SIEMENS Data Sheet
Fire Safety& Security Products
Intelligent Detection Devices
TRI Series — Intelligent Initiating Interface Modules
[For use with FireFinder® XLS and MXL Panels]
Models TRI-D, TRI-R and TRI-S
ARCHITECT AND ENGINEER SPECIFICATIONS
• Used as an intelligent initiating interface module for the
FireFinder XLS and MXL fire-alarm control panels(FACPs)
• Interfaces and supervises normally open (N.0)contacts
• Integral single-pole,double-throw(SPDT)relay(up to 4 amps),Model TRI-R
• Dual input for Model TRI-D
• Multi-color light-emitting diode(LED)indicates detector status
(green,amber,red)
• Simple front-end access to programming port and wiring terminals
�, • v k ,
• Mounts in a 4"-square,2-1/8"-deep standard or double-gang box =W•
�;* w
• Dynamic supervision F
• 5-x-5-inch faceplate included }fl44
• Two-wire operation '.
• Compatible with Model DPU or FPI-32 field programmer/tester
• Electronic-address programming is simple and dependable
• aUL Listed,€ULC Listed;
CSFM and NYC Fire Department Approved
Product Overview
The Model TRI-series of intelligent interface The sole purpose of Model TRI-S is to monitor and
modules from Siemens—Fire Safety is designed to report the status of the contact,while Model TRI-R
provide the means of interfacing direct shorting incorporates an addressable'Form C'relay. The
devices to Model MLC for the FireFinder XLS FACP, relay and contact device input for Model TRI-R are
or to Model ALD for the MXL system, respectively. controlled at the same address. The relay and input
The Model TRI-series of intelligent interface contact can be controlled as a separate function.
modules provides the most advanced method of The relay is typically used where control or shunting
address programming and supervision—combined of external equipment is required.
with sophisticated FACP communication. Each Model TRI-D is a dual-input module that is designed to
Model TRI-series interface module incorporates a supervise and monitor two (2) sets of dry contacts.
microcomputer chip. In turn,the microcomputer- Model TRI-D requires two(2) address settings. Model
chip technology and its sophisticated bi-directional TRI-D is ideal for monitoring a waterflow switch and its
communication capabilities with the FACP,achieve respective valve tamper switch.
the state of an'Intelligent Device.' Model TRI-series has a multi-color LED that flashes
Specifications green when operating normally;amber, if unit is in
The Model TRI series of intelligent interface trouble condition, and red to indicate a change of
modules is available in three (3) models. Models status command. Model TRI-D flashes two (2)times—
once for each address, and the red LED of Model TRI-R
TRI-S and TRI-R are designed to monitor a normally
indicates a change of state in the relay.
open (N.O.) dry contact. The interface module
reports the contact's status to the FACP.
TRI Series—Intelligent Initiating Interface Modules 61 79
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued) Electrical Ratings
The microcomputer chip for the Model TRI-series of Current Draw: 1.5mA
devices has the capacity of storing—in memory— [Active or Standby]
identification information as well as important Model TRI-R Relay Ratings:
operating status information. 4A, 125VAC
Resistive: 4A,30VDC
Siemens—Fire Safety innovative technology allows
all Model TRI-series intelligent interface modules to 3.5A, 120VAC[0.6 P.F]
be programmed and tested,via Model DPU or the 3.OA,30VDC[0.6 P.F]
Inductive: 2.0A, 120VAC[0.4 P.F]
FPI-32 Programmer I Tester. Each of these z.oA, 120VAC[0.35 P.F]
programmer I testers is a compact, portable and 2.0A, 120VAC[0.35 P.F]
menu-driven accessory that makes programming
and testing an interface device faster,easier and
more dependable than previous methods.
Mounting Diagram
Model DPU or the FPI-32 eliminates the need for
mechanical addressing mechanisms (such as: MOIJNTING SLOTS
FOR 4-INCH
program jumpers, DIP switches, or rotary dials), SWITCHBO
since either programmer/tester device
electronically sets the address of the Model TRI-
series into the interface's microcomputer-chip, nonaf
-
volatile memory. Vibration, corrosion and other �_� TRI-s/a f R
conditions that deteriorate mechanical addressing I I MODULE
mechanisms are no longer a cause for concern. 11[=1 �"�p
47 MOUNTING
The Model TRI-series of intelligent interface HOLES FOR
modules is fitted with screw terminals for swITCHPLarE
connection to an addressable circuit,and is fully .Ah__
compatible on the same circuit with all intelligent
Model FP; Model IL and Model ID-60-series Cs\ Q • 0
detectors; Model MSI Series addressable manual
stations, or any other addressable intelligent M4UNTINGSIOTS
modules,such as Model CZM or Model ICP. FOR DOUBLE-GANG
SV 1TCHBOX
All Model TRI-series intelligent interface modules
are®UL and 4 ULC Listed.
Details for Ordering
Model Part Description Shipping Weight
Number Number Oz. Kg.
Dual-Input Intelligent i
TRI-D 500-896226 7 0.2
Interface Module
Single-Input[wl relay]
TRI-R 500-896224 Intelligent Interface 7 0.2
Module
Single-Input
TRI-S 500-896225 Intelligent Interface 7 0.2
Module
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information,refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park,NJ 07932 Brampton,Ontario
Building Technologies Division Tel:(973)593-2600 (sii.rs) L6T 5E4/Canada July 2012
FAX:(908)547-6877 Printed in U.S.A. Tel:(905)799-9937 Supersedes sheet dated 5/06
(Rev.Ii
URL:www.usa.Siemens.com/Fire FAX:(905)799-9858