Report (39) 11 Generated by check-Web Software
Envelope Compliance Certificate
Section 1: Project Information
RECEIVED
MAR 14 2019
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:AltardState-Tigard, OR CITY OF TIGARD
Project Type: Alteration BUILDING DIVISION
Envelope Compliance Method: Prescriptive
Construction Site: Owner/Agent: Designer/Contractor:
9345 SW Washington Square Rd Suite T013 Altar'd State Ghafari//Concept Design
Tigard,Oregon 97223 150 West Church Ave 89 Monroe Center NW,Suite 400
Maryville,Tennessee 37801 Grand Rapids, Michigan 49503
865-288-7700 616-771-0909
Building Location(for weather data): Tigard,Oregon
Climate Zone: 4c
Vertical Glazing/Wall Area Pct.: 0%
Building Use:Area Type Floor Area
1-First Floor(Retail):Nonresidential 5972
2-Second Floor stock(Retail):Nonresidential 3331
Section 2: Envelope Assemblies and Requirements Checklist
Envelope PASSES
Envelope Assemblies:
R-Value Proposed Max.Allowed
Post-Alteration Assembly Cavity Cont. U-Factor SHGC U-Factor SHGC
Ext.Wall:Steel-Framed, 16in.o.c.,[Bldg. Use 1 -First Floor] 21.0 7.5 0.059 --- 0.064 ---
Window: ,Clear,[Bldg.Use 1 -First Floor] --- --- 0.450 0.350 0.450 0.400
Door: ,Entrance Door,Entrance Door,[Bldg.Use 1 -First Floor] --- --- 0.680 0.250 0.800 0.400
Ext.Wall:Steel-Framed, 16in.o.c.,[Bldg. Use 2-Second Floor 21.0 7.5 0.059 --- 0.064 ---
stock]
Window: ,Clear,[Bldg.Use 2-Second Floor stock] --- --- 0.450 0.350 0.450 0.400
Roof:Insulation Entirely Above Deck,[Bldg.Use 2-Second Floor --- --- --- --- ---
stock],Exemption: Insulation not exposed.
(a)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Fenestration Product Rating:
® 1. U-factors of fenestration products(windows,doors and skylights)are determined in accordance with NFRC 100 by an accredited,
independent laboratory,and labeled and certified by the manufacturer or are determined using the commercial size category values
listed in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.4 and shall include the effects of the window frame.
The temporary label afixed to the fenestration products must not be removed prior to inspection.
Exception(s):
Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
Plans reference page/section: A8,5-A8,7
Li 2. Solar heat gain coefficient(SHGC)of glazed fenestration products(windows,glazed doors and skylights)shall be determined in
accordance with NFRC 200 by an accredited,independent laboratory,and labeled and certified by the manufacturer or be determined
Project Title: Altar' State-Tigard, OR Report date: 03/14/19
Data filename: Page 1 of 3
using the Solar Heat Gain Coefficients(SHGC)in Chapter 15 of the 2009 ASHRAE Handbook of Fundamentals,Table No.10.The
overall values must consider type of frame material and operator for the SHGC at normal incidence.
Exception(s):
❑ Site-built fenestration products shall have a single certificate specifying glazing type,special coatings,spacers,gas fills,
center-of-glass and overall U-factor,and center-of-glass SHGC for every type of site built glass used.These certificates shall be
maintained on the jobsite and made available to the inspector.
Plans reference page/section:
Air Leakage, Insulation, and Component Certification:
• 3. Sealing of the building envelope.Openings and penetrations in the building envelope are sealed with caulking materials or closed with
gasketing systems compatible with the construction materials and location.Joints and seams are sealed in the same manner or taped
or covered with a moisture vapor-permeable wrapping material.Sealing materials spanning joints between construction materials allow
for expansion and contraction of the construction materials.
Plans reference page/section: A8 .
7
LI 4. Window and door assemblies.The air leakage of window and sliding or swinging door assemblies that are part of the building envelope
are determined in accordance with AAMA/WDMA/CSA 101/I.S.2/A440,or NFRC 400 by an accredited,independent laboratory,and
labeled and certified by the manufacturer.
Exception(s):
❑ Site-constructed windows and doors that are weatherstripped or sealed in accordance with Section 502.4.3.
Plans reference page/section:
Ai 5. Curtain wall,storefront glazing and commercial entrance doors.Curtain wall,storefront glazing and commercial-glazed swinging
entrance doors and revolving doors are tested for air leakage in accordance with ASTM E 283. For curtain walls and storefront glazing,
the maximum air leakage rate is 0.3 cubic foot per minute per square foot of fenestration area.For commercial glazed swinging
entrance doors and revolving doors,the maximum air leakage rate is 1.00 cfm/ft2 of door area.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section: i .5- .
7
Eri 6. Building thermal envelope insulation.An R-value identification mark is applied(by manufacturer)to each piece of insulation 12
inches or greater in width.Alternately,the insulation installers have provided a signed,dated and posted certification listing the type,
manufacturer and R-value of insulation installed.Refer to code section for blown or sprayed insulation installation/settling depths and
marker requirements.
® 7. Insulation mark installation. Insulating materials are installed such that the manufacturer's R-value mark is readily observable upon
inspection.
j 8. Insulation product rating.The thermal resistance(R-value)of insulation has been determined in accordance with the U.S.FTC R-value
rule.
Li 9. Installation.All material,systems and equipment are installed in accordance with the manufacturer's installation instructions and the
International Building Code.
❑ 10.Outdoor air intakes and exhaust openings.Stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral
to the building envelope shall be equipped with not less than a Class I motorized,leakage-rated damper with a maximum leakage rate
of 4 cfm per square foot at 1.0 inch water gauge when tested in accordance with AMCA 500D.Stair and shaft vent dampers shall be
capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection
systems.
Exception(s):
A Requirement is not applicable. EXISTING
Plans reference page/section:
❑ 11.Loading dock weatherseals.Cargo doors and loading dock doors are equipped with weather seals to restrict infiltration when vehicles
are parked in the doorway.
Exception(s):
A Requirement is not applicable.
Plans reference page/section:
12.Recessed lighting. Recessed luminaires installed in the building thermal envelope are sealed to limit air leakage between conditioned
and unconditioned spaces.All recessed luminaires are IC-rated and labeled as meeting ASTM E 283.All recessed luminaires are
sealed with a gasket or caulk between the housing and interior wall or ceiling covering.
Exception(s):
❑ Requirement is not applicable.
Plans reference page/section:
Project Title: Altar' State-Tigard, OR Report date: 03/14/19
Data filename: Page 2 of 3
13.Vestibules. Doors that separate conditioned space from the exterior are protected with an enclosed vestibule,with all doors of the
vestibule equipped with self-closing devices.Vestibules are designed so interior and exterior doors to not operate simultaneously.
Exception(s):
J Doors not intended to be used as a building entrance door,such as doors to mechanical or electrical equipment rooms.
❑ Doors opening directly from a sleeping unit or dwelling unit.
❑ Doors that open directly from a space less than 3000 sq.ft.in area.
❑ Revolving doors.
❑ Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors.
O Requirement is not applicable. EX FERIOR DOORS ARE NOT THE PRIMARY ENTRANCE.
Plans reference page/section:
14.'Other'components have supporting documentation for proposed U-Factors.
Exception(s):
LA Requirement is not applicable.
Plans reference page/section:
Section 3: Compliance Statement
Compliance Statement: The proposed envelope alteration project represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application.The proposed envelope alteration project has been designed to
meet the 2014 Oregon Energy Efficiency Specialty Code requirements in COMcheck-Web and to comply with the mandatory requirements in
the Requirements Checklist.
Raymond S. Clark ,4��, 3.14.19
Name-Title �lgnature Date
soRAYMOND
S.CLARK
a 4583
.:
Project Title:Altar'State-Tigard, OR Report date: 03/14/19
Data filename: Page 3 of 3
check SoftwareVersion 4.1 .1
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:Altar'd State
Project Type:Alteration
Construction Site: Owner/Agent: Designer/Contractor:
9585 SW Washington Square Rd Peter Hilger
Space#T-13 5800 East Skelly Drive
Tigard,OR 97223 Suite 1100
Tulsa,OK 74135
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B x C)
Retail:Sales Area(Ceiling Height 20 ft.) 8867 1.5 13301
Total Allowed Watts= 13301
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description I Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Retail:Sales Area(8867 sq.ft.)
LED 1:CH1:Other: 1 51 44 2244
LED 2:PD1,PD2,PD3,PD10,PD11:Other: 1 26 100 2600
LED 3:PD12,PD21:LED Other Fixture Unit 60W: 1 3 60 180
LED 4:PD7,PD13:LED Other Fixture Unit 25W: 1 4 25 100
LED 5:PD25:LED PAR lOW: 1 25 10 250
LED 6:R3:Store Front:LED Other Fixture Unit 50W: 1 42 50 2100
LED 7:R3:LED Other Fixture Unit 50W: 1 15 50 750
LED 8:R8:Other: 1 32 12.5 400
LED 9:R10:Other: 1 4 32 128
LED 10:R11:LED PAR 16W: 1 12 16 192
LED 11:S10:Perimeter:Other: 1 21 23.1 485.1
LED 12:54:Other: 1 1 285.6 285.6
LED 13:S6:LED PAR 13W: 1 37 13 481
LED 14:57:LED MR 8W: 1 2 8 16
LED 15:S10:Other: 1 1 9.2 9.2
LED 16:W1:Other: 1 14 100 1400
Total Proposed Watts= 11621
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Wattage:13301 Proposed Wattage:11621
Complies:YES
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept Design\Altar'd State(Concept Design)\Tigard,OR(Washington Square)\Engineering\Eiec\Tigard,
OR-031219.cck Page 1 of 7
Mandatory Requirements:
✓ 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section:
✓ 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
Plans reference page/section:
✓ 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Plans reference page/section:
✓ 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section:
✓ 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Plans reference page/section:
✓ 7. Additional controls.Each area that is required to have a manual control shall have additional controls that meet the requirements of
1/ Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section:
✓ 8. Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load by at least
50 percent by either
1)controlling(dimming or multi-level switching)all luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
Plans reference page/section:
✓ 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:
1)a scheduled basis,using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area is unoccupied.
Plans reference page/section:
✓ 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section:
✓ 11 An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Plans reference page/section:
✓ 12Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Plans reference page/section:
• 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that:1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Plans reference page/section:
✓ 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Plans reference page/section:
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept Design\Altar'd State(Concept Design)\Tigard,OR(Washington Square)\Engineering\Elec\Tigard,
OR-031219.cck Page 2 of 7
✓ 15.Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section:
✓ 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Plans reference page/section:
✓ 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section:
✓ 18.Each dwelling unit in a building is metered separately.
Plans reference page/section:
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the Requirements
Checklist.
`.- L Li r Al: /7/,6,�lo•�" Pr,J s+''L.G site,`C' '� ~ jam' —/Z—/)*
Name-Title / Si nature Date
r. CTRI -4-7
.‹.&-----
�.p PRO,
65203PE
OREGON
y�_ 14 2/)
creRA, Ntj
Expiration Date 4,-.3a 15
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept Design\Altar'd State(Concept Design)\Tigard,OR(Washington Square)\Engineering\Elec\Tigard,
OR-031219,cck Page 3 of 7
•
Sw Software Version 4.1.1.
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:Altar'd State
Project Type:Alteration
Exterior Lighting Zone: 3(Other)
Construction Site: Owner/Agent: Designer/Contractor:
9585 SW Washington Square Rd Peter Hilger
Space#T-13 5800 East Skelly Drive
Tigard,OR 97223 Suite 1100
Tulsa,OK 74135
Section 2: Exterior Lighting Area/Surface Power Calculation
A B C D EF
Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed
Watts Wattage Watts Watts
/Unit (B x C)
Entry canopy 96 ft2 0.4 Yes 38 500
Total Tradable Watts*= 38 500
Total Allowed Watts= 38
Total Allowed Supplemental Watts**= 750
*Wattage tradeoffs are only allowed between tradable areas/surfaces.
**A supplemental allowance equal to 750 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A BCD E
Fixture ID:Description I Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Entry canopy(96 ft2):Tradable Wattage
LED 1:W5:Other: 1 5 100 500
Total Tradable Proposed Watts= 500
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Controls, Switching,and Wiring:
1. Lighting designated to operate more than 2000 hours per year for Uncovered Parking Areas shall be equipped with motion sensors that
will reduce the luminaire power by thirty-three percent or turn off one-third the luminaires when no activity is detected.
Plans reference page/section:
Exterior Lighting Restrictions and Exceptions:
✓ 2. Mercury vapor and incandescent lighting is not permitted for use as exterior lighting.
✓ 3. Exempt lighting fixtures are equipped with a control device independent of the control of the nonexempt lighting and are identified in
Section 3 table above.
Plans reference page/section:
Athan Codilt0M,42
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept DesignlAltar'd State(Concept Design)1Tigard.OR(Washington Square)\Engineering\Elec\Tigard,
OR-031219.cck Page 4 of 7
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon
Energy Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the
Requirements Checklist.
-tet/4.
y�
Pe 1 eI, . l4•r �je-r* t /i 1t �t R .x _ 9 `
Afr
Name-Title �! Si nature Date
c�;,0��,,t�i1i��4.�4
�y6520.�PE `�
OREGON
y�V 14 e?PcQ�
cr4"RA. Hfi
Expiration Date 'SC*/
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept Design\Altar'd State(Concept Design)\Tigard,OR(Washington Square)\Engineering\Elec\Tigard,
OR-031219.cck Page 5 of 7
COM check oftare Version 41.1 .0
Mechanical Compliance Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:Altar'd State
Project Type:Alteration
Construction Site: Owner/Agent: Designer/Contractor:
9585 SW Washington Square Rd Peter Hilger
Space#T-13 5800 East Skelly Drive
Tigard,OR 97223 Suite 1100
Tulsa,OK 74135
Section 2: General Information
Building Location(for weather data): Tigard,Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Type&Description
1 Water Heater 1:
Electric Storage Water Heater,Capacity:6 gallons
No minimum efficiency requirement applies
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Requirements Specific To:Water Heater 1 :
1. Newly purchased equipment meets the efficiency requirements. No efficiency requirements for water heater with storage capacity less
than 20 gallons.
1 2. Service water-heating equipment performance efficiency.Water heating equipment efficiency has been verified through data furnished
by the manufacturer or through certification under an approved certification program.
✓ 3. Temperature controls.Service water-heating equipment have controls to allow a setpoint of 110°F for equipment serving dwelling units
and 90°F for equipment serving other occupancies.The outlet temperature of lavatories in public facility rest rooms is limited to 110°F.
Plans reference page/section:
✓ 4. Heat traps.Water-heating equipment not supplied with integral heat traps and serving noncirculating systems have heat traps on the
supply and discharge piping associated with the equipment.
Plans reference page/section:
✓ 5. Pipe Insulation.For automatic-circulating hot water and externally heated(such as heat trace or impedance heating)systems,piping is
insulated in accordance with the specifications of this section.
✓ 6. Hot Water System Controls.Systems designed to maintain usage temperatures in hot water pipes is turned off automatically when
the hot water system is not in operation and has demand sensing controls that turn off the system when there is no demand when the
system is operational.A check valve or similar device is installed per requirement details.
Plans reference page/section:
Generic Requirements: Must be met by all systems to which the requirement is applicable:
7 1. All service water heating requirements are listed in requirements section specific to the system.
Section 5: Compliance Statement
Project Title:Altar'd State Report date:03/12/19
Data filename:J:\Concept Design\Aitar'd State(Concept Design)\Tigard,OR(Washington Square)lEngineering\Elec\Tigard,
OR-031219.cck Page 6 of 7
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans,
• specifications and other calculations submitted with this permit application.The proposed mechanical alteration project has been designed
to meet the 2014 Oregon Energy Efficiency Specialty Code,Chapter 8,requirements in COMcheck Version 4.1.1.0 and to comply with the
mandatoryatrequirementsinnthe Requirements Checklist. [[
1.717 *JTo?14 nty/T'i t^' - tVi.GUI?Prt.. ^,,,t V1�Cr{may 3—jZ-1
Name-Title Signatur Date
Section 6: Post Construction Compliance Statement
O HVAC record drawings of the actual installation,system capacities,calibration information,and performance data for each equipment
provided to the owner.
❑ HVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor.
❑ Written HVAC balancing and operations report provided to the owner.
The above post construction requirements have been completed.
Principal Mechanical Designer-Name Signature Date
,r t 1IAN1{;
�'J'Y' , ..kiss
\ G1NE:e,Lyv
1.4
`c. 77585 PE
a cat-
.,..n.rr•-.-"..PEGCN
10
. n
Jo{! M. JAR
FXPiRES 4-30,' 1,4\
Project Title:Altar'd State Report date:03/12119
Data filename:J:\Concept Design\Altar'd State(Concept Design)\Tigard,OR(Washington Square)\Engineering\Elec\Tigard,
OR-031219.cck Page 7 of 7