cis-FICE COPY RECEIVED Gamer) MAY 2 0 2019 CITY OF TIGARD BUILDING DIVISION SUBMITTAL Bryant/Carrier Ductless Mini-Splits Project Tigard Self Storage Tigard, OR Date Thursday, March 21, 2019 Table Of Contents Project: -Untitled2 03/21/201.c Prepared By: 09:07AN HP 1 - 10 3 Unit Report 4 Certified Drawing 6 Performance Summary 9 HP 11 11 Unit Report 12 Certified Drawing 14 Performance Summary 16 Ductless Systems Builder (Carrier) 1.09s Page 3 of 18 lid' '9 ? Project:-Untitled2 03/21/2019 Prepared By: 09:07A1VV HP - 10 Tag Cover Sheet Unit Report Certified Drawing Performance Report Ductless Systems Builder(Carrier) 1.09s Page 4 of 18 } Unit Report For HP 1 - 10 Project: -Untitled2 03/21/201c Prepared By: d3u4fi na r System Parameter System Quantity. 10 Refrigerant Type: R-410A Std. Min.Outdoor Temp(Cooling): -13.0 F Std. Max Outdoor Temp(Cooling): 122 F Indoor Unit Parameters Indoor Unit 2 Parameters Unit Quantity: 1 Unit Quantity: 1 Unit Model. 40MBDQ18---3 Unit Model. 40MBDQ18---3 Unit Size• 18,000 Btuh Unit Description• Voltage. 208/230-1-60 V-Ph-Hz Unit Size• 18,000 Btuh Voltage• 208/230-1-60 V-Ph-Hz Outdoor Unit Parameters Indoor Unit 1 Dimensions and Weight Unit Quantity: 1 Unit Model: 40MBDQ18---3 Unit Model' 38MGRQ36D--3 Unit Length' 2'1" Unit Description:DLS MULTI 36K 230V HPCDU Unit Width• 3'0" Unit Size• 36,000 Btuh Unit Height: 8" Voltage. 208/230-1-60 V-Ph-Hz Unit Operating Weight. 51 lb Indoor Unit 2 Dimensions and Weight Outdoor Unit Dimensions and Weight Unit Model. 40MBDQ18---3 Unit Model. 38MGRQ36D--3 Unit Length• 2'1" Unit Length• 1'6" Unit Width: 3'0" Unit Width• 3'5" Unit Height: 8" Unit Height: 4'4" Unit Operating Weight. 51 lb Unit Operating Weight 222 lb Warranty Information NOTE: Please see Warranty Card for explanation of policies. LIMITED WARRANTY* - 10 year limited to original purchaser on compressor and parts upon timely registration,otherwise 5 years *For residential applications.See warranty for full details. Ordering Information Part Number Description Quantity Base Unit-Indoor 40MBDQ18---3 FCU 1.1 -FCU 10.1 10 Ductless Systems Builder (Carrier) 1.09s Page 5 of 18 Unit Report For HP 1 Project: -Untitled2 03/21/201 Prepared By: 40MBDQ18---3 FCU 1.2—FCU 10.2 10 Outdoor Unit 38MGRQ36D--3 DLS MULTI 36K 230V HPCDU 10 Ductless Systems Builder (Carrier) 1.09s Page 6 of 18 Certified Drawing for HP 1 - 10 Project: -Untitled2 03/21/201 Prepared By: 09:07Ary _ -1411111 -'- , .....- - Air Rtar alrinle4 from rear side , ....- r I - 11. 111111111111 , . 0,.. 0 _ ti 1010 L ,. 0 4-hata1 Navel A WAS side MI - - r , - a 0 v, 1 iiiks 2,6,9325) ..1 ,mama Pill Gat aido W,0 1. Drain# #t , .,_ . , 9* , Toot mouth&Ti aal com '; ..A .,-Dr/4r,'r4971 ta? 0 4) . , . ,,..... 0 0,02474)Drain come:ft A in rir i J e 11„ In Mod&carom,boa Outside Air Intake .,....."..........___j.....i. . . . Air filter E ., \a f infat on tottorn sno Fig.2 -Indoor Unit Utak 3—Indoor Uatt —1 '--Citittiiii LA ounzr A31 firn304 AVOW 00000140tiS OP0000 siZE aseito SC4, i SIRACOM =MVOs On Ain— C I C F 0 H I , J K i I &I ID , 112 WI 192 (6* 21.2 82 ', 25 234 2.6, MA 1.3 42 ZIA : 72 1 3.1 tI2,1 131 47 52 33 52 392 , (7oo) Cal CO ,PO 1(57 1035) 14$13) 1111 MS/ (5.9gl ; 2001 1 (&) f P,441 CM) 020) (1414 PC8 050) pe.1) 27.6 $2 i SS 22.4 2b 18.4 13 4.6 23.4 7i 3.11 NJ 12J 47 GA 37 62 302 12 POO) (01CCI 1_1 OEM (971:0 PS) PM PIO - 01$0 CAP 1:2021 (110) (144 WO OM L140 000 0001 (MI 18 / —243-3ii- 24 224- iiiiia Ito 13 ii.s slio , 72 ; 3.1 374/ -133-41:/ 116--Ti— 89 (020) OM (03110 0701 1 10e0, 714 Ws) (113) 011151 IMO°, i ($(8 010 060) {UM (140) ,"' MO (231 3g 24 i 104 i 25 214 i Is 28b1 1$ /4 3114 J102 1 03 37,a OA 4.7 54 3.7 5.0 tem Pei ; PM 060) PR___........ 4i3)._._ OA Ji __JL se 444 103 302 27,0 24 387 13 7,0 40/ 102 07 4 103 42 CO 3.7 4,0 rti (1140) (2711 (T75) 1710) PT/ PA 173% (ag) 0035) OE% : OM (1180) $W) (120) Oa) OR 081 (38) —1151341 . 314 -If '41111-1-A---111 glib its CI Ei (120:0 4304 i(8E05) 91C0) PO Pek (415 (209 Om) (28E9 . #46) 1112401 010:0 ON DE9 1155) PM 149 Ductless Systems Builder (Carrier) 1.09s Page 7 of 18 Certified Drawing for HP 1 - 10 Project: -Untitled2 03/21/201 Prepared By: 09:07AN ----_-- _I --TO WIRE 1 7 _i WIRING DIAGRAM Inner Driver O r CONTROLLER 1 NOTE____ I (INDOOR UNIT) DC Motor .�4 1 pttorcia indicates the ha rret a0. i 202052290108 �p 3I---11 1 RED .ter IVIp CN15 t_ CN40 I I CN$J REDS FORTEMR COMPENSATIONOrEATING) L pl ON r '-l DC MOTOR 1 ® Reactor SW6 I r1(1 um mu De L-YIGI DRIVER MOBLE ___ 1 a 1.2 1 a ,a L Outer Driver DC Motor 1 CODE 6'C 2t 4r Acuord6g NICN11I • I FACTOR EFondle, 3tog 441 rn 2 r) INDOOR UNIT L , g n �� ,� II 7 NEVVFAN ....... r ;,s 0 44 a ' MAINBOARD FOR SETTING STATIC PRESSURE n X �• i OTp ire; �f(J0�1j? �f0/,; ie.: .,5 El \ /�� dDIV( i ENC2 14 °A�i' �r �i° /60 SB5 0 CN13 2 PU'M`P/ t OL bL OL 101 4L+ , , 1 CODE 0 1 2 3 4 MODE HEATING COOLING STAi1CP2E2SURE 0-10 71-20 21.'30 31-40 41-50 PRIORITY PRIORITY 1 i FACTORYSErnRE s...,"" eE�OTY r/ CN10{CN1OA) 15"), BOARD fr CONTROLLER FOR ANTI-COLD WIND ON ON r 1 SWICON ON ON ON FUNCTION Li N6 �/ i�.-."" T2 Q� �e �O M2 $w3 AUIOiFSTNiT ACTIVE INACTIVE CN3 CN26 4� BLACK MIDDLE PIPE TEMP. TOR 0 ACtOMUG CONTROLTHENFAN FAN CN23 CN33 L H�E Ti TELO 24t 1st at Fu oR. $N2 NO POWER ON OFF ffREQUEST I®la IGO Z z 71 ROOM TEMP. %way FACTORY _I ON/OFF ALARM U U .2 CN5 1 �` �r1 i SETTING 1 WATER LEVEL SWITCH I. FOR SETTING NETADDRESS — V-- m o > I a , J tor ON f07, ON fAl ON or. ON� r >1: �'6p .r t rr r. - , i ! S ®1_ L0.t} ti : Lt ) ;ILv87+82 m> oo m4 4d ®; oo Cis ee t �T ;tfA;, m ; C®©:_ �``__� _z *51 1a ;Ave a* 12 0I.` 12 OMS. 12 :C__...:11 I 1 Iii ��1A. .. "ER - I- L{L1)N(LT) S CF3;, ii CODE 0-F 0-F 0-F 0-F 1---1 `-_� - ttt I NETADORE88. '0-15. 16-31 32-47 48-63 Remotntrol Oue AlarmT. 00 ,.,• IT TO OUTDOOR UNIT i Cotput Fat,._,,.•• 1 SUPPLY FOR MOOR POKER StFPLY -FACTORY EETT \-----. .... ; NI \-----. _ 1 Ductless Systems Builder (Carrier) 1.09s Page 8 of 18 Performance Summary For HP 1 - 10 Project: -Untitled2 03/21/201. Prepared By: 09:07AN System Outdoor Unit. 38MGRQ36D--3 Indoor Unit: 40MBDQ18---3 Indoor Unit 2: 40MBD018---3 System Quantity 10 Altitude: 0.0 ft Linear Pipe Length. 10.0 ft Long Line Charge. 0.0 oz. Vertical Lift: 0.0 ft Outdoor Suction Line Size: ' 1/2*1+3/8*3 in. Outdoor Liquid(Mixed Phase)Line Size• 1/4*4 in. Suction Line Size: 1/2 in. Liquid(Mixed Phase)Line Size- • 1/4 in. Suction Line Size Unit 2• 1/2 in. Liquid(Mixed Phase)Line Size Indoor Unit 2: 1/4 in. System Performance Selected System Type: Ducted Rated Cooling Capacity: 35000.0 BTU/hr Cooling Capacity Range: 8460-40250 BTU/hr Rated Heating Capacity: 36000.0 BTU/hr Heated Capacity Range: 6880-45250 BTU/hr SEER: 17.0 EER• 10.8 HSPF: 9.2 High Temp COP• 3.8 System Performance System Type: Mixed-Ducted Rated Cooling Capacity: 35500.0 BTU/hr Cooling Capacity Range: 8510-42635 BTU/hr Rated Heating Capacity: 36000.0 BTU/hr Heated Capacity Range: 7045-47800 BTU/hr SEER: 19.3 EER• 12.2 HSPF: 9.9 System Performance Selected System Type: Non-Ducted Rated Cooling Capacity: 36000.0 BTU/hr Cooling Capacity Range: 8560-45020 BTU/hr Rated Heating Capacity: 36000.0 BTU/hr Heated Capacity Range: 7210-50350 BTU/hr SEER: 21.5 EER- 13.5 HSPF: 10.5 Indoor Acoustics Model: 40MBDQ18---3 Airflow Low 300.0 CFM Airflow Medium• 400.0 CFM Airflow High. 480.0 CFM Clg Sound Press. Low 35.0 dB Clg Sound Press. Medium: 37.0 dB Clg Sound Press. High. 39.0 dB Htg Sound Press. Low: 34.0 dB Htg Sound Press.Medium: 36.0 dB Htg Sound Press. High• 37.0 dB Indoor Unit 2 Acoustics Model: 40MBDQ18---3 Ductless Systems Builder (Carrier) 1.09s Page 9 of 18 Performance Summary For HP 1 - 10 Project: -Untitled2 03/21/2010 Prepared By: 09:07AN Airflow Low• 300.0 CFM Airflow Medium. 400.0 CFM Airflow High• 480.0 CFM Clg Sound Press. Low• 35.0 dB Clg Sound Press. Medium: 37.0 dB Clg Sound Press. High• 39.0 dB Htg Sound Press. Low: 34.0 dB Htg Sound Press. Medium: 36.0 dB Htg Sound Press. High- 37.0 dB Outdoor Acoustics Outdoor Clg Sound Pressure: 64.0 dB Outdoor Htg Sound Pressure. 64.0 dB Airflow: 4500 CFM Electrical Data Indoor Unit 1 Model: 40MBDQ18---3 Indoor MCA• NA Amps Indoor MOCP: NA Amps Fan Motor FLA: 0.83 Amps Powered From Outdoor. Yes Electrical Data Indoor Unit 2 Model: 40MBDQ18---3 Indoor MCA• NA Amps Indoor MOCP: NA Amps Fan Motor FLA: 0.83 Amps Powered From Outdoor. Yes Electrical Data Outdoor Unit Outdoor Unit Voltage 208/230-1-60 V-Ph-Hz Outdoor Voltage Range Min• 187 V Outdoor Voltage Range Max. 253 V Outdoor MCA: 35.0 Amps Outdoor MOCP: 50.0 Amps Compressor RLA• 21.00 Amps Compressor LRA• NA Amps System Operating Envelope Cooling Max Outdoor DB: 122.0 F Min Outdoor DB: -13.0 F Max Indoor DB: 90.0 F Max Indoor WB: 59.0 F Min Indoor DB: 70.0 F Min Indoor WB: 59.0 F Heating Max Outdoor DB: 86.0 F Min Outdoor DB: -22.0 F Max Indoor DB: 72.0 F Min Indoor DB: 59.0 F Ductless Systems Builder (Carrier) 1.09s Page 10 of 18 HP 1 . Project: -Untitled2 03/21/201 Prepared By: 09:07AM HP 11 Tag Cover Sheet Unit Report Certified Drawing Performance Report Ductless Systems Builder (Carrier) 1.09s Page 11 of 18 , Unit Report For HP 11 Project: -Untitled2 03/21/201 Prepared By: ,t, � I I ii it i i1 111l j .sl, k� ,. At _-7-~-d'f:::-, rF'° �w b+A1 s Atil System Parameter System Quantity. 1 Refrigerant Type: R-410A Std. Min.Outdoor Temp(Cooling): -13.0 F Std. Max Outdoor Temp(Cooling): 122 F Indoor Unit Parameters Indoor Unit 2 Parameters Unit Quantity: 1 Unit Quantity: 1 Unit Model. 40MHHQ09---3 Unit Model: 40MHHQ12---3 Unit Size• 9,000 Btuh Unit Description• Voltage. 208/230-1-60 V-Ph-Hz Unit Size• 12,000 Btuh Voltage. 208/230-1-60 V-Ph-Hz Indoor Unit 3 Parameters Outdoor Unit Parameters Unit Quantity: 1 Unit Quantity: 1 Unit Model. 40MHHQ12---3 Unit Model. 38MGRQ30D--3 Unit Description. Unit Description:DLS MULTI 30K 230V HPCDU Unit Size• 12,000 Btuh Unit Size 30,000 Btuh Voltage. 208/230-1-60 V-Ph-Hz Voltage. 208/230-1-60 V-Ph-Hz Indoor Unit 1 Dimensions and Weight Indoor Unit 2 Dimensions and Weight Unit Model. 40MHHQ09---3 Unit Model. 40MHHQ12---3 Unit Length• 8" Unit Length• 8" Unit Width: 2'5" Unit Width• 2'8" Unit Height: 12" Unit Height: 12" Unit Operating Weight. 21 lb Unit Operating Weight. 22 lb Indoor Unit 3 Dimensions and Weight Outdoor Unit Dimensions and Weight Unit Model. 40MHHQ12---3 Unit Model: 38MGRQ30D--3 Unit Length• 8" Unit Length• 1'6" Unit Width: 2'8" Unit Width• 3'5" Unit Height: 12" Unit Height: 2'8" Unit Operating Weight. 22 lb Unit Operating Weight. 157 lb Warranty Information NOTE: Please see Warranty Card for explanation of policies. LIMITED WARRANTY" - 10 year limited to original purchaser on compressor and parts upon timely registration,otherwise 5 years Ductless Systems Builder (Carrier) 1.09s Page 12 of 18 Unit Report For HP 11 Project: -Untitled2 03/21/201 Prepared By: *For residential applications.See warranty for full details. Ordering Information Part Number Description Quantity Base Unit-Indoor 40MHHQ09---3 FCU 11.1 1 40MHHQ12---3 FCU 11.2 1 40MHHQ12---3 FCU 11.3 1 Outdoor Unit 38MGRQ30D--3 DLS MULTI 30K 230V HPCDU 1 Ductless Systems Builder (Carrier) 1.09s Page 13 of 18 Certified Drawing for HI 11 Project: -Untitled2 03/21/201.c. Prepared By: 09:07AN ...___ 41. .2:-------7-1 Ea' -i "fE •, p• 1 11 1 1 ---- .,„1 1 1 1 1 ' \L.__ I ', 11' ,0. - , 1 , ,,,-,0.,..----,77.7,,,,,,,,., ...,,,;;;,..„.5- -----_-_- :,-..: ,,0,-,-:70-, 1 vg-c-';',-,)\x ,, .00,..,., iz,05,0:0,;,„ . , T.,-- 1, 1 11 1 0- .,- --FT---; 1 ,..;ttA,'• /4/i '',, '' , - 1 I _ , i i A' 1 I 1 14 67___ --a 11,-,-111. ^I' --., -4.- -,.. ..--- ..4 r L ±19 ) _____ 37 24946) o 4u 71(1() 4) I I-- _ V co• C-'I'=-,:1,. --- i T - - ---\ 2 : //f Y , t-t - --,- " ---- --=----- — 9-i--* - --,- ,' H\ , - . •,2 0, ---- There is no Certified Drawing available for this tag Ductless Systems Builder (Carrier) 1.09s Page 14 of 18 Certified Drawing for HP 11 Project: -Untitled2 03/21/201 Prepared By: 09:07AN w ' w Hu, Applicable In the unite amp v adopting AC motor only 3' Q 411 U 13A %Svc I 61 r, ai ra 3/ xCD (CN431 ICN41I CN9 I I CNA I ICN331 ® 5 6 ei,: f �O BLUE I CN3 I CN42 i8® /5(6)_/I1 I Hilin 7 CN2Z ---- 5(R) t-i EEV C M / TILLIE_ RED ICN4 BLUE ® / -Iu1 I� -, — W � ��� LACK —1ie� i(fi) 0i : N a HEAT Y RED CNiO � :E — A u 0 L^^a• 77 BLACKICN44I 'E� /-5N lr1; qqq �HEATD ' g i§ 3 x 3,— /7 ® MAW BOARD ,i, Da 0- N a DSR J BLACK es w _m Q 1 —M RED ® o P-1 ® IYIG �L� oi W N N yZ. ICN2 I o ,o m ® if 3/ 3/ 3/ II~it 15 — _ u 3 z 01 k z a! z m x o �.sy7 a a a yd.� m „Qd a „�� a 2 J < ,a� 1 "'t '" � � "i" 0 000000 0 00000C)0()000O0 L LI L2 016 LI:A)L2'A'Eh A) L1(B)L2(B)S(B)LI(C)L2( S(C)L1(D�L2 D S(D) EDC 00 0 ecoeeoes) 0 I I I 11 1 I 1 1 i I ! I I I I ; t ; I ! I ! I I I ; I ; I I I I 1 1 I 1 I I 1 ��� i I I I I I 1 1;-- II - 1 —, powER'-, TOn I TOB 1 50 C I �TO D �,SUPPLY/ 1. L_.—.� L.—.—._j L._._.� �, ..../ ivio Iwo Ira hr 1G ‘ 4 e e OUTDOOR UNIT MAIN BOARD CODE PART NAME CODE PART NAME CODE PART NAME COMP COMPRESSOR L PAC INDUCTOR CN]-CN2 Input:230VAC High voltage CN5'CN6 Output:230VAC High voltage CAPt PAN MOTOR CAPACITOR L-PRO LOW PRESSURE SWITCH P-1 Connection In the earth , HEAT CRANKCASE HEATING TP EXHAUST SENSOR CN70-c6144 Output:230VAC High voltage Chassis Crank.=Healer CN4-CN40 Outpul:230VAC High voltage Compressor Crankcase Heater Fill OUTDOOR DC FAN SV 4-WAY VALVE CN3--CN22 Output:230VAC High voltage FAN] OUTDOOR AC FAN T3 CONDENSER CN17-CN21 Output:Pin]-Pin4:Pulae waveform(0-]2VDC),PieS,Pin6(1 ZVDC) TEMPERATURE SENSOR CN7 Output:Pin7(7 2VDC),Pin2(5VDC),Pin3(FARTH) EEV ELECTRONIC T4 OUTDOOR AMBIENT C6/27-CN30 Output:Pin 2-Pin 3(230VAC High voltage)-MDU Power&"S" EXPANSION VALVE TEMPERATURE SENSOR CN13 Pint,Pie3,Pin5,Pin7,Pin9(SVDC);Pin2,Pin4,Pin6,PinR,Pin1O(O-5VDCH-PRO HIGH PRESSURE SWITCH TH HEATSINK TEMPERATURE SENSOR CN33 lnpul:Pin](0-5 V DC),Pin2(SVDC)-Discharge Temp CNS Input:Pin3,Pin4(SVDC),Pin2(OVDC),PinI,PInS(O-5VDC)T3&T4 CN9 Input:Pin2,Pin4(0VDC),Pinl,Pin3(0-IVDC)NIL Pressure Switches OUTDOOR UMT PFC&IPM BOARD CODE PART NAME CN53-CN54 lnput:230VAC High voltage CNS5 Output:Pint(]2VDC),Pin2(SVDC),Pin3(EARTH) CNI 9 Pin]-Pin3:Connect to FAN voltage wrong phases 0-200VAC U.-V-W Connect to compressor voltage among phases 0-200VAC CN51—CN52 CNS7—EARTH,CN52-EARTH OuIpul 224-3ROVDC High voltage I Ductless Systems Builder (Carrier) 1.09s Page 15 of 18 Performance Summary For HP 11 Project: -Untitled2 03/21/201 Prepared By: 09:07AN System Outdoor Unit 38MGRQ30D--3 Indoor Unit: 40MHHQ09---3 Indoor Unit 2: 40MHHQ12---3 Indoor Unit 3: 40MHHQ12---3 System Quantity. 1 Altitude: 0.0 ft Linear Pipe Length: 10.0 ft Long Line Charge. 0.0 oz. Vertical Lift: 0.0 ft Outdoor Suction Line Size: 1/2*1+3/8*3 in. Outdoor Liquid(Mixed Phase)Line Size• 1/4*4 in. Suction Line Size: 3/8 in. Liquid(Mixed Phase) Line Size. 1/4 in. Suction Line Size Unit 2: 1/2 in. Liquid(Mixed Phase)Line Size Indoor Unit 2: 1/4 in. Suction Line Size Unit 3: 1/2 in. Liquid(Mixed Phase) Line Size Indoor Unit 3: 1/4 in. System Performance Selected System Type: Non-Ducted Rated Cooling Capacity: 30000.0 BTU/hr Cooling Capacity Range: 8090-41470 BTU/hr Rated Heating Capacity: 28000.0 BTU/hr Heated Capacity Range: 6350-41950 BTU/hr SEER: 23.8 EER. 12.5 HSPF: 10.0 High Temp COP• 3.8 System Performance System Type: Mixed-Ducted Rated Cooling Capacity: 29000.0 BTU/hr Cooling Capacity Range: 8060-39990 BTU/hr Rated Heating Capacity: 28000.0 BTU/hr Heated Capacity Range: 6275-42305 BTU/hr SEER: 21.7 EER. 12.0 HSPF: 9.5 System Performance Selected System Type: Ducted Rated Cooling Capacity: 28000.0 BTU/hr Cooling Capacity Range: 8030-38510 BTU/hr Rated Heating Capacity: 28000.0 BTU/hr Heated Capacity Range: 6200-42660 BTU/hr SEER: 19.5 EER• 11.5 HSPF: 9.0 Indoor Acoustics Model: 40MHHQ09---3 Airflow Low• 165.0 CFM Airflow Medium• 229.0 CFM Airflow High. 271.0 CFM Airflow Turbo. 324.0 CFM Clg Sound Press. Low 31.0 dB Clg Sound Press.Medium: 36.0 dB Clg Sound Press. High• 40.0 dB Clg Sound Press.Turbo. 42.0 dB Ductless Systems Builder (Carrier) 1.09s Page 16 of 18 f rrn nee Summary For HP 11 • Project: -Untitled2 03/21/201 Prepared By: 09:07A1V Indoor Unit 2 Acoustics Model: 40MHHQ12---3 Airflow Low' 212.0 CFM Airflow Medium• 282.0 CFM Airflow High• 324.0 CFM Airflow Turbo- 353.0 Clg Sound Press. Low. 34.0 dB Clg Sound Press. Medium: 39.0 dB Clg Sound Press.High. 41.0 dB Clg Sound Press.Turbo- 43.0 dB Indoor Unit 3 Acoustics Model: 40MHHQ12---3 Airflow Low- 212.0 CFM Airflow Medium• 282.0 CFM Airflow High: 324.0 CFM Airflow Turbo- 353.0 Clg Sound Press. Low. 34.0 dB Clg Sound Press. Medium: 39.0 dB Clg Sound Press. High• _ 41.0 dB Clg Sound Press.Turbo. 43.0 dB Outdoor Acoustics Outdoor Clg Sound Pressure: 62.3 dB Outdoor Htg Sound Pressure- 62.3 dB Airflow: 2130 CFM Electrical Data Indoor Unit 1 Model: 40MHHQ09---3 Indoor MCA- NA Amps Indoor MOCP: NA Amps Fan Motor FLA: 0.24 Amps Powered From Outdoor Yes Electrical Data Indoor Unit 2 Model: 40MHHQ12---3 Indoor MCA: NA Amps Indoor MOCP: NA Amps Fan Motor FLA: 0.24 Amps Powered From Outdoor Yes Electrical Data Indoor Unit 3 Model: 40MHHQ12---3 Indoor MCA. NA Amps Indoor MOCP: NA Amps Fan Motor FLA: 0.24 Amps Powered From Outdoor Yes Electrical Data Outdoor Unit Outdoor Unit Voltage. 208/230-1-60 V-Ph-Hz Outdoor Voltage Range Min• 187 V Outdoor Voltage Range Max. 253 V Outdoor MCA: 30.0 Amps Outdoor MOCP: 45.0 Amps Compressor RLA• 19.00 Amps Compressor LRA• NA Amps System Operating Envelope Cooling Max Outdoor DB: 122.0 F Min Outdoor DB: -13.0 F Max Indoor DB: 90.0 F Max Indoor WB: 59.0 F Ductless Systems Builder (Carrier) 1 .09s Page 17 of 18 Performance Summary For HP 11 Project: -Untitled2 03/21/201 Prepared By: 09:07AIv Min Indoor DB: 70.0 F Min Indoor WB: 59.0 F Heating Max Outdoor DB: 86.0 F Min Outdoor DB: -22.0 F Max Indoor DB: 72.0 F Min Indoor DB: 59.0 F Ductless Systems Builder (Carrier) 1.09s Page 18 of 18 '.40MHH High Wall Ductless System ant Sizes 09 to 24IbLy Product Data INDUSTRY LEADING FEATURES / BENEFITS A PERFECT BALANCE BETWEEN BUDGET LIMITS,ENERGY SAVINGS AND COMFORT. The 40MHH series ductless systems are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires. The fan coil is mounted on the wall,near the ceiling.This selection of fan coils permits creative solutions to design problems such as: • Add—ons to current space (an office or family room addition) • Special space requirements • When changes in the load cannot be handled by the existing system • When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork • Historical renovations or any application where preserving the look of the original structure is essential. The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork. These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels. LOW SOUND LEVELS BUILT-IN RELIABILITY When noise is a concern,the ductless systems are the answer.The Ductless system indoor and outdoor units are designed to provide indoor units are whisper quiet.There are no compressors indoors, years of trouble—free operation. either in the conditioned space or directly over it,and there is The high wall indoor units include protection against freeze—up none of the noise usually generated by air being forced through and high evaporator temperatures on heat pumps. ductwork. The condensing units on heat pumps are protected by a three minute time delay before the compressor starts the over—current SECURE OPERATION protection and the high temperature protection. If security is an issue,outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling INDIVIDUAL ROOM COMFORT through ductwork. In addition, since the outdoor units can be Maximum comfort is provided because each space can be installed close to an outside wall,coils are protected from vandals controlled individually based on usage pattern. The air sweep and severe weather. feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year—round FAST INSTALLATION comfort can be provided with heat pumps. This compact ductless system is simple to install. A mounting bracket is standard with the indoor units and only wire and piping ECONOMICAL OPERATION need to be run between the indoor and outdoor units. These units The ductless system design allows individual room heating or are fast and easy to install ensuring minimal disruption to cooling when required. There is no need to run large supply—air customers in the home or workplace. This makes the ductless fans or chilled water pumps to handle a few spaces with unique systems the equipment of choice,especially in retrofit situations. load patterns.In addition,because air is moved only in the space required,no energy is wasted while air moves through the ducts. SIMPLE SERVICING AND MAINTENANCE Removing the top panel on outdoor units provides immediate EASY-TO-USE CONTROLS access to the control compartment,providing a service technician The high wall units have microprocessor—based controls to provide access to check unit operation.In addition,the draw—thru design of the ultimate in comfort and efficiency. The user friendly wireless the outdoor section means that dirt accumulates on the outside remote control provides the interface between the user and the unit. surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent. ACCESSORIES On all indoor units,service and maintenance expense is reduced due to easy—to—use cleanable filters.In addition,these high wall Customizing these ductless systems to your application is easily systems have extensive self—diagnostics to assist in accomplished. troubleshooting. Adding a condensate pump accessory to the high wall fan coil provides installation flexibility. OPTIONAL WIRED CONTROLLER AGENCY LISTINGS All systems are listed with AHRI(Air Conditioning,Heating& Refrigeration Institute),and ETL. 2 MODEL NUMBER NOMENCLATURE INDOOR UNIT 40 MH H 0 09 — —— 40=FAN COIL UNIT VOLTAGE 1 =115-1-60 MH=MODEL 3=208/230-1-60 INDOOR FAN COIL TYPE H=HIGH WALL SYSTEM TYPE H=COOLING ONLY O=HEAT PUMP NOT USED NOMINAL CAPACITY 09—3/4 TON 12-1TON 18—1-1/2 TONS NOT USED 24—2 TONS aritERro i+. %CERTIFIED,. `" k www.enriaimctarnora Use of the AHRI Certified TM Mark indicates a `+ us manufacturer's participation in the <lSTEt1 program For verification of certification for individual products,go to www.ahridirectory.org. 3 STANDARD FEATURES AND ACCESSORIES Ease Of Installation INDOOR UNITS Mounting Brackets S Low Voltage Controls S Comfort Features Microprocessor Controls S I, Wired Remote Control A NN Wireless Remote Control S hit Up—Down Airflow Louver Swing S Air Direction Control S i Auto Restart Function Cold Blow Protection On Heat Pumps S %r* Freeze Protection Mode On Heat Pumps Turbo Mode Silence Mode Auto Changeover On Heat Pumps S Fig.1 Condensate Pump Accessory Follow Me S On high wall fan coils,the condensate pump has a lift capability Energy Saving Features of 12 ft.(3.6 m)on the discharge side with the pump mounted in Sleep Mode S the fan coil or 6 ft.(1.8 m)on the suction side if the pump is Stop/Start Timer S remote mounted.The pump is recommended when an adequate 46°F Heating Mode(Heating Setback) S drain line pitch cannot be provided,or when the condensate must Safety And Reliability move up to exit. Indoor Coil Freeze Protection S NOTE: An external 115v power source is required to run the Indoor Coil High Temp Protection in Heating Mode S pump on unit sizes 9k and 12k. Ease Of Service And Maintenance Cleanable Filters S Diagnostics g Application Flexibility Condensate Pumps A Legend S Standard A Accessory ACCESSORIES ACCESSORY NO. DESCRIPTION FOR MODELS 53DS-900---117 CONDENSATE PUMP SIZES 09,12(115V) (115V) 53DS-900---118 CONDENSATE PUMP SIZES 09,12,18,24, (208-230V) (208-230V) KSACN0401AAA WIRED REMOTE ALL SIZES CONTROL 53DS-900---089 INSULATED 25'LINE SIZE 09 SET—1/4"X 3/8" 53DS-900---008 INSULATED 25'LINE SIZES 12,18 SET-1/4"X 1/2" 4 DIMENSIONS—INDOOR HIGH WALL UNIT SIZE 9K 12K 9K 12K 18K 24K Voltage (115V) (115V) (208/230V) (208/230V) (208/230V) (20/230V) Height In.(mm) 11.81(300) 11.81(300) 11.81(300) 11.81(300) 12.8(325) 13.41(341) Width In.(mm) 28.53(725) 32.00(813) 28.53(725) 32.00(813) 38.36(974) 43.83(1113) Depth In.(mm) 7.75(197) 7.75(197) 7.75(197) 7.75(197) 8.87(225) 9.22(234) Weight—Net (cooling onis) Lbs(kg) 16.53(7.5) 17.64(8) 16.53(7.5) 17.64(8) 23.15(10.5) 30.86(14) Weight—Net Lbs(kg) 21.83(9.9) 22.49(10.2) 21.16(9.6) 22.49(10.2) 31.97(14.5) 40.12(18.2) (Heat Pump) 78"2 0 17151 r i 1 9E, [13041 16 24 14121 1 ....._ -"-1-•- 5 06. 112181 13 81 135111 9.33 [237] 11: --. 8 -7 - -- -t- - ----7- - -- - I C-. .„.:.) el_..1 c.:7741,AF,111 0 4 DE/ 'fr:fra: LJ l[ ,----- _. Eri 0 / cr.( 1 2 45 Cb3J 8 1.J___0, , J-0 J 1 --J-% 49 1E83 : 1 — . ,-3 • I 5 40 11371 L ______.„1__ L4 61_11173 -1 i.- 0• 0 -t.1‘,--r--Lt- v •*_--1•1_ 1-8-7=11-3-, 7,75 11771 1-1 /2-1 / I I I-- 28 513 17251 -1 r-r- - -- nmmmpp.m..-wp.....g......mim. ' 0 11 e 1012 1257] 101E1 12571 ( — 1183 13011 0,07 1221 ,-- = =4 -I i I-11 imintimmo 003 [161-1 _f 2 17 15511 0 45 1.11.11 0 71 1181,1 1 90 14631 110 C28] 1.50 146J 2 17 155,1 2 13 45 11] L______:1 Units:Inches[mm] ____:----_-_t_-_, L NI ME= 1111111•11MIMINF-7 1 I ---r_nmalimmimmiria r _1 L.- 7103] 151h8 ...J 1 : 17_111111.•111.1.111,1111111111L_L_,I,r_ I 152 _8J. . _...i , I In IIBIMMIii:ii,WM,Viii OM (-2 Fig.2—Size 9K ., 5 DIMENSIONS-INDOOR(CONT) 9.09 1.2.1.1 9.10 C2311 7_......_.......___—._..__.-T i r. 7.95 1:20374. 5.01.[2037 1 1.eC - - .. B ;, :G_ C7... - 7 I � l ... 41:1f U<]--__L 1''„j J-. ...- .191 1491 137 C47 31 - (if'47..._ 1,'34 [9a] 1. 1 �n 32.00 [8137 0,49 1121 MN L rof1.27 [227 .- r r_ ' - � U. 3 CG7 --- .._-- - ...., 047 [127 98.2---L- .79 02071 - - - - - --- - .._ ..-- - 277 [55j f- 0.'1 '18] - I P7 1461 - 1.81[46]1 1.10 C 4] -- _ _ U.4: 1111 2.17 1557 __ _ __ _...." - •'1UNiai ilii W,5111i MPi ' -_—i Units:Inches[mm] I - a ISI 21 1 5161 15 irrr..+ti* Yw .... ,Il _.... 1,19 [ .�7 _ Fig.3—Size 12K 6 I • DIMENSIONS—INDOOR(CONT) f I , -- 71 111_- -,-r-I9 71 io._ Ec -1 - - -1 3 r0 e00 - i ; _ 2 - -_ T -i 7) Ili r-.....-..L.,.-.) •4 0 0 -2 ,.,,,„, t- + : . 0 „... ..„ 4,---,- :i: Li + OE 4_ .1,, , , t ) a _____ ___ ___ ,I.,,'"r,I 1 ' (1 ,y it- -- ------ 3,.. _j. 1 '- 741771172 -- 1747 1444/ -.1... -I'I0 (1571- 9-.3; 2,20 171,-- 153 1270-4430 [1041J- -- - ,-,_...._____, .6-.......-. 4-.... .,___,_._ ),. o co _Cl_ C-1 i L 3,,, L9/4 F - 4 49 El I AI IF) , Lr 11 1111111111111111 .1 .1 .00.0 (.1.-' j _ -MIIIIIIMIIIN __ 4 41 0,0 E„,_, J„ ,,6i ___ _I ,33 I r -----7; 0 SO CI Fl- 1 0 71 [19I 195 C491, 0 s.0 El 31 131 14/14 110 [291 _ __ _ # 1 r 1 ' ., 1 .1 .I I, 1 , ; i I LI .I - ii] --,_ I__ - .___. L - - T ' " Hi, . I Units:Inches[mm] po 1 [SI,1-- . -- .I1 1 --- - Fig.4—Size 18 ,._ o- Aftrouidorsimaiiii . 4minowainomwasommiiimminww_ _ 7 DIMENSIONS-INDOOR(CONT) • 7 1265,121.1 sr-, IP 610 1,611—-, 17 124 13171-- .8- 18 4 i 11171 —.11 11 r• II 00 0E781 .--- 1100[2,91 11 1 r---_4 75 18481 --,76 12480---1 1 II 1,1 1,3 ill f I .Cr, 1 T1 .................... - - i - I ni- .,l‘ l '-• r, 2J, 4 p_3015 46_1098.1 1,81 - 2, 1.16,co1i 1''d ;02,54_18 201 i,g 0j, ,;,, 7 i : i f" '( : 1 t J 4 2 1 taird l ------- F + -} 12 154) --t— 1810 14081 5166_ _ '4. 4 k 4 01 11 L. 46 83 111141 —..1 r 0 el 5101 a 1 1 1 4 4 0 I rial'O 0 1 7 0 c."-.. 0 87 12217 f-- '..2 -i- ., e — _____ , i 0 79 1200 101 11510 71 1121-j 1.9 E4/ - 1 69 15N-1 0 63 1161 [44 1501- ,3 89 1611 110 1263- 062 C161 i - 1 .....F WU ilfillip inionmig En_w_j,._Wii cm_emiA` — 1— 20 31 C51t1 —.1 1 I I 4 T __T . Units:Inches[mm] ii ____1,_________ _ Fig.5-Size 24 aWmiiiiiiiiiiiiiiiiii, 8 CLEARANCES — INDOOR CEILING 6" (0.15+in5" . r ; 4 5" (0.13m) min. min. ii 6' (1.8m) FLOOR Fig.6—Indoor Unit Clearance 9 SPECIFICATIONS-COOLING ONLY COOUNG ONLY Size 9 12 9 12 18 24 System Indoor Model 40MHHC09---1 40MHHC12---1 4OMHHC09---3 40MHHC12---3 40MHHC18---3 4OMHHC24---3 Voltage,Phase, V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Cycle Electrical Power Supply Indoor and powered from outdoor unit _ _ MCA A. 0.3 0.3 0.25 0.25 0.4 0.45 Wireless Remote Controller Standard Standard Standard Standard Standard Standard Controls C F/C Convertible) Wired Remote Controller (°F/°C Convertible) Optional Optional Optional Optional Optional Optional Operating Cooling Indoor DB ° FCC) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63--90(17-32 Range Min-Max ) Pipe Connection in(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.52) Size-Liquid Piping Pipe Connection in(mm) 3/8(9.52) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(16) Size-Suction Face Area(sq.ft) Sq.Ft 1.14 1.48 1.14 1.48 2.58 2.59 No.Rows 2 2 2 2 2 2 Indoor Coil Fins per inch 20 20 20 20 20 20 Circuits 2 2 2 2 2 2 Unit Width in(mm) 28.53(725) 32.00(813) 28.53(725) 32.00(813) 38.36(974) 43.83(1113) Unit Height in(mm) 11.81 (300) 11.81 (300) 11.81 (300) 11.81 (300) 12.8(325) 13.41 (341) Unit Depth in(mm) 7.75(197) 7.75(197) 7.75(197) 7.75(197) 8.87(225) 9.22(234) Net Weight lbs(kg) 16.53(7.5) 17.64(8) 16.53(7.5) 17.64(8) 23.15(10.5) 30.86(14) Number of Fan Speeds 4 4 4 4 4 4 Airflow(lowest to CFM 163/205/239/265 190/239/301/328 177/224/260/286 188/238/305 344/422/506/550 420/514/609/640 Indoor highest) Sound Pressure dB(A) 27/35/39/40 29/36/41/42 28/35/39/40 28/35/40/42 34/39/43/45 I 39/44/49/49 (lowest to highest) Air throw Data ft(m) 20(6.1) 22(6.7) 20.3(6.2) 22(6.7) 24(7.3) 39.4(12) � Moisture removal Pmt/h 2.07(0.98) 3.17(1.50) 2.07(0.98) 3.09(1.46) 4.61 (2.18) 6.38(3.02) (L/h) Field Drain Pipe in(mm) 0.625(16) 1 0.625(16) 0.625(16) 0.625(16) 0.625(16) 0.625(16) Se O.D. Performance may vary based on the compatible outdoor units.See the respective pages on the outdoor unit's product data for performance data. COMPATIBILITY TABLE Indoor Unit 40MHHC09---1 40MHHC12---1 40MHHC09---3 40MHHC12---3 40MHHC18---3 40MHHC24---3 Outdoor Unit Single Zone 38MHRCO9A--1 38MHRC12A--1 38MHRCO9A--3 38MHRC12A--3 38MHRC18A--3 38MHRC24A--3 Outdoor Unit Multi-Zone Cooling Only NOT compatible with Multi-zone Outdoor Units. 10 SPECIFICATIONS-HEAT PUMP HEAT PUMP Size 9 12 9 12 18 24 System Indoor Model 40MHHQ09---1 40MHHQ12---1 40MHHQ09---3 4OMHHQ12---3 40MHHQ18---3 40MHHQ24---3 Voltage,Phase, V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Cycle Electrical Power Supply Indoor unit powered from outdoor and MCA A. 0.3 0.3 0.25 0.25 0.28 0.45 Wireless Remote Controller Standard Standard Standard Standard Standard Standard Controls C FP C Convertible) Wired Remote Controller Optional Optional Optional Optional Optional Optional C FP C Convertible) Cooling Indoor DB a FC C) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63-90(17-32) 63-90(17-32) Operating Min-Max Range Heating Indoor DB o FC C) 32-86(0-30) 32-86(0-30) 32-86(0-30) 32-86(0-30) 32-86(0-30) 32-86(0-30) Min-Max Pipe Connection in(mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.52) Size-Liquid Piping Pipe Connection Size-Suction in(mm) 3/8(9.52) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(16) Face Area(sq.ft) Sq.Ft. 1.14 1.48 1.14 1.48 2.58 2.58 No.Rows 2 2 2 2 2 2 Indoor Coil Fins per inch 20 20 20 20 20 20 Circuits 2 2 2 2 2 2 Unit Width in(mm) 28.53(725) 32.00(813) 28.53(725) 32.00(813) 38.36(974) 43.83(1113) Unit Height in(mm) 11.81 (300) 11.81 (300) 11.81 (300) 11.81 (300) 12.8(325) 13.41 (341) Unit Depth in(mm) 7.75(197) 7.75(197) 7.75(197) 7.75(197) 8.87(225) 9.22(234) Net Weight lbs(kg) 21.83(9.9) 22.49(10.2) 21.16(9.6) 22.49(10.2) 31.97(14.5) 40.12(18.2) Number of Fan Speeds 4 4 4 4 4 4 Airflow(lowest to CFM 153/253/282/312 200/265/306/329 165/229/271/324 212/282/324/353 353/412/529/559 353/483/589/647 Indoor highest) Sound Pressure d6(A) 31/35/39/41 29/38/42/42 31/36/40/42 34/39/41/43 34/39/44/46 38/42/48/49 (lowest to highest) Air throw Data ft(m) 20.7(6.3) 22(6.7) 20.3(6.2) 22.6(6.9) 25(7.6) 37.7(11.5) Moisture removal Pint/h 2.03(0.96) 3.49(1.65) 2.05(0.97) 3.38(1.6) 4.63(2.19) 5.73(2.71) (L/h) Field Drain Pipe in(mm) 0.625(16) 0.625(16) 0.625(16) 0.625(16) 0.625(16) 0.625(16) Se O.D. Performance may vary based on the compatible outdoor units.See the respective pages on outdoor unit's product data for performance data. COMPATIBILITY TABLE Indoor Unit 40MHHQ09---1 4OMHHQ12---1 40MHHQ09---3 40MHHQ12---3 40MHHQ18---3 40MHHQ24---3 Outdoor Unit Single Zone 38MHRQ09A--1 38MHRQ12A--1 38MHRQ09A--3 38MHRQ12A--3 38MHRQ18A--3 38MHR024A--3 38MGRQ18B--3 38MGRQ24C--3 Outdoor Unit Multi-Zone f. 38MGRQ30D--3 38MGRQ36D--3 38MGRQ48E--3 11 APPLICATION DATA UNIT SELECTION SYSTEM OPERATING CONDITIONS Select equipment that either matches or is supports slightly more OPERATING RANGE than the anticipated peak load. This provides better humidity MIN/MAX°F(°C) control,fewer unit cycles,and less part—load operation. COOLING HEATING For units used in spaces with high sensible loads,base equipment Indoor DB 63/90(17/32) 32/86(0/30) selection on unit sensible load,not on total anticipated load.Adjust NOTE:Reference the product installation instructions for more for anticipated room wet bulb temperature to avoid undersizing the equipment. information. UNIT MOUNTING (INDOOR) DRAIN CONNECTIONS Refer to the unit's installation instructions for further details. Install drains to meet the local sanitation codes.If adequate gravity Unit leveling For reliable operation,units should be level in all drainage cannot be provided,the unit should be equipped with an U Un t l accessory condensate pump.The high wall fan coil unit condensate plapumps have a maximum lift of 10' (3.05 m)for 9k and 12k units Clearance—Provide adequate clearance for airflow(see Fig.6). and 25'(7.62 m)for 18k and 24k units. Unit location — Select a location which provides the best air See the physical dimension tables for the drain sizes. circulation for the room.These units should be positioned as high NOTE:High wall fan coil units have internal condensate traps. as possible on the wall for the best air circulation. The unit return A trap is not required. and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. Drain connections may be routed through alternate locations on Place the unit in the middle of the selected wall(if possible).Use most fan coils(see Fig.7). an outside wall, if available,to make piping easier, and place the unit so it faces the normal location of room occupants. Pipe holder Pipe cover UNIT MOUNTING (OUTDOOR) I ��4 Left piping Refer to the unit's installation instructions for further details. , ���r Pipe cover ( � 3 Left back piping Do not install the indoor or outdoor units in a location with special environmental conditions. For those applications, contact your �:.,f Ductless representative. 1 1 ♦7— Right back piping MOUNTING TEMPLATE Right piping Fig.7—Piping Locations Refer to the unit's installation instructions for further details. The fan coil units are furnished with mounting to mark the location of the wiring,and the refrigeration line hole locations. SUPPORT Adequate support must be provided to support the weight of all the fan coils.Refer to the Physical Data section for fan coil _ weights,and the base unit dimensional drawings for the mounting bracket locations. 12 WIRING CAUTION All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA(minimum circuit amps)and MOCP(maximum EQUIPMENT DAMAGE HAZARD over current protection) to correctly size the wires and the Failure to follow this caution may result in equipment disconnect fuse or breakers respectively.Per the caution note,only damage or improper operation. stranded copper conductors with a 600 volt rating and double • Be sure to comply with local codes while running wire insulated copper wire must be used. from the indoor unit to the outdoor unit. The use of BX cable is not recommended. • Every wire must be connected firmly.Loose wiring Recommended Connection Method for Power and may cause the terminal to overheat or result in unit malfunction.A fire hazard may also exist.Ensure all Communication Wiring—Power and Communication Wiring: wiring is tightly connected. • No wire should touch the refrigerant tubing, The main power is supplied to the outdoor unit.The field supplied compressor or any moving parts. 14/3 power/communication wiring from the outdoor unit to indoor • Disconnecting means must be provided and shall be unit consists of four (4) wires and provides the power for the located within sight and readily accessible from the air indoor unit. Two wires are high voltage AC power, one is conditioner. communication wiring and the other is a ground wire. • Connecting cable with conduit shall be routed through Recommended Connection Method for Power and i-he le in I.- cond i I.i'1. Communication Wiring(To minimize CONTROL SYSTEM communication wiring interference) The indoor unit is equipped with a microprocessor control to PowerWiring: perform two functions: The main power is supplied to the outdoor unit.The field supplied 1. Provide safety for the system power wiring from the outdoor unit to indoor unit consists of three 2. Control the system and provide optimum levels of comfort (3)wires and provides the power for the indoor unit.Two wires are and efficiency. high voltage AC power and one is a ground wire. The main microprocessor is located on the control board of the To minimize voltage drop, the factory recommended wire size is fan coil unit(outdoor units also have a microprocessor)with 14/2 stranded with a ground. thermistors located in the fan coil air inlet and on the indoor coil. Communication Wiring: Heat pump units have a thermistor on the outdoor coil.These A separate shielded Stranded copper conductor only, with a 600 thermistors monitor the system operation to maintain the unit volt rating and double insulated copper wire,must be used as the within acceptable parameters and controls the operating mode. communication wire from the outdoor unit to the indoor unit. WIRELESS REMOTE CONTROL Please use a separate shielded 16GA stranded control wire. v CAUTION 111111 • EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. • Wires should be sized based on NEC and local codes. Fig.8— Wireless remote control • Use copper conductors only with a 600 volt rating and 1. A wireless remote control is supplied for system operation double insulated copper wire. for system operation of all high wall units. 2. Each battery operated wireless(infrared)remote control may be used to control more than one unit. WIRED REMOTE CONTROL (OPTIONAL) P/N KSACNO401AAA 1. Optional wired remote controller used for system operation of all high wall units. 2. Kit includes a wired remote controller and a connecting cable. 3. Connect with wire terminal between remote controller and indoor unit. 4. Display in °F or °C and temperature increments every 1°F or every 1°C. 13 AIR FLOW DATA o COOLING ONLY 9K(115V) 12K(115V) 9K(208/230V) 12K(208/230V) 18K(208/230V) 24K(208/230V) Turbo 265 328 286 335 550 640 High 239 301 260 305 506 609 Indoor(CFM) Medium 205 239 224 238 422 519 Low 163 190 177 188 344 420 HEAT PUMP 9K(115V) 12K(115V) 9K(208/230V) 12K(208/230V) 18K(208/230V) 24K(208/230V) Turbo 312 329 312 329 312 329 High 282 306 271 324 529 589 Indoor(CFM) Medium 253 265 229 282 412 483 Low 153 200 165 212 353 353 AIR THROW DATA HIGH WALL UNIT CAPACITY MAX.APPROXIMATE AIR THROW FT.(M) APPROXIMATE AIR THROW RANGE.(M) COOLING ONLY 9K(115) 20(6.1) 4.6-20.7 (1.4-6.3) 12K(115) 22(6.7) 4.6-22.6 (1.4-6.9) 9K(208) 20.3(6.2) 4.6-20.7 (1.4-6.3) 12K(208) 22(6.7) 4.6-22.6 (1.4-6.9) 18K(208) 24(7.3) 4.6-29.5 (1.4-9.0) 24K(208) 39.4(12) 7.2-44.9 (2.2-13.7) HEAT PUMP 9K(115) 20.7(6.3) 4.6-21.3 (1.4-6.5) 12K(115) 22(6.7) 4.6-22.6 (1.4-6.9) 9K(208) 20.3(6.2) 4.6-20.7 (1.4-6.3) 12K(208) 22.6(6.9) 4.6-23.6 (1.4-7.2) 18K(208) 25(7.6) 4.6-30.2 (1.4-9.2) 24K(208) 37.7(11.5) 5.9-43.3 (18.-13.3) MOISTURE REMOVAL COOLING ONLY Size 9K 12K 9K 12K 18K 24K Voltage,Phase,Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Dehumidifying L/h 0.98 1.50 0.98 1.46 2.18 3.02 volume Dehumidifying PINT/h 2.07 3.17 2.07 3.09 4.61 6.38 volume HEAT PUMP Size 9K 12K 9K 12K 18K 24K Voltage,Phase,Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Dehumidifying L/h 0.96 1.65 0.97 1.60 2.19 2.71 volume Dehumidifying PINT/h 2.03 3.49 2.05 3.38 4.63 5.73 volume SOUND PRESSURE Cooling Only 9K(115V) 12K(115V) 9K(208/230V) 12K(208/230V) 18K(208/230V) 24K(2081230V) Cooling Dba at Operation (High/Med/ 40/39/35/27 42/41/36/29 40/39/35/28 42.8/40.5/35/28 45.2/43.5/39.5/34.5 49.4/49/44/39.5 Indoor Low CFM Heat Pump 9K(115V) 12K(115V) 9K(208/230V) 12K(2081230V) 18K(208/230V) 24K(208/230V) Cooling Operation 41.4/39.4/35.7/31.1 42.6/42.0/38.4/29.6 42.5/40.9/36.6/31.4 43.9/41.8/39.5/34.0 46.4/44.5/39.0/34.6 49.7/48.2/42.9/38.5 Indoor Dba at Heating (High/Med/ Operation Low CFM 38.3/37.9/34.1/29.2 41.5/41.2/35.9/25.8 42.3/39.5/33.3/28 42.6/42.0/39.3/34.2 44.9/42.3/36.7/33.2 49.7/44.9/38.9/31.3 Indoor Sound Pressure 14 FAN AND MOTOR SPECIFICATIONS s. Cooling Only 9K 12K 9K 12K 18K 24K (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V) Material Acrylonitrile Styrene+30%GF High Wall Fan Type GL-94*520-1 GL-94*605-N GL-94*520-I GL-94*605-N GL-98*758-I GL-108*818 Diameter In.(mm) 3.7(94) 3.7(94) 3.7(94) 3.7(94) 3.86(98) 4.25(108) Height In.(mm) 20.5(520) 23.8(605) 20.5(520) 23.8(605) 29.8(758) 32.2(818) Model RPG15A/YKFG RPG15A/YKFG RPG20B/YKFG RPG20B/YKFG YKFG-28-4- RPG45B/YKFG -15-4-28-1 -15-4-28-1 -20-4-10L -20-4-10L 6-5 -45-4-13 Volts V 115 115 220 220 220 220 Phase 1 1 1 1 1 1 FLA 0.43 0.43 0235 0.235 0.4 0.6 Type AC Insulation E E E E E B Class Safe IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 Class High Wall Input W 46 46 47.4 47.4 58.5 83.5 Fan Motor Output W 15 .15 20 20 28 45 Range of Amps 0.425±10% 0.425±10% 0.218±10% 0.218±10% 0.267±10% 0.38±10% Current Rated Amps 0.3 0.3 0.25 0.25 0.4 0.45 Current Rated HP HP 0.02 0.02 0.027 0.027 0.037 0.061 Speed Rev/min 1030/900/750 1100/900/750 1030/900/750 1100/900/750 1150/1000/850 1150/1000/850 Rated Rev/min 1030 1100 1030 1100 1150 1150 RPM Max. W 56 56 50 50 74.4 129 Input Heat Pump 9K 12K 9K 12K 18K 24K (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V) Material Acrylonitrile Styrene+30%GF High Wall Fan Type GL-94*605-N GL-94*605-N GL-94*605-N GL-94*605-N GL-98*758-1 GL-108*818 Diameter In.(mm) 3.7(94) 3.7(94) 3.7(94) 3.7(94) 3.86(98) 425(108) Height In.(mm) 23.8(605) 23.8(605) 23.8(605) 23.8(605) 29.8(758) 32.2(818) Model YKFG-15-4- ZKFP-20-8- ZKFP-20-8- ZKFP-20-8- YKFG-28-4- ZKFP-58-8- 28-1 5 6 6 6-5 1 Volts V 115 DC160 DC310 DC310 220 DC310 Phase 1 3 3 3 1 3 FLA 0.43 0.47 0.34 0.34 0.4 0.45 Type AC DC DC DC AC DC Insulation E E E E E E Class Safe IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 Class High Wall Input W 46 25 21 21 58.5 62 -- Fan Motor Output W 15 20 20 20 28 58 8 Range of Amps 0.425±10% 0.17±10% 0.067±10% 0.067±10% 0.267±10% 0.19±10% Current I CurrenRatt Amps 0.3 0.3 0.25 025 0.28 0.45 Rated HP HP 0.02 0.027 0.027 0.027 0.037 0.078 Speed Rev/min 1080/900/750 1250/900/800 1200/1050/800 1100/900/750 1150/900/800 1100/900/700 Rated Rev/min 1080 1250 1200 1100 1150 1100 RPM Max. ,W 56 25 21 21 74.4 62 Input I 15 WIRING DIAGRAMS rOPTIONAL4 'OPTIONAL INDOOR FAN r CAP INDOOR WIRING DIAGRAM YIG ION ttoACble A r g® Oo _O 0 motor ~ only I ® I zi M Cl- 5 z O 3/ /5(3or2) y y CN271 I I I ( I O I I I I CN13 CN12 P-i CN19 CN22 FOPTIONAL ❑ i a PLASMA CN26 2rOPTIONAL o RED UT SWITCH MAIN BOARD CN290 / BOARD BLUE(BLACK) L-IN RYt 2ICN701I YELLOW PIPE TEMPERATURESENSOR YIG 1 IN_IN 0150 N I CN32 CN18 Ma FM rt. I ICN31 E I I CNI40 I L N S 0 JXI 2, , wi 1 ROOMTEMPERATURESENSOR .• 0 0 0 INDOOR UNIT % CN1 CN3 z MULTI-FUNCTION CONTROL BOARD ICN43I �� /3 DISPLAY BOARD 4i r OPTIONAL -R OUTDOOR UNIT O CN42 CN41 CN44 CN45 CN46 �CN4I n — . Controller E XIY�IEI12V/5VI IHAIHBI I I I I I I Lo I il` j Wire Controllei OPTIONAL To CCM Comm. To Randomly To Remote To Remote ROOIITEMPERATAE Bus or 485 Connected Alarm Switch SENSOR Wire-controller Wire-controller FOR SETTING NETADDRESS(CCM Comm.Bus) --This symbol indicates the ENC 3+F 1 07\ ON07�\, ON 07\ ON "07 ON element is optional,the actual (MULTI-FUNCTION T a VDy % t) r lshape shall prevail. CONTROL BOARD) 8L 1 2t 1 2 1 800 1 2 81.0 1 2 CODE 0-F 0-F 0-F 0-F NETADDRESS 0-15 16-31 32-47 48-63 FACTORY SETTING Fig.9-Wiring Diagram Sizes 09-12(115V) 1114 lavaii**L-- 16 WIRING DIAGRAMS (CONTINUED) 'OPTIONAL 'OPTIONAL INDOOR FAN r CAP r _J Y/G Applicable z 4. INDOOR WIRING DIAGRAM ION to AC A r (-2® Oo _O motor -- ~ — a0 only 1_cJ z i 5 z 3/ /5(3or2) vii CN27I 1 1111 ° I I I I CN13 CN12 P 1 CN19 CN22 rOPTIONAL ❑ i IE PIASMA CN26 2 rOPTIONAL L-OUT UT SWITCH MAIN BOARD CN29❑ / BOARD BLUEIBLACKI L-lN 1=6 RY1 2ICN701j YELLOW VG l IN IN CN15�NRESENSOR eICN31 CN32 CN18 maw�: :� 1 I I 0 CNi4n 1 L1 L2 S 1X1 2, 4i I ROOtITEMPERATUPESERSOR' 0 0 0 ® INDOOR UNIT MI CM CN3 zMULTI-FUNCTION CONTROL BOARD IC 43) ® �3 DISPLAY BOARD 4, OPTIONAL AL OUTDOOR UNIT p st,K. CN41 CN44 CN45 CN46 r a 1EI12VI5VI IHAIHBI I I I I I J ICN4I CN2 §, I Controller o -- 4 _j Wire Controllei OPTIONAL To CCM Comm. To Randomly To Remote To Remote ROOMTEMFFRAIDRE Bus or 485 Connected Alarm Switch SENSOR Wire-controller Wire-controller FOR SETTING NETADDRESS(CCM Comm.Bus) --This symbol indicates the ENC 3+F 1 07 O N07\ON 07N ON (07,,. ON element is optional,the actual (MULTI-FUNCTION (IV 1;W Cr % cf)shape shall prevail. CONTROL BOARD) 819 1 2 819 1 2 8l 1 28151 1 2 CODE 0–F 0–F 0–F 0–F NETADDRESS 0-15 16-31 32-47 48-63 FACTORY SETTING Fig.10–Wiring Diagram Sizes 09-24(208-230V) 17 GUIDE SPECIFICATIONS INDOOR WALL—MOUNTED DUCTLESS UNITS Size Range:3/4 to 2 Ton Nominal Cooling and Heating Capacity Model Number:40MHH PART 1 —GENERAL The unit has the following functions as a minimum: 1.01 System Description 1. An automatic restart after a power failure at the same operating conditions as at the failure. Indoor,wall—mounted,direct—expansion fan coils are matched with 2. A timer function to provide a minimum 24—hour timer the cooling only or the heat pump outdoor unit. cycle for system Auto Start/Stop. 1.02 Agency Listings 3. Temperature—sensing controls have sense return air Unit is rated per AHRI Standards 210/240 and listed in the AHRI temperature. directory as a matched system. 4. Indoor coil freeze protection. 1.03 Delivery, Storage,And Handling 5. Wireless infrared remote control to enter set points and Units are stored and handled per the unit manufacturer's operating conditions. recommendations. 6. Automatic air sweep control to provide on or off activation 1.04 Warranty(For Inclusion By Specifying of air sweep louvers. Engineer) 7. Dehumidification mode provides increased latent removal capability by modulating the system operation and the set PART 2 —PRODUCTS point temperature. 8. Fan—only operation to provide room air circulation when no 2.01 Equipment cooling is required. A. General:Indoor,direct—expansion,wall—mounted fan coil 9. Diagnostics provide continuous checks of unit operation The unit is complete with a cooling/heating coil, fan, fan motor, and warn of possible malfunctions.Error messages appear piping connectors, electrical controls, microprocessor control on the unit. system, and integral temperature sensing. The unit is furnished 10. Fan speed control is user—selectable: turbo, high,medium, with an integral wall mounting bracket and mounting hardware. low, or microprocessor controlled automatic operation B. Unit Cabinet: during all operating modes. Cabinet discharge and inlet grilles are attractively styled, 11. Automatic heating—to—cooling changeover in the heat pump high—impact polystyrene. The Cabinet is fully insulated for mode. The control includes a deadband to prevent rapid improved thermal and acoustic performance. mode cycling between heating and cooling. C. Fans: 12. Indoor coil high temperature protection are provided to 1. Fan is the tangential direct—drive blower type with air intake detect excessive indoor discharge temperature when the unit at the top of the unit and discharge at the bottom front.An is in the heat pump mode. automatic,motor—driven vertical air sweep is provided as G. Filters: standard equipment. Unit has a filter track with factory—supplied cleanable filters. 2. The air sweep operation is user selectable. The vertical H. Electrical Requirements: sweep may be adjusted (using the remote control). The Indoor fan motor to operate on 115V on model sizes 09-12 and on horizontal air direction may be set manually. 208-230V on model sizes 09-24,as specified.Power is supplied D. Coil: by the outdoor unit. The coil is a copper tube with aluminum fins and galvanized steel tube I. Operating Characteristics: sheets.The fins are bonded to the tubes by mechanical expansion and The system has a minimum SEER(Seasonal Energy Efficiency blue hydrophilic pre—coated. A drip pan under the coil has a drain Ratio)and HSPF at AHRI conditions,as listed on the connection for the hose attachment to remove condensate. The specifications table. condensate pan has an internal trap. J. Refrigerant Lines: E. Motors: All units should have refrigerant lines that can be oriented to Motors are open drip—proof, with a permanently lubricated ball connect from the left,right or back of unit. Both refrigerant lines bearing.The fan motors shall be 4—speed. need to be insulated. F. Controls: K. Special Features(Field Installed): Controls consist of a microprocessor—based control system which 1. Condensate Pump: shall control space temperature,determine optimum fan speed, The condensate pump removes condensate from the drain and run self diagnostics.The temperature control range is from pan when gravity drainage cannot be used.The pump is 62°F to 86°F(17°C to 30°C)in increments of 1°F or 1°C,and designed for quiet operation.The pump consists of two have 46°F Heating Mode(Heating Setback).The wireless remote parts:an internal reservoir/sensor assembly,and a remote controller has the ability to act as the temperature sensing location sound—shielded pump assembly.A liquid level sensor in for room comfort. the reservoir stops the cooling operation if the liquid level in the reservoir is unacceptable. ©2017 Bryant Heating&Cooling Systems•7310 W.Morris St.•Indianapolis,IN 46231 Edition Date:01/17 Catalog No.PDS40MHH-01 Manufacturer reserves the right to discontinue,or change at any time,specifications or designs without notice and without incurring obligations. Replaces:NEW 18 Bathroom Exhaust Fans „...„� �^►!�Y■ ^•`�`` FV-05-11 VKSL1 h _ �l ;. eeeet Adjustable Airflow for VENTILATION a FAN Maximum Performance Specification Submittal Data /Panasonic Ventilation Fan Description Customizable Ventilation Fan/Light shall be low sone ceiling mount rated for continuous run. 4 OC 6 duct Fan shall be ENERGY STAR®rated and certified by the Home Ventilating Institute(HVI).Fan shall include energy efficient LED lighting.Evaluated by Underwriters Laboratories and conform J to both UL and cUL safety standards. • Motor/Blower: 'yl�i� i\i� •Enclosed DC brushless motor technology rated for continuous run. J \\ •Fan ventilation rates shall be manually adjustable for 50-80-110 CFM. •Power rating shall be 120 volts and 60 Hz. � 1�1 •Fan shall be UL listed for tub/shower enclosure when used with a GFCI protected circuit and a l II� I used in insulated ceiling(TYPE I.C.). � • :'� R ;‘- '; % o •Fan equipped with thermal cutoff fuse. / ,y. •Removable,permanently lubricated,plug-in motor. _ ! Housing: •Rust proof epoxy and polyester resin coating,26 gauge galvanized steel body. ." rim •Integrated dual 4'or 6"diameter duct adapter. ` •Built-in metal flange provides blocking for penetrations through drywall as an Air Barrier,and 0.' \/a assists with the decrease in leakage in the Building Envelope during blower door testing. ,-, •Built in backdraft damper. •Articulating and expandable installation bracket up to 24". \ Grille: •Attractive design using Poly Pro material. \ •Attaches directly to housing with torsion springs. / •Includes a motion sensor cap for use as a cover when the motion sensor Plug'n PlayTM module has not been selected. Light: *(2)7W GU24 base \ \ •Two replaceable,ENERGY STAR®rated,7W GU24 LED(amps included. y :,GGG base LED lamps Warranty: •ALL Parts:3 Years from original purchase date. F V-05 1 V KS I-1 DC Motor:6 Years from original purchase date. LED:5 years from original purchase date. Architectural Specifications: Customizable Ventilation Fan/Light shall be ceiling mount,ENERGY STAR®rated type with multi-speed control(0,30-100 CFM,in 10 CFM increments)that shall be built-in with a Performance Curve 4"or 6"duct high/low adjustable delay timer and activated by a wall switch,Motion Sensor Plug'N PIayTM 0.80 module or Condensation Sensor Plug'N PlayTM module.Features a built-in speed selector. Select from 50/80/110 CFM and no more than<0.3/<0.3/0.4 sone as certified by the Home t °70 ' Ventilating Institute(HVI)at 0.1 w.g.with no less than 53/86/114 CFM and no more thano.eo „ _ ..., <0.3/0.6/0.9 sones at.25 w.g.Power Consumption shall be no greater than 3.2/5.8/11.1 watts i iii� , -AFM at 0.1 w.g.and 6.6/11.1/17.6 watts at 0.25 w.g.ENERGY STAR®rated with efficiency of no i 0.w i S --110.11less than 12.8/13.3/9.9 CFM/watt at 0.1 w.g.and than 7.7/7.7/6.3 CFM/watt at 0.25 w.g.The h - MOM motor shall be enclosed with brushless DC motor engineered to run continuously.DC motor 040 mmullip —"�F, speed shall automatically increase when the fan senses static pressure to maintain selected LLL\��` i 30CFM CFM. Power rating shall be 120v/60Hz.Duct diameter shall be no less than 4",inclusive of an 0.30 ol,' —7 integrated dual 4"or 6"duct adapter.Plug'N PI3yTM modules provide up to two additional 0.20 features.Select from Condensation Sensor,LED Night Light and Motion Sensor.Fan shall IMMM..'I be UL and cUL listed for tub/shower enclosure when used with a GFCI protected circuit.Fan o.to can be used to comply with ASHRAE 62.2,LEED,ENERGY STAR®,IAP,EarthCraft,CaliforniaPFAIIMINS:_1 Title-24 and WA Ventilation Code.Lamps shall be of the LED type with the fan utilizing no less 0.00 0 20 40 eo 80 than two 7 Watt,ESTAR rated,GU24 base LED lamps. 00 120 Airflow(CM DC Motor Technology: y4,PRT F4O4 When fan senses static pressure,its speed is automatically increased to ensure DC - that the desired CFM is not compromised,which allows the fan to perform as rated. '',,,-p4' For complete Installation Instructions visit us.panasonic.com/ventfans Model Quantity Comments Project: Location: Architect: Engineer: Contractor: Submitted by: Date: v • iliVjl FV-05-11VKSL1 ispaeCeGt- Adjustable Airflow for VENTILATION a FAN Maximum Performance Plug 'N PIayTM Modules Plug 'N Play'modules provide up to two features(multi-speed is already built-in to FV-05-11VKSL1).Select from Motion Sensor, Condensation Sensor and LED Night Light. FV-VS15VK1: Multi-Speed with Time Delay- N/A for this Fan, already built-in. isAllows you to select the proper CFM settings to satisfy ASHRAE 62.2 continuous ventilation requirements. The fan runs continuously at a pre-set lower level(0,30-100 CFM, in 10 CFM increments),then elevates to a maximum level of operation (50-80-110 CFM)when the wall switch is turned on,or when the motion sensor or Condensation Sensor module is activated. A High/Low delay timer returns the fan to the pre-set CFM level after a period of time set by the user. MSVK1: Motion Sensor Automatically activa- •. ?.• •u-••,. -- - e room.Once the settings have been applied,the fan becomes truly automatic. i. This mos - _ _: . a es a 20 minute•-.• :• 'ner for the fan. -CSVK1: Condensation Sensor 1 Helps control bathroom co •-- _.'•a o a revent mold and milde. -: - •ogy detects relative humidity and temperature 44 to anticipate dew point,automatical - - . - •ntrol humidity.Built-in Relative Humidity(RH)sensitivity adjustment enable 'a- _ -. • _ oist conditions and for satisfying CalGreen .. :••-a .When the condensation sensor is used in a• conjunction with multi-speed functionality,the fan will kick up to high speed when the con.- a • -nsor detects moisture in the room.This module also activates a 20 minute delay off timer for the fan. -. VK-1: LED Night Light A photocell automatically u .- •- watt LED ni•• -n •arkness is sensed in the room. High/Low brightness 1 7 . �r switch enables you to fine tune t - ••: : - o w. • ' - - •• action with the darkness level of your bathroom.This module -/ also activate -• -. . . lc 20 minute delay off timer for the fan. Fan Specifications WYisper6reen SelectT"':FV-05-11VKSL1 Static Pressure in inches w.g. 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 0.1 0.25 Air Volume(CFM) 110 114 100 105 90 94 80 86 70 71 60 62 50 53 40 43 30 35. Noise(sones) 0.4 0.9 <0.3 0.8 <0.3 0.6 <0.3 0.5 <0.3 0.4 <0.3 0.3 <0.3 <0.3 <0.3 <0.3 <0.3 <0.3 - Power Consumption(watts) 11.1 17.6 8.7 15.0 7.0 12.8 5.8 11.1 4.7 8.9 3.9 7.6 3.2 6.6 2.8 5.7 2.5 '5.0 Energy Efficiency(CFM/Watt) 9.9 6.3 11.6 7.1 13.1 7.5 13.3 7.7 15.3 8.2 15.9 8.4 12.8 7.7 14.6 7.7 12.8 7.4 Speed(RPM) 960 1237 926 1213 872 1184 837 1157 796 1119. 769 1102 740 1081 739 1077 731 1058 Current(amps) 0.12 0.17 0.09 0.15 0.08 0.13 0.07 0.12 0.05 0.09 0.05 0.08 0.04 0.07 0.04 0.06 0.03 0.06 MAX.Current(amps) 0.42 Power Rating(V/Hz) 120/60 ENERGY STAR rated Yes 0.25=Installed Performance Panasonic Eco Solutions Company of North America Eco Products Division Two Riverfront Plaza Newark,NJ 07102 us.panasonic.com/ventfans Panasonic MVI cS us VF16009SS0116 Wall Heater at Base of Stairwells COM— PAK k 1ih imh�1�11ik�&af^e e,q' • b 5 f il _ y [ �' 01 ss Get warm on your terms with our most popular wall heater. The Com-Pak is an efficient, affordable way to add warmth without installing ductwork. Our hard wired heaters have proven safety features and multiple installation options, so your family can enjoy safe, sensible warmth for years. ARCHITECTURAL-ENGINEERING INF' TION Fan forced up flow electric air heaters are ETL listed,factory rated at 120V,208V, • Efficient, quiet fan and dual field rated 208V/240V.A powder coated 20 gauge wall mounting can • Warm up in a hurry with with six knockouts and 34 cubic inch wiring compartment is provided with each complete heater. Each complete heater is powder coated,of unitized a fast heating element construction and attaches to the wall can with a single screw and is self- • Unique compact design contained and completely separate from the wall mounting can. Element is is recess mounted into of nichrome type wire wrapped on mica insulators with a 16 amp rated, at your wall to suit any room 240V, high temperature manual power reset limit switch, and a one-time over • All metal surfaces are temperature thermal back-up fuse,both located on the element board in the powder-coated paint to heated air flow for faster response time to abnormal conditions.A two stage remove sharp edges and centrifugal blower delivering approximately 40 to 55 CFM is driven by an provide a durable finish impedance protected motor.The motor is totally isolated from the heating • Easy to install chamber. Metal grill is of one piece,20-gauge construction and finished with • Rest easy—includes high a powder coat paint system. temperature safety shutoff TECHNICAL INFORMATION • Available with or without UL safety standards require the heater to be placed a minimum distance of 3/4 built-in thermostat inches(1.9 cm)from adjacent surfaces and 4-1/2 inches(11.4 cm)from the floor. Manufacturer recommends installations 12 inches from all surfaces for longer and cleaner performance.All models 1500 watts or less may be ceiling mounted. A 3-foot(91.4 cm)minimum clearance is required for furniture or other objects CADETplaced directly in front of the heater. INVITING WARMTH Electric wall heaters and thermostats work best when installed on an inside wall. cadetheat.com POE N 855.CADET.US �Paaa"< Vancouver,Washington IUSA� ( 2 I us (O *** \YEAR/ Intertak tested to UL standards Wall heater located at base of stairwells. COM- PAK CADET :* N \."; N ', , Grill:9"W x 12"H x 1"D • Rough-in:8"W x 10-1/8"H x 4"D Thermostat temperature range 40°F to 85°F Heater assemblies require a wall can, grill kit, and may require a thermostat Side Grill Front ' PART MODEL*. DESCRIPTION WAITS VOLTS t. AMPS BTUS WT/LBS 0 67508 CSC101 TW Complete unit with stat,wall can&grill,white or almond 1000 120 8.3 3415 7 67580 CSC101TA 67509 CSC151TW oto l JVf51lH 1500 1211 125 5170 7 t2" 67505 CSC102TW30.5 cm 67577 CSC102TA 1000/750 240/208 4.2/3.6 3415/2560 7 67506 CSC152TW „ 1500/1125 240/208 6.3/5.4 5120/3840 7 67578 CSC152TA 67507 CSC202TW „ 67579 CSC202TA 2000/15/0 240/208 8.3/7.2 6825/5120 7 0 67549 CSC101 Complete unit w/o stat,with wall can&grill 1000 120 8.3 3415 7 2.5cm I..,_2 9cm .l 67553 CSC151 1500 120 12.5 5120 7 67541 CSC102 " 1000 240/208 4.2/3.6 3415/2560 7 67543 CSC152 " 1500 240/208 6.3/5.4 5120/3840 7 Wall Can Side 67544 CSC202 " 2000 240/208 8.3/7.2 6825/5120 7 67550 CS051 Heater assembly w/o thermostat 3.5 67560 CS051T Heater assembly with thermostat 500 120 4.2 1710 4 67515 CS101 1000 120 8.3 3415 3.5 67523 CS101T 4 67516 C5151 1500 120 12.5 5120 3.5 w/8" is" 67524 CS151T 4 28.3cm 25.4cm 67563 CS058 3.5 563 208 2.7 1925 3'k^�Q 67573 CS058T 4 8.3 cm 67564 C5078 „ 3.5 32cm 67589 C5078T 750 208 3.6 2560 4 67557 CS108 1000 208 4.8 3415 3.5 67586 CS108T 4 67569 CS118 3.5 67598 CS118T 1125 208 5.4 3840 4 Wall Can Bottom 67571 CS158 3.5 l° 20cm 'I 67599 CS158T 1500 208 7.2 5120 4 t i 67517 CS2083.5 3" 4" 67525 C5208T 2000 208 9.6 6825 4 7. cm 0.2cm 67584 CS052 3.5 .® 0 L 67585 CS052T 500/375 240/208 2.1/1.8 1710/1280 4 It4"I 11/ I 67510 C5072 3.5 4.Scm 3.2cm 67518 CS072T „ 750/563 240/208 3.1/2.7 2560/1925 4 67511 CS102 3.5 67519 CS102T 1000/750 240/208 4.2/3.6 3415/2560 4 40" 208" m) 67512 CS122 3.5 �1M n .3cm� 1250/937 240/208 5.2/4.5 4265/3200 T 67520 CS122T 4 67513 CS152 3.5 CS152T " 1500/1125 240/208 6.3/5.4 5120/3840 4 ZJ ----- 67521 10/a" x(25 67514 CS202 3.5 U ern) 67522 CS202T 2000/1500 240/208 8.3/7.2 6825/5120 4 < � I �� WALL H EATER ACCESSORIES (MODEL CS) Q 4y2•(11 4em)Minirnu PART MODELL* DCSCRtPT1O '� VOLTS MP$ L ' Fir, hl 67061 CC Wall can for model CS,single or 10-pack 2.8 67060 CC10 22.5 69110 CCSMB ROUGH-IN:11"W X 1O-1/8"H X 4"D 69111 CCSMW Surface mount wall can for model CS,black,white or almond 4.4 69112 CCSMA Model No. Code 67079 CGW 1.5 67081 CGW10 Vertical grill kit for model CS,single or 10-pack,white 12 3 CS C 15 2 T W 67075 CGA 1.5 i am Com-Pak wall heater Vertical grill kit for model CS,single or 10-pack,almond 67080 CGA10 12.3 1 1111With wall can 65015 CMGA 2.0 l Wattage: 20=2000 65016 CMGA5 Horizontal grill kit for model CS,single or 5-pack,almond 7.5 1 15=1500 65005 CMGW 2.0 l 12=1250 Horizontal grill kit for model CS,single or 5-pack,white • 65006 CMGW5 7.5 10=1000 67063 CTT1W Built-in thermostat kit for model CS,single pole, I 07=750 240/208/120 22 .2 67065 CTT1A 40°F to 85°F,white or almond 05=500 67064 CTT2W Built-in thermostat kit for model CS,double pole, Voltage: 1=120 67066 CTT2A 40°F to 85°F,white or almond 240/208/120 22 .2 i 2=240/208 67067 CTT1 P Built-in thermostat kit,tamper proof for model CS, 240/208/120 22 .2 8=208 single pole,40°F to 85°F , Includes thermostat 67105 CAMW -Adapter plate for model CS,18-1/2"w x 22"h,white or almond 3.5 Color: W=White 67100 CAMA A=Almond 67115 SAMW Adapter plate for model CS,12"w x21-1/4"h,white or almond 2lIhorizont,al mounting is preferred for heater 67110 SAMA assemblies without thermostat,use model 67088 FWAP Adapter kit repurposes outdated model FW wall can and grill, 1 CMGA or CMGW. use with model CS heater osxmbly Q4 2016 *Suffix W or Ain model designates color „fy5. rij;/9r uet / ! € Spun Aluminum�+ � + E . Iod@� GiRS�1Gi�SR/GD 'F ,,, ngl/.. . ..i , • All aluminum exterior for corrosion-resistant construction • Integral birdscreen to prevent entry of birds and/or small objects .�. a • Built-in curb cap with prepunched holes for easy attachment to roof curbs °1 ': • Optional built-in flashing flange(model GRSF)with prepunched holes for quick and easy installations - . ”. without a roof curb. The GRS can be used with the following accessories: Gravity or motorized dampers to assure weather Construction Features tightness. When you buy a Greenheck Gravity Ventilator, you Prefab curbs to reduce installation time. receive a ventilator with the industry's best performance Protective coatings to extend the life of the unit or and durability for intake (model GRSI) or relief(model blend its color with other equipment. GRSR)for natural gravity or positive pressure systems. Exceptional low silhouette design and construction features make this unit a rugged, efficient and economical air inlet or outlet. • Broadest performance in the industry, up to .1 TM 18,400 cfm (31,300 m3/hr) ,,i4 " • Most advanced weather protection of any ventilator ' _ —' in its class : • Greenheck subjects these products to extensive life GRSF � Optional � testing, assuring the ventilator will provide years of Flashing Integral reliable performance Flange Birdscreen GRSI/GRSR Sizes 8-24 Dimensions B Model A B C D ''= E F Damper Curb Shroud ' Unit Size Size Thickness-Thickness Weight s 8 19 2012 7'/4 1Yz 20% 8% 8 x 8 0.051 0.051 7 (483) (521) (184) (38) (514) (210) (203 x 203) I (1.3) (1.3) 1 (3) mit .--1-+D C 10 ' 19 2012 7'/a 2 1 20% 1 10% 10 x 10 ' 0.051 0.051 a 8 (483) (521) (197) (51) (514) 1 (260) (254 x 254) (1.3) (1.3) i (4) I 7.— 13/a(44) 1 12 22 29 10 3%z 2344 I 12% 12 x 12 0.064 0.064 ( 10 i F (559) (737) a (254) ! (89) (591) (311) (305 x 305) (1.6) (1.6) (5) i A 15 22 29 10 31/2 23% 14% 16 x 16 0.064 0.064 13 ' (559) (737) (254) (89) (591) (362) i (406 x 406) . (1.6) (1.6) (6) GRSI/GRSRy S� '48 16 26 29 11 4% 27% 16% ! 16 x 16 0.064 0.064 16 (660) (737) (279) (108) (692) (413) (406 x 406) (1.6) (1.6) (7) B 18 30 35Yz 9/a 1'/a 31% 20% 18 x 18 0.064 0.064 19AIIIMMINIMMIIR C (762) (902) (248) (44) (794) (514) . (457 x 457) (1.6) 0(/-6) (9) AL 1 20 30 35% 11% 3% 31% 20% 18 x 18 0.064 0.064 24 + (762) (902) (286) * (95) (794) (514) , (457 x 457) (1.6) (1.6) (11) D 24 34 38% 11 4 35% 24% 24 x 24 0.064 0.064 29 —� f 13/4(44) (864) (972) (279) (102) (895) (622) (610 x 610) (1.6) (1.6) (13) _._. F 30 40 48 18% 5'/,s 30Yz 30 x 30 0.064 0.)64 35 A (1016) (1219) (476) (138) i (775) (762 x 762) (1.6) (1.6) (16) i46 56% 21% 6 , 36% 36 x 36 0.064 0.080 45 36 GRSF-Sizes 8-24 (1168) (1441) (540) (152) j (927) (914 x 914) (1.6) (2.0) (20) with Optional Flashing Flange I 42 52 63%4 24% 6%4 _ 42'hz 42 x 42 0.064 0.080 60 (1321) (1607) (616) (159) (1089) (1067 x 1067) (1.6) (2.0) (27) B 48 ._' 58 72 26'/ 6Yz 48% 48 x 48 0.064 ` 0.080 80 (1473) (1829) (667) , (165) (1232) (1219 x 1219) (1.6) (2.0) (36) C All dimensions in inches(millimeters)and the weight in pounds(kilograms).NOTE:Sizes GRS-8 through 24 have a Dl one-piece cover and shroud.Access is gained through the removal of screws.Sizes GRS-30 through 48 have a L F I } removable cover,separate from the shroud,to facilitate maintenance and servicing of dampers. E {I 14 Spun Aluminum -'r,,,,,,,046400:,,,,,,,.,..-.. ,. Model GRSUGRSR '' ,, K , Y i r'�' All'�ki i Sri$ $'"t ��� �. Performance Performance data for these units was obtained through actual testing. The information is presented in capacity versus total pressure drop through the GRS.Total pressure drop includes the static and velocity pressure drops.To find the static drop alone, use the following equations. Throat Velocity= Throat oat Area r Total [Velocity] Velocity r 2 Throat Velocity Static Pressure = I Pressure, [ yPressure] P(in wg)re =* L 4008.6 *1 inch wg=249 Pa The data is presented for both discharge and intake units.The intake velocity of the intake unit should not exceed 600 feet per minute.Above this velocity, airborne particles may be carried into the building.The table below displays the maximum recommended values for the respective intake units. In areas where snow depths may be a problem, 12 inch (305 mm)or higher curbs are recommended. Volume(CFM) Recommended Maximum Intake Ca•acities Throat GRSI Total Pressure Drop(in.wg) Area Intake Area(ft2) Max.CFM Intake Size (ft2) ' 0.04 0.06 0.08 0.10 0.15 0.20 0.25 0.30 0.35 i 8 0.37 178 218 252 282 345 398 445 488 527 1.30 780 10 0.57 279 342 395 442 541 624 698 " 765 826 1.72 1032 o 12 0.82 400 490 566 633 775 895 1001 1097 1184 2.52 1512 (/) = 15 1.12 553 677 782 874 1071 1237 1383 1515 .0,1,ts i 2.57 1542 CC E 16 1.45 742 908 1049 1173 1436 1658 s) 2031 2194 3.02 1812 O 18 1.83 901 1104 1274 1425 1745 2015 2253 t 2468 2665 3.42 2052 _3 d W 20 2.25 1096 1343 1550 1733 2123 2452 2741 3002 3243 4.43 2658 CL m 24 3.24 1542 1888 2180 2438 , 2983 3447 3854 4222 4560 4.95 2970 O ,�., --- _,. ", 5 30 5.03 2013 2465 2847 3183 3898 4501 5032 5512 5954 7.49 4496 _ 36 7.29 2921 3577 4130 4618 5656 6531 7301 7998 8639 10.2 6111 6 42 9.77 3911 4791 5532 6185 i 74 8746 9779 ' 10712 11570 12.0 7159 48 12.8 5139 6294 7268 8126 1 9952 11491 128491 14074 15201 15.5 9286 GRSR Throat Total Pressure Drop(in.wg) Area Size (ft2) 0.04 0.06 0.08 0.10 0.15 0.20 0.25 0.30 0.35 Table is based on 600 k/m "' .---{ --- - -- -- -- - - -- maximum intake velocity.Above 8 0.37 231 282 326 365 446 516 576 631 682 these values(numbers in gray), provisions should be made to 10 0.57 331 406 468 524 641 741 828 907 980 contain incoming moisture. I{ d1,---^ 12 0.82 468 573 662 740 907 1047 1171 1282 1385 ( (1 15 1.12 663 811 937 1048 1283 1481 1656 1814 1960 C EI 16 1.45 870 1065 1230 1375 1685 1945 2175 2382 2573 0 , O 18 1.83 1060 1298 1499 1676 2052 2370 2649 2902 3135 1 d' 20 2.25 1284 1572 1815 2029 2486 2870 3209 3515 3797 , "0 •4••• 3.24 1879 2301 2657 2971 3638 4201 4697 5145 5558 Off°' 30 5.03 2281 2794 3226 3607 4418 1 5101 5703 r 6247 6748 re 36 7.29 13279 4016 i 4637 5184 6349 7331 j 8197 8979 9699 42 9.77 1 4672 15722 f 6607 7387 r 9047 10447 111680 12795 13820 48 12.8 6211 1 7607 i 8783 9820 12027 13888 15527 117009 18372 15