• TRANS' Submittal ` `' � ' `S-. Prepared For: Date:February 7, 2019 RECEIVED HVAC Inc. Andy Vail MAY 9 2019 Job Name: OFFICE COPV Frontier Split J81J13172 CITY OF TIGARD BUILDING DIVISION Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Commercial Self-Contained Air Conditioning Unit(W/Controls) 1 Air-Cooled Condenser Units (Commercial) The attached information describes the equipment we propose to furnish for this project,and is submitted for your approval. Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed Chris Smith between submittal generation and equipment release,the product Trane performance and submittal data will need to be verified. It is the 7257 SW Kable Lane customer's responsibility to obtain such verification. Portland, OR 97224-7181 Phone: (503)431-2561 Email: chrisp.smith(a7trane.com J:IJOBSI124175369121Submittal Rev 0.doc Table Of Contents Product Summary 1 Commercial Self-Contained Air Conditioning Unit(W/Controls)(Item Al) Tag Data 3 Product Data 3 Performance Data 4 Mechanical Specifications 5 Unit Dimensions 9 Fan Curve 12 Weight, Clearance&Rigging Diagram 13 Accessory 14 Field Wiring 16 Air-Cooled Condenser Units(Commercial)(Item B1) Tag Data 20 Product Data 20 Mechanical Specifications 21 Unit Dimensions 22 Weight, Clearance&Rigging Diagram 23 Field Wiring 24 Field Installed Options -Part/Order Number Summary Commercial Self-Contained Air Conditioning Unit(W/Controls) 25 Air-Cooled Condenser Units(Commercial) 25 Frontier Split J81J13172 February 7,2019 Tag Data -Commercial Self-Contained Air Conditioning Unit(W/Controls) (Qty: 1) Item Tag(s) Qty Description Model Number Al SCXG-1 1 Commercial Self Contained -Modular Ser SCRGU3243 Product Data-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 Self-Contained Air Conditioning Unit Commercial application Air-cooled (Remote condenser required) Standard Capacity 32 tons nominal 460 volt/60 hertz/3 phase VFD/Inverter w/bypass&supply air temp control (Fld) Vertical discharge 15 hp(1350 rpm) Premium efficiency open drip proof motor Spring isolators(Fld) Standard Fan Unit terminal block Galvanized drain pan w/positive slope Ventilation for 2 position control (interface only) Dirty filter switch UL Agency Listed-US/CAN 2"construction throwaway filters with 2"filter rack Plenum high static switch (Fld) Startup Included-Trane Service must start equipment for warranty to be honored FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 3 of 25 — — Frontier Split J81J13172 February 7,2019 Performance Data-Commercial Self-Contained Air Conditioning Unit(W/Controls) Tags SCXG-1 Design airflow(cfm) 13000 Elevation (ft) 0.00 Duct SP (in H2O) 1.250 TESP (in H2O) 1.460 Actual motor power(hp) 13.015 Cooling EDB(F) 80.00 Cooling EWB(F) 67.00 Cooling LDB (F) 56.96 Cooling LWB (F) 56.72 Total cooling capacity(MBh) 421.69 Sensible capacity(MBh) 332.83 Fluid type Water Ambient temp (F) 95.00 Heating EAT(F) 60.00 Min circuit ampacity 1 (A) 78.68 Max fuse size 1 (A) 100.00 Discharge arrangement Front/Top disch, Strght duct EER @ AHRI (EER) 10.2 IEER @ AHRI (EER) 13.4 Total kW(kW) 46.23 Approx Installed Weight(Ib) 2448.0 Baseunit weight(Ib) 2448.0 Unit shipping weight piece 1 (Ib) 2598.0 Remote Mounted VFD(Ib) 85.0 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 4 of 25 Others Frontier Split J81J13172 February 7,2019 Mechanical Specifications -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 Cabinet Construction The unit framework shall be formed structural steel members of 14-gauge galvanized steel. Exterior panels shall be fabricated from 18-gauge galvanized steel.The fan and compressor sections shall be insulated with 3/4-inch(19 mm)of 1.75 lb./cu. Ft(28 kg/cu. Ft) density fiberglass insulation. The unit shall be provided with removable panels to allow service access to compressors, condensers, fan motor, fan bearings, coils and valves. Removable panels shall be secured with quick-acting fasteners. The refrigerant sight glasses shall be accessible during operation. The control panel door shall have lift-off hinges. The filter section shall be removable and shipped attached to the inlet of the unit. The filter section shall accommodate 2 inch filters and shall be field convertible to accommodate 4 inch filters. The unit cabinet and any insulated ship-separate modules for indoor installation shall be wrapped on top and 4 sides with a recyclable, transparent, seven-mil-thick, low-density polyethylene heat-shrink film. The film shall have adequate transparency for unit nameplates and labels to be readable through the film. Cabinet corners shall have protective padding in place to prevent damage to the film. All seams and edges in the film shall be heat welded and adequately taped to minimize unit exposure to rain, snow, ice and road grime during shipping. Unit Finish (Slate Grey Paint) The unit exterior is painted with a one mil coat of alkyd acrylic slate grey paint. Unit Construction (Vertical Discharge) The unit is shipped with a vertical discharge fan section that can be separated from the compressor section in the field. Compressors Units shall have multiple compressors with independent circuits for water-cooled units and manifolded for air-cooled units. Compressors shall be manufactured by the unit manufacturer. Scroll compressors shall be heavy duty suction cooled type with suction screen, centrifugal oil pump with dirt separator,oil charging valve and oil sight glass. Protective devices for low pressure, high pressure and motor temperature shall be provided. The compressors shall be mounted on rubber-in-shear isolators for vibration isolation. Evaporator The evaporator coil is constructed of 1/2-inch (13 mm)OD internally enhanced copper tubes expanded into aluminum Delta-Flo(TM)fins. The coil has a staggered tube arrangement with intertwined circuiting and no more than 12 fins per inch. Drain Pan (Galvanized Steel) The drain pan shall be positively sloped in all directions to ensure proper condensate removal. The drain pan shall be fabricated of galvanized steel and insulated with 3/4-inch (19 mm)of 1-lb. (0.5 kg)density fiberglass. Drain piping, including a trap with cleanout, shall be provided with a single-point connection to the unit's exterior. Refrigeration Circuits Two refrigerant circuits shall be piped to the exterior of the unit.The refrigerant piping includes filter driers, sight glasses, distributors, thermal expansion valves with adjustable superheat and external equalizer. Unit shall be provided with adequate means of frost control. The circuits shall be factory tested, dehydrated and then charged with dry nitrogen. Circuits to be field charged with oil and refrigerant. Supply Fan Supply fan shall be dual, forward curved medium pressure fans secured to a solid steel shaft with grease lubricated bearings designed for 200,000 hours. Both fan bearings shall have greaselines extended to a common location. The drive components shall include fixed pitch sheaves and multiple V-belt sized for 130 percent of nominal motor horsepower.The supply fan motor shall have a service factor of 1.15. The supply fan motor shall be Premium efficiency open drip-proof. Supply fan motor shall have a standard T-frame.All drive components shall be accessible without using scaffolds or ladders. The entire fan assembly including drive components shall be mounted on a common base. The fan base shall be isolated inside the unit. The entire assembly shall be statically and dynamically balanced at the factory. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 5 of 25 Others Frontier Split J81J13172 February 7,2019 Isolation The fan base and compressors are mounted on rubber-in-shear isolators for vibration isolation. The entire assembly is statically and dynamically balanced at the factory. Unit Isolation (Spring Isolators) Spring-flex vibration isolators are provided for field installation under the unit base. Unit Controls(Intellipak) Microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to control CV or VAV applications. The controls shall be factory-installed and mounted in the main control panel.All factory-installed controls shall be fully commissioned(run tested)at the factory.The unit shall have a human interface panel with 16-key keypad, a two line, 40 character clear language(English, French, Spanish) display as standard to provide the operator with full adjustment and display of control data functions. The unit controls shall be used as a stand-alone controller or as part of a building management system involving multiple units. The unit shall be equipped with a complete microprocessor control system.This system shall consist of temperature and pressure(thermistor and static pressure transducer) sensors, printed circuit boards (modules)and a unit mounted human interface panel. Modules(boards)shall be individually replaceable for service ease.All microprocessors, boards and sensors shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not dependent on communications with an on-site PC or building management network. The microprocessors shall be equipped with on-board diagnostics, indicating that all hardware, software and interconnecting wiring are in proper operating condition. The modules(boards)shall be protected to prevent RFI and voltage transients from affecting the board's circuits.All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring no battery or capacitive backup, while maintaining all data. Zone sensors shall be available in several combinations with selectable features depending on sensor. The human interface panel's keypad display character format shall be 40 characters x two lines.The character font shall be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display(LCD)with blue characters on a gray/green background that provides high visibility and interface ease. The display format shall be in clear language (English, French, Spanish). The keypad shall be equipped with 16 individual touch sensitive membrane key switches. The switches shall be divided into four separate sections and password-protected to prevent tampering by unauthorized personnel. The six main menus shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION, and SERVICE MODE. VAV Control with VFD When a Variable Frequency Drive(VFD) option is desired, the unit will come with a field mounted, functionally tested, adjustable frequency drive which will safely vary the speed of the fan motor while allowing the motor to meet the dynamic requirements at the shaft of the motor and meet the system static. The VFD will be matched to the fan motor according to the FLA rating of the motor. The VFD will convert input line voltage to an adjustable frequency and voltage. A rectifier stage will convert fixed voltage, fixed frequency, AC line power to fixed DC voltage. The input power section shall utilize a full wave bridge design incorporating diode rectifiers. The rectifier shall be insensitive to phase rotation of the AC line. The DC voltage will be filtered. The VFD will change fixed DC voltage to variable frequency AC. The VFD section will utilize insulated gate bipolar transistors(IGBTs). Environmental: The VFD will be housed in an IP20 or IP21 enclosure and be designed to operate in an ambient temperature range of -10 to 45 degrees C minimum (14 to 104 F). The maximum relative humidity shall not exceed 95%at 40 C, non-condensing. The VFD is rated to operate at altitudes less than or equal to 3,300 ft. For altitudes above this,consult Trane for proper drive selection. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 6 of 25 Others Frontier Split J81J13172 February 7,2019 Ratings: The VFD is designed to operate within the unit's voltage utilization range,which is+/-10%. The output carrier frequency of the drive no less than 8 kHz, and will be randomly modulated for low noise operation. The output frequency will be adjusted by the unit controller from 22 -60 Hz to meet duct static requirements. Protection: The VFD will meet UL requirements for motor over-current protection and UL 508C for controller containing power switching devices. The VFD will also provide internal protection from over-current, overheat and transient situations. External over-current protection will be provided by properly sized fuses placed on the line side of the VFD. Controls: The run command signal to the VFD will be provided by the unit controller. To maintain duct static pressure, the unit controller will also output a 0- 10 volt dc signal which will be the speed reference input for the VFD. Faults: Alarms resulting from loss of airflow will cause latching diagnostics on the unit controller. When latching diagnostics occur, the unit controller will require a manual reset. VFD Keypad Display: The VFD will have a five digit display which provides readout functions that include: output frequency, output voltage and output current. Harmonic Analysis (WARNING): The Trane Company does not assume responsibility for system harmonic performance. Harmonic performance anomalies can be a direct resultant of distribution system characteristics, not unit performance. A harmonic analysis can be performed, by the VFD manufacturer or qualified professional, based upon system documentation consisting of but not limited to one-line diagrams and specific distribution transformer information consisting of X/R, %Z, and KVA data. The data shall consist of but not be limited to total harmonic voltage distortion and total RMS current. The amount of harmonic distortion at the point of common coupling (PCC) is due to the distribution system characteristics(impedance of the source),the power source size relative to the AC drive load and other power switching devices such as computers,fax machines, copy machines,etc. The harmonic current magnitude and voltage distortion values can be estimated through computer modeling. If the resulting calculations determine that the harmonic distortion will be above the IEEE-519 specifications of 5%, isolation transformers or line reactors can be purchased from others to lower the harmonic levels. Variable Frequency Drive with Bypass When the VFD with Bypass option is desired, a VFD and Bypass control enclosure will be supplied with the unit for field installation. The VFD and bypass will ship, from the factory, completely wired and functionally tested. Properly sized motor protection shall be provided in both Drive and Bypass modes by a motor overload relay and fuses. Manual selection between Drive and Bypass modes is to be made by the operator at the unit Human Interface(HI). Full unit control and protection is provided in both the Drive and Bypass modes,with the exception of air-flow modulation for duct static control. When placed in the Bypass mode, the'VAV Box Drive Max"relay will be energized. This point can be used to sequence the VAV boxes top open in preparation for an across the line fan motor start. The Run Command signal,to the bypass motor starter,will be provided by the unit controller. While operating in bypass mode,temperature control will reference a user defined zone sensor and setpoint. High duct static protection must be active in Drive and Bypass modes of operation. Filters(Construction Throwaway) Two-inch (51 mm)construction throwaway filters are installed in the unit filter section. Filters may be removed from the left side of the unit. Unit Connection (Terminal Block) A terminal block is provided to bring power to the unit. Unit Interrupt Rating (Standard Short Circuit Current Rating-SCCR) Ventilation Control for Standard 2-Position Dampers(Interface Only) The unit will be provided with a 0-10 VDC control output suitable for controlling a field provided modulating actuator. In occupied modes of operation the output will be driven to maximum position. When the system is unoccupied,the output will be driven to minimum position. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 7 of 25 Others Frontier Split J81J13172 February 7,2019 Dirty Filter Sensor A factory installed pressure switch is provided to sense the pressure differential across the filters. The switch is adjustable between 0.1"and 5.0"an is factory set at 0.9" (23mm)W.G. When the differential pressure exceeds the setpoint, contact closure will occur.A field installed indicator device is wired to the relay terminals to indicate when filter service is required. Contacts are rated for 115 VAC which are powered by a field provided transformer. Plenum High Static Switch A factory supplied sensor used to provide additional protection from over-pressurization of ductwork. This sensor should be located downstream from the discharge of the unit in the supply duct. This is a field installed accessory. Agency Listing: UL The unit shall be US/Canada Underwriter's Laboratory labeled and approved. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 8 of 25 Others Frontier Split J81J13172 February 7,2019 Unit Dimensions-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 (2)7/8"HOLES.(115V CUSTOMER CONN) 1 1/8"HOLES(115V CUSTOMER CONN) 1 1/8"HOLES(115V ELECTRIC HEAT CONN) HIGH VOLTAGE CUSTOMER CONN O A 4j ^ II 123/4" II 8 1/2" 10 5/8" / 6 a o- 12" LEFT VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 9 of 25 Others Frontier Split J81J13172 February 7,2019 Unit Dimensions-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 13 1/4" \11 1/2" 14 5/8" 56 1/2" S 14 5/8" 18" 57" ELECTRICAL CONNECTIONS 351/2" 110 0 0 861/2" FILTER DOOR FRONT VIEW BACK ISO VIEW VERTICAL DISCHARGE 5313/16" 731/2" 1 2X 5/8"OD PIPING CONNECTIONS -_ 3/4"(4X)ISOLATOR MOUNTING LOCATION 30 7/8" �ON BOTTOM OF UNIT OD PIPING G CONNECTIONS 36 15/16" 2 1/8" — 641/2" 35.. 613/4" TOP VIEW RIGHT VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 25 Others Frontier Split J81J13172 February 7,2019 Unit Dimensions-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 RIGHT SIDE VIEW AIR COOLED PIPING CIRCUIT 2 2X 7/8"OD /DISCHARGE LINES CIRCUIT 1 2X 5/8"OD /LIQUID LINES /1 1/2"NPTI DRAIN 7 3/4 0 6 a 4 1/8" 4 1/4" a b b 4 1/2" a-9 1/4" 1-12 3/4" ' FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 25 otners Frontier Split J81J13172 February 7,2019 Fan Curve-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 SCRG32CV —.6.5 — _ 38%.1l10 UnitS¢e:32 Ions O36 50%WO N 6.0 17Operating Airflow:13000.00 cfm Operating Static Pressure:1.46 in H2O _ _ 6)%WO Operating RPM:1350.00 — \ 5.5 / Operating Brake Power:13.02 hp _ / �� Altitude:0.00 ft — 1900_RP\ki ` ,\ Design Temp:80.00 F 5.0 — 7 %W o a) — Date:217119 ._ — 180B RPM 0,7,, s, 4.5 - - , A �, u' 1700 Rpt 4.0 _ 8(YaWO 1 _ 60U RcM _,A v , —_ 1500 RPM �.. �. 1.7 — .. 140)RP1; : \ � " 2cr) .5 ca 2.0 2 RPM \__. —i 00 RPM o — — __ �,,, � �N y� 1.5 _0 0 RPMs • goon ��. 0.5 1 _ � v� ov �� �'v .� 0.0 - -4_�- i I I I I �I I i tv • �H i vti 1 1'i yea" i . "i 'y. I (`, I I i i 0 2500 5000 7500 10000 12500 15000 17500 20000 22500 Airflow (cfm) FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 12 of 25 Others Frontier Split J81J13172 February 7,2019 Weight,Clearance& Rigging Diagram -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 SPREADER BAR FILTER RACK CLEARANCE SPREADER BAR 1111. 1111.1 SLING STRAP FRONT OF BASE UNIT 4\1\ q2" L- J 77" 36" 111. 114111411411111* CLEARANCE SLING STRAP RIGGING NOTES: APPROX INSTALLED WEIGHT: 2448.0 lb 1.IF ANY ACCESSORIES SHIP SEPARATE FROM UNIT,ADD 150.0 lb. 2.A CLEARANCE OF 77"IS REQUIRED ON LEFT HAND SIDE OF UNIT(WHEN FACING FRONT OF UNIT) BASE UNIT WEIGHT 2448.0 lb IF SHAFT IS REMOVED. UNIT SHIPPING WEIGHT#1 2598.01b UNIT SHIPPING WEIGHT#2 N/A• AIRSIDE ECONOMIZER N/A• VFD 85.0 lb HEATING N/A' PLENUM N/A• WATERSIDE ECONOMIZER N/A' FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 25 Others Frontier Split J81J13172 February 7,2019 Accessory -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 1 ' 5 7/8" FRONT VIEW NOTE: 1. HEIGHT OF ISOLATOR IS ±.375" (10mm). FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 14 of 25 Others Frontier Split J81J13172 February 7,2019 • Accessory-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 NOTE 1)VFD/BYPASS ENCLOSURES ARE FIELD INSTALLED. 2)THE APPROXIMATE WEIGHT OF THE VFD/BYPASS ENCLOSURE IS 85.0 lb 3)PROVIDE AT LEAST 4"OF MOUNTING CLEARANCE ON THE TOP&BOTTOM OF THE ENCLOSURE. 4)CONDUIT HOLES ARE FIELD CUT AS NEEDED. 5)BRANCH CIRCUIT PROTECTION&MOTOR WRING MUST BE SELECTED IN ACCORDANCE WITH NEC,ANY APPLICABLE LOCAL CODES& WIRE SIZE THE DRIVE CURRENT RATING INPUT WRING MUST BE 75 DEG C COPPER WITH MINIMUM SIZE,ACCORDING TO THE FOLLOWING TABLE (REFER TO MOTOR FLA FOR SIZING DRIVE OUTPUT WIRING): 10 AWG 19 1/16" 11/16" - 8 7/8" (f• 8 7/8" 12 5/8" { a 3X 03/8" ® MOUNTING HOLES .m..Fm ElCXDOCI El :D 0 I 6BEI O 21 1/2" I il I _ _ 1- IL 11/16' 3X03/8" MOUNTING HOLES FRONT VIEW RIGHT VIEW ACCEPTABLE CONDUIT ENTRYAREA - - I I °oOOk,, 11 Y' BOTTOM VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 15 of 25 Owers — — — I. Frontier Split J81J13172 February 7,2019 Field Wiring -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 1TB8(24 VDC) -- ® ® ® el el 41!) (111 411)-- 1 2 3 4 5 6 7 8 9 10 �I __ SAI W31o0elsoeoo (0 NEC CLASS 2 11 12 13 14 15 16 17 18 19 20 WIRING 4111 4111 4111 4110 ® ® ®® 4111 4111 21 22 23 24 25 26 27 28 29 30 1TB8 4111 4111 1111 ® 42 0111 4111 ® 4111 24 VDC = 17611 DODUUUOOUC 31 32 33 34 35 36 37 38 39 40 D00000000C 24 VAC 000000000 117662 4111 4111 3 4 5 6 7 8 9 10 11 12 13 14 ® ® � 42 (111 1111 1111 ® 00000000c 41 42 43 44 45 46 47 48 49 50 yJ0uu00000c �000000000C 127 128 129 130 131 132 AI ® ® el 0 ® ell LL ell 49 ell 1TB10 51 52 53 54 55 56 57 58 59 60 24 VDC 1TB9 1TB7 �p = 343 341 64 102 258 65 63 104 103 292 291 17611(24 VAC) 24 VAC y�00000000c 0 ® 0 0 0 0 0 0 0 0100000000c 00000000c _ _14 13 12 11 10 9 8 7 6 5 4 3 2 1 40 259260 1050 I 000000000 1 2 3 4 5 6 7 8 9 10 00000000C NEC CLASS 1 0 107 0 266 0 268 0 0 0 0 WIRING 11 12 13 14 15 16 17 18 19 20 LEFT HAND SIDE OF I UPPER CONTROL BOX `Nl -- 1TB10(24 VDC) I' I -1 j 0000 ® 4D ® ® ® 411:4 1TB6 115 VAC 1 2 3 4 5 6 7 8 9 10 ` 0000000000 1789 1 1 1 '1 115 VAC 11 12 13 14 15 16 17 18 19 20 ® ® 4111 ® (Ill ® Ill) ® el)el I I 21 22 23 24 25 26 27 28 29 30 EQUIPMENT GROUNDS 0000000000 31 32 33 34 35 36 37 38 39 40 � ,=, =,I 1TB7(24 VAC) LEFT SIDE OF UNIT LOWER 0000000 0111 0 0 CUSTOMER ONTROLCONNECTIONS IOX 8 WARNING 113 CUSTOMER CONNECTIONS HAZARDOUS VOLTAGE! 1 2 3 4 5 6 7 8 9 10 DISCONNECT GR MOTELL DIRK ISCON POWER ECTS 114 ® 116 ® 116 INCLUDING REMOTE AND FOLLOW LOCK OUT AND TAG PROCEDURES BEFORE SERVICING.INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED 11 12 13 14 15 16 17 18 19 20 STORED VOLTAGE.UNITS WITH VARIABLE SPEEDDRIVE.FORRTODRNE NOTICE `0 0 '0 0 42 52 0 0 0 0 INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO W THE ABOVE BEFORE USE COPPER CONDUCTORS ONUS SERVICING COULD RESULT IN DEATH ORTo M. 21 22 23 24 25 26 27 28 29 30 v..TERmiNALs APF Nor PFNGNE0 SERIOUS INJURY OTHER TYPES Or CONDUCTORS Acc ®AVERTISSEMENT EGLIPM TO DOTHEE ABOVE COULD RESULT IN TENSION DANGEREUSE! AVIS SIDNS PT oONVRER LES SEECTIO NTU IRS AOSTANCE, NvTILISER RULE DES CONDUCEVRV to COIVHtI - "CUSTOMERSUEWLIED CONTROL RATINGS PUTS SUNRE LES PROCEDURES DE LES SCENES DE uuNITE NE SONT PAs CONCUSS OUILLAGE ET CES ETIOUETTES AVANT POUR TOUTS INTERVENTION.VERIFIER OUETOUS FAIRE TTYPES URs .A IA PBocAoARECIOEssus PEAT LES CONDENSATFURS DES MOTEURN SORT OUTPUT CONTACT RATING AVAILABLE DECHARGES.DANS LE CAS DMS S ENrRAIrvER D.ROMNa ESALfanPEM T / A COMPORTANTDESENTRAINEMENTSA GAVISOEN <\ 1 AMP AT 115 VAC. VITESSNMARAS..SE REPORTER AUX IUTILICE UNICAMENTE CONDUCTOR.DE COME / LwTRAiNEMEN POUR PARA ACEPTAR OTROS n LAS.TERMINALES DE LA Esrary usEanws \ B K.DE CONDUCTORES. I INPUT CONTACT RATING AVAILABLE ORCHARGER LES NE PAs RESPECTER CES MESUREs DENO SEGUIR RIOREs PUEDE 12 MA AT 24 VDC. PRECAUTION PREAVEs TRAINEPOUVAiTNOES PROVOCAR wags EN ELL EOUIPo.rvT / C I OUTPUT CONTACT RATING AVAILABLE MORTELLESG \ 2AMPS AT 24 VAC. A,ADVERTENCIA iVOLTAJE PELIGROSO! DE`USE,LA DESCOTODA A ENEROXIONES ELECTRICA, LINE VOLTAGE CUSTOMER CONNECTION LUG SIZE NCL USO LAODESIMIENT SIDE REMOTA`Y SIGHLOS DO ANTES PROCECIERREr EAOUEUDA ANTES OE P EOUE ER AL TODD S LOS CAPACITOR. EL MOTOR T000s SUPPLY FAN CUSTOMER CUSTOMER EQUIPMENT Los CAEN ER ES DELMOTOR CE UNIT UNIT MOTOR TERM BLOCK DISC SWITCH GROUND DESCARGADOEL AEESCOJEALMACENPDO. TONNAGE SIZE VOLTAGE PARA LAS UNIDADES CON EJE DE HORSEPOWER WIRE RANGE WIRE RANGE WIRE RANGE DIRECCION DE VELOCIDAD VARIABLE, CONSULTS LAS INSTRUCCIONES PARA LA DESCARGA DEL CONDENSADOR. EL NO REALI]ARLOANTERORMFNTE 32 TON SCRG/SIRG 460 15 14-2/0 14-1/0 14-2 INDICADO.KEPI..OCAS..LA MUERTE O SERIAS LESIONES PERSONALES. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 16 of 25 Others Frontier Split J81J13172 February 7,2019 • Field Wiring -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 SEE UNIT NAMEPLATE ----- 1 FOR LINE VOLTAGE OPTIONAL -161 ---�- TO 1TB8(24 VDC) L7 L2 L3 ZONE RESET I TEMPERATURE t° SENSOR I - TO 1TB11(24 VAC) I 6 + O-162 --- r"-'---'--'--'-- 'I r TO 1769 I 351B 353B 2898 5S22 OPTIONAL -163 - 3526 288B 2908 I it I' I( I OUTDOOR t I • I I TEMPERATURE I 17B11TB15 L SENSOR_ -- _- - O-164 --- TO FROM_-__-_--_- ___ INVERTER INVERTER 1 . _ _ MTh 7 5U27 OPTIONAL -165 --- LOCATED INSIDE THE CONTROL PANEL - �$}I J,I Lt L2 L3 OUTDOOR �II�v�,H I�`� ON THE RIGHT SIDE WALL. EQUIPMENT-'"1" HUMIDITY I - --- GROUND ///777777 I_ SENSORO 166 ✓ i I I I EXHAUST _ -0 I 196 __a AIRFLOW PROVING rI II 17, < B I iJ--197 ---I ✓ i I° I° I ° I EM SRGENCY i -261 --- CIR1TB1 < 1 CUIT 1TOP 17 INPUT I I (SINGLE POINT POWER CONNECTIONS) <-4-1 g I j -262 --- NOTES: r 1 1. ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY i THE CUSTOMER IN ACCORDANCE WITH THE LOCAL AND NATIONAL ELECTRICAL CODES. EXTERNAL rH k--191 --- < 2 I IF THE ELECTRIC HEAT OPTION IS DESIRED,REMOVE THE SUPPLY AIR TEMPERATURE SEN- AUTO/STOP i I i SOR FROM THE FAN HOUSING AND RE-INSTALL DOWNSTREAM OF THE ELECTRIC HEATER. INPUT I I � \�I / g I I i CTI I UNOCCUPIED INPUT IS USED WITH FIELD INSTALLED TIME CLOCK. OPTIONAL FACTORY I \ i j0-_t92 ___ INSTALLED TIME CLOCK OR PROGRAMMABLE NIGHT SETBACK REQUIRES NO FIELD WIRING. UNIT WILL BE UNOCCUPIED WHEN CONTACT IS CLOSED. ra r-I 1-4,--192 --- cTi IFEEMERGENCY STOP INPUT IS DESIRED,REMOVE JUMPER W12 FROM 1TB8-25 AND UNIT 1 1 SCHEDULING I I < 5 I WHEN CUSTOMER SUPPLIED EXTERNAL AUTO STOP IS USED,REMOVE WIRE JUMPER MARKED INPUT i I W14 LOCATED ON TERMINAL BLOCK 1788 BETWEEN TERMINALS 22&23. L (OCC./UNOCC.) 1 j}--193 --- r i 1 CHANGE- i- 1--10--198 --- OVER 1 1 INPUT I I 7. ALL THREE PHASE MOTORS SUPPLIED WITH THE UNIT ARE PROTECTED UNDER PRIMARY �_ j0-- 199 < 8 I TO INSTALL SE FAILURE CONDITIONS.L THE SUPPLY HIGH DUCT TEMP.T'STAT,REMOVE JUMPER WIRE W13 AND OPTIONAL INSTALL THE DEVICE ON 1768-27 AND 1788-28. SUPPLY • -263 --- < 9 I TO INSTALL A FACTORY PROVIDED AIR-SIDE ECONOMIZER,CONNECT THE TWO ENDS OF HIGH DUCT TEMPERATURE I 5J3. IF THE AIRSIDE ECONOMIZER ACTUATOR IS FIELD PROVIDED,WIRE THE 0-10 VDC T'STAT/� CONTROL SIGNAL TO 1TB8-33 AND 1788-34.THE 24 VAC POWER CONNECTION SHOULD Cl < ") • -264 ---) BE MADE TO 1767-1. r 11 FAN RUN NO k--259 ----a REQUEST OUTPUT I <11 I FIELD INSTALLED FOR SCRG&SIRG UNITS MATCHED WITH CCRC OR CIRC. SEE THE ' <13 II CONNECTIONS ILLUSTRATED IN THE CXRC IOM. COM -260 ----a OPTIONAL 5U23 REMOTE ZONE TEMP.SENSOR IS USED FOR REMOTE ZONE SENSING.THE ✓ 1 ZONE SENSOR MAY BE ORDERED 3 DIFFERENT WAYS:1)TEMP.THERMISTOR ONLY 2) ALARM NO I-268 -----1 TEMP.THERMISTOR W/OVERRIDE AND CANCEL BUTTONS 3)TEMP.THERMISTOR W/OVER- I _ RIDE,CANCEL BUTTONS,AND VARIABLE COOLING SETPOINT POTENTIONMETER. SEE IOM I OUTPUTS NC b--269 _ --A FOR DETAILS. <14 I 13 COM;--270 ---� IF R TB9-7MISSION INPUT IS DESIRED,REMOVE JUMPER W11 FROM TERMINALS 1789-6 LAND ✓ 14 ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC. I3--291 EXHAUST FAN OUTPUT L <-q _292 -I ✓ 1 RUN rH Ik-- 65 -' 17 DISCONNECT SWITCH,1S1,IS OPTIONAL WITH SINGLE POINT POWER,NOT WITH DUAL POINT PERMISSION I I ) POWER CONNECTIONS. 17613(CIRCUIT 2)IS FOR DUAL POINT POWER CONNECTIONS. INPUTBYPASS UTPUTS ARE L 13 �i _ 258----J 18 BETTER UUNDERSTANDING OF CONTLROLOCIRCUIT,SEE R UNITS WITH ICHEMAT C SHEET 2NVERTER WITH POF 5.FOR FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 17 of 25 Others Frontier Split J81J13172 February 7,2019 Field Wiring -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 1TB8(24 VDC) I REMOTE - - - - - 1TB11(24 VAC) ASE �/�/�/`�167 1 T67(24 VAC) POSITION I IPOTENIOMETER ID-168 y I 1TB6(115 VAC) �/t'V 189 I 265 -01 NO VAV BOX I (_- - 1TB10(24 VDC) SUPPLY -Vit q' AIR I I OU266 NC DRIVE MAX. �I TEMPERATURE I VAVV))S SENSOR 0 190 I ZONE TEMP.1 2-- 150 - 267 H COM ( I COMMON 2 0- 151 -I I- SACSP3 0- 152 SYSTEM OFF/AUTO4 0- 153 -I HEAT7 3- 156 -J COOL 8 0- 157 -1 SYS.ON 9 3-- 158 i SERVICE 10 0- 159 5U25 GND 6 0-155 -I (OPTI NAL) ISPEED REFERENCE T81-1�0-136 I I VANEOEMOTE FOR WO/BYPASS - - - I ENCLOSURE TB1-2 ID-137 -I I - - - - TB1-3 SHIELD-I 8RT21 SATURATED I-236 • CONDENSER I t TEMP.SENSOR I CIRCUIT 1 237 - - - (OPTIONAL) HEAT 7 0--156 - I CVNAV - REMOTE COOL 8 0-157 __IBRT22 SATURATED PANEL r 238 CONDENSER W/NSB SYS.ON 9 0-158 H I I t° TEMP.SENSOR I CIRCUIT 2 5U24 SERVICE 10 0-159 -I L_23911 I I- 0 91 GND 11 0-W31-{ - _ - II_0 S2 COMM(+)12 0-160 J1 -_ I I I I 24 VAC 14...3-40.- 1. _... __... III t I _ - - RUN COMMAND TB1-6-ID-603 - I • (OPTIONAREMOTE) OUTPUT FOR I t ZONE I I VFD/BYPASS I TEMP. I ENCLOSURE TB19 254 -J I . - SENSOR I _ - 1• 150 J IBFDBYPASSYPASS PUTS FOR I b -127 621 CONDENSING UNIT ENCLOSURE -128 B2-2 • t • 12 I I T81� 601 LOUTPUTS I I tg <] TB1-5 ID-254 -129 82-3 a a ZONE A •SWN1. SENSORI -130 -01TB2-4 2• CONDENSING UNIT I .SW2 151 131 ITB2-5 FAN CONTROL C132 B26 OUTPUTS CANCEL J SU23 LD-152 a 11 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 18 of 25 Others Frontier Split J81J13172 February 7,2019 Field Wiring -Commercial Self-Contained Air Conditioning Unit(W/Controls) Item: Al Qty: 1 Tag(s): SCXG-1 r — 1TB8(24 VDC) coco 00 M E — — — - 1TB10(24 VDC) e — — — — — — — 1TB7(24 VAC) OPTIONAL I<11 I I 1 AIRSIDE — — 41 •+24V ECONOMIZER I LOW 5U9 a DAMPER AMBIENT 8U44 fir— 144 — H <2_1< ACTUATOR I CIOPTION RCUIT 1 ( >— 145 - - I F-- - 41 <11 I +24V LOW AMBIENT 8U45 (al— 146— — OPTION (_)— 147— CIRCUIT 2 A\WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS AND FOLLOW LOCH OUT AND TAG PROCEDURES BEFORE SERVICING.INSURE THAT ALL MOTOR CAPACITORS HAVE DISCHARGED STORED VOLTAGE.UNITS WITH VARIABLE SPEED DRIVE,REFER TO DRIVE INSTRUCTIONS FOR CAPACITOR DISCHARGE. FAILURE TO DO BEFORE BIKING COULDLD RESULT RESULT IN DEATH OR SERIOUS INJURY Q AVERTISSEMENT TENSION DANGEREUSEI COUPER TOEES LES TENSIONS ET W VRIR LES SECTIONNEURS A DISTANCE, PUTS SUIVRE LES PROCEDURES DE VERROUILLAGE ET DES ETIOUETTES AVANT TOUTE INTERVENTION.VERIFIER OUE TOUS LES ONDENSATEURS DES MOTEURS SONT DECHARGES.DANS LE CAS,UNITES COMPORTANT DES ENTRAINEMENTS A VITESSE VARAIBLE,SE REPORTER AUX INSTRUCTIONS DE UEERAINEMENT POUR DECHARGEE LES CGTDENSATEURS. NE PAS RESPECTER CES MESURES DE PRECAEION PEUT ENTRAINED DES BLESSURES GRAVES PIXNANT ETRE MORTELLES 8 ADVERTENCIA iVOLTAJE PELIGROSO! DESCONECTE TODA LA ENERGIA ELECTRICA, INCLUSO LAS DESCONEXIONES REMOTAS Y GA LOS PROCEDIMIENTOS DE CIERRE Y ETIOUETADO ANTES DE PROCEDER AL SERVICIO.AS ESE DE OUE TOO. LOS CAPACITORES DEL MOTOR MAYAN DESCARGADO EL VOLTAJE ALMACENADO. PARA LAS UNIDADES CON EJE OE DIRECCON DE VELOCIDAD VARIABLE, CONSULTS LAS INSTRUCCIONES PARA LA DESCARGA DEL CONDENSADOR. EL NO REALIEAR LO ANTERIORMENTE INDICA.,PODRIA OCASIONAR LA MUERTE °SEWS LESIONES PERSONALES. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 19 of 25 Others Frontier Split J81J13172 February 7,2019 Tag Data-Air-Cooled Condenser Units(Commercial)(Qty: 1) Item Tag(s) Qty Description Model Number B1 CU-32 ton 1 32 Ton Commercial Air-Cooled Condenser CCRC0324 Product Data-Air-Cooled Condenser Units(Commercial) Item: B1 Qty: 1 Tag(s): CU-32 ton Air-cooled Condenser Commercial application 32 tons nominal 460 volt/60 hertz/3 phase Spring isolators(Fld) Louvered panel coil guard UL Agency Listed-US/CAN FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 20 of 25 Others Frontier Split J81J13172 February 7,2019 • Mechanical Specifications-Air-Cooled Condenser Units(Commercial) Item: B1 Qty: 1 Tag(s): CU-32 ton Cabinet The unit framework shall be formed structural steel members of 14-gauge galvanized steel. Panels and access doors shall be 18-gauge galvanized steel. The unit exterior shall be phosphatized and finished with air-dried enamel paint. Refrigerant Circuits and Controls All sizes shall have dual refrigerant circuits and include an integral subcooling circuit for each circuit.All necessary controls to run unit fans shall be factory installed. The control panel shall include fan motor contactors, terminal block connection for compressor interlock, and 115-volt control power transformer. Condenser Coils The condenser coil arrangement shall be slab type. Coils shall be seamless 3/8-inch (10mm)OD copper tubes expanded into aluminum fins. Each circuit shall include an integral subcooler.The coil shall be leak tested at 450 psig air pressure. Condenser Fans and Motor Vertical discharge direct drive fans shall be statically and dynamically balanced at the factory. Motors shall be three-phase with permanently lubricated ball bearings, built-in current and thermal overload protection,and weathertight rain slinger over the fan's shaft. Standard Ambient Control Standard ambient control allows operation down to 45 F (-7.2 C) by cycling the condenser fans. Unit Finish (Slate Grey) The unit exterior is painted with a one mil coat of alkyd acrylic slate grey paint. Louvered Coil Guards Option The unit coils shall be covered with a factory installed decorative louvered grill type panel for protection. Unit Isolators: Spring Spring-Flex vibration isolators are encased with cast iron feet and are provided for field installation under the base of the unit. Agency Listing: UL The unit shall be US/Canada Underwriter's Laboratory labeled and approved. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal _ Page 21 of 25 Others — — — — — Frontier Split J81J13172 February 7,2019 Unit Dimensions-Air-Cooled Condenser Units(Commercial) • Item: B1 Qty: 1 Tag(s): CU-32 ton REFRIGERANT CIRCUIT 2 REFRIGERANT CIRCUIT 1 0 1 / 0 te It/ IIIIIII" 5/8"OD LIQUID LINE CONNECTION ' 7/8"OD HOT GAS LINE CONNECTION 5/8"OD LIQUID LINE CONNECTION 7/8"OD HOT GAS LINE CONNECTION 1,,, 4.0 1 III CONTROL PANEL 24 VOLT WIRE ENTRY 88" HOLE SIZED FOR 3/4 IN.CONDUIT 115 VOLT WIRE ENTRY HOLE SIZED FOR 3/41N.CONDUIT FRONT ISO VIEW SUPPLY VOLTAGE WIRE ENTRY HOLE SIZED FOR 1 IN.CONDUIT ELECTRICAL CONDUIT OPENING ii EiM T •• •., , 70 1/8" 66 7/8" 1 32 5/8" i■i 4 1/2"I I■ I" _,14_ 10 1/2" 14 3/8" 17 1/2" 181/2" - 24 3/4" - 29" - 88" NOTE 1.THE DISCHARGE HEIGHT IS 2 3/4". RIGHT SIDE VIEW FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 22 of 25 Others Frontier Split J81J13172 February 7,2019 • Weight, Clearance& Rigging Diagram -Air-Cooled Condenser Units(Commercial) Item: B1 Qty: 1 Tag(s): CU-32 ton SPREADER BAR SPREADER BAR / I' NI SLING STRAP SLING STRAP RIGGING O 98" CONTROL PANEL 00 O 96., t__ SHIPPING WEIGHT TABLE —48" - - 48" BASE UNIT SIZE SHIPPING WEIGHT 2,014.0 lb 2138.0 lb NOTE: CLEARANCE AND ANCHORING 1.FOR CLEARANCE INFORMATION ON MOUNTING OF UNIT IN A PIT OR NEAR OTHER UNITS THAT WILL (TOP VIEW) RESTRICT AIR FLOW,SEE I.O.M. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 23 of 25 Others —_-_. • Or- — — — CCRC OUTDOOR CONDENSER UNIT m �D C (3D Q INDOOR EVAP UNIT CONTROL PANEL Q, M y II INTELLIPAK 1767 W C C) Z1 CONTROLLED UNIT CONTROL PANEL C C UNIT ED———W51 —. 11©©13©1:11:113112113111® ,76, —_—W47: �1I 17826 ��1���111111 ra Ca X W , 27,2, 6 3---W48 — —\` .� CO Q. 30T 35T,40T, y Q 307,35T,407. 6?———W82 — —`� _ "� _i ♦C 50T,60T 7 0_——W53 — — V \\\ 3 3 3 3 3 3 1 c. ——W49 — T 1 1 1 1 1 1 _ V , SCRG, 9J� —W54 y CONTROL_A l L L L L l p V CCD 20T,25T,32T 1 ——W54 _Th.I GROUND �—1 L\1\_.1———— ta O N . ,-1— I —WSS —\Y EQUIPMENT 17814 r �I GROUND ©©�©�����®® co a 5 /7c1786 \I IIII 17821 11:11110101:101111 0 0 —N,:.....P•-.. 2 0———W 421 ———— 1 • Ce 0M W Q. Co, CD 4 3---W 4 4' —————\s — LI L2 L3 \-\1 3 3 5 5 5 N _, 5>-1--W45 ---- —I— I I I I I I I I I O CD6r-L —W461 ----�� I J J J CPOWER —� lllllllll M el a' —1\—'i\s L\1 7 J—t GROUND J C J I— SEE UNIT NAMEPLATE FOR LINE VOLTAGE I—II I WI: Fr LI I L3II n � 2, J II p m CUSTOMER SUPPLIED EVAP UNIT I I- J CUSTOMER I I _. r --W42 ————\A SUPPLIED FIELD , L _ I DISCONNECT I WARNING f) 3 x--CD I11 —0---———W41I — ——\ SW TCH II II IIHAZARDOUS VOLTAGE, DO .1 I REFRIGERANT I — • • • I �i CIRCUIT 1A T c L_H I Q D --W ---- L— — l �y J ——J I NEC CLASS \ WIRING eromroe.awe�re.e 3 REFRIGERANT r I ®AVERTISSEMENT CIRCUIT I6 NEC CEASING , iz, , I _L WIRING r__ �.___w _--- L - J I REFRIGERANT J ' CAUTION CIRCUIT 2A USE COPPER GONIXICTORSONLY1 OrcirrtZEt===- UlarrPRIANALS .onccen L J._ ' —— `w ,ERZ...TO.o,~eazseunes oM �"� �Y--W — ewwue... I 7 DO SO /fADVERTENCIA .11.13E12 WE DES CONDUCTEURS DI REFRIGERANT eNOLTAMPEIAGROSOI .CIRCUIT 2BLES[MINES OE CUHrFE HE soxi pas ccx,uEs I POUR RECEVOIR"ANTES T.. cow oucTEu L J/ �W eMuR PEW' PRECAUC16N. °° L .,-/c J — — — — 3.0 Lo race, a co ,.WDA,EaIPo. .WRNS« P. L... u NOTES. NOMINAL VOLTAGE it OF MOTOR MOTOR MCA MFS 1.ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE TONNAGE FANS FLA(EA.) LRA(EA.) MCBS CUSTOMER IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES.PHANTOM LINE ENCLOSURES INDICATE ALTERNATE CIRCUITRY OR AVAILABLE SALES OPTIONS. 32 460 4 1.8 9 7.7 15 FOR CANADIAN INSTALLATION(CSA)ONLY.LOCAL INSPECTION AUTHORITIES MAY REQUIRE SINGLE POWER SOURCE DISCONNECTING MEANS. LINE VOLTAGE CUSTOMER CONNECtION LUG SIZE 3.ALL THREE PHASE FAN MOTORS SUPPLIED WITH THE UNIT ARE PROTECTED UNDER PRIMARY 71 SINGLE PHASE FAILURE CONDITIONS. N Q Cu CUSTOMER TERMINAL EQUIPMENT GROUND INPUT CONTACT RATING 120 VAC/60 Hz/I PH MINIMUM 31 VA SEALED. C UNIT TONNAGE SIZE UNIT VOLTAGE(V) BLOCK WIRE RANGE WIRE RANGE 9) CD (AWG) (AWG) CT USE CLASS 1 WIRING FOR ALL 115 VOLT APPLICATIONS.BINARY INPUTS/OUTPUTS N ASSOCIATED WITH FAN CONTROL A RE 115 VAC. v 4, 200/230 O CC RC 20T-60T 142/0 14-2 C6.USE CLASS 2 WIRING FOR ALL24 VDC AND 24 VAC APPLICATIONS.ANALOG/BINARY N A 460/575 INPUTS AND ANALOG OUTPUTS ARE 24 VDC.BINARY OUTPUTS ARE 24 VAC. 0 cm co Frontier Split J81J13172 February 7,2019 Field Installed Options -Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family-Commercial Self-Contained Air Conditioning Unit(W/Controls) Item Tag(s) Qty Description Model Number Al SCXG-1 1 Commercial Self Contained -Modular Ser SCRGU3243 Field Installed Option Description Part/Ordering Number VFD/Inverter w/bypass&supply air temp control Spring isolators Product Family-Air-Cooled Condenser Units(Commercial) Item Tag(s) Qty Description Model Number B1 CU-32 ton 1 32 Ton Commercial Air-Cooled Condenser CCRC0324 Field Installed Option Description Part/Ordering Number Spring isolators FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 25 of 25 Others