.23 1099 3.41 1127 3.61 1154 3.80 1179 3.98 1203 4.17 1227 4.36 1251 4.56 1278 4.80 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor Refer to Table PD-89 to determine additional static pressure drop failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1VM50x7/8",Fan Sheave 4K89 and Belt AX40 required. Table PD-52 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM FFM BHP FWV1 BHP RPM BHP RPM BHP RPM 81-P RPM BI-P RPM BI-P RPM BFP RPM BHP FPM BI-P 3-HP Standard Motor&Drive 5-HP Oversized Motor&Drive 3200 1077 2.45 1103 2.60 1126 2.73 1150 2.87 1171 3.01 1193 3.15 1214 3.29 1233 3.42 1253 3.56 1274 3.71 3600 1140 3.02 1165 3.18 1190 3.34 I 1214 3.51 1235 3.66 1257 3.82 1279 3.98 1298 4.13 1317 4.28 1338 4.45 4000 1196 3.62 1225 3.83 1252 4.03 1276 4.22 1299 4.40 1321 4.58 1342 4.76 1363 4.94 1383 5.11 1401 5.28 4400 1250 4.28 1280 4.52 1307 4.75 1334 4.98 1359 5.20 1384 5.43 1405 5.62 - - - - - - 4800 1305 5.03 1334 5.28 1361 5.54 - - - - - - - - - - - - Table PD-53 - Belt Drive Evaporator Fan Performance - 10-Ton -YSC120A3,A4,AW,AK*H- High Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied 3-HP Standard Motor&Drive Low Static Drive(1) 3200 768 1.12 805 1.25 842 1.38 884 1.54 924 1.71 962 1.88 998 2.04 1028 2.19 1055 2.34 1082 2.48 3600 856 1.56 888 1.70 I 921 1.84 955 2.00 992 2.19 1028 2.37 1063 2.57 1096 2.75 1126 2.93 1153 3.10 4000 943 2.10 973 2.26 1002 2.41 1031 2.58 1062 2.76 1096 2.96 1129 3.17 1161 3.38 11192 3.59 1222 3.81 4400 1031 2.76 1060 2.94 1086 3.11 1113 3.28 1139 3.45 I 1167 3.66 1198 3.89 1228 4.11 1257 4.34 1287 4.58 4800 1119 3.45 1146 3.74 1171 3.93 1195 4.11 1219 4.30 1243 4.50 1270 4.72 1297 4.96 1325 5.21 1353 5.46 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: Trane's factory supplied motors,in commercial equipment,are definite purpose Data includes pressure drop due to standard filters and wet coils. motors,specifically designed and tested to operate reliably and continuously at No accessories or options are included in pressure drop data. all cataloged conditions.Using the full horsepower range of our fan motors as Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature due to other options/accessories motor failure.Our product's warranty will not be affected. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1 VM50x 7/8",Fan Sheave 4K89 and BeltAX40 required. Table PD-53 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 5-HP Oversized Motor&Drive 3200 1107 2.62 1131 2.76 1154 2.90 1176 3.04 1197 3.17 1218 3.32 1238 3.46 1257 3.59 1276 3.73 1296 3.87 3600 1178 3.27 1202 3.42 I 1224 3.58 1247 3.74 1268 3.90 1288 4.05 1308 4.21 1328 4.37 1346 4.52 1366 4.69 4000 1249 4.01 1273 4.19 1296 4.38 1318 4.56 1339 4.73 1361 4.91 1380 5.08 1399 5.26 1418 5.44 - - 4400 1315 4.81 1340 5.03 1366 5.26 1389 5.48 1410 5.67 - - - - - - - - - - 4800 1379 5.71 - - - - - - - - - - - - - - - - - 54 RT-PRC006-EN 0 TRANE' Performance Data Table PD-54- Direct Drive Evaporator Fan Performance 3,4 And 5 Ton YHC036A**L,M,YHC048A**L,M, YHC060A**L,M -Low and Medium Heat External Static Pressure(Inches of Water)&Motor Power(Bhp)' Standard Motor Oversized Motor' Unit High Speed Low Speed High Speed Low Speed Tons Model No. CFM ESP BFP ESP 81-P ESP B-P ESP B-P 960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35 1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36 1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38 1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40 3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41 Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42 1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44 1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45 1440 0.34 0.44 - - 0.57 0.51 0.45 0.48 1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56 1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58 1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60 1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63 4 YHC048A**L,M 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64 Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66 1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68 1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70 1920 0.16 0.57 - - 0.62 0.85 0.13 0.73 1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85 1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89 1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91 1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94 5 YHC060A**L,M 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95 Horizontal Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96 2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96 2300 0.37 0.95 - - 0.68 1.17 0.18 0.97 2400 0.26 0.97 - - 0.55 1.20 - - 960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35 1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36 1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38 1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40 3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41 DownflowAirflow 1260 0.51 0.41 0.19 0.30 - 0.70 0.45 0.61 0.42 1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44 1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45 1440 0.34 0.44 - - 0.57 0.51 0.45 0.48 1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56 1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58 1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60 1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63 4 YHC048A**L,M 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64 Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66 1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68 1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70 1920 0.21 0.57 - - 0.67 0.85 - - 1600 1.04 0.78 0.94 0.64 1.37 0.90 1.23 0.85 1700 0.97 0.80 0.81 0.65 1.29 0.94 1.13 0.89 1800 0.92 0.85 0.70 0.65 1.21 0.98 1.02 0.91 1900 0.82 0.88 0.61 0.65 1.20 1.02 0.92 0.94 5 YHC060A**L,M 2000 0.74 0.90 0.45 0.66 1.03 1.05 0.81 0.95 DownflowAirflow 2100 0.64 0.93 0.30 0.66 0.94 1.10 0.68 0.96 2200 0.51 0.94 0.15 0.67 0.83 1.12 0.47 0.96 2300 0.42 0.95 - - 0.73 1.17 0.23 0.97 2400 0.31 0.97 - - 0.60 1.20 - - ran motor heat IMBH)=3.72 x I-an Bhp+.24. Trane's factory supplied motors,in commercial equipment,are definite purpose motors,specifically designed and tested to operate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure.Our product's warranty will not be affected. NOTES: 1. Data includes pressure drop due to wet coil and filters. RT-PRC006-EN 55 0 . TWE' Performance ( 9 n si Data a Table PD-55 - Direct Drive Evaporator Fan Performance 3,4 And 5 Ton YHC036A**H,YHC048A**H,YHC060A**H -High Heat External Static Pressure(Inches of Water)&Motor Power(Bhp)1 Standard Motor Oversized Motor' Unit High Speed Low Speed High Speed Low Speed Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP 960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35 1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36 1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38 1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40 3 YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41 Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42 1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44 1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45 1440 0.34 0.44 - - 0.57 0.51 0.45 0.48 1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56 1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58 1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60 1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63 4 YHC048A**H 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64 Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66 1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68 1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70 1920 0.16 0.57 - - 0.62 0.85 0.13 0.73 1600 0.94 0.78 0.84 0.64 1.27 0.90 1.13 0.85 1700 0.87 0.80 0.71 0.65 1.19 0.94 1.03 0.89 1800 0.82 0.85 0.60 0.65 1.11 0.98 0.92 0.91 1900 0.72 0.88 0.51 0.65 1.10 1.02 0.82 0.94 5 YHC060A**H 2000 0.64 0.90 0.35 0.66 0.93 1.05 0.71 0.95 Horizontal Airflow 2100 0.54 0.93 0.20 0.66 0.84 1.10 0.58 0.96 2200 0.41 0.94 0.05 0.67 0.73 1.12 0.37 0.96 2300 0.32 0.95 - - 0.63 1.17 0.13 0.97 2400 0.21 0.97 - - 0.50 1.20 - - 960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35 1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36 1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38 1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40 3 YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41 Downflow Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42 1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44 1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45 1440 0.34 0.44 - - 0.57 0.51 1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56 1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58 1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60 1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63 4 YHC048A**1-1 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64 Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66 1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68 1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70 1920 0.21 0.57 - - 0.67 0.85 - - 1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85 1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89 1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91 1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94 5 YHC060A**H 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95 Downflow Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96 2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96 2300 0.37 0.95 0.00 0.68 0.68 1.17 0.18 0.97 2400 0.26 0.97 - - 0.55 1.20 - - Fan motor heat(MBH)=3.72 x Fan Bhp+.24. Trane's factory supplied motors,in commercial equipment,are definite purpose motors,specifically designed and tested to operate reliably and continuously at all cataloged conditions.Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure.Our product's warranty will not be affected. NOTES: 1. Data includes pressure drop due to wet coil and filters. 2. 5 Ton oversized motor peformance is with 12 x 11 FC Centrifugal blower fan. 56 RT-PRC006-EN • TRANE' Performance Data Table PD-56 - Evaporator Fan Performance - 3 Ton -YHCO36A3,A4,AW*L,M - Low and Medium Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 - - 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52 1080 537 0.14 606 0.18 669 0.23 724 0.27 I 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58 1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65 1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73 1440 673 0.29 728 0.34 [780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat IMBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave 4K69 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-56 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1000 0.57 1037 0.63 1072 0.69 1106 0.75 1139 0.81 1080 1022 0.64 1058 0.70 1093 0.76 1127 0.82 1161 0.89 1200 1047 0.71 1083 0.77 1117 0.83 1150 0.90 1183 0.97 1320 1075 0.79 1108 0.85 I 1141 0.92 1174 0.99 1206 1.06 1440 1104 0.88 1137 0.95 1170 1.02 1201 1.09 1231 1.16 1-HP Standard Motor& Field Supplied High Static Drive(2) Table PD-57- Evaporator Fan Performance - 3 Ton -VHCO36A3,A4,AW*L,M- Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60 1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69 1200 645 0.22 720 0.28 I 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79 1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 I 1135 0.89 1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00 1-HP Standard Motor&Field Supplied High Static Drive(2) For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat IMBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt may be necessary. Table PD-57 - Continued 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt maybe necessary. External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90 1080 1090 0.75 I 1123 0.81 1154 0.87 1185 0.93 1215 0.99 1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12 1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26 1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41 1-HP Standard Motor& Field Supplied High Static Drive(2) RT-PRC006-EN 57 0 TWINE' Performance 'Ton) Data Table PD-58- Belt Drive Evaporator Fan Performance -3 Ton - YHC036A3,A4,AW*H - High Heat -Down flow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52 1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59 1200 593 0.19 657 0.23 716 0.28 I 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66 1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74 1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite NOTES: purpose motors,specifically designed and tested to operate reliably and Data includes pressure drop due to standard filters and wet coils. continuously at all cataloged conditions.Using the full horsepower range of No accessories or options are included in pressure drop data. our fan motors as shown in our tabular data will not result in nuisance Refer to Table PD-89 to determine additional static pressure drop tripping or premature motor failure.Our product's warranty will not be due to other options/accessories affected. Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK69 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-58- Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 960 1005 0.58 1041 0.64 1076 0.70 1110 0.76 1142 0.82 1080 1029 0.65 1064 0.71 1099 0.77 I 1133 0.83 1166 0.90 1200 1053 0.72 1089 0.78 1123 0.85 1156 0.91 1189 0.98 1320 1082 0.80 1116 0.87 1150 0.93 1182 1.00 1214 1.07 1440 1113 0.90 1146 0.97 1178 1.04 1209 1.11 1240 1.18 1-HP Standard Motor& Field Supplied High Static Drive(2) Table PD-59 - Belt Drive Evaporator Fan Performance - 3 Ton -YHC036A3,A4,AW*H - High Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60 1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70 1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80 1320 711 0.29 I 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 I 1142 0.90 1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02 1-HP Standard Motor&Field Supplied High Static Drive(2) For Standard Evaporator Fan Speed(RPM),reference Table PD-85. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-88 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied FanSheaveAK69required.FieldSuppliedBelt may be necessary. Table PD-59 - Continued 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt may benecessary. External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&Field Motor&Drive Supplied High Static Drive(2) 960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90 1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00 1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13 1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28 1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43 58 RT-PRC006-EN TRM/E® ANE Perform44)4 t Data Ictency Table PD-60 - Belt Drive Evaporator Fan Performance - 4 Ton -YHC048A3,A4,AW*L,M - Low and Medium Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 614 0.22 675 0.26 733 0.31 787 0.37 834 0.42 878 0.48 919 0.53 959 0.59 997 0.65 1034 0.71 1440 676 0.30 731 0.34 784 0.39 I 835 0.46 883 0.52 925 0.58 965 0.64 1003 0.70 1039 0.76 1075 0.83 1600 739 0.40 789 0.45 I 838 0.50 885 0.56 931 0.63 973 0.70 1012 0.77 1049 0.84 1085 0.91 1118 0.97 1760 803 0.51 1 850 0.57 894 0.63 938 0.69 981 0.76 1021 0.83 1061 0.92 1097 0.99 1131 1.07 1164 1.14 1920 867 0.65 911 0.72 952 0.78 993 0.84 1033 0.91 1071 0.99 1110 1.07 1145 1.16 1180 1.25 1213 1.33 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessoriesdue to other options/accessories Fan Motor Heat)MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan SheaveAK61 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-60 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1069 0.77 1104 0.83 1138 0.90 1170 0.97 1203 1.04 1440 1109 0.89 1141 0.96 1175 1.03 1205 1.10 1236 1.17 • 1600 1151 1.04 1183 1.11 1215 1.19 1246 1.26 I 1275 1.33 1760 1197 1.21 1227 1.29 1 1258 1.36 1287 1.44 - - 1920 1243 1.41 1 1274 1.49 - - - - -1 1-HP Standard Motor&Field Supplied High Static Drive(2) Table PD-61- Belt Drive Evaporator Fan Performance - 4 Ton -YHC048A3,A4,AW*L,M - Low and Medium Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor& Field Supplied Low Static Drive(1) 1-HP Standard Motor&Drive 1280 681 0.26 755 0.32 816 0.38 870 0.45 921 0.51 968 0.58 1013 0.65 1053 0.72 1091 0.79 1127 0.86 1440 748 0.36 817 0.43 I 876 0.49 927 0.56 976 0.63 1022 0.70 1065 0.78 1106 0.85 1144 0.93 1180 1.01 1600 816 0.47 1 879 0.55 937 0.62 987 0.70 1033 0.78 1076 0.85 1119 0.93 1158 1.01 1197 1.10 1233 1.18 1760 885 0.61 943 0.69 999 0.78 1049 0.86 1093 0.94 1135 1.03 1174 1.11 1213 1.20 1250 1.29 11286 1.38 1920 956 0.77 1009 0.86 1062 0.96 1110 1.05 1154 1.14 1195 1.23 1232 1.32 11269 1.41 1304 1.50 - - For Standard Evaporator Fan Speed(RPM),reference Table PD-S6. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includas pressure drop due to standard-.and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1-HP Standard Motor&Field 1. Field Supplied Fan SheaveAK61 required.Field Supplied Belt Supplied High Static Drive(2) may be necessary. 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt may be necessary. Table PD-61 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1162 0.94 1193 1.01 1225 1.09 1255 1.16 1284 1.23 1440 1214 1.09 1247 1.18 I 1278 1.26 1309 1.35 1337 1.43 1600 1268 1.27 1300 1.35 1332 1.45 - - - - 1760 1320 1.47 - - - - - - 1920 - - - - - - - - 1-HP Standard Motor&Field Supplied High Static Drive(2) RT-PRC006-EN 59 0 rRANE° Performance Data u 44 Table PD-62- Belt Drive Evaporator Fan Performance - 4 Ton -YHC048A3,A4,AW*H- High Heat- Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1280 627 0.23 688 0.27 745 0.32 797 0.38 844 0.43 887 0.49 928 0.54 967 0.60 1006 0.66 1042 0.72 1440 691 0.31 746 0.36 798 0.41 I 848 0.47 894 0.54 936 0.60 975 0.66 1012 0.72 1049 0.78 1085 0.85 1600 756 0.41 806 0.47 I 854 0.52 901 0.58 945 0.66 987 0.73 1025 0.79 1061 0.86 1096 0.93 1129 1.00 1760 822 0.54 I 868 0.60 912 0.65 955 0.71 997 0.79 1038 0.87 1076 0.95 1111 1.02 1145 1.10 1178 1.17 1920 889 0.69 931 0.75 972 0.81 1012 0.88 1051 0.95 1090 1.03 1127 1.11 1162 1.20 1196 1.29 1228 1.37 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK61 required.Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary. Table PD-62 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1077 0.78 1112 0.85 1145 0.91 1178 0.98 1210 1.05 1440 1118 0.91 1150 0.98 1183 1.05 1214 1.12 1244 1.19 1600 1162 1.06 1193 1.13 1225 1.21 I 1255 1.28 1285 1.36 1760 1208 1.24 1239 1.32 11268 1.39 1297 1.47 - - 1920 I 1258 1.45 - - - - - 1-HP Standard Motor&Field Supplied High Static Drive(2) Table PD-63 - Belt Drive Evaporator Fan Performance -4 Ton -YHC048A3,A4,AW*H- High Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor& Field Supplied Low Static Drive(1) 1-HP Standard Motor&Drive 1280 698 0.28 769 0.34 828 0.40 881 0.46 932 0.52 978 0.59 1021 0,66 1061 0.73 1099 0.81 1134 0.88 1440 767 0.37 I 834 0.44 890 0.51 941 0.58 988 0.65 1034 0.72 1077 0.80 1116 0.87 1153 0.95 1190 1.03 1600 837 0.50 899 0.57 955 0.65 1003 0.72 1048 0.80 1091 0.88 1132 0.96 1171 1.04 1209 1.12 1245 1.21 1760 908 0.64 966 0.73 1020 0.81 1067 0.89 1110 0.98 1151 1.06 1190 1.15 1228 1.23 11264 1.32 1300 1.41 1920 981 0.82 1035 0.91 1085 1.00 1133 1.09 1174 1.18 1213 1.27 1250 1.37 I 1286 1.46 - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1-HP Standard Motor&Field 1. Field Supplied Fan Sheave AK61 required.Field Supplied Belt maybe necessary. Supplied High Static Drive(2) 2. Field Supplied Fan SheaveAK41 required.Field Supplied Belt may be necessary. Table PD-63 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1280 1169 0.96 1201 1.03 1231 1.10 1262 1.17 1290 1.24 1440 1222 1.11 I 1256 1.20 1286 1.28 1317 1.37 1346 1.45 1600 1278 1.29 1311 1.38 1342 1.48 - - - - 1760 - - - - - - - 1920 - - - - - - - - - 1-HP Standard Motor&Field Supplied High Static Drive(2) 60 RT-PRC006-E N 1 TWIE° Performance Data Table PD-64 - Belt Drive Evaporator Fan Performance - 5 Ton -YHCO6OA3A4,AW*L,M- Low and Medium Heat- Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1600 704 0.36 757 0.41 806 0.47 853 0.52 899 0.58 942 0.65 984 0.72 1021 0.79 1058 0.85 1092 0.92 1800 777 0.49 828 0.56 872 0.62 I 915 0.67 957 0.73 998 0.80 1038 0.88 1076 0.96 1112 1.04 1146 1.11 2000 851 0.66 I 900 0.73 942 0.80 981 0.87 1019 0.93 1057 0.99 1094 1.07 1130 1.15 1165 1.24 1199 1.33 2200 927 0.86 973 0.94 1012 1.02 1049 1.09 1084 1.17 1119 1.23 1153 1.30 1188 1.38 1220 1.46 I - - 2400 1003 1.10 1045 1.19 1084 1.28 1119 1.36 1152 1.44 I - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: Trane's factory supplied motors,in commercial equipment,are definite purpose Data includes pressure drop due to standard filters and wet coils. motors,specifically designed and tested to operate reliably and continuously at No accessories or options are included in pressure drop data. all cataloged conditions.Using the full horsepower range of our fan motors as Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature due to other options/accessories motor failure.Our product's warranty will not be affected. Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt may be necessary. Table PD-64 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1125 0.98 1158 1.06 1190 1.13 1220 1.20 1250 1.27 1800 1178 1.19 1209 1.26 1239 1.33 1269 1.41 1296 1.48 2000 1232 1.42 1263 1.50 I - - - - - - 2200 - - - - - - - - - - 2400 - - - - - - - - - - Table PD-65- Belt Drive Evaporator Fan Performance - 5 Ton -YHC060A3,A4,AW*L,M- Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor& Field Supplied Low Static Drive 11) 1-HP Standard Motor&Drive 1600 775 0.42 837 0.50 898 0.57 952 0.65 1000 0.72 1044 0.79 1086 0.87 1127 0.95 1166 1.03 1203 1.11 1800 856 0.58 I 912 0.66 967 0.74 1020 0.83 1069 0.91 1112 1.00 1152 1.08 1189 1.16 1227 1.25 1263 1.34 2000 939 0.77 990 0.86 1040 0.96 1089 1.05 1136 1.141180 1.24 1219 1.33 1256 1.42 1292 1.50 I 2200 1023 1.01 1070 1.11 1115 1.21 1160 1.31 1205 1.41 I - - - - - - - 2400 1108 1.29 1151 1.39 1193 1.50 I - - - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt may be necessary. Table PD-65 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 CFM RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1239 1.19 1272 1.28 1304 1.37 1336 1.46 1800 1299 1.43 I - - - - - - 2000 - - - - - - 2200 - - - - - - 2400 - - - - - - RT-PRC006-EN 61 0 TRANE° Performance Data Table PD-66- Belt Drive Evaporator Fan Performance -5 Ton -YHC060A3,A4,AW*H - High Heat- Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Feld Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1600 723 0.38 774 0.43 822 0.48 869 0.54 914 0.60 957 0.68 997 0.75 1035 0.81 1070 0.88 1104 0.94 1800 801 0.52 847 0.58 891 0.64 I 933 0.70 975 0.76 1015 0.83 1054 0.91 1091 0.99 1126 1.07 1160 1.15 2000 878 0.70 I 922 0.77 962 0.84 1001 0.90 1039 0.96 1076 1.03 1113 1.11 1149 1.20 1183 1.28 1217 1.38 2200 957 0.91 999 0.99 1036 1.07 1072 1.14 1107 1.21 1142 1.28 1176 1.35 1209 1.43 I - - - - 2400 1036 1.17 1076 1.26 1111 1.34 1144 1.42 1177 1.50 I - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt maybe necessary. Table PD-66 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 1600 1137 1.01 1168 1.08 1199 1.15 1230 1.22 1260 1.29 1800 1191 1.22 1222 1.29 1252 1.37 1281 1.44 1310 1.50 1000 1248 1.46 I - - - - - - - - 2200 - - - - - - - - - - 2400 - - - - - - - - - - Table PD-67- Belt Drive Evaporator Fan Performance - 5 Ton - YHC060A3,A4,AW*H - High Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor& 1-HP Standard Motor&Drive Field Supplied High Static Drive(1) 1600 796 0.45 858 0.52 917 0.60 969 0.67 1015 0.75 1059 0.82 1100 0.90 1141 0.98 1178 1.06 1216 1.14 1800 881 0.61 I 935 0.70 991 0.78 1042 0.87 1087 0.95 1129 1.03 1168 1.12 1206 1.20 1244 1.29 1279 1.38 2000 967 0.82 1016 0.91 1066 1.01 1115 1.10 1160 1.19 1201 1.28 1239 1.38 1275 1.47 I - - - - 2200 1054 1.07 1099 1.17 1144 1.27 1189 1.38 1233 1.48 I - - - - - - - - - 2400 1141 1.37 1183 1.48 - - - - - - - - - - - - - - - - For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuouslyat Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 1. Field Supplied Fan Sheave AK56 required.Field Supplied Belt maybe necessary. Table PD-67 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 CFM RPM BHP RPM BHP RPMBHP RPM BHP RPM BHP 1-HP Standard Motor&Drive 160 0 1251 1.22 1283 1.31 1315 1.40 1345 1.49 1800 1313 1.47 I - - - - - - 2000 - - - - - - - - 2200 - - - - - - - - 2400 - - - - - - - - 62 RT-PRC006-EN 0 TRANS' Performance ¢ } f Data 11 Mil Liii Glen Table PD-68- Belt Drive Evaporator Fan Performance - 6 Ton -YHC072A3,A4,AW*L,M- Low and Medium Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 - - - - 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91 2160 - - 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04 2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20 2640 606 0.53 657 0.62 703 0.70 I 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37 2880 651 0.67 699 0.77 I 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 11010 1.58 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose / NOTES: motors,specifically designed and tested to operate reliably and continuously at 2-HP Oversized Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Motor&Drive No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. • due to other options/accessories 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. Table PD-68 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&High Static Drive Kit Motor&Drive (or 2 HP Oversized Motor&Drive) 1920 941 0.99 977 1.07 1009 1.15 1041 1.23 1073 1.32 1103 1.40 1132 1.49 1159 1.57 1187 1.66 1213 1.75 2160 964 1.13 997 1.23 1031 1.32 1061 1.41 1093 1.50 11123 1.60 1151 1.69 1179 1.78 1207 1.87 1234 1.97 2400 988 1.29 11020 1.39 1054 1.50 I 1085 1.60 1114 1.70 1143 1.80 1171 1.90 1200 2.01 1227 2.11 1254 2.21 2640 1014 1.47 I 1046 1.58 107/ 1.69 1107 1.80 1138 1.91 1166 2.02 1193 2.13 1222 2.25 - - - - 2880 1042 1.68 1073 1.79 1103 1.90 1132 2.02 1162 2.14 1190 2.26 - - - - - - - - 2-HP Oversized Motor&Drive Table PD-69 - Belt Drive Evaporator Fan Performance - 6 Ton -YHC07243,A4,AW*H- High Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 - - 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95 2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11 2400 612 0.48 662 0.56 711 0.65 I 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29 2640 663 0.63 709 0.71 I 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 11018 1.49\ 2880 715 0.80 758 0.88 - 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72 For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: 2-HP Oversized Motor&Drive Trane's factory supplied motors,in commercial equipment,are definite purpose 1-HP Standard Motor&High Static motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive Kit(or 2-HP Oversized Motor) No accessories or options are included in pressure drop data, shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP-F.4024.2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan SheaveAK84andBeltAX34required. Table PD-69 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1,90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&High Static Drive Kit Motor&Drive (or 2 HP Oversized Motor&Drive) 1920 963 1.04 997 1.12 1028 1.20 1061 1.28 1090 1.36 1119 1.45 1149 1.54 1177 1.63 1203 1.71 1229 1.80 2160 990 1.21 11023 1.30 1055 1.39 1086 1.48 I 1115 1.57 1144 1.66 1173 1.76 1200 1.85 1227 1.95 1253 2.04 2400 1019 1.39 1051 1.49 I 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 - - 2640 1050 1.59 1081 1.70 1111 1.81 1141 1.93 1170 2.04 1198 2.15 1226 2.27 - - - - - - 2880 1084 1.83 1114 1.94 1143 2.06 1172 2.18 1199 2.30 - - - - - - - - - - 2-HP Oversized Motor&Drive RT-PRC006-EN 63 TRANS® Performance Data x: - - :H Table PD-70- Belt Drive Evaporator Fan Performance - 6 Ton -YHC072A3A4,AW*L,M- Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 - - 591 0.34 649 0.42 699 0.48 745 0.56 789 0.64 834 0.72 877 0.81 918 0.89 957 0.97 2160 587 0.38 633 0.44 690 0.52 1 740 0.61 784 0.68 825 0.76 865 0.85 904 0.95 943 1.04 981 1.13 2400 643 0.51 682 0.58 1 732 0.65 781 0.75 825 0.84 864 0.92 902 1.01 938 1.11 974 1.21 I 1010 1.32 2640 700 0.66 1 736 0.74 775 0.81 822 0.90 866 1.01 906 1.11 942 1.20 976 1.29 1009 1.40 I 1042 1.51 2880 756 0.84 790 0.93 823 1.01 864 1.09 907 1.20 947 1.32 983 1.4.3 1017 1.53 1048 1.62 1080 1.73 2-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor&High Static Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as Drive(or 2-HP Oversized Motor) No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH(=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84 and Belt AX34 required. 2. Field Supplied Fan Sheave AK54 and Belt AX30 required. Table PD-70 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 -_ 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard 1-HP Standard Motor&High Static Motor&Drive Drive Kit(or 2 HP Oversized Motor&Drive) 1920 996 1.06 1033 1.16 1067 1.25 1102 1.35 1134 1.44 1165 1.53 1195 1.63 1223 1.72 1251 1.82 1277 1.91 2160 1018 1.23 1054 1.32 1090 1.42 1 1123 1.52 1156 1.63 1188 1.73 1218 1.84 1247 1.94 1276 2.05 1 1304 2.16 2400 1044 1.42 I 1079 1.52 1112 1.62 1145 1.73 1177 1.83 1208 1.94 1240 2.06 1268 2.17 1298 2.29 - - 2640 1075 1.62 1107 1.74 1139 1.85 1170 1.96 1201 2.08 1232 2.19 - - - - 2-HP Oversized Motor 2880 1111 1.85 1140 1.97 1169 2.09 1200 2.22 - - - - - - - - &FieldSupplied High 2-HP Oversized Motor&Drive Static Drive 121 Table PD-71 - Belt Drive Evaporator Fan Perfomrance - 6 Ton -YHC072A3A4,AW*H- High Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&Field Supplied 1-HP Standard Motor&Drive Low Static Drive(1) 1920 565 0.31 627 0.39 680 0.46 727 0.52 772 0.61 816 0.69 859 0.77 902 0.86 942 0.94 981 1.03 2160 621 0.43 677 0.50 I 729 0.59 774 0.66 816 0.74 856 0.83 895 0.93 934 1.02 973 1.11 1 1009 1.21 2400 680 0.57 I 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 11006 1.31 1041 1.41 2640 741 0.75 782 0.82 828 0.92 872 1.03 911 -1.13 947 1.21 981 1.31 1014 1.41 11048 1.53 1079 1.64 2880 802 0.95 837 1.04 880 1.13 921 1.24 960 1.56 995 1.47 1028 1.56 1060 1.66 1091 1.77 1122 1.89 2-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose 1-HP Standard Motor&High Static NOTES: motors,specifically designed and tested to operate reliably and continuously at Drive Kit(or 2-HP Oversized Motor) Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 1-HP Fan Motor Heat(MBH)=2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat(MBH)=3.000 x Fan BHP+.5000 1. Field Supplied Fan Sheave AK84and Belt AX34required. 2. Field Supplied Fan Sheave AK54 and Belt AX30 required. Table PD-71 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1-HP Standard Motor&High Static Drive Kit (or 2 HP Oversized Motor&Drive) 1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78 1268 1.88 1293 1.97 2160 1045 1.30 1081 1.40 1114 1.50 1 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03 11298 2.13 1324 2.24 2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 - - - - 2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21 - - - - - - - - - - 2880 1151 2.02 1180 2.14 1209 2.27 - - - - - - - - - - - - - - 2-HP Oversized Motor&Drive 2-HP Oversized Motor&Field Supplied High Static Drive(2) 64 RT-PRC006-E N TRANE` Performance Data Table PD-72 - Belt Drive Evaporator Fan Performance - T/2-Ton -YHC092A3A4AW*L,M- Low and Medium Heat -DownfowAirfow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2400 - - - 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30 2700 - - - - 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 1796 1.18 828 1.32 857 1.45 3000 - - 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 I 792 1.22 826 1.36 858 1.49 888 1.64 3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 I 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85 3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10 2-HP Standard Motor&Drive For Standard Evaporator Fan Speed(RPM).reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-72 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2400 858 1.4.3 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75 2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00 3000 916 1.79 944 1.94 970 2.10 995 2.26 I 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27 3300 947 2.01 974 2.16 11000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 - - 3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 - - - - - - 3-HP Oversized Motor&Drive Table PD-73 - Belt Drive Evaporator Fan Performance - Th-Ton - YHC092A3,A4,AW*H - High Heat -DownflowAirflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2400 - - - - - - 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32 2700 - - - - 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 1 804 1.21 835 1.35 865 1.49 3000 - - 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 I 804 1.26 837 1.40 868 1.54 897 1.69 3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 1 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91 3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17 2-HP Standard Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. --dYlte--Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-73 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78 2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 I 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05 3000 925 1.83 952 1.99 978 2.15 I 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33 3300 958 2.06 984 2.22 I 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 - - - - 3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 - - - - - - 3-HP Oversized Motor&Drive RT-PRC006-EN 65 0 TRANE" Performance / I Data Table PD-74 - Belt Drive Evaporator Fan Performance - 7/2-Ton -YHC092A3,A4,AW*L,M- Low and Medium Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2400 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39 2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68 3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99 3300 719 1.00 758 1.11 I 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 11048 2.34 3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan SheaveAK79andBeltAX38required. Table PD-74 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49 2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 I 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86 3000 1031 2.12 1056 2.25 I 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30 3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36 - - - - - - 3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 - - - - - - - - - - - - 3-HP Oversized Motor&Drive Table PD-75 - Belt Drive Evaporator Fan Performance - 7/2-Ton -YHCO92A3,A4,AW*H - High Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2400 - - 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42 2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72 3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05 3300 740 1.06 780 1.19 I 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 11063 2.42 3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 I 1043 2.45 1077 2.64 1108 2.83 2-HP Standard Motor&Drive I 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and BeltAX38 required.. Table PD-75 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52 2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 I 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90 3000 1043 2.18 I 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35 3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43 - - - - - - 3600 137 3.00 1163 3.17 1188 3.33 - - - - - - - - - - - - - - 3-HP Oversized Motor&Drive 66 RT-PRC006-EN 0 TRAPIE® Performance Data Table PD-76- Belt Drive Evaporator Fan Performance - 81/2-Ton -YHC102A3,A4,AW*L - Low Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2720 - - - - 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52 3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 I 814 1.32 846 1.45 878 1.60 907 1.75 3400 643 0.77 683 0.89 718 1.00 753 1.13 I 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02 3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 I 982 2.33 4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data, shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied FarrSheave AK79 and Belt AX38 required. Table PD-76 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09 3060 936 1.90 962 2.06 989 2.22 I 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43 3400 973 2.17 I 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 - - 3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 - - - - - - - - 4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 - - - - - - - - - - - - 3-HP Oversized Motor&Drive Table PD-77- Belt Drive Evaporator Fan Performance - 8'/2-Ton - YHC102A3,A4AW*M- Medium Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2720 - - - - 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53 3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 I 815 1.32 848 1.46 880 1.60 909 1.75 3400 645 0.77 685 0.89 721 1.01 755 1.13 I 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02 3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 I 984 2.34 4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-77 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10 3060 936 1.91 964 2.07 989 2.23 I 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44 3400 974 2.18 I 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 - - - - 3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 - - - - - 4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 - - - - - - - 3-HP Oversized Motor&Drive RT-PRC006-EN 67 TRANS® Performance Data icy Table PD-78- Belt Drive Evaporator Fan Performance - 81/2-Ton -YHC102A3,A4,AW*H - High Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2720 - - 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56 3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 I 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80 3400 660 0.82 698 0.94 733 1.05 767 1.18 I 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08 3740 718 1.06 754 1.19 I 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 I 996 2.41 4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-78 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13 3060 945 1.95 971 2.11 997 2.28 I 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 3400 985 2.24 I 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 - - - - - - 3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 - - - - - - - - 4080 1063 2.96 1089 3.15 1114 3.34 - - - - - - - - - - - - 3-HP Oversized Motor&Drive Table PD-79 - Belt Drive Evaporator Fan Performance - 81/2-Ton -YHC102A3A4,AW*L- Low Heat-Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74 3060 688 0.85 732 0.97 770 1.09 I 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13 3400 756 1.14 1 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 11049 2.40 1079 2.56 3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 I 1025 2.42 1061 2.62 1095 2.82 1127 3.02 4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 - - 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750. 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-79 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94 3060 1053 2.26 I 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45 3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 - - - - - - - - 3740 1158 3.21 1185 3.39 - - - - - - - - - - - - - 4080 - - - - - - - - - - - - - - - - 3-HP Oversized Motor&Drive 68 RT-PRC006-EN TRANS® Performance K Data Table PD-80- Belt Drive Evaporator Fan Performance - 81/2-Ton -YHC102A3,A4,AW*M - Medium Heat - Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied Low Static Drive(1) 2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75 3060 691 0.86 734 0.98 772 1.10 I 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14 3400 759 1.15 I 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 I 1052 2.41 1082 2.57 3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 I 1029 2.44 1064 2.64 1098 2.84 1130 3.03 4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 - - 2-HP Standard Motor&Drive 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane'sfactory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-8O - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95 3060 1054 2.27 I 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 - - 3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 - - - - - - - - - - 3740 1160 3.23 1187 3.41 - - - - - - - - - - - - - - 4080 - - - - - - - - - - - - - - - - - - 3-HP Oversized Motor&Drive Table PD-81 - Belt Drive Evaporator Fan Performance - 81/2-Ton -YHC102A3,A4,AW*H- High Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Field Supplied 2-HP Standard Motor&Drive Low Static Drive(1) 2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79 3060 709 0.91 750 1.03 I 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19 3400 778 1.21 1 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.301 1067 2.49 1095 2.65 3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 I 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15 4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 - - - - 3-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane'sfactory supplied motors,in commercial equipment,are definite purpose NOTES: ��- motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 2-HP Fan Motor Heat(MBH)=2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.4750 1. Field Supplied Fan Sheave AK79 and Belt AX38 required. Table PD-81 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2-HP Standard Motor&Drive 2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98 3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 - - 3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 - - - - - - - - 3740 1177 3.34 - - - - - - - - - - - - - 4080 - - - - - - - - - - - - - - - 3-HP Oversized Motor&Drive RT-PRC006-EN 69 TRANE Performance Data f" Table PD-82- Belt Drive Evaporator Fan Performance - 10-Ton - YHC120A3,A4,AW*L,M - Low and Medium Heat - Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied Low Static Drive(1) 3200 - - - - - - 743 1.06 779 1.20 814 1.35 847 1.49 879 1.63 910 1.78 938 1.93 3600 - - 735 1.10 768 1.22 802 1.36 834 1.50 866 1.66 897 1.82 1927 1.98 957 2.14 985 2.30 4000 767 1.29 802 1.44 833 1.58 863 1.71 892 1.87 [ 922 2.04 951 2.21 979 2.39 1006 2.56 1034 2.74 4400 837 1.69 869 1.85 899 2.00 I 926 2.15 953 2.31 980 2.48 1007 2.66 1033 2.85 1059 3.04 1085 3.24 4800 908 2.16 937 2.33 965 2.50 991 2.67 1017 2.83 1041 3.00 1066 3.19 1090 3.38 1115 3.59 1139 3.80 3-HP Standard Motor&Drive 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. NOTES: Trane's factory supplied motors,in commercial equipment,are definite purpose Data includes pressure drop due to standard filters and wet coils. motors,specifically designed and tested to operate reliably and continuously at No accessories or options are included in pressure drop data. all cataloged conditions.Using the full horsepower range of our fan motors as Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature due to other options/accessories motor failure.Our product's warranty will not be affected. 3-HP Fan Motor Heat IMBHI=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave t VM50 x 7/8 inch,Fan Sheave AK89,and Belt AX40 required. Table PD-82 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 3200 966 2.10 992 2.26 1018 2.43 1042 2.60 1066 2.78 1091 2.96 1114 3.15 1136 3.33 1159 3.51 1182 3.70 3600 1013 2.47 1039 2.64 1065 2.82 1089 3.00 1113 3.19 1135 3.38 I 1157 3.56 1179 3.76 1201 3.97 1221 4.16 4000 1060 2.92 1086 3.10 1111 3.28 1 1135 3.47 1159 3.66 1182 3.86 1203 4.05 1224 4.26 1246 4.47 1266 4.68 4400 1110 3.43 I 1134 3.62 1159 3.82 1183 4.02 1205 4.22 1229 4.43 1251 4.64 1272 4.84 1292 5.05 1313 5.27 4800 1162 4.01 1185 4.22 1209 4.44 1231 4.64 1253 4.86 1276 5.07 1298 5.30 1319 5.51 1338 5.73 - - 5-HP Oversized Motor&Drive Table PD-83- Belt Drive Evaporator Fan Performance - 10-Ton - YHC120A3,A4,AW*H- High Heat -Downflow Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied 3-HP Standard Motor Low Static Drive(1) &Drive 3200 - - 739 1.05 774 1.19 809 1.33 843 1.47 874 1.61 905 1.76 935 1.92 963 2.08 3600 738 1.11 772 1.23 805 1.37 838 1.52 869 1.68 900 1.84 I 930 2.00 960 2.16 988 2.32 1016 2.49 4000 813 1.49 844 1.63 873 1.77 903 1.93 I 932 2.10 961 2.27 989 2.45 1017 2.63 1043 2.80 1070 2.98 4400 889 1.95 I 917 2.10 944 2.25 971 2.42 998 2.59 1024 2.78 1050 2.97 1076 3.17 1101 3.371 1126 3.56 4800 964 2.50 991 2.66 1016 2.83 1040 3.00 1065 3.18 1090 3.38 1114 3.58 1138 3.79 1161 4.00 1184 4.22 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed IRPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1VM50x7/flinch,Fan Sheave AK89,and Belt AX4orequired Table PD-83 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 3200 989 2.24 1015 2.41 1039 2.58 1064 2.76 1087 2.93 1111 3.12 1133 3.30 1156 3.48 1179 3.68 1200 3.85 3600 1042 2.66 1067 2.84 1091 3.02 1115 3.21 1138 3.40 I 1160 3.59 1181 3.78 1203 3.98 1224 4.19 1244 4.39 4000 1095 3.17 1120 3.35 I 1145 3.54 1167 3.73 1190 3.93 1212 4.14 1233 4.35 1253 4.55 1273 4.76 1293 4.97 4400 1150 3.75 1174 3.95 1197 4.15 1221 4.36 1243 4.56 1265 4.77 1285 4.97 1306 5.20 1326 5.42 1345 5.65 4800 1208 4.42 1231 4.64 1253 4.86 1275 5.07 1297 5.29 1317 5.50 1338 5.72 - - - - 5-HP Oversized Motor&Drive 70 RT-PRC006-EN TRANE' Performance Data Table PD-84 - Belt Drive Evaporator Fan Performance - 10-Ton -YHC120A3,A4,AW*L,M-Low and Medium Heat- Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied Low Static Drive(1) 3200 - - 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38 3600 819 1.42 857 1.57 890 1.71 I 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96 4000 902 1.91 I 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 I 1189 3.57 4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 I 1155 3.58 1186 3.80 1217 4.03 1246 4.25 4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05 3-HP Standard Motor 5-HP Oversized Motor&Drive &Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES: motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1 VM50 x 7/8 inch,Fan Sheave AK89,and Belt AX40 required. Table PD-84 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 3200 1090 2.53 1115 2.67 1139 2.81 1161 2.95 1183 3.09 1205 3.23 1225 3.37 1246 3.51 1265 3.65 1284 3.78 3600 1157 3.13 1181 3.29 1205 3.45 I 1228 3.61 1250 3.77 1272 3.93 1293 4.09 1312 4.24 1331 4.40 1351 4.56 4000 1218 3.78 1246 3.99 1271 4.18 1294 4.36 1317 4.55 1338 4.72 1360 4.91 1379 5.07 1398 5.25 1418 5.43 4400 1276 4.49 1304 4.73 1333 4.97 1359 5.20 1383 5.42 1405 5.62 - - - - - - - - 4800 1336 5.30 1363 5.56 - - - - - - - - - - - - - - - - 5-HP Oversized Motor&Drive Table PD-85 - Belt Drive Evaporator Fan Performance - 10-Ton -YHC120A3,A4,AW*H- High Heat -Horizontal Airflow External Static Pressure(Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Field Supplied 3-HP Standard Motor&Drive Low Static Drive(1) 3200 785 1.18 821 1.31 861 146 903 62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55 3600 874 164 907 178 I 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21 4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 11185 3.55 1215 3.76 1242 3.96 4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 I 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79 4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74 5-HP Oversized Motor&Drive For Standard Evaporator Fan Speed(RPM),reference Table PD-86. Trane's factory supplied motors,in commercial equipment,are definite purpose NOTES. motors,specifically designed and tested to operate reliably and continuously at Data includes pressure drop due to standard filters and wet coils. all cataloged conditions.Using the full horsepower range of our fan motors as No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Refer to Table PD-89 to determine additional static pressure drop motor failure.Our product's warranty will not be affected. due to other options/accessories 3-HP Fan Motor Heat(MBH)=2.900 x Fan BHP+.475. 5-HP Fan Motor Heat(MBH)=2.950 x Fan BHP+.470. 1. Field Supplied Motor Sheave 1VM50 x 7/8 inch,Fan Sheave AK89,and Belt AX40 required Table PD-85 - Continued External Static Pressure(Inches of Water) 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3-HP Standard Motor&Drive 3200 1120 2.70 1143 2.84 1166 2.98 1188 3.12 1208 3.25 1229 3.39 1249 3.53 1269 3.67 1289 3.82 1308 3.96 3600 1194 3.37 I 1217 3.53 1240 3.69 1262 3.85 1282 4.01 1303 4.17 1322 4.32 1341 4.48 1361 4.64 1378 4.79 4000 1269 4.16 1292 4.34 1314 4.52 1335 4.70 1356 4.88 1377 5.06 1397 5.24 1415 5.41 - - - - 4400 1339 5.02 1365 5.25 1388 5.47 1410 5.67 - - - - - - - - - - 4800 - - - - - - - - - - - - - - - - - 5-HP Oversized Motor&Drive RT-PRC006-EN 71 0 'FRAME Performance Data Table PD-86— Standard Motor&Sheave/Fan Speed(Rpm) Unit 6Turns 5Turns 4Tums 3Turns 2Tums 1Tum Tons Model No. Open Open Open Open Open Open Closed 3 Y#C036A NA 745 819 894 968 1043 1117 4 Y#C048A NA 833 916 1000 1083 1167 1250 5 Y#C060A NA 897 987 1077 1166 1256 1346 6 Y#C072A N/A 723 779 835 890 946 1002 71/2 Y#C090,092A N/A 835 891 946 1002 1057 1113 81/2 Y#C102A N/A 787 847 908 968 1029 1089 10 Y#C120A N/A 908 969 1029 1090 1150 1211 Factory set at3 turns open. Table PD-87— Standard Motor& High Static Drive Accessory Sheave/Fan Speed(Rpm) Unit 6Tums 5Turns 4Turns 3Turns 2Turns 1Turn Tons Model No. Open Open Open Open Open Open Closed 6 Y#C072A3,A4,AW N/A 831 895 959 1022 1086 1150 6 YSC072AK N/A 958 1022 1086 1150 1214 1278 71/2 YSC090,092A N/A 958 1022 1086 1150 1214 1278 Factory set at 3 turns open. Table PD-88 — Oversized Motor&Drive Sheave/Fan Speed(Rpm) Unit 6Tums 5Turns 4Tums 3Turns 2Turns 1Turn Tons Model No. Open Open Open Open Open Open Closed 6 Y#C072A3,A4,AW N/A 958 1022 1086 1150 1214 1278 71/2 Y#C090,092A N/A 1068 1150 1232 1315 1397 1479 81/2 Y#C102A N/A 958 1022 1086 1150 1214 1278 10 Y#C120A 1050 1135 1200 1275 1350 1425 N/A Factory set at 3 turns open. #Indicates both standard and high efficiency units. *Indicates both ReliaTel and Electromechanical controls. 72 RT-PRC006-EN 0 TRAM'' Performance Data Table PD-89 - Static Pressure Drops Through Accessories (Inches Water Column) Economizer with OA/RA Dampers2 Unit Standard Through 2"Pleated 100%OA 100%RA 100%OA 100%RA Tons Model No CFM Filters' Reheat Coil(WC) Filters Downflow Horizontal 960 0.03 - 0.05 0.05 0.01 0.05 0.00 YSC036A 1200 0.04 - 0.07 0.07 0.02 0.07 0.01 1440 0.06 - 0.10 0.10 0.03 0.10 0.01 3 960 0.02 .03 0.04 0.05 0.01 0.05 0.00 YHC036A 1200 0.03 .04 0.05 0.07 0.02 0.07 0.01 1440 0.04 .06 0.07 0.10 0.03 0.10 0.01 1280 0.04 - 0.06 0.08 0.03 0.08 0.01 YSC048A 1600 0.05 - 0.09 0.12 0.04 0.12 0.01 4 1920 0.08 - 0.12 0.17 0.06 0.17 0.02 1280 0.04 .05 0.06 0.08 0.03 0.08 0.01 YHC048A 1600 0.05 .07 0.09 0.12 0.04 0.12 0.01 1920 0.08 .09 0.12 0.17 0.06 0.17 0.02 1600 0.10 - 0.15 0.12 0.04 0.12 0.01 YSC060A 2000 0.15 - 0.22 0.18 0.07 0.18 0.02 2400 0.22 - 0.29 0.26 0.10 0.26 0.04 5 1600 0.04 0.07 0.07 0.12 0.04 0.12 0.01 YHC060A 2000 0.06 0.10 0.10 0.18 0.07 0.18 0.02 2400 0.09 0.14 0.14 0.26 0.10 0.26 0.04 1920 0.04 - 0.07 0.10 0.01 0.06 0.02 6 Y#C072A 2400 0.06 - 0.09 0.11 0.02 0.08 0.02 2880 0.09 - 0.12 0.13 0.04 0.10 0.04 2400 0.06 - 0.09 0.11 0.02 0.08 0.02 YSC090,092A 3000 0.10 - 0.13 0.14 0.05 0.12 0.05 71/2 3600 0.14 - 0.18 0.21 0.07 0.25 0.08 2400 0.04 .10 0.06 0.11 0.02 0.08 0.02 YHC092A 3000 0.06 .14 0.09 0.14 0.05 0.12 0.05 3600 0.09 .19 0.13 0.21 0.07 0.25 0.08 2720 0.05 - 0.08 0.12 0.03 0.09 0.04 YSC102A 3400 0.08 - 0.11 0.19 0.06 0.18 0.06 81/2 4080 0.12 - 0.16 0.30 0.07 0.31 0.09 2720 0.05 .12 0.08 0.12 0.03 0.09 0.04 YHC102A 3400 0.08 .17 0.11 0.19 0.06 0.18 0.06 4080 0.12 .23 0.16 0.30 0.07 0.31 0.09 3200 0.07 - 0.10 0.17 0.05 0.14 0.05 YSC120A 4000 0.11 - 0.15 0.26 0.07 0.30 0.08 10 4800 0.16 - 0.20 0.34 0.09 0.35 0.10 3200 - 0.15 0.10 0.17 0.05 0.14 0.05 YHC120A 4000 - 0.22 0.15 0.26 0.07 0.30 0.08 4800 0.16 0.31 0.20 0.34 0.09 0.35 0.10 Notes: 1. Tested with standard filters 13-5 tons 1",6-10 tons 2").Difference in pressure drop should be considered when utilizing optional 2"pleated filters. 2. OA=Outside Air and RA=Return Air. RT-PRC006-EN 73 0 TRANE® Performance Data Table PD-90— Outdoor Sound Power Level-dB(ref 10-12 Watts) Unit Octave Center Frequency Overall Tons Model No. 63. 125 250 500 1000 2000 4000 8000 dBA 3 Y*C036A 86 83 81 80 78 74 69 68 83 YSC048A1 92 87 84 83 81 76 72 69 86 4 YSC048A3,A4,AW 90 84 78 77 76 72 70 68 82 Y1-1C048A 92 86 83 82 81 75 72 69 85 YSC060A 94 87 83 82 79 75 73 69 84 5 YHCO60A 94 87 82 81 78 74 72 69 84 YSC072A 90 94 90 87 83 78 74 67 88 6 YHC072A 91 95 90 87 84 79 75 68 89 YSC090A 92 95 91 88 84 80 75 68 90 71/2 YSC092A 89 93 88 85 81 76 72 66 87 YHC092A 92 96 92 89 85 80 76 69 91 YSC102A 88 92 87 84 80 75 72 65 86 81/2 YHC102A 91 95 90 87 84 79 75 68 89 10 YSC120A 91 88 84 82 81 76 73 67 86 YHC120A 94 89 87 85 84 78 75 69 88 Note: Tests follow AR 1270-95. Table PD-91 — Gas-Fired Heating Capacities Unit Heating Heating Air Temp. Tons Efficiency Model No. Input MBH Output MBH Rise,F Y*C036A1*L 60.0 47.0 25-55 Y*C036A3,A4,AWL 60.0 48.0 25-56 Standard and Y*C036A1*M 80.0 63.0 35-65 3 High Efficiency Y*C036A3,A4,AW*M 80.0 64.0 35-65 Y*C036A1*H 120.0 95.0 55-85 Y*C036A3,A4,AW*H 120.0 96.0 55-85 Y*C048A1*L, 60.0 47.0 15-45 Y*C048A3,A4,AW*L 60.0 48.0 15-45 Standard and Y*C048A1*M 80.0 63.0 20-50 4 High Efficiency Y*C048A3,A4,AW*M 80.0 64.0 20-50 Y*C048A1*H 120.0 95.0 40-70 Y*C048A3,A4,AW*H 120.0 96.0 40-70 YSCO60A1*L 60.0 47.0 10-40 C060A3.A4 AW AK*C 60.0 - 48.0 10-40 YSC060A1*M 80.0 63.0 15-45 Standard Eff. YSC060A3 A4,AW*M 80.0 64.0 15-45 YSC060A1*H 130.0 103.0 35-65 YSCORflA4 A4,AW AK*H 130 fl 1(14 0 15-fi5 5 YHC060A1*L 60.0 47.0 10-40 YHC060A3,A4,AW,AK*L 60.0 48.0 10-40 High Eff. YHC060A1*M 80.0 63.0 15-45 YHC060A3,A4,AW*M 80.0 64.0 15-45 YHC060A1*H 130.0 103.0 35-65 YHC060A3,A4,AW,AK*H 130.0 104.0 35-65 Standard and Y*C072A1,A3,A4,AW,AK*L 80.0 64.8 15-45 6 High Efficiency Y*C072A1,A3,A4,AW*M 120.0 97.2 20-50 Y*C072A1,A3,A4,AW,AK*H 150.0 121.5 25-55 Standard and Y*C090,092A1,A3,A4,AW,AK*L 120.0 97.2 20-50 71/2 Y*C090,092A1,A3,A4,AW*M 150.0 121.5 25-55 High Efficiency Y*C090,092A1,A3,A4,AW,AK*H 200.0 162.0 35-65 Standard and Y*C102A1,A3,A4,AW,AK*L 120.0 97.2 15-45 81/2 Y*C102A1,A3,A4,AW*M 150.0 121.5 20-50 High Efficiency Y*C102A1,A3,A4,AW,AK*H 200.0 162.0 35-65 Standard and Y*C120A1,A3,A4,AW,AK*L 150.0 121.5 20-50 10 Y*C120A1,A3,A4,AW*M 200.0 162.0 25-55 High Efficiency Y*C120A1,A3,A4,AW,AK*H 250.0 202.5 35-65 Ratings shown are for elevations up to 2,000 ft.For higher elevations,reduce ratings at a rate of 4%per 1,000 ft.elevation. 74 RT-PRC006-EN TWINE' Performance Data Table PD-92-Hot Gas Reheat Temperature Rise? SCFM Leaving Evaporator Dry Bulb[F] Tons SCFM 35 40 45 50 55 60 65 960 17.6 17.3 17.0 16.6 16.2 15.8 15.5 1080 16.7 16.4 16.1 15.7 15.4 15.0 14.6 3 1200 15.8 15.5 15.2 14.9 14.5 14.1 13.8 1320 14.9 14.6 14.3 14.0 13.6 13.3 12.9 1440 14.0 13.8 13.5 13.1 12.8 12.4 12.0 Tons SCFM 35 40 45 50 55 60 65 1280 19.0 18.7 18.4 18.1 179 17.5 172 1440 17.9 17.7 17.4 171 16.9 16.5 16.2 4 1600 16.9 16.6 16.4 16.1 15.8 15.5 15.2 1760 15.9 15.6 15.4 15.1 14.8 14.5 14.2 1920 14.8 14.6 14.4 14.1 13.8 13.5 13.2 Tons SCFM 35 40 45 50 55 60 65 1600 20.3 20.1 19.9 19.7 19.5 19.3 19.0 1800 19.1 18.9 18.7 18.5 18.4 18.1 178 5 2000 17.9 178 176 174 172 16.9 16.6 2200 16.8 16.6 16.4 16.2 16.0 15.7 15.4 2400 15.6 15.4 15.2 15.1 14.9 14.6 14.3 Tons SCFM 35 40 45 50 55 60 65 2400 16.7 17.3 18.0 18.7 19.3 20.1 20.9 2700 14.9 15.5 16.1 16.7 173 18.0 18.7 71/2 3000 13.1 13.7 14.2 14.7 15.2 15.9 16.5 3300 11.4 11.8 12.3 12.7 13.1 13.7 14.3 3600 9.6 10.0 10.3 10.7 11.1 11.6 12.2 Tons SCFM 35 40 45 50 55 60 65 2720 16.6 17.4 18.2 18.9 19.7 20.3 21.0 3060 14.7 15.3 15.9 16.6 172 177 18.1 81 3400 12.7 13.2 13.7 14.2 14.7 15.0 15.3 3740 10.7 11.1 11.4 11.8 12.2 12.3 12.5 4080 8.7 9.0 9.2 9.4 9.6 9.7 9.7 Tons SCFM 35 40 45 50 55 60 65 3200 18.7 19.5 20.3 21.2 22.0 22.7 23.4 3600 16.2 172 18.1 19.1 20.1 20.8 21.6 10 4000 13.8 14.9 15.9 170 18.1 19.0 19.8 4400 11.3 12.5 13.7 14.9 16.1 171 18.1 4800 8.9 10.2 11.5 12.9 14.2 15.3 16.3 NOTES: 1.Temperature rise does not account for indoor fan heat. 2.70 deg OD Ambient Temperature. 3.For units with the Dehumidification(Hot Gas Reheat)option. RT-PRC006-EN 75 0 MANE' • Zone Controls ReliaTelTM Controlled Units Integrated Comfort System— Programmable Night Setback—Auto Zone Sensors are the building Sensor(s)available with optional or manual changeover with seven-day temperature adjustment and override programming. Keyboard selection of occupant's comfort control devices for buttons to provide Precedent" units with the Micro control: central control liii through aTrane <�°°"" Manual Changeover—Heat,Cool or Off Integrated -82:08 p ;:, TMSystem Switch.Fan Auto or Off Switch. Comfort system. ��D o<. `o One temperature / o o 7:setpoint lever. 2 0 Bim, o0 CANCEL Heat,Cool,Fan,Auto,or On. All programmable sensors have System On, Heat,Cool, l,Se rvice LED/indicators as standard. Night Setback Sensors have eDualThermistor Remote Zone Sensor [� s senso r will allow the customer to reduce the total number of remote one(1)Occupied,one(1)Un-occupied, sensors to obtain space temperature and two(2)Override programs per day. averaging.This sensor should be utilized with ReliaTel controls. Humidity Sensor — Field installed, wall-mounted or duct-mounted humidity Manual/Automatic Changeover— Auto,Heat,Cool or Off System Switch. Digital Display Zone Sensor sensor is used to control activation of the Fan Auto or Off Switch.Two temperature The Digital LCD(Liquid Crystal Display) hot gas reheat setpoint levers. zone sensor has the look and functionality dehumidification p option.The f Optional Status of standard zone I sensors1 — COOL .This sensor � humidity sensor Indication LED 1 lights,System On, includes a digital can be set for 9 Y humidity levels Heat,Cool,or SYS ON display of set point EE.Fii between 40%and Service. adjustment and a space temperature �.'' '°0 60% relative in F(Fahrenheit)or C humidity by (Celsius).Includes 0 A adjusting the �h FAN and SYSTEM ® v ReliaTel Options FM Module. MI m buttons(supports ® the service stlIMIK 11 _of of the standard \ i CO2 Sensing —The CO2 sensor shall sensor).E-squared have the ability to to monitor space memory stores last occupancy levels within the building by programmed set points.Requires 24VAC measuring the parts per million of CO2 (Volts AC).This sensor should be utilized (Carbon Dioxide)in the air.As the CO2 with ReliaTel"^ controls. levels increase, Remote Sensor — Sensor(s)available for all zone sensors to provide remote the outside air `' sensing capabilities. damper modulates to meet the CO2 space ventilation co, requirements. u= The CO2 1,= � 1 accessory shall LI be available as '•-��� field installed. 1 76 RT-PRC006-EN 0 TRANE' Zone Controls Electromechanically Controlled Units Conventional Thermostats are the building occupant's comfort control devices for electromechanically controlled units. Manual Changeover— One Heat,One CoolThermostat. Heat,Cool or Off System Switch. Fan Auto or On Switch.Set Point I. Dial.Adjustable Heat Anticipator. to � Automatic Changeover— One Heat, Two CoolThermostat.Off,Auto System Switch.Auto/On Fan Switch. 14 ti C 4/ a F:l® 111111111 7RANE Programmable Electronic Night Setback Thermostat— Heating setback and cooling setup with 7-day,5-1-1 programming capability. Available in two heating/ cooling or one heating/ cooling 12 versions with a 42- automatic 0 changeover. 69 J RT-PRC006-EN 77 0 TRANS® Electrical Data j Table ED-1 - Unit Wiring-Standard Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Optional Belt Drive Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum Tons Model No. Voltage Range Ampacity Circuit Breaker' Ampacity Circuit Breaker' Ampacity Circuit Breaker' YSC036A1 187-253 25.3 40 277 40 - - 3 YSC036A3 187-253 17.9 25 20.3 30 20.6 30 YSC036A4 414-506 9.2 15 10.4 15 10.6 15 YSC036AW 517-633 77 15 8.3 15 8.3 15 YSC048A1 187-253 34.0 50 36.1 50 - - YSC048A3 187-253 23.9 35 26.0 40 25.3 35 4 YSC048A4 414-506 12.8 20 14.4 20 13.6 20 YSC048AW 517-633 9.8 15 10.6 15 10.0 15 YSC060A1 187-253 47.3 60 49.0 60 - - YSC060A3 187-253 31.5 50 33.6 50 30.3 45 5 YSC060A4 414-506 16.0 25 16.3 25 15.6 25 YSC060AW 517-633 12.2 15 12.8 20 11.8 15 YSCO60AK 342-418 19.6 30 - - - - YSC072A3 187-253 32.7 50 34.0 50 - - 6 YSC072A4 414-506 176 25 18.2 25 - - YSC072AW 517-633 12.8 20 13.6 20 YSC072AK 342-418 23.2 35 - - - - YSC090A3 187-253 42.7 60 45.8 60 YSC090A4 414-506 22.6 35 24.1 35 - - YSC090AW 517-633 176 25 18.8 25 71/2YSC090AK 342-418 28.9 40 29.9 45 YSC092A3 187-253 38.9 50 42.0 50 - - YSC092A4 414-506 20.5 25 22.0 25 YSC092AW 517-633 15.5 20 16.7 20 - - YSC102A3 187-253 45.1 60 48.2 60 - - 81/2 YSC102A4 414-506 24.0 30 25.5 35 - - YSC102AW 517-633 19.5 25 20.7 25 - - YSC102AK 342-418 29.6 40 31.1 40 - - YSC120A3 187-253 52.6 60 56.6 60 - - 10 YSC120A4 414-506 26.9 35 28.9 35 - - YSC120AW 517-633 21.8 25 23.5 30 - - YSC120AK 342-418 32.8 40 35.6 45 - - NOTES: 1. HACK breaker per NEC. #Indicates both standard and high efficiency airflow. 78 RT-PRC006-EN 0 TRANS® Electrical DataV: enc vf) Table ED-2 - Unit Wiring-High Efficiency Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size co-Maximum Circuit Size or Maximum Circuit Size or Maximum Tons Model No. Voltage Range Ampacity Circuit Breaker' Ampacity Circuit Breaker' Ampacity Circuit Breaker' YHC036A1 187-253 23.9 40 26.3 40 - - 3 YHC036A3 187-253 17.2 25 19.6 30 19.9 30 YHC036A4 414-506 9.0 15 10.2 15 10.4 15 YHC036AW 517-633 71 15 77 15 77 15 YHC048A1 187-253 29.4 45 31.5 50 - - YHC048A3 187-253 21.2 30 23.3 35 22.6 35 4 YH C048A4 414-506 11.0 15 12.6 15 11.8 15 YHC048AW 517-633 8.3 15 9.1 15 8.5 15 YHC060A1 187-253 39.5 60 41.2 60 - - YHC060A3 187-253 30.0 45 31.7 45 28.8 45 5 YHC060A4 414-506 14.7 20 15.0 20 14.3 20 YH C060AW 517-633 11.8 15 12.4 15 11.4 15 YHC072A3 187-253 34.8 50 36.1 50 - - 6 YHC072A4 414-506 175 25 18.1 25 - - YHC072AW 517-633 13.5 20 14.3 20 - - YHC092A3 187-253 38.1 50 41.2 50 71/2 YHC092A4 414-506 19.4 25 20.9 25 - - YHC092AW 517-633 14.8 15 16.0 20 - - YHC102A3 187-253 42.3 50 45.4 60 - - 81/2 YHC102A4 414-506 21.4 25 22.9 30 - - YHC102AW 517-633 16.6 20 178 20 - - YHC120A3 187-253 48.6 60 52.6 60 - - 10 YHC120A4 414-506 25.3 30 27.3 35 - - YHC120AW 517-633 19.9 25 21.6 25 NOTES: 1. HACR breaker per NEC. RT-PRC006-EN 79 0 TRANE° Electrical Data Table ED-3 - Electrical Characteristics - Evaporator Fan Motors - Direct Drive Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Unit Amps Amps Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA Y#C036A1 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80 3 Y#C036A3 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80 Y#C036A4 1 460 1 .33 1.10 2.00 1 460 1 .50 2.30 5.20 Y#C036AW 1 575 1 .33 1.10 1.80 1 460 1 .50 1.70 3.60 Y#C048A1 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60 4 Y#C048A3 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60 Y#C048A4 1 460 1 .60 1.70 2.80 1 460 1 .80 3.30 7.20 Y#C048AW 1 575 1 .60 1.50 2.40 1 575 1 .80 2.30 5.80 Y#C060A1 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40 5 Y#C060A3 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40 Y#C060A4 1 460 1 .90 2.90 6.60 1 460 1 1.00 3.20 8.20 Y#C060AW 1 575 1 .90 2.10 4.90 1 575 1 1.00 2.70 5.00 YSC060AK 1 380 1 1.00 4.30 8.30 N/A N/A N/A N/A N/A N/A 80 RT-PRC006-EN • TRANE' Electrical Data Table ED-4 - Electrical Characteristics - Evaporator Fan Motors - Belt Drive Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Unit Amps Amps Tons Model No. No. Volts Phase FP RA LRA No. Volts Phase FP FLA LRA 3 Y#C036A3 1 208-230 3 1.0 5.0 32.2 - - - - - - Y#C036A4 1 460 3 1.0 2.5 16.1 - - - - - - Y#C036AW 1 575 3 1.0 1.7 13.2 - - - - - - Y#C048A3 1 208-230 3 1.0 5.0 32.2 - - - - - - 4 Y#C048A4 1 460 3 1.0 2.5 16.1 - - - - - - Y#C048AW 1 575 3 1.0 1.7 13.2 - - - - - - Y#C060A3 1 208-230 3 1.0 5.0 32.2 - - - - - - 5 Y#C060A4 1 460 3 1.0 2.5 16.1 - - - - - - Y#C060AW 1 575 3 1.0 1.7 13.2 - - - - - - YSCO6OAK 1 380 1 1.0 4.3 8.3 - - - - - Y#C072A3 1 208-230 3 1.00 5.00 32.20 1 208-230 3 2.00 6.30 48.00 6 Y#C072A4 1 460 3 1.00 2.50 16.10 1 460 3 2.00 3.10 24.00 Y#C072AW 1 575 3 1.00 1.70 13.20 1 575 3 2.00 2.50 18.20 YSC072AK 1 380 3 2.0 4.9 35.0 - - - - - - YSC090A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00 YSC090A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00 YSC090AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00 YSC090AK 1 380 3 2.0 4.9 3.50 1 3.80 3 3.0 6.4 51.1 71/2 Y#C092A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00 Y#C092A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00 Y#C092AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00 Y#C102A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00 81/2 Y#C102A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00 Y#C102AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00 YSC102AK 1 380 3 2.0 4.9 35.0 1 380 3 3.0 6.4 51.1 Y#C120A3 1 208-230 3 3.00 9.40 83.00 1 208-230 3 5.00 13.40 112.00 10 Y#C120A4 1 460 3 3.00 4.60 42.00 1 460 3 5.00 6.60 56.00 Y#C120AW 1 575 3 3.00 3.70 31.00 1 575 3 5.00 5.40 41.00 YSC120AK 1 380 3 3.0 6.4 51.1 1 380 3 5.0 10.8 66.5 RT-PRC006-EN 81 0 TRANE® Electrical ata p � v _� � Table ED-5 - Electrical Characteristics-Compressor Motor And Condenser Motor- Standard Efficiency Compressor Motor Condenser Fan Motors Unit Amps Amps Tons Model No. No. Volts Phase FP RPM RLA LRA No. Phase FP FLA LRA YSC036A1 1 208-230 1 3.1 3450 17.2 104.0 1 1 .20 1.5 2.5 3 YSC036A3 1 208-230 3 3.1 3450 11.3 74.0 1 1 .20 1.5 2.5 YSC036A4 1 460 3 3.1 3450 6.0 37.6 1 1 .20 0.6 1.3 YSC036AW 1 575 3 3.1 3450 4.9 30.4 1 1 .20 0.5 1.2 YSC048A1 1 208-230 1 3.9 3450 22.7 131.0 1 1 .33 2.0 6.6 YSC048A3 1 208-230 3 as 3450 14.6 91.0 1 1 .33 2.0 6.6 4 YSC048A4 1 460 3 3.9 3450 7.9 46.0 1 1 .33 1.2 2.5 YSC048AW 1 575 3 3.9 3450 6.1 370 1 1 .33 0.7 1.5 YSC060A1 1 208-230 1 5.1 3450 31.3 144.0 1 1 .33 2.0 6.6 YSC060A3 1 208-230 3 5.1 3450 18.6 128.0 1 1 .33 2.0 6.6 5 YSC060A4 1 460 3 5.1 3450 9.5 63.0 1 1 .33 1.2 2.5 YSC060AW 1 575 3 5.1 3450 7.5 49.0 1 1 .33 0.7 1.5 YSCO6OAK 1 380 3 5.1 3450 11.4 64 1 1 .40 1.1 4.3 YSC072A3 1 208-230 3 6 3450 19.0 156 1 1 .70 3.85 9.30 6 YSC072A4 1 460 3 6 3450 10.1 75 1 1 .70 2.50 5.80 YSC072AW 1 575 3 6 3450 77 54 1 1 .70 1.54 3.60 YSC072AK 1 380 3 6 3450 12.2 70 1 1 .75 2.5 77 YSC090A3 1 208-230 3 75 3450 26.0 181.5 1 1 .70 3.85 9.30 YSC090A4 1 460 3 7.5 3450 13.6 95.0 1 1 .70 2.50 5.80 YSC090AW 1 575 3 7.5 3450 10.9 69.0 1 1 .70 1.54 3.60 YSCO9OAK 1 380 3 7.5 3450 16.4 106.3 1 1 .75 2.5 7.7 71/2 YSC092A3 2 208-230 3 4/2.8 3450 14.7/10.3 91/77 1 1 .70 3.85 9.30 YSC092A4 2 460 3 4/2.8 3450 76/5.4 50/39 1 1 .70 2.50 5.80 YSC092AW 2 575 3 4/2.8 3450 5.8/4.2 37/31 1 1 .70 1.54 3.60 YSC102A3 2 208-230 3 5.1/2.8 3450 18.6/10.3 128/77 1 1 .75 4.0 9.4 81/2 YSC102A4 2 460 3 5.1/2.8 3450 10.0/5.4 63/39 1 1 .75 2.8 6.8 YSC102AW 2 575 3 5.1/2.8 3450 8.2/4.2 49/31 1 1 .75 2.4 6.2 YSC102AK 1 380 3 5.1/2.8 3450 12.1/6.6 64/39 1 1 75 2.5 77 YSC120A3 2 208-230 3 5.1/3.9 3450 18.6/14.7 128/91 1 1 .75 4.0 9.4 10 YSC120A4 2 460 3 5.1/3.9 3450 9.5/74 63/46 1 1 .75 2.8 6.8 YSC120AW 2 575 3 5.1/3.9 3450 78/5.8 49/37 1 1 .75 2.4 6.2 YSC120AK 1 380 3 5.1/3.9 3450 11.5/9.0 64/54 1 1 .75 2.5 7.7 82 RT-PRC006-EN 0 TRANE' Electrical Data44 Table ED-6 - Electrical Characteristics-Compressor Motor And Condenser Motor- High Efficiency Compressor Motor Condenser Fan Motors Unit Amps' Amps Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP2 FLA LRA YHC036A1 1 208-230 1 2.8 3450 16.1 88.0 1 1 .20 1.5 2.5 YHC036A3 1 208-230 3 2.8 3450 10.7 77.0 1 1 .20 1.5 2.5 3 YHC036A4 1 460 3 2.8 3450 5.8 39.0 1 1 .20 0.6 1.3 YHC036AW 1 575 3 2.8 3450 4.4 31.0 1 1 .20 0.5 1.2 YHC048A1 1 208-230 1 3.5 3450 19.0 109.0 1 1 .33 2.0 6.6 YHC048A3 1 208-230 3 3.5 3450 12.5 88.0 1 1 .33 2.0 6.6 4 YHC048A4 1 460 3 3.5 3450 6.5 44.0 1 1 .33 1.2 2.5 YHC048AW 1 575 3 3.5 3450 4.9 34.0 1 1 .33 0.7 1.5 YHC060A1 1 208-230 1 4.5 3450 25.0 169.0 1 1 .33 2.0 6.6 YHC060A3 1 208-230 3 4.5 3450 17.4 124.0 1 1 .33 2.0 6.6 5 YHC060A4 1 460 3 4.5 3450 78 59.6 1 1 .33 1.2 2.5 YHC060AW 1 575 3 4.5 3450 6.2 49.4 1 1 .33 0.9 1.5 YHC072A3 1 208-230 3 5.7 3450 20.7 156 1 1 .70 3.85 9.30 6 YHC072A4 1 460 3 5.7 3450 10 75 1 1 .70 2.50 5.80 YHC072AW 1 575 3 5.7 3450 8.2 54 1 1 .70 1.54 3.60 YHC092A3 2 208-230 3 3.5/3.3 3450 12.4/12.4 88/88 1 1 .70 3.85 9.30 71/2 YHC092A4 2 460 3 3.5/3.3 3450 6.4/5.8 44/44 1 1 .70 2.50 5.80 YHC092AW 2 575 3 3.5/3.3 3450 4.8/4.8 34/34 1 1 .70 1.54 3.60 YHC102A3 2 208-230 3 3.9/3.5 3450 14.7/12.4 91/88 1 1 .75 4.0 9.4 81/2 YHC102A4 2 460 3 3.9/3.5 3450 7.1/6.4 50/44 1 1 .75 2.8 6.8 YHC102AW 2 575 3 3.9/3.5 3450 5.4/4.8 37/34 1 1 .75 2.4 6.2 YHC120A3 2 208-230 3 4.8/3.5 3450 17.3/12.4 124/88 1 1 .75 4.0 9.4 10 YHC120A4 2 460 3 4.8/3.5 3450 9.0/6.4 59.6/44 1 1 .75 2.8 6.8 YHC120AW 2 575 3 4.8/3.5 3450 7.1/4.8 49.4/34 1 1 .75 2.4 6.2 Notes: 1. Amp draw for each motor;multiply value by numbers of motors to determine total amps. 2. HP for each compressor. RT-PRC006-EN 83 0 rRANE® Electrical Data Table ED-7 — Electrical Characteristics—Inducer Motor Unit Model No. Stages HP RPM Volts Phase LRA Y*C036-060A 1 1/35 3000 208-230 1 0.6 Y*C072A*L,M Y*C090,092,102A*L 1 1/35 3000/3000 208-230 1 0.6 Y*072A*H Y*090,092,102A*M,H 2 1/15 3500 208-230 1 0.42 Y*120A*L,M,H Table ED-8— Electrical Characteristics—Power Exhaust Accessory Tons Model No. Volts Phase HP RPM' FLA LRA 6-10 BAYPWRX026 208-230 1 0.87 1075 5.7 16.3 6-10 BAYPWRX027 460 1 0.87 1075 3.3 6.8 6-10 BAYPWRX028 575 1 0.87 1075 2.3 5.4 Note 1. Two speed. 84 RT-PRC006-EN 0 TRANS Jobsite Connections Typical Number Of Wires DISCONNECT Zone Sensors SWITCH A— Manual Changeover 4 (BY OTHERS) Manual/Auto Changeover 5 OManual/Auto Changeover with B Status Indication LED's 10 L Programmable Night Setback ZONE SENSOR OR (q — with Status Indication LED's 7 THERMOSTAT ROOFTOP Thermostats UNIT A— 4 Wires,24-volts B— 3 Power Wires+1 Ground Wire(three phase) 2 Power Wires+1 Ground Wire(single phase) For specific wiring information,see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to applicable electrical codes(such as NEC or CEC)and local electrical codes.Wiring shown dotted is to be furnished and installed by the customer. RT-PR C006-EN 85 0 TRANS' Dimensional Data All dimensions are in inches/millimeters. 3,4,and 5 Ton Standard Efficiency— Low and Medium Heat 3 and 4Ton High Efficiency—Low and Medium Heat TOP PANEL EVAPORATOR SECTION ACCESS PANEL O CONDENSER FAN t1`7 32 1/4" 819 MM 41/4' I ___-- 158 req V ALTERNATE CONDENSATE DRAIN 'N CONNECTION 3/4-14 NPT DIA.HOLE `��; I PIP' CONDENSER COIL OP,' / UNIT CONTROL WIRE df� 7/8"(22MM)DIA.HOLE ~239/16" �\ a416111 .- 598 01/4" 598 M \ 5{4MM / SERVICE GAUGE PORT ACCESS \jO'� �'/�� / 1 3/8'(35MM)DIA.HOLE 421/4" e'" 108MM• 69 7/8" 1073 MM 1775 MM rUNIT POWER WIRE . 5 9/16" 13132"(28MM)DIA.HOLE X141 MM 55/8"A 143 MM� 194MM f 95/8' I' 7 5/8"44 1/4" / 244 MM 1124 MM 1/2 NPT GAS CONNECTION / 3,4,and 5 Ton Standard Efficiency—High Heat CONTROL AND COMPRESSOR // ACCESS PANEL 3 and 4Ton High Efficiency—High Heat 5Ton—High Efficiency—Low,Medium, and High Heat TOP PANEL EVAPORATOR SECTION ACCESS PANEL O CONDENSER FAN / - ,: 36 1/4" 921 MM 4 1/4" 108 MM ® ALTERNATE CONDENSATE DRAIN 1 \ \� CONNECTION 3/4-14 NPT DIA.HOLE � � ® 11F , CONDENSER COIL IIII�II�� UNIT CONTROL WIRE _...�01*%1 , ® 20,1/4" //' 7/8"(22MM)DIA.HOLE �598 MM �\ II 514MM i/ SERVICE GAUGE PORT ACCESS -�14 1/4" 1 3/8"(35MM)DIA.HOLE 697/8" 421/4' 00111" 108MM= 1775 MM 1073 MM UNIT POWER WIRE . 5 9/16" 1 3132"(28MM)DIA.HOLE 141 MM 55/8" 7 5/8' 143 MM 194 MM f 9 5/8" 44 1/4" 244 MM 1124 MM 1/2 NPT GAS CONNECTION CONTROL AND COMPRESSOR ACCESS PANEL 86 RT-PRC006-E N 0 TRANS' Dimensional Data All dimensions are in inches/millimeters. 35/B' I _ 14. 81/4' 1512' 92MM 968MA 7, MMS-3WMM_ + u. 102MM " i, SUPPLY 4 1579 M _\.. 814. RETURN • j \1,13-5 Tons — Downflow PP Y giiiti) ))))))l��l������Through the Base Utilit e sow Su l and Return; \ - �' .per \'=%j 279'16 701 MM y 9+h TSU CONDENSATE 2916 } 08 MM \\ 1 MN 9110 166 MM }.... -47/6f 121MM 2212' TH110110H 507 MIA THROUGHSE HE ELECTRICAL A SE 72619~ 299E GAS -91&16~ 259 MIA 3 3/16" 81MM 23 1/4' �_ 591 MM Q RETURN 14 3/4" 4 3/4" 375MM 121 MM 0 SUPPLY - 3-5 Tons — Horizontal Airflow Supply and 0 ,..,4„„Y.. .- • 3 va" Return 11.1%,„ -` MM _ � 38MM7 1/4 87M 43811 22511 3/4-14 NPT CONDENSATE DRAIN - " CLEARANCE CLEARANCE 37"(940 MM) 4Pk HORIZONTAL FLOW-18"(457 MM) j// DOWNFLOW 36"(914 MM) \ \L ROOF OPENING CLEARANCE FROM TOP OF UNIT 72" \\ \\ 683/18' (1016 MM) 37° (1732 MM) �\��(940 MM) /� 44 1/2" 3-5 Tons — Unit Clearance and Roof \�(1130 MM)" Opening CLEARANCE 48"(1219 MM) CLEARANCE 36"(914 MM) RT-PRC006-EN 87 0 TRANS' Dimensional Data All dimensions are in inches/millimeters. 1 3/4" 37 1/8" 45 MM 928 MM 25 3/16" 14 9/16" 640 MM - 370 MM IINW11\A.10213MM 63/8" 65/ 1656 MM61 3/4" 14" /e1568 MM <C ` 4126511 356 MM - 25 MM • 13/4" \/\/�\' 251M" 45 MM \�, \\- ' 18 7/8".. j 47/ lb- 653/4" 1670 MM 40 3-5 Tons— Roof Curb 1034 MM 41 7/16° 51 MM 2" 1052 MM 51 MM 24 3/8" jII /16Id," MM),/ Jr 4,....-- N/ 15 MM - -- (459 MM) 1 ALL FLANGES 1 1/4"(32 MM) 3-5 Tons — Downflow Duct Connections— Field Fabricated I =J� 7E-7,7..„_____ , Ar li- iv 11111/ 14" =�� 356 MM Mlt-malrmm/ 88 RT-PRC006-E N W TWINE' Dimensional Data y H, on -. All dimensions are in inches/millimeters. TOP PANEL 6 Ton Standard and High Efficiency \ 7/Ton Standard Efficiency EVAPORATOR SEOTION CONDENSER FAN ACCESS PANEL \` 40 7/8 I 1038 MM 4 1/4 108MM I I O ",....O ALTERNATE CONDENSATE DRAIN �," CONNECTION 3/4-14 NPT DIA.HOLE 18 7/2" y 470 MM1 ig., 275/8" ® °' CONDENSER COIL 701 MMIIIIIIIIII ;, UNIT CONTROL WIRE Arr-.....attv // 7/8"(22MM)DIA.HOLE 47 7/8'88 5/8"1216 MM 5/8 �� SERVICE GAUGE PORT ACCESS 2251 MM 4 MM ,�., 13/8"(35MM)DIA.HOLE 41110, 5/8 �f1 4 1/4 143 MM 108 MM UNIT POWER WIRE 5 5/8 1 3/8"(35MM)DIA.HOLE 143 7 5/8 5/8 194 MM 53 1/4" 1/2 NPT GAS CONNECTION 1353 MM (80 mbh,120 mbh); 3/4 NPT GAS CONNECTION ' (150 mbh,200 mbh,250 mbh) CONTROL AND COMPRESSOR ACCESS PANEL 71/2 Ton High Efficiency TOP PANEL 8%2 and 10 Ton Standard and High Efficiency EVAPORATOR SECTION CONDENSER FAN ACCESS PANEL � 1190MM 4 1/4 108MM ALTERNATE CONDENSATE DRAIN ", CONNECTION 3/4-14 NPT DIA.HOLE " 241/2" ® 622 MM 275/8--.1111%.,....... ' i 1� CONDENSER COIL 701 MM UNIT CONTROL WIRE \, l '`® �/ 7/8"(22MM)DIA.HOLE 47 7/8" 7,----...4p 1216 MM , SERVICE GAUGE PORT ACCESS 88 5/8" 9 5/8 �,:.., /. 2251 MM 244 5 8M `,�- 4 1/4 1 3/8'(35MM)DIA.HOLE ' 143 MM 108 10 UNIT POWER WIRE 5 5/e 73/8"(35MM)DIA.HOLE �43 MM 7 5/8 194 MM 1/2 100 GAS CONNECTION 1353 MM (PT GAS 120CO mbh); ....,,,,,,,,,--'7.- 3/4 //// 3/4 NPT GAS CONNECTION (150 mbh,200 mbh,250 mbh) CONTROLAND COMPRESSOR ACCESS PANEL RT-PRC006-EN 89 0 TRAIN° 1 Dimensional Data All dimensions are in inches/millimeters. 35/8 92 MI 1 ' 1'4.11M -.--".;5T1•71; V44'11 ` 102 w. � RETURN SUPPLY \ 6-10 Tons — Downflow Airflow Supply and Return; 816 a w11 /jj�'. \ Through the Base Utilities ���� l iii.����������� Illr1(r�l«��,�• )l,� 1 • • `moi MSC�[o/NDENSGH ATE 1035 HA t z /// 1 1 ',,'z 16 1/2' 104NN ® 119/Y - -J 95MMN 1 1165 MI TMSMY i iHRCNGH THC BASE E�LCCCTTFE N CAL y12]NN,— I 1 HASC WS ?,9714,;, 10]i9 2]fi MM , � � - a-', , tea T 38 m I I) _:-- 1238 MM T �_3 ir' • I ,IIS II 6-10 Tons — Horizontal Airflow Supply and Return T I Return III III, 11 32 1/4" 1 Supply 1— 425 MM�. 832 MM u1 11 I s 1/423 na I 11 III SI 489 MM 606 MM II 11 I � 1 ITMI 1 I f.J- 43/4" I91 z7 s/a ■ iiiiiiiiiiiii -�-- =_701 MM___ 4 108MM 3/4-14 NPT DIA.HOLE CONDENSATE DRAIN CLEARANCE CLEARANCE 36"(914 MM) HORIZONTAL FLOW-18"(457 MM) // ^ DOWNFLOW 36"(914 MM) / \L ROOF OPENING CLEARANCE FROM 6-10 Tons — Unit Clearance and Roof TOP OF UNIT 72" Opening t /\j� 46" 88 5/8' 46" (2251 MM) (1168 MM) (1768 MM)) /531/4 V / (1352 MM) illbr CLEARANCE 48"(1219 MM) CLEARANCE 36"(914 MM) 90 RT-PRC006-E N 0 TRANE' Dimensional Data i All dimensions are in inches/millimeters. 1 3/4" 44 MM 46 3/8" 1178 MM 181/2" 470 MM 873 3/8" A MM 269 MM 80 1/2" 2045 MM 14" 83 7/8" 355 MM1,1W 1" 470Mv1 2131 MM 1 3/4" 25 MM 44 MM 000 ��MM 6-10 Tons — Roof Curb IP. 34 3�" 873 MM 84 1/2" 49 7/6" 2146 MM �2.. 1265 MM 2" 51 MMMM—....\,....s., 28 3/8" 1280 MM 51 MM /'-- 17 3/4" 45 / 17 3/4" y 45 33 3/ 8L4I.f / I i 1 1LANGES 1 1/4" (31 MM) 4 . , IIpr4 I __ 1 iJia/47111 -w, � _ � I __ __ 1/1 �JQ 6-10 Tons — Downflow Duct /44r Connections—Field Fabricated _= RT-PRC006-EN 91 0 TRANE"' Dimensional '3 40115 0t10 Si Data ...-----'-',- .' ,,071 f C) 111111114111111111%)O \ 618/18.11111111r, 17111 MM 31 AMM�159r f 232 MM 3-5 Tons — Economizer, Manual, or Motorized Damper Hood 3-5 Tons — Barometric Relief Damper Hood I 1 �������������Me•�i�l) a I 1 4 5/8" 0 I II �(( d ;) 1 1 J 3 5 Tons — Height of Gas Pipe required 11— from Inside Base of Unit to Gas Shut off assembly (Factory Provided) — — Cty, N / 17 5/8" 15 3/4" 22" \ / (448MM) (400MM) (559MM) _ 3-5 Tons — Swing Diameter for Hinged Door(s) Option 92 RT-PRC006-E N • 0 TRANE Dimensional Options Datai 1I \� , 4 ,AJil. 5 \ ECONOMIZER HOOD \ BAROMETRIC RELIEF HOOD / \�� � 5 5/8" % } 143 MM 21 5/8 7 3/4• - 549 MM ECONOMIZER HOOD 198 MM 12" 6 7/8" 1 304 MM ', 175 MM r. 16 3/4" 425 MM 6-10 Tons — Economizer and Barometric Relief Damper Hoods 6-10 Tons — Power Exhaust i leis 9 \ 1 1 4 5/8' 5 ' 11000(D04) 1 1 1 I 6-10 Tons — Height of Gas Pipe required from Inside Base of Unit to Gas Shut off [t assembly (Factory Provided) 173/4" 451 MM / 224 MM 1M iii 35 VT 56902 MM 6-10 Tons — Swing Diameter for Hinged Door(s)Option RT-PRC006-EN 93 0 TRANS° Weights Table W-1 — Maximum Unit And Comer Weights(Lbs)And Center Of Gravity Dimensions(In.) Unit Maximum Weights(Lbs)2 Corner Weights(Lbs)1 Center of Gravity(In.) Tons Model No. Shipping Net A B C D Length Width YSC036A 572 480 151 124 96 109 32 19 3YHC036A 589 497 158 128 101 110 32 19 YSC048A 597 505 159 130 108 109 33 19 RTU 4 4 YHC048A 631 539 166 133 114 126 32 20 YSC060A 614 522 169 134 105 114 32 18 5 YHC060A 666 574 179 140 119 136 32 20 6 YSC072A 878 735 249 193 132 161 39 21 YHC072A 915 772 249 198 141 184 39 22 YSC090A 963 820 273 208 146 193 38 22 RTU 1 71/2 YSC092A 965 822 277 222 147 175 40 21 YHC092A 1066 923 306 243 165 210 39 22 YSC102A 1042 899 297 243 165 194 40 21 81/2 YHC102A 1100 957 310 252 175 220 40 22 10 YSC120A 1063 958 317 261 177 202 41 21 YHC120A 1203 1060 342 277 197 245 40 22 NOTES: 1. Corner weights are given for information only. 2. Weights are approximate. CENTER OF GRAVITY -..--LENGTH A ,--. ,---, r-- B CENTER OF0 GRAVITY WIDTH iv • D C CENTER OF GRAVITY—/ Table W2 — Factory-installed Options Net Weights (Lbs)12 Net Weight Ae,,Csury 3-5Tons 6-10Tons Economizer 26 36 Barometric Relief 7 10 Powered Exhaust — 80 Motorized Outside Air Damper 20 30 Manual Outside Air Damper 16 26 Roof Curb 70 115 Oversized Motor 5 8 Belt Drive Motor 31 — Smoke Detector,Return 7 7 Smoke Detector,Supply 5 5 Coil Guards 12 20 Hinged Doors 10 12 Powered Convenience Outlet 38 38 Through the Base Electrical 8 13 Through the Base Gas 5 5 Unit Mounted Circuit Breaker 5 5 Unit Mounted Disconnect 5 5 Novar Control 8 8 Dehumidification(Hot Gas Reheat)Coil 15 25 NOTES: 1.Weights for options not listed are<5 lbs. 2.Net weight should be added to unit weight when ordering factory-installed accessories. 94 RT-PRC006-EN 0 TRANE® Mechanical Sl�eafic .ons General UnitTop Evaporator and Condenser Coils Units shall be convertible airflow. The top cover shall be one piece Internally finned,5/16"copper tubes Operating range shall be between 115°F construction or,where seams exist,it mechanically bonded to a configured and 0°F cooling as standard from the shall be double-hemmed and gasket- aluminum plate fin shall be standard. factory for units with microprocessor sealed. The ribbed top adds extra Coils shall be leak tested at the factory controls.Operating range for units with strength and prevents water from to ensure pressure integrity.The electromechanical controls shall be pooling on unit top. evaporator coil and condenser coil between 115°F and 40°F. Cooling Filters shall be leak tested to 200 psig and performance shall be rated in One inch,throwaway filters shall be pressure tested to 450 psig.The accordance with DOE and/or ARI testing condenser coil shall have a patent standard on all 3-5 ton units.The filter procedures.All units shall be factory rack can be converted to two inch pending 1 +1+1 hybrid design with assembled,internally wired,fully slight gaps for ease of cleaning.A cacharged with R-22,and 100 percent run- py.Two inch filters shall be factory removeable, reversible, double-sloped supplied on all 6-10 ton units.Optional tested before leaving the factory.Wiring two inch pleated filters shall be available. condensate drain pan is standard. internal to the unit shall be colored and Provision for through the base numbered for simplified identification. Compressors condensate drain is standard. Units(except 380/60/3)shall be UL listed All 3 ton standard units shall have direct- and labeled,classified in accordance to drive,hermetic,reciprocating type Gas Heating Section ANSIZ21.47 for gas fired central furnaces compressors.The reciprocating type The heating section shall have a and UL 1995/CAN/CSA No.236-M90 for compressors have a centrifugal oil pump progressive tubular heat exchanger central cooling air conditioners. providing positive lubrication to moving design using stainless steel burners Canadian units shall be CSA certified. parts.Motor shall be suction gas-cooled and corrosion resistant steel and shall have a voltage utilization range throughout.An induced draft Casing of plus or minus 10 percent of unit combustion blower shall be used to Unit casing shall be constructed of zinc nameplate voltage. Crankcase heater, pull the combustion products through coated,heavy gauge,galvanized steel. internal temperature,and current- the firing tubes.The heater shall use a Exterior surfaces shall be cleaned, sensitive motor overloads shall be direct spark ignition(DSI)system.On phosphatized,and finished with a included for maximum protection. initial call for heat,the combustion weather-resistant baked enamel finish. Compressors shall have internal spring blower shall purge the heat exchanger Unit's surface shall be tested 1000 hours isolation and sound muffling to minimize for 20 seconds before ignition After in a salt spray test in compliance with vibration transmission and noise.Low three unsuccessful ignition attempts,the ASTM B117. Cabinet construction shall pressure switches shall be standard. entire heating system shall be locked allow for all maintenance on one side of out until manually reset at the 3 ton high efficiency and 4-10 ton the unit.Service panels shall have lifting thermostat/zone sensor. Units shall be handles and be removed and reinstalled standard and high efficiency units shall suitable for use with natural gas or by removing only a single fastener while have direct drive,hermetic,scroll type propane(field-installed kit) and also providing a water and air tight seal.All compressors with centrifugal type oil comply with the California requirement exposed vertical panels and top covers pumps.Motor shall be suction gas-cooled for low NOx emissions. in the indoor air section shall be and shall have a voltage utilization range insulated with a cleanable foil faced,fire- of plus or minus 10 percent of unit Outdoor Fans retardent permanent,odorless glass nameplate voltage.Internal overloads The outdoor fans shall be direct-drive, fiber material. The base of the unit shall shall be provided with the scroll statically and dynamically balanced, be insulated with 1/2 inch,1 pound compressors. Crankcase heaters shall be draw-through in the vertical discharge density foil faced,closed cell material.All included on 71/2 ton standard efficiency position.The fan motor shall be insulation edges shall be either captured units. permanently lubricated and shall have or sealed.The unit's base pan shall have Refrigerant Circuits built-in thermal overload protection. no penetrations within the perimeter of Each refrigerant circuit offers a choice of the curb other than the raised 178 inch independent fixed orifice expansion high downflow supply/return openings device or thermal expansion valve. to provide an added water integrity Service pressure ports,and refrigerant precaution,if the condensate drain backs line filter driers shall be factory-installed up.The base of the unit shall have as standard.An area shall be provided provisions for forklift and crane lifting, for replacement suction line driers. with forklift capabilities on three sides of the unit. RT-PRC006-EN 95 0TRAIVEP' Mechanical S� cava'�s Indoor Fan Accessories/Options Oversized Motors All 3-5 ton 3-phase units offer a choice of Factory or field-installed direct drive direct-drive,FC,centrifugal fans or belt Roof Curb oversized motors shall be available for driven,FC centrifugal fans with The roof curb shall be designed to mate high static applications. adjustable motor sheaves.3-5 ton direct with the unit's downflow supply and Powered Exhaust drive oversized motors shall be available return openings and provide support and The field installed powered exhaust, for high static operations.All 6-10 ton a watertight installation when installed available for 6-10 ton units,shall provide units shall have belt drive motors with an properly.The roof curb design shall allow exhaust of return air,when using an adjustable idler-arm assembly for quick- field-fabricated rectangular supply/return adjustment to fan belts and motor ductwork to be connected directly to the economizer,to maintain better bulding pressurization. sheaves.All motors shall be thermally curb.Curb design shall comply with protected.All indoor fan motors meet the NRCA requirements.Curb shall be Discharge Air Sensing U.S.Energy Policy Act of 1992(EPACT). shipped knocked down for field assembly This factory or field option provides true Controls and shall include wood nailer strips. discharge air sensing in heating models. Economizer This sensor is a status indicator readable Unit shall be completely factory wired throughTracerim orTradkerT".This option with necessary controls and contactor This accessory shall be either field or is available for microprocessor controlled pressure lugs or terminal block for power factory-installed and is available with or wiring.Units shall provide an external without barometric relief.The assembly units. location for mounting a fused disconnect includes fully modulating 0-100 percent Coil Guards device. motor and dampers,minimum position Hail protection quality coil guards shall be A choice of micro processor controls or setting,preset linkage,wiring harness either factory or field-installed for electromechanical controls shall be with plug,spring return actuators and condenser coil protection. available. fixed dry bulb control.Optional solid state Through the Base Electrical Access enthalpy and differential enthalpy control An electrical service entrance shall be Microprocessor controls provide for all 24 shall be either factory or field-installed. factory provided allowing electrical volt control functions.With the The factory-installed economizer arrives access for both control and main power microprocessor controls,the resident in the shipping position and shall be connections inside the curb and through control algorithms shall make all heating, moved to the operating position by the the base of the unit.Option will allow for cooling,and/or ventilating decisions in installing contractor. field installation of liquid-tight conduit and response to electronic signals from Remote Potentiometer an external field-installed disconnect sensors measuring indoor and outdoor Field-installed,the minimum position switch. temperatures.The control algorithm setting of economizer shall be adjusted maintains accurate temperature control, Through the Base Electrical with minimizes drift from set point,and with this accessory. Disconnect Switch provides better building comfort.A Motorized Outside Air Dampers Factory-installed 3-pole,molded case centralized Micro-processor shall provide Factory or field-installed manually set disconnect switch with provisions for anti-short cycle timing and time delay outdoor air dampers shall provide up to through the base electrical connections between compressors to provide a 50 percent outside air.Once set,outdoor are available.The disconnect switch will higher level of machine protection. air dampers shall open to set position be installed in the unit in a water tight 24 volt electromechanical control circuit when indoor fan starts.The damper shall enclosure with access through a swinging shall include control transformer and close to the full closed position when door.Factory wiring will be provided from indoor fan shuts down. the switch to the unit high voltage contactor pressure lugs for power wiring. terminal block.The switch will be UL/CSA Unit shall have single point power entry Manual Outside Air Damper as standard. Factory or field-installed rain hood and agency recognized.Note:The disconnect screen shall provide up to 50 percent switch will be sized per NEC and UL outside air. guidelines but will not be used in place of unit overcurrent protection. 96 RT-PRC006-EN 0 TRANS® Mechanical Speafic .or�s Through the Base Electrical with Circuit Reference or Comparative Enthalpy Control Options Breaker Reference or Comparative Enthalpy This option is a factory-installed thermal option shall be available when a factory- Trane Communication Interface magnetic,molded case,HACR Circuit installed Downflow Economizer is This factory or field-installed option shall Breaker with provisions for through the ordered.This option is available for micro be provided to interface microprocessor base electrical connections.The circuit controlled units. controlled units with theTrane Integrated breaker will be installed in a water tight Comfort systems. High Pressure Cutout enclosure in the unit with access through This factoryinstalled option is offered for LonTalk®Communication Interface a swinging door.Factory wiring will be units that do not have High Pressure This factory or field-installed option shall provided from the switch to the unit high cutout as standard.All 3-phase models be provided to allow the unit to voltage terminal block.The circuit breaker with scroll compressors include High communicate as aTracer'LCI-R device will provide overcurrent protection,be Pressure Cutout as standard. or directly with generic LonTalk Network sized per NEC and UL guidelines,and be Building Automation System Controls. agency recognized by UL/CSA. Hinged Access Doors Powered or Un owered Convenience Sheet metal hinges are available factory- Zone Sensor p installed on the Filter/EvaporatorAccess Field installed,this accessory shall be OutletDoor,Indoor Fan/Heat Exchanger Door, provided to interface with the Micro This factory-installed option is a GFCI, and the Compressor/Control Access equipped units and shall be available in 120v/15amp,2 plug,convenience outlet, Door. either manual,automatic programmable either powered or unpowered.When the with night setback,with system convenience outlet is powered,a service Supply and/or Return Air Smoke malfunction lights or remote sensor receptacle disconnect will be available. Detector options. The convenience outlet is powered from With this option installed,if smoke is the line side of the disconnect or circuit detected,all unit operation will be shut Thermostats breaker,and therefore will not be down. Reset will be manual at the unit. Two stage heating and cooling operation affected by the position of the disconnect Return Air Smoke Detectors require or one stage heating and cooling shall be or circuit breaker.This option can only be minimum allowable airflow when used available,for field installation,in either ordered when theThrough the Base with certain models.See the Installation, manual or automatic changeover. Electrical with either the Disconnect Operation,and Maintenance(IOM) Automatic programmable electronic with Switch,or Circuit Breaker,option is manual for the models affected and the night set back shall also be available. ordered. minimum allowable airflow required.This Novar Unit Controls Phase Monitor option is available for micro controlled Optional Novar rooftop unit controls shall Phase monitor shall provide 100% units. be factory installed and tested.The protection for motors and compressors Black Epoxy Coated Condenser Coil Novar electronic thermostat module will against problems caused by phase loss, The coil provides corrosion protection to interface to the unit microprocesser and phase imbalance,and phase reversal. condenser coils for seacoast application. will control the unit to the desired stage of Phase monitor is equipped with an LED The protection is a factory applied cooling or heating. that provides an ON or FAULT indicator. thermoset vinyl coating,bonded to Novar Return Air Sensor Base Gas Piping normal aluminum fin stock.The uniform This option,when used in conjunction The Throughunishall theBase Gasde a Piping standthough thickness of the bonded vinyl layer with Novar Controls,will contain a factory the base gas provision.This factory- exhibits excellent corrosion protection in provided and wired zone temperature installed option shall have all piping salt spray tests performed in accordance sensor located in the return air stream. with ASTM B117. necessary including,black steel,manual Enthalpy Control gas shut-off valve,elbows,and union.The Dehumidification Option Replaces the dry bulb control with a wet manual shut-off valve shall include a 1/8" The dehumidification(hot gas reheat) bulb changeover controller which has a NPT pressure tap.This assembly will option shall be a factory-installed option fully adjustable setpoint.Enthalpy control require minor field labor to install. that provides increased dehumidification. offers a higher level of comfort control, Fan Failure/Clogged Filter Switches The option shall consist of a hot-gas along with energy savings potential,than factory or field installed options reheat coil located on the leaving air side the standard dry bulb control.This is due These for individual fan failure and dirtynsof the evaporator coil prepiped and to the additional wet bulb sensing allowfilter indication in microprocessor circuited. capability.This option shall be available controlled units.The fan failure switch will The option shall be equipped with for microprocessor controlled units.It can disable all unit functions and"flash"the crankcase heater(s), low pressure be field-installed or factory-installed with Service LED on the zone sensor.The dirty switch(es),FrostatTM,and a thermostatic the factory-installed economizer. filter switch will light the Service LED on expansion valve(s)(TXV)as standard. the zone sensor and will allow continued unit operation. RT-PRC006-EN 97 TRANE' Mechanical Speci ' .or�s Differential Enthalpy Digital Display Zone Sensor Replaces the standard dry bulb control The Digital LCD(Liquid Crystal Display) with two enthalpy sensors that compare zone sensor has the look and functionality total heat content of the indoor air and of standard zone sensors.This sensor outdoor air to determine the most includes a digital display of set point efficient air source.This control option adjustment and space temperature in F offers the highest level of comfort control, (Fahrenheit)or C(Celsius).Includes FAN plus energy efficiency,available.This and SYSTEM buttons(supports the option shall be available for service functions of the standard sensor). microprocessor controlled units.It can be E-squared memory stores last field-installed or factory-installed with the programmed set points.Requires 24VAC factory-installed economizer. (Volts AC).This sensor should be utilized Low Ambient Cooling with ReliaTelT"^ controls. All microprocessor units shall have Dual Thermistor Remote Zone Sensor cooling capabilities down to 0°F as This sensor will allow the customer to standard.Electromechanical models reduce the total number of remote have cooling capabilites to 40°F as built, sensors to obtain space temperature or to 0°F by adding the optional low averaging.This sensor should be utilized ambient(frostat)control. with ReliaTel controls. Thermal Expansion Valve Humidity Sensor All units shall have a short orifice Field installed,wall-mounted humidity refrigerate control metering device. For sensor is used to control activation of the more exact refrigerant flow,when using hot gas reheat dehumidification option. unit in low airflow applications,aThermal The humidity sensor can be set for Expansion Valve option shall be available. humidity levels between 40%and 60% CO2 Sensing relative humidity by adjusting the ReliaTel The CO2 sensor shall have the ability to Options Module. monitor space occupancy levels within Humidity Sensor the building by measuring the parts per Field installed,duct-mounted humidity million of CO2(Carbon Dioxide)in the air. sensor is used to control activation of the As the CO2 levels increase,the outside air hot gas reheat dehumidification option. damper modulates to meet the CO2 The humidity sensor can be set for space ventilation requirements.The CO2 humidity levels between 40%and 60% accessory shall be available as field relative humidity by adjusting the ReliaTel installed. Options Module. Ventilation Override Accessory With the Ventilation Override Accessory installed,the unit can be set to transition up to 3 different pre-programmed sequences for Smoke Purge, Pressurization,and Exhaust.The transition occurs when a binary input on the RTOM is closed(shorted).This would typically be a hard wired relay output from a smoke detector or fire control panel.The ventilation override accessory shall be available as field installed. 98 RT-PRC006-EN .._ r --- , .._ ... , - -. . ,.: , 4 -- ., ; 10) $ pc) s , „.",.,,„,,.„,„ '''sr,,,..0'4 'High Efficiency Units on Iv 8 . Literature Order Number RFPRC006-EN File Number PL-UN-RT-YSCMiC3-10TONS-PRC006-EN-2-04 Trane Supersedes PL-UN-RT-YSGYHC3-10TONS-PRCO06-EN-12-03 A business of American Standard Companies Stocking Location 05-03 Webb/Mason 2-04 Electronic Only www.trane.com For more information contact your local dealer (distributor),local district office,or e-mail us at Trane has a policy of continuous product and product data improvement and reserves the right to change comfort@trane.com design and specifications without notice.