Report (36) U-C t3c Sk,() St Seubert Engineering DESIGNING& CONSULTING FROM CONCEPT TO PRODUCTION. 25125 S. Mt. View Rd. Robert C. Seubert, PE Phone/Fax (503) 824-5030 Colton, OR 97017 Rseubert@seubertmachininq.com Cell (503) 805-2920 AFP Systems, Inc. 4/16/19 19435 SW 129th Ave. Tualatin, OR 97062 RECEIVED ATT: Steve APR 17 20192v Subject: System Review/PE Stamping CITY OF TIGARD Pape BUILDING DIVISION Job #18191 Hi Steve, I've reviewed the three drawing sheets, one remote area calculation, and seismic bracing calcs for this project. Remote area one is designed for rack storage of group'A' plastic and rubber tires to 20'using K25.2 heads @ .976 gpm/sq. ft. (15psi min). Seismic bracing calcs include two lateral, two longitudinal braces. I find no concerning issues with the design, layout or calculations with respect to NFPA 13 standards the project is adhering to. Given the compliance with the stated and supplied specifications it's my pleasure to approve this packaged with my PE stamp. Best Regards, Robert Seubert, PE C!_ ` RECEIVED AFP Systems, Inc. Automatic Fire Protection APR 1 7 2019 \ ` 19435 SW 129th Avenue CITY OF TIGARD g S (503)6 992-2-9284 MS Tualatin, 97062 BUILDING DIVISION y �p? (503)692-1186 fax i4 Phaf Submittal Project Name: Pape Material Handling Phase 2 6955 SW Sandburg St. Tigard, OR 97223 For Perlo Construction 11450 SW Amu St. Tualatin, OR 97062 tqco Worldwide www.tyco-fire.com Fire Protection Contacts Products Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response General having nominal K-factors of 14.0 and 16.8.This feature offers flexibility when Description sizing system piping, as well as possi- bly reducing or eliminating the need for r TYCO Model ESFR-25 Pendent Sprin- a system fire pump. a y klers are Early Suppression, Fast Also,Model ESFR-25 Sprinklers permit Response (ESFR) sprinklers having a use of a maximum deflector-to-ceiling nominal K-factor of 25.2(Ref.Figure 1). distance of 18 inches(460 mm)versus They are suppression-mode sprinklers 14 inches (356 mm). Additionally, a that are especially advantageous as a storage arrangement of 40 ft. (12,2 means of eliminating the use of in-rack m) with a ceiling height of 45 ft. (13,7 ‘ sprinklers when protecting high-piled m) does not require in-rack sprinklers storage. as do other ESFR Sprinklers having The Model ESFR-25 Sprinklers are pri- nominal K-factors of 14.0 and 16.8. r �''- marily used for ceiling-only sprinkler The Model ESFR-25 Sprinklers are protection of(but not limited to)the fol- listed by Underwriters Laboratories lowing storage applications: (UL) for specific applications with a lines. The general guidelines in this maximum storage height of 43 ft.(13,1 data sheet are not intended toprovide • most encapsulated or non-encap- m)with a maximum ceiling height of 48 p sulated common materials including ft.(14,6 m)without the requirement for complete installation criteria. cartoned, unexpanded plastics in-rack sprinklers.Refer to the Specific • uncartoned (exposed) expanded Application Listing (UL)for the design Sprinkler plastics in accordance with NFPA 13 criteria. Identification and FM Global standards Applications for the TYCO ESFR Sprin- • some storage arrangements of rub- klers are expanding beyond currently Number (SIN) ber tires, roll paper, flammable liq- recognized installation standards. For uids, aerosols, and automotive information on research fire tests(e.g., TY9226 components with flammable liquids and aerosols) TY9226 is a re-designation for Central For more specific criteria,refer to Table that may be acceptable to an author- SIN 9226, Gem SIN G8441, and Star A as well as the applicable design ity having jurisdiction,contact Tyco Fire SIN S8010. standard. Protection Products (TFPP) Technical Services. Technical The Model ESFR-25 Pendent Sprin- klers provide the system designer NOTICE Data with hydraulic and sprinkler place- ment options not presently available to The Model ESFR-25 Sprinklers the traditional ESFR sprinklers having described herein must be installed Approvals nominal K-factors of 14.0 and 16.8. In and maintained in compliance with this UL and C-UL Listed particular, the Model ESFR-25 Sprin- document,as well as with the applica- FM Approved kler has been designed to operate at ble standards of the National Fire Pro- VdS ApprovedNYC Approved under MEA 356-01-E substantially lower-end head pres- tection Association(NFPA),in addition LPCB Certified(Cert.Nos.094b and 0071) sures,as compared to ESFR Sprinklers to the standards of any authorities CE Certified(Certificate of Conformity having jurisdiction (e.g., FM Global). 1725-CPD-Hoo10) Failure to do so may impair the perfor- IMPORTANT mance of these devices. Maximum Working Pressure Always refer to Technical Data The owner is responsible for main- 175 psi(12,1 bar) Sheet TFP700 for the `INSTALLER taining their fire protection system Pipe Thread Connections WARNING" that provides cautions and devices in proper operating con- 1 Inch NPT or ISO 7-R 1 with respect to handling and instal- dition. Contact the installing contrac- Discharge Coefficient lation of sprinkler systems and com- tor or product manufacturer with any K=25.2 gpm/psi' (362,9 Ipm/bar's) ponents. Improper handling and questions. installation can permanently damageIn all cases, the appropriate NFPA or Temperature Ratings a sprinkler system or its compo- FM Global installation standard, or 165°F(74°C)and 212°F(100°C) nents and cause the sprinkler to fail other applicable standard, must be Finish to operate in a fire situation or cause referenced to ensure applicability and Natural Brass it to operate prematurely. to obtain complete installation guide- Page 1 of 4 JULY 2016 TFP312 TFP312 _ Page 2 of 4 1 } 7 1" NPT ---------------- Components: 8g 1-13/16" 1 - Frame Y�� ,� 9/16" (46,0 mm) 2 - Deflector �IP'��_Y (14,3 mm) FLIMI1=111 3 Compression 9 A��� NOMINAL MAKE-IN ■ In Screw 1. �raT4 - Hook g ��5 - Strut 1,6 Link Assembly3-13/16" C 7 - Button 5 (96,8 mm) THERMAL 8 - Sealing .� SENSING AssemblyJELEMENT 9 - Election Spring 4c WRENCH FLATS 3 ARS ARP 11....E ..■11 2 TEMPERATURE RATING - 2"(50,8 mm)---.--1 FIGURE 1 MODEL ESFR-25 PENDENT SPRINKLER,25.2K EARLY SUPPRESSION,FAST RESPONSE Storage Type NFPA FM Global • Open Frame(i.e.,no solid shelves) Refer to NFPA 13 Refer to FM Global Single,Double,Multiple-Row,or Portable Rack Storage of Chapters 16 and 17 2-0 and 8-9 Class I-IV and Group A or B Plastics Solid Pile or Palletized Storage of Refer to NFPA 13 Refer to FM Global Class I-IV and Group A or B Plastics Chapters 14 and 15 2-0 and 8-9 Idle Pallet Storage Refer to NFPA 13 Refer to FM Global Chapter 12 2-0,8-9,and 8-24 Rubber Tire Storage Refer to NFPA 13 Refer to FM Global Chapter 18 2-0 and 8-3 Roll Paper Storage Refer to NFPA 13 (Refer to the Standard) Chapter 19 Refer to FM Global 8-21 Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM Global 7-29 (Refer to the Standard) Aerosol Storage Refer to NFPA 30B Refer to FM Global 7-31 (Refer to the Standard) Automotive Components in Portable Racks Refer to NFPA 13 N/A (Control mode only;refer to the Standard) Chapter 20 N/A-Not Applicable TABLE A MODEL ESFR-25 PENDENT SPRINKLER COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW - TFP312 Page 3 of 4 Physical Characteristics System Type Sprinkler Position Frame Brass Wet Pipe Pendent: Deflector Bronze Frame arms aligned with pipe Compression Screw Stainless Steel Roof Construction Deflectors parallel with ceiling or roof Hook MONEL Unobstructed or obstructed con- Strut MONEL struction (e.g., smooth ceiling, bar System Type Link Assembly Solder,Nickel joists, beam and girder, and so forth). Wet Pipe only Button Brass Where the depths of the solid struc- Sealing Assembly. Beryllium Nickel w/TEFLON p Maximum Area of Coverage Ejection Spring INCONEL tural members(e.g., beams and stem) 100 ft2(9,3 m2) exceed 12 inches (302 mm), install Operation ESFR Sprinklers in each channel In some cases, the installation p stan- formed by the structural members. dards permit a greater coverage area. The fusible link assembly is com- Ceiling Slope Minimum Area of Coverage prised of two link halves that are joined Maximum 2 inch rise for 12 inch run 64 ft2(5,8 m2)according to NFPA 13 together by a thin layer of solder.When (16.7%) the rated temperature is reached, the Maximum Slope Ceiling solder melts and the two link halves Maximum Coverage Area 2 inch rise for 12 inch run(16.7%) separate, activating the sprinkler and 100 ft2(9,3 m2) Maximum Spacing flowing water. In some cases, the installation stan- 10 feet(3,1 m) dards permit a greater coverage area. Design Minimum Coverage Area In some cases, the installation stan- dards permit a greater spacing. Criteria 64 ft2(5,8 m2)per Minimum Spacing NFPA 13/FM Global 2-0 8 feet(2,4 m) The following general guidelines pro- Maximum Spacing vided for the TYCO Model ESFR-25 12 feet(3,7 m)for building heights up to Temperature Rating Pendent Sprinklers can be used for a 30 feet(9,1 m) 165°F(74°C)and 212°F(100°C) quick reference. Deflector Distance from Walls 10 feet (3,1 m) for building heights 102 mm The National Fire Protection Associa- greater than 30 feet(9,1 m). Minimum of 4 inches (102 from tion(NFPA)and FM Global(FM Approv- walls but no more than 1/2 the allow- als) provide installation standards that In some cases, installation standards able distance permitted between must be used to properly design an permit a greater spacing. sprinklers automatic sprinkler system utilizing Minimum Spacing Deflector to Top of Storage Early Suppression, Fast Response 8 feet(2,4 m) Minimum of 36 inches(914 mm) (ESFR)Sprinklers.The guidelines pro- vided by NFPA and FM Global may Minimum Clearance to Commodity Deflector-to-Ceiling Distance differ. Consequently, the appropri- 36 inches(914 mm) 6 to 14 inches(152 to 356 mm) ate standard must be used for a given NFPA Maximum Ceiling Height installation. Deflector-to-Ceiling Distance 48 feet(14,6 m) In all cases, the appropriate NFPA or 6 to 18 inches(152 to 457 mm) Maximum Storage Height FM Global installation standard must FM Global 43 feet(13,1 m) be referenced to ensure applicabil- Centerline of Thermal Sensing ity and to obtain complete installation Storage Arrangement guidelines. Element-to-Ceiling Distance Palletized, solid piled, open frame, Refer to FM Global 2-0 for Storage single row,or double row The following general guidelines are not Sprinklers. intended to provide complete installa- Commodity tion criteria. Specific Class I-IV; Cartoned, unexpanded In addition to this technical data sheet, p plastic the following data sheets describe Application Sprinkler System Design other TYCO ESFR Sprinklers: NFPA 13 for ESFR Sprinklers based • TFP315 Listing (UL) upon 45 psi (3,1 bar) design pressure, Model ESFR-17(TY7226) TYCO Model ESFR-25 Pendent Sprin- 169 gpm (640 Ipm) with 12 sprinkler K=16.8 Pendent Sprinkler klers are listed by Underwriters Labo- remote area • TFP316 ratories (UL) for Specific Applications Minimum Aisle Width Model ESFR-17(TY7126) with a ceiling height greater than 5 feet(1,5 m) K=16.8 Upright Sprinkler 45 ft. (13,7 m) up to and includ- ing 48 ft. (14,6 m), and a storage • TFP317 arrangement up to and including Model ESFR-17(TY7223) 43 ft. (13,1 m), the following guide- K=16.8 Pendent Sprinkler line are provided for the TYCO Model • TFP318 ESFR-25 Pendent Sprinklers: Model ESFR-1 (TY6226) K=14.0 Pendent Sprinkler • TFP319 Model ESFR-14(TY6236) K=14.0 Pendent Sprinkler TFP312 Page 4 of 4 Step 4. After installation, inspect the ■ imited Link Assembly of each Model ESFR-25 f• FITTING SIDE" Pendent Sprinkler for damage. In par- warrant TOWARDS SPRINKLER ticular, verify that the Link Assembly y FITTING and Hook are positioned as illustrated For warranty terms and conditions,visit in Figure 1, and that the Link Assem www.tyco-fire.com. 11"; bly is not bent, creased, or forced out Illi) �t of normal position in any way. Replace .,� N damaged sprinklers. Ordering Care and Procedure Maintenance Contact your local distributor for WRENCH avail- ability.When placing an order,indicate RECESS the full product name and part number TYCO Model ESFR-25 Early Suppres- sion, Fast Response 25.2K Pendent (P/N). FIGURE 2 Sprinklers must be maintained and ser- Sprinkler Assemblies W-TYPE 1 viced in accordance with this section. Specify: Model ESFR-25 Early Sup- SPRINKLER WRENCH Before closing a fire protection system pression, Fast Response 25.2K main control valve for maintenance Pendent Sprinklers (TY9226), (specify Installation work on the fire protection system that temperaturemating),with Natural Brass it controls,permission to shut down the finish, P/N(specify): TYCO Model ESFR-25 Early Suppres- affected fire protection system must be 165°F(74°C) 58-441-1-165 sion, Fast Response 25.2K Pendent obtained from the proper authorities 212°F(100°C) 58-441-1-214 Sprinklers must be installed in accor- and notify all personnel who may be Special Order dance with this section. affected by this action. Sprinkler Assemblies with General Instructions Sprinklers which are found to be ISO 7-1 Thread Connection Damage to the fusible Link Assem leaking or exhibiting visible signs of Specify: Model ESFR-25, Early Sup- bly during installation can be avoided corrosion must be replaced. pression, Fast Response 25.2K Pendent by handling the sprinkler by the frame Automatic sprinklers must never be Sprinklers ISO 7-1 thread d connection,(TY9226) with (specify arms only (i.e., do not apply pressure painted, plated, coated, or other- temperature rating),with Natural Brass to the fusible Link Assembly), and by wise altered after leaving the factory. finish, P/N(specify): using the appropriate sprinkler wrench. Modified sprinklers must be replaced. Failure to do so can lead to an unstable Sprinklers that have been exposed to 165°F(74°C) 58-442-1-165 link assembly and premature activation corrosive products of combustion, but 212°F(100°C) 58-442-1-214 of the sprinkler. Damaged sprinklers have not operated,should be replaced Sprinkler Wrench must be replaced. if they cannot be completely cleaned Specify: W-Type 1 Sprinkler Wrench, A leak tight 1 inch NPT sprinkler joint by wiping the sprinkler with a cloth or P/N 56-872-1-025 should be obtained by applying a min by brushing it with a soft bristle brush. imum-to-maximum torque of 20 to 30 Care must be exercised to avoid lbs.-ft. (26,8 to 40,2 Nm). Higher levels damage to the sprinklers before, of torque can distort the sprinkler inlet during, and after installation. Sprin- with consequent leakage or impairment klers damaged by dropping, striking, of the sprinkler. wrench twist/slippage,or the like,must Note: Install the Model ESFR-25 be replaced. Also, replace any sprin Pendent Sprinkler in the pendent posi kler that has a cracked bulb or that has tion(Ref. Figure 2). lost liquid from its bulb (Ref. Installa- tion section). Step 1. With pipe thread sealant The owner is responsible for the applied,hand-tighten the sprinkler into the sprinkler fitting. Do not apply pres inspection,testing,and maintenance of sure to the Link Assembly, and handle their fire protection system and devices the Model ESFR-25 Pendent Sprinkler in compliance with this document, as only by the Frame arms. well as with the applicable standards of the National Fire Protection Asso- Step 2. Wrench-tighten the Model ciation (e.g., NFPA 25), in addition to ESFR-25 Pendent Sprinkler using only the standards of any authorities having the W-Type 1 Sprinkler Wrench (Ref. jurisdiction.Contact the installing con- Figure 2)and by fully engaging(seating) tractor or product manufacturer with the wrench on the sprinkler wrench any questions. flats(Ref. Figure 1). Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright©2016 Tyco Fire Products,LP. All rights reserved. t G>D MONEL and INCONEL are trademark of Special Metals Corporation. Fire Protection Products TEFLON is trademark of DuPont Corporation. t11117Worldwide Fire Protection Contacts www.tyco-fire.com Products Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the p standard corrosion tests of the appli- z The TYCO Series TY FRB, 2.8, 4.2, cable approval agencies,the testing is 0 u not representative of all possible cor- 5.6,and 8.0 K-factor,Upright,Pendent, � and Recessed Pendent Sprinklers rosive atmospheres. Consequently, ': described in this data sheet are quick it is recommended that the end user response, standard coverage, deco be consulted with respect to the suit- IJAL rative 3 mm glass bulb-type spray ability of these coatings for any given ;� y sprinklers designed for use in light or corrosive environment. The effects of �, �, ambient temperature,concentration of ordinary hazard,commercial occupan- cies such as banks, hotels, and shop- chemicals, and gas/chemical velocity, e - should be considered, as a minimum, .. ping malls. along with the corrosive nature of the _ The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable, is intended for use in areas An intermediate level of the Series with a finished ceiling. This recessed TY-FRB Pendent Sprinklers is detailed pendent sprinkler uses one of the in Technical Data Sheet TFP356, and following: Sprinkler Guards are detailed in Tech- • A two-piece Style 10 (1/2 inch NPT) nical Data Sheet TFP780. or Style 40(3/4 inch NPT) Recessed Escutcheon with 1/2 inch (12,7 mm) NOTICE of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment The Series TY-FRB, 2.8, 4.2, 5.6, from the flush pendent position,or a and 8.0 K-factor, Upright, Pendent, and Recessed Pendent Sprinklers g • A two-piece Style 20 (1/2 inch NPT) described herein must be installed ... 1 or Style 30(3/4 inch NPT)Recessed and maintained in compliance with , Escutcheon with 1/4 inch (6,4 mm) this document and with the applica- , of recessed adjustment or up to 1/2 ble standards of the National Fire Pro- " 44, inch (12,7 mm) of total adjustment tection Association, in addition to the from the flush pendent position. standards of any authorities having The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler accuracy to which the fixed pipe drops The owner is responsible for maintain- Identification to the sprinklers must be cut. ing their fire protection system and Corrosion-resistant coatings, where devices in proper operating condition. Number (SIN) applicable,are utilized to extend the life The installing contractor or sprinkler of copper alloy sprinklers beyond that manufacturer should be contacted with TY1131 -Upright 2.8K, 1/2"NPT which would otherwise be obtained any questions. TY1231 Pendent 2.8K, 1/2"NPT TY2131 -Upright 4.2K,1/2"NPT TY2231 -Pendent 4.2K,1/2"NPT IMPORTANT TY3131 -Upright 5.6K,1/2"NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT Sheet TFP700 for the "INSTALLER TY4131 -Upright 8.0K,3/4"NPT WARNING" that provides cautions TY4231 -Pendent 8.0K,3/4-NPT with respect to handling and instal- TY4831 -Upright 8.0K,1/2"NPT lation of sprinkler systems and corn- TY4931 -Pendent 8.0K, 1/2"NPT ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing lir 1 (11,1 mm) ' Nl ______ ` 3 NOMINAL 2_1,4" ,L� WI MAKE-IN (57,2 mm) 2 ter 2-3/16" /i# li 4 � 1-9/16" (55,6 mm) (39,7 mm) 4. $:' 5 // \\ / \\ ±+L... t „./.....re =A�� Ti //f_1�\ :•mo i: .���—6* 1/2"NPT** I WRENCH STYLE 10 or 20 P-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE S. 1 7/16" di 1 / fri . tA !4 : (11,1 mm)04 NOMINAL ' 2-3/16" �,�� r MAKE-IN 1 (55,6 mm) I I 2-3/16" 1-1/2" 1 4 (55,6 mm) i . (38,1 mm) . ,�, 5 1 i \ R/ 1/2" NPT** t WRENCH STYLE 10 or 20 1--- 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE r 1 Dili / R\D __ =-- -----* 01 E 7/16" III� 3 (11,1 mm) ..„,..� ��i i NOMINAL I a A g 2 — 2-3/16" �`� A r MAKE-IN IN 14 (55,6 mm) Ilif 1 1-1/2" (38,1 mm) 5 ^ --,-iritm-- 6* 1/2" NPT** WRENCH STYLE 10 or 20 - 2-7/8"(73,0 mm)DIA. -- FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT . TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1Frame 3Sealing 5 - Compressionression is indicated on ISO 7-1 can beP rovided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE trilivvt ,,-_-_-- ---- 1/2" ri�� 0 l 3 (12,7 mm) +�, 014 II . NOMINAL 1. 1 � I�41— A :I, 2 MAKE IN I (58,7 m) = 1 (57,2/mm) I 1 1-9/16" I 4 -� (39,7 mm) \ __At_ , la o 3/4"NPT** I WRENCH STYLE 30 or 40 FLATS RECESSED 2_7/8"(73,0 mm)DIA. UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw ._____, 1 3 - Sealing 6 - Deflector * Ij Assembly —=--- ------- / ____ i s 3 4 Bulb (1117/16" � 21/4"1 (57,2 mm) A4 2 NOMINALMAKE-IN * Temperature rating is �r 2 3/16" 1-9/16" 4 indicated on Deflector. (55,6 mm) 1 i (39,7 mm) . ��5 ** Pipe thread connections \ -- i+,`\ * per ISO 7-1 can be 6 provided on special 1/2" NPT** I WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT Gl WRENCH RECESS WRECESS (END"A"USED FOR /��� / RENCH 1/2"NPT MODELS) WRENCH RECESS 1.1 ter, (END"B"USED FOR 3/4"NPT MODELS) PUSH WRENCH INTO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 FIGURE 7 W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED WRENCH SPRINKLER WRENCH TFP171 _ Page 4 of 10 Technical Design Do not attempt to compensate for insufficient adjustment in the Escutch- Data Criteria eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of Approvals The TYCO Series TY-FRB, 2.8, 4.2, the sprinkler fitting to suit. UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed resistant status. dard installation rules recognized by in accordance with the following Maximum Working Pressure the applicable Listing or Approval instructions. Refer to Table C. agency (such as, UL Listing is based Step 1.Install Pendent sprinklers in the on the requirements of NFPA 13, and Discharge Coefficient FM Approval is based on the require- pendent position. Install upright sprin- K=2.8 gpm/psi'(40,3 Ipm/bar's) ments of FM's Loss Prevention Data klers in the upright position. K=4.2 gpm/psi' (60,5 Ipm/bar's) Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant K=5.6 gpm/psi' (80,6 Ipm/bar's) 40 Recessed Escutcheon, as applica- applied to the pipe threads, hand- K=8.0 gpm/psi' (115,2 Ipm/bar's) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler Temperature Rating installations. fitting. Refer to Table A and B. Step 3. Tighten the sprinkler into the Finishes Installation sprinkler fitting using only the W-Type Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, 6 Sprinkler Wrench(Figure 6).With ref and 8.0 K-factor,Upright,Pendent,and erence to Figures 1 through 5, apply Recessed Escutcheon:Signal or Pure Recessed Pendent Sprinklers must the W-Type 6 Sprinkler Wrench to the White,Jet Black,Chrome Plated,or be installed in accordance with this sprinkler wrench flats. Natural Brass section. Series TY-FRB Recessed Pendent Physical Characteristics Sprinklers Frame Bronze General Instructions Button Brass/Copper Do not install any bulb-type sprinkler The Series TY FRB Recessed Pendent Sealing Assembly..Beryllium Nickel w/TEFLON if the bulb is cracked or there is a loss Sprinklers must be installed in accor Bulb Glass of liquid from the bulb.With the sprin- dance with the following instructions. Compression Screw Bronze kler held horizontally,a small air bubble Step A.After installing the Style 10,20,Deflector Copper/Bronze Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica- air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tern- threads,hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B. Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained by applying a sprinkler fitting using only the W-Type expands sufficiently to shatter the glass bulb, allowing the sprinkler to minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure activate and water to flow. 14 ft.-lbs. (9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4, 3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and torque can distort the sprinkler Inlet with consequent leakage or impairment finishing, slide on the Style 10, 20, 30, of the sprinkler. or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER*** FACTOR COLOR BRASS PLATED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) • and 175°F(79°C) Yellow 1,2,3,4 UPRIGHT (TY1131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 68° 155°F C 1/2"NPT PENDENT 155 ( ) Red (TY1231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 1,2,4 135°F(57°C) Orange RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED ° ° 155F 68C 1/2"NPT PENDENT ( ) Red 1,2 (TY2231)* 175°F(79°C) Yellow Figure 10 200°F(93°C) Green 135°F(57°C) Orange RECESSED PENDENT 155°F(68°C) Red (TY2231)** 175°F(79°C) Yellow Figure 11 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. `Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. "Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 - Page 6 of 10 SPRINKLER FINISH(See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER*** LEAD FACTOR COLOR BRASS PLATED COATED 135°F(57°C) Orange PENDENT (TY3231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT .200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT .175°F(79°C) Yellow 1,2,4,5 N/A • 1/2"NPT (TY3231)* Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A (TY3231)** Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT (TY4231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231) Figure 14 200°F(93°C) Green 286°F(141°C) Blue _ 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A (TY4231)** Figure 15 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red 8.0 (TY4931) 1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5 UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. ""Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME POLYESTER LEAD FACTOR BRASS PLATED COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231) 175 PSI and (12,1 BAR) UPRIGHT(TY4131) 3/48.0 NPT 175 PSI(12,1 BAR) — RECESSED N/A PENDENT(TY4231) PENDENT.0 (TY4931) 175 PSI and 1/2$NPT UPRIGHT(TY4831) 175 PSI(12,1 BAR) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and have not operated,should be replaced Care must be exercised to avoid if they cannot be completely cleaned damage to the sprinklers -before, Maintenance by wiping the sprinkler with a cloth or during, and after installation. Sprin- by brushing it with a soft bristle brush. klers damaged by dropping, striking, The TYCO Series TY-FRB must be Care must be exercised to avoid wrench twist/slippage,or the like,must maintained and serviced in accordance damage to the sprinklers before, be replaced. Also, replace any sprin- with this section. during, and after installation. Sprin- kler that has a cracked bulb or that has klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- Before closing a fire protection system tion Section main control valve for maintenance wrench twist/slippage,or the like,must )• work on the fire protection system be replaced. Also, replace any sprin- Initial and frequent visual inspections of that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for shut down the affected fire protection lost liquid from its bulb. (Ref. Installa- corrosion-resistant sprinklers to verify systems from the proper authorities tion Section.) the integrity of the corrosion-resistant and notify all personnel who may be The owner is responsible for the material of construction. Thereafter, affected by this action. inspection,testing,and maintenance of annual inspections per NFPA 25 should their fire protection system and devices suffice. Absence of the outer piece of an in compliance with this document, as Inspections escutcheon, which is used to cover well as with thea applicable standards of corrosion resistant a clearance hole, can delay sprinkler pp sprinklers are recommended at close operation in a fire situation. of the National Fire Protection Asso- range, instead of from the floor level ciation (e.g., NFPA 25), in addition to per NFPA. Inspection at close range Sprinklers which are found to be the standards of any other authorities can better determine the exact sprin- leaking or exhibiting visible signs of having jurisdiction.Contact the install- kler condition and the long-term integ- corrosion must be replaced. ing contractor or sprinkler manufac- rity of the corrosion-resistant material, Automatic sprinklers must never be turer regarding any questions. which can be affected by the corrosive painted, plated, coated, or other- Automatic sprinkler systems are rec- conditions present. wise altered after leaving the factory. ommended to be inspected, tested, Modified sprinklers must be replaced. and maintained by a qualified Inspec- Sprinklers that have been exposed to tion Service in accordance with local corrosive products of combustion,but requirements and/or national codes. TFP171 Page 8 of 10 2-7/8" DIA. 2-7/8"DIA. (73,0 mm) 3/4" mm) (73,0 mm) 1/2"(12,7 mm) 5/8±1/4" (19,11/2-1.-1/8" (15,9±6,4 mm) 2 1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / (57,2 mm) / FACE OF (57,2 mm) MOUNTING FACE OF MOUNTING SPRINKLER PLATE SPRINKLER7------- PLATE FITTING FITTING / 1/8" 1/8" (3,2 mm) / (3,2 mm) ipt �liL 'i ad_ .-----------o____• PTi�. � 11111P } \ lir il MOUNTING MOUNTING SURFACEI SURFACE iirrAmi . �, ' CLOSURESERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA. 2-7/8" DIA. (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) 5/8±1/4" (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) 57,2 mm (57,2 mm) 1 / FACE OF ( ) MOUNTING / FACE OF I MOUNTING SPRINKLER PLATE SPRINKLERr____ PLATE FITTING FITTING / 1/8" 1/8" (3,2 mm) / (3,2 mm) I _=-1,__ , I ,�,,,i_ \ ,�, 1 MOUNTING III) MOUNTING R. SURFACE . SURFACE .. •- -- CLOSURE SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm) TY-FRB CLOSURE 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. _ 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) (15,9±6,4 mm) 1/4"(6,4 mm) 1/2±1/8" 1/2"(12,7 mm) 2-1/4"DIA. (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) (57,2/ FACE mm) '1 SPRINKLER I MOUNTING / FACE OF (57,2 mm) ~ MOUNTING FITTING PLATE SPRINKLER PLATE FITTING / 1/8" 1/8" (3,2 mm) / (3,2 mm) ...7.,_ I_ rk i i r 7; ex./ i f _,,,,,_ 1------- \ I MOUNTI/EESi:/4" MOUNTING , • CLOSURE SERS1 /4"(31,8mm) (31,8 mm) TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB 1"(25,4 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm) 1/2±1/8" (15,9±6,4 mm) _ 2-1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING / (57,2 mm FACE OF ) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" (3,2 mm) (3,2 mm) MI NIE"..11 } \ _n-,L„ 177 7;'. , /77 f MOUNTING �'� MOUNTING vSURFACESURFACE . CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 14 FIGURE 15 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE t 155 155°F(68°C) POLYESTER(RAL9010) 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) POLYESTER(RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 2 200 200°F(93°C) POLYESTER(RAL9005)2 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available in only 2.8K,4.2K,and 8.0K,155°F(68°C) and 200°F(93°C);requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831' 361 8.0K PENDENT(1/2"NPT) TY4931* TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify') finish, P/N (specify*) Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 'Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Fire Protection Products • • % 5 z ., s -9k -59;;1•9,,155-51-1•4•1\1;•••11.• r� j / r rr r e rtA �W •OOD , SAMMYS° FOR WOOD - Vertical Application Application II Not less than Product Features Wood Flooring2"nominal width •No pre-drilling required. (�)♦ •Quick to install using the Sammy Not lass man Nut Driver with an 18V cordless 3°nominal '- drill/driver. thickness(2-1/2") -` (depth or Wood Joist at vertical member) •Saves time from traditional ? methods. 'V Double Sheetrodc For vertical use Ceiling •Reduces installation costs. install in.center of tower race. Mnlmum2"emliedmentintobase •Manufactured in the U.S.A. material for NFPA 13 compliance. Composite 1 Truss `Consult buss manufacturer ton r >reeomanended instana£ion pont p *Pre.oa trvy may be regei rotfar 6ST r, 2538 .,at araiiahre a.page if. r, a 3 Watch asides denrorshatian at www.itwbuildex.com) Approvals Rod Part Model Screw Ultimate UL Test FM Test Box Case Size Number Descriptions Pullout(lbs) Load(lbs) Load(lbs) Qty Qty VERTICAL MOUNT 1/4" 8002957 GST 100 1/4 x 1" 210(7/16"OSB) 25 125 670(3/4"Ply) ic 210 (7/16"OSB) 3/8" 8007957 GST 10 1/4 x 1" 670(3/4"Ply) 300 25 125 n 64'il. 3/8" 8068925 GST 20-SS 1/4 x 2' 1760 (Fir) 850 a, Oe25 125.; #14 Black 11 , r m < x 'I/2' 21.13, t --- ,_550€1 ��.. .. ...,t'5 s {el9925 fa z. d� � {F`r} rr �' Nut Driver 'r, 3/8 8010957 GST 30 1/4 x 3 2060 (Fir) 1500 1475 25 125 Part#8113910 'v ``-rif r4 �� m�;9925 •� � ����.�`� ,..��Fa. ZIfZ; •iii".:,Lk,�K it��$ ... "O(/ 1/2" 8013925 GST 2 114 x 2 1760 (Fir) 25 125 �_. ... 1111,1..,, ;,15925 i,. 2275 Wir)z,1 7 r? �,,.I. 25. , ,I, #14 SW Red Nut Driver Part#8114910 ) WM ,....i...„..,,„ { weUS Y MPNUFAGNPEOUSA SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.itwbuildex.com 4 e'it iw s' ;7 104-',T.- SIDEWINDER° FOR WOOD -Horizontal Application Application Product Features Not less than 2"nominal width •No pre-drilling required. (1-1/2")up to 3-1/2"pipe;not less than - a 3'(2-1/2°)nominal width 4"&5°pipe •Quick to install using the Sammy 4-0 Floor Joist Nut Driver with an 18V cordless Minimum 2-1/2°from bottom for -- drillldriver.; branch lines.Minimum 3°from hot- tom for main lines Exception:This •Saves time from traditional J requirement shall not apply to 2°or thicker nailing strips resting on top of methods. W1,1 steel beams. W •Reduces installation costs. ti ». _ I" •Manufactured in the U.S.A. t r � t Composite/Truss Consuhtrussmanufaeturerf� recommended installation z*Pre dellmg may be requued for oriel ° ; `SWG 25 380.Tootavailable on page 11. ; �,� ,watch a Ndea demonshatlon at wwwativbuddex.com LI W Rod Part Screw Ultimate UL Test Box Case Approvals Model Size Number Descriptions Pullout(lbs) Load(lbs) Qty Qty HORIZONTAL MOUNT 1/4" 8019957 SWG 200 1/4 x 2" 1725 (Fir) 25 125 ice' .< -f: e$•"> f.Hsw j7; .1/4x1 ` ' 622 i:Fi€ 300 . 25 ,r 'i 3/8 8021957 SWG 20 1/4 x 2 1725(Fir) 1050 25 125 1 ', `" '>.: n : iftI7 25,-- SSW 20-SS f4 x 2" 172, Fx . *, :1 2 y 12tl�`: ce 3/8"" 8022925 SWG 25-380 3/8 x 2-1/2" 2249 (Fir) 1500 25 125 #14 SW Red s¢r . . €s 252%%, SWG 3O`' ',1f4 -3 .(trl a ' H. ? Z''',.:;Y:' 125t" Nut Driver Part#8114910 *May require pre-drilling;consult joist manufacturer. LU SAMMYS SWIVEL HEAD TM FOR WOOD -Swivel Application Z O Application Product Features V ,..near. •Eliminates distortion of threaded rod. •Accommodates up to 3%"x 12 pitch roof. •Allows 17°deflection from vertical. •Saves time from traditional methods. W •Reduces installation costs. CZ p ax aacvoGs Manufactured in the U.S.A. „ O e*im C) If Approvals Rod Part Screw Ultimate UL Test Load FM Test Min Box Case w Model Size Number Descriptions Pullout(lbs) (lbs) Load(lbs) Thickness Qty Qty V 4 1414 Black SWIVELfMOUNT Nut Driver 3/8" 8139957 SH-GST 20 1/4 x 2" 1257(Fir) 1050 1475 25 125 1' Q .: art#8113910 * '11 ii ° 15ea ) 8"" 8269 7 5H-QST/CS�'r -3f4 1 r o •q vertu e t °•- -,i'- 2-4 125 i 1 903 Dim.Lumber 1/2" 8303957 SH-GST/CST 2.0 5/16 x 1-3/4" 1406 @ 45°off vertical 25 125 J Dim.Lumber Q *May require pre-drilling;consult joist manufacturer. #14 SH Orange 0 Nut Driver M Part#8273910 �Cr 0 To find a distributor near you,call 800-BUILDEX o A47./ good P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 555 BRACKET SIZE-ROD: 1/2" SIZE-SYSTEM PIPE: 8"max. bti5o MATERIAL-Carbon Steel. I� FINISH-Plain or E.G. LISTING/APPROVAL- / ` 4� °'203- EX 2551 o usTev 5 ry FUNCTION- Attachment component of an AFCON hanger. /iso INSTALLATION Per NFPA 13 and these instructions. Install on vertical mounting surface. ASSEMBLY/ATTACHMENT- Mounting hole accepts 1/2"or 5/8"fasteners. FEATURES-Tapped rod bore. ORDERING-Part#and finish. 556 BRACKET SIZE-ROD: 1/2" SIZE-SYSTEM PIPE:8"max. MATERIAL-Carbon Steel. FINISH-Plain or E.G. LISTING/APPROVAL- 4l os 203- EX 2551 usrev NOTE-Criteria same as 555 except smooth 17/32"rod bore. Install hanger rod with%2"nut. 4/13 Victaulic® FirelockTM Rigid Coupling jctaulic Style 009N 10.64 9d i Patented 1.0 CERTIFICATION/LISTINGS c®u I LPCB una C104-1a/36 2.0 PRODUCT DESCRIPTION • The FireLock EZTM Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. • The coupling's unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. • IMPORTANT: FireLock EZTM Style 009N couplings are recommended for use ONLY on fire protection systems. 3.0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Orange enamel (North America, Asia Pacific) ® Red enamel (Europe) O Hot dipped galvanized Gasket: (specify choicer) ❑ Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: Zinc electroplated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. IIS • System No. Location Spec Section Paragraph Submitted By Date Approved Date • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 ictaUlie victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • • 4.0 LISTINGS/APPROVAL 2 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus FM Vds LPCB Sch.5 Sch. 10 Sch.40 Sch.5 Sch.10 Sch.40 inches psi psi psi psi psi psi psi psi mm kPa kPa kPa kPa kPa kPa kPa kPa 1'/a 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 2500 11/2 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 1205 2502 2502 2500 2500 2Y2 N/A 365 365 175 363 363 363 363 65 2517 2517 1205 2502 2502 2500 2500 76.1 mm N/A 3653 N/A N/A 3634 N/A 363 363 25173 25024 2500 2500 3 N/A 365 365 175 363 363 363 363 80 2517 2517 1205 2502 2502 2500 2500 4 N/A 365 365 175 363 363 363 363 100 2517 2517 1205 2502 2502 2500 2500 363 363 108.0 mm N/A N/A N/A 11205 75 2502 2502 N/A N/A 5 N/A 290 365 N/A 363 363 232 N/A 125 2000 2517 2502 2502 1600 133.0 mm N/A N/A N/A N/A 250 4 N/A N/A N/A 232 139.7 mm N/A 2000ss N/A N/A 2502 4 N/A 600 N/A 159.0 mm N/A N/A N/A N/A 250 4 N/A N/A N/A 165.1 mm N/A 2000 a N/A N/A 2522 4 N/A N/A N/A 6 290 365 363 363 232 150 N/A 2000 2517 N/A 2502 2502 1600 N/A 216.0 mm N/A N/A N/A N/A 250' N/A N/A N/A 8 N/A 290 365 N/A 363 363 232 N/A 200 2000 2517 2502 2502 1600 2 Listed/Approved for wet and dry pipe systems(>—40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic Installation Manual 1-009N/009H for details concerning when supplemental lubrication is required. 3 cULus listed for DIN 2458 2.6 mm pipe wall. 4 FM approved for BS 1387 Medium 3.6 mm pipe wall. 5 cULus listed for EN 10220 4.0 mm pipe wall. 6 cULus listed for EN 10255 4.5 mm pipe wall. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic° victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • . 4.1 LISTINGS/APPROVAL Speciality Pipe Pipe Size Pressure Rating I Pipe Size Pressure Rating Pipe Size Pressure Rating cULus FM ; cULus FM cULus FM inches psi psi I 1 inches psi psi inches psi psi - kPa kPa kPa kPa kPa kPa BLT 114-2 300 365 EZT 11/4-2 300 365 MT 11/4-2 300 365 2068 2517 2068 2517 2068 2517 DF PA-4 300 365 FF 11/4-4 300 365 MLT 11/4-2 N/A 365 2068 2517 2068 2517 2517 DT 11/4-2 300 365 FLF 1 1/4—4 N/A 365 ST 1 1/4-2 N/A 365 2068 2517 2517 2517 EF P4-4 175 175 FLT 11/4-2 N/A 365 STF 11/4-4 N/A 365 1206 1206 2517 2517 EL 11/4-2 300 365 FLTL 11/4-2 N/A 365 TF 21/4-4 N/A 365 2068 2517 2517 2517 ET40 11/4-2 300 365 GL 11/4-2 300 365 WLS 11/4-2 300 365 2068 2517 2068 2517 2068 2517 EZF 3-4 300 365 MF 11/4-4 300 365 WST 11/4-2 N/A 365 2068 2517 2068 2517 2517 XL 11/4-2 300 365 2068 2517 NOTES • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaUIic victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 - 5.0 DIMENSIONS Style 009N Y 4-Z 4' Y Z FIT��rl par �T" Iri Mil Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) 1 Dimensions Pre-assembled Actual Maximum Maximum Allow. Approx. Nominal Outside Working End Pipe End Bolt/Nut s (Push On Condition) Joint Assembled Weight Size Diameter Pressure 7 Load 7 Separation$ Size X Y X Y Z Each inches inches psi lbs. inches inches inches inches inches inches inches lbs. mm mm kPa N mm No. mm mm mm mm mm mm kg 11/4 1.660 365 790 0.102 %x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 M10 x2 79 127 70 127 51 0.6 11/2 1.900 365 1035 0.102 3 x 2 338 5.13 3.00 5.13 2.00 1.5 40 48.3 2517 4604 2.54 M10 x2 86 130 76 130 51 0.7 2 2.375 365 1616 0.122 3/a x2' 4.00 5.63 3.50 5.63 2.00 1.9 50 60.3 2517 7193 3.05 M10 x 2'h 102 143 89 143 51 0.9 21/2 2.875 365 2370 0.12 2 3,43x 2'% 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 M10 x 21/2 114 156 102 156 51 1.0 3.000 365 2580 0.12 '/e x 2'h 4.63 6.00 4.13 6.13 2.00 2.1 76.1 mm 76.1 2517 11476 3.05 2 M10 x 2'k 118 152 105 156 51 1.0 3 3.500 365 3512 0.122 %x 2'k 5.13 6.75 4.63 6.75 2.00 2.3 80 88.9 2517 15622 3.05 M10 x 21/2 130 171 117 171 51 1.0 4 4.500 365 5805 0.172 4,13x 21/2 6.00 7.88 5.63 7.50 2.13 2.9 100 114.3 2517 25822 4.32 M10 x 2'h 152 200 143 191 54 1.3 4.250 365 5175 0.17 3/4x 2'h 5.63 7.38 5.38 7.38 2.13 3.1 108.0 mm 108.0 2517 23020 4.32 2 M10 x 21h 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.172 Y x 3 7.25 9.25 6.75 9.13 2.25 5.0 125 1413 2000 39456 4.32 M12 x 3 184 235 171 232 57 23 5.250 365 7897 0.17 1/2 x 3 6.63 9.00 6.38 9.00 2.25 4.8 133.0 mm 133.0 2517 35106 4.32 2 M12 x3 168 229 162 229 57 2.2 5.500 365 8667 0.17 1 x 3 6.88 9.25 6.75 9.13 2.25 4.9 139.7 mm 139.7 2517 38529 4.32 2 M12 x3 175 235 171 232 57 2.2 6.250 365 11192 0.17 '/2 x 3 V4 7.88 10.00 738 9.88 2.25 5.6 159.0mm 159.0 2517 49753 4.32 2 M12x3'/4 200 254 187 251 57 2.5 _ 6.500 365 12105 0.17 1/2x31/4 8.00 10.25 7.75 10.13 2.25 6.0 165.1 mm 165.1 2517 53813 4.32 2 M12 x VA 203 260 197 257 57 2.7 6 6.625 365 12582 0.17 ' x 31/4 8.38 10.38 7.88 10.13 2.25 6.0 150 168.3 2000 44469 4.32 2 M12 x 3'/4 213 264 200 257 57 2.7 8.500 365 20712 0.17 5/8 x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 mm 216.0 2517 55968 4.32 2 M16 x 4 270 337 260 257 67 5.2 8 8.625 365 21326 0.17 2 %x 4 10.88 13.38 10.25 13.13 2.50 11.4 200 219.1 1620 94863 4.32 M16 x4 276 340 260 333 64 5.2 7 Working Pressure and End Load are total,from all internal and external loads,based-un standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 8 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZT'couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 9 Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZTM Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZT"couplings are supplied with FireLock EZTM Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealTM gaskets are not compatible and cannot be used with the FireLock EZTM couplings. 10.64 7072 Rev G Updated 10/2014 m 2014 Victaulic Company.All rights reserved. victaulic.com4 ✓ctaulic° • • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 6.0 REFERENCE MATERIALS Publication 05.01:Seal Selection Guide I-009N/009H:Installation Instructions FireLock EZT",Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,as well as Victaulic performance,maintenance, Victaulic reserves the right to change product specifications,designs and standard safety,and warning instructions.Nothing in this or any other document,nor any verbal equipment without notice and without incurring obligations. recommendation,advice,or opinion from any Victaulic employee,shall be deemed to Installation alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Reference should always be made to the l-009N/I-009H Firelock EZ Rigid Coupling of sale,installation guide,or this disclaimer. Installation Instructions for the product you are installing.Handbooks are included with Intellectual Property Rights each shipment of Victaulic products,providing complete installation and assembly data, No statement contained herein concerning a possible or suggested use of any material, and are available in PDF format on our website at www.victaulic.com. product,service,or design is intended,or should be constructed,to grant any license Warranty under any patent or other intellectual property right of Victaulic or any of its subsidiaries Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such material,product,service,or design in the infringement of any patent or other intellectual Trademarks property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic,FireLock ELO5,Flush-SealT",and Installation-Readyno are trademarks or or patent applications for articles and/or methods of use in the United States and/or other registered trademarks of Victaulic Company,and/or its affiliated entities,in the U.S.and/ countries, or other countries. • • 10.64 7072 Rev G Updated 10/2014 m 2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic' Victaulic® FireLockTM Fittings ✓ctauiac' 10.03 • 1.0 PRODUCT DESCRIPTION Available Sizes • 11/4—8"/DN32—DN200 Maximum Working Pressure • Pressure ratings for Victaulic FireLockTM Fittings conform to the ratings of Victaulic FireLock EZTM Style 009N couplings (refer to publication 10.64 for more information). Application • FireLockTM fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. • Connects pipe, provides change in direction and adapts sizes or components Pipe Materials • Carbon steel 2.0 CERTIFICATION/LISTINGS D "L Ds ® 1.PCB VdS ( E LISTED EN 10311 Regulation(EU) No.305/2011 3.0 SPECIFICATIONS- MATERIAL Fitting: Ductile iron conforming to ASTM A536, Grade 65-45-12. Fitting Coating: Orange enamel. Red enamel in Europe, Middle East, Africa, and India. Optional: Hot dipped galvanized. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. System No. Location Spec Section [ Paragraph Submitted By Date Approved 1 Date • victaulic.com 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. 1 ictauIic. victaulic.com • • 4.0 DIMENSIONS F•CtoEM '' toEl I I v I e __ g CtoE _p p � r to ,;�‘ ,e;e -to _ I o I I -x No.001 No.003 No.002 No.006 No.001 No.003 No.002 No.006 90°Elbow 45°Elbow Straight Tee Cap Actual Approximate Approximate Approximate Approximate Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each T Each inches inches inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg ® ��j1 2 0.3 1'h 1.900 - - - - 0.82 0.4 DN40 48 3 - _� 21 0.2 ' 62375 275 17 -. 2.00 : 275 4 08ff i NSO tr0 3 71k...., ff8...... . .51 " 74' . El.0Z8 2.2 1.0 2.875 3.00 IRE 730 76 1.0 7622 0.5 �: a ps 0 fi t"�'-, 's', az 3 3.500 3.38 4.0 2.50 0.88 1.2 DN80 88.9 86 1.8 64 22 0.5 $25t3; $fl0 e '7 3 a o 51;: 00 73 /„/ i s : 108 fl 102 26 i,:. 76 a, 3«; h;. ::.. 102 4 4.500 4.00 6.7 3.00 5.6 4.00 1.00 DN100 114.3 102 3.0 76 2.5 102 25 5 X563 X138 12 6 325 8 3;, 488Li,,fc -10f1.k a�„ g 4.1 1,1 ,R i 5.- *g3 3.8 .... ' 5 ''1.9 5.500 1111E111111111E11111M'I. 6 9 DN125 139,7 6 9 - u 58.8 140;s 57 % < 4 °/ 40 v°." `% % ./ ' Eall 6 .. 5.50 18.3 3.50 11.7 5.50 22.7 1.00 DN150 140 8.3 89 5.3 140 10.3 25 6.500 5 43il 17 3.50, • T 4 %-$450 22.0 s1 165.1 l40 89 4; 8 4 25 20.4 38.7 11111111 DN200 108 9 3 111111111 17 6 L 8.515 81 X31..., . , 33 6 ,,,,„:„ a ,. kiln 2163„%•' 73 ' 0.5".�.. 176 ,, ,;. .. '5.2 • 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 2 ✓cta u I is c° victaulic.com • 5.0 PERFORMANCE Flow Data Size Frictional Resistance Equivalent of Straight Pipel No.002 Actual Elbows Straight Tee Nominal Outside No.001 No.003 Size Diameter 90°Elbow 45°Elbow Branch Run inches inches feet feet feet feet DN mm meters meters meters meters 1 1 660 DN32 424 -.. �,, /rir? ',--"-',,*ft, i, 1Y2 1.900 - - - - DN40 48.3 - - - - 2 \ 3:5 1,6,.-i-2, a� 21/2 2.875 4.3 2.2 10.8 4.3 73.0 1.3 0.7 3.3 1.3 a 3000 4:5 1�:- a ,. 761 ', 0 3.4„ ; 1 4 w4e,13Nfi5 1.4 ,,, . �y 3 3.500 5.0 2.6 13.0 5.0 DN80 88.9 [ 1.5 0.8 4.0 1.5 4250 64 15:3 64 ;: t .. 108A,., 2.t O 't,O9,,.:" _ 4.7 ..z . .20. 4 4.500 6.8 3.4 16.0 6.8 DN100 114.3 2.1 n1.0 4.9 2.1 itilt Iia 1.3 ." ,g.2.6 ' 'i "a i.,, 4 >i,, 2.60, 5.500 8.3 4.1 20.6 8.3 DN125 139.7 2.5 1.3 6.3 2.5 �t50 � / �,,,:,` �`':" ' 358$ `, ;o .--.---(;,,,,--,, ?,,,,i,;,:-. - - 7.6 ',,t,''''-:::;''''''./.9 6 6.625 1 10.0 5.0 25.0 10.0 DN150 168.3 1 3.0 1.5 7.6 3.0 //6500 98 , 49 s 24.5 9 �I651 3.0 .." i.S` J: 7.5 :!, 3® ` 8 8.625 13.0 5.0 33.0 13.0 DN200 219.1 4.0 1.5 10.1 4.0 a� ;- .. 5.., , r', , 851 �, 1�0 � ..33.0 R 13.0" 216,3''} E '^ 4.0 , : 10.1 4.0. 1 The flow data listed is based upon the pressure drop of Schedule 40 pipe. 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulie victaulic.com • • 6.0 NOTIFICATIONS General Notes NOTE:When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZTM Style 009N/009H couplings, use FireLockTM No.006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings. 7.0 REFERENCE MATERIALS 1264:Victaulic®FireLockTM Rigid Coupling Style 009N 10.02:Victaulic®FireLocknM Rigid Coupling Style 005H with Vic-PIusTm Gasket System 29.01:Victaulic®Terms and Conditions of Sale • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.03 1539 Rev N Updated 09/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 4 \iataulic" • • x » 4 ,. ,.„:1122 ;77-:,., m ; -4 i _4444 ; : '' f£L,s.j ; '',..L>,, ',1r:.1 ..... , r " .. • , , , r : tL1'CD 'Fire & Building 11121 Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services: Tel: (800)381-9312/Fax:(800)791-5500 BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical Description Data Tyco Fire& Building Products (TFBP) Sizes BlazeMaster CPVC Pipe and Fittings 3/4"to 3" , are designed exclusively for use in wet Maximum Working Pressure pipe automatic fire sprinkler systems. 175 psi They are made from a specially devel- „� oped thermoplastic compound com- Approvals posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, chloride(CPVC) resin and state of the LPCB,MEA,and the City of Los Ange- art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu- !; CPVC products are easier to install ary 2005 "Installation Instruction & than traditional steel pipe systems, Technical Handbook" for exact list- and at the same time,provide superior ing/approval information.) t _ heat resistance and strength as corn- Manufacture Source pared to traditional CPVC and PVC U.S.A. piping materials used in the plumbing trade. Various adapters are available Material to connect CPVC pipe to metallic pip- ing. All female pipe thread adapters • Pipe:ASTM F442, SDR 13.5 have brass inserts for durability. . Fittings: ASTM F438 (Sch. 40) and Grooved adapters connect directly to ASTM F439(Sch.80),ASTM F1970 grooved end valves and metallic pipe, with flexible grooved end couplings. Color Orange WARNING Tyco Fire&Building Products(TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster®is a registered trademark of Noveon IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFP1915 WATER NOMINAL AVERAGE AVERAGE WEIGHT FILLED WEIGHT FT.OF PIPE WEIGHT PER LIFT SIZE O.D. I.D. lbs./ft. lbs./ft. PER LIFT lbs. 3/4" 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4" 1.660" 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 2.20 1260 1084 2-1/2" 2.875" 2.423" 1.26 3.26 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1—PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH-1900, Rev. 0, January spection, testing, and maintenance of 2005"Installation Instruction&Techni- their fire protection system and de- cal Handbook". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys tem that it controls,permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni- toring proprietary and/or central sta- tion alarms. TFP1915 Page 3 of 6 - FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (TIO) (lb.) TEE 80000 3/4" 5/8" 40 0.11 J„/ TIO 80001 1" 11/16" 40 0.19 j. , 80002 1-1/4" 7/8" 40 0.26 .iI. 80003 1-1/2" 1-1/16" 80 0.51 •J ( 80004 2" 1-3/8" 80 0.90 • aw. 80005 2-1/2" 1-9/16" 80 1.59 T/O .11. TIO 80006 3" 1-13/16" 80 2.41 XxYxZ X Y Z 80132 3/4"x 3/4"x 1" 3/4" 3/4" 5/8" 40 0.14 80133 1"x 3/4"x 3/4" 9/16" 9/16" 3/4" 40 0.14 80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17 80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-1/4"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21 80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22 80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4"x 1-1/4"x 3/4" 5/8" 5/8" 7/8" 40 0.23 80262 1-1/4"x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26 Z 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" 1" 80 0.43 �i�„� TIO 80140 1-1/2"x 1-1/4"x 3/4" 9/16" 9/16" 1" 80 0.36 Mt". 80141 1-112"x 1-1/4"x 1" 9/16" 9/16" 1-1/16" 80 0.38 80263 1-1/2"x 1-1/2"x 3/4" 9/16" 9/16" 1" 80 0.36 X.■■.Y 80264 1-1/2"x 1-1/2"x 1" 9/16" 9/16" 1-1/16" 80 0.38 ������' 80275 1-1/2"x 1-1/2"x 1-1/4" 7/8" 7/8" 1" 80 0.45 T/O •• T/O 80265 2"x 2"x 3/4" 3/4" 3/4" 1-3/8" 80 0.61 80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66 80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74 80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78 80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43 80272 2-1/2"x 2-1/2"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46 80273 2-1/2"x 2-1/2"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48 80276 2-1/2"x 2-1/2"x 2" 1-9/16" 1-9/16" 1-9/16" 80 1.50 80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28 80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25 80269 3"x 3"x 2-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.44 CROSS&REDUCING CROSS 80009 3/4" 9/16" 40 0.13 80010 1" 11/16" 40 0.23 ..-1==.,....„,11 = T/O 80011 1-1/4" 15/16" 40 0.34 11111111111M.■ 80012 1-1/2" 1-1/16" 80 0.67 •�iilj•■ 80014 2-1/2" 1-9/16" 80 1.91 11 11 TIO 80008 3" 1-13/16" 80 2.89 T/O ■■ T/O 80015 1"x 1"x 3/4"x 3/4" 7/8" 40 0.28 80025 3/4" 5/8" 40 0.09 90°ELBOW& REDUCING ELBOW 80026 1" 3/4" 40 0.14 80027 1-1/4" 7/8" 40 0.21 X 80028 1-1/2" 1-1/16" 80 0.40 /.,i T/O 80029 2" 1-5/16" 80 0.79 j�• 80030 2-1/2" 1-9/16" 80 1.14 9.�- 80031 3" 1-13/16" 80 1.82 -VIP.Y (umon XxY X Y T/0 80032 1"x 3/4" 11/16" 13/16" 40 0.16 FIGURE 2-FITTING DIMENSIONS(Part 1 of 4) Page 4 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (T/O) (lb.) 45"ELBOW 80050 3/4" 3/8" 40 0.08 T/O 80051 1" 3/8" 40 0.11 80052 1-1/4" 3/4" 40 0.20 ,A• 80053 1-1/2" 1/2" 80 0.31 T/O ** 80054 2" 3/4" 80 0.56 **Tim 80055 2-1/2" 13/16" 80 0.89 80056 3" 1" 80 1.19 80075 3/4" 1/8" 40 0.07 COUPLING& 80076 1" 1/8" 40 0.11 REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12 al 80078 1-1/2" 3/16" 80 0.25 I80079 2" 3/16" 80 0.38 80080 2-1/2" 1/4" 80 0.67 T/O 80081 3" 3/16" 80 0.91 80220 1"x 3/4" 1/8" 40 0.08 80200 1"x 3/4" 7/16" 40 0.04 80201 1-1/4"x 3/4" 1/2" 40 0.11 80202 1-1/4"x 1" 5/16" 40 0.12 80203 1-1/2"x 3/4" 5/8" 80 0.16 80204 1-1/2"x 1" 1/2" 80 0.14 REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17 80206 2"x 3/4" 13/16" 80 0.27 1.r....,4/4 80207 2"x 1" 11/16" 80 0.26 111 80208 2"x 1-1/4" 9/16" 80 0.24 ..J' 80209 2"x 1-1/2" 7/16" 80 0.19 --I T/O 80215 2-1/2"x 1" 15/16" 80 0.42 80214 2-1/2"x 1-1/4" 13/16" 80 0.45 80213 2-1/2"x 1-1/2" 11/16" 80 0.46 80211 2-1/2"x 2" 5/8" 80 0.29 80210 3"x 2" 3/4" 80 0.72 80212 3"x 2-1/2" 1/2" 80 0.47 CAP 80100 3/4" 5/16" 40 0.04 80101 1" 3/8" 40 0.06 80102 1-1/4" 7/16" 40 0.10 80103 1-1/2" 11/16" 80 0.20 i ••I I 80104 2" 5/8" 80 0.31 T/O-I F- 80105 2-1/2" 7/8" 80 0.58 80106 3" 1" 80 0.88 GROOVED T/O PIPE O.D. COUPLING ADAPTER 80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 80 0.95 PIPE 80162 2"x 2"Groove 2-5/16" 2"(2.375") 80 1.42 O.D. r�r'w'mo 80163 2-1/2"x 2-1/2"Groove 2-5/16" 2-1/2"(2.875") 80 2.28 �iii��i 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00 T/O--I 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28 FIGURE 2-FITTING DIMENSIONS(Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (TIO) (lb.) SPRINKLER HEAD ADAPTER 80175E 3/4"x 1/2"NPT 7/16" 80 0.20 80176E 1"x 1/2"NPT 7/16" 80 0.22 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16 80179 1"x 3/4"NPT 13/16" 40 0.43 T/O SPRINKLER HEAD ADAPTER 80175W 3/4"x 1/2"NPT 1/2" 40 0.19 80176W 1"x 1/2"NPT 1/2" 40 0.18 - T/O SPRINKLER HEAD ADAPTER(SPIGOT) �-) 80177L 3/4"x 1/2"NPT 1/2" 40 0.16 80178 1"x 1/2"NPT 9/16" 40 0.20 si 80180 1"x 3/4"NPT 7/8" 40 0.40 -I T/O FEMALE ADAPTER ,,\\ 80142 3/4"x 3/4"NPT 13/16" 40 0.41 801451'x 1"NPT7/8" 400.63 801461-1/4"x 1-1/4"NPT1-1/8" 401.03 1111111`�` 80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42 rA�Aa;N\\\ 80148 2"x 2"NPT 1-11/16" 80 2.66 T/0 MALE ADAPTER I1I110 80157 80158 3/4"x 3/4"NPT 1-5/16" 40 0.33 1'x 1"NPT 1-3/8" 40 0.56 a'2y T/O XxYxZ X Y Z SPRINKLER HEAD 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22 ADAPTER TEE Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29 all.4 T/O 80249 1"x 1"x 1"NPT 15/16" 15/16" 1-9/16" 40 0.73 ---4I\I% 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16" 40 0.30 ,0[.......,_ -MI- 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5/16" 40 0.31 X =MEM,,I 80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43 wiW 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46 T/0 •• T/O 80258 2"x 1-1/2"x 1/2"NPT 1/2" 5/8" 1-11/16" 80 0.56 80253 2"x 2"x 1/2"NPT 1/2" 1/2" 1-11/16" 80 0.62 FIGURE 2—FITTING DIMENSIONS(Part 3 of 4) Page 6 of 6 TFP1915 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (T/O) (ib.) BACK-TO-BACK TEE X x Y x Z X Y,Z x ��J!IL ' r!o =" 80459 1x 1/2"NPTx 1/2"NPT 5/8" 1-5/16" 40 048 Wm11IIII u110/,L001U!z 80460 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 T/O •• T/O BACK-TO-BACK CROSS X x Y x Z x W X,Y Z,W x 1111 T/O Z J 0-- IIIIIIINMMMI llll 1111 .1111 w 80462 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 �a`f: 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47 I/O 1111 T/O T/0 SPRINKLER HEAD X x Y X Y ADAPTER 90°ELBOW Y 7`I T/O ht�Jl 80199 3/4"x 1/2"NPT 9/16" 1" 40 0.20 ai0 80198 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26 X444'-X 80196 1"x 3/4"NPT 1-1/16" 1-7/16" 40 0.26 T/O FIGURE 2—FITTING DIMENSIONS(Part 4 of 4) by TFBP to be defective shall be either of merchantability and fitness for a par- Limited repaired or replaced, at TFBP's sole ticular ourpose. Y option. TFBP neither assumes, nor This limited warranty sets forth the ex Warrant authorizes any person to assume for it, clusive remedy for claims based on any other obligation in connection with failure of or defect in products, materi- Products manufactured byTyco Fire& parts of rod Y the sale of products or P als or components, whether the claim Building Products (TFBP) are war- ucts.TFBP shall not be responsible for ranted solely to the original Buyer for sprinkler system design errors or inac- is made in contract, tort, strict liability or any other legal theory. ten(10)years against defects in mate- curate or incomplete information sup rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law.The invalidity, in under normal use and service. Thispart, of anyportion of this liable, in whole or In no event shall TFBP be ab warranty will expire ten (10) years Y warrant will not affect the remainder. from date of shipment by TFBP. No contract, tort, strict liability or under warranty is given for products or com any other legal theory, for incidental, ponents manufactured by companies indirect,special or consequential dam not affiliated byownershipwith TFBP ages, including but not limited to labor charges, regardless of whether TFBP or for products and components which have been subject to misuse,improper was informed about the possibility of installation, corrosion, or which have such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount fied or repaired in accordance with ap— plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and/or the of any and all other warranties. ex- standards of any other Authorities press or impliedincluding warranties Having Jurisdiction. Materials found TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 AFP SYSTEMS, INC. • 19435 S.W. 129th AVENUE TUALATIN,OR 97062 HYDRAULIC CALCULATIONS FOR Pape Material Handling RECEIVED Area #1 APR 17 2019 FILE NUMBER: Area #1 CITY OF TIGARD DATE: APR 12, 2019 BUILDING DIVISION -DESIGN DATA- OCCUPANCY CLASSIFICATION: Group "A" Plastics and Rubber Tires in Racks to Max. 20 ft. DENSITY: .976 gpm/sq.ft. (Min. 15 psi) AREA OF APPLICATION: 1200 sq. ft. (12 Sprinklers) COVERAGE PER SPRINKLER: 100 sq.ft. Max. NUMBER OF SPRINKLERS CALCULATED: 12 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 1198.8 gpm TOTAL WATER REQUIRED (including hose) : 1448.7 gpm FLOW AND PRESSURE (@ BOR) : 1198.7 gpm @ 34.7 psi SPRINKLER ORIFICE SIZE: K25.2 NAME OF CONTRACTOR: AFP Systems, Inc. DESIGN/LAYOUT BY: R. Berry AUTHORITY HAVING JURISDICTION: City Of Tigard CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 38040986 ) HRS SYSTEMS, INC. CC5433OPE ORECADDI 11;1c�, 0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 . DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 78.0 64.0 1803.0 68.7 1448.7 58.7 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 1448.7 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1198.7 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 21.5 K=25.20 15.1 98.0 2 21.5 K=25.20 15.2 98.3 3 21.5 - - - - 15.8 - - - 4 19.8 - - - - 17.4 - - - 5 21.5 K=25.20 15.8 100.2 6 21.5 K=25.20 15.9 100.5 7 19.0 - - - - 19.5 - - - 8 21.5 K=25.20 15.0 97.6 9 21.5 K=25.20 15.1 97.9 10 21.5 - - - - 16.1 - - - 11 19.8 - - - - 17.6 - - - 12 21.5 K=25.20 16.1 101.0 13 21.5 K=25.20 16.2 101.4 14 19.0 - - - - 19.5 - - - 15 21.5 K=25.20 15.7 99.8 16 21.5 K=25.20 15.8 100.1 17 21.5 - - - - 16.4 - - - 18 19.8 - - - 17. - - - - 19 21.5 - K=25.20 16.3 101 . 9 20 21.5 K=25.20 16.4 102.1 21 19.0 - - - - 19.5 - - - 22 19.8 - - - - 18.3 - - - 23 19.0 - - - - 19.6 - - - 24 19.8 - - - - 18.8 - - - 25 19.0 - - - - 19.7 - - - 26 19.8 - - - - 19.1 - - - 27 19.0 - - - - 19.9 - - - 28 19.8 - - - - 19.4 - - - 29 19.0 - - - - 20.0 - - - 30 19.8 - - - - 19.5 - - - 31 19.0 - - - - 20.2 - - - 32 19.8 - - - - 19.7 - - - 33 19.0 - - - - 20.4 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 34 19.8 - - - - 19.8 - - - 35 19.0 - - - - 20. 6 - - - 36 19.8 - - - - 19.9 - - - 37 19.0 - - - - 20.9 - - - 38 19.8 - - - - 19.9 - - - 39 19.0 - - - - 21.1 - - - A 17.3 - - - - 24.4 - - - B 0.0 - - - - 32.4 - - - C 0.0 - - - - 34.0 - - - D 0.0 - - - - 34.7 - - - E 0.0 - - - - 39.4 - - - F 0.0 - - - - 47.6 - - - SOURCE -23.0 SOURCE 58.7 1198.7 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 1 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -98.0 3.334 PL 11.25 PF 0.1 1 21.5 25.2 15.1 98.0 3.6 120 FTG ---- PE 0.0 2 21.5 25.2 15.2 98.3 0.009 TL 11.25 PV Pipe: 2 -196.4 3.334 PL 4.83 PF 0.6 2 21.5 25.2 15.2 98.3 7.2 120 FTG T PE 0.0 3 21.5 0.0 15.8 0.0 0.032 TL 17.83 PV Pipe: 3 -200.6 3.334 PL 1.67 PF 0.9 3 21.5 0.0 15.8 0.0 7.4 120 FTG 2T PE 0.7 4 19.8 0.0 17.4 0.0 0.033 TL 27.67 PV Pipe: 4 4.3 3.334 PL 6.42 PF 0.0 3 21.5 0.0 15.8 0.0 0.2 120 FTG T PE 0.0 5 21.5 25.2 15.8 100.2 0.000 TL 19.42 PV Pipe: 5 -95.9 3.334 PL 11.25 PF 0.1 5 21.5 25.2 15.8 100.2 3.5 120 FTG ---- PE 0.0 6 21.5 25.2 15.9 100.5 0.008 TL 11.25 PV Pipe: 6 -196.4 3.334 PL 41.83 PF 2.5 6 21.5 25.2 15.9 100.5 7.2 120 FTG 2E2T PE 1.1 7 19.0 0.0 19.5 0.0 0.032 TL 77.83 PV Pipe: 7 -97.6 3.334 PL 11.25 PF 0.1 8 21.5 25.2 15.0 97.6 3.6 120 FTG ---- PE 0.0 9 21.5 25.2 15.1 97.9 0.009 TL 11.25 PV Pipe: 8 -195.5 3.334 PL 7.33 PF 1.0 9 21.5 25.2 15.1 97.9 7.2 120 FTG 2ET PE 0.0 10 21.5 0.0 16.1 0.0 0.032 TL 30.33 PV Pipe: 9 -182.8 3.334 PL 1.67 PF 0.8 10 21.5 0.0 16_1 0-.0 6.7___ 120 FTG 2T PE 0.7 11 19.8 0.0 17.6 0.0 0.028 TL 27.67 PV Pipe: 10 -12.8 3.334 PL 8.92 PF 0.0 10 21.5 0.0 16.1 0.0 0.5 120 FTG 2ET PE 0.0 12 21.5 25.2 16.1 101.0 0.000 TL 31.92 PV Pipe: 11 -113.8 3.334 PL 11.25 PF 0.1 12 21.5 25.2 16.1 101.0 4.2 120 FTG ---- PE 0.0 13 21.5 25.2 16.2 101.4 0.012 TL 11.25 PV Pipe: 12 -215.2 3.334 PL 40.00 PF 2.2 13 21.5 25.2 16.2 101.4 7.9 120 FTG ET PE 1.1 14 19.0 0.0 19.5 0.0 0.038 TL 58.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 13 -99.8 3.334 PL 11.25 PF 0.1 15 21.5 25.2 15.7 99.8 3.7 120 FTG ---- PE 0.0 16 21.5 25.2 15.8 100.1 0.009 TL 11.25 PV Pipe: 14 -199. 9 3.334 PL 4.83 PF 0.6 16 21.5 25.2 15.8 100.1 7.3 120 FTG T PE 0.0 17 21.5 0.0 16.4 0.0 0.033 TL 17.83 PV Pipe: 15 -228.4 3.334 PL 1.67 PF 0.6 17 21.5 0.0 16.4 0.0 8.4 120 FTG T PE 0.7 18 19.8 0.0 17.7 0.0 0.042 TL 14.67 PV Pipe: 16 28.5 3.334 PL 6.42 PF 0.0 17 21.5 0.0 16.4 0.0 1.0 120 FTG T PE 0.0 19 21.5 25.2 16.3 101.9 0.001 TL 19.42 PV Pipe: 17 -73.4 3.334 PL 11.25 PF 0.1 19 21.5 25.2 16.3 101. 9 2.7 120 FTG ---- PE 0.0 20 21.5 25.2 16.4 102.1 0.005 TL 11.25 PV Pipe: 18 -175.4 3.334 PL 41.83 PF 2.0 20 21.5 25.2 16.4 102.1 6.4 120 FTG 2E2T PE 1.1 21 19.0 0.0 19.5 0.0 0.026 TL 77.83 PV Pipe: 19 -94.8 3.334 PL 59.33 PF 0. 9 22 19.8 0.0 18.3 0.0 3.5 120 FTG 4T PE 0.4 23 19.0 0.0 19.6 0.0 0.008 TL 111.33 PV Pipe: 20 -73.8 3.334 PL 59.33 PF 0.6 24 19.8 0.0 18.8 0.0 2.7 120 FTG 4T PE 0.4 25 19.0 0.0 19.7 0.0 0.005 TL 111.33 PV Pipe: 21 -58.4 3.334 PL 59.33 PF 0.4 26 19.8 0.0 19.1 0.0 2.1 120 FTG 4T PE 0.4 27 19.0 0.0 19.9 0.0 0.003 TL 111.33 PV Pipe: 22 -49.0 3.334 PL 59.33 PF 0.3 28 19.8 0.0 19.4 0.0 1.8 120 FTG 4T PE 0.4 29 19.0 0.0 20.0 0.0 0.002 TL 111.33 PV Pipe: 23 -51.3 3.334 PL 62.33 PF 0.3 30 19.8 0.0 19.5 0.0 1.9 120 FTG 2E4T PE 0.4 31 19.0 0.0 20.2 0.0 0.003 TL 124.33 PV Pipe: 24 -52.9 3.334 PL 59.33 PF 0.3 32 19.8 0.0 19.7 0.0 1.9 120 FTG 4T PE 0.4 33 19.0 0.0 20.4 0.0 0.003 TL 111.33 PV Pipe: 25 -62.7 3.334 PL 59.33 PF 0.4 34 19.8 0.0 19.8 0.0 2.3 120 FTG 4T PE 0.4 35 19.0 0.0 20. 6 0.0 0.004 TL 111.33 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 , DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 26 -76.3 3.334 PL 59.33 PF 0.6 36 19.8 0.0 19.9 0.0 2.8 120 FTG 4T PE 0.4 37 19.0 0.0 20.9 0.0 0.006 TL 111.33 PV Pipe: 27 -92.4 3.334 PL 59.33 PF 0.9 38 19.8 0.0 19.9 0.0 3.4 120 FTG 4T PE 0.4 39 19.0 0.0 21.1 0.0 0.008 TL 111.33 PV Pipe: 28 -200.6 4.310 PL 11.83 PF 0.1 4 19.8 0.0 17.4 0.0 4.4 120 FTG ---- PE 0.0 11 19.8 0.0 17.6 0.0 0.010 TL 11.83 PV Pipe: 29 -383.4 4.310 PL 4.83 PF 0.2 11 19.8 0.0 17 .6 0.0 8.4 120 FTG ---- PE 0.0 18 19.8 0.0 17.7 0.0 0.032 TL 4.83 PV Pipe: 30 -611.8 4.310 PL 8.33 PF 0.6 18 19.8 0.0 17.7 0.0 13.5 120 FTG ---- PE 0.0 22 19.8 0.0 18.3 0.0 0.075 TL 8.33 PV Pipe: 31 -517.0 4.310 PL 8.33 PF 0.5 22 19.8 0.0 18.3 0.0 11.4 120 FTG ---- PE 0.0 24 19.8 0.0 18.8 0.0 0.055 TL 8.33 PV Pipe: 32 -443.1 4.310 PL 8.33 PF 0.3 24 19.8 0.0 18.8 0.0 9.7 120 FTG ---- PE 0.0 26 19.8 0.0 19.1 0.0 0.041 TL 8.33 PV Pipe: 33 -384.7 4.310 PL 8.33 PF 0.3 26 19.8 0.0 19.1 0.0 8.5 120 FTG ---- PE 0.0 28 19.8 0.0 19.4 0.0 0.032 TL 8.33 PV Pipe: 34 -335.7 4.310 PL 4.83 PF 0.1 28 19.8 0.0 19.4 0.0 7.4 120 FTG ---- PE 0.0 30 19.8 0.0 19.5 0.0 0.025 TL 4.83 PV Pipe: 35 -284.4 4.31-0 PL 11.83 PF 0.2 30 19.8 0.0 19.5 0.0 6.3 120 FTG ---- PE 0.0 32 19.8 0.0 19.7 0.0 0.018 TL 11.83 PV Pipe: 36 -231.5 4.310 PL 8.33 PF 0.1 32 19.8 0.0 19.7 0.0 5.1 120 FTG ---- PE 0.0 34 19.8 0.0 19.8 0.0 0.012 TL 8.33 PV Pipe: 37 -168.7 4.310 PL 8.33 PF 0.1 34 19.8 0.0 19.8 0.0 3.7 120 FTG ---- PE 0.0 36 19.8 0.0 19.9 0.0 0.007 TL 8.33 PV Pipe: 38 -92.4 4.310 PL 8.33 PF 0.0 36 19.8 0.0 19.9 0.0 2.0 120 FTG ---- PE 0.0 38 19.8 0.0 19.9 0.0 0.002 TL 8.33 PV 1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 39 -196.4 6.357 PL 6.25 PF 0.0 7 19.0 0.0 19.5 0.0 2.0 120 FTG ---- PE 0.0 14 19.0 0.0 19.5 0.0 0.001 TL 6.25 PV Pipe: 40 -411.6 6.357 PL 6.25 PF 0.0 14 19.0 0.0 19.5 0.0 4.2 120 FTG ---- PE 0.0 21 19.0 0.0 19.5 0.0 0.005 TL 6.25 PV Pipe: 41 -587.0 6.357 PL 10.42 PF 0.1 21 19.0 0.0 19.5 0.0 5.9 120 FTG ---- PE 0.0 23 19.0 0.0 19.6 0.0 0.010 TL 10.42 PV Pipe: 42 -681.8 6.357 PL 8.33 PF 0.1 23 19.0 0.0 19.6 0.0 6.9 120 FTG ---- PE 0.0 25 19.0 0.0 19.7 0.0 0.014 TL 8.33 PV Pipe: 43 -755.6 6.357 PL 8.33 PF 0.1 25 19.0 0.0 19.7 0.0 7.6 120 FTG ---- PE 0.0 27 19.0 0.0 19.9 0.0 0.017 TL 8.33 PV Pipe: 44 -814.1 6.357 PL 8.33 PF 0.2 27 19.0 0.0 19. 9 0.0 8.2 120 FTG ---- PE 0.0 29 19.0 0.0 20.0 0.0 0.019 TL 8.33 PV Pipe: 45 -863.1 6.357 PL 8.33 PF 0.2 29 19.0 0.0 20.0 0.0 8.7 120 FTG ---- PE 0.0 31 19.0 0.0 20.2 0.0 0.021 TL 8.33 PV Pipe: 46 -914.4 6.357 PL 8.33 PF 0.2 31 19.0 0.0 20.2 0.0 9.2 120 FTG ---- PE 0.0 33 19.0 0.0 20.4 0.0 0.024 TL 8.33 PV Pipe: 47 -967.3 6.357 PL 8.33 PF 0.2 33 19.0 0.0 20.4 0.0 9.8 120 FTG ---- PE 0.0 35 19.0 0.0 20.6 0.0 0.026 TL 8.33 PV Pipe: 48 -1030.0 6.357 PL 8.33 PF 0.2 35 19.0 0.0 20.6 0.0 10.4 120 FTG ---- PE 0.0 37 19.0 0.0 20.9 0.0 0.030 TL 8.33 PV Pipe: 49 -1106.4 6.357 PL 8.33 PF 0.3 37 19.0 0.0 20.9 0.0 11.2 120 FTG ---- PE 0.0 39 19.0 0.0 21.1 0.0 0.034 TL 8.33 PV Pipe: 50 -1198.8 6.357 PL 18.75 PF 2.5 39 19.0 0.0 21.1 0.0 12.1 120 FTG 2ET PE 0.7 A 17.3 0.0 24.4 0.0 0.039 TL 63.75 PV Pipe: 51 -1198.8 6.065 PL 11.67 PF 0. 6 A 17.3 0.0 24.4 0.0 13.3 120 FTG ---- PE 7.5 B 0.0 0.0 32.4 0.0 0.049 TL 11.67 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 j DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 52 FIXED PRESSURE LOSS DEVICE C 0.0 0.0 34.0 0.0 1.6 psi, 1198.8 gpm B 0.0 0.0 32.4 0.0 Pipe: 53 -1198.8 6.065 PL 2.75 PF 0.6 C 0.0 0.0 34.0 0.0 13.3 120 FTG B PE 0.0 D 0.0 0.0 34.7 0.0 0.049 TL 12.75 PV Pipe: 54 -1198.8 6.280 PL 101.00 PF 4.7 D 0.0 0.0 34.7 0.0 12.4 140 FTG E2L PE 0.0 E 0.0 0.0 39.4 0.0 0.031 TL 151.00 PV Pipe: 55 FIXED PRESSURE LOSS DEVICE F 0.0 0.0 47.6 0.0 8.2 psi, 1198.8 gpm E 0.0 0.0 39.4 0.0 Pipe: 56 -1198.7 6.280 PL 37.00 PF 1.2 F 0.0 0.0 47.6 0.0 12.4 140 FTG ---- PE 10.0 SOURCE -23.0 SRCE 58.7 (N/A) 0.031 TL 37.00 PV NOTES (HASS) : (1) Calculations were performed by the HASS 8.8 computer program in accordance with NFPA13 (2016) under license no. 38040986 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.004 gpm and a maximum imbalance at any node of 0.171 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 13.5 ft/sec at pipe 30. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node SOURCE under full flow conditions is 66.69 psi with a flow of 1606.58 gpm. 3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 (6) PIPE FITTINGS TABLE User Pipe Table Name: EDDY FLOW.PIP PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 6.065 14.00 30.00 9.00 32.00 10.00 3.00 28.00 28.00 30.00 PAGE: B MATERIAL: THNWL HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 6.357 10.00 25.00 5.00 40.00 11.10 4.00 35.00 35.00 38.00 PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N Ell Tee LngEll ChkVly BfyVly GatVly NPTee 6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00 PAGE: G MATERIAL: Eddyflow HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 3.334 5.00 13.00 2.60 23.99 14.99 1.50 19.49 19.49 22.49 4.310 6.80 16.00 3.40 30.66 4.50 2.79 27.87 27.87 27.87 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 WATER SUPPLY ANALYSIS Static: 78.00 psi Resid: 64.00 psi Flow: 1803.0 gpm 100.0 LEGEND 1 I Available pressure 80.0 C 68.66 psi @ 1448.7 gpm G A 2 a Required pressure U 1A 1 �.� 58.70 psi @ 1448.7 gpm lllll G _ E 60.0 ` 1A 2 Avail. OnSite Demand Press. 2A g 2 68.66 psi @ 1198.7 gpm P R 2A J Req. OnSite Demand Press. E 58.70 psi @ 1198.7 gpm S 40.0 S A. Source Supply Curve U B. System Demand Curve R C. Available at Source E 20.OB P s i -14.7 I I I I I I I 1 400600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source 1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 I DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 SPRINKLER SYSTEM DIAGRAM WITH FLOWPLOT 2 3 <4> 5 <5> 6 196.4 210.6 4.3 • • <6> 196200.6 8 - • 10 111-2- <10> 12 7 97.6 195.5 182.8 8 1111wwww- <39> <11> <29> 196.4 113.8 383.4 1A 16 17 <15> ....1"---.......18 14 99.8 228.4 • <16> 28.5 c 1J <40> <17> 20 <30> • 411.6 73.4 611.8 <18> 21/1 ^ 175.4 2n 2 587.0 94.8 517.0 2A 2A 681 .8 73 8 443.1 2A 2A /1<43> <21> �<33> 755.6 58.4 384.7 2" 2" A<44> <22> A<34> 814.1 49.0 335.7 2A 3A /1<45> <23> �<35> 863.1 51.3 284.4 3A 3y% 914.4 52 9 231 .5 3A 3A "<47> <25> <37> 967.3 62.7 168.7 3A <38> 3A 92.4 SOURCE SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12 DATE: 4/12/2019 C:\CALCS\PAPE MATERIAL HANDLING\AREA #1.SDF JOB TITLE: Pape Material Handling Area #1 WATER SUPPLY CURVE 84+ *\\\\\\ 77+ \\\\\\\ \\\\\\\ I \\\\\\ I \\\\\\\ 70+ \\\\\\\ I 0 \\\\\\\ \\\\\\ 64.0 psi @ 1803 gpm-> * 63+ Flow Test Point I X P 56+ R I E I S I S 49+ U I R I E I 42+ ( I P I S I I 35+ I 28+ 21+ 14+ LEGEND I " I X = Required Water Supply 58.70 psi @ 1448.7 gpm 7+ I 0 = Available Water Supply " I 68. 66 psi @ 1448.7 gpm 0++-+---+----+ + + + + + + 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM)