Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications (40)
1A BALTIMORE RECEIVED C AIRCOIL COMPANI0I � APR 112019 CITY OF TIGARD BUILDING DIVISION Mechanical Specifications 4-8-2019 Customer: Willamette HVAC,LLC Project: Executive Building Purchase Order No: Engineer: BAC Order# Q19053742903 All Information is per Unit Quantity:1 Model FXV-0806A-20D-K CLOSED CIRCUIT COOLING TOWER CTI Certification: The thermal performance of this BAC unit has been certified through performance tests conducted by the Cooling Technology Institute in accordance with their standard STD-201 RS. Your equipment may be selected for factory-testing to verify CTI certified performance. Such certification by an independent third party assures engineers and users that the published thermal capacities accurately reflect the actual unit performance. CTI certification eliminates the additional costs of on-site,individual unit testing,oversizing the equipment or operating cost penalties from deficient equipment. Materials of Construction: All structural steel components are constructed from G-235(Z700 metric)hot-dip galvanized steel.The edges of the hot-dip galvanized steel components are given a protective coat of zinc-rich compound.The basin includes a depressed section with drain/clean-out connection and the areas under the fill sections are sloped toward the depressed section for easy cleaning. The casing is constructed entirely from heavy gauge,G-235(Z700 metric)hot-dip galvanized steel panels.Hinged access doors are provided on each side wall of the tower for access to the eliminators and the fan plenum section for all cells.The doors are made of a steel frame matching the unit construction. The air inlet louvers are constructed of PVC honeycomb shape louver which also act as an air inlet screen and block sunlight to the basin and the front of the fill. Fan Type: The unit is provided with the standard fan to maximize the capacity. The fan is driven by the BALTIDRIVE Power Train. This drive system consists of cast aluminum sheaves located on minimum shaft centerline distances. A premium efficient fan motor provides maximum performance and is backed by BAC's comprehensive 5-year motor and fan drive warranty. Fan Guard(s): A heavy gauge,G-235(Z700 metric)hot-dip galvanized steel wire fan guard is provided over each fan cylinder. Fill: The BACross®Fill and integral drift eliminators are formed from self-extinguishing(per ASTM D-568)polyvinyl chloride(PVC),having a flame spread rating of 5 per ASTM Standard E84-77a,and are impervious to rot,decay,and fungus or biological attack.The fill is elevated above the cold water basin floor to facilitate cleaning. This fill is suitable for a maximum entering water temperature of 130°F(54.44°C). The eliminators are designed to effectively strip entrained moisture from the leaving airstream with a minimum of air resistance. Coil Type: The coil is suitable for cooling fluids compatible with carbon steel in a closed system. The coil(s)will be constructed with continuous 1.05"O.D. all prime surface steel tubes continuously formed and bent in a serpentine shape,encased in steel framework.The entire assembly is hot-dip galvanized after fabrication.Coil will be designed for free liquid drainage.Coil has a maximum allowable working pressure of 300 psig(2170 kPa) and is tested at 375 psig(2685 kPa)air pressure under water. The system should have a vent placed at the highest point in the installation to facilitate filling and drainage(provided and installed by others). Equipment Structure: The structure of this product has been designed and analyzed in accordance with the wind and seismic load requirements of the 2006 IBC,2009 IBC,2012 IBC,2015 IBC,ASCE/SEI 7-05,and ASCE/SEI 7-10. Seismic qualification is based on analysis. For more information and specific wind and seismic load capacity ratings,please see the Certificate of Wind and Seismic Load Capacity. Spray Water Pump Assembly: Corporate Headquarters:7600 Dorsey Run Road,Jessup,MD 20794—Tele:(410)799-6200/Fax:(410)799-6416 Each cold water basin has an integral pump with large area,lift out,steel strainer screens including perforated openings sized smaller than the water distribution nozzle orifices. Strainers include anti-vortexing baffles to prevent air entrainment. A close-coupled,bronze-fitted pump with a mechanical seal is mounted on the basin. The pump motors are premium efficiency,totally enclosed,fan cooled(TEFC). A water bleed line with a metering valve to control the bleed rate is installed between the pump discharge and the overflow connection. Electrical requirements match the fan motor. Spray Distribution System: Spray header with schedule 40 PVC branches.Removable branches and 360°spray pattern plastic spray nozzles are held in place with snap-in rubber grommets. Basin Water Level Control: The unit is supplied with a make-up valve with unsinkable polystyrene filled plastic float arranged for easy adjustment. The corrosion resistant make-up valve is suitable for water supply pressures between 15 psig(103 kPa)and 50 psig(345 kPa). Basin Heater(s): A minimum number of high-watt-density electric immersion heater elements,sized to maintain+40°F(+4°C)basin water at 0°F(-18°C)ambient with a 10 mph(16 km/h)wind speed,is provided. Electrical requirements match fan motor. Wiring is not included. Heater Element Material of Construction: The unit is supplied with copper heater elements. Basin Heater Control: An electric immersion heater control package,including thermostat(s)and low water cutout switch(es)or probe(s),is provided. Disconnect switch,contactor,and wiring are not included. Vibration Cutout Switch: Fan system is provided with an appropriate number of vibration cutout switches to limit collateral damage to the unit in the event of a catastrophic fan failure.The vibration switch(es)is mechanically tripped with a frequency range of 0 to 3,600 RPM and trip point of 0.2 to 2.0 g's. No input power is required. Switch rating is 10 amperes at a maximum 480 VAC,and 1/4 ampere at 250 Vdc. Extended Lubrication Lines: Bearing lubrication lines are extended to grease fittings located inside the unit and are accessible from the access door. Internal Access Option: The unit has access doors on both ends,an internal walkway,and an internal aluminum ladder with galvanized steel supports to facilitate access to the mechanical equipment.All components meet pertinent OSHA standards. Corporate Headquarters:7600 Dorsey Run Road,Jessup,MD 20794—Tele:(410)799-6200/Fax:(410)799-6416 20180 Baltimore Aircoil Company.All Rights Reserved. I Data Version 1.09 DWG Version 1.2 • Notes 1) All dimensions are in feet and inches. Weights are in pounds. 2) Dimensions showing location of coil and spray water connections are approximate and should not be used for prefabrication of connecting piping. 3) The area above the discharge of the fan must be unobstructed. 4) For weight loading and support requirements refer to the suggested steel support drawing. 5) Do not support piping from unit connections. All necessary piping supports to be supplied by others. 6) Weights include all the options and accessories. 1'2" Vent 7) All unit piping connections 3" and smaller are MPT unless otherwise noted. , 4" Fluid Out 8) Heaviest Section is the Coil Section. /I iii " 9) Coil is provided with a 1/2" threaded vent • dil' located on the upper outlet pipe stub. N 10) All col connections are beveled for M M M welding unless otherwise noted. O 0 M 1—2"--I NE • IIIMIIMig r1/4"�— 4" Fluid In I•-•-•-••-•-•-•-•-•-•-•-•-•-•-I1,1 11/2" I -- Make Up Access ?:;�?:?�;�;:;::=:•:;:•:•: Access Door -lii.cL,,,,' '1, '''•'••:•:•:: •. Doo 1. t • ei�ll ill— _I —lid t�� 3 1/4"} f 41', l'-9 3/8" 9p A L 5'-11 3/4" I 1'-9 4111 2" Drain 8'-5 3/4" 3" Overflow Connection End Air Inlet Side Model Shipping Operating Heaviest Right Hand Number Weight Weight Section FXV-0806A-20D-K 5400 8437 3556 ORDER NO: Q19053742903 (.AJ BALTIMORE AIRCOIL COMPANY DRAWING NUMBER: DATE: 4/8/2019 2:46:08 PM o UP-Q19053742903 20180 Baltimore Aircoil Company.M Rights Reserved. I Data Version 1.09 Notes DWG Version 1.00 1) Supporting steelwork and anchor bolts to be designed and furnished by others. 2) All supporting steel must be level at top. 3) Beoms should be selected in accordance with (4)7/80 MOUNTING HOLES 10 accepted structural practice, maximum deflection of beam under unit to be 1/360 of span, not to - FACE D UNIT OUTLINE exceed 1/2 inch. 4) Supporting steel will be greater than or equal to ■r the length of the basin. 5) Alternatively the unit may be supported on columns at the four corners of the unit. Consult I I I I your BAC Representative for details. II II I ZO 6) If vibration isolation rails are used between unit I= and supporting steel, be certain to allow for the Q CO length of the vibration rails when determining length . IN w w w of supporting steel. Vibration rail length and M C.) I I I I 0 I mounting hole locations may differ from those of "i i' u I I I I . I W the unit. Refer to vibration isolator drawings for a, co CO this data. W 7) Each beam should be designed, as a minimum, Z Q for 65% of the total unit operating weight applied z I I I I I as a uniformly distributed load. c., I I I I 8) Do not use this drawing to size point vibration isolators. See your BAC Representative for details. •1 9) All Dimensions are in feet and inches. All �I weights are in pounds. 10) Weights include all of the options and •� z_ z accessories. N 4 1/4' 5-3 1/4' 4 1/4' 5-11 3/4' FACE C(AIR INLET) PLAN VIEW 1 1 PLAN "A"STEEL Model Shipping Operating Number Weight Weight FXV-0806A-20D-K 5400 8437 FXV/CXV Cell Unit Support ORDER NO: Q19053742903 BAC AIRCOI BALTIMORE DRAWING NUMBER: DATE: 4/8/2019 2:46:39 PM o SS-019053742903 2018©Baltimore Aircoil Company.All Rights Reserved. j Data Version 1.09 Notes DWG Version 1.0 • 1) All Dimensions are in feet and inches. All weights are in pounds. 2) Center of gravity location is based on operating weight. 3) Unit shown may not reflect the configured options. r Io a T. —1 O S 0 •.•.•.����� .•.•.•ice%ice - .••x.•.44.�.�.�.�.�.�.�. ••••••••••••• ...... ...... •••••••••••••••••••••••••• cl l 14o o G. 1L_Cg.l l ---45"--I 35" - Connection End Air Inlet Side Model Shipping Operating Heaviest Number Weight Weight Section FXV-0806A-20D-K 5400 8437 3556 8.5 X 6 Unit Center of Gravity BALTIMRE ORDER NO: Q19053742903 i3A C A RCOI LCOMPANY DRAWING NUMBER: DATE: 4/8/2019 2:47:34 PM o CG-Q19053742903 20180Baltimore Aircoil Company.All Rights Reserved. I Data Version 0.00 Notes DWG Version 1.3 Internal Walkway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Air Inlet 1" Low Water Cutout 2" Heater Connection ��� o ��-Thermostat � i t 1 rivinem. to ° :1 :1 \-1 2" Thermoprobe 11" 1'-41/2" - - 3'-6" -- Air Inlet End AMBIENT TEMPERATURE: 0 DEGREES F POWER (EACH): 4 KW VOLTAGE: 200V PHASE: 3 FREQUENCY: 60HZ 8.5 X 6 Basin Accessories BALTIMORE ORDER NO: Q19053742903 i3A C AIRCOIL COMPANY DRAWING NUMBER: DATE 4/8/2019 2:51:01 PM 0 BA-Q19053742903 2018®Baltimore Aircoil Company.M Rights Reserved. NOTES: 1.INTERLOCK IMMERSION HEATERS WITH CIRCULATING PUMP TO DE-ENERGIZE HEATERS WHEN PUMP IS RUNNING. 2.CONTROL THERMOSTAT IS TO BE SET FOR 40°F.DO NOT SET THERMOSTAT LOWER THAN 40°F. 3.BROKEN LINES INDICATE COMPONENTS AND WIRING TO BE SUPPLIED BY OTHERS. 4.CONTACTOR,FUSE PROTECTION AND POWER SUPPLY WIRING ARE TO BE SIZED TO MATCH HEATER REQUIREMENTS.WIRING MUST COMPLY TO APPLICABLE CODES AND ORDINANCES. DISCONNECT SWITCH FUSE MAGNETIC CONTACTS (BY OTHERS) (BY OTHERS) (BY OTHERS) (WIRE MULTIPLE HEATERS L1— — — — I — — H I II— — L — IN PARALLEL) C1 L2— — — — —o — — —{I — H C1 _ — HEATER L3— — — — —a — — I II— CI— N HEATER CONTROL POWER SUPPLY H _ - - o MANUAL AUXILLIARY FUSE SWITCH CONTACT-N.C. (BY OTHERS) THERMOSTAT HEATER (BY OTHERS) SPRAY WATER PUMP • PENN A19-ANC MAGNETIC CONTACTOR (BY OTHERS (BY BAC-SEE NOTE 2) (BY OTHERS-SEE NOTE 4) SEE NOTE 1) LOW WATER CUTOUT PENN F-63 (BY BAC) Data Version 1.00 DWG Version 1.10 Electric Immersion Heater Wiring ORDER NO: Q19053742903 BAC BALTIMORE Standard Controls AIRCOIL COMPANY DRAWING NUMBER: DATE: 4/8/2019 2:51:15 PM o HW-Q19053742903 2018@ Baltimore Aircoil Company.All Rights Reserved. I Data Version 1.09 DWG Version 1.2 Notes 1)Motor Heater should only be energized when the fan is stopped(0%fan speed). 2)Interposing relay must be sized per the heater power consumption. 3)Heater sizes shown below are maximum values.Refer to the motor nameplate for final power requirements. 4)General heater wiring details shown,see diagram on motor for specific details. 5)All wiring must comply with all codes and standards applicable for the instated jurisdiction,which may include requirements for additional disconnects,over current protection,and/or other safety devices. 6)Dashed lines represent field supplied wiring. 7)Space heater wiring leads may be located in either the main outlet box,or an auxiliary box if so equipped. HEATER HEATER POWER POWER HOT NEUTRAL INTERPOSING RELAY MOTOR SPACE HEATER (BY OTHERS) (BY BAC) r- -CI I J I I I I t— J L J MOTOR STARTER/VFD N.C.AUXILIARY CONTACTS (BY OTHERS) CONTROL CONTROL POWER POWER HOT NEUTRAL Heaters are 110-120 VAC/50 or 60 Hz based on motor configuration. Fan Motor Space Heater ORDER NO: Q19053742903 BABALTIMORE Wiring wlNhemMaER Geic-General C A RCOIL COMPANY DATE: 4/8/2019 2:47:47 PM o SW-Q19053742903 • 20180 Baltimore Aircoil Company. All Rights Reserved. I Data Version 0.00 A DWG Version 1.0 • f 1]± 1 r 0 � • • I I CONDUIT BOX �_ • A J o RIGID CONDUIT OUTSIDE TOWER TURNED DOWN TO JUNCTION BOX STD. MOTOR OR SAFETY SWITCH , LOCATION 4111111 FLEXIBLE CONDUIT O (ALLOW SUFFICIENT SLACK FOR BELT J A TENSION) -.- DISCONNECT/SAFETY SWITCH IN PLAN VIEW WEATHER PROOF ENCLOSURE MUST BE RATED FOR PROPER VOLTAGE AND HORSEPOWER OF FAN MOTOR -,, I �'-"- ( SECTION B-B -P- ADJUSTABLE L Notes MOTOR BASE — p.4— r= r 1) All conduit must be water tight and pitched downward to allow condensation to drain away from motor I' i I` conduit box, therefore, do not run the conduit through the fan deck. -0 _ u • 2) All wiring must conform to local and national electrical codes. Junction box/safety switch and all conduit • I from fan motor conduit box to be sized, provided and installed by others. o 3) Rigid conduit outside casing panel must turn down to junction box. STD. MOTOR LOCATION--..< • 4) On multi—cell units, use seprate conduit lines for each fan motor. Run conduit through adjacent cell to junction box and/or disconnect switch. • B HOLE IN CASING PANEL SHOULD BE LARGE ENOUGH TO ACCOMMODATE CONDUIT. SEAL HOLE WITH WATER PROOF SEALANT • II SECTION A-A Motor and Conduit Location ORDER NO: Q19053742903 gQC BALTIMORE Single Fan Standard Motor System C/ AIRCOIL COMPANY DRAWING NUMBER: DATE: 4/8/2019 2:46:55 PM o ML-Q19053742903 2018©Baltimore Aircoil Company.All Rights Reserved. I Data Version 0.00 DWG Version 1.0 OPERATING INSTRUCTIONS: Follow the installation drawings and wiring diagram to ensure the proper operation of the vibration switch. Direct any questions to your local BAC Representative. NOTE: Moisture inside the switch can lead to switch failure.Care must be taken when replacing the cover on the vibration switch to ensure that the proper watertight seal is obtained. CAUTION: Before performing any maintenance,adjustment or inspection of the switch,make certain that all power has been disconnected and locked in the off position. SWITCH LOCATION % FAN SHAFT r111 *1_0tion MECHANICAL EQUIPMENT ��II., SUPPORT(TYP) it DRIVEN -41871,' VIBRATION CUTOUT SWITCH SHEAVE (Refer to the wiring diagram for specific switch type.) VCOS LOCATION ORDER NO: 019053742903 BQ C BALTIMORE C) AIRCOIL COMPANY DRAWING NUMBER: • DATE: 4/8/2019 2:51:46 PM o VL-Q19053742903 20180 Baltimore Aircoil Company.M Rights Reserved. MECHANICAL VIBRATION CUT-OUT SWITCH NOTES: (ONE-SINGLE POLE DOUBLE THROW SWITCH) 1.LOCAL PUSH BUTTON RESET. 2.TO MAINTAIN HAZARDOUS DUTY RATINGS,THE FACTORY INSTALLED WATER TIGHT CONDUIT/CABLE CONNECTION FITTINGS MUST BE REMOVED AND THE FOUR CONDUCTOR CABLE MUST BE ROUTED INSIDE OF A SUITABLE EXPLOSION PROOF CONDUIT.NOTE:THE LOCAL RESET CONNECTORS CAN EASILY BE REMOVED WITHOUT HAVING TO UN-WIRE THE CONDUCTORS FROM INSIDE THE CUTOUT SWITCH. SETPOINT ADJUSTMENT (SEE NOTE 1) 3.THE MECHANICAL VIBRATION CUTOUT SWITCH COMES WITH TWO WATER TIGHT CONDUIT/CABLE CONNECTORS.ONE CONNECTOR IS USED TO PROVIDE A WATER TIGHT CONNECTION TO THE VIBRATION CUTOUT SWITCH AND THE OTHER IS PROVIDED FOR THE 7'FLEXIBLE ELECTRICIAN TO CONNECT THE WIRE CABLE TO A JUNCTION BOX LOCATED IN THE VICINITY OF THE VIBRATION CUTOUT SWITCH. JACKET _ WATERTIGHT 4.THE SWITCH IN THE NORMALLY CLOSED CIRCUIT(BLACK WIRE)WILL OPEN WHEN THE DEVICE EXPERIENCES VIBRATION LEVELS SEAL sson ABOVE THE SETPOINT VALVE.IF REVERSE CONTROL LOGIC IS DESIRED,CUT OFF THE BUTT END CONNECTOR ON THE WHITE CUSTOMER (SEE NOTE 6) WIRE AND INSTALL A WIRE NUT OR BUTT CONNECTOR ON THE NORMALLY CLOSED WIRE(BLACK). WIRES -1I1960110111I11 5.THIS MECHANICAL VIBRATION CUTOUT SWITCH COMES WITH ONE SINGLE POLE DOUBLE THROW SWITCH.THE SWITCH CONTACTS ARE (FOR HAZARDOUS 'DRY CONTACTS'WHICH CAN BE SUCCESSFULLY USED DIRECTLY IN THE FAN STARTER CONTROL(TYPICALLY A/C VOLTAGE) RATINGS SEE CIRCUIT OR DIRECTLY IN A BUILDING MANAGEMENT SYSTEM(TYPICALLY D/C VOLTAGE). NOTE 2) CONTACT RATINGS:3 AMPS@ 125 OR 480 VAC,1/2 AMP@ 125 VDC,1/4 AMP@ 250 VDC. 6.CAUTION:MOISTURE INSIDE THE SWITCH CAN LEAD TO SWITCH FAILURE.CARE MUST BE TAKEN WHEN REPLACING WATER PROOF TI IC COVER ON THE VIBRATION SWITCH TO ENSURE THAT THE PROPER WATERTIGHT SEAL IS OBTAINED. CONDUIT CONN (SEE NOTE 3) MOUNTING PLATE ADJUSTMENTS OF BAC MECHANICAL VIBRATION CUTOUT SWITCH BAC RECOMMENDS THAT EACH VIBRATION CUTOFF SWITCH BE FIELD ADJUSTED AT START-UP TO OPTIMIZE THE TRIP POINT RELATIVE TO THE FINAL MOUNTING POSITION AND VIBRATION CHARACTERISTICS OF THE INSTALLED EQUIPMENT. NOTE: INSTALLATION AND ADJUSTMENT MUST BE PERFORMED BY QUALIFIED,COMPETENT TECHNICIAN WIRING DIAGRAM 1.FOR YOUR SAFETY,TURN OFF,THEN LOCK&TAG-OT THE ELECTRICAL SUPPLY TO THE FAN MOTOR(S). (ONE-SINGLE POLE DOUBLE THROW SWITCH-SEE NOTE 5) 2.PUSH IN THE MANUAL RESET SWITCH TO ENSURE UNIT IS IN UNTRIP STATE(USING AN OHMMETER,VERIFY THE CIRCUIT BETWEEN"COMMON"AND"N.C."IS CLOSED.THE SWITCH COMES WITH PRE-WIRED CABLE SO OPENING THE SWITCH IS NOT NECESSARY TO PERFORM THIS TASK.IF CIRCUIT IF OPEN(TRIPPED STATE)SKIP STEP 3 AND GO TO STEP 4. 3.TURN ADJUSTMENT SCREW CONTERCLOCKWISE(CCW)1/8 TURN AT A TIME UNTIL THE CIRCUIT BETWEEN"COMMON"AND"N.C."IS OPEN(TRIPPED STATE) (SEE NOTE 4) 4.ONCE TRIPPED,ROTATE ADJUSTMENT SCREW'A TURN CLOCKWISE(CW)AND THEN PUSH IN MANUAL RESET BUTTON(THE CIRCUIT BETWEEN"COMMON"AND "N.C."IS CLOSED) (WHITE) N.O. 5.START UP FAN(S)TO DETERMINE IF THE START-UP WILL CAUSE THE CUT-OUT SWITCH TO TRIP. a.IF THE VIBRATION CUTOUT SWITCH DOES NOT TRIP: i. START AND STOP THE FAN TWO MORE TIMES AND IF THE CUTOUT SWITCH STILL DOES NOT TRIP,THEN CALIBRATION IS COMPLETE. TO CUSTOMER FAN (RED) b.IF THE VIBRATION CUTOUT SWITCH DID TRIP: CIRCUIT OR BUILDING =11 COMMON i. TURN OFF,THEN LOCK&TAG-OUT THE ELECTRICAL SUPPLY TO THE FAN MOTOR(S). MANAGEMENT SYSTEM (BLACK) ii.ADJUST THE SET POINT SCREW AN ADDITIONAL'Ai TURN CW AND THEN PUSH IN THE RESET BUTTON. (SEE NOTE 5) Y N.C. iii.RE-START THE FAN(S)TO DETERMINE IF THE START-UP WILL CAUSE THE SWITCH TO TRIP. NOTE: REPEAT THIS ADJUSTMENT PROCESS(STEP 5.b.i-S.b.iii)UNTIL THE UNIT DOES NOT TRIP. (GREEN) CASE GROUND iv.ONCE THE FINAL ADJUSTMENT HAS BEEN MADE,START AND STOP THE FAN TWO MORE TIMES AND IF THE CUOUT SWITCH STILL DOES NOT TRIP,THEN • CALIBRATION IS COMPLETE. WIRING OF VIBRATION CUTOUT SWITCHES ON UNITS WITH MULTIPLE MOTORS OR CUTOUT SWITCHES: VIBRATION CUTOUT SWITCHES SHOULD BE WIRED TO SHUT OFF ALL MOTORS ON THE ASSOCIATED FAN DRIVE SYSTEM.THIS MAY REQUIRE WIRING MULTIPLE BEFORE PERFORMING ANY MAINTENANCE,ADJUSTMENT OR INSPECTION OF THE CUTOUT SWITCHES TO SHUT OFF A SINGLE MOTOR OR WIRING A SINGLE CUTOUT SWITCH TO SHUT OFF MULTIPLE MOTORS.CONTACT YOUR CONTROLS SWITCH,MAKE CERTAIN THAT ALL POWER HAS BEEN DISCONNECTED AND LOCKED INTEGRATOR FOR DETAILS ON HOW TO WIRE MULTIPLE SWITCHES. IN THE OFF POSITION. Data Version 1.12 DWG Version 1.10 Mechanical VCOS Wiring ORDER NO: 019053742903 C BALTIMORE Shut Off with Local Reset AIRCOIL COMPANY DRAWING NUMBER: DATE: 4/8/2019 2:51:29 PM o VW-Q19053742903 20180Baltimore Mrrnl Company.NI Rights Roomed. Notes Data Version 0.00 1) All Dimensions are in feet and inches. All weights are in pounds. DWG Version 1.0 2) This drawing is not indicative of the specific configuration of the unit. Please refer to the unit print and other supporting drawings for configuration details. 3) Internal Ladder ships loose for field assembly to I111 .01 � i i 1t Intemal Service Ladder I • - I •? r �_ rr .- \ Internal Walkway SII', — 1 CL—LL I , ll,11 1. iiiiiiii Connection End Air Inlet Side Model Shipping Operating Heaviest Number Weight Weight Section FXV-0806A-20D-K 5400 8437 3556 8.5 X 6 Internal Access ORDER NO: Q19053742903 B C BALTIMORE AIRCOIL COMPANY DRAWING NUMBER: DATE: 4/8/2019 2:50:09 PM ® IA-Q19053742903 BILL OF MATERIAL ITEM QTY BRAND PART NUMBER DESCRIPTION 1 1 HOFFMAN C50363012 WaII-Mount Type 4/12 Endo 2 1 HOFFMAN CP3630 Panel,34.20x28.20 3 1 HOFFMAN CMFK Mounting Foot Kit(Qty4) 4 1 HOFFMAN AVDR4NM PNLVENT/DRAIN 5 1 HOFFMAN T10S3R (2)3R HOOD 12X12 FOR 10 6 1 RITTAL SK-3325.117 "'OBS USE SK-3241.110 7 1 RITTAL SK-3325.200 "'OBS USE SK-3325.207 8 1 STEGO KT501141-9-00 COOLING THERMOSTAT 9 1 THOMAS&BETTS ADR11 #14-1/O CU/AL LUG 10 1 CUTLER HAMMER GBK10 GROUND BAR 30"W / 12"D — 11 1 ABB OT60F3 60A 30HPN ON FUSED DISC. 12 1 ABB OXP6X430 SHAFT 19.7 77 ) 0 n I 13 1 ABB OHB80L6 BLKTl-T3 CB HANDLE N4X ' l/.'-lJ 14 3 ERICO 569020 (1)1/0.8X(6)4-14 150A `� 'J �yV.` 15 1 ABS OT63F3 60A 30HP NONFUSED DISC. MUST FILTER 11/11011113.031 ° s�I 16 1 ABBABS OA1G1O NO AUX-OT16/OT100 -�= 17 2 ABB AF38-30-00-13 10/2OHP 3P CTR,120VAC = (sem 18 2 ABS AF26-30.00-13 7.5/15HP 3P CTR,120VAC 11.11 �7/ 19 2 ABB CA4-10 1-NO FRONT A-LINE AUX K0 rVAT 0 100001 0 Bm DIA 20 1 ABB CA4-01 1-NC FRONT A-UNEAUX - MAIM Dl 1fl4L gl 0 u■0 0 0 0 21 1 ABB VEM4 AF09-AF38 ELEC/MECH INTRLC - 0• I0 Iz (0 22 1 ABB TF42-35 29-35 AMP AF09-A38 OLR IIIIIIIIM0 \1=1 0 0 0 23 1 ABB TF42-13 10-13 AMP AF09-A380LR 24 3 BUSSMANN 1760060 CLASS J SAFETY FUSE BLOCK ID 25 6 BUSSMANN JT60030 CLASS I SAFETY FUSE BLOCK 26 3 BUSSMANN LPJ-605P CLASS J 600 VOLT FUSE ®NIS 00 j////.(KY////// 27 3 BUSSMANN LEI-15SP CLASS 1600 VOLT FUSE � J 28 3 BUSSMANN LPJ-15SP CLASS 1600 VOLT FUSE a 29 2 BUSSMANN LPCC-5 CLASS CC 600 VOLT FUSE 36' NI FUNDS le MED IFAIER n1YT YE! 0 30 1 BUSSMANN FNM-6.25 250 VOLT MIN.FUSE /fie e e o �.0ss0,ol 31 1 GENERAL ELECT. 9T58K0090G385AMI XFMR SOOVA 208 X 120 // . z. �r a 32 2 ALLEN BRADLEY 800FPLSM33PN5X20 3-POS GRN ILL SEL W/2NO LP //// zz a a u 33 1 ALLEN BRADLEY 800FPL5M23PN5X10 2-POS GRN ILL SW W/NO&LP 1 ALLEN COMIC!ON/GIL.VhEARFRID]D ////// / /////////// 34 5 ELECTRO PAC F A35VE PLAS NP PPSM22PX11 LLASTIC NAME PLATES1NONCCOMIC =1( MINE_ 0 0 0 0 ow w 0e an a. lk, 36 4 AUTOMATION DI 782-2C-120A 2PDT 15A RELAY 120AC s9(i•• 37 4 AUTOMATION DI 782-2C-SKT RELAY SOCKET A rinirarr 38 20 ALLEN BRADLEY 1492-J3 TERM 25 AMP 600V GRAY - ( 0 0 0' I.�A 10m+ra© • . . •°• TR 39 3 ALLEN BRADLEY 1492-J4 TERM 35AMP 600v GRAY - Is •0° 40 3 ALLEN BRADLEY 1492-316 TERM 85 AMP 600V GRAY = % le 0 41 1 ALLEN BRADLEY 1492-EB116 END PLATE116 an CUR 42 6 ALLEN BRADLEY 1492-EBB END BARRIER 13 0 / 22) a) //////////T�' 43 4 ALLEN BRADLEY44 2 PHO 1492-ERL355ST1146 J SCREWLESS END STOP ;(/// )///// 10 THOEMASNIX&BETTS TY15X2WPW6 DIN RAIL USE 0801733 35)(7 DUCT 1.5 X 2 DUCT WHITE DU J 46 10 THOMAS&BETTS TY15CPW6 COVER 1.5 WIDE WHITE CVR L 47 1 TOSHIBA VT130Q9+U2110 10HPVARIFREQ DRIVE 208V 48 1 ELECTRO PAC UL LABEL(NITW) 51844 ENCLOSED CONTROL PNL REV BY DATE DESCRIPTION SERVING INDUSTRY FOR CUSTOMER APPLIED SYSTEMS DRAWN BY MIK APPR ELECTRICAL POWER AND CONTROE LL SINCE D197T2 PANEL JOB DATE 04/08/19 PAC PORTLAND, OR R9721 1 (( )) TITLE 208 VOLT IOHP VFD COOLING TOWER DRAWING NUMBER PNFAX•(503/285-0844 COOLING TOWER LAYOUT 39072-1 (FIELD WIRED) (FIELD WIRED) 0 H❑ SPRAY PUMP AUTO START/DRY CONTACT 208/3/60 42 F.L A. NOTE: E----i 1----EI CD LI LI1 LI3 G It is the Installers responsibility to set overload heaters (FIELD WIRED) I I I I and drive motor parameters per motor nameplate specification. Sower fun AUTO START/DRY CONTACT 1111 1111 This equipment Is to be installed in accordance with ID---11----0 0 1 i_ the National Electric Code and local codes and ordinances. Installation to be performed by a licensed (FIELD WIRED) 60 NIP MAIN d \ = electrician and inspected by local authorities. BASIN LOW LEVEL FLOAT DISCONNECT WITCH -��-- �B 1 (�R ami enl VFD CONTROL BOARD ' E (FIELD WIRED) (�Y-I1 9 (� ��0761 (0.K)(FLM)BV/1 SIG O • SPEED REFERENCE INPUT(-)--Y l0 Q (0.D)JIILC ' I. I 4/20NA Ti -D.GSFLD L JW (18)DCC-RTN •—i I (1910 ST-PERMISSIVE CR4 (20) F 60 60 60 15 15 15 I., 155 15 5 5 -I I o -START/STOP — _ _ _ _ — — J I I C INN• III TOWER FAN 02A IMM 02B 2081120 OFF ' 503VA. CPT HN(O\AUTO BP 2D i� , o_o I I O O %m � 63A VFD -\\ E (FIELD WIRED) ISOLATION SWITCH p o O (22) IRI ISI - ❑ ---VIBRA7I4-i- OFF 1 OIOIOI1 RNLI S/1.2 T/L3 DRY CONTACT JUMPER FERE IF NOT USED VFD 1 (H) (N) 1011P VFD 0 ❑5 POWER CONNECTIONS N SPRAY PUP OFF U/TI V/T2 W/T3 G HAND\ AUTO / QI Q -.••• %W O 1 l OF/ i — —BP — — _KS2 — — —CI J 00Xo 0 (23) I I (20 4 � (25)30.82 (26) CD i I OLRIT OLR2 T III TOWER FAN NODE VFD BYPASS �o (27) DISI (28) BP 00 ..-= I / I IE 'E ET T I IT o% o (29) CR4 C30) sun 131) I W L 0 J PAN HEATER• • •)), [CO (FIELD VIREO) OFF AUTO PAN FREEZE T'STAT (OPEN OF RIZE) CR3 ( NOT (33) 0 àY ® ° ma_o II O H� 01L PANEL COOLING FAN FAN OR SPRAY RMP MOTIF 410/SUMP WATER PANEL T'STAT G MOT (CLOSE ON RIZE) / (FIELD WIRED) (FIELD WIRED) (FIELD WIRED) o 6.v� O (REFER TO MFG INSTRUCTION FOR WIRING) Wil/ —II REV BY DATE DESCRIPTIONSERVING INDUSTRY FOR CUSTOMER APPLIED SYSTEMS DRAWN BY MUG APPR ELECTRICAL POWER AND CONTROL SINCE 1972 PANEL JOB DATE 04/08/19 PAC PORTLAND MBAR9721 1 TITLEDRAWING NUMBER ( 208 VOLT 10 VFD COOLING TOWER PNFAXT 500333283=OOaa7a COOLING TOWER ELECTRICAL POWER & CONTROL WIRING 39072-2 BBaltimore Aircoil Company AC Closed Circuit Product Selection Report Version: 7.6.15 NA Product data correct as of: January 31,2019 Project Name: Executive Tower Selection Name: VF1 Project State/Province: Oregon Project Country: United States Date: February 20,2019 Model Information Design Conditions Product Line: VF1 Fluid: EG,30%by Vol. Model: VF1-036-51L Fluid Freeze Point: 4.00°F Number of Units: 1 Flow Rate: 275.00 USGPM Coil Type: Standard Coil Entering Fluid Temp.: 95.00°F Coil Finning: None Leaving Fluid Temp.: 85.00°F Fan Type: Standard Fan Wet Bulb Temp.: 70.00°F Fan Motor: (1) 15.00= 15.00 HP/Unit Total Standard Fan Power: Full Speed, 15.00 BHP/Unit Total Pump Motor Power: (1) 1.00=1.00 HP/Unit Fluid Pressure Drop: 10.70 psi Intake Option: None Reserve Capability at 15.00 HP: 1.01% Internal Option: None Discharge Option: None External Static Pressure: 0.00 in.of H2O Thermal performance at design conditions and total standard fan motor power is certified by the Cooling Technology Institute(CTI). Engineering Data,per Unit Unit Length: 12'00.00"+ 11.50"(Pump)= 12' 11.50" (Total) Unit Width: 03' 11.50" Unit Height: 10'07.00" • Approximate Shipping Weight: 6,310 lbs --` *~ Heaviest Section: 4,720 lbs Approximate Operating Weight: 8,390 lbs Approximate Remote Sump Operating Weight: 7,800 lbs ��{{ ` _- i6'- • Air Flow: 24,100 CFM `'`4 °14ii: Spray Water Flow: 150 USGPM Coil Volume: 162 U.S.gallons �! L Coil Connections: (1)4"Coil Inlet and Outlet,Based on 275.00 USGPM Flow per Unit Remote Sump Connections: (1) 4" Heater kW Data(Optional) 0°F(-17.8°C)Ambient Heaters: (1) 3 kW -20°F(-28.9°C)Ambient Heaters: (1) 5 kW Minimum Distance Required: From Solid Wall: 3.5 ft. From 50%Open Wall: 3.5 ft. Energy Rating: 15.94 per ASHRAE 90.1,ASHRAE 189 and CA Title 24. Note: These unit weights and dimensions account for the selected fan type for the standard cataloged drive configuration, but they do not account for other options/accessories. Please contact your local BAC sales representative for weights and dimensions of units with other options/accessories. Page 1/1 • Bosch Buderus Engineering SSB800/1000/1000TL Submittal I BOSCH Stainless Steel Condensing Boiler Sheet 4ItoiketOiponents wl I'll 0., 44 US �[AriF1Ep F.• CERTIFIED r, 0 A• SME -e"" • ENERGY STAR H d �i.:NC!1 CERTIFIED° Jww.ahri Eireciory.arg 414 oi Engineering Specifications There shall be provided and installed Bosch Buderus Model Heat exchanger modules shall be labeled for 80 psig (MAWP) SSB800 SA,_Model SSB1000 SA, Model SSB1000 TL in maximum allowable working pressure rating. An integrated quantities of . Bosch Bosch Buderus Stainless Steel Boilers referred pressure sensor shall ensure minimum water pressures are to as SSB are condensing hot water boilers,suitable for direct maintained. In addition to the minimum water pressure sensor, venting. The SSB is factory set for operation using Natural each module shall encompass a low water cut-out(LWCO) and Gas but shall be field convertible to LP Gas using the supplied an individual flow-sensor on each module to identify low water conversion kit. or low flow conditions. The SSB SA series Boiler(s) shall utilize two individual plasma Boiler(s) shall be capable of up to 40:1 turndown ratio based welded 316L dual tube stainless steel heat exchanger modules. upon supply and return water temperatures and/or outdoor Both Modules contain independent fan motor,gas valve,burner reset control. Boiler(s)shall have a settable Power Mode tube,circulator and all the necessary safety components to allow parameter to allow for selection of desired module operation for true on-board redundancy. Each module is provided with for either parallel or serial operation of up to 8 modules. isolation valves and drain to allow for independent service. Boiler(s) shall be designed for large residential,commercial and light industrial applications. Boiler(s) shall be constructed,tested and labeled in accordance with ASME Section IV and shall bear the ASME stamp. Boilers Boiler(s) shall be equipped with a 75 lb. pressure relief valve shall be CSA approved for USA and Canada and have an per boiler module. applicable Canadian registration Number. Bosch Thermotechnology Corp. 1 of 9 Watertown,MA• Londonderry,NH •Ft.Lauderdale,FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com • Bosch Buderus SSB800/1000/1000TL L � BOSCH Stainless Steel Condensing Boiler Engineering Specifications s Boiler(s)shall be equipped with Manual Reset High Limits operation,outdoor reset using a demand signal,full outdoor reset (MRHL), Low water cut-outs with test button,and Flow Sensors with constant circulation, permanent heat demand,analog 0-10 Vdc on each boiler module. (4—20 mA) Setpoint control or power% modulation. Boiler(s) shall be equipped with Low and High gas pressure The Boiler(s) control shall have multiple domestic hot water switches with manual resets per ASME CSD-1 requirements. heating parameters designed for the most common application including boiler control of an indirect tank thru a manufacturer Boiler(s)shall utilize multiple (twin-pipe)or single (concentric supplied 10k ohm NTC thermistor or a field supplied aquastat. or single-pipe)terminations for both vertical and horizontal vent configurations as outlined in the boiler installation manual. The Boiler(s) hydraulic manifold piping(water,gas and exhaust/ air) shall be factory installed and self-contained within the Boiler(s) Boiler(s) shall be installed in a system that meets the water outer cabinet. All external Boiler(s) hydraulic connections shall quality standards outlined in the boiler installation manual. be able to be connected in any configuration on either the left or right side of the Boiler(s) in order to allow for maximum installation Boiler(s)shall function directly with hydronic emitters. flexibility and site requirements. Boiler(s) may be controlled using an enable/disable command The Boiler(s)shall be capable of installation in combinations of 2, from "dry"closure contacts such as a relay or BMS system. 3 or 4 TL modules with respective turn-down ratios of 20,30 and 40 to 1. Multiple Boiler sections shall be engineered so that up to Boiler(s) shall be equipped with an optional outdoor air 4 Boilers may be interconnected using the manufacturers provided temperature sensor to control supply water temperature based flanged connections. All manifold piping(water,gas and exhaust/ upon outdoor air temperatures for increased fuel efficiency. air) between Boiler sections shall be engineered and sized by the manufacturer to accommodate the hydraulic requirements of up to Boiler(s) shall contain an on-board,7"color touch-screen which a maximum of 4 Boilers. allows for multiple heating configurations including set point General Data . Unit SSB800 SSB1000 SSB1000TL - �wr Boiler cattgbry — ASME Sect.IV ASME Sect.IV ASME Sect.IV Type of Gas — Natural Gas,Propane Natural Gas.Propane Natural Gas,Propane Heat exchanger construction — 316L Stainless Steel 316L Stainless Steel 316L Stainless Steel Surface heat exchanger(total) Sq. Ft(m2) 54(5.0) 86(8.0) 86(8.0) uonnections 0 Inch I 2` NPT 3'Flanged Water Connections 0 Inch 3 3 5 Vent/Air Intake Connections 0 Inch (0 mm) 6(160) 6(160) 10(254) CPVC,PP,Stainless Steel CPVC,PP,Stainless Steel PP, Vent Materials AL29-4C AL29-4C Stainless Steel AL29-4C Water Volume Gallons(Liters) 13.0(50) 16.0(60) 20.0(75) Weight-dry Lbs(kg) 743 (337) 787 (357) 849 (385) Shipping Weight Lbs(kg) 836(379) 880(399) 941(427) Min.clearance to combustibles Inch (mm) 12 (305) 12(305) 12 (305) 31.5 x 35.4 x 70.9 1 31.5 x 35.4 x 70.9 31.5 x 35.4 x 70.9 Dimension LxWxH Inch(mm) (800x900x1800) (800x900x1800) (800x900x1800) **The 2"minimum clearance is required for all sides of the boiler.The boiler may be installed on combustible(wood)floors excluding carpets. Bosch Thermotechnology Corp. 2 of 9 Watertown,MA• Londonderry, NH•Ft.Lauderdale,FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB800/1000/1000TL BOSCH Stainless Steel Condensing Boiler a f= Unit 1 SSB800 SSB1000 SSB1000TL Max Input* BTU/hr(kW) 798,000(234) 1,024,000(300) 1,024,000(300) Mm Input BTU/hr(kW) 79,800(23) I 100,000(29) 100,000(29) Turndown Ratio(%) 10:1(10%) I 10:1(10%) 10:1(10%) Combustion Eff.* Efficiency(%) 97.6 95.4 95.4 Thermal Eff.* Efficiency(%) 96.8 96.8 96.8 Gross Output' BTU/hr(kW) 772,000(226) 991,000(290) 991,000(290) Net Rating* BTU/hr(kW) 671,300(197) 861,700(252) 861,700(252) =AHRI certified performance data Unit SSB800 SSB1000 SSB1000TL Max.NG pressure ' Inch W.C.(mbar) 20(50) ;, 20(50) 20(50) Min.NG pressure Inch W.C. (mbar) 3.5(8.72) 3.5(8.72) 3.5(8.72) Max.LPG pressure Inch W.C. (mbar) 20(50) 20(50) 20(50) Min.LPG pressure Inch W.C. (mbar) 8 (19.9) 8(19.9) 8(19.9) CO2 working range NO (LP) % 8.5-9.5(10.3-10.7) 8.5-9.5(10.3-10.7) 8.5-9.5(10.3-10.7) Max.allowable working pressure(MAWP) PSI (bar) 80(5.5) 80(5.5) 80(5.5) Recommended water flow at max power(AT 36°F/20°C) GPM(m3/h) 44.4(10.0) 56.8(12.9) 56.8(12.9) Water pressure drop @ recommended water flow Feet Head (mbar) 19(568) 28(837) 25(747) Max.operating temperature °F(°C) 194(90) 194(90) + 194(90) l Max HE allowable temperature °F(0C) 210(98.9) 210(98.9) 210(98.9) i 1 , Ambient storage temperature dry °F(°C) ) 5 to 158(-15 to 70) 5 to 158(-15 to 70) 5 to 158(-15 to 70) Ambient functioning temperature °F(°C) 32 to 120(0 to 49) 32 to 120(0 to 49) 32 to 120(0 to 49) Electrical Req.120VAC/1PH/60Hz 15.1 FLA* 15.1 FLA* 15.1 FLA* *FLA(Full Load Amperage)-maximum current drawn by the boiler if all pumps reach rated horsepower. APPr°Yalt ��" Approval description SSB800 SSB1000 SSB1000TL Standard listings&approvals A Massachusetts Plumbing Boarder Approved CRNtf, aJ =r ° ' ,'•.,, „ a ,�.•R ;s .0 '€ R SCAQMD approval Approved Bosch Thermotechnology Corp. 3 of 9 Watertown, MA• Londonderry, NH •Ft. Lauderdale, FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB800/1000/1000TL 1BOSCH Stainless Steel Condensing Boiler SSB800fSSB1000 Boiler Dimensions AZ jai 31.49(800) • 02.00 06.30 35.43(900) (51) (160) 8.54(217) 9.88(251) ,,,..---•--- --- til hi.--- ---,,-; ,...-,c [',i I N •• ti N CO • • � LI �� •0 • 1111, ti MM -Eill) O . .— O o 0 co coco O O O n N M O O ON �� `I41) 4 �i7 l 00 • „F 2 , s CGS. lV V Y M v' O .-1 • Ilinmomenmesa_I I!ti aILt)O 14! I N %—f CI CI 1 ' I 1 I I, r+irc0r d CO C4 II .,4 c,c i 5.31(135) ' r;•-i o3.00(76) 03.00(76) __. 10.63(269) 7.48(190) Dimensions in inches(mm) Tolerances on all dimensions shown is+/-1/4"(6.35mm) Bosch Thermotechnology Corp. 4 of 9 Watertown,MA• Londonderry,NH•Ft.Lauderdale,FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB80O/1000/1000TLI:4BOSCH Stainless Steel Condensing Boiler SSB1000TL Boiler Dimensions 31.49(800) 35.43(900) '.03.00 ( 6) 09.84(2 0 r 8.54(217) 9.88(251) A Ir—mo— iii f I N 1 LI r 1. —T O o n N • i;4 VI . 0 Il 11 • r o~p. ml nf co v o ri o a 0 m 0 ell m I 0 0 TI LID • • • • CO O O O N mCI 1 O � e v N �� x t Ii_mam� diI J I I I N ,�� 00 I 111 III I S 5.31(1351 .. ® 05.00(127)05.00(127) a? 11.81(300) 7.48(190) rs Dimensions in inches(mm) Tolerances on all dimensions shown is+/-1/4"(6.35mm) 1 Bosch Thermotechnology Corp. 5 of 9 Watertown, MA• Londonderry, NH•Ft. Lauderdale, FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB800/1000/1000TL s) BOSCH Stainless Steel Condensing Boiler SSB800/SSB1000/SSB1000TL Boiler Connections A MI E:j L , (1) C I 0a 11 E 1 to ., F I -- _ ® C A D Boiler Connections Data • iticor 42 _ll'T. ` Item Description Unit SSB800 SSB1000 SSB1000 A Gas Inlet Inch 2"male NPT 2"male NPT 3"Flanged B Flue Exhaust(Flanged) Inch(mm) 6(160) 6(160) 10(254) C Air Intake Inch(mm) 6(160) 6(160) 10(254) D System Supply(Flanged) Inch (mm) 3(76) 3 (76) 5 (127) E System Return(Flanged) Inch(mm) 3(76) I 3(76) 5,(127) F Condensate Outlet Inch (mm) 1-1/2(50) 1-1/2(50) 1-1/2(50) G j Relief Valve Outlet Inch(mm) I 2(60) 2(60) 2(60) Bosch Thermotechnology Corp. 6 of 9 Watertown,MA• Londonderry,NH •Ft.Lauderdale,FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances l BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB800/1000/1000TL fm, BOSCH Stainless Steel Condensing Boiler Thermal Efficiency Curves SSB800/SSB1000/SSB1000TL 100% 1 __ •1% 100%input Ts E ........ •••••• 30%input E 96% •N. --- 20%input ♦\ ♦ •%\ 94% ♦ •\ ♦♦•\ ♦ •\ 88% -- - 80% 70(21) 80(27) 90(32) 100(38) 110(43) 120(49) 130(54) 140(60) 150(66) 160(38) 170(77) Return water temperature°F(°C)©36 Degree Rise .;r SSB800 Water Pressure Drop , 40(12.2) al moo """ - IBM ¢ - - �i _. BOSCH D-S5B800 35(107) 6 -}F-� ! 3 tLj:- 20)61) I WILO-TOP-S 1Sx40115V-x2 30(9.1) IL 25(76) pi {E— 4 . , , ,,, t"I-- 1 I I -.- .! I 1" tt F t -1-1- i -1-11 4 :Ir. , I 1 i 10(3.0) j� 1 1 LI_ -; - � 3 , - 171:1 ' 5(is) -1 . I1 —1 ' I l r— i-- 1 t ) . - I 0 10 20 30 40 50 60 70 80 90 (38) (76) (114) (151) (189) (227) (265) (303) (341) Q[gpm(Ipm)] Bosch Thermotechnology Corp. 7 of 9 Watertown, MA• Londonderry, NH•Ft.Lauderdale, FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Bosch Buderus SSB800/1000/1000TL talf) BOSCH Stainless Steel Condensing Boiler ..........„ SSB1000 Water Pressure pro 40(12.2) _ I t--(1. 1 t WA J lar 7 t j .,. —BOSCH D-5581000 pp .�... _...., _ 1_} i ._.__,._ ._t...._- ,_.T_ .. �*WILO-TOP-S 1,Sx40 115V-x2 30(9.1) � Ill 1 �� ,,,, , . ...4. -_....,...41/1 ! „..,i , , , .1 25 1 ) nem 1 gm T #7. I..I ._: " E I I_ ,_ --1: - . _ ■.T I �. I a _II L IMO I i } . ! ESU -. . r .. a . ■rte . r1 nun �15(4.6) . _ ! ....f.——4.f. i -I .t.it_mt . _I. :� 1 . • - t t T E T1 t10(30) ti ppr awl 0 .... 0 10 20 30 40 50 60 70 80 90 (38) (76) (114) (151) (189) (227) (265) (303) (341) 0[gpm(Ipm)] T ;�'. r. . SSB1000TL Water Pressure Df 40(12.21 I L Ii. 1 I i I !� I I 1 1 ...ttj I i I F--)—#- )---+ I '1 _ + -(- '-{I BOSCH D-5581000 TL t 1 , (.,I * I 1 ¢ 1 I — ] ]-- -{ WILO-TOP-S 1,5x40 115V-x2 I 35(10.7) i � E T_..... ...). .� .... j� ' I 1 30(9.1) iiiiiiiillailmiumusimImo ,�..- Nam arreas 11111111111111111111111111111111111111 111111111111101111 I 20(6.1) ( I-- —7} I- I -,-t , 1 . E � t 1 � I � . 1r i1 I ' _ is 4.6All - ,._T . .. _MU ._.�... 11 1 fli :- r - 4_. all : ia -�it= _ E� - r 10(3.0) ._ T 1 ' I L j —14 MI itli IIII 1 j s(1s 1 -L I t 0 10 20 30 40 50 60 70 80 90 (38) (76) (114) (151) (189) (227) (265) (303) (341) 0[gpm(Ipm)] Bosch Thermotechnology Corp. 8 of 9 Watertown,MA• Londonderry,NH •Ft.Lauderdale, FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com • Bosch Buderus SSB800/1000/1000TL *,`' BOSCH Stainless Steel Condensing Boiler Recommended Boiler Clearances t. RECOMMENDED SERVICE CLEARANCES REQUIRED CLEARANCE FROM COMBUSTIBLES Qt .u , Y,' "" zikSK , 2„s. .ri4,", E 0 31.49"(800mm) 0, 31.49"(800mm) m 4 ZD T .( I A r JI I• A EE E • . Q8 • •• 88 O 00 1 ti r-- . o aI a © ' 0 0. s , ,f:.. ° ,,vr. :Avg„ 20" 2" (508mm) (51 mm) iiimumminmemmimp iiiimmorrommorg 1. 24" 24" 12il "` 12,,, (610mm) ! 1 (610mm) (305mm) 1 l (305mm) Front Front 40' 40" (1016mm) (1016mm) *Excluding side with connections. DISCLAIMER Specifications subject to change without notice.All dimensions shown on these engineering submittal sheets are for reference only and should not be used for field installation purposes.Please refer to current product installation manuals for detailed installation instructions and dimensions. Bosch Thermotechnology Corp. 9 of 9 Watertown,MA• Londonderry, NH•Ft. Lauderdale, FL Bosch Thermotechnology Corp.reserves the right to make changes without notice due to continuing engineering and technological advances I BTC 438008103 C 109.2017 Tel: 1-866-642-3198 Fax:1-603-965-7581 www.boschheatingandcooling.com Form No. 3950 (Rev. 5/04) Bryan "Flexible Water Tube" F Series Steam & Water Boilers 250,000 to 850,000 BTUH Atmospheric Gas Fired 011 ,441 . s...,. r ' ' . . --,,,>q,,,.400000F<•..,, ,f,',4.;140.,u to,:fr; ,'4,..xy .'.Y k , 4"7' t 1�'1": ..W ':yam v �YYt__ h..E :4'i,Y:." .'E' tu^ II.".'n sb4 N.i"*'* £h • - , 1). • 7�u.. A 'µ!^t «F't9. ; Y k 'y.�RNri. _ .. . .... i . $`Y^� •i "` ` u<1�,. %4 . „^ fi -" ' I - +AK• • Steam Boiler a, 4,, 1 .\ F850-5150-GI `. , ��-"^,row 35y �� "..`+ h. N' ,y�: '� Qom^ Water Boiler F350-W-GI la BRYAN BOILERS „....„.:,._.;,) Originators of the "Flexible Water Tube"design TM ;^ .'; .s..,a �,,.asa«3. ,�,r�'x�1,a.,=. -.-.-r ".. '.:.':�. �"s,::fks,? ,,,c" ',to-.�„�` ' _.. : s'n,' al .,, High efficiency hot; ;ter and steam for commercial and industrial applications Bryan flexible water tube boilers are ideally suited Steam Boilers: for both hot water and steam space heating sys- Steam release area tems as well as either high or low pressure process Large, full-size steam drum provides for dry steam steam. In a range of sizes from 250,000 to 850,000 and stable water level. BTUH input, Bryan F series flexible tube boilers are ideal for many commercial, institutional and High or low pressure construction industrial applications. These include healthcare Boiler is constructed as standard for 15 psi or 150 psi facilities; schools; apartments; churches; office maximum working pressure.Also available for higher buildings; correctional facilities; airports; sewage pressures to 300 psi. treatment plants; golf, tennis and fitness clubs. Water Boilers: Hospitals,dairies,restaurants,laundries,dryclean- ers, food processing, tire recapping and metal High or low pressure construction plating are just a few of the many applications. Boiler is constructed as standard for 60 psi maxi- All Bryan boilers are built in accordance with the mum working pressure at 230°F operating tempera- requirements of the ASME Boiler and ture and 250°F design temperature.Also Pressure Vessel Code. ,v - available for higher pressures to 250 psi, Efficient "Flexible Water Tube" =x at 285°F operating temperature and 300°F design th , ', design temperature. *. Natural internal circulation The Bryan bent water tube provides rapid �- internal circulation —for maximum heat ,:; The water tube design and the large transfer and operating efficiency. downcomer legs provide adequate inter- Easily replaceable tubes '' 1 � • nal circulation without concern over ex- � _ terior pumping conditions.Low pressure Tubes are easily removable and replace- drop through boiler. able without welding or rolling. Requires little ser- vice space. Compact—minimum floor space No "Thermal Shock" Requires less floor space than most boilers — The flexibility of the bent water tube design eliminate minimum boiler room size. Shipped completely assembled and wired. Units all possible damage from "Thermal Shock"and from can also be shipped "Knocked Down" for on-site stresses caused by poor or unequal internal circula- assembly. tion. This is particularly important with forced hot Tubes are easily removable and replaceable, water heating systems designed for higher tempera- requiring little service space. tures and greater temperature drops. Bryan F Series Boiler Specifications NOMINAL OUTPUT STEAM M. HEATING APPROX. � '° " 1�#�TU�` �4 .. .OUTPUT � SURFACE ' ; SHIP WT. j' BH (KW) . .MBH (KW) BHP (KW) .ESIHR*..(KG/HR) SQ. FT. (M2)`' ': °'LBS. (KG) F-250** 250 (73) 200 (58) 6(58.6) 206 (93.4) 22 (2.04) 825 (315) F-350*** 350 (102) 280(82) 8(82.0) — 27(2.51) 945(429) F-450 450 (131) 360 (105) 10 (98.0) 371 (168.3) 40(3.72) 1,000 (454) F-650 650 (190) 520 (152) 15 (147.0) 536 (243.1) 58(5.39) 1,250 (561) I F-850 850 (249) 680 (199) 20 (196.0) 701 (318.0) 76(7.06) 1,525 (692) ti i FS kis.steam per Ficru trc ;r a 212°F. **O^ly available as a high pressure r i .0 asi)steam boiler. ***Only available as a hot water bailer. 0 • Check these quality construction features A. Heavy steel boiler frame, built and stamped in , accordance with the ASME boiler code. Hot water boilers constructed as standard for operating pres- sures to 60 psi. Also available for higher operating f. ±I pressures. Steam boilers constructed as standard I 41) �," for operating pressures of 15 psi or 150 psi. Also 46. available for higher operating pressures.Large steam r . ,.- K release area for dry steam. .riS :O „y B. Water leg downcomers to insure rapid internal circu- „ • • • lation and temperature equalization. . C. Bryan flexible water tubes, easily replaceable, re- quiring no welding or rolling. Tubes installed from one side. r ° D. Boiler tube access panel bolted tightly and sealed to boilerframe.Constructed of high temperature insula- © , ® tion in steel framework.Tubes installed from one side pe ,, et �' for easy accessible service and inspection. E. Boilerjacket,heavy gauge zinc coated,with attractive ,;rn ' enamel. _ Fk 0 AC F. Atmospheric gas-Url lei t.:ontrols—alloy steel atmo- ® - spheric burner.Quiet electric ignition and operation. <.•V41.4111013/40100K Kle.. x .` No moving parts or complicated adjustments. illia G. Steam boiler frame has 11/2" fiberglass insulation to insure cool jacket surfaces. H. All controls factory installed and wired. Bryan F Series Boilers Standard and Optional Equipment STANDARD EQUIPMENT OPTIONAL EQUIPMENT OPTIONAL When orderin g, please specify: f'` FURNISHED EXTRA COST: CONSTRUCTION:' 1. Boiler size Water Boiler 1. Manual reset high limit control Steam boiler 2. Supply and return tempera- s Combination thermometer and alti- 2. Manual reset low water cutoff Optional construction to ASME tures required tude gauge,ASME Code rated boiler 3. Auxiliary low water cutoff Power Boiler Code requirements for 3. Boiler relief valve setting t ru,`" relief valve,water temperature con- (water) pressure exceeding 150 psi to maxi W; trol(240°F max std.),high limit con- 4. Combination low water cutoff mum of 300 psi design pressure. 4. Type of fuel:natural or LP trol,probe LWCO. and feeder 5. Ifgas,type,BTU content, Hot water boiler YP Steam Boiler 5. Alarm bells or hornsspecific gravity and pressure Optional construction to ASME Combination low water cutoff and 6. UL,CSD-1,FM,IRI or other Power BoilerCode requirements available $pum control,auxilialow water cut insurance approved control for tempeatures exceeding 240` 6. Electric power voltage, off,high limit pressure control,ASME- systems F and/or pressure exceeding 160 phase and frequency ° <' rated safety valve,water glass set. 7. Indicating lights,as desired psi to maximum of 285°F operat- 7. Optional extra equipment or wx,� iv " Atmospheric equipment 8. Lead-lag systems for two or ing and 300° F design tempera- construction more boilers with or without ture and 250 psi. construction l" a 7 '. Electronic combustion safety con- : mow trol,automatic operating gas valve, outdoor reset control 8. Special approvals required safety gas valve,pilot solenoid valve, 9. Barometer draft control (UL,CSD-1,FM,or IRI) ; electric ignition assembly, main 10.Heat exchanger coils for 9. Altitude manual gas shut-off valve,pilot cock, domestic water pilot and main gas pressure regula- 11.Low fire start,Hi-Lo or tors,all controls installed and wired. modulation fire control Bryan F Series Steam & Hot Water Boilers F I F .. I B _ ' � W A � Ell WI I a ....).,........;.... , • D PLAN VIEW LEFT END VIEW RIGHT END VIEW FRONT VIEW STEAM BOILER DIMENSIONS-Inches (Metric) 'STEAM A B C D E F G H 1* J BOILER Length Width Height Supply Nozzle Height Gas Feedwater Flue Flue Removal MODEL Over Over Over Over Train Jacket Jacket Jacket 15 psi 150psi Conn. Size Location Diverter Connection Space 35 24 5211 NA (1) 14/2 NPT 1/2NPT 8 91/2 771/. 3/4 NPT 24 F-250-S'° (88.90) (60.96) (133.35) (3.81) (3.81) (20.32) (24.13) (196.22) (1.91) (60.96) 35 32' 521/2 3 NPT 172 NPT 11/2 NPT 10 91/2 803/4 1 NPT 24 F-450-S (88.90) (81.28) (133.35) (7.62) (3.81) (3.81) (25.40) (24.13) (205.11) (2.54) (60.96) 35 40 521/2 4 NPT 2 NPT 11/2NPT 12 91/2 841/2 1 NPT 24 F-650-S (88.90) (101.6) (133.35) (10.16) (5.09) (3.81) (30.48) (24.13) (214.63) (2.54) (60.96) 35 48 521/2 4 NPT 2 NPT 11/2NPT 14 91/2 893/4 11/4 NPT 24 F-850-S (88.90) (121.92) (133.35) (10.16) (5.09) (3.81) (35.56) (24.13) (227.97) (3.18) (60.96) F B II .....,,,..--D J W D 3� 1 �M41111 t:440o MI di 0 NAE A1 li O Q I 1' PLAN VIEW LEFT END VIEW RIGHT END VIEW FRONT VIEW i WATER BOILER DIMENSIONS-Inches (Metric) WATER I A B C D E F G H 1* J BOILER Length Width Height Height Gas Tube - Supply Return ' Flue _ MODEL,. , . ...Over. Over Over Over Train I Removal --- Jacket Jacket Jacket .Conn,_ Conn Size ration." Diver##er Connection Space 35 24 431/2 2 NPT 11/2 NPT 9 91/z 691/4 1 NPT 24 F-350-W (88.90) (60.96) (110.49) (5.08) (3.81) (22.86) (24.13) (175.90) (2.54) (60.96) ( t S 35 28 431/2 2 NPT 11/2 NPT 10 91/2 713/4 1 NPT 24 F-450-W (88.90) (71.12) (110.49) (5.08) (3.81) (25.40) (24.13) (182.25) (2.54) (60.96) 35 36 4312 2 NPT 11/2NPT 12 91/2 751/4 1 NPT 24 F-650-W (88.90) (91.44) (110.49) (5.08) (3.81) (30.48) (24.13) (191.14) (2.54) (60.96) 35 45 431/2 2 NPT 1'/2NPT 14 91h 801/4 11/4 NPT 24 ,80-W (88.90) (114.30) (110.49) (5.08) (3.81) (35 56) (24.13) (203.84) (3.18) (60.96) NOTE*Gas train and control location dimensions will vary depending on job specifications and conditions. **Not available in 15 psi construction. Dimensions and specifications are subject to change without notice.Consult factory for certified dimensions. rnt _. BOILERS Bryan Steam LLC-Leaders Since 1916 783 N.Chili Ave.,Peru, Indiana 46970 U.S.A. Phone:765-473-6651•Internet:www.bryanboilers.com Fax:765-473-3074 • E-mail:bryanboilers@iquest.net Form No.3950 02004 Bryan Steam LLC Printed in USA 54-6167