Project:Willow_Windwood Homes_Lot 19 Annand_Beams Page
?.,Judith Souers
Location:Beam Nr.01 -Front Porch Beam on Outside of Porch Suntel Design /
Roof Beam t 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] •
.,w Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 8.5 FT
#2-Douglas-Fir-Larch(North)-Wet Use StruCalc Version 9.0.2.5 3/13/2018 9:31:50 AM
Section Adequate By:72.3%
Controlling Factor:Moment
DEFLECTIONS Center .h-r } • I LOADING DIAGRAM
Live Load 0.07 IN U1560
Dead Load 0.04 in
Total Load 0.11 IN L/924
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria:L/180
REACTIONS A B
Live Load 787 lb 787 lb
Dead Load 541 lb 541 lb
Total Load 1328 lb 1328 lb
Bearing Length 0.91 in 0.91 in
BEAM DATA
Span Length 8.5 ft
Unbraced Length-Top 2 ft 8.5 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 10 :12
Roof Duration Factor 1.15
ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 850 psi Fb'= 1169 psi Tributary Width: TW= 1.5 ft
Cd=1.15 CI=1.00 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 201 psi Roof Live Load: LL= 30 psf
Cd=1.15 Cm=0.97 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E'= 1440 ksi Tributary Width: TW= 4.7 ft
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 522 ksi
Cm=0.90 Wall Load: WALL= 0
Comp.-I-to Grain: Fc-1= 625 psi Fc-1'= 419 psi plf
Cm=0.67 SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
Controlling Moment: 2822 ft-lb Adjusted Beam Length: Ladj= 8.5 ft
4.25 ft from left support Beam Self Weight: BSW= 7 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 185 plf
Controlling Shear: 1328 Ib Beam Uniform Dead Load: wD_adj= 127 plf
At support. Total Uniform Load: wT= 312 plf
Created by combining all dead and live loads.
Comparisons with required sections: Read Provided
Section Modulus: 28.98 in3 49.91 in3
Area(Shear): 9.92 in2 32.38 in2
Moment of Inertia(deflection): 44.97 in4 230.84 in4
Moment: 2822 ft-lb 4861 ft-lb
Shear: -1328 lb 4334 lb
NOTES
Project:Willow_Windwood Homes_Lot 19 Annand_Beams page
Judith Souers
Location: Beam Nr.02-Garage Door Header " Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 or
[2015 International Building Code(2012 NDS)] .. '' Lake Oswego,OR 97035
5.5 IN x 11.5 IN x 16.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:50 AM
Section Adequate By: 123.2%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.18 IN U1104
Dead Load 0.12 in
Total Load 0.30 IN U667
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria:U180
REACTIONS A B
Live Load 990 lb 990 lb
Dead Load 647 lb 647 lb
Total Load 1637 lb 1637 lb
Bearing Length 0.48 in 0.48 in
BEAM DATA
Span Length 16.5 ft
Unbraced Length-Top 2 ft 16.5 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 5 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#1 -Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 1300 psi Fb'= 1492 psi Tributary Width: TW= 2 ft
Cd=1.15 CI=1.00 CF=1.00 Side Two:
Shear Stress: Fv= 170 psi Fv'= 196 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Tributary Width: TW= 2 ft
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp. L to Grain: Fc- 1 = 625 psi Fc--L'= 625 psi Wall Load: WALL= 0
plf
Controlling Moment: 6753 ft-lb SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
8.25 ft from left support Adjusted Beam Length: Ladj= 16.5 ft
Created by combining all dead and live loads. Beam Self Weight: BSW= 13 plf
Controlling Shear: -1637 lb Beam Uniform Live Load: wL= 120 plf
At support. Beam Uniform Dead Load: wD_adj= 78 plf
Created by combining all dead and live loads. Total Uniform Load: wT= 198 plf
Comparisons with required sections: Req'd Provided
Section Modulus: 54.32 in3 121.23 in3
Area(Shear): 12.56 in2 63.25 in2
Moment of Inertia(deflection): 188 in4 697.07 in4
Moment: 6753 ft-lb 15072 ft-lb
Shear: -1637 lb 8244 lb
NOTES
page
P4oject:Willow_Windwood Homes_Lot 19 Annand_Beams Souers
Location:Beam Nr.03-Front Porch Beam at Entry ` + Suntel Design
Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] .w Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 5.5 FT
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:51 AM
Section Adequate By:353.7%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.01 IN L/6579
Dead Load 0.01 in
Total Load 0.02 IN L/4164
Live Load Deflection Criteria:U240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 495 lb 495 lb
Dead Load 287 lb 287 lb
Total Load 782 lb 782 lb
Bearing Length 0.36 in 0.36 in
BEAM DATA
Span Length 5.5 ft �v.....:� , .. ..n.
Unbraced Length-Top 0 ft 5.5 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 5 :12
Roof Duration Factor 1.15
ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 850 psi Fb'= 1173 psi Tributary Width: TW= 2 ft
Cd=1.15 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 207 psi Roof Live Load: LL= 30 psf
Cd=1.15 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Tributary Width: TW= 4 ft
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi
Comp.-L to Grain: Fc-1= 625 psi Fc--- = 625 psi Wall Load: WALL= 0
plf
Controlling Moment: 1075 ft Ib SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
2.75 ft from left support Adjusted Beam Length: Ladj= 5.5 ft
Created by combining all dead and live loads. Beam Self Weight: BSW= 7 plf
Controlling Shear: 782 lb Beam Uniform Live Load: wL= 180 plf
At support. Beam Uniform Dead Load: wD_adj= 104 plf
Created by combining all dead and live loads. Total Uniform Load: wT= 284 plf
Comparisons with required sections: Req'd provided
Section Modulus: 11 in3 49.91 in3
Area(Shear): 5.67 in2 32.38 in2
Moment of Inertia(deflection): 9.98 in4 230.84 in4
Moment: 1075 ft-lb 4879 ft-lb
Shear: 782 lb 4468 lb
NOTES
Project:Willow_Windwood Homes_Lot 19 Annand_Beams page
Judith Souers
Location:Beam Nr.04-Front Porch Beam at Garage Side -Suntel Design
Multi-Span Roof Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] xi' .t,Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 8.5 FT
#2-Douglas-Fir-Larch(North)-Wet Use StruCalc Version 9.0.2.5 3/13/2018 9:31:51 AM
Section Adequate By:28.6%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.09 IN U1141
Dead Load 0.06 in
Total Load 0.15 IN U685
Live Load Deflection Criteria:L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 1154 lb 919 lb
Dead Load 762 lb 621 lb
Total Load 1916 lb 1540 lb
Bearing Length 1.31 in 1.05 in
SEAM DATA Center
Span Length 8.5 ft .,. ... „ _..� . s. .. .,..�
Unbraced Length-Top 0 ft 8.5 ft
•
Unbraced Length-Bottom 8.5 ft
Roof Pitch 10 :12
Roof Duration Factor 1.15 ROOF LOADING Center
Notch Depth 0.00 Roof Live Load RLL= 30 psf
MATERIAL PROPERTIES Roof Dead Load RDL= 15 psf
#2-Douglas-Fir-Larch(North) Roof Tributary Width Side One TW1 = 4.7 ft
Base Values Adjusted Roof Tributary Width Side Two TW2= 1.5 ft
Bending Stress: Fb= 850 psi Fb'= 1173 psi Wall Load WALL= 0 plf
Cd=1.15 CF=1.20 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 201 psi Load Number One
Cd=1.15 Cm=0.97 Live Load 500 lb
Modulus of Elasticity: E= 1600 ksi E'= 1440 ksi Dead Load 300 lb
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 522 ksi Location 2.25 ft
Cm=0.90
Comp.1 to Grain: Fc-1= 625 psi Fc-L'= 419 psi BEAM LOADING Quiff
Cm=0.67 Total Live Load 185 plf
Total Dead Load(Adjusted for Roof Pitch) 120 plf
Controlling Moment: 3794 ft-lb Beam Self Weight 7 plf
3.57 Ft from left support of span 2(Center Span) Total Load 312 plf
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: 1916 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req'd Provided
Section Modulus: 38.81 in3 49.91 in3
Area(Shear): 14.31 in2 32.38 in2
Moment of Inertia(deflection): 60.62 in4 230.84 in4
Moment: 3794 ft-lb 4879 ft-lb
Shear: 1916 lb 4334 lb
NOTES
Project:Willow_Windwood Homes_Lot 19 Annand_Beams page
Location: Beam Nr.05-CeilingBeam at Garage Judith Sowers /
9 �" Suntel� Design
Multi-Loaded Multi-Span Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] Lake Oswego,OR 97035
6.75 IN x 18.0 IN x 18.5 FT
24F-V4-Visually Graded Western Species-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:51 AM
Section Adequate By:88.4%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.23 IN U956
Dead Load 0.15 in
Total Load 0.38 IN U578
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: U240
REACTIONS A B
Live Load 5054 lb 4411 lb
Dead Load 3245 lb 2932 lb
Total Load 8299 lb 7343 lb
Bearing Length 1.89 in 1.67 in TRS TR2
BEAM DATA Center
Span Length 18.5 ft
Unbraced Length-Top 1.33 ft
Unbraced Length-Bottom 18.5 ft 11111111111.
Live Load Duration Factor 1.00
Camber Adj.Factor 1
Camber Required 0.15 UNIFORM LOADS Center
Uniform Live Load 0 plf
Notch Depth 0.00 Uniform Dead Load 0 plf
MATERIAL PROPERTIES Beam Self Weight 26 plf
24F-V4-Visually Graded Western Species Total Uniform Load 26 plf
Base Values Adjusted POINT LOADS-CENTER SPAN
Bending Stress: Fb= 2400 psi Controlled by:
Fb_cmpr= 1850 psi Fb'= 2271 psi Load Number ne
Live Load 1200 lb
Cd=1.00 C1=1.00 Cv=0.95 Dead Load 720 lb
Shear Stress: Fv= 265 psi Fv'= 265 psi
Cd=1.00 Location 5 ft
Modulus of Elasticity: E= 1800 ksi E'= 1800 ksi TRAPEZOIDAL LOADS-CENTER SPAN
Min. Mod.of Elasticity: E_min= 930 ksi E_min'= 930 ksi Load Number ne Two Three Four
Comp.1 to Grain: Fc-1= 650 psi Fc- = 650 psi Left Live Load 375 plf 320 plf 90 plf 120 plf
Left Dead Load 220 plf 210 plf 45 plf 60 plf
Controlling Moment: 36607 ft-lb Right Live Load 375 plf 320 plf 90 plf 120 plf
8.51 Ft from left support of span 2(Center Span) Right Dead Load 220 plf 210 plf 45 plf 60 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft 5 ft 0 ft 5 ft
Controlling Shear: 8299 lb Load End 5 ft 18.5 ft 5 ft 18.5 ft
At left support of span 2(Center Span) Load Length 5 ft 13.5 ft 5 ft 13.5 ft
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Read Provided
Section Modulus: 193.46 in3 364.5 in3
Area(Shear): 46.97 in2 121.5 in2
Moment of Inertia(deflection): 1362.94 in4 3280.5 in4
Moment: 36607 ft-lb 68970 ft-lb
Shear: 8299 lb 21465 lb
NOTES
Project:Willow_Windwood Homes_Lot 19 Annand_Beams #► page
Judith Souers /
Location:Beam Nr.06-Ceiling Beam at Garage `�Suntel Design
Uniformly Loaded Floor Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] `, Lake Oswego,OR 97035
5.5 IN x 9.5 IN x 9.25 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:51 AM
Section Adequate By:24.7%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.13 IN L/883
Dead Load 0.05 in
Total Load 0.18 IN U631
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: L/240
REACTIONS A D
Live Load 2220 lb 2220 lb
Dead Load 884 lb 884 lb
Total Load 3104 lb 3104 lb
Bearing Length 0.90 in 0.90 in
BEAM DATA Center
Span Length 9.25 ft „.:,. .. ....: . .
Unbraced Length-Top 1.33 ft 9.25 ft
Floor Duration Factor 1.00
Notch Depth 0.00
MATERIAL PROPERTIES FLOOR LOADING
#1 -Douglas-Fir-Larch(North) Side 1 Side 2
Base Values Adjusted Floor Live Load FLL= 40 psf 40 psf
Bending Stress: Fb= 1300 psi Fb'= 1299 psi Floor Dead Load FDL= 15 psf 15 psf
Cd=1.00 CI=1.00 CF=1.00 Floor Tributary Width FTW= 8 ft 4 ft
Shear Stress: Fv= 170 psi Fv'= 170 psi
Cd=1.00 Wall Load WALL= 0 plf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi BEAM LOADING
Min. Mod.of Elasticity: E_min580 ksi E_miL'= 580 ksi Beam Total Live Load: wL= 480 plf
Comp. to Grain: Fc- = 625 psi Fc- = 625 psi Beam Total Dead Load: wD= 180 plf
Controlling Moment: 7178 ft-lb Beam Self Weight: BSW= 11 plf
4.625 ft from left support Total Maximum Load: wT= 671 plf
Created by combining all dead and live loads.
Controlling Shear: 3104 lb
At support.
Created by combining all dead and live loads.
Comparisons with required sections: Rea'd Provided
Section Modulus: 66.32 in3 82.73 in3
Area(Shear): 27.39 in2 52.25 in2
Moment of Inertia(deflection): 160.24 in4 392.96 in4
Moment: 7178 ft-lb 8954 ft-lb
Shear: 3104 lb 5922 lb
NOTES
page
Project:Willow_Windwood Homes_Lot 19 Annand_Beams . Judith Souers
Location:Beam Nr.07-Slider Header at Nook Suntel Design /
Multi-Loaded Multi-Span Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] 2-411 Lake Oswego,OR 97035
5.5 IN x 11.5 IN x 6.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:52 AM
Section Adequate By:51.2%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/3018
Dead Load 0.02 in
Total Load 0.04 IN U1900
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: U240
REACTIONS A B
Live Load 3028 lb 1572 lb
Dead Load 1714 lb 1001 lb TR2
Total Load 4742 lb 2573 lb TR1 TR3
Bearing Length 1.38 in 0.75 in
w
BEAM DATA Center
Span Length 6.5 ft
Unbraced Length-Top 0 ft 111111111.
Unbraced Length-Bottom 6.5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Qpigm
MATERIAL PROPERTIES Uniform Live Load 0 plf
#1 -Douglas-Fir-Larch(North) Uniform Dead Load 90 plf
Base Values Adjusted Beam Self Weight 13 plf
Bending Stress: Fb= 1300 psi Fb'= 1300 psi Total Uniform Load 103 plf
Cd=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 1400 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 700 Ib
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi Location 2 ft
Comp.1 to Grain: Fc- 1 = 625 psi Fc-1'= 625 psi
TRAPEZOIDAL LOADS-CENTER SPAN
Controlling Moment: 6573 ft-lb Load Number One Two Three
2.01 Ft from left support of span 2(Center Span) Left Live Load 570 plf 360 plf 280 plf
Created by combining all dead loads and live loads on span(s)2 Left Dead Load 285 plf 135 plf 105 plf
Controlling Shear: 4742 lb Right Live Load 570 plf 360 plf 280 plf
At left support of span 2(Center Span) Right Dead Load 285 plf 135 plf 105 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft 0 ft 3 ft
Load End 2ft 3ft 6.5ft
Comparisons with required sections: Req'd Provided Load Length 2 ft 3 ft 3.5 ft
Section Modulus: 60.67 in3 121.23 in3
Area(Shear): 41.84 in2 63.25 in2
Moment of Inertia(deflection): 88.07 in4 697.07 in4
Moment: 6573 ft-lb 13133 ft-lb
Shear: 4742 lb 7168 lb
NOTES
Project:Willow_Windwood Homes Lot 19 Annand_Beams
page
Judith Souers
Location: Beam Nr.08-Rear Patio Roof Beam `Suntel Design /
Roof Beam ;16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] ��"' Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 10.0 FT
#2-Douglas-Fir-Larch(North)-Wet Use StruCalc Version 9.0.2.5 3/13/2018 9:31:52 AM
Section Adequate By:25.5%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.13 IN U909
Dead Load 0.08 in
Total Load 0.21 IN U570
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: U180
REACTIONS A B
Live Load 975 lb 975 lb
Dead Load 579 lb 579 lb
Total Load 1554 lb 1554 lb
Bearing Length 1.06 in 1.06 in
BEAM DATA
Span Length 10 ft
Unbraced Length-Top 0 ft loft
Unbraced Length-Bottom 0 ft
Roof Pitch 6 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch(North) Roof Live Load: LL= 30 psf
Base Values Adjusted Roof Dead Load: DL= 15 psf
Bending Stress: Fb= 850 psi Fb'= 1173 psi Tributary Width: TW= 1.5 ft
Cd=1.15 CF=1.20 Side Two:
Shear Stress: Fv= 180 psi Fv'= 201 psi Roof Live Load: LL= 30 psf
Cd=1.15 Cm=0.97 Roof Dead Load: DL= 15 psf
Modulus of Elasticity: E= 1600 ksi E'= 1440 ksi Tributary Width: TW= 5 ft
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 522 ksi
Cm=0.90 Wall Load: WALL= 0
Comp.1 to Grain: Fc- = 625 psi Fc- = 419 psi plf
Cm=0.67 SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
Controlling Moment: 3886 ft-lb Adjusted Beam Length: Ladj= 10 ft
5.0 ft from left support Beam Self Weight: BSW= 7 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 195 plf
Controlling Shear: 1554 Ib Beam Uniform Dead Load: wD_adj= 116 plf
At support. Total Uniform Load: wT= 311 plf
Created by combining all dead and live loads.
Comparisons with required sections: Read Provided
Section Modulus: 39.76 in3 49.91 in3
Area(Shear): 11.61 in2 32.38 in2
Moment of Inertia(deflection): 72.85 in4 230.84 in4
Moment: 3886 ft-lb 4879 ft-lb
Shear: -1554 lb 4334 lb
NOTES
Pyoj ect:Willow_Windwood Homes Lot 19 Annand Beams t page
— — Judith Souers
Location:Beam Nr.09-Header at Grt Rm Suntel Design /
Multi-Loaded Multi-Span Beam - 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] '' Lake Oswego,OR 97035
5.5 IN x 9.5 IN x 5.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:52 AM
Section Adequate By:42.1%
Controlling Factor:Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.03 IN L/2088
Dead Load 0.02 in
Total Load 0.05 IN L/1331
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria:U240
REACTIONS A B
Live Load 2615 lb 1852 lb
Dead Load 1490 lb 1108 lb
Total Load 4105 lb 2960 lb TRI
Bearing Length 1.19 in 0.86 in
w
BEAM DATA Center
Span Length 5.5 ft
Unbraced Length-Top 1.33 ft 111111
Unbraced Length-Bottom 5.5 ft
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 280 plf
#1 -Douglas-Fir-Larch(North) Uniform Dead Load 195 plf
Base Values Adjusted Beam Self Weight 11 plf
Bending Stress: Fb= 1300 psi Fb'= 1299 psi Total Uniform Load 486 plf
Cd=1.00 C1=1.00 CF=1.00 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 170 psi Fv'= 170 psi Load Number One
Cd=1.00 Live Load 1400 lb
Modulus of Elasticity: E= 1600 ksi E= 1600 ksi Dead Load 700 lb
Min.Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi Location 2.75 ft
Comp. L to Grain: Fc-1= 625 psi Fc--- = 625 psi
TRAPEZOIDAL LOADS-CENTER SPAN
Controlling Moment: 6300 ft-lb Load Number One
2.75 Ft from left support of span 2(Center Span) Left Live Load 555 plf
Created by combining all dead loads and live loads on span(s)2 Left Dead Load 278 plf
Controlling Shear: 4105 lb Right Live Load 555 plf
At left support of span 2(Center Span) Right Dead Load 278 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft
Load End 2.75 ft
Comparisons with required sections: Read Provided Load Length 2.75 ft
Section Modulus: 58.22 in3 82.73 in3
Area(Shear): 36.22 in2 52.25 in2
Moment of Inertia(deflection): 70.85 in4 392.96 in4
Moment: 6300 ft-lb 8954 ft-lb
Shear: 4105 lb 5922 lb
NOTES
fe
page
Pypject:Willow_Windwood Homes_Lot 19 Annand_Beams Judith Souers
Location: Beam Nr. 10-Header at Grt Rm Suntel Design /
Multi-Loaded Multi-Span Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] .
,,Lake Oswego,OR 97035
3.5 IN x 11.25 IN x 5.5 FT
#1 -Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:53 AM
Section Adequate By:25.9%
Controlling Factor:Shear
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/4342
Dead Load 0.01 in
Total Load 0.02 IN U2666
Live Load Deflection Criteria:L/360 Total Load Deflection Criteria:L/240
REACTIONS A U
Live Load 2385 lb 1016 lb
Dead Load 1367 lb 682 lb
Total Load 3752 lb 1698 lb TRI
Bearing Length 1.72 in 0.78 in
BEAM DATA Center
Span Length 5.5 ft t �... . .... :..... ....... >.n
Unbraced Length-Top 1.33 ft
Unbraced Length-Bottom 5.5 ft11111111 .11
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 280 plf
#1 -Douglas-Fir-Larch(North) Uniform Dead Load 195 plf
Base Values Adjusted Beam Self Weight 8 plf
Bending Stress: Fb= 850 psi Fb'= 933 psi Total Uniform Load 483 plf
Cd=1.00 C1=1.00 CF=1.10 POINT LOADS-CENTER SPAN
Shear Stress: Fv= 180 psi Fv'= 180 psi Load Number One
Cd=1.00 Live Load 1400 lb
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Dead Load 700 lb
Min. Mod.of Elasticity: E_min= 580 ksi E_min'= 580 ksi Location 0.83 ft
Comp.-L to Grain: Fc- L= 625 psi Fc- = 625 psi
TRAPEZOIDAL LOADS-CENTER SPAN
Controlling Moment: 2984 ft-lb Load Number One
1.98 Ft from left support of span 2(Center Span) Left Live Load 555 plf
Created by combining all dead loads and live loads on span(s)2 Left Dead Load 278 plf
Controlling Shear: 3752 lb Right Live Load 555 plf
At left support of span 2(Center Span) Right Dead Load 278 plf
Created by combining all dead loads and live loads on span(s)2 Load Start 0 ft
Load End 0.83 ft
Comparisons with required sections: Read Provided Load Length 0.83 ft
Section Modulus: 38.37 in3 73.83 in3
Area(Shear): 31.26 in2 39.38 in2
Moment of Inertia(deflection): 37.38 in4 415.28 in4
Moment: 2984 ft-lb 5740 ft-lb
Shear: 3752 lb 4725 lb
NOTES
Project:Willow Windwood Homes_Lot 19 Annand_Beams page
Judith Souers
Location: Beam Nr. 11 -Front Porch Deck Beam ' Suntel Design /
Uniformly Loaded Floor Beam 16865 Boones Ferry Rd Suite 201 of
[2015 International Building Code(2012 NDS)] "` Lake Oswego,OR 97035
3.5 IN x 9.25 IN x 9.33 FT
#2-Douglas-Fir-Larch(North)-Dry Use StruCalc Version 9.0.2.5 3/13/2018 9:31:53 AM
Section Inadequate By: Infinity%,
Controlling Factor:Shear/Depth Required Infinity In.
PEFLECTIONS LOADING DIAGRAM
Live Load
Dead Load
Total Load
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A
Live Load 1260 lb 1260 Ib
Dead Load 210 lb 210 lb
Total Load 1470 lb 1470 lb
Bearing Length Infinity in Infinity in
BEAM DATA Center
, <.
Span Length 9.33 ft ., ......r. _..... . . ... .. .�r .... .,�. ,.. ..._.,. ....._ ,.� h.,=�
Unbraced Length-Top 0 ft 9.33 ft
Floor Duration Factor 1.00
Notch Depth 0.00
MATERIAL PROPERTIES FLOOR LOADING
#2-Douglas-Fir-Larch(North) Side 1 Side 2
Base Values Adjusted Floor Live Load FLL= 60 psf 60 psf
Bending Stress: Fb= 0 psi Fb'= 0 psi Floor Dead Load FDL= 10 psf 10 psf
Cd=1.00 CF=1.20 Floor Tributary Width FTW= 0.5 ft 4 ft
Shear Stress: Fv= 0 psi Fv'= 0 psi
Cd=1.00 Wall Load WALL= 0 plf
Modulus of Elasticity: E= 0 ksi E'= 0 ksi BEAM LOADING
Comp.-t-to Grain: Fc-1= 0 psi Fc-1'= 0 psi Beam Total Live Load: wL= 270 plf
Controlling Moment: 3428 ft-lb Beam Total Dead Load: wD= 45 plf
4.665 ft from left support Beam Self Weight: BSW= 0 plf
Total Maximum Load: wT= 315 plf
Created by combining all dead and live loads.
Controlling Shear: -1469 lb
At support.
Created by combining all dead and live loads.
Comparisons with required sections: Req'd Provided
Section Modulus: Infinity in3 49.91 in3
Area(Shear): Infinity in2 32.38 in2
Moment of Inertia(deflection): 0 in4 230.84 in4
Moment: 3428 ft-lb 0 ft-lb
Shear: -1469 lb 0 lb
NOTES