Memorandum
July 2, 2019
To: Amilian Avgi, Riverside Homes
From: Corina Muntean, P.E
Re: Plan 2885 at Elderberry Lot 31
eased on our conversation and photographs that were send from the job site,the knock
out for the furnace was incorrectly located in the shear wall at the back of garage. Rebar
was drilled and epoxied into the concrete foundation on both sides. I have reviewed it and
take no exception.
If you have any questions, don't hesitate to ask.